Selection of Permanent Hydrogen Mitigation Sys for Sequoyah Nuclear Plant
ML20008G336
Person / Time
Site: Sequoyah  
Issue date: 06/23/1981
From:
TENNESSEE VALLEY AUTHORITY
To:
Shared Package
ML20008G333 List:
References
NUDOCS 8107070329
Download: ML20008G336 (100)


Text

{{#Wiki_filter:9 4 lp-r t 4 4 4 i I SELECTION OF THE PERMANENT HYDROGEN MITIGATION SYSTEM FOR THE-SEQUOYAH NICLEAR PLANT TENNESSEE VALLEY AUTHORITY JUNE 23, 1981 .1 l 3 i e ~ 8107070329 810701 % l - PDR ADOCK 05000327.4 i..._ PDRJ P l

1.0 Introduction In the original operating license for Sequoyah Nuclear Plant unit 1, one of the conditions stated that "for operation of the facility beyond January 31, 1982, the Commission must confirm that an adequate hydrogen control system for the plant is installed and will perform its intended function in a manner that provides adequate safety margins." The present report is submitted to document the selection of controlled combustion using thermal igniters as the Permanent Hydrogen Mitigation . System (PHMS) for Sequoyah. The report is being submitted in June 1981 to allow for early review by the NRC staff and timely resolution of all issues before the January 31, 1982, licensing date. However, because of the satisfactory capability of the Interim Distributed Ignition System (IDIS) currently installed in units 1 and 2 at Sequoyah, its similarity with the PHMS, and beenuse of the tremendous expense associated with a forced-outage, TVA plans to request approval to complete installation of the PHMS components inside containment during the first refueling outage on each unit. 4 This report describes the various hydrogen mitigation concepts considered, evaluation criteria, and results of the evaluation. Note that a quantitative cost / benefit assessment, as originally proposed for each of the concepts selected for final evaluation, was not performed because no concept passed the preliminary

TABLE OF CONTENTS fage 1 1.0 Introduction

2.0 Background

3 30 Major and Other Concepts Considered 5 31 Major Concepts 5 3 1.1 Controlled Combustion Using Thermal Igniters 5 3 1.2 Controlled Combustion Using Thermal Igniters Enhanced 6 by Spray Fogging 3 1.3 Postaccident Inerting Using Halon 1301 6 3 1.4 Controlled Combustion Using Catalytic Combustors 6 32 Other Concepts Considered 7 3.2.1 Or.ygen Removal Using a Gas Turbine 7 3 2.2 Postacciient Inerting Using Carbon Dioxide 7 8 4.0 System Evaluation Criteria 5.0 Concepts Rejected for Permanent Hydrogen Mitigation System (PHMS) 10 5.1 Major Concepts Rejected 10 5.1.1 Controlled Combustion Using Thermal Igniters Enhanced by Spray Fogging 10 5.1.2 Postaccident Inerting Using Halon 1301 14 5.1 3 Controlled Combustion Using Catalytic Combustors 20 5.2 Other Concepts Rejected for PHMS 26 5.2.1 Oxygen Removal Using a Gas Turbine 26 5.2.2 Postaccident Inerting Using Carbon Dioxide 29 6.0 Concept Accepted for PHMS 31 7.0 Preliminary Details of the PHMS 36 7.1 System Design Requirements 36 7.2 Description and Justification of Igniter Locations 36 7.3 Operating Procedures 38 40 8.0 Ongoing Efforts

+ .o 2 evaluation except controlled ignition. In addition to the l selection process, preliminary details of the PHMS design are provided, and ongoing work in support of the system is described. W* 4 e i l l l \\ f I l i .. - - - ~,,., -. -, -,,.,. .,n,--.--_.-,--,-- ,,---n.,,,...,

4 3 2.0 - Background In February 1980, the TVA staff was requested by its Bos=4 of Directors to undertake a preliminary internal study of potential concepts suitable for mitigation of a degraded core event at Sequoyah Nuclear Plant. A report of the study was completed on April 15, 1980, and submitted to the NRC as Volume I of the Sequoyah Degraded Core Study on September 2,1980. During the intensive period of the study, several concepts and combinations of concepts were evaluated. These included concepts to prevent or minimize the effects of hydrogen combustion, such as preinerting with nitrogen, postinerting with Halon, or controlled combustion with igniters, and concepts to increase containment capacity for overpressure events such as augmented atmospheric cooling within the containment, venting containment to the atmosphere through a filter, to an additional empty containment, or to another reactor containment. Conceptual designs were developed for each of these mitigations based on best-estimate design criteria. Each of these mitigation strategies was evaluated on their effectiveness, technical feasibility, additional risk, reliability, and cost. In the event that a commitment to incorporate some mitigation of hydrogen effects became necessary, the report recommended controlled combustion i with igniters. In June 1980, a TVA commitment was made to enhance hydrogen mitigation at Sequoyah. At tb*', t ime, an Interim Distributed Ignition System (IDIS) was developed based on the best information available about postaccident containment 2.. .- - - -. - ~.

L 4 response to a hydrogen release, its distribution, and combustion. A detailed report on the safety evaluation of the IDIS was submittad as Volume II of the Sequoyah Degraded Core Study on September 2, 1980, that included a description of the system, those evento for which it was designad, the physical phenomena associated with hydrogen combustion, the pertinent containment processes and design, the expected distribution of hydrogen in the containment, the anlaysis of containment conditions during controlled combustion of hydrogen, and the resulting environmental impact on containment structures and equipment. Following igniter durability testing at TVA's Singleton Laboratory and igniter hydrogen combustion perforinance testing at Fenwal, Incorporated, and in response to NRC requests for further information, a revised version of Volume II was submitted on December 15, 1980. Through these submittals, "TVA ... by testing and analysis show(ed) to the satisfaction of the NRC staff that an interim hydrogen control system will provide with reasonable assurance protection against breach of containment in the event that a substantial quantity of hydrogen is generated" as required by the Sequoyah unit 1 operating license. TVA has continued its twsearch and anlaysis efforts in the mean time and submitted quarterly reports on the work as required by the operating license. Also in response to a condition in the license, TVA has recently submitted (May 31, 1981) a report resolving all equipment survivability issues related to controlled combustion of hydrogen inside containment.

5 30 Major and Other Concepts Considered Based on the information we assembled for Volume I of the Sequoyah Degraded Core Study (see section 2.0 above) and current thinking in the industry, four major hydrogen mitigation concepts were selected for evaluation as a Permanent Hydrogen Mitigation System (PHMS). These included controlled combustion using thermal igniters, controlled combustion with thermal igniters. enhanced by spray fogging, postaccident inerting using Halon 1301, and controlled combustion using catalytic combustors. Each of these concepts will be described briefly in the following and evaluated in detail in section 5.0. In addition, limited evaluations have been made for an oxygen removal cencept using a gas turbine and for a postaccident carbon dioxide inerting concept. Results of these evaluations are also included in section 5.0. 31 Major Concepts 3 1.1 Controlled Combustion Using Thermal Igniters The controlled combustion concept has been explored in detail over the past year since TVA introduced its Interim Distributed Ignition System (IDIS). The concept, as evaluated for the PHMS, is similar in purpose: to ignite hydrogen at concentrations near the lower flammability limit to ensure small stepwise or continuous burning in order that the energy addition rate to the containment may be moderated as much as possible. However, the system evaluated for the PHMS had additional and relocated igniters, potentially different types of thermal igniters,

4 1 6 improved reliability and availability, and operator actuation from the main control room. 3.1.2 Control Combustion Using Thermal Igniters Enhanced by Spray Fogging Very fine microfogs have been proposed as a means to inert a containment postaccident against hydrogen combustion. However, the concept evaluated by TVA for the PHMS consisted of larger droplet fogs used instead as a heat sink in conjunction with igniters to extend the containment capability to accommodate hydrogen combustion. The spray fog systed evaluated for the PHMS consisted of spray headers in both the upper and lower compartments and associated oump" controls to provide a continuous, dense fog f, lowing degraded core events. 313 Postaccident Inerting Using Halon 1301 Following a degraded core accident, Halon 1301 could be added to the containment atmosphere in sufficient amounts to inert it against hydrogen combustion. The i system considered for the PHMS consisted of discharge l headers, supply tanks, accumulators, and controls to allow the rapid postaccident injection of Halon. 3 1.4 controlled combustion Using catalytic combustors An alternative method for recombining hydrogen following a degraded core accident uses catalytic action to enhance and accolerate the process. Two catalytic combustor applications were considered fer the PHMS. One involved using a combustor on the

3 ~ 7 discharges of the reactor vessel vent and the pressurizer relief line and the other used combustors in the general open containment volume. 32 Other Concepts Considered 3 2.1 0xygen Removal Using a Gas Turbine Reducing the overall containment oxygen concentration could prevent the uncontrolled combustion of hydrogen following an accident. Gas turbines have been proposed as a postaccident means to eliminate sufficient oxygen. 3.2.2 Postaccident Inerting Using Carbon Dioxide Similar to Halon 1301, carbon dioxide could be added in sufficient enounts to the containment atmosphere following a degraded core accident to inert it agair.st hydrogen combustion. ~. - -, ,,,a.

W 4 i 8 4.0 System Evaluation Criteria Several criteria were used to compare the suitability of each of the four candidates for the PHMS outlined in section 3.1. The comparisons were qualitative in nature and attempted to arrive at a suitable balance of the factors described in the remainder of this section. First, the concept selected for the PHNS must satisfy the condition in the Sequoyah operating license that requires that "for operation of the facility beyond January 31, 1982, the Countission must confirm that an adequate hydrogen control system for the plant is installed and will perform its intended function in a manner that provides adequate safety margins." An adequate hydrogen mitigation system would be effective in reducing the risk from reasonable accident scenarios such as proposed in the interim rule on October 2.,1980. Specifically, "the maximum duration for hydrogen generation was specified to be eight hours . (and) an upper Ibnit of 75 percent should be used for the percent of fuel clad that reacts to produce hydrogen." In addition, the original plant margins of safety should be maintained, if possible, even for chese accicents beyond the design basis. The concept selected for the PHMS should be flexible in application and suitable for further enhancements should such features become available and are believed to be necessary. In addition, the selection should not irrevocably commit the plant to 1 system with severe limitations pending the outcome of the

4 h 9 proposed generic rulemaking on the issue of d'egraded core accident mitigation. The selected concept should be feasible for immt '. late implementation without requiring extensive further development. No major unresolved technical issues should remain in the functional or implementational capability of the concept. The concept should be able to be designed, procured, installed, tasted, and approved by January 31, 1982. The concept should have minimal impact on existing plant systems providing support functions or features such as physical layout. The concept selected for the PHMS should avoid adverse 4 operational impacts. Specifically, life safety, effects of inadvertent operation, potential uncertainty of the operator to manually initiate operation, performance monitoring requirements, preoperational and surveillance testing, maintenance, and reliability should be considered. Finally, the concept selection should minimize cost associated with design, hardware, construction, downtime, operation, and maintenance.

+ 10 5.0 Concepts Rejected for PHMS 51 Major Concepts Rejected The four hydrogen mitigation concepts outlined in section 3.1 were evaluated qualitatively based on the PHMS selection criteria discussed in section 4.0. Based on that evaluation, controlled combustion with thermal igniters enhanced PT spray fogging, postaccident inerting using Halon 1301, and controlled combustion using catalytic combustors were eliminated from consideration for the PHMS. Details of the evaluations are presented in the rest of section 5.1. 5.1.1 Controlled Combustion Using Thermal Igniters Enhanced by Spray Fogging As stated in section 31.2, spray fogging could be used in conjunction with a controlled combustion system using thermal igniters. Since the fog would serve as an additional heat sink for containment pressure suppression and the resulting turbulence would aid igniter effectiveness, fog addition should accommodate a higher rate of hydrogen combustion. Our conceptual design of the igniter / spray system included redundant spray headers and thermal igniters in all areas of the upper and lower compartment. The spray razzles in the present containment spray system in the upper compartment could probably be replaced to produce the desired nominal droplet size of 100 mic rons. The spray system would require additional i redundant pumping capacity to maintain a drop I density of 0.05 percent by volume. The thermal y .4 ,m, ,,.. _ - - - - -, -... -. ~. -, __

11 igniter system would be identical to that described in sections 3 1.1 and 6.0. Since TVA believes that a controlled combustL:,n system using thermal igniters would meet the operating license condition of being an " adequate hydrogen control system" (see section 6.0), we believe that an enhancement of that system with spray fogging wo tid also be adequate. Similarly, it would satisfy the interim rule and maintain an adequate margin of safety in the containment pressure capability. An enhanced system should have even more flexibility to mitigate a broad spectrum of hydrogen transients that might result from the degraded core rulemaking. N' wever, there remain enough unanswered questions about the true magnitude of the enhancement and whether a practical system could be installed to maintain the required droplet density against the ~ effects of agglomeration and rainout to have caused TVA to reject igniters enhanced by spray fogging for the PHMS. l The spray fogging concept is not feasible for immediate implementation at Sequoyah. is not known presently how much pressure suppression capability the addition of the spray fog system would contribute. The conceptual design called for 100 micron drops distributed throughout the containment. . _ ~ _ _. _ _. -. _ _ _.,... _

e 12 This would yield benefits mainly for burns occurring in the lower compartment since the present containment spray system already would produce a spray in the upper compartment with a median drop size of 200-300 microns. The latest theoretical and analytical predictions indicate tent controlled combustion would generally occur more often in the ice condenser upper plenum than in the lower compartment. In addition, the losa rates for turbulent containment scale fogs of this droplet size are unknown but may be so large as to make the ptmping requirements impractical. Sandia National Laboratories state in NUREG/CR-1762, " Analysis of Hydrogen Mitigation for Degraded Core Accidents in the Sequoyah Nuclear Power Plant," that "the suspension of a large mass of water droplets in the containment atmosphere for an extended time may be the most difficult technical problem with fogging. This issue must be settled before fogging systems can be designed." The makeup supply system to maintain a fog of specified density would haia to be sized based on the currently unknown loss rate. These issues certaic'.y could not be resolved ~ consistent with the January 31, 1982, license condition. The addition of a spray fogging system could have a significant impcot on the existing plant. System

9 13 requirements would include space for ptmps, containment penetrations, a system of spray headers and nozzles that could be quite elaborate, and accompanying instruments and controls. The electric power requirements for the additional ptmps could be substantial and force additional emergency diesel capacity to be obtained. An analy sis of the negative pressure following inadvertent spray would also be required. The impact on operations of an igniter / spray system should not be severe since the or.ly undesirable effects of inadvertent opesation would be containment depressurization which could be avoided through pressure relief modifications. The spray system would have to be activated early enough in the accident to allow the steady-state fog density to be achieved. Preoperational testing of the system would be of a fairly standard type for a mechanical fluid system except that air instead of water would be used to verify that flow to each nozzle was unobstructed. The surveillance test would consist of powering valves and pumps. Maintenance would consist of routine mechanical servicing of pumps and valves. A small amount of plant downtime might be associated with this testing and maintenance. Reliability of a , - _. _.... ~., _ _ _.,

14 redundant spiay fogging system should be good and on the order of any other large, electrically-powered mechanical fluid system. A spray fogging system could be relatively expensive if an extensive nozzle system or large pumps are required and if installation ar.d downtime are considered. In conclusion, the use of spray fogging to enhance the performance of controlled combustion with thermal igniters was rejected by TVA because of the uncertain magnitude of the improvement and the unknown spray droplet loss rate required to size the system. Efforts underway to help TVA quantify these two parameters are described further in section 8.0. 5.1.2 Postaccident Inerting Using Halon 1301 As stated in section 3 1 3, Halon 1301 could be injected into the containment following a degraded core accident to inert the atmosphere against hydrogen combustion. Halon 1301 (CF Br) is a 3 halogenated hydrocarbon that was selected as an inertant because of several favorable qualities. While most gases used for this purpose work by diluting oxygen below the mixture's flammability limits, the Halons work by chemically interrupting the combustion process. This effect results in less Halon 1301 being needed to inert a given volume than

15 other inertants such as nitrogen or carbon dioxide. In addition, there is considerable experience with Halons since they are widely used in commercial applications for fire suppression. Halon 1301 also has the desirable property that it can be stored as a liquid under pressure but vaporizes. rapidly when depressurized. Based on their prior studies and experiments on reactor containment inerting with Halon 1301, Atlantic Research Corporation ( ARC) was selected to perform a conceptual design study for an ice condenser inerting system and to adartss inadvertent actuation, long-term accident recovery, Halon decomposition, water chemistry, a'nd corrosion potential. Their final report is included as Attachment A. As st own in figure 6 of that report, a conceptual system could consist of four Halon tanks and a backup, each pressurized by individual nitrogen accumulators to maintain the Halon as a liquid and propel it into the containment when necessary. The spray headers and nozzles would be located in upper and lower compartments to ensure that the entire containment would receive enough Halon to inert each region. Th' system piping and discharge pressure was sized to allow the containment to be inerted within 1000 seconds after injection began. l e._ ,,_.v_. ,.._-._mm,-._.

