l Septembsr 2,1987

)

s, 4

Docket No. 50-267 l

Mr. R. O. Williams, Jr.

i Vice President, Nuclear Operations Public Service Company of Colorado P.O. Box 840 Denver, Colorado, 80201-0840

Dear Mr. Williams:

SUBJECT:

FORT ST. VRAIN FIRE BARRIER PENETRATION SEALS We have reviewed your letters dated July 2 and 27,1987 (P-87241 and P-87269) l concerning Fort St. Vrain's fire barrier penetration seals.

In these letters, l

you requested to eliminate or reduce maintenance requirements on certain fire l

seals.

You justified this reduction in fire protection requirements by the l

fact that these seals were not required to conform with staff fire protection j

guidelines, which are delineated in Appendex A to BTP APCSB 9.5-1, and the requirements of Appendix R to 10 CFR 50.

In most cases, the seals were part of a barrier that was not evaluated or credited in any fire protection analysis.

These seals were not previously reviewed and approved by the NRC.

We were concerned that some of these seals were located in fire barriers that are relied upon to limit fire spread so as to assure that systems relied upon to safely shut down that plant are free of fire damage.

In a telephone j

conference on August 18, 1987, your representative reaffirmed that these seals are not located in such barriers.

On this basis, and as a result of their review of the information provided in the above-referenced letters, the staff concurs with your position that the surveillance of these seals can be reduced or eliminated.

Our safety evaluation is enclosed.

Sincerel,

4 l$

l l

l Kenneth L. Heitner, Project Manager Project Directorate - IV Division of Reactor Projects - III, IV, V and Special Projects Office of Nuclear Peactor Regulation

Enclosure:

As stated I

cc w/ enclosure:

See next page DISTRIBUTION Docket Files NRC PDR Local PDR PD4 Reading "F, Schroeder"".

P. Noonan K. Heitner J. Calvo OGC-Bethesda E. Jordan J. Partlow ACRS (10)

PD4 Plant File LTR NAME: FSV 87137 e1 SPlepciSF L

=

e m m #"

e m eM PNoonh KHeitner:sr y/JCalvo DKubi JWermiel JC aig C./4Cndo 8/Ja/87 y Q/p/87 8M1I/87 8/7J/87 87

'l 8/15/87

[f7 8709100352 870902 PDR ADDCK 05000267 F

PDR

4 4

i o

Mr. R. O. Williams Public Service Company of Colorado Fort St. Vrain cc:

Mr. D. W. Warembourg, Manager Albert J. Hazle, Director Nuclear Engineering Division Radiation Control Division Public Service Company Department of Health of Colorado 4210 East lith Avenue P. O. Box 840 Denver, Colorado 80220 Denver, Colorado 80201 Mr. David Alberstein, 14/159A Mr. R. O. Williams, Acting Manager GA Technologies, Inc.

Nuclear Production Division l

Post Office Box 85608 Public Service Company of Colorado San Diego, California 92138 16805 Weld County Road 19-1/2 Platteville, Colorado 80651 Mr. H. L. Brey, Manager Nuclear Licensing and Fuel Division Mr. P. F. Tomlinson, Manager Public Service Company of Colorado Quality Assurance Division P. O. Box 840 Public Service Company of Colorado Denver, Colorado 80201 16805 Weld County Road 19-1/2 Platteville, Colorado 80651 Senior Resident Inspector U.S. Nuclear Regulatory Commission Mr. R. F. Walker P. 0. Box 840 Public Service Company of Colorado Platteville, Colorado 80651 Post Office Box 840 Denver, Colorado 80201-0840 Kelley, Stansfield & 0'Donnell Public Service Company Building Commitment Control Program Room 900 Coordinator 550 15th Street Public Service Company of Colorado Denver, Colorado 80202 2420 W. 26th Ave. Suite 100-0 Denver, Colorado 80211 Regional Administrator, Region IV U.S. Nuclear Regulatory Commission 611 Ryan Plaza Drive, Suite 1000 Arlington, Texas 76011 i

Chairman, Board of County Commissioners of Weld County, Colorado Greeley, Colorado 80631 l

Regional Representative l

Radiation Programs l

Environmental Protection Agency j

1 Denver Place j

i 999 18th Street, Suite 1300 Denver, Colorado 80202-2413 i

1

-)