LER 78-052/03L-0:on 780922,during Surveillance Test,Diesel Failed to Start Due to Air Start Sys Fault.Second Attempt Was Sucessful.Air Start Sys Will Be Modified to Provide Multiple Start Attempts
ML20027A207
Person / Time
Site: Dresden Constellation icon.png
Issue date: 10/19/1978
From: Doyle J
COMMONWEALTH EDISON CO.
To:
Shared Package
ML17173A317 List:
References
LER-78-052-03L, LER-78-52-3L, NUDOCS 7810270296
Download: ML20027A207 (1)


Text

..ne 4.o,s .a.T . u. :..reacLLAs awui,A. cay ce;. .a.:w 4 67 77* * *6 LICENSEE EVENT REPORT '

^

CONTROL BLCCK: l l l l } l lh (PLEASE PRINT OR TYPE ALL DEQUIRED INFORMATION) t o l 8t 3l l I l LiCONSEE L I D lCODE R l S 14I 2 l@l 3 0 l 0'l- l LICEN3E 0 l 010 NU.VuER l 0 l 0 l- l0 l .a0 l@l 26 4lLICENSE 1l 1l TYPE1l 1l@l JO l

5 7 GAT Sd l@

CON'T lolil "E',"_'

3g l60L l@l 0 l 5 l 0 l 0 l 0 l 2 l 3 l 764 l@l63 0 l 9EVENT l 2 OATE l 2 l 7 l 874 l@l1 l 0REPolT l 1 lDATE 9 l 7 l 880l@

8 til DOGK ET *JUMSER 75 EVENT DESCRIPTION AND PROSABLE CONSEQUENCES h Io I:I l While performing the Unit 2/3 D/G surveillance the diesel failed to start. The air i 1Ot3l l start motors engaged but failed to turn engine. A second attempt to start the diesell 10lal l was successful. The safety significance of this event was minimal because the re- I la ieI ! dundant diesel was operable. I lO !6 l l l

'S II I J I3 l l l g 3 80 SYSTEN1 CAUSE CAUSE COMP. VALV E CODE CODE SURCODE COMPONENT CODE SU8 CODE SU8 CODE g0l9l

. 4 l 5 E l@ l Ei(E) l A l@ l El N!G l I! Nl El@ W@ lZ J 0 ..  ;;  : 13 ' .s M l@

, IEOUENTIAL OCCURRE?!CE nEPORT R EVISION 3 3 pg g d'.ENT YEAR AC50RT NO. CCOE TYPE N O.

h Qy{ I [ 7 ' 8 ; li l 0! 5.8 2! l/l l0l3I lL l l-j l0l L: 1 u = u ;s n .a :3 a 3 32 ACTICN FUTt;RE EF8E07 SHUTCO'.;N ATTAC4P.E N T NPRO-4

  • RIME COMP. COMPoN E'4 T T AP.E N ,.CTI C N ON PLA*.T *. :ETHOD e, curs 3UEMa TT ED FORM bus. SUPPLIER MANUFACTURER IG i@(F j@ lZ l@ l 0 l 01 0, L,yj @

03 34 ., l35 Zi@ 06 37 40 l

41 , lYl@

42 l43A l@ l W l O ! 9 i 747 l@

44 CAUSE DESCRIPTION AND CORRECTIVE ACTIONS i i I t] l Probable cause was failure in air start system. Air start solenoid and timer were i Qiij ] tested but found normal. Air start valve inspected satisfactorilv. Siesel I

liI21 I surveillance interval increased to weekly for one month. Air startasystem will be I

!i!3l l modified to provide multiple start attempts. l

'at i  !

. d S 80 SA t  % POWER OT**ER STATUS bl OV RY OtSCOvFRY DESCRIPTION -

l. 3i j C !@ l 0! OI 0l@.] NA l l B j@l Surveillance Testing l
  • AC%v,Tv CJ  : " " '

TENT l

EtE m C OPnEtEuE tOCAT,0N o, RETE =SE @

1 iG4 l9l Z l @ 10l Z!@l NA AMOuNTO ACTiviTv 44 l

45 NA@ l l i.

  • i f.0 l PERSONNEL EXPOSURES NUMBER TYPE CESCRIPTION l I l 7 l l 0 l 0 l 0 l@l Z l@l NA l d 3 11 12 13
  • 80 PERSONNE L INJU AiES NuveER DESCRIPTION j a l l 01010 l(2il NA l 88 9 11 12 80 LOSS CF OR t,A*.1 A8,E TO F ACILITY Q TY'E O ESCRIP TION y

'iJj lZ!@l NA' l s J 10 da

, """LLPr,0N @ ~"c u=n w a .

2 i a l Ls[81 NA l lllI!IlIlIIIl5 8 3 10 66 69 60 5 7 P/441L J.E. Doyle - - z.s R

t s. .

L ATTACHMENT TO LICENSEE EVENT REPORT 78-052/03L-0 CO>c!0NWEALTH EDISON COMPANY (CWE)

DRESDEN UNIT-2 (ILDRS-2)

DOCKET #050-237 While performing the Unit 2/3 diesel generator monthly surveillance, the diesel failed to start. The air start motors engaged but failed to turn ,

the engine. A second attempt to start the dimel was successful. The  !

~

safety significance of this event was minimal because the redundant diesel was operable.

The c,ause of this event is unknown, but it is thought to have been caused

( ,

by a failure in the air start system. The air start solenoid and timer were tested but they appeared to be operating normally. Also,-the air ,

start valve was inspected. The valve was disassembled and the internal inspection showed the valve was in satisfactory condition. The seals ,

were replaced and the valve was reassembled."' r t

l The diesel generator operating surveillance interval has been increased i from monthly to weekly for a one month period following the event in order to better determine the cause. There have been five successful starts on this diesel since this event occurred and no failures. Because of the number of starting failurcs which have occurred previously as ,

a result of failures of the air start motors to properly engr the ,

station is modifying the air start system. This modificati llow i automatic restart attempts if the pinion gears fail to properly e je to start the engine. The modification has been designed and approved and the required materials are being purchased. It is expected to be '-

i completed by February,1979.  ;