IR 05000266/2024003

From kanterella
Jump to navigation Jump to search
Integrated Inspection Report 05000266/2024003 and 05000301/2024003
ML24309A119
Person / Time
Site: Point Beach  NextEra Energy icon.png
Issue date: 11/05/2024
From: Dariusz Szwarc
NRC/RGN-III/DORS/RPB2
To: Durbin M
Point Beach
References
IR 2024003
Download: ML24309A119 (1)


Text

SUBJECT:

POINT BEACH NUCLEAR PLANT - INTEGRATED INSPECTION REPORT 05000266/2024003 AND 05000301/2024003

Dear Michael Durbin:

On September 30, 2024, the U.S. Nuclear Regulatory Commission (NRC) completed an inspection at Point Beach Nuclear Plant. On October 8, 2024, the NRC inspectors discussed the results of this inspection with you and other members of your staff. The results of this inspection are documented in the enclosed report.

One finding of very low safety significance (Green) is documented in this report. This finding involved a violation of NRC requirements. We are treating this violation as a non-cited violation (NCV) consistent with Section 2.3.2 of the Enforcement Policy.

If you contest the violation or the significance or severity of the violation documented in this inspection report, you should provide a response within 30 days of the date of this inspection report, with the basis for your denial, to the U.S. Nuclear Regulatory Commission, ATTN: Document Control Desk, Washington, DC 20555-0001; with copies to the Regional Administrator, Region III; the Director, Office of Enforcement; and the NRC Resident Inspector at Point Beach Nuclear Plant.

If you disagree with a cross-cutting aspect assignment in this report, you should provide a response within 30 days of the date of this inspection report, with the basis for your disagreement, to the U.S. Nuclear Regulatory Commission, ATTN: Document Control Desk, Washington, DC 20555-0001; with copies to the Regional Administrator, Region III; and the NRC Resident Inspector at Point Beach Nuclear Plant.

November 5, 2024 This letter, its enclosure, and your response (if any) will be made available for public inspection and copying at http://www.nrc.gov/reading-rm/adams.html and at the NRC Public Document Room in accordance with Title 10 of the Code of Federal Regulations 2.390, Public Inspections, Exemptions, Requests for Withholding.

Sincerely, Dariusz Szwarc, Chief Reactor Projects Branch 2 Division of Operating Reactor Safety Docket Nos. 05000266 and 05000301 License Nos. DPR-24 and DPR-27

Enclosure:

As stated

Inspection Report

Docket Numbers:

05000266 and 05000301

License Numbers:

DPR-24 and DPR-27

Report Numbers:

05000266/2024003 and 05000301/2024003

Enterprise Identifier:

I-2024-003-0064

Licensee:

NextEra Energy Point Beach, LLC

Facility:

Point Beach Nuclear Plant

Location:

Two Rivers, WI

Inspection Dates:

July 01, 2024 to September 30, 2024

Inspectors:

J. Masse, Resident Inspector

V. Myers, Senior Health Physicist

M. Stafford, Senior Resident Inspector

Approved By:

Dariusz Szwarc, Chief

Reactor Projects Branch 2

Division of Operating Reactor Safety

SUMMARY

The U.S. Nuclear Regulatory Commission (NRC) continued monitoring the licensees performance by conducting an integrated inspection at Point Beach Nuclear Plant, in accordance with the Reactor Oversight Process. The Reactor Oversight Process is the NRCs program for overseeing the safe operation of commercial nuclear power reactors. Refer to https://www.nrc.gov/reactors/operating/oversight.html for more information.

List of Findings and Violations

Unacceptable Preconditioning of Reactor Protection System Trip Relay Cornerstone Significance Cross-Cutting Aspect Report Section Mitigating Systems Green NCV 05000266,05000301/2024003-01 Open/Closed

[H.11] -

Challenge the Unknown 71111.15 The inspectors identified a Green finding and associated Non-cited Violation (NCV) of Title 10 of the Code of Federal Regulations Part 50, Appendix B, Criterion XI, Test Control, when the licensee failed to evaluate test results to assure that test requirements have been satisfied. Specifically, the licensee did not evaluate the effect of preconditioning following the performance of reactor protection system technical specification surveillance testing.

Additional Tracking Items

None.

