ML091480342

From kanterella
Jump to navigation Jump to search
Combined Annual Radiological Environmental Operating Report for 2008
ML091480342
Person / Time
Site: Davis Besse 
Issue date: 04/30/2009
From:
FirstEnergy Nuclear Operating Co
To:
Office of Nuclear Reactor Regulation
References
FOIA/PA-2010-0209, L-09-111
Download: ML091480342 (191)


Text

2008 AnnualI Radiological Environmental Operating Report includina the I

C' *fflue Radiologi I uent R*lease ort 4,p rt, 40ý*

F --

lP:

12 1

t-'.:

c

.S

ANNUAL RADIOLOGICAL ENVIRONMENTAL OPERATING REPORT Davis-Besse Nuclear Power Station January 1, 2008 through December 31, 2008 Davis-Besse Nuclear Power Station April 2009

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report TABLE OF CONTENTS Title Page List of Tables iv List of Figures vi Executive Summary viii INTRODUCTION Fundamentals I

Radiation and Radioactivity 2

Interaction with Matter 3

Quantities and Units of Measurement 5

Sources of Radiation 7

Health Effects of Radiation 9

Health Risks 10 Benefits of Nuclear Power 11 Nuclear Power Production 11 Station Systems 16 Reactor Safety and Summary 19 Radioactive Waste 19 Description of the Davis-Besse Site 22 References 24 RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM Introduction 26 Pre-Operational Surveillance Program 26 Operational Surveillance Program Objectives 27 Quality Assurance 27 Program Description 28 Sample Analysis 32 Sample History Comparison 34 i

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Title Page RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM (continued) 2008 Program Anomalies 36 Atmospheric Monitoring 36 Terrestrial Monitoring 43 Aquatic Monitoring 55 Direct Radiation Monitoring 67 Conclusion 78 References 78 RADIOACTIVE EFFLUENT RELEASE REPORT Protection Standards 81 Sources of Radioactivity Released 81 Processing and Monitoring 82 Exposure Pathways 83 Dose Assessment 84 Results 85 Regulatory Limits 86 Effluent Concentration Limits 87 Average Energy 87 Measurements of Total Activity 87 Batch Releases 88 Abnormal Releases 88 Percent of ODCM Limits 88 Sources of Input Data 89 Doses to Public Due to Activities Inside the Site Boundary 89 Inoperable Radioactive Effluent Monitoring Equipment 90 Changes to The ODCM and PCP 90 Borated Water Storage Tank Radionuclide Concentrations 90 Groundwater Monitoring 106 LAND USE CENSUS Program Design 112 Methodology 112 Results 113 ii

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Title Patee NON-RADIOLOGICAL ENVIRONMENTAL PROGRAMS Meteorological Monitoring 118 On-Site Meteorological Monitoring 119 Land and Wetlands Management 134 Water Treatment Plant Operation 135 Chemical Waste Management 138 Other Environmental Regulating Acts 139 Other Environmental Programs 141 APPENDICES Appendix A: Interlaboratory Comparison Program Results 142 Appendix B: Data Reporting Conventions 161 Appendix C: Maximum Permissible Concentrations of Radioactivity in Air 163 and Water Above Background in Unrestricted Areas Appendix D: REMP Sampling Summary 165 iii

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report List of Tables Title Risk Factors: Estimated Decrease in Average Life Expectancy Sample Codes and Collection Frequencies Sample Collection Summary Radiochemical Analyses Performed on REMP Samples Air Monitoring Stations Milk Monitoring Location Groundwater Monitoring Locations Broadleaf Vegetation and Fruit Locations Animal/Wildlife Feed Locations Wild Meat Locations Soil Locations Treated Surface Water Locations Untreated Surface Water Locations Shoreline Sediment Locations Fish Locations Thermoluminescent Dosimeter Locations Gaseous Effluents - Summation of All Releases Gaseous Effluents - Ground Level Releases - Batch Mode Gaseous Effluents - Ground Level Releases - Continuous Mode Ground Level Releases - LLDs for Continuous and Batch Mode Gaseous Effluents - Mixed Mode Releases -Batch Mode Gaseous Effluents - Mixed Mode Releases - Continuous Mode LLDs for Gaseous Effluents - Mixed Mode Releases Liquid Effluents - Summation of All Releases Liquid Effluents - Nuclides Released in Batch Releases Liquid Effluents - Nuclides Released Batch Releases Table Number 1

2 3

4 5

6 7

8 9

10 11 12 13 14 15 16 17 18 18 18 19 19 19 20 21 21 Page Number 10 30 31 33 39 44 46 47 48 49 51 57 60 61 63 69 91 92 93 94 95 96 97 98 99 101 iv

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Table Page Title Number Number Liquid Effluents - Nuclides Released Continuous Releases 21 101 Liquid Effluents - LLDs for Nuclides Released 21 102 Liquid Effluents - LLDs for Nuclides Released Solid Waste and Irradiated Fuel Shipments 22 103 Groundwater Monitoring Wells Sampled in 2008 23 106 Groundwater Results Following 3" Condensate Line Leak 24 108 Doses Due to Gaseous Releases for January through December2008 25 109 Doses Due to Liquid Releases for January through December 2008 26 110 Annual Dose to the Most Exposed (from all pathways) Member of the Public 2008 27 H]l Closest Exposure Pathways Present in 2008 28 115 Pathway Locations and Corresponding Atmospheric Dispersion (X/Q) 29 117 and Deposition (D/Q) Parameters Summary of Meteorological Data Recovery for 2008 30 123 Summary of Meteorological Data Measured for 2008 31 124 Joint Frequency Distribution by Stability Class 32 129 V

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report List of Figures Figure Page Description Number Number The Atom 1

I Principal Decay Scheme of the Uranium Series 2

3 Range and Shielding of Radiation 3

4 Sources of Exposure to the Public 4

8 Fission Diagram 5

12 Fuel Rod, Fuel Assembly, Reactor Vessel 6

13 Station Systems 7

15 Dry Fuel Storage Module Arrangement 8

21 Map of Area Surrounding Davis-Besse 9

22 2008 Airborne Particulate Gross Beta 10 38 Air Sample Site Map 11 40 Air Samples 5-mile Map 12 41 Air Sample 25-mile Map 13 42 Gross Beta Groundwater 1982-2008 14 45 Cs-137 in Soil 1972-2008 15 50 Terrestrial Site Map 16 52 Terrestrial 5-mile Map 17 53 Terrestrial 25-mile Map 18 54 Gross Beta in Treated Surface Water 1972-2008 19 56 Gross Beta Concentration in Untreated Surface Water 1977-2008 20 59 Gross Beta Fish 1972-2008 21 62 Aquatic Site Map 22 64 Aquatic 5-mile Map 23 65 Aquatic 25-mile Map 24 66 Gamma Dose for Environmental TLDs 1973 - 2008 25 68 TLD Site Map 26 75 TLD 5-mile Map 27 76 TLD 25-mile Map 28 77 Exposure Pathways 29 84 vi

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Figure Page Number Number Description Land Use Census Map Wind Rose Annual Average I OOM Wind Rose Annual Average 75M Wind Rose Annual Average 1 OM 30 31 32 33 114 126 127 128 vii

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Executive Summary The Annual Radiological Environmental Operating Report (AREOR) is a detailed report on the Environmental Monitoring Programs conducted at the Davis-Besse Nuclear Power Station from January 1 through December 31, 2008. This report meets all of the requirements in Regulatory Guide 4.8, Section 5.6 of Davis-Besse Improved Standard Technical Specifications, and Davis-Besse Offsite Dose Calculation Manual (ODCM) Section 7.1. Reports included are the Radio-logical Environmental Monitoring Program, Radiological Effluents Release Report, Land Use Census, Groundwater Monitoring, and the Non-Radiological Environmental Programs, which consist of Meteorological Monitoring, Land and Wetland Management, Water Treatment, Chemical Waste Management, and Waste Minimization and Recycling. This report also includes the Radiological Effluent Release Report for the reporting period of January 1 through December 31, 2008.

Radiological Environmental Monitoring Program The Radiological Environmental Monitoring Program (REMP) is established to monitor the ra-diological condition of the environment around Davis-Besse. The REMP is conducted in accor-dance with Regulatory Guide 4.8, Davis-Besse Improved Technical Specifications, and the Davis-Besse ODCM Section 6.0. This program includes the sampling and analysis of environ-mental samples and evaluating the effects of releases of radioactivity on the environment.

Radiation levels and radioactivity have been monitored within a 25-mile radius around Davis-Besse since 1972. The REMP was established at Davis-Besse about five years before the Station became operational. This pre-operational sampling and analysis program provided data on radia-tion and radioactivity normally present in the area as natural background. Davis-Besse has con-tinued to monitor the environment by sampling air, groundwater, milk, wild meat, fruit and vegetables, wild animal feed, drinking water, surface water, fish, shoreline sediment, and by di-rect measurement of radiation.

Samples are collected from Indicator and Control locations. Indicator locations are within ap-proximately 5 miles of the site and are expected to show naturally occurring radioactivity plus any increases of radioactivity that might occur due to the operation of Davis-Besse. Control lo-cations are farther away from the Station and are expected to indicate the presence of only natu-rally occurring radioactivity. The results obtained from the samples collected from indicator locations are compared with the results from those collected from control locations and with the concentrations present in the environment before Davis-Besse became operational. This allows for the assessment of any impact the operation of Davis-Besse might have had on the surround-ing environment.

Over 2,000 radiological environmental samples were collected and analyzed in 2008. An expla-nation for the sample anomalies for this reporting period is provided on page 36.

The results of the REMP indicate that Davis-Besse continues to be operated safely in accordance with applicable federal regulations. No significant increase above background radiation or radio-activity is attributed to the operation of Davis-Besse.

viii

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report The sampling results are divided into four sections: atmospheric monitoring, terrestrial monitor-ing, aquatic monitoring and direct radiation monitoring.

Air samples are continuously monitored at ten locations. Four samples are collected onsite. The other six are located between one-half and twenty-two miles away. Particulate filters and iodine cartridges are collected weekly. The 2008 indicator results were in close agreement with the samples collected at control locations.

Terrestrial monitoring includes analysis of milk, groundwater, meat, fruits, vegetables, animal feed, and soil samples. Samples are collected onsite and up to twenty-five miles away, depend-ing on the type of sample. Results of terrestrial sample analyses indicate concentrations of radio-activity similar to previous years and indicate no build-up of radioactivity due to the operation of Davis-Besse.

Aquatic monitoring includes the collection and analysis of drinking water, untreated surface wa-ter, fish and shoreline sediments from onsite and the vicinity of Lake Erie. All samples of un-treated surface water contained tritium at concentrations <330 pCi/liter, well below the 20,000 pCi/liter EPA drinking water limit for tritium. The 2008 results of analysis for fish, drinking wa-ter and shoreline sediment indicate normal background concentration of radionuclides and show no increase or build-up of radioactivity due to the operation of Davis-Besse The operation of Davis-Besse in 2008 caused no detected increase in the concentrations of ra-dionuclides or adverse effects on the quality of the environment surrounding the plant. Radioac-tivity released in the Station's effluents was well below the applicable federal regulatory limits.

The estimated radiation dose to the general public due to the operation of Davis-Besse in 2008 was well below all applicable regulatory limits.

In order to estimate radiation dose to the public, the pathways through which public exposure can occur must be known. To identify these exposure pathways, an Annual Land Use Census is per-formed as part of the REMP. During the census, Station personnel travel every public road within a radius of five miles of Davis-Besse to locate radiological exposure pathways (e.g., resi-dences, vegetable gardens, milk cows/goats, etc.). The most important pathway is the one that, for a specific radionuclide, provides the greatest dose to a sector of the population. This is called the critical pathway. The critical pathway for 2008 was a garden in the West sector 1,560 meters from Davis-Besse, and is unchanged from 2007.

Radiological Effluent Release Report The Radiological Effluent Release Report (RERR) is a detailed listing of radioactivity released from the Davis-Besse Nuclear Power Station during the period January 1 through December 31, 2008. The doses due to radioactivity released during this period were only a fraction of what is allowed by our operating license:

The Total Body doses to an individual and population in an unrestricted area due to direct radiation from Davis-Besse is not distinguishable from background. These doses represent an extremely small fraction of the limits set by the NRC or the limits set in the ODCM.

One unplanned gaseous release occurred during plant startup on March 7, when High Pres-sure Feedwater Heater relief valves lifted. The steam released contained 1.08 E-03 curies of Tritium and had a calculated whole body dose of 1.44E-07 millirem.

ix

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report There were no abnormal liquid releases during 2008.

There was one revision of the Process Control Program (PCP) and one revision of the Offsite Dose Calculation Manual (ODCM) during 2008.

Groundwater Monitoring As a result of a 2007 Nuclear Energy Institute initiative, Davis-Besse began monitoring ground-water wells near the plant in order to determine whether there have been any inadvertent releases of radioactivity that have impacted groundwater or could potentially affect local water supplies.

The water was sampled from both pre-construction era wells and from 16 monitoring wells drilled in 2007. In 2008, tritium values in these wells ranged from <140 to 1,477 pCi/liter. There is no indication that the contaminated groundwater is moving offsite. These wells are not used for drinking water purposes, and the tritium concentrations found were all below the 20,000 pCi/liter EPA drinking water limit. Sampling of these wells is performed on a semi-annual basis.

On October 22, a leak was discovered in an underground 3 inch condensate line, which carries low-level tritiated water to an approved radioactive effluent discharge point. The line was im-mediately isolated and repaired, and several wells surrounding the line break were sampled. All wells showed tritium concentrations at less than the courtesy notification level of 2,000 pCi/liter.

No gamma or hard-to-detect radionuclides (Strontium 89/90, Fe-55, Ni-63) were present in these samples. Follow-up sampling of these wells will occur in spring of 2009. Notifications were made to the NRC, State of Ohio, and Lucas and Ottawa County officials on October 23, 2008.

Non-Radiological Environmental Programs Meteorological Monitoring The Meteorological Monitoring Program at Davis-Besse is part of a program for evaluating the radiological effects of the routine operation of Davis-Besse on the surrounding environment.

Meteorological monitoring began in October of 1968.

Meteorological data recorded at Davis-Besse include wind speed, wind direction, sigma theta (standard deviation of wind direction), ambient temperature, differential temperature, dew point and precipitation. Two instrument-equipped meteorological towers are used to collect data. Data recovery for the five instruments that are operationally required by Davis-Besse Technical Re-quirements Manual was 99.09%.

Marsh Management FirstEnergy owns the Navarre Marsh. It is leased to the U.S. Fish and Wildlife Service, who manage it as part of the Ottawa National Wildlife Refuge.

The Davis-Besse site cun-ently has two active American Bald Eagle nests on the property. A total of seventeen healthy eaglets have fledged from Davis-Besse nests since 1995.

x

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Water and Wastewater Treatment Davis-Besse withdraws water from Lake Erie and processes it through a vendor-supplied water treatment process to produce the high-purity water used in the Station's cooling systems.

Since December 1, 1998, the Carroll Township Water Treatment Plant has provided for domestic water needs at Davis-Besse.

Sewage is treated at the Davis-Besse Wastewater Treatment Plant (WWTP) and its effluent is pumped to a settling basin. Following a retention period, this water is discharged with other Sta-tion liquid effluents back to Lake Erie.

Chemical Waste Management The Chemical Waste Management Program at Davis-Besse was developed to ensure that the off-site disposal of non-radioactive hazardous and nonhazardous chemical wastes is performed in accordance with all applicable state and federal regulations. Chemical waste disposal vendors contracted by Davis-Besse use advanced technology for offsite disposal, including recycling of chemical wastes, in order to protect human health and the environment.

In 2008, the Davis-Besse Nuclear Power Station generated approximately 7,350 pounds of hazardous waste. Non-hazardous wastes generated include 9,540 gallons of used oil, latex paints, caulks and grout.

As required by Superfund Amendment and Reauthorization Act (SARA), Davis-Besse re-ported hazardous products and chemicals to local fire departments and local and state plan-ning commissions.

As part of the program to remove PCB fluid from Davis-Besse, all electrical transformers have been retrofilled and reclassified as non-PCB transformers.

Waste Minimization and Recycling The Waste Minimization and Recycling Program at Davis-Besse began in 1991 with the collec-tion and recycling of paper. This program was expanded and reinforced during 1993 to include the recycling of paper, aluminum cans, cardboard, and metal. Paper and cardboard recycling typically exceeds 50 tons annually. The scrap metal collected onsite is sold to scrap companies.

Appendices Appendix A contains results from the Interlaboratory Comparison Program required by Davis-Besse Technical Specifications.

Samples with known concentrations of radioisotopes are pre-pared by the Environmental Resources Associates (ERA), and then sent (with information on sample type and date of collection only) to the laboratory contracted by the Davis-Besse Nuclear Power Station to analyze its REMP samples. The Environmental Resources Associates (ERA) compares results to known standards.

Appendix B contains data reporting conversions used in the REMP at Davis-Besse. The appen-dix provides an explanation of the format and computational methods used in reporting REMP data. Information on counting uncertainties and the calculations of averages and standard devia-xi

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report tions are also provided.

Appendix C lists the effluent concentration limits for alpha and beta-emitting radioisotopes and for certain other radioisotopes in air and water samples. These concentrations are taken directly from the Code of Federal Regulations, and provide comparison values for actual REMP sampling results for 2008.

Appendix D provides a REMP sampling summary from 2008. The appendix provides a listing of the following for each sample type:

" number and types of analyses performed

" lower limit of detection for each analysis

" mean and range of results for control and indicator locations

  • mean, range, and description of location with highest annual mean

" number of non-routine results For detailed studies, Appendix D provides more specific information than that listed in this report. The information presented in Appendices A through D was provided by Environmental, Inc. Midwest Laboratory in their Final Progress Re-port to Davis-Besse (February, 2009).

xii

Introduction

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Introduction Coal, oil, natural gas and hydropower are used to run this nation's electric generating stations; how-ever, each method has its drawbacks. Coal-fired power can affect the environment through mining, acid rain and air pollution. Oil and natural gas are in limited supply and are, therefore, costly. Hy-dropower is limited due to the environmental impact of damming our waterways and the scarcity of suitable sites.

Nuclear power provides a readily available source of energy. The operation of nuclear power sta-tions has a very small impact on the environment. In fact, the Davis-Besse Nuclear Power Station is surrounded by hundreds of acres of marshland, which make up part of the Ottawa National Wildlife Refuge. In order to provide better understanding of this unique source of energy, background infor-mation on basic radiation characteristics, risk assessment, reactor operation and effluent control is provided in this section.

Fundamentals The Atom All matter consists of atoms. Simply de-scribed, atoms are made up of positively and negatively charged particles, and particles which are neutral. These particles are called(

0/

7,.o-protons, electrons, and neutrons, respec-rjNEUTON tively (Figure 1). The relatively large pro-r@E*

LTRo!

tons and neutrons are packed tightly to-gether in a cluster at the center of the atom called the nucleus. Orbiting around the nu-cleus are one or more smaller electrons. In

/

an electrically neutral atom the negative charges of the electrons are balanced by the/

positive charges of the protons. Due to their

-T°oaI-dissimilar charges, the protons and electrons

)

ORBIT have a strong attraction for each other. This holds the atom together.

Other attractive Figure 1: An atom consists of two parts: a nucleus forces between the protons and neutrons containing positively charged protons and electrically keep the densely packed protons from repel-neutral neutrons and one or more negatively charged electrons orbiting the nucleus. Protons and neutrons ling each other, and prevent the nucleus are nearly identical in size and weight, while each is from breaking apart.

about 2000 times heavier than an electron.

1

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Radiation and Radioactivity Isotopes and Radionuclides A group of identical atoms containing the same number of protons make up an element. In fact, the number of protons an atom contains determines its chemical identity. For instance, all atoms with one proton are hydrogen atoms, and all atoms with eight protons are oxygen atoms. How-ever, the number of neutrons in the nucleus of an element may vary. Atoms with the same num-ber of protons but different numbers of neutrons are called isotopes. Different isotopes of the same element have the same chemical properties, and many are stable or nonradioactive. An un-stable or radioactive isotope of an element is called a radioisotope, a radioactive atom, or a radionuclide. Radionuclides usually contain an excess amount of energy in the nucleus. The excess energy is usually due to a surplus or deficit in the number of neutrons in the nucleus. Ra-dionuclides such as Uranium-238, Berylium-7 and Potassium-40 occur naturally.

Others are man-made, such as Iodine-131, Cesium-137, and Cobalt-60.

Radiation Radiation is simply the conveyance of energy through space. For instance, heat emanating from a stove is a form of radiation, as are light rays, microwaves, and radio waves. Ionizing radiation is another type of radiation and has similar properties to those of the examples listed above. Ion-izing radiation consists of both electromagnetic radiation and particulate radiation. Electro-magnetic radiation is energy with no measurable mass that travels with a wave-like motion through space. Included in this category are gamma rays and X-rays. Particulate radiation con-sists of tiny, fast moving particles which, if unhindered, travel in a straight line through space.

The three types of particulate radiation of concern to us are alpha particles, which are made up of 2 protons and 2 neutrons; beta particles, which are essentially free electrons; and neutrons.

The properties of these types of radiation will be described more fully in the Range and Shielding section.

Radioactive Decay Radioactive atoms, over time, will reach a stable, non-radioactive state through a process known as radioactive decay. Radioactive decay is the release of energy from an atom through the emis-sion of ionizing radiation. Radioactive atoms may decay directly to a stable state or may go through a series of decay stages, called a radioactive decay series, and produce several daugh-ter products that eventually result in a stable atom. The loss of energy and/or matter through radioactive decay may transform the atom into a chemically different element. For example, when Uranium-238 decays, it emits an alpha particle and, as a result, the atom loses 2 protons and 2 neutrons. As discussed previously, the number of protons in the nucleus of an atom deter-mines its chemical identity. Therefore, when the Uranium-238 atom loses the 2 protons and 2 neutrons, it is transformed into an atom of Thorium-234. Thorium-234 is one of the 14 succes-sive daughter products of Uranium-238. Radon is another daughter product, and the series ends with stable Lead-206.

2

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report This example is part of a known radioactive decay series, called the Uranium series, which be-gins with Uranium-238 and ends with Lead-206 (Figure 2).

2 3 8 u

4.5 x 109 Yr 234 U

,*2.5 x 10 Yr 1,

2 mPa 4 J 12 mm in 234 Th 24 d 2 30Th 8.0 x 104 Yr 4

22 6Ra 1600 Yr I

3.82 d Beta Decay Alpha Decay 218Po 3.05 min 214 Po

~1.6 x104 S 210P S138.4 d 4

21461 B

210 Bi j.19.7 mi 5.01___

[~_~

d 214 Pb 26.8 min 21 0Pb 23 Yr 206Pb stable Figure 2: Principal Decay Scheme of the Uranium Series.

Half-life Most radionuclides vary greatly in the frequency with which their atoms release radiation. Some radioactive materials, in which there are only infrequent emissions, tend to have a very long half-lives. Those radioactive materials that are very active, emitting radiation more frequently, tend to have comparably shorter half-lives. The length of time an atom remains radioactive is defined in terms of half-lives. Half-life is the amount of time required for a radioactive substance to lose half of its activity through the process of radioactive decay. Half-lives vary from millionths of a second to millions of years.

Interaction with Matter Ionization Through interactions with atoms, alpha, beta, and gamma radiation lose their energy. When these forms of radiation interact with any form of material, the energy they impart may cause 3

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report atoms in that material to become ions, or charged particles. Normally, an atom has the same number of protons as electrons. Thus, the positive and negative charges cancel, and the atom is electrically neutral. When one or more electrons are removed an ion is formed. Ionization is one of the processes that may result in damage to biological systems.

Range and Shielding Particulate and electromagnetic radiation each travel through matter differently because of their different properties. Alpha particles contain 2 protons and 2 neutrons, are relatively large, and carry an electrical charge of +2. Alpha particles are ejected from the nucleus of a radioactive atom at speeds ranging from 2,000 to 20,000 miles per second. However, due to its compara-tively large size, an alpha particle usually does not travel very far before it loses most of its en-ergy through collisions and interactions with other atoms. As a result, a sheet of paper or a few centimeters of air can easily stop alpha particles (Figure 3).

Beta particles are very small, and comparatively fast particles, traveling at speeds near the speed of light (186,000 miles per second). Beta particles have an electrical charge of either +1 or -1.

Because they are so small and have a low charge, they do not collide and interact as often as al-pha particles, so they can travel farther. Beta particles can usually travel through several meters of air, but may be stopped by a thin piece of metal or wood.

S..c~...............

c).

---B at..............

P.AD I OA-I"VE PIATERIAL PAPER ALuMI NUT1 LEAD CONCRETE Figure 3: As radiation travels, it collides and interacts with other atoms and loses energy. Alpha particles can be stopped by a sheet of paper, and beta particles by a thin sheet of aluminum. Gamma radiation is shielded by highly dense materials such as lead, while hydrogenous materials (those containing hydrogen atoms), such as water and concrete, are used to stop neutrons.

Gamma rays are pure energy and travel at the speed of light. They have no measurable charge or mass, and generally travel much farther than alpha or beta particles before being absorbed. After repeated interactions, the gamma ray finally loses all of its energy and vanishes. The range of a gamma ray in air varies, depending on the ray's energy and interactions.

Very high-energy gamma radiation can travel a considerable distance, whereas low energy gamma radiation may travel only a few feet in air. Lead is used as shielding material for gamma radiation because of its density. Several inches of Lead or concrete may be needed to effectively shield gamma rays.

4

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Neutrons come from several sources, including the interactions of cosmic radiation with the earth's atmosphere and nuclear reactions within operating nuclear power reactors. However, neu-trons are not of environmental concern since the neutron source at nuclear power stations is sealed within the containment building.

Because neutrons have no charge, they are able to pass very close to the nuclei of the material through which they are traveling. As a result, neutrons may be captured by one of these nuclei or they may be deflected. When deflected, the neutron loses some of its energy. After a series of these deflections, the neutron has lost most of its energy. At this point, the neutron moves about as slowly as the atoms of the material through which it is traveling, and is called a thermal neu-tron. In comparison, fast neutrons are much more energetic than thermal neutrons and have greater potential for causing damage to the material through which they travel. Fast neutrons can have from 200 thousand to 200 million times the energy of thermal neutrons.

Neutron shielding is designed to slow fast neutrons and absorb thermal neutrons.

Neutron shielding materials commonly used to slow neutrons down are water or polyethylene. The shield is then completed with a material such as Cadmium, to absorb the now thermal neutrons. At Davis-Besse, concrete is used to form an effective neutron shield because it contains water mole-cules and can be easily molded around odd shapes.

Quantities and Units of Measurement There are several quantities and units of measurement used to describe radioactivity and its ef-fects. Three terms of particular usefulness are activity, absorbed dose, and dose equivalent.

Activity: Curie Activity is the number of atoms in a sample that disintegrate (decay) per unit of time. Each time an atom disintegrates, radiation is emitted. The curie (Ci) is the unit used to describe the activity of a material and indicates the rate at which the atoms of a radioactive substance are decaying.

One curie indicates the disintegration of 37 billion atoms per second.

A curie is a unit of activity, not a quantity of material. Thus, the amount of material required to produce one curie varies. For example, one gram (1/28th of an ounce) of radium-226 is the equivalent of one curie of activity, but it would take 9,170,000 grams (about 10 tons) of thorium-232 to equal one curie.

Smaller units of the curie are often used, especially when discussing the low concentrations of radioactivity detected in environmental samples. For instance, the microcurie (uCi) is equal to one millionth of a curie, while the picocurie (pCi) represents one trillionth of a curie.

5

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Absorbed Dose: Rad Absorbed dose is a term used to describe the radiation energy absorbed by any material exposed to ionizing radiation, and can be used for both particulate and electromagnetic radiation. The Rad (radiation absorbed dose) is the unit used to measure the absorbed dose. It is defined as the energy of ionizing radiation deposited per gram of absorbing material (1 Rad = 100 erg/gmn).

The rate of absorbed dose is usually given in Rad/hr.

If the biological effect of radiation is directly proportional to the energy deposited by radiation in an organism, the Rad would be a suitable measurement of the biological effect. However, bio-logical effects depend not only on the total energy deposited per gram of tissue, but on how this energy is distributed along its path. Experiments have shown that certain types of radiation are more damaging per unit path of travel than are others. Thus, another unit is needed to quantify the biological damage caused by ionizing radiation.

Dose Equivalent: Rem Biological damage due to alpha, beta, gamma and neutron radiation may result from the ioniza-tion caused by this radiation. Some types of radiation, especially alpha particles which cause dense local ionization, can result in up to 20 times the amount of biological damage for the same energy imparted as do gamma or X-rays. Therefore, a quality factor must be applied to account for the different ionizing capabilities of various types of ionizing radiation. When the quality factor is multiplied by the absorbed dose, the result is the dose equivalent, which is an estimate of the possible biological damage resulting from exposure to a particular type of ionizing radia-tion. The dose equivalent is measured in rem (radiation equivalent man).

An example of this conversion from absorbed dose to dose equivalent uses the quality factor for alpha radiation, which is equal to 20. Thus, 1 Rad of alpha radiation is approximately equal to 20 rem. Beta and gamma radiation each have a quality factor of 1, therefore one Rad of either beta or gamma radiation is approximately equal to one rem. Neutrons have a quality factor rang-ing from 2 to 10. One rem produces the same amount of biological damage, regardless of the source. In terms of radiation, the rem is a relatively large unit. Therefore, a smaller unit, the mil-lirem, is often used. One millirem (mrem) is equal to 1/1,000 of a rem.

Deep Dose Equivalent (DDE)

Deep dose equivalent is the measurement of dose within the body, from sources of radiation that are external to the body. It is what is measured and recorded on thermoluminescent dosimeters (TLDs), film badges or other dosimeters. For example, at Davis-Besse or at any hospital that has x-ray equipment, you will see people wearing these devices. These instruments are worn to measure DDE.

Committed Effective Dose Equivalent (CEDE)

Committed effective dose equivalent is a measure of the dose received from any radioactive ma-terial taken into the body. It is calculated from the sum of the products of the committed dose 6

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report equivalent to the organ or tissue multiplied by the organ or tissue-weighting factor. CEDE ac-counts for all the dose delivered during the entire time the radioactive material is in the body.

Total Effective Dose Equivalent (TEDE)

Total effective dose equivalent is the sum of the deep dose equivalent (for dose from sources ex-ternal to the body) and the committed effective dose-equivalent (for internal dose). Since they are both doses to the body, they are not tracked separately. The NRC limits occupational dose to a radiation worker to five rem (5,000 mrem) TEDE per year.

Sources of Radiation Background Radiation Radiation did not begin with the nuclear power industry, and occurs naturally on earth. It is probably the most "natural" thing in nature. Mankind has always lived with radiation and proba-bly always will. In fact, during every second of life, over 7,000 atoms undergo radioactive decay "naturally" in the body of the average adult. In addition, radioactive decay occurs naturally in soil, water, air and space. All these common sources of radiation contribute to the natural back-ground radiation to which we are all exposed.

The earth is being showered by a steady stream of high-energy gamma rays and particulate radia-tion that come from space known as cosmic radiation. The atmosphere shields us from most of this radiation, but everyone still receives about 20 to 50 mrem each year from this source. The thinner air at higher altitudes provides less protection against cosmic radiation. People living at higher altitudes or flying in an airplane are exposed to even higher levels cosmic radiation. Ra-dionuclides commonly found in the atmosphere as a result of cosmic ray interactions include Be-ryllium-7, Carbon-14, tritium (H-3), and Sodium-22.

Another common naturally occurring radionuclide is Potassium-40. About one-third of the ex-ternal and internal dose from naturally occurring background radiation is attributed to this radio-active isotope of potassium.

The major source of background radiation is Radon, a colorless, odorless, radioactive gas that results from the decay of Radium-226, a member of the Uranium-238 decay series. Since Ura-nium occurs naturally in all soils and rocks, everyone is continuously exposed to Radon and its daughter products. Radon is not considered to pose a health hazard unless it is concentrated in a confined area, such as buildings, basements or underground mines. Radon-related health con-cerns stem from the exposure of the lungs to this radioactive gas. Radon emits alpha radiation when it decays, which can cause damage to internal tissues when inhaled. As a result, exposure to the lungs is a concern, since the only recognized health effect associated with exposure to Ra-don is an increased risk of lung cancer. This effect has been seen when Radon is present at levels common in uranium mines. According to the National Council on Radiation Protection and Measurement (NCRP), more than half of the radiation dose the average American receives is at-tributed to Radon.

7

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report SOURCES OF EXPOSURE TO THE PUBLIC Terrestrial 8%.

/

j Radon 55%

Internal 11%

Manmade 18% (X-Rays 10%, Nuclear Medicine 4%,

Consumer Products 3%,

Nuclear Power <0.2%)

Figure 4: The most significant annual dose received by an individual of the public is that received from naturally occurring radon. A very small annual dose to the public results from producing electricity by nuclear power.

Further information on Radon, its measurement, and actions to reduce the Radon concentration in buildings can be obtained by contacting the state Radon program office at the following ad-dress:

Ohio Department of Health, Bureau of Radiation Protection P.O. Box 118, 35 East Chestnut Building 7th Floor Columbus, Ohio 43216-0118 614) 481-5800 (800) 523-4439 (in Ohio Only)

The approximate average background radiation in this area (see Figure 4) is 300 mrern/year.

Man-made Radiation In addition to naturally occurring cosmic radiation and radiation from naturally occurring radio-activity, people are also exposed to man-made radiation. The largest sources of exposure include 8

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report medical x-rays and radioactive pharmaceuticals. Small doses are also received from consumer products such as televisions, smoke detectors, and fertilizers. Fallout from nuclear weapons tests is another source of man-made exposure. Fallout radionuclides include Strontium-90, Cesium-137, and tritium. Less than one percent of the annual dose a member of the public re-ceives is a result of having electricity generated by nuclear power.

Health Effects of Radiation The effects of ionizing radiation on human health have been under study for more than ninety years. Scientists have obtained valuable knowledge through the study of laboratory animals that were exposed to radiation under extremely controlled conditions. However, it has been difficult to relate the biological effects of irradiated laboratory animals to the potential health effects on humans.

The effects of radiation on humans can be divided into two categories, somatic and genetic. So-matic effects are those which develop in the directly exposed individual, including an unborn child. Genetic effects are those which are observed in the offspring of the exposed individual.

Somatic effects can be divided further into acute and chronic effects. Acute effects develop shortly after exposure to large amount of radiation. Much study has been done with human populations that were exposed to ionizing radiation under various circumstances. These groups include the survivors of the atomic bomb, persons undergoing medical radiation treatment, and early radiologists, who accumulated large doses of radiation, unaware of the potential hazards.

Chronic effects are a result of exposure to radiation over an extended period of time. Examples of such groups are clock dial painters, who ingested large amounts of Radium by "tipping" the paint brushes with their lips, and Uranium miners, who inhaled large amounts of radioactive dust while mining pitchblende (Uranium ore). The studies performed on these groups have increased our knowledge of the health effects from comparatively very large doses of radiation received over long periods of time.

Continuous exposure to low levels of radiation may produce somatic changes over an extended period of time. For example, someone may develop cancer from man-made radiation, back-ground radiation, or some other source not related to radiation. Because all illnesses caused by low level radiation can also be caused by other factors, it is virtually impossible to determine in-dividual health effects of low level radiation. Even though no effects have been observed at doses less than 50 rem, we assume the health effects resulting from low doses of radiation occur proportionally to those observed following large doses of radiation. Most radiation scientists agree that this assumption over-estimates the risks associated with a low-level radiation expo-sure. The effects predicted in this manner have never been actually observed in any individuals exposed to low level radiation. Therefore, the most likely somatic effect of low level radiation is believed to be a small increased risk of cancer. Genetic effects could occur as a result of ionizing radiation interacting with the genes in the human cells. Radiation (as well as common chemi-cals) can cause physical changes or mutations in the genes. Chromosome fibers can break and rearrange, causing interference with the normal cell division of the chromosome by affecting their number and structure. A cell is able to rejoin the ends of a broken chromosome, but if there are two breaks close enough together in space and time, the broken ends from one break could 9

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report join incorrectly with those from another. This could cause translocations, inversions, rings, and other types of structural rearrangements.

When this happens, new mutated genes are created.

Radiation is not the only mechanism by which such changes can occur. Spontaneous mutations and chemically induced mutations also have been observed. These mutated genes may be passed from parent to offspring. Viable mutations due to low level, low dose radiation have not been observed in humans.

Health Risks While people may accept the risks inherent in their personal activities, such as smoking and driv-ing to work each day, they are less inclined to accept the risk inherent in producing electricity.

As with any industrial environment, it is not possible to guarantee a risk free environment. Thus, attention should be focused on taking steps to safeguard the public, on developing a realistic as-sessment of the risks, and on placing these risks in perspective. The perceptions of risk associ-ated with exposure to radiation may have the greatest misunderstanding. Because people do not understand ionizing radiation and its associated risks, many fear it. This fear is compounded by the fact that we cannot hear, smell, taste or feel ionizing radiation.

We do not fear other potentially hazardous things for which we have the same lack of sensory perception, such as radio waves, carbon monoxide, and small concentrations of numerous cancer-causing substances. These risks are larger and measurable compared to those presumed to be as-sociated with exposure to low level, low dose radiation. Most of these risks are with us through-out our lives, and can be added up over a lifetime to obtain a total effect. Table 1 shows a number of different factors that decrease the average life expectancy of individuals in the United States.

Table 1: Risk Factors: Estimated Decrease in Average Life Expectancy Overweight by 30%:

3.6 years Cigarette smoking:

1 pack/day 7.0 years 2 packs/day 10.0 years Heart Disease:

5.8 years Cancer:

2.7 years City Living (non-rural):

5.0 years All operating commercial nuclear power plants totaled:

less than 12 minutes 10

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Benefits of Nuclear Power Nuclear power plays an important part in meeting today's electricity needs, and will continue to serve as an important source of electric energy well into the future. Today more than twenty per-cent of the electricity produced in the United States is from nuclear powered electrical generating stations.

Nuclear power offers several advantages over alternative sources of electric energy:

  • Nuclear power has an excellent safety record dating back to 1957, when the first commercial nuclear power station began operating,

" Uranium, the fuel for nuclear power stations, is a relatively inexpensive fuel that is readily available in the United States,

" Nuclear power is the cleanest energy source for power stations that use steam to produce electricity. There are no greenhouse gases or acid gases produced when using nuclear fuel.

The following sections provide information on the fundamentals of how Davis-Besse uses nu-clear fuel and the fission process to produce electricity.

Nuclear Power Production Electricity is produced in a nuclear power station in the same way as in a fossil-fueled station with the exception of the source of heat. Heat changes water to steam that turns a turbine. In a fossil-fueled station, the fuel is burned in a furnace, which is also a boiler. Inside the boiler, wa-ter is turned into steam. In a nuclear station, a reactor that contains a core of nuclear fuel, primar-ily uranium, replaces the furnace. Heat is produced when the atoms of Uranium are split, or fissioned, inside the reactor.

What is Fission?

A special force called the binding force holds the protons and neutrons together in the nucleus of the atom. The strength of this binding force varies from atom to atom. If the bond is weak enough, the nucleus can be split when bombarded by a free neutron (Figure 5). This causes the entire atom to split, producing smaller atoms, more free neutrons, and heat. In a nuclear reactor, a chain reaction of fission events provides the heat necessary to boil the water to produce steam.

11

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Heat Bombardin~

Neutron Free Neutron Atom

/~

Figure 5: When a heavy atom, such as uranium-235 is split or fissioned, heat, free neutrons, and fission fragments result-The free neutrons can then strike neighboring atoms causing them to fission also. In the proper environment, this process can continue indefinitely in a chain reaction.