9 16 TVA believes that a Halon postinerting system would, in principle, meet the operating license condition of being an " adequate hydrogen control system." It would also satisfy the requirements proposed in the interim rule and should maintain an adequate margin of safety under the containment ultimate pressure capability. In addition, assuming the Halon could ba injected rapidly enough, it should have the flexibility to inert against a broad spectrum of hydrogen transients ti.at might result from the degraded cora rulemaking. However, there are fairly severe drawbacks to the actual implementation and use of a Halon system that have caused us to reject it for the PHMS. The Halon 1301 postinerting concept is not feasible for insnediate implementation at Sequoyah. Following its use after an accident, a portion of the injected Halon would dissolve in the sump water inside containment. Enough additional Halon could be initially injected to overcome this loss, but the dissolved Halon would radiolytically decompose to form HF and HBr in low concentrations (1200 ppm and 400 ppa, respectively). In addition to general acidic corrosion, potentially severe stress corrosion cracking of stainless steel piping could occur due to the presence of these halides. From section 6.3 of Attachment A, "without treatment... potential exists for the following detrimental effects:

i 9 17 Probable stress corrosion cracking of stainless steel of neated surfaces. Possible stress corrosion cracking of stainless steel in water held above 150 F for an extended period. Extensive crevice corrosion, pitting and galvanic corrosion initiated during the period of low pH and high temperature perpetuated by increased conductivity of the water and presence of bromide ion." However, the report goes on to say, "with treatment Halon decomposition may be avoidable by addition of dcomide ion (NaBr, KBr, LiBr); likewise, the pH depression may also be avoided. Either of these should mitigate the general corrosion and reduce the potential for stress corrosion cracking. Inhibitors can be added which may prevent localized corrosion." Despite ARC's statement in section 1.0 of Attachment A that " potential corrosion of metals in the primary and secondary cocling systems... is not a safety J i question but rather an economic matter related to f system recovery after a LOCA," TVA believed the issue was definitely one of long-term operability and safety and deserved further study. Therefore, we performed experiments at our Singleton Materials Engineering Laboratory to investigate the (

18 metallurgical effects on SS304 of squeous bromine and fluorine solutions in the concentrations predicted by ARC. The test reports are included in this report as Attachment B. The test results show these environments to be very aggressive and that the straight unbuffered solution caused heavy, intergranular attack. Even when buffered, as suggested above by ARC, the solutions resulted in heavy pitting. Note that these tests were conducted at 200 F because of the unavailability of an autoclave. In practice, the specimen would see system temperatures of up to 650 F and attack would be expected to be even more severs. Based on the effects on the sensitized samples (representing weld areas), long-term postaccident system integrity would be questionable. An extensive development and testing effort would be required to identify whether a suitable postaccident water chemistry control method existed and to demonstrate its effectiveness. The issue certainly could not be resolved consistent I with the January 31, 1982, license conditions. ( l The addition of a Halon postinerting system would have a fairly sizable impact on the existing plant. Space would have to be allocated for the five Halon tanks and their five nitrogen accumulators, two I containment penetrations would have to be added, an l l extensive system of injection headers would be

1 l 19 required to ensure timely coverage of each compartment, and enough instrtsnentation and controls to initiate system injection and monitor its performance would be necessary. The impact on operations of a Halon postinerting system could be severe. Stringent guidelines for system activation would be required to prevent i inadvertent actuation during personnel occupancy since only about ten minutes would be available to evacuate before physiological harm results. Inadvertent operation would also dump the relatively expensive Halon and require several days of purge and cleanup. These impacts would naturally cause the i operator to be hesitant about manually initiating the rystem even during an event when it might be needed. Since the effectiveness of Halon inerting depends on I l complete achievement of the required concentration everywhere in the containment, the partial or local injection that might result from a late actuation could still allow uncontrolled hydrogen combustion to occur. This condition would be compounded by the additional pressure from the presence of Halon and l I thermal decomposition products from the high I combustion temperatures. In addition, it is not certain that for all events leading to ' ydrogen release, the warning signs available to the operator would be both unmistakable enough to require Halon

20 injection and early enough to allow it. Operator reluctance and unclear guidelines are major drawbacks to the u.ne of Halon. Preoperational testing of the system would verify valve operability and obstruction-free flow (of air) to each nozzle. The surveillance test would consist of powering valves and verifying sufficient accumulator pressure. Maintenance would consist of routine mechanical servicing of the valves. Little plant downtime would be requid for this testing and maintenance. ' Reliability of a Halon system with a backup tank and re@ ndant valves should be very good since it is a passive system after valve cycling. A Halon postir.seting system would be relatively cxpensive when costs of the Halon itself, the system hardware, installation, and downtime are considered. l In conclusion, the use of Halon postaccidr7t inerting ( l for the PHMS was rejected by TVA because of probable I i long-term corrosion effects and operational uncertainties and is not being considered furt'.ter. ( l l 5.1 3 controlled combustion Using catalytic combustors l l As stated in section 31.4, a method of controlled combustion alternate to thermal or spark ignition uses catalytic combustors. The catalytic combustor [ operates by providing a noble metal substrate to i

21 facilitate the rea'ction of hydrogen and oxygen to form water vapor. Compared to a thermal recombiner, a catalytic combustor operates at a higher flow rate for a given size and should be effective at lower and higher concentrations of hydrogen. The conceptual design for the catalytic combustor system consisted of a combination of two distinct applications. One type of combustor would be located in the discharge of each vent from the reactor coolant system (such as reactor vessel head vent and pressurizer relier line) to burn hydrogen before it would be released to the contaminant. Another combustor type would be located in the general containment volume to buru any hydrogen in the atmosphere. A fairly sophisticated mixing system would be required to remove moisture and add air to obtain a fuel / air mixture in the operating range of the vent combustors. A forced-air induction system would be required to achieve a reaconably fast throughput rate in the containment combustors. Either supplemental cooling or an exhaust gas distribution system would probably be required for l either type of application to prevent local heating problems. In theory, the catalytic combustor concept would satisfy the operating license condition of being an f f-r -a y y m

c-22 " adequate hydrogen control system." It also would meet the requirements proposed in the interim rule and maint.-in an adequate margin of safety in the containment pressure capability. However, the concept is not suitably developed to be accepted as the PHMS for Sequoyah. Under ideal operating conditions, controlled combustion using catalytic combastors may be slightly more flerible in mitigating any hydrogen transients that might result from rulemaking than controlled combustion using thermal igniters. This is because 'mder ideal conditions (in the absence of any S cLtalyst poisons), the catalytic combustor would operate efficiently at lower hydrogen concentrations. l ( Following a degraded core event, the containment atmosphere could contain some amounts of core fission products. One of these, methyl iodide (CH I ""* 3 selectad as the basis for catalyst poisoning experiments performed for TVA by Acurex Corporation. The studies showed that combustors could remove hydrogen from the inlet stream at high efficiencies and velocities in the absence of methyl iodide. However, at concentrations that could be expected in the postaccident containment atmosphere, the catalyst was easily poisoned and eventually deactivated by the i i

23 methyl iodide. This effect was dependent on both methyl iodide and hydrogen concentrations. It was especially pronounced at the low hydrogen concentrations where the prospect of using the catalytic combustor had been proposed as being particularly attractive. Poisoning at low hydrogen concentrations would eliminate the major advantage of catalytic combustors over thermal igniters for controlled combustion. The design of a practical steam removal and air addition mechanism upstream of the vent combustor would be a difficult obstacle considering the variable water, steam, and hydrogen flows that could be expected in the vent line. Unless the mixing device was able to add sufficient tiir, unburned hydrogen could pass through the combustor and into the containment. A more serious problem could be the potential for not sufficiently diluting mixtur9s containing high concentrations of hydrogen before l causing ignition. i The poisoning experiments performed by Acurex care l bench-scale. Since the poisoning proceeded gradually along the axis of the catalyst bed, it was proposed that merely extending the length of the catalyst as much as necessary to allow for the maximum expected deactivation could overcome the poisoning problem. i

9 24 However, TVA believes more accurate predictions of anximum atmospheric fission p: odue ; concentrations and larger scale catalyst tests would be necessary before such basic required information as the nianber and size of combustors could be reasonably assured. The impact on plant features could be significant if several containment combustors and an accompanying forced-air induction system were required. Space, power, and cooling or distribution requirements cannot be determined at this time but could be sizable. The impact on plant operations of a combustor system should not be severe. The containment combustors would have to be activated before hydrogen release to the containment would be expected similar to initiation of controlled combustion using thermal igniters. Inadvertent actuation would not cause any major problems. The vent combustor mixing device should be. automatic since the operator could not be expected to provide control under rapidly changing conditions. Preoperational testing of the system would verify the fan flow rates and the cooling system (if required) heat removal rates. The surveillance test would consist of. powering the fans and the vent combustor

4 - 25 mixing device. The maintenance would be of a routine mechanical nature unless the catalyst bed required regeneration or replacement. Some plant downtime would be required to perform this testing and maintenance inside containment. Reliability of a catalytic combustor system should be good unless the catalyst bed performs poorly since the rest of the system is like any other active mechanical system. The cost of a catalytic combustor system cannot be determined at present since the materials and quantities have not been specified. However, the cost of a number of large, platinum combustors with an extensive forced-air induction system and cooling or distribution system could be fairly sizable. In addition, the research program that would be necessary to develop a practicsl, proven catalytic combustor, '4 be relatively expensive. 1 In conclusion, due to the poisoning effects observed at low concentrations of hydrogen, controlled combustion 091ng catalytic combustors does not appear to be superior to controlled combustion using thermal igniters. In addition, not enough information is known about the sizes and numbers of containment combustors or the design of the vent combustor mixing device to judge whether a practical cystem could eventually be developed. Since these issues

26 definitely could not be resolved consistent with the January 31, 198?, license condition and since the catalytic comaustor system does not appear to be superior to a thermal igniter system, TVA has rejected catalytic comousters for the PHMS for Sequoyah. 5.2 Other Concepts Rejected far PHMS 5.2.1 0xygen Removal Using a Gas Turbine A mixture of air and hydrogen can be rendered nonflammable by reducing the oxygen concentration below 5 percent. Gas turbines have been proposed as a means to rapidly inert the containment by reducing the oxygen level following a degraded core accident before hydrogen could be releasd. Such a system would involve one or more turbines, fuel supply lines, and monitoring instrumentation and controls. It would require an additional forced-air induction system with fans and associated ductwork. It should also include its own supplemental cooling to avoid impacting the containment heat removal capability. Using a representative fuel such as methane as

followJ, 20 i CO

+2H O CH4+ 2 2 2 estimates were made of some of the combustion parameters. In order to reduce the containment l oxygen concentration from the original 20 percent to the required level of 5 percent (conservatively l neglecting the addition of CO ), two tons of methane t

l l 27 i would be required and 82 million BTU would be l generated. To inert the containment within 30 minutes, an average airflow of 54,000 scfm would be i required. The installation and operation of a gas turbine oxygen removal system would have a significant impact on existing plant systems and features. Several major auxiliary systems would be required to support operation of the turbine. First, a forced-air circulation system with extensive ductwork would be necessary to allow high volume throughput. Maintaining a steady, dry combustible air / fuel mixture even with such a circulation system would be difficult under postaccident containment conditions. As the overall oxygen concentration became leaner, [ airflows much higher than the 54,000 scfm would be required to prevent flaneout and restart. A number of other auxiliary systems would be needed to support r turbine operation such as cooling of the lubricating oil and the combustion chamber walls. Finding ' adequate space in the lower compartment of the containment for the gas turbines and these supporting systems would be difficult. i The 82 million BTU heat load would be comparable to the heat load f 9m combustion of the amount of i. hydrogen generated by a 75-percent metal-water i 1 -... ~ , ~.. _ _.. _. _,. -. - -....., _.. - _., ~ -... _ _. _.,.. _.. - _. _... _. _,

4 28 reaction (1500 lbs H ). However, unless several i 2 distributed gas turbines were used, the local heating effects from rapid inerting could be severe if supplemental cooling were not provided. In addition, the gas turbine would pose other hazards to the containment or equipment, including the presence of a flammable fuel and the potential for internal missile generation. The reduction in the volume of noncondensibles in the containment due to depletion of the oxygen concentration could necessitate opening the vacuum relief valves to avoid exceeding the negative pressure capability. Opening these valves would introduce air which could deinert the containment after hydrogen had been released. Also, it would not be desirable to have to defeat any containment isolation feature. Preventing the formation of a flammable mixture during long-term accident recovery and hydrogcn disposal could be a difficult problem. Since purging the containment with air would have to be avoided, provisions for nitrogen (or some other inertant) purge would be required. For the gas turbine system to inert the containment by the time hydrogen could be released, it must be initiated in time to perform its function. The previous estimate of 30 minutes to deplet6 the oxygen is probably a reasonable minimum time. It would be

29 difficult, for all scenarios, for the operator to determine that the event was serious enough to warrant initiating the gas turbine that far in advance of hydrogen release into the containment. In addition, the operator would naturally be reluctant t to activate a system that would impose such a heat load, cause ice t eiting, and force a plant shutdown for several montha until he was absolutely sure it was necessary. In summary, our evaluation of the oxygen removal

oncept using gas turbines has identified major impacts on existing plant features, potentially asvere local heat loads, fire and missile hazards, and perhaps most important, undependable actuation of the system when needed. These drawbacks prevent the further consideration of gas turbinea for hydrogen mitigation.

l 5.2.2 Postaccident Inerting Using carbon Dioxide l l As stated in section 3 2.2, carbon dioxide (CO ) 2 could be injected into the postaccident containment atmosphere in sufficient quantities to inert against the eventual release and combustion of hydrogen. Such a system would be very similar to the Halon postinerting system described in section 5.1.2. The 1 evaluation in that section would be applicable to a C0 system except that more CO would be required to 2 2

30 inert the containment and that no corrosion problems would result from the use of CO. The excessive 2 pressure resulting from the additional amount of gas required is the major drawback associated with the CO2 postinerting concept. A comparative analysis of the physical properties of Halon, carbon dioxide, and nitrogen and the containment pressures following their injection was submitted in Appendix C of TVA's first quarterly progress report December 15, 1980. This analysis showed that the overall pressure following CO inje tion after a degraded core 2 accident would be well above the containment design pressure. The deliberate overpressurization of the containment above its design pressure was rejected by TVA for use at Sequoyah, especially since other hydrogen mitigation methods such as controlled combustion using thermal igniters would be able to prevent excessive postaccident pressures. i I i I i a

4 31 6.0 Concept Accepted for PHMS Controlled combustion using thermal igniters has been selected by TVA as the only suitable candidate for the PHMS. As stated in section 3 1.1, this concept is the same one employed by TVA in the Interim Distributed Ignition System (IDIS) that has been installed in Sequoyah units 1 and 2. The operating principle is straightforward: to reliably ignite hydrogen throughout the containment at concentrations near the lower flammability limit to achieve periodic or continuous lean burning in order that the energy addition rate to the containment may be distributed as evenly as possible throughout the duration of the hydrogen combustion part of the accident. Since the containment pressure response is rate-dependent, this moderated energy addition rate would allow the active and passive containment heat sinks to absorb the. heat of combustion more effectively and reduce the overall containment pressurization. The design of the thermal igniter system as evaluated for PHMS selection is described in some detail in section 7.0. The basic design as presently contemplated includes a total of 60 igniters in two trains distributed throughout the ccritainment with at least one pair of redundant igniters located in each region. Manual control capability is provided in the main control room. TVA believes that, in principle and in practice, a controlled combustion system using thermal igniters would satisfy the operating license condition of being an " adequate hydrogen control system... that provides adequate safety margins." It

~- i - 0 32 has been demonstrated to meet the requirements of the interim rule. In additior. analyses have shown that a margin of safety is maintained below the containment desian pressure for a small break LOCA (S D). The thermal igniter system should have good 2 flexibility to mitigate other hydrogen transients that might be stipulated in the rulemaking and still maintain a margin of safety below the containment ultimate capability. Enhancements such as spray fogging are potential additions if necessary and feasible. The thermal igniter concept is feasible for insnediate implementation at Sequoyah. Based on testing and extensive analyses performed for the IDIS over the past year by TVA and others, the major issues have been identified and resolved and the system design parameters have been well established. TVA T believes that any remaining issues could be resolved and NRC confirmation obtained consistent with the January 31, 1982, license condition. However, as noted in section 1.0, due to the protection capability of the currently installid IDIS and to avoid a forced shutdown for modifications inside containment, TVA plans to request approval to replace the IDIS with the PHMS at the first refueling outage on each unit. l l The implementation of an upgraded thermal igniter system would not have a major impact on present plant features or systems. Nominal amounts of normal and emergency electrical power would be i required, along with containment penetrations for the power l supplies. One switch per train of igniters would be required in l ..___,..-~..,._.,._....,.,_,m. -.,..,.,,._.-.m.,--._.,_..,,..m._-.