PLANT STATUS

Unit 1 began the inspection period at rated thermal power and remained at or near full power throughout the remainder of the inspection period.

Unit 2 began the inspection period at rated thermal power. On September 12, 2024, the unit began coastdown for the upcoming refueling outage. At the end of the inspection period, Unit 2 was operating at 89 percent power.

INSPECTION SCOPES

Inspections were conducted using the appropriate portions of the inspection procedures (IPs) in effect at the beginning of the inspection unless otherwise noted. Currently approved IPs with their attached revision histories are located on the public website at http://www.nrc.gov/reading-rm/doc-collections/insp-manual/inspection-procedure/index.html. Samples were declared complete when the IP requirements most appropriate to the inspection activity were met consistent with Inspection Manual Chapter (IMC) 2515, Light-Water Reactor Inspection Program - Operations Phase. The inspectors performed activities described in IMC 2515, Appendix D, Plant Status, observed risk significant activities, and completed on-site portions of IPs. The inspectors reviewed selected procedures and records, observed activities, and interviewed personnel to assess licensee performance and compliance with Commission rules and regulations, license conditions, site procedures, and standards.

REACTOR SAFETY

71111.04 - Equipment Alignment

Partial Walkdown Sample (IP Section 03.01) (2 Samples)

The inspectors evaluated system configurations during partial walkdowns of the following systems/trains:

(1) Unit 2 component cooling water, trains A and B on July 25, 2024
(2) G-02 emergency diesel generator starting air system on August 13, 2024

71111.05 - Fire Protection

Fire Area Walkdown and Inspection Sample (IP Section 03.01) (3 Samples)

The inspectors evaluated the implementation of the fire protection program by conducting a walkdown and performing a review to verify program compliance, equipment functionality, material condition, and operational readiness of the following fire areas:

(1) Fire Zones 237 and 238 on August 7, 2024
(2) Fire Zones 770, 771, 772, and 773 on August 13, 2024
(3) Fire Zones 101, 104, 105, 108, and 109 on September 26, 2024

71111.11Q - Licensed Operator Requalification Program and Licensed Operator Performance

Licensed Operator Requalification Training/Examinations (IP Section 03.02) (1 Sample)

(1) The inspectors observed and evaluated a licensed operator continuing training evaluation on July 24, 2024.

71111.12 - Maintenance Effectiveness

Maintenance Effectiveness (IP Section 03.01) (4 Samples)

The inspectors evaluated the effectiveness of maintenance to ensure the following structures, systems, and components (SSCs) remain capable of performing their intended function:

(1) Maintenance Rule periodic evaluation review (2)125-volt swing station battery electrolyte levels
(3) Containment cooling fan functional failure evaluation
(4) Removed reactor protection system relay failed bench testing

71111.13 - Maintenance Risk Assessments and Emergent Work Control

Risk Assessment and Management Sample (IP Section 03.01) (4 Samples)

The inspectors evaluated the accuracy and completeness of risk assessments for the following planned and emergent work activities to ensure configuration changes and appropriate work controls were addressed:

(1) Unit 2 elevated risk due to increased lake temperatures and challenges to containment cooling on August 6, 2024
(2) Elevated risk due to work over the forebay and potential foreign material concerns on August 12, 2024
(3) Elevated risk due to new fuel receipt and lifting over the spent fuel pool on August 22, 2024
(4) Unit 2 elevated risk during 4160 V under voltage relay testing, on September 10, 2024

71111.15 - Operability Determinations and Functionality Assessments

Operability Determination or Functionality Assessment (IP Section 03.01) (7 Samples)

The inspectors evaluated the licensees justifications and actions associated with the following operability determinations and functionality assessments:

(1) Operability determination for containment based on rising lake temperatures on August 7, 2024
(2) Past operability of containment accident recirculation fan on August 20, 2024
(3) Operability of G-04 emergency diesel generator following receipt of lube oil fault alarm on August 20, 2024
(4) Operability of G-04 emergency diesel generator following trip on reverse power on September 6, 2024
(5) Operability the G-01 emergency diesel generator after a fuel pump failure on September 10, 2024
(6) Operability of Unit 1 containment after items left unattended on September 24, 2024
(7) Operability of the 2RT-7A and 2RT-8A reactor protection system relays following failure of initial test on September 30, 2024

