MONTHYEARPMNS20201328, Partially Closed Meeting with NextEra Energy/Florida Power & Light Company to Discuss a Pending Digital Instrumentation and Control Upgrade and Standard Technical Specifications Update at Turkey Point Nuclear Generating Unit Nos. 3 and2020-12-0909 December 2020 Partially Closed Meeting with NextEra Energy/Florida Power & Light Company to Discuss a Pending Digital Instrumentation and Control Upgrade and Standard Technical Specifications Update at Turkey Point Nuclear Generating Unit Nos. 3 and 4 Project stage: Request ML20338A0472020-12-0909 December 2020 December 9, 2020 FPL Slides Rps/Esfas Nuclear Instrumentation Project stage: Request PMNS20201397, Partially Closed Meeting with NextEra Energy/Florida Power & Light Company to Discuss a Pending Digital Instrumentation and Control Upgrade and Standard Technical Specifications Update at Turkey Point Nuclear Generating Unit Nos. 3 and2020-12-16016 December 2020 Partially Closed Meeting with NextEra Energy/Florida Power & Light Company to Discuss a Pending Digital Instrumentation and Control Upgrade and Standard Technical Specifications Update at Turkey Point Nuclear Generating Unit Nos. 3 and 4 Project stage: Request ML21011A2382021-01-11011 January 2021 Slides for January 13, 2021 Presubmittal Meeting with NextEra Concerning Digital I&C Closed Non-Proprietary Project stage: Request ML21011A2232021-01-22022 January 2021 Requests for Withholding Information from Public Disclosure Project stage: Other PMNS20210136, Partially Closed Meeting with NextEra Energy/Florida Power & Light Company to Discuss a Pending Digital Instrumentation and Control Upgrade and Standard Technical Specifications Update at Turkey Point Nuclear Generating Unit Nos. 3 and2021-02-0404 February 2021 Partially Closed Meeting with NextEra Energy/Florida Power & Light Company to Discuss a Pending Digital Instrumentation and Control Upgrade and Standard Technical Specifications Update at Turkey Point Nuclear Generating Unit Nos. 3 and 4 Project stage: Request ML21047A2102021-02-16016 February 2021 NRC Presubmittal Meeting Telecon February 18, 2021 Open Meeting - FPL Safety System Replacement Project LAR - Nonproprietary Project stage: Meeting PMNS20210305, Partially Closed Meeting with NextEra Energy/Florida Power & Light Company to Discuss a Pending Digital Instrumentation and Control Upgrade at Turkey Point Nuclear Generating, Unit Nos. 3 and 42021-03-29029 March 2021 Partially Closed Meeting with NextEra Energy/Florida Power & Light Company to Discuss a Pending Digital Instrumentation and Control Upgrade at Turkey Point Nuclear Generating, Unit Nos. 3 and 4 Project stage: Request ML21054A0012021-03-29029 March 2021 Summary of Pre-Application Meetings with Florida Power and Light Concerning a Proposed Digital Instrumentation and Control Upgrade Project stage: Meeting ML21096A0772021-04-0808 April 2021 FPL Slides for Meeting with FPL-Turkey Point Units 3 and 4 Concerning Digital Instrumentation and Control Modification Project stage: Request ML21096A0612021-04-0808 April 2021 FPL Slides for Meeting with FPL-Turkey Point Units 3 and 4 Concerning Digital Instrumentation and Control Modification - Open Project stage: Request ML21099A1052021-04-23023 April 2021 Request for Withholding Information from Public Disclosure Project stage: Withholding Request Acceptance PMNS20210737, Partially Closed Meeting with NextEra Energy/Florida Power & Light Company to Discuss a Pending Digital Instrumentation and Control Upgrade and Standard Technical Specifications Update at Turkey Point Nuclear Generating Unit Nos. 3 and2021-05-28028 May 2021 Partially Closed Meeting with NextEra Energy/Florida Power & Light Company to Discuss a Pending Digital Instrumentation and Control Upgrade and Standard Technical Specifications Update at Turkey Point Nuclear