2003 Annual Radioactive Effluent Release Report
ML041320539
Person / Time
Site: Sequoyah  Tennessee Valley Authority icon.png
Issue date: 04/26/2004
From: Salas P
Tennessee Valley Authority
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
Download: ML041320539 (241)


Text

Tennessee Valley Authority, Post Office Box 2000, Soddy-Daisy, Tennessee 37384-2000 April 26, 2004 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, D.C. 20555 Gentlemen:

In the Matter of ) Docket Nos. 50-327 Tennessee Valley Authority ) 50-328 SEQUOYAH NUCLEAR PLANT - 2003 ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT (ARERR)

Enclosed is the ARERR for the period of January 1 to December 31, 2003. This report (Enclosure 1) is being submitted in accordance with Sequoyah Technical Specification (TS) 6.9.1.8.

The Offsite Dose Calculation Manual requires that a Radiological Impact Assessment be submitted for the same reporting period. The assessment is included as (Enclosure 2). In addition, in accordance with TS 6.1.14.3, a complete copy of the Offsite Dose Calculation Manual (Enclosure 3) is submitted with marked revisions implemented during calendar year 2003.

Please direct questions concerning this issue to me at (423) 843-7170 or J. D. Smith at (423) 843-6672.

Licensing and Industry Affairs Manager Enclosures Priotedon recycled .Per

U.S. Nuclear Regulatory Commission Page 2 April 26, 2004 PS:JDS:JWP:KTS Enclosures cc (Enclosures):

D. K. Baker, BR 3H-C M. J. Burzynski, BR 4X-C M. F. DeRoche, OPS 4A-SQN D. A. Kulisek, POB 2B-SQN D. C. Olcsvary, LP 6A-C R. T. Purcell, OPS 4A-SQN R. E. Richie, SB 2B-SQN NSRB Support, LP 5M-C J. A. Scalice, LP 6A-C EDMS, WTC A-K I:license\worddoc\2003 ARERR

ENCLOSURE I ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT SEQUOYAH NUCLEAR PLANT 2003

EFFLUENT AND WASTE DISPOSAL ANNUAL REPORT 2003 SUPPLEMENTAL INFORMATION REGULATORY LIMITS A. Gaseous Effluents

1. Dose rates due to radioactivity released in gaseous effluents from the site to areas at and beyond the unrestricted area boundary shall be limited to the following:
a. Noble gases: - Less than or equal to 500 mrem/year to the total body.

- Less than or equal to 3000 mrem/year to the skin.

b. Iodine-131, iodine-133, tritium, and all radionuclides in particulate form with half-lives greater than eight days:

- Less than or equal to 1500 mrem/year to any organ.

2. Air dose due to noble gases released in gaseous effluents to areas at and beyond the unrestricted area boundary shall be limited to the following:
a. Less than or equal to 5 mrad for gamma radiation and less than or equal to 10 mrad for beta radiation during any calendar quarter.
b. Less than or equal to 10 mrad for gamma radiation and less than or equal to 20 mrad for beta radiation during any calendar year.
3. Dose to a member of the public from lodine-1 31, lodine-1 33, tritium, and radionuclides in particulate form with half-lives greater than eight days in gaseous effluents released to areas at and beyond the unrestricted area boundary shall be limited to the following:
a. Less than or equal to 7.5 mrem to any organ during any calendar quarter.
b. Less than or equal to 15 mrem to any organ during any calendar year.

B. Liquid Effluents

1. The annual average concentration of radioactivity released in liquid effluentsto unrestricted areas shall be limited to the concentrations specified in Title 10 of the Code of Federal Regulations, Part 20 E1 -2

EFFLUENT AND WASTE DISPOSAL ANNUAL REPORT 2003 SUPPLEMENTAL INFORMATION (Standards for Protection Against Radiation), Appendix B, Table 2, Column 2, for radionuclides other than dissolved or entrained noble gases. For dissolved or entrained noble gases, the concentration shall be limited to 2.0 E-04 microcuries/milliliter (pCi/ml) total activity.

2. The dose or dose commitment to a member of the public from radioactivity in liquid effluents released to unrestricted areas shall be limited to:
a. Less than or equal to 1.5 mrem to the total body and less than or equal to 5 mrem to any organ during any calendar quarter.
b. Less than or equal to 3 mrem to the total body and less than or equal to 10 mrem to any organ during any calendar year.

II. EFFLUENT CONCENTRATION LIMITS A. Liquids

  • 1. The Effluent Concentration Limits (ECL) for liquids are those listed in 10 CFR 20, Appendix B, Table 2, Column 2. For dissolved and entrained gases, the ECL of 2.0E-04 tCi/ml is applied. This ECL is based on the Xe-135 concentration in air (submersion dose) converted to an equivalent concentration in water as discussed in the International Commission on Radiological Protection (ICRP), Publication 2.
  • These values are used as applicable limits for liquid and gaseous effluents.

B. Gaseous

a. Noble gas dose rate at the unrestricted area boundary:

- Less than or equal to 500 mrem/year to the total body.

- Less than or equal to 3000 mrem/year to skin.

b. lodine-131, lodine-133, tritium, and particulates with half-lives greater than eight days dose rate at the unrestricted area boundary:

- Less than or equal to 1500 mrem/year to any organ.

  • These values are used as applicable limits for liquid and gaseous effluents.

E1-3

EFFLUENT AND WASTE DISPOSAL ANNUAL REPORT 2003 SUPPLEMENTAL INFORMATION Ill. AVERAGE ENERGY Sequoyah's ODCM limits the dose equivalent rates due to the release of noble gases to less than or equal to 500 mrem/year to the total body and less than or equal to 3000 mrem/year to the skin. Therefore, the average beta and gamma energies (E) for gaseous effluents as described in Regulatory Guide 1.21, "Measuring, Evaluation, and Reporting Radioactivity in Solid Wastes and Releases of Radioactive Materials in Liquid and Gaseous Effluents from Light-Water-Cooled Nuclear Power Plants," are not applicable.

IV. MEASUREMENTS AND APPROXIMATIONS OF TOTAL RADIOACTIVITY NOTE: Every effort is made to ensure that effluent releases from Sequoyah are conducted such that all ODCM Lower Limit of Detection (LLD) values are met. Whenever an analysis does not identify a radioisotope, an "0.OOE-01 Ci" is recorded for the release. This does not necessarily mean that no activity was released for that particular radionuclide, but that the concentration was below the ODCM and analysis LLD. Refer to Tables A and B for estimates of these typical LLD values.

A. Fission and Activation Gases Airborne effluent gaseous activity is continuously monitored and recorded.

Additional grab samples from the shield building, auxiliary building, service building, and condenser vacuum exhausts are taken and analyzed at least monthly to determine the quantity of noble gas activity released for the month based on the average vent flow rates recorded for the sample period. Also, noble gas samples are collected and evaluated for the shield and auxiliary buildings following startup, shutdown, or rated thermal power change exceeding 15 percent within one hour (sampling is only required if the dose equivalent 1-131 concentration in the primary coolant or the noble gas activity monitor shows that the containment activity has increased more than a factor of 3).

The quantity of noble gases released through the shield and auxiliary building exhausts due to purging or venting of containment and releases of waste gas decay tanks are also determined.

The total noble gas activity released for the month is then determined by summing of the activity released from each vent for the sampling periods.

B. lodines and Particulates Iodine and particulate activity is continuously sampled. Charcoal and particulate samples are taken from the shield and auxiliary building exhausts and analyzed at least weekly to determine the total activity released from the plant based on the average vent flow rates recorded for sampling period.

E1-4

EFFLUENT AND WASTE DISPOSAL ANNUAL REPORT 2003 SUPPLEMENTAL INFORMATION Also, particulate and charcoal samples are taken from the auxiliary and shield building exhausts once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> for 2 days following startup, shutdown, or a rated thermal power change exceeding 15 percent within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />. The quantity of iodine and particulate released from each vent during each sampling period is then determined using the average vent flow rates recorded for the sampling period and activity concentration.

The total particulate and iodine activity released for the month is then determined by summing all activity released from the shield and auxiliary building exhausts for the sampling periods.

C. Liquid Effluents Batch (Radwaste and during periods of primary to secondary leakage, condensate regenerants to cooling tower blowdown)

Total gamma isotopic activity concentrations are determined on each batch of liquid effluent prior to release. The total activity of a released batch is determined by summing each nuclide's concentration and multiplying by the total volume discharged. The total activity released during a month is then determined by summing the activity content of each batch discharged during the month.

Continuous Releases and Periodic Continuous Releases (Condensate regenerants, turbine building sump, and steam generator blowdown)

Total gamma isotopic activity concentration is determined daily on a composite sample from the condensate system and turbine building sump and weekly for steam generator blowdown. The total activity of the continuous release is determined by summing each nuclide's concentration and multiplying by the total volume discharged. The total activity released during the month is then determined by summing the activity content of each daily and weekly composite for the month.

V. BATCH Value 1st 2nd Half Half Units A. Liquid (Radwaste only)

1. Number of releases 102 90 Each
2. Total time period of releases 39279 12790 Minutes
3. Maximum time period of release 20160 234 Minutes
4. Average time period of releases 385 142 Minutes
5. Minimum time period for release 7.0 15.0 Minutes
6. Average dilution stream flow during 51654 44101 CFS release periods E1 -5

EFFLUENT AND WASTE DISPOSAL ANNUAL REPORT 2003 SUPPLEMENTAL INFORMATION B. Gaseous (Batches only, containment purges, containment vents, and waste decay tanks)

1. Number of releases 68 90 Each
2. Total time period of releases 34594 40338 Minutes
3. Maximum time period for release 7923 6060 Minutes
4. Average time period for releases 509 448 Minutes
5. Minimum time period for release 15 15 Minutes VI. ABNORMAL RELEASES Value 1st 2nd Half Half Units A. Liquid Number of Releases 1* 0 Total Activity Released 4.68E-02 0.OOE-01 Ci B. Gaseous Number of Releases 0 1**

Total Activity Released 0.OOE-01 8.326E-04 Ci

  • As part of the U1 Steam Generator replacement project, two holes were cut in the roof of U1 containment for generator replacement using hydro-demolition. The water collected during the demolition process contained tritium. It was determined that 4.68E-02 curies of tritium was released to the river. The 4.68E-02 curies of tritium was added to the second quarter tritium value and included in the dose calculations.
    • During the start of U2 refueling outage in November steam was released for a period of time through the #3 SIG PORV with a small quantifiable tube leak of 0.14 gpd. It was determined that the total activity released to the atmosphere was 8.3257 curies. lodines (1-131 and 1-133), Xeon (Xe-133), and Tritium made composed this mix of nuclides that was released. The 8.3257 curies was added to the fourth quarter values and included in the dose calculations.

El-6

EFFLUENT AND WASTE DISPOSAL ANNUAL REPORT 2003 LIQUID EFFLUENTS - SUMMATION OF ALL RELEASES A. Fission and 1st 2nd 3rd 4th Activation Products Unit Qtr Qtr Qtr Qtr %Error

1. Total Released Curies 1.64E-01 1.48E-01 4.23E-02 2.27E-01
2. Average diluted concentration lCi/ml 5.11E-10 5.20E-10 1.45E-10 1.41E-10 during period
3. Percent of  %/

Applicable Limit B. Tritium

1. Total Released Curies 1.28E+03 2.19E+02 2.94E+02 2.87E+02
2. Average diluted concentration RiCi/ml 3.99E-06 7.77E-07 1.01E-06 1.80E-07 during period
3. Percent of Applicable Limit C. Dissolved and Entrained Gases
1. Total Released Curies 1.56E+00 1.83E-01 3.64E-01 9.72E-01
2. Average diluted concentration jiCi/ml 4.87E-09 6.43E-10 1.25E-09 6.05E-10 during period
3. Percent of  % 2.44E-05 3.22E-04 6.25E-04 3.03E-04 Applicable Limit D. Gross Alpha
1. Total Released Curies O.OOE-01 O.OOE-01 O.OOE-01 O.OOE-01 E. Volume of Waste Released Liters 3.61 E+06 3.41 E+06 5.44E+06 3.68E+07 F. Volume of Dilution Water for Period Liters 3.17E+08 2.81E+08 2.87E+08 1.57E+09
  • Applicable limits are expressed in terms of dose. See Tables 1 thru 4.

E1-7

EFFLUENT AND WASTE DISPOSAL ANNUAL REPORT 2003 LIQUID EFFLUENTS - TOTAL PLANT DISCHARGE G. Nuclide Summary (Note: Refer to Table A for ODCM nuclides reported as O.OOE-01)

Required by ODCM/Others Fission and Activation Products Continuous Mode Batch Mode Quarter Quarter Quarter Quarter 1 st 2 nd St 2nd Nuclide Unit 1

1. Silver-11OM Ci 0.OOE-01 O.OOE-01 7.71 E-03 1.96E-03
2. Cobalt-57 Ci 0.OOE-01 O.OOE-01 3.39E-04 3.21 E-04
3. Cobalt-58 Ci 0.OOE-01 0.OOE-01 4.55E-02 7.OOE-02
4. Cobalt-60 Ci 0.OOE-01 0.OOE-01 1.58E-02 5.91 E-03
5. Chromium-51 Ci O.OOE-01 0.OOE-01 5.74E-03 3.91 E-03
6. Cesium-134 Ci O.OOE-01 0.OOE-01 1.31E-03 1.92E-03
7. Cesium-137 Ci 0.OOE-01 0.OOE-01 3.71E-03 4.13E-03
8. Iron-55 Ci O.OOE-01 O.OOE-01 5.83E-02 3.09E-02
9. Iron-59 Ci 0.OOE-01 O.OOE-01 6.88E-04 2.53E-03
10. Iodine-131 Ci O.OOE-01 O.OOE-01 7.86E-04 1.21 E-04
11. Iodine-132 Ci O.OOE-01 O.OOE-01 1.03E-03 6.58E-05
12. Iodine-133 Ci 0.OOE-01 O.OOE-01 1.89E-05 0.OOE-01
13. Lanthanum-140 Ci 0.OOE-01 O.OOE-01 1.03E-04 1.17E-05
14. Manganese-54 Ci 0.O0E-01 0.OOE-01 1.46E-03 4.81 E-04
15. Sodium-24 Ci 0.OOE-01 O.OOE-01 2.67E-05 7.51 E-06
16. Niobium-95 Ci 0.OOE-01 O.OOE-01 1.49E-03 1.07E-03
17. Ruthenium-103 Ci 0.OOE-01 0.OOE-01 0.OOE-01 1.55E-05 18 Rubidium-88 Ci 0.OOE-01 0.O0E-01 9.83E-04 0.OOE-01
19. Antimony-124 Ci 0.OOE-01 O.OOE-01 1.23E-03 1.40E-03
20. Antimony-125 Ci 0.OOE-01 O.OOE-01 1.21E-02 2.02E-02
21. Tin-113 Ci 0.OOE-01 0.O0E-01 6.64E-05 5.48E-05 E1 -8

EFFLUENT AND WASTE DISPOSAL ANNUAL REPORT 2003 LIQUID EFFLUENTS - TOTAL PLANT DISCHARGE G. Nuclide Summary (Note: Refer to Table A for ODCM nuclides reported as O.OOE-01)

Required by ODCM/Others Fission and Activation Products Continuous Mode Batch Mode Quarter Quarter Quarter Quarter St nF st 2 nd Nuclide Unit 1 2 1

22. Tellurium-129M Ci O.OOE-01 O.OOE-01 4.02E-03 2.53E-03
23. Tellurium-132 Ci O.OOE-01 O.OOE-01 9.93E-04 2.75E-05
24. Zinc-65 Ci O.OOE-01 O.OOE-01 O.OE-01 8.36E-05
25. Zirconium-95 Ci O.OE-01 O.OOE-01 8.20E-04 5.50E-04 Total for Period ci O.OOE-01 O.OOE-01 1.64E-01 1.48E-01 El -9

EFFLUENT AND WASTE DISPOSAL ANNUAL REPORT 2003 LIQUID EFFLUENTS - TOTAL PLANT DISCHARGE G. Nuclide Summary (Note: Refer to Table A for ODCM nuclides reported as 0.OOE-01)

Required by ODCM/Others Continuous Mode Batch Mode Quarter Quarter Quarter Quarter Nuclide Unit ____ 2n_ 1st 2 nd Tritium H-3 Ci 0.OOE-01 O.OOE-01 1.28E+03 2.19E+02 Dissolved and Entrained Noble Gases

1. Argon-41 Ci 0.OOE-01 0.00E-01 4.17E-04 8.03E-06
2. Krypton-85M Ci 0.OOE-01 0.OOE-01 2.92E-04 0.OOE-01
3. Krypton-88 Ci O.OOE-01 0.OOE-01 1.71 E-04 0.OOE-01
4. Xeon-131M Ci O.OOE-01 0.OOE-01 2.43E-02 4.07E-03
5. Xeon-133 Ci O.OOE-01 O.OOE-01 1.50E+00 1.79E-01
6. Xeon-133M Ci O.OOE-01 O.OOE-01 1.31 E-02 5.71 E-04
7. Xeon-135 Ci O.OOE-01 O.OOE-01 1.65E-02 0.OOE-01 Total for Period Ci O.OOE-01 O.OOE-01 1.56E 00 1.83E-01 El -10

EFFLUENT AND WASTE DISPOSAL ANNUAL REPORT 2003 LIQUID EFFLUENTS - TOTAL PLANT DISCHARGE G. Nuclide Summary (Note: Refer to Table A for ODCM nuclides reported as O.OOE-01)

Required by ODCM/Others Fission and Activation Products Continuous Mode Batch Mode Quarter Quarter Quarter Quarter Nuclide Unit 3 rd 4th 3 rd 4 th

1. Silver-11OM Ci 0.OOE-01 0.OOE-01 9.05E-04 3.05E-02
2. Cerium-141 Ci O.OOE-01 0.OOE-01 5.09E-06 O.OOE-01
3. Cobalt-57 Ci 0.OOE-01 0.OOE-01 1.80E-04 6.54E-04
4. Cobalt-58 Ci 0.OOE-01 O.OOE-01 1.83E-02 1.18E-01
5. Cobalt-60 Ci O.OOE-01 O.OOE-01 3.56E-03 1.72E-02
6. Chromium-51 Ci O.OOE-01 0.OOE-01 7.81 E-05 6.75E-03
7. Cesium-134 Ci O.OOE-01 O.OOE-01 2.41E-03 3.91E-04
8. Cesium-137 Ci O.OOE-01 O.OOE-01 5.53E-03 5.94E-04
9. Iron-55 Ci O.OOE-01 0.OOE-01 8.19E-03 2.78E-02
10. Iron-59 Ci 0.OOE-01 0.OOE-01 1.90E-04 9.47E-04
11. Iodine-131 Ci O.OOE-01 0.OOE-01 0.OOE-01 1.26E-03
12. Iodine-132 Ci 0.OOE-01 0.OOE-01 2.44E-06 3.41E-05
13. Iodine-133 Ci O.OOE-01 0.OOE-01 4.67E-06 O.OOE-01
14. Lanthanum-140 Ci O.OOE-01 0.OOE-01 0.OOE-01 1.69E-04
15. Manganese--54 Ci 0.OOE-01 O.OOE-01 1.89E-04 1.56E-03
16. Sodium-24 Ci 0.OOE-01 O.OOE-01 0.OOE-01 3.35E-06
17. Niobium-95 Ci O.OOE-01 O.OOE-01 2.79E-04 1.51E-03
18. Rubidium-86 Ci 0.OOE-01 O.OOE-01 4.93E-05 0.OOE-01
19. Ruthenium-103 Ci 0.OOE-01 O.OOE-01 5.04E-06 0.OOE-01
20. Ruthenium-105 Ci O.OOE-01 0.OOE-01 O.OOE-01 1.07E-04
21. Antimony-124 Ci O.OOE-01 0.OOE-01 3.99E-05 1.65E-03
22. Antimony-125 Ci O.OOE-01 0.OOE-01 2.27E-03 1.56E-02 E1-11

EFFLUENT AND WASTE DISPOSAL ANNUAL REPORT 2003 LIQUID EFFLUENTS - TOTAL PLANT DISCHARGE Continuous Mode Batch Mode Quarter Quarter Quarter Quarter Unit 3 rd 4 th 3 rd 4 th Nuclide

23. Tin-113 ci O.OOE-01 O.OOE-01 9.44E-06 6.24E-05
24. Tellurium-132 Ci O.OOE-01 0.OOE-01 O.OOE-01 6.08E-06
25. Yttrium-93 ci O.OOE-01 O.OOE-01 2.79E-05 O.OOE-01
26. Zinc-65 ci O.OOE-01 O.OOE-01 O.OOE-01 2.05E-04
27. Zirconium-95 ci O.OOE-01 O.OOE-01 6.21 E-05 1.87E-03 Total for Period ci O.OOE-01 O.OOE-01 4.23E-02 2.27E-01 El-12

EFFLUENT AND WASTE DISPOSAL ANNUAL REPORT 2003 LIQUID EFFLUENTS - TOTAL PLANT DISCHARGE G. Nuclide Summary (Note: Refer to Table A for ODCM nuclides reported as O.OOE-01)

Required by ODCM/Others Continuous Mode Batch Mode Quarter Quarter Quarter Quarter Nuclide Unit 3 rd 4 th 3 rd 4 th Tritium H-3 Ci O.OOE-01 1.13E-01 2.94E+02 2.87E+02 Dissolved and Entrained Noble Gases

1. Argon-41 Ci O.OOE-01 O.OOE-01 3.44E-06 2.56E-04
2. Krypton-85 Ci O.OOE-01 O.OOE-01 O.OOE-01 1.32E-03
3. Krypton-85M Ci O.OOE-01 O.OOE-01 9.12E-06 O.OOE-01
4. Krypton-88 Ci O.OOE-01 O.OOE-01 1.19E-05 1.25E-05
5. Xeon-131M Ci 0.00E-01 O.OOE-01 6.29E-03 2.71E-02
6. Xeon-133 Ci 0.00E-01 O.OOE-01 3.56E-01 O.OOE-01
7. Xeon-133M Ci O.OOE-01 O.OOE-01 1.97E-03 4.76E-03
8. Xeon-135 Ci O.OOE-01 O.OOE-01 2.39E-04 5.43E-04 Total for Period Ci O.OOE-01 O.OOE-01 3.64E-01 9.72E-01 E1-13

EFFLUENT AND WASTE DISPOSAL ANNUAL REPORT 2003 TABLE A LIQUID "TYPICAL LLD" EVALUATION")

ESt(2)

Nuclide 00CM LLD 1 hr 8 hr 32 hr Manganese-54 5.OE-07 3.36E-08 3.36E-08 3.37E-08 Cobalt-58 5.OE-07 2.53E-08 2.54E-08 2.56E-08 Iron-59 5.OE-07 5.26E-08 5.29E-08 5.37E-08 Cobalt-60 5.OE-07 4.63E-08 4.63E-08 4.64E-08 Zinc-65 5.OE-07 2.95E-08 2.95E-08 2.96E-08 Molybdenum-99 5.OE-07 1.55E-07 1.67E-07 2.15E-07 Cesium-134 5.OE-07 1.91 E-08 1.91E-08 1.92E-08 Cesium-137 5.OE-07 3.87E-08 3.87E-08 3.87E-08 Cerium-141 5.OE-07 2.80E-08 2.81 E-08 2.87E-08 Cerium-144 5.OE-06 1.11E-07 1.12E-07 1.12E-07 Iodine-131 1.OE-06 2.28E-08 2.34E-08 2.55E-08 Krypton-87 1.OE-05 1.16E-07 5.25E-07 (3)

Krypton-88 1.OE-05 9.95E-08 5.49E-07 (3)

Xenon-1 33 1.OE-05 4.19E-08 4.36E-08 4.98E-08 Xenon-1 33m 1.OE-05 1.42E-07 1.55E-07 2.13E-07 Xenon-135 1.OE-05 2.06E-08 3.50E-08 2.17E-07 Xenon-138 1.OE-05 8.37E-06 (3) (3)

Nuclide 0DCM LLD Typical LLD Tritium 1.OE-05 1.2E-06 Gross Alpha 1.OE-07 2.OE-08 Strontium-89/90 5.OE-08 3.8E-08/1.4E-08 Iron-55 1.OE-06 1.3E--08 NOTES: (1) LLD values are in pCi/ml.

(2. [t is the time between sample collection and counting time.

(3. T 1/2 too short.

El-14

EFFLUENT AND WASTE DISPOSAL ANNUAL REPORT 2003 GASEOUS EFFLUENTS - SUMMATION OF ALL RELEASES (GROUND LEVEL RELEASES)

Summation of All 1 St 2 nd 3 rd 4 th Releases Unit Qtr Qtr Qtr Qtr %Error A. Noble Gases

1. Total Released Ci 5.96E+02 1.33E+03 4.61E+02 2.75E+02 <1.1E+01
2. Average Release Rate of Period PCi/sec 7.66E+01 1.69E+02 5.80E+01 3.46E+01
3. Percent of Limit  % * * *
  • B. lodines
1. Total lodine-131 Ci 2.75E-04 3.51 E-06 O.OOE-01 1.21E-03 <1.3E+01
2. Average Release Rate for Period guCi/sec 3.54E-05 4.46E-07 O.OOE-01 1.52E-04
3. Percent of Limit C. Particulates
1. Particulates with half-lives >8 days Ci 2.90E-06 O.OOE-01 O.OOE-01 O.OOE-01 <1.6E+01
2. Average Release Rate for Period jlCi/sec 3.73E-07 O.OOE-01 O.OOE-01 O.OOE-01
3. Percent of Limit
4. Gross Alpha Ci O.OOE-01 O.OOE-01 O.OOE-01 O.OOE-01 <2.1E+01 Radio-activity D. Tritium
1. Total Release Ci 1.83E+01 1.85E+01 8.72E+OO 3.05E+00 <1.5E+01
2. Average Release Rate for Period ptCi/sec 2.54E+00 2.36E+00 1.10 E+00 3.84E-01
3. Percent of Limit
  • Applicable limits are expressed in terms of dose. See Tables 5 thru 8.

El-15

EFFLUENT AND WASTE DISPOSAL ANNUAL REPORT 2003 GASEOUS EFFLUENTS - SUMMATION OF ALL RELEASES (GROUND LEVEL RELEASES)

1. Noble Gases Required by ODCM/Others Continuous Mode Batch Mode Quarter Quarter Quarter Quarter Nuclide Unit 1st 2nd 1st 2nd
1. Krypton-87 Ci O.OOE-01 O.OOE-01 4.87E-02 O.OOE-01
2. Krypton-88 Ci O.OOE-01 O.OOE-01 2.91 E-01 4.59E-02
3. Krypton-85M Ci O.OOE-01 O.OOE-01 4.29E-01 6.39E-02
4. Krypton-85 Ci O.OOE-01 O.OOE-01 1.85E-01 2.17E-01
5. Argon-41 Ci O.OOE-01 O.OOE-01 2.47E+00 4.54E-01
6. Xeon-135 Ci 5.89E-03 8.04E-03 9.09E+00 1.49E+00
7. Xeon-133M Ci 0.00E-01 O.OOE-01 6.55E+00 1.52E+00
8. Xeon-131M Ci O.OOE-01 O.OOE-01 3.77E+00 1.56E+00
9. Xeon-133 Ci 4.64E+00 1.17E+03 5.68E+02 9.865E2 Total for Period Ci 4.64E+00 1.17E+03 5.91E+02 1.61E+02
2. lodines
1. Iodine-133 Ci 2.22E-04 7.11E-05
2. Iodine-131 Ci 2.75E-04 5.91 E-04 Total for Period Ci 4.97E-04 3.51 E-06 NOTE: Refer to Table B for ODCM nuclides reported as O.OOE-01.

E1-16

EFFLUENT AND WASTE DISPOSAL ANNUAL REPORT 2003 GASEOUS EFFLUENTS - SUMMATION OF ALL RELEASES (GROUND LEVEL RELEASES)

3. Particulates Required by ODCM/Others Continuous Mode Quarter Quarter Nuclide Unit 1st 2nd
1. Cerium-141 Ci 2.90E-06 O.OOE-01
2. Bromine-82 Ci O.OOE-01 2.69E-06 Total for Period Ci 2.90E-06 2.69E-06 NOTE: Refer to Table B for ODCM nuclides reported as O.OOE-01.

El-17

EFFLUENT AND WASTE DISPOSAL ANNUAL REPORT 2003 GASEOUS EFFLUENTS - SUMMATION OF ALL RELEASES (GROUND LEVEL RELEASES)

1. Noble Gases Required by ODCM/Others Continuous Mode Batch Mode Quarter Quarter Quarter Quarter Nuclide Unit 3rd 4th 3rd 4th
1. Krypton-88 ci O.OOE-01 1.77E-04 5.91 E-02 6.69E-04
2. Krypton-85M ci 2.19E-03 1.23E-03 9.07E-02 2.22E-02
3. Krypton-85 ci O.OOE-01 0.OOE-01 0.OOE-01 7.76E-02
4. Xenon-1 35 ci 8.87E-03 3.86E-03 2.01 E+00 6.57E-01
5. Xeon-133M ci 0.OOE-01 O.OOE-01 3.92E+00 2.13E+00
6. Argon-41 ci O.00E-01 0.OOE-01 1.44E+00 2.17E+00
7. Xenon-131 M ci 1.51 E-02 0.OOE-01 5.20E+00 3.22E+00
8. Xenon-133 ci 7.41 E+00 2.14E+00 4.41 E+02 2.64E+02 Total for Period ci 7.44E+00 2.14E+00 4.54E+02 2.73E+02
2. lodines
1. Iodine-131 Ci 0.OOE-01 1.143E-03 2 Iodine-133 7.11E-05 Total for Period Ci O.OOE-01 1.214E-03 NOTE: Refer to Table B for ODCM nuclides reported as O.OOE-01.

E1-18

EFFLUENT AND WASTE DISPOSAL ANNUAL REPORT 2003 GASEOUS EFFLUENTS - SUMMATION OF ALL RELEASES (GROUND LEVEL RELEASES)

3. Particulates Required by ODCM/Others Continuous Mode Quarter Quarter Nuclide Unit 3rd 4th
1. Bromine-82 Ci 3.33E-06 4.44E-07 Total for Period Ci 3.33E-06 4.44E-07 NOTE: Refer to Table B for ODCM nuclides reported as O.OOE-01.

E1-19

EFFLUENT AND WASTE DISPOSAL ANNUAL REPORT 2003 TABLE B GASEOUS "TYPICAL" LLD EVALUATION( 1 )

Noble Gas ot(2)

Nuclide ODCM LLD 1 hr 1.5 hr Krypton-87 1.OE-04 2.08E-06 2.73E-06 Krypton-88 1.OE-04 1.61 E-06 1.81 E-06 Xenon-1 33 1.OE-04 6.61 E-07 6.63E-07 Xenon-133m 1.OE-04 2.34E-06 2.35E-06 Xenon-1 35 1.OE-04 3.43E-07 3.56E-07 Xenon-138 1.OE-04 1.40E-04 6.1OE-04 Particulate Sam le(3) 1 hr 24 hr 7.0 da Manganese-54 1.OE-10 7.47E-12 3.12E-13 4.48E-14 Cobalt-58 1.OE-10 5.62E-12 2.35E-13 3.46E-14 Iron-59 1.OE-10 1.20E-11 5.02E-13 7.49E-14 Cobalt-60 1.OE-10 1.07E-1 1 4.46E-13 6.38E-14 Zinc-65 1.OE-10 6.71E-12 2.80E-13 4.03E-14 Molybdenum-99 1.OE-10 3.43E-11 1.61E-12 4.70E-13 Cesium-134 1.0E-10 4.25E-12 1.77E-13 2.54E-14 Cesium-137 1.OE-10 8.48E-12 3.54E-13 5.05E-14 Cerium-141 1.OE-10 5.10E-12 2.15E-13 3.26E-14 Cerium-144 1.OE-10 2.01E-11 8.33E-13 1.20E-13 lodine-131 1.OE-10 4.76E-12 2.07E-13 3.77E-14 Charcoal Sample lodine-131 1.OE-11 7.25E-12 3.15E-13 5.74E-14 (1) LLD values are in jtCi/ml.

(2) Ot is the time between sample collection and counting time.

(3) LLD based on sample time + 30 min. sample to analysis.

El-20

EFFLUENT AND WASTE DISPOSAL ANNUAL REPORT 2003 TABLE B GASEOUS "TYPICAL" LLD EVALUATION" 1 )

Nuclide ODCM LLD Typical LLD Tritium 1.OE-06 1.OE-11 Gross Alpha 1.OE-11 1.5E-14 Strontium-89 1.OE-11 1.OE-14 Strontium-90 1.OE-11 1.OE-15 NOTES: (1) LLD values are in liCi/cc.

(2) Ft for noble gases is the time from sampling to analysis.

Elt for charcoal and particulate samples is the midpoint of sampling to analysis.

E1-21

EFFLUENT AND WASTE DISPOSAL ANNUAL REPORT 2003 SOLID WASTE (RADIOACTIVE SHIPMENTS)

A. Solid Waste Shipped Offsite for Burial or Disposal (not Irradiated Fuel) 12 Month Est. Tot.

1. Type of Waste Unit Period Error %
a. Spent Resins, Filter Sludges, Evaporator m3 3.41 E+00 +3.OE-01 Bottoms, etc. Ci 5.30E+01 +1.OE+01
b. Dry Active Waste, Compressible Waste m3 3.82E+01 +1.OOE-01 Contaminated Equipment, etc. Ci 1.02E+00 +3.00E-01
c. Irradiated Components, Control m3 None N/A Rods, etc. Ci None N/A
d. Other: Mechanical Filters m3 3.41 E+00 +3.OE-01 Ci 9.26E+00 +1.0E+00
2. Estimate of Maior Nuclide Composition (by type of waste)
a. Spent resins, filter sludges, evaporator bottoms, etc. (nuclides determined by measurement)

Curies Percent

1. Carbon-14 6.08E-01 1.15
2. Manganese-54 4.85E-01 0.91
3. Iron-55 5.47E+00 10.32
4. Nickel-59 2.77E-01 0.52
5. Cobalt-60 1.04E+01 19.62
6. Nickel-63 2.92E+01 55.08
7. Antimony-125 8.35E-01 1.57
8. Cesium-134 1.43E+00 2.70
9. Cesium-137 4.09E+00 7.71
10. Plutonium-238 3.84E-04 0.00
11. Plutonium-241 9.67E-03 0.02
12. Americium-241 1.90E-04 0.00
13. Curium-243 5.32E-04 0.00
14. Curium-244 5.25E-04 0.00
b. Dry active waste, compressible waste, contaminated equipment, etc. (nuclides determined by estimate)

Curies Percent

1. Chromium-51 4.61E-02 4.54
2. Manganese-54 1.45E-02 1.42
3. Iron-55 3.94E-01 38.69 El-22

EFFLUENT AND WASTE DISPOSAL ANNUAL REPORT 2003 SOLID WASTE (RADIOACTIVE SHIPMENTS)

2. Estimate of Major Nuclide Composition (by tyre of waste) (Cont.)
b. Dry active waste, compressible waste, contaminated equipment, etc. (nuclides determined by estimate) continued Curies Percent
4. Cobalt-57 1.12E-03 0.11
5. Cobalt-58 2.28E-01 22.36
6. Iron-59 4.04E-03 0.40
7. Cobalt-60 7.96E-02 7.82
8. Nickel-63 1.88E-01 18.46
9. Zinc-65 2.68E-03 0.26
10. Zirconium-95 3.85E-03 0.38
11. Niobium-95 7.03E-03 0.69
12. Silver-110m 3.03E-03 0.30
13. Tin-113 1.30E-03 0.13
14. Antimony-125 8.03E-03 0.79
15. Cesium-134 6.61E-03 0.65
16. Cesium-137 3.05E-02 3.00
c. Irradiated Components Curies Percent None N/A N/A
d. Other: Mechanical Filters Curies Percent Curies Percent
1. Carbon-14 2.27E-01 2.45
2. Manganese-54 7.74E-02 0.84
3. Iron-55 7.08E+00 76.45
4. Cobalt-58 4.22E-02 0.46
5. Cobalt-60 7.93E-01 8.56
6. Nickel-63 2.68E-01 2.89
7. Ruthenium-106 1.84E-02 0.20
8. Silver-110m 9.47E-03 0.10
9. Tin-113 4.30E-02 0.46
10. Antimony-125 1.76E-02 0.19
11. Cesium-134 6.68E-02 0.72
12. Cesium-137 5.76E-01 6.22
13. Plutonium-238 1.40E-04 0.00
14. Plutonium-241 1.25E-02 0.13
15. Curium-243 4.10E-04 0.00
16. Curium-244 4.02E-04 0.00 E1-23

EFFLUENT AND WASTE DISPOSAL ANNUAL REPORT 2003 SOLID WASTE (RADIOACTIVE SHIPMENTS)

3. Solid Waste Disposition
a. Spent resins, filter sludges, evaporator bottoms, etc.

Number of Shipments Tvpe Quantity Mode of Transportation Destination 1 B-LSA II Motor Freight Chem-Nuclear Barnwell, SC

b. Dry active waste, compressible waste, contaminated equipment, etc.

Number of Shipments Type Quantity Mode of Transportation Destination 66* A-LSA Motor Freight Envirocare near Clive, Utah

  • 66 of the shipments were shipped by a waste processor.
c. Irradiated components, control rods, etc.

Number of Shipments Type Quantity Mode of Transportation Destination None N/A N/A N/A

d. Other: Mechanical Filters Number of Shipments Type Quantity Mode of Transportation Destination 1 A-LSA II Motor Freight Chem-Nuclear Barnwell, SC
4. Irradiated Fuel Shipments (Disposition)

Number of Shipments Type Quantity Mode of Transportation Destination None N/A N/A N/A

5. Solidification of Waste Was solidification performed? NO If yes, solidification media: N/Ak E1-24

ENCLOSURE 2 RADIOLOGICAL IMPACT ASSESSMENT REPORT SEQUOYAH NUCLEAR PLANT JANUARY - DECEMBER 2003

EFFLUENT AND WASTE DISPOSAL ANNUAL REPORT 2003 INTRODUCTION Potential doses to maximum individuals and the population around Sequoyah Nuclear Plant (SQN) are calculated for each quarter as required in Section 5.2 of the Offsite Dose Calculation Manual (ODCM). Measured plant releases for the reporting period are used to estimate these doses.

Dispersion of radioactive effluents in the environment is estimated using meteorological data and riverflow data measured during the period. In this report, the doses resulting from releases are described and compared to limits established for SQN.

DOSE LIMITS The ODCM specifies limits for the release of radioactive effluents, as well as limits for doses to the general public from the release of radioactive effluents. These limits are set well below the Technical Specification limits which govern the concentrations of radioactivity and doses permissible in unrestricted areas. This ensures that radioactive effluent releases are "As Low As Reasonably Achievable."

The limits for doses in unrestricted areas from airborne noble gases releases are:

Less than or equal to 5 mrad per quarter and 10 mrad per year (per reactor unit) for gamma radiation,

- and -

Less than or equal to 10 mrad per quarter and 20 mrad per year (per reactor unit) for beta radiation.

The limit for the dose to a member of the general public in an unrestricted area from iodines and particulates released in airborne effluents is:

Less than or equal to 7.5 mrem per quarter and 15 mrem per year (per reactor unit) to any organ.

The limit for doses to a member of the general public from radioactive material in liquid effluents released to unrestricted areas is:

Less than or equal to 1.5 mrem per quarter and 3 mrem per year (per reactor unit) to the total body,

- and -

Less than or equal to 5 mrem per quarter and 10 mrem per year (per reactor unit) to any organ The EPA limits for total dose to the public in the vicinity of a nuclear power plant, established in the Environmental Dose Standard of 40 CFR 190 are:

Less than or equal to 25 mrem per year to the total body, Less than or equal to 75 mrem per year to the thyroid,

-and -

Less than or equal to 25 mrem per year to any other organ.

E2-2

EFFLUENT AND WASTE DISPOSAL ANNUAL REPORT

  • 2003 DOSE CALCULATIONS Estimated doses to the public are determined using computer models: Gaseous Effluent Licensing Code (GELC), and the Quarterly Water Dose Assessment Code (QWATA). These models are based on guidance provided by the NRC (in Regulatory Guides 1.109, 1.111 and 1.1 13) for determining the potential dose to individuals and populations living in the vicinity of the plant. The area around the plant is analyzed to determine the pathways through which the public may receive a dose. The doses calculated are a representation of the dose to a "maximum exposed individual." Some of the factors used in these calculations (such as ingestion rates) are maximum values. Many of these factors are obtained from NUREG/CR-1004. The values chosen will tend to overestimate the dose to this "maximum" person. The expected dose to actual individuals is lower. The calculated doses are presented in Tables I through 9.

DOSES FROM AIRBORNE EFFLUENTS For airborne effluents, the public can be exposed to radiation from several sources: direct radiation from the radioactivity in the air, direct radiation from radioactivity deposited on the ground, inhalation of airborne radioactivity, ingestion of vegetation which contains radioactivity deposited from the atmosphere, and ingestion of milk and beef which contains radioactivity deposited from the atmosphere onto vegetation and subsequently eaten by milk and beef animals.

Airbome Discharge Points Releases from SQN are considered ground-level releases. The ground-level Joint Frequency Distribution (JFD) is derived from windspeeds and directions measured 10 meters above ground and from the vertical temperature difference between 10 and 46 meters, and are presented for each quarter in Attachment 1.0.

Meteorological Data Meteorological variables at SQN are measured continuously. Measurements collected include wind speed, wind direction, and temperature at heights of 10, 46, and 91 meters above the ground. Quarterly joint frequency distributions (JFDs) are calculated for each release point using the appropriate levels of meteorological data. A JFD gives the percentage of the time in a quarter that the wind is blowing out of a particular upwind compass sector in a particular range of wind speeds for a given stability Class A through G. The wind speeds are divided into nine wind speed ranges. Calms are distributed by direction in proportion to the distribution of noncalm wind directions less than 0.7 m/s (1.5 mph). Stability classes are determined from the vertical temperature difference between two measurement levels.

External Exposure Dose Dose estimates for maximum external air dose (gamma-air and beta-air doses) are made for points at and beyond the unrestricted area boundary as described in the SQN ODCM. The highest of these doses is then selected.

E2-3

EFFLUENT AND WASTE DISPOSAL ANNUAL REPORT 2003 Submersion Dose External doses to the skin and total body, due to submersion in a cloud of noble gases, are estimated for the nearest residence in each sector. The residence with the highest dose is then selected from all sectors.

Organ Dose Doses to organs due to releases of airborne effluents are estimated for the inhalation, ground contamination, and ingestion pathways. The ingestion pathway is further divided into four possible contributing pathways: ingestion of cow/goat milk, ingestion of beef, and ingestion of vegetables. Doses from applicable pathways are calculated for each real receptor location identified in the most recent land use survey. To determine the maximum organ dose, the doses from the pathways are summed for each receptor. For the ingestion dose, however, only those pathways that exist for each receptor are considered in the sum, i.e., milk ingestion doses are included only for locations where milk is consumed without commercial preparation and vegetable ingestion is included only for those locations where a garden is identified. To conservatively account for beef ingestion, a beef ingestion dose equal to that for the highest unrestricted area boundary location is added to each identified receptor. For ground contamination, the dose added to the organ dose being calculated is the total body dose calculated for that location, i.e., it is assumed that the dose to an individual organ is equal to the total body dose.

Doses from airborne effluents are presented in Tables 1 through 4.

DOSES FROM LIQUID EFFLUENTS For liquid effluents, the public can be exposed to radiation from three sources: the ingestion of water from the Tennessee River, the ingestion of fish caught in the Tennessee River, and direct exposure from radioactive material deposited on the river shoreline sediment (recreation).

The concentrations of radioactivity in the Tennessee River are estimated by a computer model which uses measured hydraulic data downstream of SQN. Parameters used to determine the doses are based on guidance given by the NRC (in Regulatory Guides 1.109) for maximum ingestion rates, exposure times, etc. Wherever possible, parameters used in the dose calculation are site specific use factors determined by TVA. The models that are used to estimate doses, as well as the parameters input to the models, are described in detail in the SQN ODCM.

Liquid Release Points and River Data Radioactivity concentrations in the Tennessee River are calculated assuming that releases in liquid effluents are continuous. Routine liquid releases from SQN, located at Tennessee River Mile 484, are made through diffusers which extend into the Tennessee River. It is assumed that releases to the river through these diffusers will initially be entrained in one-fifth of the water which flows past the plant. The QWATA code makes the assumption that this mixing condition holds true until the water is completely mixed at the first downstream dam, at Tennessee River Mile 471.0.

E2-4

EFFLUENT AND WASTE DISPOSAL ANNUAL REPORT 2003 Doses are calculated for locations within a 50-mile radius downstream of the plant site. The maximum potential recreation dose is calculated for a location immediately downstream from the plant outfall. The maximum individual dose from ingestion of fish is assumed to be that calculated for the consumption of fish caught anywhere between the plant and the first downstream dam (Chickamauga Dam). The maximum individual dose from drinking water is assumed to be that calculated at the nearest downstream public water supply (East Side Utilities). This could be interpreted as indicating that the maximum individual, as assumed for liquid releases from Sequoyah, is an individual who obtains all of his drinking water at East Side Utilities, consumes fish caught from the Tennessee River between SQN and Chickamauga Dam, and spends 500 hours0.00579 days <br />0.139 hours <br />8.267196e-4 weeks <br />1.9025e-4 months <br /> per year on the shoreline just below the outfall from Sequoyah. Dose estimates for the maximum individual due to liquid effluents for each quarter in the period are presented in Tables 5 through 8, along with the average river flows past the plant site for the periods.

Population doses are calculated assuming that each individual consumes milk, vegetables, and meat produced within the sector annulus in which he resides. Doses from external pathways and inhalation are based on the 50-mile human population distribution.

POPULATION DOSES Population doses for highest exposed organ due to airborne effluents are calculated for an estimated 1,060,000 persons living within a 50-mile radius of the plant site. Doses from external pathways and inhalation are based on the 50-mile human population distribution.

Ingestion population doses for total body and the maximum exposed organ due to liquid effluents are calculated for the entire downstream Tennessee River population. Water ingestion population doses are calculated using actual population figures for downstream public water supplies. Fish ingestion population doses are calculated assuming that all sport fish caught in the Tennessee River are consumed by the Tennessee River population.

Recreation population doses are calculated using actual recreational data on the number of shoreline visits at downstream locations.

Population dose estimates for airborne and liquid effluents are presented in Tables 1 through 8.

DIRECT RADIATION External gamma radiation levels were measured by thermoluminescent dosimeters (TLDs) deployed around SQN as part of the offsite Environmental Radiological Monitoring Program.

The quarterly gamma radiation levels determined from these TLDs during this reporting period averaged approximately 16.25 mR/quarter at onsite (at or near the site boundary) stations and approximately 14.75 mR/quarter at offsite stations, or approximately 1.5 mR/quarter higher onsite than at offsite stations. This difference is consistent with levels measured for preoperation and construction phases of the TVA nuclear plant site where the average radiation levels onsite were generally 2-6 mR/quarter higher than the levels offsite. This may be attributable to natural variations in environmental radiation levels, earth moving activities onsite, the mass of concrete employed in the construction of the plants, or other E2-5

EFFLUENT AND WASTE DISPOSAL ANNUAL REPORT 2003 undetermined influences. Fluctuations in natural background dose rates and in TLD readings tend to mask any small increments which may be due to plant operations. Thus, there was no identifiable increase in dose rate levels attributable to direct radiation from plant equipment and/or gaseous effluents.

DOSE TO A MEMBER OF THE PUBLIC INSIDE THE UNRESTRICTED AREA BOUNDARY As stated in the SQN Offsite Dose Calculation Manual, an evaluation of the dose to a member of the public inside the unrestricted area boundary is performed for a hypothetical TVA employee who works just outside the restricted area fence for an entire work year (2000/8760 hours). Results from onsite TLD measurements for the calendar year in question indicate that the highest onsite TLD reading was 76 mrem. Using this value, and subtracting an annual background value of 65 mrem/year, and multiplying by the ratio of the occupancy times, the external dose was 2.5 mrem. The doses due to radioactive effluents released to the atmosphere calculated in this report would not add a significant amount to this measured dose. This dose is well below the 10 CFR 20 annual limit of 100 mrem.

TOTAL DOSE To determine compliance with 40 CFR 190, annual total dose contributions to the maximum individual from SQN radioactive effluents and other nearby uranium fuel cycle sources are considered.

The annual dose to any organ other than thyroid for the maximum individual is conservatively estimated by summing the following doses: the total body air submersion dose for each quarter, the critical organ dose (for any organ other than the thyroid) from airborne effluents for each quarter from ground contamination, inhalation and ingestion, the total body dose from liquid effluents for each quarter, the maximum organ dose (for any organ other than the thyroid) from liquid effluents for each quarter, and any identifiable increase in direct radiation dose levels as measured by the environmental monitoring program. This dose is compared to the 40 CFR 190 limit for total body or any organ dose (other than thyroid) to determine compliance.

The annual thyroid dose to the maximum individual is conservatively estimated by summing the following doses: the total body air submersion dose for each quarter, the thyroid dose from airborne effluents for each quarter, the total body dose from liquid effluents for each quarter, the thyroid dose from liquid effluents for each quarter, and any identifiable increase in direct radiation dose levels as measured by the environmental monitoring program. This dose is compared to the 40 CFR 190 limit for thyroid dose to determine compliance.

Cumulative annual total doses are presented in Table 9.

E2-6

EFFLUENT AND WASTE DISPOSAL ANNUAL REPORT 2003 Table 1 Doses from Airborne Effluents First Quarter Individual Doses Quarterly Percent of Location Pathway Dose Limit Limit Sector/Distance External Gamma Air 3.48E-02 mrad 5 mrad <1 N/950 Beta Air 9.12E-02 mrad 10 mrad <1 N/950 Submersion Total Body 1.95E-02 mrad 10 mrad <1 NNW/841 Skin 4.47E-02 mrad 10 mrad <1 NNW/841 Organ Doses Child/Thyroid 3.27E-02 mrem 7.5 mrem <1 NNW/841 Child/Total Body 3.07E-02 mrem 7.5 mrem <1 NNW/841 Population Doses Total Body Dose 5.5r iE-02 man-rem Maximum Organ Dose (organ) 6.05E-02 man-rem (thyroid)

Population doses can be compared to the natural background dose for the entire 50-mile population of about 95,400 man-rem/year (based on 90 mrem/yr for natural background).

E2-7

EFFLUENT AND WASTE DISPOSAL ANNUAL REPORT 2003 Table 2 Doses from Airborne Effluents Second Quarter Individual Doses Quarterly Percent of Location Pathway Dose Limit Limit Sector/Distance External Gamma Air 1.03E-01 mrad 5 mrad <1 N/950 Beta Air 3.03E-01 mrad 10 mrad <1 N/950 Submersion Total Body 5.31E-02 mrad 10 mrad <1 N/1295 Skin 1.26E-01 mrad 10 mrad <1 N/1295 Organ Doses Child/Thyroid 6.20E-02 mrem 7.5 mrem <1 NNW/841 Child/Total Body 6.19E-02 mrem 7.5 mrem <1 NNW/841 Population Doses Total Body Dose 1.05E-01 man-rem Maximum Organ Dose (organ) 1.05E-01 man-rem (thyroid, liver, bone, GIT, lung, kidney)

Population doses can be compared to the natural background dose for the entire 50-mile population of about 95,400 man-rem/year (based on 90 mrem/yr for natural background).

E2-8

EFFLUENT AND WASTE DISPOSAL ANNUAL REPORT 2003 Table 3 Doses from Airborne Effluents Third Quarter Individual Doses Quarterly Percent of Location Pathway Dose Limit Limit Sector/Distance External Gamma Air 3.67E-02 mrad 5 mrad <1 N/950 Beta Air 1.02E-01 mrad 10 mrad <1 N/950 Submersion Total Body 2.03E-02 mrad 10 mrad <1 S/1786 Skin 4.73E-02 mrad 10 mrad <1 S/1786 Organ Doses Child/Thyroid 2.46E-02 mrem 7.5 mrem <1 NNW/841 Child/Total Body 2.46E-02 mrem 7.5 mrem <1 NNW/841 Population Doses Total Body Dose 4.1OE-02 man-rem Maximum Organ Dose (organ) 4.10E-02 man-rem (thyroid, Liver, Bone, GIT, Lung, Kidney)

Population doses can be compared to the natural background dose for the entire 50-mile population of about 95,400 man-rem/year (based on 90 mrem/yr for natural background).

E2-9

EFFLUENT AND WASTE DISPOSAL ANNUAL REPORT 2003 Table 4 Doses from Airborne Effluents Fourth Quarter Individual Doses Quarterly Percent of Location Pathway Dose Limit Limit Sector/Distance External Gamma Air 1.87E-02 mrad 5 mrad <1 SSW/1 840 Beta Air 4.86E-02 mrad 10 mrad <1 SSW/1 840 Submersion Total Body 1.28E-02 mrad 10 mrad <1 SSW/2134 Skin 2.89E-02 mrad 10 mrad <1 SSW/2134 Organ Doses Child/Thyroid 2.08E-02 mrem 7.5 mrem <1 NNW/841 Child/Total Body 1.45E-02 mrem 7.5 mrem <1 NNW/841 Population Doses Total Body Dose 2.1( 3E-02 man-rem Maximum Organ Dose (organ) 3.18E-02-man-rem (thyroid)

Population doses can be compared to the natural background dose for the entire 50-mile population of about 95,400 man-rem/year (based on 90 mrem/yr for natural background).

E2-1 0

EFFLUENT AND WASTE DISPOSAL ANNUAL REPORT 2003 Table 5 Doses from Liquid Effluents First Quarter Individual Doses (mrem)

Quarterly Percent Age Group Organ Dose Limit of Limit Child Total Body 5.30E-03 1.5 mrem <1 %

Child Liver 6.OOE-03 5 mrem <1 %

Child Thyroid 5.20E-03 5 mrem <1 %

Average Riverflow past SQN (cubic feet per second): 52,583 Population Doses Total Body Dose 3.20E-01 man-rem Maximum Organ Dose (organ) 3.30E-01 man-rem (liver, thyroid, GIT)

Population doses can be compared to the natural background dose for the entire 50-mile population of about 95,400 man-rem/year (based on 90 mrem/yr for natural background).

E2-11

EFFLUENT AND WASTE DISPOSAL ANNUAL REPORT 2003 Table 6 Doses from Liquid Effluents Second Quarter Individual Doses (mrem)

Quarterly Percent Age Group Organ Dose Limit of Limit Adult Total Body 1.60E-03 1.5 mrem < 1%

Child Liver 2.1OE-03 5 mrem <1 %

Child Thyroid 1.10E-03 5 mrem < 1%

Average Riverflow past SQN (cubic feet per second): 50,724 Population Doses Total Body Dose 7.20E-02 man-rem Maximum Organ Dose (organ) 7.40E-02 man-rem (GIT)

Population doses can be compared to the natural background dose for the entire 50-mile population of about 95,400 man-rem/year (based on 90 mrem/yr for natural background).

E2-12

EFFLUENT AND WASTE DISPOSAL ANNUAL REPORT 2003 Table 7 Doses from Liquid Effluents Third Quarter Individual Doses (mrem)

Quarterly Percent Age Group Organ Dose Limit of Limit Adult Total Body 2.40E-03 1.5 mrem <1 %

Child Liver 3.1OE-03 5 mrem < 1%

Child Thyroid 1.50E-03 5 mrem <1%

Average Riverflow past SQN (cubic feet per second): 42,309 Population Doses Total Body Dose 1.1OE-01 man-rem Maximum Organ Dose (organ) 1.10E-01 man-rem (bone, GIT, liver, kidney, lung)

Population doses can be compared to the natural background dose for the entire 50-mile population of about 95,400 man-rem/year (based on 90 mrem/yr for natural background).

E2-13

EFFLUENT AND WASTE DISPOSAL ANNUAL REPORT 2003 Table 8 Doses from Liquid Effluents Fourth Quarter Individual Doses (mrem)

Quarterly Percent Age Group Organ Dose Limit of Limit Child Total Body 1.80E-3 1.5 mrem <1 %

Adult Bone 2.50E-3 5 mrem < 1%

Child Thyroid 1.90E-03 5 mrem <1 %

Average River flow past SQN (cubic feet per second): 45,893 Population Doses Total Body Dose 1.10E-01 man-rem Maximum Organ Dose (organ) 1.20E-01 man-rem (GIT)

Population doses can be compared to the natural background dose for the entire 50-mile population of about 95,400 man-rem/year (based on 90 mrem/yr for natural background).

