Rev 10 to Procedure 255.0, Cable Terminations. Incomplete Procedure Re Installation Spec for Cable Splicing Termination & Supports,Quality Class Q & R,Encl
ML20128M720
Person / Time
Site: Palo Verde  
Issue date: 04/02/1982
From:
BECHTEL GROUP, INC.
To:
Shared Package
ML20079P594 List:
References
FOIA-83-161, FOIA-83-A-9 255.0, NUDOCS 8506030062
Download: ML20128M720 (19)


Text

if

% ED et Nuc:.t Au cch tt2 ATiNG sT AT TITLE =

p

.*3

~

<46 CAELE TETr.NA~~0:S 255.0 2C

.aCC,

cr g

'55"**

7/;906 wcax PL AN *noecount ov ALivy cosinot iNrTauctioN acvisto (g m

  • c

.s. u j

,,,c

$$~lL ~

'l

(

JH

(/

i 1.0,J PURPOSE 1.1 This document establishes a work procedure and inspection plan for the i

installation of electrical cable tereinations and for assuring ec pliance with all applicable drawings.

l 2.0 DEFINITIONS l

i 2.1 Abbreviations, terns and definitions cost co=nonly used in this procedure are centained in k'PP/QCI No.1.0.

l r

3.0 REFERDiCES I

3.1 Circuit Schedule.

L 3.2 ANSI N45.2.4-1972 (IEEE-336-1971) Installation Inspection, l

i 3.3 I

PSAR Yol. XIV Section 8.0, Subsection 8.3.1.5 on page 8-3-62.

I 1

3.4 Installation Specification 13-EM-306.

\\

4.0 Cl'ALIIT CONTROL E".0UIRD:EhTS l

4.1 The TE shall notify the responsible QCE prior to any Quality Class "Q" 1

and associated cable te =inatiens.

The " Termination Inspection I

Record" (TIR) (Exhibit 255.0-2) shall be used to document the f

inspection.

l Associated cables are Non-Class IE circuits that share d

4.1.1 power supplies, enclosures, or raceways with class IE p

i circuits or are not physically separated fro: class 1E a

circuits by acceptable separation distance or barriers.

g 4.2 Quality Class "R" and "S" excluding associated cable terminations will be selected at random by the TE for his examination.

The "TIR" lb (Exhibit 255.0-2) shall be used to document the exa=ination.

The f

responsible TE shall deter =ine the nucher of terminations to be exa ined and shall adjust the percent of surveillance to provide reasonable assurance of proper tereinations.

g P,

b h-8506030062 831110 PDR FOIA

. o :.m..m DERNADE03-A-9 PDR

%.p S- @2^i m m.s_.

-y-v~~.

,, 9 ee, 9 TITLE -

d' -

CA31.E TERMINATIONS

" 8-255.0

9 e

5.0 CENERA1.

N 1

/*

5.1 The ter=inations shall be inspected in'accordance with Appendix I, and the results documented on the "Ter=ination Inspection Record".

(ExhibR 255.0-2).

5.2 prior to and after cable ter=ination, visually inspect (exacine) termination cabinets it r da:. age to nearby' equipment, cables, or connectors.

5.3 For motors 20 horsepower and above all motor leads shall be checked with'a phase rotation meter for correct identification, k' hen any motors are found to have incorrect phasing, field may reidentify Vendor motor leads to insure proper rotation.

5.3.1 Any cotor operated valve (MOV) which has been received without identificatien on the motor leads or te::inal points shall have its ter=inal points or motor leads tagged or labeled with a =arker.

This marking process I

shall be carried out only after identifying these leads from the latest Vender drawings.

(

5.4 After the termination has been accepted by the QCE for Quality Class "Q" and associated cables, the eriginal of the " Control and Tracking System Termination Installation Card" shall be forwarded to'the DCC for file.

All Quality Class "R" and "S" ca.rds (excluding those'for associated cable) shall be maintained in the Electrical FE's files.

5.'5 In the evant a design change fron Home Office Ingineering occurs, or any cause for rework (e.g. NCR, DCP, etc.), af ter cable ter=ination has been made, the following criteria shall apply:

5.5.1 Issue a new contro1 and cracking system termination installation card with instructions to the field to rework cable termination.

The rework document number shall be entered in the "re= arks" section of the TIR.

I 5.5.2 Document inspection of cable ter=ination rework on the new card and attach old card for permanent record of installation.

