energy U. ^ y~ V~\ r\ r* Energy Harbor Nuclear Corp Perry Nuclear Power Plant 10 Center Road Perry, Ohio 44081 RodLPenfleld 440-280-5382 Site Vice President, Perry Nuclear 724-462-0816 (cell)

April 26, 2023 L-23-121 10CFR50.36(a)

ATTN: Document Control Desk U. S. Nuclear Regulatory Commission Washington, DC 20555-0001

SUBJECT:

Perry Nuclear Power Plant Docket No. 50-440 Annual Radiological Effluent Release Report Enclosed is the Annual Radiological Effluent Release Report for the Perry Nuclear Power Plant (PNPP) for the period of January 1, 2022 through December 31, 2022. This document partially satisfies the requirements of the PNPP Technical Specifications (TS), the PNPP Offsite Dose Calculation Manual (ODCM), and the Environmental Protection Plan contained in Appendix B of the PNPP Operating License.

There are no regulatory commitments contained in this letter. If there are any questions or if additional information is required, please contact Mr. Eli Crosby, Manager of Radiation Protection and Chemistry at (440) 280-5032.

Sincerely, Rod Penfield

Enclosures:

A PNPP 2022 Annual Radiological Effluent Release Report cc: NRC Project Manager NRC Resident Inspector NRC Region III

Enclosure A L-23-121 PNPP 2022 Annual Radiological Effluent Release Report

Annual Radioactive Effluent Release Report YEAR: 2022 Page 1 of 32 Company: Energy Harbor Plant: Perry Nuclear Power Plant 2022 Annual Radioactive Effluent Release Report Document Number: L-23-121

YEAR: 2022 Annual Radioactive Effluent Release Report Page 2 of 32 L-23-121 Company: Energy Harbor Plant: Perry Nuclear Power Plant TABLE OF CONTENTS 1.0 EXECUTIVE

SUMMARY

5 1.1 Radioactive Effluent Releases 5

2.0 INTRODUCTION

6 2.1 About Nuclear Power 6 2.2 About Radiation Dose 7 2.3 Lower Limit of Detection 9 3.0 RADIOACTIVE EFFLUENT RELEASES 10 3.1 Introduction 10 3.2 Regulatory Limits 11 3.3 Release Summary 13 3.4 40CFR 190 and 10 CFR 72.104-Uranium Fuel Cycle Dose Assessment 13 4.0 LIQUID EFFLUENTS 14 5.0 GASEOUS EFFLUENTS

SUMMARY

18 5.1 Land Use Census Changes 21 5.2 Meteorological Data 21 6.0 DOSE ASSESSMENT 21 7.0 SOLID WASTE 25 8.0 APPLICABLE TECHNICAL SPECIFICATION AND ODCM DEVIATIONS 26 9.0 OFFSITE DOSE CALCULATION MANUAL (ODCM) CHANGES 26 10.0 PROCESS CONTROL PROGRAM (PCP) CHANGES 26 11.0 RADIOACTIVE WASTE TREATMENT SYSTEM CHANGES 26 12.0 CORRECTIONS TO PREVIOUS ARERRS 26 13.0 CARBON-14 SUPPLEMENTAL INFORMATION 26 14.0 NEI 07-07 ONSITE RADIOLOGICAL GROUNDWATER MONITORING PROGRAM....27 14.1 Voluntary Notification 29 15.0 Abnormal Releases 29 15.1 Nuclear Closed Cooling 29 15.2 Auxiliary Boiler 31 16.0 BIBLIOGRAPHY 32

YEAR: 2022 Annual Radioactive Effluent Release Report Page 3 of 32 L-23-121 Company: Energy Harbor Plant: Perry Nuclear Power Plant TABLES Table 1: Liquid Batch Releases 15 Table 2: Summation of All Liquid Effluent Releases 16 Table 3: Radioactive Liquid Effluent Nuclide Composition 18 Table 4: Summation of All Gaseous Effluents 19 Table 5: Radioactive Gaseous Effluent Nuclide Composition 20 Table 6: Maximum Yearly Individual Site Boundary Dose, Considering All Sectors 22 Table 7: Population Yearly Dose, Considering All Sectors out to 50 miles 22 Table 8: Maximum Yearly Individual Site Boundary Dose (Only Land Sectors) 23 Table 9: Maximum Site Dose from Liquid Effluents 24 Table 10: Maximum Site Dose from Gaseous Effluents 24 Table 11: Average Individual Whole-Body Dose 24 Table 12: Solid Waste Shipped Offsite for Burial or Disposal 25 Table 13: Summary of Onsite Groundwater and Outdoor Piezometer Samples 28 Table 14: Summary of Underdrain Manhole Samples 29 Table 15: NCC Continuous Releases 30 Table 16: NCC Total Activity 30 Table 17: Auxiliary Boiler Batch Release 31 Table 18: Auxiliary Boiler Total Activity 31 FIGURES Figure 1: Boiling Water Reactor (BWR) [2] 6 Figure 2: Pressurized Water Reactor (PWR) [1] 7 Figure 3: Sources of Radiation Exposure (NCRP Report No. 160) [3] 8 Figure 4: Potential exposure pathways to Members of the Public due to Plant Operations [6] ..10 Figure 5: Underdrain System and Groundwater Monitoring Wells 28

YEAR: 2022 Annual Radioactive Effluent Release Report Page 4 of 32 L-23-121 Company: Energy Harbor Plant: Perry Nuclear Power Plant LIST OF ACRONYMS AND DEFINITIONS

1. ARERR: Annual Radioactive Effluent Release Report
2. AREOR: Annual Radiological Environmental Release Report
3. Alpha Particle (a): A charged particle emitted from the nucleus of an atom having a mass and charge equal in magnitude of a helium nucleus.
4. BWR: Boiling Water Reactor
5. Curie (Ci): A measure of radioactivity; equal to 3.7E+10 disintegrations per second, or 2.22E+12 disintegrations per minute.
6. Direct Radiation Monitoring: The measurement of radiation dose at various distances from the plant is assessed using thermoluminescent dosimeters (TLDs).
7. EPRI: Electric Power Research Institute
8. Ingestion Pathway: The ingestion pathway includes milk, fish, and garden produce. Meat or other food products may also be included.
9. ISFSI: Independent Spent Fuel Storage Installation
10. Lower Limit of Detection (LLD): The smallest concentration of radioactive material in a sample that will yield a net count (above system background) that will be detected with 95% probability with a 5% probability of a false conclusion that a blank observation represents "real" signal.
11. Microcurie (uCi): 3.7E+04 disintegrations per second, or 2.22E+06 disintegrations per minute.
12. millirem (mrem): 1/1000 rem; a unit of radiation dose equivalent in tissue.
13. NA: Not Applicable
14. NEI: Nuclear Energy Institute
15. NRC: Nuclear Regulatory Commission
16. ODCM: Offsite Dose Calculation Manual
17. qC\: one trillionth of a curie (3.7E-02 disintegration per second or 2.22 disintegrations per minute).
18. PNPP: Perry Nuclear Power Point
19. PWR: Pressurized Water Reactor
20. RETS: Radiological Effluent Technical Specifications
21. REMP: Radiological Environmental Monitoring Program
22. Restricted Area: Any area where access is controlled for the purpose of protecting individuals from exposure to radiation or radioactive materials.
23. TLD: Thermoluminescent Dosimeter
24. IS: Technical Specification

YEAR: 2022 Annual Radioactive Effluent Release Report Page 5 of 32 L-23-121 Company: Energy Harbor Plant: Perry Nuclear Power Plant 1.0 EXECUTIVE

SUMMARY

Perry Nuclear Power Plant (PNPP) Radiological Effluent Technical Specifications (RETS) Program was established to limit the quantities of radioactive material that may be released based on calculated radiation doses or dose rates. Dose to Members of the Public due to radioactive materials released from the plant is limited by Appendix I of 10 CFR 50 and by 40 CFR 190. Operational doses to the public during 2022 were calculated to be very small compared to the limits required by regulation and pose no health hazard when compared to other sources of radiation dose.

The Annual Radioactive Effluent Release Report (ARERR) details the results of the effluent monitoring program conducted at the Perry Nuclear Power Plant (PNPP) from January 01 through December 31, 2022. This report meets all the requirements in PNPP Technical Specifications, the Offsite Dose Calculation Manual (ODCM), and Regulatory Guide 1.21.

In addition to monitoring radioactive effluents, PNPP has a Radiological Environmental Monitoring Program (REMP) that monitors for buildup of radioactivity in the offsite environment. Data from the REMP is published in the Annual Radiological Environmental Operating Report (AREOR).

1.1 Radioactive Effluent Releases During the normal operation of a nuclear power plant, small quantities of radioactivity are released to the environment through liquid and gaseous effluent pathways. Radioactive material is also shipped offsite as solid waste. PNPP maintains a comprehensive program to control and monitor the release of radioactive materials from the site in accordance with Nuclear Regulatory Commission (NRC) release regulations.

