ML20084D395
| ML20084D395 | |
| Person / Time | |
|---|---|
| Site: | Turkey Point |
| Issue date: | 08/26/1974 |
| From: | Robert E. Uhrig FLORIDA POWER & LIGHT CO. |
| To: | Anthony Giambusso US ATOMIC ENERGY COMMISSION (AEC) |
| Shared Package | |
| ML20084D330 | List: |
| References | |
| NUDOCS 8304110145 | |
| Download: ML20084D395 (1) | |
Text
_ _ _ _ -. - _ _.. - _ _ _
e.o. sox sioo mAm, nomoA nioi l9
%@h<
FLORIDA POWER & UGHT COMPANY
}
1 i
August 26, 1974 1
Mr. Angelo Giambusso Deputy Director for Reactor Projects j
^ ~, Directorate of Licensing
< Office of Regulation
)
U. S. Atomic Energy Cossaission i
% Washington, D. C.
20545 1
Dear Mr. Glimbussor i
1 TURKEY POINT UNIT NO. 4 8
DOCKET No. 50-251 INSPECTION OF SAFETY RELATED HYDRAULIC PIPE RESTRAINTS Inspection of the safety related pipe restraints that are accessi-ble during power operation was completed on August 12, 1974, in
{
accordance with the continuing requirements of the Atomic Energy j
comunission Directorate of Licensing letter of November 8,1973.
i The inspection showed that fourteen out of fifteen restraints were
- I in satisfactory condition.
The hydraulic unit of one restraint located on the main steam piping had an indicated hydraulic fluid
.l level below the allowable limit.
This hydraulic unit was replaced l
with a spare unit.
1
{
The cause of the leakage is a mechanical wearing of the piston i
shaft seal.
The wear is caused by constant in and out movement of j
the piston shaft coupled with a slight cocking of the piston shaft due to the horizontal mounting of the restraint.
The horizontal mounting causes a downward force to be exerted on the unit just fron the unit's weight.
We have referred the problem to Bergen-Paterson and requested their assistance in providing a solution.
Very-truly yours, n
/
1
,/
-I Q j}
' h "/
} M #
l
^'
R. E. UhrLg g',_'[c,
4 Vice President
/,
s..,
REU/HNP/pam
[
j
,a n,
cci Mr. Norman C. Moseley l $ '.# 9
);
Jack R. Newman, Esquire
,9
^
D '%s( f,,
}T&gsc
- s 1
,,n l l
o I
8304i10145 741024 r
i PDR ADOCK 05000251 O
PDR C01'Y SENT REGION _
g
.r HELPING BUILD FLORID A
-..,.