Similar Documents at Maine Yankee |
---|
Category:MONTHLY OPERATING ANALYSIS REPORT
MONTHYEARML20217D9691998-02-28028 February 1998 Monthly Operating Rept for Feb 1998 for Maine Yankee.W/ ML20203A3011998-01-31031 January 1998 Monthly Operating Rept for Jan 1998 for Maine Yankee ML20199C2281997-12-31031 December 1997 Monthly Operating Rept for Dec 1997 for Maine Yankee ML20203F8551997-11-30030 November 1997 Monthly Operating Rept for Nov 1997 for Maine Yankee ML20198P9431997-10-31031 October 1997 Monthly Operating Rept for Oct 1997 for Maine Yankee ML20198K0201997-09-30030 September 1997 Monthly Operating Rept for Sept 1997 for Maine Yankee ML20217A9251997-08-31031 August 1997 Monthly Operating Rept for Aug 1997 for Maine Yankee ML20210M4451997-07-31031 July 1997 Monthly Operating Rept for July 1997 for Myaps ML20141H2691997-06-30030 June 1997 Monthly Operating Rept for June 1997 for Maine Yankee ML20141B9951997-05-31031 May 1997 Monthly Operating Rept for May 1997 for Maine Yankee.W/ ML20141G2871997-04-30030 April 1997 Monthly Operating Rept for Apr 1997 for Maine Yankee ML20138B1491997-03-31031 March 1997 Monthly Operating Rept for Mar 1997 for Maine Yankee ML20137C7161997-02-28028 February 1997 Monthly Operating Rept for Feb 1997 for Maine Yankee ML20134L8711997-01-31031 January 1997 Monthly Operating Rept for Jan 1997 for Maine Yankee ML20133N0701996-12-31031 December 1996 Monthly Operating Rept for Dec 1996 for Maine Yankee ML20132C0231996-11-30030 November 1996 Monthly Operating Rept for Nov 1996 for Maine Yankee.W/ ML20134N5041996-10-31031 October 1996 Monthly Operating Rept for Oct 1996 for Maine Yankee ML20128Q0431996-09-30030 September 1996 Monthly Operating Rept for Sept 1996 for Maine Yankee ML20149K2351996-01-31031 January 1996 Monthly Operating Rept for Jan 1996 for Maine Yankee Nuclear Power Plant ML20149H8891994-11-30030 November 1994 Monthly Operating Rept for Nov 1994 for Maine Yankee.W/ ML20058B9681993-10-31031 October 1993 Monthly Operating Rept for Oct 1993 for Maine Yankee Atomic Power Station ML20057F8461993-09-30030 September 1993 Monthly Operating Rept for Sept 1993 for Maine Yankee Atomic Power Station ML20058B9831993-08-31031 August 1993 Revised Operating Data for Aug 1993 for Maine Yankee Atomic Power Station ML20128K4051993-01-31031 January 1993 Monthly Operating Rept for Jan 1993 for Maine Yankee.W/ ML20127E4821992-12-31031 December 1992 Monthly Operating Rept for Dec 1992 for Myaps ML20125E3901992-11-30030 November 1992 Monthly Operating Rept for Nov 1992 for Myaps ML20217C2701991-06-30030 June 1991 Monthly Operating Rept for June 1991 for Maine Yankee.W/ ML20062E6861990-10-31031 October 1990 Monthly Operating Rept for Maine Yankee Atomic Power Station for Oct 1990 ML20059N4581990-09-30030 September 1990 Monthly Operating Rept for Sept 1990 for Maine Yankee Atomic Power Station ML20059N4641990-08-31031 August 1990 Revised Monthly Operating Rept for Aug 1990 for Maine Yankee Atomic Power Station ML20059K7481990-08-31031 August 1990 Monthly Operating Rept for Aug 1990 for Maine Yankee Atomic Power Station ML20059N4621990-07-31031 July 1990 Revised Monthly Operating Rept for July 1990 for Maine Yankee Atomic Power Station ML20058P3771990-07-31031 July 1990 Monthly Operating Rept for Jul 1990 for Maine Yankee Atomic Power Station ML20058P3811990-06-30030 June 1990 Revised Monthly Operating Rept for June 1990 ML20059N4591990-06-30030 June 1990 Revised Monthly Operating Rept for Jun 1990 for Maine Yankee Atomic Power Station ML20247F2291989-08-31031 August 1989 Monthly Operating Rept for Aug 1989 for Maine Yankee Atomic Power Station ML20245G0191989-07-31031 July 1989 Monthly Operating Rept for Jul 1989 for Maine Yankee Atomic Power Station ML20246F7701989-06-30030 June 1989 Monthly Operating Rept for June 1989 for Maine Yankee Power Station ML20244D2001989-05-31031 May 