E2-14

EFFLUENT AND WASTE DISPOSAL ANNUAL REPORT 2003 Table 9 Total Dose from Fuel Cycle First Second Third Fourth Dose Quarter Quarter Quarter Quarter Total Body or any Organ (except thyroid)

Total body air submersion 1.95E-02 5.31 E-02 2.03E-02 1.28E-02 Critical organ dose (air) 3.07E-02 6.19E-02 2.46E-02 1.46E-02 Total body dose (liquid) 5.30E-03 1.60E-03 2.40E-03 1.80E-03 Maximum organ dose 6.OOE-03 2.10E-03 3.10E-03 2.50E-03 (liquid)

Direct Radiation Dose O.OOE-00 O.OOE-00 O.OOE-O0 O.OOE-00 Total 6.15E-02 1.19E-01 5.04E-02 3.17E-02 Cumulative Total Dose (Total body or any other organ) mrem 2.62E-01 Annual Dose Limit (mrem) 25 Percent of Limit 1.05 Thyroid Dose (mrem)

Total body air submersion 1.95E-02 5.31 E-02 2.03E-02 1.28E-02 Thyroid dose (airborne) 3.27E-02 6.20E-02 2.46E-02 2.08E-02 Total body dose (liquid) 5.30E-03 1.60E-03 2.40E-03 1.80E-03 Thyroid dose (liquid) 5.20E-03 1.10E-03 1.50E-03 1.90E-03 Direct Radiation Dose O.OOE-00 O.OOE-00 O.OOE-00 O.OOE-00 Total 6.27E-02 1.18E-01 4.88E-02 3.73E-02 Cumulative Total Dose (Thyroid) mrem 2.67E-01 Annual Dose Limit (mrem) 75 Percent of Limit 3.56E-01 E2-15

Attachment 1.0 Joint Frequency Distribution Tables Al-1

JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS A (DELTA T<=-1.9 C/100 M)

Sequoyah Nuclear Plant JAN 1, 2003 - MAR 31, 2003 WIND WIND SPEED(MPH)

DIRECTION CALM 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4 >=24.5 TOTAL N 0.000 0.000 0.000 0.000 0.236 0.094 0.000 0.000 0.000 0.330 NNE 0.000 0.000 0.000 0.142 0.472 0.660 0.000 0.000 0.000 1.274 NE 0.000 0.000 0.047 0.189 0.330 0.330 0.000 0.000 0.000 0.896 ENE 0.000 0.000 0.000 0.047 0.000 0.000 0.000 0.000 0.000 0.047 E 0.000 0.000 0.047 0.094 0.000 0.000 0.000 0.000 0.000 0.142 ESE 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0 .000 0.000 SE 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0 .000 0.000 SSE 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 S 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 SSW 0.000 0.000 0.000 0.000 0.189 0.000 0.000 0.000 0.000 0.189 SW 0.000 0.000 0.000 0.000 0.189 0.094 0.000 0.000 0.000 0.283 WSW 0.000 0.000 0.000 0.000 0.047 0.000 0.000 0.000 0.000 0.047 W 0.000 0.000 0.000 0.047 0.142 0.000 0.000 0.000 0.000 0.189 WNW 0.000 0.000 0.000 0.047 0.142 0.000 0.000 0.000 0.000 0.189 NW 0.000 0.000 0.000 0.000 0.047 0.047 0.000 0.000 0.000 0.094 NNW 0.000 0.000 0.000 0.000 0.142 0.377 0.000 0.000 0.000 0.519 SUBTOTAL 0.000 0.000 0.094 0.566 1.934 1.604 0.000 0.000 0.000 4.198 TOTAL HOURS OF VALID STABILITY OBSERVATIONS 2134 TOTAL HOURS OF STABILITY CLASS A 89 TOTAL HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS A 89 TOTAL HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS 2120 TOTAL HOURS CALM 0 METEOROLOGICAL FACILITY: Sequoyah Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 9.25 AND 45.99 METERS WIND SPEED AND DIRECTION MEASURED AT 9.73 METER LEVEL DATE PRINTED: 2003/06/02 MEAN WIND SPEED = 6.99 NOTE: TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS A1-2

JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS B (-1.9< DELTA T<=-1.7 C/100 M)

Sequoyah Nuclear Plant JAN 1, 2003 - MAR 31, 2003 WIND WIND SPEED(MPH)

DIRECTION CALM 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4 >=24.5 TOTAL N 0.000 0.000 0.000 0.094 0.047 0.142 0.000 0.000 0.000 0.283 NNE 0.000 0.000 0.047 0.047 0.142 0.142 0.000 0.000 0.000 0.377 NE 0.000 0.000 0.142 0.189 0.094 0.047 0.000 0.000 0.000 0.472 ENE 0.000 0.000 0.094 0.000 0.000 0.000 0.000 0.000 0.000 0.094 E 0.000 0.000 0.047 0.094 0.000 0.000 0.000 0.000 0.000 0.142 ESE 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 SE 0.000 0.000 0.000 0.047 0.000 0.000 0.000 0.000 0.000 0.047 SSE 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 S 0.000 0.000 0.000 0.000 0.000 0.047 0.000 0.000 0.000 0.047 SSW 0.000 0.000 0.000 0.094 0.283 0.094 0.000 0.000 0.000 0.472 SW 0.000 0.000 0.000 0.000 0.142 0.000 0.000 0.000 0.000 0.142 WSW 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 W 0.000 0.000 0.000 0.047 0.000 0.047 0.000 0.000 0.000 0.094 WNW 0.000 0.000 0.000 0.000 0.094 0.047 0.000 0.000 0.000 0.142 NW 0.000 0.000 0.000 0.000 0.142 0.142 0.000 0.000 0.000 0.283 NNW 0.000 0.000 0.000 0.094 0.189 0.236 0.000 0.000 0.000 0.519 SUBTOTAL 0.000 0.000 0.330 0.708 1.132 0.943 0.000 0.000 0.000 3.113 TOTAL HOURS OF VALID STABILITY OBSERVATIONS 2134 TOTAL HOURS OF STABILITY CLASS B 66 TOTAL HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS B 66 TOTAL HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS 2120 TOTAL HOURS CALM 0 METEOROLOGICAL FACILITY: Sequoyah Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 9.25 AND 45.99 METERS WIND SPEED AND DIRECTION MEASURED AT 9.73 METER LEVEL DATE PRINTED: 2003/06/02 MEAN WIND SPEED = 6.35 NOTE: TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS Al -3

JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS C (-1.7< DELTA T<=-1.5 C/100 M)

Sequoyah Nuclear Plant JAN 1, 2003 - MAR 31, 2003 WIND WIND SPEED(MPH)

DIRECTION CALM 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4 >=24.5 TOTAL N 0.000 0.000 0.000 0.283 0.142 0.047 0.000 0.000 0.000 0.472 NNE 0.000 0.000 0.094 0.142 0.142 0.047 0.000 0.000 0.000 0.425 NE 0.000 0.000 0.236 0.236 0.047 0.000 0.000 0.000 0.000 0.519 ENE 0.000 0.000 0.094 0.047 0.000 0.000 0.000 0.000 0.000 0.142 E 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 ESE 0.000 0.000 0.000 0.094 0.000 0.000 0.000 0.000 0.000 0.094 SE 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 SSE 0.000 0.000 0.000 0.047 0.047 0.000 0.000 0.000 0.000 0.094 S 0.000 0.000 0.000 0.000 0.142 0.047 0.000 0.000 0.000 0.189 SSW 0.000 0.000 0.000 0.330 0.849 0.000 0.000 0.000 0.000 1.179 SW 0.000 0.000 0.000 0.047 0.189 0.000 0.000 0.000 0.000 0.236 WSW 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0 .000 0.000 W 0.000 0.000 0.000 0.047 0.094 0.047 0.000 0.000 0.000 0.189 WNW 0.000 0.000 0.000 0.047 0.000 0.047 0.000 0.000 0.000 0.094 NW 0.000 0.000 0.000 0.000 0.330 0.000 0.000 0.000 0.000 0.330 NNW 0.000 0.000 0.000 0.000 0.189 0.094 0.000 0.000 0.000 0.283 SUBTOTAL 0.000 0.000 0.425 1.321 2.170 0.330 0.000 0.000 0.000 4.245 TOTAL HOURS OF VALID STABILITY OBSERVATIONS 2134 TOTAL HOURS OF STABILITY CLASS C 91 TOTAL HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS C 90 TOTAL HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS 2120 TOTAL HOURS CALM 0 METEOROLOGICAL FACILITY: Sequoyah Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 9.25 AND 45.99 METERS WIND SPEED AND DIRECTION MEASURED AT 9.73 METER LEVEL DATE PRINTED: 2003/06/02 MEAN WIND SPEED = 5.66 NOTE: TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS A1 -4

JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS D (-1.5< DELTA T<=-0.5 C/100 M)

Sequoyah Nuclear Plant JAN 1, 2003 - MAR 31, 2003 WIND WIND SPEED(MPH)

DIRECTION CALM 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4 >=24.5 TOTAL N 0.000 0.047 1.557 0.849 1.698 1.085 0.000 0.000 0.000 5.236 NNE 0.000 0.047 1.745 2.877 2.170 1.509 0.000 0.000 0 .000 8.349 NE 0.000 0.094 0.566 0.330 0.236 0.142 0.000 0.000 0 .000 1.368 ENE 0.000 0.236 0.330 0.094 0.000 0.000 0.000 0.000 0.000 0.660 E 0.000 0.047 0.283 0.000 0.000 0.000 0.000 0.000 0.000 0.330 ESE 0.000 0.000 0.330 0.047 0.000 0.000 0.000 0.000 0.000 0.377 SE 0.000 0.047 0.236 0.000 0.000 0.000 0.000 0.000 0.000 0.283 SSE 0.000 0.000 0.283 0.236 0.047 0.047 0.000 0.000 0.000 0.613 S 0.000 0.189 0.849 1.132 0.613 0.330 0.000 0.000 0.000 3.113 SSW 0.000 0.000 2.075 4.292 1.415 0.566 0.000 0.000 0.000 8.349 SW 0.000 0.047 1.698 3.302 0.896 0.094 0.000 0.000 0.000 6.038 WSW 0.000 0.000 0.142 0.425 0.189 0.094 0.000 0.000 0.000 0.849 W 0.000 0.047 0.425 0.330 0.236 0.377 0.000 0.000 0.000 1.415 WNW 0.000 0.142 0.330 0.472 0.519 0.377 0.000 0.000 0.000 1.840 NW 0.000 0.047 0.519 1.226 1.462 0.519 0.000 0.000 0.000 3.774 NNW 0.000 0.000 0.472 0.519 1.462 1.085 0.000 0.000 0.000 3.538 SUBTOTAL 0.000 0.991 11.840 16.132 10.943 6.226 0.000 0.000 0.000 46.132 TOTAL HOURS OF VALID STABILITY OBSERVATIONS 2134 TOTAL HOURS OF STABILITY CLASS D 981 TOTAL HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS D 978 TOTAL HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS 2120 TOTAL HOURS CALM 0 METEOROLOGICAL FACILITY: Sequoyah Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 9.25 AND 45.99 METERS WIND SPEED AND DIRECTION MEASURED AT 9.73 METER LEVEL DATE PRINTED: 2003/06/02 MEAN WIND SPEED = 4.93 NOTE: TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS A1 -5

JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS E (-0.5< DELTA T<= 1.5 C/100 M)

Sequoyah Nuclear Plant JAN 1, 2003 - MAR 31, 2003 WIND WIND SPEED(MPH)

DIRECTION CALM 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4 >=24.5 TOTAL N 0.000 0.142 1.981 1.604 1.038 0.142 0.000 0 .000 0 .000 4.906 NNE 0.000 0.472 2.689 1.179 0.472 0.094 0.000 0.000 0 .000 4.906 NE 0.000 0.236 0.330 0.047 0.000 0.000 0.000 0.000 0 .000 0.613 ENE 0.000 0.094 0.142 0.047 0.000 0.000 0.000 0.000 0.000 0.283 E 0.000 0.142 0.047 0.000 0.000 0.000 0.000 0.000 0.000 0.189 ESE 0.000 0.000 0.094 0.000 0.000 0.000 0.000 0.000 0 .000 0.094 SE 0.000 0.189 0.094 0.000 0.000 0.000 0.000 0.000 0 .000 0.283 SSE 0.000 0.330 0.425 0.094 0.094 0.000 0.000 0.000 0.000 0.943 S 0.000 0.189 0 .849 0.755 0.425 0.142 0.000 0.000 0.000 2.358 SSW 0.000 0.377 2.547 1.321 0.802 0.236 0.047 0.000 0.000 5.330 SW 0.000 0.236 2.311 1.745 0.519 0.142 0.047 0.000 0.000 5.000 WSW 0.000 0.142 0.566 0.142 0.000 0.000 0.000 0.000 0.000 0.849 W 0.000 0.189 0.236 0.000 0.000 0.000 0.000 0.000 0.000 0.425 WNW 0.000 0.047 0.330 0.142 0.047 0.000 0.000 0.000 0.000 0.566 NW 0.000 0.189 0. 425 0.189 0.047 0.000 0.000 0.000 0.000 0.849 NNW 0.000 0.189 1.132 0.802 0.283 0.142 0.000 0.000 0.000 2.547 SUBTOTAL 0.000 3.160 14.198 8.066 3.726 0.896 0.094 0.000 0.000 30.142 TOTAL HOURS OF VALID STABILITY OBSERVATIONS 2134 TOTAL HOURS OF STABILITY CLASS E 647 TOTAL HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS E 639 TOTAL HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS 2120 TOTAL HOURS CALM 0 METEOROLOGICAL FACILITY: Sequoyah Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 9.25 AND 45.99 METERS WIND SPEED AND DIRECTION MEASURED AT 9.73 METER LEVEL DATE PRINTED: 2003/06/02 MEAN WIND SPEED = 3.49 NOTE: TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS Al -6

JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS F ( 1.5< DELTA T<= 4.0 C/100 M)

Sequoyah Nuclear Plant JAN 1, 2003 - NAR 31, 2003 WIND WIND SPEED(MPH)

DIRECTION CALM 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4 >=24.5 TOTAL N 0.000 0.000 0.425 0.047 0.000 0.000 0.000 0.000 0.000 0.472 NNE 0.000 0.142 1.226 0.000 0.000 0.000 0.000 0.000 0.000 1.368 NE 0.000 0.142 0.330 0.000 0.000 0.000 0.000 0.000 0.000 0.472 ENE 0.000 0.142 0.189 0.000 0.000 0.000 0.000 0.000 0.000 0.330 E 0.000 0.142 0.094 0.000 0.000 0.000 0.000 0.000 0.000 0.236 ESE 0.000 0.047 0.094 0.000 0.000 0.000 0.000 0.000 0.000 0.142 SE 0.000 0.142 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.142 SSE 0.000 0.236 0.189 0.000 0.000 0.000 0.000 0.000 0.000 0.425 S 0.000 0.283 0.330 0.000 0.000 0.000 0.000 0.000 0.000 0.613 SSW 0.000 0.189 0.849 0.142 0.000 0.000 0.000 0.000 0.000 1.179 SW 0.000 0.000 1.274 0.189 0.000 0.000 0.000 0.000 0.000 1.462 WSW 0.000 0.047 0.236 0.000 0.000 0.000 0.000 0.000 0.000 0.283 W 0.000 0.000 0.047 0.000 0.000 0.000 0.000 0.000 0.000 0.047 WNW 0.000 0.000 0.000 0.047 0.000 0.000 0.000 0.000 0.000 0.047 NW 0.000 0.047 0.283 0.000 0.000 0.000 0.000 0.000 0.000 0.330 NNW 0.000 0.000 0.236 0.047 0.000 0.000 0.000 0.000 0.000 0.283 SUBTOTAL 0.000 1.557 5.802 0.472 0.000 0.000 0.000 0.000 0.000 7.830 TOTAL HOURS OF VALID STABILITY OBSERVATIONS 2134 TOTAL HOURS OF STABILITY CLASS F 168 TOTAL HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS F 166 TOTAL HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS 2120 TOTAL HOURS CALM 0 METEOROLOGICAL FACILITY: Sequoyah Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 9.25 AND 45.99 METERS WIND SPEED AND DIRECTION MEASURED AT 9.73 METER LEVEL DATE PRINTED: 2003/06/02 MEAN WIND SPEED = 2.14 NOTE: TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS A1 -7

JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS G (DELTA T > 4.0 C/100 M)

Sequoyah Nuclear Plant JAN 1, 2003 - MAR 31, 2003 WIND WIND SPEED(MPH)

DIRECTION CALM 0.6-1.4 1 .5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4 >=24 .5 TOTAL N 0.000 0.000 0.142 0.000 0.000 0.000 0.000 0 .000 0.000 0.142 NNE 0 . 000 0.142 0. 660 0.000 0.000 0.000 0.000 0.000 0 .000 0.802 NE 0.000 0.236 0.377 0.000 0.000 0.000 0.000 0.000 0 .000 0.613 ENE 0.000 0.283 0.283 0.000 0.000 0.000 0.000 0.000 0.000 0.566 E 0.000 0.142 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.142 ESE 0.000 0.189 0.000 0.000 0.000 0 .000 0.000 0.000 0.000 0.189 SE 0 .000 0.094 0.094 0.000 0.000 0.000 0.000 0 . 000 0.000 0.189 SSE 0 .000 0.142 0.094 0.000 0.000 0.000 0.000 0.000 0.000 0.236 S 0.000 0.236 0.142 0.000 0.000 0.000 0.000 0.000 0.000 0.377 SSW 0.000 0.142 0.425 0.000 0.000 0.000 0 .000 0.000 0.000 0.566 SW 0.000 0.000 0.283 0.047 0.000 0.000 0.000 0.000 0.000 0.330 WSW 0.000 0.047 0.047 0.000 0.000 0.000 0.000 0.000 0.000 0.094 W 0.000 0.000 0.047 0.000 0.000 0.000 0.000 0.000 0 .000 0.047 WNW 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 NW 0.000 0.000 0.047 0.000 0.000 0.000 0.000 0.000 0 .000 0.047 NNW 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0 .000 SUBTOTAL 0.000 1.651 2.642 0.047 0.000 0 .000 0.000 0.000 0.000 4.340 TOTAL HOURS OF VALID STABILITY OBSERVATIONS 2134 TOTAL HOURS OF STABILITY CLASS G 92 TOTAL HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS G 92 TOTAL HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS 2120 TOTAL HOURS CALM METEOROLOGICAL FACILITY: Sequoyah Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 9.25 AND 45.99 METERS WIND SPEED AND DIRECTION MEASURED AT 9.73 METER LEVEL DATE PRINTED: 2003/06/02 MEAN WIND SPEED = 1.72 NOTE: TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS A1-8

JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS A (DELTA T<=-1.9 C/100 M)

Sequoyah Nuclear Plant APR 1, 2003 - JUN 30, 2003 WIND WIND SPEED(MPH)

DIRECTION CALM 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4 >=24.5 TOTAL N 0.000 0.000 0.000 0.240 0.431 0.096 0.000 0.000 0.000 0.767 NNE 0.000 0.000 0.192 1.294 1.533 0.096 0.000 0.000 0.000 3.115 NE 0.000 0.000 0.431 0.623 0.192 0.096 0.000 0.000 0.000 1.342 ENE 0.000 0.000 0.096 0.144 0.000 0.000 0.000 0.000 0.000 0.240 E 0.000 0.000 0.048 0.096 0.000 0.000 0.000 0.000 0.000 0.144 ESE 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 SE 0.000 0.000 0.000 0.048 0.000 0.000 0.000 0.000 0.000 0.048 SSE 0.000 0.000 0.000 0.000 0.000 0.048 0.000 0.000 0.000 0.048 S 0.000 0.000 0.048 0.000 0.000 0.048 0.000 0.000 0.000 0.096 SSW 0.000 0.000 0.048 0.527 0.575 0.671 0.000 0.000 0.000 1.821 SW 0.000 0.000 0.048 0.431 0.287 0.000 0.000 0.000 0.000 0.767 WSW 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 W 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 WNW 0.000 0.000 0.000 0.000 0.144 0.096 0.000 0.000 0.000 0.240 NW 0.000 0.000 0.000 0.048 0.048 0.000 0.000 0.000 0.000 0.096 NNW 0.000 0.000 0.000 0.000 0.144 0.096 0.000 0.000 0.000 0.240 SUBTOTAL 0.000 0.000 0.910 3.450 3.354 1.246 0.000 0.000 0.000 8.960 TOTAL HOURS OF VALID STABILITY OBSERVATIONS 2090 TOTAL HOURS OF STABILITY CLASS A 187 TOTAL HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS A 187 TOTAL HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS 2087 TOTAL HOURS CALM 0 METEOROLOGICAL FACILITY: Sequoyah Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 9.25 AND 45.99 METERS WIND SPEED AND DIRECTION MEASURED AT 9.73 METER LEVEL DATE PRINTED: 2003/08/18 MEAN WIND SPEED = 5.57 NOTE: TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS A1 -9

JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS B (-1.9< DELTA T<=-1.7 C/100 M)

Sequoyah Nuclear Plant APR 1, 2003 - JUN 30, 2003 WIND WIND SPEED(MPH)

DIRECTION CALM 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4 >=24.5 TOTAL N 0 .000 0.000 0.048 0.144 0.144 0.048 0.000 0.000 0.000 0.383 NNE 0.000 0.000 0.048 0.335 0.144 0.048 0.000 0.000 0 .000 0.575 NE 0.000 0.000 0.144 0.144 0.048 0.000 0.000 0.000 0 .000 0.335 ENE 0.000 0.000 0.096 0.096 0 .000 0.000 0.000 0.000 0.000 0.192 E 0.000 0.000 0.096 0.048 0 .000 0.000 0.000 0.000 0.000 0.144 ESE 0.000 0.000 0.048 0.096 0 .000 0.000 0.000 0.000 0 .000 0.144 SE 0.000 0.000 0.048 0.048 0.000 0.048 0.000 0.000 0 .000 0.144 SSE 0.000 0.000 0.000 0.000 0.048 0.048 0.000 0.000 0 .000 0.096 S 0.000 0.000 0.000 0.096 0.000 0.048 0.000 0.000 0.000 0.144 SSW 0.000 0.000 0.000 0.575 0.479 0 .048 0.000 0.000 0 .000 1.102 SW 0.000 0.000 0.096 0.767 0.096 0 .000 0.000 0.000 0 .000 0.958 WSW 0.000 0.000 0.000 0.048 0.000 0 . 000 0.000 0.000 0.000 0.048 W 0 . 000 0.000 0.000 0.048 0.000 0.000 0.000 0.000 0.000 0.048 WNW 0.000 0.000 0 .000 0.000 0.000 0.096 0.000 0.000 0.000 0.096 NW 0.000 0.000 0 .000 0.144 0.096 0.096 0.000 0.000 0.000 0.335 NNW 0.000 0.000 0 .000 0.048 0.048 0.000 0.000 0.000 0.000 0.096 SUBTOTAL 0.000 0.000 0.623 2.635 1.102 0.479 0.000 0.000 0.000 4.839 TOTAL HOURS OF VALID STABILITY OBSERVATIONS 2090 TOTAL HOURS OF STABILITY CLASS B 101 TOTAL HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS B 101 TOTAL HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS 2087 TOTAL HOURS CALM METEOROLOGICAL FACILITY: Sequoyah Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 9.25 AND 45.99 METERS WIND SPEED AND DIRECTION MEASURED AT 9.73 METER LEVEL DATE PRINTED: 2003/08/18 MEAN WIND SPEED = 4.96 NOTE: TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS Al-10

JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS C (-1.7< DELTA T<=-1.5 C/100 M)

Sequoyah Nuclear Plant APR 1, 2003 - JUN 30, 2003 WIND WIND SPEED(MPH)

DIRECTION CALM 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4 >=24.5 TOTAL N 0 .000 0 . 000 0.000 0.048 0.144 0.000 0.000 0.000 0.000 0.192 NNE 0 .000 0.000 0.192 0.335 0.048 0.000 0.000 0.000 0.000 0.575 NE 0.000 0.000 0.192 0.240 0.000 0 .000 0.000 0.000 0.000 0.431 ENE 0.000 0.000 0.144 0.000 0.000 0.000 0.000 0.000 0.000 0.144 E 0 .000 0.000 0.048 0.000 0.000 0.000 0.000 0.000 0.000 0.048 ESE 0 .000 0.000 0.048 0.048 0.000 0.000 0 .000 0.000 0.000 0.096 SE 0 .000 0.000 0 .000 0.048 0.000 0.000 0 .000 0.000 0.000 0.048 SSE 0.000 0.000 0.000 0.096 0.000 0.000 0.000 0.000 0.000 0.096 S 0.000 0 .000 0.144 0.383 0.000 0.048 0 .000 0.000 0 . 000 0.575 SSW 0.000 0 .000 0.240 1 .342 0.240 0.000 0 .000 0.000 0.000 1.821 SW 0.000 0 .000 0.335 0.383 0.096 0.000 0.000 0 .000 0.000 0.815 WSW 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 W 0 .000 0.000 0.000 0.096 0.000 0.000 0.000 0 .000 0.000 0.096 WNW 0.000 0.000 0.000 0.000 0.048 0.048 0.000 0.000 0.000 0.096 NW 0.000 0.000 0.000 0.144 0.000 0.144 0.000 0.000 0.000 0.287 NNW 0.000 0.000 0 .000 0 .000 0.048 0.096 0.000 0.000 0 .000 0.144 SUBTOTAL 0.000 0.000 1.342 3.162 0.623 0.335 0.000 0.000 0.000 5.462 TOTAL HOURS OF VALID STABILITY OBSERVATIONS 2090 TOTAL HOURS OF STABILITY CLASS C 114 TOTAL HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS C 114 TOTAL HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS 2087 TOTAL HOURS CALM 0 METEOROLOGICAL FACILITY: Sequoyah Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 9.25 AND 45.99 METERS WIND SPEED AND DIRECTION MEASURED AT 9.73 METER LEVEL DATE PRINTED: 2003/08/18 MEAN WIND SPEED = 4.48 NOTE: TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS Al-11

JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS D (-1.5< DELTA T<=-0.5 C/100 M)

Sequoyah Nuclear Plant APR 1, 2003 - JUN 30, 2003 WIND WIND SPEED(MPH)

DIRECTION CALM 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4 >=24.5 TOTAL N 0.000 0.096 1.054 0.671 0.335 0.000 0.000 0.000 0.000 2.156 NNE 0.000 0.144 1.054 0.958 0.383 0.096 0.000 0.000 0.000 2.635 NE 0.000 0.048 0.671 0.383 0.000 0.000 0.000 0.000 0.000 1.102 ENE 0.000 0.096 0.575 0.000 0.000 0.000 0.000 0.000 0.000 0.671 E 0.000 0.048 0.096 0.096 0.000 0.000 0.000 0.000 0.000 0.240 ESE 0.000 0.048 0.240 0.000 0.000 0.000 0 .000 0.000 0.000 0.287 SE 0.000 0.096 0.623 0.096 0.000 0.048 0.000 0.000 0.000 0.862 SSE 0.000 0.048 0.862 0.383 0.287 0.192 0 .000 0.000 0.000 1.773 s 0.000 0.144 2.827 2.971 0.719 0.240 0.096 0.000 0.000 6.996 SSW 0.000 0.144 3.594 5.367 0.910 0.192 0.000 0.000 0.000 10.206 SW 0.000 0.096 1.390 1.485 0.527 0.096 0.000 0.000 0.000 3.594 WSW 0.000 0.096 0.335 0.335 0.096 0.000 0.000 0.000 0.000 0.862 W 0.000 0.096 0.096 0.192 0.144 0.000 0.000 0.000 0.000 0.527 WNW 0.000 0.048 0.048 0.096 0.096 0.000 0.000 0.000 0.000 0.287 NW 0.000 0.000 0.192 0.383 0.144 0.144 0.000 0.000 0.000 0.862 NNW 0.000 0.000 0.575 0.767 0.287 0.192 0.000 0.000 0.000 1.821 SUBTOTAL 0.000 1.246 14.231 14.183 3.929 1.198 0.096 0.000 0.000 34.883 TOTAL HOURS OF VALID STABILITY OBSERVATIONS 2090 TOTAL HOURS OF STABILITY CLASS D 729 TOTAL HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS D 728 TOTAL HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS 2087 TOTAL HOURS CALM 0 METEOROLOGICAL FACILITY: Sequoyah Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 9.25 AND 45.99 METERS WIND SPEED AND DIRECTION MEASURED AT 9.73 METER LEVEL DATE PRINTED: 2003/08/18 MEAN WIND SPEED = 3.87 NOTE: TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS A1-12

JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS E (-0.5< DELTA T<= 1.5 C/100 M)

Sequoyah Nuclear Plant APR 1, 2003 - JUN 30, 2003 WIND WIND SPEED (MPH)

DIRECTION CALM 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4 >=24.5 TOTAL N 0.000 0.240 2.779 1.054 0.192 0.000 a .000 0 .000 0 .000 4.264 NNE 0.000 0.240 2.731 1.150 0.096 0.000 0 .000 0.000 0.000 4.217 NE 0,000 0.096 0.671 0.048 0.048 0.000 0 .000 0.000 0.000 0.862 ENE 0.000 0.000 0.192 0.048 0.000 0.000 0.000 0.000 0.000 0.240 E 0.000 0.144 0.096 0.000 0.000 0.000 0.000 0.000 0 .000 0.240 ESE 0.000 0.287 0.144 0.000 0.000 0.000 0.000 0 .000 0.000 0.431 SE 0.000 0.144 0.096 0.096 0.000 0.000 0.000 0.000 0.000 0.335 SSE 0.000 0.144 0.671 0.192 0.144 0.000 0.000 0.000 0 .000 1 .150 S 0.000 0.383 1.677 0.671 0.144 0.048 0.000 0.000 0 .000 2.923 SSW 0.000 0.431 3.402 1.246 0.144 0.048 0.000 0.000 0 .000 5.271 SW 0.000 0.287 2.683 0.719 0.240 0.048 0.000 0.000 0.000 3.977 WSW 0.000 0.335 0.719 0.144 0.144 0.000 0.000 0.000 0.000 1.342 W 0.000 0.096 0.192 0.240 0.048 0.000 0.000 0.000 0.000 0.575 WNW 0.000 0.335 0.527 0.287 0.048 0 .000 0.000 0.000 0.000 1.198 NW 0.000 0.000 0.431 0.335 0.096 0.096 0.000 0.000 0.000 0.958 NNW 0.000 0.671 1.102 0.479 0.240 0 .000 0.000 0.000 0.000 2.492 SUBTOTAL 0.000 3.833 18.112 6.708 1.581 0.240 0.000 0.000 0.000 30.474 TOTAL HOURS OF VALID STABILITY OBSERVATIONS 2090 TOTAL HOURS OF STABILITY CLASS E 638 TOTAL HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS E 636 TOTAL HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS 2087 TOTAL HOURS CALM 0 METEOROLOGICAL FACILITY: Sequoyah Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 9.25 AND 45.99 METERS WIND SPEED AND DIRECTION MEASURED AT 9.73 METER LEVEL DATE PRINTED: 2003/08/18 MEAN WIND SPEED = 2.86 NOTE: TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS A1-13

JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS F 1 1.5< DELTA T<= 4.0 C/100 M)

Sequoyah Nuclear Plant APR 1, 2003 - JUN 30, 2003 WIND WIND SPEED(MPH)

DIRECTION CALM 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4 >=24.5 TOTAL N 0.000 0.048 1.581 0.144 0.000 0.000 0.000 0.000 0.000 1.773 NNE 0.000 0.527 2.779 0.048 0.000 0.000 0.000 0.000 0.000 3.354 NE 0.000 0.335 0.287 0.000 0.000 0.000 0.000 0.000 0.000 0. 623 ENE 0.000 0.096 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.096 E 0.000 0.048 0.144 0.000 0.000 0.000 0.000 0 .000 0.000 0.192 ESE 0.000 0.144 0.048 0.000 0.000 0.000 0.000 0 .000 0.000 0.192 SE 0.000 0.192 0.192 0.000 0.000 0.000 0.000 0.000 0.000 0.383 SSE 0.000 0.144 0.048 0.000 0.000 0.000 0.000 0.000 0 .000 0.192 S 0.000 0.144 0.144 0.000 0.000 0 .000 0.000 0.000 0 .000 0.287 SSW 0.000 0.048 1.054 0.000 0.000 0.000 0.000 0.000 0 .000 1.102 SW 0.000 0.192 0.719 0.048 0.000 0.000 0.000 0.000 0.000 0.958 WSW 0.000 0.096 0.479 0.000 0.000 0.000 0.000 0.000 0.000 0.575 W 0.000 0.096 0.096 0.048 0.000 0.000 0.000 0.000 0.000 0.240 WNW 0.000 0.000 0.096 0.048 0.000 0.000 0.000 0 .000 0.000 0.144 NW 0.000 0.000 0.192 0.000 0.000 0 .000 0.000 0.000 0.000 0.192 NNW 0.000 0.000 0.479 0.192 0.000 0 .000 0.000 0.000 0.000 0.671 SUBTOTAL 0-000 2.108 8.337 0.527 0.000 0.000 0.000 0.000 0.000 10.973 TOTAL HOURS OF VALID STABILITY OBSERVATIONS 2090 TOTAL HOURS OF STABILITY CLASS F 229 TOTAL HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS F 229 TOTAL HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS 2087 TOTAL HOURS CALM 0 METEOROLOGICAL FACILITY: Sequoyah Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 9.25 AND 45.99 METERS WIND SPEED AND DIRECTION MEASURED AT 9.73 METER LEVEL DATE PRINTED: 2003/08/18 MEAN WIND SPEED = 2.10 NOTE: TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS A1-14

JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS G (DELTA T > 4.0 C/100 M)

Sequoyah Nuclear Plant APR 1, 2003 - JUN 30, 2003 W IND WIND SPEED(MPH)

DIR ECTION CALM 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12. 4 12.5-18.4 18.5-24.4 >=24 .5 TOTAL N 0.000 0.048 0.000 0.000 0.000 0.00C 0 .000 0.000 0.000 0.048 NNE 0.000 0.192 0.431 0.000 0.000 0.00C 0.000 0.000 0.000 0. 623 NE 0.000 0.144 0.479 0.000 0.000 0.00C 0.000 0.000 0.000 0.623 ENE 0.000 0.240 0.048 0.000 0.000 0.00C 0.000 0.000 0.000 0.287 E 0.000 0.240 0.000 0.000 0.000 0.00C 0.000 0.000 0.000 0.240 ESE 0.000 0.192 0.000 0.000 0.000 0.00C 0.000 0 .000 0.000 0.192 SE 0.000 0.240 0.096 0.000 0.000 0.00C 0.000 0 .000 0.000 0.335 SSE 0.000 0.335 0.048 0.000 0.000 0.00C 0.000 0 .000 0.000 0.383 S 0.000 0.335 0.192 0.000 0.000 0.00C 0.000 0 .000 0.000 0. 527 SSW 0.000 0.096 0.431 0.000 0.000 0.00C 0.000 0.000 0.000 0.527 SW 0.000 0.000 0.527 0.000 0.000 0.00C 0.000 0.000 0.000 0.527 WSW 0.000 0.000 0.000 0.000 0.000 0.00C 0.000 0.000 0.000 0.000 W 0.000 0.000 0.000 0.000 0.000 0.00C 0.000 0.000 0 .000 0.000 WNW 0.000 0.000 0.000 0.000 0.000 0.00CI 0.000 0.000 0 .000 0.000 NW 0.000 0.000 0.048 0.000 0.000 0.00CI 0.000 0.000 0 .000 0.048 NNW 0.000 0.000 0.048 0.000 0.000 0.00C I 0.000 0.000 0 .000 0.048 SUB'TOTAL 0.000 2.060 2.348 0.000 0.000 0.00C I 0.000 0.000 0.000 4.408 TOTAL HOURS OF VALID STABILITY OBSERVATIONS 2090 TOTAL HOURS OF STABILITY CLASS G 92 TOTAL HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS G 92 TOTAL HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS 2087 TOTAL HOURS CALM METEOROLOGICAL FACILITY: Sequoyah Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 9.25 AND 45.99 METERS WIND SPEED AND DIRECTION MEASURED AT 9.73 METER LEVEL DATE PRINTED: 2003/08/18 MEAN WIND SPEED = 1.65 NOTE: TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS Al-15

JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS A (DELTA T<=-1.9 C/100 M)

Sequoyah Nuclear Plant JUL 1, 2003 - SEP 30, 2003 WIND WIND SPEED(MPH)

DIRECTION CALM 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4 =24.5 TOTAL N 0 .000 0.000 0.046 0.463 0.324 0.000 0.000 0.000 0.000 0.833 NNE 0 .000 0.000 0.463 1.481 0.648 0.185 0.000 0.000 0.000 2.776 NE 0 .000 0.000 0.602 1.018 0.000 0.000 0.000 0.000 0.000 1.620 ENE 0 .000 0.000 0.093 0.046 0.000 0.000 0.000 0.000 0.000 0.139 E 0 .000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 ESE 0.000 0.000 0.046 0.000 0.000 0.000 0.000 0.000 0.000 0.046 SE 0 .000 0.000 0.000 0.046 0.000 0.000 0.000 0.000 0.000 0.046 SSE 0 .000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0 .000 0.000 S 0 .000 0.000 0.000 0.185 0.046 0.000 0.000 0.000 0.000 0.231 SSW 0 .000 0.000 0.093 0.740 0.463 0.000 0.000 0.000 0.000 1.296 SW 0 .000 0.000 0.046 0.740 0.000 0.000 0.000 0.000 0 . 000 0.787 WSW 0 .000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 W 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 WNW 0 .000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0 .000 0.000 NW 0 .000 0.000 0.000 0.000 0.093 0.000 0.000 0.000 0 .000 0.093 NNW 0 .000 0.000 0.000 0.046 0.000 0.000 0.000 0.000 0.000 0.046 SUBTOTAL 0.000 0.000 1.388 4.766 1.573 0.185 0.000 0.000 0.000 7.913 TOTAL HOURS OF VALID STABILITY OBSERVATIONS 2181 TOTAL HOURS OF STABILITY CLASS A 171 TOTAL HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS A 171 TOTAL HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS 2161 TOTAL HOURS CALM 0 METEOROLOGICAL FACILITY: Sequoyah Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 9.25 AND 45.99 METERS WIND SPEED AND DIRECTION MEASURED AT 9.73 METER LEVEL DATE PRINTED: 2003/12/08 MEAN WIND SPEED = 4.50 NOTE: TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS A1-16

JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS B (-1.9< DELTA T<=-1.7 C/100 M)

Sequoyah Nuclear Plant JUL 1, 2003 - SEP 30, 2003 WIND WIND SPEED(MPH)

DIRECTION CALM 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4 >=24.5 TOTAL N 0.000 0.000 0.093 0.139 0.093 0.000 0.000 0 .000 0.000 0. 324 NNE 0.000 0.000 0.602 0.370 0.046 0.046 0.000 0 .000 0.000 1. 064 NE 0.000 0.000 0.416 0.139 0.000 0.000 0.000 0 .000 0.000 0.555 ENE 0.000 0.000 0.093 0.046 0.000 0.000 0.000 0.000 0.000 0.139 E 0.000 0.000 0.046 0.046 0.000 0.000 0.000 0.000 0.000 0.093 ESE 0.000 0.000 0.046 0.000 0.000 0.000 0.000 0.000 0 .000 0.046 SE 0.000 0.000 0.046 0.046 0.000 0.000 0.000 0.000 0 .000 0.093 SSE 0.000 0.000 0.139 0.093 0.000 0.046 0.000 0 .000 0.000 0.278 S 0.000 0.000 0.000 0.416 0.093 0.000 0.000 0.000 0.000 0.509 SSW 0.000 0.000 0.324 1.203 0.046 0.000 0.000 0.000 0.000 1.573 SW 0.000 0.000 0.324 0.648 0.093 0.000 0.000 0.000 0 .000 1.064 WSW 0.000 0.000 0.046 0.093 0.000 0.000 0.000 0.000 0 .000 0.139 W 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0 .000 0.000 WNW 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0 .000 0 .000 NW 0.000 0.000 0.000 0.093 0.046 0.046 0.000 0.000 0.000 0.185 NNW 0.000 0.000 0.046 0.000 0.046 0.000 0 .000 0.000 0.000 0.093 SUBTOTAL 0.000 0.000 2.221 3.332 0.463 0.139 0.000 0 .000 0.000 6.155 TOTAL HOURS OF VALID STABILITY OBSERVATIONS 2181 TOTAL HOURS OF STABILITY CLASS B 133 TOTAL HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS B 133 TOTAL HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS 2161 TOTAL HOURS CALM 0 METEOROLOGICAL FACILITY: Sequoyah Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 9.25 AND 45.99 METERS WIND SPEED AND DIRECTION MEASURED AT 9.73 METER LEVEL DATE PRINTED: 2003/12/08 MEAN WIND SPEED = 4.05 NOTE: TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS A1-17

JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS C (-1.7< DELTA T<=-1.5 C/100 M)

Sequoyah Nuclear Plant JUL 1, 2003 - SEP 30, 2003 WIND WIND SPEED(MPH)

DIRECTION CALM 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4 >=24.5 TOTAL N 0.000 0.000 0.185 0.231 0.093 0.000 0.000 0.000 0.000 0.509 NNE 0.000 0.000 0.370 0.463 0.000 0.000 0.000 0.000 0.000 0.833 NE 0.000 0.000 0.370 0.046 0.000 0.000 0.000 0.000 0.000 0.416 ENE 0.000 0.000 0.231 0.046 0.000 0.000 0.000 0.000 0.000 0.278 E 0.000 0.000 0.139 0.000 0.000 0.000 0.000 0.000 0.000 0.139 ESE 0.000 0.000 0.370 0.000 0.000 0.000 0.000 0.000 0.000 0.370 SE 0.000 0.000 0.185 0.000 0.000 0.000 0.000 0.000 0.000 0.185 SSE 0.000 0.000 0.185 0.093 0.000 0.000 0.000 0.000 0.000 0.278 S 0.000 0.000 0.278 0.833 0.000 0.000 0.000 0.000 0.000 1.111 SSW 0.000 0.000 1.203 1.342 0.093 0.000 0.000 0.000 0.000 2.638 SW 0.000 0.000 0.324 0.694 0.000 0.000 0.000 0.000 0.000 1.018 WSW 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 W 0.000 0.000 0.046 0.000 0.000 0.000 0.000 0.000 0.000 0.046 WNW 0.000 0.000 0.046 0.046 0.000 0.000 0.000 0.000 0.000 0.093 NW 0.000 0.000 0.000 0.046 0.093 0.000 0.000 0.000 0.000 0.139 NNW 0.000 0.000 0.000 0.093 0.000 0.000 0.000 0.000 0.000 0.093 SUBTOTAL 0.000 0.000 3.933 3.933 0.278 0.000 0.000 0.000 0.000 8.144 TOTAL HOURS OF VALID STABILITY OBSERVATIONS 2181 TOTAL HOURS OF STABILITY CLASS C 176 TOTAL HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS C 176 TOTAL HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS 2161 TOTAL HOURS CALM 0 METEOROLOGICAL FACILITY: Sequoyah Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 9.25 AND 45.99 METERS WIND SPEED AND DIRECTION MEASURED AT 9.73 METER LEVEL DATE PRINTED: 2003/12/08 MEAN WIND SPEED = 3.55 NOTE: TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS Al-18

JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS D (-1.5< DELTA T<=-0.5 C/100 M)

Sequoyah Nuclear Plant JUL 1, 2003 - SEP 30, 2003 WIND WIND SPEED(MPH)

DIRECTION CALM 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4 >=24.5 TOTAL N 0.000 0.093 1.203 0.370 0.231 0.000 0.000 0.000 0 .000 1.897 NNE 0.000 0.046 1.296 0.879 0.370 0.093 0.000 0.000 0 .000 2.684 NE 0.000 0.046 0.416 0.463 0.139 0.046 0.000 0.000 0 .000 1.111 ENE 0.000 0.000 0.278 0.093 0.000 0.000 0.000 0.000 0 .000 0.370 E 0.000 0.046 0.278 0.139 0.000 0.000 0.000 0.000 0 .000 0.463 ESE 0.000 0.000 0.093 0.093 0.000 0.000 0.000 0.000 0 .000 0.185 SE 0.000 0.046 0.602 0.093 0.046 0.000 0.000 0.000 0 .000 0.787 SSE 0.000 0.139 1.481 0.139 0.000 0.139 0.000 0.000 0 .000 1.897 S 0.000 0.139 3.193 1.666 0.185 0.046 0.000 0.000 0 .000 5.229 SSW 0.000 0.093 4.396 2.453 0.046 0.000 0.000 0.000 0.000 6.988 SW 0.000 0.093 1.064 0.555 0.231 0.000 0.000 0.000 0 .000 1.944 WSW 0.000 0.093 0.093 0.139 0.093 0.000 0 .000 0.000 0 .000 0.416 W 0.000 0.093 0.046 0.093 0.093 0.000 0.000 0.000 0.000 0.324 WNW 0.000 0.139 0.046 0.046 0.000 0.046 0 .000 0.000 0.000 0.278 NW 0.000 0.046 0.278 0.139 0.046 0.000 0.000 0.000 0.000 0 .509 NNW 0.000 0.093 0.463 0.463 0.231 0.000 0 .000 0.000 0.000 1.249 SUBTOTAL 0.000 1.203 15.224 7.820 1.712 0.370 0 .000 0.000 0.000 26.330 TOTAL HOURS OF VALID STABILITY OBSERVATIONS 2181 TOTAL HOURS OF STABILITY CLASS D 576 TOTAL HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS D 569 TOTAL HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS 2161 TOTAL HOURS CALM 0 METEOROLOGICAL FACILITY: Sequoyah Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 9.25 AND 45.99 METERS WIND SPEED AND DIRECTION MEASURED AT 9.73 METER LEVEL DATE PRINTED: 2003/12/08 MEAN WIND SPEED = 3.37 NOTE: TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS Al-19

JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS E (-0.5< DELTA T<= 1.5 C/100 M)

Sequoyah Nuclear Plant JUL 1, 2003 - SEP 30, 2003 WIND WIND SPEED(MPH)

DIRECTION CALM 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4 >=24.5 TOTAL N 0.000 0.787 5.044 0.787 0.046 0.000 0.000 0.000 0.000 6.664 NNE 0.000 1.111 3.609 0.509 0.046 0.000 0.000 0.000 0.000 5.275 NE 0.000 0.555 0.602 0.046 0.000 0.000 0.000 0.000 0.000 1.203 ENE 0.000 0.278 0.139 0.046 0.000 0.000 0.000 0.000 0.000 0.463 E 0.000 0.093 0.231 0.000 0.000 0.000 0.000 0.000 0.000 0.324 ESE 0.000 0.093 0.231 0.000 0.000 0.000 0.000 0.000 0.000 0.324 SE 0.000 0.231 0.509 0.000 0.000 0.000 0.000 0.000 0.000 0.740 SSE 0.000 0.416 0.925 0.185 0.046 0.000 0.000 0.000 0.000 1.573 S 0.000 0.740 3.054 0.370 0.000 0.000 0.000 0.000 0.000 4.165 SSW 0.000 0.416 3.841 0.324 0.000 0.000 0.000 0.000 0.000 4.581 SW 0.000 0.463 3.239 0.463 0.000 0.000 0.000 0.000 0.000 4.165 WSW 0.000 0.416 1.249 0.093 0.000 0.000 0.000 0.000 0.000 1.758 W 0.000 0.509 0.463 0.000 0.000 0.000 0.000 0.000 0.000 0.972 WNW 0.000 0.694 0.555 0.000 0.046 0.000 0.000 0.000 0.000 1.296 NW 0.000 0.416 0.694 0.093 0.093 0.000 0.000 0.000 0.000 1.296 NNW 0.000 0.278 2.314 0.278 0.093 0.000 0.000 0.000 0.000 2.962 SUBTOTAL 0.000 7.497 26.701 3.193 0.370 0.000 0.000 0.000 0.000 37.760 TOTAL HOURS OF VALID STABILITY OBSERVATIONS 2181 TOTAL HOURS OF STABILITY CLASS E 827 TOTAL HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS E 816 TOTAL HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS 2161 TOTAL HOURS CALM 0 METEOROLOGICAL FACILITY: Sequoyah Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 9.25 AND 45.99 METERS WIND SPEED AND DIRECTION MEASURED AT 9.73 METER LEVEL DATE PRINTED: 2003/12/08 MEAN WIND SPEED = 2.19 NOTE: TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS A1-20

JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS F ( 1.5< DELTA T<= 4.0 C/100 M)

Sequoyah Nuclear Plant JUL 1, 2003 - SEP 30, 2003 WIND WIND SPEED(MPH)

DIRECTION CALM 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4 >=24.5 TOTAL N 0.000 0.463 3.748 0.139 0.000 0.000 0.000 0.000 0.000 4.350 NNE 0.000 0.416 3.424 0.093 0.000 0.000 0.000 0.000 0.000 3.933 NE 0.000 0.463 0.278 0.000 0.000 0.000 0.000 0.000 0.000 0.740 ENE 0.000 0.231 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.231 E 0.000 0.139 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.139 ESE 0.000 0.139 0.046 0.000 0.000 0.000 0.000 0.000 0.000 0.185 SE 0.000 0.231 0.139 0.000 0.000 0.000 0.000 0.000 0.000 0.370 SSE 0.000 0.231 0.093 0.000 0.000 0.000 0.000 0.000 0.000 0.324 S 0.000 0.046 0.139 0.000 0.000 0.000 0.000 0.000 0.000 0.185 SSW 0.000 0.093 0.231 0.046 0.000 0.000 0.000 0.000 0.000 0.370 SW 0.000 0.046 0.093 0.000 0.000 0.000 0.000 0.000 0.000 0.139 WSW 0.000 0.000 0.093 0.000 0.000 0.000 0.000 0.000 0.000 0.093 W 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 WNW 0.000 0.093 0.093 0.046 0.000 0.000 0.000 0.000 0.000 0.231 NW 0.000 0.046 0.740 0.046 0.000 0.000 0.000 0.000 0.000 0.833 NNW 0.000 0.185 0.740 0.231 0.000 0.000 0.000 0.000 0.000 1.157 SUBTOTAL 0.000 2.823 9.857 0.602 0.000 0.000 0.000 0.000 0.000 13.281 TOTAL HOURS OF VALID STABILITY OBSERVATIONS 2181 TOTAL HOURS OF STABILITY CLASS F 289 TOTAL HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS F 287 TOTAL HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS 2161 TOTAL HOURS CALM 0 METEOROLOGICAL FACILITY: Sequoyah Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 9.25 AND 45.99 METERS WIND SPEED AND DIRECTION MEASURED AT 9.73 METER LEVEL DATE PRINTED: 2003/12/08 MEAN WIND SPEED = 1.99 NOTE: TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS A1-21

JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS G (DELTA T > 4.0 C/100 M)

Sequoyah Nuclear Plant JUL 1, 2003 - SEP 30, 2003 WIND WIND SPEED(MPH)

DIRECTION CALM 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4 >=24.5 TOTAL N 0.000 0.000 0.046 0.000 0.000 0.000 0.000 0.000 0.000 0.046 NNE 0.000 0.000 0.046 0.000 0.000 0.000 0.000 0.000 0.000 0.046 NE 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 ENE 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0 . 000 0.000 0.000 E 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0 . 000 0.000 0.000 ESE 0.000 0.046 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.046 SE 0.000 0.046 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.046 SSE 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 S 0.000 0.000 0.093 0.000 0.000 0.000 0.000 0.000 0.000 0.093 SSW 0.000 0.000 0.046 0.000 0.000 0.000 0.000 0.000 0 .000 0.046 SW 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0 .000 0.000 WSW 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 W 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0 . 000 WNW 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 NW 0.000 0.000 0.000 0.046 0.000 0.000 0.000 0.000 0.000 0.046 NNW 0.000 0.000 0.046 0.000 0.000 0.000 0.000 0 .000 0.000 0.046 SUBTOTAL 0.000 0.093 0.278 0.046 0.000 0.000 0.000 0.000 0.000 0.416 TOTAL HOURS OF VALID STABILITY OBSERVATIONS 2181 TOTAL HOURS OF STABILITY CLASS G 9 TOTAL HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS G 9 TOTAL HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS 2161 TOTAL HOURS CALM 0 METEOROLOGICAL FACILITY: Sequoyah Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 9.25 AND 45.99 METERS WIND SPEED AND DIRECTION MEASURED AT 9.73 METER LEVEL DATE PRINTED: 2003/12/08 MEAN WIND SPEED = 2.18 NOTE: TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS Al -22

JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS A (DELTA T<=-1.9 C/100 M)

Seqcuoyah Nuclear Plant OCT 1, 2003 - DEC 31, 2003 WIND WIND SPEED(MPH)

DIRECTION CALM 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4 >=24.5 TOTAL N 0.000 0.000 0.047 0.190 0.095 0.190 0.000 0.000 0 .000 0.522 NNE 0.000 0.000 0.047 0.380 0.380 0.332 0.000 0.000 0 .000 1.140 NE 0.000 0.000 0.095 0.617 0.142 0.000 0.000 0.000 0 .000 0.855 ENE 0.000 0.000 0.142 0.047 0.000 0.000 0.000 0.000 0 .000 0.190 E 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0 .000 0.000 ESE 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0 .000 0.000 SE 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0 .000 0.000 SSE 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0 .000 0.000 S 0.000 0.000 0.000 0.047 0.047 0.000 0.000 0.000 0.000 0 .095 SSW 0.000 0.000 0.000 0.142 0.237 0.000 0.000 0.000 0 .000 0.380 SW 0.000 0.000 0.000 0.142 0.047 0.000 0.000 0.000 0 .000 0.190 WSW 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 W 0 .000 0.000 0.000 0.047 0.047 0.000 0 . 000 0.000 0.000 0.095 WNW 0.000 0.000 0.000 0.047 0.000 0.000 0.000 0.000 0.000 0.047 NW 0.000 0.000 0.000 0.000 0.047 0.000 0.000 0.000 0.000 0.047 NNW 0.000 0.000 0.000 0.000 0.142 0.380 0 . 000 0.000 0.000 0.522 SUBTOTAL 0.000 0.000 0.332 1.662 1.187 0.902 0.000 0.000 0.000 4.084 TOTAL HOURS OF VALID STABILITY OBSERVATIONS 2108 TOTAL NOURS OF STABILITY CLASS A 86 TOTAL NOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS A 86 TOTAL HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS 2106 TOTAL NOURS CALM 0 METEOROLOGICAL FACILITY: Sequoyah Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 9.25 AND 45.99 METERS WIND SPEED AND DIRECTION MEASURED AT 9.73 METER LEVEL DATE PRINTED: 2004/03/08 MEAN WIND SPEED = 5.92 NOTE: TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS Al-23

JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS B (-1.9< DELTA T<=-1.7 C/100 M)

Sequoyah Nuclear Plant OCT 1, 2003 - DEC 31, 2003 WIND WIND SPEED(MPH)

DIRECTION CALM 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4 >=24.5 TOTAL N 0.000 0.000 0.047 0.142 0.000 0.047 0.000 0.000 0.000 0.237 NNE 0.000 0.000 0.190 0.427 0.332 0.190 0.000 0.000 0.000 1.140 NE 0.000 0.000 0.190 0.237 0.047 0.000 0.000 0.000 0.000 0.475 ENE 0.000 0.000 0.047 0.000 0.000 0.000 0.000 0.000 0.000 0.047 E 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 ESE 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 SE 0.000 0.000 0.000 0.047 0.000 0.000 0.000 0.000 0.000 0.047 SSE 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 S 0.000 0.000 0.000 0.047 0.047 0.000 0.000 0.000 0.000 0.095 SSW 0.000 0.000 0.047 0.380 0.332 0.000 0.000 0.000 0.000 0.760 SW 0.000 0.000 0.047 0.380 0.095 0.000 0.000 0.000 0.000 0.522 WSW 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 W 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 WNW 0.000 0.000 0.000 0.000 0.047 0.095 0.000 0.000 0.000 0.142 NW 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 NNW 0.000 0.000 0.000 0.047 0.047 0.047 0.000 0.000 0.000 0.142 SUBTOTAL 0.000 0.000 0.570 1.709 0.950 0.380 0.000 0.000 0.000 3.609 TOTAL HOURS OF VALID STABILITY OBSERVATIONS 2108 TOTAL HOURS OF STABILITY CLASS B 77 TOTAL HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS B 76 TOTAL HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS 2106 TOTAL HOURS CALM 0 METEOROLOGICAL FACILITY: Sequoyah Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 9.25 AND 45.99 METERS WIND SPEED AND DIRECTION MEASURED AT 9.73 METER LEVEL DATE PRINTED: 2004/03/08 MEAN WIND SPEED = 5.17 NOTE: TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS Al-24

JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS C (-1.7< DELTA T<=-1.5 C/100 M)

Sequoyah Nuclear Plant OCT 1, 2003 - DEC 31, 2003 WIND WIND SPEED(MPH)

DIRECTION CALM 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4 >=24.5 TOTAL N 0.000 0.000 0.000 0.095 0.285 0.000 0.000 0.000 0.000 0.380 NNE 0.000 0.000 0.142 0.380 0.190 0.047 0.000 0.000 0.000 0.760 NE 0.000 0.000 0.190 0.380 0.047 0.000 0.000 0.000 0.000 0.617 ENE 0.000 0.000 0.190 0.000 0.000 0.000 0.000 0.000 0.000 0.190 E 0.000 0.000 0.047 0.000 0.000 0.000 0.000 0.000 0.000 0.047 ESE 0.000 0.000 0.047 0.047 0.000 0.000 0.000 0.000 0.000 0.095 SE 0.000 0.000 0.047 0.047 0.000 0.000 0.000 0.000 0.000 0.095 SSE 0.000 0.000 0.095 0.000 0.000 0.000 0.000 0.000 0.000 0.095 S 0.000 0.000 0.000 0.380 0.047 0.000 0.000 0.000 0.000 0.427 SSW 0.000 0.000 0.142 0.475 0.237 0.047 0.000 0.000 0.000 0.902 SW 0.000 0.000 0.000 0.237 0.142 0.000 0.000 0.000 0.000 0.380 WSW 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 W 0.000 0.000 0.047 0.047 0.000 0.000 0.000 0.000 0.000 0.095 WNW 0.000 0.000 0.000 0.000 0.047 0.095 0.000 0.000 0.000 0.142 NW 0.000 0.000 0.000 0.000 0.047 0.000 0.000 0.000 0.000 0.047 NNW 0.000 0.000 0.000 0.095 0.000 0.047 0.000 0.000 0.000 0.142 SUBTOTAL 0.000 0.000 0.950 2.184 1.045 0.237 0.000 0.000 0.000 4.416 TOTAL HOURS OF VALID STABILITY OBSERVATIONS 2108 TOTAL HOURS OF STABILITY CLASS C 94 TOTAL HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS C 93 TOTAL HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS 2106 TOTAL HOURS CALM 0 METEOROLOGICAL FACILITY: Sequoyah Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 9.25 AND 45.99 METERS WIND SPEED AND DIRECTION MEASURED AT 9.73 METER LEVEL DATE PRINTED: 2004/03/08 MEAN WIND SPEED = 4.73 NOTE: TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS Al-25

JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS D (-1.5< DELTA T<=-0.5 C/100 M)

Sequoyah Nuclear Plant OCT 1, 2003 - DEC 31, 2003 WIND WIND SPEED(MPH)

DIRECTION CALM 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4 >=24.5 TOTAL N 0.000 0 .095 1.187 0.760 0.760 0.095 0 .000 0.000 0.000 2.896 NNE 0.000 0 .095 1.994 2.232 1.614 0.380 0.000 0.000 0.000 6.315 NE 0.000 0 .095 0.997 0.285 0.237 0 .095 0.000 0.000 0.000 1.709 ENE 0.000 0.142 0.285 0.047 0.000 0.000 0.000 0 .000 0.000 0.475 E 0.000 0.047 0.237 0.047 0.000 0.000 0.000 0 .000 0 .000 0.332 ESE 0.000 0.000 0.142 0.000 0.000 0.000 0.000 0 .000 0.000 0.142 SE 0.000 0.047 0.047 0.000 0.000 0.000 0.000 0.000 0 .000 0.095 SSE 0.000 0.047 0.760 0.285 0.047 0.190 0.000 0.000 0 .000 1 .330 S 0.000 0.047 0 . 665 1.045 0.380 0.570 0.000 0.000 0 .000 2.707 SSW 0.000 0.000 1.330 1.852 0.807 0.190 0.000 0.000 0.000 4.179 SW 0.000 0.047 1.519 1 . 662 0.332 0.190 0.000 0.000 0.000 3.751 WSW 0.000 0 .095 0.427 0.332 0.332 0.142 0.000 0.000 0.000 1.330 W 0.000 0.047 0.142 0.142 0.522 0.190 0.000 0.000 0.000 1 .045 WNW 0.000 0.047 0.285 0.237 0.427 0.427 0.000 0.000 0.000 1.425 NW 0.000 0 .095 0.665 0.522 0.617 0.475 0 .000 0.000 0.000 2.374 NNW 0.000 0.000 0.332 0.617 0.807 0.237 0.000 0.000 0.000 1.994 SUBTOTAL 0.000 0.950 11.016 10.066 6.885 3.181 0.000 0.000 0.000 32.099 TOTAL HOURS OF VALID STABILITY OBSERVATIONS 2108 TOTAL HOURS OF STABILITY CLASS D 676 TOTAL HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS D 676 TOTAL HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS 2106 TOTAL HOURS CALM 0 METEOROLOGICAL FACILITY: Sequoyah Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 9.25 AND 45.99 METERS WIND SPEED AND DIRECTION MEASURED AT 9.73 METER LEVEL DATE PRINTED: 2004/03/08 MEAN WIND SPEED = 4.54 NOTE: TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS A1-26

JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS E (-0.5< DELTA T< 1.5 C/100 M)

Sequoyah Nuclear Plant OCT 1, 2003 - DEC 31, 2003 WIND WIND SPEED(MPH)

DIRECTION CALM 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4 >=24.5 TOTAL N 0.000 0.332 3.229 1.472 0.285 0.047 0.000 0 .000 0.000 5.366 NNE 0.000 0.522 4.463 1.519 0.760 0.000 0.000 0 .000 0.000 7.2 65 NE 0.000 0.190 0.427 0.047 0.000 0.000 0.000 0.000 0 .000 0.665 ENE 0.000 0.285 0.095 0.000 0.000 0.000 0.000 0 .000 0.000 0.380 E 0.000 0.142 0.095 0.000 0.000 0.000 0.000 0 .000 0.000 0.237 ESE 0.000 0.047 0.142 0.000 0.000 0.000 0.000 0.000 0.000 0.190 SE 0.000 0.380 0.380 0.000 0.000 0.000 0.000 0.000 0.000 0.760 SSE 0.000 0.190 0.475 0.237 0.142 0.237 0.000 0.000 0 .000 1.282 S 0.000 0.522 1.804 0.807 0.950 0.332 0.000 0.000 0 .000 4.416 SSW 0.000 0.142 2.564 1.804 0.285 0.047 0.000 0.000 0 .000 4.843 SW 0.000 0.380 2.849 0.475 0.000 0.000 0.000 0.000 0 .000 3.704 WSW 0.000 0.237 0.427 0.095 0.000 0.000 0.000 0.000 0 .000 0.760 W 0.000 0.095 0.142 0.000 0.000 0.000 0.000 0.000 0 .000 0.237 WNW 0.000 0.095 0.665 0.047 0.047 0.000 0.000 0.000 0 .000 0.855 NW 0.000 0.095 0.427 0.427 0.380 0.095 0.000 0.000 0 .000 1.425 NNW 0.000 0.332 1.140 0.712 0.237 0.237 0.000 0.000 0 .000 2.659 SUBTOTAL 0.000 3.989 19.326 7.645 3.086 0.997 0.000 0.000 0.000 35.043 TOTAL HOURS OF VALID STABILITY OBSERVATIONS 2108 TOTAL HOURS OF STABILITY CLASS E 738 TOTAL HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS E 738 TOTAL HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS 2106 TOTAL HOURS CALM 0 METEOROLOGICAL FACILITY: Sequoyah Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 9.25 AND 45.99 METERS WIND SPEED AND DIRECTION MEASURED AT 9.73 METER LEVEL DATE PRINTED: 2004/03/08 MEAN WIND SPEED = 3.18 NOTE: TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS A1 -27

JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS F ( 1.5< DELTA T<= 4.0 C/100 M)

Sequoyah Nuclear Plant OCT 1, 2003 - DEC 31, 2003 WIND WIND SPEED(MPH)

DIRECTION CALM 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4 >=24.5 TOTAL N 0.000 0.095 2.232 0.475 0.000 0.000 0.000 0.000 0.000 2.802 NNE 0.000 0.427 4.416 0.475 0.000 0.000 0.000 0.000 0.000 5.318 NE 0.000 0.617 0.570 0.000 0.000 0.000 0.000 0.000 0.000 1.187 ENE 0.000 0.332 0.237 0.000 0.000 0.000 0.000 0.000 0.000 0.570 E 0.000 0.332 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.332 ESE 0.000 0.285 0.142 0.000 0.000 0.000 0.000 0.000 0.000 0.427 SE 0.000 0.427 0.047 0.000 0.000 0.000 0.000 0.000 0.000 0.475 SSE 0.000 0.142 0.475 0.000 0.000 0.000 0.000 0.000 0.000 0.617 S 0.000 0.047 0.522 0.000 0.047 0.000 0.000 0.000 0.000 0.617 SSW 0.000 0.047 1.330 0.000 0.000 0.000 0.000 0.000 0.000 1.377 SW 0.000 0.237 0.285 0.000 0.000 0.000 0.000 0.000 0.000 0.522 WSW 0.000 0.047 0.285 0.000 0.000 0.000 0.000 0.000 0.000 0.332 W 0.000 0.000 0.095 0.000 0.000 0.000 0.000 0.000 0.000 0.095 WNW 0.000 0.047 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.047 NW 0.000 0.047 0.142 0.095 0.047 0.000 0.000 0.000 0.000 0.332 NNW 0.000 0.047 0.380 0.190 0.000 0.000 0.000 0.000 0.000 0.617 SUBTOTAL 0.000 3.181 11.159 1.235 0.095 0.000 0.000 0.000 0.000 15.670 TOTAL HOURS OF VALID STABILITY OBSERVATIONS 2108 TOTAL HOURS OF STABILITY CLASS F 330 TOTAL HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS F 330 TOTAL HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS 2106 TOTAL HOURS CALM 0 METEOROLOGICAL FACILITY: Sequoyah Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 9.25 AND 45.99 METERS WIND SPEED AND DIRECTION MEASURED AT 9.73 METER LEVEL DATE PRINTED: 2004/03/08 MEAN WIND SPEED = 2.16 NOTE: TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS Al-28

JOINT PERCENTAGE FREQUENCIES OF WIND SPEED BY WIND DIRECTION FOR STABILITY CLASS G (DELTA T > 4.0 C/100 M)

Sequoyah Nuclear Plant OCT 1, 2003 - DEC 31, 2003 WIND WIND SPEED(MPH)

DIRECTION CALM 0.6-1.4 1.5-3.4 3.5-5.4 5.5-7.4 7.5-12.4 12.5-18.4 18.5-24.4 >=24.5 TOTAL N 0.000 0.000 0.047 0.000 0.000 0.000 0.000 0.000 0.000 0.047 NNE 0.000 0.000 0.950 0.095 0.000 0.000 0.000 0.000 0.000 1.045 NE 0.000 0.190 1.140 0.000 0.000 0.000 0.000 0.000 0.000 1.330 ENE 0.000 0.332 0.142 0.000 0.000 0.000 0.000 0.000 0.000 0.475 E 0.000 0.190 0.000 0.000 0.000 0.000 0.000 0 .000 0.000 0.190 ESE 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 SE 0.000 0.142 0.142 0.000 0.000 0.000 0.000 0.000 0.000 0.285 SSE 0.000 0.285 0.095 0.000 0.000 0.000 0.000 0.000 0 .000 0.380 S 0.000 0.047 0.332 0.000 0.000 0.000 0.000 0.000 0.000 0.380 SSW 0.000 0.095 0.475 0.000 0.000 0.000 0.000 0.000 0.000 0.570 SW 0.000 0.095 0.237 0.000 0.000 0.000 0.000 0.000 0.000 0.332 WSW 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 W 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 WNW 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 NW 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 NNW 0.000 0.000 0.047 0.000 0.000 0.000 0.000 0.000 0.000 0.047 SUBTOTAL 0.000 1.377 3.609 0.095 0.000 0.000 0.000 0.000 0.000 5.081 TOTAL HOURS OF VALID STABILITY OBSERVATIONS 2108 TOTAL HOURS OF STABILITY CLASS G 107 TOTAL HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY CLASS G 107 TOTAL HOURS OF VALID WIND DIRECTION-WIND SPEED-STABILITY OBSERVATIONS 2106 TOTAL HOURS CALM 0 METEOROLOGICAL FACILITY: Sequoyah Nuclear Plant STABILITY BASED ON DELTA-T BETWEEN 9.25 AND 45.99 METERS WIND SPEED AND DIRECTION MEASURED AT 9.73 METER LEVEL DATE PRINTED: 2004/03/08 MEAN WIND SPEED = 1.91 NOTE: TOTALS AND SUBTOTALS ARE OBTAINED FROM UNROUNDED NUMBERS A1 -29

Attachment 2.0 Deviations from ODCM Controls/Surveillance Requirements 1/9/03 1/2.1 A malfunction alarm came in ORM-90-101. Chemistry and an AUO were Table 1.1-2 dispatched. The sample pump was found to be off. The sample pump was Item 4.b and cturned back on and Chemistry replaced and counted the fliters per 0-SI-CEM-030-407.2 3/20/03 1/2.1 Operations declared 1-RM-90-400 operable with temporary sampling Table 1.1-2 equipment still in place. Actions 41 and 43 were met, however action 45 for Item 5.b flow reading every four hours was exceeded.