'O 33 the main control room. Existing containment instrumentation would be adequate to monitor system performance. No additional cooling capacity is required since the thermal igniter system is designed to depend on the ice condenser and containment sprays for cooling. Likewise, no added forced circulation is required since the air return fans do an acceptable job of mixing and distribution. Licensing issues to be addressed to support the addition of the upgraded thermal igniter system should not be extensive since TVA has already made a number of submittals during the past year that satisfactorily supported TVA's position that the IDIS provided, with reasonable assurance, protection against breach of containment. For example, resolution of the equipment survivability and local detonation issues were adcressed in TVA's report submitted to the NRC in May 1981. The impact on operations of a thermal igniter system would not be severe. The system poses no threat to personnel since it is not required during normal operation and would normally be deenergized. Inadvertent actuation of the syste7. during any phase of plant operation presents no threat to personnel or equipment. This would prevent reluctance by the operator to activate the system and would enable him to activate it at a point in the acaident before hydrogen could be released *.; the containment. The relatively short warmup time for the thermal igniters following acti"ation would contribute to the high likelihood of their availability.

1 l l 34 i f. Preoperational testing of the thermal igniter system would involve verifying that individual igniter temperatures were adequate. At that time, the current in each circuit would be recorded as a baseline for future use in surveillance tests. The complete igniter system will be periodically tested. This test, consisting of measuring the current in each circuit and comparing it with the original baseline, can be performed at the electrical distribution panel outside containment and can detect the failure of one or more igniters. Mnintenance on the thermal igniter system is expected to be minimal since the system consists of electrical components such as thermal igniters (heaters), transformers, circuit breakers, control switches, indicating lights, and electrical cables that do not require adjustment or periodic replacement. The reliability of a thermal igniter system should be extremely good since there are no moving parts (other than switches) or no variable controls'(just ON/0FF). The cost of design and hardware should be moderate for a thermal igniter system since the technology is prove and does not need extensive development. Installation costs should not be excessive if the work is performed du"ing the first refueling outage instead of during a special forced outage. In conclusion, after examining a number of hydrogen mitigation concepts and evaluating controlled combustion using thermal igniters enhanced by spray fogging, postaccident inerting using

35 Halon 1301, and controlled combustion using catalytic combustors in particular, TVA has selected controlled combustion using thermal ignitors for the Pennanent Hydrogen Mitigation System at Sequoyah. Although a considerable amount of e-:arience has been accumulated with the thermal igniter concept through work on the IDIS, as described earlier, TVA is pursuing additional confirmatary studies which are outlined in section 8.0. e

36 i 7.0 Preliminary Details of the PHMS l As described in the previous section, controlled combustion using thermal ignitors has been selected for the PHMS at Sequoyah. Design of the system is currently underway. Preliminary information about the system implementation is provided in this section including a design requirements document, a description i and justification of igniter locations, and basic operating procedures. 7.1 System Design Requirements The design requirements document used internally by TVA is provided as Attachment . 7.2 Description and Justification of Igniter Locations The principle of the controlled combustion concept selected for the PHMS is to ignite hyd s gen at any containment location as soon as the concentration exceeds the lower flammability limit. To assure this, a total of 60 igniters will De distributed throoghout the msjor regions in which hydrogen could be released or to which it could flow in significant quantities. There will be at least two igniters, powered from separate trained source % generally located near the top of each of these regions. See figures 2 through 8 in Attachment C for igniter locations. t l Following a degraded core accident, any hydrogen which is l I produced would be released from a break or the pressurizer l' I relief tank into the containment in the lower compartment inside the crane wall. To cover this source region, there will be 18 igniters (equally divided between trains) located

37 high in the lower compartment inside the crane wall. Four of the igniters will be equally distributed around the interior of the crane wall between ice condenser inlet doors at elevation 730'. Two ignitors will be located at the lower edge of each of the five steam generator and pressurizer enclosures at elevation 731'. A pair of igniters will be located in the top of the pressurizer enclosure at elevation 772'. Another pair of igniters will be placed above the reactor vessel in the upper reactor cavity at elevation 730'. Since there are no potential hydrogen sources in the steam generator enclosures and significant flows into these enclosures are not expected from the rest of the lower compartment, igniters will not be located in the top of these enclosures. The pair of igniters located at the entrance to each steam generator ennlosure would ignite My flammable mixtures that may pass by them. Any hydrogen not burned in the lower compartment would be l carried up through the ice condenser and into the upper l compartment. To cover these regions, there will be 22 igniters (equally divided between trains) located in the ice condenser and the upper compartment. Since steam would be removed from the mixture as it passed through the ice bed, l l thus concentrating the hydrogen, a nonflammable mixture in l j the lower compartment could become a flammable mixture in l the ice condenser upper plenum. To provide controlled combustion in this region, four igniters will be equally l

l l ) 38 distributed around the upper plenum at elevation 792'. Six more ignitors will be equally spaced on the crane collector rails above tM ice condenser top deck blanket at elevation 809'. Four ignitors will be located around the upper compartment dome at elevation 846'. Four more igniters will be spaced around the inside of the crane wall below the upper plenum exit at elevation 787'. An "A" train igniter will be located above the "A" train air roturn fan at elevation 755' and a "B" train igniter will be located above the "B" train fan at elevation 746'. One igniter is also located on the outer face of each of the two steam generator chambers at elevation 742'. The two air return fans provide recirculation flow from the upper compartment through the accumulator rooms, pipe chase, and HVAC rooms (the sum of which are referred to as the " dead-ended" volume) and back into the main area of the lower compartment. To cover these regions, there will be 20 igniters (equally divided between trains)' distributed throughout the rooms through which the recirculation flow passes. Four igniters will be equally spaced around the pipe chase at elevation 689'. A pair of igniters will be located in each of the four accumulator rooms, the two HVAC rooms, the instrument room, and the heat exchanger room between elevations 700' and 716'. 7.3 Operating Procedures Since the principle of controlled combustion using thermal igniters., amite mixtures as they become flammable at any

39 containment location is fairly straightforward, no sophisticated operating procedures are necessary. TVA has not identified any reasonable rationale for individual or group oc trol of igniters to try to achieve local or partial combustion. Tnerefore, manual initiation of all ignitors by the operator betere any potential release of hydrogen into the containment is the only major objective. Basically, the PHMS uill be initiated manually from the main control room following any event that requires the use of Emergency Operating Instruction 1 (E0I-1), " Loss cf Reactor Coolant." The ignitors will be divi.ded into two redundant groups (trains A and B), with a ;Ntrol switch and status (ON/0FF) indication for each group located in the main control room. - More detailed information about the system design of the PHMS and its interaction with other key systems will be provided by the end of October 1981. L

4 40 8.0 Ongoing Work As mentioned in several sections of this report, TVA is continuing to pursue information to confirm the effectiveness and characteristics of controlled combustion for hydrogen mitigation. The major portion of this effort is being coordinated by the Electric Power Research Institute (EPRI). A number of areas are being investigated at several research facilities. Hydrogen combustion properties such as flame speeds, burn completeness, lower flammability limits, propagation between mixtures of different concentration, and effects of obstacles and turbulence are being examined at the Whiteshell Nuclear Research Establishment along with the effectiveness of various types of igniters. At Acurex Corporation and Factory Mutual Research Corporation, the effects of sprays and fogs are being studied. A large-scale model of an ice condenser containment is being used at Hanford Engineering Development Laboratory to investigate hydrogen mixing and distribution. A detailed explanation, test matrix, and schedule for the EPHI program was submitted by TVA to the NRC in our third quarterly report on June 16, 1981. f TVA is presently exploring details of an igniter endurance testing program to be conducted at our Singleton Labcratory. Items being investigated include methods to continuously inject controlled amounts of hydrogen and air into the combustion chamber, methods for detecting the presence of a hydrogen flame, and the excent of the test matrix. This program is cc::rently scheduled to be complete by the end of October 1981. l 1 l -~- -

41 TVA is making arrangements to establish an environmental qualification testing program for the thermal igniters at Wyle Laboratories in Huntsville, Alabama. The igniters will be subjected to tM at31g:. basis environmental conditions listed in section 3 11.2 of the Sequoyah FSAR. No hydrogen ignition tests will be perfomed by Wyle since they are being conducted at Singleton. Teat schedules, when available, will be provided. TVA has committed verbally to analyze the effects < extending s the design basis hydrogen transient into the core t-eflood and accident recovery phase. In addition, sensitivity studies of further hydrogen-producing scenarios will be performed. The results of these additional analyses ane scheduled for submittal in October 1981. E71163.04

1 O t 9 ATTACHMENT A i l I l I l s - ~.

3 F l. FINAL TILICAL REPORT I. I SYSTEM FEASIBILITY ANALYSIS OF USING HALON 1301 k IN AN ICE CONDENSER CONTAIhENT i i Submittad to: Tennessee Valley Authority 400 Cot::merce Avenue Knoxville, TN 37902 g l American Electric Power i 1 2 Broadway i New York, NY 10004 i i Duke Power Co. Design Engineering Department l i Post Office Box 33189 Charlotte, NC 28240 Contract TV-55205A e Submitted by: l Edward T. McHale I Atlantic Research Corporation 5390 Cherokee Avenue Alexandria, Virginia 22314 g i ARC No. 42-6522 February 1981 ATLANTIC AESEAACH COAAQAATION ALEXAND AIA.VI AGINIA. 223%% l J ( l 1. m

FINAL TECHNICAL REPORT SYSTEM FEASIBILITY ANALYSIS OF USING HALON 1301 IN AN ICE CONDENSER CONTAI:: MENT F Submitted to: Tennessee Wiley Authority l 400 Commerce Avenue Knoxville, TN 37902 e American Electric Power 2 Broadway New York, NY 10004 Duke Power Co. Design Engineering Department c Post Office Box 33189 Charlotte, NC 28240 contract TV-55205A s i Submitted by: Edward T. McHale c Atlantic Research Corporation 5390 Cherokee Avenue Alexandria, Virginia 22314 February 1981 ARC No. 42-6522 i i I f I i 4 a b - -y. r.- ...m. m--. c__

l t L r (, b, t L i s FOREk'ORD E i I: lv I This study was jointly funded oy Tent issee Valley p Authority, Duke Power and American Electri-Power under 6-Contract No. TV-55205A. The following persons made major technical contributions to the program: A. J. Biedermann of C. P. Dillon and Associates (Section 6.0); N. P. Ross-f meissi of Atlantic Research Corporation (Section 2.0); 5.' Dr. S. A. Turner of Southern Service AppItcations, Inc ,a (Section 4.0); and Dr. G. von Elbe of Atla ' Research Corporation (Section 5.0). b i-S iW l e:. l$.. r b e l Ps I l L-N u i., - ? v n ,-a.-, , - - - - -,, -,. -, - ~ - ,,--.-,n. .w,-,,, w, n-,

i l TABLE OF CONTENTS 1 Title

Page, Section INTRODUCTION AND SL M Y.....................................

1 1.0 SYSTEM DESIGN................................................ 7 2.0 INADVERTENT. ACTIVATION AND LONG-TERM ACCIDFh'T 3.0 e RECOV ERY CON SIDERATIONS...................................... 15 HALON DECOMPOSITION AND WATER CHEMISTRY........ '.............. 18 4.0 IGNITION OF HYDROGEN-AIR-HALON MIXTURES...................... 2 6 5.0 5.1 Flame Propagation and Flammability Limits............... 27 5.2 Halon Percentage Required for Preventing Ignition of Post-LOCA Hydrogen / Air Mixtures by Detonating Hydrogen / Air Pockets..............................,..... 32 35 6.0 EFFECTS OF HALON 1301 AND 1ECOMPOSITION PRODUCTS UNDER POST-LCCA CONDITIONS 1N MATERIALS OF CCN-STRUCTION.................................................... 3? Corrosion Mechanisms.................................... 25 6.1 ? 6.2 Literature Search.................... .................. 38 Discussion of Corrosive Ef fects Expected 6.3 in Containment Coolit-g Water............................ 41 6.4 Conclusions f rom Materials Corrosion Study.............. 42 REFERENCES........................................................... 44 I l 1 l I h f i l 1 if .4. e = 3e ,y l m..

F-{ l

n. i L

LIST OF FIGURES _ k Pm Figure 4 1 Vapor Pressure of Halon 1301 Vs. Temperature {. 2 Calculated Adiabatic Constant Volume Explosion and 5 Chapman-Jouget Detonation Pressures and Temperatures for H -Air. Initial P = 14.7 psia, T = 298'K 2 3 Measured Explosion Pressures for Les.n Hydrogen-Air 6 3 Spheri-l Mixtures Ignited with Central Spark in 12 ft cal Vessel (Reference 4) g 8 + 4 Explosion Limits, H -Air-1301. 2 5 Conceptual Diagram of Halon 1301 Post-LOCA Hydrogen 10 Suppression System for Ice Condenser Containment h 12 6

iagram of Valving and Piping for Five Halon Storage Vessels i

7 Bromide' Ion Concentration as a Function of the Halon 19 Pressurc (P) and Radiation Dose (R) ] <M S Variation in pH as a Function of the Halon Pressure (P) 20 and Radiation Dose (R) 22 9 Halon Radiolytic Decomposition Race in Water 10 Time-Dependent Br Concentration 23 ~ 24 11 pH Changes in Containment Water 12 Explosion Pressure Growth for Stoichiometric CH,-Air 28 Mixtures with Added C/ Br in 12-ft Diameter Sphere l 3 (3.6% of CF Br renders this mixture inert). From 3 Reference 11. l 13 (a) Flama Propagation in a Tube 31 (b) Unconfined Flame (c) Upward and Downward Propagation of Flames in Vertical Tubes lb 14 Diagrams Illustrating Various Types of Metallic 36 Co rosion Mechanisms 15 Localir. d Corrosion for 304 and 316 S.S. in River Water 40 at Various Chloride Levels ln 11 f P) 1 e 1.- --wr, ,s, w-w-. am..,. -,,

1.0 INTRODUCTION

A';D

SUMMARY

A development program had been conducted during the mid-seventies under sponsorship of the Maritime Administration, which established that Halon 1301 could provide protection against any combustion hazard that hydrogen gas might present fo11 ewing a loss-of-coolant accident in rela-l tively small LWF,contain=ents of nuclear-powered ships. That program comprised analytical study, laboratory experiments and large-scale test- . ing to define th. requirements for a Halon 1301 system and to examine Full details are certain operational problema that were hypothesized. cracained in reference (1), available through NTIS. The present study reported here examined the question of whether a There are Halon system would be suitable for an ice condenser containment. two aspects to the suitability question - one concerns saf ety and is related The conclusion of the study is that a Halon system would pro-to licensing. vide full safety. The other aspect of the question concens potential cor-rosion of metals in the primary and secondary cooling systems, which might arise 'from a small amount of decomposition of Halon. This is not a safety question but rather an economic =atter related to system recovery af ter a. l The conclusion of the study is that any corrosion problem can prob-LOCA. ably be eliminated by adjusting the water chemistry, and night even be self-r -eliminating. Halon 1301, which has the chemical formula CF Br. h a vehown 3An inerting system for fire extinguishing and explosion suppressing agent. nuclear-related application would consist cf a predetermined quantity of Halon In stored as a liquified gas in several storage vessels near the containment. the event of a LOCA the' system could be i= mediately activated, or alternatively 1301 could be discharged 'if hydregen concentration reached a certain point, either automatically or manually into the containment through a piping and L Many operational advantages are associated with the si=plicity valve system. For example, there are f ew moving parts, minimal power re-of a 1301 system.- quirements, complete reliability, relative economy, storage convenience, ease l f t.r cher .of periodic testing, and once activated the system requires litt e l attention. The quantity of Halon varies with the particular application being de-pendent mainly on containment volume and amount of hydrogen that could develop. i 1 9 1 w e. es-e e-an-- e +-,,r w + ---*r n, s -m-e -, - +s-- - = - ,--~n, --w v---,,e----~-,,,,-------evw--m,+, e-,,,wv,-v,---,,--