Nuclear Fuel The fissioning of one Uranium atom releases approximately 50 million times more energy than the combustion of a single Carbon atom commnon to all fossil fuels. Since a single small reactor fuel pellet contains trillions of atoms, each pellet can release an extremely large amount of en-ergy. The amount of electricity that can be generated from three small fuel pellets would require about 3.5 tons of coal or 12 barrels of oil to generate.

Nuclear fission occurs spontaneously in nature, but these natural occurrences cannot sustain themselves because the freed neutrons either are absorbed by non-fissionable atoms or quickly decay. In contrast, a nuclear reactor minimizes neutron losses, thus sustaining the fission proc-ess by several means:

" using fuel that is free of impurities that might absorb the free neutrons,

" enriching the concentration of the rarer fissionable isotope of Uranium (U-235) relative to the concentration of U-238, a more common isotope that does not fis-sion easily,

  • slowing down neutron by providing a "~moderator"~ such'as water to increase the probability of fission.

Natural Uranium contains less than one percent U-235 compared to the more abundant U-238 when it's mined. Before it can be economically used in a reactor, it is enriched to three to five percent U-235, in contrast to nuclear material used in nuclear weapons which is enriched to over 97 percent. Because of the low levels of U-235 in nuclear fuel, a nuclear power station cannot explode like a bomb.

12

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report After the Uranium ore is separated from the earth and rock, it is concentrated in a milling proc-ess. After milling the ore to a granular form and dissolving out the Uranium with acid, the Ura-nium is converted to Uranium hexafluoride (UF 6). UF 6 is a chemical form of Uranium that exists as a gas at temperatures slightly above room temperature. The UF 6 is then highly purified and shipped to an enrichment facility where gaseous diffusion converters increase the concen-tration of U-235. The enriched gaseous UF 6 is then converted into powdered Uranium dioxide (U0 2), a highly stable ceramic material. The U0 2 powder is put under high pressure to form fuel pellets, each about 5/8 inch long and 3/8 inch in diameter. Approximately five pounds of these pellets are placed into a 12-foot long metal tube made of Zirconium alloy. The tubes constitute the fuel cladding. The fuel cladding is highly resistant to heat, radiation, and corrosion. When the tubes are filled with fuel pellets, they are called fuel rods.

The Reactor Core Two hundred eight fuel rods comprise a single fuel assembly. The Reactor core at Davis-Besse contains 177 of these fuel assemblies, each approximately 14 feet tall and 2,000 pounds in weight. In addition to the fuel rods, the fuel assembly also contains 16 vacant holes for the inser-tion of control rods, and one vacant hole for an incore-monitoring probe. This probe monitors temperature and neutron levels in the fuel assembly. The Davis-Besse reactor vessel, which con-tains all the fuel assemblies, weighs 838,000 pounds, has a diameter of 14 feet, is 39 feet high, and has steel walls that are 8 1/ inches thick.

~1

-dab-F~.I Rod REACTOR VESSEL Figure 6: The reactor core at Davis-Besse contains 177 fuel assemblies. Each assembly contains 208 fuel rods.

Each fuel rod is filled with approximately five pounds of fuel pellets, each pellet is approximately 3/8 inch diameter and 5/8 inch long.

13

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Fission Control Raising or lowering control rod assemblies into the reactor core controls the fission rate. Each assembly consists of "fingers" containing Silver, Indium, and Cadmium metals that absorb free neutrons, thus disrupting the fission chain reaction. When control rod assemblies are slowly withdrawn from the core, fissioning begins and heat is produced. If the control rod assemblies are inserted rapidly into the reactor core, as during a plant "trip", the chain reaction ceases. A slower acting (but more evenly distributed) method of fission control is achieved by the addition of a neutron poison to the reactor coolant water. At Davis-Besse, high-purity boric acid is con-centrated or diluted in the coolant to achieve the desired level of fission. Boron-10 readily ab-sorbs free neutrons, forming Boron-11, removing the absorbed neutrons from the chain reaction.

Reactor Types Virtually all of the commercial reactors in this country are either boiling water reactors (BWRs) or pressurized water reactors (PWRs). Both types are also called light water reac-tors (LWRs) because their coolant, or medium to transfer heat, is ordinary water, which contains the light isotope of Hydrogen. Some reactors use the heavy isotope of Hydrogen (deuterium) in the reactor coolant. Such reactors are called heavy water reactors (HWRs).

In BWRs, water passes through the core and boils into steam. The steam passes through separa-tors, which remove water droplets. The steam then travels to dryers before entering the turbine.

After passing though the turbine the steam is condensed back into water and returns to the core to repeat the cycle.

In PWRs, the reactor water or coolant is pressurized to prevent it from boiling. The reactor water is then pumped to a steam generator (heat exchanger) where its heat is transferred to a secon-dary water supply. The secondary water inside the generator boils into steam, which is then used to turn the turbine. This steam is then condensed back into water and returned to the steam gen-erator. Davis-Besse uses a PWR design.

The following paragraphs describe the various systems illustrated in Figure 7. Major systems in the Davis-Besse Station are assigned a different color in the figure.

14

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report 0OU) h..O Wz1 Ca Z =

U)

Coo Q\\

PCm 3z Wn Figure 7: Station Systems 15

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Station Systems Containment Building and Fission Product Release Barriers The Containment building houses the reactor vessel, the pressurizer, two steam generators, the Reactor Coolant Pumps and Reactor Coolant System piping. The building is constructed of an inner 1 -1/2 inch thick steel liner or Containment vessel, and the Shield Building with steel-reinforced concrete walls 2 feet thick. The shield building protects the containment vessel from a variety of environmental factors and provides an area for a negative pressure boundary around the steel Containment vessel. In the event that the integrity of the Containment vessel is com-promised (e.g., a crack develops), this negative pressure boundary ensures that any airborne ra-dioactive contamination present in the containment vessel is prevented from leaking out into the environment. This is accomplished by maintaining the pressure inside the Shield Building lower than that outdoors, thus forcing clean outside air to leak in, while making it impossible for the contaminated air between the Containment vessel and the Shield Building to leak out. The Con-tainment vessel is the third in a series of barriers that prevent the release of fission products in the unlikely event of an accident. The first barrier to the release of fission products is the fuel cladding itself. The second barrier is the walls of the primary system, i.e. the reactor vessel, steam generator and associated piping.

The Steam Generators The steam generators perform the same function as a boiler at a fossil-fueled power station.

The steam generator uses the heat of the primary coolant inside the steam generator tubes to boil the secondary side feedwater (secondary coolant). Fission heat from the reactor core is trans-ferred to the steam generator in order to provide the steam necessary to drive the turbine. How-ever, heat must also be removed from the core even after reactor shutdown in order to prevent damage to the fuel cladding. Therefore, pumps maintain a continuous flow of coolant through the reactor and steam generator. Primary loop water (green in Figure 7) exits the reactor at ap-proximately 606'F, passes through the steam generator, transferring some of its heat energy to the Secondary loop water (blue in Figure 7) without actually coming in contact with it. Primary coolant water exits the steam generator at approximately 558°F to be circulated back into the re-actor where it is again heated to 606'F as it passes up through the fuel assemblies. Under ordi-nary conditions, water inside the primary system would boil long before it reached such temperatures. However, it is kept under a pressure of approximately 2,200 pounds-per-square-inch (psi) at all times. This prevents the water from boiling and is the reason the reactor at Davis-Besse is called a Pressurized Water Reactor. Secondary loop water enters the base of the steam generator at approximately 450'F and under 1,100 psi pressure. At this pressure, the water can easily boil into steam as it passes over the tubes containing the primary coolant water.

Both the primary and the secondary coolant water are considered closed loop systems. This means that they are designed not to come in physical contact with one another. Rather, the cool-ing water in each loop transfers heat energy by convection. Convection is a method of heat transfer that can occur between two fluid media. It is the same process by which radiators are used to heat homes. The water circulating inside the radiator is separated from the air (a "fluid" medium) by the metal piping.

16

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report The Turbine Generator The turbine, main generator, and the condenser are all housed in What is commonly referred to as the Turbine Building. The purpose of the turbine is to convert the thermal energy of the steam produced in the steam generator (referred to as main steam, red in Figure 7) to rotational energy of the turbine generator shaft. The turbine at Davis-Besse is actually composed of one six-stage high-pressure turbine and two seven-stage low-pressure turbines aligned on a common shaft. A turbine stage refers to a set of blades. Steam enters at the center of each turbine and moves outward along the shaft in opposite directions through each successive stage of blading.

As the steam passes over the turbine blades, it loses pressure. Thus, the blades must be propor-tionally larger in successive stages to extract enough energy from the steam to rotate the shaft at the correct speed.

The purpose of the main generator is to convert the rotational energy of the shaft to electrical energy for commercial usage and support of station systems. The main generator is composed of two parts, a stationary stator that contains coils of copper conductors, and a rotor that supplies a rotating magnetic field within the coils of the stator. Electrical current is generated in the stator portion of the main generator. From this point, the electric current passes through a series.of transformers for transmission and use throughout northern Ohio.

The Condenser After the spent steam in the secondary loop (blue in Figure 7) passes through the High and Low Pressure Turbines, it is collected in the condenser, which is several stories tall and contains more than 70,000 small tubes. Circulating Water (yellow in Figure 7) goes to the Cooling Tower after passing through the tubes inside the Condenser. As the steam from the Low Pres-sure Turbines passes over these tubes, it is cooled and condensed. The condensed water is then purified and reheated before being circulated back into the steam generator again in a closed loop system. Circulating water forms the third (or tertiary) and final loop of cooling water used at the Davis-Besse Station.

Similar to the primary to secondary interface, the secondary-to-tertiary interface is based on a closed-loop design. The Circulating Water, which is pumped through the tubes in the Water Box, is able to cool the water in the Condenser by the processes of conduction and convection.

Even in the event of a primary-to-secondary leak, the water vapor exiting the Davis-Besse Cool-ing Tower would remain non-radioactive. Closed loops are an integral part of the design of any nuclear facility. This feature greatly reduces the chance of environmental impact from Station operation.

The Cooling Tower The Cooling Tower at Davis-Besse is easily the most noticeable feature of the plant. The tower stands 493 feet high and the diameter of the base is 411 feet. Two nine-foot diameter pipes circu-late 480,000 gallons of water per minute to the tower. Its purpose is to recycle water from the Condenser by cooling and returning it.

17

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report After passing through the Condenser, the Circulating Water has warmed to approximately I 00°F.

In order to cool the water back down to 70'F, the Circulating Water enters the Cooling Tower forty feet above the ground. It is then sprayed evenly over a series of baffles called fill sheets, which are suspended vertically in the base of the tower. A natural draft of air is swept upward through these baffles and cools the water by evaporation. The evaporated water exits the top of the Cooling Tower as water vapor.

As much as 10,000 gallons of water per minute are lost to the atmosphere via the Cooling Tower. Even so, approximately 98 percent of the water drawn from Lake Erie for station opera-tion can be recycled through the Cooling Tower for reuse. A small portion of the Circulating Water is discharged back to Lake Erie at essentially the same temperature it was withdrawn ear-lier. The slightly warmer water has no adverse environmental impact on the area of lake sur-rounding the discharge point.

Miscellaneous Station Safety Systems The orange system in Figure 7 is part of the Emergency Core Cooling System (ECCS) housed in the Auxiliary Building of the station. The ECCS consists of three overlapping means of keeping the reactor core covered with water, in the unlikely event of a Loss-of-Coolant Accident (LOCA), thereby protecting the fuel cladding barrier against high-temperature failure. Depend-ing on the severity of the loss of pressure inside the Primary System, the ECCS will automati-cally channel borated water into the Reactor by using High Pressure Injection Pumps, a Core Flood Tank, or Low Pressure Injection Pumps. Borated water can also be sprayed from the ceiling of the Containment Vessel to cool and condense any steam that escapes the Primary Sys-tem.

The violet system illustrated in Figure 7 is responsible for maintaining the Primary Coolant water in a liquid state. It accomplishes this by adjusting the pressure inside the Primary System. Heat-ers inside the Pressurizer turn water into steam. This steam takes up more space inside the Pres-surizer, thereby increasing the overall pressure inside the Primary System. The Pressurizer is equipped with spray heads that shower cool water over the steam in the unit. In this case, the steam condenses and the overall pressure inside the Primary System drops. The Quench Tank pictured in Figure 8 is simply where excess steam is directed and condensed for storage.

The scarlet system in Figure 7 is part of the Auxiliary Feedwater System, a key safety system in event the main feedwater supply (blue in Figure 7) to the Steam Generator is lost. Following a reactor shutdown, the Auxiliary Feedwater System can supply water to the Steam Generators from the Condensate Storage Tanks. The Auxiliary Feedwater System is housed in the Turbine Building along with the Turbine, Main Generator, and the Condenser.

18

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Reactor Safety and Summary Nuclear power plants are inherently safe, not only by the laws of physics, but by design. Nuclear power plants cannot explode like a bomb, because the concentration of fissionable material is far less than is necessary for such a nuclear explosion. Also, many safety features are equipped with several backup systems to ensure that any possible accident would be prevented from causing a serious health or safety threat to the public, or serious impact on the local environment. Davis-Besse, like all U.S. nuclear units, has many overlapping, or redundant safety features. If one sys-tem should fail, there are still back-up systems to assure the safe operation of the Station. During normal operation, the Reactor Control System regulates the power output by adjusting the posi-tion of the control rods. The Reactor can be automatically shut down by a separate Reactor Pro-tection System, which causes all the control rod assemblies to be quickly and completely inserted into the Reactor core, stopping the chain reaction. To guard against the possibility of a Loss of Coolant Accident, the Emergency Core Cooling System is designed to pump reserve wa-ter into the reactor automatically if the reactor coolant pressure drops below a predetermined level.

The Davis-Besse Nuclear Power Station was designed, constructed, and operates to produce a reliable, safe, and environmentally sound source of electricity.

Radioactive Waste Many of the activities we depend on in our everyday lives produce radioactive waste by-products.

Nuclear energy, industrial processes, and medical treatments are some of these activities. These by-products are managed and disposed of under strict requirements set by the federal govern-ment. With the exception of used nuclear fuel assemblies, these by-products produced at com-mercial power plants are referred to as low level radioactive waste.

Low Level Radioactive Waste Low level radioactive waste consists mainly of ordinary trash and other items that have become contaminated with radioactive materials. It includes plastic gloves and other protective clothing, machine parts and tools, medical and laboratory equipment, filters, resins, and general scrap.

The radioactive material in low level radioactive waste emits the same types of radiation that naturally occurring radioactive materials tend to emit. Most low level activity in radioactive waste decay to background levels within months or years. Nearly all activity diminishes to stable materials in less than 300 years.

Davis-Besse currently ships low-level radioactive waste to facilities in South Carolina and Ten-nessee for waste minimization processing prior to disposal. Davis-Besse has the capacity to store low-level waste produced on site for several years in the Low Level Radioactive Waste Storage Facility (LLRWSF), should these facilities close.

19

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report High Level Nuclear Waste Like any industrial or scientific process, nuclear energy does produce waste. The most radioac-tive is defined as "high-level" waste (because it has high levels of radioactivity). Ninety-nine percent of high-level waste from nuclear plants is used nuclear fuel. The fuel undergoes certain changes during fission. Most of the fragments of fission, pieces that are left over after the atom is split, are radioactive. After a period of time, the fission fragments trapped in the fuel assem-blies reduce the efficiency of the chain reaction. The oldest fuel assemblies are removed from the reactor and replaced with fresh fuel at 18-24 month intervals.

High-level nuclear waste volumes are small. Davis-Besse produces about 30 tons of used fuel every 24 months. All the used fuel produced by all America's nuclear energy plants since the first plant started operating over 30 years ago would cover an area the size of a football field about five yards deep. All of America's nuclear plants combined produce only 3,000 tons of used fuel each year. By contrast, the U.S. produces about 300,000,000 tons of chemical waste annu-ally. Also, nuclear waste slowly loses its radioactivity, but some chemical waste remains hazard-ous indefinitely.

Davis-Besse presently stores most of its used fuel in a steel-lined water-filled concrete vault in-side the. plant. The Department of Energy is charged with constructing a permanent high-level waste repository for all of the nation's nuclear plants. By law, the Department of Energy was required to accept fuel from utilities by the end of 1998. Currently, Yucca Mountain, Nevada, is being considered as a possible site. Until the permanent DOE site is developed, nuclear plants will be responsible for the continued safe storage of high-level waste. At Davis-Besse, the fuel pool reached its capacity in 1996. At the end of 1996, Davis-Besse began the process of moving the older fuel assemblies that no longer require water cooling to air-cooled concrete shielded can-isters. These will remain onsite until the Department of Energy facilities are ready to receive them. Dry fuel storage is already used in many countries, including Canada, and in the U.S. at nuclear plants in Arkansas, Colorado, Maryland, Michigan, Minnesota, Virginia, Wisconsin and South Carolina. Figure 8 illustrates the Dry Fuel Storage module arrangement at Davis-Besse.

In 2001, work was performed to increase the storage capacity of the Spent Fuel Pool. The pool remains the same size, however, removing old storage racks and replacing them with new ones changed the configuration of storage, and allows the site to safely hold all the fuel used during its 40 years of expected life. This modification was completed in April of 2002.

20

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report z

LU t

F D

u Figure 8: Dry Fuel Storage Module Arrangement 21

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Description of the Davis-Besse Site The Davis-Besse site is located in Carroll Township of Ottawa County, Ohio. It is on the south-western shore of Lake Erie, just north of the Toussaint River. The site lies north and east of Ohio State Route 2, approximately 10 miles northwest of Port Clinton, 7 miles north of Oak Harbor, and 25 miles east of Toledo, Ohio (Figure 9).

This section of Ohio is flat and marshy, with maximum elevations of only a few feet above the level of Lake Erie. The area originally consisted of swamp forest and marshland, rich in wildlife but unsuitable for settlement and farming. During the nineteenth century, the land was cleared and drained, and has been farmed successfully since. Today, the terrain consists of farmland with marshes extending in some places for up to two miles inland from the Sandusky Lake Shore Ridge.

L.ake Erie A

Figure 9: Davis-Besse is near Oak Harbor, Port Clinton, and the Ottawa National Wildlife Refuge.

The Davis-Besse site is mainly comprised of marshland, with a small portion consisting of farm-land. The marshes are part of a valuable ecological resource, providing a breeding ground for a variety of wildlife, and a refuge for migratory birds. The site includes a tract known as Navarre Marsh, which was acquired from the U.S. Bureau of Sport Fisheries and Wildlife, Department of the Interior. In 1971, Toledo Edison purchased the 188-acre Toussaint River Marsh. The Tous-saint River Marsh is contiguous with the 610-acre Navarre Marsh section of the Ottawa National Wildlife Refuge.

22

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report The immediate area near Davis-Besse is sparsely populated. The year 2000 Census listed the population of Ottawa County at 40,985. The incorporated communities nearest to Davis-Besse are:

Port Clinton - 10 miles southeast, population 6,391 Oak Harbor - 7 miles south, population 2,841 Rocky Ridge - 7 miles west southwest, population 389 Toledo (nearest major city) - 25 miles west, population 313,619 There are some residences along the lakeshore used mainly as summer homes. However, the ma-jor resort area of the county is farther east, around Port Clinton, Lakeside, and the Bass Islands.

The majority of non-marsh areas around the Davis-Besse site are used for farming. The major crops include soybeans, corn, wheat, oats, hay, fruits and vegetables. Meat and dairy animals are not major sources of income in the area. The main industries within five miles of the site are lo-cated in Erie Industrial Park, about four miles southeast of the station.

Most of the remaining marshes in the area have been maintained by private hunting clubs, the U.S. Fish and Wildlife Service, and the Ohio Department of Natural Resources, Division of Wildlife. The State of Ohio Department of Natural Resources operates many wildlife and recrea-tional areas within 10 miles of the Station. These include Magee Marsh, Turtle Creek, Crane Creek State Park, and the Ottawa National Wildlife Refuge. Magee Marsh and Turtle Creek lie between three and six miles WNW of the Station. Magee Marsh is a wildlife preserve that al-lows public fishing, nature study, and a controlled hunting season. Turtle Creek, a wooded area at the southern end of Magee Marsh, offers boating and fishing. Crane Creek State Park is adja-cent to Magee Marsh, and is a popular birding and hunting area. The Ottawa National Wildlife Refuge lies four to nine miles WNW of the Site, immediately west of MageeMarsh.

23

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report References

1. "Basic Radiation Protection Criteria," Report No. 39, National Council on Radiation Protec-tion and Measurement, Washington, D.C. (January 1971).
2.

"Cesium-137 from the Environment to Man: Metabolism and Dose," Report No. 52, National Council on Radiation Protection and Measurements, Washington, D.C. (January 1977).

3. Deutch, R., "Nuclear Power, A Rational Approach," Fourth edition, GP Courseware, Inc.,

Columbia, MD. (1987).

4. Eisenbud, M., "Environmental Radioactivity," Academic Press, Inc., Orlando, FL. (1987).
5. "Environmental Radiation Measurements," Report No. 50, National Council on Radiation Protection and Measurements, Washington, D.C. (December 1976).
6. "Exposure of the Population in the United States and Canada from Natural Background Ra-diation," Report No. 94, National Council on Radiation Protection and Measurements, Wash-ington, D.C. (December 1987).
7. "Health Effects of Exposure to Low Levels of Ionizing Radiation: BEIR V," Committee on the Biological Effects of Ionizing Radiations, Board on Radiation Effects Research Commis-sion on Life Sciences, National Research Council, National Academy Press, Washington, D.C. (1990).
8.

Hendee, William R., and Doege, Theodore C., "Origin and Health Risks of Indoor Radon,"

Seminars in Nuclear Medicine, Vol. XVIII, No. 1, American Medical Association, Chicago, IL. (January 1987).

9. Hurley, P., "Living with Nuclear Radiation," University of Michigan Press, Ann Arbor, MI.

(1982).

10. "Indoor Air Quality Environmental Information Handbook: Radon," prepared for the United States Department of Energy, Assistant Secretary for Environment, Safety and Health, by Mueller Associated, Inc., Baltimore, MD. (January 1986).
11. Introduction to Davis-Besse Nuclear Power Station Plant Technology, July 1992, Rev. 4, Pg.2-9.
12. "Ionizing Radiation Exposure of the Population of the United States," Report No. 93, Na-tional Council on Radiation Protection and Measurements, Washington, D.C. (September.

1987).

13. "Natural Background Radiation in the United States," Report No. 45, National Council on Radiation Protection and Measurements, Washington, D.C. (November 1975).

24

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report

14. "Nuclear Energy Emerges from 1980's Poised for New Growth," U.S. Council for Energy Awareness, Washington, D.C. (1989).
15. "Nuclear Power: Answers to Your Questions," Edison Electric Institute, Washington, D.C.

(1987).

16. "Public Radiation Exposure from Nuclear Power Generation in the United States," Report No. 92, National Council on Radiation Protection and Measurement, Washington, D.C. (De-cember 1987).
17. "Radiation Protection Standards," Department of Environmental Sciences and Physiology and the Office of Continuing Education, Harvard School Of Public Health, Boston, MA.

(July 1989).

18. Radiological Environmental Monitoring Report for Three Mile Island Station," GPU Nuclear Corporation, Middletown, PA. (1985).
19. "Sources, Effects and Risk of Ionizing Radiation," United Nations Scientific Committee on the Effects of Atomic Radiation, 1988 Report to the General Assembly, United Nations, New York (1988).
20. "Standards for Protection Against Radiation," Title 10, Part 20, Code of Federal Regulation, Washington, D.C. (1988).
21. "Domestic Licensing of Production and Utilization Facilities," Title 10, Part 50, Code of Federal Regulations, Washington, D.C. (1988).
22. "Environmental Radiation Protection Standard for Nuclear Power Operations," Title 40, Part 190, Code of Federal Regulations, Washington, D.C. (1988).
23. "Tritium in the Environment," Report No. 62, National Council on Radiation Protection and Measurement, Washington, D.C. (March 1979).
24. Site Environmental Report, Fernald Environmental Management Project, United States De-partment of Energy (June 1993).
25. "Exposure from the Uranium Series with Emphasis on Radon and its Daughters" Report No.

77, National Council on Radiation Protection and Measurements, Washington, D.C. (1984).

26. "Evaluation of Occupational and Environmental Exposures to Radon and Radon daughter in the United States,"Report No. 78, National Council on Radiation Protection and Measure-ments, Washington, D.C. (1984).

25

Radiological Environmental Monitoring Program

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Radiological Environmental Monitoring Program Introduction The Radiological Environmental Monitoring Program (REMP) was established at Davis-Besse for several reasons: to provide a supplementary check on the adequacy of containment and effluent controls, to assess the radiological impact of the Station's operation on the surrounding area, and to determine compliance with applicable radiation protection guides and standards. The REMP was established in 1972, five years before the Station became operational.

This pre-operational surveillance program was established to describe and quantify the radioactivity, and its variability, in the area prior to the operation of Davis-Besse. After Davis-Besse became operational in 1977, the operational surveillance program continued to measure radiation and radioactivity in the surrounding areas.

A variety of environmental samples are collected as part of the REMP at Davis-Besse. The se-lection of sample types is based on the established critical pathways for the transfer of radionu-clides through the environment to humans.

The selection of sampling locations is based on sample availability, local meteorological and hydrological characteristics, local population char-acteristics, and land usage in the area of interest. The selection of sampling frequencies for the various environmental media is based on the radionuclides of interest, their respective half-lives, and their effect in both biological and physical enyironments.

A description of the REMP at Davis-Besse is provided in the following section. In addition, a brief history of analytical results for each sample type collected since 1972, and a more detailed summary of the analyses performed during this reporting period, is also provided.

Pre-operational Surveillance Program The federal government requires nuclear facilities to conduct radiological environmental moni-toring prior to constructing the facility. This pre-operational surveillance program is for the col-lection of data needed to identify critical pathways, including selection of radioisotope and sample media combinations for the surveillance conducted after facility operations begin. Ra-diochemical analyses performed on samples should include nuclides that are expected to be re-leased during normal facility operations, as well as typical fallout radionuclides and natural background radioactivity. All enviromnental media with a potential to be affected by facility op-eration, as well as those media directly in the critical pathways, should be sampled during the pre-operational phase of the environmental surveillance program.

The pre-operational surveillance design, including nuclide/media combinations, sampling fre-quencies and locations, collection techniques, and radiochemical analyses performed, should be carefully considered and incorporated in the design of the operational surveillance program. In 26

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report this manner, data can be compared in a variety of ways (for example: from year to year, location to location, etc.) in order to detect any radiological impact the facility has on the surrounding en-vironment. Data collection during the pre-operational phase should be planned to provide a com-prehensive database for evaluating any future changes in the environment surrounding the nuclear facility.

Davis-Besse began its pre-operational environmental surveillance program five years before the Station began producing power for commercial use in 1977. Data accumulated during that time provides an extensive database from which Station personnel are able to identify trends in the radiological characteristics of the local environment. The environmental surveillance program at Davis-Besse will continue after the Station has reached the end of its economically useful life and decommissioning has begun.

Operational Surveillance Program Objectives The operational phase of the environmental surveillance program at Davis-Besse was designed with the following objectives in mind:

  • to determine whether any significant increase in the concentration of radionu-clides in critical pathways occurs
  • to identify and evaluate the buildup, if any, of radionuclides in the local envi-ronrnent, or any changes in normal background radiation levels

" to verify the adequacy of Station controls for the release of radioactive mate-rials Quality Assurance An important part of the environmental monitoring program at Davis-Besse is the Quality Assurance (QA) Program, which is conducted in accordance with the guidelines specified in NRC Regulatory Guide 4.15, "Quality Assurance for Radiological Monitoring Programs". The QA Program is designed to identify possible deficiencies in the REMP so that corrective actions can be initiated promptly. Davis-Besse's Quality Assurance program also provides confidence in the results of the REMP through:

  • performing regular audits (investigations) of the REMP, including a careful examination of sample collection techniques and record keeping
  • performing audits of contractor laboratories which analyze the environmental samples

" requiring analytical contractor laboratories to participate in the United States Environmental Protection Agency Cross Check Program o requiring analytical contractor laboratories to split samples for separate analy-sis followed by a comparison of results splitting samples prior to analysis by independent laboratories, and then com-paring the results for agreement 27

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report 0

requiring analytical contractor laboratories to perform in-house spiked sample analyses Quality Assessment audits and inspections of the Davis-Besse REMP are performed by the FirstEnergy Nuclear Operating Company QA Department and the NRC. In addition, the Ohio Department of Health (ODH) also performs independent environmental monitoring in the vicin-ity of Davis-Besse. The types of samples collected and list of sampling locations used by the ODH was incorporated in Davis-Besse's REMP, and the analytical results from their program can be compared to Davis-Besse's. This practice of comparing results from identical samples, which are collected and analyzed by different parties, provides a valuable tool to verify the quality of the laboratories' analytical procedures and data generated.

In 1987, environmental sampling personnel at Davis-Besse incorporated their own QA program into the REMP. Duplicate samples, called quality control samples, were collected at several lo-cations. These duplicate samples were assigned different identification numbers than the num-bers assigned to the routine samples. This ensured that the analytical laboratory would not know the samples were identical. The laboratory results from analysis of the quality control samples and the routine samples could then be compared for agreement. Quality control sampling has been integrated into the program and has become an important part of the REMP since 1987.

Quality control sampling locations are changed frequently in order to duplicate as many sampling locations as possible, and to ensure the contractor laboratory has no way of correctly pairing a quality control sample with its routine sample counterpart.

Program Description The Radiological Environmental Monitoring Program (REMP) at Davis-Besse is conducted in accordance with Title 10, Code of Federal Regulations, Part 50; Regulatory Guide 4.8; the Davis-Besse Nuclear Power Station Operating License, Sections 5.6.1 and 5.6.2 of Davis-Besse Im-proved Standard Technical Specifications, the Davis-Besse Offsite Dose Calculation Manual (ODCM) and Station Operating Procedures. Samples are collected weekly, monthly, quarterly, semiannually, or annually, depending upon the sample type and nature of the radionuclides of interest. Environmental samples collected by Davis-Besse personnel are divided into four gen-eral types:

" atmospheric -- including samples of airborne particulate and airborne radio-iodine

" terrestrial -- including samples of milk, groundwater, broad leaf vegetation, fruits, animal/wildlife feed, soil, and wild and domestic meat

" aquatic -- including samples of treated and untreated surface water, fish, and shoreline sediments

" direct radiation -- measured by thermoluminescent dosimeters All environmental samples are labeled using a sampling code. Table 2 provides the sample codes and collection frequency for each sample type.

REMP samples are collected onsite and offsite up to 25 miles away from the Station. Sampling locations may be divided into two general categories: indicator and control. Indicator locations are those which would be most likely to display the effects caused by the operation of Davis-28

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Besse, and are located within five miles of the station. Control locations are those which should be unaffected by Station operations, and are more than five miles from the Station. Data from indicator locations are compared with data from the control locations. This comparison allows REMP personnel to take into account naturally-occurring background radiation or fallout from weapons testing in evaluating any radiological impact Davis-Besse has on the surrounding envi-rorment. Data from indicator and control locations are also compared with pre-operational data to determine whether significant variations or trends exist.

Since 1987 the REMP has been reviewed and modified to develop a comprehensive sampling program adjusted to the current needs of the utility. Modifications have included additions of sampling locations above the minimum amount required in the ODCM and increasing the num-ber of analyses performed on each sample. Besides adding new locations, duplicate or Quality Control (QC) sample collection was initiated to verify the accuracy of the lab analyzing the envi-ronmental samples. These additional samples are referred to as the REMP Enhancement Sam-ples. Approximately 2,000 samples were collected and over 2,300 analyses were performed during 2008. In addition, 15% of the sampling locations were quality control sampling locations.

Table 3 shows the number of the sampling location and number collected for each type.

29

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Table 2: Sample Codes and Collection Frequencies Sample Type Airborne Particulate Airborne Iodine Thermoluminescent Dosimeter Milk Groundwater Broadleaf Vegetation Surface Water - Treated Surface Water -

Untreated Fish Shoreline Sediment Soil Wildlife Feed Meat-Wild Fruit Sample Code AP Al TLD MIL WW BLV SWT SWU FIS SED Sol WFE WME FRU Collection Frequency Weekly Weekly Quarterly, Annually Monthly (semi-monthly during grazing season)

Quarterly Monthly (when available)

Weekly Weekly Annually Semiannually Annually Annually Annually Annually 30

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Table 3: Sample Collection Summary Sample

  • Type (Remarks)

Collection Type*/

Frequency**

Number of Locations Number of Samples Collected Number of Samples Missed Atmospheric Airborne Particulates Airborne Radioiodine Terrestrial Milk (Jan.-Dec.)

Groundwater Wild Meat Broadleaf Vegetation Fruit Soil Animal/Wildlife Feed Aquatic Treated Surface Water Untreated Surface Water Fish (2 species)

Shoreline Sediments Direct Radiation Thermoluminescent Dosimeters (TLD)

C/W C/W G/M G/Q**

G/A G/M G/A G/A G/A Comp/WM G/WM***

G/WM***

Comp/WM G/A G/SA C/Q***

C/A***

10 10 1

3 2

3 3

10 3

4 1

3 3

2 5

88 88 519 519 12 9

2 9

3 10 3

208 52 156 156 6

10 352 88 1

1 0

  • Type of Collection: C = Continuous; G = Grab; Comp = Composite
    • Frequency of Collection: WM = Weekly composite Monthly; W = Weekly, M = Monthly; Q = Quarterly when available; SA = Semiannually; A = Annually
      • Includes quality control location. SWU and SWT QC included in weekly grab sample/composited monthly 31

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Sample Analysis When environmental samples are analyzed, several types of measurements may be performed to provide information about the radionuclides present. The major analyses that are performed on environmental samples collected for the Davis-Besse REMP include:

Gross beta analysis measures the total amount of beta emitting radioactive material present in a sample. Beta radiation may be released by many different radionuclides. Since beta decay gives a continuous energy spectrum rather than the discrete lines or "peaks" associated with gamma radiation, identification of specific beta emitting nuclides is much more difficult. Therefore, gross beta analysis only indicates whether the sample contains normal or abnormal concentra-tions of beta emitting radionuclides; it does not identify specific radionuclides. Gross beta analy-sis merely acts as a tool to identify samples that may require further analysis.

Gamma spectral analysis provides more specific information than does gross beta analysis.

Gamma spectral analysis identifies each gamma emitting radionuclide present in the sample, and the amount of each nuclide present. Each radionuclide has a very specific "fingerprint" that al-lows for swift and accurate identification. For example, gamma spectral analysis can be used to identify the presence and amount of Iodine-131 in a sample. Iodine-131 is a man-made radioac-tive isotope of Iodine that may be present in the environment as a result of fallout from nuclear weapons testing, routine medical uses in diagnostic tests, and routine releases from nuclear power stations.

Tritium analysis indicates whether a sample contains the radionuclide tritium (H-3) and the amount present. As discussed in the Introduction section, tritium is an isotope of Hydrogen that emits low energy beta particles.

Strontium analysis identifies the presence and amount of Strontium-89 and Strontium-90 in a sample. These man-made radionuclides are found in the environment as a result of fallout from nuclear weapons testing. Strontium is usually incorporated into the pool of the biosphere. In other words, it accumulates in living organisms, where it is stored in the bone tissue. The princi-pal Strontium exposure pathway is via milk produced by cattle grazed on pastures exposed to deposition from airborne releases.

Gamma Doses measured by thermoluminescent dosimeters while in the field are determined by a special laboratory procedure. Table 4 provides a list of the analyses performed on environ-mental samples collected for the Davis-Besse REMP.

Often samples will contain little radioactivity, and may be below the lower limit of detection for the particular type of analysis used. The lower limit of detection (LLD) is the smallest amount of sample activity that can be detected with a reasonable degree of confidence at a predetermined level. When a measurement of radioactivity is reported as less than LLD (<LLD), it means that the radioactivity is so low that it cannot be accurately measured with any degree of confidence by a particular method for an individual analysis.

32

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Table 4: Radiochemical Analyses Performed on REMP Samples Sample Type Atmospheric Monitoring Airborne Particulate Airborne Radioiodine Terrestrial Monitoring Analyses Performed Gross Beta Gamma Spectroscopy Strontium-89 Strontium-90 Iodine-131 Milk Groundwater Broadleaf Vegetation and Fruits Wildlife Feed Soil Wild Animal Meat Gamma Spectroscopy Iodine-131 Strontium-89 Strontium-90 Stable Calcium Stable Potassium Gross Beta Gamma Spectroscopy Tritium Strontium-89 Strontium-90 Gamma Spectroscopy Iodine-131 Strontium-89 Strontium-90 Gamma Spectroscopy Gamma Spectroscopy Gamma Spectroscopy 33

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Table 4: Radiochemical Analyses Performed on REMP Samples (continued)

Sample Type Analyses Performed Aquatic monitoring Untreated Surface Water Treated Surface Water Fish Gross Beta Gamma Spectroscopy Tritium Strontium-89 Strontium-90 Gross Beta Gamma Spectroscopy Tritium Strontium-89 Strontium-90 Iodine-131 Gross Beta Gamma Spectroscopy Gamma Spectroscopy Shoreline Sediment Direct Radiation Monitoring Thermoluminescent Dosimeters Gamma Dose Sample History Comparison The measurement of radioactive materials present in the environment will depend on factors such as weather or variations in sample collection techniques or sample analysis. This is one reason why the results of sample analyses are compared with results from other locations and from ear-lier years. Generally, the results of sample analyses are compared with pre-operational and op-erational data. Additionally, the results of indicator and control locations are also compared.

This allows REMP personnel to track and trend the radionuclides present in the environment, to assess whether a buildup of radionuclides is occurring and to determine the effects, if any, the operation of Davis-Besse is having on the environment. If any unusual activity is detected, it is investigated to determine whether it is attributable to the operation of Davis-Besse, or to some other source such as nuclear weapons testing.

34

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Atmospheric Monitoring

" Airborne Particulates: No radioactive particulates have been detected as a result of Davis-Besse's operation. Only natural and fallout radioactivity from nuclear weapons testing and the 1986 nuclear accident at Chernobyl have been detected.

  • Airborne Radioiodine: Radioactive Iodine-131 fallout was detected in 1976, 1977, and 1978 from nuclear weapons testing, and in 1986 (0.12 to 1.2 picocuries per cubic meter) from the nuclear accident at Chernobyl.

Terrestrial Monitoring:

  • Groundwater: Tritium was not detected above the lower limit of detection dur-ing 2008 in any REMP samples.
  • Milk: Iodine-131 from nuclear weapons testing fallout was detected in 1976 and 1977 at concentrations of 1.36 and 23.9 picocuries/liter respectively. In 1986, concentrations of 8.5 picocuries/liter were detected from the nuclear accident at Chernobyl. No Iodine-131 detected has been attributable to the operation of Davis-Besse.
  • Wild Meat: Only naturally-occurring Potassium-40 and very low Cesium-137 from fallout activity has been detected in meat samples. Potassium-40 has ranged from 1.1 to 4.6 picocuries/gram weight (wet). Cesium-137 was detected in 1974, 1975, and 1981 due to fallout from nuclear weapons testing.
  • Broadleaf Vegetation and Fruits: Only naturally-occurring radioactive material and material from nuclear weapons testing have been detected.

" Soil: Only natural background and material from nuclear weapons testing and the 1986 nuclear accident at Chernobyl have been detected.

" Animal/Wildlife Feed: Only natural background and material from weapons test-ing have been detected.