71111.24 - Testing and Maintenance of Equipment Important to Risk

The inspectors evaluated the following testing and maintenance activities to verify system operability and/or functionality:

Post-Maintenance Testing (PMT) (IP Section 03.01) (8 Samples)

(1) IT-06 Train A after packing adjustment on 2SI-871A, containment spray pump suction from residual heat removal heat exchanger, on August 20, 2024
(2) IT 07B and IT 07C after valve internals replacement on SW-32B, service water pump discharge check valve, on August 21, 2024
(3) Cable spreading room recirculation fans following maintenance on September 5, 2024
(4) OI-163 for Unit 1, A safety injection pump after replacement of flow transmitter on September 9, 2024
(5) G-04 emergency diesel generator following testing, on September 13, 2024
(6) G-02 emergency diesel generator following replacement of air receivers, on September 25, 2024
(7) G-01 emergency diesel generator following a maintenance window on September 26, 2024 (8)1DY-01 red channel inverter following circuit board replacement on September 30, 2024

Surveillance Testing (IP Section 03.01) (2 Samples)

(1) TS-86, manual start of G-02 and G-03 emergency diesel generators for technical specification surveillance requirements on September 3, 2024
(2) TS-83, G-03 emergency diesel generator monthly technical specification surveillance on September 4,

RADIATION SAFETY

71124.08 - Radioactive Solid Waste Processing & Radioactive Material Handling,

Storage, & Transportation

Radioactive Material Storage (IP Section 03.01)

The inspectors evaluated the licensees performance in controlling, labeling and securing the following radioactive materials:

(1) Sealed source storage, labeling, and leak testing results
(2) Storage of radioactive material in warehouse
(3) Storage of radioactive material in the Flex building

Radioactive Waste System Walkdown (IP Section 03.02) (3 Samples)

The inspectors walked down the following accessible portions of the solid radioactive waste systems and evaluated system configuration and functionality:

(1) Demineralizer cubicles
(2) Advanced Liquid Processing System
(3) Resin liners in the truck bay

Waste Characterization and Classification (IP Section 03.03) (2 Samples)

The inspectors evaluated the following characterization and classification of radioactive waste: (1)2022 Dry Active Waste Stream (2)2023 Class B Resin

Shipping Records (IP Section 03.05) (3 Samples)

The inspectors evaluated the following non-excepted radioactive material shipments through a record review:

(1) Shipment 24-015; Type A shipment for reactor coolant pump impeller
(2) Shipment 23-047; SCO-II shipment for outage equipment
(3) Shipment 23-042; LSA-II shipment for dry active waste

OTHER ACTIVITIES - BASELINE

===71151 - Performance Indicator Verification The inspectors verified licensee performance indicators submittals listed below:

MS06: Emergency AC Power Systems (IP Section 02.05)===

(1) Unit 1 (July 1, 2023 through June 30, 2024)
(2) Unit 2 (July 1, 2023 through June 30, 2024)

MS07: High Pressure Injection Systems (IP Section 02.06) (2 Samples)

(1) Unit 1 (July 1, 2023 through June 30, 2024)
(2) Unit 2 (July 1, 2023 through June 30, 2024)

MS08: Heat Removal Systems (IP Section 02.07) (2 Samples)

(1) Unit 1 (October 1, 2023 through June 30, 2024)
(2) Unit 2 (October 1, 2023 through June 30, 2024)

71152A - Annual Follow-up Problem Identification and Resolution Annual Follow-up of Selected Issues (Section 03.03)

The inspectors reviewed the licensees implementation of its corrective action program related to the following issues:

(1) Part 21 assessment pertaining to transmitters used for pressurizer pressure channels

INSPECTION RESULTS

Unacceptable Preconditioning of Reactor Protection System Trip Relay Cornerstone Significance Cross-Cutting Aspect Report Section Mitigating Systems Green NCV 05000266,05000301/2024003-01 Open/Closed

[H.11] -

Challenge the Unknown 71111.15 The inspectors identified a Green finding and associated Non-cited Violation (NCV) of Title 10 of the Code of Federal Regulations Part 50, Appendix B, Criterion XI, Test Control, when the licensee failed to evaluate test results to assure that test requirements have been satisfied. Specifically, the licensee did not evaluate the effect of preconditioning following the performance of reactor protection system technical specification surveillance testing.