3/31/03 1/2.1 Operations erroneously recorded the radiation monitor background.

Table 1.1-1 Chemistry used the errounous background to process the pre-release Item 1.a report. The erroneous background caused the setpoint to be set artificially high. The release package was closed and no ODCM limits were exceeded.

4/24/03 1/2.1 Radiaton Monitors 1,2RM-90-99 and 119 were discovered to have been tested Table 1.2-2 for circuit failure by using the CAL/OPERATE switch instead of pulling fuses. This Item 2.a diagnostic testing is required by the ODCM Functional Test but does not affect the monitors ability to measure and indicate radioactivity nor does it impact its ability to actuate upon a high radiation condition.

6/3/03 1/2.1 The channel functional test procedure for radiation monitor did not independently Table 2.2-1 verify that automatic isolation of the release pathway (0-RCV-77-43 occurs when an Item l.a instrument malfunction condition from a downscale failure exits The channel calibration test procedure does verify that high radiation, downscale failure and circuit failure isolates 0-RCV-77-43 and were performed.

A2-1

Attachment 3.0 Radiation Monitors Inoperable for Greater than 30 days None A3-1

ENCLOSURE 3 OFFSITE DOSE CALCULATION MANUAL SEQUOYAH NUCLEAR PLANT

SEQUOYAH NUCLEAR PLANT OFFSITE DOSE CALCULATION MANUAL Revision 47 Prepared By: W. Kenneth Kimsey Sponsor: Charles E. Kent Date: 110712003 PORC Review: Mike Lorek Date: 1/10/2003 PORC Meeting No.: 6093 Approval--Plant Manager: Dennis L. Koehl Date: 1/13/2003 Effective Date: 1/15/2003

SQN ODCM Revision 47 Page 2 of 168 SEQUOYAH NUCLEAR PLANT OFFSITE DOSE CALCULATION MANUAL REVISION LOG (Page 1 of 1)

Revision Approval Date Revision Approval Date Effective Date Original ODCM 2/29/801 Revision 23 6/28/89, 9/15/894 Revision 1 4/15/802 Revision 25 11/2/90, 4/24/912 Revision 2 10/7/802 Revision 26 1/17/925 3/17/92 Revision 3 11/3/80, 2/10/81, Revision 27 4/15/92 4/8/81, 6/4/812 Revision 4 10/22/81,11/28/81, Revision 28 9/22/926 12/1/92 4/29/82,11/22/822 Revision 5 10/21/822 Revision 29 3/30/932 Revision 6 1/20/832 Revision 30 9/30/932 Revision 7 3/23/832 Revision 31 10/13/932 Revision 8 12/16/832 Revision 32 11/29/932 1/1/94 Revision 9 3/7/842 Revision 33 2/25/942 Revision 10 4/24/842 Revision 34 4/29/942 5/15/94 Revision 11 8/21/84 Revision 35 10/20/946 11/15/94 Revision 12 2/19/852 Revision 36 7/20/956 8/4/95 Revision 13 12/02/852 Revision 37 10/26/956 11/6/95 Revision 14 4/14/862 Revision 38 2/15/966 2/23/96 Revision 15 11/5/863 Revision 39 11/12/966 1/17/97 Revision 16 1/16/872 Revision 40 4/2/986 4/23/98 Revision 17 10/28/872 Revision 41 8/7/98 8/11/98 Revision 18 1/5/882 Revision 42 4/29/99 4/30/99 Revision 19 3/30/882 Revision 43 4/29/99 4/30/99 Revision 20 7/19/882 Revision 44 6/17/996 6/21/99 Revision 20A 12/14/882 Revision 45 2/17/006 3/11/00 Revision 21 2/15/892 Revision 46 10/6/01 10/9/01 Revision 22 6/1/892' Low power license for Sequoyah Unit 1.

2 RARC Meeting Date.

3 Date approved by RARC Chairman.

4 Revision 23 implements the Nuclear Data Effluent Management Software. This ODCM revision and the software will be implemented concurrently on October 9,1989.

Releases made during the month of October prior to the software implementation will be backfitted to comply with this revision.

5 Revision 26 was recommended for approval by the SQN RARC at the October 2, 1991 meeting. The revision date is January 17, 1992. The final implementation date for Revision 26 will be March 17, 1992.

6 PORC Meeting Date.

SQN ODCM Revision 47 Page 3 of 168 INTRODUCTION......................................................................................................................................8 1/2 CONTROLS AND SURVEILLANCE REQUIREMENTS .................................................................... 11 1/2.0 APPLICABILITY ............................................................................. 11 1/2.1 INSTRUMENTATION ............................................................................. 13 1/2.1.1 RADIOACTIVE LIQUID EFFLUENT MONITORING INSTRUMENTATION ............................. 13 TABLE 1.1-1 RADIOACTIVE LIQUID EFFLUENT MONITORING INSTRUMENTATION ............. 14 TABLE 2.1 RADIOACTIVE LIQUID EFFLUENT MONITORING INSTRUMENTATION SURVEILLANCE REQUIREMENTS ............................................................................. 16 1/2.1.2 RADIOACTIVE GASEOUS EFFLUENT MONITORING INSTRUMENTATION ......................... 18 TABLE 1.1-2 RADIOACTIVE GASEOUS EFFLUENT MONITORING INSTRUMENTATION ......... 19 TABLE 2.1-2 RADIOACTIVE GASEOUS EFFLUENT MONITORING INSTRUMENTATION SURVEILLANCE REQUIREMENTS ............................................................................. 21 1/2.2 RADIOACTIVE EFFLUENTS ............................................................................. 23 1/2.2.1 LIQUID EFFLUENTS ............................................................................. 23 1/2.2.1.1 CONCENTRATION ............................................................................. 23 TABLE 2.2-1 RADIOACTIVE LIQUID WASTE SAMPLING AND ANALYSIS PROGRAM ............... 24 1/2.2.1.2 DOSE ............................................................................. 27 1/2.2.1.3 LIQUID RADWASTE TREATMENT SYSTEM .......................................................................... 28 1/2.2.2 GASEOUS EFFLUENTS ............................................................................. 29 1/2.2.2.1 DOSE RATE ............................................................................. 29 TABLE 2.2-2 RADIOACTIVE GASEOUS WASTE MONITORING SAMPLING AND ANALYSIS PROGRAM ............................................................................. 30 1/2.2.2.2 DOSE -NOBLE GASES ............................................................................. 33 1/2.2.2.3 DOSE - I-131, 1-133, TRITIUMAND RADIONUCLIDES IN PARTICULATE FORM WITH HALF-LIVES GREATERTHAN EIGHT DAYS ............................................................... 34 1/2.2.2.4 GASEOUS RADWASTE TREATMENT ............................................................................. 35 1/2.2.3 TOTAL DOSE ............................................................................. 36 1/2.3 RADIOLOGICAL ENVIRONMENTAL MONITORING .................................................................. 37 1/2.3.1 MONITORING PROGRAM ............................................................................. 37 TABLE 2.3-1 MINIMUM REQUIRED RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM ............................................................................. 39 TABLE 2.3-2 REPORTING LEVELS FOR RADIOACTIVITY CONCENTRATIONS IN ENVIRONMENTAL SAMPLES ............................................................................. 41 TABLE 2.3-3 MAXIMUM VALUES FOR THE LOWER LIMITS OF DETECTION (LLD) ................... 42 1/2.3.2 LAND USE CENSUS ............................................................................. 44 1/2.3.3 INTERLABORATORY COMPARISON PROGRAM ..................................................................... 46 BASES ............................................................................. 48 INSTRUMENTATION ............................................................................. 48 1/2.1.1 RADIOACTIVE LIQUID EFFLUENT MONITORING INSTRUMENTATION ............................. 48 1/2.1.2 RADIOACTIVE GASEOUS EFFLUENT MONITORING INSTRUMENTATION ......................... 48

SQN ODCM Revision 47 Page 4 of 168 1/2.2 RADIOACTIVE EFFLUENTS ............................................................... 48 1/2.2.1.1 CONCENTRATION ............................................................... 48 1/2.2.1.2 DOSE ............................................................... 48 1/2.2.1.3 LIQUID RADWASTE TREATMENT SYSTEM ............................................................... 49 1/2.2.2.1 DOSE RATE ............................................................... 49 1/2.2.2.2 DOSE -NOBLE GASES ............................................................... 50 1/2.2.2.3 DOSE - I-131, 1-133, TRITIUM AND RADIONUCLIDES IN PARTICULATE FORM WITH HALF-LIVES GREATER THAN EIGHT DAYS .................................................... 50 1/2.3.2.4 GASEOUS RADWASTE TREATMENT ............................................................... 51 1/2.2.3 TOTAL DOSE ............................................................... 51 1/2.3 RADIOLOGICAL ENVIRONMENTAL MONITORING ............................................................... 52 1/2.3.1 MONITORING PROGRAM ............................................................... 52 1/2.3.2 LAND USE CENSUS ............................................................... 52 1/2.3.3 INTERLABORATORY COMPARISON PROGRAM ............................................................... 52 3.0 DEFINITIONS ............................................................... 54 3.1 CHANNEL CALIBRATION ............................................................... 54 3.2 CHANNEL CHECK ............................................................... 54 3.3 CHANNEL FUNCTIONAL TEST ............................................................... 54 3.4 CIRCUIT FAILURE ............................................................... 54 3.5 CONTROLLED AREA ............................................................... 54 3.6 DOSE EQUIVALENT I-131 ............................................................... 54 3.7 GASEOUS RADWASTE TREATMENT SYSTEM ............................................................... 53 3.8 MEMBER(S) OF THE PUBLIC ............................................................... 55 3.9 OPERABLE - OPERABILITY ............................................................... 55 3.10 MODE ............................................................... 55 3.11 PURGE -PURGING ............................................................... 55 3.12 RADIATION MONITOR (RM) ............................................................... 55 3.13 RATED THERMAL POWER ............................................................... 55 3.14 RESTRICTED AREA ............................................................... 54 3.15 SITE BOUNDARY ............................................................... 56 3.16 SOURCE/SENSOR CHECK ............................................................... 56 3.17 UNRESTRICTED AREA/BOUNDARY ............................................................... 56 3.18 VENTILATION EXHAUST TREATMENT SYSTEM ............................................................... 56 3.19 VENT FLOW RATE MONITOR (F) ............................................................... 56 3.20 VENTING ............................................................... 56 TABLE 3.1 FREQUENCY NOTATION ................................................................. 57 FIGURE 3.1 UNRESTRICTED AREA BOUNDARY ................................................................. 58 5.0 ADMINISTRATIVE CONTROLS ......................................................... 61 5.1 ANNUAL RADIOLOGICAL ENVIRONMENTAL OPERATING REPORT ......................................... 61 5.2 ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT .............................................................. 61 5.3 OFFSITE DOSE CALCULATION MANUAL CHANGES ............................................................... 63 5.4 SPECIAL REPORTS ............................................................... 63 SECTION 6.0 LIQUID EFFLUENTS ......................................................... 65 RELEASE POINTS ............................................................... 65 6.1 LIQUID RELEASES ............................................................... 66 6.1.1 Pre-Release Analysis ............................................................... 66 6.1.2 Effluent Concentration Limits (ECL)-Sum of the Ratios ............................................................... 66 6.1.3 Post-Release Analysis ............................................................... 67

SQN ODCM Revision 47 Page 5 of 168 6.2 INSTRUMENT SETPOINTS ......................................................................... 68 6.2.1 Discharge Point Monitor Setpoints (0-RE-90-133,134,140,141) .................................................... 68 6.2.2 Release Point Monitor Setpoints (0-RM-90-122; 0-RM-90-225; 0-RM-90-212; 1,2-RM-90-20,121) ......................................................................... 68 6.2.3 Batch Release Point Monitor Setpoint ........................................................................ 68 6.3 CUMULATIVE LIQUID EFFLUENT DOSE CALCULATIONS .......................................................... 70 6.3.1 Monthly Dose Calculations ......................................................................... 71 6.3.2 Cumulative Doses ......................................................................... 71 6.3.3 Comparison to Limits ........................................................................ 71 6.4 LIQUID RADWASTE TREATMENT SYSTEM ........................................................................ 72 6.5 DOSE PROJECTIONS ........................................................................ 73 6.6 QUARTERLY DOSE CALCULATIONS ........................................................................ 74 6.6.1 WATER INGESTION ........................................................................ 74 6.6.2 FISH INGESTION ......................................................................... 75 6.6.3 SHORELINE RECREATION ........................................................................ 75 6.6.4 TOTAL MAXIMUM INDIVIDUAL DOSE ........................................................................ 76 6.6.5 POPULATION DOSES ........................................................................ 76 6.7 LIQUID DOSE FACTOR EQUATIONS ........................................................................ 79 6.7.1 WATER INGESTION ........................................................................ 79 6.7.2 FISH INGESTION ......................................................................... 79 6.7.3 SHORELINE RECREATION ........................................................................ 79 TABLE 6.1 RECEPTORS FOR LIQUID DOSE CALCULATIONS ........................................................ 80 TABLE 6.2 RADIONUCLIDE DECAY AND STABLE ELEMENT TRANSFER DATA ....................... 81 TABLE 6.3 DOSE CALCULATION FACTORS ........................................................................... 84 TABLE 6.4 INGESTION DOSE FACTORS ........................................................................... 86 TABLE 6.5 BIOACCUMULATION FACTORS FOR FRESHWATER FISH ......................................... 94 TABLE 6.6 EXTERNAL DOSE FACTORS FOR STANDING ON CONTAMINATED GROUND ........ 95 FIGuRlE 6.1 LIQUID EFFLUENT RELEASE POINTS ........................................................................... 97 FIGuRE 6.2 LIQUID RADWASTE SYSTEM ........................................................................... 98 SECTION 7.0 GASEOUS EFFLUENTS .................................................................. 100 RELEASE POINTS DESCRIPTION ........................................................................ 100 7.1 INSTRUMENT SETPOINTS ......................................................................... 101 7.1.1 Release Point Monitor Setpoints (1,2-RM-90-130,-131, 0-RM-90-118) ....................................... 101 7.1.1.1 Containment Purge Effluent Monitors (1,2-RM-90-130,-131) ................................................... 101 7.1.1.2 Waste Gas Decay Tank Effluent Monitor (0-RM-90-118) ......................................................... 101 7.1.2 Discharge Point Monitor Setpoints (1,2-RE-90-400, 0-RM-90-101, 0-RM-90-132, 1,2-RM-90-99,119) ........................................................................ 103 7.1.3 Condenser Vacuum Exhaust Vent (1,2-RM-90-99,119) .............................................................. 103 7.2 GASEOUS EFFLUENTS - DOSE RATES ......................................................................... 104 7.2.1 (Deleted) ........................................................................ 104 7.2.2 RELEASE SAMPLING ........................................................................ 104 7.2.3 NOBLE GAS DOSE RATES ......................................................................... 104 7.2.3.1 Total Body Dose Rate ........................................................................ 104 7.2.3.2 Skin Dose Rate ........................................................................ 105 7.2.4 1-131, 1-133, TRITIUM AND ALL RADIONUCLIDES IN PARTICULATE FORM WITH HALF-LIVES OF GREATER THAN 8 DAYS - ORGAN DOSE RATE ...................................... 106

SQN ODCM Revision 47 Page 6 of 168 7.3 DOSE-NOBLE GASES ......................................................................... 107 7.3.1 Gamma dose to air ........................................................................ 107 7.3.2 Beta dose to air ......................................................................... 107 7.3.3 Cumulative Dose - Noble Gas ......................................................................... 108 7.3.4 Comparison to Limits ........................................................................ 108 7.4 DOSE DUE TO I-131,1-133, TRITIUM AND ALL RADIONUCLIDES IN PARTICULATE FORM WITH HALF-LIVES OF GREATER THAN 8 DAYS ............................................................... 109 7.4.1 Organ dose Calculation ........................................................................ 109 7.4.2 Cumulative Doses ........................................................................ 110 7.4.3 Comparison to Limits ......................................................................... 110 7.5 DOSE PROJECTIONS ......................................................................... 111 7.5.1 GASEOUS RADWASTE TREATMENT SYSTEM DESCRIPTION .......................................... 111 7.6 QUARTERLY DOSE CALCULATIONS ......................................................................... 112 7.6.1 NOBLE GAS - GAMMA AIR DOSE ........................................................................ 112 7.6.2 NOBLE GAS - BETA AIR DOSE ........................................................................ 112 7.6.3 RADIOIODINE, PARTICULATE AND TRITIUM - MAXIMUM ORGAN DOSE ..................... 113 7.6.4 POPULATION DOSES ........................................................................ 114 7.6.5 REPORTING OF DOSES ........................................................................ 115 7.6.6 DOSE TO A MEMBER OF THE PUBLIC INSIDE THE UNRESTRICTED FOR RESTRICTED AREA BOUNDARY ......................................................................... 115 7.7 GASEOUS RELEASES - DOSE FACTORS ........................................................................ 116 7.7.1 PASTURE GRASS-COW/GOAT-MILK INGESTION DOSE FACTORS ................................... 116 7.7.2 STORED FEED-COW/GOAT-MILK INGESTION DOSE FACTORS ....................................... 117 7.7.3 PASTURE GRASS-BEEF INGESTION DOSE FACTORS ......................................................... 118 7.7.4 STORED FEED-BEEF INGESTION DOSE FACTORS .............................................................. 119 7.7.5 FRESH LEAFY VEGETABLE INGESTION DOSE FACTORS ................................................. 120 7.7.6 STORED VEGETABLE INGESTION DOSE FACTORS ........................................................... 121 7.7.7 TRITIUM-PASTURE GRASS-COW/GOAT-MILK DOSE FACTOR ......................................... 122 7.7.8 TRITIUM-STORED FEED-COW/GOAT-MILK DOSE FACTOR .............................................. 122 7.7.9 TRITIUM-PASTURE GRASS-BEEF DOSE FACTOR ............................................................... 123 7.7.10 TRITIUM-STORED FEED-BEEF DOSE FACTOR .................................................................. 123 7.7.11 TRITIUM-FRESH LEAFY VEGETABLES DOSE FACTOR .................................................... 124 7.7.12 TRITIUM-STORED VEGETABLES DOSE FACTOR .............................................................. 125 7.7.13 INHALATION DOSE FACTORS ......................................................................... 125 7.7.14 GROUND PLANE DOSE FACTORS ........................................................................ 125 7.8 DISPERSION METHODOLOGY ........................................................................ 126 7.8.1 AIR CONCENTRATION ......................................................................... 126 7.8.2 RELATIVE CONCENTRATION ......................................................................... 127 7.8.3 RELATIVE DEPOSITION ........................................................................ 128 TABLE 7.1 SEQUOYAH MAXIMUM QUARTERLY X/Q (1986-1995) SORTED BY QUARTER.....129 TABLE 7.2 SEQUOYAH MAXIMUM QUARTERLY D/Q (1986-1995) SORTED BY QUARTER ...... 130 TABLE 7.3 DOSE FACTORS FOR SUBMERSION IN NOBLE GASES .............................................. 131 TABLE 7.4 SECTOR ELEMENTS CONSIDERED FOR POPULATION DOSES ............................... 132 TABLE 7.5 POPULATION WITHIN EACH SECTOR ELEMENT ...................................................... 133 TABLE 7.6 INHALATION DOSE FACTORS ........................................................................... 134 FIGURE 7.1 GASEOUS EFFLUENT RELEASE POINTS ..................................................................... 142 FIGURE 7.2 AUXILIARY AND SHIELD BUILDING VENTS (DETAIL) ............................................. 143 FIGURE 7.3 GASEOUS RADWASTE TREATMENT SYSTEM ........................................................... 144 FIGURE 7.4 PLUME DEPLETION EFFECT FOR GROUND LEVEL RELEASES ............................. 145

SQN ODCM Revision 47 Page 7 of 168 FIGURE 7.5 VERTICAL STANDARD DEVIATION OF MATERIAL IN A PLUME ........................... 146 FIGURE 7.6 RELATIVE DEPOSITION FOR GROUND LEVEL RELEASES ..................................... 147 SECTION 8.0 TOTAL DOSE ................................................................. 149 8.1 ANNUAL MAXIMUM INDIVIDUAL DOSES - TOTAL REPORTED DOSE ..................................... 149 SECTION 9.0 RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM ...... 151 9.1 MONITORING PROGRAM .......................................................................... 151 9.2 DETECTION CAPABILITIES .......................................................................... 151 9.3 LAND USE CENSUS .......................................................................... 151 9.4 INTERLABORATORY COMPARISON PROGRAM ......................................................................... 151 TABLE 9.1 RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM ............................. 152 TABLE 9.2 ENVIRONMENTAL RADIOLOGICAL MONITORING PROGRAM SAMPLING LOCATIONS .......................................................................... 156 TABLE 9.3 THERMOLUMINESCENT DOSIMETRY LOCATIONS .................................................. 157 FIGURE 9.1 ENVIRONMENTAL MONITORING LOCATIONS WITHIN ONE MILE OF THE PLANT .......................................................................... 159 FIGURE 9.2 ENVIRONMENTAL MONITORING LOCATIONS FROM ONE TO FIVE MILES FROM THE PLANT .......................................................................... 160 FIGURE 9.3 ENVIRONMENTAL MONITORING LOCATIONS GREATER THAN FIVE MILES FROM THE PLANT .......................................................................... 161 APPENDIX A SQN ODCM REVISION PROCESS .......................................................................... 162

SQN ODCM Revision 47 Page 8 of 168 INTRODUCTION This Offsite Dose Calculation Manual (ODOM) is in support of the Tennessee Valley Authority (TVA) facility operating licenses for a two-unit nuclear power plant located approximately 7.5 miles northeast of Chattanooga at the Sequoyah site in Hamilton County, Tennessee.

This facility has been designated the Sequoyah Nuclear Plant (SQN). The plant has been designed, built, and is operated by TVA. Each of the two identical units employs a Pressurized Water Reactor Nuclear Steam Supply System (NSSS) with four coolant loops furnished by Westinghouse Electric Corporation.

Each of the two reactor cores is rated at 3,411 MWt and, at this core power, each NSSS will operate at 3,423 MWt. The additional 12 MWt is due to the contribution of heat of the Primary Coolant System from nonreactor sources, primarily reactor coolant pump heat. Each of the reactor cores has an Engineered Safeguards Design rating of 3557 MWt and each NSSS 3570 MWt. The net electrical output is 1,183 MWe for the rated core power. All plant safety systems, including containment and engineered safety features, are designed and evaluated at the higher power level. In addition, the higher power rating is used in the analysis of postulated accidents having as a consequence the release of fission product activity to the environment.

The containment for each of the reactors consists of a freestanding steel vessel with an ice condenser and separate reinforced concrete shield building. The freestanding steel vessel and the concrete shield building were designed by TVA and the ice condenser was furnished by the Westinghouse Electric Corporation.

Unit 1 began commercial operation on July 1, 1981. Unit 2 began commercial operation on June 1,1982.

SQN ODCM Revision 47 Page 9 of 168 The ODCM is divided into two major parts. The first part of the ODCM contains:

1) Radioactive Effluent Controls required by Section 6.8.4.f of the SQN Technical Specifications; 2) Radiological Environmental Monitoring Controls; 3) descriptions of the information that should be included in the Annual Radiological Environmental Operating and Annual Radioactive Effluent Release Reports required by SQN Technical Specifications 6.9.1.6 and 6.9.1.8; and, 4) Administrative Controls for the ODCM requirements.

The second part of the ODCM contains the methodologies used to: 1) calculate offsite doses resulting from radioactive gaseous and liquid effluents to the unrestricted area/boundary and the Tennessee River; 2) calculate gaseous and liquid effluent monitor Alarm/Trip setpoints; and, 3) conduct the Environmental Radiological Monitoring Program.

The SQN ODCM will be maintained for use as a reference guide on accepted methodologies and calculations. Changes in the calculation methods or parameters will be incorporated into the ODCM in order to assure that the ODCM represents the present methodology in all applicable areas. Any licensee initiated ODCM changes will be implemented in accordance with SQN Technical Specification 6.14 and ODCM Administrative Control 5.3.

SQN ODCM Revision 47 Page 10 of 168 SECTIONS 1.0 AND 2.0 CONTROLS AND SURVEILLANCE REQUIREMENTS

SQN ODCM Revision 47 Page 11 of 168 112 CONTROLS AND SURVEILLANCE REQUIREMENTS 1/2.0 APPLICABILITY CONTROLS 1.0.1 Compliance with the Controls contained in the succeeding controls is required during the OPERATIONAL MODES or other conditions specified therein; except that upon failure to meet the Control, the associated ACTION requirements shall be met.

1.0.2 Noncompliance with a Control shall exist when the requirements of the Control and associated ACTION requirements are not met within the specified time intervals. If the Control is restored prior to the expiration of the specified intervals, completion of the ACTION requirements is not required.

1.0.3 When a Control is not met, except as provided in the associated ACTION requirements, within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> action shall be initiated to place the unit in a MODE in which the Control does not apply by placing it, as applicable, in:

a. At least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />,
b. At least HOT SHUTDOWN within the following 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />, and
c. At least COLD shutdown within the subsequent 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

1.0.4 Entry into an OPERATIONAL MODE or other specified condition shall not be made when the conditions for the Control are not met and the associated ACTION requires a shutdown if they are not met within a specified time interval. Entry into an OPERATIONAL MODE or specified condition may be made in accordance with ACTION requirements when conformance to them permits continued operation of the facility for an unlimited period of time. This provision shall not prevent passage through or to OPERATIONAL MODES as required to comply with the ACTION requirements. Exceptions to these requirements are stated in the individual Controls.

SQN ODCM Revision 47 Page 12 of 168 1/2 CONTROLS AND SURVEILLANCE REQUIREMENTS 112.0 APPLICABILITY SURVEILLANCE REQUIREMENTS 2.0.1 Surveillance Requirements shall be met during the OPERATIONAL MODES or other conditions specified for individual Controls unless otherwise stated in the individual Surveillance Requirement.

2.0.2 Each Surveillance Requirement shall be performed within the specified time interval with a maximum allowable extension not to exceed 25% of the specified surveillance interval.

If an ACTION requires periodic performance on a "once per ..." basis, the above frequency extension applies to each performance after the initial performance.

2.0.3 Failure to perform a Surveillance Requirement within the specified time interval shall constitute a failure to meet the OPERABILITY requirements for a Control. The time limits of the ACTION requirements are applicable at the time it is identified that a Surveillance Requirement has not been performed. The ACTION requirements may be delayed for up to 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> to permit the completion of the surveillance when the allowable outage time limits of the ACTION requirements are less than 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />. Surveillance Requirements do not have to be performed on inoperable equipment.

2.0.4 Entry into an OPERATIONAL MODE or other specified applicable condition shall not be made unless the Surveillance Requirement(s) associated with the Control has been performed within the applicable surveillance interval or as otherwise specified. This provision shall not prevent passage through or to OPERATIONAL MODES as required to comply with ACTION requirements. Exceptions to these requirements are stated in the individual Controls.

SQN ODCM Revision 47 Page 13 of 168 112 CONTROLS AND SURVEILLANCE REQUIREMENTS 1/2.1 INSTRUMENTATION 1/2.1.1 RADIOACTIVE LIQUID EFFLUENT MONITORING INSTRUMENTATION CONTROLS 1.1.1 In accordance with SQN Technical Specification 6.8.4.f.1, the radioactive liquid effluent monitoring instrumentation channels shown in Table 1.1-1 shall be OPERABLE with their alarm/trip setpoints set to ensure that the limits of ODCM Control 1.2.1.1 are not exceeded. The alarm/trip setpoints of these channels shall be determined in accordance with the methodology and parameters in ODCM Section 6.2.

APPLICABILITY: This requirement is applicable during all releases via these pathways.

ACTION:

a. With a radioactive liquid effluent monitoring instrumentation channel alarm/trip setpoint less conservative than required above, without delay suspend the release of radioactive liquid effluents monitored by the affected channel or declare the channel inoperable, or change the setpoint so that it is acceptably conservative.
b. With less than the minimum number of radioactive liquid effluent monitoring instrumentation channels OPERABLE, take the action shown in Table 1.1-1. Exert best effort to return the instruments to OPERABLE status within 30 days and, if unsuccessful, explain in the next Annual Radioactive Effluent Release Report why the inoperability could not be corrected within 30 days.
c. The provisions of Controls 1.0.3 and 1.0.4 are not applicable. Report all deviations in the Annual Radioactive Effluent Release Report.

SURVEILLANCE REQUIREMENTS 2.1.1 Each radioactive liquid effluent monitoring channel shall be demonstrated OPERABLE by performance of the CHANNEL CHECK, SOURCE/SENSOR CHECK, CHANNEL CALIBRATION, and CHANNEL FUNCTIONAL TEST operations at the frequencies shown in Table 2.1-1.

SQN ODCM Revision 47 Page 14 of 168 Table 1.1-1 RADIOACTIVE LIQUID EFFLUENT MONITORING INSTRUMENTATION (Page 1 of 2)

Minimum Instrument Channels Action OPERABLE

1. Gross Radioactivity Monitors Providing Automatic Termination of Release
a. Liquid Radwaste Effluent Line (0-RM-90-122) 1 30
b. Steam Generator Blowdown Effluent Line 1 31 (1,2-RM-90-120A,121 A)
c. Condensate Demineralizer Effluent Line 1 30 (0-RM-90-225A)
2. Gross Radioactivity Monitors
a. Essential Raw Cooling Water Effluent Header** 32 (0-RM-90-133A,-134A,-140A,-141A)
b. Turbine Building Sump Effluent Line 31 (0-RM-90-212A)
3. Flow Rate Measurement Devices
a. Liquid Radwaste Effluent Line 1 33 (0-FI-77-42)
b. Steam Generator Blowdown Effluent Line 1 33 (1,2-FI-1 5-44, 1,2-F-1 5-43)
c. Condensate Demineralizer Effluent Line 1 33 (0-FR-14-456, 0-F-14-185, 0-F-14-192)
d. Cooling Tower Blowdown Effluent Line 1 33 (0-LS-27-225)
4. Tank Level Indicating Devices
a. Condensate Storage Tank (0-L-2-230, 0-L-2-233) ] 1 34
5. Continuous Composite Sampler and Sample Flow Monitor
a. Condensate Demineralizer Regenerant Effluent Line 1 35 (0-FI-14-466)
    • Requires minimum of 1 Channel/Header to be OPERABLE.

SQN ODCM Revision 47 Page 15 of 168 Table 1.1-1 RADIOACTIVE LIQUID EFFLUENT MONITORING INSTRUMENTATION (Page 2 of 2) TABLE NOTATION ACTION 30 - With the number of channels OPERABLE less than required by the Minimum Channels OPERABLE requirement, effluent releases may continue provided that prior to initiating a release:

a. At least two independent samples are analyzed in accordance with ODCM Control 1.2.1.1, and
b. At least two technically qualified members of the Facility Staff independently verify the release rate calculations and discharge line valving; Otherwise, suspend release of radioactive effluents via this pathway.

ACTION 31 - With the number of channels OPERABLE less than required by the Minimum Channels OPERABLE requirement, effluent releases via this pathway may continue provided grab samples are analyzed for principal gamma emitters in accordance with SR 2.2.1.1.1 and 2.2.1.1.2.

a. At least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> when the specific activity of the secondary coolant is greater than or equal to 0.01 giCi/g DOSE EQUIVALENT 1-131.
b. At least once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> when the specific activity of the secondary coolant is less than 0.01 gCi/g DOSE EQUIVALENT 1-131.

ACTION 32 - With the number of channels OPERABLE less than required by the Minimum Channels OPERABLE requirement, effluent releases via this pathway may continue provided that, at least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />, grab samples are collected and analyzed for principal gamma emitters at a limit of detection of at least 5.0x10-7 jiCi/ml.

ACTION 33 - With the number of channels OPERABLE less than required by the Minimum Channels OPERABLE requirement, effluent releases via this pathway may continue provided the flow rate is estimated at least once per 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> during actual releases. Pump curves may be used to estimate flow.

ACTION 34 - With the number of channels OPERABLE less than required by the Minimum Channels OPERABLE requirement, liquid additions to this tank may continued provided the tank liquid level is estimated during all liquid additions to the tank.

ACTION 35 - With the number of channels OPERABLE less than required by the Minimum Channels OPERABLE requirement, effluent releases via this pathway may continue provided representative batch samples of each tank to be released are taken prior to release and composited for analysis according to Table 2.2-1, footnote g.

SQN ODCM Revision 47 Page 16 of 168 Table 2.1 RADIOACTIVE LIQUID EFFLUENT MONITORING INSTRUMENTATION SURVEILLANCE REQUIREMENTS (Page 1 of 2) 1 1 SOURCE/ CHANNEL CHANNEL CHANNEL SENSOR CALIBRA- FUNCTIONAL Instrument CHECK CHECK TION TEST

1. Gross Beta or Gamma Radioactivity Monitors Providing Alarm and Automatic Termination of Release
a. Liquid Radwaste Effluent Line D P R(3) Q(1)

(0-RM-90-122)

b. Steam Generator Blowdown Effluent D M R(3) Q(5)

Line (1,2-RM-90-120A,121A)

c. Condensate Demineralizer Effluent D M R(3) Q(5)

Line (0-RM-90-225A)

2. Gross Beta or Gamma Radioactivity Monitors Providing Alarm But Not Providing Automatic Termination of Release
a. Essential Raw Cooling Water Effluent D M R(3) Q(2)

Line (0-RM-90-133A,134A,140A,141A)

b. Turbine Building Sump Effluent Line D M R(3) Q(2)

(0-RM-90-212A)

3. Flow Rate Measurement Devices
a. Liquid Radwaste Effluent Line D(4) N.A. R Q (0-FI-77-42) _ l
b. Steam Generator Blowdown Effluent D(4) N.A. R Q Line (1,2-FI-1 5-44, 1,2-F-1 5-43)
c. Condensate Demineralizer Effluent D(4) N.A. R Q Line (0-FR-14-456,0-F-14-192, 0-F-14-185)
d. Cooling Tower Blowdown Effluent Line D(4) N.A. R Q (0-L-27-225)
4. Tank Level Indicating Devices

[a. Condensate Storage Tank l D* l N.A. l R Q I (0-L-2-230, O-L-2-233) I l l l

5. Continuous Composite Sampler and Sample Flow Monitor

[a. Condensate Demineralizer Regenerant P N.A. 7 R N.A.

Effluent Line (0-FI-14-466) II l l l

SQN ODCM Revision 47 Page 17 of 168 Table 2.1-1 RADIOACTIVE LIQUID EFFLUENT MONITORING INSTRUMENTATION SURVEILLANCE REQUIREMENTS (Page 2 of 2)

  • During liquid additions to the tank.

(1) The CHANNEL FUNCTIONAL TEST shall also demonstrate that automatic isolation of this pathway and control room alarm annunciation occurs if any of the following conditions exists:

1. Instrument indicates measured levels above the alarm/trip setpoint.
2. Circuit failure.
3. Downscale failure.

(2) The CHANNEL FUNCTIONAL TEST shall also demonstrate that control room alarm annunciation occurs if any of the following conditions exists:

1. Instrument indicates measured levels above an alarm setpoint.
2. Circuit failure.
3. Downscale failure.

(3) The initial CHANNEL CALIBRATION shall be performed using one or more of the reference standards certified by the National Institute of Standards and Technology (NIST) or using standards that have been obtained from suppliers that participate in measurement assurance activities with NIST. These standards shall permit calibrating the system over its intended range of energy and measurement range. For subsequent CHANNEL CALIBRATION, sources that have been related to the initial calibration shall be used.

(4) CHANNEL CHECK shall consist of verifying indication of flow during periods of release.

CHANNEL CHECK shall be made at least once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> on days on which continuous periodic, or batch releases are made.

(5) The CHANNEL FUNCTIONAL TEST shall also demonstrate that automatic isolation of this pathway and control room alarm annunciation occurs if any of the following conditions occur:

1. Instrument indicates measured levels above an alarm/trip setpoint.
2. Circuit failure.

The CHANNEL FUNCTIONAL TEST shall also demonstrate that control room annunciation occurs if the following condition occurs:

1. Downscale failure.

SQN ODCM Revision 47 Page 18 of 168 1/2 CONTROLS AND SURVEILLANCE REQUIREMENTS 112.1 INSTRUMENTATION 1/2.1.2 RADIOACTIVE GASEOUS EFFLUENT MONITORING INSTRUMENTATION CONTROLS 1.1.2 In accordance with SQN Technical Specification 6.8.4.f.1, the radioactive gaseous effluent monitoring instrumentation channels shown in Table 1.1-2 shall be OPERABLE with their alarm/trip setpoints set to ensure that the limits of ODCM Control 1.2.2.1 are not exceeded. The alarm/trip setpoints of these channels shall be determined in accordance with the methodology and parameters in ODCM Section 7.1.

APPLICABILITY: As shown in Table 1.1-2.

ACTION:

a. With a radioactive gaseous effluent monitoring instrumentation channel alarm/trip setpoint less conservative than required above, without delay suspend the release of radioactive gaseous effluents monitored by the affected channel, declare the channel inoperable, or change the setpoint so it is acceptably conservative.
b. With less than the minimum number of radioactive gaseous effluent monitoring instrumentation channels OPERABLE take the action shown in Table 1.1-2. Exert best efforts to return the instruments to OPERABLE status within 30 days and, if unsuccessful, explain in the next Annual Radioactive Effluent Report why the inoperability could not be corrected within 30 days.
c. The provisions of Controls 1.0.3 and 1.0.4 are not applicable. Report all deviations in the Annual Radioactive Effluent Release Report.

SURVEILLANCE REQUIREMENTS 2.1.2 Each radioactive gaseous effluent monitoring instrumentation channel shall be demonstrated OPERABLE by performance of the CHANNEL CHECK, SOURCE/SENSOR CHECK, CHANNEL CALIBRATION, and CHANNEL FUNCTIONAL TEST operations at the frequencies shown in Table 2.1-2.

SQN ODCM Revision 47 Page 19 of 168 Table 1.1-2 RADIOACTIVE GASEOUS EFFLUENT MONITORING INSTRUMENTATION (Page 1 of 2)

Minimum Channels Instrument OPERABLE Applicability Action

1. WASTE GAS DISPOSAL SYSTEM
a. Noble Gas Activity Monitor (0-RM-90-118A) 1 *** 40
b. Waste Decay Tanks Effluent Flow Rate 1* 41 Measuring Device (0-FI-77-230)
2. CONDENSER VACUUM EXHAUST SYSTEM
a. Noble Gas Activity Monitor (1,2-RM-90-99,119) 1 *** 42
b. Vent Flow Rate Monitor (1,2-F-2-256,257) 1 41
3. SHIELD BUILDING EXHAUST SYSTEM
a. Noble Gas Vent Rate Activity Monitor 1** 43 (1,2-R-90-400_,Eff)
b. Iodine Sampler (1,2-FLT-90-402A or 402B) 1 *** 43,44
c. Particulate Sampler (1,2-FLT-90-402A or 402B) 1 *** 43,44
d. Vent Flow Rate Monitor (1,2-F-90-400),(1,2-RI- 1** 41,43

_ 90-400 Monitor Item 029 or 1,2-FI-90-400) _

e. Sampler Flow Rate Monitor (1,2-RI-90-400 1 45 Monitor Item 028 or 1,2-FI-90-400A)
4. AUXILIARY BUILDING VENTILATION SYSTEM
a. Noble Gas Activity Monitor (0-RM-90-101B) 1 42
b. Iodine Sampler (0-FLT-90-101) 1
  • 44
c. Particulate Sampler (0-FLT-90-101) 1 44
d. Vent Flow Rate Monitor 0-F-30-5174A 1
  • 41

____ (0-F-30-1174)*****

e. Sampler Flow Rate Monitor (0-FIS-90-101) 1 45
5. SERVICE BUILDING VENTILATION SYSTEM
a. l Noble Gas Activity Monitor (0-RM-90-132B) i1 I* l 42
b. l Vent Flow Rate Monitor ( 0-F-90-5132A) 1
  • 41
  • At all ti mes.
    • Operability of shield building noble gas vent rate activity monitor (Eff) requires both vent flow rate and "Low Rng" radiation inputs since the high radiation alarm is only on the effluent channel (piCi/s). When the vent flow rate monitor is inoperable only the 'Low Rng" radiation monitor is still capable of providing noble gas indication. It's associated malfunction alarm on M-30 will alert Operations to any secondary failures such as loss of sample flow or detector failure. Therefore as long as the "Low Rng' is selected and the malfunction alarm is monitored RE-90-400 can be used to meet ODCM Noble gas and Particulate/Iodine sampler requirements. Mid or High range channels do not have any ODCM requirements. The vent flow rate monitor can be OPERABLE without the noble gas vent rate activity monitor.

During exhaust system operation.

        • 1,2-F-2-256 is the low range flow element (0-100 cfm). 1,2 -F-2-257 is a mid (0-1000) cfm flow element which should only be used for abnormal conditions.
          • New UNID will be in effect following completion of DCN D20744.

SQN ODCM Revision 47 Page 20 of 168 Table 1.1-2 RADIOACTIVE GASEOUS EFFLUENT MONITORING INSTRUMENTATION (Page 2 of 2)TABLE NOTATION ACTION 40 - With the number of channels OPERABLE less than required by the Minimum Channels OPERABLE requirement, the contents of the tank(s) may be released to the environment provided that prior to initiating the release:

a. At least two independent samples of the tank's contents are analyzed, and
b. At least two technically qualified members of the Facility Staff independently verify the release rate calculations and discharge valve lineup; Otherwise, suspend release of radioactive effluents via this pathway.

ACTION 41 - With the number of channels OPERABLE less than required by the Minimum Channels OPERABLE requirement, effluent releases via this pathway may continue provided the flow rate is estimated at least once per 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />.

ACTION 42 - With the number of channels OPERABLE less than required by the Minimum Channels OPERABLE requirement, effluent releases via this pathway may continue provided grab samples are taken at least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and these samples are analyzed for noble gas activity.

ACTION 43 - Vent Flow Rate only InoDerable - With any inoperable vent flow monitor on a discharge pathway where a fan is operating (Purge A, Purge B, ABGTS, or EGTS),

effluent release may continue provided: (a) "Low Rng" on RI-90-400 is selected instead of "Eff"; and (b) at least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> associated instrument malfunction is verified not annunciated; and (c) a reading from "Low Rng" on RE-90-400 is obtained at least once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />. The High Rad alarm on M-30 will not be operable under this alignment. Also Action 41 must be complied with.

Radiation Monitor Inoperable - With the low range channel inoperable, effluent releases may continue provided grab samples are taken at least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and these samples are analyzed for noble gas activity. Also Action 44 must be complied with.

ACTION 44 - With the number of channels OPERABLE less than required by the Minimum Channels OPERABLE requirement, effluent releases via the affected pathway may continue provided that within 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> after the channel has been declared inoperable samples are continuously collected with auxiliary sampling equipment as required in Table 2.2-2. Also Action 45 must be complied with.

ACTION 45 - With the number of channels OPERABLE less than required by minimum channels OPERABLE requirement, effluent releases via this pathway may continue provided the sampler flow rate is verified at least once per 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br />.

SQN ODCM Revision 47 Page 21 of 168 Table 2.1-2 RADIOACTIVE GASEOUS EFFLUENT MONITORING INSTRUMENTATION SURVEILLANCE REQUIREMENTS (Page 1 of 2)

SOURCE/ CHANNEL CHANNEL CHANNEL SENSOR CALIBRA- FUNCTIONAL oble Uas Activity N (1,2-RM-90-99,119' b.Vent Flow Rate Monitor (1,2-F-2-256,257)

3. SHIELD BUILDING EXHAUST SYSTEM
a. Noble Gas Vent Rate Activity D Monitor (1,2-R-90-400A,Eff)
b. Iodine Sampler W

\(1.2-FLT-90-40,

c. Particulate Sampler (1,2-FLT-90-402A or 402B' 9r 90-400) 101 ine Sampler

)-FLT-90-101'

c. Particulate Sampler (0-FLT-90-101)
d. Vent Flow Rate Monitor 0-F-30-5174A (0-F-30-174:
e. Sampler Flow Rate Monitor (0-FIS-90-101)
5. SERVICE BUILDING VENTILATI'
a. Noble Gas Activi (0-RM-90-132B) lent Flow Rate 0-F-90-5132A)
  • New UNID will be in effect following completion of DCN D20744.

SQN ODCM Revision 47 Page 22 of 168 11 Table 2.1-2 RADIOACTIVE GASEOUS EFFLUENT MONITORING INSTRUMENTATION SURVEILLANCE REQUIREMENTS (Page 2 of 2) TABLE NOTATION

  • At all times.

During shield building exhaust system operation.

During waste gas releases.

(1) The CHANNEL FUNCTIONAL TEST shall also demonstrate that automatic isolation of this pathway and control room alarm annunciation occurs if any of the following conditions exists:

1. Instrument indicates measured levels above the alarm/trip setpoint.
2. Circuit failure.
3. Downscale failure.

(2) The CHANNEL FUNCTIONAL TEST shall also demonstrate that control room alarm annunciation occurs if any of the following conditions exists:

1. Instrument indicates measured levels above an alarm setpoint.
2. Circuit failure.
3. Downscale failure.

For the auxiliary building ventilation system, at least once every 18 months, the CHANNEL FUNCTIONAL TEST shall also demonstrate automatic isolation of this pathway if the instrument indicates measured levels above the alarm/trip setpoint.

(3) The initial CHANNEL CALIBRATION shall be performed using one or more of the reference standards certified by the National Institute of Standards and Technology (NIST) using standards that have been obtained from suppliers that participate in measurement assurance activities with NIST. These standards shall permit calibrating the system over its intended range of energy and measurement range. For subsequent CHANNEL CALIBRATION, sources that have been related to the initial calibration shall be used.

(4) The SOURCE/SENSOR CHECK for the Condenser Vacuum Exhaust Monitor will be accomplished using an LED sensor check source or a radioactive source.

(5) Applicable only to in-service monitor. Either 99 or 119 monitor will be in service for each unit.

SQN ODCM Revision 47 Page 23 of 168 1/2 CONTROLS AND SURVEILLANCE REQUIREMENTS 1(2.2 RADIOACTIVE EFFLUENTS 112.2.1 LIQUID EFFLUENTS 1/2.2.1.1 CONCENTRATION CONTROLS 1.2.1.1 In accordance with SQN Technical Specifications 6.8.4.f.2 and 3, the concentration of radioactive material released through the diffuser piping to UNRESTRICTED AREAS (see Figure 3.1) shall be limited at all times to ten times the concentrations specified in 10 CFR Part 20, Appendix B, Table 2, Column 2 for radionuclides other than dissolved or entrained noble gases. For dissolved or entrained noble gases, the concentration shall be limited to 2X10- 4 jlCi/mI total activity.

APPLICABILITY: At all times.

ACTION:

a. With the concentration of radioactive material released to UNRESTRICTED AREAS exceeding the above limits, without delay, restore the concentration to within the above limits.
b. If samples or analyses required by Table 2.2-1 are not performed, report these in the next Annual Radioactive Effluent Release Report with an explanation why they were missed and what actions were taken to prevent reoccurrence.
c. The provisions of Controls 1.0.3 and 1.0.4 are not applicable.

SURVEILLANCE REQUIREMENTS 2.2.1.1.1 Radioactive liquid wastes shall be sampled and analyzed according to the sampling and analysis program of Table 2.2-1.

2.2.1.1.2 The results of the radioactivity analysis shall be used in accordance with the methods in ODCM Section 6.1 to assure that the concentration at the point of release is maintained within the limits stated above.

SQN ODCM Revision 47 Page 24 of 168 Table 2.2-1 RADIOACTIVE LIQUID WASTE SAMPLING AND ANALYSIS PROGRAM (Page 1 of 3)

Minimum Lower Limit of Sampling Analysis Type of Activity Detection (LLD)

Liquid Release Type Frequency Frequency Analysis (,4 Ci/ml)a A. Batch Waste Release Tanks P P Principal Garnma 5x1 0-

1. Cask Decontamination Each Batch Each Batch Emitters Tank
2. Laundry Tanks (2) 1-131 1x1o-
3. Chemical Drain Tank 5
4. Monitor Tank P M Dissolved/ 1x10-One Batch/M Entrained Gases (Gamma Emitters) 5 P M H-3 1x10 Each Batch Compositeb Gross Alpha 1x10-7 P Q Each Batch Compositeb Sr-89, Sr-90 5x10-8 Fe-55 1x10-6 B. Continuous Releasese D W Principal Gamma 5x10-
1. Steam Generator Grab Sample Compositec Emitters f Blowdownh
2. Turbine Building Sumph M M 1-131 1x10-5 Grab Sample Dissolved/ 1x10-Entrained Gases (Gamma Emitters) 5 D M H-3 1x10-7 Grab Sample Compositec Gross Alpha 1x10-D Q 8 Grab Sample Compositec Sr-89, Sr-90 5x10-Fe-55 1x10-C. Periodic Continuous Continuous W Principal Garma 5x10-Releasesesh CompositeC Emitters
1. Non-Reclaimable Waste Tank M9 M 1-131 1x10-
2. High Crud Tanks (2) Grab Sample Dissolved/ 1x10-
3. Neutralizer Tank Entrained Gases (Gamma Emitters)

Continuous9 M H-3 x10-7 Compositec Gross Alpha 1x10-Continuous9 Q Sr-89, Sr-90 5x10-8 Compositec Fe-55 1x10-

SQN ODCM Revision 47 Page 25 of 168 Table 2.2-1 RADIOACTIVE LIQUID WASTE SAMPLING AND ANALYSIS PROGRAM (Page 2 of 3) TABLE NOTATION a The LLD is defined for the purpose of these specifications as the smallest concentration of radioactive material in a sample that will yield a net count above system background that will be detected with 95% probability with only a 5% probability of falsely concluding that a blank observation represents a "real" signal.

For a particular measurement system (which may include radiochemical separation):

4.66s b LLD =

E V 2.22x106 Y exp (-mot)

Where:

LLD is the "a priori" lower limit of detection as defined above in microcurie per unit mass or volume, Sb is the standard deviation of the background counting rate or of the counting rate of a blank sample as appropriate (as counts per minute),

E is the counting efficiency as counts per disintegration, V is the sample size in units of mass or volume, 2.22x10 6 is the number of disintegrations per minute per microcurie, Y is the fractional radiochemical yield (when applicable),

0 is the radioactive decay constant for the particular radionuclide, and Elt for plant effluents is the elapsed time between midpoint of sample collection and time of counting (midpoint).

