IR 05000327/1980048

From kanterella
Jump to navigation Jump to search
IE Insp Repts 50-327/80-48 & 50-328/80-26 on 801216-19.No Noncompliance Noted.Major Areas Inspected:Installed Equipment Review Per NUREG-0588 Response
ML19345G335
Person / Time
Site: Sequoyah  Tennessee Valley Authority icon.png
Issue date: 02/09/1981
From: Conlon T, Gibbons T
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To:
Shared Package
ML19345G334 List:
References
50-327-80-48, 50-328-80-26, NUDOCS 8103180426
Download: ML19345G335 (4)


Text

.

( ~

[

jo, UNITED STATES

V}

NUCLEAR REGULATORY COMMISSION

,,

,,

2.h

$

REGION 11 2

101 MARIETTA ST., N.W..SulTE 31C3

'

c,.

ATLANTA, GEORGIA 30303 o

FEB - 91981 Report Nos. 50-327/80-48 and 50-328/80-26 i

Docket Nos. 50-327 a...

w-328 Licensee: Tennessee Valley Authority 500A Chestnut Street Chattanooga, Tennessee 37401 Facility Name: Sequoyah, Units 1 and 2 License Nos. DPR-77 and CPPR-73 Inspection at Sequoya site near Chattanooga, Tennessee 2/9![/

Inspector:

/

T. D. Gibbons Date Signed Of9!f/

Approved b

  1. 1

/

T. E. Conlon, Section Chief, RC&ES Branch D6te' Signed Dates of Inspection: December 16-19, 1980 Areas Inspected This special announced inspection involved 33 inspector-hours on site in the areas of installed equipment review with respect to the NUREG 0588 response.

Results Of the areas inspected, no violations or deviations were identified, d103184

.

DETAILS 1.

Persons Contacted Licensee Employees

  • W. D. Cottle, Assistant Plart Manager

"G. L. Dill, Engineering Associ +-

'

"M. A. Sisson, Engineering Aide NRC Resident Ins;+ tor

  • S. D. Butler
  • Attended exit interview 2.

Exit Interview The inspection scope and findings were summarized on December 19, 1980 with those persons indicated in paragraph I above.

3.

Licensee Action on Previous Inspection Findings Not inspected.

,

4.

Unresolved Items Unresolved items were not icentified during this inspecticn.

5.

NUREG 0588 (Unit 1)

A physical examination was made of installed electrical instrumentation and control equipment associated with the Emergency Raw Cooling Wa+?r, Fe'edwater and Component Cooling Water sptems.

The equipment that ws axamined is located outside primary containmenk The specific equipme -t examined is listed below:

'

EMERGENCY RAW COOLING WATER Plant.ID Description MFGR Model 1-TIC-67-84

. Temperature Ind.: Cont-Robertshaw 326-C3-C1 1-TIC-67-85-Temperature Ind. Cont Robe'rtshaw 326-C3-C1 1-TIC-67-92 Temperature Ind. Cont Robertshaw 326-C3-C1 1-TIC-67-93-Temperature Ind.' Cont Robertshaw 326-C3-C1 1-TIC-67-100 Temperature Ind. Cont Roberts..aw 326-C3-C1 1-TIC-67-101 Temperature Ind. Cont -Robertshaw 326-C3-C1 1-TIC-67-108.

-Temperature Ind. Cont. Robertshaw 326-C3-C1

-

L__

-

-

-

,M

.

-

. - _. -

-.

.-

. - _ - _ -

-

-.

..-.

-.

.

.

3 J

,

.