Aquatic Monitoring

  • Surface Water (Treated and Untreated): Historically, tritium has been detected sporadically at low levels in treated and untreated surface water at both Control and Indicator locations. During 2008 there were no samples of either Treated or Untreated Water that showed detectable tritium.

" Fish: Only natural background radioactive material and material from nuclear testing have been detected.

  • Shoreline Sediments: Only natural background radiation, material from nuclear testing and the 1986 nuclear accident at Chernobyl have been detected.

Direct Radiation Monitoring

  • Thermoluminescent Dosimeters (TLDs): The annual gamma dose rates for the current reporting period recorded by TLDs averaged 65.8 millirem/year at Control locations, and 59.4 millirem/year at Indicator locations. No increase above natural 35

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report background radiation attributable to the operation of Davis-Besse has been ob-served.

2008 Program Anomalies All ODCM-required samples were collected during 2008. Provided below is a description of sample collection irregularities:

" On March 10, ODCM-required air samplers T-1, T-2, and T-3 were without-power for 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br /> due to scheduled maintenance. There were no radioactive gaseous batch releases or abnormal gaseous releases during the time the samplers were without power.

  • On April 29, the air iodine/particulate sample at location T-7 (ODCM required) was missed due to an equipment malfunction. Enhancement sample T-9 was substituted in its place to fulfill the intent of the ODCM. Therefore, this is not considered a missed ODCM sample.

All other samples were collected as scheduled.

Atmospheric Monitoring Air Samples Environmental air sampling is conducted to detect any increase in the concentration of airborne radionuclides that may be inhaled by humans or serve as an external radiation source. Inhaled radionuclides may be absorbed from the lungs, gastrointestinal tract, or from the skin. Air sam-ples collected by the Davis-Besse REMP include airborne particulate and airborne radioio-dine.

Samples are collected weekly with low volume vacuum pumps, which draw a continuous sample through a glass fiber filter and charcoal cartridge at a rate of approximately one cubic foot per minute. Airborne particulate samples are collected on 47mm diameter filters. Charcoal car-tridges are installed downstream of the particulate filters to sample for the airborne radioiodine.

The airborne samples are sent to an offsite contract laboratory for analysis. At the laboratory, the airborne particulate filters are stored for 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> before they are analyzed to allow for the decay of naturally-occurring short-lived radionuclides. However, due to the short half-life of iodine-131 (approximately eight days), the airborne radioiodine cartridges are analyzed upon receipt by the contract laboratory.

36

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Airborne Particulate Davis-Besse has ten continuous air samplers that monitor for air particulate and iodine. There are six indicator locations including four around the site boundary (T-1, T-2, T-3, and T-4), one at Sand Beach (T-7), and another at a local farm (T-8). There are four control locations, Oak Harbor (T-9), Port Clinton (T-1 1), Toledo (T-12) and Crane Creek (T-27). Gross beta analysis is performed on each of the weekly samples.

Each quarter, the filters from each location are combined (composite) and analyzed for gamma-emitting radionuclides, Strontium-89 and Strontium-90. Beta-emitting radionuclides were de-tected at both the indicator and control locations at average concentrations of 0.026 pCi/m3'. Be-ryllium-7 was the only gamma-emitting radionuclide detected by the gamma spectroscopic analysis of the quarterly composites.

Beryllium-7 is a naturally-occurring radionuclide produced in the upper atmosphere by cosmic radiation. No other gamma-emitting radionuclides were detected above their respective LLDs.

Strontium-89 and Strontium-90 were not detected above their LLDs. These results show no ad-verse change in radioactivity in air samples attributable to the operation of the Davis-Besse Nu-clear Power Station in 2008.

37

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Airborne Iodine-131 Airborne iodine.-131 samples are collected at the same ten locations as the airborne particulate samples. Charcoal cartridges are placed downstream of the.particulate filters. These cartridges are collected weekly, sealed in separate collection bags and sent to the laboratory for gamma analysis. There was no detectable iodine-131 above the LLD of 0.07 pCi/mi3.

2008 Air Gross Beta 0.04 -

0.035-0.03 -

0.025 0.02---

0.015-0.01 0.005 0

January February March April May June July August September October November December date c.--Control Indicator Figure 10. Concentrations of beta-emitting radionuclides in airborne particulate samples were nearly identical at indicator and control locations.

38

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Table 5: Air Monitoring Locations Sample Location Number T-1 T-2 T-3 T-4 T-7 Type of Location I

I I

I I

Location Description Site boundary, 0.6 miles ENE of Station Site boundary, 0.9 miles E of Station Site boundary, 1.4 miles ESE of Station Site boundary, 0.8 miles S of Station Sand Beach, main entrance, 0.9 miles NW of Station Earl Moore Farm, 2.7 miles WSW of Station Oak Harbor Substation, 6.8 miles SW of Station Port Clinton Water Treatment Plant, 9.5 miles SE of Station Toledo Water Treatment Plant, 20.7 miles WNW of Station Crane Creek State Park, 5.3 miles WNW of Station T-8 T-9 T-11 T-12 T-27 I

C C

C C

I = Indicator C = Control 39

DAVIS-BESSE NUCLEAR POWER STATION RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM AIR SAMPLES:

SITE NW NNW N

0 NEaN E

0S DISCHARCnPIP I

0 ING ENE Lo 0

S SSW YAR E

E T-4

-4 0

S S

,R EPE 0,

INT 7 Ill o~ff SR C

T-oAC I/l CL (D

WSW__

0 u) 0 AIR SAMPLE0 (D

T-4 S

SSE

%1 DB0 04-02-09 DFN-FtISCHEDISKZ817.DGN

DAVIS-BESSE NUCLEAR POWER STATION RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM AIR SAMPLES: 5 MILE RADIUS WNW' 16 CD CD uCD z

U)

-u 0

x CD, c 0 C

0 cc 0

TOUSSAI EAST RD CD RICLE 0

USSAIN R

FI0 00 WSW

_jRUSfr0 Creek Cc 0

0 4

0-0 BIER FINDCATR STTIOS

~

1

~

F CD

DAVIS-BESSE NUCLEAR POWER STATION RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM AIR SAMPLES: 5-25 MILE RADIUS OREGON CD CD

('o 0) 01 K)

OD z3 CD CL 0

CD 0

0 0

DB: 04-02-09 DFN=F:/SCHED/SKZ815.DGN I

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Terrestrial Monitoring The collection and analysis of groundwater, milk, meat, fruits and broad leaf vegetation provides data to assess the buildup of radionuclides that may be ingested by humans. Animal and wildlife feed samples provide additional information on radionuclides that may be present in the food chain. The data from soil sampling provides information on the deposition of radionuclides from the atmosphere.

Many radionuclides are present in the environment due to sources such as cosmic radiation and fallout from nuclear weapons testing. Some of the radionuclides present are:

" tritium, present as a result of the interaction of cosmic radiation with the upper atmosphere and as a result of routine release from nuclear facilities

  • Beryllium-7, present as a result of the interaction of cosmic radiation with the upper atmosphere
  • Cesium-137, a manmade radionuclide which has been deposited in the environment, (for example, in surface soils) as a result of fallout from nu-clear weapons testing and routine releases from nuclear facilities
  • Potassium-40, a naturally occurring radionuclide normally found through-out the environment (including in the human body)

" Fallout radionuclides from nuclear weapons testing, including Strontium-89, Strontium-90, Cesium-137, Cerium-141, Cerium-144, and Ruthenium-106. These radionuclides may also be released in minute amounts from nuclear facilities The radionuclides listed above are expected to be present in many of the environmental samples collected in the vicinity of the Davis-Besse Station. The contribution of radionuclides from the operation of Davis-Besse is assessed by comparing sample results with pre-operational data, op-erational data from previous years, control location data, and the types and amounts of radioac-tivity normally released from the Station in liquid and gaseous effluents.

Milk Samples Milk sampling is a valuable tool in environmental surveillance because it provides a direct basis for assessing the build up of radionuclides in the environment that may be ingested by humans.

Milk is collected and analyzed because it is one of the few foods commonly consumed soon after production. The milk pathway involves the deposition of radionuclides from atmospheric re-leases onto forage consumed by cows. The radionuclides present in the forage-eating cow be-come incorporated into the milk, which is then consumed by humans.

When available, milk samples are collected at indicator and control locations once a month from November through April, and twice a month between May and October. Sampling is increased in the summer when the herds are usually outside on pasture and not on stored feed. In Decem-ber of 1993, indicator location T-8 was eliminated from the sampling program, and no other in-dicator milk site has existed since that time. The control location will continue to be sampled 43

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report monthly in order to gather additional baseline data. If any dairy animals are discovered within five miles of the station, efforts will be made to include them in the milk-sampling program as indicator sites.

The 2008 milk samples were analyzed for Strontium-89, Strontium-90, Iodine-131, other gamma-emitting radionuclides, stable Calcium and Potassium. A total of 12 milk samples were collected in 2008. Strontium-89 was not detected above its LLD of 1.0 pCi/l. The annual aver-age concentration of Strontium-90 was 1.0 pCi/l. For all sample sites, the annual average con-centration was similar to those measured in the previous years.

Iodine-131 was not detected in any of the milk samples above the LLD of 0.5 pCi/I. The concen-trations of Barium-140 and Cesium-137 were below their respective LLDs in all samples col-lected.

Since the chemistries of Calcium and Strontium are similar, as are Potassium and Cesium, organ-isms tend to deposit Cesium radioisotopes in muscle tissue and Strontium radioisotopes in bones.

In order to detect the potential environmental accumulation of these radionuclides, the ratios of the Strontium radioactivity (pCi/1) to the concentration of Calcium (g/l), and the Cesium radioac-tivity (pCi/1) compared to the concentration of Potassium (g/l) were monitored in milk. These ratios are compared to standard values to determine if buildup is occurring. No statistically sig-nificant variations in the ratios were observed.

Table 6: Milk Monitoring Location Sample Location Type of Number Location Location Description T-24 C

Toft Dairy, Sandusky, 21.0 miles SE of Station C = Control Groundwater Samples Soil acts as a filter and an ion exchange medium for most radionuclides. However, tritium and other radionuclides such as Ruthenium-106 have a potential to seep through the soil and could reach groundwater. Davis-Besse does not discharge its liquid effluents directly to the ground. In the past, REMP personnel sampled local wells on a quarterly basis to ensure early detection of any adverse impact on the local groundwater supplies due to Station operation. In addition, a quality control sample was collected at one of the wells each quarter. The groundwater samples were analyzed for beta-emitting radionuclides, tritium, Strontium-89, Strontium-90 and gamma-emitting radionuclides.

During the fall of 1998, the Carroll Township Water Plant began operation and offered residents a reliable source of high-quality, inexpensive drinking water. This facility has replaced all of the 44

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report drinking water wells near Davis-Besse, as verified by the Ottawa County Health Department, and the indicator groundwater sampling was discontinued for a year. Since that time, two beach wells were located within five miles of the Station. Although the residents are seasonal and only use the township system for their drinking water needs, these wells were added to our sampling program as Indicator locations. The gross beta averaged 2.1 pCi/1 at Indicator site. The Control location is sampled as available at T-27, and the gross beta averaged 2.7.pCi/1 gross beta for the year 2008. REMP Groundwater samples did not appear to be affected by the operation of the Davis-Besse Nuclear Power Station.

Gross Beta Ground Water 1982-2008 7

6 5

4. ~AAY.I K&kV J

[]

in V

M

-;r' Lo CD r--

00 C) 0 N

M'

-I M)

L0 r-M0 M

0 M

-It ~

0 (0

P_

M0 co oo C0

(

0 (0

(

0C)

CC)

CC) 0o co 00 M)

M DC C

)

a)

M) 0 C

0 0

0 0

0 0

0 C)~~

n)

C

)

C

)

C

)

C

)

)

C

)

C

)

C

)

C 0

0>

0 0

0D 0D 0

0 0

ý2

ý2 (N

04 C

N C1 0

N CN N

Year

-*-I IrdfCalr -~-GContrd Figure 14: Shown above are the annual averages for gross beta in groundwater from 1982-2008. There were no known indicator samples available in 2000.

45

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Table 7: Groundwater Monitoring Locations Sample Location Type of Number Location Location Description T-27 C

Crane Creek State Park, 5.3 miles WNW of Station T-226 Allen residence, 1.6 miles NW of Station C = control I = indicator Broadleaf Vegetation and Fruit Samples Fruits and broadleaf vegetation also represent a direct pathway to humans. Fruits and broadleaf vegetation may become contaminated by deposition of airborne radioactivity (nuclear weapons fallout or airborne releases from nuclear facilities), or from irrigation water drawn from lake wa-ter which receives liquid effluents (hospitals, nuclear facilities, etc.). Radionuclides from the soil may be absorbed by the roots of the plants and become incorporated into' the edible portions.

During the growing season, edible broadleaf vegetation samples, such as kale and cabbage, are collected from gardens and farms in the vicinity of the Station. Fruit, such as apples, is collected from orchards in the vicinity of Davis-Besse.

In 2008, broadleaf vegetation samples were collected at two indicator locations (T-227 and T-19) and one control location (T-37). Fruit samples were collected at two indicator locations (T-8 and T-25) and one control location (T-209). Broadleaf vegetation was collected once per month dur-ing the growing season and consisted of cabbage. The fruit that was collected was apples. All samples were analyzed for gamma-emitting radionuclides, Strontium-89, Strontium-90, and lo-dine-131.

Iodine-131 was not detected above the LLD of 0.022 pCi/g (wet) in any broadleaf vegetation nor above the LLD of 0.032 pCi/g (wet) in fruit samples. The only gamma-emitting radionuclide de-tected in the fruit and broadleaf vegetation samples was Potassium-40, which is naturally occur-ring. Results of broadleaf vegetation and fruit samples were similar to results observed in previous years. Neither Strontium 89 and Strontium 90 were detected in broadleaf or in apple samples. Operation of Davis-Besse had no observable adverse radiological effect on the sur-rounding environment in 2008.

46

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Table 8: Broadleaf Vegetation and Fruit Locations Sample Location Type of Number Location Location Description T-8 I

Moore Farm, 2.7 miles WSW of Station T-19 I

L. Bowyer Jr., 1.0 mile W of Station T-25 I

Witt Farm, 1.6 miles S of Station T-37 C

Befich Farm, 13.0 miles SW of Station T-209 C

Roving Control Fruit location T-227 I

Roving BLV location I = indicator, C = control AnimallWildlife Feed Samples Vegetation consumed by wildlife can provide an indication of airborne radionuclides deposited in the vicinity of the Station. Analyses of wildlife feed samples can also provide data for deter-mining radionuclide concentration in the food chain. Wildlife feed samples are collected from the Navarre Marsh and from a local marsh within five miles of the Station. As in all terrestrial samples, naturally occurring Potassium-40, cosmic ray-produced radionuclides such as Beryl-lium-7, and fallout radionuclides such as Strontium 89 and Strontium 90 from nuclear weapons testing may be present in the feed samples.

Wildlife feed was collected at three locations (T-3 1, T-32 and T-198), and consisted of the edible portions of cattails. Samples were analyzed for gamma-emitting radionuclides. Naturally occur-ring Potassium-40 was detected in all samples. Beryllium-7 was detected at indicator location T-31 at 0.72 pCi/g (wet), and 0.27 pCi/g (wet) at the control location. All other radionuclides were below their respective LLDs. These samples indicate that the operation of Davis-Besse had no observable adverse effects on the surrounding environment.

47

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Table 9: Animal/Wildlife Feed Locations Sample Location Type of Number Location Location Description T-31 I

Davis-Besse Navarre Marsh T-32 C

Roving offsite location, 7.0 miles W of station in 2008 T-198 Toussaint Creek Wildlife Area, 4.0 miles WSW of the Station I = indicator C = control Wild Meat Samples Sampling of wild meat provides information on environmental radionuclide concentrations that humans may be exposed to through an ingestion pathway. The principle pathways for radionu-clide contamination of meat animals include deposition of airborne radioactivity in their food and drinking water and contamination of their drinking water from radionuclides released in liquid effluents.

The REMP generally collects wild meat on an annual basis. Wild animals commonly consumed by residents in the vicinity of Davis-Besse include waterfowl, deer, rabbits and muskrats. Analy-ses from these animals provide general information on radionuclide concentration in the food chain. When evaluating the results from analyses performed on meat animals, it is important to consider the age, diet and mobility of the animal before drawing conclusions from radionuclide concentrations in the local environment or in a species as a whole.

Meat samples were taken in 2008 as follows:

Wild Meat: Muskrat samples were collected on Station property in Navarre Marsh and at a control location west of Crane Creek. The samples showed only naturally-occurring activity.

48

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Table 10: Wild Meat Locations Sample Location Type of Number Location Location Description T-31 I

Onsite roving location T-210 C

Roving offsite location (7.0 mi. W of the Station in 2008)

I = indicator C = control Soil Samples Soil samples are generally collected once a year adjacent to our ten continuous air samplers.

Only the top layer of soil is sampled in an effort to identify possible trends in the local environ-mental nuclide concentration caused by atmospheric deposition of fallout and station-released radionuclides. Generally, the sites are relatively undisturbed, so that the sample will be represen-tative of the actual deposition in the area. Ideally, there should be little or no vegetation present, because the vegetation could affect the results of analyses. Approximately five pounds of soil are taken from the top two inches at each site. Many naturally occurring radionuclides such as Be-ryllium-7 (Be-7), Potassium-40 (K-40) and fallout radionuclides from nuclear weapons testing are detected. Fallout radionuclides that are often detected include Strontium-90 (Sr-90) and Ce-sium-137 (Cs-137).

Soil was collected at ten sites in 2008. The indicator locations included T-1, T-2, T-3, T-4, T-7, and T-8. The control locations were T-9, T-1 1, T-12, and T-27. All soil samples were analyzed for gamma-emitting radionuclides. The only gamma emitter detected (in addition to naturally occurring Be-7 and K-40) was Cs-137. Cs-137 was found in Indicator and Control locations at average concentrations of 0.13 pCi/g (dry) and 0.12 pCi/g (dry), respectively. The concentrations were similar to that observed in previous years (Figure 15).

49

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Cs-137 in Soil 1972-2008 1.15 1.1 1.05 1 -2 0.95-0,9.

0.85-0,8-0.75-0,7- -

E0.65--

0,6

.0.55-C" 0,5 0.45 0A -

0.35 0.3 0.25 A

0.2

/,

0.15

,i 0.1-0.05-N~ M

I LO) (0 I'-- M 0)tM C)~

CD M `4-0O CO r, M

~

M CD N

M'I O(r-MCD

) 0 M ":4, Lo W0 t-M M

N0 00 00 M N

N MD CD CD CD CD CD CD CD CD CD M) 0

))00)

0) 00 0

0 000 0

0

0)
0) 0) 0") 0") 0) 0") 0)
0) 0) 0") 0") 0) 0) 0M) 0) 0M) 0M) 0

)

M) 0

)

(

0)

) 0) 0 C) C) 0 00 Irdcator --- Ccntrd Figure 15: The concentration of Cesium-137 in soil has steadily declined in recent years. The peak seen in 1978 was due to fallout from nuclear weapons testing.

50

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Table 11: Soil Locations Sample Location Number T-1 T-2 T-3 T-4 T-7 Type of Location I

I I

I I

Location Description Site boundary, 0.6 miles ENE of Station Site boundary, 0.9 miles E of Station Site boundary 1.4 miles ESE of Station Site boundary 0.8 miles S of Station Sand Beach, main entrance, 0.9 miles NW of Station Moore Farm, 2.7 miles WSW of Station Oak Harbor Substation, 6.8 miles SW of Station Port Clinton Water Treatment Plant, 9.5 miles SE of Station Toledo Water Treatment Plant, 20.7 miles WNW of Station Crane Creek State Park, 5.3 miles WNW of Station T-8 T-9 T-11I T-12 I

C C

C C

T-27 I = indicator C = control 51

I DAVIS-BESSE NUCLEAR POWER STATION RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM TFRRFCTRIAI SAMPI FS.

cITF CD (tD U'

-I i'l)

CD 0

ID

DAVIS-BESSE NUCLEAR POWER STATION RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM TERRESTRIAL SAMPLES: 5 MILE RADIUS WNW

-n

'I CD LPJ (Dl

-LW

_tý!

I III INDICATOR STATIONS BROAD LEAF VEGETABLE 4 FRUIT 4

ANIMAL FEED.WILD il SOIL 6

GROUND WATER 14 bJ 0

c

<1![1 iz In

DAVIS-BESSE NUCLEAR POWER STATION RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM TERRESTRIAL SAMPLES: 5-25 MILE RADIUS OREGON (D

(, D CD Ui C0 Ci)

(A ch CD z

-u 0

CD 0

0

  • 0 ID 0

ESE lk..

ow CONTROL STATIONS 4PANIMAL FEEDWILD

& GROUND WATER

  • . MEAT.WILD

'M MILK SOIL DB0 04-02-09 DFN=Fs/SCHED/SKZ815.DGN

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Aquatic Monitoring Radionuclides may be present in Lake Erie from many sources including atmospheric deposition, run-off/soil erosion, and releases of radioactive material in liquid effluents from hospitals or nu-clear facilities. These sources provide two forms of potential exposure to radiation, external and internal. External exposure can occur from the surface of the water, shoreline sediments and from immersion (swimming) in the water. Internal exposure can occur from ingestion of ra-dionuclides, either directly from drinking water, or as a result of the transfer of radionuclides through the aquatic food chain with eventual consumption of aquatic organisms, such as fish. To monitor these pathways, Davis-Besse samples treated surface water (drinking water), untreated surface water (lake or river water), fish, and shoreline sediments.

Treated Surface Water Treated surface water is water from Lake Erie, which has been processed for human consump-tion. Radiochemical analysis of this processed water provides a direct basis for assessing the dose to humans from ingestion of drinking water.

Samples of treated surface water were collected from two indicators (T-22B and T-50) and two control locations (T-11 and T-12). These locations include the water treatment facilities for Car-roll Township, Erie Industrial Park, Port Clinton and Toledo. Samples were collected weekly and composited monthly. The monthly composites were analyzed for beta-emitting radionu-clides. The samples were also composited in a quarterly sample and analyzed for Strontium-89, Strontium-90, gamma-emitting radionuclides, and tritium. One QC sample was collected from a routine location, which was changed each month.

The annual average of beta-emitting radionuclides for indicator and control locations was 2.1 and 1.9 pCi/l, respectively. These results are similar to previous years shown in Figure 19. Tritium 55

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report was not detected above the LLD of 330 pCi/1 during 2008. Strontium-89 was not detected above the LLD of 1.1 pCi/1. Strontium-90 activity was not detected above its LLD of 0.6 pCi/1. These results are similar to those of previous years and indicate no adverse impact on the environment resulting from the operation of Davis-Besse during 2008.

Each month, weekly quality control samples were collected at different locations. The results of the analyses from the quality control samples were in agreement with the routine samples. The average concentration of beta-emitting radionuclides detected at the QC locations was 3.2 pCi/I.

Gross Beta in Treated Surface Water 1972-2008 5

4.5 4

3.5 3

2.5 2

1.5 1

0.5 N NN N

NN C

C COCOCO O

O C

C 0)0)0)

0)

M)0)

0) 00 0

0 0

0 0

0 0

I Indicator ----

controli Figure 19: Since 1974, the annual concentrations of beta emitting radionuclides in treated surface water samples col-lected from indicator locations have been consistent with those from control locations. Davis-Besse has had no measurable radiological impact on surface water used to make drinking water.

56

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Table 12: Treated Surface Water Locations Sample Location Type of Number Location Location Description T-11 C

Port Clinton Water Treatment Plant, 9.5 miles SE of Station T-12 C

Toledo Water Treatment Plant, 20.7 miles WNW of Station T-22B I

Carroll Township Water Treatment Plant, sampled at Davis-Besse REMP lab T-50 I

Erie Industrial Park, Port Clinton, 4.5 miles SE of Station T-143 QC Quality Control Site I = indicator C = control QC = quality control 57

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Untreated Surface Water Sampling and analysis of untreated surface water provides a method of assessing the dose to hu-mans from external exposure from the lake surface as well as from immersion in the water. It also provides information on the radionuclides present, which may affect drinking water, fish, and irrigated crops.

Routine Program The routine program is the basic sampling program that is performed year round. Untreated wa-ter samples are collected from water intakes used by nearby water treatment plants. Routine samples are collected at Port Clinton, Toledo, Carroll Township and Erie Industrial Park. A sample is also collected from Lake Erie at the mouth of the Toussaint River. These samples are collected weekly and composited monthly. The monthly composite is analyzed for beta-emitting radionuclides, tritium, and gamma-emitting radionuclides.

The samples are also composited quarterly and analyzed for Strontium-89 and Strontium-90.

A QC sample is also collected weekly, with the location changing each month.

58

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Sample Results For the routine untreated surface water samples that are composited weekly, the beta emitting radionuclides had an average concentration of 2.2 pCi/L at indicator locations during 2008. Con-trol locations averaged 1.9 pCi/L during this period.

Tritium was not detected at untreated surface water indicator or control sites above the LLD of 330 pCi/ L during 2008. The EPA drinking water limit for tritium is 20,000 pCi/l.

Each month, weekly composited quality control samples were analyzed from different locations.

The results of the analyses from the quality control samples were consistent with the routine samples, and averaged 1.8 pCi/L of beta emitting radionuclides.

Gross Beta Concentration in Untreated Surface Water 1977-2008 7

m) m) cD I

u) to C

r-

=)

C)

C) c

)

n 1'

Lo (o

C) m

) m

)

m m)

Lo w)