Description:

On March 21, 2024, Point Beach instrumentation and controls personnel performed technical specification surveillance testing in accordance with test procedure 2ICP 02.003A, Reactor Protection System Logic Train A Surveillance Test. The test uses a selector switch to select different logic configurations and then technicians depress pushbuttons to insert simulated logic conditions into the control scheme. A test light is observed throughout the procedure to validate that the logic signals correctly actuate the reactor trip relays. The test light is illuminated normally throughout the procedure, but it is extinguished when the technicians depress the sufficient combination of pushbuttons to simulate a reactor trip. Prior to starting the test, the station declared the A train of the reactor protection system (RPS) inoperable.

A note prior to step 5.16 in the procedure reads as follows:

Testing of Reactor Protection system logic channels in steps 5.16 through 5.21 are performed by selecting the logic channel to be tested on the selector switch, depressing the trip combination being tested, checking the test light is OFF, releasing the trip combination, and then checking the test light is ON. This will be performed for all the trip combinations. Each individual trip logic test pushbutton will then be depressed, and test light checked that it remained ON.

The technicians performed the procedure without any issues until they reached step 5.20.2.

At this step, the procedure tests the reactor trip on a loss of reactor coolant pump breaker power with reactor power above the P-8 permissive setpoint (35 percent reactor power). This step is associated with selector switch position 23, and it verifies that the reactor would trip if one of the two reactor coolant pump breakers were to open while the reactor is above 35 percent power. Either of the pushbuttons called out in the procedure, S2 or S3, should simulate a reactor trip and extinguish the test light. However, when the S2 button was depressed the test light did not extinguish. With first line supervisor permission, the selector switch was rotated fully clockwise and counterclockwise and then returned to position 23.

Then the S2 pushbutton was depressed again, and the test light still did not extinguish. The S3 pushbutton was depressed, and the test light again did not extinguish. The technicians and first line supervisor notified the control room, and the shift manager came to observe the test. The technicians depressed the S2 pushbutton, and the test light did not extinguish. The technicians released S2 and depressed S3 and the test light did not extinguish. At this point, there had been five instances where the test light did not indicate as expected.

The personnel then reviewed prints of the control logic to troubleshoot the issue. The licensee wrote condition report AR 2481984 to document the issue. To extinguish the test light there are 2 reactor trip relays, 2RT-7A and 2RT-8A, which both must deenergize, which causes their associated contacts in the reactor trip control to open. These relays are downstream of the logic relays, and the logic relays open their contacts when the pushbuttons are depressed. Therefore, if the logic relay contacts were not opening, then the reactor trip relays would not deenergize. If the logic relay contacts were opening, then there could be an issue with the reactor trip relays.

A technician was stationed to observe the logic relay contacts and the technicians performing the test were instructed to hold the pushbutton in its depressed position to give the technician time to observe the logic relay. The test was reperformed with the selector switch in position 23, and the S2 pushbutton was depressed and held in place. The test light did not immediately extinguish, but the logic relay contact was observed to have opened.

After about 2 seconds of holding the pushbutton, the technicians heard an additional relay actuate and the test light extinguished. When the S2 pushbutton was released the test light reilluminated. Then the technicians depressed the S3 pushbutton, and the test light immediately extinguished. Under shift manager direction the technicians performed the next steps of the procedure which test the same trip relays with the selector switch in position 16 and 17. Both tests were satisfactory, and then they reperformed the test on position 23, which was again satisfactory with the test light extinguishing immediately after each depression of the S2 and S3 pushbuttons. The remainder of the procedure was completed satisfactorily, and the reactor protection system was returned to service and declared operable. The licensee decided to replace the reactor trip relays 2RT-7A and 2RT-8A after the next performance of the surveillance test.

On June 20, 2024, the licensee again performed 2ICP 02.003A to satisfy the surveillance requirement. The test was performed satisfactorily, and the reactor trip relays 2RT-7A and 2RT-8A were replaced with new relays, which were bench tested on April 4, 2024. The affected surveillance test steps were reperformed satisfactorily with the new relays installed.