Generating Unit Nos. 3 and 4 Project stage: Request ML21159A1652021-06-0404 June 2021 Affidavit for Nextera Tricon Presentation for Turkey Point 5th Presubmittal Meeting Project stage: Meeting ML21159A1892021-06-0909 June 2021 Non-Proprietary - FPL NRC Presubmittal Meeting June 9th Closed Slides Project stage: Meeting ML21159A1712021-06-0909 June 2021 FPL NRC Presubmittal Meeting June 10th Week Open Session Project stage: Meeting ML21176A0102021-06-29029 June 2021 Summary of Drop-in Meeting with NextEra-Florida Power and Light to Discuss Pending Submittals Related to Digital Instrumentation and Controls and Improved Standard Technical Specifications for Turkey Point Nuclear Plant, Units 3 & 4 (EPID L Project stage: Meeting ML21172A2712021-06-29029 June 2021 Request for Withholding Information from Public Disclosure for Turkey Point Nuclear Generating Unit Nos. 3 and 4 Project stage: Withholding Request Acceptance PMNS20210933, Partially Closed Meeting with NextEra Energy/Florida Power & Light Company to Discuss a Pending Digital Instrumentation and Control Upgrade and Standard Technical Specifications Update at Turkey Point Nuclear Generating Unit Nos. 3 and2021-07-12012 July 2021 Partially Closed Meeting with NextEra Energy/Florida Power & Light Company to Discuss a Pending Digital Instrumentation and Control Upgrade and Standard Technical Specifications Update at Turkey Point Nuclear Generating Unit Nos. 3 and 4 Project stage: Request ML21200A1472021-07-22022 July 2021 Nextera/Fpl Meeting Slides for July 22, 2021 Partially Closed Meeting Concerning Control Room Digital Modernization - Closed Public Project stage: Request ML21200A1562021-07-22022 July 2021 Nextera/Fpl Meeting Slides for July 22, 2021 Partially Closed Meeting Concerning Control Room Digital Modernization - Open Project stage: Request ML21190A1862021-08-0202 August 2021 Summary of Pre-Application Meetings with Florida Power and Light Concerning a Proposed Digital Instrumentation and Control Upgrade on Turkey Point Units 3 and 4 Project stage: Meeting ML21232A0172021-08-20020 August 2021 Licensees Non-Proprietary Presentation (2 of 2) for August 23 and 25, 2021 Public Meeting Project stage: Meeting ML21279A0962021-08-20020 August 2021, 23 August 2021, 15 October 2021 Pre-Application Meetings with Florida Power and Light Concerning a Proposed Digital Instrumentation and Control Upgrade for Turkey Point, Units 3 and 4 Project stage: Request ML21235A0932021-08-23023 August 2021 Licensees Non-Proprietary Presentation (1 of 2) for August 23 and 25, 2021 Public Meeting Project stage: Meeting PMNS20211047, Pre-submittal Meeting with NextEra Energy/Florida Power & Light Company to Discuss a Pending Digital Instrumentation and Control License Amendment Request for Turkey Point Nuclear Generating Unit Nos. 3 and 42021-08-23023 August 2021 Pre-submittal Meeting with NextEra Energy/Florida Power & Light Company to Discuss a Pending Digital Instrumentation and Control License Amendment Request for Turkey Point Nuclear Generating Unit Nos. 3 and 4 Project stage: Meeting ML21279A0432021-10-15015 October 2021 Summary of Pre-Application Meetings with Florida Power and Light Concerning a Proposed Digital Instrumentation and Control Upgrade for Turkey Point, Units 3 and 4 Project stage: Meeting ML21246A0212021-11-23023 November 2021 Summary of Pre-Application Meetings with Florida Power and Light Concerning a Proposed Digital Instrumentation and Control Upgrade on Turkey Point Units 3 and 4 Project stage: Meeting ML21214A1192021-11-23023 November 2021 Request for Withholding Information from Public Disclosure for Turkey Point Nuclear Generating Unit Nos. 3 and 4 Project stage: Withholding Request Acceptance ML21302A0052021-12-23023 December 2021 Email to Nextera/Fpl Re Discussion of Availability of Human Factor Validation