C

=

~~~-o m-w-

w) co m) m)

m) m) m) m) m)

C) m) m)

C

)

C

)

C

)

)

C C) c>

c

) C) C)

INDICATOR -

CONTROL Figure 20: The average concentration of beta-emitting radionuclides in untreated water was similar between control and indicator locations. This demonstrates that Davis-Besse had no significant radiological impact on the surround-ing environment.

59

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Table 13: Untreated Surface Water Locations Sample Location Type of Number Location Location Description T-3 I

Site boundary, 1.4 miles ESE of Station T-1 1 C

Port Clinton Water Treatment Plant, 9.5 miles SE of Station T-12 C

Toledo Water Treatment Plant, sample taken from intake crib, 12.6 miles NW of Station T-22A I

Carroll Township Water Plant, State Route 2, 2.1 miles NW of Station T-50 Erie Industrial Park, Port Clinton, 4.5 miles SE of Station T-145 QC Roving Quality Control Site I = indicator, C control 60

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Shoreline Sediment The sampling of shoreline sediments can provide an indication of the accumulation of insoluble radionuclides which could lead to internal exposure to humans through the ingestion of fish, through re-suspension into drinking water supplies, or as an external radiation source from shore-line exposure to fishermen and swimmers.

Samples of deposited sediments in water along the shore were collected at various times from three indicator sites (T-3, T-4, and T-132) and one control location (T-27), and were analyzed for gamma-emitting radionuclides. Naturally occurring Potassium-40 was d~tected at both control and indicator locations. These results are similar to previous years.

Table 14: Shoreline Sediment Locations Sample Location Number Type of Location Location Description T-3 T-4 T-27 T-132 I

I Site boundary, 1.4 miles ESE of Station Site boundary, 0.8 miles S of Station Crane Creek State Park, 5.3 miles WNW of Station Lake Erie, 1.0 miles E of Station C

I I = indicator C = control 61

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Fish Sample Fish are analyzed primarily to quantify the dietary radionuclide intake by humans, and secondar-ily to serve as indicators of radioactivity in the aquatic ecosystem. The principal nuclides that may be detected in fish include naturally occurring Potassium-40, as well as Cesium-137, and Strontium-90.

Depending upon the feeding habit of the species (e.g., bottom-feeder versus predator), results from sample analyses may vary.

Davis-Besse routinely collects three species of fish once per year from sampling locations near the Station's liquid discharge point and more than ten miles away from the Station where fish populations would not be expected to be impacted by the Station operation. Walleye are col-lected because of being a popular sport fish and white perch or white bass are collected because their importance as a commercial fish. Carp are collected because they are bottom feeders where contaminants may settle.

The average concentration of beta-emitting radionuclides in fish was similar for indicator and control locations (4.12 pCi/g and 4.10 pCi/g wet weight, respectively). No other gamma emitters were detected above their respective LLDs.

Gross Beta in Fish 1972-2008 E

e0 10 00 N-00 Ir 0

CON.Q

1.

00 CV

,0 CE-C C'J

§ 2 9 1.

N----NNN C0 0

C CC Year Figure 21: Average concentrations of beta-emitting radionuclides in fish samples were similar at indicator and con-trol locations, and were within the range of results of previous years.

62

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Table 15: Fish Locations Sample Location Type of Number Location Location Description T-33 I

Lake Erie, within 5 miles radius of Station T-35 C

Lake Erie, greater than 10 mile radius of Station I = indicator C= control 63

DAVIS-BESSE NUCLEAR POWER STATION RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM AQUATIC SAMPLES: SITE NW NNW N,

I LIn CD If BLDG.CD T,

0 W

S` TMD r\\)

o I

N' A" APFA INSPECTI 3

,ET I'.

N n

W S W I r 0

INDICATORNSTATIONS I to CD J

D (N) j 0

SRACE WAE TRAE SURAC FAATLET UNRETE D

n+

CC

-TT

-3 0

"0 t

&sm ii SHOELIN SEIMENS sITj

,F

  • SURFCE WTER REATD I

1

,*0 S

I W'N.

Ij SURFCE ATERUNTEATE

,,3 I

-C-SSW4

________SE____"_____-__

I t

\\

CD

/I s

-D0

-4 t

-4 0

DAVIS-BESSE NUCLEAR POWER STATION RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM AQUATIC SAMPLES: 5 MILE RADIUS WNW o

CD (D

CD a:

z CD

<r 0

0 0

ý

_u 0

OD*,

°",

"+S' RD.

WS 4---..______

4 To S,

c ° "USAN RC "I?

PnPFR CD 0

WS

-"5ý cre SW*,-

i 4,;

0 cr t.

CC CD 00 0

.1 0.

.7i II i R.t

_S S ALEM 8

J_,,

.IRLlI RDs.

D 0

.GNZ.N.

SU 1 AE 0

0 54I A O ST T O STwV i0a..

i CD RD. __

0 I

0 FIS m0 u

w mI-SURROLL RD.E TREATE

-S

-S V

SURFACE WATER UNTREATED DB. 04-20-09 OFN-F l/SCHED/SICZB1G.DGN DB. 04-20-09 DFN-F,/SCHED/SKZBl6.DGN

DAVIS-BESSE NUCLEAR POWER STATION RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM AQUATIC SAMPLES: 5-25 MILE RADIUS H i~.G A.N~

OREGON

  • ~

An)

T-137 0

  • tJJ i-a J~.

.~.-

Jo 0

(IC (AC

,51 D

0 0

u 0

0 0

No 0

-1

'OR STATIONS F FISH SHORELINE SEDIMENTS SURFACE WATER TREATED i

SURFACE WATER UNTREATED

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Direct Radiation Monitoring Thermoluminescent Dosimeters Radionuclides present in the air and deposited on the ground may directly irradiate individuals.

Direct radiation levels at and around Davis-Besse are constantly monitored by thermo-luminescent dosimeters (TLDs). TLDs are small devices which store radiation dose information.

The TLDs used at Davis-Besse contain a Sulfate:Dysprosium (CaSO 4:Dy) card with four main readout areas. Multiple readout areas are used to ensure the precision of the measurements.

Thermoluminescence is a process in which ionizing radiation interacts with phosphor, which is the sensitive material in the TLD. Energy is trapped in the TLD material and can be stored for several months or years. This provides an excellent method to measure the dose received over long periods of time. The energy that was stored in the TLD as a result of interaction with radia-tion is released and measured by a controlled heating process in a calibrated reading system. As the TLD is heated, the phosphor releases the stored energy in the form of light. The amount of light detected is directly proportional to the amount of radiation to which the TLD was exposed.

The reading process re-zeroes the TLD and prepares it for reuse.

TLD Collection Davis-Besse has 88 TLD locations (77 indicator and 11 control locations). TLDs are collected and replaced on a quarterly and annual basis. Nineteen QC TLDs are also collected on this schedule. There are a total of 214 TLDs in the environment surrounding Davis-Besse. By col-lecting them on a quarterly and annual basis from a single site, each measurement serves as a quality control check on the other. All quarterly and annual TLDs placed in the field were re-trieved and evaluated during the current reporting period.

In 2008, the average dose equivalent for quarterly TLDs at indicator locations was 16.5 mrem/91 days, and for control locations was 17.5 mrem/91 days. The average dose equiva-lent for annual TLDs in 2008 was 59.4 mremi/365 days at indicator locations and 65.8 mrem/365 days for control locations.

Quality Control TLDs Duplicate TLDs have been placed at 18 sites. These TLDs are placed in the field at the same time and location as some of the routine TLDs, but are assigned quality control site numbers.

This allows us to take several measurements at the location without the laboratory being aware that they are the same. A comparison of the quality control and routine results provides a method to check the accuracy of the measurements. The average dose equivalent of indicator quality control TLDs averaged 14.5 mrem/91 days while the quality control TLDs at control locations yielded an average dose equivalent of 16.6 mrem/91 days.

67

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Direct Radiation Monitoring Gamma Dose for Environmental TLDs 1973-2008 24.-

22 20 49 18-

-- 16 E

14-12 V

10 ID(

(D

ý0 (0

(0 0

(0 (D F

(

R 0

'D

'D

§ S

8 0(S0(0 L

M 4

(0(

M0 W0 T0 (00

~

~

(

4 (0

N).

-4 u

4 indicator -i-control Figure 25: The similarity between indicator and control results demonstrates that the operation of Davis-Besse has not caused any abnormal gamma dose.

68

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Table Sample Location Number T-1 T-2 T-3 T-4 T-5 T-6 T-7 T-8 T-9 16: Thermoluminescent Dosimeter Locations Type of Location Location Description I

Site boundary, 0.6 miles ENE of Stati I

Site boundary, 0.9 miles E of Station I

Site boundary, 1.4 miles ESE of Static I

Site boundary, 0.8 miles S of Station I

Site boundary, 0.5 miles W of Station I

Site boundary, 0.5 miles NNE of Stati I

Sand Beach entrance, 0.9 miles NW o I

Earl Moore Farm, 2.7 miles WSW of C

Oak Harbor Substation, 6.8 miles SW on

)n on f Statiom Station of Station T-10 T-11 T-12 T-24 T-27 T-38 T-39 T-40 T-41 T-42 I

C C

C C

Site boundary, 0.5 miles SSW of Station near warehouse Port Clinton Water Treatment Plant, 9.5 miles SE of Station Toledo Water Treatment Plant, 20.7 miles WNW of Station Sandusky, 21.0 miles SE of Station Crane Creek State Park, 5.3 miles WNW of Station Site boundary, 0.6 miles ENE of Station Site boundary 1.2 miles ENE of Station Site boundary, 0.7 miles SE of Station Site boundary, 0.6 miles SSE of Station Site boundary, 0.8 miles SW of Station I

I I

I I

69

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Table 16: Thermoluminescent Dosimeter Locations (continued)

Sample Location Number T-43 T-44 T-45 T-46 T-47 T-48 T-49 T-50 Type of Location I

I I

I I

I I

I T-51 T-52 T-53 T-54 T-55 T-60 T-62 T-65 T-66 T-67 T-68 T-69 Location Description Site boundary, 0.5 miles SW of Station Site boundary, 0.5 miles WSW of Station Site boundary, 0.5 miles WNW of Station Site boundary, 0.5 miles NW of Station Site boundary, 0.5 miles N of Station Site boundary, 0.5 miles NE of Station Site boundary, 0.5 miles NE of Station Erie Industrial Park, Port Clinton, 4.5 miles SE of Station on Siren Pole, 5.5 miles SSE of Station Miller Farm, 3.7 miles S of Station Nixon Farm, 4.5 miles S of Station McNutt residence, 4.8 miles SW of Station King Farm, 4.5 miles W of Station Site boundary, 0.3 miles S of Station Site boundary, 1.0 mile SE of Station Site boundary, 0.3 miles E of Station Site boundary, 0.3 miles ENE of Station Site boundary, 0.3 miles NNW of Station Site boundary, 0.5 miles WNW of Station Site boundary, 0.4 miles W of Station 70

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Table 16: Thermoluminescent Dosimeter Locations (continued)

Sample Location Type of Number Location Location Description T-71 I

Site boundary, 0.1 mile NNW of Station T-73 I

Site boundary, 0.1 mile WSW of Station T-74 I

Site boundary, 0.1 mile SSW of Station T-75 I

Site boundary, 0.2 mile SSE of Station T-76 I

Site boundary, 0.1 mile SE of Station T-80 QC Quality Control Site T-81 QC Quality Control Site T-82 QC Quality Control Site T-83 QC Quality Control Site T-84 QC Quality Control Site T-85 QC Quality Control Site T-86 QC Quality Control Site T-88 QC Quality Control Site T-87 QC Quality Control in lead pig DBAB Annex T-89 QC Quality Control Site T-90 I

Site Personnel Processing Facility T-91 T-92 T-93 T-94 T-95 I

I I

State Route 2 and Rankie Road, 2.5 miles SSE Locust Point Road, 2.7 miles WNW of Station Twelfth Street, Sand Beach, 0.6 miles NNE of Station State Route 2, 1.8 miles WNW of Station State Route 579, 9.3 miles W of Station C

71

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Table 16: Thermoluminescent Dosimeter Locations (continued)

Sample Location Number T-1O0 Type of Location C

T-1ll T-112 T-113 T-1 14 T-115 T-1 16 T-117 T-118 T-119 T-120 T-121 T-122 T-123 T-124 T-125 T-126 T-127 C

I QC QC QC QC QC QC QC QC i

i Location Description Ottawa County Highway Garage, Oak Harbor, 6.0 miles S of Station Toussaint North Road, 8.3 miles WSW of Station Thompson Road, 1.5 miles SSW of Station Quality Control Site Quality Control Site Quality Control Site Quality Control Site Quality Control Site Quality Control Site Quality Control Site Quality Control Site State Route 19, 2.0 miles W of Station Duff Washa and Humphrey Road, 1.7 miles W of Station Zetzer Road, 1.6 miles WSW of Station Church and Walnut Street, Oak Harbor, 6.5 miles SSW of Station Behlman and Bier Roads, 4.4 miles SSW of Station Camp Perry Western and Toussaint South Road, 3.7 miles S of Station Camp Perry Western and Rymers Road, 4.0 miles SSE of Station I

C I

I 72

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Table 16: Thermoluminescent Dosimeter Locations (continued)

Sample Location Type of Number Location T-128 I

T-142 T-150 T-151 T-153 T-154 T-155 I

I I

I C

Location Description Erie Industrial Park, Port Clinton Road, 4.0 miles SE of Station Site Boundary, 0.8 miles SSE of Station Humphrey and Hollywood Roads, 2.1 miles NW of Station State Route 2 and Humphrey Road, 1.8 miles WNW of Station Leutz Road, 1.4 miles SSW of Station State Route 2, 0.7 miles SW of Station Fourth and Madison Streets, Port Clinton, 9.5 miles SE of Station Quality Control Site Sand Beach, 1.1 miles NNW of Station Sand Beach, 0.8 miles NNW of Station Sand Beach, 0.7 miles N of Station Sand Beach, 0.7 miles N of Station Sand Beach, 0.5 miles NNE of Station Site Boundary, 0.6 miles NW of Station Site Boundary, 0.5 miles N of Station Site Boundary, 0.5 miles NNE of Station.

T-200 T-201 T-202 T-203 T-204 T-205 T-206 T-207 T-208 I = Indicator C = Control QC.- Quality Control QC I

I I

I I

I I

I 73

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Table 16: Thermoluminescent Dosimeter Locations (continued)

Sample Location Type of Number Location Location Description T-211 I

Site boundary, 0.79 miles E of Station T-212 I

Site boundary, 1.2 miles ESE of Station T-213 I

Site boundary, 0.6 miles SSW of Station T-214 I

Site boundary, 0.7 miles SW of Station T-215 I

Site boundary, 0.5 miles W of Station T-216 I

Site boundary, 0.7 miles NW of station T-217 I

Salem-Carroll Rd., 4.7 miles SSW of Station T-218 I

Toussaint East Rd., 4.0 miles WSW of Station T-219 I

Toussaint Portage Rd., 4.8 miles WSW of Station T-220 I

Duff-Washa Rd., 4.8 miles W of Station T-221 C

Magee Marsh, 5.1 miles WNW of Station T-222 I

Turtle Creek Access, 3.7 miles WNW of Station T-223 I

Lawrence Rd., 5.0 miles SE of Station T-224 I

Erie Industrial Park, 4.4 miles SE of Station 74

DAVIS-BESSE NUCLEAR POWER STATION RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM TLD SAMPLES: SITE NW NNW N

Nt T

ti I

I I

tt I

t WNW I

S I

S I

~I I

ENE T-38 COLLECTION BOX DISCHARGE PIPE

-7 C

71 (S

NT E

-65 STRU."TRE T-N T-2 I

ci (AJ (I

0 F--- -

I I

ESE 0N T -21; I

INDICATOR STATIONS

,e

-1 I

I (fr THERMOLUMINESCENT DOSIMETER (TLD)

I I I

I I

SW SE SSE 1

ODT-142 I

/

I

DAVIS-BESSE NUCLEAR POWER STATION RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM TLD SAMPLES: 5 MILE RADIUS WNW T-!21CD-*

T -82

Oro, T -5511M ir T 8 11

.1 T-92>

IJdHd, T-20l T -2W~

U)

U) a:

C7 (D

T N)

Or-J

-J -

"0 W

WSW 1

Li 0r JO wl~j T-122 RD. fb

-154' dl 4 ~

4

  • z'II~~~ * ~

4 ~

P ml AL (j0T-8

'-U, -

r,

  • m m

Ad a:k m

r w

T-112 L

I -

U I L..

  1. USSý IL STRICKLE-OUbf A NTI 0uho I

T I

ItoII~

II~i II a:

RFr.

FAST I

_____z______.

II T -21801 3>T-219

Creek, r

r.;.j FICK RDQ ir I

0a:

rT.1 2T9

'7-01 UENZMAN

-RU.

CAMP PERRY-j

..T -5(

-223 O)T -52 T -2; WESTERN RD CAMP PEARY-

..CD T -52 4-

<E ion a:

0 II SW-F RTFR Rfl.

0CT-126 o_

=-

  • __....___"__,"L

_" itI___

r z

CARROLL II on T-717

D 0

II a:.

.0~

0a:

fNI LV

,t j LJ,

or a:

c1 CL SAE-CARL RD

-2 T

1r

-53 m.-

0

.L LJ~

~ ~

I II lI INDICATOR STATIONS THERMOLUMI NESCENT DOSIMETER (TLD)

II z

-jmw 01 a:

01.

4i Z

U) 0F-I-

0x:

a:

0a:

a:

u 21

"'Lu 9ý

-tLTC IE RD

~1I

'-IIII wit k9

__--+-

SSW e-I I-SE

~U jJ ISE DB.i 04m20-09 0F'N-Fs /SCHED/SKLlfiUGN

DAVIS-BESSE NUCLEAR POWER STATION RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM TLD SAMPLES: 5-25 MILE RADIUS HI A-N OREGON C

0 N,)

T -95

'Ii 5

S LO Q

z C

9 0

57

-u 0

0 D o

0 C

0 0

0 D

]

0

I-D 0

f-02

-4

I J

0 0

7 ESE INDICATOR STATIONS (DTHERMOLUM INIESCENT DOSIMETER (TLO)

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Conclusion The Radiological Environmental Monitoring Program at Davis-Besse is conducted to determine the radiological impact of the Station's operation on the environment. Radionuclide concentra-tions measured at indicator locations were compared with concentrations measured at control lo-cations in previous operational studies and in the pre-operational surveillance program. These comparisons indicate normal concentrations of radioactivity in all environmental samples col-lected in 2008. Davis-Besse's operation in 2008 indicated no observable adverse radiological impact on the residents and environment surrounding the station. The results of the sample analyses performed during the period of January through December 2008 are summarized in Ap-pendix D of this report.

References

1. "Cesium-137 from the Environment to Man: Metabolism and Dose," Report No. 52, National Council on Radiation Protection and Measurement, Washington, D.C. (January 1977).
2. "Enviromnental Radiation Measurements," Report No. 50, National Council on Radiation Protection and Measurement, Washington, D.C. (December 1976).
3. "Exposure of the Population in the United States and Canada from Natural Background Ra-diation," Report No. 94, National Council on Radiation Protection and Measurement, Wash-ington, D.C. (December 1987).
4. "A Guide for Environmental Radiological Surveillance at U.S. Department of Energy Instal-lations," DOE/EP-0023, Department of Energy, Washington, D.C. (July 1981).
5. "Ionizing Radiation Exposure of the Population of the United States," Report No. 93, Na-tional Council on Radiation Protection and Measurement, Washington, D.C. (September 1987).
6. "Natural Background Radiation in the United States," Report No. 45, National Council on Radiation Protection and Measurement, Washington, D.C. (November 1975).
7. "Numerical Guides for Design Objectives and Limiting Conditions for Operation to meet the Criterion 'As Low As Reasonably Achievable' for Radioactive Material in Light Water Cooled Nuclear Power Reactor Effluents," Code of Federal Regulations, Title 10 Energy, Part 50 "Domestic Licensing of Production and Utilization Facilities," Appendix I (1988).
8. "Performance, Testing and Procedural Specifications for Thennoluminescent Dosimetry,"

American National Standards Institute, Inc., ANSI-N45-1975, New York, New York (1975).

9. "Public Radiation Exposure from Nuclear Power Generation in the United States," Report No. 92, National Council on Radiation Protection and Measurement, Washington, D.C. (De-cember 1987).

78

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report

10. "Radiological Assessment: Predicting the Transport, Bioaccumulation and Uptake by Man of Radionuclides Released to the Environment," Report No. 76, National Council on Radiation Protection and Measurement, Washington, D.C. (March 1984).
11. Regulatory Guide 4.1, "Programs for Monitoring Radioactivity in the Environs of Nuclear Power Plants," US NRC (April 1975).
12. Regulatory Guide 4.13, "Performance, Testing, and Procedural Specifications for Thermolu-minescent Dosimetry: Environmental Applications," US NRC (July 1977).
13. Regulatory Guide 4.15, "Quality Assurance for Radiological Monitoring Programs (Normal Operations) - Effluent Streams and the Environment," US NRC (February 1979).
14. Regulatory Guide 0475, "Radiological Environmental Monitoring by NRC Licensees for Routine Operations of Nuclear Facilities," US NRC (September 1978).
15. "Standards for Protection Against Radiation," Code of Federal Regulations, Title 10, Energy, Part 20 (1993).
16. Teledyne Isotopes Midwest Laboratory, "Operational Radiological Monitoring for the Davis-Besse Nuclear Power Station Unit No. 1, Oak Harbor, OH," Annual Report, Parts I and II (1977 through 1990).
17. Teledyne Isotopes Midwest Laboratory, "Final Monthly Progress Report to Toledo Edison Company", (199 1-1999).
18. Environmental, Inc. Midwest Laboratory, "Final Report to FirstEnergy Corporation", (2000-2008)
19. Teledyne Isotopes Midwest Laboratory, "Pre-operational Environmental Radiological Moni-toring for the Davis-Besse Power Station Unit No. 1", Oak Harbor, OH (1972-1977).
20. Toledo Edison Company, "Davis-Besse: Nuclear Energy for Northern Ohio."
21. Toledo Edison Company, Davis-Besse Nuclear Power Station, Unit No. 1, Radiological Ef-fluent Technical Specifications", Volume 1, Appendix A to License No. NPF-3.
22. Toledo Edison Company, "Final Environmental Statement -Related to the Construction of Davis-Besse Nuclear Power Station," Docket #50-346 (1987).
23. Toledo Edison Company, "Performance Specifications for Radiological Environmental Monitoring Program," S-72N.
24. Davis-Besse Nuclear Power Station, "Radiological Environmental Monitoring Program,"

DB-CN-00015.

79

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report

25. Davis-Besse Nuclear Power Station, "Radiological Environmental Monitoring Quarterly, Semiannual, and Annual Sampling", DB-CN-03004.
26. Davis-Besse Nuclear Power Station, "Radiological Monitoring Weekly, Semimonthly, and Monthly Sampling," DB-CN-03005.
27. Davis-Besse Nuclear Power Station, "REMP Enhancement Sampling", DB-CN-10101.
28. Toledo Edison Company, "Updated Safety Analysis for the Offsite Radiological Monitoring Program", USAR 11.6, Revision 14, (1992).
29. Davis-Besse Nuclear Power Station, "Annual Radiological Environmental Operating Report Preparation and Submittal", DB-CN-00014.
30. Davis-Besse Nuclear Power Station, "Preparation of Radioactive Effluent Release Report",

DB-CN-00012.

31. Davis-Besse Nuclear Power Station, "Offsite Dose Calculation Manual".
32. "Tritium in the Environment", Report No. 62, National Council on Radiation Protection and Measurements, Washington, D.C. (March 1979).
33. NEI07-07, "Industry Ground Water Protection Initiative - Final Guidance Document",

August, 2007.

34. "Groundwater Monitoring Well Installation & Monitoring Report Davis-Besse Nuclear Power Station Oak Harbor, Ohio", Environmental Resources Management, March 18, 2008.

80

.4-

.-,p ~

Radioactive Effluent Release Report

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Radioactive Effluent Release Report January 1 through December 31, 2008 Protection Standards Soon after the discovery of x-rays in 1895 by Wilhelm Roentgen, the potential hazards of ioniz-ing radiation were recognized and efforts were made to establish radiation protection standards.

The primary source of recommendations for radiation protection standards within the United States is the National Council on Radiation Protection and Measurement (NCRP). Many of these recommendations have been given legislative authority by being published in the Code of Federal Regulations by the Nuclear Regulatory Commission.

The main objective in the control of radiation is to ensure that any dose is kept not only within regulatory limits, but kept as low as reasonably achievable (ALARA). The ALARA principle applies to reducing radiation dose both to the individual working at Davis-Besse and to the gen-eral public. "Reasonably achievable" means that exposure reduction is based on sound economic decisions and operating practices. By practicing ALARA, Davis-Besse minimizes health risk and environmental detriment and ensures that doses are maintained well below regulatory limits.

Sources of Radioactivity Released During the normal operation of a nuclear power station, most of the fission products are retained within the fuel and fuel cladding. However, small amounts of radioactive fission products and trace amounts of the component and structure surfaces, which have been activated, are present in the primary coolant water. The three types of radioactive material released are noble gases, Io-dine and particulates, and tritium.

The noble gas fission products in the primary coolant are given off as a gas when the coolant is depressurized. These gases are then collected by a system designed for gas collection and stored for radioactive decay prior to release.

Small releases of radioactivity in liquids may occur from valves, piping or equipment associated with the primary coolant system. These liquids are collected through a series of floor and equipment drains and sumps. All liquids of this nature are monitored and processed, if neces-sary, prior to release.

Noble Gas Some of the fission products released in airborne effluents are radioactive isotopes of noble gases, such as Xenon (Xe) and Krypton (Kr). Noble gases are biologically and chemically inert.

They do not concentrate in humans or other organisms. They contribute to human radiation dose by being an external source of radiation exposure to the body. Xe-133 and Xe-135, with half-lives of approximately five days and nine hours, respectively, are the major radioactive noble gases released. They are readily dispersed in the atmosphere.

81

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Iodine and Particulates Annual releases of radioisotopes of Iodine, and those particulates with half-lives greater than 8 days, in gaseous and liquid effluents are small. Factors such as their high chemical reactivity and solubility in water, combined with the high efficiency of gaseous and liquid processing sys-tems, minimize their discharge. The predominant radioiodine released is Iodine-i131 with a half-life of approximately eight days. The main contribution of radioactive Iodine to human dose is to the thyroid gland, where the body concentrates Iodine.

The principal radioactive particulates released are fission products (e.g., Cesium-134 and Ce-sium-137) and activation products (e.g., Cobalt-58 and Cobalt-60). Radioactive Cesium and Co-balt contribute to internal radiation exposure of tissues such as muscle, liver, and the intestines.

These particulates are also a source of external radiation exposure if deposited on the ground.

Tritium Tritium, a radioactive isotope of Hydrogen, is the predominant radionuclide in liquid effluents. It is also present in gaseous effluents. Tritium is produced in the reactor coolant as a result of neu-tron interaction with deuterium (also a Hydrogen isotope) present in the water and with the Bo-ron in the primary coolant. When tritium, in the form of water or water vapor, is ingested or in-haled it is dispersed throughout the body until eliminated.

Processing and Monitoring Effluents are strictly controlled to ensure radioactivity released to the environment is minimal and does not exceed regulatory limits. Effluent control includes the operation of monitoring sys-tems, in-plant and environmental sampling and analysis programs, quality assurance programs for effluent and environmental programs, and procedures covering all aspects of effluent and en-vironmental monitoring.

The radioactive waste treatment systems at Davis-Besse are designed to collect and process the liquid and gaseous wastes that contain radioactivity. For example, the Waste Gas Decay Tanks allow radioactivity in gases to decay prior to release via the Station Vent.

Radioactivity monitoring systems are used to ensure that all releases are below regulatory limits.

These instruments provide a continuous indication of the radioactivity present. Each instrument is equipped with alarms and indicators in the control room. The alarm setpoints are low enough to ensure the limits will not be exceeded. If a monitor alarms, a release from a tank is automati-cally stopped.

All wastes are sampled prior to release and analyzed to identify the specific concentrations of ra-dionuclides. Sampling and analysis provides a more sensitive and precise method of determining effluent composition than can be accomplished with monitoring instruments.

A meteorological tower is located in the southwest sector of the Station which is linked to com-puters that record its data. Coupled with the effluent release data, the meteorological data are used to calculate the dose to the public.

82

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Beyond the plant, devices maintained in conjunction with the Radiological Environmental Moni-toring Program continuously sample the air in the surrounding environment. Frequent samples of other environmental media, such as water and vegetation, are taken to determine if buildup of deposited radioactive material has occurred in the area.

Exposure Pathways Radiological exposure pathways define the methods by which people may become exposed to ra-dioactive material. The major pathways of concern are those which could cause the highest cal-culated radiation dose. These projected pathways are determined from the type and amount of radioactive material released, the environmental transport mechanism, and the use of the envi-ronment. The environmental transport mechanism includes consideration of physical factors, such as the hydrological (water) and meteorological (weather) characteristics of the area. An an-nual average of the water flow, wind speed, and wind direction are used to evaluate how the ra-dionuclides will be distributed in an area for gaseous or liquid releases. An important factor in evaluating the exposure pathways is the use of the envirornent. Many factors are considered such as dietary intake of residents, recreational use of the area, and the locations of homes and farms in the area.

The external and internal exposure pathways considered are shown in Figure 29. The release of radioactive gaseous effluents involves pathways such as external whole body exposure, deposi-tion of radioactive material on plants, deposition on soil, inhalation by animals destined for hu-man consumption, and inhalation by humans. The release of radioactive material in liquid efflu-ents involves pathways such as drinking water, fish consumption, and direct exposure from the lake at the shoreline while swimming.

83

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Figure 29: The exposure pathways shown here are monitored through the Radiological Environmental Monitoring Program (REMP) and are considered when calculating doses to the public.

Although radionuclides can reach. humans by many different pathways, some result in more dose than others. The critical pathway is the exposure route that will provide, for a specific radionu-clide, the greatest dose to a population, or to a specific group of the population called the critical group. The critical group may vary depending on the radionuclides involved, the age and diet of the group, or other cultural factors. The dose may be delivered to the whole body or to a specific organ. The organ receiving the greatest fraction of the dose is called the critical organ.

Dose Assessment Dose is the energy deposited by radiation in an exposed individual. Whole body exposure to ra-diation involves the exposure of all organs. Most background exposures are of this form. Both radioactive and non-radioactive elements can enter the body through inhalation or ingestion.

When they do, they are usually not evenly distributed. For example, Iodine concentrates in the thyroid gland, Cesium collects in muscle and liver tissue, and Strontium collects in the bone.

The total dose to organs from a given radionuclide depends on the amount of radioactive material present in the organ and the length of time that the radionuclide remains there. Some radionu-clides remain for short times due to their rapid radioactive decay and/or elimination rate from the body. Other radionuclides may remain in the body for longer periods of time.

84

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report The dose to the general public in the area surrounding Davis-Besse is calculated for each liquid or gaseous release. The dose\\due to radioactive material released in gaseous effluents is calcu-lated using factors such as the amount of radioactive material released, the concentration beyond the site boundary, the average weather conditions at the time of the release, the locations of expo-sure pathways (cow milk, goat milk, vegetable gardens and residences), and usage factors (inha-lation, food consumption). The dose due to radioactive material released in liquid effluents is calculated by using factors such as the total volume of the liquid released, the total volume of di-lution water (near field dilution), and usage factors, such as water and fish consumption, and shoreline and swimming factors. These calculations produce a conservative estimation of the dose.

Results The Radioactive Effluent Release Report is a detailed listing of radioactivity released from the Davis-Besse Nuclear Power Station during the period from January 1 through December 31, 2008.

Summation of the quantities of radioactive material released in gaseous and liquid efflu-ents (Tables 17-23)

" Summation of the quantities of radioactive material contained in solid waste packaged and shipped for offsite disposal at federally approved sites (Table 24)

" A listing of all radioactive effluent monitoring instrumentation required by the Offsite Dose Calculation Manual, but which were inoperable for more than 30 days A listing of all radioactive effluent monitoring instrumentation required by the Offsite Dose Calculation Manual, but which were inoperable for more than 30 days During this reporting period, the estimated maximum individual offsite dose due to radioactivity released in effluent was:

Liquid Effluents:

" 2.60E-03 mrem, maximum individual whole body

  • 3.42E-03 mrem, maximum significant organ dose (liver)

Gaseous Effluents:

Noble Gas:

  • 4.30E-04 mrem, whole body
  • 1.48E-03 mrem, skin Iodine - 131, Tritium, and Particulates with Half-lives greater than 8 Days:
  • 1.93E-03 mrem, whole body dose

" 2.21E-03 mrem, significant organ dose (thyroid)

These doses are a small fraction of the limits set by the NRC in the Davis-Besse ODCM.

85

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Additional normal release pathways from the secondary system exist. For gaseous effluents, these pathways include the Auxiliary Feed Pump Turbines exhaust, the main steam safety valve system and the atmospheric vent valve system, steam packing exhaust and main feed water. For liquid effluents, the additional pathways include the Turbine Building drains via the settling ba-sins. Releases via these pathways are included in the normal release tables in this report.

Regulatory Limits Gaseous Effluents In accordance with Offsite Dose Calculation Manual, dose rates due to radioactivity released in gaseous effluents from the site to areas at and beyond the site boundary shall be limited to the following:

Noble gases:

" Released at a rate equal to or less than 500 mrem TEDE per year.

  • Released at a rate such that the total dose to the skin will be less than or equal to 3000 mrem in a year.

Iodine-131, tritium, and all radionuclides in particulate form with half-lives greater than 8 days:

  • Released at a rate such that the total dose to any organ will be less than or equal to 1500 mrem in a year.

In accordance with 1 OCFR50, Appendix I, Sec. IIB. 1, air dose due to radioactivity released in gaseous effluents to areas at and beyond the site boundary shall be limited to the following:

e Less than or equal to 10 mrad total for gamma radiation and less than or equal to 20 mrad total for beta radiation in any calendar year.