5.6 k' hen schedule does not permit vaiting for a termination installation card to be cocputer printed;'the TE shall handwrite / type a card providing all necessary information.

After co=p'letion of termination the handwritten card shall be held by the TE pending receipt of the coeputer printed card.

Inspection acceptance shall be indicated cn the computer printed card.

The two (2) cards shall be kept stapled together.

....,,,....,i..n.

,y

m.

r 4

( 3 VCRSC Nucl.CAQ CENER ATINS sT Ak 4 CCI ]-

TITLE '-

CA3t! TITRINATIONS.

~255.0

9 i
  • Ass or 3

p 5.0 GENE?at (con't)

  • ' ~

,e 5.7 When phasingitape is.used to identify'the conductors of a power cable, the folloving convention will be'used: One three conductor cable: A6 blach BG vhite, C6 red.

Three single conductor cables:

A6 black, B6 red. C6 blue.

s 6.0 INSTALLATION 6.1 The " Control and Tracking System Termination Installation Card" shall be the basis of all associated field construction activities.

6.2 The TE shall review all cards for accuracy and completeness. prior to issue.

6.3 The TE's shall review installation spee. 13-EM-306 for specific ter=ination requirements and copies of referenced associated documents of purchase order 13-EM-106 and transmit information to supervision for direction to crafts.

Fh' 6.3.1 The annunciator'and computer field cable terminations shall be completed using nylon sereus and washers.

When nylon screvs and vashers are used, the TE or his designee shall enter the following in the " Remarks" section of al'

' termination cards: " Nylon screws and washers used".

The TE shall initial and date. QCE stamp and date. The TE or his designee shall.be responsible to collect all the normal terminal block screws on the field side, place them in a plastic / cloth bag.

Eags will be clearly labeled as to which piece of equipment they were taken from and be turned over to the Engineering Coordination Supervisor or-his designee.

Startup shall be responsible to return the terminations to the normal installation configuration.

'6.4 Upon completing the termination, the superintendent, or his designee, shall assure that the signature of the installer, badge number, and date has been entered in the appropriate space signifying satisfactory completion of termination.

In addition, the serial number of crimp tool (s) used to make terminations shall be recorded on the front of

.the card (Exhibit 255.0-1) by the installer. The Superintendent shall then return the "TIR" to the TE for his completion.

l t

ee sse. s,eens sene C

_g g

CA3LI TE?.MINATIONS a m.

ccv 255.0 t9 nac er 5.0 CINERAL (een't) s i

5.7 When phasing tape is used to identify'the cenductors of a power cable, the following conven: ion vill be used:

One three conductor cable:

AC blach, 30 vhite, CC red.

Three single condue:or cables:

AB black, 30 red. CC blue.

6.0 INSTALLATION 6.1 The " Con:rel and Tracking System Ter=ination installatics Card" shall be the basis of all associated field cons:ru.ction activities.

6.2 The TE shall review all cards for ~ accuracy and cocpleteness prior to issue.

6.3 The TI's shall review installation Spec. '3-EM-306 for specific ter ination recuire=ents and ceptes of ref erenced associated documents of purchase order 13-EM-106 and transmit informa: ion to supervision fer direction to crafts.

(

6.3.1 The annunciater and ce=puter field cable terminations shall be comple:ed using nylen screvs and vashers.

When nylon screws and vashers are used, the TE or his designee shall enter the f ollowing in :he "Re arks" sectici cf al'.

ter=ination cards:

"Nylen screvs and vashers used".

The TE shall initial and date, QCE sta=p and date.

The !! or his designee shall be responsible to collec: all the nor=al ter=inal block screws en the field side, place them in a plastic /cleth bag.

Eags vill be clearly labeled as to which piece of equipcent they were taken fron and be turned over to the Engineering Coordination Supervisor er his designee.

Startup shall be responsible to return the terminations to the noruAl installation configura: ion.

'6.4 Upon ce:pleting the ;er=ination, the superin:endent, or his designee, shall assure that the signature of the ins: aller, badge number, and date'has been entered in :he appropriate space sigelfying satisf actory co:ple: ion of scre't.ation.

In addition, the serial nucher of cri=p tool (s) used to =a,.e terminations chall be recorded on the front of

.:he card (Ixhibi 153.0-1) by the installer.

The Superintendent shall then return the "I1R to the TE for his co:pletion.