Dose to the general public from the plant's liquid and gaseous effluent pathways were well below regulatory limits. The calculated maximum individual whole-body dose potentially received by an individual resulting from PNPP liquid effluents was 9.37E-02 mrem (3.1 percent of the regulatory limit). The calculated maximum individual whole-body dose potentially received by an individual resulting from PNPP gaseous effluents, excluding carbon-14 (C-14) was 9.98E-03 mrem (2.0E-01 percent of the regulatory limit).

Radioactivity released to the environment in the form of gaseous C-14 was estimated based on plant type and power production. The calculation is based on an industry initiative supported by the Nuclear Energy Institute (NEI), the Electric Power Research Institute (EPRI), and the NRC. The calculated hypothetical maximum annual individual whole-body dose potentially received by an individual resulting from PNPP gaseous effluents for C-14 is 2.46E-01 mrem/yr (4.92E+00 percent of the limit). Refer to Section 13 for additional C-14 information.

YEAR: 2022 Annual Radioactive Effluent Release Report Page 6 of 32 L-23-121 Company: Energy Harbor Plant: Perry Nuclear Power Plant The summation of the hypothetical maximum individual dose from effluents is less than 5 percent of the total dose an individual living in the PNPP area receives from all sources of man-made and background radiation.

Shipments of solid waste consisted of waste generated during water treatment, radioactive material generated during normal daily operations and maintenance, and irradiated components. PNPP complied with regulations governing radioactive shipments of solid radioactive waste.

2.0 INTRODUCTION

Nuclear energy provides an alternative energy source that is readily available with a very limited impact upon the environment. To understand nuclear energy more fully as a source of generating electricity, it is helpful to understand basic radiation concepts and the occurrence of radioactivity in nature.

2.1 About Nuclear Power Commercial nuclear power plants are generally classified as either Boiling Water Reactors (BWRs) or Pressurized Water Reactors (PWRs), based on their design.

A BWR includes a single coolant system where water used as reactor coolant boils as it passes through the core, and the steam generated is used to turn the turbine generator for power production (Figure 1). A PWR, in contrast, includes two separate water systems: radioactive reactor coolant and a secondary system (Figure 2). Reactor coolant is maintained under high pressure to prevent boiling.

The high-pressure coolant is passed through a heat exchanger called a steam generator where the secondary system water is boiled, and the steam is used to turn the turbine generator for power production.

Containment Structure Condenser Figure 1: Boiling Water Reactor (BWR) [12]

YEAR: 2022 Annual Radioactive Effluent Release Report Page 7 of 32 L-23-121 Company: Energy Harbor Plant: Perry Nuclear Power Plant Containment Structure Pressurizer Steam Generator Figure 2: Pressurized Water Reactor (PWR) [11]

Electricity is generated by a nuclear power plant similar to the way that electricity is generated at other conventional types of power plants, such as those driven by coal or natural gas. Water is boiled to generate steam. The steam turns a turbine that is attached to a generator, and the steam is condensed back into water to be returned to the boiler. What makes nuclear power different from these other types of power plants is that heat is generated by fission and decay reactions occurring within and around the core containing fissionable uranium (U-235).

Nuclear fission occurs when certain nuclides (primarily U-233, U-235, and Pu-239) absorb a neutron and break into several smaller nuclides (called fission products) as well as some additional neutrons.

Fission results in production of radioactive materials including gases and solids that must be contained to prevent release or treated prior to release. These effluents are generally treated by filtration and/or hold-up prior to release. Releases are generally monitored by sampling and by continuously indicating radiation monitors. The effluent release data is used to calculate doses to ensure that dose to the public due to plant operation remains within required limits 2.2 About Radiation Dose Ionizing radiation, including alpha, beta, and gamma radiation from radioactive decay, has enough energy to break chemical bonds in tissues and result in damage to tissue or genetic material. The amount of ionization that will be generated by a given exposure to ionizing radiation is quantified as dose. Radiation dose is generally reported in units of millirem (mrem) in the US.

YEAR: 2022 Annual Radioactive Effluent Release Report Page 8 of 32 L-23-121 Company: Energy Harbor Plant: Perry Nuclear Power Plant Space Internal (background)

(background) (5%)

Terrestrial (background)

(3%)

Radon & thoron (background)

(37%)

Computed tomography (medical)

(24%)

Industrial

(<0.1%)

Occupational Nuclear medicine

(<0.1%)

(medical)

(12%) Consumer Conventional Interventional fluoroscopy radiography/fluoroscopy (medical)

(medical)

(7%) (5%)

Figure 3: Sources of Radiation Exposure (NCRP Report No. 160) [1]

The National Council on Radiation Protection (NCRP) has evaluated the population dose for the US and determined that the average individual is exposed to approximately 620 mrem per year [1] (Figure 3). There are many sources for radiation dose, ranging from natural background sources to medical procedures, air travel, and industrial processes. Approximately half (310 mrem) of the average exposure is due to natural sources of radiation including exposure to radon, cosmic radiation, and internal radiation and terrestrial due to naturally occurring radionuclides. The remaining 310 mrem of exposure is due to man-made sources of exposure, with the most significant contributors being medical (48%) due to radiation used in various types of medical scans and treatments. Of the remaining 2% of dose, most is due to consumer activities such as air travel, smoking cigarettes, and building materials. A small fraction of this 2% is due to industrial activities including generation of nuclear power.

Readers that are curious about common sources and effects of radiation dose that they may encounter can find excellent sources of information from the Health Physics Society, including the Radiation Fact Sheets [2], and from the US Nuclear Regulatory Commission website [3].

YEAR: 2022 Annual Radioactive Effluent Release Report Page 9 of 32 L-23-121 Company: Energy Harbor Plant: Perry Nuclear Power Plant Concentrations of radioactive material in the environment resulting from plant operations are very small and it is not possible to determine doses directly using measured activities of environmental samples. To overcome this, Dose Calculations based on measured activities of effluent streams are used to model the dose impact for Members of the Public due to plant operation and effluents. There are several mechanisms that can result in dose to members of the public: ingestion of radionuclides in food or water, inhalation of radionuclides in air, immersion in a plume of noble gases, and direct radiation from the ground, the plant, or from an elevated plume.

2.3 Lower Limit of Detection Sample results are often reported as below the Lower Limit of Detection (LLD). The LLD for an analysis is the smallest amount of radioactive material that will show a positive result, for which there can be a 95% confidence that radioactivity is present. This statistical parameter is used as a measure of the sensitivity of a sample analysis. When a measurement is reported as less than the LLD (<LLD), it means that no radioactivity was detected. Had radioactivity been present at or above the stated LLD value, it statistically would have been detected. The NRC has established the required LLD values for environmental and effluent sample analyses.

For liquid releases, dilution and mixing factors are used to model the environmental concentrations in water. Drinking water pathways are modeled by determining the concentration of nuclides in the water at the point where the drinking water is sourced.

Fish and invertebrate pathways are determined by using concentration at the release point, bioaccumulation factors for the fish or invertebrate, and an estimate of the quantity offish consumed.

Each year a Land Use Census is performed to determine what potential dose pathways currently exist within a five-mile radius around the plant, the area most affected by plant operations. The Annual Land Use Census identifies the locations of vegetable gardens, nearest residences, milk animals, and meat animals. The data from the census is used to determine who is the likely to be most exposed to radiation dose because of plant operation.

There is significant uncertainty in dose calculation results, due to modeling dispersion of material released and bioaccumulation factors, as well as assumptions associated with consumption and land-use patterns. Even with these sources of uncertainty, the calculations do provide a reasonable estimate of the order of magnitude of the exposure.

Conservative assumptions are made in the calculation inputs such as the number of various foods and water consumed, the amount of air inhaled, and the amount of direct radiation exposure from the ground or plume, such that the actual doses received are likely lower than the calculated doses. Even with the built-in conservatism, doses calculated for the highest hypothetical exposed individual due to plant operation are a very small fraction of the annual dose that is received due to other sources. The low calculated doses due to the plant effluents, along with REMP results indicating no detectible radioactive material due to plant operations, serve to provide assurance that the site is not having a negative impact on the environment or people living near the plant.

YEAR: 2022 Annual Radioactive Effluent Release Report Page 10 of 32 L-23-121 Company: Energy Harbor Plant: Perry Nuclear Power Plant The Offsite Dose Calculation Manual (ODCM) specifies the methodology used to obtain the doses in the Dose Assessment section of this report. The methodology in the ODCM is based on NRC Regulatory Guide 1.109 [4] and NUREG-0133 [5]. Doses are calculated by determining what the nuclide concentration will be in air, water, on the ground, or in food products based on plant effluent releases. Release points are continuously monitored to quantify what concentrations of nuclides are being released.

For gaseous releases meteorological data is used to determine how much of the released activity will be present at a given location outside of the plant either deposited onto the ground or in gaseous form. Intake patterns and nuclide bio-concentration factors are used to determine how much activity will be transferred into animal milk or meat. Finally, human ingestion factors and dose factors are used to determine how much activity will be consumed and how much dose the consumer will receive.