4- -'A J -A

  • L-_

J A,_4., I t For an ice condenser containment of the Sequoyah type, the exact requirement as determined in this study is 236,300 lb mass. This amount of agent would p be stored in four 12-foot diameter vessels, each containing 59,075 lb. In L principle, it is possible to use gases other than Halen 1301 for inerting, such as nitrogen or carbon dioxide. In practice, however, the storage re-quirements and the pressures that these gases would produce la the contain-mont would be excassive. Halons other than 1301 also have been considered. Halon 2402 does not have sufficient vapor pressure for such application. ] Halon 1211 may be comparable to 1301. Halon 1301 is well suited for containment vessels because of its physical and chemical properties and because of its favorable toxicological characteristics (2,3). Some physical properties are listed in Table 1 and Figure 1. The chemical properties of Halon 1301 of interest concern its compatibility with materials of construction, its reactivity and thermal stability. Relevant toxicity and chemical behavic are discussed later in the report. It is of interest to consider the pressures and temperatures that would be expected in the event that a noninerted hydrogen-air mixture were ignited. The theoretically calculated values for such sixtures are presented in Figure 2. These were computed using JA'.GAF data and the Atlantic Research thermochemical code. The explosion curves of Figure 2 refer to the ca6e of ordinary slow (subsonic) combustion in a closed vessel. The dator.ation curves give the pressures and temperatures associated with the supersonic combustion. The detonation limits are ordinarily given as 18 to 59% hydrogen in air. The j explosion or flammability limits for hydrogen are usually cited as about 4 to 95%. Concerning the lower flammability 'Isit, it is true that small flame-I lets can be made to propagate at this concentration; however, no significant overpressures develop until a mixture strength c,2 about 7% is reached. This can be seen in the data of Figure 3, which is taken from reference (4). (In h the figure, overpressures are not produced below about 8%, but the authors reported that with repeateo sparking tne limit was lowered to about 7%.) The tests of Figure 3 were performed in a 12-f t. sphere with central spark ignition. Above about 12: hydrogen, the experimental measure =ents coincid,e g closely with calculated pressures. .i f !n i a 0 .... u. -.,,.,-.-,..-.n .-.nn-- --,....,-n.--


n,

Table 1. Physical Properties of Halon 1301 Chemical Formula CF Br 3 Molecular Weight 149 Boiling Poir.: -72*F -270*F Freezing Point Critical Temperature 152.6*F Critical Pressure 575 psi.s critical Density 46.5 lbs/en ft Heat of Vaporization 35.5 BTU /lb 6 70*F Surface Tension of Liquid 9.7 dynes /cm 0 0'T 4.5 dynes /cm 0 70*F Density: Liquid 82.2 lbs/cu ft 8120*F 98.0 lbs/cu ft G 70*F Saturated Vapor 16.2 its/cu ft 0 120*F 7.4 lbs/cu ft 0 70*F i 0.257 N/lb 'T C 120*F Heat Capacity 0.205 ETU/lb *F G 70*F i 0.176 BTU /lb 'T 0 0*F r 8 Vapor Pressure 400.4 psia 0 120*F ,13.7 psia 0 70*F 2 71.2 psia 0 0*F Thermal Conductivity 0.025 BTU f t/hr 'T f t 0 70*F 100 ppm at 15 psia and 120*F Solubility in H O 2 300 ppm at 15 psia and 70*F 9 m. 3 l l m-cg--*


e.+-.

e--m_e--wy ,,e,,-- gyg- ---m--w-- -e.d- -gy e. w ,e-w-ewm,.s,e,y s y eg g-yw

I ) C I .E 600 I A soo I ~ G 4 co-- I'[ CRITICAL POINT 0 l l e D W goc wea D N k " goo / 152.6 ' r, 5 6 0,2 P 5 f G if \\ \\ b. inmI / Wu j '5g ISO p Q. - /, l y I gW 10 0 /- OC 4 A< 40 4' 3 I / t 6 6 6 e i t q"., 1/ i >ca l i l 5 S0 I. e / m-W I b z ' 40 [ l l l' O c1 30 Jc / <z / h

  • 3 I

to }( T ss ~ o 20 o ao 40 to ao loo tao 14 o iso ~40.-40 TEMPERATURE

  • F

-5 eJ l m' i pe tw* .r i s e '. Figure 1. Vapor Pressure of Halon 1301 Vs. Temperature. ,k 1 4 e.' L-e OMM O' ,--m--- s-e-- -u-,,---w ,,-o,- ,-o--, 4 w-am-ew---em,,v--m- >--,---,,w w -e--n-w-ww -.-w-e e vem ,mm -ew~-c---- wm-

,J !ll i nM. nE3ygsa22.( .tu u 0 0 0 0 0 0 0 0 0 0 0 0 5 0 5 0 0 5 00 1 3 2 2 1 0 r' 0 no T 7 i t a n n o o q i t s e o D s lp ~ x s t eK 0 E s g 6 u *8 o s' ~ J 92 ~ n= P R aT r n m. I o A pa ~ ai \\ is s 0 N h p o l ' T 5 C I 7 n p' 2 d o? ,u Q x n4 1 1 i 1 P a ta T n= n n N oP o o E it i t sl e a C lptin oa D\\ n 0 R i o 4 E x te P EI % ',, %D C e r miA i R ~ T lu -2 ol E Vf ~ 0 M r t o 3 U nI ~, L a s ~/ / t O s e r n V ot u Ca f ce r , /4 it p a m 7 'e / 0 b e r 2 aiT - /' s d /# f d L An ! e /', 'p d a e s t e e a r 's lus e / u / 0 la r cs e s 1 CP /e,# 2 I s s e 1 s rug

F 0

0 0 0 0 0 0 0 5 0 5 0 5 3 2 2 1 1 5a~ E3*yE* u i a

ilI i.l 1

s 1 ,.i; ,I!' 'i': il l t

_e-- I n-L <.. I L P! 19 70 1 i l I L l ~ CALCULATED Ap y 17 60 6 15 w 50 / ~ M ~ e f a 13 / c.r. 40 9 CALCULATED Tg E E t

=

b g E 11 S' E 30 a a w ' M w >= ( b I ~ / ~ II' iL., +-EXPERIMENTAL Ap g 20 UPWARD PROPAGATION UPWARD AND DOWNWARD !L., e_ PROPAGATION , ONLY - 7 L. 10 { I M' I I 0 4 8 12 16 20 HYDROGEN, % Figure 3. Measured Explosion Pressures for Lean Hydrogen-Air Mixtures ) 3 ignited with Central Spark in 12 ft Spherical Vessel (Reference 4). F ke 6 m

  • 9.

e.mee * '" 'ese* &e e# .y 7$ ,g. e p, g qe ,e g, g g, ,,,,g g, ' ~ ' ' T ew -e w

2.0 SYSTEM DESIGN Prior to discussing any potential problems associated with the use of Halon 1301, which items are dealt with in following sections of the report, we will first determine the Halon requirements and present a conceptual scheme The requirements include the amount of agent needed for for a system design. post-LOCA monitoring. inerting, storage, injection system, and H2 In order to compute the amount of Halon required for inerting, the following information is needed: Sequoyah taken as 1,191,500 ft Containment Free Volume o includirs upper and lower compartments and ice condenser when empty of ice. Taken to be Containment Initial Temperature and Pressure e 70*F and 1 ata, respectively. 1450 lb mass of H r 277,800 ft Hydrogen Release 2 e at 70*F, equivalent to 75% zirconium cladding reaction. (Additionally, it is assumed that all Halon must be injected within 1000 seconds.) Assumed to be crdinary air with no oxygen e Oxidant enrichment. e Total Maximum Water Inventory - Assumed to be, 0 5.9 x 10 lbs. Assumed to be zero. Containment Leak Race e Tests were performed ten the work of referarce (1) from which can be detsrmined the amount of Halon required for any given oxygen content of the atmosphere. No credit is taken for steam inerting. The flammability dia-i gram shown in Figure 4, taken from (1), can be used to specify Halon, since l I the oxidant is air. The peak percentage is selected, conservatively, as 25 l volumetric percent Halon. The peak percentage represents the quantity of Halon required to inert against hydrogen-air mixtt.res of any composition. The amount of Halon required is then calculated to be 489,800 ft at 70*F, or 191,500 lb mass. Knowledge of the total water inventory allows the estinate of Halon loss by radiolytic decomposition in solution (4540 lb mass; see a later section of the repor;), and loss by disaolution (885 lb mass assuming !.t 7 l t a "ll J .c. .. u... .-r c_

i P =- <i. me-1301

e-

/\\hk 80 70* F QNo Explosion GExplosion Propagated 1 atm APartial Propagation Dry Gases g Souib Ignition A ; e : ' x " n, v 60 - o NWWVN NN/VVW\\ NN/\\/V\\/ \\ /\\/N/N/\\/\\Wxf\\ l\\ c /\\/x/Nb>11&N\\' \\, s H2 L' f I f Figure 4. Explosion Limits. H Air 1301. 2 s 8 q i -.mt1 .~....,6. s v .r......

l Ealon solubility of 150 ppm; see reference (1)). The Halon requirement therefore will be 196,900 lb = ass. Per standard good safety practice, a nomtn.t.ne... to apeutet a (for exempt., Jot), bringing the tusat to 236,300.lb mass of Halen. The partial pressures corresponding to the containment gases will be: 14.70 psia Air 1.000 ats = 3.43 psia H2 0.233 atm = 7.46 psia Halon 0.507 ats = 4 10.89 psig 1.740 ats 25.59 psia = Due to the presence of steam and elevated temperature (possibly 160'F) the sum of the partial pressures in the containment early in the LOCA might be as high as 30 psia. The assumptien of 75: zirconium reaction should be examined. As will be seen in a later section of this report, if insufficient Halon is present for inerting, substantial overpressures might develop upon ignition, possibly approaching those pressures that would be reached if no Halon were present at all. Therefore. it is prudent to ask what would happen for the case of greater than 75% zirconium reaction. Consider the worst case, that of 100% reaction. This case represents 1933 lb H, r 959 lb = oles. The mass of air in the con-2 tainment is about 90,000 lb, or 3,100 lb soles. Accordingly, the 25% Ealon peak percentage requires 1353 lb soles or 201,600 lb cass.of agent to inert I against 100% zirconium reaction. Adding the losses of 4540 and 885 lb mass gives an amount of 207,025 lb. Thus the 236,300 lb design quantity for 75% zirconium reaction still represents a 14% excess for the 100% reaction case. The Halon system would consist of storage vessels to contain the I 236,300 lb of agent stored as a liquified gas, which vessels would be con-nected to a manifold, to which spray nozzles would be attached for Halon g 4 injection if required. The present design calls for the 236,300 lb of f Halon to be stored in four vessels with a fifth vessel containing 59,075 lb serving as a reserve in the event of failure of one of the required four. { The storage tanks are sized to contain the Halon at temperatures above 130*F where the liquid density (77.6 lb/f t ) is less than at 70*F. Each tank would be of 316 stainless steel, with an equivalent spherical diameter of 12 feet and a wall thickness calculated to be three inches. This provides a working pressure of 500 psig for the system, conforming to Section VIII of the ASME Unified Pressure Vessel Code. A diagram illustrating the system design is shown in tigure 5. 9 m a w-yn e ,r ~ ~-e- + v e w-+w-a- rw m v ,w

i 9 g i L, i e, r. .z CC l , M >o,<,a M E w-e ,,,ww aM W2*Ng g 2 m N -- e ECCC* T <uwz-g [ g v e ,g Lxw-wgxw j I ss E O l* c t i i o P ';;i F. W >2 w a L. z >- zu m2 o we i WM z ;= w ,=g = 2 <o. y a a o m z aum r. 3 2

  • wN as e

L-o z o 2 e w W EE O m G 2 EOg"r p/ V 1 I m. 2 e a [ 84 i ~ Eh $$N\\M ' c'*\\\\\\\\ W a 9= L ,= o e E b m 1 c2

n.,lu m. in) - -

o. 2e i- = 3 6 M N l N5 e.y 7. M jl t a..S m rp 3 F c 88 M UV Mz 4.. %( Nk"C e s v~ e<a os = w "C < x was 5 2 c >od 2* w OwWcE2w e-

==v-=.s z<>w><E 4 dQ WM*CC2 E d w c >m a w = < wr p. azma wu t I r v a 10 l........ .a c

Each storage vessel would have an associated tank of nitrogen gas (approximately 7.5 ft diameter tanks containing N (or air) at nominal 3000 psi) connected to it which would maintain a delivery pressure of 600 psig if the Halon had to be discharged (per NFPA standards; see reference (3)). The five Halon tanks are valved independently to two manifolds of 4-1/2" SS Schedule 40 pipe. The manifold piping diameter may have to be larger if a total run of much more than about 500 feet is required. The requirement to be met is that the Halon pressure at the discharge nozzle should exceed the i vapor pressure at the ambient temperature (e.g., 434 psig at 130*F) to insure that agent is injected as a liquid. Therefore, a pressure drop of more than about 160 psi is not allowed. A 4-1/2" SS pipe will permit a 500 ft. ran with a pressure drop of about 0.3 psi /fc. Two penetrations of the containment will be. required for the pipes. The piping will conform to ANST B-31.10 classifi-cation. Inside the containment, the piping branches to the upper and lower compartments. An array of spray nozeles comes off each manifold pipe inside the containment. The requirement is to deliver 236,300 l'b. Halon in 1000 sec-onds, or 1366 spa at 130*F. One arrangement to accomplish this is to use 20 full cone nozzles of 15/32" orifice on each manifold, one of which is sufficient. This feature of the system design is being left open at pre-sent. The exact nozzle system configuration would have to be determined by actua1' inspection of the containment and computation of the requirement -in each area. The nozzles would simply be sized based on a constant area I equivalent to that of the total twenty 15/32" orifices. The flow into the upper and lower compartments would be proportioned according to the volume .I of each. Other sections such as the pressurizer and steam generator enclo-sures, accumulator rooms, and instrument room, may be provided with a sepa- '~ rate proportionately-sized nozzle, although the sizing is not critical since the air return fans will provide adequate circulation and mixing. Once the I gases are mixed, damixing will not occur. The storage vessel, piping and valving configuration is based on the guiding principle that the system must function properly even if three in-dependent malfunctions occur. The configuration is shown in Figure 6 for i all five Halon tanks, wherein standard symbolism is used in the drawing. g Referring to Figures 5 and 6, it can be seen that any three valves in the l system can fail to open and the required Halon injection could still be J made. (The symbol NO of the figure indicates a normally open valve.) T j 11 1 w -tsy-r e v v-- 4-g wy--f T ' TT -r-'- - - * ' T-7r'

  • w9
    • rT'--'rr#""T e-e*g=**e 7-7

--u-' ' --97^9- ' - --*--*tvue -at +' ty

y.. ~ 'b. ~ m >. s y _5 L 4>- -s > i.. ?* y w> w r~ Y m m ( r, l l ~ M N l 2 ) m tJ -o e' s 5 \\ h i 3 E m h C' Y* m \\ y O ~ n l m z T, o 1 s' A

w s

N 1 N h .i s u. e r* C o m .E 1 C' P r, m .e. ) a. ,k; s-a = l z C I (' WD, <r. / 9 4 6 \\ S 3 P E o ( 1 A W 3 s .e O m N = s l a l ) M ( K~ i m = O 9 N k u. C m 'y - V ( ) l \\ 1 m n J z j w2 m t j X. w m> \\ k >C 'm 12 , t s., 4. 's- ..i.** - 't l l ~,

4 9 9 Inasmuch as there are no other moving parts or parts requiring power, it is hard to see how any cther malfunction could occur except with the nitro-gen gas regulators. The nitrogen tank valves would be controlled by the pressure sensors, so that if a regulator failed to produce the correct pressure level, that side of the nitrogen flow would be stopped and the other side opened. In the event of a LOCA the Halon system could be activated either i manually or automatically. The present study required that Halon injection be designed for a rate of delivery of the total required amount in 1000 e seconds, corresponding to a design basis accident. Following injection, the Halon and hydrogen concentrations of the containment would be moni-tored continuously during the post-LOCA period. The method of choice for monitoring is gas chromatography. Any method that functions on the principle of thermal conductivity, heat of combustion on a catalytic wire, or any other measurement that depends for its calibration on a two-component mixture being present will not be suitable, since a three-component mixture is present in the post-LOCA containment -- H, air and 1301 (steam can be 2 condensed, and air is considered a single component since its composition is constant). In reference (1) an evaluation of gas chromatography was performed and the method found to be suitable for the present application. The prin-ciple of operation of the method is as follows. A mixture of gases to be analyzed is passed into a tube that is packed with some type of absorbent (charcoal, silica gel, molecular sieves, etc.). A carrier gas, typically helium, sweeps the gases through the column. The absorbent material ex-hibits.different affinity for each component of the gas mixture and thereby retains each gas for a different length of time. Accordingly, each component elutes separately from the column at its own characteristic retention time. As it slutes, it passes through some type of detector which responds and provides a quantitative measure of the amount of that component. To separate all components, two column packings are required. One is a material known as Porapak Q, an organic polymeric absorbent, which will separate Halon from air and hydrogen. It will also separate the Halen from other impurities or decomposition products.such as CF Br ' C F, CO ' 4* 2 2 26 2 In series with Porapak Q, a molecular sieve column is placed which separates and N ' H,02 2 2 13 ' ' ~'