It should be recognized that the LLD is defined as an a priori (before the fact) limit representing the capability of a measurement system and not an a posteriori (after the fact) limit for a particular measurement.

b A composite sample is one in which the quantity of liquid sampled is proportional to the quantity of liquid waste discharged and in which the method of sampling employed results in a specimen which is representative of the liquids released.

c Prior to analyses, all samples taken for the composite shall be thoroughly mixed in order for the composite sample to be representative of the effluent release.

SQN ODCM Revision 47 Page 26 of 168 Table 2.2-1 RADIOACTIVE LIQUID WASTE SAMPLING AND ANALYSIS PROGRAM (Page 3 of 3) TABLE NOTATION d A batch release is the discharge of liquid wastes of a discrete volume. Prior to sampling for analyses, each batch shall be isolated, and then thoroughly mixed, by the method described in ODCM Section 6.1.1, to assure representative sampling.

e A continuous release is the discharge of liquid wastes of a nondiscrete volume; e.g., from a volume or system that has an input flow during the continuous release.

f The principal gamma emitters for which the LLD specification applies exclusively are the following radionuclides: Mn-54, Fe-59, Co-58, Co-60, Zn-65, Mo-99, Cs-134, Cs-137, Ce-141.

Ce-144 shall also be measured with an LLD of 5x10-6 . This list does not mean that only these nuclides are to be detected and reported. Other peaks which are measurable and identifiable, together with the above nuclides, shall also be identified and reported.

g Releases from these tanks are continuously composited during releases. With the composite sampler or the sampler flow monitor inoperable, the sampling frequency shall be changed to require representative batch samples from each tank to be released to be taken prior to release and manually composited for these analyses.

h Applicable only during periods of primary to secondary leakage or the release of radioactivity as detected by the effluent radiation monitor provided the radiation monitor setpoint is set to alarm if activity in the stream exceeds a routine normal background, or compensatory requirements associated with applicable inoperable monitors are met.

SQN ODCM Revision 47 Page 27 of 168 1/2 CONTROLS AND SURVEILLANCE REQUIREMENTS 112.2 RADIOACTIVE EFFLUENTS 1/2.2.1 LIQUID EFFLUENTS 1/2.2.1.2 DOSE CONTROLS 1.2.1.2 In accordance with SQN Technical Specification 6.8.4.f.4 and 5, the dose or dose commitment to a MEMBER OF THE PUBLIC from radioactive materials in liquid effluents released to UNRESTRICTED AREAS shall be limited from each reactor unit:

a. During any calendar quarter to less than or equal to 1.5 mrem to the total body and to less than or equal to 5 mrem to any organ, and
b. During any calendar year to less than or equal to 3 mrem to the total body and to less than or equal to 10 mrem to any organ.

APPLICABILITY: At all times.

ACTION:

a. With the calculated dose from the release of radioactive materials in liquid effluents exceeding any of the above limits, prepare and submit to the Commission within 30 days, pursuant to ODCM Administrative Control 5.4, a Special Report which identifies the cause(s) for exceeding the limit(s) and defines the corrective actions that have been taken to reduce the releases and the proposed corrective actions to be taken to assure that subsequent releases will be in compliance with the above limits. This Special Report shall also include (1) the results of radiological analyses of the drinking water source and (2) the radiological impact on finished drinking water supplies with regard to the requirements of 40 CFR 141 (applicable only if drinking water supply is taken from the receiving water body within three miles downstream of the plant discharge).
b. The provisions of Controls 1.0.3 and 1.0.4 are not applicable.

SURVEILLANCE REQUIREMENTS 2.2.1.2 Cumulative dose contributions from liquid effluents for the current calendar quarter and current calendar year shall be determined in accordance with the methodology and parameters in ODCM Section 6.3 at least once per 31 days.

SQN ODCM Revision 47 Page 28 of 168 112 CONTROLS AND SURVEILLANCE REQUIREMENTS 112.2 RADIOACTIVE EFFLUENTS 1/2.2.1 LIQUID EFFLUENTS 1/2.2.1.3 LIQUID RADWASTE TREATMENT SYSTEM CONTROLS 1.2.1.3 In accordance with SQN Technical Specification 6.8.4.f.6, the liquid radwaste treatment system shall be used to reduce the radioactive materials in liquid wastes prior to their discharge when the projected doses due to the liquid effluent to UNRESTRICTED AREAS (see Figure 3.1) would exceed 0.06 mrem per reactor unit to the total body or 0.2 mrem per reactor unit to any organ in a 31-day period.

APPLICABILITY: At all times.

ACTION:

a. With radioactive liquid waste being discharged without treatment and in excess of the above limits, prepare and submit to the Nuclear Regulatory Commission within 30 days pursuant to ODCM Administrative Control 5.4, a Special Report which includes the following information:
1. Identification of the inoperable equipment or subsystems and the reason for inoperability,
2. Action(s) taken to restore the inoperable equipment to OPERABLE status, and
3. Summary description of action(s) taken to prevent a recurrence.
b. The provisions of Controls 1.0.3 and 1.0.4 are not applicable.

SURVEILLANCE REQUIREMENTS 2.2.1.3 Doses due to liquid releases from each unit to UNRESTRICTED AREAS shall be projected at least once per 31 days, in accordance with the methodology and parameters in ODCM Section 6.5.

SQN ODCM Revision 47 Page 29 of 168 112 CONTROLS AND SURVEILLANCE REQUIREMENTS 112.2 RADIOACTIVE EFFLUENTS 112.2.2 GASEOUS EFFLUENTS 112.2.2.1 DOSE RATE CONTROLS 1.2.2.1 In accordance with SQN Technical Specification 6.8.4.f.7, the dose rate at any time due to radioactive materials released in gaseous effluents to areas at or beyond the UNRESTRICTED AREA BOUNDARY (see Figure 3.1) shall be limited to the following:

a. For noble gases: Less than or equal to a dose rate of 500 mrem/yr to the total body and less than or equal to a dose rate of 3000 mrem/yr to the skin, and
b. For Iodine-131, Iodine-133, tritium, and for all radionuclides in particulate form with half-lives greater than 8 days: Less than or equal to a dose rate of 1500 mrem/yr to any organ.

APPLICABILITY: At all times.

ACTION:

a. With dose rate(s) exceeding the above limits, without delay restore the release rate to within the above limit(s).
b. If samples or analyses required by Table 2.2-2 are not performed, report these in the next Annual Radioactive Effluent Release Report with an explanation why they were missed and what actions were taken to prevent reoccurrence.
c. The provisions of Controls 1.0.3 and 1.0.4 are not applicable.

SURVEILLANCE REQUIREMENTS 2.2.2.1.1 The dose rate due to noble gases in gaseous effluents shall be determined to be within the above limits in accordance with the methodology and parameters in ODCM Section 7.2.3, and 2.2.2.1.2The dose rate due to Iodine-131, Iodine-133, tritium, and for all radionuclides in particulate form with half-lives greater than 8 days in gaseous effluents shall be determined to be within the above limits in accordance with the methodology and parameters in ODCM Section 7.2.4 and by obtaining representative samples and performing analyses in accordance with the sampling and analysis program specified in Table 2.2-2.

SQN ODCM Revision 47 Page 30 of 168 Table 2.2-2 RADIOACTIVE GASEOUS WASTE MONITORING SAMPLING AND ANALYSIS PROGRAM (Page 1 of 3)

Lower Limit of Sampling Minimum Analysis Detection (LLD)

Gaseous Release Type Frequency Frequency Type of Activity Analysis (jjCilml)a A. Waste Gas Storage P P Principal Gamma 1x10-4 Tank Each Tank Each Tank Emitters9 Grab B. Containment Pi pi Principal Gamma 1x10-4 I

1. PURGE Each PURGE Each PURGE Emittersg Grab Sample H-3 1x10-6
2. Vent Wi Wi Principal Gamma 1x10-4 Grab Sample Emittersg H-3 jx10-6 C. Noble Gases and M M Principal Gamma 1x10-4 Tritium Grab Sample Emitters9
1. Condenser Vacuum Exhausth H-3 1x10-6
2. Auxiliary Building Exhaustb,e
3. Service Bldg.

Exhaust

4. Shield Bldg.

Exhaustbch D. Iodine and Particulates Continuous Wd 1-131 1xi1-12

1. Auxiliary Building Samplerf Charcoal Sample Exhaust
2. Shield Building Continuous Wd Principle Gamma 1x10-<

Exhaust h Samplerf Particulate Emittersg Sample (1-131, Others)

M Continuous Composite Gross Alpha x1 0-11 Sampler Particulate Sampler Q

Continuous Composite Sr-89, Sr-90 1x10-11 Samplerf Particulate Sample E. Noble Gases Continuous Noble Gas Noble Gases 1x10-6 All Release types Monitorf Monitor Gross Beta or Gamma as listed in C

SQN ODCM Revision 47 Page 31 of 168 Table 2.2-2 (Page 2 of 3)

RADIOACTIVE GASEOUS WASTE MONITORING SAMPLING AND ANALYSIS PROGRAM TABLE NOTATION a The LLD is defined, for the purpose of these Controls, as the smallest concentration of radioactive material in a sample that will yield a net count above system background that will be detected with 95% probability with only a 5% probability of falsely concluding that a blank observation represents a "real" signal.

For a particular measurement system (which may include radiochemical separation):

4.66Sb LLD = -- - ----------------

E V 2.22x106 Y exp (-El St)

Where:

LLD is the "a priori" lower limit of detection as defined above in microcurie per unit mass or volume, Sb is the standard deviation of the background counting rate or of the counting rate of a blank sample as appropriate (as counts per minute),

E is the counting efficiency as counts per disintegration, V is the sample size in units of mass or volume, 2.22x10 6 is the number of disintegrations per minute per microcurie, Y is the fractional radiochemical yield (when applicable),

[1 is the radioactive decay constant for the particular radionuclide, and Pit is the elapsed time between midpoint of sample collection and time of counting (midpoint) in minutes.

It should be noted that the LLD is defined as an a priori (before the fact) limit representing the capability of a measurement system and not an a posteriori (after the fact) limit for a particular measurement.

b Sampling and analysis shall also be performed following shutdown, startup, or a thermal power change exceeding 15% of RATED THERMAL POWER within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> unless (1) analysis shows that the DOSE EQUIVALENT 1-131 concentration in the primary coolant has not increased more than a factor of 3 and (2) the containment noble gas activity monitor (RE-90-106 or RE-90-112) shows that the radioactivity has not increased by more than a factor of 3.

c Tritium grab samples shall be taken periodically when the refueling canal is flooded.

SQN ODCM Revision 47 Page 32 of 168 Table 2.2 RADIOACTIVE GASEOUS WASTE MONITORING SAMPLING AND ANALYSIS PROGRAM TABLE NOTATION (Page 3 of 3) d Samples shall be changed at least once per 7 days. Sampling shall also be performed at least once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> for at least 2 days following each shutdown from >15% RATED THERMAL POWER, startup of >15% RATED THERMAL POWER or THERMAL POWER change exceeding 15% of RATED THERMAL POWER in one hour. Only one set of samples will be required in a 24-hour period. When samples collected for <24 hours are analyzed, the corresponding LLD's may be increased by a factor of 10.

e Tritium grab samples shall be taken periodically from the ventilation exhaust from the spent fuel pool area, whenever spent fuel is in the spent fuel pool.

f The ratio of the sample flow rate to the sampled stream flow rate shall be known for the time period covered by each dose or dose rate calculation made in accordance with ODCM Sections 7.2, 7.3, and 7.4.

g The principal gamma emitters for which the LLD specification applies exclusively are the following radionuclides: Kr-87, Kr-88, Xe-133, Xe-133m, Xe-135, and Xe-138 for noble gases and Mn-54, Fe-59,1-131, Co-58, Co-60, Zn-65, Mo-99, Cs-134, Cs-137, Ce-141 and Ce-144 for particulate principal gamma emitters. This list does not mean that only these nuclides are to be detected and reported. Other gamma peaks which are measurable and identifiable, together with the above nuclides, shall also be analyzed and reported in the Annual Radioactive Effluent Release Report pursuant to ODCM Administrative Control 5.2.

h During releases via this exhaust system.

i PURGING - Applicable in MODES 1, 2, 3 and 4, the upper and lower compartments of the containment shall be sampled prior to PURGING. Prior to breaking containment integrity in MODE 5 or 6, the upper and lower compartments of the containment shall be sampled. The incore instrument room purge sample shall be obtained at the shield building exhaust between 20 and 25 minutes following initiation of the incore instrument room PURGE or at the peak of the discharge based on the radiation monitor response.

j VENTING - Applicable in MODES 1, 2, 3, and 4; the containment will be VENTED to the containment annulus and then to the auxiliary building via containment annulus fans. The lower containment compartment shall be sampled weekly and the lower containment radiation monitor response will be recorded daily when VENTING is to occur to account for the radioactivity being discharged from the VENTING process. The lower containment will be re-sampled when the reading on the lower containment radiation monitor (RE-90-106 or 112),

increases by 50% from the initial value. If the lower containment noble gas monitor (RE-90-106 or 112) is inoperable, noble gas grab samples may be used to perform this comparison.

SQN ODCM Revision 47 Page 33 of 168 112 CONTROLS AND SURVEILLANCE REQUIREMENTS 112.2 RADIOACTIVE EFFLUENTS 112.2.2 GASEOUS EFFLUENTS 1/2.2.2.2 DOSE - NOBLE GASES CONTROLS 1.2.2.2 In accordance with SQN Technical Specification 6.8.4.f.8, the air dose due to noble gases released in gaseous effluents from each reactor unit to areas at or beyond the UNRESTRICTED AREA BOUNDARY (see Figure 3.1) shall be limited to the following:

a. During any calendar quarter: Less than or equal to 5 mrad for gamma radiation and less than or equal to 10 mrad for beta radiation and
b. During any calendar year: Less than or equal to 10 mrad for gamma radiation and less than or equal to 20 mrad for beta radiation.

APPLICABILITY: At all times.

ACTION:

a. With the calculated air dose from radioactive noble gases in gaseous effluents exceeding any of the above limits, prepare and submit to the Nuclear Regulatory Commission within 30 days, pursuant to ODCM Administrative Control 5.4, a Special Report which identifies the cause(s) for exceeding the limit(s) and defines the corrective actions that have been taken to reduce the releases and the proposed corrective actions to be taken to assure that subsequent releases will be in compliance with the above limits.
b. The provisions of Controls 1.0.3 and 1.0.4 are not applicable.

SURVEILLANCE REQUIREMENTS 2.2.2.2 Cumulative dose contributions for the current calendar quarter and current calendar year for noble gases shall be determined in accordance with the methodology and parameters in ODCM Section 7.3 at least once per 31 days.

SQN ODCM Revision 47 Page 34 of 168 1/2 CONTROLS AND SURVEILLANCE REQUIREMENTS 1/2.2 RADIOACTIVE EFFLUENTS 112.2.2 GASEOUS EFFLUENTS 1/2.2.2.3 DOSE 131. 1-133. TRITIUM AND RADIONUCLIDES IN PARTICULATE FORM WITH HALF-LIVES GREATER THAN EIGHT DAYS CONTROLS 1.2.2.3 In accordance with SQN Technical Specification 6.8.4.f.9, the dose to a MEMBER OF THE PUBLIC from 1-131, 1-133, tritium and all radionuclides in particulate form with half-lives greater than 8 days in gaseous effluents released to areas at or beyond the UNRESTRICTED AREA BOUNDARY (see Figure 3.1) shall be limited to the following from each reactor unit:

a. During any calendar quarter: Less than or equal to 7.5 mrem to any organ and,
b. During any calendar year: Less than or equal to 15 mrem to any organ.

APPLICABILITY: At all times.

ACTION:

a. With the calculated dose from the release of 1-131, 1-133, tritium and all radionuclides in particulate form with half-lives greater than 8 days, in gaseous effluents exceeding any of the above limits, prepare and submit to the Nuclear Regulatory Commission within 30 days, pursuant to ODCM Administrative Control 5.4, a Special Report which identifies the cause(s) for exceeding the limit(s) and defines the corrective actions that have been taken to reduce the releases and the proposed corrective actions to be taken to assure that subsequent releases will be in compliance with the above limits.
b. The provisions of Controls 1.0.3 and 1.0.4 are not applicable.

SURVEILLANCE REQUIREMENTS 2.2.2.3 Cumulative dose contributions for the current calendar quarter and current calendar year for 1-131, 1-133, tritium and all radionuclides in particulate form with half-lives greater than 8 days shall be determined in accordance with the methodology and parameters in ODCM Section 7.4 at least once per 31 days.

SQN ODCM Revision 47 Page 35 of 168 1/2 CONTROLS AND SURVEILLANCE REQUIREMENTS 1/2.2 RADIOACTIVE EFFLUENTS 1/2.2.2 GASEOUS EFFLUENTS 1/2.2.2.4 GASEOUS RADWASTE TREATMENT CONTROLS 1.2.2.4 In accordance with SQN Technical Specification 6.8.4.f.5 and 6, the GASEOUS RADWASTE TREATMENT SYSTEM and the VENTILATION EXHAUST TREATMENT SYSTEM shall be used to reduce radioactive materials in gaseous waste prior to their discharge when the projected gaseous effluent doses due to gaseous effluent releases to areas at or beyond the SITE BOUNDARY (see Figure 3.1), when averaged over 31 days, would exceed 0.2 mrad per unit for gamma radiation, and 0.4 mrad per unit for beta radiation. The appropriate portions of the VENTILATION EXHAUST TREATMENT SYSTEM shall be used to reduce radioactive materials in gaseous waste prior to their discharge when the projected doses due to gaseous effluents to areas at or beyond the UNRESTRICTED AREA BOUNDARY (See Figure 3.1) when averaged over 31 days would exceed 0.3 mrem per unit to any organ.

ACTION:

a. With the radioactive gaseous waste being discharged without treatment for more than 31 days and in excess of the above limits, prepare and submit to the Commission within 30 days, pursuant to ODCM Administrative Control 5.4, a Special Report which includes the following information:
1. Identification of the inoperable equipment or subsystems and the reason for inoperability.
2. Action(s) taken to restore the inoperable equipment to OPERABLE status.
3. Summary description of action(s) taken to prevent a recurrence.
b. The provisions of Controls 1.0.3 and 1.0.4 are not applicable.

SURVEILLANCE REQUIREMENTS 2.2.2.4 Doses due to gaseous releases from the site shall be projected at least once per 31 days, in accordance with the methodology and parameters in ODCM Section 7.5.

SQN ODCM Revision 47 Page 36 of 168 112 CONTROLS AND SURVEILLANCE REQUIREMENTS 1/2.2 RADIOACTIVE EFFLUENTS 112.2.3 TOTAL DOSE CONTROLS 1.2.3 In accordance with SQN Technical Specification 6.8.4.f.10, the annual (calendar year) dose or dose commitment to any MEMBER OF THE PUBLIC, due to releases of radioactivity from uranium fuel cycle sources, shall be limited to less than or equal to 25 mrem to the total body or any organ (except the thyroid, which shall be limited to less than or equal to 75 mrem).

APPLICABILITY: At all times.

ACTION:

a. With the calculated doses from the release of radioactive materials in liquid or gaseous effluents exceeding twice the limits of ODCM Control 1.2.1.2, 1.2.2.2, or 1.2.2.3, calculations should be made to determine whether the above limits have been violated. If such is the case, prepare and submit a Special Report to the Director, Nuclear Reactor Regulation, U.S. Nuclear Regulatory Commission, Washington D.C. 20555, within 30 days, which defines the corrective action to be taken to reduce subsequent releases to prevent recurrence of exceeding the limits above. This Special Report, as defined in 10 CFR Part 20.2203, shall include an analysis which estimates the radiation dose to a MEMBER OF THE PUBLIC from uranium fuel cycle sources (including all effluent pathways and direct radiation) for a calendar year that includes the release(s) covered by this report. If the estimated dose(s) exceeds the above limits, and if the release condition resulting in violation of 40 CFR Part 190 has not already been corrected, the Special Report shall include a request for a variance in accordance with the provisions of 40 CFR Part 190 and include the specified information of Section 190.11(b). Submittal of the report is considered a timely request, and a variance is granted until the staff action on the request is complete.
b. The provisions of Controls 1.0.3 and 1.0.4 are not applicable.

SURVEILLANCE REQUIREMENTS 2.2.3 Cumulative dose contributions from liquid and gaseous effluents shall be determined in accordance with the methodology and parameters in ODCM Sections 6.3, 7.3, and 7.4.

SQN ODCM Revision 47 Page 37 of 168 1/2 CONTROLS AND SURVEILLANCE REQUIREMENTS 112.3 RADIOLOGICAL ENVIRONMENTAL MONITORING 112.3.1 MONITORING PROGRAM CONTROLS 1.3.1 The radiological environmental monitoring program shall be conducted as specified in Table 2.3-1.

APPLICABILITY: At all times.

ACTION:

a. With the radiological environmental monitoring program not being conducted as specified in Table 2.3-1, prepare and submit to the Commission, in the Annual Radiological Environmental Operating Report, a description of the reasons for not conducting the program as required and the plans for preventing a recurrence.
b. With the level of radioactivity in an environmental sampling medium exceeding the reporting levels of Table 2.3-2 when averaged over any calendar quarter, prepare and submit to the Commission within 30 days from the end of the affected quarter, pursuant to ODCM Administrative Control 5.4, a Special Report that identifies the cause(s) for exceeding the limit(s) and defines the corrective actions to be taken to reduce radioactive effluents so that the potential annual dose to a MEMBER OF THE PUBLIC is less than the calendar year limits of ODCM Controls 1.2.1.2, 1.2.2.2 and 1.2.2.3. When one or more of the radionuclides in Table 2.3-2 is detected in the sampling medium, this report shall be submitted if:

concentration(1) concentration(2)

+ +. .> 1.0 limit level(1) limit level(2)

When radionuclides other than those in Table 2.3-2 are detected and are the result of plant effluents, this report shall be submitted if the potential annual dose to a MEMBER OF THE PUBLIC from all radionuclides is equal to or greater than the calendar year limits of ODCM Controls 1.2.1.2, 1.2.2.2, and 1.2.2.3. This report is not required if the measured level of radioactivity was not the result of plant effluents; however, in such an event, the condition shall be reported and described in the Annual Radiological Environmental Operating Report.

SQN ODCM Revision 47 Page 38 of 168 1/2 CONTROLS AND SURVEILLANCE REQUIREMENTS 1/2.3 RADIOLOGICAL ENVIRONMENTAL MONITORING 1/2.3.1 MONITORING PROGRAM ACTION (CONTINUED):

c. With milk or fresh leafy vegetable samples unavailable from one or more of the sample locations required by Table 2.3-1, identify locations for obtaining replacement samples and add them to the radiological environmental monitoring program within 30 days. The specified locations from which samples were unavailable may then be deleted from the monitoring program. Pursuant to ODCM Administrative Control 5.1, identify the new locations for obtaining replacement samples in the Annual Radiological Environmental Operating Report. A revised figure(s) and table(s) for the ODCM reflecting the new location(s) shall be included in the next Annual Effluent Release Report pursuant to ODCM Administrative Control 5.2.
d. The provisions of Controls 1.0.3 and 1.0.4 are not applicable.

SURVEILLANCE REQUIREMENTS 2.3.1 The radiological environmental monitoring samples shall be collected pursuant to Table 2.3-1 from the locations given in the tables and figures given in ODCM Section 9.0 and shall be analyzed pursuant to the requirements of Table 2.3-1 and the detection capabilities required by Table 2.3-3.

SQN ODCM Revision 47 Page 39 of 168 Table 2.3-1 MINIMUM REQUIRED RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM (Page 1 of 2)

I Location of Samples* Frequency Analysis NE I Minimum of 5 W Radioiodine canister:

and locations Continuous sampler** Weekly 1-131 Particulates Particulate sampler: Analyze for gross beta activity > 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> following filter change.

Perform gamma isotopic analysis on each sample when gross beta activity is >

10 times the yearly mean of control samples Q: Perform gamma isotopic analysis on composite ( by location) samDle.

DIRECT RADIATION 35 to 40 locations Q Q: Gamma Dose with > 2 dosimeters for continuously measuring and recording dose rate at each location.

WATERBORNE Surface 2 locations M Gamma isotopic Composite*** sample Each composite sample Tritium analysis Ground 2 locations Q Gamma isotopic and tritium analyses of each sample.

Gross beta and gamma isotopic analysis Drinking Minimum of 1 M Q location Composite*** sample Tritium analysis M

2 locations Grab sample Gross beta and gamma isotopic analysis Shoreline Minimum of 2 S Gamma isotopic analysis Sediment locations from each sample.

locations

  • Sample locations are given in Table 9.1.
    • Continuous sampling with sample collection as required by dust loading, but at least once per 7 days.
      • Composite samples shall be collected by collecting an aliquot at intervals not exceeding 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />.

SQN ODCM Revision 47 Page 40 of 168 Table 2.3-1 MINIMUM REQUIRED RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM (Page 2 of 2)

Exposure Number and Sampling and Pathway Location of Collection Type and Frequency of and/or Samples* Frequency Analysis Sample INGESTION Milk Milk from 3 B**** Gamma isotopic and 1-131 locations. analysis of each sample.

Samples of broad leaf vegetation at offsite locations of highest D/Q if no milk samples are available.

Fish 2 locations One sample in Gamma isotopic analysis on season, or at least edible portions.

once per 184 days if not seasonal.

One sample representing a commercially important species and one sample representing a recreationally important species.

Food Products Minimum of 2 At time of harvest. Gamma isotopic analysis on locations One sample of each edible portions.

of the following or similar classes of food products, as available

1. Lettuce and/or cabbage
2. Corn
3. Beans
4. Tomatoes
        • When animals are on pasture, at least once per 31 days at other times.

SQN ODCM Revision 47 Page 41 of 168 Table 2.3-2 REPORTING LEVELS FOR RADIOACTIVITY CONCENTRATIONS IN ENVIRONMENTAL SAMPLES Analysis Water Airborne Fish Milk Food (pCi/L) Particulate (pCi/kg, wet) (pCi/L) Products or gases (pCi/kg, wet)

(pCi/m 3 )

H-3 2 x 104(a) N.A N.A N.A. N.A.

Mn-54 1x 103 N.A. 3 x 104 N.A. N.A.

Fe-59 4x102 N.A. 1 x 104 N.A. N.A.

Co-58 1 x 103 N.A. 3 x 104 N.A. N.A.

Co-60 3 x 102 N.A. 1 X 104 N.A. N.A.

Zn-65 3 x 102 N.A. 2 x 104 N.A. N.A.

Zr-Nb-95 4 x 102 N.A. N.A. N.A. N.A.

1-131 2 (b) 0.9 N.A. 3 lx1 02 Cs-1 34 30 10 1x10 3 60 1x103 Cs-137 50 20 2x10 3 70 2x10 3 Ba-La-140 2 x 102 N.A. N.A. 3 x 102 N.A.

(a) For drinking water samples. This is 40 CFR Part 141 value. If no drinking water pathway exists, a value of 30,000 pCi/L may be used.

(b) If no drinking water pathway exists, a value of 20 pCi/L may be used.

SQN ODCM Revision 47 Page 42 of 168 Table 2.3-3 MAXIMUM VALUES FOR THE LOWER LIMITS OF DETECTION (LLD)a~b (Page 1 of 2)

Airborne Particulate Fish Food Water or Gases (pCi/kg, Milk Products Sediment Analysis (pCi/L) (pCi/rn 3) wet) (pCi/L) (pCi/kg,wet) (pCi/kg,dry) gross beta 4 1x10-2 N.A. N.A N.A. N.A.

H-3 2000* N.A N.A N.A N.A. N.A.

Mn-54 15 N.A. 130 N.A. N.A. N.A.

Fe-59 30 N.A. 260 N.A. N.A. N.A.

Co-58,60 15 N.A. 130 N.A. N.A. N.A.

Zn-65 30 N.A. 260 N.A. N.A. N.A.

Zr-95 30 N.A. N.A. N.A. N.A. N.A.

Nb-95 15 N.A. N.A. N.A. N.A. N.A.

1-131 1** 7x1 0-2 N.A. 1 60 N.A.

Cs-1 34 15 5x1 0-2 130 15 60 150 Cs-1 37 18 6x1 0-2 150 18 80 180 Ba-140 60 N.A. N.A. 60 N.A. N.A.

La-140 15 N.A. N.A. 15 N.A. N.A.

  • If no drinking water pathway exists, a value of 3000 pCi/L may be used.
    • If no drinking water pathway exists, a value of 15 pCi/L may be used.

SQN ODCM Revision 47 Page 43 of 168 Table 2.3-3 MAXIMUM VALUES FOR THE LOWER LIMITS OF DETECTION (LLD)asb (Page 2 of 2) TABLE NOTATION a The LLD is defined, for the purpose of these Controls, as the smallest concentration of radioactive material in a sample that will yield a net count above system background that will be detected with 95% probability with only a 5% probability of falsely concluding that a blank observation represents a "real" signal.

For a particular measurement system (which may include radiochemical separation):

4 66

. Sb LLD = -----------

E V 2.22 Y exp(-Wt) where:

LLD is the "a priori" lower limit of detection as defined above in picocurie per unit mass or volume, Sb is the standard deviation of the background counting rate or of the counting rate of a blank sample as appropriate (as counts per minute),

E is the counting efficiency as counts per disintegration, V is the sample size in units of mass or volume, 2.22 is the number of disintegrations per minute per picocurie, Y is the fractional radiochemical yield (when applicable),

[1 is the radioactive decay constant for the particular radionuclide, and Lit for environmental samples is the elapsed time between sample collection (or end of the sample collection period) and time of counting.

It should be recognized that the LLD is defined as an a Priori (before the fact) limit representing the capability of a measurement system and not an a posteriori (after the fact) limit for a particular measurement. Analysis will be performed in such a manner that the stated LLDs will be achieved under routine conditions.

b Other peaks which are measurable and identifiable, together with the radionuclides above, shall be identified and reported.

SQN ODCM Revision 47 Page 44 of 168 112 CONTROLS AND SURVEILLANCE REQUIREMENTS 112.3 RADIOLOGICAL ENVIRONMENTAL MONITORING 1/2.3.2 LAND USE CENSUS CONTROLS 2.3.2 A Land Use Census shall be conducted and shall identify within a distance of 8 km (5 miles) the location in each of the 16 meteorological sectors of the nearest milk animal, the nearest residence, and the nearest gardena of greater than 50 m2 (500 ft2 )

producing fresh leafy vegetables.

aBroad leaf vegetation sampling of at least three different kinds of vegetation may be performed at the site boundary in each of two different direction sectors with the highest predicted D/Qs in lieu of the garden census. Specifications for broad leaf vegetation sampling in Table 2.3-1 shall be followed, including analysis of control samples.

APPLICABILITY: At all times.

ACTION:

a. With a Land Use Census identifying a location(s) that yields a calculated dose or dose commitment 20% greater than at a location from which doses are currently being calculated in ODCM Section 7.3 and 7.4 identify the new location(s) in the next Annual Radioactive Effluent Release Report pursuant to ODCM Administrative Control 5.2.
b. With a Land Use Census identifying a location(s) that yields a calculated dose or dose commitment (via the same pathway) 20% greater than at a location from which samples are currently being obtained in accordance with the requirements of ODCM Control 1.3.1, add the new location(s) within 30 days to the radiological environmental monitoring program given in ODCM Section 9.0, if samples are available. The sampling location(s), excluding the control station location, having the lowest calculated dose or dose commitment(s), via the same exposure pathway, may be deleted from this monitoring program after October 31 of the year in which this Land Use Census was conducted. Pursuant to ODCM Administrative Controls 5.2 and 5.3, submit in the next Annual Radioactive Effluent Release Report documentation for a change in the ODCM including a revised figure(s) and table(s) for the ODCM reflecting the new location(s) with the information supporting the change in sampling locations.
c. The provisions of Controls 1.0.3 and 1.0.4 are not applicable.

SQN ODCM Revision 47 Page 45 of 168 112 CONTROLS AND SURVEILLANCE REQUIREMENTS 112.3 RADIOLOGICAL ENVIRONMENTAL MONITORING 112.3.2 LAND USE CENSUS SURVEILLANCE REQUIREMENTS 2.3.2 The Land Use Census shall be conducted during the growing season at least once per 12 months using that information that will provide the best results, such as by a door-to-door survey, mail survey, telephone survey, aerial survey, or by consulting local agricultural authorities. The results of the Land Use Census shall be included in the Annual Radiological Environmental Operating Report pursuant to ODCM Administrative Control 5.1.

SQN ODCM Revision 47 Page 46 of 168 1/2 CONTROLS AND SURVEILLANCE REQUIREMENTS 112.3 RADIOLOGICAL ENVIRONMENTAL MONITORING 1/2.3.3 INTERLABORATORY COMPARISON PROGRAM CONTROLS 1.3.3 Analyses shall be performed on radioactive materials supplied as part of an Interlaboratory Comparison Program which has been approved by the Commission.

APPLICABILITY: At all times.

ACTION:

a. With analyses not being performed as required above, report the corrective actions being taken to prevent a recurrence to the Commission in the Annual Radiological Environmental Operating Report pursuant to ODCM Administrative Control 5.1.
b. The provisions of Controls 1.0.3 and 1.0.4 are not applicable.

SURVEILLANCE REQUIREMENTS 2.3.3 A summary of the results obtained as a part of the above required Interlaboratory Comparison Program and in accordance with the guidance below shall be included in the Annual Radiological Environmental Operating Report pursuant to ODCM Administrative Control 5.1.

SQN ODCM Revision 47 Page 47 of 168 BASES FOR SECTIONS 1.0 AND 2.0 CONTROLS AND SURVEILLANCE REQUIREMENTS NOTE The BASES contained in succeeding pages summarize the reasons for the Controls in Sections 1.0 and 2.0, but are not part of these Controls.

SQN ODCM Revision 47 Page 48 of 168 BASES INSTRUMENTATION 112.1.1 RADIOACTIVE LIQUID EFFLUENT MONITORING INSTRUMENTATION The radioactive liquid effluent instrumentation is provided to monitor and control, as applicable, the releases of radioactive materials in liquid effluents during actual or potential releases of liquid effluents. The alarm/trip setpoints for these instruments shall be calculated in accordance with the procedures in ODCM Section 6.2 to ensure that the alarm/trip will occur prior to exceeding ten times the limits of 10 CFR Part 20. The OPERABILITY and use of this instrumentation is consistent with the requirements of General Design Criteria 60, 63, and 64 of Appendix A to 10 CFR Part 50.

1/2.1.2 RADIOACTIVE GASEOUS EFFLUENT MONITORING INSTRUMENTATION The radioactive gaseous effluent instrumentation is provided to monitor and control, as applicable, the releases of radioactive materials in gaseous effluents during actual or potential releases of gaseous effluents. The alarm/trip setpoints for these instruments shall be calculated in accordance with the procedures in ODCM Section 7.1 to ensure that the alarm/trip will occur prior to exceeding ten times the limits of 10 CFR Part 20. The OPERABILITY and use of this instrumentation is consistent with the requirements of General Design Criteria 60, 63, and 64 of Appendix A to 10 CFR Part 50.

112.2 RADIOACTIVE EFFLUENTS 1/2.2.1.1 CONCENTRATION This Control is provided to ensure that the concentration of radioactive materials released at any time in liquid waste effluents to UNRESTRICTED AREAS will be less than ten times the concentration levels specified in 10 CFR Part 20, Appendix B, Table 2, Column 2. This limitation provides additional assurance that the levels of radioactive materials in bodies of water in UNRESTRICTED AREAS will result in exposures within (1) the Section II.A design objectives of Appendix I, 10 CFR 50, and (2) the limits of 10 CFR 20.1301(a)(1) to a MEMBER OF THE PUBLIC. The concentration limit for dissolved or entrained noble gases is based upon the assumption that Xe-135 is the controlling radioisotope and its MPC in air (submersion) was converted to an equivalent concentration in water using the methods described in International Commission of Radiological Protection (ICRP) Publication 2.

1(2.2.1.2 DOSE This Control is provided to implement the requirements of Sections II.A, III.A, and IV.A of Appendix 1,10 CFR Part 50. The requirement implements the guide set forth in Section II.A of Appendix I. The action statements provide the required operating flexibility and at the same time implement the guides set forth in Section IV.A of Appendix I to assure that the releases of radioactive materials in liquid effluents will be kept "as low as reasonable achievable." Also, for fresh water sites with drinking water supplies which can be potentially affected by plant operations, there is reasonable assurance that the operation of the facility will not result in radionuclide concentrations in the finished drinking water that are in excess of the requirements of 40 CFR Part 141. The dose calculations in ODCM Section 6.3 implement the requirements in Section III.A of Appendix I that conformance with the guides of Appendix I be shown by calculational procedures based on models and data, such that the actual exposure of a MEMBER OF THE PUBLIC through appropriately modeled pathways is unlikely to substantially underestimated. The equations specified in Section 6.3 for calculating the doses due to the actual release rates of radioactive

SQN ODCM Revision 47 Page 49 of 168 BASES 1/2.2.1.2 DOSE (continued) materials in liquid effluents are consistent with the methodology provided in Regulatory Guide 1.109, "Calculation of Annual Doses to Man from Routine Releases of Reactor Effluents for the Purposes of Evaluating Compliance with 10 CFR Part 50, Appendix I," Revision 1, October 1977 and Regulatory Guide 1.113, "Estimating Aquatic Dispersion of Effluents from Accidental and Routine Reactor Releases for the Purpose of Implementing Appendix I," April 1977.

This Control applies to the release of liquid effluents from each reactor at the site. For units with shared radwaste treatment systems, the liquid effluents from the shared systems are proportioned among the units sharing that system.

Compliance with this Control will be considered to demonstrate compliance with the 0.1 rem limit of 10 CFR Part 20.1301 (a)(1) per 56 FR 23374.

1/2.2.1.3 LIQUID RADWASTE TREATMENT SYSTEM The Control that the appropriate portions of this system be used when specified provides assurance that the releases of radioactive materials in liquid effluents will be kept "as low as reasonable achievable." This requirement implements the requirements of 10 CFR Part 50.36a, General Design Criteria 60 of 10 CFR Part 50 Appendix A, and the design objective given in 10 CFR Part 5OAppendix 1,Section II.D. The specified limits governing the use of appropriate portions of the liquid radwaste system were specified as a suitable fraction of the dose design objectives set forth in 10 CFR Part 50 Appendix I, Section II.A, for liquid effluents.

112.2.2.1 DOSE RATE This Control is provided to ensure that the external dose rate at any time at the UNRESTRICTED AREA BOUNDARY from gaseous effluents from all units on the site will be within the limits of 10 CFR Part 20.1301(a)(1) for UNRESTRICTED AREAS. The 500 mrem/year dose rate will ensure that the instantaneous dose rate is well below 2 mrem/hour. The limits provide reasonable assurance that radioactive material discharged in gaseous effluents will not result in the exposure of a MEMBER OF THE PUBLIC, to annual average concentrations exceeding the limits specified in of 10 CFR Part 20, Appendix B, Table 2. For MEMBERS OF THE PUBLIC who may at times be within the CONTROLLED or RESTRICTED AREA, the occupancy of the individual will be sufficiently low to compensate for any increase in the atmospheric diffusion factor above that for the UNRESTRICTED AREA BOUNDARY. The specified release rate limits restrict, at all times, the corresponding gamma and beta dose rates above background to an individual at or beyond the UNRESTRICTED AREA BOUNDARY to less than or equal to 500 mrem/year to the total body or to less than or equal to 3000 mrem/year to the skin. These release rate limits also restrict, at all times, the corresponding thyroid dose rate above background to an infant via the cow-milk-infant pathway to less than or equal to 1500 mrem/year for the nearest cow to the plant. This requirement applies to the release of gaseous effluents from all reactors at the site. For units with shared radwaste treatment systems, the gaseous effluents from the shared systems are proportioned among the units sharing that system.

SQN ODCM Revision 47 Page 50 of 168 BASES 112.2 RADIOACTIVE EFFLUENTS 112.2.2.2 DOSE - NOBLE GASES This requirement is provided to implement the requirements of 10 CFR Part 50 Appendix I, Sections II.B,III.A and IV.A. The requirement implements the guides set forth in Appendix I Section II.B Compliance with this Control will be considered to demonstrate compliance with the 0.1 rem limit of 10 CFR Part 20.1301(a)(1) per 56 FR 23374. The action to be taken provides the required operating flexibility and at the same time implements the guides set forth in Section IV.A of Appendix I to assure that the releases of radioactive material in gaseous effluents will be kept "as low as reasonably achievable." The surveillance implements the requirements in Section IIL.A of Appendix I that conformance with the guides of Appendix I be shown by calculational procedures based on models and data such that the actual exposure of a MEMBER OF THE PUBLIC through appropriately modeled pathways is unlikely to be substantially underestimated. The dose calculations established in ODCM Section 7.3 for calculating the doses due to the actual release rates of radioactive noble gases in gaseous effluents are consistent with the methodology provided in Regulatory Guide 1.109, "Calculation of Annual Doses to Man from Routine Releases of Reactor Effluents for the Purposes of Evaluating Compliance with 10 CFR Part 50, Appendix I," Revision 1, October 1977 and Regulatory Guide 1.1 11, "Methods for Estimating Atmospheric Transport and Dispersion of Gaseous Effluents in Routine Releases from Light-Water Cooled Reactors," Revision 1, July 1977. The ODCM equations provided for determining the air doses at the UNRESTRICTED AREA BOUNDARY are based upon the historical average atmospheric conditions.

1/2.2.2.3 DOSE 131.1-133. TRITIUM, AND RADIONUCLIDES IN PARTICULATE FORM WITH HALF-LIVES GREATER THAN EIGHT DAYS This Control is provided to implement the requirements 10 CFR Part 50 Appendix I Sections II.C, III.A and IV.A. The requirement implements the guides set forth in Appendix I Section II.C. The action to be taken provides the required operating flexibility and at the same time implements the guides set forth in Appendix I Section IV.A to assure that the releases of radioactive material in gaseous effluents will be kept "as low as reasonably achievable." Section 7.4 calculational methods implement the requirements in Appendix I Section III.A that conformance with the guides of Appendix I be shown by calculational procedures based on models and data such that the actual exposure of a MEMBER OF THE PUBLIC through appropriately modeled pathways is unlikely to be substantially underestimated. Section 7.4 calculational methods for calculating the doses due to the actual release rates of the subject materials are consistent with the methodologies provided in NUREG/CR-1004, "A Statistical Analysis of Selected Parameters for Predicting Food Chain Transport and Internal Dose of Radionuclides," October 1979 and Regulatory Guide 1.109, "Calculation of Annual Doses to Man from Routine Releases of Reactor Effluents for the Purposes of Evaluating Compliance with 10 CFR Part 50, Appendix I,"

Revision 1, October 1977 and Regulatory Guide 1.111, "Methods for Estimating Atmospheric Transport and Dispersion of Gaseous Effluents in Routine Releases from Light-Water Cooled Reactors," Revision 1, July 1977. These equations also provide for determining the actual doses based upon the historical average atmospheric conditions. The release rate specifications for Iodine-131, Iodine -133, tritium and all radionuclides in particulate form with half-lives greater than 8 days are dependent on the existing radionuclide pathways to man, beyond the UNRESTRICTED AREA BOUNDARY. The pathways which were examined in the development of these calculations were: 1) individual inhalation of airborne radionuclides, 2) deposition of radionuclides onto green leafy vegetation with subsequent consumption by man, 3) deposition onto grassy areas where milk animals and meat producing animals graze with consumption of the milk and meat by man, and 4) deposition on the ground with subsequent exposure of man.

SQN ODCM Revision 47 Page 51 of 168 BASES 1/2.2 RADIOACTIVE EFFLUENTS 112.2.2.4 GASEOUS RADWASTE TREATMENT This Control that the appropriate portions of these systems be used, when specified, provides reasonable assurance that the releases of radioactive materials in gaseous effluents will be kept "as low as reasonably achievable." This Control implements the requirements of 10 CFR Part 50.36a, General Design Criteria 60 of 10 CFR Part 50 Appendix A, and the design objectives given in 10 CFR Part 50 Appendix I Section II.D. The specified limits governing the use of appropriate portions of the systems were specified as a suitable fraction of the dose design objectives set forth in 10 CFR Part 50 Appendix I Section II.B and II.C, for gaseous effluents.

1/2.2.3 TOTAL DOSE This Control is provided to meet the dose limitations of 40 CFR Part 190 that have been incorporated into 10 CFR Part 20 by 46 FR 18525. Compliance with this Control will be considered to demonstrate compliance with the 0.1 rem limit of 10 CFR Part 20.1301(a)(1) per 56 FR 23374. The ACTION requires the preparation and submittal of a Special Report whenever the calculated doses due to releases of radioactivity and to radiation from uranium fuel cycle sources exceed 25 mrem to the total body or any other organ except thyroid, which shall be limited to less than or equal to 75 mrem. For sites containing up to 4 reactors, it is highly unlikely that the resultant dose to a MEMBER OF THE PUBLIC will exceed the dose limits of 40 CFR Part 190 if the individual reactors remain within twice the dose design objectives of Appendix I and if direct radiation doses from the units and from outside storage tanks are kept small. The Special Report will describe a course of action that should result in the limitation of annual dose to a MEMBER OF THE PUBLIC to within the 40 CFR Part 190 limits. For the purposes of the Special Report, it may be assumed that the dose commitment to the MEMBER OF THE PUBLIC from other uranium fuel cycle sources is negligible, with the exception that dose contributions from other nuclear fuel cycle facilities at the same site or within a radius of 8 km must be considered.

If the dose to any MEMBER OF THE PUBLIC is estimated to exceed the requirements of 40 CFR Part 190, the Special Report with a request for a variance (provide the release conditions resulting in violation of 40 CFR Part 190 have not already been corrected), in accordance with the provisions of 40 CFR Part 190.11 and 10 CFR Part 20.2203, is considered to be a timely request and fulfills the requirements of 40 CFR Part 190 until NRC staff action is completed. The variance only relates to the limits of 40 CFR Part 190, and does not apply in any way to the other requirements for dose limitation of 10 CFR Part 20, as addressed in ODCM Controls 1.2.1.1 and 1.2.2.1. An individual is not considered a MEMBER OF THE PUBLIC during any period in which he/she is engaged in carrying out any operation that is a part of the nuclear fuel cycle.

SQN ODCM Revision 47 Page 52 of 168 BASES 1/2.3 RADIOLOGICAL ENVIRONMENTAL MONITORING 1/2.3.1 MONITORING PROGRAM The radiological environmental monitoring program required by this Control provides representative measurements of radiation and of radioactive materials in those exposure pathways and for those radionuclides that lead to the highest potential radiation exposures of MEMBERS OF THE PUBLIC resulting from the station operation. This monitoring program implementsSection IV.B.2 of Appendix I to 10 CFR Part 50 and thereby supplements the radiological effluent monitoring program by verifying that the measurable concentration of radioactive materials and levels of radiation are not higher than expected on the basis of the effluent measurements and modeling of the environmental exposure pathways. Guidance for this monitoring program is provided by the Radiological Assessment Branch Technical Position on Environmental Monitoring.

The required detection capabilities for environmental sample analyses are tabulated in terms of the lower limits of detection (LLDs). The LLDs required by Table 2.3-3 are considered optimum for routine environmental measurements in industrial laboratories. It should be recognized that the LLD is defined as an a Priori (before the fact) limit representing the capability of a measurement system and not as a posteriori (after the fact) limit for a particular measurement.

Detailed description of the LLD, and other detection limits can be found in HASL Procedures Manual, HASL-300 (revised annually), Curie, L. A., "Limits for Qualitative Detection and Quantitative Determination - Application to Radiochemistry," Anal. Chem. 40, 586-93 (1968), and Hartwell, J. K., "Detection Limits for Radioanalytical Counting Techniques," Atlantic Richfield Hanford Company Report ARH-SA-215 (June 1975).

1/2.3.2 LAND USE CENSUS This Control is provided to ensure that changes in the use of unrestricted areas are identified and that modifications to the monitoring program are made if required by the results of that census.

The best survey information from the door-to-door, aerial, or consulting with local agricultural authorities shall be used. This census satisfies the requirements of Section IV.B.3 of Appendix I to 10 CFR Part 50. Restricting the census to gardens of greater than 500 ft2 provides assurance that significant exposure pathways via leafy vegetables will be identified and monitored since a garden of this size is the minimum required to provide the quantity (26 kg/yr) of leafy vegetables assumed in Regulatory Guide 1.109 for consumption by a child. To determine this minimum garden size, the following assumptions were used, 1) that 20% of the garden was used for growing broad leaf vegetation (i.e., similar to lettuce and cabbage), and 2) a vegetation yield of 2 kg/im2.

1/2.3.3 INTERLABORATORY COMPARISON PROGRAM The requirement for participation in an Interlaboratory Comparison Program is provided to ensure that independent checks on the precision and accuracy of the measurements of radioactive material in environmental sample matrices are performed as part of the quality assurance program for environmental monitoring in order to demonstrate that the results are reasonably valid.

SQN ODCM Revision 47 Page 53 of 168 SECTION 3.0 DEFINITIONS

SQN ODCM Revision 47 Page 54 of 168 3.0 DEFINITIONS The defined terms in this section appear in capitalized type in the text and are applicable throughout the ODCM.

3.1 CHANNEL CALIBRATION A CHANNEL CALIBRATION shall be the adjustment, as necessary, of the channel output such that it responds with the necessary range and accuracy to known values of the parameter which the channel monitors. The CHANNEL CALIBRATION shall encompass the entire channel including the sensor and alarm and/or trip functions, and shall include the CHANNEL FUNCTIONAL TEST. The CHANNEL CALIBRATION may be performed by any series of sequential, overlapping, or total channel steps such that the entire channel is calibrated.

3.2 CHANNEL CHECK A channel check shall be the qualitative assessment of channel behavior during operation by observation. This determination shall include, where possible, comparison of the channel indication and/or status with other indications and/or status derived from independent instrument channels measuring the same parameter.

3.3 CHANNEL FUNCTIONAL TEST A CHANNEL FUNCTIONAL TEST shall be:

a. Analog channels - the injection of a simulated signal into the channel as close to the sensor as practicable to verify OPERABILITY including alarm and/or trip functions.
b. Bistable channel - the injection of a simulated signal into the sensor to verify OPERABILITY including alarm and/or trip function.
c. Digital channels - the injection of a simulated signal into the channel as close to the sensor input to the processor as practicable or the manipulation of a setpoint below existing background to verify operability including alarm and/or trip function.

3.4 CIRCUIT FAILURE shall be defined as the loss of circuit power to the monitor.

3.5 CONTROLLED AREA A CONTROLLED AREA is the area outside the RESTRICTED AREA but inside the UNRESTRICTED AREA BOUNDARY (See Figure 3.1).

3.6 DOSE EQUIVALENT 1-131 DOSE EQUIVALENT 1-131 shall be that concentration of 1-131 (pACi/gram) which alone would produce the same thyroid dose as the quantity and isotopic mixture of 1-131, 1-132, 1-133, 1-134, and 1-135 actually present. The thyroid dose conversion factors used for this calculation shall be those listed in Table III of TID-14844, "Calculation of Distance Factors for Power and Test Reactor Sites."

SQN ODCM Revision 47 Page 55 of 168 3.0 DEFINITIONS (continued) 3.7 GASEOUS RADWASTE TREATMENT SYSTEM A GASEOUS RADWASTE TREATMENT SYSTEM is any system designed and installed to reduce radioactive gaseous effluents by collecting primary coolant system offgases from the primary system and providing for delay or holdup for the purpose of reducing the total radioactivity prior to release to the environment.

3.8 MEMBER(S) OF THE PUBLIC MEMBER(S) OF THE PUBLIC as defined in 10 CFR 20, is any individual except when that individual is receiving an occupational dose.

3.9 OPERABLE - OPERABILITY A system, subsystem, train, component, or device shall be OPERABLE or have OPERABILITY when it is capable of performing its specified function(s), and when all necessary attendant instrumentation, controls, a normal or an emergency electrical power source, cooling or seal water, lubrication or other auxiliary equipment that are required for the system, subsystem, train, component, or device to perform its function(s) are also capable of performing their related support function.

3.10 MODE A MODE shall correspond to any one inclusive combination of core reactivity condition, power level, and average reactor coolant temperature specified in Table 1.1 of the SQN Technical Specifications.

3.11 PURGE -PURGING PURGE or PURGING is the controlled process of discharging air or gas from a confinement to maintain temperature, pressure, humidity, concentration or other operating condition, in such a manner that replacement air or gas is required to purify the confinement.

3.12 RADIATION MONITOR (RM) OR (R)

A radiation monitor is identified by 'RM" under instrumentation. To be OPERABLE, it is minimally defined as an instrumentation channel that includes the radiation detector, associated sample delivery system, signal processing electronics, malfunction alarm, high radiation alarm, and at least one indicator (main control room, local, or computer point).

3.13 RATED THERMAL POWER RATED THERMAL POWER shall be a total reactor core heat transfer rate to the reactor coolant of 3411 MWt.

SQN ODCM Revision 47 Page 56 of 168 3.0 DEFINITIONS (continued) 3.14 RESTRICTED AREA The RESTRICTED AREA, as defined in 10 CFR Part 20, is that area, access to which is limited by the licensee for the purposes of protecting individuals against undue risks from exposure to radiation and radioactive materials. The permanent RESTRICTED AREA is shown on Figure 3.1, but temporary restricted areas outside the permanent RESTRICTED AREA may be defined by SQN.

3.15 SITE BOUNDARY NOT USED 3.16 SOURCE/SENSOR CHECK A SOURCE/SENSOR CHECK shall be the qualitative assessment of channel response when the channel sensor is exposed to a radioactive source or other channel sensor internal test circuit.

3.17 UNRESTRICTED AREAIBOUNDARY An UNRESTRICTED AREA/BOUNDARY, as used for calculations performed pursuant to 10 CFR Part 50.36a, shall be an area at or beyond the site boundary which is utilized in the ODCM Controls to keep levels of radioactive materials in liquid and gaseous effluents as low as is reasonably achievable. The UNRESTRICTED AREA does not include areas over water bodies (See Figure 3.1).

3.18 VENTILATION EXHAUST TREATMENT SYSTEM A VENTILATION EXHAUST TREATMENT SYSTEM is any system designed and installed to reduce gaseous radioiodine or radioactive material in particulate form in effluents by passing ventilation or vent exhaust gases through charcoal adsorbers and/or HEPA filters for the purpose of removing iodines or particulates from the gaseous exhaust stream prior to the release to the environment (such a system is not considered to have any effect on noble gas effluents). Engineered Safety Feature (ESF) atmospheric cleanup systems are not considered to be VENTILATION EXHAUST TREATMENT SYSTEM components.

3.19 VENT FLOW RATE MONITOR (F)

The vent flow rate monitors are identified by "F" under instrumentation. To be OPERABLE is minimally defined as an instrumentation channel that includes the flow sensor, processing electronics and at least one indicator (main control room, local or computer point).

3.20 VENTING VENTING is the controlled process of discharging air or gas from a confinement to maintain temperature, pressure, humidity, concentration, or other operating condition, in such a manner that replacement air or gas is not provided or required during VENTING. Vent, used in system names, does not imply a VENTING process.

SQN ODCM Revision 47 Page 57 of 168 Table 3.1 FREQUENCY NOTATION P = Completed prior to each release D = At least once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> W = At least once per 7 days B = At least once per 15 days M = At least once per 31 days Q = At least once per 92 days R = At least once per 18 months S = At least semi-annual N.A. = Not Applicable

SQN ODCM Revision 47 Page 58 of 168 Figure 3.1 UNRESTRICTED AREA BOUNDARY Area between the RESTRICTED AREA and the UNRESTRICTED AREA BOUNDARIES is the CONTROLLED AREA. Dark shaded area outside the UNRESTRICTED AREA BOUNDARY is the UNRESTRICTED AREA.

SQN ODCM Revision 47 Page 59 of 168 SECTION 4.0 (NOT USED)

SQN ODCM Revision 47 Page 60 of 168 SECTION 5.0 ADMINISTRATIVE CONTROLS

SQN ODCM Revision 47 Page 61 of 168 5.0 ADMINISTRATIVE CONTROLS 5.1 ANNUAL RADIOLOGICAL ENVIRONMENTAL OPERATING REPORT As required by SQN Technical Specification 6.9.1.6, the Annual Radiological Environmental Operating Report covering the operation of the unit during the previous calendar year shall be submitted prior to May 1 of each year.

The annual radiological environmental operating reports shall include summaries, interpretations, and an analysis of trends of the results of the radiological environmental surveillance activities for the report period, including a comparison with preoperational studies, operational controls (as appropriate), and previous environmental surveillance reports and an assessment of the observed impacts of the plant operation on the environment. The reports shall also include the results of land use censuses required by ODCM Control 1.3.2 and a listing of the new locations for dose calculations and/or environmental monitoring identified by the land use census. If harmful effects or evidence of irreversible damage are detected by the monitoring, the report shall provide an analysis of the problems and a planned course of action to alleviate the problem.

The annual radiological environmental operating reports shall include summarized and tabulated results in the format of Regulatory Guide 4.8, December 1975 of all radiological environmental samples taken during the report period. In the event that some results are not available for inclusion with the report, the report shall be submitted noting and explaining the reasons for the missing results. The missing data shall be submitted as soon as possible in a supplementary report.

The reports shall also include the following: a summary description of the radiological environmental monitoring program; a map of all sampling locations keyed to a table giving distances and directions from one reactor; and the results of licensee participation in the Interlaboratory Comparison Program required by ODCM Control 1.3.3.

5.2 ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT As required by SQN Technical Specification 6.9.1.8, an Annual Radioactive Effluent Release Report covering the operation of the site during the previous calendar year of operation shall be submitted prior to May 1 of each year.

Annual radioactive release reports shall include a summary of the quantities of radioactive liquid and gaseous effluents and solid waste released from the site as outlined in Regulatory Guide 1.21, "Measuring, Evaluating, and Reporting Radioactivity in Solid Wastes and Releases of Radioactive Materials in Liquid and Gaseous Effluents from Light-Water-Cooled Nuclear Power Plants,"

Revision 1, June 1974, with data summarized on a quarterly basis following the format of Appendix B thereof.

The annual radioactive release report shall include unplanned releases from the site to unrestricted areas on a quarterly basis and shall also include any changes made to the ODCM pursuant to ODCM Administrative Control 5.3.

SQN ODCM Revision 47 Page 62 of 168 5.0 ADMINISTRATIVE CONTROLS 5.2 ANNUAL RADIOACTIVE EFFLUENT RELEASE REPORT (continued)

The annual radioactive effluent release report shall include information for solid waste as outlined in the Process Control Program, and shall also include any changes made to the PCP during the reporting period.

The annual radioactive effluent release report shall include a discussion of any licensee initiated major changes to the radioactive waste systems as required by SQN Technical Specification 6.15.1.1.