Information to Support the Planned Turkey Point Digital I&C License Amendment Request Project stage: Other PMNS20220162, Meeting Between the U.S. Nuclear Regulatory Commission (NRC) and Florida Power & Light Company (FPL) to Discuss Planned Digital Instrumentation and Controls License Amendment Request for Turkey Point Nuclear Generating, Units 3 and 42022-02-25025 February 2022 Meeting Between the U.S. Nuclear Regulatory Commission (NRC) and Florida Power & Light Company (FPL) to Discuss Planned Digital Instrumentation and Controls License Amendment Request for Turkey Point Nuclear Generating, Units 3 and 4 Project stage: Meeting ML22063A4482022-03-0202 March 2022 Nextera/Fpl Affidavit for Proprietary Presentation for March 7, 2022, Public Meeting Project stage: Meeting ML22082A2222022-03-23023 March 2022 Terrapower Slide Presentation for Met Tower Water Supply Public Meeting Project stage: Request PMNS20220150, Pre-application Meeting with Terrapower to Discuss the Meteorological Data and Plant Water Source for the Natrium Plant Design2022-03-28028 March 2022 Pre-application Meeting with Terrapower to Discuss the Meteorological Data and Plant Water Source for the Natrium Plant Design Project stage: Meeting ML22101A2042022-04-0606 April 2022 Nextera/Fpl Affidavit for Proprietary Presentation for April 13, 2022 Public Meeting Re Planned Turkey Point Digital Instrumentation and Controls License Amendment Request Project stage: Meeting ML22101A2262022-04-11011 April 2022 NRC Staff Presentation for April 13, 2022 Public Meeting Re Planned Turkey Point Digital Instrumentation and Controls License Amendment Request Project stage: Meeting ML22098A0932022-04-13013 April 2022 Nextera/Fpl Redacted Presentation for April 13, 2022 Public Meeting Re Planned Turkey Point Digital Instrumentation and Controls License Amendment Request (Public Version) Project stage: Meeting ML22098A0902022-04-13013 April 2022 Nextera/Fpl Non-Proprietary Presentation for April 13, 2022 Public Meeting Re Planned Turkey Point Digital Instrumentation and Controls License Amendment Request (EPID L-2021-LRM-0007) (Slides) Project stage: Meeting ML22129A1812022-05-11011 May 2022 Summary of Pre-Application Meetings with Florida Power and Light Concerning a Proposed Digital Instrumentation and Control Upgrade on Turkey Point, Units 3 and 4 Project stage: Meeting ML22137A2512022-05-19019 May 2022 Summary of Pre-Application Meeting with Florida Power and Light Concerning a Proposed Digital Instrumentation and Control Upgrade on Turkey Point, Units 3 and 4 Project stage: Meeting ML22189A2092022-07-20020 July 2022 March 30, 2022, Summary of Public Meeting with Terrapower, LLC to Discuss the Meteorological Data and Plant Water Source for the Natrium Reactor Project stage: Meeting 2021-06-09
[Table View] |
Text
From:
Marshall, Michael To:
Catron, Steve Cc:
Jain, Bhagwat
Subject:
FYI: Discuss of Availability of Human Factor Validation Information to Support the Planned Turkey Point Digital I&C License Amendment Request (L-2021-LRM-0007)
Date:
Thursday, December 23, 2021 8:56:00 AM Hello Steve, The NRC staff would like to meet with NextEra/FPL to discuss the availability of human factor validation information in support of the planned Turkey Point digital instrumentation and controls (I&C) license amendment request (LAR). After comparing the proposed review timeline developed by the NRC staff for the planned Turkey Point digital I&C LAR to the licensees planned Human Factors Engineering (HFE) phase activities (last discussed at the August 23/25, 2021, public meeting between the NRC and NextEra/FPL), it has come to the attention of NRC staff that there may be challenges to completing the review (i.e., within the original NRC estimate of 15 months) of the planned LAR in time to support the 2023 Unit4 refueling outage.