(( i V-L- The total instrumental method would consist of a commercially availa!,ie I. procest chromatograph, with the column console, programmer and readout located on an instrument panel in the control room. Sampling would be provided at 1, several locations within the containment via an automatic scream selector. Wa have obtained product literature from vendors for virtually off-the-shelf 6 No additional penetrations of the containment would be required packages. over those normally present. No cost analysis for a Halon system is being performed in the present I. study; however, it can be noted that duPont is quoting a price (January 1981) of $2.70 per lb for 1301 in tank car quantities (120,000 lb per car). .i E u E ILe O E C E E 14 r 6 ....c....,,,e.... .....,,,,.3.. .._.m.. ..us. 4

'3.0 INADVERTENT ACTt'ATION CONSIDERATIONS When Halon is injected as a liquid into a gaseous atmosphare it will vaporize, drawing its enthalpy of vaporization from sensible heat of the atmosphere, thereby lowering the temperature of the atmosphere. A corre-spending decrease in pressure might occur. Since the ice condenser contain-ment is not designed for much more than one psi underpressure, the question arises as to what pressure drop sight result if Halon were inadvertently injected. The pr:bles is limited to the discharge of a single vessel out of the five storage tanks, since no common code failure exists that would allow more than one tank to inadvertently inject. The problem could be set up in a for=al way since the pressure decrease is offset by a pressure increase due to Halon gas being added to the contain-ment. Hewever, a straightforward exa=ple will answer the question: i 59,07 5 lb. , Halon Discharged = 35.5 BTU /lb. (70*F: less at higher Heat of Vapor.ization = i tenperature) 2.1 x 10 BTU i Heat Absorbed = i I 1.2 x 10 ft 90,000 lb. Contain=ent Air = = I 0.25 BTU /lb 'F Specific Heat Air = f I Temperature Drop from 93*F Heat Absorbed = I { Corresponding Drop in 2.50 psia (Ideal Cas Law) 0.17 ats Air Pressure = = 7.46/4 psia = Pressure Increase from = Halon Addition 1.87 psis (See Section 2.0) Net Pressure Drop from Inadvertent Halon 0.63 psia Injection = 15 1 ? *Y as. w C.'G mWe

  • '"=',.-an'st".

sv W ' bank 3 3.' t'.

'a S M W.

\\

s-t e..i Thus it can be seen that the inadve: ent discharge of one Halon tank i 'w-would not be cause for concern. Furthermore, the above estimates are con-i *- servative in that heat from the containment vessel would be absorbed and I would lead to lass pressure drop. Fairly soon the pressure would be re- .L stored to ambient.

6...

A corollary question can be asked which concerns whether there is f e-sufficient heat to vaporize the Halon if all 236,300 lb. had to be dis- ,s.. charged. This question was tested in reference (1) wherein the situation l was similar in that there was not enough sensible heat in the air to provide 7" '~ the heat of vaporization. In tests using a "minicontainment" it was found that no vaporization problems were encountered, the Halon receiving heat ap - from the contain=ent vessel itself. It is noted that the total heat of $a; 6 } vaporization requirement is about 8.4 x 10 BTU which is about 2.5 percent ,,3 8 g,h of the total blowdown energy of 3.35 x 10 BTU. Short term cooling of certain (small) components in the contain=cnt P-could conceivably occur if Halon were inadvertently injected directly onto e them. No problem is envisioned from this effect. If one tank of Halon were to be discharged into the containment, the

F" 1"~

concentration weeld er.ceed ten percent. This amount is not considered safe for human exposure for any extended period of cine and ther'efore, personnel, if any were present, would have to immediately evaeuate the area and the con-G -; tainment would have to be purged. Reference (5) details the extensive studies ] that duPont and others performed on Halen toxicity. The key piece of informa- ,s-tion seems to be the classification of Underwriters' Laboratories, which it is emphasized is based on animal studies and not human exposures. Under-lI~ W writers' places Halen 1301 in its least toxic Group 6, " Cases or vapors which j in concentrations up to at least 20% by volume for durations of exposure of e-14d the order of 2 hours do not appear to produce injury." Carbon dioxide is considered more toxic and placed in Group SA. It is to be noted that in order for an inadvertent injection of a tank of Halon to cccur, two independent solenoid valves which are nor-mally closed must be activated and the malfunction left unremedied for some time. y he <~ 16 p, .r-O 4 ap 4 ,M, og+8. 9 3 O y Pe $tt 88 e4 8 Oe a ga

~ 9 4 I The containment can be purged of Halon f airly easily following inadvertent j discharge. The containment atmosphere would be vented through charcoal filters. It has been established that there is no deleterious effect on such filters and that they adsorb iodine compounds just as effectively with Halen present in the atmosphere. Even at a low purge rate of, say, 2000 cfm. a complete change of air in a containment would occur in 10 hours. Several complete changes would be required to render the atmosphere habitable. l O w '1r ) ' I ai l' t J> i t il I 1 }. 1 17 i a

m i 'g n. L. 4.0 HALON DECOMPOSITION AND 'JATER CHEMISTRY l There had been concern that Halon night dissolve in emergency cooling water and radiolytically decompose as it passed near the reactor I I core and encountered radiation from decay products. Even though Halon is only slightly soluble in H 0, if decomposition occurred and the agent was 2 This continuously replenished, one can calculate a high level of loss. question was experimentally investigated in reference (1) wherein the main conclusion is illustrated in Figures 7 and 8. These show that Halon in water when irradiated does ' decompose to some small extent, but that the process is self-arresting when the Br-concentration builds to about 5.2 x 10 moles / liter. Figure 8 shows the measured pH change associated -3 (The water contained small amounts of.K C 0 /H PO /KOH 224 3 4 with the process. and the pH was set to 11.0 at start of irradiation (see reference (1), Phase III, Section 4.1).) Based on these experimental data the rate of decomposinon of Halon in the Sequoyah reactor was calculated. It is necessary to know fission product release to the water, from which decay energies are determined and the accumulated radiation dose calculated for a given water inventory. These computations were performed by Dr. Stanley E. Turner of Southern Science Applications Inc., and the following material is principally that which was reported by Dr. Turner. The assumptions were the following: TID-14833 fission product releases (100% of noble gases, 50% of the iodines and 1% of solids). h, e SRP 6.2.5 relationships for energy deposition in the water. e Halon radiolysis race relaticuship-in reference (1). e Instantanecus injection of all Halen (to 7.46 psia partial e pressure) at time rero. (Actual Halon injection rate would perturb the early decomposition rates but not very signifi-fki cantly.) Uniform mixing of water and re-pumping through the core e for energency cooling. Equilibrium solubility of Halon at all times (i.e., that e consumed is instantly replenished.) Halon Decoccasition ~ Since the net decomposition of Halon ceases at equilibrium Br con- -3 cercration of 5.2 x 10 moles /1, the total quantity of Halon decomposed d 18 v n ,j, ,,,,7

  • * = = *

..'C# m- ~

I i e i I 6 10 2 e t

  • E EXPERIMENTAL DATA e

\\ ~ -- LEAST SQU AMES FlT 2 10'3 ~ o E e

wm L

.i y . f l' i 10 t 1 I o 50 100 150 200 250 300 P x R, psi MRAD .\\ Figure 7. Bromide ton Concentration as a Function of the ~ Halon pressure (P) and Radiation Dose (R) 9 19 N' I' =.e p .,.g ,.-.-y._ y-m. .-,,,wg-y ,,,,,.,y. y ---9..%__-p..-_-

I i 1.0 - i i i i i L

7..

l0.0 y r. e a.- ~. 9.0 5-8.0 r-~ b., r-7.0 J ro. e c,~ 6.0 4..-. I' e 5.0 i,.. I .g.J I 4.0 -.t l {~ 3.0 2.0 I I I I L-0 40 80 120 160 200 240 ( P x R, psi-MR AD l Figure 8. Variation in pH as a function of the Halon e pressues (P) and Radiation Dose (R). i - l M ** 20 (-. I o

n. '

...v. <e.

  • ~-

.-r.. s m.

i 1 i 1 i depends (at equilibrium).4pon the total quantity of water in the containment ~3 (6.46 x 10 lbs Halon decomposed per gallon of water). For the maximum i amount (702,950 gallons, re: TVA letter of Oct. 31, 1980), the quantity of Halon decomposed is 4540 lb, independent of the fission product release to the water. An additional 885 lb will remain dissolved in the 702,950 gallons of water. The rate of Halon decomposition also depends upon the quantity of water in the containment. Figure 9 shows the time-dependent quantity of Halon decomposed for several potential values of the containment water in- ~ ventory. Figure 10 shows the time-dependent concentration of 3r for the same assumed values of water (time zero on these figures refers to thi be-ginning of the assumed accident sequesce and assumes Halon injection starts ~3 ~ at this point). The final saturation concentration of Br is 5.2 x 10 moles /l in all cases. Water Chemistry and pH Br is presumably formed as HBr, and deco'mposition of Halon also ~ produces RF at concentrations 3 times that of HBr. RF ionize.cion, how-ever, is suppressed by the H+ from HBr ionization, and at equilibrium most i of the M1 is undissociated. Thus, Figure 10 may also be interpreted as the i HBr conce tration nith the RF concentration being 3 tLaes that indicated for Br. The pH changes depend upon the initial chemical composition and pH 1 of the water in the containment system. Although the system water will likely be slightly alkaline (pH >7) and perhaps buffered (presence of i sodium borate, for example, to prevent criticality), cciculations of the f pH changes have been made conservatively assuming pure water (pH of 7.0) in the containment system initially. Assuming complete ionization of HBr j and an fonization constant of 3.53 x 10 ' for HF, the resulting pH is shown ~ in Figure 11. At equilibrium, the pH would be s 2.2, determined principally by the HBr, with HF ionization largely suppressed. Further discussion of the adjustment of pH and of Br" concentration is given later in connection i _ concentration was not mea;sred but is cal-with materials corrosion. The F culated to be 8.3 x 10 moles /1, and the calculated HF concentration 14.8 x 10~ moles /1. n 21 a i +

  • i

ll lill S Y 7 Al 0 O 0-0 0 0 Dl 1 5 5 5 5-9 9 9, 0 2 0 9 H 2 1 8 8 1 SN 7-0 4 0 8 5 1 0 O 5l L L A G R E T E 0 A 2 T I A % R H N 6 0 AO OT i 1 YI 0 1 O C O E J EN SI 5l s ~ r e t a e W in 2I f t e l YI 5 a 5 R A DI n 1 I i o 1 SD it s i s S N o f R O p HI C m 0 E o S, ce 1 / E D M

  1. [

I itc T ly o "0 d i 1 aR n o la R H i HI 1 9 I. e ru f ig F 0 / 1 /// / / / Y ///' j I' / 20 0 0 0 1 0 0 0 0 0 1 1 0 g 8 o>$ 5 1 0 I .c I? j 1ll

SY 7 A1 3 D 9 ~ 1 0 ~ 0 1 05l NO R T I .E CT CE NI ET L JA 0l O/ J 2 CS CR OH E 7 ,j A 6 8 LO 2 0 HY NM O 01 1 I O E 1 / L U j T '0 BQ A1 / I S AE R x / R R 5l UT2 L A E A5 / A V_ P S.= G / 0 / 5 / 9, 2l n 2 / 0 o / j 7 i / / - 5 a t Yl 0 r k Al n 1 t L A / D ec G / n 1 0 o 5 S C S D 9, R N r / H1 O B 80 / 0 C t 1 1 r. n / S e L A d G ne / p 05 e 8, / 4 D L ( 8 0 -e 1 A )/ 1 4 m G / iT 0 / 5 9, 0 8 R 1 8 HI e r 1 u g iF y' 30 1 _ 20 o1 0 0 0 0 0 6 5 4 3 2 -aF zoo'n gbdUdsr'o5}oe u iii: i,1 iii,

J s

1 )

SYAg Dl 00 1 05y 0 g 2 0 O 1 2 H ER 5 U P YL I w L re A t I 2 a T W IN t Y n 0 e D m 1 1 ina tn S S o R O C H N 1 C in 0 O s E e S gna hC 4 H 0 1 p N 1 i e r R u ~ ig H 1 F 30 1 2o 0 0 0 0 0 2 1 5 4 3 i 8o a3<oga Ne 7 : 9 .; i, 5 .l t 1 l, 4 1

Halon decomposition will only occur by water radiolysis. It has been shown (1) that gas phase radiolytic decomposition is negligible. Neither should Halon decompose by contact with hot surfacas. It should not come into direct contact with the core, and other sa: faces will not be hoc enough. Reference (2) reports that only 1.6% desr-cposition oc-curred in 25 hours when Halon was exposed to 316 stainless steel at 600*F (surface area of steel and quantity of Halon not given). Tects at 250*F with ten different metals for 44 months showed negligible effects. In general, temperatures of about 1000*F must be reached before rapid decom-position occurs. A litera*ste search on Halon decomposition failed to turn up any data beyond these cited (see for example, reference (6)). I i i t 4 i I t t 4 i i I 1 h I t I t< 25 b a h i e1 j*. O a t. e#, & fp, 3

  • p

't e 8 W,e 'I* e$' e 4 W ,.7, r y -r-y- .- =--- m- -. e

r El 5.0 IGNITION OF HYDROGEN-AIR-HALON MIXTURES ~ The question has been considered whether hydrogen-air mixturcs that are f inerted with Halon 1301 against ignition by sparks and squibs could be ignited by another ignition source, such as a shock wave that might emanate from the detonation of a pure uninerted hydrogen-air mixtura. In a containment appli-cation, it is hypothesized that a pocket of uninerted mixture might develop. In the absence of experimental data, the question was answerc d by a fundamental analysis of the processes of ignition and flame propagation, performed by Dr. Cuenther von Elbe and presented in the following subsections of this report. For further details the reader is referred to reference (7). The conclusion of the analysis is that if a mixtere 1: inerted against 7 spark or squib, it cannot be ignited by a shock wave. The reason is that mix-b tures that are inerted are outside of the flammability li:uits (for the present J Halon design they are far outside the limits). Any ignition source that is W 4 t applied will, in the very process of trying to pr'oduce ignition, perturb the mixture in the vicinity of itself. Such limit mixtures are very sensitive to perturbation and self-quench themselves by the small turbulace of their own l gas produced by the ignition attempt. Therefore, a "stronscr" ignition source chan a spark or squib would ha represented by a more quiesecat one. In this t 5: sense a shock is a weaker source because it produces perturbation of the gas. However, even a calm ignition, if one could be imagined and if it produced an c.h incipient flame, would no*. lead to sustained propagation, since the inerted 7 mixture is so sensitive to perturbation that *he flame would soon self-quench i by the gas disturbance its very propagation produced. These matters are dis-I cussed further below. Literature search was conducted but did not produce any reporra of I cxperimental work bearing exactly on this question of shock ignition. Several other relevant points can be mentioned. In referccce (8), various uninerted i I hydrogen-air mixtures were ignited by flame and also by detonation, and no lowering of the limit was produced. Also at tha " Workshop on The Impact of I Hydro;en on Water Reactor Safety" held January 26 - 28, 1981, in Albuquerque, New Mexico. -it was reported (9) by an attendee that hydrogen-air mixtures in-h crted with Halon could not be ignited by a detonati n wave. No written report cf the work is available. I ?S. I. 26 W f. I l v I

l i ) .s 9 The improbability of obtaining a hydrogen-air pocket has not been considered,- but the fact is that the Halon spray configuration is designed t to prevent _such pocketing. Moreover, there is a misconception that if un-inerted hydrogen-air mixtures reach a concentration of 18% hydrogen, a detonation will occur upon ignition. While 18% is considered the lower de-tonation limit, the value refers to tests performed in shock tubes with shock or blast wave initiation, i.e., the strongest and most ideal conditions. In configurations _other than tubes, such as spherical geometries, to our know-ledge, detonations have never been produced with anywhere near limit concen-trations. In reference (10), for example, spherical detonations could only be produced with stoichiometric H / air mixtures, a d then only if one gram of 2 high explosive was used as initiator. The authors predicted that limit mix-tures might be made to detonate if one quarter pound of high explosive were used to initiate the process. These data are cited to provide some idea of the difficulty, if not the impossibility, of detonating anything much below stoichiometric mixtures, and the strength the initiator required. There is one required precaution that must be taken when specifying the Halon require =ent for inerting. If insufficient agent is present, mix-tures may combust with substantial overpressure. The perce-tion that the combustion intensity would be reduced even if agent concentration were de-This may be seen in Figure 12, taken f' rom reference (11), ficient is not true. 'where the data refer to methane rather than hydrogen (Atlantic Research ex-periments with deficiently-inerted hydrogen mixtures showed a similar but not quita so sharp a limit behavior). The CH -air mixture used in reference (11) 4 was rendered inert with 3.6 percent Halon but produced high overpressure with 3.4-percent. The present containment design calls for 20 percent excess Halon beyond the maximum required to inert for 75% zirconium-water reaction. l 6 S.1 Flame Propagation and Fla=mability Limits One may ask whether fla:znability limits determined in small-scale l laboratory apparatus are in fact applicable to systems of very large dimensions i such as the containment vessel. In practice this has already been affirmed by experience with coal mine atmospheres and numerous other hazard situations. (For example, in a case that occurred in Pittsburgh in the 1920's, a very large L gas reservoir that contained an explosive mixture of coal gas, (hydrogen and 1 1 i 27 t s... c. ,,y