The annual radioactive effluent release report (Radiological Impact) shall include an annual summary of hourly meteorological data collected over the previous year. This annual summary may be either in the form of an hour-by-hour listing of wind speed, wind direction, atmospheric stability, and precipitation (if measured) on magnetic tape, or in the form of joint frequency distributions of wind speed, wind direction, and atmospheric stability. In lieu of submission with the annual radioactive effluent release report, this summary of required meteorological data may be retained on site in a file that shall be provided to NRC upon request). This same report shall include an assessment of the radiation doses due to radioactive liquid and gaseous effluents released from the unit or station during the previous calendar year. This same report shall also include an assessment of the radiation doses from radioactive liquid and gaseous effluents to MEMBERS OF THE PUBLIC due to their activities inside the UNRESTRICTED AREA BOUNDARY (Figure 3.1) during the report period. All assumptions used in making these assessments (i.e., specific activity, exposure time, and location) shall be included in these reports.

The meteorological conditions concurrent with the time of release of radioactive materials in gaseous effluents (as determined by sampling frequency and measurement) shall be used for determining the gaseous pathway doses. The assessment of radiation doses shall be performed in accordance with Sections 6.6 and 7.6.

The annual radioactive effluent release report to be submitted after January 1 of each year shall also include an assessment of radiation doses to the likely most exposed MEMBERS OF THE PUBLIC from reactor releases and other nearby uranium fuel cycle sources (including doses from primary effluent pathways and direct radiation) for the previous calendar year to show conformance with 40 CFR 190, Environmental Radiation Protection Standards for Nuclear Power Operation, in accordance with ODCM Section 8.0. Acceptable methods for calculating the dose contribution from liquid and gaseous effluents are given in Regulatory Guide 1.109, Revision 1.

SQN ODCM Revision 47 Page 63 of 168 5.0 ADMINISTRATIVE CONTROLS 5.3 OFFSITE DOSE CALCULATION MANUAL CHANGES As required by SQN Technical Specification 6.14 and Appendix A, changes to the ODCM:

1. Shall be documented and records of reviews performed shall be retained in a manner convenient for review. This documentation shall contain:
a. Sufficient information to support the change together with the appropriate analyses or evaluations justifying the change(s) and
b. A determination that the change will maintain the level of radioactive effluent control required by 10 CFR Part 20.1302, 40 CFR Part 190, 10 CFR Part 50.36a, and Appendix I to 10 CFR Part 50 and not adversely impact the accuracy or reliability of effluent, dose, or setpoint calculations.
2. Shall become effective after review and acceptance by the process described in TVA-NQA-PLN89-A.
3. Shall be submitted to the Commission in the form of a complete, legible copy of the entire ODCM as a part of or concurrent with the Annual Radioactive Effluent Release Report for the period of the report in which any change to the ODCM was made. Each change shall be identified by markings in the margin of the affected pages, clearly indicating the area of the page that was changed, and shall indicate the date (i.e., month/year) the change was implemented.

5.4 SPECIAL REPORTS Special Reports shall be submitted within the time period specified for each report, in accordance with 10 CFR Part 50.4.

SQN ODCM Revision 47 Page 64 of 168 SECTION 6.0 LIQUID EFFLUENTS

SQN ODCM Revision 47 Page 65 of 168 SECTION 6.0 LIQUID EFFLUENTS RELEASE POINTS There are four systems from which liquid effluents are released to the environment. These are the Liquid Radwaste System, the Condensate Demineralizer System, the Turbine Building Sump (TBS), and the Units 1 and 2 Steam Generator Blowdown. Figure 6.1 provides an outline of the liquid release paths and discharge points with associated flow rates and radiation monitors.

All liquid effluents are ultimately discharged to the Diffuser Pond which releases to the Tennessee River where they are evaluated for offsite dose. The Essential Raw Cooling Water (ERCW) routinely provides dilution for liquid effluents at a minimum flow rate of 15,000 gpm. ERCW flow is monitored by radiation monitors 0-RM-90-133, -134, -140, -141.

Liquid Radwaste System The Liquid Radwaste System processes liquid from the Reactor Building and Auxiliary Building Floor Drains and the laundry/hot shower and chemical drain tanks. Figure 6.2 provides a schematic of the Liquid Radwaste System, showing the liquid pathways, flow rate and radiation monitors. The normal release points for liquid radwaste are the Monitor Tank and the Cask Decontamination Collector Tank (CDCT). The Monitor Tank has a capacity of 22,000 gal and is released routinely at a flow rate of 125 gpm. The CDCT has a capacity of 15,000 gal and is also released routinely at a flow rate of 125 gpm. The Monitor Tank and CDCT discharge to the Cooling Tower Blowdown (CTBD) line as a batch release and are monitored by radiation monitor 0-RM-90-122.

Condensate Demineralizer System The Condensate Demineralizer System processes liquid wastes coming from the High Crud Tanks (HCT-1 and -2), the Neutralization Tank, and the Non-Reclaimable Waste Tank (NRWT). The HCTs have a capacity of 20,000 gal and a maximum discharge flow rate of 245 gpm. The Neutralization Tank has a capacity of 19,000 gal and a maximum discharge flow rate of 245 gpm.

The NRWT has a capacity of 11,000 gal and a maximum discharge flow rate of 245 gpm. The Condensate Demineralizer System is routinely released to the CTBD line but can be released to the TBS during periods of low radioactivity levels and is monitored by radiation monitor 0-RM 225.

Turbine Building Sump The Turbine Building Sump (TBS) normally releases to the Low Volume Waste Treatment Pond (LVWTP) but can be released to the Yard Pond. The TBS has a capacity of 30,000 gal and a design discharge release rate of 1,750 gpm per pump. TBS releases are monitored by radiation monitor 0-RM-90-212.

Steam Generator Blowdown The Steam Generator Blowdown (SGBD) is processed in the Steam Generator Draindown Flash Tanks or SGBD Heat Exchangers. The SGBD discharge has a maximum flow rate of 80 gpm per steam generator. SGBD discharges to the CTBD line are continuous and are monitored by radiation monitors 1,2-RM-90-120, -121.

SQN ODCM Revision 47 Page 66 of 168 6.1 LIQUID RELEASES 6.1.1 Pre-Release Analysis To ensure representative sampling, radwaste tanks will be recirculated for a procedurally established length of time, or through two volumes. Periodically, checks will be made to ensure a representative mixing of tank contents. All radwaste tanks will be released as "batch" releases.

Releases from condensate demineralizer tanks are routinely continuous releasesa and utilize a composite sampler to obtain a representative sample while being discharged. In the event of an inoperable composite sampler, the releases will be made as a batch release, and will be recirculated for a procedurally established length of time or through two volumes to ensure representative sampling.

Steam generator blowdown and turbine building sumpa are considered continuous and grab sampled daily during releases.

Prior to any batch release, a grab sample will be taken and analyzed to determine the concentration, jiCi/ml, of each gamma-emitting nuclide. For continuous releases, daily grab or composite samples will be taken on days when releases are being made and analyzed to determine the concentration, iLCi/ml, of each gamma-emitting nuclide. Composite samples are maintained during periods of radioactive discharge from all pathways (as required by Table 2.2-1) to determine the concentration of certain nuclides (H-3, Fe-55, Sr-89, Sr-90, and alpha emitters).

For those nuclides whose activities are determined from composite samples, the concentrations for the previous composite period can be assumed as the concentration for the next period to perform the calculations in Sections 6.3 and 6.5. The actual measured concentrations will be used for the dose calculations described in Section 6.6.

a Sampling requirements for these release points are applicable only during periods of significant primary to secondary leakage or the release of radioactivity as detected by the effluent radiation monitor provided the radiation monitor setpoint is at a LLD of <1 E-06 OCi/ml and allowing for background radiation during periods when primary to secondary leakage is occurring. Sampling and analysis is routinely performed versus utilizing the radiation monitor at this LLD.

6.1.2 Effluent Concentration Limits (ECL)-Sum of the Ratios The sum of the ratios (R.) for each release point will be calculated by the following relationship.

Ci RI= ---- (6.1) i ECL.

where:

R! = the sum of the ratios for release point j.

ECLj = the ECL of radionuclide i, gCi/ml, from 10 CFR Part 20, Appendix B, Table 2, Column 2.

C. = concentration of radionuclide i, plCi/ml.

The sum of the ECL ratios must be < 10 following dilution at the Cooling Tower Blowdown due to the releases from any or all of the release points described above. The ECL ratios for releases from the Turbine Building Sump will be < 10 at the sump.

SQN ODCM Revision 47 Page 67 of 168 The following relationship is used to ensure that this criterion is met:

f1R1 + f2R2 + f 3R3 + f4 R4 (6.2)

RTBS + < 10.0 F

where RTBS = sum of the ECL ratios of the turbine building sump as determined by equation 6.1.

flf2,f3,f4 = effluent flow rate for radwaste, condensate demineralizer system and each of the steam generator blowdowns, respectively, gpm.

R1 ,R2 ,R3 ,R4 = sum of ECL ratios for radwaste, condensate demineralizer system and each of the steam generator blowdowns, respectively, as determined by equation 6.1.

F = dilution flow rate for CTBD, routinely 15,000 gpm.

6.1.3 Post-Release Analysis A post-release evaluation will be done using actual release data to ensure that the limits specified in ODCM Control 1.2.1.1 were not exceeded. This analysis will include an evaluation of the noble gas concentration with regard to ODCM Control 1.2.1.1.

A composite list of concentrations (Ci), by isotope, will be used with the actual waste (f) and dilution (F) flow rates (or volumes) during the release. The data will be evaluated to demonstrate compliance with the limits in ODCM Control 1.2.1.1.

SQN ODCM Revision 47 Page 68 of 168 6.2 INSTRUMENT SETPOINTS Liquid effluent monitor setpoints are determined to ensure that the concentration of radioactive material released at any time from the site to UNRESTRICTED AREAS does not exceed ten times the ECL limits referenced in ODCM Control 1.2.1.1 and to identify any unexpected releases. The essential raw cooling water (ERCW) will be used for dilution for liquid effluents; however, the very large dilution factors afforded by the circulating coolant will not be used to allow high concentrations of liquid radioactive waste to be discharged from the plant.

6.2.1 Discharge Point Monitor Setpoints (0-RM-90-133,134,140,141)

The setpoints for the ERCW monitors (RM-90-133, 134, 140, 141) are set to ensure that the concentration of radioactive materials released at any time from the site do not exceed the limits given in ODCM Control 1.2.1.1. The setpoints for these monitors will be set at a small value above background to ensure that any radioactivity is identified. Site procedures will document and control this value.

6.2.2 Release Point Monitor Setpoints (0-RM-90-122; O-RM-90-225; O-RM-90-212; 1,2-RM-90-120,121)

There are five liquid release point effluent monitors: the Liquid Radwaste System radiation monitor 0-RM-90-122; the Condensate Demineralizer System radiation monitor 0-RM-90-225; the Turbine Building Sump radiation monitor 0-RM-90-212; and the Steam Generator Blowdown (SGBD) radiation monitors 1,2-RM-90-120,121.

The batch release points, the Liquid Radwaste System and the Condensate Demineralizer System (if being released in a batch mode), are looking at an undiluted waste stream as it comes out of a tank. The purpose of the monitor setpoints for these batch releases is to identify any release that is larger than expected and would have the potential to exceed the limits after dilution. Setpoints are calculated as described in Section 6.2.3.

The continuous release points, the Condensate Demineralizer System, the Steam Generator Blowdowns, and the Turbine Building Sump, will not be releasing radioactivity unless there is or has been a primary to secondary leak. When there is no identified primary to secondary leakage, these release points are monitored to indicate the presence of elevated activity levels in these systems. The setpoints for these monitors will be set to alarm if the activity in the stream exceeds a routine nominal background. These setpoints are controlled by site instructions.

When there is identified significant primary to secondary leakage, the continuous release points are monitored to identify any release that is larger than expected or would have the potential to exceed the 10 CFR Part 20 limits after dilution. The monitor setpoints are calculated in the same manner as the batch release point monitor setpoints (described in Section 6.2.3) when this is the case. When these release points are being treated in this manner, a single batch release is defined as all effluent released through this point on a continuous bases for a period of time (usually one week).

6.2.3 Batch Release Point Monitor Setpoint For each release from a release point, two setpoints are calculated: one based on the monitor response to the contents of the effluent stream multiplied by an adminstrative factor to account for monitor fluctuations; and another based on the predicted response of the monitor to the activity in

SQN ODCM Revision 47 Page 69 of 168 the release stream if it were large enough to exceed ten times the 10 CFR Part 20 limits after dilution. The expected monitor response, R in cpm, is calculated using equation 6.3 below.

The maximum calculated setpoint, Smax, is calculated using Equation 6.4 below. A comparison is made between these two calculated setpoints to determine which is used. The actual monitor setpoint for the release is set equal to X times the expected radioactivity response plus background, or to the maximum calculated setpoint, whichever is less. X is an administrative factor designed to account for expected variations in monitor response (it will be defined in approved plant instructions). The X times expected response setpoint allows for the identification of any release of radioactivity above the expected amount. The maximum calculated setpoint ensures that the release will be stopped if it exceeds ten times the 10 CFR Part 20 concentration limits after dilution.

Expected response / Expected Response Setpoint (Ser)

R=B+ LIEffi*C 1 (6.3) i Ser = X* R where B = monitor background, cpm.

Eff. = monitor efficiency for nuclide i, cpm per itCi/ml.

C. = tank concentration of nuclide i, jLCi/ml.

X = Adminstrative Factor designed to account for expected variations in monitor response and background (The range of values is 1.5 < X < 2.0).

Calculated Maximum Monitor Setpoint 10 FS (FW + (A

  • Fdil))

Smax = (R- B) + B (6.4)

F, Rj where FS = fluctuationsafety factor for the monitor, which is set at 1.0 < SF < 1.5. The fluctuationsafety factor is set to account for minor changes in monitor response and background.

F, = flow of waste stream, gpm.

FdII = flow of the dilution stream, routinely set @ 15,000 gpm.

A = fraction of dilution flow allocated to this release point. For the TBS, this fraction is zero.

The fractions for the remaining 4 release points are defined as the ratio of the allocated CTBD flow for that release point to the total CTBD flow. The CTBD flow allocation fractions for these release points are routinely:

Radwaste 0.60 Condensate demineralizer 0.20 Steam Generator Blowdown (Ul) 0.10 Steam Generator Blowdown (U2) 0.10 NOTE: These allocation factors may be adjusted for a particular release if it is known that there are no releases being made through other release points into the CTBD. For example, if there are no releases being made through the Condensate Demineralizer or either Steam Generator Blowdown, the allocation factor for the Radwaste System may be set equal to one.

RI = sum of the ECL ratios for release point j as calculated in Section 6.1.2.

R = expected monitor response, cpm, as calculated above.

B = background, cpm.

SQN ODCM Revision 47 Page 70 of 168 10 = ECL ratio limit at the Cooling Tower Blowdown discharge.

6.3 CUMULATIVE LIQUID EFFLUENT DOSE CALCULATIONS Doses due to liquid effluents are calculated for each release for all age groups: adult (E017 years of age), teen (E111, but 017 years), child (01, but El11 years) and infant (0-1 years) and organs:

bone, liver, total body, thyroid, skin, kidney, lung and GI tract. Pathways considered are ingestion of drinking water, fish consumption and recreation-shoreline. The maximum individual dose from drinking water is assumed to be that calculated at the location immediately downstream from the diffuser in the Tennessee River. The maximum individual dose from fish ingestion is assumed to be that calculated for the consumption of fish caught anywhere between the plant and the first downstream dam (Chickamauga Dam). The maximum potential recreation dose is calculated for a location immediately downstream of the plant outfall. Dose factors for these age groups and pathways are calculated as described in Section 6.7. For pathways with no age or organ specific dose factors (i.e. shoreline recreation), the total body dose will be added to the internal organ doses for all age groups.

The general equation for the dose calculations is:

Dose = ElAit T C1 D (6.5) i where:

Ait = the total dose factor to the total body or any organ t for nuclide i, mrem/hr per AiCi/ml. The total dose factor is the sum of the dose factors for water ingestion, fish ingestion, and shoreline recreation, as defined in Section 6.7.

T = the length of time period over which the concentrations and the flows are averaged for the liquid release, hours.

C. = the average concentration of radionuclide i, in undiluted liquid effluent during the time period T from any liquid release, [tCi/ml.

D = the near field average dilution factor for C1 during any effluent release. D is calculated by the following equation:

FLOWW D =

0.60 RF where:

FLOWW= maximum undiluted liquid waste flow during the release, cfs. For TBS releases, this term is the diluted waste flow into the pond.

0.60 = mixing factor of effluent in river, defined as the percentage of the river flow which is available for dilution of the release.

RF = default riverflow, cfs. For each release, this value is set to 7900 cfs (the lowest average quarterly riverflow recorded from the period 1978-1988).

From the four age groups considered, the maximum is determined by comparing all organ doses for all age groups. The age group with the highest single organ dose is selected as the critical age group. The total body and maximum organ doses for the critical age group are used in the calculation of the monthly dose described in Section 6.3.1.

SQN ODCM Revision 47 Page 71 of 168 6.3.1 Monthly Dose Calculations At the end of each month, the actual average riverflow for the month is used to recalculate the liquid doses. The monthly cumulative dose is defined as the sum of the doses for the critical age group for each release during the month. Thus, the monthly cumulative dose will be a conservative value, consisting of doses belonging to various age groups depending on the mix of radionuclides. These doses are multiplied by the ratio of the default riverflow (7900 cfs) to the actual monthly average riverflow to obtain the monthly dose. The total body and maximum organ doses determined in this manner are then used to determine the cumulative quarterly and annual doses described in Section 6.3.2, and for the dose projections described in Section 6.5.

6.3.2 Cumulative Doses Quarterly and annual sums of all doses are determined at the end of each month to compare to the limits given in ODCM Control 1.2.1.2. These quarterly and annual sums will be the sum of the monthly cumulative doses described in Section 6.3.1 for the appropriate months in the quarter or year. These doses will be used in the comparison to the limits.

6.3.3 Comparison to Limits The cumulative calendar quarter and calendar year doses are compared to the limits in ODCM Control 1.2.1.2 once per 31 days to determine compliance.

SQN ODCM Revision 47 Page 72 of 168 6.4 LIQUID RADWASTE TREATMENT SYSTEM The liquid radwaste treatment system described below shall be maintained and operated to keep releases ALARA.

A flow diagram for the LRTS is given in Figure 6.2. The system consists of one reactor coolant drain tank with two pumps and a floor and equipment drain sump inside the containment of each unit and the following shared equipment inside the auxiliary building: one sump tank and pumps, one tritiated drain collector tank with two pumps and one filter, one floor drain collector tank with two pumps and one filter, a waste condensate tank filter, three waste condensate tanks and two pumps, a chemical drain tank and pump, two laundry and hot shower tanks and pump, a spent resin storage tank, a cask decontamination tank with two pumps and two filters, Auxiliary Building floor end equipment drain sump and pumps, and evaporator with two distillate tanks, a Mobile Waste Demineralizer System (if needed) and the associated piping, valves and instrumentation.

SQN ODCM Revision 47 Page 73 of 168 6.5 DOSE PROJECTIONS In accordance with ODCM Surveillance Requirement 2.2.1.3, dose projections will be performed by averaging the two previous month's doses as determined in Section 6.3.1. To determine compliance with the limits, these averages are assigned as the dose projections for the upcoming month.

The projected doses are compared to the limits of ODCM Control 1.2.1.3. If the projected doses exceed 0.06 mrem per reactor unit to the total body or 0.2 mrem per reactor unit to any organ in a 31-day period, the liquid radwaste treatment system shall be used to reduce the radioactive materials in liquid wastes prior to their discharge to UNRESTRICTED AREAS.

D= a+b 2

where:

D = the 31-day dose projection, mrem a = the cumulative dose for the previous month, mrem b = the cumulative dose for the present month, mrem

SQN ODCM Revision 47 Page 74 of 168 6.6 QUARTERLY DOSE CALCULATIONS A complete dose analysis utilizing the total estimated liquid releases for each calendar quarter will be performed and reported as required in ODCM Administrative Control 5.2. Methodology for this analysis is that which is described in this section using the quarterly release values reported by the plant personnel. The releases are assumed, for this calculation, to be continuous over the 90 day period.

The average dilution factor, D, used for the quarterly calculations is:

1 D= (for receptors upstream (6.6)

RF

  • 0.60 of Chickamauga Dam) and 1

D= (for receptors downstream (6.7)

RF of Chickamauga Dam) where:

RF = the average actual riverflow for the location at which the dose is being determined, cfs.

0.60 = the fraction of the riverflow available for dilution in the near field, dimensionless.

6.6.1 WATER INGESTION Water ingestion doses are calculated for each water supply identified within a 50 mile radius downstream of SQN (Table 6.1). The summation of water ingestion doses are calculated for the total body and each internal organ as described below:

Dorg = 106 9.80E-09 0.25 Awit Qj D exp(-8.64E+04 Di td)

(6.8) where 106 = conversion factor, glCi/Ci.

9.80E-09 = conversion factor, cfs per ml/h.

0.25 = fraction of the yearly water consumption in one quarter, dimensionless Awit = dose factor for water ingestion for nuclide i, age group t, mremlh per laCi/ml, as calculated in Section 6.7.1.

Qj = Quantity of nuclide i released during the quarter, Ci.

D = dilution factor, as described above, cfs-1 .

a, = radiological decay constant of nuclide i, s-1 (Table 6.2).

td = decay time for water ingestion, equal to the travel time from the plant to the water supply plus one day to account for the time of processing at the water supply (per Regulatory Guide 1.109), d.

8.64E+04 = conversion factor, seconds per day.

SQN ODCM Revision 47 Page 75 of 168 6.6.2 FISH INGESTION Fish ingestion doses are calculated for each identified reach within a 50 mile radius downstream of SQN (Table 6.1). The summation of individual fish ingestion doses are calculated for the total body and each internal organ as described below:

0 = 106 9.80E-09 0.25 nAFit Qj D exp(-8.64E+04 Eltd) (6.9) where 106 = conversion factor, ptCi/Ci.

9.80E-09 = conversion factor, cfs per ml/h.

0.25 = fraction of the yearly fish consumption eaten in one quarter, dimensionless.

AFit = dose factor for fish ingestion for nuclide i, age group t, mrem/h per jtCi/ml, as calculated in Section 6.7.2.

Qj = Quantity of nuclide i released during the quarter, Ci.

D = dilution factor, as described above, cfs-1 .

Oq = radiological decay constant of nuclide i, s-1 (Table 6.2).

td = decay time for fish ingestion, equal to the travel time from the plant to the center of the reach plus one day to account for transit through the food chain and food preparation time (per Regulatory Guide 1.109), d.

8.64E+04 = conversion factor, seconds per day.

6.6.3 SHORELINE RECREATION Recreation doses are calculated for each identified reach within a 50 mile radius downstream of SQN (Table 6.1). It is assumed that the maximum exposed individual spends 500 hours0.00579 days <br />0.139 hours <br />8.267196e-4 weeks <br />1.9025e-4 months <br /> per year on the shoreline at a location immediately downstream from the diffusers. The summation of individual recreation shoreline doses are calculated for the total body and skin as described below:

Dorg = 106 9.80E-09 rf YARIt Qi D exp(-8.64E+04 Di td) (6.10) where 106 = conversion factor, ptCi/Ci.

9.80E-09 = conversion factor, cfs per ml/h.

rf = recreation factor, used to account for the fact that the same amount of time will not be spent at a recreation site during each quarter. Recreation factors used are:

1st quarter- 0.1 2nd quarter - 0.3 3rd quarter - 0.4 4th quarter - 0.2.

ARt = dose factor for shoreline recreation for nuclide i, age group t, mrem/h per p.Cilml, as calculated in Section 6.7.3.

Q. = Quantity of nuclide i released during the quarter, Ci.

D = dilution factor, as described above, cfs-1 Q = radiological decay constant of nuclide i, s-1 (Table 6.2).

td = decay time for recreation, equal to the travel time from the plant to the center of the reach, d.

8.64E+04 = conversion factor, seconds per day.

SQN ODCM Revision 47 Page 76 of 168 6.6.4 TOTAL MAXIMUM INDIVIDUAL DOSE The total maximum individual total body dose is obtained by summing the following for each age group: the highest total body water ingestion dose from among all the public water supplies; the highest total body fish ingestion dose from among all the reaches; and the total body maximum shoreline recreation dose. The total maximum individual organ dose is obtained by summing the following for each organ and each age group: that organ's highest water ingestion dose from among all the public water supplies; that organ's highest fish ingestion dose from among all the reaches; and the total body maximum shoreline recreation dose. The total maximum individual skin dose is that skin dose calculated for the maximum shoreline dose.

6.6.5 POPULATION DOSES For determining population doses to the 50-mile population around the plant, an average dose is calculated for each age group and each pathway and then multiplied by the population.

For water ingestion, the general equation used for calculating the population doses, POPWTR, in man-rem for a given PWS is:

4 4 POPWTRt = 10-3 1 POPm L POPa ATMWa TWDOSamt (6.11) m=1 a=1 where:

POPWTRt = water ingestion population dose to organ t, man-rem.

POPa = fraction of population in each age group a (from NUREG CR-1004, table 3.39).

Adult = 0.665 Child = 0.168 Infant = 0.015 Teen = 0.153 POPM = population at PWS m. The 4 PWSs and their populations are listed in Table 6.1.

ATMWa = ratio of average to maximum water ingestion rates for each age group a. Maximum water ingestion rates are given in Table 6.3. Average water ingestion rates, in I/year, (from R.G. 1.109 Table E-4) are:

Adult = 370 Child = 260 Infant = 260 Teen = 260 TWDOSamt = total individual water ingestion dose to organ t at PWS m, to the age group a, as described in Section 6.6.1, mrem.

10-3 = conversion factor for rem/mrem.

SQN ODCM Revision 47 Page 77 of 168 For population doses resulting from fish ingestion the calculation assumes that all fish caught within a 50-mile radius downstream of SQN are consumed by local population. The general equation for calculating population doses, POPF, in man-rem from fish ingestion of all fish caught within a 50-mile radius downstream is:

453.6 HVST APR 4 3 TFDOSart P°pa POPFt= o E (6.12) 103 103 r=1 a=1 FISHa POPa where:

POPFt = total fish ingestion population dose to organ t, man-rem.

HVST = fish harvest for the Tennessee River, 3.04 lbs/acre/y.

APR = size of reach, acres (Table 6.1).

TFDOSart = total fish ingestion dose to organ t for reach r, for the age group a, as described in Section 6.6.2, mrem.

POPa = fraction of population in each age group a, as given above.

FISHa = amount of fish ingested by each age group a, kg/y. Average fish ingestion rates (R.G. 1.109 Table E-4) are:

Adult = 6.9 Child = 2.2 Teen = 5.2 453.6 = conversion factor, g/lb.

103 = conversion factor, mrem/rem.

103 = conversion factor, g/kg.

SQN ODCM Revision 47 Page 78 of 168 For recreation shoreline, the general equation used for calculating the population doses, POPR, in man-rem is:

REQFRA 4 POPRt = f TSHDOSrt SHVISr HRSVISr (6.13) 10 3 8760 r=1 where:

POPRt = total recreation population dose for all reaches to organ t, man-rem.

REQFRA = fraction of yearly recreation which occurs in that quarter, as given in Section 6.6.3.

TSHDOSrt= total shoreline dose rate for organ t, in reach r, mrem/h.

SHVISr = shoreline visits per year at each reach r, (Table 6.1).

HRSVISr = length of shoreline recreation visit at reach r, 5 hours5.787037e-5 days <br />0.00139 hours <br />8.267196e-6 weeks <br />1.9025e-6 months <br />.

103 = conversion factor, mrem/rem.

8760 = conversion factor, hours per year.

SQN ODCM Revision 47 Page 79 of 168 6.7 LIQUID DOSE FACTOR EQUATIONS 6.7.1 WATER INGESTION Awit (mrem/h per jtCi/ml)

DFLiat Uwa 106 103 Awit = _

8760 where:

DFLijt= ingestion dose conversion factor for nuclide i, age group a, organ t, mrem/pCi, (Table 6.4).

UW = water consumption rate for age group a, L/y, (Table 6.3).

106 = conversion factor, pCi/RCi.

103 = conversion factor, ml/I.

8760 = conversion factor, hours per year.

6.7.2 FISH INGESTION AFit (mrem/h per 0Ci/ml)

DFLiat Ufa Bi 106 103 AFit =

8760 where:

DFLiat= ingestion dose conversion factor for nuclide i, age group a, organ t, mrem/pCi, (Table 6.4).

Ufa = fish consumption rate for age group a, kg/y, (Table 6.3).

B. = bioaccumulation factor for nuclide i, pCi/kg per pCi/L, (Table 6.5).

106 = conversion factor, pCi/RCi.

103 = conversion factor, ml/L.

8760 = conversion factor, hours per year.

6.7.3 SHORELINE RECREATION ARit (mrem/h per igCi/ml).

DFGit Kc M W 103 106 U ARit= [1 -exp(-ODtb)]

8760

  • 3600 E where:

DFGit= dose conversion factor for standing on contaminated ground for nuclide i and organ t (total body and skin), mrem/h per pCi/m 2, (Table 6.6).

K, = transfer coefficient from water to shoreline sediment, L/kg-h, (Table 6.3).

M = mass density of sediment, kg/m2 , (Table 6.3).

W = shoreline width factor, dimensionless, (Table 6.3).

103 = conversion factor, ml/L.

106 = conversion factor, pCi/gCi.

3600 = conversion factor, s/h.

o; = decay constant for nuclide i, s-1, (Table 6.2).

tb = time shoreline is exposed to the concentration on the water, s, (Table 6.3).

U = usage factor, 500 h/y.

8760 = conversion factor, hours per year.

SQN ODCM Revision 47 Page 80 of 168 Table 6.1 RECEPTORS FOR LIQUID DOSE CALCULATIONS Tennessee River Reaches Within 50 Mile Radius Downstream of SQN Beginning Ending Size Recreation Name TRM TRM (acres) visits/w 3ar Chickamauga Lake 484 471 9939 5,226, 700 below SQN Nickajack Lake 471 435 5604 240,' 700 (Chickamauga Dam to TRM 435)

Nickajack Lake 435 425 5326 607,( 300 (TRM 435 to Nickajack Dam)

Guntersville Lake 425 400 6766 104,()00 (Nickajack Dam to SQN 50 mi. Radius)

Public Water Supplies Within 50 Mile Radius Downstream of SQN Name TRM Population East Side Utility 473.0 35000 (Formally C.F. Industries)

Chattanooga, TN 465.3 224,000 South Pittsburg, TN 418.0 4,898 Bridgeport, AL 413.6 4,650

SQN ODCM Revision 47 Page 81 of 168 Table 6.2 RADIONUCLIDE DECAY AND STABLE ELEMENT TRANSFER DATA (Page 1 of 3)

Half-Life Biv Fmi Fm; Ff1 (minutes) (1s) (cow) (goat) (beef)

H-3 6.46E+06 1.79E-09 4.80E+00 1.00E-02 1.70E-01 1.20E-02 C-14 3.01E+09 3.84E-12 5.50E+00 1.20E-02 1.OOE-01 3.10E-02 Na-24 9.OOE+02 1.28E-05 5.20E-02 4.OOE-02 4.OOE-02 3.OOE-02 P-32 2.06E+04 5.61E-07 1.10E+00 2.50E-02 2.50E-01 4.60E-02 Cr-51 3.99E+04 2.90E-07 2.50E-04 2.20E-03 2.20E-03 2.40E-03 Mn-54 4.50E+05 2.57E-08 2.90E-02 2.50E-04 2.50E-04 8.OOE-04 Mn-56 1.55E+02 7.45E-05 2.90E-02 2.50E-04 2.50E-04 8.OOE-04 Fe-55 1.42E+06 8.13E-09 6.60E-04 1.20E-03 1.30E-04 1.20E-02 Fe-59 6.43E+04 1.80E-07 6.60E-04 1.20E-03 1.30E-04 1.20E-02 Co-57 3.90E+05 2.96E-08 9.40E-03 1.00E-03 1.OOE-03 1.30E-02 Co-58 1.02E+05 1.13E-07 9.40E-03 1.OOE-03 1.OOE-03 1.30E-02 Co-60 2.77E+06 4.17E-09 9.40E-03 1.00E-03 1.OOE-03 1.30E-02 Ni-63 5.27E+07 2.19E-10 1.90E-02 6.70E-03 6.70E-03 5.30E-02 Ni-65 1.51E+02 7.65E-05 1.90E-02 6.70E-03 6.70E-03 5.30E-02 Cu-64 7.62E+02 1.52E-05 1.20E-01 1.40E-02 1.30E-02 9.70E-04 Zn-65 3.52E+05 3.28E-08 4.OOE-01 3.90E-02 3.90E-02 3.OOE-02 Zn-69m 8.26E+02 1.40E-05 4.OOE-01 3.90E-02 3.90E-02 3.OOE-02 Zn-69 5.56E+01 2.08E-04 4.OOE-01 3.90E-02 3.90E-02 3.OOE-02 Br-82 2.12E+03 5.45E-06 7.60E-01 5.OOE-02 5.OOE-02 2.60E-02 Br-83 1.43E+02 8.08E-05 7.60E-01 5.OOE-02 5.OOE-02 2.60E-02 Br-84 3.18E+01 3.63E-04 7.60E-01 5.OOE-02 5.OOE-02 2.60E-02 Br-85 2.87E+00 4.02E-03 7.60E-01 5.OOE-02 5.OOE-02 2.60E-02 Rb-86 2.69E+04 4.29E-07 1.30E-01 3.OOE-02 3.OOE-02 3.1OE-02 Rb-88 1.78E+01 6.49E-04 1.30E-01 3.OOE-02 3.OOE-02 3.1OE-02 Rb-89 1.54E+01 7.50E-04 1.30E-01 3.OOE-02 3.OOE-02 3.1OE-02 Sr-89 7.28E+04 1.59E-07 1.70E-02 1.40E-03 1.40E-02 6.OOE-04 Sr-90 1.50E+07 7.70E-10 1.70E-02 1.40E-03 1.40E-02 6.OOE-04 Sr-91 5.70E+02 2.03E-05 1.70E-02 1.40E-03 1.40E-02 6.OE-04 Sr-92 1.63E+02 7.09E-05 1.70E-02 1.40E-03 1.40E-02 6.OOE-04 Y-90 3.85E+03 3.OOE-06 2.60E-03 1.00E-05 1.OOE-05 4.60E-03 Y-91 m 4.97E+01 2.32E-04 2.60E-03 1.OOE-05 1.OOE-05 4.60E-03 Y-91 8.43E+04 1.37E-07 2.60E-03 1.00E-05 1.OOE-05 4.60E-03 Y-92 2.12E+02 5.45E-05 2.60E-03 1.00E-05 1.00E-05 4.60E-03 Y-93 6.06E+02 1.91 E-05 2.60E-03 1.OOE-05 1.OOE-05 4.60E-03 Zr-95 9.22E+04 1.25E-07 1.70E-04 5.OOE-06 5.OOE-06 3.40E-02 Zr-97 1.01E+03 1.14E-05 1.70E-04 5.OOE-06 5.OOE-06 3.40E-02 Nb-95 5.05E+04 2.29E-07 9.40E-03 2.50E-03 2.50E-03 2.80E-01 Nb-97 7.21 E+01 1.60E-04 9.40E-03 2.50E-03 2.50E-03 2.80E-01 Mo-99 3.96E+03 2.92E-06 1.20E-01 7.50E-03 7.50E-03 1.10E-03 Tc-99m 3.61E+02 3.20E-05 2.50E-01 2.50E-02 2.50E-02 4.OOE-01 Tc-101 1.42E+01 8.13E-04 2.50E-01 2.50E-02 2.50E-02 4.OOE-01 Ru-1 03 5.67E+04 2.04E-07 5.OOE-02 1.00E-06 1.00E-06 4.OOE-01 Ru-105 2.66E+02 4.34E-05 5.OOE-02 1.OOE-06 1.OOE-06 4.OOE-01 Ru-106 5.30E+05 2.18E-08 5.OOE-02 1.OOE-06 1.OOE-06 4.OOE-01

SQN ODCM Revision 47 Page 82 of 168 Table 6.2 RADIONUCLIDE DECAY AND STABLE ELEMENT TRANSFER DATA (Page 2 of 3)

Half-Life 0 Bj, Fmi Fmi Ffi (minutes) (1is) (cow) (goat) (beef)

Ag-11 Om 3.60E+05 3.21 E-08 1.50E-01 5.OOE-02 5.OOE-02 1.70E-02 Sb-124 8.67E+04 1.33E-07 N/A 1.50E-03 1.50E-03 N/A Sb-125 1.46E+06 7.91E-09 N/A 1.50E-03 1.50E-03 N/A Sn-125 1.39E+04 8.32E-07 N/A N/A N/A N/A Te-125m 8.35E+04 1.38E-07 1.30E+00 1.OOE-03 1.OOE-03 7.70E-02 Te-127m 1.57E+05 7.36E-08 1.30E+00 1.OOE-03 1.OOE-03 7.70E-02 Te-127 5.61E+02 2.06E-05 1.30E+00 1.OOE-03 1.OOE-03 7.70E-02 Te-129m 4.84E+04 2.39E-07 1.30E+00 1.OOE-03 1.OOE-03 7.70E-02 Te-129 6.96E+01 1.66E-04 1.30E+00 1 .OOE-03 1.OOE-03 7.70E-02 Te-131 m 1.80E+03 6.42E-06 1.30E+00 1.OOE-03 1.OOE-03 7.70E-02 Te-131 2.50E+01 4.62E-04 1.30E+00 1.OOE-03 1.00E-03 7.70E-02 Te-132 4.69E+03 2.46E-06 1.30E+00 1.OOE-03 1.OOE-03 7.70E-02 1-130 7.42E+02 1.56E-05 2.OOE-02 1.20E-02 4.30E-01 2.90E-03 1-131 1.16E+04 9.96E-07 2.OOE-02 1.20E-02 4.30E-01 2.90E-03 1-132 1.38E+02 8.37E-05 2.OOE-02 1.20E-02 4.30E-01 2.90E-03 1-133 1.25E+03 9.24E-06 2.OOE-02 1.20E-02 4.30E-01 2.90E-03 1-134 5.26E+01 2.20E-04 2.OOE-02 1.20E-02 4.30E-01 2.90E-03 1-135 3.97E+02 2.91E-05 2.OOE-02 1.20E-02 4.30E-01 2.90E-03 Cs-134 1.08E+06 1.06E-08 1.OOE-02 8.OOE-03 3.OOE-01 1.50E-02 Cs-136 1.90E+04 6.08E-07 1.OOE-02 8.OOE-03 3.OOE-01 1.50E-02 Cs-137 1.59E+07 7.26E-10 1.OOE-02 8.OOE-03 3.OOE-01 1.50E-02 Cs-138 3.22E+01 3.59E-04 1.OOE-02 8.OOE-03 3.OOE-01 1.50E-02 Ba-139 8.31E+01 1.39E-04 5.OOE-03 4.OOE-04 4.OOE-04 3.20E-03 Ba-140 1.84E+04 6.28E-07 5.OOE-03 4.OOE-04 4.OOE-04 3.20E-03 Ba-141 1.83E+01 6.31 E-04 5.OOE-03 4.OOE-04 4.OOE-04 3.20E-03 Ba-142 1.07E+01 1.08E-03 5.OOE-03 4.OOE-04 4.OOE-04 3.20E-03 La-140 2.41 E+03 4.79E-06 2.50E-03 5.OOE-06 5.OOE-06 2.OOE-04 La-142 9.54E+01 1.21 E-04 2.50E-03 5.OOE-06 5.OOE-06 2.OOE-04 Ce-141 4.68E+04 2.47E-07 2.50E-03 1.OOE-04 1.OOE-04 1.20E-03 Ce-143 1.98E+03 5.83E-06 2.50E-03 1.OOE-04 1.OOE-04 1.20E-03 Ce-144 4.09E+05 2.82E-08 2.50E-03 1.OOE-04 1.OOE-04 1.20E-03 Pr-143 1.95E+04 5.92E-07 2.50E-03 5.OOE-06 5.00E-06 4.70E-03 Pr-144 1.73E+01 6.68E-04 2.50E-03 5.OOE-06 5.OOE-06 4.70E-03 Nd-147 1.58E+04 7.31 E-07 2.40E-03 5.OOE-06 5.OOE-06 3.30E-03 W-187 1.43E+03 8.08E-06 1.80E-02 5.OOE-04 5.OOE-04 1.30E-03 Np-239 3.39E+03 3.41 E-06 2.50E-03 5.OOE-06 5.OOE-06 2.OOE-04 Ar-41 1.10E+02 1.05E-04 N/A N/A N/A N/A Kr-83m 1.10E+02 1.05E-04 N/A N/A N/A N/A Kr-85m 2.69E+02 4.29E-05 N/A N/A NIA N/A Kr-85 5.64E+06 2.05E-09 N/A N/A N/A N/A Kr-87 7.63E+01 1.51 E-04 N/A N/A N/A N/A Kr-88 1.70E+02 6.79E-05 N/A N/A N/A N/A Kr-89 3.16E+00 3.66E-03 N/A N/A N/A N/A Kr-90 5.39E-01 2.14E-02 N/A N/A N/A N/A Xe-131m 1.70E+04 6.79E-07 N/A N/A N/A N/A

SQN ODCM Revision 47 Page 83 of 168 Table 6.2 RADIONUCLIDE DECAY AND STABLE ELEMENT TRANSFER DATA (Page 3 of 3)

Half-Life Biv Fmi Fmj Ffi (minutes) (11s) (cow) (goat) (beef)

Xe-133m 3.15E+03 3.67E-06 N/A N/A N/A N/A Xe-1 33 7.55E+03 1.53E-06 N/A N/A N/A N/A Xe-1 35m 1.54E+01 7.50E-04 N/A N/A N/A N/A Xe-1 35 5.47E+02 2.11E-05 N/A N/A N/A N/A Xe-1 37 3.83E+00 3.02E-03 N/A N/A N/A N/A Xe-1 38 1.41 E+01 8.19E-04 N/A N/A N/A N/A

References:

Half lives for all nuclides: DOE-TIC-1 1026, "Radioactive Decay Data Tables - A handbook of Decay Data for Application to Radiation Dosimetry and Radiological Assessment," D. C. Kocher, 1981.

Transfer factors for Sb- isotopes are from ORNL 4992, "Methodology for Calculating Radiation Doses from Radioactivity Released to the Environment," March 1976, Table 2-7.

Cow-milk transfer factors for Iodine, Strontium, and Cesium nuclides are from NUREG/CR-1004, Table 3.17.

Goat-milk transfer factors for Iodine nuclides are from NUREG/CR-1004, Table 3.17.

Beef transfer factors for Iron, Copper, Molybdenum, and Cesium nuclides are from NUREG/CR-1004, Table 3.18.

All other nuclides' transfer factors are from Regulatory Guide 1.109, Tables E-1 and E-2.

SQN ODCM Revision 47 Page 84 of 168 Table 6.3 DOSE CALCULATION FACTORS (Page 1 of 2)

Factor Value Units Reference BRa (infant) 1400 m3 /year ICRP 23 BRa (child) 5500 m3 /year ICRP 23 BRa (teen) 8000 m3 /year ICRP 23 BRa (adult) 8100 m3 /year ICRP 23 fg 1 TVA Assumption fLy 1 R. G. 1.109 (Table E-15) fP 1 TVA Assumption 0 TVA Assumption H 9 g/m 3 TVA Value Kc 0.072 L/kg-h R. G. 1.109 (Section 2.C.)

M 40 kg/M2 R. G. 1.109 (Section 2.C.)

P 240 kg/M2 R. G. 1.109 (Table E-15)

Qf (cow) 64 kg/d NUREG/CR-1004 (Sect. 3.4)

Qf (goat) 08 kg/d NUREG/CR-1004 (Sect. 3.4) r 0.47 NUREG/CR-1004 (Sect. 3.2) tb 4.73E+08 seconds R. G. 1.109 (Table E-15)

(15 years) tcb 7.78E+06 seconds SQN FSAR Section 11.3.9.1 (90 days) tcsf 1 .56E+07 seconds SQN FSAR Section 11.3.9.1 (180 days) te 5.1 8E+06 seconds R. G. 1.109 (Table E-15)

(60 days) tep 2.59E+06 seconds R. G. 1.109 (Table E-15)

(30 days) tesf 7.78E+06 seconds R. G. 1.109 (Table E-15)

(90 days) tfm 8.64E+04 seconds SQN FSAR Section 11.3.9.1 (1 day) thc 8.64E+04 seconds NUREG/CR-1004, Table 3.40 (1 day) ts 1.12E+06 seconds NUREG/CR-1004, Table 3.40 (13 days) tsv 2.38E+07 seconds SQN FSAR Section 11.3.9.1 (275 days)

Uam (infant) 0 kg/year R. G. 1.109 (Table E-5)

Uam (child) 41 kg/year R. G. 1.109 (Table E-5)

Uam (teen) 65 kg/year R. G. 1.109 (Table E-5)

Uam (adult) 110 kg/year R. G. 1.109 (Table E-5)

Uap (infant) 330 I/year R. G. 1.109 (Table E-5)

Uap (child) 330 I/year R. G. 1.109 (Table E-5)

Uap (teen) 400 I/year R. G. 1.109 (Table E-5)

Up (adult) 310 I/year R. G. 1.109 (Table E-5)

Ufa(infant) 0 kg/year R. G. 1.109 (Table E-5)

Ufa(child) 6.9 kg/year R. G. 1.109 (Table E-5)

Uf8 (teen) 16 kg/year R. G. 1.109 (Table E-5)

SQN ODCM Revision 47 Page 85 of 168 Table 6.3 DOSE CALCULATION FACTORS (Page 2 of 2)

Factor Value Units Reference Ufa(adult) 21 kg/year R. G. 1.109 (Table E-5)

Ufla (infant) 0 kg/year R. G. 1.109 (Table E-5)

Ufla (child) 26 kg/year R. G. 1.109 (Table E-5)

Ufla (teen) 42 kg/year R. G. 1.109 (Table E-5)

Ufla (adult) 64 kg/year R. G. 1.109 (Table E-5)

Usa (infant) 0 kg/year R. G. 1.109 (Table E-5)

Usa (child) 520 kg/year R. G. 1.109 (Table E-5)

Usa (teen) 630 kg/year R. G. 1.109 (Table E-5)

Usa (adult) 520 kg/year R. G. 1.109 (Table E-5)

Uwa(infant) 330 L/year R. G. 1.109 (Table E-5)

Uwa(child) 510 Uyear R. G. 1.109 (Table E-5)

Uwa(teen) 510 L/year R. G. 1.109 (Table E-5)

Uwa(adult) 730 L/year R. G. 1.109 (Table E-5) w 0.3 none R. G. 1.109 (Table A-2)

Yf 1.85 kg/m2 NUREG/CR-1004 (Table 3.4)

Yp 1.18 kg/M2 NUREG/CR-1004 (Table 3.3)

Y~f 0.64 kg/m2 NUREG/CR-1004 (Table 3.3)

Ysv 0.57 kg/m2 NUREG/CR-1004 (Table 3.4)

(value selected is for non-leafy vegetables)

E]w (iodines) 7.71 E-07 sec-1 NUREG/CR-1004 (Table 3.10)

(10.4 d half-life) 1 Dw (particulates) 5.21 E-07 sec NUREG/CR-1004 (Table 3.10)

(15.4 d half-life)

SQN ODCM Revision 47 Page 86 of 168 Table 6.4 INGESTION DOSE FACTORS (mrem/pCi ingested)

(Page 1 of 8)

ADULT bone liver t body thyroid kidney lung gi-lli H-3 1.05E-07 1.05E-07 1.05E-07 1.05E-07 1.05E-07 1.05E-07 1.05E-07 C-14 2.84E-06 5.68E-07 5.68E-07 5.68E-07 5.68E-07 5.68E-07 5.68E-07 Na-24 1.70E-06 1.70E-06 1.70E-06 1.70E-06 1.70E-06 1.70E-06 1.70E-06 P-32 1.93E-04 1.20E-05 7.46E-06 0.OOE+00 O.OOE+00 O.OOE+00 2.17E-05 Cr-51 0.OOE+00 0.OOE+00 2.66E-09 1.59E-09 5.86E-10 3.53E-09 6.69E-07 Mn-54 O.OOE+00 4.57E-06 8.72E-07 O.OOE+00 1.36E-06 O.OOE+00 1.40E-05 Mn-56 0.OOE+00 1.15E-07 2.04E-08 O.OOE+00 1.46E-07 0.OOE+00 3.67E-06 Fe-55 2.75E-06 1.90E-06 4.43E-07 O.OOE+00 O.OOE+00 1.06E-06 1.09E-06 Fe-59 4.34E-06 1.02E-05 3.91 E-06 O.OOE+00 O.OOE+00 2.85E-06 3.40E-05 Co-57 0.OOE+00 1.75E-07 2.91 E-07 0.OOE+00 O.OOE+00 O.OOE+00 4.44E-06 Co-58 O.OOE+00 7.45E-07 1.67E-06 O.OOE+00 O.OOE+00 O.OOE+00 1.51 E-05 Co-60 0.OOE+00 2.14E-06 4.72E-06 0.OOE+00 0.OOE+00 0.OOE+00 4.02E-05 Ni-63 1.30E-04. 9.01 E-06 4.36E-06 0.OOE+00 0.OOE+00 O.OOE+00 1.88E-06 Ni-65 5.28E-07 6.86E-08 3.13E-08 0.OOE+00 0.OOE+00 0.OOE+00 1.74E-06 Cu-64 O.OOE+00 8.33E-08 3.91E-08 0.OOE+00 2.10E-07 0.OOE+00 7.1OE-06 Zn-65 4.84E-06 1.54E-05 6.96E-06 O.OOE+00 1.03E-05 0.OOE+00 9.70E-06 Zn-69 1.03E-08 1.97E-08 1.37E-09 O.OOE+00 1.28E-08 O.OOE+00 2.96E-09 Zn-69m 1.70E-07 4.08E-07 3.73E-08 0.OOE+00 2.47E-07 0.OOE+00 2.49E-05 Br-82 0.OOE+00 O.OOE+00 2.26E-06 0.OOE+00 O.OOE+00 O.OOE+00 2.59E-06 Br-83 O.OOE+00 O.OOE+00 4.02E-08 O.OOE+00 O.OOE+00 0.OOE+00 5.79E-08 Br-84 0.OOE+00 0.OOE+00 5.21 E-08 O.OOE+00 0.OOE+00 0.OOE+00 4.09E-13 Br-85 O.OOE+00 O.OOE+00 2.14E-09 0.OOE+00 0.OOE+00 0.OOE+00 O.OOE+00 Rb-86 0.OOE+00 2.11E-05 9.83E-06 0.OOE+00 O.OOE+00 0.OOE+00 4.16E-06 Rb-88 O.OOE+00 6.05E-08 3.21E-08 O.OOE+00 0.OOE+00 O.OOE+00 8.36E-19 Rb-89 0.OOE+00 4.01 E-08 2.82E-08 0.OOE+00 O.OOE+00 0.OOE+00 2.33E-21 Sr-89 3.08E-04 0.OOE+00 8.84E-06 0.OOE+00 0.OOE+00 O.OOE+00 4.94E-05 Sr-90 7.58E-03 0.OOE+00 1.86E-03 0.OOE+00 0.OOE+00 0.OOE+00 2.19E-04 Sr-91 5.67E-06 O.OOE+00 2.29E-07 0.OOE+00 0.OOE+00 0.OOE+00 2.70E-05 Sr-92 2.15E-06 0.OOE+00 9.30E-08 0.OOE+00 0.OOE+00 O.OOE+00 4.26E-05 Y-90 9.62E-09 O.OOE+00 2.58E-10 0.OOE+00 O.OOE+00 O.OOE+00 1.02E-04 Y-91m 9.09E-11 O.OOE+00 3.52E-12 O.OOE+00 0.OOE+00 O.OOE+00 2.67E-10 Y-91 1.41 E-07 O.OOE+00 3.77E-09 0.OOE+00 O.OOE+00 0.OOE+00 7.76E-05 Y-92 8.45E-10 0.OOE+00 2.47E-11 0.OOE+00 0.OOE+00 O.OOE+00 1.48E-05 Y-93 2.68E-09 0.OOE+00 7.40E-11 O.OOE+00 0.OOE+00 O.OOE+00 8.50E-05 Zr-95 3.04E-08 9.75E-09 6.60E-09 0.OOE+00 1.53E-08 0.OOE+00 3.09E-05 Zr-97 1.68E-09 3.39E-10 1.55E-10 O.OOE+00 5.12E-10 0.OOE+00 1.05E-04 Nb-95 6.22E-09 3.46E-09 1.86E-09 0.OOE+00 3.42E-09 0.OOE+00 2.10E-05 Nb-97 5.22E-11 1.32E-11 4.82E-12 0.OOE+00 1.54E-11 0.OOE+00 4.87E-08 Mo-99 O.OOE+00 4.31 E-06 8.20E-07 0.OOE+00 9.76E-06 0.OOE+00 9.99E-06 Tc-99m 2.47E-10 6.98E-10 8.89E-09 0.OOE+00 1.06E-08 3.42E-10 4.13E-07 Tc-101 2.54E-10 3.66E-10 3.59E-09 0.OOE+00 6.59E-09 1.87E-10 1.10E-21 Ru-103 1.85E-07 O.OOE+00 7.97E-08 0.OOE+00 7.06E-07 0.OOE+00 2.16E-05 Ru-105 1.54E-08 0.OOE+00 6.08E-09 O.OOE+00 1.99E-07 0.OOE+00 9.42E-06 Ru-106 2.75E-06 O.OOE+00 3.48E-07 0.OOE+00 5.31E-06 O.OOE+00 1.78E-04

SQN ODCM Revision 47 Page 87 of 168 Table 6.4 INGESTION DOSE FACTORS (mrem/pCi ingested)

(Page 2 of 8)

ADULT bone liver t body thyroid kidney lung gi-Ili Ag-11 Om 1.60E-07 1.48E-07 8.79E-08 0.OOE+00 2.91 E-07 O.OOE+O0 6.04E-05 Sb-1 24 2.80E-06 5.29E-08 1.11E-06 6.79E-09 O.OOE-00 2.18E-06 7.95E-05 Sb-125 1.79E-06 2.00E-08 4.26E-07 1.82E-09 O.OOE-00 1.38E-06 1.97E-05 Sn-125 8.33E-06 1.68E-07 3.78E-07 1.39E-07 O.OOE-00 O.OOE-OO 1.04E-04 Te-125m 2.68E-06 9.71 E-07 3.59E-07 8.06E-07 1.09E-05 O.OOE+OO 1.07E-05 Te-127m 6.77E-06 2.42E-06 8.25E-07 1.73E-06 2.75E-05 O.OOE+0O 2.27E-05 Te-127 1.1OE-07 3.95E-08 2.38E-08 8.15E-08 4.48E-07 O.OOE+0O 8.68E-06 Te-129m 1.15E-05 4.29E-06 1.82E-06 3.95E-06 4.80E-05 O.OOE+0O 5.79E-05 Te-129 3.14E-08 1.18E-08 7.65E-09 2.41 E-08 1.32E-07 O.OOE+00 2.37E-08 Te-131m 1.73E-06 8.46E-07 7.05E-07 1.34E-06 8.57E-06 O.OOE+O0 8.40E-05 Te-131 1.97E-08 8.23E-09 6.22E-09 1.62E-08 8.63E-08 O.OOE+O0 2.79E-09 Te-132 2.52E-06 1.63E-06 1.53E-06 1.80E-06 1.57E-05 O.OOE+00 7.71 E-05 1-130 7.56E-07 2.23E-06 8.80E-07 1.89E-04 3.48E-06 O.OOE+00 1.92E-06 1-131 4.16E-06 5.95E-06 3.41 E-06 1.95E-03 1.02E-05 O.OOE+O0 1.57E-06 1-132 2.03E-07 5.43E-07 1.90E-07 1.90E-05 8.65E-07 O.OOE+O0 1.02E-07 1-133 1.42E-06 2.47E-06 7.53E-07 3.63E-04 4.31 E-06 O.OOE+00 2.22E-06 1-134 1.06E-07 2.88E-07 1.03E-07 4.99E-06 4.58E-07 O.OOE+00 2.51 E-10 1-135 4.43E-07 1.16E-06 4.28E-07 7.65E-05 1.86E-06 O.OOE+00 1.31 E-06 Cs-134 6.22E-05 1.48E-04 1.21 E-04 O.00E+00 4.79E-05 1.59E-05 2.59E-06 Cs-136 6.51 E-06 2.57E-05 1.85E-05 0.00E+00 1.43E-05 1.96E-06 2.92E-06 Cs-1 37 7.97E-05 1.09E-04 7.14E-05 0.00E+00 3.70E-05 1.23E-05 2.i1 E-06 Cs-1 38 5.52E-08 1.09E-07 5.40E-08 0.00E+00 8.01 E-08 7.91 E-09 4.65E-1 3 Ba-139 9.70E-08 6.91E-1I 2.84E-09 0.00E+00 6.46E-11 3.92E-1i1 1.72E-07 Ba-140 2.03E-05 2.55E-08 1.33E-06 0.00E+00 8.67E-09 1.46E-08 4.18E-05 Ba-141 4.71 E-08 3.56E-1i1 1.59E-09 0.00E+00 3.31E-11 2.02E-i 1 2.22E-1 7 Ba-142 2.13E-08 2.19E-11 1.34E-09 0.OOE+00 1.85E-11 1.24E-11 3.OOE-26 La-140 2.50E-09 1.26E-09 3.33E-1 0 0.OOE+00 O.OOE+O0 O.OOE+O0 9.25E-05 La-142 1.28E-1 0 5.82E-1 1 1.45E-11 0.00E+00 O.OOE+00 O.OOE+00 4.25E-07 Ce-141 9.36E-09 6.33E-09 7.18E-10 0.00E+00 2.94E-09 O.OOE+00 2.42E-05 Ce-143 1.65E-09 1.22E-06 1.35E-10 O.00E+00 5.37E-1 0 O.OOE+O0 4.56E-05 Ce-144 4.88E-07 2.04E-07 2.62E-08 0.OOE+00 1.21 E-07 O.OOE+00 1.65E-04 Pr-143 9.20E-09 3.69E-09 4.56E-10 0.OOE+00 2.13E-09 O.OOE+00 4.03E-05 Pr-144 3.01 E-11 1.25E-11 1.53E-12 0.OOE+00 7.05E-1 2 O.OOE+00 4.33E-1 8 Nd-147 6.29E-09 7.27E-09 4.35E-10 0.OOE+00 4.25E-09 O.OOE+00 3.49E-05 W-187 1.03E-07 8.61 E-08 3.01 E-08 0.00E+00 O.OOE+00 O.OOE+00 2.82E-05 Np-239 1.19E-09 1.17E-10 6.45E-1 1 0.00E+00 3.65E-1 0 O.OOE+00 2.40E-05 NOTE: The tritium dose factor for bone is assumed to be equal to the total body dose factor.