Inhalation dose is calculated by determining the concentration of nuclides and how much air is breathed by the individual. Figure 4 depicts how the public may interact with nuclear facility gaseous and liquid effluents - thus determining how the plants sample.

o * ° *^^ Deposition Livestock prod Gaseous effluents

                        • . Agricultural products River

.Radiation O  : Radionuclides

Behavior of radionuclides Figure 4: Potential exposure pathways to Members of the Public due to Plant Operations [6]

3.0 RADIOACTIVE EFFLUENT RELEASES 3.1 Introduction The source of radioactive material in a nuclear power plant is the generation of fission products (e.g., noble gas, iodine, and particulate) or neutron activation of water and corrosion products (e.g., tritium and cobalt). Most of the fission products generated remain within the nuclear fuel pellet and fuel cladding. Most fission products that escape from the fuel cladding, as well as the majority of the activated corrosion products, are removed by plant processing equipment.

YEAR: 2022 Annual Radioactive Effluent Release Report Page 11 of 32 L-23-121 Company: Energy Harbor Plant: Perry Nuclear Power Plant During the normal operation of a nuclear power plant, small amounts of radioactive material are released in the form of solids, liquids, and gases. PNPP was designed and is operated in such a manner as to control and monitor these effluent releases. Effluents are controlled to ensure any radioactivity released to the environment is minimal and within regulatory limits. Effluent release programs include the operation of monitoring systems, in-plant sampling and analysis, quality assurance, and detailed procedures covering all aspects of effluent monitoring.

The liquid and gaseous radioactive waste treatment systems at PNPP are designed to collect and process these wastes to remove most of the radioactivity. Effluent monitoring systems are used to provide continuous indication of the radioactivity present and are sensitive enough to measure several orders of magnitude lower than the release limits.

This monitoring instrumentation is equipped with alarms and indicators in the plant control room. The alarms are set to provide warnings to alert plant operators when radioactivity levels reach a small fraction of the limits. The waste streams are sampled and analyzed to identify and quantify the radionuclides being released to the environment.

Gaseous effluent release data is coupled with on-site meteorological data in order to calculate the dose to the general public. Devices are maintained at various locations around PNPP to continuously sample the air in the surrounding environment. Frequent samples of other environmental media are also taken to determine if any radioactive material deposition has occurred.

Generation of solid waste is controlled to identify opportunities for minimization. Limiting the amount of material taken into the plant and sorting material as radioactive or non-radioactive waste helps to lower the volume of radioactive solid waste generated. After vendor processing, solid waste is shipped to a licensed burial site.

3.2 Regulatory Limits The Nuclear Regulatory Commission has established limits for liquid and gaseous effluents that comply with:

  • 10 CFR 20: Title 10 of the Code of Federal Regulations, Part 20, Standards for Protection Against Radiation, Appendix B;
  • 10 CFR 50: Title 10 of the Code of Federal Regulations, Part 50, Domestic Licensing of Production and Utilization Facilities, Appendix I;
  • 10 CFR 72.104: Title 10 of the Code of Federal Regulations, Part 72.104, Criteria for Radioactive Materials in Effluents and Direct Radiation from an ISFSI or MRS
  • 40 CFR 190: Title 40 of the Code of Federal Regulations, Part 190, Environmental Radiation Protection Standards for Nuclear Power Operations These limits were incorporated into the PNPP Technical Specifications, and subsequently into the PNPP ODCM. The ODCM prescribes the maximum doses and dose rates due to radioactive effluents resulting from the operation of PNPP. These limits are defined in several ways and serve to limit the overall impact on persons living

YEAR: 2022 Annual Radioactive Effluent Release Report Page 12 of 32 L-23-121 Company: Energy Harbor Plant: Perry Nuclear Power Plant near the plant. Since there are no other fuel sources near the PNPP, the 40 CFR 190 limits described below were not exceeded.

3.2.1 Liquid Effluents The maximum effluent concentrations for each isotope of radioactive material released in liquid effluents to unrestricted areas shall be limited to the concentrations specified in 10 CFR 20, Appendix B, Table 2, Column 2 for radionuclides other than dissolved or entrained noble gases, as required by the ODCM. For dissolved or entrained noble gases, the concentration is limited to 2.0E-04 uCi/ml. These values are the maximum effluent concentrations.

The dose or dose commitment to a member of the public from radioactive materials in liquid effluents released to unrestricted areas shall be limited to the following:

During any calendar quarter:

Less than or equal to 1.5 mrem to the whole body, and Less than or equal to 5 mrem to any organ During any calendar year:

Less than or equal to 3 mrem to the whole body, and Less than or equal to 10 mrem to any organ 3.2.2 Gaseous Effluents The dose rate due to radioactive materials released in gaseous effluents (including any releases from the on-site ISFSI) from the site to areas at and beyond the site boundary are governed by 10 CFR 20 and shall be limited to the following as required by the PNPP ODCM:

Noble gases:

Less than or equal to 500 mrem per year to the whole body, and Less than or equal to 3000 mrem per year to the skin lodine-131, iodine-133, tritium, and all radionuclides in particulate form with half-lives greater than eight days:

Less than or equal to 1500 mrem per year to any organ Air dose due to noble gases to areas at and beyond the site boundary are governed by 10 CFR 50 Appendix I and shall be limited to the following:

During any calendar quarter:

Less than or equal to 5 mrad for gamma radiation, and Less than or equal to 10 mrad for beta radiation During any calendar year:

Less than or equal to 10 mrad for gamma radiation, and Less than or equal to 20 mrad for beta radiation Dose to a member of the public from iodine-131, iodine-133, tritium, and all radionuclides in particulate form with half-lives greater than eight days in gaseous

YEAR: 2022 Annual Radioactive Effluent Release Report Page 13 of 32 L-23-121 Company: Energy Harbor Plant: Perry Nuclear Power Plant effluents released to areas at and beyond the site boundary shall be limited to the following:

Less than or equal to 7.5 mrem to any organ per any calendar quarter, and Less than or equal to 15 mrem to any organ per any calendar year The PNPP ODCM does not contain a concentration limit for gaseous effluents. For this reason, effluent concentrations are not used to calculate maximum release rates for gaseous effluents.

3.3 Release Summary Effluents are sampled and analyzed to identify both the typeand quantity of radionuclides present. This information is combined with effluent path flow measurements to determine the composition, concentration, and dose contribution of the radioactive effluents.

3.4 40 CFR 190 and 10 CFR 72.104 - Uranium Fuel Cycle Dose Assessment The 40 CFR 190 limit for whole body dose is 25 mrem. Considering all sectors, the total whole-body dose to a member of the general public was 0.35 mrem. This value was determined by summing the annual whole-body doses from liquid and gaseous radioactive effluents and the annual gaseous C-14 dose. Since the direct radiation dose, as determined by TLD, was indistinguishable from natural background, it was not included in the calculation. More information regarding direct radiation dose and the Independent Spent Fuel Storage Installation (ISFSI), may be found in Section 3.5.1.

3.5 Independent Spent Fuel Storage Installation (ISFSI)

Dose rates from the ISFSI contributing to a dose to a member of the public at or beyond the site boundary is governed by 10 CFR 72.104 and shall be limited to the following as required by the PNPP ODCM during any calendar year:

Less than or equal to 25 mrem whole body dose; Less than or equal to 75 mrem thyroid dose; and Less than or equal to 25 mrem to any other critical organ.

3.5.1 10 CFR 72.104, ISFSI Compliance Since installation of the Independent Spent Fuel Storage Installation (ISFSI) in 2011, eight TLDs have been placed on the outer perimeter fence of the cask storage area (located within the site boundary) to monitor dose due to direct radiation from the spent fuel stored on the ISFSI.

Since the dosimeters measure an accumulation of all sources of radiation, the following method was used to determine how to most accurately calculate the dose received to the nearest resident contributed only by the spent fuel at the ISFSI.

To determine the dose contributed by the spent fuel only, one needs to discriminate out the dose associated with background radiation as described above and other sources.

Dosimeters close to the plant are susceptible to "shine" which is radiation from

YEAR: 2022 Annual Radioactive Effluent Release Report Page 14 of 32 L-23-121 Company: Energy Harbor Plant: Perry Nuclear Power Plant nitrogen-16 that is reflected by the atmosphere. Background radiation and shine affect the surrounding TLDs almost uniformly.

The dosimeters closest to the dry casks receive more dose from the spent fuel and are thus affected by a lesser percentage by background radiation and plant effluents than those further away. To more accurately calculate the dose contribution to the nearest resident from the spent fuel, the dosimeter nearest to the point source is used.

The dose calculation was performed using the location of the nearest residence, assuming they remain at the location all year, because that individual would incur the maximum potential dose from direct exposure. The TLD at REMP location 7 found in the AREOR is positioned neighboring the nearest resident, was also reviewed for significant changes in readings.

To determine the dose rate to the nearest resident and demonstrate compliance, the following equation was used:

DiRi2=D2R22 where:

Di = dose rates (mrem/yr) at the TLD location D2 = dose rates (mrem/yr) to nearest resident R1 = distance (feet) of nearest TLD location to max individual R2 = distance (feet) to nearest resident The two nearest TLDs were chosen to estimate dose rates, which were #15 and #20, directly east and west of the dry casks. The corresponding estimated dose rates to the nearest resident was 1.81E-01 and 1.99E-01 mrem/yr, respectively, in 2022. In 2021, the calculated values were slightly higher, but statistically comparable to results of 2022.