W* D y e I r,.. I e' L. i a ],.. I i 100 A B D E +I 90 C m. 80 e t l 2 70 a. N 60 i_ iii! g 350 N N KEY {- s g "^ CF Br pct g 40 3 E 'O A0 ~ 8 0.6 20 C 1.2 D 2.4 7 10 _), ~ ~ ~ 5 3.4 0 2 4 6 5 'io c. TIME, see L. ~ x-. l t 1 Figure 12. Explosien Pressure Growth for Stoichiometric CH. Air Mixtures 4 with Added CF Br in 12.ft Diameter Sphere (3.6% of CF Br 3 3 renders this mixture inert). From Reference 11. 7' 4. M9 28 r- \\ 's-a t... ......i....,r.>.=.- r - l e

I carbon monoxide) and accidentally admitted air had to be made saf e for work This was accomplished by admitting engine exhaust gas with velding torches. until the laboratory-determined f1semability liait was reached.) With Halon the safety of a Raion-inerted atmosphere of hydrogen and air has been demon-strated by a test in a vessel with linear dimensions of the order of ten feet. An understanding of the subject requires a discussion <.f combustion waves and ~ the quenching of combustion waves by convection currents. A' local ignition source in a volume of flammable gas generates a combustion wave by igniting a layer of the ambient unburned gas, which in turn ~ The wave thus comprises a zone of chemical ignites the next layer, and so on. reaction and heat release across which the gas temperature rises from the ig-nition temperature of the unburned gas to the flame temperature of the burned gass and a preceding zone of unburned gas which receives heat from the reaction zone by thermal diffusio's, and across which the temperature rises from the am-If there is no external heat loss, the heat bient to the ignition temperature. flux from the reaction zone to the preheat zone 'is balanced by the convection of heat back into the reaction zone as the preheated unburned gas ignites and In this the reaction zone advances, so that the overall process is adiabatic. case the temperature increases continuously across the wave from the ambient to the adiabatic flame temperature, which is calculable f rom thermodynamic data. The wave propagates into the unburned gas at a " velocity correspond-ing to the diffusion flux across the isothermal plane of the ignition tenpera-The magnitude of this " burning velocity" is thus dependent on the rate ture. of chemical heat release in the reaction zone and en the diffusion parameters. l At high reaction rate the temperature gradient across the wave is steep, the i l l At burning velocity is large, the width of the wave is small, and vice versa. t l approximately stoichiometric composition of the flammable gas mixture, the flame temperature is at its maximum, hence the strongly temperature-dependent is at reaction rate is at its maxi =um, the slope of the temperature gradient i its maximum, the buraing velocity is at its maximum, and the wave width is at t On dilution of the mixture either by an excess of fuel or oxygen, l its minimum. gas such as nitrogen, or by an agent such as Halon which acts or by an inert both as an inert gas and a chemical inhibitor, the flaue temperature decreases, ~ the reaction rate decreases, the slope of the temperature gradient decreases. l r l 29 0 ( tv l l e ,.i, ; *,, p, g .C e:,% 2 9,. s. .e .,.-. - ~ -. -.. _.,

c h>-

  • Burning velocity the burning velocity decreases, and the wave width increases.

/ burning and wave width are inversely related by the ratio ther=al dif fusivity g velocity, which has the dimension of length and represents a characteristic + length of the wave width. The strongest mixSares have burning velocities of the order of b 100 cm/sec or = ore with corresponding wave widths in the 10 to 100 micron range. The theory of adiabete combustion waves places no limit on the stability of d the wave down to an asymptotic approach of the burning velocity to zero an In practice, the burn-pg corresponding approach of the wave width to infinity. s, ing velocity can be decreased only to the order of JC cm/see with corresponding I F.xperience shows that fla=mable mixtures e wave width.c in the milli =eter range. L cannot be diluted beyond some limit at which a esmbustion wave l in this range In this way, one becomes extinct as it draws away from an ignition source. F obtains a " lean" limit of flammability if the diluent is excess oxygen or air; y d a " rich" limit if the diluent is excess fuel; or a limit defined by the require h inert-gas addition to a given fuel / oxygen or fuel / air sixture, or for the present b / purpose a limit defined by the required Halon addition to a post-LOCA hydrogen air mixture. The existance of fla=cability limits implies that in the indicated range of low burning velocities the chemical reaction in the wave is quenched V -4 This is attributable to a convection process which is not shown by' heat loss. The in the idealized model of a plane co bustion wave but occurs in real waves. hich shows (f' mechanism of this process is illustrated by the sketch in Figure 13a, w Q f a tube, the the profile of a combustion wave propagating toward the closed end o It is seen that the thermal expansion of the gas in the p O other end being open. i st the wave generates a flow of burned gas, and that the resulting thrust aga n heat unburned gas generates a current along the wave front which transports

a This flow pattern follows from theoretical laterally away from the center.

The illustrated wave consideration but has also been verified experimentally. h. f and flow configuration is stable in the flam=able region of mixture compositions w [ if the flow of burned gas is in the laminar range, but in a limit mixture the Figure 133 illus-wave is gradually quenched by the lateral heat convection. i trates the same nachanism of quenching for the case of flame propagat on m a The flow field becomes turbulent and the consequent random dis- { M-large volume. It has been observed tortion of the wave generates lateral heat convection. d. L' 30 f L t,., ,...e..4. e

l O i s'/ t ' ~ ~ :. -

~..~.~

twa.d ~~. Swaed .. ' ~... - -.. :.: ~~ ~ 4 .s~~.~.~._ y s,.. cio e4 ene Cr ead_ Figure 13a. Flarne Propagation in a Tube. 4 % \\e T e Figure 13b. Unconfined Flame. ~ < n m_c 2 ,s, r, s a ". \\,,/ ', !,!!.li: 6 \\ l 1 / e is di!!./N \\\\'si i: l i s i i i l '. // !;,n',,'!: ! e en / Ja::ir:::! e :: i l .i E 3 + 2 l ~ - Figure 13c. Upward and Downward Propagation of Flames in Vertical Tubes. 6 I I l 31 i i i

= _ _ _ _ +. 4 j axperimentally that extinction occurs in randor areas of a turbulent combustion I wave even if the sixture is well inside the region of flacusability. The effect p. depends on mixture composition and turbulence level, and the holet chat are 4 i thus formed in the wave sheet close up again. At the flammability limit, this W** does not accur and extinction progresses over the whole wave area. It follows l l that flammability limits depend on the combustion wave parameters,'viz., the burning velocity and wave width, and on the thermal stress which is exerted on T the wave by the heat-dissipating convection currests. The wave parameters are ~ determined by the sixture composition, whereas the thermal stress depends on i am the. turbulence level and other environmental condition. A conservative value e-of the flammability limit'is obtained if the thermal stress is reduced to the I minimum theti may occur in practice. It is well known that limits for upward g l flame propagation require a larger mixture dilution than limits for downward I f propagation, and accordingly, limits are always determined for upward propaga-tion. The dif ference between limits for upward and downward propagation is due g to the effect of gravity on the thermal stress. This may be visualized with 7" l the aid of 71gure 13c. In upward propagation the thrust of the buoyant flame h l 5 gas against the unburned gas is added to the thrust 'f the thermal gas expen-p sion, with the result:that the lateral convectiop.. shifted to a egion that M i i 1-is sot as close to the wave as in downward propagation, and.the et..rmal stress e is correspondingly reduced. 1 In special laboratory apparatus known as flat-flame burners, the thermal. stress is miniszed by passing the unburned gas through a grid of ori-7> Cices in proximity of the combustion wave. Ir. chis way, the lateral heat con-vection esa be so much restricted that mixture compositions corresponding to ir-l burning veslocities of less than 5 c 2/see and as low as 2 cm/sec become flammable. gut for practical purposes, the flammability limit for upward propagation, as determined in standard apparatus at low turbulence levels, furnishes a proven k ] 1 standard of safety. I 5.2 Halon Percentage f.equired for Preventing Ignition of Post-LCCA Hydresen/ Air Mixtures by Detonatinz H*drogen/ Air Pockets l IF* It has been found (1) that the Halon percentage required to prevent ignition by strong condenser rpar's is somewhat smaller than the percentage re- .6.-. quired to prevent ignition by squibs, i.e., by electrically ignited match heads. c e i { 32 i C 1 ,,,,j., f,,j .J }' .s. .= 't

  • o, c".%,.
3...,, *.

..,t., ,,..? .+ .,. _. _. _.. _ ~...... - - -

Inasmuch as s,uibs release more energy than the condenser sparks that had been used in the work, it may be thought that the Halon require =ent depends on the source energy, and hence, that the limit percentage determined with squib ig-niters is too low in a post-LOCA situation where the ignition source might be a detonating pocket of hydrogen and air. This reasoning is based on a miscon-ception of the cause of the observed difference between ignition by sparks and squibs. The energy that is generated by these sources already vastly exceeds the minimum energy required for initiating a combustion wave (of the order of a millijoule); hence, the source energy is not a factor in determining the critical Halon percentage. The diff erence between sparks and squibs arises from the fact that a condenscr spark releases its energy explosively and thus generates locally a zone of high turbulence which tends to quench the ir.:1pient combustion wave. Accordingly, even though the critical Halon percentage that prevents ignition by sparks may not be sufficiently large to make the mixture non-flac=able, or in other words, to prevent the propagation of a combustion vave through the mixture volume, the wave that forms in the high-temperature j field of a spark is quenched by the spark-generated turbulence and does not C reach the calm region beyond the zone of turbulence where it can propagate; thus, no ignition occurs. In contrast, the relatively slow energy release that.ccurs in firing a squib generates a much less disturbed temperature field that allows the wave to develop and propagate through a vaak but flam-mable mir.ture of this kind, so that ignition occurs. But if the Halen per-centage is increased, the wave that propagetes from a squib flame eventually becomes so slow and wide that it is quenched by the convection currents which are induced by the thermal expansion of the burning gas, as discussed pre-viously. In this inerted state the mixture cannot be ignited by any local energy source, including a source that is as largo, hot and powerful as a detonating hydrogen / air pocket in a post-LCCA situation. Such detonation would produce a large volume of hot flame gas and an additional volu=e of mixture that is heated by shock compression, and a combustion wave would develop within the te=perature field that is thus formed; but the wave would decay as it draws away from the vicinity of the pocket and the pressure in-crease in the hoge containment vessal would be negligible. There would, in fact, be very little combustion outside the volume of detonation products 33 6.

P l V' w ,,,.cause the flame-quenching convection currents would bs strongly augmented Accordingly, a Halon ,,, the high turbulence at the site of the detonation. ,,,,o:entage that prevents ignition by such an opti=al ignition source as a ,,,pitb is certainly sufficient to prevent ignition. of a post-LOCA atmosphere n-j,,. any source including a detonating hydrogen / air pocket.- t,0.- It may be mentioned that (ironically) a low-voltage electric arc ,, an ignition sourte similar to a squib fla:ne and thus should be regarded as But the recomnended dose ,,t.itively more hazardous than a hydrogen / air pocket. ,g Italon in a post-LOCA atmosphere eliminates any such consideration. W o e lV W '.5 'r-u I. e , P, h y 4.,. I d 4 I e L' e-W i" p. l' f I 6 1 Y \\C"" 34 r

  • + -. ~...

$ 4..,,,,, l l

3 6.0 EFFECTS OF HALON 1301 AND D; COMPOSITION PRODUCTS UNDER POST-LOCA *:0NDITIONS ON MATERIALS OF CONSTRUCTION In Section 4.0 of this report and also in reference (1), it is shown that Halon 1301 can decompose in water solution. The decomposition proceeds -3 until the bromide ion concentration reachts 5.2 x 10 moles / liter, equiva-lent to 415 ppm by weight. Without control measures, the pH would fall to about 3. This process could give rise to corrosion if it occurred in the reactor cooling water and was lef t uncontrolled for extended periods. The following study of the situation has been conducted by A.J. Biedermann of the corrosion consulting firm of C.P. Dillon and Associates. 6.1 Corrosion Mschanisms It is worth presenting descriptions of the potential types of corrosion that could result in the containment post-LOCA case. These de-scriptions will f amiliarize the reader with terms used in following sections. It is emphasized that the corrosion assumes no mitigation procedures or in-hibitor addition. General Corrosion (Uniform Thinning) - General corrosion occurs by chemical or electrochemical rea,ction over the entire exposed metallic sur-faces resulting in general thinning. Fcr er.a:ple, n piece of :ine or steel immersed in dilute acid will dissolve at a uniform rate over its entire surface. The reaction equation is: Fe* + 2HBr + Fe* + 2Br" + H + (1) 2 Since bromide ion is not involved in tha reaction, the iron reacts with hydrogen ions to form ferrous ions and hydrogen gas. The reaction is depicted in Figure 14a. Calvanic Corrosion (Cathodic Protect.on) - When dissimilar, con-caccing setals are immersed in a corrosive c; electrically conductive solution, a potential difference develops that produces alactron flow between the metals. Corrosion of the less corrosion-resistant metal is usually increased and' that of the more resistant metal is decreased. This effect is depicted in Figure 14b. In this case the zinc (anode) is corroded at an incI 2ased rate while the iron (cathode) is not corroded, i.e., cathodic protection is produced. In the fol-lovin; list of metals an upper metal will be protected while the lower material will undergo accelerated corrosion. 35 asrymtsspeMnT.*.3meWTrM/.?A9tStrMWAWD9mfF r..im.xmTdN1"?J7TfWE'K't?T".s.4.--m. ScG ww.? h

L ~ I i 7 e.- L 1W

  1. ~

d+ I ~ 7,41. 4 --e 1,4 4 e. f bs* ZINC e-i., , g++ gf 1 'e-IRON a // S r' ek #(Af 5# E.- ~ e u "* s ;qt J c' / 0f \\w. r 8.w.= ' IRON

e...
s. El trochemical Reection illustrating General Corrosion

'd <e-

b. Electrochemistry of Galvanic Corrosion Cathode Protection 1he k

METAL y 0.+ 0N 1 og.e, y ' 0 l 2 \\ " ~.;

\\

b* CI.'I. 4*)'H%'M* y ~ ~

  • Q/ Cl* ci~ cj
  • f.