On July 8, 2024, the old 2RT-7A and 2RT-8A reactor trip relays that were removed in the June test were bench tested. It was found that 2RT-7A had a dropout voltage of 9 VDC which is below its acceptance criteria of 12-35 VDC. Reactor trip relay 2RT-8A passed bench testing satisfactorily. This is documented in AR 2490186. The old 2RT-7A and 2RT-8A relays are currently energized in a test setup so that the licensee can perform additional evaluations.

NRC Technical Guidance Part 9900, Maintenance - Preconditioning of Structures, Systems, and Components Before Determining Operability, provides guidance on evaluating the acceptability of preconditioning prior to surveillance testing. Licensee procedure MA-AA-203-1000, Maintenance Testing, uses much of the language of the NRC Technical Guidance to define unacceptable preconditioning as the alteration, variation, manipulation, or adjustment of the physical condition of a System, Structure, or Component (SSC) before or during technical specification surveillance or ASME IST Code Testing that will alter one or more of an SSCs operational parameters which results in acceptable test results, potentially masking the actual as-found condition of the SSC, making it difficult to determine whether the SSC would perform its intended function. MA-AA-203-1000 also states that steps and tasks must be executed such that unacceptable preconditioning is avoided prior to obtaining the as-found data.

Additionally, licensee procedure EN-AA-203-1001, Operability Determinations / Functionality Assessments, Attachment 4, step 15, states repetitive testing to achieve acceptable test results without identifying the root cause or correction of a problem in a previous test is not acceptable as a means to establish or verify operability and may constitute preconditioning.

After the initial test failures in March, the licensee did not assess for potential preconditioning on the reactor trip relay. There were five instances where the pushbuttons were pressed while the selector switch was in position 23 that should have extinguished the test light but did not. The licensee stated that in an event where a reactor coolant pump breaker lost power the matrix relay condition would be present for longer than the 2 seconds that were needed to deenergize the trip relays. However, the licensee did not account for the cycling of the logic relays prior to the test where the pushbutton was held down. If a reactor coolant pump breaker lost power, the matrix relay contacts would not cycle multiple times; they would only open once. Since the conditions of the test could not be reproduced, it is difficult to ascertain whether the reactor trip relays needed multiple cycles of their upstream logic relay contacts to ultimately open the contacts on both reactor trip relays. Therefore, the inspectors determined that the repetitive testing of the reactor trip relay constituted unacceptable preconditioning.

Corrective Actions: On June 20, 2024, the licensee replaced the reactor trip relays that failed initial testing on March 21, 2024, with new relays. The new relays passed their bench testing prior to installation and passed their subsequent surveillance satisfactorily. The licensee is assessing the impacts of this preconditioning.

Corrective Action References: AR 2481984

Performance Assessment:

Performance Deficiency: The licensees performance of repetitive testing to achieve acceptable test results without identifying a root cause or correction of a problem in a previous test is not acceptable as a mean to establish or verify operability and was a performance deficiency.

Screening: The inspectors determined the performance deficiency was more than minor because it was associated with the Equipment Performance attribute of the Mitigating Systems cornerstone and adversely affected the cornerstone objective to ensure the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. Specifically, the licensee depressed the test pushbuttons multiple times prior to obtaining an acceptable result, which masked the as-found condition of the reactor trip relay, and no evaluation was performed to verify the acceptability of preconditioning.

Significance: The inspectors assessed the significance of the finding using IMC 0609 Appendix A, The Significance Determination Process (SDP) for Findings At-Power. The finding was determined to be of very low safety significance (Green) because the inspectors answered no to the reactor protection question in Exhibit 2 - Mitigating Systems Screening Questions.

Cross-Cutting Aspect: H.11 - Challenge the Unknown: Individuals stop when faced with uncertain conditions. Risks are evaluated and managed before proceeding. Specifically, the licensee assumed that the relay would perform its safety function because a trip condition would hold the matrix relay contacts open and would mimic the effect of the test when the technicians held the pushbutton. However, no evaluation was performed to address the effect of cycling the matrix relays numerous times, a condition that would not occur if a trip condition were present.

Enforcement:

Violation: Title 10 of the Code of Federal Regulations Part 50, Appendix B, Criterion XI, Test Control, requires, in part, test results shall be documented and evaluated to assure that test requirements have been satisfied. Contrary to above, on March 21, 2024, the licensee failed to evaluate test results to assure that test requirements have been satisfied. Specifically, the licensee did not evaluate the effect of preconditioning during technical specification surveillance testing to assure that the reactor protection system would have fulfilled its safety function.

