LER 82-070/03L-0:on 820604,containment Spray Pump 1-CS-P-1A Failed to Start During Performance Testing 17.1.Caused by Pump Motor Breaker.Breaker Replaced & Pump Tested Satisfactorily
ML20054L645
Person / Time
Site: Surry Dominion icon.png
Issue date: 06/28/1982
From: Joshua Wilson
VIRGINIA POWER (VIRGINIA ELECTRIC & POWER CO.)
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
Shared Package
ML20054L628 List:
References
LER-82-070-03L, LER-82-70-3L, NUDOCS 8207080323
Download: ML20054L645 (2)


LER-2082-070,
Event date:
Report date:
2802082070R00 - NRC Website

text

. _ _ ~ . - ._.- .. - - . . - - . . . - - - . - . . -. _ .

' NRC F OAM 365 U. S. NUCLE AR REGULATORY COMMIS$10N

'7 77) -

. LICENSEE EVENT REPORT CONTROL BLOCK: l i

l l l l )

.h l (PLEASE PRINT OR TYPE ALL REQUIRED INFORMATIONI

!Io l t l l V l A l S l P l S l 1 l 0 l 0 l - l 0 lLICENSE 0 l 0 %l Meta 0 l 0 l - l O ! 250 l@ 26 4 lLICENSE 1l 1l TYPE 11 1]@lJC 67 LAT $4 l

l@

]- 8 9 LICENSEE CODE la S CON'T

!oI1I

$ *,,"e g lL hl015l010l q 2 l 8 l0 @l 0EVENT 68 69 l 6DATE l0 l4 l 8l2 @l0l6l2I8I8l2l@

74 75 aEPORT DATs 80 8 W 61 coCKET Nyug gm EVENT CESCRIPTION ANO PROBABLE CONSEQUENCES h

!!o !21 I With the unit at 100%, containment spray pump, 1-CS-P-1A, failed to start during the l

io ;3; l performance of PT-17.1. The pump was declared inoperabic. This event is contrary tol

,go,,ilT.S. 3.4.A.1 and is reportable per T.S. 6.6.2.b.(2). The redundant containment spray l g o ,,, ;was verified operabic, therefore there was no threat to public health and safety. l I

' F5TG 1 ,

I 10171 l l

i 10181 l 80 7 8 9 DE Coot sueC E COMPONENT CooE 34,3 co't sy E

[ octs 1 I S I B l@ W@ l A l@ l ClK l T l B l R l K lh l A l@ (_Z,,j 19 20 8 9 10 11 12 13 18 7

StoVENTIAL OCCURRENCE REPORT REvlsioN g EVENTvtAR MEPoMT No. CooE TYPE No.

@ ,a'ga yg;;no I 812l l_i 10 17 l 0 i Lc.J 10 13 I I LI l-l ll]

,,,,, 21 22 23 24 26 27 28 29 J0 31 32 M Nouns sei som t. suppgi MANUp C mEm K N A oN C P NT lA_j@(_f,j@

3J 34 lZ l@

2S lZ lh 2,6 3l30 l0 l0 l040l W@ lNl@

41 42 l43A l@ ' l44I l 0 l 0 l 5l@ 47 5

CAUSE OESCRIPTION AND CORRECTIVE ACTICNS g,ioglThe event was caused by the pump motor breaker. The protective relay setpoints were l I

i,,,g i found to be set at less than specified values and were tripping the breaker during 1

,,,,,; starting currents. The breaker was replaced with a tested spare and the pump was  ;

, , y tested to prove operability.

j I

l i 6 41 1 .

'sYA'E 'r spowEm orsEn status @ "EoNav' i oiscovsny oEscairTioN @

N/A l l Bl@l Routine Test l l l l' 1 15 '

AEnviry l lE ]@ l 1l 0l0"l@l Co'OTENT f

i (ELEAsto or aELEASE LOCATION OF RELIAst @

'l1 l6l]Zl@ W @l AMOUNT N/A OF" ACT1vlTV l N/A @ l l

etasoNNsL ExposuaEs wMsta Tvet otscaimeN @ l

' ] i l 7 ) l0 l 0 10 l@l Z l@l N/A

  • EasoNN E'L imav'dits wesEn lIt 13j l0l0l0l@lotscaimoN @ N/A '

l s 9 ii 12 8207080323 820628 1

'r$5,C' C"ots'Ca er oN

"' '7 .A itiry@ DR ADOCK 05000280

, I 219I lZ l@l N/a PDR l 30 7 4 9 to issut of CatPTioN i7LusJ8 trJ 81 m I 68 69 i ' ' I'I:

80 3 9 ;0 J. L. Wilson ,

(804) 357-3184  ;

yAve ,..g.2pp.

ATTACilMENT 1 (PACE 1 0F 1)

SURRY POWER S'IATION, UNIT No. 1 LOCKET NO: 50-280 REPORT NO: 82-070/03L-0 EVENT DATE: 06-04-82 TITLE OF Tile EVENT: Containment Spray Pump Failed to Start

1. DESCRIPTION OF EVENT:

On June 4,1982 with the unit at 100% the reactor operator was performing PT-17.1 (Containment Spray System) when containment spray pump,1-CS-P-1A, failed to start. Control Room indication showed the motor tripped on a current overload. Subsequent attempts to start the pump produced the same results.

The pump was declared inoperabic. This event is contrary to Technical Specification 3.4. A.1 and is reportable per Technical Specification 6.6.2.b.(2) .

2. PROBABLE CONSEQUENCES OF OCCURRENCE:

The redundant containment spray pump was verified to be operabic, therefore the health and safety of the public were not affected.

3. CAUSE OF Tile EVENT:

The event was caused by the pump motor breaker. The setpoints of the instan-taneous and long time overload relays were found to be set at values less than specified. On attempted pump starts, the overload relays were tripping the breaker and stopping the motor.

4. IMMEDIATE CORRECTIVE ACTIONS:

The normal valve line-up was re-established for the inoperabic containment spray pump and the redundant pump, 1-CS-P-1B, was verified operabic.

5. SUBSEQUENT CORRECTIVE ACTION 3:

The inoperable pump was manually rotated to determine if it was physically seized and the motor was bridged and meggered to determine if electrical f aults existed. Finding no prob 1 cms, the breaker was suspected to be malfunctioning.

The breaker was replaced with a tested spare and the pump was verified operable.

The suspect breaker was tested and found to be functional but the overload relays were set below the specified values. The imprcper settings caused the breaker to trip at less than motor starting current.

6. ACTIONS TAKEN TO PREVENT RECURRENCE:

None are scheduled.

7. GENERIC IMPLICATIONS:

None.