1-TIC-67-109 Temperature Ind. Cont Robertshaw 326-C3-C1 1-FCV-67-125 Motor Operator Raymond TN-2000

1-FSV-67-342 Solenoid Valve ASCO HB830081RU

,

'

1-FSV-67-344 Solenoid Valve ASCO HC8300C58RU

,

1-FSV-67-354 Solenoid Valve ASCO HB8300C58RU 1-FSV-67-356 Solenoid Valve ASCO HE'300C58RU i

FEEDWATER 1FCV-3-136B Motor Operator Limitorque SMB-00 i

IFCV-3-136A Motor Operator Limitorque SMB-00 IFCV-3-179A Motor Operator Limitorque SMB-00 IFCV-3-179B Motor Operator Limitorque SMB-00

-.1FCV-3-1168 Motor Operator Limitorque SMB-000 1FCV-3-1268 Motor Operator Limitorque SMB-000 1FCV-3-116A Motor Operator Limitorque SMB-000 IFCV-3-126A Motor Operator Limitorque SMB-000

=1-PS-3-138A Pressure Switch Custom Camponents 604GBJR3-489S

1-PS-3-1388 Pressure Switch Custom Components 604GCMI-7009 1-PS-3-139A.

Pressure Switch Custom Components 604GBJR1-489S

-

1-PS-3-1408 Pressure -Switch Custom Components 604GCJR3-5405 1-PS-3-140A Pressure Switch Custom Components 604GCJR3-540S

L 1-PS-3-150A Pressure Switch Custom Components 604GCJR3-540S-1-FT-3-142 Flow Transmitter GE 50-555-111BDAA4WBE

'

COMPONENT COOLING WATER FT-70-81E Flow Transmitter GE 50-555-111BCAA4WBF FT-70-818 Flow Transmitter GE 50-555-111BCAA4WBF FCV-70-134-Motor Operator Limitorque SM8000

-

FCV-70-133 Motor Operator Limitorque SMB000 FCV-70-153 Motor Operator Raymond TN 2000

~

FCV-70-156 Motor Operator Ra,mond TN 2000

'

.

The. equipment 0 inspected was examined. for proper installation, overall interface integrity 'and manufacturer's nameplate data was obtained.

The

'

nameplate data was compared to the information listed on the licensee report.

. The licensee has conducted.a walkdown for corrections to the report. The discrepancies have'L4an identified by the licensee and a revision to the report.will be issued. Within the areas examined there were no violations

. identi fied.

l6.

'NUREG 0588 (Unit 2)

-

'

s A physical, examination was made of installed electrical ir.strumentatter and control equipment associated with the Reactor Coolant, Emergency. Raw Doling

. Water and the Chemical and Volume Control systems. ' The equipment examined is

< located 11n i the '. primary containment.. The 's ecificl equ',pment examined is 311sted below:

.

l J

.

'

~

n

..

.

o m

._.

.

_ _.

-

d S

p

REACTOR COOLANT 2-FT-68-6A Flow Transmitter Foxboro E13DH 2-FT-68-29A'

Flow Transmitter Foxboro E13DH 2-FT-68-48A Flow Transmitter Foxboro E13DH 2-FT-68-71A Flow Transmitter Foxboro E13DH 2-FT-68-6B Flow Transmitter Foxboro E13DH 2-FT-68-29B Flow Transmitter Foxboro E130H 2-FT-68-48B Flow Transmitter Foxboro E13DH 2-FT-68-718 Flow Transmitter Foxboro E13DH 2-FT-68-60 Flow Transmitter Foxboro E13DH 2-FT-68-290 Flow Transmitter Foxboro E13DH 2-FT-68-480 Flow Transmitter Foxboro E130H 2-FT-68-71B Flow Transmitter Foxboro E13DH EMERGENCY RAW COOLING WATER 2-FCV-67-95 Motor Operator Limitarque SMB000 2-FCV-67-103 Motor Operator Limitorque SMB000 2-TSV-37-100 Solenoid Valve ASCO WP HT8300853U 2-TSV-67-101 Solenoid Valve ASCO WP HT8300B58U CHEMICAL AND VOLUME CONTROL 2-FSV-62-74 Solenoid Valve ASCO NP831654V 2-FCV-62-74 Limit Switches NAMCO 18015302 18014302 The equipment inspected was examined for proper installation, overall

. interface integrity and manufacturer's nameplate data was obtained.

The nameplate data was compared to the information listed on the licensee report.

The licensee has conducted a walkdown for corrections to the report.

The discrepancies have been identified by the licensee and a revision to the report will be issued.

Within the areas examined there were no violations identified.

.

- -. - - - - -. - - -

- - -. - - - - - - - - - - - -. - -.