Enforcement Action: This violation is being treated as a non-cited violation, consistent with Section 2.3.2 of the Enforcement Policy.

EXIT MEETINGS AND DEBRIEFS

The inspectors verified no proprietary information was retained or documented in this report.

  • On October 8, 2024, the inspectors presented the integrated inspection results to Michael Durbin, Site Vice President, and other members of the licensee staff.
  • On August 15, 2024, the inspectors presented the radiation protection inspection results to Michael Durbin, Site Vice President, and other members of the licensee staff.

DOCUMENTS REVIEWED

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

110E029 Sheet 1

P&ID Auxiliary Coolant System

Drawings

110E029 Sheet 3

P&ID Auxiliary Coolant System

2CL-CC-001

Component Cooling Unit 2

CL 11A G-02

G-02 Diesel Generator Checklist

NP 2.1.3

Administrative Control of Red Locks, Lead Seal Wires, and

Padlocks on Plant Equipment

71111.04

Procedures

STPT 19.2

Emergency Diesel: Generator G-02 General Instrumentation

Corrective Action

Documents

2493075

Smoke Detector Connection Broke

08/16/2024

PFP-0-PAB 46

Pre-Fire Plan Unit 1 & 2 Auxiliary Building 46 ft

PFP-0-PAB-8

Pre-Fire Plan Primary Auxiliary Building Elevations 8' and

Below

71111.05

Fire Plans

PFP-0-PAN

Pre-Fire Plan Protected Area North (Inside the Fence)

