IE Insp Repts 50-416/79-26 & 50-417/79-26 on 791016-19. Noncompliance Noted:Test Sieves Used for Particulate Size Analysis Not Calibr or Checked for Conformance W/Astm E-11
ML19296C094
Person / Time
Site: Grand Gulf  
Issue date: 10/26/1979
From: Conlon T, Harris J
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To:
Shared Package
ML19296C067 List:
References
50-416-79-26, 50-417-79-26, NUDOCS 8002250211
Download: ML19296C094 (4)


Text

p atogN

o UNITED STATES

~ ' '

! ' t ).,., c

'g NUCLEAR REGULATORY COMMISSION

"

  • f~

- e REGION 11

-/

o

!

101 MARIETT A ST., N.W., Suf 7E 3100 E

ATLANTA, G EORO LA 30303 o

.....

Report Nos. 50-416/79-26 and 50-417/79-26 Licensee: !iississippi Power and Light Company Jackson, Mississippi Facility Name:

Grand Gulf Docket Nos. 50-416 and 50-417 License Nos. CPPR-118 and CPPR-119 Inspection at Grand Gulf near Port Gibson, Mississippi J. Q. d C kV &

_ / /2 // >

Inspector:

lia r ri s Date Signed Approved by: hkhrtt e fec

/C/h [' /

T. E. Conlon, Section Chief, RC&ES Branch Dfite Signed SUMMARY Inspection on October 16-19, 1979 Areas Inspected This routine, unannounced inspection involved 28 inspector-hours on-site in the areas of general construction, structural concrete and structural backfill.

Results Of the three areas inspected, no items of noncompliance or deviations were identified in one area; one item of noncompliance was found in two areas (Infrac-tion-Calibration of soils and concrete aggregate test sieves paragraph 5).

800 2 2 5 0 r_ ll

.

/

DETAILS 1.

Pers ns Contacted Licensee Employees

  • J. C. Fuller, Acting QA Field Supervisor
  • W. M. Garnec, Civil QA Representative T. E. Reeves, Managet of Quality Assurance all. D. Morgan, Construction Supervisor Other licensee employees contacted during this inspection included three construction craftsmen and eight technicians.

Other Organizations kJ. W. Yelverton, Quality Assurance Engineer, Bechtel

  • A. S. Bettencourt, Quality Assurance Engineer, Bechtel W. Bearden, Cadweld QC Inspector, Bechtel L. Luckett, Concrete QC Inspector, Pittsburgh Testing Laboratory kJ. II. Conway, Assistant Project Field QC Engineer, Bechtel
  • B. Bailess, Lead Civil QC Engineer, Bechtel hAttended exit interview.

2.

Exit Interview The inspection scope and findings were summarized on October 19, 1979 with those persons indicated in Paragraph 1 above 3.

Licensee Action on Previous Inspection Findings Not inspected.

4.

Unresolved Items Unresolved items were not identified during this inspection.

5.

Independent Inspection The inspector examined the following areas:

General inspection of the site and ongoing work activities a.

b.

Partial placement of pour number QIT22-WO7174 SOA(B), slab in unit I auxiliary building c.

Storage facilities for concrete materials

.

.

.

-2-d.

Compaction and testing of granular backfill between the tieback wall and Unit 2 auxiliary building Backfill compaction test record numbers 803, 804, 805, 842 and 844 e.

f.

Calibration controls on concrete and soils laboratory testing equipment Examination of calibration controls at the soils and concrete testing laboratories disclosed the following noncompliance.

Paragraph 4.12 of Appendix C to specification 9645-C-191.0, Materials Testing Services, states, "

. measuring and testing devices used in checking quality shall be calibrated ar.d documented at established periods against valid standards having known relationships to national standards where they exist".

Para-graph 6.21 of specification 9645-C-1910.0 requires that the soils and concrete laboratory be equipped with calibrated equipment for the perfor-mance of all field tests required under the specification.

Tais equipment is to include all testing devices and apparatus listed in applicable ASTM specifications.

Paragraphs 8.3.5 and 11.2e require that sieve analyses be done on aggregates in accordance with ASTM C-136-71 and on granular backfill in accordance with /STM D422-63. ASTM C-136-71 and ASTM D422-63 state that sieves used shall conform to ASTM E-11.

Examination of test sieves and discussions with responsible engineers showed that test sieves used for particle size analysis of concrete aggregates and granular backfill are not calibrated or checked for conformance to ASTM E-11.

Failure to perform test activities as required by documented instructions is ccntrary to Criterion V of Appendix B to 10 CFR 50 and was identified to the licensee as Infraction 417/79-26-01.

The licensee acknowledged the item of noncom-pliance. Quality Action Request number F-172 was issued to Bechtel's headquarters QC staff in Gaithersburg, Maryland by the site QC staff, requesting applicability ol ASTM E-11 for calibration of test sieves.

6.

Containment (Structural Concrete II)-Observation of Work and Work Activities, Unit 2 The inspector observed curing controls on pour number Q2T22-W-21164WXA, exterior wall in the unit 2 auxiliary building and splicing of Cadweld number CD 3056 in the Unit 2 drywell. Acceptance criteria examined by the insepctor appear in the following documents:

a.

PSAR Section 3.8.1.7.6 and 3.8.1.7.7 b.

Specification 9645-C-103, Form, Place Finish and Cure Concrete Specification 9645-C-115.0, Install Reinforcing Mechanical Splices c.

d.

QCI 9.1, Concrete Inspection Activities QCI 9.1.7, Inspection of Reinforcing Mechanical Splices e.

Curing and Cadwelding operations were done by qualified personnel in accordance with acceptance criteria and were inspected by QC inspector.

.

.

g-3-No deviations or items of noncompliance were identified.

7.

Conta irtment (Structural Concrete II) Review of Quality Records, Unit 2 The inspector examined quality records on concrete materials, batch plant operations, audits of concrete operations, and eleven nonconformance report s.

Acceptance criteria examined by the inspector, in addition to those listed in paragraph 6, appear in the following documents:

a.

PSAR 3.8.1.7 b.

Specification 9645-C-191.0, Materials Testing Services c.

Specification 9645-C-101, Furnish and Deliver Concrete Records examined included:

Calibration records on batch plant scales and metering devices for a.

1979 to date b.

Physical and chemical tests on aggregates, cement, water, AEA and WRA for 1979 to date Nonconformance report, numbers 3732, 3884, 3886, 3990, 3995, 4048, c.

4070, 4218, 4140, 4212 and 3862 d.

Bechtel audit numbers F-C-31, F-C-46, F-C-43, F-C-32, F-C-40 and F-C-35; MP&L audit numbers QACI-79-18 and QACI-79-06 No deviations or items of noncompliance we:e identified.