~* Cl y*gg+ sH cg j c' f METAL e.- [ Electrochimistry ofkrevice Corrosion e Figure 1?. Diagrams Illustrating Various Types of Metallic Corrosion Mechanisms. .h) ' 'N E %een ' {* ; <Yj , o WMygs,g

  • QZp y g?op ~,[,',Wfk%

{w l 0 4 f.12'"3 M. u __ _~

Calvanic Serirs of Commercial Metals Titanium Silver Stainless Steel (passive) Copper Tin Lead Stainless Steel (active) Cast Iron Steel Aluminum (2024) Zine Magnesium Crevice Corrosion - Intense localised corrosion can occur in

crevices, i.e., holes, lap joints, under bolt heads, in, incomplete welds and under gaskets when exposed to corrosives. The initial reaction around and inside a crevice is the same as for general corrosion; however, due to the stagnant condition'inside, oxygen"is consumed by the following reaction:

2 + 2H O + 4e + 40H" ~ 0 2 .As metal continues to dissolvi, the crevice is filled with e'xcess of positively charged metal ions which is balanced by migration of halogen ions into the cre-vice resulting in high concentration of metal halide. The phenomenon is illus-trated in Figure 14c,. and requires some initiation time (usually months) to form; however, the time is significantly affected by temperature and pH, high temperature and low pH being the worst case. Pitting Corrosion - Intense localized corrosion can occur at random locations by the mechanism of crevice corrosion; however, no pre-existing cre-vice or void is required. Since halides stimulate metal dissolution by break-ing down the protective surf ace film, solutions containing halides can cause pits primarily in acid environments; however, neutral and alkaline systems can still pic. Again, as in crevice corrosion, high temperature and low pH are the worst case. Stress Corrosion tracking - Stress corrosion cracking occurs by the simultaneous application of censile stress (applied or residual) and a 37 l

e J I E~ y Since the mechanism involved is not well under-specific corrosive medium. stood, the most reliable and useful infor=ation can only be determined by m-- As in pitting and crevice corrosion, for example, halides break testing. 1 the passive film or enriched surface layer on stainless steel allowing more Breaking of rapid corrosion at various points,.thereby initiating cracks. f films ahead of the advancing crack prevents healing and propagation continues. The requirement of corrosion in stress cracking was demonstrated when advancing I cracking was stopped by application of cathodic protection (12). f T 4 k Literature search 6.2 Extensive literature searching was conducted to determine exactly f! for what could be expected in the af termath of a LOCA and use of Halon 1301 A Unfortunately, very lictie published corrosion in - combustible gas control. formation is available on Halon 1301, and practically nothing is published on hydrogen bromide and bromide ion corrosion in the low concentrations expected g in the post-LOCA system. . bromide solutions are quite {' Since, according to Hise (13), ".. comparable to the other halogen" solution in the sense that pitting of stain- " available corrosive data were collected and itss steel is somewhat common, The follow- ~ ', reocrted here for chloride systems as well as for bromide systema. ing a c summsries from specific rv erences that were foundt U Testing has induced stress corrosion cracking in e 304 stainless steel at tenerature as low as 60*C G where Nacl was deposited from solution, i.e., chlor-(14). ides collected and concentrated in a humid environment e Stress corrosion cracking occurred ae 80'C in neutral e solution at chloride concentration of 100,000 ppm (15). Stress corrosion cracking has been produced in tests e at 260*C to 343*C in oxygenated water (02 " 2 EE*) rj containing from 0 to 200 ppm chlorides where there is evidence that at red tced oxygen levels higher { chloride icvels are required (16). Cracking of 304 stainless steel occurred at a pH of 2 (8000 ppm Nacl and 141*C) and (40,000 ppm Nacl and 82*C)(17). { e !{ 38 h

jPWG* Ip. hPa. w. W= 'tre-100 = 'l II 80 7 L g Ub! 318 S.S. y 60 w a c: hee. N 3 a:w 4 40 l 3M ES. <W 20 pH = 8.3 1." b 0 100 1000 F CHLORIDE CONCENTRATION (ppm) m l l l C I Figure 15. Localized Corrosion for 304 and 316 S.S.in River Water m at Various Chloride Levels. .m f e 40 IP' ...a.... 4 l .. +.,_ r. ,_-..__m..

e The curves of Figure 15 predict the onset of crevice corrosion for stainless steels at various chloride concentrations (18). it is known that at temperatures above 150*F chloride e stress corrosioa cracking is a problem during refinery shut-down where moisture would reach chloride deposits in stainless steel equipment (19). e Nitrate and carbonate solutions are used to avoid stress cracking of stainless steel (20). The presence of chloride ion, water, oxygen, or some e oxidizing agent upon the surface of an austenitic stainless steel held in tension (stressed) above room temperature is necessary to induce cracking. The time l to failure is temperature dependent, decreasing rapidly above 65*c (21). Bromides have caused cracking of 316 stainless steel (22). e e Bromide ion pitting of citanium will occur in aerated 1 M EBr at 23'C (23). Bromide ion environments are markedly less dangerous e than chloride environments (24). The following is a summary of some relevant effects of plain Halen 1301 on construction materials per reference (2): Negligible corrosion occurred on various metals including e aluminum, stainless steel, steel, and brass at 250'F, 130*F, and room te=perature and at moisture levels of 2 ppm (commercial material) and 72 ppm (75% saturation). (Galvanized steel was not tested.) Pure Halon 130'. at 600*F exhibits the following e metallic corrosion rates: l 39 B i I 5. t-m.;.. -k WL

Netal Mils per Year Inconel 3.0 1 316 Stainless Steel 7.5 Steel 14.4 e Pure Halon 1301 at room temperature significantly damaged ethyl cellulose, cellulose acetate /butyrate, and Silicone rubber. Polyethylene resin, cellose acetate, acrylic resin, " Teflon", as well as butyl, "Adiprene," and "Viton" were slightly damaged. i 6.3 Discussion of Corrosive Effects Expected in Containment Cooling Water Metals (Without Treatment) - If a Halon system were used during a LOCA with no effort at corrosion control, and clean-up did not occur within a few months, potential exists for the following detrimental effects: Probable stress corrosion cracking of stainicss steel e of heated surfaces. e Possible stress corrosion cracking of stainless steel in water held abeve 150'? for an extauded period. Er. tensive crevice corrosion, pitting and ga15anic e corrosion initiated during the period of low pH and high temperatura perpetuated by increased conductivity of the water and presence of bromide ion. l General corrosion by hydrogen ion would be limited to e that produced by the ionization of HBr. The following informative estimates can be made concerning e the amount of metals that would react with the total bromide ion inventory. Referring to equation (1) on page 35, it can be calculated that the 2465 total pounds of bromide from Halon decomposition would consume approximately 860 lbs. of iron in steel. In so doing, the sclution would dep!ste i itself of hydrogen ion and self-neutralize. This amount of iron is somewhat less than two cubic feet in volume. l 41 e -m-

P 6-- m o As an illustration, if this volume of metal came from, say, the inside surface of the reactor pressure vessel, ~ the loss on the surface would be about 8 - 10 mils. Simi-lar estimates yield consumptions of 277 lbs of A1, or of j, about 1,000 lbs of zinc. As predicted by the galvanic y series, the zine on the galvanized steel would be rapidly attached followed by aluminum, then steel. Lu. Metals ('Jith Treatrentl - If 9e Halon system were used during a LOCA, corrosion control should be possible an one or core of the following ways, v.. testing being required to determine which s'.thod is suitable: p P Halon der neposition may be avoidable by addition of e bromide ion (Na3r, K77, LiBr); likewise, the pH de-L'. a pressica may also be avoided. Anoth2: approach would ,,.i be to let decomposition of Halon occur and control pH (8 - 10) with caustic addition (NaOH, KOH, or LiCH). ~ Either of these should mitigate the general corrosion 'and reduce the potential for stress corrosion cracking. Inhibitors can be added which may prevent localized j,, o corrosion. For example, chromates, nitrates, borates, silicates,'and zine have been effective in'similar systems. +. .f. The use of sacrificial zine or magnesiu= anodes could I e potentially eliminate both the pH depression and the L-localized corrosion problems as well. Non-Metals (With or Without Treatment) - It is doubtful that the various nea-metals will be significantly affected due to the very low concen-l P trations of corrosives involved. -m .6.4 conclusions From Materials corresion Studv The use of Halon 1301 to suppress post-LOCA hydrogen burning may result in significant corrosion problems if allowed in place for years without adecuate control procedures. The exact effects with or without i corrosion control are unknown since little corrosion study is reported for b' ~ H3r or bromide salts in the concentrations expected. w m 42 L.' y L.. i _._ d

p Projections based on available bromide data along with hcl and chloride salt data indicate that lack of corrosion control would result in minor general corrosion; however, localized corrosion (pitting, galver.ic, crevice, and stress corrosion cracking) could be serious. Corrosion mitigation would employ pH adjustment, addition of inhibitors (chromates, nitrites / borates, silicates, and zine), possibly cathodic protection and sacrificial metal. Corrosion testing is indicated to determine the ef fects on the systen with and without treatment. / ? i e e { f i 43 t i [8 e 8 4F " W i 1

W REFERENCFS (1) McHale, E.T., " Hydrogen Suppression Study and Testing of Halon 1301," Phases I and II, Final Report, Dec. 1976. (NTIS Order No. PB 262 180); Phase III, Final Report, March 1978. (NTIS Order No. PB 278 911). (2) Product Bulletin B-29D, "Halon 1301 Fire Extinguishant," E.I. duPonc de Nemours and Co., Inc., Wilmington, Delaware 19898. ~~ (3) Standard No.12A, "Halogene.ted Extinguishing Agent Systems - Halon 1301," National Fire Protection Association, Boston, Massachusetts 02210. (4) Furno A.L., Cook, E.B., Kuchta, J.M. and Burgess, D.S., "Some Observa-tions on Near Limit Flames," Thirteenth Symposium (International) on Combustion. The Combustion Institute, Pittsburgh, PA,1971, p. 593. ~' (5) Product Bulletin S-35A, " Toxicity of duPont Halon 1301 Fire Extinguishant," E.I. duPont de Nemours and Co., Inc., Wilmington, Delaware 19898. L'", (6) Musick, J.K. and Williams, F.W., "The Use of Halon as Fire Suppressants - A Literature Survey," NRL Report 8161. Naval Research Laboratory, Wash-ington, D.C., October 1977. j. (7) Lewis, B. and von Elbe, G., Combustion. Flamer and Explosions of Cases, Second Edition Academic Press, New York, 1961. (8) Carlson, L.W., Knight, R.M. and Henrie, J.O., " Flame and Detonation Initiation and Propagation in Various Hydrogen-Air Mixtures, With and Without Water Spray," Rockwell International Atomics International Division, Canoga Park, CA 91304, March 1980. rw.. (9) Nesbitt, L., General Electric Company, private connunication. ?*" (10) Atkinson, R., Bull, D.C. and Shuf f, P.J., Combustion and Flame, 3 9, 287 (1980). e-- 9 (11) Johnson, A. L., Furno. A.L. and Kuchta, J.M., " Infrared Spectral m+- Radiances and Explosion Properties of Inhibited Methane-Air Flames," Report of Investigations 8246, U.S. Bureau of Mines, Washington, D.C. 1977. f (12) Priest, D.K., Trans-America Society of Metals, 47,, 473 (1955). d'; (13) Hise, D.R., Process Industries Corrosion, p. 240-246 (1975). f*~k (14) Yajima, M. and Aril, M., Materials Perfornance, Vol.19:No.12, ' i

p. 17 (1980).
  1. ^

(15) Truman, J.E., Corrosion Science, Vol. 17, p. 737 (1977). F-(continued) w-- i "e-44 u~, ... c..: ..,. e s.

REFERENCES (Continued) (16) Cordon, B.M., Materials Performance, Vol. 19:No. 11, p. 29 (1980). (17) Asphahani, A.I., Materials Performance, Vol. 19:No.jll, p. 9 (1980). (18) Efird. K.D. and Holler, C.E., Materials Performance, Vol. 18:No. 7,

p. 34 (197 9).

(19) Bryant, R.E. and Greer, J.B., Materials Performance, Vol.19:No.11,

p. 19 (1970).

(20) NACE Standard, "Protaction of. Austenitic Stainless Steel in Refineries Against Stress Corrosion Cracking by Use of Neutralizing Solutions During Shut Down," RP-01-70 (1970). (21) Van Drcffelaar, H. and Hudson, G.B., Materials Performance, Vol. 5:No. 3,

p. 62 (1966).

(22) Spahn, H., Technische Veberwachung, Vol.14:Nos. 7, 8, 9,10 (1973) VDI VerlagGmbH, Dusseldorf, FRP. (23) Petic, J.A., Kondro, B. and Dabosi, F., Corrosion, Vol. 36:No. 3,

p. 145 (1980).

(24) Dillon, C.P., MTI Manual No. 1 (1979). 5 m 45

it, 4.- ) d I = s y e { ( 1 ATTACIDENT B ) i i hi i n eh= -n-w-h e-


m5

--n S carnr- --- + e n - - n e-artrnnsww-h - --- re r -- - - -me v r e mw err N e-vv-m --w or sere---Mr*-e+

  • *- We -ea rn sy n--

w,- - - - - -me

r" ~. '.. UNITED ST/.TES COVERNM::NT . MeniorandMm TENNESSEE VALLEY AUTHORIIY. TO- -W. P. Joest, Superviso Codes, Standards and Materials Section, lil9El.8,4,',C K,, \\ R. 0. Lane, Supervisor, Siggleton Materials F.ngineerit.g Laboratory, l' ROM ' : SHE-K DATE April 2, 1981 Str.'OCT:. SEQUOYAH NUCLEAR PLANT - EFFECTS OF.** 70'O PPM HF ON 304 STAINLESS STEEL AT 2000F (TR 2-18-81) An evaluation of the enrrosive action of a 1200 ppm HF colution on 304 stEinless steel at 200 F was conducted as follows: 1. 'Two solutien-annealed U-bend samples"from as-received stock in solution-annealed condition were prepared by bending 1/4-in. wide strips of 16 ga 304 stainless steel around a 3/4-in. mandrel. Eending was stopped approximately 15 degrees prior to the point where the legs of the U-bend became parallel. A 304 stainless steel bolt inserted in holes in the legs of the U-bend uas used te draw the legs approxicately 15 degrees beyond parallel. Edges of the U-bend were prepared prior to bending by water-cooled grinding.on' a 240-grit belt to prod,;ce a flat, which would easily reveol.any cracks or fissures upon subseqtent evaluation. 2. Two additional U-bends of the sa=e =aterial were prepared in a similar fashion as above, except they were given a sensitization heat treatment at 12000F for 3 h in argon. !~ 3. A HF. solution was prepared by adding 1/2 cl of a 49 percent'solutien of HF to 200 ml of deionized water. The ph of this solution was 3.0, and the fluoride ion concentration was measured to be 1170 ppm by specific fon techniquss. 0 4. This solution was placed in a nalgene bottle, heated to 200 F, the four U-bends added, sealed, and placed in a convection oven to maintain 2000F. After 24 h the samples vere removed and exacined under a stereomicroscope at magnifications of 20 to 70X. Rapid corrosive attack at the grain boundaries of the sensitized samples was evident, particularly at the square edges of the specimen. No cracks were found. The unsensitized semples did nc.t reveal any appreciable ef fects af ter 24 h. All samples were beginning to develop a black adherent film on their exposed surfaces. S .qv; M5. a.... r.. c c :. n s..r. .s..:...-... ; .., c -.: m,.,...

. s 2 'W. P. Joact April 2, 1981 3 SEQUOYAH El' CLEAR PLANT - EFFECTS OF 1200 PPM HF ON 304 STAINLESS STEEL AT 200 F (TR 2-18-81)- 0 4 Af ter an additional 96 h (120 h total) the four U-bend samples were reexamined end found to be-covered with a black film obscuring visual or microscopic evaluation. Ultrasonic cleaning in inhibited hcl at rocs temperature eliminated the black film. Stereemicroscopy revealed advanced intergranular corrosive attack of the sensitized U-bends--actual grains .and clusters of grains had fallen out of the prepared surfaces. Inter-granular corrosion had virtually clic.tnated the square edges of these U-bends. -The unsensitized' samples, on the other hand did not show intergranular corrosion. Rather, some pitting corrosion had taken place on the U- . bend surfaces (edges) which had been prepared by grinding. Pitting . was not observed, however, on the outer surf ace of the' U-bend represent-ing the rolling plane of the as-received material. Detailed metallography will follow in a supple =entary report. AWl R. O. Lane ROL:PVG:PGK-cc: Frank Van Meter, 500 SPT-K MEDS, '4B37 C-K 4 J e 6 S O Y G O ~. _,... _.... _, _.. _. _.., _.,,

UNITED STATES CSVERMENT SE '810605 0 u c. ' Memorandum TENNESSEE VALLEY AUTHORITY To C. E. Roberts, Supervisor, Codes, Standards, and Materials Section, _.V.19D,l_85 _C_-K_ _ FROM R. O. Lane, Supervisor, Singleton Materials Engineering Laboratory, SME-K DATE June 6, 1981 $UBJECT: SEQUOYAH AUCLEAR PLANT - EFFECTS OF HF AND HBr SOLUTIONS ON 304 STAINLESS STEEL U-BENDS Initial tests evaluating the effects of a 1200 ppm HF solution on both sensitized and solution annealed 304 stainless steel U-bends at 200 F vere reported in SHE 810403001. This memorandum covers additional tests involving similarly prepared U-bends in a solution containing 1200 ppm HF and 400 ppm HBr at a pH of 2.9 and a gortion of the same solution buffered to a pH of 7.0 with NaOH, both at 200 F. Two solution annealed U-bends and two sensitized U-bends prepared identical to thati described in the previous memorandum were placed in each solution contained in an enclosed Nalgene bottle and maintained at 200 F. Results are as follows: After 24 h all samples were examined under a stereomicroscope at magnifi-cations of 20 to 70X. An extremely rapid attack of the sensitized samples was present in both buffered and unbuffered HF plus HBr. Figures 1 and 2 show stereomacrographs of the sauples af ter altrasonic cleaning with an i inhibited Hel solution. The sensitized samples in the unbuffered 1200 ppm HF plus 400 ppm HBr show uniform grain boundary attack on both the tensile and compressive surfaces with the r.eutral axis of the sample showing light attack. Near the tensile surface the grain boundary attack tends to create fissures normal to the specimen axis. See figure la. Also, the sharp edges of the tensile surface are completely eliminated through removal of grains by the grain boun 'y corrosion. The sensitized samples exposed to the buffered 1200 ppm HF plus 400 ppm HBr showed very severe but localized grain boundary attack af ter 24 h. See figure 2a. The attack shown in this photograph at the tensile surface consists basically of deep pits. Fissures of the type seen at the right side of the photograph were also ebserved. Picting was observed predomi-nantly on the tensile surf ace but also was seen on the compressive surf ace. Conventional intergranular cracking was not observed. p e e em Buy U.S. Savings ends Regularly on the_ Payroll Savings Plan 3 e n-,- ,-w,.