....... n..oi.ns h

O

=.p

, f' g

,+

.g

.p

,f V

3

@l o VenoE NuCL.E AR ScNCQ ATINS sTA l'

M w

cc c

TITLE --

1

.c CA3*E-TERP! NATIONS.-

,,3, 255.0 10 p

nos or 4

16.0.

INSTAI.1.ATION (con' t) 6.'4.1 Termination Engineer 'sh'all enter in remarks ' column the

  1. ~

specific type of termination or splice kit and lot number, t

whenever a 5 or 15KV heat shrink kit is used. -

6'.4.1 After the TE co=pletes his portion of the "TIR" all Quality Class "Q" and associated TIR"s will be routed to the QCE for his completion.

-6.5 k*nen the terminations have been completed. the TE and/or QCE will.

initial /sta=p the appropriate blocks on the TIRland it will be processed for filing per para.' 5.4 of this procedure.

In.the event the card is 'enly partially ce=pleted due to work suspension. it will' be. returned to the TE and suspense filed until the work can be scheduled for co=pletion.' k" hen rescheduled the same requirements specified by para. 4.1. 4.2, and other applicable paragraphs of this' procedure vill be in effect.-

6.6 In the event a. Quality Class."Q"'or associated termination is found

' unacceptable the QCE.shall place an asterisk (*) by the discrepant item.in the QCE column and an asterisk (*) in the remarks section of..

!p theTIRwithabriefdescriptienofthe. anomaly,hisinitials,andthe(

date..The.TIR shall then be returned to the TE for rework'.

6.6.1 After the rework has be'en comp 1'eted satisfactorily the TE shall initial and date the statement in the remarks section and the TIR returned to the QCE for reinspection.

If the reinspection results are acceptable, the QCE will stamp the item in the QCE celumn_and the-TIR shall be closed out (Ref.' para. 5.4).' If the reinspection results are unacceptable the nonconformance vill be documented on an NCR per k'FF/QCI No. 5.0, and the NCR number noted in the remarks, section of the TIR.. The TIR will.then be routed to the TE for suspense filing until the NCR is resolved and the TIR can be closed by the QCE.

6.7 k'her". terminations for equipment and/or motor heater leads can not be completed due to temporary power being connected the following shall.

apply:

'6.7.1 The field shall' form cable and install the permanent ter=inal lugs on field run cable.

All required counting hardware such as screws, nuts, bolts, etc., shall be attached to the ends of field run cable for final.

installation at a later date by others.

The installed

?

t i

1

......, tie.en ie m

m w,-

),.

( LD vtact NUCLcAR nCNCQATINS srk JN f

,f - '

TITLE -

[

CAELE TEPI SATIONS

,, 3,

~55.0 W

., s

    • c or

{-

6.0 INSTALLATION (con't)

L,

\\

e. ?

t l

6.7.1 lugs shall be protected from touching any ta=porarily f

(con't) energited ' ircuit by' taping lugs and tying cable away f rom c

l energized connections.

If te=porary power source is cennected to Vendor supplied' pig-tailed leads, the field shall disconnect the temporary power leads and install the permanent lugs to Vender supplied leads if required.

NOTE:

Ensure that power has been turned off and tagged at the sourch before disconn'ection of temporary power.

~

6.7.2 Reconnect the te=porary power leads to the Vander heater leads and re-energite heater circuit with temporary power source.

The Temination Engineer shall note in the re= arks section on the back of the termination inspection record (TIR) any teminations not completed due to I

te=porary power hook-up.

All te minations meeting this criteria shall be entered into the EE580 as construction partial (CP), but not field inspected (TI). The persen responsible for =aking the actual permanent connection jf shall request the ter=ination EE580 card from the Lead 7

Temination Engineer-(TE) and sign at the bottom of the card when connection is ce=plete.

A't this time, the temination vill be advanced to the construction co=plete

, status (CC) and the secondary status of field inspected (FI) will be added. When the pe =anent ter=ination is complete, the TIR shall be processed for filing per paragraph 5.4 of this procedure.

6.8 Ju=pers shall be installed as indicated on the ju=per termination cards L for left side.of termination block and R for right side of temination block.

If.no side is indicated on'the termination card, terminate jumper on field side of block provided no more than two (2) vires are teminated at any one terminal point.