71111.11Q

Miscellaneous

PBN LOC 24D

2E

SM Read/STA Eval

2433110

22 - Point Beach Maintenance Rule (A)(3) Assessment

07/29/2022

2449580

Fleet MREP Action Tracking

2/27/2023

2461514

D-305 Post Recovery Specific Gravity Outside Admin Limits

07/03/2023

2485820

GT Maintenance Rule (A)(1) Action Plan Item Not Completed

05/24/2023

2486793

2W-001A2-A Second Blade Disconnected from Damper Shaft

05/21/2024

2489806

D-305 Battery Specific Gravity Readings

07/01/2024

2489879

D-305 Battery Specific Gravity Reading High

07/02/2024

2490186

Removed 2RT-7A Reactor Protection Relay OOT on Bench

Test

07/08/2024

Corrective Action

Documents

2490382

24 PB Maintenance Rule (A)(3) Assessment

07/10/2024

2ICP 02.003A

Reactor Protection System Logic Train A Surveillance Test

ER-AA-100-2002

Maintenance Rule Program Administration

ICP 09.013

Bench Testing of Miscellaneous Relays

Procedures

RMP 9046-1

Station Battery 92 Day 12 Month Surveillance Tests

40726204-03

2RP - RT/RC Replacement Relay Bench Testing

09/17/2021

71111.12

Work Orders

40971502-01

2C-153 - Replace 2RT-7A / 2RT-8A

06/20/2024

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

40971502-02

2C-153 - Bench Check Relays for 2RT-7A and 2RT-8A

04/04/2024

2486793

2W-001A2-A Second Blade Disconnected from Damper Shaft

05/21/2024

2489084

2W-1B2 Containment Cooling Fan Tripped

06/21/2024

2489197

U2 Ctmt Cooling Fans ACMP: Check for Operator Challenge

06/22/2024

Corrective Action

Documents

2492032

U2 Containment Temperatures is Greater than 110F

08/03/2024

Corrective Action

Documents

Resulting from

Inspection

2496102

High Risk PDC Not Covered during PJB

09/24/2024

Miscellaneous

Adverse

Condition

Monitoring and

Contingency Plan

ACMP for CRs 2489084 and 2486793

06/21/2024

2ICP 02.013

4.16kV Undervoltage Matrix Relays Surveillance Test

Procedures

MA-AA-101-1000

Foreign Material Exclusion Procedure

40796092-04

Unit 2 Build Scaffolding

08/05/2024

71111.13

Work Orders

40957153-01

2ICP 2.13 - 4160 Volt UV Testing

09/10/2024

Calculations

NEE-021-CALC-

001

Point Beach Unit 1 Debris Generation Calculation

2395149

Received Lube Oil System Fault Alarm

06/06/2021

2430657

U2 RX Trip BKR Did Not Trip during 2ICP 02.003A

06/24/2022

2481984

Unit 2ICP 02.003A RCP Loss of Power Trip Test Failed

03/21/2024

2483050

New NBFD31S Reactor Trip Relay Failed Initial Inspection

04/02/2024

2486793

2W-001A2-A Second Blade Disconnected from Damper Shaft

05/21/2024

2492032

U2 Containment Temperature is Greater than 110F

08/03/2024

2493277

Item Left in U1 Containment

08/19/2024

2493405

Item Left in U1 Containment

08/21/2024

2494041

G-01 Engine Driven Fuel Oil Pump Low Discharge Pressure

08/30/2024

2494264

G-04 Tripped on Revers Pwr While Being Unloaded at

[approximately] 1300 kW

09/02/2024

2494340

G-01 Engine Oil Pressure Lower than Before CMM

09/03/2024

71111.15

Corrective Action

Documents

2494342

G-01 EDG Injector #16 Has an Exhaust Product Leak

09/03/2024

Corrective Action

Documents

Resulting from

Inspection

2495176

CE Assignment Not Performed

09/11/2024

499B466, Sheet

269

Schematic Diagram 4160V Swgr Bus 1A06 (2A06) Output

Breaker 1A52-80 (2A52-93) from Diesel Generator G-03

(G-04)

6090F03001

Sheet 1

Lube Oil System P&ID

617F354-2 Sheet

4A1

Schematic Diagram - Logic Reactor Protection System Train

A

617F354-2 Sheet

5A

Schematic Diagram Reactor Protection System Reactor Trip

Breaker Switchgear Train A

AWVI 81921 001-

000

Backdraft Damper

Drawings

M-2215, Sheet 1

Heating & Ventilation

Miscellaneous

-

G-01 Main Lube Oil Pressure Deviation

09/05/2024

ARB C01 C3-9

Unit 2 Containment Recirc Coolers Air Flow Low

ARB C102 2-3

Lube Oil System Fault

EN-AA-203-1001

Operability Determinations

EN-AA-203-1001

Operability Determinations / Functionality Assessments

MA-AA-203-1000

Maintenance Testing

NP 7.7.37

Surveillance Frequency Control Program Manual

ORT 7

Operation of Backdraft Dampers Unit 2

PI-AA-104-1000

Condition Reporting

SEM 7.14

Air Flow Rate Measurement for Containment Accident Fans

W-1A1, W-1B1, W-1C1, W-1D1

STPT 17.1

Heating and Ventilation System

Procedures

TS 34

Containment Accident Recirculation Fan-Cooler Units Unit 2

351180

G-04 / Spurious G-04 Lube Oil Fault Alarm

2/12/2008

376173

G-04 / Monitor G-04 for Cause of Lube Oil Fault Alarm

07/20/2010

40321153-01

LS-03354B / Replace G-04 Lo Low Level Switch

08/18/2017

40844092-01

ICP-13.7B2 - G-04 - Perform Data Sheets 3-10, 14-57, Cals

08/10/2023

40883153-01

2ICP 2.3A - Reactor Protection Logic Test - Train A

03/21/2024

71111.15

Work Orders

40933123-01

TS-84, G-04 Emergency Diesel Generator Operability Test

06/03/2024

40955301-01

G-01, 18Y Fuel Pump PMs

09/06/2024

40955301-03

G-01 (P-240A) / Repair Fuel Pump

09/05/2024

40990171

G-04 Tripped on Reverse Load While Being Unloaded

09/05/2024

Calculations

2003-0014

MOV Operating Parameters

2489379

2SI-871A Packing Torque Increased Without Proper PMT

06/25/2024

2492827

Parts Issue Extending P-32B SW Pump TSAC Time

08/14/2024

2493155

Multiple Air Leaks on G-01 Air Receivers

08/17/2024

Corrective Action

Documents

2495670

Broke Lead on C13 Inside 1DY-01 Inverter

09/18/2024

Corrective Action

Documents

Resulting from

Inspection

2492837

NRC Identified Work Order Closeout Gap

08/14/2024

Drawings

M-209, Sheet 12

Emergency Diesel Air Starting System

1RMP 9036-2

1DY-01 Red Channel Instrument Bus Static Inverter

Maintenance Procedure

CL 11A G-02

G-02 Diesel Generator Checklist

IT 07B

P-32B Service Water Pump (Quarterly)