Unlike the whole-body dose value of 3.50E-01 mrem presented in Section 3.4, the dose rates of 1.81E-01 and 1.99E-01 mrem/yr are an estimate based on TLD readings to demonstrate compliance. The calculation confirms that direct dose from the ISFSI does not exceed the 40 CFR 190 limit of 25 mrem/year.

Review of the TLD results from 2022 have shown no detectable impact on dose to the public due to radiation from the ISFSI nor significant changes in results to the public since employment of the ISFSI.

4.0 LIQUID EFFLUENTS The PNPP liquid radioactive waste system is designed to collect and treat all radioactive liquid waste produced in the plant. The treatment process used for radioactive liquid waste depends on its physical and chemical properties. It is designed to reduce the concentration of radioactive material in the liquid by filtration to remove suspended solids and demineralization to remove dissolved solids. Normally, the effluent from the liquid radioactive waste system is returned to plant systems. To reduce the volume of water stored in plant systems, however, the processed liquid effluents may be discharged from the plant via a controlled release. In this case, effluent activity and dose calculations are

YEAR: 2022 Annual Radioactive Effluent Release Report Page 15 of 32 L-23-121 Company: Energy Harbor Plant: Perry Nuclear Power Plant performed prior to and after discharging this processed water to Lake Erie to ensure regulatory compliance and dose minimization principles are maintained.

Liquid radioactive waste system effluents may be intermittently released. These intermittent releases are considered "batch" releases. Table 1 provides information on the number and duration of these releases for 2022.

Table 1: Liquid Batch Releases Quarter 1 Quarter 2 Quarter 3 Quarter 4 Number of batch releases 5 1 28 6 Total time period for batch releases, min 1.28E+03 2.21 E+02 7.79E+03 3.91 E+03 Maximum time for a batch release, min 5.82E+02 2.21 E+02 7.05E+02 2.11E+03 Average time period for a batch release, min 2.56E+02 2.21 E+02 2.78E+02 6.52E+02 Minimum time for a batch release, min 4.50E+01 2.21 E+02 3.00E+00 1.77E+02 Average quarterly flow rate, L/min 3.79E+00 3.79E+00 1.78E+05 6.57E+03 Table 2 provides information on the nuclide composition for the liquid radioactive effluent system releases.

YEAR: 2022 Annual Radioactive Effluent Release Report Page 16 of 32 L-23-121 Company: Energy Harbor Plant: Perry Nuclear Power Plant Table 2: Summation of All Liquid Effluent Releases Uncertaint Quarter 1 Quarter 2 Quarter 3 Quarter 4 y (%)

A. Fission and Activation Products

1. Total Released, Ci 0.00E+00 0.00E+00 1.48E-01 5.39E-05 1.00E+01 (excluding tritium, gases, alpha) 2 Average Diluted Concentration, 0.00E+00 0.00E+00 5.62E-09 2.39E-12 uCi/mL *
3. Percent of Applicable Limit, % 0.00E+00 0.00E+00 1.01 E-01 7.97E-05 B. Tritium
1. Total Released, Ci 3.24E-02 1.12E-02 6.37E+00 9.32E-03 1.00E+01
2. Average Diluted Concentration, 1.85E-09 5.88E-10 2.41 E-07 4.13E-10 uCi/mL
3. Percent of Applicable Limit, % 1.85E-04 5.88E-05 2.41 E-02 4.13E-05 C. Dissolved and Entrained Gases
1. Total Released, Ci 0.00E+00 0.00E+00 0.00E+00 0.00E+00 1.00E+01
2. Average Diluted Concentration, 0.00E+00 0.00E+00 0.00E+00 0.00E+00 uCi/mL
3. Percent of Applicable Limit, % 0.00E+00 0.00E+00 0.00E+00 0.00E+00 D. Gross Alpha Activity, Ci 0.00E+00 0.00E+00 0.00E+00 1.98E-07 1.00E+01 E. Waste Volume Released, Liters 2.70E+05 2.00E+05 8.56E+06 6.32E+06 (prior to dilution)*

F. Dilution Water Volume Used, 1.75E+10 1.91E+10 2.64E+10 2.25E+10 Liters In each case, LLDs were at or below the required values. Table 2a provides information specific to radioactive effluent batch releases. A batch release is the discharge of liquid waste of a discrete volume. Potential sources for a batch release at Perry are Liquid Radwaste Discharges via the Emergency Service Water system and auxiliary steam tritium in-leakage to the Auxiliary Boiler vented into the atmosphere.

Table 2a: Summation of Batch Liquid Effluent Releases

YEAR: 2022 Annual Radioactive Effluent Release Report Page 17 of 32 L-23-121 Company: Energy Harbor Plant: Perry Nuclear Power Plant Uncertainty Quarter 1 Quarter 2 Quarter 3 Quarter 4

(%)

A. Fission and Activation Products Total Released, Ci 1.00E+01 0.00E+00 0.00E+00 1.48E-01 5.39E-05 (excluding tritium, gases, alpha)

B. Tritium Total Released, Ci 3.15E-02 1.12E-02 6.36E+00 3.42E-03 1.00E+01 C. Dissolved and Entrained Gases Total Released, Ci 0.00E+00 0.00E+00 0.00E+00 0.00E+00 1.00E+01 D. Gross Alpha Activity, Ci 0.00E+00 0.00E+00 0.00E+00 1.98E-07 1.00E+01 E. Waste Volume Released, Liters 3.16E+04 5.47E+03 3.26E+06 1.86E+05 (prior to dilution)*

<LLD - Less than the lower limit of detection

  • Average diluted concentrations are based on total volume of water released during quarter.

Table 2b provides information specific to continuous radioactive effluent releases.

Potential sources for a continuous release at Perry are Residual Heat Removal (RHR) heat exchanger leakage into the Emergency Service Water system, Nuclear Closed Cooling (NCC) out-leakage into the Service Water system, tritium activity in the Turbine Building Ventilation Supply Plenum drain into storm drains, and Alternate Decay Heat Removal (ADHR) heat exchanger leakage into Service Water.

Table 2b: Summation of Continuous Liquid Effluent Releases Uncertainty Quarter 1 Quarter 2 Quarter 3 Quarter 4

(%)

A. Fission and Activation Products Total Released, Ci 0.00E+00 0.00E+00 0.00E+00 0.00E+00 1.00E+01 (excluding tritium, gases, alpha)

B. Tritium Total Released, Ci 9.13E-04 3.41 E-06 4.61 E-03 5.90E-03 1.00E+01 C. Dissolved and Entrained Gases Total Released, Ci 0.00E+00 0.00E+00 0.00E+00 0.00E+00 1.00E+01 D. Gross Alpha Activity, Ci 0.00E+00 0.00E+00 0.00E+00 0.00E+00 1.00E+01 E. Waste Volume Released, Liters 2.39E+05 1.95E+05 5.30E+06 6.14E+06 (prior to dilution)*

<LLD - Less than the lower limit of detection

  • Average diluted concentrations are based on total volume of water released during quarter.

Table 3 lists the total number of curies of each radionuclide present in liquid effluent releases for each quarter. In each case, the LLDs were either met or were below the levels required by the ODCM.