REFERENCES:

Regulatory Guide 1.109, Table E-i1.

Dose Factors for Co-57, Zn-69m, Br-82, Nb-97, Sn-125, Sb-124 and Sb-125 are from NUREG-0172 Age Specific Radiation Dose Commitment Factors for a One Year Chronic Intake,,

November, 1977, Table 4.

SQN ODCM Revision 47 Page 88 of 168 Table 6.4 INGESTION DOSE FACTORS (mrem/pCi ingested)

(Page 3 of 8)

TEEN bone liver t body thyroid kidney lung gi-lli H-3 1.06E-07 1.06E-07 1.06E-07 1.06E-07 1.06E-07 1.06E-07 1.06E-07 C-14 4.06E-06 8.12E-07 8.12E-07 8.12E-07 8.12E-07 8.12E-07 8.12E-07 Na-24 2.30E-06 2.30E-06 2.30E-06 2.30E-06 2.30E-06 2.30E-06 2.30E-06 P-32 2.76E-04 1.71 E-05 1.07E-05 0.OOE+00 0.OOE+00 O.OOE+00 2.32E-05 Cr-51 0.OOE+00 0.OOE+00 3.60E-09 2.OOE-09 7.89E-10 5.14E-09 6.05E-07 Mn-54 0.OOE+00 5.90E-06 1.17E-06 0.OOE+00 1.76E-06 O.OOE+00 1.21E-05 Mn-56 O.OOE+00 1.58E-07 2.81 E-08 0.OOE+00 2.OOE-07 0.OOE+00 1.04E-05 Fe-55 3.78E-06 2.68E-06 6.25E-07 O.OOE+00 0.OOE+00 1.70E-06 1.16E-06 Fe-59 5.87E-06 1.37E-05 5.29E-06 0.00E+00 O.OOE+00 4.32E-06 3.24E-05 Co-57 0.OOE+00 2.38E-07 3.99E-07 0.00E+00 O.OOE+00 O.OOE+00 4.44E-06 Co-58 O.OOE+00 9.72E-07 2.24E-06 0.OOE+00 O.OOE+00 0.OOE+00 1.34E-05 Co-60 0.OOE+00 2.81 E-06 6.33E-06 0.OOE+00 O.OOE+00 0.OOE+00 3.66E-05 Ni-63 1.77E-04 1.25E-05 6.00E-06 0.00E+00 0.OOE+00 0.00E+00 1.99E-06 Ni-65 7.49E-07 9.57E-08 4.36E-08 0.00E+00 0.OOE+00 0.00E+00 5.19E-06 Cu-64 0.OOE+00 1.15E-07 5.41E-08 0.OOE+00 2.91E-07 0.OOE+00 8.92E-06 Zn-65 5.76E-06 2.OOE-05 9.33E-06 0.OOE+00 1.28E-05 0.OOE+00 8.47E-06 Zn-69 1.47E-08 2.80E-08 1.96E-09 0.OOE+00 1.83E-08 0.OOE+00 5.16E-08 Zn-69m 2.40E-07 5.66E-07 5.19E-08 0.00E+00 3.44E-07 0.OOE+00 3.11E-05 Br-82 O.00E+00 0.00E+00 3.04E-06 0.OOE+00 O.00E+00 0.OOE+00 0.OOE+00 Br-83 0.OOE+00 0.00E+00 5.74E-08 0.00E+00 O.OOE+00 0.OOE+00 0.00E+00 Br-84 0.OOE+00 0.OOE+00 7.22E-08 0.OOE+00 O.OOE+00 0.OOE+00 O.OOE+00 Br-85 0.OOE+00 0.00E+00 3.05E-09 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 Rb-86 0.00E+00 2.98E-05 1.40E-05 0.00E+00 0.00E+00 0.00E+00 4.41 E-06 Rb-88 O.OOE+00 8.52E-08 4.54E-08 0.OOE+00 0.OOE+00 O.OOE+00 7.30E-15 Rb-89 0.OOE+00 5.50E-08 3.89E-08 0.OOE+00 0.00E+00 0.00E+00 8.43E-17 Sr-89 4.40E-04 0.00E+00 1.26E-05 0.OOE+00 O.00E+00 0.OOE+00 5.24E-05 Sr-90 8.30E-03 0.OOE+00 2.05E-03 0.OOE+00 0.OOE+00 0.OOE+00 2.33E-04 Sr-91 8.07E-06 O.OOE+00 3.21 E-07 0.00E+00 0.OOE+00 0.OOE+00 3.66E-05 Sr-92 3.05E-06 0.OOE+00 1.30E-07 O.OOE+00 O.00E+00 0.OOE+00 7.77E-05 Y-90 1.37E-08 0.OOE+00 3.69E-10 0.OOE+00 0.OOE+00 O.OOE+00 1.13E-04 Y-91m 1.29E-10 O.OOE+00 4.93E-12 0.OOE+00 0.OOE+00 0.OOE+00 6.09E-09 Y-91 2.01 E-07 O.OOE+00 5.39E-09 0.00E+00 0.OOE+00 0.00E+00 8.24E-05 Y-92 1.21 E-09 O.OOE+00 3.50E-11 O.OOE+00 O.OOE+00 O.00E+00 3.32E-05 Y-93 3.83E-09 O.OOE+00 1.05E-10 0.OOE+00 O.OOE+00 0.OOE+00 1.17E-04 Zr-95 4.12E-08 1.30E-08 8.94E-09 0.00E+00 1.91E-08 0.00E+00 3.OOE-05 Zr-97 2.37E-09 4.69E-10 2.16E-10 0.OOE+00 7.11E-10 0.OOE+00 1.27E-04 Nb-95 8.22E-09 4.56E-09 2.51 E-09 0.OOE+00 4.42E-09 0.OOE+00 1.95E-05 Nb-97 7.37E-11 1.83E-11 6.68E-12 0.00E+00 2.14E-11 0.OOE+00 4.37E-07 Mo-99 0.OOE+00 6.03E-06 1.15E-06 0.00E+00 1.38E-05 0.OOE+00 1.08E-05 Tc-99m 3.32E-10 9.26E-10 1.20E-08 0.00E+00 1.38E-08 5.14E-10 6.08E-07 Tc-101 3.60E-10 5.12E-10 5.03E-09 0.OOE+00 9.26E-09 3.12E-10 8.75E-17 Ru-103 2.55E-07 0.00E+00 1.09E-07 0.OOE+00 8.99E-07 0.OOE+00 2.13E-05 Ru-105 2.18E-08 0.00E+00 8.46E-09 0.OOE+00 2.75E-07 0.OOE+00 1.76E-05 Ru-106 3.92E-06 O.OOE+00 4.94E-07 0.OOE+00 7.56E-06 O.OOE+00 1.88E-04

SQN ODCM Revision 47 Page 89 of 168 Table 6.4 INGESTION DOSE FACTORS (mrem/pCi ingested)

(Page 4 of 8)

TEEN bone liver t body thyroid kidney lung gi-lli Ag-110m 2.05E-07 1.94E-07 1.18E-07 O.OOE+00 3.70E-07 0.OOE+00 5.45E-05 Sb-124 3.87E-06 7.13E-08 1.51E-06 8.78E-09 0.OOE-00 3.38E-06 7.80E-05 Sb-125 2.48E-06 2.71E-08 5.80E-07 2.37E-09 O.OOE+00 2.18E-06 1.93E-05 Sn-125 1.19E-05 2.37E-07 5.37E-07 1.86E-07 O.OOE+00 O.OOE+00 1.12E-04 Te-125m 3.83E-06 1.38E-06 5.12E-07 1.07E-06 O.OOE+00 O.OOE+00 1.13E-05 Te-127m 9.67E-06 3.43E-06 1.15E-06 2.30E-06 3.92E-05 O.OOE+00 2.41 E-05 Te-127 1.58E-07 5.60E-08 3.40E-08 1.09E-07 6.40E-07 O.OOE+00 1.22E-05 Te-129m 1.63E-05 6.05E-06 2.58E-06 5.26E-06 6.82E-05 0.OOE+00 6.12E-05 Te-129 4.48E-08 1.67E-08 1.09E-08 3.20E-08 1.88E-07 O.OOE+00 2.45E-07 Te-131m 2.44E-06 1.17E-06 9.76E-07 1.76E-06 1.22E-05 0.OOE+00 9.39E-05 Te-131 2.79E-08 1.15E-08 8.72E-09 2.15E-08 1.22E-07 O.OOE+00 2.29E-09 Te-132 3.49E-06 2.21E-06 2.08E-06 2.33E-06 2.12E-05 0.OOE+00 7.OOE-05 1-130 1.03E-06 2.98E-06 1.19E-06 2.43E-04 4.59E-06 0.OOE+00 2.29E-06 1-131 5.85E-06 8.19E-06 4.40E-06 2.39E-03 1.41E-05 0.OOE+00 1.62E-06 1-132 2.79E-07 7.30E-07 2.62E-07 2.46E-05 1.15E-06 O.OOE+00 3.18E-07 1-133 2.01E-06 3.41E-06 1.04E-06 4.76E-04 5.98E-06 0.OOE+00 2.58E-06 1-134 1.46E-07 3.87E-07 1.39E-07 6.45E-06 6.1OE-07 0.OOE+00 5.1OE-09 1-135 6.1OE-07 1.57E-06 5.82E-07 1.01E-04 2.48E-06 0.O0E+00 1.74E-06 Cs-134 8.37E-05 1.97E-04 9.14E-05 0.OOE+00 6.26E-05 2.39E-05 2.45E-06 Cs-136 8.59E-06 3.38E-05 2.27E-05 O.OOE+00 1.84E-05 2.90E-06 2.72E-06 Cs-137 1.12E-04 1.49E-04 5.19E-05 O.OOE+00 5.07E-05 1.97E-05 2.12E-06 Cs-138 7.76E-08 1.49E-07 7.45E-08 O.OOE+00 1.1OE-07 1.28E-08 6.76E-11 Ba-139 1.39E-07 9.78E-11 4.05E-09 O.OOE+00 9.22E-11 6.74E-11 1.24E-06 Ba-140 2.84E-05 3.48E-08 1.83E-06 O.OOE+00 1.18E-08 2.34E-08 4.38E-05 Ba-141 6.71E-08 5.01E-11 2.24E-09 0.OOE+00 4.65E-11 3.43E-11 1.43E-13 Ba-142 2.99E-08 2.99E-11 1.84E-09 0.OOE+00 2.53E-11 1.99E-11 9.18E-20 La-140 3.48E-09 1.71E-09 4.55E-10 0.OOE+00 O.OOE+00 0.OOE+00 9.82E-05 La-142 1.79E-10 7.95E-11 1.98E-11 0.OOE+00 O.OOE+00 0.OOE+00 2.42E-06 Ce-141 1.33E-08 8.88E-09 1.02E-09 0.OOE+00 4.18E-09 O.OOE+00 2.54E-05 Ce-143 2.35E-09 1.71E-06 1.91E-10 0.OOE+00 7.67E-10 O.OOE+00 5.14E-05 Ce-144 6.96E-07 2.88E-07 3.74E-08 O.OOE+00 1.72E-07 O.OOE+00 1.75E-04 Pr-143 1.31E-08 5.23E-09 6.52E-10 0.OOE+00 3.04E-09 0.OOE+00 4.31E-05 Pr-144 4.30E-11 1.76E-11 2.18E-12 0.OOE+00 1.01E-11 O.OOE+00 4.74E-14 Nd-147 9.38E-09 1.02E-08 6.11E-10 0.OOE+00 5.99E-09 0.OOE+00 3.68E-05 W-187 1.46E-07 1.19E-07 4.17E-08 0.OOE+00 O.OOE+00 0.OOE+00 3.22E-05 Np-239 1.76E-09 1.66E-10 9.22E-11 0.OOE+00 5.21E-10 O.OOE+00 2.67E-05 NOTE: The tritium dose factor for bone is assumed to be equal to the total body dose factor.

REFERENCES:

Regulatory Guide 1.109, Table E-12.

Dose Factors for Co-57, Zn-69m, Br-82, Nb-97, Sn-125, Sb-124 and Sb-125 are from NUREG-0172 Age Specific Radiation Dose Commitment Factors for a One Year Chronic Intake, November, 1977, Table 4.

SQN ODCM Revision 47 Page 90 of 168 Table 6.4 INGESTION DOSE FACTORS (mrem/pCi ingested)

(Page 5 of 8)

CHILD bone liver t body thyroid kidney lung gi-lli H-3 2.03E-07 2.03E-07 2.03E-07 2.03E-07 2.03E-07 2.03E-07 2.03E-07 C-14 1.21 E-05 2.42E-06 2.42E-06 2.42E-06 2.42E-06 2.42E-06 2.42E-06 Na-24 5.80E-06 5.80E-06 5.80E-06 5.80E-06 5.80E-06 5.80E-06 5.80E-06 P-32 8.25E-04 3.86E-05 3.18E-05 O.OOE+00 0.OOE+00 0.OOE+00 2.28E-05 Cr-51 O.OOE+00 0.OOE+00 8.90E-09 4.94E-09 1.35E-09 9.02E-09 4.72E-07 Mn-54 O.OOE+00 1.07E-05 2.85E-06 0.OOE+00 3.OOE-06 O.OOE+00 8.98E-06 Mn-56 O.OOE+00 3.34E-07 7.54E-08 0.OOE+00 4.04E-07 O.OOE+00 4.84E-05 Fe-55 1.15E-05 6.10E-06 1.89E-06 0.OOE+00 O.OOE+00 3.45E-06 1.13E-06 Fe-59 1.65E-05 2.67E-05 1.33E-05 0.OOE+00 0.00E+00 7.74E-06 2.78E-05 Co-57 0.OOE+00 4.93E-07 9.98E-07 0.OOE+00 O.OOE+00 O.OOE+00 4.04E-06 Co-58 0.OOE+00 1.80E-06 5.51 E-06 0.OOE+00 0.OOE+00 O.OOE+00 1.05E-05 Co-60 0.OOE+00 5.29E-06 1.56E-05 O.OOE+00 0.OOE+00 O.OOE+00 2.93E-05 Ni-63 5.38E-04 2.88E-05 1.83E-05 O.OOE+00 0.OOE+00 O.OOE+00 1.94E-06 Ni-65 2.22E-06 2.09E-07 1.22E-07 O.OOE+00 0.OOE+00 0.OOE+00 2.56E-05 Cu-64 0.OOE+00 2.45E-07 1.48E-07 O.OOE+00 5.92E-07 0.OOE+00 1.15E-05 Zn-65 1.37E-05 3.65E-05 2.27E-05 O.OOE+00 2.30E-05 0.OOE+00 6.41 E-06 Zn-69 4.38E-08 6.33E-08 5.85E-09 O.OOE+00 3.84E-08 0.OOE+00 3.99E-06 Zn-69m 7.10E-07 1.21E-06 1.43E-07 0.OOE+00 7.03E-07 0.OOE+00 3.94E-05 Br-82 O.OOE+00 O.OOE+00 7.55E-06 0.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 Br-83 O.OOE+00 O.OOE+00 1.71 E-07 0.OOE+00 O.OOE+00 O.OOE+00 0.00E+00 Br-84 O.OOE+00 O.OOE+00 1.98E-07 O.OOE+00 O.OOE+00 O.OOE+00 0.OOE+00 Br-85 O.OOE+00 O.OOE+00 9.12E-09 O.OOE+00 0.OOE+00 O.OOE+00 O.OOE+00 Rb-86 0.OOE+00 6.70E-05 4.12E-05 O.OOE+00 O.OOE+00 0.OOE+00 4.31E-06 Rb-88 0.OOE+00 1.90E-07 1.32E-07 O.OOE+00 O.OOE+00 0.OOE+00 9.32E-09 Rb-89 0.OOE+00 1.17E-07 1.04E-07 O.OOE+00 0.OOE+00 0.OOE+00 1.02E-09 Sr-89 1.32E-03 0.OOE+00 3.77E-05 O.OOE+00 0.OOE+00 0.OOE+00 5.11 E-05 Sr-90 1.70E-02 0.0OE+00 4.31 E-03 O.OOE+00 0.0OE+00 0.OOE+00 2.29E-04 Sr-91 2.40E-05 0.OOE+00 9.06E-07 O.OOE+00 O.OOE+00 0.OOE+00 5.30E-05 Sr-92 9.03E-06 0.OOE+00 3.62E-07 O.OOE+00 0.OOE+00 0.OOE+00 1.71 E-04 Y-90 4.11E-08 O.OOE+00 1.10E-09 0.OOE+00 O.OOE+00 0.OOE+00 1.17E-04 Y-91 m 3.82E-10 O.OOE+00 1.39E-11 0.OOE+00 O.OOE+00 O.OOE+00 7.48E-07 Y-91 6.02E-07 O.OOE+00 1.61 E-08 0.OOE+00 0.OOE+00 O.OOE+00 8.02E-05 Y-92 3.60E-09 O.OOE+00 1.03E-10 0.OOE+00 O.OOE+00 0.OOE+00 1.04E-04 Y-93 1.14E-08 O.OOE+00 3.13E-10 0.OOE+00 O.OOE+00 O.OOE+00 1.70E-04 Zr-95 1.16E-07 2.55E-08 2.27E-08 O.OOE+00 3.65E-08 O.OOE+00 2.66E-05 Zr-97 6.99E-09 1.01 E-09 5.96E-10 O.OOE+00 1.45E-09 0.OOE+00 1.53E-04 Nb-95 2.25E-08 8.76E-09 6.26E-09 O.OOE+00 8.23E-09 0.O0E+00 1.62E-05 Nb-97 2.17E-10 3.92E-11 1.83E-11 O.OOE+00 4.35E-11 0.OOE+00 1.21E-05 Mo-99 0.OOE+00 1.33E-05 3.29E-06 O.OOE+00 2.84E-05 O.OOE+00 1.10E-05 Tc-99m 9.23E-10 1.81E-09 3.OOE-08 O.OOE+00 2.63E-08 9.19E-10 1.03E-06 Tc-101 1.07E-09 1.12E-09 1.42E-08 O.OOE+00 1.91E-08 5.92E-10 3.56E-09 Ru-103 7.31E-07 O.OOE+00 2.81E-07 0.OOE+00 1.84E-06 0.OOE+00 1.89E-05 Ru-1 05 6.45E-08 O.OOE+00 2.34E-08 0.OOE+00 5.67E-07 0.OOE+00 4.21 E-05 Ru-106 1.17E-05 O.OOE+00 1.46E-06 0.OOE+00 1.58E-05 0.OOE+00 1.82E-04

SQN ODCM Revision 47 Page 91 of 168 Table 6.4 INGESTION DOSE FACTORS (mrem/pCi ingested)

(Page 6 of 8)

CHILD bone liver t body thyroid kidney lung gi-lli Ag-11im 5.39E-07 3.64E-07 2.91 E-07 O.OOE+00 6.78E-07 O.OOE+00 4.33E-05 Sb-1i24 1.11 E-05 1.44E-07 3.89E-06 2.45E-08 O.OOE+00 6.16E-06 6.94E-05 Sb-125 7.16E-06 5.52E-08 1.50E-06 6.63E-09 O.OOE+00 3.99E-06 1.71 E-05 Sn-125 3.55E-05 5.35E-07 1.59E-06 5.55E-07 O.OOE+00 O.OOE+00 1.10E-05 Te-125m 1.14E-05 3.09E-06 1.52E-06 3.20E-06 O.OOE+00 O.OOE+00 1.1 OE-05 Te-127m 2.89E-05 7.78E-06 3.43E-06 6.91 E-06 8.24E-05 O.OOE+00 2.34E-05 Te-127 4.71 E-07 1.27E-07 1.01 E-07 3.26E-07 1.34E-06 O.OOE+OO 1.84E-05 Te-129m 4.87E-05 1.36E-05 7.56E-06 1.57E-05 1.43E-04 O.OOE+00 5.94E-05 Te-129 1.34E-07 3.74E-08 3.18E-08 9.56E-08 3.92E-07 O.OOE+O0 8.34E-06 Te-131m 7.20E-06 2.49E-06 2.65E-06 5.12E-06 2.41 E-05 0.OOE+OO 1.01E-04 Te-131 8.30E-08 2.53E-08 2.47E-08 6.35E-08 2.51 E-07 0.OOE+OO 4.36E-07 Te-132 1.01 E-05 4.47E-06 5.40E-06 6.51 E-06 4.15E-05 O.OOE+00 4.50E-05 1-130 2.92E-06 5.90E-06 3.04E-06 6.50E-04 8.82E-06 O.OOE+OO 2.76E-06 1-131 1.72E-05 1.73E-05 9.83E-06 5.72E-03 2.84E-05 O.OOE+OO 1.54E-06 1-132 8.00E-07 1.47E-06 6.76E-07 6.82E-05 2.25E-06 O.O0E+OO 1.73E-06 1-133 5.92E-06 7.32E-06 2.77E-06 1.36E-03 1.22E-05 O.OOE+00 2.95E-06 1-134 4.19E-07 7.78E-07 3.58E-07 1.79E-05 1.19E-06 O.OOE+00 5.16E-07 1-135 1.75E-06 3.15E-06 1.49E-06 2.79E-04 4.83E-06 O.OOE+00 2.40E-06 Cs-1 34 2.34E-04 3.84E-04 8.1OE-05 O.OOE+OO 1.19E-04 4.27E-05 2.07E-06 Cs-1 36 2.35E-05 6.46E-05 4.18E-05 O.OOE+00 3.44E-05 5.13E-06 2.27E-06 Cs-1 37 3.27E-04 3.13E-04 4.62E-05 O.OOE+00 1.02E-04 3.67E-05 1.96E-06 Cs-138 2.28E-07 3.17E-07 2.01 E-07 O.OOE+0O 2.23E-07 2.40E-08 1.46E-07 Ba-139 4.14E-07 2.21 E-1 0 1.20E-08 O.OOE+00 1.93E-10 1.30E-10 2.39E-05 Ba-140 8.31 E-05 7.28E-08 4.85E-06 O.OOE+OO 2.37E-08 4.34E-08 4.21 E-05 Ba-141 2.OOE-07 1.12E-10 6.51 E-09 O.OOE+OO 9.69E-1 1 6.58E-10 1.14E-07 Ba-142 8.74E-08 6.29E-1 1 4.88E-09 O.OOE+00 5.09E- 1I 3.70E-1 1 1.14E-09 La-140 1.01E-08 3.53E-09 1.19E-09 O.OOE+00 O.OOE+00 O.OOE+00 9.84E-05 La-142 5.24E-1 0 1.67E-10 5.23E- 1I 0.OOE+OO O.OOE+00 O.O0E+OO 3.31 E-05 Ce-141 3.97E-08 1.98E-08 2.94E-09 0.OOE+OO 8.68E-09 O.OOE+00 2.47E-05 Ce-143 6.99E-09 3.79E-06 5.49E-10 O.OOE+OO 1.59E-09 O.OOE+00 5.55E-05 Ce-144 2.08E-06 6.52E-07 1.11E-07 O.OOE+OO 3.61 E-07 O.OOE+00 1.70E-04 Pr-143 3.93E-08 1.18E-08 1.95E-09 O.OOE+00 6.39E-09 O.OOE+00 4.24E-05 Pr-144 1.29E-10 3.99E-1 1 6.49E-1 2 O.OOE+00 2.11E-11 O.OOE+00 8.59E-08 Nd-147 2.79E-08 2.26E-08 1.75E-09 O.OOE+00 1.24E-08 O.OOE+00 3.58E-05 W-187 4.29E-07 2.54E-07 1.14E-07 O.OOE+00 O.OOE+00 0.OOE+OO 3.57E-05 Np-239 5.25E-09 3.77E-1 0 2.65E-1 0 0.OOE+OO 1.09E-09 0.OOE+OO 2.79E-05 NOTE: The tritium dose factor for bone is assumed to be equal to the total body dose factor.

REFERENCES:

Regulatory Guide 1.109, Table E-13.

Dose Factors for Co-57, Zn-69m, Br-82, Nb-97, Sn-125, Sb-124 and Sb-125 are from NUREG-0172 Age Specific Radiation Dose Commitment Factors for a One Year Chronic Intake.,

November, 1977, Table 4.

SQN ODCM Revision 47 Page 92 of 168 Table 6.4 INGESTION DOSE FACTORS (mrem/pCi ingested)

(Page 7 of 8)

INFANT bone liver t body thyroid kidney lung gi-lli H-3 3.08E-07 3.08E-07 3.08E-07 3.08E-07 3.08E-07 3.08E-07 3.08E-07 C-14 2.37E-05 5.06E-06 5.06E-06 5.06E-06 5.06E-06 5.06E-06 5.06E-06 Na-24 1.01E-05 1.01E-05 1.01E-05 1.01E-05 1.01E-05 1.01E-05 1.01E-05 P-32 1.70E-03 1.00E-04 6.59E-05 0.OOE+00 0.00E+00 0.00E+00 2.30E-05 Cr-51 0.00E+00 0.00E+00 1.41E-08 9.20E-09 2.01E-09 1.79E-08 4.11E-07 Mn-54 0.00E+00 1.99E-05 4.51 E-06 0.OOE+00 4.41 E-06 0.00E+00 7.31 E-06 Mn-56 0.00E+00 8.18E-07 1.41E-07 0.00E+00 7.03E-07 0.00E+00 7.43E-05 Fe-55 1.39E-05 8.98E-06 2.40E-06 0.00E+00 0.OOE+00 4.39E-06 1.14E-06 Fe-59 3.08E-05 5.38E-05 2.12E-05 0.00E+00 0.00E+00 1.59E-05 2.57E-05 Co-57 0.00E+00 1.15E-06 1.87E-06 0.00E+00 0.00E+00 0.00E+00 3.92E-06 Co-58 0.OOE+00 3.60E-06 8.98E-06 0.OOE+00 0.00E+00 0.00E+00 8.97E-06 Co-60 0.00E+00 1.08E-05 2.55E-05 0.OOE+00 0.00E+00 0.OOE+00 2.57E-05 Ni-63 6.34E-04 3.92E-05 2.20E-05 0.00E+00 0.00E+00 0.00E+00 1.95E-06 Ni-65 4.70E-06 5.32E-07 2.42E-07 0.00E+00 0.00E+00 O.OOE+00 4.05E-05 Cu-64 0.00E+00 6.09E-07 2.82E-07 0.OOE+00 1.03E-06 0.OOE+00 1.25E-05 Zn-65 1.84E-05 6.31E-05 2.91E-05 0.OOE+00 3.06E-05 0.00E+00 5.33E-05 Zn-69 9.33E-08 1.68E-07 1.25E-08 0.00E+00 6.98E-08 0.OOE+00 1.37E-05 Zn-69m 1.50E-06 3.06E-06 2.79E-07 0.00E+00 1.24E-06 0.00E+00 4.24E-05 Br-82 O.OOE+00 0.00E+00 1.27E-05 0.00E+00 0.OOE+00 0.00E+00 0.00E+00 Br-83 0.00E+00 0.00E+00 3.63E-07 0.OOE+00 0.00E+00 0.00E+00 0.00E+00 Br-84 0.00E+00 0.00E+00 3.82E-07 0.OOE+00 O.OOE+00 0.OOE+00 0.00E+00 Br-85 0.00E+00 0.00E+00 1.94E-08 0.00E+00 0.00E+00 0.00E+00 0.00E+00 Rb-86 0.00E+00 1.70E-04 8.40E-05 0.00E+00 0.00E+00 0.00E+00 4.35E-06 Rb-88 0.00E+00 4.98E-07 2.73E-07 0.00E+00 0.00E+00 0.00E+00 4.85E-07 Rb-89 0.00E+00 2.86E-07 1.97E-07 0.00E+00 0.00E+00 0.00E+00 9.74E-08 Sr-89 2.51E-03 0.OOE+00 7.20E-05 0.00E+00 0.00E+00 0.00E+00 5.16E-05 Sr-90 1.85E-02 0.00E+00 4.71 E-03 0.00E+00 0.OOE+00 0.00E+00 2.31 E-04 Sr-91 5.00E-05 0.00E+00 1.81E-06 0.OOE+00 0.00E+00 0.00E+00 5.92E-05 Sr-92 1.92E-05 0.00E+00 7.13E-07 0.00E+00 0.00E+00 0.00E+00 2.07E-04 Y-90 8.69E-08 0.00E+00 2.33E-09 0.00E+00 0.00E+00 0.00E+00 1.20E-04 Y-91m 8.10E-10 0.00E+00 2.76E-11 0.00E+00 0.00E+00 0.00E+00 2.70E-06 Y-91 1.13E-06 0.00E+00 3.01E-08 0.00E+00 0.00E+00 0.00E+00 8.10E-05 Y-92 7.65E-09 0.00E+00 2.15E-10 0.00E+00 0.00E+00 0.00E+00 1.46E-04 Y-93 2.43E-08 0.00E+00 6.62E-10 0.00E+00 0.00E+00 0.00E+00 1.92E-04 Zr-95 2.06E-07 5.02E-08 3.56E-08 0.00E+00 5.41 E-08 0.00E+00 2.50E-05 Zr-97 1.48E-08 2.54E-09 1.16E-09 0.00E+00 2.56E-09 0.00E+00 1.62E-04 Nb-95 4.20E-08 1.73E-08 1.00E-08 0.00E+00 1.24E-08 0.00E+00 1.46E-05 Nb-97 4.59E-10 9.79E-11 3.53E-11 0.00E+00 7.65E-11 0.00E+00 3.09E-05 Mo-99 0.00E+00 3.40E-05 6.63E-06 0.00E+00 5.08E-05 0.00E+00 1.12E-05 Tc-99m 1.92E-09 3.96E-09 5.10E-08 0.00E+00 4.26E-08 2.07E-09 1.15E-06 Tc-101 2.27E-09 2.86E-09 2.83E-08 0.00E+00 3.40E-08 1.56E-09 4.86E-07 Ru-103 1.48E-06 0.00E+00 4.95E-07 0.00E+00 3.08E-06 0.00E+00 1.80E-05 Ru-105 1.36E-07 0.00E+00 4.58E-08 0.00E+00 1.OOE-06 0.00E+00 5.41 E-05 Ru-106 2.41E-05 0.00E+00 3.01E-06 0.00E+00 2.85E-05 0.00E+00 1.83E-04

SQN ODCM Revision 47 Page 93 of 168 Table 6.4 INGESTION DOSE FACTORS (mrem/pCi ingested)

(Page 8 of 8)

INFANT bone liver t body thyroid kidney lung gi-Ili Ag-11Om 9.96E-07 7.27E-07 4.81 E-07 O.OOE+O0 1.04E-06 O.OOE+00 3.77E-05 Sb-124 2.14E-05 3.15E-07 6.63E-06 5.68E-08 O.OOE+00 1.34E-05 6.60E-05 Sb-125 1.23E-05 1.19E-07 2.53E-06 1.54E-08 O.OOE+00 7.72E-06 1.64E-05 Sn-125 7.41 E-05 1.38E-06 3.29E-06 1.36E-06 O.OOE+OO O.OOE+00 1.11 E-04 Te-125m 2.33E-05 7.79E-06 3.15E-06 7.84E-06 O.OOE+00 O.OOE+OO 1.11E-05 Te-127m 5.85E-05 1.94E-05 7.08E-06 1.69E-05 1.44E-04 O.OOE+00 2.36E-05 Te-127 1.OOE-06 3.35E-07 2.15E-07 8.14E-07 2.44E-06 O.OOE+00 2.1 OE-05 Te-129m 1.OOE-04 3.43E-05 1.54E-05 3.84E-05 2.50E-04 O.OOE+OO 5.97E-05 Te-129 2.84E-07 9.79E-08 6.63E-08 2.38E-07 7.07E-07 O.OOE+OO 2.27E-05 Te-131m 1.52E-05 6.12E-06 5.05E-06 1.24E-05 4.21 E-05 O.OOE+O0 1.03E-04 Te-131 1.76E-07 6.50E-08 4.94E-08 1.57E-07 4.50E-07 O.OOE+00 7.11E-06 Te-132 2.08E-05 1.03E-05 9.61 E-06 1.52E-05 6.44E-05 O.OOE+O0 3.81 E-05 1-130 6.OOE-06 1.32E-05 5.30E-06 1.48E-03 1.45E-05 O.OOE+OO 2.83E-06 1-131 3.59E-05 4.23E-05 1.86E-05 1.39E-02 4.94E-05 O.OOE+00 1.51 E-06 1-132 1.66E-06 3.37E-06 1.20E-06 1.58E-04 3.76E-06 O.OOE+00 2.73E-06 1-133 1.25E-05 1.82E-05 5.33E-06 3.31 E-03 2.14E-05 O.OOE+00 3.08E-06 1-134 8.69E-07 1.78E-06 6.33E-07 4.15E-05 1.99E-06 O.OOE+O0 1.84E-06 1-135 3.64E-06 7.24E-06 2.64E-06 6.49E-04 8.07E-06 O.OOE+0O 2.62E-06 Cs-1 34 3.77E-04 7.03E-04 7.1OE-05 O.OOE+00 1.81 E-04 7.42E-05 1.91 E-06 Cs-1 36 4.59E-05 1.35E-04 5.04E-05 O.OOE+00 5.38E-05 1.1OE-05 2.05E-06 Cs-1 37 5.22E-04 6.11E-04 4.33E-05 O.OOE+0O 1.64E-04 6.64E-05 1.91 E-06 Cs-1 38 4.81 E-07 7.82E-07 3.79E-07 O.OOE+00 3.90E-07 6.09E-08 1.25E-06 Ba-139 8.81 E-07 5.84E-1 0 2.55E-08 O.OOE+00 3.51 E-10 3.54E-10 5.58E-05 Ba-140 1.71 E-04 1.71 E-07 8.81 E-06 O.OOE+OO 4.06E-08 1.05E-07 4.20E-05 Ba-141 4.25E-07 2.91 E-10 1.34E-08 O.OOE+00 1.75E-10 1.77E-10 5.19E-06 Ba-142 1.84E-07 1.53E-10 9.06E-09 O.OOE+O0 8.81 E-11 9.26E-1 1 7.59E-07 La-140 2.11E-08 8.32E-09 2.14E-09 O.OOE+00 O.OOE+00 O.OOE+00 9.77E-05 La-142 1.1OE-09 4.04E-10 9.67E-i 1 O.OOE+00 O.OOE+00 O.OOE+00 6.86E-05 Ce-141 7.87E-08 4.80E-08 5.65E-09 O.OOE+00 1.48E-08 O.OOE+00 2.48E-05 Ce-143 1.48E-08 9.82E-06 1.12E-09 O.OOE+00 2.86E-09 O.OOE+00 5.73E-05 Ce-144 2.98E-06 1.22E-06 1.67E-07 O.OOE+00 4.93E-07 O.OOE+00 1.71 E-04 Pr-143 8.13E-08 3.04E-08 4.03E-09 O.OOE+OO 1.13E-08 O.OOE+00 4.29E-05 Pr-144 2.74E-10 1.06E-10 1.38E-11 O.OOE+00 3.84E-1 1 O.OOE+00 4.93E-06 Nd-147 5.53E-08 5.68E-08 3.48E-09 O.OOE+OO 2.19E-08 O.OOE+00 3.60E-05 W-187 9.03E-07 6.28E-07 2.17E-07 O.OOE+0O O.OOE+00 O.OOE+O0 3.69E-05 Np-239 1.11E-08 9.93E-1 0 5.61E-10 O.OOE+00 1.98E-09 O.OOE+00 2.87E-05 NOTE: The tritium dose factor for bone is assumed to be equal to the total body dose factor.

REFERENCES:

Regulatory Guide 1.109, Table E-14.

Dose Factors for Co-57, Zn-69m, Br-82, Nb-97, Sn-125, Sb-124 and Sb-125 are from NUREG-0172 Aqe Specific Radiation Dose Commitment Factors for a One Year Chronic Intake ,

November, 1977, Table 4.

SQN ODCM Revision 47 Page 94 of 168 Table 6.5 BIOACCUMULATION FACTORS FOR FRESHWATER FISH (uiCi/kg per DlCiIL)

H-3 9.OE-01 Y-91 m 2.5E+01 1-134 4.OE+01 C-14 4.6E+03 Y-91 2.5E+01 1-135 4.OE+01 Na-24 1.OE+02 Y-92 2.5E+01 Cs-1 34 1.9E+03 P-32 1.OE+05 Y-93 2.5E+01 Cs-136 1.9E+03 Cr-51 2.OE+02 Zr-95 3.3E+OO Cs-137 1.9E+03 Mn-54 4.OE+02 Zr-97 3.3E+OO Cs-138 1.9E+03 Mn-56 4.OE+02 Nb-95 3.OE+04 Ba-1 39 4.OE+O0 Fe-55 1.OE+02 Nb-97 3.OE+04 Ba-140 4.OE+O0 Fe-59 1.OE+02 Mo-99 1.OE+01 Ba-141 4.OE+00 Co-57 5.OE+01 Tc-99m 1.5E+01 Ba-142 4.OE+OO Co-58 5.OE+01 Tc-1 01 1.5E+01 La-140 2.5E+01 Co-60 5.OE+01 Ru-1 03 1.OE+01 La-144 2.5E+01 Ni-63 1.OE+02 Ru-1 05 1.OE+01 Ce-141 1.OE+OO Ni-65 1.OE+02 Ru-1 06 1.OE+01 Ce-143 1.OE+0O Cu-64 5.OE+01 Ag-110m 2.31 E+OO Ce-144 1.OE+00 Zn-65 2.OE+03 Sb-124 1.OE+OO Pr-144 2.5E+01 Zn-69 2.OE+03 Sb-1 25 1.OE+00 Pr-143 2.5E+01 Zn-69m 2.OE+03 Sn-125 3.OE+03 Nd-147 2.5E+01 Br-82 4.2E+02 Te-1 25m 4.OE+02 W-187 1.2E+03 Br-83 4.2E+02 Te-127m 4.OE+02 Np-239 1.OE+01 Br-84 4.2E+02 Te-127 4.OE+02 Br-85 4.2E+02 Te-129m 4.OE+02 Rb-86 2.OE+03 Te-129 4.OE+02 Rb-88 2.OE+03 Te-1 31 m 4.OE+02 Rb-89 2.OE+03 Te-131 4.OE+02 Sr-89 5.6E+01 Te-1 32 4.OE+02 Sr-90 5.6E+01 1-130 4.OE+01 Sr-91 5.6E+01 1-131 4.OE+01 Sr-92 5.6E+01 1-132 4.OE+01 Y-90 2.5E+01 1-133 4.OE+01

REFERENCES:

Bioaccumulation factors for Ag-11Om, Sb-124, Sb-125 and Sn-125 are from ORNL-4992, "A Methodology for Calculating Radiation Doses from Radioactivity Released to the Environment,"

March 1976, Table 4.12A.

Bioaccumulation factors for Iodine, Cesium, and Strontium nuclides are from NUREG/CR-1004, Table 3.2.4.

All other nuclides' bioaccumulation factors are from Regulatory Guide 1.109, Table A-1.

SQN ODCM Revision 47 Page 95 of 168 Table 6.6 EXTERNAL DOSE FACTORS FOR STANDING ON CONTAMINATED GROUND (mrem/h per pCi/M 2)

(Page 1 of 2)

Nuclide Total Body Skin H-3 0.0 0.0 C-14 0.0 0.0 Na-24 2.50E-08 2.90E-08 P-32 0.0 0.0 Cr-51 2.20E-10 2.60E-10 Mn-54 5.80E-09 6.80E-09 Mn-56 1.1OE-08 1.30E-08 Fe-55 0.0 0.0 Fe-59 8.OOE-09 9.40E-09 Co-57 1.77E-09 2.21 E-09 Co-58 7.OOE-09 8.20E-09 Co-60 1.70E-08 2.OOE-08 Ni-63 0.0 0.0 Ni-65 3.70E-09 4.30E-09 Cu-64 1.50E-09 1.70E-09 Zn-65 4.OOE-09 4.60E-09 Zn-69 0.0 0.0 Zn-69m 5.50E-09 6.59E-09 Br-82 3.18E-08 3.90E-08 Br-83 6.40E-11 9.30E-11 Br-84 1.20E-08 1.40E-08 Br-85 0.0 0.0 Rb-86 6.30E-10 7.20E-10 Rb-88 3.50E-09 4.OOE-09 Rb-89 1.50E-08 1.80E-08 Sr-89 5.60E-13 6.50E-13 Sr-91 7.10E-09 8.30E-09 Sr-92 9.OOE-09 1.OOE-08 Y-90 2.20E-12 2.60E-12 Y-91 m 3.80E-09 4.40E-09 Y-91 2.40E-11 2.70E-11 Y-92 1.60E-09 1.90E-09 Y-93 5.70E-10 7.80E-10 Zr-95 5.OOE-09 5.80E-09 Zr-97 5.50E-09 6.40E-09 Nb-95 5.1OE-09 6.OOE-09 Nb-97 8.11E-09 1.OOE-08 Mo-99 1.90E-09 2.20E-09 Tc-99m 9.60E-10 1.1OE-09 Tc-101 2.70E-09 3.OOE-09 Ru-1 03 3.60E-09 4.20E-09 Ru-105 4.50E-09 5.1 OE-09 Ru-106 1.50E-09 1.80E-09

SQN ODCM Revision 47 Page 96 of 168 Table 6.6 EXTERNAL DOSE FACTORS FOR STANDING ON CONTAMINATED GROUND (mrem/h per pCi/m 2 )

(Page 2 of 2)

Nuclide Total Body Skin Ag-1i1m 1.80E-08 2.1 OE-08 Sb-124 2.17E-08 2.57E-08 Sb-125 5.48E-09 6.80E-09 Sn-125 3.58E-09 4.51 E-09 Te-125m 3.50E-11 4.80E-1i1 Te-127m 1.10E-12 1.30E-12 Te-127 1.OOE-11 1.10E-11 Te-129m 7.70E-1 0 9.OOE-10 Te-129 7.10E-10 8.40E-10 Te-131m 8.40E-09 9.90E-09 Te-131 2.20E-09 2.60E-06 Te-132 1.70E-09 2.OOE-09 1-130 1.40E-08 1.70E-08 1-131 2.80E-09 3.40E-09 1-132 1.70E-08 2.00E-08 1-133 3.70E-09 4.50E-09 1-134 1.60E-08 1 .90E-08 1-135 1.20E-08 1.40E-08 Cs-1 34 1.20E-08 1.40E-08 Cs-1 36 1.50E-08 1.70E-08 Cs-1 37 4.20E-09 4.90E-09 Cs-1 38 2.1OE-08 2.40E-08 Ba-139 2.40E-09 2.70E-09 Ba-140 2.1 OE-09 2.40E-09 Ba-141 4.30E-09 4.90E-09 Ba-142 7.90E-09 9.00E-09 La-140 1.50E-08 1.70E-08 La-142 1.50E-08 1.80E-08 Ce-141 5.50E-1 0 6.20E-1 0 Ce-143 2.20E-09 2.50E-09 Ce-144 3.20E-1 0 3.70E-1 0 Pr-143 0.0 0.0 Pr-1i44 2.00E-10 2.30E-1 0 Nd-147 1.OOE-09 1.20E-09 W-187 3.1 OE-09 3.60E-09 Np-239 9.50E-10 1.1OE-09

REFERENCES:

Regulatory Guide 1.109, Table E-6.

Dose Factors for Co-57, Zn-69m, Br-82, Nb-97, Sn-1 25, Sb-1 24 and Sb-125 are from Dose-Rate Conversion Factors for External Exposure to Photon and Electron Radiation from Radionuclides Occurring in Routine Releases from Nuclear Fuel Cycle Facilities. D. C. Kocher, Health Physics Volume 38, April 1980.

SQN ODCM Revision 47 Page 97 of 168 Figure 6.1 LIQUID EFFLUENT RELEASE POINTS Steam Turbine Generator Building Condensate Blowdown Sump Demineralizer Unit 1 System (TBS)

Unit 2 Composite Sampler O-RM-90-225 "A" Train O-RE-90-133,140 "B" Train Q-RE-90-134,141

SQN ODCM Revision 47 Page 98 of 168 Figure 6.2 LIQUID RADWASTE SYSTEM Laundry and Hot Shower Tanks A & B 20 gpm (600 gal)

Monitor Tank (22000 gal) 125 gpm 125 gpm X-R(routine 0-RM-90-1 22 TO COOLING TOWER BLOWDOWN

SQN ODCM Revision 47 Page 99 of 168 SECTION 7.0 GASEOUS EFFLUENTS

SQN ODCM Revision 47 Page 100 of 168 SECTION 7.0 GASEOUS EFFLUENTS RELEASE POINTS DESCRIPTION There are six major exhaust pathways at Sequoyah Nuclear Plant that are monitored for airborne effluents. These are: a Condenser Vacuum Exhaust for each unit, a Service Building Exhaust, an Auxiliary Building Exhaust and a Shield Building Exhaust for each unit. Figure 7.1 provides an outline of the airborne effluent release and discharge points with associated radiation monitor identifications. All gaseous effluents at Sequoyah are considered ground level for the purpose of evaluating offsite dose and setpoint determination.

Condenser Vacuum Exhaust The Condenser Vacuum Exhausts (CVEs) are located in the turbine building. The CVE exhaust at a maximum design flow rate of 45 cubic feet per minute. They are monitored for routine releases by radiation monitors 1,2-RM-90-99,119.

Service Building Vent Various low-level sources exhaust to the Service Building Vent. This exhausts at a total design flow of approximately 11,200 cfm. Only a portion of this total flow (9,000 cfm) originating from the Titration Room, the Chemistry Lab, and the RCA Access Control Area is monitored by radiation monitor 0-RM-90-132.

Auxiliary Building Exhaust (see Figure 7.2 for detail)

The annulus vacuum priming system exhausts through the containment vent to the Auxiliary Building. The Auxiliary Building Exhaust consists of the Auxiliary Building General Exhaust System and the Fuel Handling Exhaust and they cumulatively exhaust at a maximum design flow of 228,000 cfm. The exhaust is monitored by radiation monitor 0-RM-90-101.

Shield Building Vent (see Figure 7.2 for detail)

The Auxiliary Building Gas Treatment System (ABGTS) draws from the Auxiliary Building and exhausts through the Shield Building Vent. There are nine Waste Gas Decay Tanks (WGDTs) that empty into the waste gas header. Either ABGTS or the Emergency Gas Treatment System (EGTS) is run to release a WGDT. Each WGDT has a design capacity of 600 cubic feet at STP and a design release rate of 22.5 cfm. Both the Containment Purge and the Incore Instrument Room Purge from each unit tie into the waste gas header. The Containment Purge exhausts at a maximum of 28,000 cfm and is monitored by radiation monitors 1,2-RM-90-130,131. If the Incore Instrument Room Purge is operating exclusively, it exhausts at 800 cfm. Under emergency conditions, and sometimes during normal operation, the EGTS is used to draw a vacuum in the annulus and exhaust to the Shield Building Vent. Auxiliary Building Isolation starts both the ABGTS and EGTS. The common header exhausts to the Shield Building Exhaust. There is one exhaust for each unit. This exhausts at a maximum design flow of 28,000 cfm and is monitored by radiation monitors 1,2-RM-90-400.

SQN ODCM Revision 47 Page 101 of 168 7.1 INSTRUMENT SETPOINTS Airborne effluent monitor setpoints are determined to ensure that the dose rate at the UNRESTRICTED AREA BOUNDARY does not exceed the dose rate limits given in ODCM Control 1.2.2.1 and to identify unexpected releases.

7.1.1 Release Point Monitor Setpoints (1,2-RM-90-130,-131, O-RM-90-118) 7.1.1.1 Containment Purge Effluent Monitors (1,2-RM-90-130,-131)

These monitors are set at a cpm value equal to the Technical Specification Limit of 08.5x10-3 iCilcc as Xe-133 (Technical Specification 3.3.2.1(U1), 3.3.2(U2), Table 3.3-4, and 3.3.3.1, Table 3.3-6). The radiation monitor vacuum setpoint is set at 9 L 1 in. of vacuum, TIS Limit = 8.5E-03

[tCi/cc, monitor efficiency for Xe-133 = 9.08E + 05 CPM/jiCi/cc, Vacuum Correction = 0.75; therefore the maximum setpoint = (8.5E-03) (9.08E+05)(0.75) = 5800 CPM.

7.1.1.2 Waste Gas Decay Tank Effluent Monitor (0-RM-90-118)

The setpoint for the Waste Gas Decay Tank effluent monitor is routinely set at a Default Setpoint, SDEF. This setpoint uses the site release rate limit and considers the dilution effect of ABGTS during the release process.

SDEF for 0-RM-90-118 is 1,882 CPM based on the following:

SDEF =DRM 25525E-03

  • 3.28E+04
  • 2.94E+02
  • XJQ
  • 472
  • RR Where: DRUM is the site dose rate limit = 500mRem/y RR = 50 ft3/min Admin. release rate limit for Waste Gas Decay Tanks 3.28E+04 cpm/uCi/cc is the radiation monitors efficiency 5.525E-03 is the max. Dilution flow factor provided by ABGTS (9OOOcfm)

XIQ = 6.94E-06 S/M3 , Section 7.2.3.1 2.94E+02 = Dose Factor for Xe-1 33 mRem/y/uCi/m 3 , Table 7.3 472 = Conversion Factor, (28317 cc/ft3 .min/60 s)

A Maximum Setpoint, Smax can also be calculated for 0-RM-90-118 based on using the radiation monitor as the primary monitor for the release path.

Smax for 0-RM-90-118 is 31,879 CPM based on the following:

SMAX =A_ DuL 3.28E+04A 2.94E+02 - X/Q

  • 472
  • RR Where: A = the Dose Rate allocation factor for the shield bldg.,0.0955 DRLIM is the site dose rate limit = 5OOmRem/y 3.28E+04 cpm/uCi/cc is the radiation monitor's efficiency for Xe-133 2.94E+02 = Dose Factor for Xe-133 mRem/y/uCi/m 3 , Table 7.3 X/Q = 6.94E-06 S/M3, Section 7.2.3.1 RR = 50 ft3/min Admin. release rate limit for Waste Gas Decay Tanks 472 Conversion Factor, (28317 cc/ft3
  • min/60 s)

SQN ODCM Revision 47 Page 102 of 168 For each release from a waste gas decay tank, two setpoints are evaluated for the monitor: one based on the expected response of the monitor to the radioactivity in the effluent stream and a calculated expected monitor response setpoint. The expected monitor response is calculated as described below in Equation 7.1. The expected monitor response setpoint is calculated as described below in Equation 7.1a. A comparison is made to verify the expected monitor response and expected monitor response setpoint is less than or equal to the Default Setpoint. If the expected monitor response or expected monitor response setpoint is greater than Default Setpoint it may be temporarily increased but can not exceed the Maximum Setpoint. The calculated setpoints ensures that the release will be stopped if it exceeds any dose rate limits.

Expected Monitor Response, CPM RCPM = B + [effi C (7.1)

Where: RCPM = Expected Monitor Response,CPM B = monitor background, cpm.

effi= efficiency factor for the monitor for nuclide i, cpm per gCi/cc.

C. = measured concentration of nuclide i, [tCi/cc.

Expected Monitor Response. uCils RUcj/- = B + 472Ci

  • RR Where: RUCjjS = Expected Release Rate, uCi/s B =monitor background, cpm.

472 = Conversion Factor, cc/ft3*m/s Ci = measured concentration of nuclide i, uCi/cc RR = Release Rate, ft3 /min Expected Monitor Response Setpoint. CPM or uCi/s (7.1a)

The expected monitor response setpoint Ser is calculated for the monitor for each release.

Ser =X^R where R = expected monitor response, CPM or uCi/s X = administrative factor designed to account for expected variations in monitor response and background The range of values is: 1.0 E X L2.0

SQN ODCM Revision 47 Page 103 of 168 7.1.2 Discharge Point Monitor Setpoints (1,2-RE-90-400, 0-RM-90-101, 0-RM-90-132, 1,2-RM-90-99,119)

A normal default setpoint, SDEF is utilized for each discharge point monitor as described below.

When release permits are generated, the expected response and expected monitor response setpoint is calculated for the appropriate discharge monitor as described in Section 7.1.1.2. A comparison is made between the two setpoints. If the expected monitor response or expected monitor response setpoint is greater than the default setpoint then the release parameters must be reevaluated. Worse case conditions will require an evaluation of the allocation factors in section 7.1.1.2.

Calculated Default Setpoint The calculated default setpoint, SDef in cpm (0-101,0-132, & 1,2-99,119), corresponding to the dose rate limit is determined using the following equation:

SDEF= A.DLmEff* 0.71 (7.2)

DRR

  • 472
  • 2.94E+02
  • XJQ Where:

A = dose rate allocation factor for the release point, dimensionless. The dose rate allocation factors for release points are defined as follows based on design flowrates:

Auxiliary Building 0.7779 Shield Building (ea) 0.0955 Service Building 0.0307 Condenser Vacuum Exhaust (ea) 0.00015 0.71 = safety factor for the monitor, dimensionless. Safety factors for these monitors includes 0.75 for the radiation monitor vacuum correction factor and 0.95 for Xe-133 primary isotope mix.

DRuim = the dose rate limit, 500 mrem/year to the total body for noble gases.

DRR = the design release rate for the release pathway or design approved flow rate.

= DRTB for total body (as described in Section 7.2.3.1).

472 = Conversion Factor, (28317 cc/ft3* min/60 s).

X/Q = 6.94E-06 S/M3, Section 7.2.3.1.

Eff = Radiation Monitor Efficiency for Xe-133, 0-101,0-132, 1,2-99,119 @ 2.27E+07 CPM/uCi/cc.

2.94E+02 = Dose Factor for Xe-i 33 mRem/y/uCi/m 3 ,Table 7.3.

The calculated default setpoint, SDef in uCi/s (1,2-400), corresponding to the dose rate limit is determined using the following equation:

SDEF = ADRIMM 2.94E+02

  • XJQ 7.1.3 Condenser Vacuum Exhaust Vent (1,2-RM-90-99,119)

This discharge point effluent monitor is set to ensure compliance with ODCM Control 1.2.2.1 and to identify the presence of primary to secondary leakage of radioactivity. The default setpoint is determined by Equation 7.2 for Xe-133, and then taking a percentage of this value as the setpoint; or by defining the setpoint as a low value above the normal background. Once a primary to secondary leak is identified, the setpoint on this monitor may be adjusted upward to enable it to be used to identify any further increases in the leak rate but will not be allowed to be set greater than the calculated default value without further evaluation of the allocation factors.

SQN ODCM Revision 47 Page 104 of 168 7.2 GASEOUS EFFLUENTS - DOSE RATES 7.2.1 (Deleted) 7.2.2 RELEASE SAMPLING Prior to each release (excluding an Incore Instrument Room Purge), a grab sample is taken and analyzed to determine the concentration, ptCi/cc, of each noble gas nuclide. On at least a weekly basis, filters are analyzed to determine the amount of iodines and particulates released.

Composite samples are maintained (as required by Table 2.2-2) to determine the concentration of certain nuclides (Sr-89, Sr-90, and alpha emitters).

For those nuclides whose activities are determined from composite samples the concentrations for the previous composite period will be assumed as the concentration for the next period to perform the calculations in Sections 7.3, 7.4, and 7.5. The actual measured concentrations will be used for the dose calculations described in Section 7.6.

7.2.3 NOBLE GAS DOSE RATES Dose rates are calculated for total body and skin due to submersion within a cloud of noble gases using a semi-infinite cloud model.

7.2.3.1 Total Body Dose Rate The dose rate to the total body, DRTB in mrem/year, is calculated using the following equation:

DRTB = (S/Q) F z1Ci DFBj (7.3) where L/Q = relative concentration, s/iM3 . Relative air concentrations are calculated for the unrestricted area boundary in each of the sixteen sectors as described in Section 7.8.2 from quarterly meteorological data from 1986-1995 (40 quarters). For dose rate calculations, the average of the highest value from the sixteen unrestricted area boundary locations from each of the 40 quarters is used.

= 6.94E-06 s/m3 (from Table 7.1).

F = flowrate of effluent stream, cc/s.

C. = concentration of noble gas nuclide i in effluent stream, gCi/cc.

DFBj = total body dose factor due to gamma radiation for noble gas nuclide i, mrem/y per p.Ci/m 3 (Table 7.3).

SQN ODCM Revision 47 Page 105 of 168 7.2.3.2 Skin Dose Rate The dose rate to the skin, DRS in mrem/year, is calculated using the following equation:

DRS = (L/Q) F o CP(DFS1 + 1.11 DFj) (7.4) where E/Q = relative concentration, s/M3 . Relative air concentrations are calculated for the unrestricted area boundary in each of the sixteen sectors as described in Section 7.8.2 from quarterly meteorological data from 1986-1995 (40 quarters). For dose rate calculations, the average of the highest value from the sixteen unrestricted area boundary locations from each of the 40 quarters is used.

= 6.94E-06 s/m3 (from Table 7.1).

F = flowrate of effluent stream, cc/s.

C. = concentration of noble gas nuclide i in effluent stream, gCi/cc.

DFSj = skin dose factor due to beta radiation for noble gas nuclide i, mrem/y per jiCi/m3 (Table 7.3).

1.11 = the average ratio of tissue to air energy absorption coefficients, mrem/mrad.

DF[I = dose conversion factor for external gamma for noble gas nuclide i, mrad/y per [tCi/m 3 (Table 7.3).

SQN ODCM Revision 47 Page 106 of 168 7.2.4 1-131,1-133, TRITIUM AND ALL RADIONUCLIDES IN PARTICULATE FORM WITH HALF-LIVES OF GREATER THAN 8 DAYS - ORGAN DOSE RATE Organ dose rates due to 1-131,1-133, Tritium and all radionuclides in particulate form with half-lives of greater than 8 days, DRg in mrem/y, are calculated for all age groups (adult, teen, child, and infant) and all organs (bone, river, total body, thyroid, kidney, lung, and GI Tract) using the following equation:

DRorg= F [ CT(EYQ)[RIT+RcTpI + II Ci[(EYQ)Rij + (D/Q) [Rcpi + RG1 ]]] (7.5) where:

F = flowrate of effluent stream, cc/s.

CT = concentration of tritium in effluent stream, g.Ci/cc.

[L1Q = relative concentration, s/M3 . Relative air concentrations are calculated for the unrestricted area boundary in each of the sixteen sectors as described in Section 7.8.2 from quarterly meteorological data from 1986-1995 (40 quarters). For dose rate calculations, the average of the highest value from the sixteen unrestricted area boundary locations from each of the 40 quarters is used.

= 6.94E-06 s/m3 (from Table 7.1).

RIT = inhalation dose factor for tritium, mrem/y per ptCilmr3 . Dose factor is calculated as described in Section 7.7.13.

RCTP= Grass-cow-milk dose factor for tritium, mrem/y per 10Ci/m 3 . Dose factor is calculated as described in Section 7.7.7.

Ci = concentration of nuclide i in effluent stream, 0Ci/cc.

R1j = inhalation dose factor for each identified nuclide i, mrem/y per gCi/m 3 . Dose factors are calculated as described in Section 7.7.13.