The Termination Engineer shall have the option to authorite installing

  • jumpers on vendor or internal side of teminal block to avoid more than two (2) wires on one field side terminal point.

i t

6.9 Tor ju=per vire the Termination Engineer (TE) shall have the option of using wire equivalent to or better than A17 cable code, which is indicated on the TIR, and of a greater nu: sher of strands.

l I

......, n e n r e s en s

1 O.

3 VCOCE NUCLE AR GCNCR ATINO SrAN d I' C

  • C t

7 3 7. g,

e#

CAI'I TEF."! NATIONS

~

~2.

cry 255.0 PACE Op 6

6 e

7.0 AUAC2ENTS N'hibit255.0-1(Rev. 1) " Control ahd Tracking Syster: Te rt:ination e

r.

7.1 Installation Card." (front) 7.2 D:hibit 255.0-2 (Rev. 5) "Ter=ination Inspection Record." (bach) 7.3 Appendix I " Instructions f or the preparation of the Ter=.ination Inspection Record."

8.0 INCORPORATID PCN'S 8.1 Revision 10 to k'PP/QCI incorporated PCN No. 18, 19, 22, 23, and 26.

PCN No. 22 superseded PCN No. 21.

8.2 Revision 8 to Appendix I incorporated PCN No. 20, 24 and 25.

)

e..

.., i i...,i i e m h

4 0

7 4

Exemption 4

'u

M

.f

.9

+

lR i ! l ! ! I Id l l i i ! I ' l J ', ' i ; j i i : e 5

lili I,.

i

-.a..

i i, j k'e

.I i.

1

[ tI g e n-1

}

i**

i n

i ii.

I i

lij l:,.I i j

i 3

i I1.

l ; I i. i !

l

'i lii

I.

Il, i,

Il I!l l i

l-l.

I.I I i. i.

l, i.

i.

l l-I i

1 e

l l

I-e l l1I i l

=

i i

i i

.n c

.l

: i i i i i i i i.

l l l!

l l 1l!

- s C

e!

,i i

.i>:

li i

c a

I ll.

r l

i u

l e

I i

w t;!

.l h3

's.

c, C

wi i

l

.l.

l.

e i i-g l

g gi

=

.n e E

s i

2 4

e m

?

i l

. Is

's W"a <a.

I E

23

.=j !

li l C

-i..!..sl >wi =*

l I

l l

l l

c, w

i s

1 I, l! -

p

i. t

=

ci j.

i H

z g w:wr =:-l f3 w

=;=.=- i l

i e l l l

l 1 I

l =.-

C = *l =. *- *i w

I-xl

..-

  • w 6.

l l

w.= -

l1., l 8

g

=

C.

w e'l 5.O. =:.i e

s t :

l

q..

r,jg s

we

.. e. ::

l

,6 l~

1 2

61 H<a bj ;:;: -. 3 l

l i

i !

r l

x.i< e Ill i

>w e. r.. =. -i.

s,

.t

~

  • 3 v.

z r-e =

l.

i

=

-i - w.i j j

e l

l l g l l

  • a l.
w=c

-. -j t z;.:. :( : 2 < ! <;( u.i. r. ;:;-

C

,=

<f e

g v

3 l

z, e'

l 1 w

v.u.

= z; e p

g 8 i e

s l - :

I w<.

= ci l

l1

.. : ) =.

! Il Il i

8lC e

i

,=l - j '

w ;ll' l

,4 m; wi -

i a-

'll

'.wI'a c l xi e

bli t.

. l

x x;

I

.I l

I 6

2.

l

='

ed l - !

l i I t.

'L.=:Mt

!. n et :

C

. :l r s. l l;:;;.c <;

le i.

3 a

I 8

+

i

. =i l :

.e

= Os

=

a w

.a s

(

= m6

s..

M y;, gi

'-: 2:. w.v:

I ' ' Q: l 1

[ -

t 1

i i*.

.., i s I u-2

, w.

l

. :. [ s 8

l? [ T,

.. p:

a:U,i

  • l

.w.n <.

-. -. e.

[ l i :

i

-e s ; = v. =: 2 ;r.; ;: w.

(.!.

l

's

I lg e *,<=!*Iw.tv.s=

.=:

i *

  • I' i

v z.:y*guipi,..=

g t

i ;

  • I I,

t g.

gj 3 :. M = *.a.,. V '..

i 4

ts I t

._.. "h t.

  • 8
N. 6"-i. m: ; ',!. ! I j i - I 2-

=: x:.

t a

. t i

.a 2

i.

3

- p' H. S c..

0:

4 i

p.

=: i 8

g. H'!. e. s'.... =; s:. n. :_:.
i. 8 [,- l I i

n: s i

. E.