YEAR: 2022 Annual Radioactive Effluent Release Report Page 18 of 32 L-23-121 Company: Energy Harbor Plant: Perry Nuclear Power Plant Table 3: Radioactive Liquid Effluent Nuclide Composition Isotope Unit Quarter 1 Quarter 2 Quarter 3 Quarter 4 Annual Tritium Ci 3.24E-02 1.12E-02 6.36E+00 9.32E-03 6.42E+00 Sodium-24 Ci <5.0E-07 1 <5.0E-07 1 <5.0E-07 1 <5.0E-07 1 <5.0E-07 1 Chromium-51 Ci <5.0E-07 1 <5.0E-07 1 1.41E-03 <5.0E-07 1 1.41E-03 Manganese-54 Ci <5.0E-07 1 <5.0E-07 1 4.90E-03 <5.0E-07 1 4.90E-03 lron-55 Ci <1.0E-061 <1.0E-061 3.56E-02 <1.0E-061 3.56E-02 Manganese-56 Ci <5.0E-07 1 <5.0E-07 1 <5.0E-07 1 <5.0E-07 1 <5.0E-07 1 Cobalt-58 Ci <5.0E-07 1 <5.0E-07 1 1.13E-02 <5.0E-07 1 1.13E-02 lron-59 Ci <5.0E-07 1 <5.0E-07 1 1.67E-03 <5.0E-07 1 1.67E-03 Cobalt-60 Ci <5.0E-07 1 <5.0E-07 1 5.13E-02 5.39E-05 5.14E-02 Nickel-63 Ci <1.0E-061 <1.0E-061 4.59E-04 <1.0E-061 4.59E-04 Zinc-65 Ci <5.0E-07 1 <5.0E-07 1 3.89E-02 <5.0E-07 1 3.89E-02 Strontium-89 Ci <5.0E-08 1 <5.0E-08 1 <5.0E-08 1 <5.0E-08 1 <5.0E-08 1 Strontium-90 Ci <5.0E-08 1 <5.0E-08 1 <5.0E-08 1 <5.0E-08 1 <5.0E-08 1 Yttrium-91m Ci <5.0E-07 1 <5.0E-07 1 <5.0E-07 1 <5.0E-07 1 <5.0E-07 1 Strontium-92 Ci <5.0E-07 1 <5.0E-07 1 3.81 E-05 <5.0E-07 1 3.81 E-05 Molybdenum-99 Ci <5.0E-07 1 <5.0E-07 1 <5.0E-07 1 <5.0E-07 1 <5.0E-07 1 Technetium-99m Ci <5.0E-07 1 <5.0E-07 1 <5.0E-07 1 <5.0E-07 1 <5.0E-07 1 Silver-110m Ci <5.0E-07 1 <5.0E-07 1 2.12E-03 <5.0E-07 1 2.12E-03 Tin-113 Ci <5.0E-07 1 <5.0E-07 1 <5.0E-07 1 <5.0E-07 1 <5.0E-07 1 Antimony-124 Ci <5.0E-07 1 <5.0E-07 1 <5.0E-07 1 <5.0E-07 1 <5.0E-07 1 Antimony-125 Ci <5.0E-07 1 <5.0E-07 1 <5.0E-07 1 <5.0E-07 1 <5.0E-07 1 Cesium-137 Ci <5.0E-07 1 <5.0E-07 1 <5.0E-07 1 <5.0E-07 1 <5.0E-07 1 Lanthanum-140 Ci <5.0E-07 1 <5.0E-07 1 6.26E-04 <5.0E-07 1 6.26E-04 lodine-131 Ci <1.0E-061 <1.0E-061 <1.0E-061 <1.0E-061 <1.0E-061 Cerium-144 Ci <5.0E-06 1 <5.0E-06 1 <5.0E-06 1 <5.0E-06 1 <5.0E-06 1 Xenon-133 Ci <1.0E-051 <1.0E-051 <1.0E-051 <1.0E-051 <1.0E-051 Xenon-135 Ci <1.0E-051 <1.0E-051 <1.0E-051 <1.0E-051 <1.0E-051 Gross Alpha Ci <1.0E-071 <1.0E-071 <1.0E-071 <1 .OE-07 1 <1.OE-071 1 (<) Less than the ODCM-required lower limit of detection, units in uCi/mL 5.0 GASEOUS EFFLUENTS

SUMMARY

Gaseous effluents are made up of fission and activation gases, iodine, and paniculate releases. Gaseous effluents from PNPP exit the plant via one of four effluent vents.

Each of these four effluent vents contains radiation detectors that continuously monitor the air to ensure that the levels of radioactivity released are below regulatory limits.

Samples are also collected and analyzed on a periodic basis to ensure regulatory compliance. Gaseous effluents released from PNPP are considered continuous and at ground level. A summation of all gaseous radioactive effluent releases is given in Table

YEAR: 2022 Annual Radioactive Effluent Release Report Page 19 of 32 L-23-121 Company: Energy Harbor Plant: Perry Nuclear Power Plant Table 4: Summation of All Gaseous Effluents Uncertainty Quarter 1 Quarter 2 Quarter 3 Quarter 4

(%)

A. Fission and Activation Gases

1. Total Released, Ci 3.73E-01 8.05E-01 2.63E+00 2.29E+00 1.00E+01
2. Average Release Rate, uCi/sec 4.79E-02 1.02E-01 3.31 E-01 2.88E-01
3. Percent of Applicable Limit, % N/A N/A N/A N/A B. Iodine
1. Total lodine-131 Released, Ci 0.00E+00 0.00E+00 0.00E+00 7.97E-06 1.00E+01
2. Average Release Rate, uCi/sec 0.00E+00 0.00E+00 0.00E+00 1.00E-06
3. Percent of Applicable Limit, % N/A N/A N/A N/A C. Participates with Half-Lives > 8 days
1. Total Released, Ci 0.00E+00 0.00E+00 0.00E+00 0.00E+00 1.00E+01
2. Average Release Rate, uCi/sec 0.00E+00 0.00E+00 0.00E+00 0.00E+00
3. Percent of Applicable Limit, % N/A N/A N/A N/A
4. Alpha Activity, Ci 2.70E-06 2.69E-06 3.32E-06 4.22E-06 D. Tritium
1. Total Released, Ci 3.62E+00 4.86E+00 3.55E+00 4.93E+00 1.00E+01
2. Average Release Rate, uCi/sec 4.65E-01 6.18E-01 4.46E-01 6.21 E-01
3. Percent of Applicable Limit, % N/A N/A N/A N/A E. Carbon-14, Ci 4.59E+00 4.67E+00 4.54E+00 4.29E+00 1.00E+01 N/A - Not Applicable, the ODCM does not have a release rate limit for gaseous effluents.

Carbon-14 activity was calculated based on power production using the EPRI-provided spreadsheet The radionuclide composition of all gaseous radioactive effluents for a continuous-mode, ground-level release is given in Table 5. In each case, LLDs were met or were below the levels required by the ODCM.

YEAR: 2022 Annual Radioactive Effluent Release Report Page 20 of 32 L-23-121 Company: Energy Harbor Plant: Perry Nuclear Power Plant Table 5: Radioactive Gaseous Effluent NucUde Composition Isotope Unit Quarter 1 Quarter 2 Quarter 3 Quarter 4 Annual

1. Fission and Activation Gases Tritium Ci 3.62E+00 4.86E+00 3.55E+00 4.93E+00 1.70E+01 Argon-41 Ci <1.0E-041 <1.0E-041 2.23E+00 5.51 E-01 2.78E+00 Krypton-85m Ci 3.73E-01 8.05E-01 4.01 E-01 1.51E+00 3.09E+00 Krypton-87 Ci <1.0E-041 <1.0E-041 <1.0E-041 <1.0E-041 <1.0E-041 Krypton-88 Ci <1.0E-041 <1.0E-041 <1.0E-041 <1.0E-041 <1.0E-041 Xenon-133m Ci <1.0E-041 <1.0E-041 <1.0E-041 2.76E-02 2.76E-02 Xenon-133 Ci <1.0E-041 <1.0E-041 <1.0E-041 <1.0E-041 <1.0E-041 Xenon-135m Ci <1.0E-041 <1.0E-041 <1.0E-041 <1.0E-041 <1.0E-041 Xenon-135 Ci <1.0E-041 <1.0E-041 <1.0E-041 1.13E-01 1.13E-01 Xenon-138 Ci <1.0E-041 <1.0E-041 <1.0E-041 8.70E-02 8.70E-02 Total for Period Ci 3.99E+00 5.66E+00 6.18E+00 7.22E+00 2.31 E+01
2. Iodine/Halogens lodine-131 Ci <1.0E-121 <1.0E-121 <1.0E-121 7.97E-06 7.97E-06 lodine-133 Ci <1.0E-101 <1.0E-101 <1.0E-101 <1.0E-101 <1.0E-101 Total for Period Ci <LLD <LLD <LLD 7.97E-06 7.97E-06
3. Particulates Chromium-51 Ci <1.0E-11 1 <1.0E-11 1 <1.0E-11 1 <1.0E-11 1 <1.0E-11 1 Manganese-54 Ci <1.0E-11 1 <1.0E-11 1 <1.0E-11 1 <1.0E-11 1 <1.0E-11 1 Cobalt-58 Ci <1.0E-11 1 <1.0E-11 1 <1.0E-11 1 <1.0E-11 1 <1.0E-11 1 lron-59 Ci <1.0E-11 1 <1.0E-11 1 <1.0E-11 1 <1.0E-11 1 <1.0E-11 1 Cobalt-60 Ci <1.0E-11 1 <1.0E-11 1 <1.0E-11 1 <1.0E-11 1 <1.0E-11 1 Zinc-65 Ci <1.0E-11 1 <1.0E-11 1 <1.0E-11 1 <1.0E-11 1 <1.0E-11 1 Strontium-89 Ci <1.0E-11 1 <1.0E-11 1 <1.0E-11 1 <1.0E-11 1 <1.0E-11 1 Molybdenum-99 Ci <1.0E-11 1 <1.0E-11 1 <1.0E-11 1 <1.0E-11 1 <1.0E-11 1 Cesium-137 Ci <1.0E-11 1 <1.0E-11 1 <1.0E-11 1 <1.0E-11 1 <1.0E-11 1 Cerium-141 Ci <1.0E-11 1 <1.0E-11 1 <1.0E-11 1 <1.0E-11 1 <1.0E-11 1 Cerium-144 Ci <1.0E-11 1 <1.0E-11 1 <1.0E-11 1 <1.0E-11 1 <1.0E-11 1 Total for Period Ci <LLD <LLD <LLD <LLD <LLD 1 (<) Less than the ODCM-required lower limit of detection, units in uCi/mL

<LLD - Less than the ODCM-required lower limit of detection

YEAR: 2022 Annual Radioactive Effluent Release Report Page 21 of 32 L-23-121 Company: Energy Harbor Plant: Perry Nuclear Power Plant 5.1 Land Use Census Changes To estimate radiation dose attributable to operation of the PNPP, the potential pathways through which public exposure can occur must be known. To identify these pathways, an Annual Land Use Census is performed as part of the REMP. During the census, PNPP personnel travel public roads within a five-mile radius of the plant to locate key radiological exposure pathways. These key pathways include the nearest resident, garden, in each of the ten meteorological land sectors that surround the plant. The information obtained from the census is entered into a computer program used to assess hypothetical dose to members of the public. The predominant land use within the census area continues to be rural and/or agricultural. There were no changes to the REMP sampling locations compared to the 2021 Land Use Census.