D/Q = relative deposition, 1/m2 . Relative deposition is calculated for the unrestricted area boundary in each of the sixteen sectors as described in Section 7.8.3 from quarterly meteorological data from 1986-1995 (40 quarters). For dose rate calculations, the average of the highest value from the sixteen unrestricted area boundary locations from each of the 40 quarters is used.

= 1.30E-08 1/m2 (from Table 7.2).

Rcp; = Grass-cow-milk dose factor for each identified nuclide i, m2 -mrem/y per ptCi/s. Dose factors are calculated as described in Section 7.7.1.

RGj = ground plane dose factor for each identified nuclide i, m2 -mrem/y per 1iCi/s. Dose factors are calculated as described in Section 7.7.14.

The maximum organ dose rate is selected from among the dose rates calculated for all the organs and all age groups.

SQN ODCM Revision 47 Page 107 of 168 7.3 DOSE - NOBLE GASES Doses to be calculated are gamma and beta air doses due to exposure to an infinite cloud of noble gases. These doses will be calculated from the unrestricted area boundary locations with the highest OQs for each quarter from 1986-1995. Dispersion factors are calculated using the methodology described in Section 7.8.2.

No credit is taken for radioactive decay.

7.3.1 Gamma dose to air The gamma air dose, D.in mrad, is calculated for each release using the following equation:

Dn= 1.9E-06 (EIQ)EJ Qj DFj T (7.6) where:

1.9E-06= conversion factor, y/min.

OfQ = average of the highest values from the sixteen unrestricted area boundary locations from each quarter, 6.94x10-6 s/M3 (from Table 7.1).

Qj = release rate for nuclide i, [OCi/s.

DIFa = dose conversion factor for external gamma for nuclide i (Table 7.3), mrad/y per pLCi/m 3 .

T = duration of release, min.

The gamma-air dose calculated by this method will be used in the cumulative dose calculations discussed in Section 7.3.3.

7.3.2 Beta dose to air The beta air dose, DD in mrad, is calculated for each release using the following equation:

DE) = 1.9E-06 (E°Q) L1Qj DFEI T (7.7) where:

1.9E-06= conversion factor, y/min.

EIQ = average of the highest values from the sixteen unrestricted area boundary locations from each quarter, 6.94x10-6 s/m3 (from Table 7.1).

Qj = release rate for nuclide i, gCils.

DFCj = dose conversion factor for external beta for nuclide i, mrad/y per pLCi/mi3 (from Table 7.3).

T = duration of release, min.

The beta-air dose calculated by this method will be used in the cumulative dose calculations discussed in Section 7.3.3.

SQN ODCM Revision 47 Page 108 of 168 7.3.3 Cumulative Dose - Noble Gas Monthly, quarterly and annual sums of all doses are calculated for each release as described below to compare to the limits listed in ODCM Control 1.2.2.2.

For noble gases, cumulative doses are calculated for gamma and beta air doses. Doses due to each release are summed with the doses for all previous release in the quarter or year to obtain cumulative quarterly and annual doses.

7.3.4 Comparison to Limits The cumulative calendar quarter and calendar year doses are compared to their respective limits once per 31 days to determine compliance.

SQN ODCM Revision 47 Page 109 of 168 7.4 DOSE DUE TO 1-131.1-133, TRITIUM AND ALL RADIONUCLIDES IN PARTICULATE FORM WITH HALF-LIVES OF GREATER THAN 8 DAYS 7.4.1 Organ dose Calculation Organ doses due to 1-131, 1-133, tritium and all radionuclides in particulate form with half-lives of greater than 8 days are calculated for each release for the critical receptors. The critical receptors are defined as the unrestricted area boundary in the sectors with the highest quarterly tQ and D/Q for each quarter from 1986-1995. The EQ and D/Q are calculated using the methodology in Sections 7.8.2 and 7.8.3 using the historical 1986-1995 meteorological data (Table 7.2). Pathways considered to exist at this location are inhalation, ground plane exposure, grass-cow-milk ingestion, grass-cow-beef ingestion and fresh leafy and stored vegetable ingestion. All age groups are considered (adult, teen, child and infant). Dose factors for these age groups and pathways are calculated as described in Section 7.7. For the ground exposure pathway, which has no age or organ specific dose factors, the total body dose will be added to the internal organ doses for all age groups. No credit is taken for radioactive decay.

The general equation for the calculation of organ dose is:

Doug = 3.17E-08 T O Rp1 [ Wp Qj] (7.8) ip where:

3.17E-08 = conversion factor, yfs T = duration of release, s.

Rpi = dose factor for pathway P for each identified nuclide i, m2 -mrem/y per jtCi/s for ground plane, grass-cow-milk, grass-cow-meat, and vegetation pathways, and mrem/y per ItCi/m3 for inhalation and tritium ingestion pathways. Equations for calculating these dose factors are given in Section 7.7.

WP = dispersion factor for the location and pathway,

= OIQ for the inhalation and tritium ingestion pathways,

= 6.94E-06 s/m 3 .

= D/Q for the food and ground plane pathways,

= 1.30E-08 m- 2 Qj = release rate for radionuclide i, pCi/s From the four age groups considered, the maximum is determined by comparing all organ doses for all age groups. The age group with the highest single organ dose is selected as the critical age group. The organ doses for the critical age group will be used in the cumulative doses discussed in Section 7.4.2.

SQN ODCM Revision 47 Page 110 of 168 7.4.2 Cumulative Doses Quarterly and annual sums of all doses are calculated for each release as described below to compare to the limits listed in ODCM Control 1.2.2.3.

For maximum organ dose, cumulative quarterly and annual doses are maintained for each of the eight organs considered. The cumulative dose is obtained by summing the doses for each organ of the critical age group (as calculated in Section 7.4.1) as determined for each release with the organ doses for all previous releases in the quarter or year to obtain the cumulative quarterly and annual doses. Thus, the cumulative organ doses will be conservative values, consisting of doses belonging to various age groups depending on the mix of radionuclides. The highest of these cumulative organ doses is used for the comparison to the limits described in ODCM Control 1.2.2.3.

7.4.3 Comparison to Limits The cumulative calendar quarter and calendar year doses are compared to their respective limits once per 31 days to determine compliance.

SQN ODCM Revision 47 Page 111 of 168 7.5 DOSE PROJECTIONS In accordance with ODCM Surveillance Requirement 2.2.2.4, dose projections will be performed by averaging the two previous month's doses as determined in Section 7.3.3. To determine compliance with the limits, these averages are assigned as the dose projections for the upcoming month.

The projected doses are compared to the limits of ODCM Control 1.2.2.4. The limits are 0.2 mrad per unit for gamma radiation, 0.4 mrad per unit for beta radiation, or 0.3 mrem per unit to any organ.

D= a+b 2

where:

D = the 31-day dose projection, mrad a = the cumulative gamma, beta, or organ dose for the previous month, mrad b = the cumulative gamma, beta, or organ dose for the present month, mrad If the projected doses exceed any of these limits, the GASEOUS RADWASTE TREATMENT SYSTEM and the VENTILATION EXHAUST TREATMENT SYSTEM shall be used to reduce radioactive materials in gaseous effluents to areas at or beyond the UNRESTRICTED AREA BOUNDARY.

7.5.1 GASEOUS RADWASTE TREATMENT SYSTEM DESCRIPTION The GASEOUS RADWASTE TREATMENT SYSTEM (GRTS) described below shall be maintained and operated to keep releases ALARA.

A flow diagram for the GRTS is given in Figure 7.3. The system consists of two waste-gas compressor packages, nine gas decay tanks, and the associated piping, valves, and instrumentation. Gaseous wastes are received from the following: degassing of the reactor coolant and purging of the volume control tank prior to a cold shutdown, displacing of cover gases caused by liquid accumulation in the tanks connected to the vent header, and boron recycle process operation.

SQN ODCM Revision 47 Page 112 of 168 7.6 QUARTERLY DOSE CALCULATIONS A complete dose analysis utilizing the total estimated gaseous releases for each calendar quarter will be performed and reported as required in ODCM Administrative Control 5.2. Methodology for this analysis is that which is described in this section using the quarterly release values reported by the plant personnel. All real pathways and receptor locations identified by the most recent land use survey are considered. In addition, actual meteorological data representative of a ground level release for each corresponding calendar quarter will be used. For iodine releases, it is assumed that half the iodine released is in organic form. Organic iodine causes a dose only by inhalation. For cow-milk and beef ingestion doses, the fraction of the time the animals are on stored feed (identified in the survey) is used in the calculation.

The highest organ dose for a real receptor is determined by summing the dose contribution from all identified pathways for each receptor including ground contamination, inhalation, vegetable ingestion (for identified garden locations), cow and/or goat milk ingestion (if a cow or goat is identified for the location), beef ingestion (the beef ingestion dose for the location of highest beef dose for all receptors will be considered the beef dose for all receptors).

7.6.1 NOBLE GAS - GAMMA AIR DOSE Gamma air doses due to exposure to noble gases, D. in mrad, are calculated using the following equation:

DD= Em DFc (7.9) where:

qm = concentration of nuclide i at location m, juCifm 3 . Air concentrations are calculated as described by Equation 7.14.

DFa = dose conversion factor for external gamma for nuclide i, mrad/y per [tCi/m3 (Table 7.3).

7.6.2 NOBLE GAS - BETA AIR DOSE Beta air doses due to exposure to noble gases, Ddp mrad, are calculated using the following equation:

Dn= Lim DFLi (7.10) where:

m = concentration of nuclide i at location m, RCi/m 3 . Air concentrations are calculated as described by Equation 7.14.

DF 0 = dose conversion factor for external beta for nuclide i, mrad/y per ,uCi/m 3 (Table 7.3).

SQN ODCM Revision 47 Page 113 of 168 7.6.3 RADIOIODINE, PARTICULATE AND TRITIUM - MAXIMUM ORGAN DOSE Organ doses due to radioiodine, particulate and tritium releases, Dorg in mrem, are calculated using the following equation:

Dorg = 3.17E-08 {(EIQ) n RPTQT + L11 (D/Q) nLERp + (D/Q)Rg + (0(Q)R1 i] Q1} (7.11)

P I P where:

3.17E-08 = conversion factor, y/s.

LYQ = Relative concentration for location under consideration, s/m3 . Relative concentrations are calculated as described by Equation 7.15.

RPT = ingestion dose factor for pathway P for tritium, m2 -mrem/y per jtCi/s. Ingestion pathways available for consideration are the same as those listed above for RR 1.

Equations for calculating ingestion dose factors for tritium are given in Sections 7.7.7 through 7.7.12.

QT = adjusted release rate for tritium for location under consideration, pCi/s. Calculated in the same manner as Qi above.

Rp; = ingestion dose factor for pathway P for each identified nuclide i (except tritium),

m2 -mrem/y per jlCi/s. Ingestion pathways available for consideration include:

pasture grass-cow-milk ingestion stored feed-cow-milk ingestion pasture grass-goat-milk ingestion stored feed-goat-milk ingestion pasture grass-beef ingestion stored feed-beef ingestion fresh leafy vegetable ingestion stored vegetable ingestion Equations for calculating these ingestion dose factors are given in Sections 7.7.1 through 7.7.6.

D/Q = Relative deposition for location under consideration, m-2 . Relative deposition is calculated as described in Equation 7.16.

RGI = Dose factor for standing on contaminated ground, m2 -mrem/y per gCi/s. The equation for calculating the ground plane dose factor is given in Section 7.7.14.

Rli = Inhalation dose factor, mrem/y per [iCi/m 3 . The equation for calculating the inhalation dose factor is given in Section 7.7.13.

Qi = adjusted release rate for nuclide i for location under consideration, jiCils. The initial release rate is adjusted to account for decay between the release point and the location, depending on the frequency of wind speeds applicable to that sector. Hence, the adjusted release rate is equal to the actual release rate decayed for an average travel time during the period.

9 Qio [ fi exp(-D, x/u;) (7.12) j=1 where Qio = initial average release rate for nuclide i over the period, p.Ci/s.

fi = joint relative frequency of occurrence of winds in windspeed class j blowing toward this exposure point, expressed as a fraction.

= radiological decay constant for nuclide i, s-1.

x = downwind distance, meters.

u; = midpoint value of wind speed class interval j, m/s.

SQN ODCM Revision 47 Page 114 of 168 7.6.4 POPULATION DOSES For determining population doses to the 50-mile population around the plant, each compass sector is broken down into elements. These elements are defined in Table 7.4. For each of these sector elements, an average dose is calculated, and then multiplied by the population in that sector element. Dispersion factors are calculated for the midpoint of each sector element (see Table 7.4).

For population doses resulting from ingestion, it is conservatively assumed that all food eaten by the average individual is grown locally.

The general equation used for calculating the population dose in a given sector element is:

Dosep ~

=l RATIOp

  • POPN
  • AGE
  • 0.001
  • DOSEp (7.13) p where RATIOp = ratio of average to maximum dose for pathway P. (Average ingestion rates are obtained from Regulatory Guide 1.109, Table E-4.)

= 0.5 for submersion and ground exposure pathways, a shielding/occupancy factor.

= 1.0 for the inhalation pathway.

= 0.515, 0.515, 0.5, and 0.355 for milk, for infant, child, teen and adult, respectively. (It is assumed that the ratio of average to maximum infant milk ingestion rates is the same as that for child.)

= 1.0, 0.90, 0.91, 0.86 for beef ingestion, for infant, child, teen and adult, respectively.

= 1.0, 0.38, 0.38, 0.37 for vegetable ingestion, for infant, child, teen and adult, respectively. (It is assumed that the average individual eats no fresh leafy vegetables, only stored vegetables.)

POPN = the population of the sector element, persons (Table 7.5).

AGE = fraction of the population belonging to each age group.

= 0.015, 0.168, 0.153, 0.665 for infant, child, teen and adult, respectively (fractions taken from NUREG/CR-1004, Table 3.39).

0.001 = conversion from mrem to rem.

DOSEp = the dose for pathway P to the maximum individual at the location under consideration, mrem. For ingestion pathways, this dose is multiplied by an average decay correction to account for decay as the food is moved through the food distribution cycle. This average decay correction, ADC, is defined as follows:

For milk and vegetables, ADC = exp(-l!jt) where -1 Pi = decay constant for nuclide i, s t = distribution time for food product under consideration (values from Regulatory Guide 1.109, Table D-1).

= 1.21 E+06 s (14 d) for vegetables.

= 3.46E+05 s (4 d) for milk.

SQN ODCM Revision 47 Page 115 of 168 7.6.4 POPULATION DOSES (continued) exp(-DJt) Litcb For meat, ADC =

1 - exP(-Oitcb) where a, = decay constant for nuclide i, s.

t = additional distribution time for meat, over and above the time for slaughter to consumption described in Section 7.7.3, 7 d.

tcb = time to consume a whole beef, as described in Section 7.7.3.

For beef ingestion, the additional factors in the calculation of ADC negate the integration of the dose term over the period during which a whole beef is consumed, for the calculation of population dose. In other words, this assumes that the maximum individual freezes and eats a whole beef, while the average individual buys smaller portions at a time.

Population doses are summed over all sector elements to obtain a total population dose for the 50-mile population.

7.6.5 REPORTING OF DOSES The calculated quarterly doses and calculated population doses described in this section are reported in the Annual Radiological Effluent Release Report as required by ODCM Administrative Control 5.2.

7.6.6 DOSE TO A MEMBER OF THE PUBLIC INSIDE THE UNRESTRICTED or RESTRICTED AREA BOUNDARY The Basis for ODCM Control 1.2.2.1 states that for MEMBERS OF THE PUBLIC who may at times be within the UNRESTRICTED or RESTRICTED AREA BOUNDARY, the occupancy factor of that MEMBER OF THE PUBLIC will usually be sufficiently low to compensate for any increase in the atmospheric dispersion factor above that for the UNRESTRICTED AREA BOUNDARY.

This basis also states that examples of calculations for such MEMBERS OF THE PUBLIC will be given in the ODCM.

The determination presented here assumes that the most exposed MEMBER OF THE PUBLIC will be an adult TVA employee who works just outside the restricted area fence for the entire workyear (2000 hours0.0231 days <br />0.556 hours <br />0.00331 weeks <br />7.61e-4 months <br />). Results from onsite Thermoluminescent Dosimeter (TLD) measurements from the years 1990-1992 indicate that the highest onsite external dose was 72.6 mrem. Using this value, subtracting an annual background value of 55 mrem/year, and multiplying by the ratio of the occupancy times, the highest external dose to a MEMBER OF THE PUBLIC inside the UNRESTRICTED AREA BOUNDARY is 4 mrem. Historical records show that the total dose contribution from effluent releases is normally less than 2 mrem. The combination of the measured direct dose (part of which is from effluent releases) and the calculated effluent dose will be below both the 10 CFR Part 20 limit of 100 mrem/year and the 40 CFR Part 190 limit of 25 mrem/year. In addition to this analysis, the dose to this hypothetical MEMBER OF THE PUBLIC will be determined on an annual basis (using the methodology above) to ensure that the actual dose to any individual is less than 100 mrem/year. The results of this review will be included in the Annual Radiological Effluent Release Report pursuant to ODCM Administrative Control 5.2.

SQN ODCM Revision 47 Page 116 of 168 7.7 GASEOUS RELEASES - Dose Factors 7.7.1 PASTURE GRASS-COW/GOAT-MILK INGESTION DOSE FACTORS (m2 -mremfy per RiCi/s)

Rcpi = 106DFLaoUapFmjQfexp(-qtfm)fp {r(1-exp(-tE!2 + B_1-exp(-_ ,t YpIE P where:

106 = conversion factor, pCi/liCi.

DFLiao = ingestion dose conversion factor for nuclide i, age group a, organ o, mrem/pCi (Table 6.4).

Uap = milk ingestion rate for age group a, LUy.

Fmi = transfer factor for nuclide i from animal's feed to milk, d/L(Table 6.2).

Qf = animal's consumption rate, kg/d.

Oq = decay constant for nuclide i, s-1 (Table 6.2) t4m = transport time from milking to receptor, s.

fp = fraction of time animal spends on pasture, dimensionless.

r = fraction of activity retained on pasture grass, dimensionless.

DE = the effective decay constant, due to radioactive decay and weathering, s-1, equal to Di +

Ow.

Dw = weathering decay constant for leaf and plant surfaces, s-1.

tep = time pasture is exposed to deposition, s.

Yp = agricultural productivity by unit area of pasture grass, kg/m2 .

Biv = transfer factor for nuclide i from soil to vegetation, pCi/kg (wet weight of vegetation) per pCi/kg (dry soil).

tb = time period over which accumulation on the ground is evaluated, s.

P = effective surface density of soil, kg/m2 NOTE: Factors defined above which do not reference a table for their numerical values are given in Table 6.3.

SQN ODCM Revision 47 Page 117 of 168 7.7.2 STORED FEED-COW/GOAT-MILK INGESTION DOSE FACTORS (m2 -mrem/y per p.Ci/s)

Rcsi 106 DFLaUapFmIQf fsexp(-itfm)

(1-exp(-atSf)) {r(1-exp(-UEtsff) + B- (1-exp(-Dtj}

tcsf Di Ysf DE PLI; where:

106 = conversion factor, pCi/pCi.

DFLiao = ingestion dose conversion factor for nuclide i, age group a, organ o, mrem/pCi (Table 6.4).

Uap = milk ingestion rate for age group a, L/y.

Fmi = transfer factor for nuclide i from animal's feed to milk, d/L (Table 6.2).

Qf = animal's consumption rate, kg/d.

fs = fraction of time animal spends on stored feed, dimensionless.

Oq = decay constant for nuclide i, s-1 (Table 6.2).

tfm = transport time from milking to receptor, s.

tcsf = time between harvest of stored feed and consumption by animal, s.

r = fraction of activity retained on pasture grass, dimensionless.

DE = the effective decay constant, due to radioactive decay and weathering, s-1, equal to fl+DL-

°w = weathering decay constant for leaf and plant surfaces, s-1 tesf = time stored feed is exposed to deposition, s.

Ysf = agricultural productivity by unit area of stored feed, kg/m2 Biv = transfer factor for nuclide i from soil to vegetation, pCi/kg (wet weight of vegetation) per pCi/kg (dry soil).

tb = time period over which accumulation on the ground is evaluated, s.

P = effective surface density of soil, kg/m2 NOTE: Factors defined above which do not reference a table for their numerical values are given in Table 6.3.

SQN ODCM Revision 47 Page 118 of 168 7.7.3 PASTURE GRASS-BEEF INGESTION DOSE FACTORS (m2 -mrem/y per IACi/s)

Rm pi106DFLiaoUamFFiQF(1-exD(-Ojtb1 ) exp(-Ljts) fp {r(I-exp(-Ete~ + B-J1-exp(-Eity O O O O ri OOODiltb tbe YpE P Oj PBD where: 106 = conversion factor, pCi/LCi. DFLiao = ingestion dose conversion factor for nuclide i, age group a, organ o, mrem/pCi (Table 6.4). Uam = beef ingestion rate for age group a, kg/y. FFi = transfer factor for nuclide i from cow's feed to meat, d/kg (Table 6.2). QF: = cow's consumption rate, kg/d. Oq = decay constant for nuclide i, s-1 (Table 6.2). tcb = time for receptor to consume a whole beef, s. ts = transport time from slaughter to consumer, s. fp = fraction of time cow spends on pasture, dimensionless. r = fraction of activity retained on pasture grass, dimensionless. DE = the effective decay constant, due to radioactive decay and weathering, s-1, equal to 0j+D, Cans = weathering decay constant for leaf and plant surfaces, s-1 tep = time pasture is exposed to deposition, s. Yp = agricultural productivity by unit area of pasture grass, kg/m2 Biv = transfer factor for nuclide i from soil to vegetation, pCi/kg (wet weight of vegetation) per pCi/kg (dry soil). tb = time over which accumulation on the ground is evaluated, s. P = effective surface density of soil, kg/m2 NOTE: Factors defined above which do not reference a table for their numerical values are given in Table 6.3.

SQN ODCM Revision 47 Page 119 of 168 7.7.4 STORED FEED-BEEF INGESTION DOSE FACTORS (m2 -mrem/y per gtCi/s) RMsi = 106 DFLiao Uam FFi QF (1-exD(- tb 0 ) exp(-Flts) fs (1-exp(-ELt,,f)j {r(0-exp(-QEtEf)j + l 1 n O1n lEElO 0 01 j oDb Di tcsf Ysf DE B. 1 -exD(-ODt PEO where: 106 = conversion factor, pCi/RCi. DFLiao = ingestion dose conversion factor for nuclide i, age group a, organ o, mrem/pCi (Table 6.4). Uam = beef ingestion rate for age group a, kg/y. FFR = transfer factor for nuclide i from cow's feed to meat, d/kg (Table 6.2). QF = coWs consumption rate, kg/d. Di = decay constant for nuclide i, S-1 (Table 6.2). teb = time for receptor to consume a whole beef, s. ts = transport time from slaughter to consumer, s. fs = fraction of time cow spends on stored feed, dimensionless. t,,f = time between harvest of stored feed and consumption by cow, s. r = fraction of activity retained on pasture grass, dimensionless. tef = time stored feed is exposed to deposition, s. Ysf = agricultural productivity by unit area of stored feed, kg/m2 . DE = the effective decay constant, due to radioactive decay and weathering, s-1, equal to Di+E1w Elw = weathering decay constant for leaf and plant surfaces, s-1. Biv = transfer factor for nuclide i from soil to vegetation, pCi/kg (wet weight of vegetation) per pCi/kg (dry soil). tb = time over which accumulation on the ground is evaluated, s. P = effective surface density of soil, kg/m 2 . NOTE: Factors defined above which do not reference a table for their numerical values are given in Table 6.3.

SQN ODCM Revision 47 Page 120 of 168 7.7.5 FRESH LEAFY VEGETABLE INGESTION DOSE FACTORS (m2 -mrem/y per jCi/s) Rvrj = 106 DFLiao exP(-OithC) UFLafL {r(l-e(-El )) + BvL_("- U1 YF E PLIq where: 106 conversion factor, pCi/RCi. DFLiao = ingestion dose conversion factor for nuclide i, age group a, organ o, mrem/pCi (Table 6.4). Oq = decay constant for nuclide i, s-1 (Table 6.2). tho = average time between harvest of vegetables and their consumption and/or storage, s. UFLa = consumption rate of fresh leafy vegetables by the receptor in age group a, kgly. fL = fraction of fresh leafy vegetables grown locally, dimensionless. r = fraction of deposited activity retained on vegetables, dimensionless. DE = the effective decay constant, due to radioactive decay and weathering, s- 1,

       = ° + X1 Daw     = decay constant for removal of activity on leaf and plant surfaces by weathering, s-1.

te = exposure time in garden for fresh leafy and/or stored vegetables, s. YF = agricultural yield for fresh leafy vegetables, kg/im2 . Biv = transfer factor for nuclide i from soil to vegetables, pCi/kg (wet weight of vegetation) per pCi/kg (dry soil). tb = time period over which accumulation on the ground is evaluated, s. P = effective surface density of soil, kg/im2 . NOTE: Factors defined above which do not reference a table for their numerical values are given in Table 6.3.

SQN ODCM Revision 47 Page 121 of 168 7.7.6 STORED VEGETABLE INGESTION DOSE FACTORS m2-mrem/y per p.Ci/s) Rvs- 106 DFLjao exp(-LDthC) Usafg (1-exp(-EItsvf {r(t-exD(-Lc)} + Bi _1-exr_(-o 0 O OOOOO t1V Ysv PE P O where: 106 = conversion factor, pCi/jgCi. DFLiao = ingestion dose conversion factor for nuclide i, age group a, organ o, mrem/pCi (Table 6.4). D, = decay constant for nuclide i, s-1 (Table 6.2). the = average time between harvest of vegetables and their consumption and/or storage, s. Usa = consumption rate of stored vegetables by the receptor in age group a, kg/y. fg = fraction of stored vegetables grown locally, dimensionless. tsv = time between storage of vegetables and their consumption, s. r = fraction of deposited activity retained on vegetables, dimensionless. OE = the effective decay constant, due to radioactive decay and weathering, s-1.

         =q+   Dw Ow      =  decay constant for removal of activity on leaf and plant surfaces by weathering, s-1.

te = exposure time in garden for fresh leafy and/or stored vegetables, s. Ysv = agricultural yield for stored vegetables, kg/mi2 . Biv = transfer factor for nuclide i from soil to vegetables, pCi/kg (wet weight of vegetation) per pCi/kg (dry soil). tb = time period over which accumulation on the ground is evaluated, s. P = effective surface density of soil, kg/im2 . NOTE: Factors defined above which do not reference a table for their numerical values are given in Table 6.3.

SQN ODCM Revision 47 Page 122 of 168 7.7.7 TRITIUM-PASTURE GRASS-COW/GOAT-MILK DOSE FACTOR (mrem/y per jtCi/m 3 ) RCTP = 103 106 DFLTao FmT QF Uap [0.75(0.5/H)] fp exp(-ElT4m) where: 103 = conversion factor, g/kg. 106 = conversion factor, pCi/luCi. DFLTao = ingestion dose conversion factor for tritium for age group a, organ o, mrem/pCi (Table 6.4). FmT = transfer factor for tritium from animal's feed to milk, d/L (Table 6.2). QF = animal's consumption rate, kg/d. Ua = milk ingestion rate for age group a, L/y. 0.75 = the fraction of total feed that is water. 0.5 = the ratio of the specific activity of the feed grass water to the atmospheric water. H = absolute humidity of the atmosphere, g/m 3 fp = fraction of time animal spends on pasture, dimensionless. ET = decay constant for tritium, s-1 (Table 6.2). 4m = transport time from milking to receptor, s. 7.7.8 TRITIUM-STORED FEED-COW/GOAT-MILK DOSE FACTOR (mrem/y per gCi/m 3 ) RCTS = 103 106 DFLTaO FFT QF Uam [0.75(0.5/H)] fs exp(-E Tts) 1 (L-exp(-EL-tcsfa (1-ex (-oTt-b 1 bTtcsf CT tcb where: 103 = conversion factor, g/kg. 106 = conversion factor, pCi/lpCi. DFLTao = ingestion dose conversion factor for H-3 for age group a, organ o, mrem/pCi (Table 6.4). FFT = transfer factor for H-3 from cow's feed to meat, d/kg (Table 6.2). QF = cow's consumption rate, kg/d. Uam = meat ingestion rate for age group a, kg/y. 0.75 = the fraction of total feed that is water. 0.5 = the ratio of the specific activity of the feed grass water to the atmospheric water. H = absolute humidity of the atmosphere, g/m3 fs = fraction of time cow spends on stored feed, dimensionless. DT = decay constant for tritium, s-1 (Table 6.2). ts = transport time from slaughter to consumer, s. tcsf = time to consume stored feed, s. tcb = time for receptor to consume a whole beef, s. NOTE: Factors defined above which do not reference a table for their numerical values are given in Table 6.3.

SQN ODCM Revision 47 Page 123 of 168 7.7.9 TRITIUM-PASTURE GRASS-BEEF DOSE FACTOR (mrem/y per gCi/m 3 ) RMTP = 103106 DFLTaoFFTQF Uam [0.75(0.5/H)] fp exp(-CTts) (1-exp(-Ecrt!) (l-exp(-Erttb) 11 CT tep LT tcb where: 103 = conversion factor, g/kg. 106 = conversion factor, pCi/pACi. DFLTao = ingestion dose conversion factor for H-3 for age group a, organ o, mrem/pCi (Table 6.4). FFT = transfer factor for H-3 from cow's feed to meat, d/kg (Table 6.2). QF = cow's consumption rate, kg/d. Uam = beef ingestion rate for age group a, kg/y. 0.75 = the fraction of total feed that is water. 0.5 = the ratio of the specific activity of the feed grass water to the atmospheric water. H = absolute humidity of the atmosphere, g/m3 fp = fraction of time cow spends on pasture, dimensionless. CT = decay constant for tritium, s-1 (Table 6.2). ts = transport time from slaughter to consumer, s. tep = time pasture is exposed to deposition, s. tCb = time for receptor to consume a whole beef, s. 7.7.10 TRITIUM-STORED FEED-BEEF DOSE FACTOR (mrem/y per jxCi/m 3 ) RMTS = 103 106 DFLTaoFFTQFUam[0. 75 (05/H)1 fs exp(-L]Tts) (L-exD(-Ttcsf)j ( -exp -OTt 1 CTTCSf OT EC where: 103 = conversion factor, g/kg. 106 = conversion factor, pCi/jiCi. DFLTao = ingestion dose conversion factor for H-3 for age group a, organ o, mrem/pCi (Table 6.4). FFT = transfer factor for H-3 from cow's feed to meat, d/kg (Table 6.2). QF = coW's consumption rate, kg/d. Uam = beef ingestion rate for age group a, kg/y. 0.75 = the fraction of total feed that is water. 0.5 = the ratio of the specific activity of the feed grass water to the atmospheric water. H = absolute humidity of the atmosphere, g/m3 . fs = fraction of time cow spends on stored feed, dimensionless. OT = decay constant for tritium, s-1 (Table 6.2). ts = transport time from slaughter to consumer, s. tcsf = time to consume stored feed, s. tcb = time for receptor to consume a whole beef, s. NOTE: Factors defined above which do not reference a table for their numerical values are given in Table 6.3.

SQN ODOM Revision 47 Page 124 of 168 7.7.11 TRITIUM-FRESH LEAFY VEGETABLES DOSE FACTOR (mrem/y per ptCi/m 3 ) RvrF = 103 106 DFLTao [0.75(0.5/H)] UFLa fL exp(-Tlithc) where: 103 = conversion factor, g/kg. 106 = conversion factor, pCi/R.Ci. DFLTao = ingestion dose conversion factor for tritium for age group a, organ o, mrem/pCi (Table 6.4). 0.75 = the fraction of total vegetation that is water. 0.5 = the ratio of the specific activity of the vegetables water to the atmospheric water. H = absolute humidity of the atmosphere, g/m 3 UFLa = consumption rate of fresh leafy vegetables by the receptor in age group a, kg/y. fL = fraction of fresh leafy vegetables grown locally, dimensionless. EJT = decay constant for tritium, s-1 (Table 6.2). tho = time between harvest of vegetables and their consumption and/or storage, s. NOTE: Factors defined above which do not reference a table for their numerical values are given in Table 6.3.

SQN ODCM Revision 47 Page 125 of 168 7.7.12 TRITIUM-STORED VEGETABLES DOSE FACTOR (mrem/year per p.Ci/m3) RVrS = 10 106 DFLTao [0.75(0.5/H)] Usafg (1-exl(-J-s-1v)1 eXP(OBthc) DT tsv where: 103 = conversion factor, g/kg. 106 = conversion factor, pCi/gCi. DFLTao = ingestion dose conversion factor for tritium for age group a, organ o, mrem/pCi (Table 6.4). 0.75 = the fraction of total vegetation that is water. 0.5 = the ratio of the specific activity of the vegetation water to the atmospheric water. H = absolute humidity of the atmosphere, g/m3 . Usa = consumption rate of stored vegetables by the receptor in age group a, kg/y. fg = fraction of stored vegetables grown locally, dimensionless. DT = decay constant for tritium, s-1 (Table 6.2). tsv = time between harvest of stored vegetables and their consumption and/or storage, s. thc = time between harvest of vegetables and their storage, s. 7.7.13 INHALATION DOSE FACTORS (mrem/y per Ci/in3 ) Rij = DFAiao BRa 106 where: DFAiao = inhalation dose conversion factor for nuclide i, age group a and organ o, mrem/pCi (Table 7.6). BRa = breathing rate for age group a, m3/y (Table 6.3). 106 = conversion factor, pCi/fuCi. 7.7.14 GROUND PLANE DOSE FACTORS (m2 -mrem/y per gCi/s) RGj = DFGj, 1/Oq 106 8760 [1 - exp(-Litb)] where: DFGj 0 = dose conversion factor for standing on contaminated ground for nuclide i and organ o (total body and skin), mrem/hr per pCi/m 2 (Table 6.6). O; = decay constant of nuclide i, s-1 (Table 6.2). 106 = conversion factor, pCi/pCi. 8760 = conversion factor, h/y. tb = time period over which the ground accumulation is evaluated, s (Table 6.3).

SQN ODCM Revision 47 Page 126 of 168 7.8 DISPERSION METHODOLOGY Dispersion factors are calculated for radioactive effluent releases using hourly average meteorological data consisting of wind speed and direction measurements at 1Oim and temperature measurements at 9m and 46m. A sector-average dispersion equation consistent with Regulatory Guide 1.111 is used. The dispersion model considers plume depletion (using information from Figure 7.4), and building wake effects. Terrain effects on dispersion are not considered. Hourly average meteorological data are expressed as a joint-frequency distribution of wind speed, wind direction, and atmospheric stability. A joint-frequency distribution for each quarter from 1986-1995 is used for calculations described in Section 7.2, 7.3, 7.4, and 7.5. A joint-frequency distribution using the actual hourly-average meteorological data is used for calculations described in Section 7.6. The wind speed classes that are used are as follows: Number Range (m/s) Midpoint (m/s) 1 <0.3 0.13 2 0.3-0.6 0.45 3 0.7-1.5 1.10 4 1.6-2.4 1.99 5 2.5-3.3 2.88 6 3.4-5.5 4.45 7 5.6-8.2 6.91 8 8.3-10.9 9.59 9 >10.9 10.95 The stability classes that will be used are the standard A through G classifications. The stability classes 1-7 will correspond to A=1, B=2, ..., G=7. 7.8.1 AIR CONCENTRATION Air concentrations of nuclides at downwind locations are calculated using the following equation: 9 7 Cl=E EE(2/El)1/2 pk QP exp(-L x/uj) (7.14)

           ]=1 k=1         Ezk Ui (2Ddn) where fjik   = joint relative frequency of occurrence of winds in windspeed class j, stability class k, blowing toward this exposure point, expressed as a fraction.

Qi = release rate of radionuclide i, RCi/s. p = fraction of radionuclide remaining in plume (Figure 7.4).

SQN ODCM Revision 47 Page 127 of 168 Dzk = vertical dispersion coefficient for stability class k which includes a building wake adjustment,

        = (ozk2 + CA/0)1/2, or = (3)1/2 Dzk, whichever is smaller.

where Lzk is the vertical dispersion coefficient for stability class k (m) (Figure 7.5), c is a building shape factor (c=0.5), A is the minimum building cross-sectional area (1800 m2). uj = midpoint value of wind speed class interval j, m/s. x = downwind distance, m. n = number of sectors, 16. Ei = radioactive decay coefficient of radionuclide i, s-1 2ExIn = sector width at point of interest, m. 7.8.2 RELATIVE CONCENTRATION Relative concentrations of nuclides at downwind locations are calculated using the following equation: 9 7 2/Q = ]rn (2/0) 112 fik (7.15) j=1 k=1 D;k uj r25n) where fjk = joint relative frequency of occurrence of winds in windspeed class j, stability class k, blowing toward this exposure point, expressed as a fraction. Ozk = vertical dispersion coefficient for stability class k which includes a building wake adjustment,

        = ([Zk 2 + CA/[])1 12 or = (3)1/2 Fzk, whichever is smaller.

where Dzk is the vertical dispersion coefficient for stability class k (m) (Figure 7.5), c is a building shape factor (c=0.5), A is the minimum building cross-sectional area (1800 m2) u; = midpoint value of wind speed class interval j, m/s. x = downwind distance, m. n = number of sectors, 16. 2E0xn = sector width at point of interest, m.

SQN ODCM Revision 47 Page 128 of 168 7.8.3 RELATIVE DEPOSITION Relative deposition of nuclides at downwind locations is calculated using the following equation: 9 7 fjkDR D/Q = El IL _ -_ (7.16) j=1 k=1 (2EiyIn) where fik = joint relative frequency of occurrence of winds in windspeed class j and stability class k, blowing toward this exposure point, expressed as a fraction. DR = relative deposition rate, m-1 (from Figure 7.6). x = downwind distance, m. n = number of sectors, 16. 2EY/n = sector width at point of interest, m.

SQN ODCM Revision 47 Page 129 of 168 Table 7.1 Sequoyah Mazdmum Quarterly EIQ (1986-1995) Sorted by Quarter QUARTER YEAR MAXIMUM SECTOR DISTANCE (METERS) EyQ(10-6 S/M3 ) 1 1986 NNW 730 5.88 2 1986 NNW 730 6.99 3 1986 N 950 5.66 4 1986 SSW 1840 9.01 1 1987 SSW 1840 6.87 2 1987 N 950 10.00 3 ,1987 S 1570 7.55 4 1987 SSW 1840 9.45 1 1988 N 950 4.11 2 1988 SSW 1840 6.00 3 1988 N 950 6.05 4 1988 SSW 1840 5.30 1 1989 NNW 730 5.58 2 1989 N 950 5.97 3 1989 S 1570 7.48 4 1989 N 950 6.67 1 1990 N 950 5.38 2 1990 N 950 4.47 3 1990 SSW 1840 6.22 4 1990 NNW 730 6.50 1 1991 SSW 1840 4.41 2 1991 N 950 7.63 3 1991 S 1570 6.76 4 1991 NNW 730 5.91 1 1992 NW 660 6.83 2 1992 N 950 7.05 3 1992 N 950 6.37 4 1992 SSW 1840 6.19 I 1993 SSW 1840 9.15 2 1993 N 950 9.59 3 1993 N 950 6.53 4 1993 N 950 5.81 1 1994 SSW 1840 7.51 2 1994 N 950 7.73 3 1994 N 950 8.77 4 1994 SSW 1840 10.20 1 1995 N 950 4.86 2 1995 N 950 6.02 3 1995 S 1570 13.20 4 1995 S 1570 6.01 Average X/Q(1986-1995) = 6.94 x 10-6

SQN ODCM Revision 47 Page 130 of 168 Table 7.2 Sequoyah Mazdmum Quarterly D/Q (1986-1995) Sorted by Quarter QUARTER YEAR MAXIMUM DISTANCE D/Q(10 8 1/M2 ) 1 1986 NNW 660 0.92 2 1986 N 950 1.33 3 1986 N 950 1.57 4 1986 SSW 1840 1.56 1 1987 SSW 1840 1.34 2 1987 N 950 1.78 3 1987 N 950 1.30 4 1987 SSW 1840 1.01 1 1988 N 950 1.09 2 1988 SSW 1840 1.08 3 1988 N 950 1.29 4 1988 SSW 1840 1.10 1 1989 SSW 1840 1.16 2 1989 N 950 1.63 3 1989 N 950 1.28 4 1989 SSW 1840 0.97 1 1990 N 950 1.22 2 1990 N 950 1.19 3 1990 SSW 1840 1.09 4 1990 SSW 1840 1.10 1 1991 N 950 1.03 2 1991 N 950 1.87 3 1991 N 950 1.33 4 1991 N 950 1.29 1 1992 SSW 1840 1.05 2 1992 N 950 1.12 3 1992 N 950 1.46 4 1992 SSW 1840 1.10 1 1993 SSW 1840 1.31 2 1993 N 950 1.47 3 1993 N 950 1.41 4 1993 N 950 1.25 1 1994 SSW 1840 1.13 2 1994 N 950 1.43 3 1994 N 950 1.80 4 1994 SSW 1840 1.69 1 1995 SSW 1840 0.99 2 1995 N 950 1.78 3 1995 S 1570 1.42 4 1995 S 1570 1.13 Average D/Q(1986-1995) = 1.30 x 10-"

SQN ODCM Revision 47 Page 131 of 168 Table 7.3 DOSE FACTORS FOR SUBMERSION IN NOBLE GASES Submersion dose Air dose mrem/y per jACi/m 3 mrad/y per pCi/m 3 DFB. DFSj DFa DFEJ Kr-83m 7.56E-02 1.93E+01 2.88E+02 Kr-85m 1.17E+03 1.46E+03 1.23E+03 1.97E+03 Kr-85 1.61 E+01 1.34E+03 1.72E+01 1.95E+03 Kr-87 5.92E+03 9.73E+03 6.17E+03 1.03E+04 Kr-88 1.47E+04 2.37E+03 1.52E+04 2.93E+03 Kr-89 1.66E+04 1.01 E+04 1.73E+04 1.06E+04 Kr-90 1.56E+04 7.29E+03 1.63E+04 7.83E+03 Xe-131m 9.15E+01 4.76E+02 1.56E+02 1.11E+03 Xe-133m 2.51 E+02 9.94E+02 3.27E+02 1.48E+03 Xe-1 33 2.94E+02 3.06E+02 3.53E+02 1.05E+03 Xe-1 35m 3.12E+03 7.11 E+02 3.36E+03 7.39E+02 Xe-1 35 1.81E+03 1.86E+03 1.92E+03 2.46E+03 Xe-1 37 1.42E+03 1.22E+04 1.51 E+03 1.27E+04 Xe-138 8.83E+03 4.13E+03 9.21 E+03 4.75E+03 Ar-41 8.84E+03 2.69E+03 9.30E+03 3.28E+03

Reference:

Regulatory Guide 1.109, Table B-1.

SQN ODCM Revision 47 Page 132 of 168 Table 7.4 SECTOR ELEMENTS CONSIDERED FOR POPULATION DOSES Range of Midpoint of Sector Element Sector Element Unrestricted Area boundary - 1 mile 0.8 mile 1 - 2 miles 1.5 miles 2 - 3 miles 2.5 miles 3 - 4 miles 3.5 miles 4 - 5 miles 4.5 miles 5 - 10 miles 7.5 miles 10 - 20 miles 15 miles 20 - 30 miles 25 miles 30 - 40 miles 35 miles 40 - 50 miles 45 miles

SQN ODCM Revision 47 Page 133 of 168 Table 7.5 POPULATION WITHIN EACH SECTOR ELEMENT Sector Midpoint (miles) 0.8 1.5 2.5 3.5 4.5 7.5 15 25 35 45 N 20 41 213 129 66 1784 5453 3470 2610 11145 NNE 0 30 123 182 62 600 0628 4910 8250 10625 NE 0 0 67 67 94 581 2884 6998 7047 18080 ENE 0 11 24 222 300 773 4707 5747 29477 18679 E 0 70 11 191 137 918 7440 6808 5072 4129 ESE 0 118 113 194 137 1849 46521 5044 1896 3624 SE 0 179 322 168 205 1507 6005 5461 15641 3417 SSE 0 125 370 750 601 2347 13242 8596 34279 1648 S 0 67 143 229 811 3930 28008 26690 19642 11622 SSW 0 82 140 400 170 8927 96966 55597 21349 11978 SW 0 10 306 634 194 9787 94225 23455 11641 11109 WSW 20 190 642 1124 1669 19089 28405 4106 15081 9548 W 10 20 233 657 657 5225 1580 6350 5699 7707 WNW 10 30 365 598 598 2622 6540 4920 6699 2450 NW 50 80 292 569 336 2696 1410 1750 1217 15856 NNW 10 263 80 75 213 1610 471 3130 2835 5719

SQN ODCM Revision 47 Page 134 of 168 Table 7.6 INHALATION DOSE FACTORS (mrem/pCi inhaled) (Page 1 of 8) ADULT bone liver t body thyroid kidney lung gi-Ili H-3 1.58E-07 1.58E-07 1.58E-07 1.58E-07 1.58E-07 1.58E-07 1.58E-07 C-14 2.27E-06 4.26E-07 4.26E-07 4.26E-07 4.26E-07 4.26E-07 4.26E-07 Na-24 1.28E-06 1.28E-06 1.28E-06 1.28E-06 1.28E-06 1.28E-06 1.28E-06 P-32 1.65E-04 9.64E-06 6.26E-06 O.OOE+00 O.OOE+00 O.OOE+00 1.08E-05 Cr-51 O.OOE+00 O.OOE+00 1.25E-08 7.44E-09 2.85E-09 1.80E-06 4.15E-07 Mn-54 O.OOE+00 4.95E-06 7.87E-07 O.OOE+00 1.23E-06 1.75E-04 9.67E-06 Mn-56 O.OOE+00 1.55E-10 2.29E-11 O.OOE+00 1.63E-10 1.18E-06 2.53E-06 Fe-55 3.07E-06 2.12E-06 4.93E-07 O.OOE+00 O.OOE+00 9.01E-06 7.54E-07 Fe-59 1.47E-06 3.47E-06 1.32E-06 O.OOE+00 O.OOE+00 1.27E-04 2.35E-05 Co-57 O.OOE+00 8.65E-08 8.39E-08 O.OOE+00 O.OOE+00 4.62E-05 3.93E-06 Co-58 O.OOE+00 1.98E-07 2.59E-07 O.OOE+00 O.OOE+00 1.16E-04 1.33E-05 Co-60 O.OOE+00 1.44E-06 1.85E-06 O.OOE+00 O.OOE+00 7.46E-04 3.56E-05 Ni-63 5.40E-05 3.93E-06 1.81 E-06 O.OOE+00 O.OOE+00 2.23E-05 1.67E-06 Ni-65 1.92E-10 2.62E-11 1.14E-11 O.OOE+00 O.OOE+00 7.OOE-07 1.54E-06 Cu-64 O.OOE+00 1.83E-10 7.69E-11 O.OOE+00 5.78E-10 8.48E-07 6.12E-06 Zn-65 4.05E-06 1.29E-05 5.82E-06 0.OOE+00 8.62E-06 1.08E-04 6.68E-06 Zn-69 4.23E-12 8.14E-12 5.65E-13 O.OOE+00 5.27E-12 1.15E-07 2.04E-09 Zn-69m 1.02E-09 2.45E-09 2.24E-10 O.OOE+00 1.48E-09 2.38E-06 1.71 E-05 Br-82 O.OOE+00 O.OOE+00 1.69E-06 O.OOE+00 O.OOE+00 O.OOE+00 1.30E-06 Br-83 O.OOE+00 O.OOE+00 3.01 E-08 O.OOE+00 O.OOE+00 O.OOE+00 2.90E-08 Br-84 O.OOE+00 O.OOE+00 3.91E-08 O.OOE+00 O.OOE+00 O.OOE+00 2.05E-13 Br-85 O.OOE+00 O.OOE+00 1.60E-09 O.OOE+00 O.OOE+00 O.OOE+00 O.OOE+00 Rb-86 O.OOE+00 1.69E-05 7.37E-06 O.OOE+00 O.OOE+O0 O.OOE+00 2.08E-06 Rb-88 O.OOE+00 4.84E-08 2.41E-08 O.OOE+00 O.OOE+00 0.OOE+0O 4.18E-19 Rb-89 O.OOE+00 3.20E-08 2.12E-08 O.OOE+00 0.OOE+OO O.OOE+00 1.16E-21 Sr-89 3.80E-05 O.OOE+00 1.09E-06 O.OOE+00 O.OOE+00 1.75E-04 4.37E-05 Sr-90 1.24E-02 O.OOE+00 7.62E-04 O.OOE+00 O.OOE+00 1.20E-03 9.02E-05 Sr-91 7.74E-09 O.0OE+OO 3.13E-10 O.OOE+00 O.OOE+00 4.56E-06 2.39E-05 Sr-92 8.43E-10 O.OOE+00 3.64E-11 O.OOE+00 O.OOE+00 2.06E-06 5.38E-06 Y-90 2.61E-07 O.OOE+00 7.01E-09 O.OOE+00 O.OOE+00 2.12E-05 6.32E-05 Y-91m 3.26E-11 O.OOE+00 1.27E-12 O.OOE+00 O.OOE+00 2.40E-07 1.66E-10 Y-91 5.78E-05 O.OOE+00 1.55E-06 O.OOE+00 O.OOE+00 2.13E-04 4.81E-05 Y-92 1.29E-09 O.OOE+00 3.77E-11 O.OOE+00 O.OOE+00 1.96E-06 9.19E-06 Y-93 1.18E-08 O.OOE+00 3.26E-10 O.OOE+00 O.OOE+00 6.06E-06 5.27E-05 Zr-95 1.34E-05 4.30E-06 2.91 E-06 O.OOE+00 6.77E-06 2.21 E-04 1.88E-05 Zr-97 1.21E-08 2.45E-09 1.13E-09 O.OOE+00 3.71E-09 9.84E-06 6.54E-05 Nb-95 1.76E-06 9.77E-07 5.26E-07 O.OOE+00 9.67E-07 6.31 E-05 1.30E-05 Nb-97 2.78E-11 7.03E-12 2.56E-12 O.OOE+00 8.18E-12 3.OOE-07 3.02E-08 Mo-99 O.OOE+00 1.51E-08 2.87E-09 O.OOE+00 3.64E-08 1.14E-05 3.1OE-05 Tc-99m 1.29E-13 3.64E-13 4.63E-12 O.OOE+00 5.52E-12 9.55E-08 5.20E-07 Tc-101 5.22E-15 7.52E-15 7.38E-14 O.OOE+00 1.35E-13 4.99E-08 1.36E-21 Ru-103 1.91E-07 0.OOE+OO 8.23E-08 O.OOE+00 7.29E-07 6.31 E-05 1.38E-05 Ru-105 9.88E-11 O.OOE+00 3.89E-11 O.OOE+00 1.27E-10 1.37E-06 6.02E-06 Ru-106 8.64E-06 O.OOE+00 1.09E-06 O.OOE+00 1.67E-05 1.17E-03 1.14E-04 Ag-1 Om 1.35E-06 1.25E-06 7.43E-07 O.OOE+00 2.46E-06 5.79E-04 3.78E-05

SQN ODCM Revision 47 Page 135 of 168 Table 7.6 INHALATION DOSE FACTORS (mrem/pCi inhaled) (Page 2 of 8) ADULT bone liver t body thyroid kidney lung gi-Ili Sb-124 3.90E-06 7.36E-08 1.55E-06 9.44E-09 0.OOE+00 3.10E-04 5.OBE-05 Sb-125 6.67E-06 7.44E-08 1.58E-06 6.75E-09 0.OOE+00 2.18E-04 1.26E-05 Sn-125 1.16E-06 3.12E-08 7.03E-08 2.59E-08 O.OOE+00 7.37E-05 6.81E-05 Te-125m 4.27E-07 1.98E-07 5.84E-08 1.31E-07 1.55E-06 3.92E-05 8.83E-06 Te-127m 1.58E-06 7.21E-07 1.96E-07 4.11E-07 5.72E-06 1.20E-04 1.87E-05 Te-127 1.75E-10 8.03E-11 3.87E-11 1.32E-10 6.37E-10 8.14E-07 7.17E-06 Te-129m 1.22E-06 5.84E-07 1.98E-07 4.30E-07 4.57E-06 1.45E-04 4.79E-05 Te-129 6.22E-12 2.99E-12 1.55E-12 4.87E-12 2.34E-11 2.42E-07 1.96E-08 Te-131m 8.74E-09 5.45E-09 3.63E-09 6.88E-09 3.86E-08 1.82E-05 6.95E-05 Te-131 1.39E-12 7.44E-13 4.49E-13 1.17E-12 5.46E-12 1.74E-07 2.30E-09 Te-132 3.25E-08 2.69E-08 2.02E-08 2.37E-08 1.82E-07 3.60E-05 6.37E-05 1-130 5.72E-07 1.68E-06 6.60E-07 1.42E-04 2.61 E-06 O.OOE+00 9.61 E-07 1-131 3.15E-06 4.47E-06 2.56E-06 1.49E-03 7.66E-06 O.OOE+00 7.85E-07 1-132 1.45E-07 4.07E-07 1.45E-07 1.43E-05 6.48E-07 0.OOE+00 5.08E-08 1-133 1.08E-06 1.85E-06 5.65E-07 2.69E-04 3.23E-06 0.OOE+00 1.11E-06 1-134 8.05E-08 2.16E-07 7.69E-08 3.73E-06 3.44E-07 0.OOE+00 1.26E-10 1-135 3.35E-07 8.73E-07 3.21E-07 5.60E-05 1.39E-06 0.OOE+00 6.56E-07 Cs-134 4.66E-05 1.06E-04 9.1OE-05 0.OOE+00 3.59E-05 1.22E-05 1.30E-06 Cs-136 4.88E-06 1.83E-05 1.38E-05 O.OOE+00 1.07E-05 1.50E-06 1.46E-06 Cs-137 5.98E-05 7.76E-05 5.35E-05 O.OOE+00 2.78E-05 9.40E-06 1.05E-06 Cs-138 4.14E-08 7.76E-08 4.05E-08 0.OOE+00 6.OOE-08 6.07E-09 2.33E-13 Ba-139 1.17E-10 8.32E-14 3.42E-12 0.OOE+00 7.78E-14 4.70E-07 1.12E-07 Ba-140 4.88E-06 6.13E-09 3.21E-07 0.OOE+00 2.09E-09 1.59E-04 2.73E-05 Ba-141 1.25E-11 9.41E-15 4.20E-13 0.OOE+00 8.75E-15 2.42E-07 1.45E-17 Ba-142 3.29E-12 3.38E-15 2.07E-13 0.OOE+00 2.86E-15 1.49E-07 1.96E-26 La-140 4.30E-08 2.17E-08 5.73E-09 0.OOE+00 0.OOE+00 1.70E-05 5.73E-05 La-142 8.54E-11 3.88E-11 9.65E-12 0.OOE+00 0.OOE+00 7.91E-07 2.64E-07 Ce-141 2.49E-06 1.69E-06 1.91 E-07 0.OOE+00 7.83E-07 4.52E-05 1.50E-05 Ce-143 2.33E-08 1.72E-08 1.91E-09 0.OOE+00 7.60E-09 9.97E-06 2.83E-05 Ce-144 4.29E-04 1.79E-04 2.30E-05 O.OOE+00 1.06E-04 9.72E-04 1.02E-04 Pr-143 1.17E-06 4.69E-07 5.80E-08 0.OOE+00 2.70E-07 3.51E-05 2.50E-05 Pr-144 3.76E-12 1.56E-12 1.91E-13 0.OOE+00 8.81E-13 1.27E-07 2.69E-18 Nd-147 6.59E-07 7.62E-07 4.56E-08 O.00E+00 4.45E-07 2.76E-05 2.16E-05 W-187 1.06E-09 8.85E-10 3.1OE-10 O.00E+00 O.OOE+00 3.63E-06 1.94E-05 Np-239 2.87E-08 2.82E-09 1.55E-09 0.OOE+00 8.75E-09 4.70E-06 1.49E-05 NOTE: The tritium dose factor for bone is assumed to be equal to the total body dose factor.

Reference:

Regulatory Guide 1.109, Table E-7. Dose Factors for Co-57, Zn-69m, Br-82, Nb-97, Sn-125, Sb-124 and Sb-125 are from NUREG-0172 Aqe Specific Radiation Dose Commitment Factors for a One Year Chronic Intake. November 1977, Table 8.