1989 Monthly Operating Rept for May 1989 for Maine Yankee Atomic Power Station ML20246L2301989-04-30030 April 1989 Monthly Operating Rept for Apr 1989 for Maine Yankee ML20245A2111989-03-31031 March 1989 Monthly Operating Rept for Mar 1989 for Maine Yankee.W/ ML20246L2351989-03-31031 March 1989 Revised Monthly Operating Rept for Mar 1989 for Maine Yankee ML20236B5931989-02-28028 February 1989 Monthly Statistical Rept for Feb 1989 for Maine Yankee Atomic Power Station ML20236B6111989-01-31031 January 1989 Revised Unit Shutdown & Power Reductions for Jan 1989 ML20206F7831988-10-31031 October 1988 Monthly Operating Rept for Oct 1988 for Maine Yankee ML20206J4841988-09-30030 September 1988 Revised Monthly Operating Rept for Sept 1988 for Maine Yankee ML20207N2021988-09-30030 September 1988 Monthly Operating Rept for Sept 1988 for Maine Yankee ML20154F0361988-08-31031 August 1988 Monthly Operating Rept for Aug 1988 for Maine Yankee ML20151U0651988-07-31031 July 1988 Monthly Operating Rept for Jul 1988 for Maine Yankee Atomic Power Station ML20151B0101988-06-30030 June 1988 Monthly Operating Rept for June 1988 for Maine Yankee 1998-02-28
[Table view] Category:TEXT-SAFETY REPORT
MONTHYEARML20211M4841999-08-31031 August 1999 Replacement Pages 2-48,2-49 & 2-50 to Rev 14 of Defueled Sar ML20211D7111999-08-0909 August 1999 Rev 17 to Maine Yankee Defueled Safety Analysis Rept (Dsar) ML20196K4821999-07-0606 July 1999 Safety Evaluation Concluding That Because of Permanently Shutdown & Defueled Status of Myaps Facility,Confirmatory Orders No Longer Necessary for Safe Operation or Maint of Plant ML20206H1611999-05-0505 May 1999 Safety Evaluation Supporting Amend 164 to License DPR-36 ML20206G5731999-05-0303 May 1999 Safety Evaluation Supporting Amend 163 to License DPR-36 ML20205D5261999-03-26026 March 1999 SER Accepting Util Rev 1 to CFH Training & Retraining Program for Maine Yankee.Rev 1 to CFH Training & Retraining Program Consistent with Current Licensing Practice for Facilities Undergoing Decommissioning ML20204C4631999-03-16016 March 1999 Safety Evaluation Supporting Amend 162 to License DPR-36 ML20206D7491998-12-31031 December 1998 Co Annual Financial Rept for 1998. with ML20155G9591998-11-0303 November 1998 Rev 1 to Post-Shutdown Decommissioning Activities Rept ML20155D8651998-10-28028 October 1998 Public Version of, Maine Yankee Emergency Preparedness Exercise ML20197C8231998-09-0303 September 1998 Safety Evaluation Supporting Request for Exemption from Certain Requirements of 10CFR50.54(q),10CFR50.47(b) & (C) & App E to 10CFR50 Re Emergency Planning ML18066A2771998-08-13013 August 1998 Part 21 Rept Re Deficiency in CE Current Screening Methodology for Determining Limiting Fuel Assembly for Detailed PWR thermal-hydraulic Sa.Evaluations Were Performed for Affected Plants to Determine Effect of Deficiency ML20236X1751998-08-0303 August 1998 Rev 16 to Defueled Sar ML20236U8451998-07-24024 July 1998 Safety Evaluation Accepting Rev 14 to Maine Yankee Atomic Power Co Operational QA Program ML20248D3011998-05-26026 May 1998 Rev 14,page 16 of 17,Section II of QA Program ML20247J0211998-05-11011 May 1998 Revised Page 16 of 17 of Section II of QA Program,Rev 14 ML20247D3451998-05-0606 May 1998 Rev 15 to Defueled SAR, Replacing List of Effective Pages ML20217J9811998-04-28028 April 1998 Part 21 Rept Re Incorrect Description of Drift Specification for Model 1154,gauge Pressure Transmitters,Range Code 0 in Manual Man 4514,Dec 1992.Cause Indeterminate.Will Issue & Include Errata Sheets in All Future Shipments to Users ML20217H5241998-03-30030 March 1998 Safety Evaluation Supporting Amend 161 to License DPR-36 ML20217D9691998-02-28028 February 1998 Monthly Operating Rept for Feb 1998 for Maine Yankee.W/ ML20216D7681998-02-25025 February 1998 Rept to Duke Engineering & Services,Inc,On Allegations of Willfulness Related