In accordance with 10CFR50, Appendix I, Sec. IIC, dose to a member of the public from Iodine-131, tritium, and all radionuclides in particulate form with half-lives greater than 8 days in gase-ous effluents released to areas at and beyond the site boundary shall be limited to the following:

0 Less than or equal to 15 total mrem to any organ in any calendar year.

Liquid Effluents In accordance with 1 OCFR50, Appendix I, Sec IIA, the dose or dose commitment to a member of the public from radioactivity in liquid effluents released to unrestricted areas shall be limited to accumulated doses of:

  • Less than or equal to 3 mrem to the total body and less than or equal to 10 mrem to any organ in any calendar year.

86

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Effluent Concentration Limits The Effluent Concentration Limits (ECs) for gaseous and liquid effluents at and beyond the site boundary are listed in 1 0CFR20, Appendix B, Table II, Columns 1 and 2, with the most restric-tive EC being used in all cases. For dissolved and entrained gases in liquids, the EC of 2.OE-04 uCi/ml is applied. This EC is based on the Xe-135 DAC of 1E-05 uCi/ml of air (submersion dose) converted to an equivalent concentration in water as discussed in the International Com-mission on Radiological Protection (ICRP), Publication 2.

Average Energy The Davis-Besse ODCM limits the dose equivalent rates due to the release of fission and activa-tion products to less than or equal to 500 mrem per year to the total body and less than or equal to 3000 mrem per year to the skin. Therefore, the average beta and gamma energies (E) for gaseous effluents as described in Regulatory Guide 1.21, "Measuring, Evaluating, and Reporting Radio-activity in Solid Wastes and Releases of Radioactive Materials in Liquid and Gaseous Effluents from Light-Water-Cooled Nuclear Power Plants" are not applicable.

Measurements of Total Activity Fission and Activation Gases:

These gases, excluding tritium, are collected in Marinelli beakers specially modified for gas sampling, in steel flasks, or in glass vials, and are counted on a Germanium detector for principal gamma emitters. Radionuclides detected are quantified via gamma spectroscopy.

Tritium gas is collected using a bubbler apparatus and counted by liquid scintillation.

Iodine Iodine is collected on a charcoal cartridge filter and counted on a germanium detector. Specific quantification of each iodine radionuclide is performed using gamma spectroscopy.

Particulates Particulates are collected on filter paper and counted on a Germanium detector. Specific quanti-fication of each radionuclide present on the filter paper is performed by using gamma spectros-copy.

Liquid Effluents Liquid effluents are collected in a Marinelli beaker and counted on a germanium detector. Quan-tification of each gamma-emitting radionuclide present in liquid samples is via gamma spectros-copy. Tritium in the liquid effluent is quantified by counting an aliquot of a composite sample in a liquid scintillation counting system.

87

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Batch Releases Liquid from 1/1/08 through 12/31/08

1. Number of batch releases:
2. Total time period for the batch releases:
3. Maximum time period for a batch release:
4. Minimum time period for a batch release:
5. Average time period for a batch release:

Gaseous from 1/1/08 through 12/31/08

1. Number of batch releases:
2. Total time period for the batch releases:
3. Maximum time period for a batch release:
4. Minimum time period for a batch release:
5. Average time period for batch release:

58 107.5 hours5.787037e-5 days <br />0.00139 hours <br />8.267196e-6 weeks <br />1.9025e-6 months <br /> 226 minutes 80 minutes 111 minutes 6

51.2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> 1,718 minutes 118 minutes 512 minutes Abnormal Releases One abnormal gaseous release occurred during plant startup on March 7>'when high pressure feed water heater relief valves lifted. The steam released contained 1.08 E-03 curies of Tritium and had a calculated whole body dose of 1.44E-07 millirem, which is well within regulatory limits.

There were no liquid abnormal releases of radioactivity during 2008.

Percent of ODCM Release Limits The following table presents the ODCM annual dose limits and the associated offsite dose to the public, in percent of limits, for January 1,2008 through December 31, 2008.

PERCENT OF SPECIFICATION ANNUAL DOSE LIMIT LIMIT Report Period: January 1, 2008-December 31, 2008 (gaseous)

Noble gases (gamma) 4.73E-04 mrad 10 mrad 4.73E-03 Noble gases (beta)

1. 1i6E-03 mrad 20 mrad 5.80E-03 1-13 1, tritium and particulates 1.93E-03 mrem 15 mrem 1.29E-02 Report Period: January 1, 2008 - December 31, 2008 (liquid)

I Total body 2.60E-03 mrem 3 mrem 8.67E-02 Organ 3.42E-03 mrem 10 mrem 3.42E-02 88

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Sources of Input Data

  • Water Usage: Survey of Water Treatment Plants (DSR-95-00347)
  • 0-50 mile meat, milk, vegetable production, and population data was taken from 1982 Annual Environmental Operating Report entitled, "Evaluation of Compliance with Appendix I to IOCFR50: Updated Population, Agricultural, Meat - Animal, and Milk Production Data Tables for 1982". This evaluation was based on the 1980 Census, the Agricultural Ministry of Ontario 1980 report entitled "Agricul-tural Statistics and Livestock Marketing Account", the Agricultural Ministry of Ontario report entitled "Agricultural Statistics for Ontario, Publication 21, 1980",

the Michigan Department of Agriculture report entitled "Michigan Agricultural Statistics, 1981", and the Ohio Crop Reporting Service report entitled "Ohio Agri-cultural Statistics, 1981".

" Gaseous and liquid source terms: Tables 17 through 21 of this report.

" Location of the nearest individuals and pathways by sector within 5 miles, see Land Use Census Section of the report.

  • Population of the 50-mile Radius of Davis-Besse (DSR-95-00398).

Dose to Public Due to Activities Inside the Site Boundary In accordance with ODCM Section 7.2, the Radioactive Effluent Release Report includes an as-sessment of radiation doses from radioactivity released in liquid and gaseous effluents to mem-bers of the public from activities'inside the site boundary.

The Wellness Center, Pavilion, Training Center pond and the intake forebay/canal area located inside DBNPS Owner Controlled Area are accessible to employees and their families. The Pavil-ion may be accessible to the public for certain social activities. The Training Center pond allows employees and their families to fish on site under a "catch-and-release" program; therefore the fish pathway is not considered applicable. Considering the frequency and duration of the visits, the resultant dose would be a small fraction of the calculated maximum site boundary dose. For purposes of assessing the dose to members of the public in accordance with ODCM Section 7.2, the following exposure assumptions are used:

  • Exposure time for maximally-exposed visitors is 250 hours0.00289 days <br />0.0694 hours <br />4.133598e-4 weeks <br />9.5125e-5 months <br /> (1 hr/day, 5 day/ week, 50 wk/yr)

" Annual average meteorological dispersion (conservative, default use of maximum site boundary dispersion).

" For direct, "shine" from the Independent Spent Fuel Storage Installation (ISFSI),

default use of the maximum dose rate for a completed (full) ISFSI, and a distance of 950 feet.

89

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report The equations in the ODCM may be used for calculating the potential dose to a member of the public for activities inside the site boundary. Based on these assumptions, this dose would be at least a factor of 35 less than the maximum site boundary air dose, as calculated in the ODCM.

Nowhere onsite are areas accessible to the public where exposure to liquid effluents could occur.

Therefore, the modeling of the ODCM conservatively estimates the maximum potential dose to members of the public.

Inoperable Radioactive Effluent Monitoring Equipment There was no required radioactive effluent monitoring that was inoperable for more than 30 days during the reporting period.

Changes to the Offsite Dose Calculation Manual (ODCM) and the Process Control Procedure (PCP)

There was one change to the OCDM and one change to the PCP during this reporting period.

Borated Water Storage Tank Radionuclide Concentrations During the reporting period of 2008, the Borated Water Storage Tank's (BWST) sum of limiting fractions of radionuclides concentration, (a unitless number between 0 and 1) exceeded the ODCM Section 2.2.4 limit of 1 on three occasions during 15RFO. The tank radioactivity was re-duced by recirculation through the Spent Fuel Pool Demineralizer/filter on all three occasions.

On each occasion, reduction to an acceptable level (<1) was accomplished in between 32 and 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br />.

90

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Table 17 Gaseous Effluents - Summation of All Releases Type Unit 1st Qtr 2nd Qtr 3rd Qtr 2008 2008 2008 4th Qtr 2008 Est. Total %

Error Fission and Activation Gases Total Release Average Release Rate for Period Percent of ODCM Limits lodines Total lodines (1-131)

Average Release Rate for Period Percent of ODCM Limits Particulates Particulates with half-lives greater than 8 days Average Release Rate for Period Percent of ODCM Limits Gross Alpha Activity Tritium Total Release Average Release Rate for Period Percent of ODCM Limits Ci 1.85E+01 2.40E+00 1.88E+00 4.23E+00 pCi/sec 2.37E+00 3.05E-01 2.22E-01 5.37E-01 See Supplemental Information in ODCM Release Limits Section 3.3, Gaseous Effluent Setpoint Determination Ci 8.19E-05 9.32E-05 1.52E-06 1.74E-06 pCi/sec 1.05E-05 1.1 8E-05 1.80E-07 2.21 E-07 See Supplemental Information in ODCM Release Limits Section 3.3, Gaseous Effluent Setpoint Determination 2.5E+01 2.5E+01 2.5E+01 Ci 0.OOE+00 0.OOE +00 0.00E+00 0.OOE+00 pCi/sec 0.OOE+00 0.OOE+00 0.OOE+0 0.OOE+00 See Supplemental Information in ODCM Release Limits Section 3.3, Gaseous Effluent Setpoint Determination Ci 0.OOE+00 0.00E+00 0.00E+00 0.00E+00 2.5E+01 2.5E+01 Ci 1.91E+01 1.70E+01 1.52E+01 1.50E+01 pCi/sec 2.46E+00 2.16E+00 1.80E+00 1.91E+00 See Supplemental Information in ODCM Release Limits Section 3.3, Gaseous Effluent Setpoint Determination Note: The average release rate is taken over the entire quarter, not over the time period of the releases.

91

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Table 18 Gaseous Effluents - Ground Level Releases - Batch Modea 1st Qtr 2008 2nd Qtr 2008 3rd Qtr 2008 4th Qtr 2008 Nuclide Unit Fission Gases Ci Kr-85 Kr-85m Kr-87 Kr-88 Xe-133 Xe-135 Xe-135m Xe-138

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD N/A

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD N/A

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD N/A

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD N/A Total for Period:

lodines Ci 1-131 1-133 1-135

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD Total for Period:

Particulates and Tritium H-3 Sr-89 Sr-90 Cs-134 Cs-137 Ba-La-140 Total for Period:

N/A N/A N/A N/A Ci 5.09E-03

<LLD

<LLD

<LLD

<LLD

<LLD 1.69E-03 1.01E-02

<LLD

<LLD

<LLD

<LLD

<LLD 1.01E-02 1.07E-02

<LLD

<LLD

<LLD

<LLD

<LLD 1.07E-02 1.25E-02

<LLD

<LLD

<LLD

<LLD

<LLD 1.25E-02 92

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Table 18 (Continued)

Gaseous Effluents - Ground Level Releases Continuous Modeb 1st Qtr 2nd Qtr 3rd Qtr 4th Qtr Nuclide Unit 2008 2008 2008 2008 Fission Gases Ci Kr-85

<LLD

<LLD

<LLD

<LLD Kr-85m

<LLD

<LLD

<LLD

<LLD Kr-87

<LLD

<LLD

<LLD

<LLD Kr-88

<LLD

<LLD

<LLD

<LLD Xe-133

<LLD

<LLD

<LLD

<LLD Xe-135

<LLD

<LLD

<LLD

<LLD Xe-135m

<LLD

<LLD

<LLD

<LLD Xe-138

<LLD

<LLD

<LLD

<LLD Total for Period:

N/A N/A N/A N/A lodines Ci 1-131

<LLD

<LLD

<LLD

<LLD 1-133

<LLD

<LLD

<LLD

<LLD 1-135

<LLD

<LLD

<LLD

<LLD Total for Period:

N/A N/A N/A N/A Particulates and Tritium Ci H-3 3.44E-03 2.77E-02 4.06E-02 3.34E-02 Sr-89

<LLD

<LLD

<LLD

<LLD Sr-90

<LLD

<LLD

<LLD

<LLD Cs-134

<LLD

<LLD

<LLD

<LLD Cs-137

<LLD

<LLD

<LLD

<LLD Ba-La-140

<LLD

<LLD

<LLD

<LLD Total for Period:

3.44E-03 2.77E-02 4.06E-02 3.34E-02 93

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Table 18 (Continued)

Gaseous Effluents - Ground Level Releases LLDs for Continuousb and Batcha Mode Kr-85 K.r-85m Kr-87 Kr-88 Xe-133 Xe-133m Xe-135 Xe-135m Xe-138 1-131 1-133 1-135 Cs-134 Cs-137 Ba-140 La-140 Sr-89 Sr-90 Mn-54 Fe-59 Co-58 Co-60 Zn-65 Mo-99 Ce-141

<2.3E-06

<9.OE-09

<1.8E-08

<2.9E-08

<2.OE-08

<5.3E-08

<7. 1E-09

<2.1E-07

<6.7E-07

<1.3E-14

<1.6E-14

<8.1E-14

<1.3E-14

<1.lE-14

<5.2E-14

<7.0E-15

<8.1E-16

<2.8E-16

<1.5E-14

<2.3E-14

<1.7E-14

<1.9E-14

<2.5E-14

<1.8E-13

<2.0E-14

ýIci/rn1 4Ci/rn-l

ýt.i/iml

ý.Ici/in1 4Ci/ml 4~Ci/n]1 iýiCi/ml

ýLiCi/m1 4ci/iml piCi/mi 4ci/mi 4.Ci/ml

ýtiCi/m1 pIci/mI 4iCi/m1 ptci/mi pci/mi

ýIci/m1

ýt.i/iml 4ci/mi ptci/mi 4.ci/ml

ýti/imi 4ci/im1 pIci/mi a

Auxiliary Feed Pump Turbine Exhaust, Main Steam Safety Valves, and Auxiliary Boiler Outage Release are listed as batch releases.

b Atmospheric Vent Valve weepage and Steam Packing Exhaust are continuous releases.

94

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Table 19 Gaseous Effluents - Mixed Mode Releases Batch Mode 1st Qtr 2nd Qtr 3rd Qtr 4th Qtr Unit 2008 2008 2008 2008 Nuclide Fission Gases Ar-41 Kr-85 Kr-85m Kr-87 Kr-88 Xe-131m Xe-133 Xe-133m Xe-135 Xe-135m Xe-138 Total for Period:

  • Iodines 1-131 1-133 1-135 Total for Period:

Ci Ci Ci Ci Ci

'Ci Ci Ci Ci Ci Ci 5.04E-04 1.70E+00

<LLD

<LLD

<LLD 3.29E-02 6.14E-01

<LLD

<LLD

<LLD

<LLD

<LLD 1.73E-01

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD 2.35E+00 1.73E-01 0.OOE+0 0.00E+00 Ci Ci Ci Ci 2.75E-07

<LLD

<LLD N/A

<LLD

<LLD

<LLD N/A

<LLD

<LLD

<LLD N/A

<LLD

<LLD

<LLD N/A

  • Release of iodines and particulates are quantified in Mixed Mode Releases, Continuous Mode (Unit Sta-tion Vent)

Ci Ci Ci Ci Ci Ci Ci 1.91E-02

<LLD

<LLD

<LLD

<LLD

<LLD 5.85E-03 1.71E-04

<LLD

<LLD

<LLD

<LLD

<LLD 5.34E-03

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD 0.00E+0

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD 0.00E+00 95

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Table 19 (Continued)

Gaseous Effluents - Mixed Mode Releases Continuous Mode 1st Qtr 2008 2nd Qtr 2008 3rd Qtr 2008 4th Qtr 2008 Nuclide Unit Fission Gases Kr-85 Kr-85m Kr-87 Kr-88 Xe-133 Xe-133m Xe-135 Xe-135m Xe-138 Ci Ci Ci Ci Ci Ci Ci Ci Ci

<LLD

<LLD

<LLD

<LLD 1.61E+01

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD 2.23E+00

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD 1.88E+00

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD 4.23E+00

<LLD

<LLD

<LLD

<LLD Total for Period:

lodines 1-131 1-132 1-133 1-135 Total for Period:

1.61E+01 2.23E+00 1.88E+i00 4.23E+00 Ci Ci Ci Ci 6.50E-05

<LLD 1.66E-05

<LLD 8.16E-05 7.5 1E-05

<LLD 1.81E-05

<LLD 9.32E-05 1.52E-06

<LLD

<LLD

<LLD 1.52E-06 1.74E-06

<LLD

<LLD

<LLD 1.74E-06 Particulates and Tritium Co-58 Sr-89 Sr-90 Cs-134 Cs-137 Ba-La-140 H-3 Total for Period:

Ci Ci Ci Ci Ci Ci Ci

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD 1.91E+01 1.91E+01

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD 1.70E+01 1.70E+01

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD 1.52E+01 1.52E+01

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD 1.50E+01 1.50E+01 96

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Table 19 (Continued)

LLDs for Gaseous Effluents - Mixed Mode Releases Kr-85 Kr-85m Kr-87 Kr-88 Xe-133 Xe-133m Xe-135 Xe-135m Xe-138 1-131 1-133 1-135 Cs-134 Cs-137 Ba-140 La-140 Sr-89 Sr-90 Mn-54 Fe-59 Co-58 Co-60 Zn-65 Mo-99 Ce-141 Continuous Mode'

<2.3E-06 4Ci/ml

<9.OE-09 tCi/ml

<1.8E-08 pCi/ml

<2.9-08 Ci/rnl

<2.0E&08 pCi/ml

<5.3E-08 4Ci/ml

<7.1E-09

ýtCi/ml

<2.1E-07 iCi/ml

<6.7E-07 pCi/ml

<1.3E-14 pCi/ml

<1.6E-14 pCi/ml

<8.1E-14

ýtCi/ml

<1.3E-14 4Ci/ml

<lIlE-14

ýtCi/ml

<5.2E-14 pCi/ml

<7.OE-15 4Ci/ml

<8.1E-16 4Ci/ml

<2.8E-16 gCi/ml

<1.5E-14 4Ci/ml

<2.3E-14

ýtCi/mrl

<1.7E-14

ýtCi/ml

<1.9E-14 gCi/ml

<2.5E-14 4Ci/ml

<1.8E-13 4Ci/ml

<2.OE-14 GCi/ml Ar-41 Kr-85b Kr-85m Kr-87 Kr-88 Xe-133 Xe-133m Xe-135 Xe-135m Xe-138 1-131 1-133 1-135 Sr-89 Sr-90 Cs-134 Cs-137 Ba-140 La-140 Batch Mode'

<2.2E-06 pCi/ml

<1.OE-04 ptCi/mi

<1.4E-06 vtCi/ml

<4.6E-06 vCi/ml

<5.OE-06 pCi/ml

<2.4E-06 uCliml

<8.6E-06 4tCi/ml

<1.2E-06 4Ci/mI

<7.7E-05 jiCi/ml

<1.8E-05 pCi/ml

<1.2E-06

[tCi/ml

<l.1E-06 4Ci/ml

<4.9E-06 jiCi/ml

<8.1E-16 ptCi/ml

<2.8 E-16 4Ci/ml

<1.2E-06

[tCi/ml

<1.8E-06 pCi/ml

<4.5E-06 uCi/mi

<1.4E-06 pCi/mj a

These radionuclides were not identified in every quarter in concentrations above the lower limit of detection (LLD).

b This nuclide was detected in all gaseous batch releases.

97

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Table 20 Liquid Effluents - Summation of All Releases Type Fission and Activation Products Unit 1st Qtr 2nd Qtr 3rd Qtr 4th Qtr Est. Total 2008 2008 2008 2008

% Error Total Release (without Tritium, Gases, Alpha)

Average Diluted Concentration During Perioda Percent of ODCM Limits Percent of IOCFR20 Limit Ci 1.22E-02 2.1OE-03 7.61E-04 1.13E-03 2.OE+01 1.35E-10 lCi/ml 1.34E-09 1.85E-10 5.47E-lIl See Supplemental information in ODCM Section 2.3, Release Limits 6.87E-03 5.02E-04 2.5 1E-04 2.13 E-04 Tritium Total Release Ci 2.64E+01 1.30E+02 4.22E+01 5.96E+01 2.OE+01 Average Diluted Concentration During Perioda Percent of 10CFR20 Limit Dissolved and Entrained Gases Total Release Average Diluted Concentration During Perioda Percent of 10CFR20 Limit Gross Alpha Total Release Volume of Waste Released (prior to dilution)

Batch gCi/ml 2.90E-06 1.15E-05 3.03E-06 7.12E-06 2.90E-01 1.15E+00 3.03E-01 7.12E-01 Ci 6.30E-04 1.75E-02 1.64E-04 8.32E-06 2.OE+01 ptCi/ml 6.92E-1 I 1.54E-09 1.18E-1I 9.93E-13 3.46E-05 7.69E-04 5.89E-06 4.97E-07 Ci 0.OOE+00 0.OOE+00 0.OOE+00 2.35E-04 2.OE+OI Continuous Volume of Dilution Water Batch Continuous Total Volume of Water Released liter 5.02E+05 5.39E+05 3.62E+05 3.64E+05 2.OE+01 liter 1.08E+08 6.25E+07 6.04E+07 5.94E+07 2.OE+01 liter 1.45E+08 1.50E+08 L.14E+08 1.1OE+08 2.OE+01 liter 8.85E+09 1.11E+I0 1.37E+10 8.21E+09 2.OE+01 liter 9.11E+09 1.14E+10 1.39E+10 8.38E+09 a Tritium and alpha are found in both continuous and batch releases. Average diluted concentrations are based on total volume of water released during the quarter. Fission and Activation products and Dissolved and Entrained Gases are normally only detected in batch releases.

98

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Table 21 Liquid Effluents - Nuclides Released In Batch Releases 1st Qtr 2nd Qtr 3rd Qtr 2008 2008 2008 Nuclide Unit Fission and Activation Products Cr-51 Mn-54 Fe-55b Co-57 Co-58 Fe-59 Co-60 Ni-63 Zn-65 Se75 Sr-89b Sr-90b Sr-92 Nb-95 Zr-95 Zr-97 Mo-99 Tc-99m Ru-103 Ru-106 Ag-10 lOn Sb-122 Sb-124 Sb-125 1-131 1-132 Te-132 Cs-134 Cs-137 Ba-140 La-140 Ce-141 Ci Ci Ci Ci Ci Ci Ci Ci Ci Ci Ci Ci Ci Ci Ci Ci Ci Ci Ci Ci Ci Ci Ci Ci Ci Ci Ci Ci Ci Ci Ci Ci Ci 1.27E-04 5.60E-05 7.03E-03 3.22E-06 2.55E-03 2.76E-06 9.53E-05 1.36E-03

<LLD

<LLD

<LLD 1.06E-05

<LLD 2.22E-05 1.50E-05

<LLD

<LLD

<LLD 1.62E-06

<LLD 2.25E-05

<LLD 1.04E-04 4.62E-04 2.13E-04

<LLD

<LLD 2.1OE-05 8.73E-05

<LLD

<LLD

<LLD

<LLD

<LLD 8.62E-04

<LLD 1.54E-04

<LLD 7.70E-06 4.58E-04

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD 4.07E-05

<LLD 4.93E-5 5.28E-04

<LLD

<LLD

<LLD

<LLD 2.09E-06

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD 9.23E-05

<LLD 7.77E-06 1.34E-04

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD 5.22E-05

<LLD 1.73E-05 4.57E-04

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD 4th Qtr 2008

<LLD

<LLD

<LLD

<LLD 2.42E-05

<LLD 5.60E-07 9.82E-04

<LLD

<LLD 3.59E-05

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD 1.89E-05

<LLD

<LLD 1.04E-04

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD Total for Period:

1.22E-02

2. 1OE-03 7.6 1E-04 1.13E-03 99

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Table 21 (continued)

Liquid Effluents - Nuclides Released Batch Releases Nuclide H-3 Unit Ci 1st Qtr 2nd Qtr 2008 2008 2.63E+01 1.30E+02 3rd Qtr 2008 4.21 E+0 1 4th Qtr 2008 5.94E+01 Dissolved and Entrained Gases Kr-85 Xe-131m Xe-133 Xe-133m Xe-135 Total for Period:

Ci Ci Ci Ci Ci Ci

<LLD 9.68E-05 5.33E-04

<LLD

<LLD 1.14E-02 1.52E-04

<LLD 4.74E-05

<LLD

<LLD 5.95E-03 2.29E-05

<LLD 1.14E-05

<LLD

<LLD 8.32E-06

<LLD

<LLD 6.30E-04 1.75E-02 1.64E-04 8.32E-06 100

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Table 21 (continued)

Liquid Effluents - Nuclidesa Released Continuous Releases Nuclide Fission and Activation Products Cr-51 Mn-54 Fe-59 Co-58 Co-60 Zn-65 Sr-89b Sr-90b Nb-95 Zr795 Mo-99 Tc-99rn 1-131 Cs-134 Cs-137 Ba/La-140 Ce-141 Unit Ci Ci Ci Ci Ci Ci Ci Ci Ci Ci Ci Ci Ci Ci Ci Ci Ci 1st Qtr 2nd Qtr 3rd Qtr 4th Qtr 2008 2008 2008 2008

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD Total for Period:

0.OOE+/-00 0.00E+00 6.02E-06 0.00E+00 3.05E-02 5.45E-02 1.39E-01 2.38E-01 Tritium Ci Dissolved and Entrained Gases Xe-133 Xe-135 Ci Ci Ci

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD

<LLD Total for Period:

0.OOE+/-00 0.0013+00 0.00E+00 0.OOE+/-00 101

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Table 21 (continued)

Liquid Effluents - LLDs for Nuclides Releaseda Cr-51 Mn-54 Fe-55b Co-57 Co-58 Fe-59 Co-60 Zn-65 Kr-85 Sr-89b Sr-90 b Sr-92 Zr-95 Zr-97 Nb-95 Tc-99m Mo-99 Ru-103 Ru-106 Ag-110m Sb-124 Sb-125

<9.9E-8

<1.2E-08

<8.7E-07

<9.2E-09

<1.2E-08

<2.6E-08

<8. 1E-09

<3.1E-08

<3.4E-06

<3.4E-08

<7.9E-09

<2.5E-08

<1.5E-08

<1.5E-08

<1.2E-08

<9.6E-09

<1.0E-07

<9.4E-09

<1.2E-07

<1.2E-08

<1.1E-08

<2.9E-08 htCi/ml LtCi/ml

[Ici/ml

ýIci/ml piCi/ml pIci/ml

[tci/ml

[tci/ml

ýIci/ml

ý.Ici/ml ptCi/ml

ýtiCi/ml

ýtCi/ml

ýiCi/ml pICi/ml

![tCi/m1

ýLci/ml jaCi/ml PCi/mi ptci/mi

[ici/mi

ýiCi/ml 1-131 Xe-131m Xe-133 Xe-133m Cs-134 Xe-135 Cs-137 Ba-140 La-140 Ce-141 Ce-144

<1.OE-08

<4.2E-07

<2.6E-08

<8.5E-08

<1.3E-08

<9.3E-08

<1.2E-08

<4.8E-08

<1.6E-08

<1.6E-08

<7.5E-08

ýLCi/ml LlCi/ml pCi/ml pCi/ml pCi/ml VCi/ml

[tCi/ml VCi/ml VCi/ml VCi/ml PCi/ml a These radionuclides were not identified every quarter in concentrations above the lower limit of detection (LLD). The largest LLD value is used for each radionuclide. LLDs are applicable to both batch and continuous modes due to identical sample and analysis methods.

b Quarterly composite sample 102

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Table 22 Solid Waste and Irradiated Fuel Shipments A.

SOLID WASTE SHIPPED OFFSITE FOR BURIAL OR DISPOSAL (Not irradiated fuel) 12-month Est. Total

1. Type of Waste Unit Period Error, %
a.

Spent resins, filter sludges, m3 1.23E+01 2.5E+O1 evaporator bottoms, etc.

Ci 2.2 1E-02 2.5E+01

b.

Dry compressible waste, in 3 4.33E+02 2.5E+01 contaminated equip., etc.

Ci 2.08E+00 2.5E+O1

c.

hrradiated components, m3 control rods, etc.

Ci N/A N/A

d.

Others: Used oils m3 1.78E+01 2.5E+O1 Ci 5.52E-06 2.5E+O1

e.

Others: Spent Resin Storage m3 1.53E+01 2.5E+01 Tank Liquor Ci 5.48E+00 2.5E+O1

2. Estimate of major nuclide composition (by type of waste)

Type Percent (%)

Est. Error, %

a.

Spent Resins

b.

Dry compressible waste, contaminated equipment, etc.

c.

None Ni63 Fe 55 Cs1 3 7 Co 60 Co 58 Mn 54 Sb 12 5 14 C,

Cs' 3 4 2.91 E+0 1 2.46E+0 1 1.94E+01 1.14E+01 5.28E+00 4.79E+00 2.55E+00 2.1OE+00 7.32E-01 2.50E+01 2.50E+01 2.50E+01 2.50E+01 2.50E+01 2.50E+01 2.50E+01 2.50E+01 2.50E+01 2.50E+01 2.50E+01 2.50E+01 2.50E+01 2.50E+01 2.50E+01 2.50E+01 2.50E+01 2.50E+01 2.50E+01 Fe 55 Cs1 37 H

3 Co 58 Co60 Cs' 3 4 Pu 24 1 Sb 125 C14 Ag lom 2.98E+01 2.68E+01 2.52E+01 7.08E+00 3.19E+00 2.91 E+00 2.68E+00 1.68E+00 3.95E-01 1.65E-01 103

Davis-Besse Nuclear Power Station 2008 Annual Radiological Enviromnental Operating Report Table 22 Solid Waste and Irradiated Fuel Shipments (Continued)

Type Percent (%)

d.

Others: Used Oils Cs' 37 Fe' 5

H 3

Co 6 0 Zn 6 5 Pu 24 1 C 14

e.

Others: Spent Resin Storage Tank Liquor

3. Solid Waste Disposition Number of Shipments:

Mode of Transportation:

Destination:

Type of Container (Container Volume):

Volume shipped for processing Number of Shipments:

Mode of Transportation:

Destination:

Type of Container (Container Volume):

Volume shipped for processing H

3 Ni 63 Fe 55 Co 58 Cs1 3 7 Ag 110 m Co 60 Nb 95 Zr 95 C14 3.20E+01 3.19E+01 2.97E+01 3.63E+00 1.49E+00 7.92E-01 4.79E-01 8.44E+01 6.63E+00 2.79E+00 2.56E+00 1.08E+00 1.01E+00 7.83E-01 3.OOE-01 1.33E-01 1.06E-01 Est. Error, %

2.50E+01 2.50E+01 2.50E+01 2.50E+01 2.50E+01 2.50E+01 2.50E+01 2.50E+01 2.50E+01 2.50E+01 2.50E+01 2.50E+01 2.50E+01 2.50E+01 2.50E+01 2.50E+01 2.50E+01 11 Truck Energy Solutions, Oak Ridge, TN for processing and disposal at Energy Solutions of Utah.

Metal boxes (assorted sizes, 3.12-36.2 in3 )

441.2 in 3

1 Truck Energy Solutions, Kingston, TN for processing and disposal at Energy Solutions of Utah High Integrity Container (6.1 in 3) 3.8 in 3

104

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Table 22 Solid Waste and Irradiated Fuel Shipments (Continued)

Number of Shipmefits:

Mode of Transportation:

Destination:

Type of Container (Container Volume):

Volume shipped for processing B. IRRADIATED FUEL SHIPMENTS 3

Truck Studsvik, Erwin, TN for processing and disposal at Energy Solutions of Utah High Integrity Container (6.1 in 3) 15.3 n3 There were no shipments of irradiated fuel.

105

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Onsite Groundwater Monitoring As a result of 2007 Nuclear Energy Institute initiative NEI 07-07, Davis-Besse began monitoring wells near the plant in order to evaluate whether there have been any inadvertent releases of radioactivity that have impacted groundwater and could potentially affect local water supplies. The groundwater samples were taken from pre-construction era wells and from 16 newly drilled wells surrounding the plant.

Tritium values in these wells ranged from <140 to 1,477 pCi/liter in 2008. There is no indication that the contaminated groundwater has moved offsite. These wells are not used for drinking water purposes, and the tritium concentrations found were all below the 20,000 pCi/liter EPA drinking water limit.

Results of this sampling are listed in Table 23 below:

Table 23. Groundwater Monitoring Wells Sampled in 2008 Well Sample Tritium Designation Date (pCi/L)

MW-100A 4/8/2008

<173 MW-100B 4/9/2008

<173 MW-100C 4/9/2008

<154 MW-101A 4/10/2008 203 MW-101B 4/10/2008

<173 MW-101C 4/10/2008

<173 MW-102A 4/15/2008 713 MW-102B 4/15/2008 442 MW-102C 4/15/2008

<143 MW-103A 4/14/2008 423 MW-103B 4/14/2008 435 MW-103C 4/14/2008

<156 MW-1 04A 4/16/2008 436 / 327*

MW-104B 4/16/2008 230 MW-104C 4/17/2008

<154 MW-105A 4/18/2008 1477 MW-1 8S 4/23/2008 436 MW-20S 6/26/2008 380 MW-37S 6/26/2008 596 MW-33S 4/23/2008 767

  • Duplicate Well Designation Sample Date Tritium (pCi/L)

MW-1 OOA 10/7/2008 405 MW-100B 10/7/2008 282 MW-100C 10/9/2008

<140 MW-101A 10/13/2008 376 MW-101B 10/13/2008 257 MW-101C 10/13/2008

<141 MW-1 02A 10/8/2008 458 MW-1 02B 10/8/2008 531 MW-102C 10/8/2008

<141 MW-103A 10/14/2008 326 MW-1 03B 10/14/2008 365 MW-103C 10/14/2008

<140 MW-104A 10/9/2008 250 MW-1 04B 10/9/2008 254 MW-104C 10/10/2008

<141 MW-105A 10/16/2008 1041 / 1054*

MW-18S 10/16/2008 324 MW-20S 10/15/2008 426 MW-37S 10/15/2008 502 / 398*

MW-33S 10/16/2008 212 106

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Davis Besse

-H--Avg of All GWM Indicator Wells Control Location Onsite Groundwater Monitoring Program H-3 Trends

<200 pCi/L = Typical LLD L-I-3 (0200 pClL) 348 pCi/L = Pre-Operational Mean re-Operational Mean H-3 (348 pCiIL) 2,000 pCiIL = NRC Required LLD

-NRC Required LLD K3 (2,000 pCVL 2,000 pCi/L = FENOCINEI Communication Level 10)0000 20,000 pCi/L = EPA Reporting Level ARprigLvlH3(000p4L Max of All GWIVl Indicator Wells 1000 100-00 Figure 30. Davis-Besse Groundwater Monitoring through 2008 Summary of Onsite Spills (>100 gallons)

On October 22, a leak was discovered in an underground 3 inch condensate line, which transports low-level tritiated water to an approved radioactive effluent discharge point. The line was immediately isolated and repaired, and several wells in the area surrounding the line break were sampled.

It was not possible to determine the volume of the leak. All wells showed tritium concentrations at less than the courtesy notification level of 2,000 pCi/liter. No gamma activity or hard-to-detect radionuclides (Sr-89, Sr-90, Fe-55, Ni-63) were present in the samples. Follow-up sampling of these wells will occur in spring of 2009. Notifications were made to the NRC, State of Ohio, and Lucas and Ottawa County officials on October 23, 2008.

107

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Summary of Items Added to Decommissioning Files per 10CFR50.75(g)

Information regarding the leaking 3 inch condensate line was added to the 10CFR50.75(g) file. Results of well sampling following the leak are given in Table 24 below:

Table 24. Groundwater Results Following 3" Condensate Line Leak Groundwater Well Sampling for Additional Test Results Tritium Well VendorLab Gross Gross Designation Sample Date Tritium Fe-55 Ni-63 Sr-89 Sr-90 Analysis (pCi/L)

Alpha Beta MW-105A 10/27/2008 1183 14.4

<18.7

<776.5

<90.1

<0.6

<0.4 MW-31S 10/27/2008 1612 11.6

<16.9

<758.5

<92.7

<1.3

<1.0 MW-31D 10/27/2008 118 MW-32S 10/29/2008 1383 5.4 10.2

<737.5

<94.2

<1.2

<0.5 MW-32D 10/29/2008 654

<19.1 222.2

<746.8

<119.6

<1.0

<0.5 MW-33S 10/28/2008 581

<11.8

<18.4

<771.4

<106.1

<0.7

<0.5 MW-33D 10/28/2008 1538

<5.2 88.6

<785.3

<109.8

<1.2

<0.9 MW-34S 10/28/2008 695 12.4 10.8

<771.4

<99.5

<0.6

<0.4 MW-34D 10/29/2008 1212

<19.3 135.4

<742.1

<82.0

<2.0

<0.9 MW-12S 10/30/2008 1219 5.1 9.0

<765.7

<104.4

<0.9

<0.4 MW-12D 10/30/2008 689

<4.1 52.8

<693.6

<103.6

<1.2

<0.5 109

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Table 25 Doses Due to Gaseous Releases for January through December 2008 Maximum Individual Dose Due to 1-131, H-3 and Particulates with Half-Lives Greater than 8 days.

Whole Body Dose 1.93E-03 mrem Significant Organ Dose (thyroid) 2.21E-03 mrem Maximum Individual Dose Due to Noble Gas Whole Body Dose 4.30E-04 mrem Skin Dose 1.48E-03 mrem Population Dose Due to 1-131, H-3 and Particulates with Half-Lives Greater than 8 days.

Total Integrated Population Dose 1.33E-02 person-rem Average Dose to Individual in Population 6.09E-06 mrem Population Dose Due to Noble Gas Total Integrated Population Dose 6.03E-04 person-rem Average Dose to Individual in Population 2.76E-07 mrem 109

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Table 26 Doses Due to Liquid Releases for January through December 2008 Maximum Individual Whole Body Dose Maximum Individual Significant Organ Dose (bone)

Population Dose Total Integrated Population Dose Average Dose to Individual 2.60E-03 mrem 3.42E-03 mrem 3.29E-01 person-rem 1.51E-04 mrem 110

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Table 27 Annual Dose to The Most Exposed (from all ANNUAL DOSE (mrem) pathways) Member of the Public 2008 40CFR190 LIMIT PERCENT OF (mrem)

LIMIT Whole Body Dose*

Noble Gas Iodine, Tritium, Particulates Liquid Total Whole Body Dose Thyroid Dose Iodine, Tritium, Particulates Skin Dose Noble Gas Significant Organ Dose (liver) 4.30E-04 1.93E-03 2.60E-03 4.96E-03 4.03E-03 1.48E-03 5.13E-03 25 75 25 25 1.99E-02 5.38E-03 5.92E-03 2.05E-02 Meteorological Data Meteorological data, stored on a compact disk for January through December 31, 2008, has been submitted with this document to the U. S. Nuclear Regulatory Commission, Document Control Desk, Washington, D.C. 20555.

  • Direct radiation from the facility is not distinguishable from natural background and is, therefore, not included in this compilation.

111

Land Use Census

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Land Use Census Program Design Each year a Land Use Census is conducted by Davis-Besse in order to update information neces-sary to estimate radiation dose to the general public and to determine if any modifications are necessary to the Radiological Environmental Monitoring Program (REMP). The Land Use Cen-sus is required by Title 10 of the Code of Federal Regulations, Part 50, Appendix I and Davis-Besse Nuclear Power Station Offsite Dose Calculation Manual, Section 5, Assessment of Land Use Census Data. The Land Use Census identifies gaseous pathways by which radioactive mate-rial may reach the general population around Davis-Besse. The information gathered during the Land Use Census for dose assessment and input into the REMP ensure these programs are as cur-rent as possible. The pathways of concern are listed below:

" Inhalation Pathway - Internal exposure as a result'of breathing radionuclides car-ried in the air.

  • Ground Exposure Pathway - External exposure from radionuclides deposited on the ground
  • Plume Exposure Pathway - External exposure directly from a plume or cloud of radioactive material.
  • Vegetation Pathway - Internal exposure as a result of eating vegetables, fruit, etc.

which have a build up of deposited radioactive material or which have absorbed ra-dionuclides through the soil.

  • Milk Pathway - Internal exposure as a result of drinking milk, which may contain radioactive material as a result of a cow or goat grazing on a pasture contaminated by radionuclides.

Methodology The Land Use Census consists of recording and mapping the locations of the closest residences, dairy cattle and goats, and broad leaf vegetable gardens (greater than 500 square feet) in each me-teorological sector within a five mile radius of Davis-Besse.

The surveillance portion of the 2008 Land Use Census was performed during the month of Au-gust. In order to gather as much information as possible, the locations of residences, dairy cows, dairy goats, and vegetable gardens were recorded. The residences, vegetable gardens, and milk animals are used in the dose assessment program. The gardens must be at least 500 square feet in size, with at least 20% of the vegetables being broadleaf plants (such as lettuce and cabbage).

Each residence is tabulated as being an inhalation pathway, as well as ground and plume expo-sure pathways. Each garden is tabulated as a vegetation pathway.

112

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report All of the locations identified are plotted on a map (based on the U.S. Geological Survey 7.5 mi-nute series of the relevant quadrangles) which has been divided into 16 equal sectors correspond-ing to the 16 cardinal compass points (Figure 30). If available, the closest residence, milk ani-mal, and vegetable garden in each sector are determined by measuring the distance from each to the Station Vent at Davis-Besse.

Results The following changes in the pathways were recorded in the 2008 census:

SSE Sector - a garden was added at 7,725 meters.

SW Sector - a garden was added at 5,580 meters.

S Sector - a garden was added at 6,035 meters.

The critical receptor is a garden in the W sector at 1,560 meters from Davis-Besse, and is unchanged from 2007.

The detailed list in Table 28 was used to update the database of the effluent dispersion model used in dose calculations. Table 28 is divided by sectors and lists the distance (in meters) of the closest pathway in each.

