ML20049H693

From kanterella
Jump to navigation Jump to search
LER 82-003/03L-0:on 820127,leak of Over 1% Detected Through Charcoal Filters in B Standby Gas Treatment Sys.Caused by Improper Packing of Charcoal Canisters.Charcoal Beds Replaced
ML20049H693
Person / Time
Site: Dresden Constellation icon.png
Issue date: 02/23/1982
From: Anandappa A
COMMONWEALTH EDISON CO.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
Shared Package
ML20049H688 List:
References
LER-82-003-03L-04, LER-82-3-3L-4, NUDOCS 8203030455
Download: ML20049H693 (2)


Text

- . _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ . _ _ _ _

LICENSEE EVENT REPORT

,' CONTROL SLCCK: l l l l l l l (PLEAsE PRINT OR TYPE ALL CEQUIRED INFOstATICN)

, e@

lo 7' ltl1 4 9 Il L lUCENsts D lR cooE lS l2 l@l 010 l- l 0 l0UCENstNumetA 14 1s l0 l0 l 0 l - l 0 l 0 l@l 2s 4

s l 1l l l 1 l 1 l@ls1 lGTl 54 @

uCENsE TYPt 40 CCN'T loi1I 7 s "oy' c:

" , so" lL hl0l5l0l0l0l2l3l7 Ql 0 l 1 l 2 l 7 l 8 l 2 @l 012 l 2 l 3 l 812 l@

l si coCxsTNuusen es se avesto4Tu 14 75 percar c4Ta a0 EVENT DESCRIPTION AND PROSABLE CONSEQUENCES h

,o m l During normal operations while performing DTS 7500-7, freon test, on the "B" SBGTS, a l g leak of over 1 percent through the charcoal filters was detected. The "B" SBGTS was j

, , declared inoperable (T.S.3.7.B.2). There was no effect on public health or safety. [

This event is of minimal safety significance since the redundant "A" SBGTS was operable.g Past occurrence reported by R.O. 75-21 on Docket 50-237.

lol7ll l 1044l l I

' cote" Tcis susci$s couPossNrcaos sifeYo'o's susEoIs loisi 7 8 IS I cl@ I B l@ IB l@ t?Ir It It IT 9 to 11 12 leIal@ U @ W h 18 19 20

_ SEQUENTIAL, OCCURRENCE REPORT REVISION EVENT YEAR REPQmT NO. CooE TYPE NO.

ge,g 1812l

@ lLER/RO l-l l010131 l-l 10131 Itl I-l Lo_J 21 22 22 24 28 27 25 29 30 31 32 EN "Acy/8s' "

oUiEr **"sE u wouns #s5sY "r"Ta 7 PEmS U s. *IEbeI' s u4a$PTEEmeR I22Al@l24Z l@ lZl@ as lsa Zl@ [

si 0 l 0 l 0 ao

@l 0l l Nl@ lYlg 4

lL l@ la B l 0 l 7 l 547l@

42 42 CAUSE DESCRIPTION AND CORRECTIVE ACTICNS @

,, ,o,l The event was caused by a leak in the charcoal beds due to improper packing of the i

,, , , , , charcoal canisters. The charcoal beds were replaced and retested satisfactorily. The i "B" SBGTS was then put back into service. Routine testing of the system will continue l

per the Tech. Spec. requirements.

y l i 141 l I 7 s 9 so ATus  % PCwdM oTHEM sTAruS Y oiscovERY oE CMIPr1CN N/A Routine Surveillance Testine l1 i s l l E l@ l 0 l 6 l 2'2[@l" "

l W @l*

l

',JnvirY co'21 uT a

  • .t:43.o er .t:4s.

4.ouurepicrivirv @l tocaric.or..t:4s @

li lsl l Zl g l Z g l N/A l

N/A l oso~~'.c uPosses "

~uu...

l1 l7* *

) l 0 l 0 l0 lhlrmZ lhlo.scaimeN

N/A @ "

l Poses ~.'c%u2 s

~uu..a li l 3 l l 0 l 0 l0 [Qloescaimeu@

7 4 9 11 12 N/A 40 l

tCss OP CR oAuAGE To P CIUTY Tvrt CEscRipTTCN N/A 11191

  • S l Z l@l'o l 7

' 8203030455 820223 so issue oEscaimoN @ PDR ADOCK 05000237 NRC USE CNLY ,

S PDR 12101 lN hl N/A  ;  ; ; , , , , , , , , ; , g ;;

7 8 9 TO 68 69 80 3

. andappa 815-942-2020, v-421 NAME OF PREP ARER PHONE: {;

.mW

DEVIATION REPORT

@ Commonwealth E_, ova NO.

STA 12 - 2/3 UNIT son 4 YEAR NO.

. TITLE OF OEVIATION PART il Freon Test Failure of Standby OCCURRED Gas Treatment System "B" Train 1-27-82 1225 cur yw 5Y S T EM AFFECTLD 7500 PLANT STATUS AT TIME OF EVENT TESTING SBGTS yoeg Run , P*RtMaT) 1578 , go,ggy g3 460 C YES Nn DESCRIPTION OF EVENT While erforming DTS 7500-7 (Freon Test) to measure the leakage of the "B" SBGTS, the measured leakage was 1.7% which exceeded Tech. Spec. 3.7.B. limit of less than 1%.

I 10 CFR50. 72 NRC RED PHONE G NOTIFICATION MADE YES NO EQUIPMENT FAILURE D18371 YES NO ACRK REQUES T NO. RESPONSIPLE SUPERVISOR A. Anandappa e,rg 1-&M PART 2 l 0PERATING ENGINEER'S C044ENTS The charcoal absorbers for 2/3 "B" SBGTS Train will be replaced and retested prior to declaring the train operable. The 2/3 "A" Train was successfully tested prior to the failure of the 2/3 "B" Train.

O EVENT Or PueLiC INTEREST O 24-H0uR NRC Noti r i CATI ON REO D TtCH. SPEC. VIOLATION TELEPH Ilike Jordan (Courtesy) 1-27-82 1530 REGION lil DATE TIME NON REPORTABLE OCCURRENCE TELECM/TELECOPY 14 DAY RE PO R T A BL E / T. S . REGION lli DATE TIME h 3D DAY REPOR TABLE / T.S. b a b

  • 3
  • 2
  • D NP Fcm W

] ANNUAL /SPECL REPORT REQ'O lF ABOVE NOTIFICATION 15 PER 10CFR21 A.I.R. e 5-CAY ARITTEN REPORT REQ'D PER 10CFR21 L.E.R.

  • 7tu, F. A. Palmer 1-28-82 0946 CECO CORPORATE OFFICER DATE TIME l

PRELIMINARY REPORT Michael Wright 1-28-82 C LM PL E TE D AND REVIE*EO getRAtiNG ENGINEEg DATE INVESTIGATED RE3 ORT S RESOLUTION g ACCEPTED BY STATICN REVIEW pg /\Amid r' a m U

t l w C ~' . l l A /J4'/f2 -

RE SOLUT t CN APPRO%ED AND yJ7 AUTHCRIZED FOR DISTRI BUTION iL 64 5f76 'F:#v '5 12.ti 10 01 STAT 'N' TINTEN0ENT / CAT'E/

_ _ _ _ _ _ _ _ _ _ _ _ _ - _ - - __ - _ _ _ _ _ _ _ _ _ _ _ _ _ _ -