to Us NRC 971219 Demand for Info ML20203A3011998-01-31031 January 1998 Monthly Operating Rept for Jan 1998 for Maine Yankee ML20202F3771998-01-31031 January 1998 Annual Rept of Facility Changes & Relief & Safety Valve Failures & Challenges ML20202E0541998-01-30030 January 1998 Rev 14 to Myaps Defueled Safety Analysis Rept ML20199K3211998-01-27027 January 1998 Rev 13 to Maine Yankee Atomic Power Co,Qa Program ML20199K3471998-01-22022 January 1998 Rev 14 to Maine Yankee Atomic Power Co QA Program ML20199C2281997-12-31031 December 1997 Monthly Operating Rept for Dec 1997 for Maine Yankee ML20217R2301997-12-31031 December 1997 Myap Annual Financial Rept for 1997 ML20203F8551997-11-30030 November 1997 Monthly Operating Rept for Nov 1997 for Maine Yankee ML20202D3181997-11-26026 November 1997 Safety Evaluation Supporting Amend 160 to License DPR-36 ML20198R6371997-11-0606 November 1997 Yankee Mutual Assistance Agreement ML20155G9511997-10-31031 October 1997 Rev 1 to M01-1258-002, Decommissioning Cost Analysis for Myaps ML20198P9431997-10-31031 October 1997 Monthly Operating Rept for Oct 1997 for Maine Yankee ML20217K5191997-10-24024 October 1997 Part 21 Rept Re Five Valves That May Have Defect Related to Possible Crack within Forging Wall at Die Flash Line.Caused by Less than Optimal Forging Temperatures.Newer Temperature Monitoring Devices at Forging Area Heating Ovens Procured ML20211N0571997-10-0707 October 1997 Revised Pages to Jul/Aug 1994 SG Insp Summary Rept ML20198K0201997-09-30030 September 1997 Monthly Operating Rept for Sept 1997 for Maine Yankee ML20199H1861997-09-25025 September 1997 Rev 12 to Maine Yankee Atomic Power Co,Qa Program ML20217A9251997-08-31031 August 1997 Monthly Operating Rept for Aug 1997 for Maine Yankee ML20217R1051997-08-27027 August 1997 Myaps Post Shutdown Decommissioning Activities Rept ML20216F1511997-08-0808 August 1997 Safety Evaluation Supporting Amend 159 to License DPR-36 ML20210M4451997-07-31031 July 1997 Monthly Operating Rept for July 1997 for Myaps ML20151M1351997-07-21021 July 1997 Rev 0 to Technical Evaluation 172-97, Cable Separation Safety Assessment Rept ML20141H2691997-06-30030 June 1997 Monthly Operating Rept for June 1997 for Maine Yankee ML20141B9951997-05-31031 May 1997 Monthly Operating Rept for May 1997 for Maine Yankee.W/ ML20141G6511997-05-19019 May 1997 Safety Evaluation Supporting Amend 158 to License DPR-36 ML20138G3541997-05-0202 May 1997 Safety Evaluation Supporting Amend 157 to License DPR-36 ML20141G2871997-04-30030 April 1997 Monthly Operating Rept for Apr 1997 for Maine Yankee ML20137Z1971997-04-14014 April 1997 Forwards to Commission Results of Staff Evaluation of Performance of Licensees W/Ownership Structure Similar to Plant ML20137N7541997-03-31031 March 1997 Rev 11 to Operational Quality Assurance Program ML20138B1491997-03-31031 March 1997 Monthly Operating Rept for Mar 1997 for Maine Yankee 1999-08-09
[Table view] |
Text
.
1 MaineVankee P.O. BOX 408
- WISCASSET. MAINE 04578 * (207) 882-6321 March 24,1998 MN-98-19 GAZ-98-17 UNITED STATES NUCLEAR REGULATORY COMMISSION Attention: Document Control Desk Washington, DC 20555
References:
(a) License No. DPR-36 (Docket No. 50-309)
(b) NUREG-0020, Licensed Operating Reactor Status Summary Report
Subject:
Maine Yankee Monthly Statistical Report - February 1998 Gentlemen:
I Enclosed please find the February 1998 Monthly Statistical Report for Maine Yankee.
If you have any questions, please do not hesitate to contact me.
Very truly yours, George A. Zinke, Director Nuclear Safety & Regulatory Affairs Enclosures 1
1 c: Mr. Ilubert Miller Mr. R. A. Rasmussen Mr. Ron Bellamy Mr. Michael T. Masnik -
P, Mr. Michael K. Webb I!"
Mr. Patrick J. Dostic
\g \
- Mr. Uldis Vanags \
'7' 9003300 A g $ $ h og PDR PDR:
R
' 5:\ LICENSE \98MN\9819.WPD-i
. :s .
. 3 .
1RT- Docket No.: Me-309 OPERATING DATA .