=: :J' s:

3 l

x =:<

w!. A.E_::=E'. n.'.:x R EI,.

=

i u

l i

a
  • i= n. * *

.l a

e" j

b H -* H f** =

6.

i 1

  • 3,

=: ::::

f..,; =

,g..

=

l

. e s.

..-.* : *. =

Il b

f*

P A( VeQEe NucLcA'4 CcNcR ATIN3 ST ATak

,p TITLE -

CASLE TERMINATIONS 3,

Apptndix

,y a

APPENDIX I 255.0 e

PAGE OF A.

PURPOSE --

t 1.

To provide instructions f o'r the preparation of the " Termination Inspection Record," (Exhibit 255.0-2).

S.

IE?MINATION ENGINEER AND OCE INSPECTION INSTRUCTIONS 1.

The TE shall provide technical guidance and surveillance during installation of Quality Class "Q",

"R",

and "S" cable terminations.

2.

The RFE/Date colu=n on the TIR =ay be lef t blank as the TE's signature in the RTE /Date block in the lower right hand corner constitutes his acceptance of the complete termination.

The TE cay elect.to initial /date this column for surveillance status at his option.

3.

The TE shall indicate co=plete acceptance with his signature and date (lower right hand corner) of the "Ter=ination Inspection Record",

(Exhibit 255.0-2) where it reads RTE /Date.

4 The QCE shall stamp and date each item in the QCE colu=n to document daily in-process inspections of cable ter=inations by the QCE for Class r

~

.IE and associated class cables.

In. the event a ter=inal board is installed in a terminal box (JE), the QCE shall make final acceptance inspection and enter in the remarks column "T.B.

installation acceptable, QC stany and date".

After final acceptance of the Class IE and associated class terminations by the QCE, the TIR shall be routed to the responsible QCE for review and final acceptance, signified by signature and date in the QCE/Date block in the lower right hand corner of the TIR.

5.

When the nylon screws and vashers are used to comply with para. 6.3.1 of this procedure the TE/QCE shall verify entry in remarks section of the TIR by the TE or his designee initials /QCE stamp and date respectively.

6.

Items that are not applicable, enter N/A.

C.

ENTRY INSTRUCTIONS 1.

Tash No.

Item Insoection Instructions 1.0 Verify that the flex conduit is properly installed as required per applicable details / drawings.

sc.i t s, in c as t) t o/7s

f

.~

-j

\\ ;.0 VcR Dc NUCLc AR CcN cR ATING sr A1ht.,N TITLE - -

CALLE. TERMINATIONS Appendin,,y s

APPENDIX !

255.0 case or C.

ENTRY' INSTRUCTIONS'(con't)

I' I

1.

Task-No.

Item Insoection Instructions 2.0 '

Verify. termination completed per " Control and Tracking System Termination Installation Card," (Exhibit 255.0-1).

Verification is recuired only for the following items:

termination number, separation group and color, number of cables, cable number. cable code, termination design details, location number, block, point, side, color..and vire number.

In the event " termination design details" and " side" and " blocks" are left. blank by the.eemputer, verification will not be required.

3.0 Verify that ter=ination~ is in accordance with the applicable portions of Spec. '13-EM-306 (excluding 'the testing delineated in Section 15.0 which vill be governed by WPP/QCI No. 256.0). -Enter specification revision number.

4.0 Enter toroue wrench' serial number and calibration due

[

date.

5.0 E.

Inter-crimp tool serial number and calibration due date.

I 6.0 Verify terminations are identifiable by the color of the-

. individual wires per." Control and Tracking System Termination Installation Card".

Ensure permanent cable markers and wire markers (if applicable) are attached as specified by 13-EM-303. Enter specification revision number.

7.0 Verify that cables are properly formed, bundled,-

supported, and separated (as required) in a good craftsman like manner.after termination is completed.

8. 0" Verify that grounding is properly installed and terminated as required per applicable details / drawings.

2.

Enter re= arks as appropriate in the blocks provided on the " Termination Inspection Record".

If a DCN'was used for termination, enter drawing and DCN number.

3.-

The motor phase rotation check for Class IE, motors shall be verifded by

,the-TE and QCE.

The TE or his designee shall enter in the remarks block:

motor phase rotation checked. The QCE shall stamp and date.