Based on our prior discussions, this LAR is expected to be submitted for review under the Alternative Review Process (ARP), discussed in the NRC digital Instrumentation and controls interim staff guidance (DI&C-ISG-06). As discussed in SectionB.1.4 of DI&C-ISG-06, HFE is a review area outside the scope of the ARP interim staff guidance. For digital I&C equipment modifications that involve HFE considerations, an NRC safety evaluation is expected to be performed in accordance with the NRC Standard Review Plan (NUREG-0800, SRP), Chapter 18, Human Factors Engineering; NUREG-0711, Human Factors Engineering Program Review Model; and NUREG-1764, Guidance for the Review of Changes to Human Actions.
Issue:
In accordance with the guidance in NUREG-0711, NRC staff typically assess validation and verification (V&V) information, including information regarding integrated system validation (ISV) testing, as part of our review. However, based on our comparison of the NRC-developed proposed review timeline and HFE phase activities described by NextEra/FPL, it is unclear whether ISV testing is expected to be completed prior to the time period wherein the NRC will need to complete all necessary review activities (incl., completion and documentation of the staffs safety evaluation) in a timely manner to support the licensees planned implantation of the proposed amendment (i.e., installation of the control room medications) during the Unit 4 2023 refueling outage.
As discussed in NUREG-0711, NRC staff typically review the content of an applicants submittal and supplemental reports, such as results summary reports (RSRs) documenting the completion of actions discussed in implementation plans (IPs). Section 11.3 of NUREG-0711 states that, at a minimum, the RSR should include (among other information) the following:
- a description of the methodology, if an NRC approved IP was not used
- a description of the results from Task Support Verification and HFE Design Verification
- details of the results of the ISV, including a statement of how the validation demonstrates the ability to safely operate the plant
- a list of HEDs generated from the V&V, the analyses associated with these HEDs, and their resolutions Section 11.3 further clarifies that summaries may be used for any of the above items, provided that references are given for more detailed documents. Documents containing the additional details supporting the RSRs would be expected to be made available for NRC review during the audit phase of the NRCs review. Section 11.4 of NUREG-0711 discusses the criteria that the NRC will use when reviewing a licensees submittal. Section 11.4.3 discusses the criteria specific to ISV testing.
These criteria include, in part, the following:
- The applicant should use a combination of quantitative and qualitative methods to analyze data. The analysis should reveal the relationship between the observed performance and the established performance criteria.
- The applicant should identify human engineering discrepancies (HEDs) when the observed performance does not meet the performance criteria.
o Furthermore, the applicant should resolve HEDs identified by pass/fail measures before the design is accepted.
- The applicant should document the statistical and logical bases for determining that performance of the integrated system is, and will be acceptable.
- The applicant should document the limitations in the validation tests, their possible effects on the conclusions of the validation, and their impact on implementing the design.
Possible Resolution:
Please prepare to discuss possible resolutions to this issue, including the following at the upcoming public pre-submittal meeting:
- Any available updates regarding the planned timeline for HFE planning, design, and V&V activities.
- If ISV testing activities are not expected to be complete prior to the date that completion of the LAR review is needed to support implementation of the proposed modifications, please discuss what alternative information will be provided for NRC staff review to support the development of the NRCs safety evaluation.
o For example, is FPL considering alternative testing approaches, such as multi-stage validation (MSV) as a means to provide reasonable assurance that the integrated system will continue to adequately support safe plant operation?
Note that discussion of MSV can be found in Nuclear Energy Agency (NEA) Report No.7466, Multi-Stage Validation of Nuclear Power Plant Control Room Designs and Modifications, issued by the Organisation for Economic Co-Operation and Development (OECD). The NRC has not officially endorsed this guidance/approach, but it (or another alternative proposed within the LAR submittal) could be considered by the NRC technical review staff as a possible alternative to the guidance/approach discussed in NUREG-0711 for this specific request.
o Are there any other alternative approaches to resolving this timing issue that FPL is considering at this time?
The document that describes the multi-stage validation approach that we want to discuss with NextEra/FPL is available from this Nuclear Energy Agency site:
https://www.oecd-nea.org/jcms/pl_15142/multi-stage-validation-of-control-room-designs-and-modifications Best Regards, Michael L. Marshall, Jr.
Senior Project Manager Plant Licensing Branch I Division of Operating Reactor Licensing Office of Nuclear Reactor Regulation 301-415-2871