IT 07C

P-32C Service Water Pump (Quarterly)

MA-AA-203-1000

Maintenance Testing

NDE-753

Visual Examination (VT-2) Leakage Detection of Nuclear

Power Plant Components

OI 163

SI, RHR, and CS Pump Runs and Venting SI Pump Casings

RMP 9043-13

Emergency Diesel Generator G-01 Mechanical Inspection

RMP 9043-17A

Emergency Diesel Generator G-01 Post-Maintenance Run and

Testing

TS 81

Emergency Diesel Generator G-01 Monthly

101

TS 83

Emergency Diesel Generator G-03 Monthly

Procedures

TS 86

Emergency Diesel Generator Manual Start

40844045-01

1FT-925 - Replace Transmitter

08/23/2024

40844045-03

1FT-925 - Ops PMT

08/23/2024

40845667-01

SW-00032B Disassemble/Visually Inspect Check Valve

08/14/2024

40845667-02

SW-00032B OPs PMT/RTS (IT-7s as Required)

08/14/2024

40872650-01

2SI-00871A / Packing Adjustments Needed for 2-PT-SI-1

05/03/2024

71111.24

Work Orders

40881834

T-61A/B/C/D/E/F G-02 EDG Air Receivers One Time

Replacement

09/11/2024

40947200-01

IT 06 Train A

06/17/2024

40952211-01

1DY-01, EM to Maintain and Inspect Inverter

09/21/2024

40952211-03

1DY-01, Operations PMT / RTS

09/21/2024

40952212-01

G-01, 2Y PMs

08/30/2024

40952212-02

G-01, Ops PMT/RTS

09/05/2024

40952212-03

G-01, Post Maint Testing Per RMP 9043-17A (W/ Ops

Support)

09/05/2024

40955872-02

W-013A2 Operations PMT/RTS

08/26/2024

40955874-02

W-013A1 Operations PMT/RTS

08/26/2024

40955924-01

TS 83, G-03 EDG Operability Test

09/03/2024

40990171-01

G-04 32/G-04 Relay Calibration

09/03/2024

40990171-02

G-04 Troubleshooting Tripped on Reverse Load

09/06/2024

40990171-05

G-04, Install Yokogawa Recorder/Perform Test Run

09/06/2024

40990171-06

G-04 Ops PMT/RTS (TS 84)

09/06/2024

2472891

Error in Shipping Characterization

11/20/2023

2474310

Deficiencies Identified with Rad Material Controls

2/12/2023

248135

RCP Impeller Shipment Has Incorrect Data

04/15/2024

2487316

Increased Dose in Resin Beds

05/29/2024

Corrective Action

Documents

2490954

Change in U2 Radionuclide Distribution Affects Shipping

07/18/2024

HP-100-060222

22 DAW 10CFR61 Analysis

07/07/2022

Miscellaneous

HP-100-071923

23 Class B Resin 10 CFR 61 Analysis

07/20/2023

RDW 18.1.1

CFR 61 Sampling Program

RP-AA-107

Radioactive Material Control Program

RP-AA-108-1002

Shipment of Radioactive Material

RP-AA-108-1002

Shipment of Radioactive Material

Procedures

RP-AA-108-1003

Radioactive Materials Surveys for Shipment

2401895

Part 37 Assessment Report

07/08/2023

Self-Assessments

2491403

Radioactive Solid Waste Processing and Radioactive

Handling, Storage and Transportation Assessment Report

07/23/2024

4091616

Sealed Source Inventory

08/01/2024

71124.08

Work Orders

40952827

Sealed Source Leak Tests

08/01/2024

71151

Miscellaneous

PBN-BFJR-18-

054

MSPI Basis Document for PBNP

2338607

Ultra Electronics Qualified Life Change Notice

2/17/2019

2340309

Follow-up AR to 02338607-Qualified Life Change Notice

01/07/2020

Corrective Action

Documents

2489869

Part 21 Notification

07/02/2024

LI-AA-102-1002

Part 21 Reporting

71152A

Procedures

PI-AA-104-1000

Condition Reporting

44