5.2 Meteorological Data The Meteorological Monitoring System at PNPP consists of a 60-meter tower equipped with two independent systems for measuring wind speed, wind direction, and temperature at both 10-meter and 60-meter heights. The tower also has instrumentation to measure dew point and barometric pressure. Data is logged from the tower through separate data loggers and transmitted to a common plant computer. The program compiles the data and calculates a variety of atmospheric parameters, communicates with the Meteorological Information Dose Assessment System (MIDAS) and sends data over communication links to the plant Control Room.

A detailed report of the monthly and annual operation of the PNPP Meteorological Monitoring Program is produced as a separate document that is retained in PNPP Records and is available upon request. The report substantiates the quality and quantity of meteorological data collected in accordance with applicable regulatory guidance.

6.0 DOSE ASSESSMENT The maximum concentration for any radioactive release is controlled by the limits set forth in 10 CFR 20. Sampling, analyzing, processing, and monitoring the effluent streams ensures compliance with these concentration limits. Dose limit compliance is verified through periodic dose assessment calculations. Some dose calculations are conservatively performed for a hypothetical maximum individual who is assumed to reside on the site boundary at the highest potential dose location all year. This person, called the "maximum individual", would incur the maximum potential dose from direct exposure (air + ground + water), inhalation, and ingestion of water, vegetation, and fish.

Because no individual actually meets these criteria, the actual dose received by a real member of the public is significantly less than what is calculated for this hypothetical individual.

Dose calculations for this maximum individual at the site boundary are performed for two cases:

  • Using data for a 360-degree radius around the plant site (land and water-based meteorological sectors); even though some of these sectors are over Lake Erie, which has no permanent residents;
  • Considering only those sectors around the plant in which people reside (land-based meteorological sectors).

YEAR: 2022 Annual Radioactive Effluent Release Report Page 22 of 32 L-23-121 Company: Energy Harbor Plant: Perry Nuclear Power Plant The calculated hypothetical, maximum individual dose values at the site boundary are provided in Table 6. This table considers all meteorological sectors around PNPP and provides whole body and worst-case organ-dose values.

Table 6: Maximum Yearly Individual Site Boundary Dose, Considering All Sectors Estimated Type of Dose Organ Limit (mrem)  % of Limit Dose, (mrem)

Whole body 9.37E-02 3 3.1E+00 Liquid Effluent Liver 1.02E-01 10 1.0E+00 Air Dose 1.53E-02 10 1.5E-01 Gamma (mrad)

Noble Gas Air Dose Beta 6.96E-03 20 3.5E-02 (mrad)

Whole body 9.98E-03 5 2.0E-01 Noble Gas Skin 1.73E-02 15 1.2E-01 Tritium, Particulate & Thyroid 1.08E-02 15 7.2E-02 Iodine Carbon-14* Whole Body 2.46E-01 5 4.9E+00

  • C-14 dose calculated at nearest garden The hypothetical maximum dose within a 50-mile radius of site was calculated and is presented in Table 7. This table considers all meteorological sectors around PNPP and provides whole body and worst-case organ dose values.

Table 7: Population Yearly Dose, Considering All Sectors out to 50 miles Estimated Dose Organ (person-rem)

Whole body 1.5E+01 Liquid Effluent Thyroid 1.2E+01 Whole body 2.9E-03 Gaseous Effluent Thyroid 2.9E-03 A noted increase from 2021 annual population dose can be seen in the liquid effluent doses in Table 6 and Table 7. This is attributed to an increase in the number batch releases from the Auxiliary Boilers (see Section 15.2 for abnormal radioactive releases

YEAR: 2022 Annual Radioactive Effluent Release Report Page 23 of 32 L-23-121 Company: Energy Harbor Plant: Perry Nuclear Power Plant from the Auxiliary Boiler). Auxiliary Boiler batch releases are calculated in accordance with ODCM-compliant methodology with a conservative approach of zero dilution flow.

This, coupled with an increase in auxiliary boiler runs during 2022, attributes a higher dose to the annual liquid dose seen in these tables.

Table 8 provides the calculated hypothetical maximum site boundary dose values considering only the land-based sectors Table 8: Maximum Yearly Individual Site Boundary Dose (Only Land Sectors)

Estimated Limit Type of Dose Organ Dose,  % of Limit (mrem)

(mrem)

Whole Body 9.37E-02 3 3.1E+00 Liquid Effluent Liver 1.02E-01 10 1.0E+00 Air Dose 2.18E-05 10 2.2E-04 Gamma (mrad)

Noble Gas Air Dose Beta 1.33E-05 20 6.6E-05 (mrad)

Whole Body 2.12E-04 5 4.2E-03 Noble Gas Skin 3.59E-04 15 2.4E-03 Tritium, Particulate Thyroid 6.65E-04 15 4.4E-03

& Iodine Carbon-14* Whole Body 2.46E-01 5 4.9E+00 C-14 dose calculated at nearest garden.

Other dose calculations are performed for a hypothetical individual assumed to be inside the site boundary for some specified amount of time. This person would receive the maximum dose during the time spent inside site boundary. Because no person actually meets the criteria established for these conservative calculations, the actual dose received by a member of the public is significantly less than what is calculated for this hypothetical individual. This dose is assessed relative to the offsite dose, and considers dilution, dispersion, and occupancy factors.

The highest hypothetical dose from liquid effluents to a member of the public inside the site boundary is to a person who is fishing on Lake Erie from the shore on PNPP property. The calculations assume that this person will spend 60 hours6.944444e-4 days <br />0.0167 hours <br />9.920635e-5 weeks <br />2.283e-5 months <br /> per year fishing, with a liquid dilution factor of 10. The ratio of the exposure pathway to the doses calculated for offsite locations yields the dose values shown in Table 9.

YEAR: 2022 Annual Radioactive Effluent Release Report Page 24 of 32 L-23-121 Company: Energy Harbor Plant: Perry Nuclear Power Plant Table 9: Maximum Site Dose from Liquid Effluents Whole Body Dose, (mrem) Organ Dose, (mrem)

First Quarter 3.2E-01 3.2E-01 Second Quarter 1.1E-01 1.1E-01 Third Quarter 1.2E-01 2.2E-01 Fourth Quarter 3.5E-02 3.5E-02 Annual 5.8E-01 6.5E-01 Although several cases were evaluated to determine the highest hypothetical dose from gaseous effluents to members of the public inside the site boundary, the activity inside the site boundary with the highest dose potential is also shoreline fishing. The cases evaluated included traversing a public road within the site boundary, shoreline fishing (assuming fishing 60 hours6.944444e-4 days <br />0.0167 hours <br />9.920635e-5 weeks <br />2.283e-5 months <br /> per year), non-plant related training, car-pooling, and job interviews. The maximum on-site gaseous doses generated are shown in Table 10.

Table 10: Maximum Site Dose from Gaseous Effluents Whole Body Dose, (mrem) Organ Dose, (mrem)

First Quarter 2.65E-04 2.81 E-04 Second Quarter 2.72E-04 3.14E-04 Third Quarter 1.05E-03 1.58E-03 Fourth Quarter 6.26E-04 8.17E-04 Annual 2.22E-03 3.02E-03 An average whole body dose to individual members of the public at or beyond the site boundary is then determined by combining the dose from gaseous and liquid radiological effluents. The dose from gaseous radiological effluents is based upon the population that lives within 50 miles of PNPP. The dose from liquid radiological effluents is determined for the population that receives drinking water from intakes within 50 miles of PNPP. The results of this calculation are provided in Table 11.

Table 11: Average Individual Whole-Body Dose Liquid Effluents, (mrem) Gaseous Effluents, (mrem)

First Quarter 3.2E-03 1.8E-07 Second Quarter 1.1E-03 3.7E-07 Third Quarter 1.4E-03 3.8E-07 Fourth Quarter 3.5E-04 3.0E-07

YEAR: 2022 Annual Radioactive Effluent Release Report Page 25 of 32 L-23-121 Company: Energy Harbor Plant: Perry Nuclear Power Plant Annual 6.3E-03 1.2E-06 7.0 SOLID WASTE All solid radioactive waste from PNPP was processed and combined with waste from several other utilities by intermediate vendors. The final waste after processing is sent to Energy Solutions' disposal facility in Clive, Utah for burial. Table 12 summarizes the solid waste characterization and disposition of waste shipments in 2022.