Table 29 provided information on pathways, critical age group, atmospheric dispersion (X/Q) and deposition (D/Q) parameters for each sector. This information is used to update the Offsite Dose Calculation Manual (ODCM). The ODCM describes the methodology and parameters used in calculating offsite doses from radioactivity released in liquid and gaseous effluents and in cal-culating liquid and gaseous effluent monitoring instrumentation alarm/trip setpoints.

113

DAVIS-BESSE NUCLEAR POWER STATION RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM PRIMARY PATHWAYS WITHIN A 5 MILE RADIUS WNW

-p9 U

W

-fi CD

(-

r-CD co0 C

0
  • u z

.C) 0

.Ir x

  • a w
  • 0

_j 0

I-.-

0-RD.

0w Ir r.i~

-J

-r Jl

- N

ý iL wj N

  • LJiA U -

U -

p.

I -

rr

-~

~-~u*=

F' m

~, ~

.5 rOUS~kIY.

T 19 Azo!

'C WSW p

r ii STRICKLE-TOUSSANT R 0

cr US 7*77-,"

ýF I RD

.Ic 2NR Creek N

II r

iLNLMAN cr w

0 CAMP PERRY-0fC 1

  • ~ ~

~

~

~

~

~

~

~

~

~

ETR R"ID.I"e',I, I

=_.I c-i 0Cr-II SW-FRIFR Rfln:

=-_-'--"-_____',.___"_"L..

RIER RD, w

z Cl)

CAl CM-

,n CARROLL

~II F-:2 0U)

II bJ*

p

  • nf SAEM w

<~--~

~

L I-j

~

[

~

1-L II oII CLOSEST SITES

_j m

mC y2*

W

.I

_j 4

Cr)

Z) 0I--

0 tIC

-I 0'c uI

.a FRLFe TIE RD.

N I-I-

'iiI-To Dovis-Besse Within Sector r

RESIDENCE a-SSW SE it VEGETABLE GARDEN F1631 U Ii S;sE VEGETABLE GARDEN

~SE D8. 04-20-09 DFN-F./SCHED/SKZ86.DGN

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Table 28 Closest Exposure Pathways Present in 2008 Sector Distance from Station (meters)

Closest Pathways N

880 Inhalation Ground Exposure Plume Exposure NNE 880 Inhalation Ground Exposure Plume Exposure NE 900 Inhalation Ground Exposure Plume Exposure ENE, E, ESE N/A Located over Lake Erie SE 8,000 Inhalation Ground Exposure Plume Exposure SSE 7,725 Vegetation SSE 1,500 Inhalation Ground Exposure Plume Exposure S

6,035 Vegetation 5

'1,090 Inhalation Ground Exposure Plume Exposure SSW 4,280 Vegetation SSW 980 Inhalation Ground Exposure Plume Exposure SW 1,070 Inhalation Ground Exposure Plume Exposure 115

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Table 28 Closest Exposure Pathways Present in 2008 Sector Distance from Station (meters)

Closest Pathways SW 5,580 Vegetation WSW 1,540 Inhalation Ground Exposure Plume Exposure WSW 6,450 Vegetation W

980 Inhalation Ground Exposure Plume Exposure W

1,560 Vegetation WNW 1,520 Inhalation Ground Exposure Plume Exposure NW 2,250 Vegetation NW 1,490 Inhalation Ground Exposure Plume Exposure NNW 1,290 Inhalation Ground Exposure Plume Exposure 116

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Table 29 Pathway Locations and Corresponding Atmospheric Dispersion (X/Q) and Deposition (D/Q)

Parameters SECTOR METERS CRITICAL AGE X/Q D/Q PATHWAY GROUP (SEC/M3)

(M-2)

N 880 Inhalation Child 9.15E-07 8.40E-09 NNE 880 Inhalation Child 1.24E-06 1.44E-08 NE 900 Inhalation Child 1.26E-06 1.58E-08 ENE*

E

  • E S E
  • SE 8,000 Inhalation Child 3.43E-08 1.45E-10 SSE**

7,725 Vegetation Child 2.75E-08 1.18E-10 S**

6,035 Vegetation Child 2.82E-08 1.56E-10 SSW 4,280 Vegetation Child 3.31E-08 3.43E-10 SW**

5,580 Vegetation Child 3.59E-08 2.94E-10 WSW 6,450 Vegetation Child 3.89E-08 2.39E-10 W

1,560 Vegetation Child 2.94E-07 4.67E-09 WNW 1,520 Inhalation Child 1.89E-07 2.27E-09 NW 1,490 Vegetation Child 7.19E-08 6.04E-10 NNW 1,290 Inhalation Child 2.31E-07 1.67E-09

  • Since these sectors are located over marsh areas and Lake Erie, no ingestion pathways are present.

117

Non-Radiological Environmental Programs

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Non-Radiological Environmental Programs Meteorological Monitoring1 The Meteorological Monitoring Program at Davis-Besse is required by the Nuclear Regulatory Commission (NRC) as part of the program for evaluating the effects of routine operation of nu-clear power stations on the surrounding environment. Both NRC regulations and the Davis-Besse Technical Requirements Manual provide guidelines for the Meteorological Monitoring Program. These guidelines ensure that Davis-Besse has the proper equipment, in good working order, to support the many programs utilizing meteorological data.

Meteorological observations at Davis-Besse began in October 1968. The Meteorological Moni-toring Program at Davis-Besse has an extensive record of data with which to perform climate studies which are used to determine whether Davis-Besse has had any impact upon the local cli-mate. After extensive statistical comparative research the meteorological personnel have found no impact upon local climate or short-term weather patterns.

The Meteorological Monitoring Program also provides data that can be used by many other groups and programs such as the Radiological Environmental Monitoring Program, the Emer-gency Preparedness Program, Site Chemistry, Plant Operations, Nuclear Security, Materials Management and Industrial Safety, as well as other plant personnel and members of the sur-rounding community.

The Radiological Environmental Monitoring Program uses meteorological data to aid in evaluat-ing the radiological impact, if any, of radioactivity released in Station effluents. The meteoro-logical data is used to evaluate radiological environmental monitoring sites to assure the program is as current as possible. The Emergency Preparedness Program uses meteorological data to cal-culate emergency dose scenarios for emergency drills and exercises and uses weather data to plan evacuations or station isolation during adverse weather. The Chemistry. Unit uses meteorological data for chemical spill response activities, marsh management studies, and wastewater discharge flow calculations. Plant Operations uses meteorological data for cooling tower efficiency calcu-lations, Forebay water level availability and plant work which needs certain environmental condi-tions to be met before work begins. Plant Security utilizes weather data in their routine planning and activities.

Materials Management plans certain Plant shipments around adverse weather conditions to avoid high winds and precipitation, which would cause delays in material deliveries and safety concerns. Industrial Safety uses weather and climate data to advise personnel of un-safe working conditions due to environmental conditions, providing a safer place to work.

Regulatory Affairs uses climate data for their investigation into adverse weather accidents in rela-tion to the Plant and personnel.

i. More detailed weather information is available upon request.

118

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report On-site Meteorological Monitoring

System Description

At Davis-Besse there are two meteorological systems, a primary and a backup. Both are housed in separate environmentally controlled buildings with independent power supplies. Both primary and backup systems have been analyzed to be statistically identical, so that if a redundant system in one unit fails, the other system can take its place. The instrumentation of each system follows:

PRIMARY BACKUP 100 Meter Wind Speed 100 Meter Wind Speed 75 Meter Wind Speed 75 Meter Wind Speed 10 Meter Wind Speed 10 Meter Wind Speed 100 Meter Wind Direction 100 Meter Wind Direction 75 Meter Wind Direction 75 Meter Wind Direction 10 Meter Wind Direction 10 Meter Wind Direction 100 Meter Delta Temperature 100 Meter Delta Temperature 75 Meter Delta Temperature 75 Meter Delta Temperature 10 Meter Ambient Temperature 10 Meter Ambient Temperature 10 Meter Dew Point 10 Meter Solar Incidence Precipitation Meteorological Instrumentation The meteorological system consists of one monitoring site located at an elevation of 577 feet above mean sea level (IGLD 1955)*. It contains a 100m free-standing tower located about 3,000 feet SSW of the Cooling Tower and a 10m auxiliary tower located 100 feet west of the 100 in tower. Both are used to gather the meteorological data. Tlhe I 00m tower has primary and backup instruments for wind speed and wind direction at 100m and 75m. The 100m tower also measures differential temperature (delta Ts): 100-10m and 75-10m. The 10m tower has instruments for wind speed and wind direction. Precipitation is measured by a tipping bucket rain gauge located near the base of the 1Gm tower.

According to the Davis-Besse Nuclear Power Station Technical Requirements Manual, a mini-mum of five instruments are required to be operable at the two lower levels (75m and 10m) to measure temperature, wind speed, and wind direction. During 2008, average annual data recov-eries for all required instruments were 99.09 percent. Minor losses of data occurred during rou-tine instrument maintenance, calibration, and data validation.

Personnel at Davis-Besse inspect the meteorological site and instrumentation regularly. Data is reviewed daily to ensure that all communication pathways, data availability and data reliability are working as required. Tower instrumentation maintenance and semiannual calibrations are performed by in-house facilities and by an outside consulting firm. These instruments are wind tunnel tested to assure compliance with applicable regulations and plant specifications.

International Great Lakes Data - 1955

.119

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Meteorological Data Handling and Reduction Each meteorological system, primary and backup, have two Campbell Scientific Data-loggers (model 21XL) assigned to them. The primary system has a first data logger to communicate 900 second averages to the control room. via a Digital Alpha computer system. This is a dedicated line. If a failure occurs at any point between the primary meteorological system and the control room the control room can utilize the second data logger in the primary shelter. Each data logger has its own dedicated communication link with battery backup. The backup meteorological sys-tem is designed the same as the primary; so to lose all meteorological data the primary and backup meteorological systems would have to lose all four data loggers. However, this would be difficult since each is powered by a different power supply and equipped with lightning and surge protection, plus four independent communication lines and data logger battery backup.

The data from the primary and backup meteorological systems are stored in a 30-day circular storage module with permanent storage held by the Digital Alpha computer. Data goes back to 1988 in this format and to 1968 in both digital and hardcopy formats. All data points are scruti-nized every 900 seconds by meteorological statistics programs running continuously. These are then reviewed by meteorological personnel daily for validity based on actual weather conditions.

A monthly review is performed using 21 NRC computer codes, which statistically analyze all data points for their availability and validity. If questionable data on the primary system can not be corroborated by the backup system, the data in question is eliminated and not incorporated into the final database. All validated data is then documented and stored on hard copy and in digital format for a permanent record of meteorological conditions.

Meteorological Data Summaries This section contains Tables 30-32, which summarize meteorological data collected from the on-site monitoring program in 2008.

Wind Speed and Wind Direction Wind sector graphics represent the frequency of wind direction by sector and the wind speed in mph by sector. This data is used by the NRC to better understand local wind patterns as they relate to defined past climatological wind patterns reported in Davis-Besse's Updated Safety Analysis Report. The maximum measured sustained wind speeds for 2008 occurred on January 30, when they were measured at 48.56 mph at the l00m level, 53.79 mph at the 75m level, and 44.66 mph at the 10m level.

Figures 31-34 give an annual sector graphic of average wind speed and percent frequency by di-rection measured at the three monitoring levels. Each wind sector graphic has two radial bars.

The darker bar represents the percent of time the wind blew from that direction. The hatched bar represents the average wind speed from that direction. Wind direction sectors are classified us-ing Pasquill Stabilities. Percent calms (less than or equal to 1.0 mph) are shown in the middle of the wind sector graphic.

120

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Ambient and Differential Temperatures Monthly average, minimum and maximum ambient temperatures for 2008 are given in Table 31.

These data are measured at the 10m level; with differential temperatures taken from 100 meter and 75 meter levels. The yearly average ambient temperature was 50.21'F.. The maximum temperature was 99.9°F on September 13 with a minimum temperature of-0.76°F on December

21. Yearly average differential temperatures were -0.227°F (100 meter), and -0.235°F (75 me-ter). Maximum differential temperatures for 100 meter and 75 meter levels were 7.99°F on No-vember 6, (100 meter), and 7.997F (75 meter), also on November 6. Minimum differential tem-peratures for 100m and 75m levels were -4.00°F on October 25 (100 meter) and -4.00°F on Oc-tober 25 (75 meter). Differential temperatures are a measurement of atmospheric stability and used to calculate radioactive plume dispersions based on Gaussian Plume Models of continuous effluent releases.

Dew Point Temperatures and Relative Humidity Monthly average and extreme dew point temperatures for 2008 are provided in Table 31. These data are measured at the 10m level. The average dew point temperature was 22.38°F with a maximum dew point temperature of 52.68°F on September 13. Please note that dew point temperatures above 75°F are highly suspect and are possibly due to calm winds and high solar heating allowing the aspirated dew point processor to retain heat. The minimum dew point (dew point under 32°F is frost point) temperature was -22.94 on December 21. It is possi-ble to have relative humidity above 100 percent, which is known as supersaturation. Conditions for supersaturation have been met a few times at Davis-Besse due to its close proximity to Lake Erie, and the evaporative pool of moisture available from such a large body of water.

Precipitation Monthly totals and extremes of precipitation at Davis-Besse for 2008 are given in Table 31. To-tal precipitation for the year was 27.88 inches. The maximum daily precipitation total was 1.18 inches on June 23. There were many days on which no precipitation was recorded. It is likely that precipitation totals recorded in colder months are somewhat less than actual due to snow/sleet blowing across the collection unit rather than accumulating in the gauge.

Lake Breeze and Lake Level Monitoring Lake Breeze is monitored at Davis-Besse because of its potential to cause major atmospheric/

dispersion problems during an unlikely radioactive release. A lake breeze event occurs during the daytime, usually during the summer, where the land surface heats up faster than the water, and therefore reaches higher temperatures than the water. The warmer air above the land rises faster because it is less dense than the cooler air over the lake. This leads to rising air currents over the land with descending denser air 'over the lake. This starts a wind circulation, which draws air from the water to the land during the daytime, creating a "Lake Breeze" effect. This event could be problematic if a release were to occur because diffusion would be slow thus creat-ing an adverse atmosphere to the surrounding site.

121

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Lake and forebay levels are monitored at Davis-Besse to observe, evaluate, predict and dissemi-nate high or low lake level information. This data is critical in the running of the plant due to the large amounts of water needed to cool plant components. If water levels get too low the plant operators can take measures for the safe shutdown of the plant. Since Lake Erie is the shallowest of the Great Lakes, it is not uncommon for five feet lake level fluctuation to occur within an eight to ten hour period (plus or minus). High water levels also affect the plant due to emergency transportation and evacuation pathways.

122

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Table 30 Summary of Meteorological Data Recovery For The Davis-Besse Nuclear Power Station January 1, 2008 through December 31, 2008 JAN FEB MAR APR MAY JUN JUL AUG SEP OCT NOV DEC 2008 100m Wind Speed 100 100 92.47 89.17 99.60 100 100 100 100 100 100 100 98.44 100M Wind Direction 100 100 100 100 100 100 100 100 100 100 100 100 100 75M Wind Speed 100 100 93.55 95.56 100 100 100' 100 100 100 100 100 99.09 75M Wind Direction 100 100 100 100 100 100 100 100 100 100 100 100 100 IOM Wind Speed 100 100 97.31 94.58 100 100 100 100 100 100 100 100 99.33 10M Wind Direction 100 100 100 100 100 100 100 100 100 100 100 100 100 1OM Ambient Air Temp 100 100 99.87 99.72 100 100 100 100 100 100 100 100 99.97 10M Dew Point Temp 100 100 99.87 99.72 100 99.86 100 100 100 100 100 100 99.95 Delta T (100M-10M) 100 100 99.87 99.72 100 100 100 100 100 100 100 100 99.97 Delta T (75M-10M) 100 100 99.87 99.72 100 100 100 100 100 100 100 100 99.97 Joint IOOM Winds and Delta T (100M-1OM) 100 100 92.47 89.17 99.60 100 100 100 100 100 100 100 98.44 Joint 75M Winds and Delta T (100M-10M) 100 100 93.55 95.56 100 100 100 100 100 100 100 100 99.09 Joint 1OM Winds and Delta T (75M-10M) 100 100 97.31 94.58 100 100 100 100 100 100 100 100 99.33

  • all data for individual months expressed as percent of time instrument was operable during the month, divided by the maximum number of hours in that month that the instru-ment could be operable. Values for annual data recoveries equals the percent of time instrument was operable during the year, divided by the number of hours in the year that the instrument was operable.

123

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Table 31 Summary of Meteorological Data Measured at Davis-Besse Nuclear Power Station January 1, 2008 through December 31, 2008 JAN FEB MAR APR MAY JUN JUL AUG SEP OCT NOV DEC 2008 100M WIND Max Speed (mph) 48.56 43.97 36.59 40.03 38.65 34.79 28.01 28.64 44.54

34. 12 39.77 48.45 48.56 Date of Max Speed 01/30 02/18 03/03 04/01 05/31 06/21 07/02 08/10 09/14 10/26 11/15 12/28 01/30 Min Speed (mph) 0.70 1.51 0.00 0.00 0.01 0.02 2.56 1.45 2.04 1.01 3.06 1.35 0.00

.Date of Min Speed 01/30 02/21 03/27 04/03 05/22 06/14 07/06 08/12 09/02 10/04 11/01 12/11 04/03

  • Ave Wind Speed" 20.27 17.31 15.73 8.76 8.26 14.84 13.67 13.18 13.74 16.18 17.83 17.67 16.41 75M WIND Max Speed (mph) 53.79 40.95 37.48 40.91 35.0079 32.34 26.22 27.34 42.65 32.98 36.17 45.97 53.79 Date of Max Speed 01/30 02/18 03/25 04/01 05/31 06/09 07/02 08/10 09/14 10/26 11/15 12/28 01/30 Min Speed (mph) 2.15 1.20 0.21 2.57 0.86 1.84 1.87 1.70 1.42 1.05 2.18 1.27 0.21 Date of Min Speed 01/31 02/21 03/04 04/15 05/21 06/05 07/06 08/30 09/28 10/04 11/01 12/11 03/04 Ave Wind Speed 18.31 15.58 14.69 14.47 16.82 13.99 12.15 11.73 12.15 14.62 16.14 16.35 14.75 10M WIND Max Speed (mph) 44.66 33.05 29.27 32.03 23.90 22.56 18.84 19.25 28.27 25.70 28.74 34.26 44.66 Date of Max Speed 01/30 02/18 03/25 04/01 05/31 06/09 07/02 08/10 09/14 10/26 11/15 12/28 01/30 Min Speed (mph) 2.39 1.43 0.12 1.86 1.06 1.99 0.99 1.07 1.15 1.17 1.65 1.06 0.12 Date of Min Speed 01/27 02/01 03/04 04/15 05/13 06/04 07/05 08/29 09/03 10/15 11/15' 12(11 03/04 Ave Wind Speed 12.10 10.29 9.90 9.25 9.59 8.34 7.43 7.58 7.68 8.85 9.65 11.57 9.35 124

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Table 31 (continued)

Summary of Meteorological Data Measured at Davis-Besse Nuclear Power Station January 1, 2008 through December 31, 2008

  • JAN FEB MAR APR MAY JUN JUL AUG SEP OCT NOV DEC 2008 IOM AMBIENT TEMP Max (F) 66.08 54.30 60.51 80.73 81.27 90.80 88.10 90.03 99.90 79.30 71.80 65.11 99.90 Date of Max 01/07 02/05 03/31 04/25 05/26 06/06 07/17 08/23 09/13 10/13 11/04 12/27 09/13 Min (F) 2.46 4.17 13.69 32.54 42.59 52.99 57.50 56.72

.51.61 29.22 19.11

-0.76

-0.76 Date of Mini 01/25 02/11 03M0 04/02 05/13 06/19 07/01 08/10 09/13 10/30 11/23 12/21 12/21 Ave Temp 29.13 26.12 34.05 52.62 57.14 70.58 73.51 71.34 67.00 52.47 40.15 28.47 50.21 IOM DEW POINT TEMP Mean (F) 8.23 5.20 10.79 23.31 27.08 39.46 41.07 39.21 35.88 22.15 12.70 3.31 22.38 Max (F) 40.37 33.11 33.81 41.07 44.59 50.93 50.33 49.53 52.68 41.53 33.85 34.50 52.68 Date of Max 01/07 02105 03/31 04/25 05/26 06/05 07/20 08/05 09/13 10/15 11/03 12/27 09/13 Min (F)

-16.34

-16.95

-7.58 3.24 14.79 27.46 29.55 29.99 25.40 5.66

-5.01

-22.94

-22.94 Date ofMin 01/25 02/10 03/09 04/02 05/19 06/17 07/02 08/10 09/10 10/30 11/22 12/21 12/21 PRECIPITATION Total (inches) 1.34 3.51 3.19 1.47 2.28 5.55 2.35 0.35 1.54 0.99 2.51 2.80 27.88 Max. in One Day 0.17 0.29 0.45 0.17 0.39 1.18 0.32 0.13 0.24 0.27 0.22 0.15 1.18 Date 01/08 02/17 03/28 04/04 05/02 06/23 07/10 08/01 09/13 10/15 11/15 12/24 06/23 125

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Figure 31 Wind Rose Annual Average 1OOM W

E H

I r

I:

DAVIS-BESSE ANNUAL 2008 lOOM LEVEL 126

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Figure 32 Wind Rose Annual Average 75M

~.

m DAVIS-BESSE ANNUAL 2008 75M LEVEL 127

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Figure 33 Wind Rose Annual Average 1 OM E

j.~:~:~-

DAVIS-BESSE ANNUAL 2008 JOM LEVEL 128

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Table 32 Joint Frequency Distribution by Stability Class DAVIS-BESSE ENVIRONMENTAL COMPLIANCE UNIT 12-Mar-09 PAGE 01 TIME OF DAY:

10:56:33 PROGRAM: JFD VERSION: F77-1.0 DAVIS-BESSE 75-10 DT, NO BACKUP DATA PERIOD EXAMINED: 01/01/2008 - 12/31/2008 SITE IDENTIFIER: 8

      • ANNUAL ***

STABILITY CLASS A STABILITY BASED ON:

DELTA T BETWEEN 250.0 AND 35.0 FEET WIND MEASURED AT:

35.0 FEET WIND THRESHOLD AT:

1.00 MPH JOINT FREQUENCY DISTRIBUTION OF WIND SPEED AND DIRECTION IN HOURS AT 35.00 FEET SPEED (MPH)

N NNE NE ENE E

ESE SE SSE S

SSW SW WSW W

WNW NW NNW TOTAL CALM 1.01-3.49 0

2 0

0 0

0 0

0 0

0 0

3.50-7.49 7

8 0

0 0

0 1

0 6

5 0

7.50-12.49 7

2 1

0 1

0 0

2 1

2 1

12.50 -18.49 0

0 0

4 3

2 0

0 0

0 1

18.50 - 24.49 0

0 0

0 0

0 0

0 0

0 0

>24.49 0

0 0

0 0

0 0

0 0

0 0

0 0

0 1

6 5

1 0

3 0

0 0

0 0

0 0

2 1

6 8

43 4

9 16 57 2

15 13 41 0

2 2

7 0

0 0

0 TOTAL 14 12 1

4 4

2 1

2 7

2 10 7

32 39 150 STABILITY CLASS B STABILITY BASED ON:

DELTA T BETWEEN 250.0 AND 35.0 FEET WIND MEASURED AT:

35.0 FEET WIND THRESHOLD AT:

1.00 MPH JOINT FREQUENCY DISTRIBUTION OF WIND SPEED AND DIRECTION IN HOURS AT 35.00 FEET SPEED (MPH)

CALM N

NNE NE ENE E

ESE SE SSE S

SSW SW WSW W

WNW NW NNW TOTAL 0

1.01-3.49 0

0 0

0 0

0 0

0 0

0 0

0 0

3.50-7.49

6.

10 2

0 0

0 0

0 1

7 3

2 0

7.50- 12.49 6

10 5

2 9

4 0

0 0

1 9

15 5

12.50-18.49 1

0 2

4 3

1 0

0 0

0 6

9 1

18.50- 24.49 0

0 0

0 0

0 0

0 0

0 0

3 0

>24.49 0

0 0

0 0

0 0

0 0

0 0

2 0

0 0

0 0

1 4

9 45 3

11 12 92 5

4 9

45 0

1 0

4 0

0 0

2 TOTAL 13 20 9

6 12 0

0 1

8 18 31 6

9 20 30 188 129

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Table 32 (continued)

Joint Frequency Distribution by Stability Class DAVIS-BESSE ENVIRONMENTAL COMPLIANCE UNIT 12-Mar-09 PAGE 02 TIME OF DAY:

10:56:33 PROGRAM:

JFD VERSION: F77-1.0 DAVIS-BESSE 75-10 DT, NO BACKUP DATA PERIOD EXAMINED: 01/01/2008 - 12/31/2008

      • ANNUAL
  • STABILITY CLASS C SITE IDENTIFIER: 8 STABILITY BASED ON:

DELTA T BETWEEN 250.0 AND 35.0 FEET WIND MEASURED AT:

35.0 FEET WIND THRESHOLD AT:

1.00 MPH JOINT FREQUENCY DISTRIBUTION OF WIND SPEED AND DIRECTION IN HOURS AT 35.00 FEET SPEED (MPH)

N NNE NE ENE E

ESE SE SSE S

SSW SW WSW W

WNW NW NNW TOTAL CALM 1.01 -3.49 1

0 3.50 -7.49 1

2 7.50-12.49 6

12 12.50-18.49 3

4 18.50 - 24.49 0

0

>24.49 0

0 0

0 0

0 8

0 3

2 5

25 33 10 6

4 5

0 0

0 0

0 0

0 0

0 0

0 3

0 0

2 0

0 0

0 0

0 0

3 1

0 0

0 0

1 0

0 4

7 5

0 9

29 41 13 3

10 16 5

0 1

9 0

0 0

2 2

0 0

3 3

3 14 1

11 0

0 0

0 0

0 2

7 51 16 219 5

73 0

10 0

4 TOTAL 11 18 19 29 41 12 3

2 4

16 48 73 20 7

28 28 359 STABILITY CLASS D STABILITY BASED ON:

DELTA T BETWEEN 250.0 AND 35.0 FEET WIND MEASURED AT:

35.0 FEET WIND THRESHOLD AT:

1.00 MPH JOINT FREQUENCY DISTRIBUTION OF WIND SPEED AND DIRECTION IN HOURS AT 35.00 FEET SPEED (MPH)

N NNE NE ENE E

ESE SE SSE S

SSW SW WSW W

WNW NW NNW TOTAL CALM 1.01-3.49 3

8 3

6 4

9 10 11 6

13 8

5 6

3.50-7.49 26 55 51 68 134 101 42 56 78 124 70 62 34 7.50- 12.49 91 74 143 164 185 65 28 29 77 182 221 236 121 12.50 - 18.49 49 63 101 60 48 5

0 0

11 99 141 276 91 18.50 - 24.49 8

5 25 10 0

0 0

0 1

12 40 92 23

>24.49 4

2 0

0 0

0 0

0 0

0 1

39 7

0 1

2 3

98 24 20 26 971 52 83 94 1845 57 79 70 1150 13 10 12 251 2

0 4

59 TOTAL 181 207 323 308 371 180 80 96 173 430 481 710 282 149 194 209 4374 130

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Table 32 (continued)

Joint Frequency Distribution by Stability Class DAVIS-BESSE ENVIRONMENTAL COMPLIANCE UNIT 12-Mar-09 PAGE 03 TIME OF DAY:

10:56:33 PROGRAM: JFD VERSION: F77-1.0 DAVIS-BESSE 75-10 DT, NO BACKUP DATA PERIOD EXAMINED: 01/01/2008 - 12/31/2008

      • ANNUAL ***

STABILITY CLASS E SITE IDENTIFIER: 8 STABILITY BASED ON:

DELTA T BETWEEN 250.0 AND 35.0 FEET WIND MEASURED AT:

35.0 FEET WIND THRESHOLD AT:

1.00 MPH JOINT FREQUENCY DISTRIBUTION OF WIND SPEED AND DIRECTION IN HOURS AT 35.00 FEET SPEED (MPH)

N NNE NE ENE E

ESE SE SSE S

SSW SW WSW W

WNW NW NNW TOTAL CALM 1.01-3.49 0

3 1

6 1

17 18 23 38 19 19 3,50-7.49 14 18 12 29 87 110 96 88 104 218 157 7.50- 12.49 6

19 14 33 54 37 26 17 55 164 100 12.50 -18.49 2

4 1

1 9

0 0

3 26 71 44 18.50-24.49 0

0 0

0 0

0 0

0 2

13

'7

>24.49 2

0 0

0 0

0 0

0 0

0 3

12 6

80 73 81 77 37 14 7

3 5

0 6

5 35 16 38 32 15 13 3

0 0

0 3

4 178 17 1154 19 772 1

241 1

36 1

11 TOTAL 24 44 28 69 151 164 140 131 225 485 330 222 173 STABILITY CLASS F STABILITY BASED ON:

DELTA T BETWEEN 250.0 AND 35.0 FEET WIND MEASURED AT:

35.0 FEET WIND THRESHOLD AT:

1.00 MPH JOINT FREQUENCY DISTRIBUTION OF WIND SPEED AND DIRECTION IN HOURS AT 35.00 FEET 97 66 43 2395 SPEED (MPH)

N NNE NE ENE E

ESE SE SSE S

SSW SW WSW W

WNW NW NNW TOTAL CALM 1.01 -3.49 2

3.50-7.49 0

7.50- 12.49 0

12.50- 18.49 0

18.50 - 24.49 0

>24.49 0

4 0

5 0

1 0

0 0

0 0

0 0

2 1

5 6

28 52 44 22 15 5

2 13 24 29 40 60 122 107 38 38 1

8 4

2 2

4 1

3 3

1 0

0 0

0 0

1 0

1 1

0 0

0 0

0 0

0 0

1 0

0 0

0 0

0 0

0 0

0 0

0 6

16 0

0 0

0 4

1 0

0 0

0 0

0 196 1

496 1

31 1

4 0

1 0

0 TOTAL 2

10 0

5 22 33 37 70 117 167 134 57 44 22 5

3 728 131

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Table 32 (continued)

Joint Frequency Distribution by Stability Class DAVIS-BESSE ENVIRONMENTAL COMPLIANCE UNIT 12-Mar-09 PAGE 04 I

TIME OF DAY:

10:56:33 PROGRAM:

JFD VERSION: F77-1.0 DAVIS-BESSE 75-10 DT, NO BACKUP DATA PERIOD EXAMINED: 01/01/2008 - 12/31/2008 SITE IDENTIFIER: 8

      • ANNUAL ***

STABILITY CLASS G STABILITY BASED ON:

DELTA T BETWEEN 250.0 AND 35.0 FEET WIND MEASURED AT:

35.0 FEET WIND THRESHOLD AT:

1.00 MPH JOINT FREQUENCY DISTRIBUTION OF WIND SPEED AND DIRECTION IN HOURS AT 35.00 FEET SPEED (MPH)

N NNE NE ENE E

ESE SE SSE S

SSW SW WSW W

WNW NW NNW TOTAL CALM 1.01 -3.49 1

3.50 - 7.49 0

7.50 - 12.49 0

12.50-18.49 0

18.50 - 24.49 0

>24.49 0

1 1

1 0

0 0

0 0

0 0

0 0

0 1

2 3

8 26 26 35 4

12 12 11 13 18 45 29 0

1 0

0 1

0 0

1 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 9

9 8

5 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

0 0

3 126 0

158 0

3 0

0 0

0 0

0 TOTAL 2

1 4

14 14 14 22 44 71 65 17 14 1

0 3

287 STABILITY CLASS ALL STABILITY BASED ON:

DELTA T BETWEEN 250.0 AND 35.0 FEET WIND MEASURED AT:

35.0 FEET WIND THRESHOLD AT:

1.00 MPH JOINT FREQUENCY DISTRIBUTION OF WIND SPEED AND DIRECTION IN HOURS AT 35.00 FEET SPEED (MPH)

CALM N

NNE NE ENE E

ESE SE SSE S

SSW SW WSW W

WNW NW NNW TOTAL 3

1.01 -3.49 7

18 5

14 7

33 37 70 122 102 85 41 26 14 11 10 602 3.50-7.49 54 99 73 103 249 249 182 197 270 525 373 195 151 80 50 68 2918 7.50-12.49 116 118 168 225 291 120 56 53 138 359 364 382 222 100 149 158 3019 12.50 - 18.49 55 71 110 73 68 8

0 3

38 173 203 340 111 80 122 99 1554 18.50 - 24.49 8

5 25 10 0

0 0

0 3

25 49 114 26 16 13 15 309

>24.49 6

2 0

0 0

0 0

0 0

0 4

48 9

2 0

5 76 TOTAL 246 313 381 425 615 410 275 323 571 1184 1078 1120 545 292 345 355 8481 132

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Table 32 (continued)

Joint Frequency Distribution by Stability Class DAVIS-BESSE ENVIRONMENTAL COMPLIANCE UNIT 12-Mar-09 TIME OF DAY:

PAGE 05 10:56:33 PROGRAM:

JFD VERSION: F77-1.0 DAVIS-BESSE 75-10 DT, NO BACKUP DATA PERIOD EXAMINED: 01/01/2008 - 12/31/2008

      • ANNUAL ***

SITE IDENTIFIER: 8 STABILITY BASED ON:

WIND MEASURED AT:

WIND THRESHOLD AT:

DELTA T 35.0 FEET 1.00 MPH BETWEEN 250.0 AND 35.0 FEET 8783

  • S:

8481 TOTAL NUMBER OF OBSERVATIONS:

TOTAL NUMBER OF VALID OBSERVATION TOTAL NUMBER OF MISSING OBSERVATIONS:

302 PERCENT DATA RECOVERY FOR THIS PERIOD:

96.6 %

MEAN WIND SPEED FOR THIS PERIOD:

9.4 MPH TOTAL NUMBER OF OBSERVATIONS WITH BACKUP DATA: 0 PERCENTAGE OCCURRENCE OF STABILITY CLASSES A

B C

D E

F G

1.77 2.22 4.23 51.57 28.24 8.58 3.38 DISTRIBUTION OF WIND DIRECTION VS STABILITY N

NNE NE ENE E

ESE SE

SSE, S

SSW Sw WSW W

WNW NW NNW CALM A

B C

D

,E F

G 14 13 11 181 24 2

1 12 1

4 4

2 1

2 7

7 2

10 6

7 32 39 0

20 18 207 44 10 2

9 19 323 6

29 308 12 41 371 5

12 180 0

3 80 0

1 8

18 31 6

2 4

16 48 73 20 96 173 430 481 710 282 131 225 485 330 222 173 9

20 30 0

7 149 28 194 28 209 0

0 28 69 151 164 140 0

5 22 33 37 1

4 14 14 14 97 66 43 3

70 117 167 134 22 44 71 65 57 17 44 14 22 1

5 0

3 3

0 0

TOTAL 246 313 381 425 615 410 275 323 571 1184 1078 1120 545 292 345 355 3

133

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Land and Wetlands Management The Navarre Marsh, which is part of the Ottawa National Wildlife Refuge, makes up 733 acres of wetlands on the southwestern shore of Lake Erie and surrounds the Davis-Besse Nuclear Power Station. The marsh is owned by FirstEnergy and jointly managed by the U.S. Fish and Wildlife Service and FirstEnergy. Navarre Marsh is divided into three pools. The pools are separated from Lake Erie and each other by a series of dikes and revetments. Davis-Besse is responsible for the maintenance and repair of the dikes and controlling the water levels in each of the pools.

A revetment is a retaining structure designed to hold water back for the purposes of erosion con-trol and beach formation. Revetments are built with a gradual slope, which causes waves to dis-sipate their energy when they strike their large surface area. Beach formation is encouraged through the passive deposition of sediment. A dike is a retaining structure designed to hold wa-ter for the purpose of flood control and to aid in the management of wetland habitat. When used as a marsh management tool, dikes help in controlling water levels in order to maintain desired vegetation and animal species. Manipulating water levels is one of the most important marsh management techniques used in the Navarre Marsh. Three major types of wetland communities exist in Navarre Marsh, the freshwater marsh, the swamp forest, and the wet meadow. Also, there exists a narrow dry beach ridge along the lakefront, with a sandbar extending out into Lake Erie. All these areas provide essential food, shelter and nesting habitat, as well as a resting area for migratory birds.

Davis-Besse personnel combine their efforts with a number of conservation agencies and organi-zations. The Ottawa National Wildlife Refuge, the Ohio Department of Natural Resources (ODNR), and the Black Swamp Bird Observatory work to preserve and enhance existing habitat.

Knowledge is gained through research and is used to help educate the public about the impor-tance of preserving wetlands.

With its location along two major migratory flyways, the Navarre Marsh serves as a refuge for a variety of birds in the spring and fall, giving them an area to rest and restore energy reserves be-fore continuing their migration. The Black Swamp Bird Observatory, a volunteer research group, captures, bands, catalogues, and releases songbirds in the marsh during these periods.

Navarre Marsh is also home to wildlife that is typical of much of the marshland in this area, in-cluding deer, fox, coyote, muskrats, mink, rabbits, groundhogs, hawks, owls, ducks, geese, her-ons, snakes and turtles. For the first time in recent history, a pair of mature American Bald Ea-gles chose the Navarre Marsh as their nesting site in late 1994, and fledged a healthy eaglet in July 1995. A new nest was built in 1999-2000, from which a dozen eaglets were fledged. In the fall of 2005 two pairs of eagles built new nests on Davis-Besse property. One nest produced two eaglets, both of which successfully fledged bringing the total number of eagles fledged to seven-teen since 1995. Ohio has gone from a low of 4 nesting eagle pairs statewide in 1978 to setting new hatch records every year for nearly three decades.

134

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Water Treatment Plant Operation Description The Davis-Besse Nuclear Power Station draws water from Lake Erie for its water treatment plant. The lake water is treated with sodium hypochlorite and/or sodium hypo-bromite, coagu-lant aid, filtration, electrolysis and demineralization to produce high-purity water used in many of the Station's cooling systems.

Water from the Carroll Township Water Treatment Plant is used in Davis-Besse's Fire Protection System.

Water Treatment System Raw water from Lake Erie enters an intake structure, then passes through traveling screens which remove debris greater than one-half inch in size. The water is then pumped to chlorine detention tanks. Next, the water is sent to the pre-treatment system, which is comprised of coagulation and filtration to remove sediment, organic debris, and certain dissolved compounds from the raw wa-ter. The next step of the process is reverse osmosis, where pressure is used to remove certain im-purities by passing the water through a selectively-permeable membrane. The water is then stripped of dissolved gases, softened, electrolytically deionized and finally, is routed through a polishing demineralization process before being sent to storage.

Domestic Water When Davis-Besse began operation over 30 years ago, all site domestic water was produced in the Water Treatment Facility. Operation of the domestic water treatment and distribution system, including the collection and analysis of daily samples, was reportable to the Ohio Environmental Protection Agency.

Since December of 1998, the Carroll Township Water Treatment Plant has supplied domestic water to Davis-Besse. Carroll Township Water and Wastewater District follow all applicable regulatory requirements for the sampling and analysis of Station drinking water.

Zebra Mussel Control With the exception of its domestic water, the Plant withdraws all of its water through an intake system from Lake Erie. Zebra mussels can severely impact the availability of water for Plant processes. Dreissena polymnorpha, commonly known as the zebra mussel, is a native European bivalve that was introduced into the Great Lakes in 1986 and was discovered in Lake Erie in 1989.

Zebra mussels are prolific breeders that rapidly colonize an area by forming byssal threads, which enable them to attach to solid surfaces and to each other. Because of their ability to attach in this manner, they may form layers several inches deep. This poses a problem to fa-cilities that rely on water intakes from Lake Erie because mussels may attach to the intake struc-tures and restrict water flow.