....., m.enions b

[

.(

as 1

2 hi PALO VCR DE NUCLEAR GENER ATING sT ATION PAGE 1

1 PCN NO. 3[

OF 65 UNITS 1,2 & 3 3,

PROCEDURE CHANGE NOTICE (PCN)

WP/P x OCl NO.

255.OREv 10 JOB NO,10407 T I T1. E : Cable Terminations

-4.

5.

CH ANGE REQUESTED BY:

OA OC O.F E INITI ATED BY:

Un, T,, S m. l o,-

6. R E ASO N FO R CH A NG'E:

Pemit use of colored (red) green yellow, blue) wire for

,e j :=pers and DCP's.

~

7. DESCRIPTION OF CHANGE:

1.

Section 6.0, add new paragraph to read as follows:

6.10 Wire of cable code A17 or better, as indicated in para. 6.9 above, may be used for DCP modifications.

Wire of cable cod.e A17-1, A17-2, A17-3, and A17-4 may be used for Class IE, DCP modifications and ju=pers providing that the wire color catches the channel color.

O o

em e

2. A?P R O '" : <Mory 4 VG22~

slM/rs A

W ww

/u r%

DA<E rQCE TE v pre -

..{ Wu A.~ -

7 p/' d /?>,

g uIR

+

DATE CCOCE DATE

[90AE 6-13

[\\

.....,,,.=

c

P C

C y

1 1

PCN NO. h PA LO VER DE NUcLC AR GENER ATING ST ATION PAGE OF UNITS 1. 2 & 3

.3.

t PROCEDURE CHANGE NOTICE (PCN)

].vP/P @ OCi NO.

255.0aEv 10 JOf3 NO.10407 TITLE: Cable Terninations OC DE i N i T i A T E D s'v :

3 Bo=b^rd CH ANGE REQUESTED iTY: 00^~

e

6. RE ASON FOR CHANGE:

Clarification of 50W to lift and re-land terninaticas after accertance by the QCE when no NCR, DCP, DCN, etc. applies.

7. DESCRIPTION OF CH ANGE:

1.

Section 5.0, change second sentence of subparagraph to read as follows:

5.5.1 The rework document nunber'EE'en applicable, shall be entered in the "recarks" section of the TIR.

2.

Section 5.0, add new subparagraph to read as follows:

5.5.3 W en terninations cust be lifted in order to co=plete any construction activities, the conditions of paragraph 5.5.1 and 5.5.2 shall apply, except that document ne ber may be omitted. A 7

brief explanation of why termination was lifted and re-landed shall be entered in the "re= arks" section of the TIR.

l b

t I

r I

E. AFPROVED: 1 h Yu @

$ /h i

) *h ( W M

POCE DATE PFE

'D4TE i

Ahk P

oArE CCOCE DarE j,0 E 3_,

......,,.=. _

Jd PALO VERDE NUCLE AR CCNCR ATINC STATION PAGE OF PCN No.

UNITS 1,2 & 3 3,

PROCEDURE CHANGE NOTICE (PCN) gwpjp g oc, no, 255.0 10 ggy JOB NO.10407 TITLE: Cable Terninations CH ANG E R EQU ESTE'D BY:

OA COC OFE INITI ATE'O BY:

E. RE ASON FOR CH ANGE:

Clarification of how to lirt anc re-lano ter=1 nations af ter acceptance by the QCE when no NCR, DCP, DCN, etc. applies.

7. D ESCRIPTION OF CH AN GE:

1.

Section 5.0, add new subparagraph to read as.follows:

5.5.4 The lif ting and relanding of cables to satisfy the requirenents of k'PF/QCI No. 258.9, refer to para. 7.2 of sane procedure.

/

t, 9

~

8. AP? ROV ED: 5"?v1 A

Jh YW

&l/ht-w E

' CIA T E

/oATt t

roCE 0-Ys7$ Awu 6WFv "I*

rou o TE ccocE o 1t

,cf g _,gg

_n--_.--...

k

(

g h1 PALO VCRDC NUCLEAR CENER ATIN2 cTATICN PAGE OF PCN NO.

UNITO l. 2 O 3 3,

d PROCEDURE CHANGE NOTICE (PCN)

" wP/P @ OCI NO. 255.0 agy 11 JOB NO.10407 TITLE: Cable Termination 4.

5.

CH ANGE REQUESTED BY:

OA OC FE INITI ATED BY:

V. Mallen

,f

6. RE ASON FOR CH ANGE:

Clarifv Exhibit 255.0-1 (fr,ont) and Exhibit 255.0-2 (back)

, entries of JEB9999 or B9999.

