LER 81-015/03L-2:on 810510,during Refueling Shutdown,Steam Flow Transmitter Was Out of Calibr Resulting in Less Conservative Hi & hi-hi Steam Flow than Required.Caused by Instrument Drift
ML20038B022
Person / Time
Site: Kewaunee Dominion icon.png
Issue date: 11/16/1981
From: Molzahn D
WISCONSIN PUBLIC SERVICE CORP.
To:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
Shared Package
ML20038B021 List:
References
LER-81-015-03L, LER-81-15-3L, NUDOCS 8111240610
Download: ML20038B022 (2)


Text

..,

t.lCENSEE EVENT llEl' ORT O

' CON THOL DLOCK: i l [ l l l l lh e

(PLEASE PRINT OR TYPE ALL REQUIRED 1% FORMATION) .

d1l O'l W 9 l 1LICENSEE l K lCODE N l P 14l 1 lgl0 l0 l -l 010 lb l 0 l 0 l 0 l - l 0 l 0 lg[4 l1 l1 l1 l1 l@l LICENSE NUMBEH l lg 25 26 LICENSE TYPE JJ 37 CAI br 2OM*T n

ol8l 8

S{ g l L jgl l 5l l l l l l 5 lgl 0 l 5 l 1 l 0 l 8 l 1 l@l 1 l 1 l1 l 6 l8 l1 l@

60 68 DOCKET NUM3EH 68 6'1 EVENT DATE 74 75 REI'OnT DATE 80 EVENT DESCRIPT!ON AND PROBABLt CONSEQUENCES h o l 2 l l Surveillance testing during refueling shutdown indicated that one steam flow transmitteg

, g was out of calibration resulting in Hi Steam Flow and Hi-Hi Steam Flow trip settings g

,  ; less conservative than T.S. requirements. TS 3.5.a. The other channels of steam flow g

, instrumentation were operable within T.S. lir.its and would have initiated steam line y

, isolation a s required. There was no ef fect on plant operation or public saf ety. ,

, , Occurrences of instrument drif t have been previously reported, y Olhl l l 8 9 80 SYSTEM CAUSE CAUSE CO'.t P.

CODE CODE SUBCODE VAtVE CCMPONENT CODE SUBCoDE SUCCODE og lI lB l@ lX l@ l Zl@ lI lN lS lT lR lU l@ l Tl@ lZ l@

O 9 to 11 12 13 18 19 20 SE QUE NTI AL OCCURRENCE REPORT l'EVISION .

LER/RO hVENT YE AR REPORT NO, CODE TYPE NO.

. @ RE7 R; l 8l 1l

_,, 21 22 l_

23 l0l1l5l 24 2G j ,,-l 27 l0 28 l3 l 23 lLl 30 j]

31 g

32 A E t7 A T CN O PL T ETH HOURS SB li O FO 4 BUS. SU PL1 MAN FACT nER

' 33 LEjg[34X J g {35Zjg l36Zl@ l 0 l 0 l 0 Yl22 {g 31 l lN lg [ Njg lB l 0 l 8 l 0]g 40 41 42 43 44 47 CAUSE DESCRIPTION AND CORRECTIVE ACTIONS h 1

101l I

'iTO l I

,y,yl See Attachment l

i t al I l 1 141 1 '

l' 8 9 80 STA S  % POWE R OTH E R STATUS Dl5 RY . OlSCOVER V OESCRIPTION NA 1 l5 l l Hl@ l 0l 0l 0l@l l lBl@l %rveillance Testing l A TiVITY CO TENT '

RELEASED CF RELEASE AMOUNT OF ACTIVITY LOCATION OF RELEASE i lc8] 9l Z l @ l Zlgl NA l l NA l

10 11 44 45 PERSONNEL EXPOSURES 80 NUY8ER TYPE OESCniPTION GTi' l'ol o l 01@l '

z l@l NA

_ l rERSONN E'L ,N,u'2 ES '

aU. gen oESCni, TION @

la l l N^

D D i I 11 l@l12 l BO LOSS OF OR DAMAGE TO FACILITY TYPE DESCRIPTION i l <s l [Zj@l NA l

8 9 '

8111240610 811116- 80 PDR ADOCK 05000305 NRC USE ONLY

'lOl etSUE l Na @DESCnIPTION s @PDR_ g  ; ; ; ; y , ; ; ; ; ; ; l ::

86 9 to 68 69 80 ;

D. J. Malzahn (414) 388-2560 o NAME OF PREPARER PHONE:

  • B Instrumentation drif t of the Barton Steam Flow Transmitter caused it to be in an out of calibratian condition. The transmitter was recalibrated and returned to service.

c A records review of the safety related Barton transmitters was conducted to identify calibration drif t characteristics. Where operational restrictions allou ndditional conservatism, the setpoints had previously been changed.

The drif t cannot be accurately predicted. These transmitters are presently within the scope of the equipment qualification program (IEB 79-OlB) and will be changed out as part of the long teza upgrade of transmitters. Because of redundancy of instrumentation for ESI activation no further action is required at thi/ time.