Date: 03/24/98 Completed By: 'M. Fortier Te1ephane: . 207-882-5810
- 1. Unit Name....................................... AN e Yankee 199$
2.. Reporting Period................................
2700 3.; Licensed Thermal Power (MWt).................... 920
- 4. Nameplate Rating (Gross MWe)....................
- 5. Design Electrical Ratin7 (Net NWe).............. 870 900 6.. Maximum Dependable Cape. city (Gross NWe)......... 860
.7.. Maximum Dependable Capacity (Net NWe)...........
- 8. If Changes in capacity Ratings (Items Number 3-7)
Since Last, Report, Give Reasons:
NO CHANGES
- 9. Power Level to Which Restricted, if Any (Net NWe) 19.. Reasons for Restrictions, if Any:
THIS MONTH YEAR-TO-DATE CUMULATIVE
- 11. Hours In Reporting Period 672.0) 1.416.00
- 12. Number of Hours Reactor 0.00 0.00 163.902.19 Was Critical...........
f- 13. Reactor Reserve Shutdown 0.00 e 00 e.00 Hours.................. 0.00 159.020.30
- 14. Hours Generator On-line.. 0.00
- 15. Unit Reserve Shutdown 0.00 0.00 0.00 Hours..................
- 16. . Gross Thermal Energy 377.611.152.00 e.00 0.00 Generated (MWH)........
-17. Gross Electrical Energy ~ _J24,570.384.00 e.00 0.00 Generated (MWH)........
- 18. Net Electrical Energy 119.543,416.00 l
0.00 0.00
- j. Generated (MWH)........ 0.00 72.60 !
0.0e
- 19. Unit ~ Service Factor......
0.00 e.00 72.60 1
-29. Unit Availabilty Factor.. l
- 21. Unit Capacity Factor 67.37i
.(Using MDC: Net)........ e.ee e.00
'22. Unit Capacity, Factor e.00 65.964 (Using DER Net)........ 0.00 RS9; l
.23. Unit Forced' Outage. Rate.. 0.00 RxtOO NONE g
<24.< Shutdowns Scheduled Over Next 6 Months:
-5.;If Shutdown'at End of Report Period, Estimated Date of Startup lD I
l Docket No 50-309-Unit Name: Maine Yankee' Date: 03/24/98 Completed By: M. FORTIER Telephone: 207-882-5810 Report Month: FEBRUARY 1998 NARRATIVE
SUMMARY
OF OPERATING EXPERIENCES Maine Yankee 10CFR50 license no longer authorizes operation of the reactor.
t l
_ _ _ = _
AVERAGE DAILY UNIT POW 1ER LEVEL FOR FEELIARY 1998 50-309 Docket No.:
Unit: Maine Yankee Date: 03/24/98 Completed By: M. FORTIER Telephone: 207-882-5810 Day Avg. Daily Power Level Day Avg. Daily Power Level (MWe-Net) (MWe-Net) 0 16 .................... 0 1 ....................
0 17' .................... 0 2 ....................
0 18 .................... 0 3 ....................
0 19 .................... 0 4 ....................
0 20 .................... 0 5 ....................
0 21 .................... 0 6 ....................
0 22 .................... 0 7 ....................
0 23 .................... 0 8 ....................
0 24 .................... 0 9 ....................
0 25 .................... 0 10 ....................
0 26 .................... 0 11 ....................
0 27 .................... 0 12 ....................
0 28 .................... 0 13 ....................
0 29 .................... 0 14 ....................
0 30 .................... 0 15 ....................
m
r---
UNIT SHUTDOWNS AND POWER REDUCTIONS Docket No.: 50-309 Unit Haine Yankee FOR FEBRUARY 1998 Date: 03/24/98 Completed By: M. IORTIER Te1ephone:
Page:
207-882-5810 1 of 1
)
l 1
Number Date ) ll ll Type (1) 4 Il J
Duration (Hours)
Reason (2) ll l- h Method (3) ll ll ll LER # H H Il System Code (4)
Component Code (5)
NONE Cause and Corrective Action TYPE: 2. REASON: (cont) 4. SYSTEM CODE:
1.
(F)orced F-Administrative Exhibit G-Instructionc G-Operational Error for Preparation of Data (S)cheduled H-Other (Explain) Entry Sheets for f Licensee Event Report (
- 2. REASON A-Equipment Failure 3. METHOD: (LER) File (NUREG.0161)
B-Maintenance or Test 1-Manual '
C-Refueling 2-Manual Scram 5. COMPONENT CODE:
D-Regulatory Restriction 3-Automatic Scram Exhibit I-Same source E-Operator Training & 4-Other (Explain) as above.
! License Examination i
. . _ . . . _ _ _ _ _ _ _ _