7. DESCRIPTION OF CH ANGE:

f g t**',,,c 1.

Section 6.0, add subparagraphs to read as follows:

6.4 -

When TIR (Termination Inspection Record) card shows ock 8 thru 53 an alpha number B9999 (located front of card, right hand bottom) and same appears in line 5 (crimp tool serial number, etc.

in back of TIR), the QCE has the option to leave entry in, stamp and date QCE coluen or single line (B9999 or JEB9999), initial and f

datejand N/A QCE column and date.

NOTE:

Entry in line 5 numbered B9999 or JEB9999 is a non-crimp tool type entry, is a mechanical installation.

1

6. 4,F T.B.'s installation in JB's "Q" Class only, the QCE shall be responsible to verify T.B. 's installation is per Dwg.13-E-ZZS-002 and ensure T.B. counting cap screws and/or machine bolts are tightened at time of termination.

2.

Section 7.0, change paragraph (in part) to read as follows:

7.2 Exhibit 255.0-2 (Rev.

6).............

l 3.

Exhibit 255.0-2 (Rev. 6) revised (see attached).

8. APPROV ED: f " "

tw ll D

/

O h

POCE 6

OATE (E

DA E O

..r/

,uf r

lR PCAE DATE CCOCE CA'C gy l I !*

0

' ~

$-4.;.?

..:;.,y; p c.:.y y15;t g em.g.n ;pp:= ya gp W :=4 W pt.q ?p, a

' 9

..gy._

r -

%.*i'T N!~ ;;.Ci_'." '11*

  • M*2MR~O' MM'" ^ ' "' ^ " MM f ',7 '..' ~ ;

y; 'o. :

(

(

??

PCN NO. h

/ I#"

PALO VERDE NUCLEA CENER ATIN3 sT ATION PAGE OF

' y UNIT 31. 2 0 3 3,

II PROCEDURE CHANGE NOTICE (PCN)

@wP/P C OCl NO.

REV JOB NO. lo407 TITLE: Cable Termination 4.

5.

CH ANGE REQUESTED BY:

OA @OC FE INITI ATED BY:

V. Mallen

6. RE ASON FOR CH ANGE:

Clarify the responsibility for the, signature on the lower leit,f

. hand side of the card.-

t

7. DESCRIPTION OF CH ANGE:

1.

This PCN-upersedes FCN No. 30.

2.

Section 6., reinstate subparagraph 6.4.1 to read as follows:

6.4.1 Termination Engineer shall enter in remarks column the specific type of termination or spl, ice kit and lot number whenever a 5 or 15KV heat shrink kit is used.

3.

Section 6.0, add new subparagraphs to read as follows:

6.5.1 For lost or nisplaced cards, where a\\ previous card has been "CC",

"FI",

"QC", a new card shall be issced and identified with the t.

word " duplicate" on the front. The AFE shall obtain crimp tool-l S/N f rc= ce=puter print out and due date from calibration records.

Enter same on card. The Superintendent or his cesignee shall single lineout the word " installed" initial and date and enter above the lineout " verified". The card shall then be processed in accordance with this procedure.

6.5.2 For lost or cisplaced cards that have been previously terminated and no record exists of crimping tool, a new card shall be issued and identified with the word " duplicate" on the front. The ternination shall be reaccomplished and card shall then be processed in accordance with this procedure.

8 f APPROVEO:,

f.

/!. l 1N nJ

JCL, j

POCE DATE

'FE

'DA E

D

/ 0.

(.

nh, 4,.

ut e.

1

,['POAE D'A 1 E CCOCE CA1t ee-i,ae.isa,p(is.>,

CW S-2X L

l

~,%

6

.t t

e TERMINATl0N INSPECTION RECORD 1.0 AEX CONI)UIT INSTAI.I.ED. IF RE0111 RED.

22)

TER}lINATIOtl PER " CONTROL & 'lalACKIt'C SYSTEtt TER!!! NATION INSTALI.ATION CARI)".

1.0 TERillflAT10tl PER SPEC. 13-EM-306. REV.

(EXCI.llDING TESTINC).

.D sd)

TOROUE WRENCil S/N CAI.IllRATION DUE:

5,0 [ CRIllPIllC TOOI. S/N CALIBRATION DUK:

6,0 TERMINATIONS IDENTIFIED PER SPEC. 13-EH-301 REV.

u LO CAlti E TIED. SUPPORTEI). ANI) SEPARATEI) (IF REQUIRED).