Table 12: Solid Waste Shipped Offsite for Burial or Disposal

1. Type of Solid Waste Shipped Volume (m3) Activity (Ci) Uncertainty (%)
a. Resins, Filters, and Evaporator 9.76E+01 2.93E+02 +/-25 Bottoms
b. Dry Radioactive Waste 2.15E+02 7.97E-02 +/-25
c. Irradiated Components 0.00E+00 0.00E+00 +/-25
d. Other Radioactive Waste 0.00E+00 0.00E+00 +/-25
2. Estimate of Major (1) Nuclide Abundance Radionuclide Uncertainty (%)

Composition (by type of waste) (%)

Mn-54 4.19

a. Resins, Filters and Evaporator Fe-55 41.63

+/-25 Bottoms Co-60 50.45 Zn-65 1.89 Mn-54 2.09

b. Dry Active Waste Fe-55 32.54 +/-25 Co-60 63.27
c. Irradiated Components, Control N/A N/A N/A Rods, etc.
d. Other Waste N/A N/A N/A
3. Dry Active Waste, Resins, Filters, and Evaporator Bottom Shipments Mode of Number of Shipments Destination Transportation Hittman Energy Solutions Bear Creek 28 Transport Operations Landstar Energy Solutions Bear Creek 1

Ranger Operations Landstar Unitech Services Group 2323 1

Ranger Zirconium Road (1) - "Major" is defined as any individual radionuclide identified as >1% of the waste type abundance.

N/A - Not applicable due to no shipments

YEAR: 2022 Annual Radioactive Effluent Release Report Page 26 of 32 L-23-121 Company: Energy Harbor Plant: Perry Nuclear Power Plant There were no irradiated fuel shipments in 2022.

8.0 APPLICABLE TECHNICAL SPECIFICATION AND ODCM DEVIATIONS There were no liquid or gaseous effluent radiation monitoring instrumentation out of service for greater than 30 days in 2022.

There were no ODCM non-compliances in 2022.

There were no Technical Specification 5.5.8.b non-compliances in 2022.

9.0 OFFSITE DOSE CALCULATION MANUAL (ODCM) CHANGES There were no changes to the ODCM in 2022.

10.0 PROCESS CONTROL PROGRAM (PCP) CHANGES There were no changes to the PCP in 2022.

11.0 RADIOACTIVE WASTE TREATMENT SYSTEM CHANGES There were no changes to the Radioactive Waste Treatment System in 2022.

12.0 CORRECTIONS TO PREVIOUS ARERRS During this annual report compilation, it was identified that a software deviation had occurred. An audit of dose assessment software parameters revealed some parameters that were not aligned with the ODCM. Corrections to software parameters were made to align with the ODCM. An audit of dose assessment software parameters was completed for the 2022 report. A review of previously submitted reports is underway in 2023.

Updated reports will be submitted in 2023 based on the results of the audit.

13.0 CARBON-14 SUPPLEMENTAL INFORMATION Carbon-14, with a half-life of 5730 years, is a naturally occurring isotope of carbon produced by cosmic ray interactions in the atmosphere. Nuclear weapons testing in the 1950s and 1960s significantly increased the amount of C-14 in the atmosphere.

Carbon-14 is also produced in commercial nuclear reactors, but the amounts produced are much less than those produced naturally or from weapons testing. It is released primarily from Boiling Water Reactors through the Off-gas system in the form of carbon dioxide (CO2). The quantity of gaseous C-14 released to the environment can be estimated using a C-14 source term scaling factor based on power generation.

The U.S. Nuclear Regulatory Commission requires an assessment of gaseous C-14 dose impact to a member of the public resulting from routine releases in radiological effluents. Prior to 2011, the industry did not estimate the dose impact of C-14 releases

YEAR: 2022 Annual Radioactive Effluent Release Report Page 27 of 32 L-23-121 Company: Energy Harbor Plant: Perry Nuclear Power Plant because the dose contribution had been considered negligible compared to the dose impact from effluent releases of noble gases, tritium, particulates, and radioiodine.

This report contains estimates of the gaseous C-14 radioactivity released and the resulting public dose resulting from this release. The calculation is performed using a spreadsheet provided by EPRI and is based on power production and is adjusted for growing season, percent daylight, age (adult), and undepleted atmospheric dispersion (X/Q) value for the critical receptor.

This method for estimating C-14 released has been endorsed by the NRC. Because the dose contribution of C-14 from liquid radioactive waste is much less than that contributed by gaseous radioactive waste, evaluation of C-14 in liquid radioactive waste at PNPP is not required. Refer to Table 4, Table 6, and Table 8 for C-14 estimated release values and doses.

14.0 NEI 07-07 ONSITE RADIOLOGICAL GROUNDWATER MONITORING PROGRAM Based on the Environmental Resource Management hydrogeology study, 12 groundwater monitoring wells were recommended for the site. Since most groundwater flow drains north toward Lake Erie, most wells are drilled north of the plant. A set of control wells were drilled south of the plant to assess a typical groundwater profile.

There are sets of three wells installed at four locations. Each set has a shallow well with a depth of approximately 25 feet, a mid-depth well with a depth of approximately 50 feet, and a deep well with a depth of approximately 75 feet. These three depths are designated A, B, and C from shallowest to deepest, respectively.

PNPP has an Underdrain system to prevent groundwater hydrostatic pressure buildup on plant structures. The Underdrain system has two installed radiation monitors that assess the process stream prior to the stream flowing into the Emergency Service Water system.

More than 30 piezometers comprise the outdoor piezometers located in four separate transects oriented in the north, south, east, and west directions. These wells were installed to monitor the performance of the Underdrain System and ensure reduction in groundwater levels around the Power Block.

Refer to Figure 5 for locations of Groundwater Wells 1A through 4C, Outdoor Quadrant Piezometers north through south, and Underdrain Manholes 20 and 23. These wells, piezometers, and manholes encompass the groundwater monitoring locations at PNPP.

The monitoring wells and quadrant piezometers are sampled twice annually, in spring and fall. The samples are shipped to a vendor for gamma isotopic and tritium analysis.

Any positive result less than 500 pCi/L is considered as background activity and not due to plant operations. The ODCM reporting level for tritium in an environmental water sample is 20,000 pCi/L. The tritium results of samples obtained in 2022 can be found in Table 13.

Effluent tritium activity LLDs are classified as uCi/ml in the ODCM. Groundwater reporting levels for tritium activity are stated in pCi/L. The unit conversion from uCi/ml to

YEAR: 2022 Annual Radioactive Effluent Release Report Page 28 of 32 L-23-121 Company: Energy Harbor Plant: Perry Nuclear Power Plant pCi/L causes a change of nine orders of magnitude. Underdrain manhole 20 and 23 effluents pathway is Emergency Service Water.

Figure 5: Underdrain System, Piezometer Tubes, and Groundwater Monitoring Wells Table 13: Summary of Onsite Groundwater and Outdoor Piezometer Samples Spring Fall Sample Type Functional Location H-3, pCi/L H-3, pCi/L Outdoor Piezometer N-3-83 216 287 Outdoor Piezometer E-2-83 268 280 Outdoor Piezometer S-2-89 <170 <160 Outdoor Piezometer W-7-83 <170 <160 Monitoring Well 1A <170 <160 Monitoring Well 1B <170 <160 Monitoring Well 1C <170 <160 Monitoring Well 2A <170 <160 Monitoring Well 2B <170 <160 Monitoring Well 2C <170 NS Monitoring Well 3A <170 263 Monitoring Well 3B <170 <160 Monitoring Well 3C <170 NS

YEAR: 2022 Annual Radioactive Effluent Release Report Page 29 of 32 L-23-121 Company: Energy Harbor Plant: Perry Nuclear Power Plant Monitoring Well 4A <170 284 Monitoring Well 4B <170 <160 Monitoring Well 4C <170 <160

(<) Less than values represent the MDA of the instrument at the time of analysis NS Insufficient sample volume for analysis The Underdrain manholes are sampled and analyzed quarterly for principal gamma emitters and tritium by PNPP personnel in accordance with site procedures. The tritium results of samples obtained in 2022 can be found in Table 14.

Table 14: Summary of Underdrain Manhole Samples Underdrain Quarter 1 Quarter 2 Quarter 3 Quarter 4 Manhole H-3, nCi/ml H-3, nCi/ml H-3, mCi/ml H-3, nCi/ml 20 5.52E-05 2.58E-06 4.53E-06 2.42E-06 23 <LLD 3.11E-07 <LLD 4.50E-07

<LLD - Less than the ODCM-required lower limit of detection On December 16, 2021 tritium was detected in Underdrain Manhole 20 during quarterly sampling. The tritium concentration was 1750 pCi/L with no detectable gamma activity. A backup sample was obtained on December 17, 2021 confirming there was detectable tritium activity present. The tritium value was 2050 pCi/L which exceeded voluntary reporting requirements, of 2000 pCi/L, to local agencies as specified in plant procedures.

A voluntary report was made on December 17, 2021.