2 C. E. Roberts June 6, 1981 SEQUOYAH NUCLEAR PLANT $FFECTS OF HF AND HBr SOLU ~ IONS ON 304 STAINLESS STEEL U-BENDS-u w..'. Its.: ? NO ' ?? The unsensitized samples (solution annealed) were returned to their - respective solutions and allowed to remain for a tecal of 120 h at 200 F. Macrographs are given in figures ib and 2b. In the unbuffered HF'plus HBr solution, uniform etching of the specimen surface took place with minor pitting of the type seen in figure Ib in the center of the photograph. Macrosegregation was also delinested as sean by the dark line extending through the midposition of ths sample. Otherwise the samples remained in good condition with no observed cracking. The unsensitized samplas exposed to the buifered HF plus HBr for:120 h at 200 F revealed much the same as for the unbuffered solution samples except to a lesser degree. See figure Ib. Figures 3a, 3b, and 3c show comparative macrographs of the previously reported samples exposed to s 1200 ppm HF solution for 120 h. After 120 h in 1200 ppm HF (pH 3.0) a 200 F, the sensitized samples exhibited less severe attack than in the unbuffered bromide solution for only 24 h. Compara 3a with la. Similarly exposed unsensitized (solution annealed) U-bends compare with those exposed to the bromide solutions. See figure 3b. Figure 3c shows an enlarged view of the nature of the grain boundary attauk in the unbuffered 1200 ppa HF solution. No cracking was observed in either the solution annealed or sensitized samples in the HF solution. R. O. Lane 4 FVG: ASH cc: MEDS, E4B37 C-K e O *e pS** l 1 e I

c} 6-81-28 I e. f *1 r'. t'h(' [x-g-/st ' gyf x 9' e. q.

.r..

y V 1 y',c, A?<t}:.... : y.; 6. .1. g'g ' :' ~"-L.E*Q'+y - Q, -.. a:Fe:: . h_ ;-Q ',

  • y s.

h i =

  • ~

s , m r-Figure la. Sensitized 304 stainless steel U-bend sample immersed in a solution of 1200 ppm HF plus 400 ppm HBr at 200 F for 24 h. 46X A_g1_ o .; a:s:L ~ w~ .n - -<. - :+ 4.. w,-.. - . p..: ...... y -!. s ;'a, *? '7 i "; -'

  • 7. f >.' r - - -

5..;..-* { hh h i'? b '.~ '_ g .g ~. U-P E 7; 35 e ~, ' ' ' a. w. - "pM; ~ 2.- u3 g 1f -k, Mh*". ~ m-r.. 1 . yn - - r. ,. - w r ~ -' *- - ' ' 4 *.w n'... u r.,,*3.. *. *, ' - m.. $ '.,';i-e. - ' q-z. t.- g, 2 - -". %,., - -,,- ;.. o., & W Tik_,^; i &g,W i+.

  • =. 5,*:

l Sw Figure ib. Solution annealed J04 otainless steeA u-pena sample gmmersec in a solution of 1200 ppm HF plus 400 ppm HBr at 200 F for i 120 h. 46X e Se v--w w, a ,we--w .-_,,m__ m -w. ,,,go-, -,.--.m wemm,.,,ymcy---wmm-rw-9-i-. , g w y gw g---wv r

l 6-81-30 l i-x. y mm m _ m 1 a mIRS: MA, ,.j, -

4... g t

[.h_, J, "...k s... - ) wnwn m%=: l.,.=. 2.G ~ ~= c3.- e. s x.e_ .?k N - L..d$' ~. 7 *.* ; ~ f; e* ' ;%' %,f,g.. gs- -+ .r. s.c h f.*~.. 9 -. ~ - -m - *gw% r~-= -.w y'.-*' % af?" w.9.'Q'.'i s .is w ~- .:..1 3. ' A*L M,. - .s,... p r G 2 ':...%4%p-. t e ~,.'. 1 ; m..c, 4 w~. y. s '. '.. g:. ?,;,y -;~ ~.,f;tet: R.AQ_%-.--qJMpcc~.-:-.= .- Q.. ~.. w - -- m v, ; :.y. -v: QF~:."b.*q?;. A g 's *.='."*. - ~- w %. 2.:,'W. fY}&e:k. ;gZtv. c..:.: c:..T~ 'C., .m. " .W.$ 'y:.;; r; l ~,;, -l.. 1. ' ~ %.e,.r V: %,,,, .~%.%->; :...; n Figure 2a. Sensitized 304 stainless steel U-bend sample irmersed in a solution of 1200 ppm RF glus 400 ppm HBr buf f ered to a pH of 7.0 with h'A0H for 24 h at 200 F. 46X 6-81-31

  • f,4 @ p>V @ ;. Q -,,y A W 24p p g fcs...,...,., 9@9 : 4.Q.

y,yp.y,; . :.v 0 -v a .- n. t yrq,. - -. ;. :.,.,,.. W uspr,~&:

?Qt{

b- + ps, .~ xa. ./'.,5.., c - 4 4 5... '; SW * ' ; ' -.

y' -
.:,=e ~g -5 '- ~. =,

...:...,.~.,.. ~ " ~ ~ :na& ~* . W, _,s.$* a.. f# dAmav+ss.a.* 4 :. ' y_ _*,,a.,.:r ) ~ r ;. -- ea<

  • g i..

g a1 %[YDj.O53 M s5kisa%m&# " % &M ~Q.u~ l $. -- ^~ E ~ ' 3* ..3.E5 I- . w % e,g. ..e _ _ e v,. ,..c .w =.. g was.-. a. %*.054 \\A .3 b -h w r.e f, y.n w, 4 D 5 4 e .. ~.

  • WM kM - _; j.sg 7 c g; w,qp;.:gp2 i-
  • 'f+,'y l? k %Y g g g f q

Figure 2b. Solution annealed 304 stainless steel b-band sagpie immersed' in the same solution of figure 2a for 120 h at 200 F. 46X

4-81-19 f $b: @%[N,; V-Q~ V,T 'Cv %.5x..-St@u? $M%p2.%.[p, N% ~ ! ,+:4-iff!'. N f Yd. 2 +- f* #8[ M.? l

  • ~

~.'., s. : %..b"'.,d.,,'.S. 'v T' W 3h , 6,a,.. c

  • Y$t'jh'.W,hft%: =k'h9 h h$Q 'h l

N ~ . l..,&$ 4:':a-hy&< tY Ni&'*'ibX%dQ. 4 k n

  • r r.

s;.. M.s:;. l=M N. Figure 3a. Sensitized 304 stainless steel U-bend sample i=mersed in a g solution of 1200 ppm HF at 200 F for 120 h. 46X 6-81-32 ' +' T '.w'^m."W!'SNk%$ ~'.~ W

  • fA M & $ (

2 c :-w m< ' ' !ym s : .6.-e: mm-g ;gp- _-r- - - r w.n - - n w - nn- _, g

e. Jg--..__

' =-- s.,- $ g rY;., W &' ~ *r - W -A*N __sC .p gr-. - - Y Y '.... .l ...' 4 . 2--.v.y. g [# T 2 % _1 2 n __E e - -w, ar=w- __. _ ---rrnar;;s,., e .. m -- -y Figure 3b. Solution annealed 304 stainless steel U-bend sample immersed in same solution as figure 3a for 120 h. 50X

s..

=

4 6 3_ .-2.s_ s .b r_ u-7_%- l 4 M id, 'h .Y3 5 ~ s. 1._.;- Figure 3c. Enlarged view showing grain boundary attack of figure 3a. Note loss of grains and clusters of grains from surface. Right side of photograph is specimen edge. 200X I l l O e em ,,._..-.-,y,ym..._,,,,.mw-.,,,--._-_7_,,...,,,._,_,,,r,.,_.,_., g --w w a w._,-

l l D l ATTACIDENT C i l

4 l o e DESIGN REQUIRSMENTS FOR A PERMANENT HYDROGEN MITIGATION SYSTEM June 12, 1981 SEQUOYAH NUCLEAR PLANT UNITS 1 AND 2 REVISION 1 d i i h ( , -,,, - -m- - - - - .-e,-, ,--e._ ,,,_-,--e.--3w.. r --,,,m,%. n, -e-.,+,y..-e<,n-, ,--y. ,--w -,3--,-%., _m-%-,rm.,,

D 1.0 SCOP 3 1.1 This document provides the functional requirements, the environmental requirements, the system features, and control and power scarce requirements for a permanent hydrogen mitigation system (PHMS). f 2.0 CENERAL DESCRIPTION i 2.1 This PHMS shall consist of the ignitors and the control and i power circuits. 30 FUNCTIONAL REQUIREMENTS 31 The ignitors shall be a reliable ignition source, capable of igniting hydrogen at low concentration levels (5 to 12 volume percent) in a post-LOCA environment. 32 The ignitors shal.1 be controlled manut.113 from the main control room. Control of the ignitors shall be divided into redundant groups with the status of each group displayed in the main control room. 33 The PHMS is not required Caring any phase of normal plant operation. 4.0 SPECIFIC SYSTEM DESIGN CONDITIONS AND REQUIREMENTS 4.1 Environmental Requirements The PHMS components inside containment shall be qualified to maintain their functional capability under the full range of main steam line break and post-LOCA temperatures, pressures, humidity, radiation, and chemical sprays present in the containment. These components of the system must survive the effects of multiple hydrogen burns and shall be protected from containment spray impingement and flooding. All components of the system outside containment shall be qualified to operate in the environment in which they are l located. 4.2 System Features The PHMS shali have the following features: 1. Meet the requirements of seismic Category I. 2. Operate in the environment specified in paragraph 4.1. 3 Redundancy 4. Maintain electrical separation per paregraph 4.3 2. . = _ _. - -

? 4 4.3 Control and Power Requirements 4.3 1 Igniter Control The total number of ignitors shall be divided into two groups, A and B, with the status of the groups indicated in the main control room. Group A shall consist of one-half of the total number of ignitors. Group B shall consist of the remaining half. The ignitors will be normally deenergized. Activation of the ignitors shall be manually from the main control t room. 4.3 2 Power Requirements The ign4 bion system shall receive its power from the class 1E ao auxiliary power system. Provisions shall be made for manually loading the ignition system onto the diesels from the main control room upon loss of offsite power. One-half of the igniters (Group A) shall receive power from the train A diesel and the remaining ignitors (Group B) from the train B diesel (see ' figure 1). The controls and power cables for the ignition system shall maintain the required separations and be identified as specified in SQN-DC-12.2. The igniters of each group shall be provided with a minimum of five power feeds per panel from the 120-volt so distribution panels. 433 Nunter and Location of Igniters There shall be a total of 60 igniters distributed throughout the containment. A minimum of two ignitors, one from Group A and one from Group B, shall be located in each enclosed volume and at the entrance to the pressurizer and steam generator chambers (see figures 2 through 7). 4.3.4 Igniter Requirements l 4.3.5.1 The igniters shall operate from a regulated 120V ao 2 10 percent power source. The maximum power requirements of each igniter shall not exceed watts. l 4.3 5.2 Thermal igniters shall reach a minimus j surface temperature of 1500 F within 90 seconds under the environmental conditions stated in paragraph 4.1. ~ ~ .~.- -. . ~ - _ - - -. -..,.

4 4.3 5 Penetration Requirements Containment electrical cable penetrations shall be provided with redundant overcurrent protection and be designed in accordance with paragraph 4.2. 4 3.6 Failure Criteria 4.3 6.1 The Class IE power system shall be protected from failures in the PHMS. 4 3.6.2 A falure in one of the 120V ac circuits of a group shall not prevent the remaining 120V ao circuits in that group from perfbraing their function when required. 5.0 TESTABILITY 51 Both groups of ignitors ( A and B) shall be capable of being tested periodically to ensure operability of all the igniter in that group. To confirm the operability of the system, the current in each 120-volt circuit shall be monitored and compared to the current recorded in that circuit during preoperational testing. -. - ~. _. _ _ _ -. - -,. ,,,7 ,.r ,_,m., ,,,~,_,.. _ _ _ _ _ _.,-.. .,.m__ e-r

HYDROGEN IGNITION PChTL SYSTEM UNIT-1 SHORN (UNIT-2 TYPICAL) Preferred Preferred h6A Train B Diesel Diesel (0 (0 QdC C NO 0 Train A 6.9KV 6 6 6 8 d 6 Train B 6.9KV Shutdown Board Mdm Board i I I IJ 6 9KV/480V 6 9KV/480V (TTTT ITIII 6 I CNC (ONC 9 9 Train A 480V j Train B 480V g o j g o Shutdown Board Shutdown Board C NC o o Train A kBOV i Train B 480V EC l o l I o I EC s o O NO NO O O Control and indication in the Main Control Em. l i u.u)480v/nov tJJJJ 480V/uCV ITITi (rm. 1 ~ (NC (NC 120V Distribution o g 120V Distribution l Panel l I Panel lO 0,. o o o o ol lo o o o O O ol C IC NC C NC NC NC NC NC C O o o o o o o No GROUP A GROUP B l FIGURE-1 e e -y, e --n- ---we,- m -. - -, -,., -. - --n,-

KEY TO FIOURES 2 THROUGH 7 @ - Denotes Hydrogen Igniter Location Igniter Identification Format: "I" X is power train designation. E71090.04 i I l

e + 8 es o',. g 7-h A EL-689 k689 / e,, o1 ~ 4 EL-639 EL-689 . gA B g

  • e

.e FIGURE -2 'I

~ 3 h EL-7 O ~~ ( 7 x 700 B gy O^ X FIGURE-3

is e, t n e o u o, s\\ \\ ^-

  • 1

\\ \\ p p A O mmm m.m e_m N A B, A -731 L 731 SE od 3 L 730 E-730 ' ". ~ 1 A' EL-772 m m ua, l m ygg L 730 s 731 O -7d % cr /*= = ~ [ s,' ~ B L 730 e', L-L 731 EL-730 A N A s N % s s' / .\\ \\ I s t g ll e e s FIGURE-4 1 1 1 l

B @ E-792 hA gA EL-787 5 792 EL-7 h EL-742 EL-787 B EL-787 i EL-755 EL-742 ( O ^ EL-7 x u l gAEL-792 l I i i-FIGURE-5 l Igniters in:

1. Upper plenum of ice condenser
2. Ltper Compartment l

l .-..a

a s "O / ^@ \\ "O h5 'N AQ FIGURE-6 76 niters on Crane Collector sans EL-809 O'

O A B O B A FIGURE-7 3 Igniters on Lighting Brackets at EL-646'-5f " 16 l l

, (4 ) 846.0 ft. 81 8.0 *. 809.0 ft.

  • (6 )

792.0 ft. e@) ,(g) '787.0 ft. L I e(2) 772.0 ft. e m O I

  • (1) 755 0 ft.

i et 7%.o ft. (1) o l e(2) { 7k2.0 ft. I I 731.0 ft. 4 (g) 9(10) ~ e(2) ~ q ~ [ I - Air Retur r= = .= ~700.0 ft. e(16) t,. ; 1....i i s 689.0 ft. e(4)' H 669.o ft. g IGNITER FIc.URE-8 _}}