135

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Zebra mussels have not caused any significant problems at Davis-Besse, but mussels have been found attached to the intake crib (the structure that allows water to be withdrawn from the lake) and the first section of the intake conduit (the pipe that connects the crib to the intake canal).

Mussels have also been found on the trash racks and on the walls of intake bay #3 prior to the traveling screens, and are periodically cleaned off by using high-pressure water. Davis-Besse uses continuous low level chlorination/bromination of the intake bays to control the mussels.

At present, the mussel population appears to be leveling off or declining. This is likely due to the increasing clarity of Lake Erie, since the mussels remove much of the algae. As the food source for the zebra mussel declines, mussel populations should continue to decline correspondingly.

Wastewater Treatment Plant (WWTP) Operation The WWTP operation is supervised by an Ohio licensed Wastewater Operator. Wastewater gen-erated by site personnel is treated in an onsite extended aeration package treatment facility de-signed to accommodate up to 38,000 gallons per day. In the treatment process, wastewater from the various collection points around the site enters the facility through a grinder, from where it is distributed to the surge tanks of one or both of the treatment plants.

The wastewater is then pumped into aeration tanks, where it is digested by microorganisms.

Oxygen is necessary for good sewage treatment, and is provided to the microbes by blowers and diffusers. The mixture of organics, microorganisms, and decomposed wastes is called activated sludge. The treated wastewater settles in a clarifier, and the clear liquid leaves the clarifier under a weir and exits the plant through an effluent trough. The activated sludge contains the organ-isms necessary for continued treatment, and is pumped back to the aeration tank to digest incom-ing wastewater. The effluent leaving the plant is drained to the wastewater basin (NPDES Out-fall 601) where further treatment takes place.

Summary of 2008 Wastewater Treatment Plant Operations All wastewater parameters were within specifications during the year 2008.

National Pollutant Discharge Elimination System (NPDES) Reporting The Ohio Environmental Protection Agency (OEPA) has established limits on the amount of pol-lutants that Davis-Besse may discharge to the environment. These limits are regulated through the Station's National Pollutant Discharge Elimination System (NPDES) permit, number 21B0001 1. Parameters such as chlorine, suspended solids and pH are monitored under the NPDES permit. Davis-Besse personnel prepare the NPDES Reports and submit them to the OEPA each month.

Davis-Besse has eight sampling points described in the NPDES permit. Seven of these locations are discharge points, or outfalls, and one is a temperature monitoring location. Descriptions of these sampling points follow:

136

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Outfall 001 Collection Box: a point representative of discharge to Lake Erie Source of Wastes: Low volume wastes "(Outfalls 601 and 602), Circulating Water system blowdown and service water Outfall 002 Area Runoff: Discharge to Toussaint River Source of Wastes: Storm water runoff, Circulating Water pump house sumps Outfall 003 Screenwash Catch Basin: Outfall to Navarre Marsh Source of Wastes: Backwash water and debris from water intake screens Outfall 004 Cooling Tower Basin Ponds: Outfall to State Route 2 Ditch Source ofWastes: Circulating Water System drain (only during system outages)

Outfall 588 Sludge Monitoring Source of Wastes: Wastewater Plant sludge shipped for offsite processing Outfall 601 Wastewater Plant Tertiary Treatment Basin: Discharge from Wastewater Treatment Plant Sources of Wastes: Wastewater Treatment Plant Outfall 602 Low volume Wastes: Discharge from settling basins Sources of wastes: Water treatment residues, Condensate Polishing Holdup Tank decanta-tion and Condensate Pit sumps Sampling Point 801 Intake Temperature: Intake water prior to cooling operation 2008 NPDES Summary During 2008, Davis-Besse Nuclear Power Station did not exceed any NPDES discharge limits.

137

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Chemical Waste Management The Chemical Waste Management Program for hazardous and nonhazardous chemical wastes generated at the Davis-Besse Nuclear Power Station was developed to ensure wastes are man-aged and disposed of in accordance with all applicable state and federal regulations.

Resource Conservation and Recovery Act The Resource Conservation and Recovery Act (RCRA) is the statute which regulates solid haz-ardous waste. Solid waste is defined as a solid, liquid, semi-solid, or contained gaseous material.

The major goals of RCRA are to establish a hazardous waste regulatory program to protect hu-man health and the environment and to encourage the establishment of solid waste management, resource recovery, and resource conservation systems. The intent of the hazardous waste man-agement program is to control hazardous wastes from the time they are generated until they are properly disposed of, commonly referred to as "cradle to grave" management. Anyone who gen-erates, transports, stores, treats, or disposes of hazardous waste are subject to regulation under RCRA.

Under RCRA, there are essentially three categories of waste generators:

  • Large quantity Generators A facility which generates 1,000 kilograms/month (2,200 lbs./month) or more.

" Small quantity Generators - A facility which generates less than 1,000 kilograms/

month (2,200 lbs./month).

  • Conditionally Exempt Small Quantity Generators - A facility which generates 100 kilo-grams/month (220 lbs./month).

In 2008, the Davis-Besse Nuclear Power Station generated approximately 7,350 pounds of haz-ardous waste.

Non-hazardous waste generated in 2008 included 9,540 gallons of used oil and other nonhazard-ous wastes such as oil filters, latex paints and caulks.

RCRA mandates other requirements such as the use of proper storage and shipping containers, labels, manifests, reports, personnel training, a spill control plan and an accident contingency plan. These are part of the Chemical Management Program at Davis-Besse. The following are completed as part of the hazardous waste management program and RCRA regulations:

" Weekly Inspections of the Chemical Waste Accumulation Areas are designated through-out the site to ensure proper handling and disposal of chemical waste. These, along with the Chemical Waste Storage Area, are routinely patrolled by security personnel and in-spected weekly by Environmental and Chemistry personnel. All areas used for storage or accumulation of hazardous waste are posted with warning signs and drums are color-coded for easy identification of waste categories.

  • Waste Inventory Forms are placed on waste accumulation drums or provided in the ac-cumulation area for employees to record the waste type and amount when chemicals are 138

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report added to the drum. This ensures that incompatible wastes are not mixed and also identi-fies the drum contents for proper disposal.

Other Environmental Regulating Acts Comprehensive Environmental Response, Compensation and Liability Act The Comprehensive Environmental Response, Compensation, and Liability Act (CERCLA, or Superfund) established a federal authority and source of funding for responding to spills and other releases of hazardous materials, pollutants and contaminants into the environment. Super-fund establishes "reportable quantities" for several hundred hazardous materials and regulates the cleanup of abandoned hazardous waste disposal sites.

Superfund Amendment and Reauthorization Act (SARA)

Superfund was amended in October 1986 to establish new reporting programs dealing with emergency preparedness and community right-to-know laws. As part of this program, CERCLA is enhanced by ensuring that the potential for release of hazardous substances is minimized, and that adequate and timely responses are made to protect surrounding populations.

Davis-Besse conducts site-wide inspections to identify and record all hazardous products and chemicals onsite as required by SARA. Determinations are made as to which products and chemicals are present in reportable quantities.

Annual SARA reports are submitted to local fire departments and state and local planning com-missions by March 1 for the preceding calendar year.

Toxic Substances Control Act (TSCA)

The Toxic Substance Control Act (TSCA) was enacted to provide the USEPAwith the authority to require testing of new chemical substances for potential health effects before they are intro-duced into the environment, and to regulate them where necessary. This law would have little impact on utilities except for the fact that one family of chemicals, polychlorinated biphenyls (PCBs), has been singled out by TSCA. This has resulted in an extensive PCB management sys-tem, very similar to the hazardous waste management system established under RCRA.

In 1992, Davis-Besse completed an aggressive program that eliminated PCB transformers onsite.

PCB transformers were either changed out with non-PCB fluid transformers or retrofilled with non-PCB liquid.

Retro-filling PCB transformers involves flushing the PCB fluid out of a transformer, refilling it with PCB-leaching solvents and allowing the solvent to circulate in the transformer during operation. The entire retro-fill process takes several years and will extract almost all of the PCB.

In all, Davis-Besse performed retro-fill activities on eleven PCB transformers between 1987 and 1992. The only remaining PCB containing equipment onsite are a limited number of capacitors.

These capacitors are being replaced and disposed of during scheduled maintenance activities.

139

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Clean Air Act The Clean Air Act identifies substances that are considered air pollutants. Davis-Besse holds an OEPA permit to operate an Air Contaminant Source for the station Auxiliary Boiler. This boiler is used to heat the station and provide steam to plant systems when the reactor is not operating.

A report detailing the Auxiliary Boiler operation is submitted annually.

The Ohio EPA has granted an exemption from permitting our six emergency diesel engines, in-cluding the Station Blackout Diesel Generator, the 2 Emergency Diesel Generators, the Emer-gency Response Facility Diesel Generator, the Miscellaneous Diesel, and the Fire Pump Diesel.

These sources are operated infrequently to verify their reliability, and would only be used in the event of an emergency.

In response to recent "Clean Air Act Title V" legislation, an independent study identifying and quantifying all of the air pollution sources onsite was performed. Of particular significance is asbestos removal from renovation and demolition projects for which USEPA has outlined spe-cific regulations concerning handling, removal, environmental protection, and disposal. Also, the Occupational Safety and Health Protection Administration (OSHA) strictly regulates asbestos with a concern for worker protection. Removal teams must meet medicail surveillance, respirator fit tests, and training requirements prior to removing asbestos-containing material. Asbestos is not considered a hazardous waste by RCRA, but the EPA does require special handling and dis-posal of this waste under the Clean Air Act.

Transportation Safety Act The transportation of hazardous chemicals, including chemical waste, is regulated by the Trans-portation Safety Act of 1976. These regulations are enforced by the United States Department of Transportation (DOT) and cover all aspects of transporting hazardous materials, including pack-ing, handling, labeling, marking, and placarding. Before any wastes are transported off site, Davis-Besse must ensure that the wastes are identified, labeled and marked according to DOT regulations, including verification that the vehicle has appropriate placards and it is in good oper-ating condition.

140

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Other Environmental Programs Underground Storage Tanks According to RCRA, facilities with Underground Storage Tanks (USTs) are required to notify the State. This regulation was implemented in order to provided protection from tank contents leaking and causing damage to the environment. Additional standards require leak detection sys-tems and performance standards for new tanks. At Davis-Besse two 40,000 gallon and one 8,000 gallon diesel fuel storage tanks are registered USTs.

Spill Kits Spill control equipment is maintained throughout the Station at chemical storage areas and haz-ardous chemical and oil use areas. Equipment in the kits may include chemical-resistant cover-alls, gloves, boots, decontamination agents, absorbent cloth, goggles and warning signs.

Waste Minimization'and Recycling Municipal Solid Waste (MSW) is normal trash produced by individuals at home and by indus-tries. In some communities, MSW is burned in specially designed incinerators to produce power or is separated into waste types (such as aluminum, glass, and paper) and recycled. The vast ma-jority of MSW is sent to landfills for disposal. As the population increases and older landfills reach their capacity, MSW disposal becomes an important economic, health, and resource issue.

The State of Ohio has addressed the issue with the State Solid Waste Management Plan, other-wise known as Ohio House Bill 592. The intent of the bill is to extend the life of existing land-fills by reducing the amount of MSW produced, by reusing certain waste material, and by recy-cling other wastes. This is frequently referred to as "Reduce, Reuse, and Recycle."

Davis-Besse has implemented and participated in company wide programs that emphasize the reduction, reuse, recycle approach to MSW management. An active Investment Recovery Pro-gram has greatly contributed to the reduction of both hazardous and municipal waste generated by evaluating options for uses of surplus materials prior to the materials entering Davis-Besse's waste streams. Such programs include paper, cardboard, aluminum cans, used tires, and metals recycling or recovery. Paper and cardboard recycling is typically in excess of 50 tons annually.

This represents a large volume of recyclable resources, which would have otherwise been placed in a landfill. Aluminum soft drink cans are collected for the Boy Scouts of America to recycle.

Additionally, lead-acid batteries are recycled and tires are returned to the seller for proper dis-posal.

Although scrap metal is not usually considered part of the MSW stream, Davis-Besse collects and recycles scrap metals, which are sold at market price to a scrap dealer for resource recovery.

141

Appendices

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Environmental, Inc.

  • Midwest Laboratory an Allegheny Technologies Co.

700 Landwehr Road

  • Northbrook, IL 60062-2310 ph. (847) 564-0700
  • fax (847) 564-4517 APPENDIX A INTERLABORATORY COMPARISON PROGRAM RESULTS NOTE:

Environmental Inc., Midwest Laboratory participates in intercomparison studies administered by Environmental Resources Associates, and serves as a replacement for studies conducted previously by the U.S. EPA Environmental Monitoring Systems Laboratory, Las Vegas, Nevada. Results are reported in Appendix A. TLD Intercomparison results, in-house spikes, blanks, duplicates and mixed analyte performance evaluation program results are also reported. Appendix A is updated four times a year; the complete Appendix is included in March, June, September and December monthly progress reports only.

January, 2008 through December, 2008 142

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Appendix A Interlaboratory Comparison Progiram Results Environmental, Inc., Midwest Laboratory has participated in interlaboratory comparison (crosscheck) programs since the formulation of it's quality control program in December 1971. These programs are operated by agencies which supply environmental type samples containing concentrations of radionuclides known to the issuing agency but not to participant laboratories. The purpose of such a program is to provide an independent check on a laboratory's analytical procedures and to alert it of any possible problems.

Participant laboratories measure the concentration of specified radionuclides and report them to the issuing agency. Several months later, the agency reports the known values to the participant laboratories and specifies control limits. Results consistently higher or lower than the known values or outside the control limits indicate a need to check the instruments or procedures used.

Results in Table A-1 were obtained through participation in the environmental sample crosscheck. program administered by Environmental Resources Associates, serving as a replacement for studies conducted previously by the U.S. EPA Environmental Monitoring Systems Laboratory, Las Vegas, Nevada.

The results in Table A-2 list results for thermoluminescent dosimeters (TLDs), via International Intercomparison of EnvironmentalDosimeters, when available, and internal laboratory testing.

Table A-3 lists results of the analyses on in-house "spiked" samples for the past twelve months. All samples are prepared using NIST traceable sources. Data for previous years available upon request.

Table A-4 lists results of the analyses on in-house "blank" samples for the past twelve months. Data for previous years available upon request.

Table A-5 lists REMP specific analytical results from the in-house "duplicate" program for the past twelve months. Acceptance is based on the difference of the results being less than the sum of the errors.

Complete analytical data for duplicate analyses is available upon request.

The results in Table A-6 were obtained through participation in the Mixed Analyte Performance Evaluation Program.

Results in Table A-7 were obtained through participation in the environmental sample crosscheck program administered by Environmental Resources Associates, serving as a replacement for studies conducted previously by the Environmental Measurement Laboratory Quality Assessment Program (EML).

Attachment A lists the laboratory precision at the 1 sigma level for various analyses. The acceptance criteria in Table A-3 is set at +/- 2 sigma.

Out-of-limit results are explained directly below the result.

143

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Attachment A ACCEPTANCE CRITERIA FOR "SPIKED" SAMPLES LABORATORY PRECISION: ONE STANDARD DEVIATION VALUES FOR VARIOUS ANALYSESa One standard deviation Analysis Level for single determination Gamma Emitters 5 to 100 pCi/liter or kg 5.0 pCi/liter

> 100 pCi/liter or kg 5% of known value Strontium-89b 5 to 50 pCi/liter or kg 5.0 pCi/liter

> 50 pCi/liter or kg 10% of known value Strontium-90b 2 to 30 pCi/liter or kg 5.0 pCi/liter

> 30 pCi/liter or kg 10% of known value Potassium-40

> 0.1 g/liter or kg 5% of known value Gross alpha 5 20 pCi/liter 5.0 pCi/liter

> 20 pCi/liter 25% of known value Gross beta

< 100 pCi/liter 5.0 pCi/liter

> 100 pCi/liter 5% of known value Tritium 5 4,000 pCi/liter

+/- lo =

169.85 x (known)00 933

> 4,000 pCi/liter 10% of known value Radium-226,-228

> 0.1 pCi/liter

.15% of known value Plutonium

> 0.1 pCi/liter, gram, or sample 10% of known value Iodine-1 31, 5 55 pCi/liter 6 pCi/liter lodine-129b

> 55 pCi/liter 10% of known value Uranium-238,

< 35 pCi/liter 6 pCi/liter Nickel-63b

> 35 pCi/liter 15% of known value Technetium-99b Iron-55b 50 to 100 pCi/liter 10 pCi/liter

> 100 pCi/liter 10% of known value Other Analyses b 20%of known value a From EPA publication, "Environmental Radioactivity Laboratory Intercomparison Studies Program, Fiscal Year, 1981-1982, EPA-600/4-81-004.

b Laboratory limit.

144

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report TABLE A-1. Interlaboratory Comparison Crosscheck program, Environmental Resource Associates (ERA)a.

Concentration (pCi/L)

Lab Code Date Analysis Laboratory ERA Control Resultb Resultc Limits Acceptance STW-1 148 STW-1148 STW-1 149 STW-1149 STW-1149 STW-1 149 STW-1 149 STW-1150 STW-1150 STW-1 151 STW-1152 STW-1152 STW-1152 03/24/08 03/24/08 03/24/08 03/24/08 03/24/08 03/24/08 03/24/08 03/24/08 03/24/08 03/24/08 03/24/08 03/24/08 03/24/08 Sr-89 Sr-90 Ba-133 Co-60 Cs-134 Cs-137 Zn-65 Gr. Alpha Gr. Beta 1-131 Ra-226 Ra-228 Uranium 50.6 42.4 56.9 73.9 50.2 97.7 109.9 43.7 36.4 29.3 15.0 18.4 23.4

+/- 2.4

+/- 1.4

+/- 5.4

+/- 1.6

+/- 1.9

+/- 2.2

+/- 5.8

+/- 7.5

+/- 1.8

+/- 1.4

+/-1.1

+ 1.8

+ 1.3 60.4 48.6

- 68.2 39.2 28.8

- 45.1 58.3 48.3

- 64.3 76.6 68.9

- 86.7 46.6 37.4

-51.3 102.0 91.8

- 115.0 106.0 95.4

- 126.0 50.8 26.5

- 63.7 51.4 35.0

-58.4 28.7 23.9

- 33.6 15.3 11.4

-17.6

-17.0 11.4

-20.4 24.6 19.8

-27.6 12000.0 10400.0 13200.0 STW-1153 03/24/08 H-3 12551.0

+/- 207.0 STW-1154 STW-1154 STW-1155 STW-1155 STW-1155 STW-1155 STW-1155 STW-1156 STW-1156 STW-1157 STW-1157 STW-1157 STWV-1164 STW-1164 STW-1165 STW-1165 STW-1 165 STW-1165 STW-1165 STW-1166 STW-1 166 STW-1167 STW-1168 STW-1168 STW-1168 STW-1169 07/07/08 07/07/08 07/07/08 07/07/08 07/07/08 07/07/08 07/07/08 07/07/08 07/07/08 07/07/08 07/07/08 07/07/08 10/06/08 10/06/08 10/06/08 10/06/08 10/06/08 10/06/08 10/06/08 10/06/08 10/06/08 10/06/08 10/06/08 10/06/08 10/06/08 10/06/08 Sr-89 Sr-90 Ba-1 33 Co-60 Cs-1 34 Cs-1 37 Zn-65 Gr. Alpha Gr. Beta Ra-226 Ra-228 Uranium Sr-89 Sr-90 Ba-133 Co-60 Cs-134 Cs-137 Zn-65 Gr. Alpha Gr. Beta 1-131 Ra-226 Ra-228 Uranium H-3 24.9 39.7 45.0 24.9 90.4 57.1 102.9 24.8 23.9 8.0 7.7 11.2 42.2 35.4 56.9 47.6 26.4 24.3 72.0 24.2 32.6 29.0 15.0 16.0 47.8 2357.0

+/- 3.5

+/- 0.5

+/- 1.2

+/- 3.0

+/- 5.3

+/- 2.8

+/- 7.3

+/- 1.6

+/- 0.9

+/- 0.6

+/- 0.8

+/- 0.3

+/- 3.2

+/- 1.2

+/- 1.0

+/- 1.3

+/- 4.0

+/- 0.7

+/- 2.9

+/- 4.8

+/- 1.0

+/- 0.3

+/- 1.0

+/- 1.0

+/- 2.0

+/- 66.0 28.7 40.0 46.6 25.7 93.2 54.6 98.8 30.7 25.8 8.1 7.4 11.3 48.7 33.6 63.5 49.1 25.6 25.6 68.6 26.9 38.0 28.1 16.1 14.1 50.3 2220.0 20.4 29.4 38.1 22.3 76.6 49.1 88.9 15.7 16.1 6.1 4.7 8.9 38.2 24ý6 52.8 44.2 19.7 21.6 61.2 13.6 25.1 23.4 12.0 9.4 40.8 1830.0

-35.3

- 46.0

-51.8

-31.0

-102.0

- 62.9

-118.0

- 40.0

-33.7

- 9.5

-9.5

- 13.0

-56.1

- 38.8

- 69.9

- 56.6

- 28.4

-31.2

- 83.0

- 35.5

-45.5

- 33.0

- 18.4

- 17.1

- 55.9

- 2460.0 Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass.

Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass a Results obtained by Environmental, Inc., Midwest Laboratory as a participant in the crosscheck program for proficiency testing in drinking water conducted by Environmental Resources Associates (ERA).

b Unless otherwise indicated, the laboratory result is given as the mean +/- standard deviation for three determinations.

145

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report c Results are presented as the known values, expected laboratory precision (1 sigma, 1 determination) and control limits as provided by ERA.

TABLE A-2. Crosscheck program results; Thermoluminescent Dosimetry, (TLD, CaSO4 : Dy Cards).

mR Lab Code Date Known Lab Result Control Description Value

+ 2 sigma Limits Acceptance Environmental, Inc.

2008-1 6/16/21 2008-1 6/16/21 2008-1 6/116/2 2008-1 6/16/2(

2008-1 6/16/21 2008-1 6/16/21 2008-1 6/16/21 2008-1 6/16/2' 2008-1 6/16/21 2008-1 6/16/21 Environmental, Inc.

2008-2 11/17/2 2008-2 11/17/2 2008-2 11/17/2 2008-2 11/17/2 2008-2 11/17/2 2008-2 11/17/2 2008-2 11/17/2 2008-2 11/17/2 2008-2 11/17/2 2008-2 11/17/2 2008-2 11/17/2 2008-2 11/17/2 2008-2 11/17/2 2008-2 11/17/2 2008-2 11/17/2 2008-2 11/17/2 2008-2 11/17/2 008 008 008 008 008 008 008 008 008 008 40 cm.

50 cm.

60 cm.

70 cm.

80 cm.

90 cm.

100 cm.

120 cm.

150 cm.

180 cm.

30.23 19.35 13.44 9.87 7.56 5.97 4.84 3.36 2.15 1.49 33.87 23.13 16.25 10.39 7.44 5.80 4.32 2.69 2.05 1.23

+/- 1.17

+/- 0.57

+/- 1.10

+/- 0.52

+/- 0.51

+/- 1.04

+/- 0.43

+/- 0.15

+/- 0.69

+/- 0.80 21.16 13.55 9.41 6.91 5.29 4.18 3.39 2.35 1.51 1.04

- 39.30

-25.16

- 17.47

- 12.83

- 9.83

- 7.76

- 6.29

- 4.37

- 2.80

-1.94 Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass 008 008

'008

'008 008 008

'008

-008 008

'008 008

'008

'008

'008

'008

'008

'008 30 cm.

40 cm.

50 cm.

60 cm.

60 cm.

70 cm.

75 cm.

80 cm.

90 cm.

90 cm.

100 cm.

110 cm.

120 cm.

120 cm.

150 cm.

150 cm.

180 cm.

63.05 35.46 22.7 15.76 15.76 11.58 10.09 8.87 7.01 7.01 5.67 4.69 3.94 3.94 2.52 2.52 1.75 73.10 40.80 24.10 15.98 19.49 11.97 9.45 9.30 7.19 6.84 5.47 3.98 3.09 3.12 2.55 2.24 1.36

+/- 1.84

+/- 2.30

+/- 0.58

+/- 0.55

+/- 0.93

+/- 0.54

+/- 0.28

+/- 0.18

+/- 0.43

+/- 0.42

+/- 0.19

+/- 0.27

+/- 0.21

+ 0.34

+0.12

+ 0.08

+ 0.08 44.14 24.82 15.89 11.03 11.03 8.11 7.06 6.21 4.91 4.91 3.97 3.28 2.76 2.76 1.76 1.76 1.23

-81.97

-46.10

- 29.51

- 20.49

- 20.49

- 15.05

- 13.12

-11.53

-9.11

-9.11

- 7.37

-6.10

-5.12

-5.12

- 3.28

- 3.28

- 2.28 Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass 146

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report TABLE A-3. In-House "Spike" Samples Concentration (pCi/L)a Lab Code b Date Analysis Laboratory results Known Control 2s, n=l c Activity Limits d Acceptance SPW-111 SPW-298 W-11708 SPW-711 SPAP-881 SPAP-881 SPAP-883, SPMI-885 SPW-887 SPW-889 W-31 808 W-31808 SPMI-885 SPMI-885 SPW-887 SPW-887 SPW-1 282 W-40308 SPW-5580 SPW-1562 SPW-1560 SPW-1621 W-51508 W-51508 SPAP-2673 SPAP-2673 SPAP-2674 SPF-2745 SPF-2745 SPMI-2677 SPMI-2677A SPW-2677 SPW-2677 SPMI-2679 SPMI-2679 SPMI-2679 SPMI-2679A SPVE-2681 SPW-2683 SPW-2685 SPW-2689 1/14/2008 1/31/2008 1/17/2008 2/25/2008 3/11/2008 3/11/2008 3/11/2008 3/11/2008 3/11/2008 3/11/2008 3/18/2008 3/18/2008 3/24/2008 3/24/2008 3/24/2008 3/24/2008 4/2/2008 4/3/2008 4/7/2008 4/8/2008 4/10/2008 4/16/2008 5/15/2008 5/15/2008 6/2/2008 6/2/2008 6/2/2008 6/2/2008 6/2/2008 6/3/2008 6/3/2008 6/3/2008 6/3/2008 6/3/2008 6/3/2008 6/3/2008 6/3/2008 6/3/2008 6/2/2008 6/2/2008 6/2/2008 Tc-99 Ni-63 Ra-226 U-238 Cs-134 Cs-137 Gr. Beta e Sr-90 Sr-90 H-3 Gr. Alpha Gr. Beta Cs-134 Cs-137 Cs-134 Cs-1 37 U-238 Ra-226 H-3 Ra-228 Tc-99 Fe-55 Gr. Alpha Gr. Beta Cs-1 34 Cs-137 Gr. Beta e Cs-134 Cs-137 Cs-1 37 1-131 Cs-1 34 1-131(G)

Cs-1 34 Cs-1 37 1-131(G) 1-131 1-131(G)

Ni-63 H-3 C-14 32.20 +/- 0.85 213.55++/- 3.07 11.34 +/- 0.43 33.56 +/- 1.74 19.29 +/- 1.53 114.04 +/- 3.03 54.56 +/- 0.12 45.93 +/- 1.60 38.82 +/- 1.60 67325.00 +/- 725.00 19.51 +/- 0.40 47.20 +/- 0.42 40.93 +/- 1.55 61.36 +/- 2.82 40.68 +/- 1.44 58.52 +/- 2.93 41.30 +/- 1.78 15.17 +/- 0.50 211.02 +/- 7.71 28.93 +/- 2.09 29.74 +/- 0.84 27205.80 +/- 982.90 24.01 +/- 0.41 47.97 +/- 0.41 17.39 +/- 1.32 106.82 +/- 3.42 53.57 +/- 0.13 0.34 +/- 0.02 2.06 +/- 0.04 53.99 +/- 6.15 26.64 +/- 0.59 40.30 +/- 3.35 25.92 +/- 4.48 35.02 +/- 2.93 58.49 +/- 6.05 25.30 +/- 4.97 30.37 +/- 0.50 1.11 +/- 0.06 2151.70 +/- 10.22 64927.20 +/- 704.80 4405.40 +/- 15.21 32.34 212.58 12.69 41.70 20.09 113.90 51.64 45.13 45.13 67384.00 20.08 45.67 39.69 56.91 39.69 56.91 41.70 12.69 240.00 30.51 32.34 28370.00 20.08 45.68 18.60 113.30 51.40 0.37 2.27 56.66 28.58 37.21 28.58 37.21 56.66 28.58 28.58 0.95 2119.30 66540.80 4742.00 20.34 - 44.34 148.81 - 276.35 8.88 - 16.50 29.19 - 54.21 10.09 - 30.09 102.51 - 125.29 30.98 - 72.30 36.10 - 54.16 36.10 - 54.16 53907.20 - 80860.80 10.04 - 30.12 35.67 - 55.67 29.69 - 49.69 46.91 - 66.91 29.69 - 49.69 46.91 - 66.91 29.19 - 54.21 8.88 - 16.50 0.00 - 806.46 21.36 - 39.66 20.34 - 44.34 22696.00 - 34044.00 10.04 - 30.12 35.68 - 55.68 8.60 - 28.60 101.97-124.63 30.84 - 71.96 0.22 - 0.52 1.36-3.18 46.66 - 66.66 16.58 - 40.58 27.21 - 47.21 18.58 - 38.58 27.21 - 47.21 46.66 - 66.66 18.58 - 38.58 16.58 - 40.58 0.57-1.33 1483.51 - 2755.09 53232.64 - 79848.96 2845.20 -6638.80 Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass 147

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report TABLE A-3. In-House "Spike" Samples Concentration (pCi/L)a Lab Code b Date Analysis Laboratory results Known Control 2s, n=1 Activity Limitsc Acceptance W-81408 SPW-1562 SPW-81808 W-81.808 W-81808 8/14/2008 8/14/2008 8/18/2008 8/18/2008 8/18/2008 Ra-226 Ra-228 U-238 Gr. Alpha Gr. Beta W-112008 11/20/2008 Gr. Alpha W-1 12008 SPAP-6839 SPAP-6839 SPAP-6841 SPW-6843 SPW-6845 SPW-6847 SPW-6849 SPW-6851 SPF-6859 SPF-6859 SPW-7059 SPMI-7061 11/20/2008 12/5/2008 12/5/2008 12/5/2008 12/5/2008 12/5/2008 12/5/2008 12/5/2008 12/5/2008 12/5/2008 12/5/2008 12/19/2008 12/19/2008 Gr. Beta Cs-1 34 Cs-1 37 Gr. Beta e C-14 Fe-55 Tc-99 Ni-63 H-3 Cs-134 Cs-1 37 Sr-90 Sr-90 12.98 +/- 0.35 29.09 +/- 2.46 42.59 +/- 1.96 21.36 +/- 0.42 49.33 +/- 1.01' 20.13 +/- 0.40 48.28 +/- 0.42 15.39 +/- 2.72 111.45 +/- 9.85 49.26 +/- 0.12 19377.50 + 55.27 7068.30 + 692.30 37.71 + 1.33 232.56 + 3.26 63664.00 +/-8745.00 0.63 + 0.02 2.35 +/- 0.01 49.19 +/- 2.62 39.39 +/- 2.19 12.69 30.51 41.70 20.08 45.68 20.08 45.60 15.68 112.00 50.72 23708.00 6028.00 32.34 211.34 64674.00 0.63 2.24 44.33 44.33 8.88-16.50 21.36 - 39.66 29.19 - 54.21 10.04 - 30.12 35.68 - 55.68 10.04 - 30.12 35.60 - 55.60 5.68 - 25.68 100.80 - 123.20 30.43 - 71.01 14224.80 - 33191.20 4822.40 - 7233.60 20.34 - 44.34 147.94 - 274.74 51739.20 - 77608.80 0.38 - 0.88 1.34 -3.14 35.46 - 53.20 35.46 - 53.20 Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass a Liquid sample results are reported in pCi/Liter, air filters( pCi/filter), charcoal (pCi/im 3), and solid samples (pCi/g).

b Laboratory codes as follows: W (water), MI (milk), AP (air filter), SO (soil), VE (vegetation),

CH (charcoal canister), F (fish).

c Results are based on single determinations.

d Control limits are established from the precision values listed in Attachment A of this report, adjusted to +/- 2a.

e Control limits based on the laboratory limit, Attachment A ("Other Analyses").

NOTE: For fish, Jello is used for the Spike matrix. For Vegetation, cabbage is used for the Spike matrix.

148

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report TABLE A-4. In-House "Blank" Samples Concentration (pCi/L)a Lab Code Sample Date Analysisb Laboratory results (4.66a)

Acceptance Type LLD Activityc Criteria (4.66 a)

SPW-17 SPW-1 12 W-1 1408 SPAP-880 SPAP-880 SPW-888 W-31808 W-31808 SPMI-884 SPMI-884 W-40308 SPW-1 563 SPW-1561 SPW-1621 SPW-2451 SPW-2676 SPW-2676 SPW-2676 SPW-2677 SPW-2677 SPW-2677 SPF-2744 SPF-2744 SPW-2676 SPMI-2678 SPVE-2680 SPW-3581 W-80708 W-80708 W-81408 SPW-1563 SPW-81808 Water Water Water Air Filter Air Filter Water Water Water Milk Milk Water Water Water Water Water Water Water Water Water Water Water Fish Fish Water Milk Vegetation Water Water Water Water Water Water 1/3/2008 1/14/2008 1/14/2008 3/11/2008 3/11/2008 3/11/2008 3/18/2008 3/18/2008 3/24/2008 3/24/2008 4/3/2008 4/8/2008 4/10/2008 4/16/2008 5/22/2008 6/2/2008

.6/2/2008 6/2/2008 6/2/2008 6/2/2008 6/2/2008 6/2/2008 6/2/2008 6/3/2008 6/3/2008 6/3/2008 7/14/2008 8/7/2008 8/7/2008 8/14/2008 8/14/2008 8/18/2008 U-238 0.09 Tc-99 4.70 Ra-226 0.05 Cs-1 34 0.91 Cs-137 1.13 H-3 159.99 Gr. Alpha 0.42 Gr. Beta 0.72 Cs-1 34 2.79 Cs-1 37 3.36 Ra-226 0.04 Ra-228 0.57 Tc-99 4.77 Fe-55 668.50 U-238 0.21 Cs-134 2.03 Cs-1 34 3.60 Cs-137 2.38 Cs-134 2.78 1-131(G) 3.49 1-131(G) 5.25 Cs-134 5.48 Cs-1 37 4.83 1-131 0.18 1-131 0.22 1-131(G) 0.01 U-238 0.10 Gr. Alpha 0.63 Gr. Beta 1.43 Ra-226 0.06 Ra-228 0.79 U-238 0.18 0.01 +/- 0.07

-0.06 +/- 2.85 0.05 +/- 0.04

-78.90 +/- 80.40

-0.05 +/- 0.29 0.09 +/- 0.51 0.05 +/- 0.03 0.31 +/- 0.30

-3.42 +/- 2.85

-170.70 +/- 397.20 0.35 +/- 0.24 0.01 +/-0.11 0.12 +/- 0.15 0.13 +/- 0.12

-0.02 +/- 0.44

-0.47 +/- 0.99 0.14 +/- 0.04 0.89 +/- 0.47 0.04 +/- 0.13 1

10 100 100 200 1

3.2 10 10 1

2 10 1000 1

10 10 10 10 20 20 100 100 0.5 0.5 20 1

1 3.2 1

2 1

149

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report TA13LE A-4. In-House "Blank" Samples Concentration (pCi/L)a Lab Code Sample Date Analysisb Laboratory results (4.66a)

Acceptance Type LLD Activityc Criteria (4.66 cr)

W-1 12008 W-1 12008 SPAP-6838 SPAP-6838 SPAP-6840 SPW-6842 SPW-6844 SPW-6846 SPW-6848 SPF-6858 SPF-6858 SPW-7058 SPW-7058 SPW-7058 SPMI-7060 SPMI-7060 SPMI-7060 SPMI-7060 i Water Water

.Air Filter Air Filter Air Filter Water Water Water Water Fish Fish Water Water Water Milk

-Milk Milk Milk 11/20/2008 11/20/2008 12/5/2008 12/5/2008 12/5/2008 12/5/2008 12/5/2008 12/5/2008 12/5/2008 12/5/2008 12/5/2008 12/19/2008 12/19/2008 12/19/2008 12/19/2008 12/19/2008

,12/19/2008 12/19/2008 Gr. Alpha Gr. Beta Cs-134 Cs-1 37 Gr. Beta C-14 Fe-55 Tc-99 Ni-63 Cs-1 34 Cs-137 Cs-134 Cs-137 Sr-90 Cs-134 Cs-137 1-131(G)

Sr-90 0.40 0.75 1.01 0.95 0.96 7.79 715.10 1.36 1.94 1.53 3.92 2.62 2.39 0.65 2.18 3.87 2.80 0.53 0.02 +/- 0.28

-0.16 +/- 0.52 2.69 +/- 0.64

-3.04 +/- 4.05 21.70 +/- 435.10

-0.47 +/- 0.82 3.08 +/- 1.23

-0.28 +/- 0.26 0.76 +/- 0.34 1

3.2 100 100 3.2 200 1000 10 20 100 100 10 10 1

10 10 20 1

a Liquid sample results are reported in pCi/Liter, air filters( pCi/filter), charcoal (pCi/charcoal canister), and solid samples (pCi/kg).

b 1-131(G); iodine-131 as analyzed by gamma spectroscopy.

c Activity reported is a net activity result. For gamma spectroscopic analysis, activity detected below the LLD value is not reported.

d Low levels of Sr-90 are still detected in the environment. A concentration of (1-5 pCi/L) in milk is not unusual.

150

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report TABLE A-5. In-House "Duplicate" Samples Concentration (pCi/L)a Averaged Lab Code Date Analysis First Result Second Result Result Acceptance AP-8809, 8810 CF-42, 43 CF-42, 43 DW-80020, 80021 U-169, 170 SO-8836, 8837 SO-8836, 8837 SO-8836, 8837 SO-8836, 8837 DW-80045, 80046 DW-80045, 80046 MI-138, 139 LW-i 90, 191 DW-8008, 8009 DW-8008, 8009 DW-80057, 80058 DW-80057, 80058 SWU-479,480 W-920,921 SW-540, 541 SW-540, 541 DW-80155, 80156 DW-80155, 80156 DW-80165, 80166 DW-80166, 80167 DW-80166, 80167 DW-80166, 80167 W-1413, 1414 DW-80189, 80190 DW-80189, 80190 MI-1006, 1007 MI-1 006, 1007 DW-80205, 80206 DW-80202, 80203 DW-80202, 80203 DW-80208, 80209 SG-1080, 1081 SO-1195, 1196 SO-1195, 1196 WW-1242, 1243 AP-1519, 1520 W-1565, 1566 W-1565, 1566 1/2/2008 1/2/2008 1/2/2008 1/7/2008 1/10/2008 1/14/2008 1/14/2008 1/14/2008 1/14/2008 1/15/2008 1/15/2008 1/15/2008 1/16/2008 1/1612008 1/16/2008 1/21/2008 1/21/2008 1/29/2008 2/4/2008 2/12/2008 2/12/2008 2/12/2008 2/12/2008 2/20/2008 2/20/2008 2/20/2008 2/20/2008 3/3/2008 3/11/2008 3/11/2008 3/12/2008 3/12/2008 3/14/2008 3/14/2008 3/14/2008 3/14/2008 3/18/2008 3/18/2008 3/18/2008 3/24/2008 4/2/2008 4/2/2008 4/2/2008 I