!!.1)

CROUNDINC IS It!STAI.I.ED AS RE0llIRED.

j@FF,lMM M

JB(sW/T. B. 's INSTALLED PER DWG. 13-E-ZZS-UUZ Kt:.V.

H E E4 4 H MS:

o eur..sme.a.. nile.s.

.../....

SIONATuriEs 7,7,3,,

13111111T 255.0 (REV. 6 )..

. (uAcx)

V.

  • ,' f a'

~

lJ y ',

(

(-

1. g j ~5/,

\\

\\

/c'/

p.

h( h.( f $Y f

f N-I y

i i a

=

g.

INST L fbH FICATI N

_?

~~

~ ~..

FOR

,I

'~

CASLE SPLICING, TERMINATION AND SUP' ORTS,

FOR THE ARIZONA PUBLIC SERVICE COF2ANY PALO VERDE INCLEAR GENERATING STATION UNITS 1, 2 AND 3 QUALITY CLASS Q AND R I?g

'V

/44y tc 10 19g, SPECIFICATION NUMBER 13-EM-306

!!Og JOB NUMBER 10407 EECHTEL POWER CORPORATION

  • NORWALK. CALIFORNI A y

/\\

V\\

/\\

N 10-7-81 Revised Sections 7, 8, and 11, Figures 18 and 19. Added Figure 26.

Incorporated SCNs 2472, 2476, 2592, 2597, 2614 (MOD), 2638, 2652 (MOD),

b 2660, 2671, 2698, 2719, 2720, and 2766.

b 11-24-80 Revised Section 9.2, Added Figures 23, 24, and 25 and Incorporated b

SCNs 2267, 2374 and 2409 b

4-2-80 Revised Sections 1.0, 4.0, and 7.0 to 15.0, Tables 1 and 2, b

Figures 5, 7, 8, 11, 13 to 17.

Added Figures 21 and 22.

bl Incorporated SCN's 2046, 2109, 2136 (MOD) and 2149 12-10-79 Revised Sections 7.0, 8.0, 15.0 and Figure 4.

Incorporated bl SCNs 1887 (MOD) and 1951 (MOD) h l'9 3o.79 Ceneral Revision.

Incorporated SCN 1669.

6-h r

!.'-6-79 Issued for ccnstruction G

  • . C v.

I e-n.

. a s

,u 13-EM-306 k

t*

7.0 DESIGN y.t _

(y 7.1 General hhe following ' criteria shall be used for splicipg,,t'er'mination, separation, h

'fireproofin'g, repair, and support of cables specified in 3.0.

t

'7. 2 Criteria 2

f a.

Cable splices shall not be made on field run cables in power block except as.specified in 7.2.b and 7.2.c.

l l

b.

Cable splices may be made on Supplier equipment furnished pigtail cables within an enclosure approved for cable termination, such as cabinet, teminal box, or penetration box. Exception is pemissible only where equipment provided pigtail cables are not of sufficient length.

Splicing to equipment pigtail may be made within a condulet fittin.

=

Cable splices in boxes, cabinets or manholes other than as described c.

in 7.2b shall be authorized ~ on a case by case basis only.

Requests j

by Bechtel for use shall be documented by formal correspondence 5

betweenBechtelandClientengineqingandshownonanapproved l

I engineering document.

/A y

m d.

(De J.eteos

+

e.

(Deleted) hj,

.i,

q f

Grounding of cable shield shall be in accor, dance with 9.0.

f.

Class IE and Non-Class IE circuits shall require separation inside l

g.

an equipment enclosure in accordance with 11.0.

h.

" Field cabling shall be fireproofed inside an equipment enclosure in accordance with 11.5.

i.

Cable entering equipment enclosure shall be routed in the wiring channels provided in the enclosure.

Cable support required to relieve stress on cable splices and teminator shall be in accord-ance with 10.0.

j.

No aluminum armored teminators or support hardware materials shall be used inside containment building.

h.

Aluminum terminators shall not be used on any conductors.

1.

All terminal blocks in local terminal boxes or cabinets, used for temination of Class IE cable, shall be procured as' Quality Class IE ciaterial.

I/C No.14 AWG and I/C No. 10 AVG (Cable Codes A17 and A19) switchboard wires shall not be used as jumpers 5

in Class IE equipment inside the containment.