An investigation, chemistry sampling plan, and tritium action plan were implemented to identify the source of the tritium. Actions were still being performed in 2022, and monitoring will continue in accordance with plant procedures. Tritium activity has returned to background levels.

14.1 Voluntary Notification No voluntary notifications were made in 2022.

15.0 Abnormal Releases There were no abnormal gaseous releases in 2022.

PNPP had two abnormal liquid release pathways present in 2022 as discussed below.

15.1 Nuclear Closed Cooling Residual radioactivity remains in the Nuclear Closed Cooling (NCC) system due to past leakage from the reactor coolant system. Radioactivity is monitored, and detectable activity measured from the NCC system to Emergency Service Water is recorded as a continuous abnormal release. NCC had no gamma activity detected in 2022 but did have detectable tritium and alpha - these were captured in the annual calculations.

YEAR: 2022 Annual Radioactive Effluent Release Report Page 30 of 32 L-23-121 Company: Energy Harbor Plant: Perry Nuclear Power Plant On December 14, 2021, the Nuclear Closed Cooling Process Radiation Monitor count rate increased indicating a radioactive leak into the system. After an investigation, it was determined that a failed thermal neck the Reactor Water Clean Up (RWCU) pump A was the cause of the in-leakage. The RWCU A pump was taken out of service to stop the radioactive ingress. The NCC gamma isotopic activity in the system was removed by decay of short-lived nuclides and using a side-stream demineralizer to remove the long-lived isotopes. The thermal neck was replaced, and the RWCU A pump was returned to service.

In August 2022, the NCC Radiation Monitor counts started increasing again.

Troubleshooting identified that the source of the ingress was again a crack in the RWCU A pump thermal neck. The RWCU A pump was out-of-service from 8/3/2022 through 8/25/2022. The repair of the thermal neck of the RWCU A pump was completed with a new design of thermal neck that addresses the weak welds that were the cause of the repeated failures.

As a result, the NCC system contained tritium activity and was recorded as a continuous abnormal release. Activity was assessed in the monthly effluent surveillance, and exposure is accounted for in Table 2, Table 2b, Table 3, Table 6, Table 7, Table 8, Table 9, and Table 11.

Continuous releases from NCC in 2022 are summarized in Table 15 with activity released tabulated in Table 16.

Table 15: NCC Continuous Releases Quarter 1 Quarter 2 Quarter 3 Quarter 4 Total time period for continuous 8.50E+04 1.31E+05 1.32E+05 8.78E+04 release, min Total volume released, liters 2.39E+05 1.95E+05 3.97E+05 3.66E+05 Average SW quarterly flow rate, 1.33E+05 1.41E+05 1.88E+05 1.52E+05 L/min Table 16: NCC Total Activity Quarter 1 Quarter 2 Quarter 3 Quarter 4 Annual A. Fission and Activation 0.00E+00 0.00E+00 0.00E+00 0.00E+00 0.00E+00 Products (Ci)

B. Tritium (Ci) 9.93E-04 2.09E-04 1.48E-03 1.60E-04 2.84E-03 C. Noble Gases (Ci) <1.0E-051 <1.0E-051 <1.0E-051 <1.0E-051 <1.0E-051 D. Gross Alpha (Ci) <1.0E-071 <1.0E-071 <1.0E-071 1.74E-09 1.74E-09 1 (<) Less than the ODCM-required lower limit of detection, units in uCi/mL

YEAR: 2022 Annual Radioactive Effluent Release Report Page 31 of 32 L-23-121 Company: Energy Harbor Plant: Perry Nuclear Power Plant 15.2 Auxiliary Boiler In March of 2020 tritium activity was detected in manhole 23's first quarterly sample. The source of this activity was auxiliary steam leaks bleeding into the auxiliary boiler deaerator. This excess water was drained into the underdrain system. Once the intrusion was discovered, the draining was stopped. Manhole 23 was monitored. Auxiliary steam valves were investigated and repaired. The auxiliary boiler tritium source was identified as an auxiliary steam to reactor feed pump turbine isolation valve. The station has scheduled to repair this valve.

The boiler was sampled and analyzed for tritium and gamma emitters each time it was operated with site procedures to quantify the tritium releases using an ODCM-compliant methodology when the boiler was vented to atmosphere. Tritium and alpha activity were detected in the Auxiliary Boilers in January, February, March, June, August, October, November, and December of 2022. Samples were composited and analyzed as a batch release using the ODCM. This activity was assessed in the monthly effluent surveillance and is included in Table 2, Table 2a, and Table 3. Exposure resulting from this release is accounted for in Table 6, Table 7, Table 8, Table 9, and Table 11.

Auxiliary Boiler batch releases in 2022 are summarized in Table 17 with activity released tabulated in Table 18.

Table 17: Auxiliary Boiler Batch Release Quarter 1 Quarter 2 Quarter 3 Quarter 4 Total time period for batch release, 1.35E+03 2.21 E+02 5.00E+01 3.79E+03 min Total volume released, liters 3.16E+04 5.47E+03 1.24E+03 9.39E+04 Average quarterly flow rate, L/min 2.34E+01 2.48E+01 2.48E+01 2.48E+01 Table 18: Auxiliary Boiler Total Activity Quarter 1 Quarter 2 Quarter 3 Quarter 4 Annual A. Fission and Activation 0.00E+00 0.00E+00 0.00E+00 0.00E+00 0.00E+00 Products (Ci)

B. Tritium (Ci) 3.82E-02 1.12E-02 1.76E-03 9.96E-04 5.22E-02 C. Noble Gases (Ci) <1.0E-051 <1.0E-051 <1.0E-051 <1.0E-051 <1.0E-051 D. Gross Alpha (Ci) <1.0E-071 <1.0E-071 <1.0E-071 1.96E-07 1.96E-07 1 (<) Less than the ODCM-required lower limit of detection, units in pCi/mL

YEAR: 2022 Annual Radioactive Effluent Release Report Page 32 of 32 L-23-121 Company: Energy Harbor Plant: Perry Nuclear Power Plant 16.0 BIBLIOGRAPHY

[I] "NCRP Report No. 160, "Ionizing Radiation Exposure of the Population of the United States"," National Council on Radiation Protection and Measurements, Bethesda, MD, 2009.

[2] [Online]. Available: http://hps.org/hpspublications/radiationfactsheets.html. [Accessed 2020].

[3] "NRC Resource Page," [Online]. Available: http://www.nrc.gov/about-nrc/radiation.html. [Accessed 10 November 2020].

[4] "Regulatory Guide 1.109, "Calculation of Annual Doses to Man from Routine Releases of Reactor Effluents for the Purpose of Demonstrating Compliance with 10 CFR Part 50, Appendix I,," Nuclear Regulatory Commission, Ocotober, 1977.

[5] "NUREG-0133, Preparation of Effluent Technical Specifications for Nuclear Power Plants," Nuclear Regulatory Commission, 1987.

[6] "40 CFR Part 141, "National Primary Drinking Water Regulations,"," US Environmental Protection Agency, Washington, DC.

[7] Nuclear Regulatory Commission, 25 June 2015. [Online]. Available: http://www.nrc.gov/reading-rm/basic-ref/students/animated-bwr.html. [Accessed October 2020].

[8] "Branch Technical Position, Revision 1," NRC000096, Submitted March 30, 2012, November 1979.

[9] "Japan Atomic Energy Agency," 06 November 2020. [Online]. Available:

https://www.jaea.go.jp/english/04/ntokai/houkan/houkan_02.html.

[10] "NUREG-0324, "XOQDOQ, Program for the Meteorological Evaluation of Routine Effluent Releases at Nuclear Power Stations,"," Nuclear Regulatory Commission, September, 1977.

[II] "NUREG-1301, "Offsite Dose Calculation Manual Guidance: Standard Radiological Effluent Controls for Pressurized Water Reactors,".," Nuclear Regulatory Commission, April 1991.

[12] "NUREG-1302, "Offsite Dose Calculation Manual Guidance: Standard Radiological Effluent Controls for Boiling Water Reactors,"," Nuclear Regulatory Commission, April 1991.

[13] Nuclear Regulatory Commission, 30 June 2015. [Online]. Available: http://www.nrc.gov/reading-rm/basic-ref/students/animated-pwr.html. [Accessed October 2020].

[14] "Regulatory Guide 4.13, Performance, Testing, and Procedural Specifications for Thermoluminescence Dosimetry: Environmental Applications, Revision 2," Nuclear Regulatory Commision, June, 2019.

[15] "Regulatory Guide 4.15, Quality Assurance for Radiological Monitoring Programs (Inception through Normal Operations to License Termination) - Effluent Streams and the Environment," Nuclear Regulatory Commission, July, 2007.

[16] "NEI 07-07, "Industry Ground Water Protection Initiative Final Guidance Document, Rev. 1"," Nuclear Energy Institute, Washington, D.C., 2019.

[17] "10 CFR 50, "Domestic Licensing of Production and Utilization Facilities"," US Nuclear Regulatory Commission, Washington, DC.

[18] "10 CFR Part 20,," US Nuclear Regulatory Commission, Washington, DC.

[19] "40 CFR 190," US Environmental Protection Agency, Washington, DC.