SQN ODCM Revision 47 Page 136 of 168 Table 7.6 INHALATION DOSE FACTORS (mrem/pCi inhaled) (Page 3 of 8) TEEN bone liver t body thyroid kidney lung gi-lli H-3 1.59E-07 1.59E-07 1.59E-07 1.59E-07 1.59E-07 1.59E-07 1.59E-07 C-14 3.25E-06 6.09E-07 6.09E-07 6.09E-07 6.09E-07 6.09E-07 6.09E-07 Na-24 1.72E-06 1.72E-06 1.72E-06 1.72E-06 1.72E-06 1.72E-06 1.72E-06 P-32 2.36E-04 1.37E-05 8.95E-06 O.OOE+00 O.OOE+00 O.OOE+00 1.16E-05 Cr-51 O.OOE+00 O.OOE+00 1.69E-08 9.37E-09 3.84E-09 2.62E-06 3.75E-07 Mn-54 O.OOE+00 6.39E-06 1.05E-06 O.OOE+00 1.59E-06 2.48E-04 8.35E-06 Mn-56 O.OOE+00 2.12E-10 3.15E-11 O.OOE+00 2.24E-10 1.90E-06 7.18E-06 Fe-55 4.18E-06 2.98E-06 6.93E-07 O.OOE+00 O.OOE+00 1.55E-05 7.99E-07 Fe-59 1.99E-06 4.62E-06 1.79E-06 O.OOE+00 O.OOE+00 1.91 E-04 2.23E-05 Co-57 O.OOE+00 1.18E-07 1.15E-07 O.OOE+00 O.OOE+00 7.33E-05 3.93E-06 Co-58 O.OOE+00 2.59E-07 3.47E-07 O.OOE+00 O.OOE+00 1.68E-04 1.19E-05 Co-60 O.OOE+00 1.89E-06 2.48E-06 O.OOE+00 O.OOE+00 1.09E-03 3.24E-05 Ni-63 7.25E-05 5.43E-06 2.47E-06 O.OOE+00 O.OOE+00 3.84E-05 1.77E-06 Ni-65 2.73E-10 3.66E-11 1.59E-11 O.OOE+00 O.OOE+00 1.17E-06 4.59E-06 Cu-64 O.OOE+00 2.54E-10 1.06E-10 O.OOE+00 8.01E-10 1.39E-06 7.68E-06 Zn-65 4.82E-06 1.67E-05 7.80E-06 O.OOE+00 1.08E-05 1.55E-04 5.83E-06 Zn-69 6.04E-12 1.15E-11 8.07E-13 O.OOE+00 7.53E-12 1.98E-07 3.56E-08 Zn-69m 1.44E-09 3.39E-09 3.11E-10 O.OOE+00 2.06E-09 3.92E-06 2.14E-05 Br-82 O.OOE+00 O.OOE+00 2.28E-06 O.OOE+00 0.00E+00 O.OOE+00 O.OOE+00 Br-83 O.OOE+00 O.OOE+00 4.30E-08 O.OOE+00 O.OOE+00 O.OOE+00 O.OOE+00 Br-84 O.OOE+00 O.OOE+00 5.41 E-08 O.OOE+00 O.OOE+00 O.OOE+00 O.OOE+00 Br-85 0.OOE+00 O.OOE+00 2.29E-09 O.OOE+00 O.OOE+00 O.OOE+00 O.OOE+00 Rb-86 Q.OOE+00 2.38E-05 1.05E-05 O.OOE+00 O.OOE+00 O.OOE+00 2.21 E-06 Rb-88 O.OOE+00 6.82E-08 3.40E-08 O.OOE+00 O.OOE+00 O.OOE+00 3.65E-15 Rb-89 O.OOE+00 4.40E-08 2.91 E-08 O.OOE+00 O.OOE+00 O.OOE+00 4.22E-17 Sr-89 5.43E-05 O.OOE+00 1.56E-06 O.OOE+00 O.OOE+00 3.02E-04 4.64E-05 Sr-90 1.35E-02 O.OOE+00 8.35E-04 O.OOE+00 O.QOE+00 2.06E-03 9.56E-05 Sr-91 1.10E-08 O.OOE+00 4.39E-10 O.OOE+00 O.QOE+00 7.59E-06 3.24E-05 Sr-92 1.19E-09 O.OOE+00 5.08E-11 O.OOE+00 O.0OE+00 3.43E-06 1.49E-05 Y-90 3.73E-07 O.OOE+00 1.OOE-08 O.OOE+00 O.QOE+00 3.66E-05 6.99E-05 Y-91 m 4.63E-11 O.OOE+00 1.77E-12 O.OOE+00 O.OOE+00 4.OOE-07 3.77E-09 Y-91 8.26E-05 O.OOE+00 2.21E-06 O.OOE+00 O.0OE+00 3.67E-04 5.11E-05 Y-92 1.84E-09 O.OOE+00 5.36E-11 O.OOE+00 O.OOE+00 3.35E-06 2.06E-05 Y-93 1.69E-08 O.OOE+00 4.65E-10 O.OOE+00 O.OOE+00 1.04E-05 7.24E-05 Zr-95 1.82E-05 5.73E-06 3.94E-06 O.OOE+00 8.42E-06 3.36E-04 1.86E-05 Zr-97 1.72E-08 3.40E-09 1.57E-09 O.OOE+00 5.15E-09 1.62E-05 7.88E-05 Nb-95 2.32E-06 1.29E-06 7.08E-07 O.OOE+00 1.25E-06 9.39E-05 1.21 E-05 Nb-97 3.92E-11 9.72E-12 3.55E-12 O.OE+00 1.14E-11 4.91E-07 2.71E-07 Mo-99 O.QOE+00 2.11E-08 4.03E-09 O.OOE+00 5.14E-08 1.92E-05 3.36E-05 Tc-99m 1.73E-13 4.83E-13 6.24E-12 O.OOE+00 7.20E-12 1.44E-07 7.66E-07 Tc-101 7.40E-15 1.05E-14 1.03E-13 O.OOE+00 1.90E-13 8.34E-08 1.09E-16 Ru-103 2.63E-07 O.OOE+00 7.70E-07 O.OOE+00 9.29E-07 9.79E-05 1.36E-05 Ru-105 1.40E-10 O.OOE+00 5.42E-11 O.OOE+00 1.76E-10 2.27E-06 1.13E-05 Ru-106 1.23E-05 O.OOE+00 1.55E-06 O.OOE+00 2.38E-05 2.01 E-03 1.20E-04 Ag-110m 1.73E-06 1.64E-06 9.99E-07 O.OOE+00 3.13E-06 8.44E-04 3.41E-05

SQN ODCM Revision 47 Page 137 of 168 Table 7.6 INHALATION DOSE FACTORS (mrem/pCi inhaled) (Page 4 of 8) TEEN bone liver t body thyroid kidney lung gi-lli Sb-124 5.38E-06 9.92E-08 2.1OE-06 1.22E-08 O.OOE+00 4.81E-04 4.98E-05 Sb-125 9.23E-06 1.01E-07 2.15E-06 8.80E-09 0.OOE+00 3.42E-04 1.24E-05 Sn-125 1.66E-06 4.42E-08 9.99E-08 3.45E-08 O.OOE+00 1.26E-04 7.29E-05 Te-125m 6.1OE-07 2.80E-07 8.34E-08 1.75E-07 0.OOE+00 6.70E-05 9.38E-06 Te-127m 2.25E-06 1.02E-06 2.73E-07 5.48E-07 8.17E-06 2.07E-04 1.99E-05 Te-127 2.51 E-10 1.14E-10 5.52E-11 1.77E-10 9.1OE-10 1.40E-06 1.01E-05 Te-129m 1.74E-06 8.23E-07 2.81 E-07 5.72E-07 6.49E-06 2.47E-04 5.06E-05 Te-129 8.87E-12 4.22E-12 2.20E-12 6.48E-12 3.32E-11 4.12E-07 2.02E-07 Te-131m 1.23E-08 7.51E-09 5.03E-09 9.06E-09 5.49E-08 2.97E-05 7.76E-05 Te-131 1.97E-12 1.04E-12 6.30E-13 1.55E-12 7.72E-12 2.92E-07 1.89E-09 Te-132 4.50E-08 3.63E-08 2.74E-08 3.07E-08 2.44E-07 5.61E-05 5.79E-05 1-130 7.80E-07 2.24E-06 8.96E-07 1.86E-04 3.44E-06 0.OOE+00 1.14E-06 1-131 4.43E-06 6.14E-06 3.30E-06 1.83E-03 1.05E-05 0.OOE+00 8.11E-07 1-132 1.99E-07 5.47E-07 1.97E-07 1.89E-05 8.65E-07 0.OOE+00 1.59E-07 1-133 1.52E-06 2.56E-06 7.78E-07 3.65E-04 4.49E-06 0.OOE+00 1.29E-06 1-134 1.11E-07 2.90E-07 1.05E-07 4.94E-06 4.58E-07 0.OOE+00 2.55E-09 1-135 4.62E-07 1.18E-06 4.36E-07 7.76E-05 1.86E-06 0.OOE+00 8.69E-07 Cs-134 6.28E-05 1.41E-04 6.86E-05 0.OOE+00 4.69E-05 1.83E-05 1.22E-06 Cs-136 6.44E-06 2.42E-05 1.71E-05 0.OOE+00 1.38E-05 2.22E-06 1.36E-06 Cs-137 8.38E-05 1.06E-04 3.89E-05 0.OOE+00 3.80E-05 1.51E-05 1.06E-06 Cs-138 5.82E-08 1.07E-07 5.58E-08 0.OOE+00 8.28E-08 9.84E-09 3.38E-11 Ba-139 1.67E-10 1.18E-13 4.87E-12 0.OOE+00 1.11E-13 8.08E-07 8.06E-07 Ba-140 6.84E-06 8.38E-09 4.40E-07 0.OOE+00 2.85E-09 2.54E-04 2.86E-05 Ba-141 1.78E-11 1.32E-14 5.93E-13 0.OOE+00 1.23E-14 4.11E-07 9.33E-14 Ba-142 4.62E-12 4.63E-15 2.84E-13 0.OOE+00 3.92E-15 2.39E-07 5.99E-20 La-140 5.99E-08 2.95E-08 7.82E-09 0.OOE+00 0.OOE+00 2.68E-05 6.09E-05 La-142 1.20E-10 5.31 E-11 1.32E-11 0.OOE+00 0.OOE+00 1.27E-06 1.50E-06 Ce-141 3.55E-06 2.37E-06 2.71E-07 0.OOE+00 1.11E-06 7.67E-05 1.58E-05 Ce-143 3.32E-08 2.42E-08 2.70E-09 0.OOE+00 1.08E-08 1.63E-05 3.19E-05 Ce-144 6.11E-04 2.53E-04 3.28E-05 0.OOE+00 1.51E-04 1.67E-03 1.08E-04 Pr-143 1.67E-06 6.64E-07 8.28E-08 O.OOE+00 3.86E-07 6.04E-05 2.67E-05 Pr-144 5.37E-12 2.20E-12 2.72E-13 0.OOE+00 1.26E-12 2.19E-07 2.94E-14 Nd-147 9.83E-07 1.07E-06 6.41 E-08 0.OOE+00 6.28E-07 4.65E-05 2.28E-05 W-187 1.50E-09 1.22E-09 4.29E-10 0.OOE+00 0.OOE+00 5.92E-06 2.21E-05 Np-239 4.23E-08 3.99E-09 2.21E-09 0.OOE+00 1.25E-08 8.11E-06 1.65E-05 NOTE: The tritium dose factor for bone is assumed to be equal to the total body dose factor.

Reference:

Regulatory Guide 1.109, Table E-8. Dose Factors for Co-57, Zn-69m, Br-82, Nb-97, Sn-125, Sb-124 and Sb-125 are from NUREG-0172 Aqe Specific Radiation Dose Commitment Factors for a One Year Chronic Intake, November 1977, Table 8.

SQN ODCM Revision 47 Page 138 of 168 Table 7.6 INHALATION DOSE FACTORS (mrem/pCi inhaled) (Page 5 of 8) CHILD bone liver t body thyroid kidney lung gi-lli H-3 3.04E-07 3.04E-07 3.04E-07 3.04E-07 3.04E-07 3.04E-07 3.04E-07 C-14 9.70E-06 1.82E-06 1.82E-06 1.82E-06 1.82E-06 1.82E-06 1.82E-06 Na-24 4.35E-06 4.35E-06 4.35E-06 4.35E-06 4.35E-06 4.35E-06 4.35E-06 P-32 7.04E-04 3.09E-05 2.67E-05 O.OOE+00 O.OOE+00 O.00E+OO 1.14E-05 Cr-51 O.OOE+00 O.00E+OO 4.17E-08 2.31E-08 6.57E-09 4.59E-06 2.93E-07 Mn-54 0.00E+00 1.16E-05 2.57E-06 O.OOE+00 2.71E-06 4.26E-04 6.19E-06 Mn-56 O.OOE+00 4.48E-10 8.43E-11 O.OOE+00 4.52E-10 3.55E-06 3.33E-05 Fe-55 1.28E-05 6.80E-06 2.1OE-06 O.OOE+00 O.OOE+00 3.OOE-05 7.75E-07 Fe-59 5.59E-06 9.04E-06 4.51 E-06 O.OOE+00 O.OOE+00 3.43E-04 1.91 E-05 Co-57 O.OOE+00 2.44E-07 2.88E-07 0.O0E+OO O.OOE+00 1.37E-04 3.58E-06 Co-58 0.0OE+OO 4.79E-07 8.55E-07 O.OOE+00 O.OOE+00 2.99E-04 9.29E-06 Co-60 O.OOE+00 3.55E-06 6.12E-06 O.OOE+00 O.O0E+OO 1.91E-03 2.60E-05 Ni-63 2.22E-04 1.25E-05 7.56E-06 O.OOE+00 O.OOE+00 7.43E-05 1.71 E-06 Ni-65 8.08E-10 7.99E-11 4.44E-11 O.OOE+00 O.OOE+00 2.21E-06 2.27E-05 Cu-64 O.OOE+00 5.39E-10 2.90E-10 O.OOE+00 1.63E-09 2.59E-06 9.92E-06 Zn-65 1.15E-05 3.06E-05 1.90E-05 O.OOE+00 1.93E-05 2.69E-04 4.41E-06 Zn-69 1.81E-11 2.61E-11 2.41E-12 O.0OE+OO 1.58E-11 3.84E-07 2.75E-06 Zn-69m 4.26E-09 7.28E-09 8.59E-10 O.OOE+00 4.22E-09 7.36E-06 2.71E-05 Br-82 O.OOE+00 O.OOE+00 5.66E-06 O.OOE+00 O.0OE+OO O.OOE+00 O.OOE+00 Br-83 O.OOE+00 O.OOE+00 1.28E-07 O.OOE+00 O.OOE+00 O.OOE+00 O.OOE+00 Br-84 O.OOE+00 O.OOE+00 1.48E-07 O.00E+OO O.OOE+00 O.OOE+00 O.OOE+00 Br-85 O.0OE+OO O.OOE+00 6.84E-09 O.0OE+OO O.OOE+00 O.OOE+00 O.OOE+00 Rb-86 0.0OE+OO 5.36E-05 3.09E-05 O.OOE+00 O.OOE+00 O.OOE+00 2.16E-06 Rb-88 O.OOE+00 1.52E-07 9.90E-08 O.OOE+00 O.OOE+00 O.OOE+00 4.66E-09 Rb-89 O.OOE+00 9.33E-08 7.83E-08 O.OOE+00 O.0OE+00 O.OOE+00 5.11E-10 Sr-89 1.62E-04 O.0OE+OO 4.66E-06 O.OOE+00 O.OOE+00 5.83E-04 4.52E-05 Sr-90 2.73E-02 O.OOE+00 1.74E-03 O.OOE+00 O.OOE+00 3.99E-03 9.28E-05 Sr-91 3.28E-08 O.OOE+00 1.24E-09 O.OOE+00 O.OOE+00 1.44E-05 4.70E-05 Sr-92 3.54E-09 O.OOE+00 1.42E-10 0.0OE+OO O.OOE+00 6.49E-06 6.55E-05 Y-90 1.11E-06 O.00E+OO 2.99E-08 O.0OE+OO O.OOE+00 7.07E-05 7.24E-05 Y-91m 1.37E-10 O.00E+OO 4.98E-12 O.OOE+00 O.OOE+00 7.60E-07 4.64E-07 Y-91 2.47E-04 O.OOE+00 6.59E-06 O.0OE+OO O.OOE+00 7.1OE-04 4.97E-05 Y-92 5.50E-09 O.OOE+00 1.57E-10 O.OOE+00 O.OOE+00 6.46E-06 6.46E-05 Y-93 5.04E-08 O.OOE+00 1.38E-09 O.O0E+OO O.OOE+00 2.01 E-05 1.05E-04 Zr-95 5.13E-05 1.13E-05 1.OOE-05 O.OOE+00 1.61E-05 6.03E-04 1.65E-05 Zr-97 5.07E-08 7.34E-09 4.32E-09 O.OOE+00 1.05E-08 3.06E-05 9.49E-05 Nb-95 6.35E-06 2.48E-06 1.77E-06 O.OOE+00 2.33E-06 1.66E-04 1.OOE-05 Nb-97 1.16E-10 2.08E-11 9.74E-12 O.OOE+00 2.31E-11 9.23E-07 7.52E-06 Mo-99 O.OOE+00 4.66E-08 1.15E-08 O.OOE+00 1.06E-07 3.66E-05 3.42E-05 Tc-99m 4.81E-13 9.41E-13 1.56E-11 O.OOE+00 1.37E-11 2.57E-07 1.30E-06 Tc-101 2.19E-14 2.30E-14 2.91E-13 0.OOE+OO 3.92E-13 1.58E-07 4.41E-09 Ru-103 7.55E-07 O.OOE+00 2.90E-07 O.OOE+00 1.90E-06 1.79E-04 1.21E-05 Ru-105 4.13E-10 O.00E+OO 1.50E-10 O.OOE+00 3.63E-10 4.30E-06 2.69E-05 Ru-106 3.68E-05 O.00E+OO 4.57E-06 O.OOE+00 4.97E-05 3.87E-03 1.16E-04 Ag-11 Om 4.56E-06 3.08E-06 2.47E-06 O.OOE+00 5.74E-06 1.48E-03 2.71 E-05

SQN ODCM Revision 47 Page 139 of 168 Table 7.6 INHALATION DOSE FACTORS (mrem/pCi inhaled) (Page 6 of 8) CHILD bone liver t body thyroid kidney lung gi-lli Sb-124 1.55E-05 2.OOE-07 5.41 E-06 3.41 E-08 O.OOE+00 8.76E-04 4.43E-05 Sb-125 2.66E-05 2.05E-07 5.59E-06 2.46E-08 0.OOE+00 6.27E-04 1.09E-05 Sn-125 4.95E-06 9.94E-08 2.95E-07 1.03E-07 0.OOE+00 2.43E-04 7.17E-05 Te-125m 1.82E-06 6.29E-07 2.47E-07 5.20E-07 0.OOE+00 1.29E-04 9.13E-06 Te-127m 6.72E-06 2.31E-06 8.16E-07 1.64E-06 1.72E-05 4.OOE-04 1.93E-05 Te-127 7.49E-10 2.57E-10 1.65E-10 5.30E-10 1.91 E-09 2.71 E-06 1.52E-05 Te-129m 5.19E-06 1.85E-06 8.22E-07 1.71E-06 1.36E-05 4.76E-04 4.91E-05 Te-129 2.64E-11 9.45E-12 6.44E-12 1.93E-11 6.94E-11 7.93E-07 6.89E-06 Te-131m 3.63E-08 1.60E-08 1.37E-08 2.64E-08 1.08E-07 5.56E-05 8.32E-05 Te-131 5.87E-12 2.28E-12 1.78E-12 4.59E-12 1.59E-11 5.55E-07 3.60E-07 Te-132 1.30E-07 7.36E-08 7.12E-08 8.58E-08 4.79E-07 1.02E-04 3.72E-05 1-130 2.21E-06 4.43E-06 2.28E-06 4.99E-04 6.61E-06 O.OOE+00 1.38E-06 1-131 1.30E-05 1.30E-05 7.37E-06 4.39E-03 2.13E-05 O.OOE+00 7.68E-07 1-132 5.72E-07 1.10E-06 5.07E-07 5.23E-05 1.69E-06 O.OOE+00 8.65E-07 1-133 4.48E-06 5.49E-06 2.08E-06 1.04E-03 9.13E-06 O.OOE+00 1.48E-06 1-134 3.17E-07 5.84E-07 2.69E-07 1.37E-05 8.92E-07 O.OOE+00 2.58E-07 1-135 1.33E-06 2.36E-06 1.12E-06 2.14E-04 3.62E-06 O.OOE+00 1.20E-06 Cs-134 1.76E-04 2.74E-04 6.07E-05 0.OOE+00 8.93E-05 3.27E-05 1.04E-06 Cs-136 1.76E-05 4.62E-05 3.14E-05 0.OOE+00 2.58E-05 3.93E-06 1.13E-06 Cs-1 37 2.45E-04 2.23E-04 3.47E-05 O.OOE+00 7.63E-05 2.81 E-05 9.78E-07 Cs-138 1.71 E-07 2.27E-07 1.50E-07 0.OOE+00 1.68E-07 1.84E-08 7.29E-08 Ba-139 4.98E-10 2.66E-13 1.45E-11 O.OOE+00 2.33E-13 1.56E-06 1.56E-05 Ba-140 2.OOE-05 1.75E-08 1.17E-06 O.OOE+00 5.71E-09 4.71E-04 2.75E-05 Ba-141 5.29E-11 2.95E-14 1.72E-12 0.OOE+00 2.56E-14 7.89E-07 7.44E-08 Ba-142 1.35E-11 9.73E-15 7.54E-13 0.OOE+00 7.87E-15 4.44E-07 7.41E-10 La-140 1.74E-07 6.08E-08 2.04E-08 0.OOE+00 O.OOE+00 4.94E-05 6.1OE-05 La-142 3.50E-10 1.11E-10 3.49E-11 0.OOE+00 0.OOE+00 2.35E-06 2.05E-05 Ce-141 1.06E-05 5.28E-06 7.83E-07 0.OOE+00 2.31 E-06 1.47E-04 1.53E-05 Ce-143 9.89E-08 5.37E-08 7.77E-09 0.OOE+00 2.26E-08 3.12E-05 3.44E-05 Ce-144 1.83E-03 5.72E-04 9.77E-05 0.OOE+00 3.17E-04 3.23E-03 1.05E-04 Pr-143 4.99E-06 1.50E-06 2.47E-07 0.OOE+00 8.11E-07 1.17E-04 2.63E-05 Pr-144 1.61E-11 4.99E-12 8.1OE-13 0.OOE+00 2.64E-12 4.23E-07 5.32E-08 Nd-147 2.92E-06 2.36E-06 1.84E-07 O.OOE+00 1.30E-06 8.87E-05 2.22E-05 W-187 4.41E-09 2.61E-09 1.17E-09 0.OOE+00 0.O0E+00 1.11E-05 2.46E-05 Np-239 1.26E-07 9.04E-09 6.35E-09 O.OOE+00 2.63E-08 1.57E-05 1.73E-05 NOTE: The tritium dose factor for bone is assumed to be equal to the total body dose factor.

Reference:

Regulatory Guide 1.109, Table E-9. Dose Factors for Co-57, Zn-69m, Br-82, Nb-97, Sn-125, Sb-124 and Sb-125 are from NUREG-0172 Age Specific Radiation Dose Commitment Factors for a One Year Chronic Intake, November 1977, Table 8.

SQN ODCM Revision 47 Page 140 of 168 Table 7.6 INHALATION DOSE FACTORS (mrem/pCi inhaled) (Page 7 of 8) INFANT bone liver t body thyroid kidney lung gi-ill H-3 4.62E-07 4.62E-07 4.62E-07 4.62E-07 4.62E-07 4.62E-07 4.62E-07 C-14 1.89E-05 3.79E-06 3.79E-06 3.79E-06 3.79E-06 3.79E-06 3.79E-06 Na-24 7.54E-06 7.54E-06 7.54E-06 7.54E-06 7.54E-06 7.54E-06 7.54E-06 P-32 1.45E-03 8.03E+05 5.53E-05 0.OOE+00 O.OOE+00 O.OOE+00 1.15E-05 Cr-51 0.OOE+00 O.OOE+00 6.39E-08 4.11E-08 9.45E-09 9.17E-06 2.55E-07 Mn-54 0.OOE+00 1.81 E-05 3.56E-06 O.OOE+00 3.56E-06 7.14E-04 5.04E-06 Mn-56 0.OOE+00 1.10E-09 1.58E-10 0.OOE+00 7.86E-10 8.95E-06 5.12E-05 Fe-55 1.41 E-05 8.39E-06 2.38E-06 O.OOE+00 O.OOE+00 6.21 E-05 7.82E-07 Fe-59 9.69E-06 1.68E-05 6.77E-06 O.OOE+00 O.OOE+00 7.25E-04 1.77E-05 Co-57 0.OOE+00 4.65E-07 4.58E-07 0.OOE+00 0.OOE+00 2.71 E-04 3.47E-06 Co-58 0.OOE+00 8.71 E-07 1.30E-06 O.OOE+00 0.OOE+00 5.55E-04 7.95E-06 Co-60 0.OOE+00 5.73E-06 8.41 E-06 0.OOE+00 0.OOE+00 3.22E-03 2.28E-05 Ni-63 2.42E-04 1.46E-05 8.29E-06 0.OOE+00 0.OOE+00 1.49E-04 1.73E-06 Ni-65 1.71E-09 2.03E-10 8.79E-11 0.OOE+00 O.OOE+00 5.80E-06 3.58E-05 Cu-64 0.OOE+00 1.34E-09 5.53E-10 0.OOE+00 2.84E-09 6.64E-06 1.07E-05 Zn-65 1.38E-05 4.47E-05 2.22E-05 0.OOE+00 2.32E-05 4.62E-04 3.67E-05 Zn-69 3.85E-11 6.91E-11 5.13E-12 0.OOE+00 2.87E-11 1.05E-06 9.44E-06 Zn-69m 8.98E-09 1.84E-08 1.67E-09 0.OOE+00 7.45E-09 1.91E-05 2.92E-05 Br-82 0.OOE+00 0.OOE+00 9.49E-06 O.OOE+00 O.OOE+00 O.OOE+00 0.OOE+00 Br-83 0.OOE+00 0.OOE+00 2.72E-07 O.OOE+00 0.OOE+00 0.OOE+00 0.OOE+00 Br-84 0.OOE+00 0.OOE+00 2.86E-07 O.OOE+00 O.OOE+00 0.OOE+00 0.OOE+00 Br-85 0.OOE+00 0.OOE+00 1.46E-08 0.OOE+00 0.OOE+00 O.OOE+00 O.OOE+00 Rb-86 0.OOE+00 1.36E-04 6.30E-05 0.OOE+00 0.OOE+00 O.OOE+00 2.17E-06 Rb-88 0.OOE+00 3.98E-07 2.05E-07 0.OOE+00 O.OOE+00 0.OOE+00 2.42E-07 Rb-89 0.OOE+00 2.29E-07 1.47E-07 0.OOE+00 0.OOE+00 0.OOE+00 4.87E-08 Sr-89 2.84E-04 0.OOE+00 8.15E-06 0.OOE+00 0.00E+00 1.45E-03 4.57E-05 Sr-90 2.92E-02 0.OOE+00 1.85E-03 0.OOE+00 0.OOE+00 8.03E-03 9.36E-05 Sr-91 6.83E-08 0.OOE+00 2.47E-09 0.OOE+00 0.OOE+00 3.76E-05 5.24E-05 Sr-92 7.50E-09 0.OOE+00 2.79E-10 0.OOE+00 O.0OE+00 1.70E-05 1.00E-04 Y-90 2.35E-06 O.OOE+00 6.30E-08 0.OOE+00 O.OOE+00 1.92E-04 7.43E-05 Y-91m 2.91E-10 0.OOE+00 9.90E-12 0.OOE+00 0.OOE+00 1.99E-06 1.68E-06 Y-91 4.20E-04 0.OOE+00 1.12E-05 0.OOE+00 O.OOE+00 1.75E-03 5.02E-05 Y-92 1.17E-08 O.OOE+00 3.29E-10 0.0OE+00 0.OOE+00 1.75E-05 9.04E-05 Y-93 1.07E-07 O.OOE+00 2.91E-09 O.OOE+00 0.OOE+00 5.46E-05 1.19E-04 Zr-95 8.24E-05 1.99E-05 1.45E-05 0.OOE+00 2.22E-05 1.25E-03 1.55E-05 Zr-97 1.07E-07 1.83E-08 8.36E-09 0.OOE+00 1.85E-08 7.88E-05 1.OOE-04 Nb-95 1.12E-05 4.59E-06 2.70E-06 0.00E+00 3.37E-06 3.42E-04 9.05E-06 Nb-97 2.44E-10 5.21 E-11 1.88E-11 0.OOE+00 4.07E-11 2.37E-06 1.92E-05 Mo-99 0.OOE+00 1.18E-07 2.31E-08 O.OOE+00 1.89E-07 9.63E-05 3.48E-05 Tc-99m 9.98E-13 2.06E-12 2.66E-11 0.OOE+00 2.22E-11 5.79E-07 1.45E-06 Tc-101 4.65E-14 5.88E-14 5.80E-13 O.OOE+00 6.99E-13 4.17E-07 6.03E-07 Ru-103 1.44E-06 O.OOE+00 4.85E-07 0.OOE+00 3.03E-06 3.94E-04 1.15E-05 Ru-105 8.74E-10 0.OOE+00 2.93E-10 O.OOE+00 6.42E-10 1.12E-05 3.46E-05 Ru-106 6.20E-05 0.OOE+00 7.77E-06 0.OOE+00 7.61E-05 8.26E-03 1.17E-04 Ag-110m 7.13E-06 5.16E-06 3.57E-06 O.OOE+00 7.80E-06 2.62E-03 2.36E-05

SQN ODCM Revision 47 Page 141 of 168 Table 7.6 INHALATION DOSE FACTORS (mrem/pCi inhaled) (Page 8 of 8) INFANT bone liver t body thyroid kidney lung gi-lli Sb-124 2.71E-05 3.97E-07 8.56E-06 7.18E-08 0.OOE+00 1.89E-03 4.22E-05 Sb-125 3.69E-05 3.41E-07 7.78E-06 4.45E-08 O.OOE+00 1.17E-03 1.05E-05 Sn-125 1.01 E-05 2.51 E-07 6.OOE-07 2.47E-07 O.OOE+00 6.43E-04 7.26E-05 Te-125m 3.40E-06 1.42E-06 4.70E-07 1.16E-06 O.OOE+00 3.19E-04 9.22E-06 Te-127m 1.19E-05 4.93E-06 1.48E-06 3.48E-06 2.68E-05 9.37E-04 1.95E-05 Te-127 1.59E-09 6.81E-10 3.49E-10 1.32E-09 3.47E-09 7.39E-06 1.74E-05 Te-129m 1.01E-05 4.35E-06 1.59E-06 3.91E-06 2.27E-05 1.20E-03 4.93E-05 Te-129 5.63E-11 2.48E-11 1.34E-11 4.82E-11 1.25E-10 2.14E-06 1.88E-05 Te-131 m 7.62E-08 3.93E-08 2.59E-08 6.38E-08 1.89E-07 1.42E-04 8.51 E-05 Te-131 1.24E-11 5.87E-12 3.57E-12 1.13E-11 2.85E-11 1.47E-06 5.87E-06 Te-132 2.66E-07 1.69E-07 1.26E-07 1.99E-07 7.39E-07 2.43E-04 3.15E-05 1-130 4.54E-06 9.91E-06 3.98E-06 1.14E-03 1.09E-05 O.OOE+00 1.42E-06 1-131 2.71E-05 3.17E-05 1.40E-05 1.06E-02 3.70E-05 O.OOE+00 7.56E-07 1-132 1.21E-06 2.53E-06 8.99E-07 1.21E-04 2.82E-06 O.OOE+00 1.36E-06 1-133 9.46E-06 1.37E-05 4.OOE-06 2.54E-03 1.60E-05 O.OOE+00 1.54E-06 1-134 6.58E-07 1.34E-06 4.75E-07 3.18E-05 1.49E-06 O.OOE+00 9.21E-07 1-135 2.76E-06 5.43E-06 1.98E-06 4.97E-04 6.05E-06 O.OOE+00 1.31E-06 Cs-1 34 2.83E-04 5.02E-04 5.32E-05 O.OOE+00 1.36E-04 5.69E-05 9.53E-07 Cs-136 3.45E-05 9.61E-05 3.78E-05 0.OOE+00 4.03E-05 8.40E-06 1.02E-06 Cs-137 3.92E-04 4.37E-04 3.25E-05 O.OOE+00 1.23E-04 5.09E-05 9.53E-07 Cs-138 3.61E-07 5.58E-07 2.84E-07 O.OOE+00 2.93E-07 4.67E-08 6.26E-07 Ba-139 1.06E-09 7.03E-13 3.07E-11 O.OOE+00 4.23E-13 4.25E-06 3.64E-05 Ba-140 4.OOE-05 4.OOE-08 2.07E-06 0.OOE+00 9.59E-09 1.14E-03 2.74E-05 Ba-141 1.12E-10 7.70E-14 3.55E-12 O.OOE+00 4.64E-14 2.12E-06 3.39E-06 Ba-142 2.84E-11 2.36E-14 1.40E-12 O.OOE+00 1.36E-14 1.11E-06 4.95E-07 La-140 3.61E-07 1.43E-07 3.68E-08 0.OOE+00 0.00E+00 1.20E-04 6.06E-05 La-142 7.36E-10 2.69E-10 6.46E-11 O.OOE+00 0.OOE+00 5.87E-06 4.25E-05 Ce-141 1.98E-05 1.19E-05 1.42E-06 O.OOE+00 3.75E-06 3.69E-04 1.54E-05 Ce-143 2.09E-07 1.38E-07 1.58E-08 O.OOE+00 4.03E-08 8.30E-05 3.55E-05 Ce-144 2.28E-03 8.65E-04 1.26E-04 0.OOE+00 3.84E-04 7.03E-03 1.06E-04 Pr-143 1.OOE-05 3.74E-06 4.99E-07 O.OOE+00 1.41 E-06 3.09E-04 2.66E-05 Pr-144 3.42E-11 1.32E-11 1.72E-12 0.OOE+00 4.80E-12 1.15E-06 3.06E-06 Nd-147 5.67E-06 5.81E-06 3.57E-07 0.OOE+00 2.25E-06 2.30E-04 2.23E-05 W-187 9.26E-09 6.44E-09 2.23E-09 0.OOE+00 O.OOE+00 2.83E-05 2.54E-05 Np-239 2.65E-07 2.37E-08 1.34E-08 0.OOE+00 4.73E-08 4.25E-05 1.78E-05 NOTE: The tritium dose factor for bone is assumed to be equal to the total body dose factor.

Reference:

Regulatory Guide 1.109, Table E-10. Dose Factors for Co-57, Zn-69m, Br-82, Nb-97, Sn-125, Sb-124 and Sb-125 are from NUREG-0172 AQe Specific Radiation Dose Commitment Factors for a One Year Chronic Intake. November 1977, Table 8.

SQN ODCM Revision 47 Page 142 of 168 Figure 7.1 GASEOUS EFFLUENT RELEASE POINTS Shield Building Auxiliary Vent Condenser Building Service Vacuum Vent 1,2-RE-90-400 Building Exhaust Vent O-RE-90-14 1,2-RM-90-13

                                            .V A TU N                        S
                               'I        -. i               C          Cnanmn M         ~(D                Il 0Containment GeniVent BUIDN                      B-1D-RE-90-119 Annuls Fns    _

Vacurn Containment_ TanMaceain ChREmistry ins600cu-VTan Titration ~60Va cuu Fantoe iraoom < 2 e unt)Lontwnent SERVICE TURBINE AUXILIARY SHIELD BUILDING BUILDING BUILDING BUILDING

SQN ODCM Revision 47 Page 143 of 168 Figure 7.2 AUXILIARY AND SHIELD BUILDING VENTS (DETAIL) (All Vents Are Considered Ground Level) Shield Building Vent

1  ::  : :  ::  : .  :  :  : :

SQN ODCM Revision 47 Page 144 of 168 Figure 7.3 GASEOUS RADWASTE TREATMENT SYSTEM (All Vents Are Considered Ground Level) lcvcs VCT unit 2 Uf: tl n f  : ffi Cf f-' f f ff f f jzvcs

ST fffffff -

RCOT1 f-:iii0000-  : 0 0 00 fl R11T UnitU / N, 0 f 1 ; -- ;0000000dS .  :  :  : : i

SQN ODCM Revision 47 Page 145 of 168 Figure 7.4 PLUME DEPLETION EFFECT FOR GROUND LEVEL RELEASES (All Stability Classes)

i 0 .7f f:i-00:f:0ft
°-0 , 11 110 i '3 011 1111
0. L3i X 1 1 1:1-0001:0 t0001011011 00 t0f0 0~~~~~~~~~~~~~~~~~~~~ 0 '1 1
                                     - ............           1.101000001ff1:00100             11         000   0    i 01f
                       ,X~~~~~~~~~~            'jT 11>d     I                                1 dX5' i00:00X i01               lliilillili i10001011100000800-000          iili     0   Xlifll     I000.00    :0 100fli  fil"li   -      TX'- 10f
                                          <l00       OtSl-%.e X00LO  000   )  100E7.;U       S       -       00   00i0 0 i C50-    1 0 ii 0;0

SQN ODCM Revision 47 Page 146 of 168 Figure 7.5 VERTICAL STANDARD DEVIATION OF MATERIAL IN A PLUME lnw

              .I.I..II.II.II-.I I-t   lI    /        F/I              IlllI.                     II I:
                                  <.1l -II                   [:,* 1 1.I1l I ~I. J.- ~: I   I  I- I ~I I!

I'll

  • iI III ,77I liI T 1 II1 I I0 I 1T AV~

P¶1F~ D1~AN~ N LOM I =Rsl V et S .nI2rd ,,,vyi- n bf Mater.21in a St M

                                       ~(.eajers   denote pjtqui0:StabZy             ias

SQN ODCM Revision 47 Page 147 of 168 Figure 7.6 RELATIVE DEPOSITION FOR GROUND LEVEL RELEASES (All Stability Classes) uJ ii;-  ; D:  : :f:f :0: 0i:i  : :i

-w 0 :IIL:1fIIIIt I HIT I) 1I!U KT R=.-,- De,-Oa= izr

SQN ODCM Revision 47 Page 148 of 168 SECTION 8.0 TOTAL DOSE

SQN ODCM Revision 47 Page 149 of 168 SECTION 8.0 TOTAL DOSE 8.1 ANNUAL MAXIMUM INDIVIDUAL DOSES - TOTAL REPORTED DOSE To determine compliance with 40 CFR 190 as required in ODCM Administrative Control 5.2, the annual dose contributions to the maximum individual from SQN radioactive effluents and all other nearby uranium fuel cycle sources will be considered. The annual dose to the maximum individual will be conservatively estimated by first, summing the quarterly total body air submersion dose, the quarterly critical organ dose from gaseous effluents, the quarterly total body dose from liquid effluents, the quarterly critical organ dose from liquid effluents, and the direct radiation monitoring program, and then taking the sum for each quarter and summing over the four quarters. The table below represents the above verbal description and relative values: First Second Third Fourth Dose Quarter Quarter Quarter Quarter Total Body or any Organ (except thyroid) Total body air submersion 9.79E-04 9.OOE-04 1.65E-03 4.27E-04 Critical organ dose (air) 9.48E-03 9.40E-03 3.77E-03 9.37E-03 Total body dose (liquid) 4.8E-03 2.1E-02 3.8E-02 6.5E-03 Maximum organ dose (liquid) 5.8E-03 2.6E-02 5.OE-02 2.OE-02 Direct Radiation Dose 0.OE-00 O.OE-00 O.OE-00 O.OOE-00 Total 2.1 E-02 5.7E-02 9.3E-02 3.6E-02 Cumulative Total Dose (Total body or any other organ) mrem 2.1E-01 Annual Dose Limit (mrem) 2.50E+01 Percent of Limit [1%

SQN ODCM Revision 47 Page 150 of 168 SECTION 9.0 RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM

SQN ODCM Revision 47 Page 151 of 168 SECTION 9.0 RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM 9.1 MONITORING PROGRAM An environmental radiological monitoring program shall be conducted in accordance with ODCM Control 1.3.1. The monitoring program described in Tables 9.1, 9.2, and 9.3, and in Figures 9.1, 9.2 and 9.3 shall be conducted. Results of this program shall be reported in accordance with ODCM Administrative Control 5.1. The atmospheric environmental radiological monitoring program shall consist of monitoring stations from which samples of air particulates and atmospheric radioiodine shall be collected. The terrestrial monitoring program shall consist of the collection of milk, soil, ground water, drinking water, and food crops. In addition, direct gamma radiation levels will be measured in the vicinity of the plant. The reservoir sampling program shall consist of the collection of samples of surface water, sediment, clams, and fish. Deviations are permitted from the required sampling schedule if specimens are unobtainable due to hazardous conditions, sample unavailability, or to malfunction of sampling equipment. If the latter, every effort shall be made to complete corrective action prior to the end of the next sampling period. 9.2 DETECTION CAPABILITIES Analytical techniques shall be such that the detection capabilities listed in Table 2.3-3 are achieved. 9.3 LAND USE CENSUS A land use survey shall be conducted in accordance with Control 1.3.2. The results of the survey shall be reported in the Annual Radiological Environmental Operating Report. 9.4 INTERLABORATORY COMPARISON PROGRAM Analyses shall be performed on radioactive materials supplied as part of an Interlaboratory Comparison Program which has been approved by the NRC. A summary of the results obtained in the intercomparison shall be included in the Annual Radiological Environmental Operating Report (or the EPA program code designation may be provided). If analyses are not performed as required corrective actions taken to prevent a recurrence shall be reported in the Annual Radiological Environmental Operating Report.

SQN ODCM Revision 47 Page 152 of 168 Table 9.1 RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM (Page 1 of 4) Exposure Pathway Sampling and Type and Frequency and/or Sample Sample Locations* Collection Frequency of Analysis AIRBORNE Particulates 4 samples from locations Continuous sampler Analyze for gross beta (in different sectors) at or operation with sample radioactivity > 24 hours near the site boundary collection once per 7 d following filter change. (LM-2,3,4,and 5) (more frequently if Perform gamma required by dust isotopic analysis on 4 samples from loading) each sample if gross communities beta> 10 times yearly approximately 6-10 miles mean of control distance from the plant. sample. (PM-2,3,8,and 9) Composite at least once per 31 d (by 4 samples from control location for gamma locations greater than 10 scan) miles from the plant (RM-1,2,3,and 4) Radioiodine Samples from same Continuous sampler 1-131 at least once per location as air operation with filter 7d particulates collection once per 7 d Soil Samples from same Once per year Gamma scan, Sr-89, locations as air Sr-90 once per year particulates DIRECT RADIATION 2 or more TLD's placed at Once per 92 d Gamma dose at least locations (in different once per 92 d sectors at or near the site boundary) in each of the 16 sectors. I

  • Sample locations are listed in Tables 9.2 and 9.3 and shown on Figures 9.1, 9.2 and 9.3

SQN ODCM Revision 47 Page 153 of 168 Table 9.1 RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM (Page 2 of 4) Exposure Pathway Sampling and Type and Frequency and/or Sample Sample Locations* Collection Frequency of Analysis DIRECT RADIATION (continued) 2 or more TLD's placed at stations located approximately 5 miles from the plant in each of the 16 sectors 2 or more dosimeters in at least 8 additional locations of special interest. WATERBORNE Surface TRM 503.8*** Collected by Gamma scan of each TRM 483.4 automatic sequential composite sample. type sampler** with Composite for H-3 composite samples analysis at least once collected at least per 92 d. once per 31 d. Ground 1 sample adjacent to At least once per 92 d Gross beta and gamma plant (location W-6) scan and H-3 analysis at least once per 92 d. 1 sample from groundwater source up-gradient

  • Sample locations are listed in Tables 9.2 and 9.3 and shown on Figures 9.1, 9.2 and 9.3
** Samples shall be collected by collecting an aliquot at intervals not exceeding 2 hours.
      • Sample used as control for surface water and drinking water.

SQN ODCM Revision 47 Page 154 of 168 Table 9.1 RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM (Page 3 of 4) Exposure Pathway Sampling and Type and Frequency and/or Sample Sample Locations* Collection Frequency of Analysis WATERBORNE (continued) Collected by automatic Gross beta and 1 sample at the first potable Drinking water supply downstream sequential type sampler** gamma scan of from the plant with composite samples each composite (TRM 473.0) collected at least once per sample. 31 d Composite for H-1 sample at the next 2 3, at least once downstream potable surface Grab sample once per 31 per 92 d. water supplies (greater than d. 10 miles downstream) (TRM 469.9 and 465.3) Samples collected by automatic sequential type 1 sample at a control location sampler** with composite upstream from the plant sample collected at least (TRM 503.8)*** once per 31 d. Shoreline TRM 485, TRM 480, TRM At least once per 184 d Gamma scan of Sediment 479 each sample. INGESTION Milk I sample from milk producing At least once per 15 d. Gamma isotopic animals in each of 1-3 areas and 1-131 analysis indicated by the cow census of each sample. where doses are calculated to Sr-89, Sr-90 once be highest. per year. If samples are not available from a milk animal location, doses to that area will be estimated by projecting the doses from concentrations detected in milk from other sectors or samples of vegetation will be taken monthly when milk is not available. At least 1 sample from a control location.

  • Sample locations are listed in Tables 9.2 and 9.3 and shown on Figures 9.1, 9.2 and 9.3
    • Samples shall be collected by collecting an aliquot at intervals not exceeding 2 hours.
      • Sample location is considered a control for drinking water and surface water.

SQN ODCM Revision 47 Page 155 of 168 Table 9.1 RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM (Page 4 of 4) Exposure Pathway Sampling and Type and Frequency and/or Sample Sample Locations* Collection Frequency of Analysis INGESTION Fish 1 sample each from At least once per 184 Gamma scan on edible Chickamauga and Watts d. One sample portion. Bar Reservoirs. representing a commercially important species and one sample representing a recreationally important species. Food 1 sample each of At least once per 365 d Gamma scan on edible Products principle food products at time of harvest. The portion. grown at private gardens types of foods and/or farms in the available for sampling vicinity of the plant. will vary. Following is a list of typical foods which may be available: Cabbage and/or lettuce Corn Green Beans Potatoes Tomatoes Vegetation** Samples from farms At least once per 31 d 1-131 and gamma scan producing milk but not at least once per 31 d providing a milk sample Control Sample from one control dairy farm

  • Sample locations are listed in Tables 9.2 and 9.3 and shown on Figures 9.1, 9.2 and 9.3
    • Vegetation sampling is applicable only for farms that meet the criteria for milk sampling and when implementation of milk sampling is not possible.

SQN ODCM Revision 47 Page 156 of 168 Table 9.2 ENVIRONMENTAL RADIOLOGICAL MONITORING PROGRAM SAMPLING LOCATIONS Map Location Approximate Indicator (I) Samples Numbera Station Sector Distance or Control Collectedb 2 LM-2 N 0.7 AP, CF, S I 3 LM-3 SSW 2.0 AP, CF, S 4 LM-4 NE 1.5 AP, CF, S 5 LM-5 NNE 1.8 AP, CF, S 7 PM-2 SW 3.8 AP, CF, S 8 PM-3 W 5.6 AP, CF, S 9 PM-8 SSW 8.7 AP, CF, S 10 PM-9 WSW 2.6 AP, CF, S 11 RM-1 SW 16.7 C AP, CF, S 12 RM-2 NNE 17.8 C AP, CF, S 13 RM-3 ESE 11.3 C C AP, CF, S 14 RM-4 NW 20.0 C AP, CF, S 15 Farm B NE 43.0 M - C 19 Farm HW NW 1.2 M, W 21 Farm HS E 4.6 M 22 Farm RJ ESE 3.9 M 23 Farm EH ENE 9.5 M 24 Well j'o. 6 NNE 0.15 W 31 TRM 473.0 East Side Utility 10.7 PW ( Formally C. F. Industries) e 32 TRM 469.9 (E. l. DuPont) - 13.8 e PW 33 TRM 465.3 (Chattanooga) - 18.4 PW 34 Deleted (R 40) 35 TRM 503.8 (Dayton) - 20.1 SWPW 37 TRM 485.0 1.3 e C SS 38 TRM 483.4 0.3 I SW e 40 TRM 479.0 4.7 3 SS 44 TRM 480.0 3.7 SS 46 Chickamauga Reservoir F 47 Watts Bar Reservoir C F a b See figures 9.1, 9.2, and 9.3 Sample Codes: AP = Air particulate filter CF = Charcoal filter F = Fish M =Milk PW = Public water R =Rainwater S =Soil SS = Shoreline sediment SW = Surface water W = Well water dA control for well water. e TRM = Tennessee River Mile. f Distance from plant discharge (TRM 483.7) Sample also used as a control for public water and surface water.

SQN ODCM Revision 47 Page 157 of 168 Table 9.3 THERMOLUMINESCENT DOSIMETRY LOCATIONS (Page 1 of 2) Map Approximate (Onsite )a Location Distance or Number Station Sector (Miles) Offsite (Off) 3 SSW-1C SSW 2.0 On 4 NE-1A NE 1.5 On 5 NNE-1 NNE 1.8 On 7 SW-2 SW 3.8 Off 8 W-3 W 5.6 Off 9 SSW-3 SSW 8.7 Off 10 WSW-2A WSW 2.6 Off 11 SW-3 SW 16.7 Off 12 NNE-4 NNE 17.8 Off 13 ESE-3 ESE 11.3 Off 14 NW-3 NW 20.0 Off 49 N-1 N 0.6 On 50 N-2 N 2.1 Off 51 N-3 N 5.2 Off 52 N-4 N 10.0 Off 53 NNE-2 NNE 5.3 Off I 54 NNE-3 NNE 12.1 Off 55 NE-1 NE 2.4 Off 56 NE-2 NE 4.1 Off 57 ENE-1 ENE 0.2 On 58 ENE-2 ENE 5.1 Off 59 E-1 E 1.2 On 60 E-2 E 5.2 Off 61 ESE-A ESE 0.3 On 62 ESE-1 ESE 1.2 On 63 ESE-2 ESE 4.9 Off 64 SE-A SE 0.4 On 65 E-A E 0.3 On 66 SE-1 SE 1.4 On 67 SE-2 SE 1.9 On 68 SE-4 SE 5.2 Off 69 SSE-1 SSE 1.6 On 70 SSE-2 SSE 4.6 Off 71 S-1 S 1.5 On 72 S-2 S 4.7 Off 73 SSW-1 SSW 0.6 On 74 SSW-2 SSW 4.0 Off aTLDs designated onsite are those located two miles or less from the plant. TLDs designated offsite are those located more than two miles from the plant.

SQN ODCM Revision 47 Page 158 of 168 Table 9.3 THERMOLUMINESCENT DOSIMETRY LOCATIONS (Page 2 of 2) Map Approximate Onsite (On)a Location Distance or Number Station Sector (Miles) Offsite (Off) 75 SW-1 SW 0.7 On I 76 WSW-1 WSW 0.9 On 77 WSW-2 WSW 2.5 Off 78 WSW-3 WSW 5.7 Off 79 WSW-4 WSW 7.8 Off 80 WSW-5 WSW 10.1 Off 81 W-1 W 0.6 On I 82 W-2 W 4.3 Off 83 WNW-1 WNW 0.4 On 84 WNW-2 WNW 5.3 Off 85 NW-1 NW 0.4 On 86 NW-2 NW 5.2 Off 87 NNW-1 NNW 0.6 On 88 NNW-2 NNW 1.7 On 89 NNW-3 NNW 5.3 Off 90 SSW-1B SSW 1.5 On aTLDs designated onsite are those located two miles or less from the plant. TLDs designated offsite are those located more than two miles from the plant.

SQN ODCM Revision 47 Page 159 of 168 Figure 9.1 ENVIRONMENTAL MONITORING LOCATIONS WITHIN ONE MILE OF THE PLANT ENE 25!

                                                             * ~p .25 2z5 E:S:C :.

1,21.25 iS I0I .Li

SQN ODCM Revision 47 Page 160 of 168 Figure 9.2 ENVIRONMENTAL MONITORING LOCATIONS FROM ONE TO FIVE MILES FROM THE PLANT 3N 1 00 37 0 aX /rr 628  : fif/8%6:>ii li/3 :i-101.2 75 77: i I : : : : SCALE  : 0  :: : 1 : 2 Z MILES

SQN ODCM Revision 47 Page 161 of 168 Figure 9.3 ENVIRONMENTAL MONITORING LOCATIONS GREATER THAN FIVE MILES FROM THE PLANT

SCALE o0o0 5 WLES

SQN ODCM Revision 47 Page 162 of 168 APPENDIX A - SQN ODCM REVISION PROCESS (Page 1 of 7) This Appendix establishes the minimum requirements for preparation, review, and approval of the Sequoyah Nuclear Plant Offsite Dose Calculation Manual. This Appendix also implements the requirements of ODCM Section 5.3 and SQN TS. 1.0 Reviewer Responsibilities 1.1 Affected Organization Review (AOR) The identification of affected organizations is the responsibility of the Sponsor and applies to all revisions of the ODCM. The affected organizations shall ensure that their reviewers have adequate understanding of the requirements and intent of the ODCM and access to pertinent background information. The AO reviews the draft for impact on the organization and adequate interface - not technical content. 1.2 Independent Qualified Review (IQR) An independent qualified review is the process of independent technical review by Qualified Reviewers of activities potentially affecting nuclear safety. The IQR shall NOT be the person who prepared the ODCM revision. An IQR is performed by an individual designated by responsible department level managers to perform an independent technical review of activities potentially affecting nuclear safety. The IQR must be qualified to perform the 10 CFR 50.59 review. 1.3 Cross Disciplinary Review (CDR) The need for a CDR is determined by the IQR. CDR is a technical review by disciplines other than those responsible for the document preparation. The CDR is responsible for only the technical aspects of the areas specified by the IQR and any portions of the document that support or justify those areas. Persons performing CDR do not have to be IQR qualified. 1.4 Plant Operations Review Committee (PORC) Review The PORC reviews the ODCM. I

SQN ODCM Revision 47 Page 163 of 168 APPENDIX A - SQN ODCM REVISION PROCESS (Page 2 of 7) 1.5 Approval Authority The Plant Manager, or designee will approve all revisions to the ODCM as required by Technical Specifications. 2.0 Processing ODCM Revisions 2.1 Requester (If other than the Sponsor) Identify the need for an ODCM improvement. Prepare a justification for the ODCM revision. Attach a marked-up copy of the existing ODCM. Forward the requested ODCM revision to the sponsoring organization. 2.2 ODCM Sponsor Evaluate requested changes and determine if necessary. If the requested change is not necessary, return the request to the requester with explanation why the change is not needed. Incorporate all changes in a draft revision on Curator. Complete the top portion of Attachment B for each organization. Distribute Attachment B to each Affected Organization and request completion of the review prior to expected PORC review date. Obtain appropriate reviews of the ODCM revision in Curator. 2.3 Reviews 2.3.1 IQR Review the ODCM using all questions on Attachment C as a guideline and forward comments to the Sponsor. Identify discipline or organization to perform CDR, if needed.

SQN ODCM Revision 47 Page 164 of 168 APPENDIX A - SQN ODCM REVISION PROCESS (Page 3 of 7) 2.3.2 Affected Organization Reviewer Review the proposed changes on Curator and provide comments to the ODCM Sponsor. Review the ODCM for impact on assigned organization, identify procedures/documents which require revision to implement the ODCM revision on the Attachment B, and return the Attachment B to the ODCM Sponsor. 2.4 Sponsor Resolve comments and obtain reviewer's concurrence in Curator. Escalate any unresolved comments to appropriate management. Ensure ODCM has been reviewed by sponsor and IQR in accordance with Attachment C. Ensure all Affected Organizations have reviewed the ODCM change and have identified the affected procedures on Attachment B. Ensure all IQR and CDR review requirements have been met. Assign an Effective Date typically 60 calendar days forward UNLESS there is reasonable justification for making it effective earlier, such as plant operating conditions, test schedules, commitment or corrective action deadlines, or implementation of upper-tier requirements, or lack of affected procedures identified on Attachment B. 2.5 PORC Review Changes and document recommendation for approval in Curator. 2.6 Plant Manager Approve the ODCM revision in Curator. 2.7 ODCM Sponsor Record the ODCM approval date and implementation date on each completed Attachment B provided by the affected organizations. Return the Attachment B to each affected organization. 2.8 Affected Organization Revise procedures identified on the Attachment B and assign an effective date which matches that of the ODCM revision. Complete the Attachment B and return to the ODCM Sponsor.

SQN ODCM Revision 47 Page 165 of 168 APPENDIX A - SQN ODCM REVISION PROCESS (Page 4 of 7) 2.9 ODCM Sponsor Ensure all Affected Organizations have completed and returned Attachment B prior to the effective date of the ODCM. Forward the approved ODCM change to Management Services at least three working days before the implementation date. The completed Attachments B, and C are QA records, and are handled in accordance with the Document Control and Records Management Program. Forward a completed copy of each revision to Licensing to be filed and forwarded to the NRC in the Annual Radiological Effluent Release Report. 2.10 Management Services Issue the ODCM and implementing procedures on the effective date of the ODCM revision.

SQN ODCM Revision 47 Page 166 of 168 APPENDIX A - SQN ODCM REVISION PROCESS (Page 5 of 7) Attachment B ODCM Affected Organization Review/lmplementation Proposed ODCM Revision No. Expected PORC Review Date: Expected Effective Date: Affected Organization: [ ] Operations [ ] RADCON Chemistry [] Maintenance [ ] Technical Support [ ] Scheduling [1 Engineering [ Licensing Emergency Preparedness [ ] Other The following procedures/documents will require revision to implement this ODCM change: PROCEDURE/DOCUMENT PROCEDURE/DOCUMENT I ODCM Approval Date: ODCM Effective Date: The required procedure/document revisions to support this ODCM revision have been completed and have an implementation date which matches that given above for the ODCM revision. Affected Organization Date

SQN ODCM Revision 47 Page 167 of 168 APPENDIX A - SQN ODCM REVISION PROCESS (Page 6 of 7) Attachment C ODCM Review Checklist All questions of this checklist are considered by the ODCM preparer and reviewed by the Independent Qualified Reviewer (IQR). Only the revised portion of the ODCM should be evaluated. Changes to Section(s) 1.0-5.0 YES NO N/A

1. Does the revision meet the intent of the guidance provided in NUREG-1301 for radiological effluent and environmental monitoring controls/surveillance requirements?
2. Do definitions in Section 3.0 match those provided in the SQN TS, NUREG-1301, or other NRC guidance?
3. Do Administrative Controls in Section 5.0 match those provided in SQN TS, NUREG-1301, or other NRC guidance?
4. Does the ODCM fulfill the requirements of TVA, Federal or State Laws, SQN FSAR, and any other referenced requirements documents?
5. Does the numbering of the Control and its accompanying Surveillance Requirement correspond?
6. Are instrument/equipment numbers and units of measure an exact match with those on the equipment?
7. Does nomenclature accurately describe the equipment and correspond to label identifiers?
8. Are referenced documents applicable, valid, and listed in the reference section?
9. Does this change maintain the level of radioactive effluent control required by 10 CFR Part 20.1302, 40 CFR Part 190, 1- CFR Part 50.36a, and Appendix I to 10 CFR Part 50? Provide justification for answer:
10. Are there methodologies given in Sections 6.0 through 9.0 which implement the applicable ODCM Controls?
11. Are references to ODCM Controls and Surveillance Requirements accurate and correct?
12. Are changes to setpoint calculation methodologies consistent with the guidance provided in NUREG-0133?

SQN ODCM Revision 47 Page 168 of 168 APPENDIX A - SQN ODCM REVISION PROCESS (Page 7 of 7) Attachment C ODCM Review Checklist (continued) Changes to Section(s) 6.0-11.0 YES NO N/A

13. Are changes to liquid effluent concentration compliance methodologies consistent with the guidance provided in NUREG-0133 and 10 CFR Part 20?
14. Are changes to gaseous effluent dose rate calculation/compliance methodologies consistent with the guidance provided in NUREG-0133 and/or Regulatory Guide 1.109?
15. Are changes to dose or dose projection calculation/compliance methodologies consistent with the guidance provided in NUREG-0133 and/or Regulatory Guide 1.109?
16. Are instrument/equipment numbers and units of measure an exact match with those on the equipment?
17. Are referenced documents applicable, valid, and listed in the references?
18. Are ODCM Sections numbered consistently and consecutively?
19. Are references to other ODCM Sections correct?
20. Are references to ODCM Tables and Figures accurate and correct?
21. Are any new acronyms defined in Appendix A?
22. Are equations numbered consecutively?
23. Does dimensional analysis yield the correct units for equations?
24. Are terms used in equations defined after the equation (and in

_ Appendix A) and the proper units given for that term?

25. Do units on equation terms which reference tables match the units used for that term in the Table?
26. Are references given for table and other values correct and accurate? X-
27. Do data values given match those in the reference?
28. Do text descriptions of release/discharge points in Sections 6.0 and 7.0 correspond with the Figures referenced in those sections?
29. The change does not adversely impact the accuracy or reliability of effluent, dose, or setpoint calculations? Provide justification for answer:

Preparer Date IQR Date}}