ML19253C994: Difference between revisions

From kanterella
Jump to navigation Jump to search
(Created page by program invented by StriderTol)
 
(Created page by program invented by StriderTol)
 
Line 22: Line 22:
Safety Imolications The purpose of seismically supporting fire extinguishers is to prevent a fire extinguisher from falling and damaging safety-related equipment during a seismic event. Thus, had this condition gone uncorrected, the safety of the plant during a seismic event could have been reduced.
Safety Imolications The purpose of seismically supporting fire extinguishers is to prevent a fire extinguisher from falling and damaging safety-related equipment during a seismic event. Thus, had this condition gone uncorrected, the safety of the plant during a seismic event could have been reduced.
Corrective Action Seismically qualified mounting brackets will be installed to secure all fire extinguishers located in category I structures. Installation of the qualified mounting brackets will be completed by May 30, 1980, for unit 1 and before fuel loading for unit 2. This matter was coordinated with V. T. Lueng of NRC-NRR in a telecon with TVA on November 27, 1979.
Corrective Action Seismically qualified mounting brackets will be installed to secure all fire extinguishers located in category I structures. Installation of the qualified mounting brackets will be completed by May 30, 1980, for unit 1 and before fuel loading for unit 2. This matter was coordinated with V. T. Lueng of NRC-NRR in a telecon with TVA on November 27, 1979.
                                        .
1541    075 7912120 N/
1541    075
                                                                              .
7912120 N/
                                                                                 .}}
                                                                                 .}}

Latest revision as of 01:26, 2 February 2020

Final Deficiency Rept Re Fire Extinguishers Not Seismically Supported.Caused by Design Oversight.Qualified Mounting Brackets Will Be Installed to Secure Extinguishers by 800530
ML19253C994
Person / Time
Site: Sequoyah  Tennessee Valley Authority icon.png
Issue date: 12/05/1979
From:
TENNESSEE VALLEY AUTHORITY
To:
Shared Package
ML19253C992 List:
References
NCR-MEB-79-43, NUDOCS 7912120481
Download: ML19253C994 (1)


Text

. .

ENCLOSURE SEQUOYAH NUCLEAR PLANT UNITS 1 AND 2 FIRE EXTINGUISHERS NOT SEISMICALLY SUPPORTED NCR MEB 79-43 10 CFR 50.55(e)

FINAL REPORT Description of Condition Section E.6 of the Sequoyah Nuclear Plant Fire Protection Program Reevaluation states that fire extinguishers within seismic category I structures shall be seismically supported. However, due to a design oversight, seismically qualified mounting brackets were not provided for fire extinguishers located in category I structures.

Safety Imolications The purpose of seismically supporting fire extinguishers is to prevent a fire extinguisher from falling and damaging safety-related equipment during a seismic event. Thus, had this condition gone uncorrected, the safety of the plant during a seismic event could have been reduced.

Corrective Action Seismically qualified mounting brackets will be installed to secure all fire extinguishers located in category I structures. Installation of the qualified mounting brackets will be completed by May 30, 1980, for unit 1 and before fuel loading for unit 2. This matter was coordinated with V. T. Lueng of NRC-NRR in a telecon with TVA on November 27, 1979.

1541 075 7912120 N/

.