Be-7 Gr. Beta K-40 Gr. Alpha Beta-K40 Cs-137 Gr. Alpha Gr. Alpha K-40 Gr. Alpha Gr. Beta K-40 Gr. Beta Ra-226 Ra-228 Gr. Alpha Gr. Beta Gr. Beta Gr. Beta Gr. Alpha Gr. Beta Ra-226 Ra-228 Gr. Alpha Ra-226 Ra-228 Uranium Gr. Beta Ra-226 Ra-228 K-40 Sr-90 Gr. Alpha Ra-226 Ra-228 U-233/4 Pb-214 U-233/4 U-238 Gr. Beta Be-7 Gr. Alpha Gr. Beta 0.06 +/- 0.02 8.88 +/- 0.19 5.08 +/- 0.29 2.28 +/- 0.84 7.50 +/- 5.50 0.80 +/- 0.05 13.30 +/- 4.31 33.68 +/- 3.73 12.31 +/- 0.74 2.94 +/- 1.13 1.86 +/- 0.66 1262.40 +/- 81.70 2.85 +/- 1.07 2.77 +/- 0.20 3.95 +/- 0.74 6.77 +/- 0.66 13.83 +/- 0.97 4.49 +/- 1.13 4.20 +/- 1.30 2.75 +/-.1.16 6.46 +/- 1.11 2.55 +/- 0.22 1.86 +/- 0.70 1.51 +/- 0.90 0.40 +/- 0.09 1.44 +/- 0.52 0.69 +/- 0.25 7.50 +/- 3.00 4.41 +/- 0.30 1.99 +/- 0.65 1451.90 +/- 112.80 0.48 +/- 0.31 3.64 +/- 0.80 3.16 +/- 0.21 2.40 +/- 1.00 1.32 +/- 0.25 3.99 +/- 0.30 0.14 +/- 0.02 0.13 +/- 0.02 10.36 +/- 1.63 0.06 +/- 0.01 8.99 +/- 0.19 5.19 +/- 0.30 1.98 +/- 0.86 11.70 +5.10 0.75 +/- 0.05 15.58 +/- 4.10 29.21 +/- 3.10 12.96 +/- 0.73 3.41 +/- 1.04 1.36 +/- 0.63 1396.20 +/- 154.20 1.64 +/- 1.02 3.11 +/- 0.22 3.96 +/- 0.77 7.91 +/- 1.73 14.78 +/- 1.01 3.13 +/- 1.14 3.30 +/- 1.30 4.01 +/- 1.18 6.71 +/- 1.03 2.01 +/- 0.16 1.53 +/- 0.67 0.80 +/- 1.05 0.46 +/- 0.09 1.42 +/- 0.57 0.69 +/- 0.26 3.70 +/- 2.60 4.09 +/- 0.25 2.17 +/- 0.66 1409.50 +/- 111.40 0.97 +/- 0.38 3.39 +/- 0.82 3.00 +/- 0.19 2.07 +/- 0.69 1.29 +/- 0.36 4.15 +/- 0.29 0.14 +/- 0.02 0.13 +/- 0.02 9.06 +/- 1.55 0.06 +/- 0.01 8.94 +/- 0.13 5.14 +/- 0.21 2.13 +/- 0.60 9.60 +/- 3.75 0.77 +/- 0.03 14.44 +/- 2.98 31.45 +/- 2.43 12.64 +/- 0.52 3.17 +/- 0.77 1.61 +/- 0.45 1329.30 +/- 87.25 2.24 +/- 0.74 2.94 +/- 0.15 3.96 +/- 0.53 7.34 +/- 0.92 14.31 +/- 0.70 3.81 +/- 0.80 3.75 +/- 0.92 3.38 +/- 0.83 6.59 +/- 0.76 2.28 +/- 0.14 1.70 +/- 0.48 1.16 +/- 0.69 0.43 +/- 0.06 1.43 +/- 0.39 0.69 +/- 0.18 5.60 +/- 1.98 4.25 +/- 0.20 2.08 +/- 0.46 1430.70 +/- 79.27 0.72 +/- 0.24 3.52 +/-.0.57 3.08 +/- 0.14 2.24 +/- 0.61 1.31 +/- 0.22 4.07 +/- 0.21 0.14 +/- 0.01 0.13 +/- 0.01 9.71 +/- 1.13 Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Fail Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass 0.07 +/- 0.01 0.82 +/- 0.64 3.73 +/- 0.86 0.08 +/- 0.01 1.58 +/- 0.72 5.51 +/- 1.09 0.08 +/- 0.01 1.20 +/- 0.48 4.62 +/- 0.69 151

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report TABLE A-5. In-House "Duplicate" Samples Concentration (pCi/L)a Averaged Lab Code Date Analysis First Result Second Result Result Acceptance DW-80255, 80256.

DW-80255, 80256 DW-80259, 80260 DW-80301, 80302 DW-80301, 80302 SO-1913,1914 DW-80313, 80314 DW-80313, 80314 SWU-2087, 2088 LW-2297, 2298 LW-2321, 2322 BS-2063, 2064 SG-2229, 2230 W-2792,2793 SG'-2229,2230 F-2850, 2851 DW-80376,80377 DW-80376, 80377 MI-2363, 2364 SG-2752,2753 SG-2752, 2753 SG-2752, 2753 SG-2752,2753 SG-2752, 2753 DW-80389, 80390 DW-80389, 80390 DW-80392, 80393 DW-80394, 80395 BS-2490, 2491 WW-2462,2463 W-2826,2827 W-2826,2827 SG-3378, 3379 SG-3378, 3379 SG-3393, 3394 SG-3393, 3394 SG-3393, 3394 SG-3393, 3394 SG-3393, 3394 LW-2939, 2940 WW-3053,3054 SW-3154, 3155 4/8/2008 4/8/2008 4/8/2008 4/11/2008 4/11/2008 4/15/2008 4/16/2008 4/16/2008 4/29/2008 4/30/2008 4/30/2008 5/1/2008 5/5/2008 5/5/2008 5/5/2008 5/7/2008 5/9/2008 5/9/2008 5/14/2008 5/14/2008 5/14/2008 5/14/2008 5/14/2008 5/14/2008 5/14/2008 5/14/2008 5/14/2008 5/14/2008 5/16/2008 5/19/2008 5/27/2008 5/27/2008 6/2/2008 6/2/2008 6/4/2008 6/4/2008 6/4/2008 6/4/2008 6/4/2008 6/12/2008 6/17/2008 6/24/2008 Ra-226 Ra-228 Gr. Alpha Ra-226 Ra-228 K-40 Ra-226 Ra-228 Gr. Beta Gr. Beta Gr. Beta Gr. Beta Ac-228 Gr. Beta Pb-214 Cs-137 Ra-226 Ra-228 K-40 Be-7 Cs-1 37 Gr. Alpha Gr. Beta K-40 Ra-226 Ra-228 Gr. Alpha U-233/4 Cs-1 37 H-3 Gr. Alpha Gr. Beta Gr. Alpha Gr. Beta Be-7 Cs-1 37 Gr. Alpha Gr. Beta K-40 Gr. Beta Gr. Beta Gr. Beta 0.19 +/- 0.08 1.79 +/- 0.57 3.39 +/- 0.82 0.47 +/- 0.09 1.02 +/- 0.42 12.79 +/- 0.73 3.39 +/- 0.22 4.27 +/- 0.72 2.20 +/- 0.60 1.41 +/- 0.43 1.33 +/- 0.54 13.71 +/- 2.06 26.25 +/- 2.70 7.20 +/- 2.30 23.28 +/- 0.30 3.37 +/- 0.21 0.94 +/- 0.13 2.05 +/- 0.57 1335.40 +/- 111.20 264.60 +/- 83.90 64.80 +/- 6.00 19.35 +/- 3.48 30.53 +/- 2.40 9121.90 +/- 191.80 2.99 +/- 0.36 2.87 +/- 0.68 19.94 +/- 1.30 2.03 +/- 0.27 6.81 +/- 1.20 158.61 +/- 80.90 3.47 +/- 2.23 10.67 +/- 1.92 6.51 +/- 1.15 16.23 +/- 0.95 0.82 +/- 0.23 0.07 +/- 0.01 18.96 +/- 3.49 30.01 +/- 2.49 9.78 + 0.30 1.46 +/- 0.59 4.28 +/- 0.83 2.15 +/- 1.01 0.28 +/- 0.11 1.32 +/- 0.55 3.62 +/- 0.82 0.47 +/- 0.09 0.82 +/- 0.45 13.88 +/- 0.85 3.28 +/- 0.21 5.14 +/- 0.77 3.50 +/- 0.90 1.02 +/- 0.40 1.23 +/- 0.54 17.60 +/- 2.49 24.90 +/- 2.55 7.00 +/- 2.50 23.54 +/- 0.33 3.16 +/- 0.19 1.07 +/- 0.13 1.40 +/- 0.51 1510.70 +/- 124.30 222.80 +/- 93.10 68.90 +/- 5.80 22.88 +/- 4.04 33.31 +/- 2.71 9183.70 +/- 194.20

  • 2.58 +/- 0.31 1.73 +/- 0.57 17.89 +/- 1.26 2.54 +/- 0.39

.6.76 +/- 1.23 205.63 +/- 83.06 4.22 +/- 2.20 9.43 +/- 1.76 7.83 +/- 1.32 15.76 +/- 1.06 0.66 +/- 0.33 0.07 +/- 0.01 16.96 +/- 3.34 30.17 +/- 2.56 10.00 +/- 0.28 1.74 +/- 0.59 5.27 +/- 0.91 2.79 +/- 0.97 0.24 1.56 3.51 0.47 0.92 13.34 3.34 4.71 2.85 1.22 1.28 15.66 25.58 7.10 23.41 3.27 1.01 1.73 1423.05 243.70 66.85 21.12 31.92 9152.80 2.79 2.30 18.92 2.29 6.78 182.12 3.84 10.05 7.17 16.00 0.74 0.07 17.96 30.09 9.89 1.60 4.77 2.47

+/- 0.07

+/- 0.40

+/- 0.58

+/- 0.06

+/- 0.31

+/- 0.56

+/- 0.15

+/- 0.53

+/- 0.54

+/- 0.30

+/- 0.38

+/- 1.62

+/- 1.86

+/- 1.70

+/- 0.22

+/- 0.14

+/- 0.09

+/- 0.38

+/- 83.39

+/- 62.66

+/- 4.17

+/- 2.67

+/- 1.81

+/- 136.47

+/- 0.24

+/- 0.44

+/- 0.91

+/- 0.24

+/- 0.86

+/- 57.97

+/- 1.57

+/- 1.30

+/- 0.88

+/- 0.71

+/- 0.20

+/- 0.01

+/- 2.42

+/- 1.79

+/- 0.21

+/- 0.42

+/- 0.61

+/- 0.70 Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass 152

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report TABLE A-5. In-House "Duplicate" Samples Concentration (pCi/L)a Averaged Lab Code Date Analysis First Result Second Result Result Acceptance BS-3245,3246 BS-3245,3246 XW-1080,1081 XW-3786, 3787 G-3274,3275 SL-3295, 3296 AP-3531, 3532 AP-3663, 3664 AP-,3690, 3691 W-4333,4334 W-4840,4841 DW-80415,80416 SG-3964,3965 SG-3964,3965 SG-3964,3965 SG-3964, 3965 SG-3964,3965 DW-80427, 80428 DW-80427, 80428 DW-80451, 80452 DW-80451, 80452 DW-80481, 80482 DW-80481, 80482 MI-3842, 3843 MI-3892, 3893 DW-4067, 4068 SWT-4158, 4159 LW-4221, 4222 LW-4242, 4243 VE-4046, 4047 VE-4046, 4047 VE-4046, 4047 W-4821,4822 W-4821,4822 W-4801,4802 W-4801,4802 DW-80522, 80523 DW-80522, 80523 6/27/2008 6/27/2008 6/30/2008 6/30/2008 7/1/2008 7/1/2008 7/1/2008 7/2/2008 7/2/2008 7/7/2008 7/7/2008 7/7/2008 719/2008 7/9/2008 7/9/2008 7/9/2008 7/9/2008 7/9/2008 7/9/2008 7/15/2008 7/15/2008 7/16/2008 7/16/2008 7/21/2008 7/28/2008 7/29/2008 7/29/2008 7/31/2008 7/31/2008 8/4/2008 8/4/2008 8/4/2008 8/4/2008 8/4/2008 8/5/2008 8/5/2008 8/5/2008 8/5/2008 Co-60 Cs-1 37 Fe-55 Fe-55 Gr. Beta Gr. Beta Be-7 Be-7 Be-7 Gr. Beta Gr. Beta Ra-226 Be-7 Cs-137 Gr. Alpha Gr. Beta K-40 Ra-226 Ra-228 Ra-226 Ra-228 Ra-226 Ra-228 K-40 K-40 Gr. Beta Gr. Beta Gr. Beta Gr. Beta Be-7 Gr. Beta K-40 Gr. Alpha Gr. Beta Gr. Alpha Gr. Beta Ra-226 Ra-228 108.84 952.18 2.96 2.96 7.65 3.76 0.10 0.08 0.07 7.20 6.70 2.81 1.35 0.04 23.17 28.99 6.86 3.25 2.65 1.02 1.09 1.20 1.69 1282.60 1371.50 10.46 1.58 1.35 1.36 0.77 8.81 5.17 1.70 3.90 4.40 13.20 0.50 1.23

+/- 44.14

+/- 52.78

+/- 0.32

+/-,0.32

+/- 0.24

+/- 0.24

+/- 0.01

+/- 0.01

+/- 0.01

+/- 1.90

+/- 1.60

+/- 0.47

+/- 0.23

+/- 0.01

+/- 3.39

+/- 2.12

+/- 0.19

+/- 0.24

+/- 0.67

+/- 0.10

+/- 0.62

+/- 0.13

+/- 0.68

+/- 108.30

+/- 102.90

+/- 2.37

+/- 0.45

+/- 0.56

+/- 0.56

+/- 0.13

+/- 0.36

+/- 0.34

+/- 0.80

+/- 0.80

+/- 2.40

+/- 1.30

+/- 0.12

+/- 0.60 91.10 941.56 2.71 2.71 7.44 3.64 0.08 0.08 0.07 7.70 6.70 2.00 1.51 0.04 18.76 29.25 6.84 3.27 3.25 0.96 1.14 1.40 1.65 1379.00 1501.20 14.25 1.80 0.91 1.18 0.82 8.34 5.33 1.70 3.70 4.80 14.50 0.28 1.09

+/- 22.32

+/- 13.61

+/- 0.30

+/- 0.30

+/- 0.24

+/- 0.24

+/- 0.01

+/- 0.02

+/- 0.01

+/- 1.70

+/- 1.80

+/- 0.34

+/- 0.22

+/- 0.01

+/- 3.24

+/- 2.31

+/- 0.17

+/- 0.20

+/- 0.72

+/- 0.12

+/- 0.60

+/- 0.14

+/- 0.77

+/- 111.40

+/- 111.80

+/- 2.78

+/- 0.47

+/- 0.52

+/- 0.53

+/- 0.19

+/-0.31

+/- 0.42

+/- 0.90

+/- 0.90

+/- 2.30

+/- 1.40

+/- 0.12

+/- 0.57 99.97 +/- 24.73 946.87 +/- 27.25 2.84 +/- 0.22 2.84 +/- 0.22 7.55 +/- 0.17 3.70 +/- 0.17 0.09 +/- 0.01 0.08 +/- 0.01 0.07 +/- 0.01 7.45 +/- 1.27 6.70 +/- 1.20 2.41 +/- 0.29 1.43 +/- 0.16 0.04 +/- 0.00 20.97 +/- 2.34 29.12 +/- 1.57 6.85 +/- 0.13 3.26 +/- 0.16 2.95 +/- 0.49 0.99 +/- 0.08 1.12 +/- 0.43 1.30 +/- 0.10 1.67 +/- 0.51 1330.80 +/- 77.68 1436.35 +/- 75.97 12.36 +/- 1.83 1.69 +/- 0.33 1.13 +/- 0.38 1.27 +/- 0.38 0.80 +/- 0.12 8.58 +/- 0.24 5.25 +/- 0.27 1.70 +/- 0.60 3.80 +/- 0.60 4.60 +/- 1.66 13.85 +/- 0.96 0.39 +/- 0.08 1.16 +/- 0.41 Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass 153

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report TABLE A-5. In-House "Duplicate" Samples Concentration (pCi/L)a Averaged Lab Code Date Analysis First Result Second Result Result Acceptance DW-80531, 80532 DW-80534, 80535 DW-80534, 80535 SG-4584, 4585 SG-4584, 4585 SG-4584, 4585 SG-4584, 4585 SG-4573, 4574 SG-4573, 4574 SG-4584, 4585 SG-4584, 4585 DW-80547, 80548 DW-80551, 80552 DW-80553, 80554 DW-80553, 80554 DW-80566, 80567 DW-80566, 80567 VE-4647, 4648 SL-4690, 4691 ME-4732, 4733 ME-4732, 4733 SG-5180, 5181 SG-5180, 5181 SG-5180, 5181 SG-5180, 5181 SG-5180, 5181 SG-5187, 5188 SG-5187, 5188 SG-5193, 5194 SG-5193, 5194 DW-4871, 4872 VE-5022, 5023 DW-5337, 5338 WW-4977, 4978 BS-5088, 5089 DW-80584, 80585 DW-80584, 80585 DW-80579, 80580 DW-80579, 80580 DW-80579, 80580 G-5389, 5390 G-5389, 5390 G-5389, 5390 8/5/2008 8/5/2008 8/5/2008 8/6/2008 8/6/2008 8/6/2008 8/6/2008 8/13/2008 8/13/2008 8/13/2008 8/13/2008 8/13/2008 8/13/2008 8/13/2008 8/13/2008 8/20/2008 8/20/2008 8/27/2008 9/2/2008 9/2/2008 9/2/2008 9/3/2008 9/3/2008 9/3/2008 9/3/2008 9/3/2008 9/3/2008 9/3/2008 9/3/2008 9/3/2008 9/5/2008 9/10/2008 9/10/2008 9/17/2008 9/19/2008 9/19/2008 9/19/2008 9/25/2008 9/25/2008 9/25/2008 10/1/2008 10/11/2008 10/1/2008 Gr. Alpha Ra-226 Ra-228 Be-7 Cs-137 K-40 Ra-226 Gr. Alpha Gr. Beta Gr. Alpha Gr. Beta Gr. Alpha U-233/4 Ra-226 Ra-228 Ra-226 Ra-228 K-40 Gr. Beta Gr. Beta K-40 Be-7 Cs-137 Gr. Alpha Gr. Beta K-40 Be-7 K-40 Gr. Alpha Gr. Beta 1-131 K-40 Gr. Beta Gr. Beta K-40 U-233/4 U-238 Gr. Alpha Ra-226 Ra-228 Be-7 Gr. Beta K-40 18.90 3.01 2.24 7.11 0.05 7.88 3.94 240.72 201.60 14.07 22.08 3.33 2.57 0.92 2.20 1.10 2.01 1.97 2.28 2.86 2.44 15.50 0.07 18.74 29.19 8.55 6.18 7.16 5.80 15.60 1.15 1.27 3.00 3.71 10493 3.01 0.70 10.69 3.13 3.03 1.49 10.86 7.42

+/- 1.86

+/- 0.18

+/- 0.59

+/- 0.20

+/- 0.01

+/- 10.18

+/- 0.18

+/- 8.74

+/- 4.28

+/- 3.10

+/- 2.36

+1.11

+ 0.48

+0.14

+/-+0.61

_+0.11

  • 0.58

+0.17

- 0.25

+/- 0.09

+/- 0.37

+/- 0.43

+/- 0.01

+ 3.33

+/-+2.10

+/- 0.32

+/- 0.54

+ 0.60

+ 1.30

+/-+1.10

+/- 0.27

+/- 0.14

+/- 1.07

+/- 1.10

+/- 607

+/- 0.52

+/- 0.25

+/- 1.31

+/- 0.22

+/- 0.73

+/- 0.32

+/- 0.24

+/- 0.67 17.80 +/- 1.96 3.33 +/- 0.18 2.12 +/- 0.59 7.44 +/- 0.37 0.04 +/- 0.01 8.02 +/- 0.21 3.74 +/- 0.22 251.53 +/- 9.56 206.88 +/- 4.71 12.97 +/- 3.04 23.02 +/- 2.34 3.88 +/- 1.07 2.13 + 0.46 1.21 +/-+0.17 1.64 +/- 0.56 1.10 +/- 0.10 1.74 +/- 0.58 2.00 +/- 0.21 2.35 +/- 0.24 2.70 +/- 0.09 2.82 +/- 0.51 15.54 +/- 0.38 0.07 +/- 0.01 17.61 +/- 3.15 28.49 +/- 2.15 8.11 +/- 0.27 5.90 +/- 0.77 7.29 +/- 0.60 7.00 +/- 1.50 15.60 +/- 1.10 1.16 +/- 0.31 1.11 +/- 0.06 2.19_+/- 1.05 2.32 +/- 1.11 10299 +/-470 2.44 +/- 0.47 0.27 +/- 0.18 12.84 +/- 1.51 2.89 +/- 0.21 1.98 +/- 0.69 1.36 +/- 0.28 11.18 +/- 0.25 8.06 +/- 0.63 18.35 +/- 1.35 3.17 +/- 0.13 2.18 +/- 0.42 7.27 +/- 0.21 0.04 +/- 0.00 7.95 +/- 5.09 3.84 +/- 0.14 246.13 +/- 6.48 204.24 +/- 3.18 13.52 +/- 2.17 22.55 +/- 1.66 3.61 +/- 0.77 2.35 +/- 0.33 1.07 +/- 0.11 1.92 +/- 0.41 1.10 +/- 0.07 1.88 +/- 0.41 1.99 +/- 0.14 2.32 +/- 0.17 2.78 +/- 0.06 2.63 +/- 0.32 15.52 +/- 0.29 0.07 +/- 0.01 18.18 +/- 2.29 28.84 +/- 1.50 8.33 +/- 0.21 6.04 +/- 0.47 7.23 +/- 0.42 6.40 +/- 0.99 15.60 +/-0.78 1.16 +/- 0.21 1.19 +/- 0.08 2.60 +/- 0.75 3.01 +/- 0.78 10396 +/-384 2.73 +/- 0.35 0.49.+/- 0.15 11.77 +/- 1.00 3.01 +/- 0.15 2.51 +/- 0.50 1.43 +/- 0.21 11.02 +/- 0.17 7.74 +/- 0.46 Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass 154

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report TABLE A-5. In-House "Duplicate" Samples Concentration (pCi/L)a Averaged Lab Code Date Analysis First Result Second Result Result Acceptance AP-5814, 5815 SG-6111, 6112 SG-6111, 6112 DW-80592, 80593 DW-80594, 80595 DW-80650, 80651 DW-80650, 80651 DW-80629, 80630 DW-80629, 80630 DW-80663, 80664 MI-5572, 5573 MI-5603, 5604 DW-80676, 80677 DW-80676, 80677 DW-80676, 80677 SW-80687, 80688 DW-80729, 80730 DW-80729, 80730 DW-80738, 80739 DW-80747, 80748 DW-80747, 80748 BS-6271, 6272 SS-6593,6594 MI-7046, 7047 DW-80698, 80699 DW-80698, 80699 SW-7281, 7282 10/1/2008 10/6/2008 10/6/2008 10/7/2008 10/7/2008 10/8/2008 10/8/2008 10/13/2008 10/13/2008 10/13/2008 10/14/2008 10/14/2008 10/20/2008 10/20/2008 10/20/2008 10/22/2008 10/30/2008 10/30/2008 10/31/2008 10/31/2008 10/31/2008 11/3/2008 11/19/2008 12/16/2008 12/23/2008 12/23/2008 12/30/2008 Be-7 Gr. Alpha Gr. Beta Gr. Alpha Ra-228 Gr. Alpha Gr. Beta Ra-226 Ra-228 Gr. Alpha K-40 K-40 Gr. Alpha Ra-226 Ra-228 Gr. Alpha Gr. Alpha Gr. Beta U-233/4 Ra-226 Ra-228 Gr. Beta K-40 K-40 Ra-226 Ra-228 Gr. Beta 0.08 +/- 0.01 9.34 +/- 1.82 17.46 +/- 1.46 2.30 +/- 1.14 1.41 +/- 0.55 1.30 +/- 0.86 2.92 +/- 0.69 3.12 +/- 0.18 2.71 +/- 0.80 5.91 +/- 1.70 1391.00 +/- 97.39 1412.80 +/- 109.30 12.20 +/- 1.48 5.04 +/- 0.25 5.87 +/- 0.86 3.42 +/- 1.03 8.40 +/- 1.45 16.94 +/- 1.45 2.94 +/- 0.50 0.60 +/- 0.09 1.33 +/- 0.59 12.26 +/- 1.69 12.35 +/- 0.57 1380.10 +/- 109.80 3.13 +/- 0.22 5.48 +/- 0.91 0.87 +/- 0.54 0.08 +/- 0.01 8.95 +/- 1.67 18.86 +/- 1.35 1.57 +/- 0.88 1.22 +/- 0.50 0.12 +/- 0.79 3.03 +/- 0.64 2.87 +/- 0.17 3.28 +/- 0.81 3.14 +/- 1.44 1443.90 +/- 110.60 1413.80 +/- 110.50 11.87 +/- 1.54 5.10 +/- 0.25 6.98 +/- 0.95 2.98 +/- 1.01 7.76 +/- 2.00 15.41 +/- 1.37 3.06 + 0.63 0.50 + 0.08 1.38 +/-0.60 13.78 +/- 1.84 13.10 + 0.76 1477.30 +/- 98.32 3.21 +/- 0.23 5.86 +/- 0.93 1.35 +/-0.54 0.08 +/- 0.01 9.15 +/- 1.24 18.16+/- 0.99 1.94 +/- 0.72 1.32 +/- 0.37 0.71 +/- 0.58 2.98 +/- 0.47 3.00 +/- 0.12 3.00 +/- 0.57 4.53 +/- 1.11 1417.45 +/- 73.68 1413.30 +/- 77.71 12.04 +/- 1.07 5.07 +/- 0.18 6.43 +/- 0.64 3.20 +/- 0.72 8.08 +/- 1.24 16.18 +/- 1.00 3.00 +/- 0.40 0.55 +/- 0.06 1.36 +/- 0.42 13.02 +/- 1.25 12.73 +/- 0.48 1428.70 +/- 73.69 3.17 +/- 0.16 5.67 +/- 0.65 1.11 +/- 0.38 Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Note: Duplicate analyses are performed on every twentieth sample received in-house. Results are not listed for those analyses with activities that measure below the LLD.

a Results are reported in units of pCi/L, except for air filters (pCi/Filter), food products, vegetation, soil, sediment (pCi/g).

155

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report TABLE A-6. Department of Energy's Mixed Analyte Performance Evaluation Program (MAPEP)a.

Concentration b Known Control Lab Codec Date Analysis Laboratory result Activity Limits d Acceptance STW-1 137 STW-1 137 STW-1 137 STW-1 137e STVW-1137e STW-1137 STW-1137 STW-1 137 STW-1 137 STW-1137 STW-1137 STW-1137 STW-1137 STW-1137 STW-1137 STW-1 137 STW-1 138 STW-1 138 STAP-1 139 STAP-1 139 STAP-1 139 STAP-1 139 STAP-1 139 STAP-1 139 STAP-1 139 STAP-1 139 STAP-1 139e STAP-1 139e STAP-1 139 STAP-1 140 STAP-1 140 STVE-1 141 STVE-1 141 STVE-1 141 STVE-1 141 STVE-1 141 STVE-1 141 01/01/08 01/01/08 01/01/08 01/01/08 01/01/08 01/01/08 01/01/08 01/01/08 01/01/08 01/01/08 01/01/08 01/01/08 01/01/08 01/01/08 01/01/08 01/01/08 Am-241 Co-57 Co-60 Cs-134 Cs-1 37 Fe-55 H-3 Mn-54 Ni-63 Pu-238 Pu-239/40 Sr-90 Tc-99 U-233/4 U-238 Zn-65 1.27 +/- 0.06 23.80 + 0.60 8.60 + 0.50

-0.021 + 0.10 0.00 + 0.10 32.60 + 11.60 515.10 +/- 12.70 12.90 +/- 0.80 29.50 +/- 2.30 0.60 +/- 0.06 0.019 +/- 0.015 12.00 +/- 1.50 9.40 +/- 1.70 3.37 +/- 0.20 3.63 +/- 0.21 16.90 +/- 1.40 1.23 22.80 8.40 0.00 0.00 36.50 472.00 12.10 30.70 0.73 0.01 11.40 11.20 3.63 3.74 16.30 0.86-1.60 16.00 - 29.60 5.88 - 10.92

-1.00- 1.00

-1.00-1.00 25.60 - 47.50 330.00 - 614.00 8.50 - 15.70 21.50 - 39.90 0.51 - 0.95 0.00-1.00 7.98-14.82 7.80 - 14.60 2.54 - 4.72 2.62 - 4.86 11.40 - 21.20 01/01/08 Gr. Alpha 01/01/08 Gr. Beta 0.96 +/- 0.14 2.30 +/- 0.15 1.40 0.00 - 2.80 2.43 1.22 - 3.65 01/01/08 01/01/08 01/01/08 01/01/08 01/01/08 01/01/08 01/01/08 01/01/08 01/01/08 01/01/08 01/01/08 Co-57 Co-60 Cs-1 34 Cs-1 37 Mn-54 Pu-238 Pu-239/40 Sr-90 U-233/4 U-238 Zn-65 3.90 +/- 0.07 1.43 +/- 0.07 2.59 +/- 0.16 3.05 +/- 0.12 0.43 +/- 0.58 0.080 +/- 0.016 0.12 +/- 0.02 1.30 +/- 0.27 0.43 +/- 0.03 0.44 +/- 0.03 2.36 +/- 0.18 0.11 +/- 0.03 0.34 +/- 0.04 8.30 +/- 0.18 3.03 +/- 0.13 6.53 +/- 0.29 3.90 +/- 0.19 5.43 +/- 0.21 0.033 +/- 0.10 3.55 1.31 2.52 2.70 0.00 0.11 0.11 1.55 0.22 0.23 2.04 2.49-4.62 0.92-1.70 1.76 - 3.28 1.89-3.51 0.00 - 1.00 0.07-0.14 0.08 -0.15 1.08 -2.01 0.15 -0.28 0.16 -0.29 1.43 -2.65 Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Fail Fail Pass Pass Pass Pass Pass Pass Pass Pass Pass 01/01/08 Gr. Alpha 01/01/08 Gr. Beta 0.35 0.00 - 0.70 0.29 0.14-0.43 01/01/08 01/01/08 01/01/08 01/01/08 01/01/08 01/01/08 Co-57 Co-60 Cs-1 34 Cs-1 37 Mn-54 Zn-65 6.89 2.77 6.28 3.41 4.74 0.00 4.82 - 8.96 1.94-3.60 4.40 -8.16 2.39 - 4.43 3.32 -6.16 0.00 - 1.00 156

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report TABLE A-6. Department of Energy's Mixed Analyte Performance Evaluation Program (MAPEP)a.

Concentration b Known Control Lab Codec Date Analysis Laboratory result Activity Limits d Acceptance STSO-1 142 STSO-1 142 STSO-1 142 STSO-1 142 STSO-1 142 STSO-1 142 STSO-1142 STSO-1 142 STSO-I 142 STSO-1 142 STSO-1 142 STSO-1 158 STSO-1 158 STSO-1 158 STSO-1 158 STSO-1 158 STSO-1 158 STSO-1 158 STSO-1158 STSO-1 158 STSO-1 158 STSO-1 158 STSO-1158 STSO-1 158 STSO-1 158 STVE-1 159 STVE-1 159 STVE-1 159 STVE-1 159 STVE-1 159 STVE-1 159 01/01/08 01/01/08 01/01/08 01/01/08 01/01/08 01/01/08 01/01/08 01/01/08 01/01/08 01/01/08 01/01/08 08/01/08 08/01/08 08/01/08 08/01/08 08/01/08 08/01/08 08/01/08 08/01/08 08/01/08 08/01/08 08/01/08 08/01/08 08/01/08 08/01/08 08/01/08 08/01/08 08/01/08 08/01/08 08/01/08 08/01/08 Co-57 Co-60 Cs-1 34 Cs-1 37 Mn-54 Ni-63 Pu-238 Pu-239/40 U-233/4 U-238 Zn-65 Am-241 Co-57 Co-60 Cs-134 Cs-1 37 K-40 Mn-54 Ni-63 Pu-238 Pu-239/40 Sr-90 Tc-99 U-238 Zn-65 Co-57 Co-60 Cs-134 Cs-137 Mn-54 Zn-65 483.00 +/- 3.00 3.00 +/- 0.80 896.50 +/- 7.40 624.40 +/- 4.10 667.20 +/- 3.80 536.00 +/- 15.50 78.60 + 4.80 89.10 + 4.50 134.41 + 5.40 139.00 + 5.50 0.093 + 0.91 57.73 +/- 4.78 353.02 + 2.01 151.99 + 1.58 499.72 + 2.65 2.54 + 0.25 643.94 +/- 15.50 452.14 +/- 2.96 803.09 +/- 17.01 0.12 +/- 0.54 60.88 + 5.89 1.95 + 2.04 337.00 + 17.30 315.67 + 11.29 0.10 + 2.04 421.00 2.90 854.00 545.00 570.00 640.00 72.80 90.10 142.00 148.00 0.00 69.10 333.00 145.00 581.00 2.80 570.00 415.00 760.00 0.00 55.60 0.00 335.00 303.00 0.00 295.00 - 547.00 0.00-5.00 598.00 -1110.00 382.00 - 709.00 399.00- 741.00 448.00 - 832.00 51.00 -94.60 63.10-117.10 99.00 - 185.00 104.00 - 192.00 0.00-1.00 48.40 - 89.80 233.00 - 433.00 102.00 - 189.00 407.00 - 755.00 0.00-5.00 399.00- 741.00 291.00- 540.00 532.00 - 988.00 0.00-5.00 38.90 - 72.30 0.00-5.00 235.00 - 436.00 212.00- 394.00 0.00 - 5.00 5.00 - 9.20 3.30 -6.10 3.90 - 7.20 0.00 - 1.00 4.10-7.50 4.80 - 9.00 Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass 8.52 +/- 0.23 5.08 +/- 0.19 5.26 +/- 0.18 0.01 +/- 0.14 6.39 +/- 0.28 7.73 +/- 0.45 7.10 4.70 5.50 0.00 5.80 6.90 157

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report TABLE A-6. Department of Energy's Mixed Analyte Performance Evaluation Program (MAPEP)a.

Concentration b Known Control Lab Codec Date Analysis Laboratory result Activity Limits d Acceptance STW-1 162 STW-1 162 STW-1 162 STW-1 162 STW-1 162 STW-1162 STW-1162 STW-1 162 STW-1162 STW-1 162 STW-1 162 STW-1 162 STW-1 162 STW-1 162 STW-1162 STW-1162 STW-1163 STW-1 163 08/01/08 08/01/08 08/01/08 08/01/08 08/01/08 08/01/08 08/01/08 08/01/08 08/01/08 08/01/08 08/01/08 08/01/08 08/01/08 08/01/08 08/01/08 08/01/08 Am-241 Co-57 Co-60 Cs-1 34 Cs-1 37 Fe-55 H-3 Mn-54 Ni-63 Pu-238 Pu-239/40 Sr-90 Tc-99 U-233/4 U-238 Zn-65 0.20 +/- 0.06 0.03 +/- 0.16 11.27 +/- 0.23 17.93 +/- 0.52 23.72 +/- 0.43 43.36 +/- 16.81 385.15 +/- 8.93 13.87 +/- 0.37 10.77 +/- 2.01 0.33 +/- 0.06 0.14 +/- 0.15 6.49 +/- 1.12 1.80 +/- 0.62 3.33 +/- 0.18 3.38 +/- 0.18 17.64 +/- 0.61 0.08 +/- 0.04 0.12 +/- 0.05 0.00 0.00 11.60 19.50 23.60 46.20 341.00 13.70 0.00 0.50 0.00 6.45 3.76 3.44 3.55 17.10 0.00 -0.10 0.00 - 5.00 8.10 - 15.10 13.70 - 25.40 16.50 - 30.70 32.30 - 60.10 239.00 - 443.00 9.60 - 17.80 0.00 - 5.00 0.40 - 0.70 0.00 - 0.20 4.52-8.39 2.63 - 4.89 2.41 - 4.47 2.49 - 4.62 12.00 - 22.20 Fail Pass Pass Pass Pass Pass Pass Pass Fail Fail Pass Pass Fail Pass Pass Pass Pass Pass 08/01/08 Gr. Alpha 08/01/08 Gr. Beta 0.00 0.00 - 0.56 0.00 0.00 - 1.85 a Results obtained by Environmental, Inc., Midwest Laboratory as a participant in the Department of Energy's Mixed Analyte Performance Evaluation Program, Idaho Operations office, Idaho Falls, Idaho b Results are reported in units of Bq/kg (soil), Bq/L (water) or Bq/total sample (filters, vegetation).

c Laboratory codes as follows: STW (water), STAP (air filter), STSO (soil), STVE (vegetation).

d MAPEP results are presented as the known values and expected laboratory precision (1 sigma, 1 determination) and control limits as defined by the MAPEP.

e The results of a repeat analysis were still unacceptable. A spiked air filter was prepared (known activity 4.17 pCi/filter) to verify the methodology; results of the spike analysis were acceptable, 4.64 pCi/filter.

f Corrected result. An error in calculation was found.

g Included in the testing series as a "false positive". Result of reanalysis, 0.04 t 0.01 Bq/L.

h Included in the testing series as a "false positive". Result of reanalysis, 3.78 +/- 2.03 Bq/L.

'The reason for the deviation is unknown. Result of the original sample recount: 0.47 +/- 0.07 Bq/L.

The analysis was then repeated from the beginning. Result of reanalysis: 0.51 +/- 0.07 Bq/L.

1The lower result was due to a higher than average background count used in the calculation. Average background result:, 4.11 +/- 0.66 Bq/L.

158

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report TABLE A-7. Interlaboratory Comparison Crosscheck program, Environmental Resource Associates (ERA)a.

Concentration (pCi/L)

Lab Code b Date Analysis Laboratory ERA Control Result c Result d Limits Acceptance STAP-1 143 STAP-1 143 STAP-1 143 STAP-1 143 STAP-1 143 STAP-1 143 STAP-1 143 STAP-1 143 STAP-1 143 STAP-1 143 STAP-1 143 STAP-1 143 STAP-1 143 STAP-1 144 STAP-1 144 03/24/08 03/24/08 03/24/08 03/24/08 03/24/08 03/24/08 03/24/08 03/24/08 03/24/08 03/24/08 03/24/08 03/24/08

.03/24/08

  • Am-241 Co-60 Cs-134 Cs-1 37 Fe-55 Mn-54 Pu-238 Pu-239/40 Sr-90 U-233/4 U-238 Uranium Zn-65 60.48 +/- 3.52 650.72 +/- 3.00 467.50 +/- 5.53 1375.90 +/- 25.41 145.60 +/- 28.94 0.00 +/- 0.00 53.65 +/- 1.54 70.44 +/- 3.11 157.60 +/- 7.70 62.15 +/- 3.41 64.11 +/- 3.29 128.40 +/- 3.29 889.90 +/- 15.90 13.08 +/- 1.09 99.90 +/- 3.09 50.1 730.0 523.0 1450.0 241.0 0.0 46.8 64.1 152.0 66.7 66.2 136.0 872.0 8.8 92.2 29.3 - 68.7 565.0 - 912.0 341.0 - 647.0 1090.0 - 1900.0 106.0 - 375.0 0.0 - 10.0 32.1 -61.5 46.5 - 83.0 66.9 - 236.0 42.0 - 98.8 42.4 - 94.0 69.5 -216.0 604.0 - 1210.0 4.56 - 13.2 56.80 - 135.0 Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass 03/24/08 Gr. Alpha 03/24/08 Gr. Beta STSO-1 145 STSO-1 145 STSO-1 145 STSO-1 145 STSO-1 145 STSO-1 145 STSO-1 145 STSO-1 145 STSO-1 145 e STSO-1 145 STSO-1 145 STSO-1 145 STSO-1 145 STSO-1145 f STSO-1 145 STSO-i 145 STSO-1 145 03/24/08 03/24/08 03/24/08 03/24/08 03/24/08 03/24/08 03/24/08 03/24/08 03/24/08 03/24/08 03/24/08 03/24/08 03/24/08 03/24/08 03/24/08 03/24/08 03/24/08 Ac-228 Am-241 Bi-212 Bi-214 Co-60 Cs-1 34 Cs-1 37 K-40 Mn-54 Pb-212 Pb-214 Sr-90 Th-234 U-233/4 U-238 Uranium Zn-65 1269.02 +/- 36.81 1268.50 +/- 85.80 1407.10 +/- 56.64 2145.50 +/- 305.63 5219.70 +/- 90.30 5427.30 +/- 102.94 6346.60 +/- 201.80 11052.70 +/- 181.80 0.00 +/- 0.00 1198.20 +/- 96.58 2253.30 +/- 291.60 6407.00 +/- 277.00 2421.80 +/- 321.00 1227.93 +/- 91.52 1319.90 +/- 48.81 2592.00 +/- 140.50 2936.20 +/- 73.50 1180.0 1230.0 1360.0 1790.0 5130.0 5640.0 6010.0 11000.0 0.0 1080.0 2020.0 5360.0 2030.0 2050.0 2030.0 4180.0 2660.0 757.0 - 1660.0 735.0 - 1580.0 357.0 - 2030.0 1100.0 -2570.0 3730.0 - 6890.0 3630.0 - 6790.0 4600.0 - 7810.0 7980.0 -14900.0 0.0-10.0 697.0 - 1520.0 1210.0 -3010.0 1940.0 - 8750.0 644.0 - 3870.0 1240.0 - 2580.0 1240.0 -2580.0 2380.0 - 5640.0 2110.0 -3570.0 Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Fail Pass Pass Pass 159

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report TABLE A-7. Interlaboratory Comparison Crosscheck program, Environmental Resource Associates (ERA)'.

Concentration (pCi/L)

Lab Code b Date Analysis Laboratory ERA Control Result c Result d Limits Acceptance STVE-1 146 STVE-1 146 STVE-1 146 STVE-1 146 STVE-1 146 STVE-1 146 STVE-1146 e STVE-1 146 STVE-1 146 STVE-1 146 STVE-1 146 STVE-1 146 STW-1 147 STW-1 147 STW-1147 STW-1 147 STW-1 147 STW-1 147 e STW-1 147 STW-1 147 STW-1 147 STW-1147 STW-1147 STW-1 147 STW-1147 STW-1120 STW-1 120 03/24/08 03/24/08 03/24/08 03/24/08 03/24/08 03/24/08 03/24/08 03/24/08 03/24/08 03/24/08 03/24/08 03/24/08 03/24/08 03/24/08 03/24/08 03/24/08 03/24/08 03/24/08 03/24/08 03/24/08 03/24/08 03/24/08 03/24/08 03/24/08 03/24/08 03/19/07 Am-241 Cm-244 Co-60 Cs-1 34 Cs-1 37 K-40 Mn-54 Sr-90 U-233/4 U-238 Uranium Zn-65 Am-241 Co-60 Cs-134 Cs-137 Fe-55 Mn-54 Pu-238 Pu-239140 Sr-90 U-233/4 U-238 Uranium Zn-65 Uranium 1261.50 +/- 73.90 1152.50 +/- 57.44 912.41 +/- 13.59 1547.70 +/- 38.81 1163.80 +/- 20.62 22186.00 +/- 339.40 0.00 +/- 0.00 3825.90 +/- 140.66 2753.30 +/- 227.90 2697.10 +/- 143.20 5586.10 +/- 155.20 1676.80 +/- 43.00 97.56 +/- 1.02 1430.00 +/- 33.33 730.18 +/- 33.39 1947.80 +/- 13.80 1422.70 +/- 172.16 0.00 +/- 0.00 144.16 +/- 4.54 82.16 +/- 2.50 512.03 +/- 43.37 74.40 +/- 1.20 75.10 +/- 1.35 152.10 +/- 2.55 708.90 +/- 29.00 339.60 +/- 10.66 2009.00 +/- 36.40 1260.0 1200.0 888.0 1540.0 1100.0 24600.0 0.0 4130.0 3070.0 3050.0 6260.0 1430.0 90.9 1420.0 751.0 1990.0 2080.0 0.0 135.0 80.7 512.0 81.0 80.3 165.0 694.0 391.0 718.0 - 1730.0 591.0 - 1870.0 600.0 - 1280.0 882.0 - 2130.0 807.0 - 1530.0 17700.0 - 34800.0 0.0-10.0 2310.0 - 5480.0 2110.0 - 4070.0 2140.0 - 3850.0 4300.0 - 8080.0 1030.0 - 1960.0 62.0 - 124.0 1240.0 - 1680.0 555.0 - 862.0 1690.0 - 2380.0 1210.0 - 2780.0 0.0 - 10.0 102.0 - 168.0 62.4 -99.8 325.0 - 684.0 61.0-104.0 61.3 - 99.5 119.0 -220.0 588.0 - 865.0 282.0 - 521.0 Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass 03/19/07 Zn-65 1910.0 1600.0 -2410.0 a Results obtained by Environmental, Inc., Midwest Laboratory as a participant in the crosscheck program for proficiency testing administered by Environmental Resources Associates, serving as a replacement for studies conducted previously by the Environmental Measurements Laboratory Quality Assessment Program (EML).

b Laboratory codes as follows: STW (water), STAP (air filter), STSO (soil), STVE (vegetation).

c Unless otherwise indicated, the laboratory result is given as the mean +/- standard deviation for three determinations.

d Results are presented as the known values, expected laboratory precision (1 sigma, 1 determination) and control limits as provided by ERA.

e Included in the testing series as a "false positive". No activity expected.

f The analysis was repeated by leaching and total dissolution methods. Total dissolution yielded results within expected range.

Results of the reanalysis: U-233,4, 1655 +/- 95 pCi/kg. U-238 1805 +/- 97 pCi/kg.

160

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report APPENDIX B DATA REPORTING CONVENTIONS 161

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Data Reporting Conventions 1.0.

All activities, except gross alpha and gross beta, are decay corrected to collection time or the end of the collection period.

2.0. Single Measurements Each single measurement is reported as follows:

x +/- s where:

x = value of the measurement; s = 2s counting uncertainty (corresponding to the 95% confidence level).

In cases where the activity is less than the lower limit of detection L, it is reported as: <L, where L = the lower limit of detection based on 4.66s uncertainty for a background sample.

3.0. Duplicate analyses 3.1 Individual results: For two analysis results; xi +/- sl and x2 +/- S2 Reported result:

x +/- s; where x = (1/2) (xi + x2) and s = (1/2)

+S2 3.2.

Individual results:

<L1, <L2 Reported result: <L, where L = lower of Li and L2 3.3.

Individual results:

x +/- s, <L Reported result:

x +/- s if x > L; <L otherwise.

4.0. Computation of Averages and Standard Deviations 4.1 Averages and standard deviations listed in the tables are computed from all of the individual measurements over the period averaged; for example, an annual standard deviation would not be the average of quarterly standard deviations. The average x and standard deviation s of a set of n numbers x1, x2... xn are defined as follows:

X =

EX Sx" n

n-1

.4.2 Values below the highest lower limit of detection are not included in the average.

4.3 If all values in the averaging group are less than the highest LLD, the highest LLD is reported.

4.4 If all but one of the values are less than the highest LLD, the single value x and associated two sigma error is reported.

4.5 In rounding off, the following rules are followed:

4.5.1.

If the number following those to be retained is less than 5, the number is dropped, and the retained numbers are kept unchanged. As an example, 11.443 is rounded off to 11.44.

4.5.2. If the number following those to be retained is equal to or greater than 5, the number is dropped and the last retained number is raised by 1. As an example, 11.445 is rounded off to 11.45.

162

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report APPENDIX C Maximum Permissible Concentrations of Radioactivity in Air and Water Above Background in Unrestricted Areas 163

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Table C-1.

Maximum permissible concentrations of radioactivity in air and water above natural background in unrestricted areasa.

Air (pCi/m 3 )

Water (pCi/L)

Gross alpha Gross beta Iodine-1 3 1b 1 x i0- 3 1

2.8 x 10-1 Strontium-89 Strontium-90 Cesium-137 Barium-140 Iodine-1 31 Potassium-40c Gross alpha Gross beta Tritium 8,000 500 1,000 8,000 1,000 4,000 2

10 1 x 106 a Taken from Table 2 of Appendix B to Code of Federal Regulations Title 10, Part 20, and appropriate footnotes.

Concentrations may be averaged over a period not greater than one year.

b Value adjusted by a factor of 700 to reduce the dose resulting from the air-grass-cow-milk-child pathway.

c A natural radionuclide.

164

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report APPENDIX D REMP SAMPLING

SUMMARY

165

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Table 4.5 Radiological Environmental Monitoring Program Summary Name of Facility Location of Facility Davis-Besse Nuclear Power Station Docket No.

Reporting Period 50-346 January-December, 2008 Ottawa, Ohio

( County, State)

Indicator Location with Highest Control Number Sample Type and Locations Annual Mean Locations Non-Type Number of LLDb Mean (F)c Mean (F)c Mean (F)c Routine Results (Units)

Analysesa Rangec Locationd Range' Rangec 0.026 0.026 Airborne GB 519 0.005 (311/311)

T-4, Site Boundary 0.027 (52/52)

(208/208) 0 Particulates (0.006-0.055) 0.8 mi. S (0.009-0.045)

(0.006-0.047).

(pCi/m 3)

Sr-89 40 0.0009

< LLD

< LLD 0

Sr-90 40 0.0005

< LLD

< LLD 0

GS 40 T-1 1, Ottawa Be-7 0.015 0.083 (24/24)

County 0.091 (4/4) 0.085 (16/16) 0 (0.056-0.101)

WTP, 9.5 mi. SE (0.067-0.102)

(0.059-0.102)

K-40 0.031

< LLD

< LLD 0

Nb-95 0.0013

< LLD

< LLD 0

Zr-95 0.0020

< LLD

< LLD 0

Ru-103 0.0014

< LLD

< LLD 0

Ru-106 0.0087

< LLD

< LLD 0

Cs-134 0.0011

< LLD

< LLD 0

Cs-137 0.0011

< LLD

< LLD 0

Ce-141 0.0020

< LLD

< LLD 0

Ce-144 0.0058

< LLD

< LLD 0

Airborne Iodine 1-131 519 0.07

< LLD

< LLD 0

(pCi/m 3)

TLD (Quarterly)

Gamma 352 1.0 16.5 (308/308)

T-8, Farm 25.2 (4/4) 17.5 (44/44) 0 (mR/91 days)

(7.4-27.5) 2.7 mi. WSW (23.5-27.5)

(12.8-25.1)

TLD (Quarterly)

Gamma 4

1.0 8.2 (4/4)

None 0

(mR/91 days)

(7.2-9.4)

(Shield)

TLD (Annual)

Gamma 88 1.0 59.4 (77/77)

T-8, Farm 95.0(1/1) 65.8 (11/11) 0 (mR/365 days)

(35.2-95.0) 2.7 mi. WSW (55.1-83.1)

TLD (Annual)

Gamma 1

1.0 29.1 (1/1)

None 0

(mR/365 days)

(Shield) 166

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Table 4.5 Radiological Environmental Monitoring Program Summary Name of Facility Location of Facility Davis-Besse Nuclear Power Station Docket No.

Reporting Period 50-346 January-December, 2008 Ottawa, Ohio

( County, State)

Indicator Location with Highest Control Number Sample Type and Locations Annual Mean Locations Non-Type Number of

. LLDb Mean (F)0 Mean (F)c Mean (F)c Routine Results (Units)

Analyses' Range' Locationd Range0 Range' Milk (pCi/L) 1-131 12 0.5 none

< LLD 0

Sr-89 12 1.0 none

< LLD 0

Sr-90 12 0.8 none T-24, Sandusky 1.0 (3/12) 1.0 (3/12) 0 21.0 mi. SE (0.8-1.3)

(0.8-1.3)

GS 12 K-40 100 none T-24, Sandusky 1390 (12/12) 1390 (12/12) 0 21.0 Mi. SE (1339-1466)

(1339-1466)

Cs-134 5.7 Cs-137 5.0 none

< LLD 0

Ba-La-140 5.9 none

< LLD 0

(g/L)

Ca 12 0.50 none T-24, Sandusky 1.25 (12/12) 1.25 (12/12) 0 21.0 mi. SE (1.11-1.51)

(1.11-1.51)

(g/L)

K (stable) 12 none T-24, Sandusky 1.61 (12/12) 1.61 (12/12) 0 21.0 mi. SE (1.55-1.69)

(1.55-1.69)

(pCi/g)

Sr-90/Ca 12 none T-24, Sandusky 0.78 (3/12) 0.78 (3/12) 0 21.0 mi. SE (0.71-0.86)

(0.71-0.86)

(pCi/g)

Cs-137/K 12 none

< LLD 0

T-225, Ground Water GB (TR) 9 0.9 2.1 (5/6) residence 2.1 (5/6) 2.7 (3/3)

(pCi/L)

(1.6-2.7) 1.55 mi. NW (1.6-2.7)

(2.0-3.2)

H-3 9

330

< LLD

< LLD 0

Sr-89 9

1.4

< LLD

< LLD 0

Sr-90 9

0.7

< LLD

< LLD 0

GS Mn-54 15

< LLD

< LLD 0

Fe-59 30

< LLD

< LLD 0

Co-58 15

< LLD

< LLD 0

Co-60 15

< LLD

< LLD 0

Zn-65 30

< LLD

< LLD 0

Zr-95 15

< LLD

< LLD 0

Cs-134 10

< LLD

< LLD 0

Cs-137 10

< LLD

< LLD 0

Ba-La-140 15

< LLD

< LLD 0

167

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Table 4.5 Radiological Environmental Monitoring Program Summary Name of Facility Location of Facility Davis-Besse Nuclear Power Station Docket No.

Reporting Period 50-346 January-December, 2008 Ottawa, Ohio

( County, State )

Indicator Location with Highest Control Number Sample Type and Locations Annual Mean Locations Non-Type Number of LLDb Mean (F)c Mean (F)0 Mean (F)0 Routine Results (Units)

Analyses' Range' Locationd Range' Rangec e

Edible Meat GS 2

(pCi/g wet)

K-40 0.10 2.90(1/1)

T-31, Onsite 2.90(1/1) 2.34(1/1) 0 Roving location Nb-95 0.011

< LLD

< LLD 0

Zr-95 0.020

< LLD

< LLD 0

Ru-103 0.014

< LLD

< LLD 0

Ru-106 0.12

< LLD

< LLD 0

Cs-134 0.011

< LLD

< LLD 0

Cs-137 0.009

< LLD

< LLD 0

Ce-141 0.024

< LLD

< LLD 0

Ce-144 0.11

< LLD

< LLD 0

Fruits and Sr-89 3

0.007

< LLD

< LLD 0

Vegetables Sr-90 3

0.003

< LLD

< LLD 0

(pCi/g wet) 1-131 3

0.032

< LLD

< LLD 0

GS 3

K-40 0.50 1.17 (2/2)

T-209, Roving 1.67(1/1) 1.67(1/1) 0 (1.07-1.27)

Off-site location Nb-95 0.013

< LLD

< LLD 0

Zr-95 0.027

< LLD

< LLD 0

Cs-134 0.010

< LLD

< LLD 0

Cs-137 0.013

< LLD

< LLD 0

Ce-141 0.015

< LLD

< LLD 0

Ce-144 0.081

< LLD

< LLD 0

Broad Leaf Sr-89 9

0.004

< LLD

< LLD 0

Vegetation Sr-90 9

0.002

< LLD

< LLD 0

(pCi/g wet) 1-131 9

0.022

< LLD

< LLD 0

GS 9

K-40 0.50 2.25(6/6)

T-227, Roving 2.42 (3/3) 2.15 (3/3) 0 (1.83-2.60)

Off-site location (2.14-2.60)

(1.97-2.25)

Nb-95 0.011

< LLD

< LLD 0

Zr-95 0.025

< LLD

< LLD 0

Cs-134 0.009

< LLD

< LLD 0

Cs-137 0.017

< LLD

< LLD 0

Ce-141 0.027

< LLD

< LLD 0

Ce-144 0.10

< LLD

< LLD 0

168

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Table 4.5 Radiological Environmental Monitoring Program Summary Name of Facility Location of Facility Davis-Besse Nuclear Power Station Ottawa, Ohio Docket No.

Reporting Period 50-346 January-December, 2008

( County, State )

Indicator Location with Highest Control Number Sample Type and Locations Annual Mean Locations Non-Type Number of LLDb Mean (F)0 Mean (F)'

Mean (F)c Routine Results (Units)

Analyses' Range' Locationd Range' Rangec 0

Animal/

GS 3

Wildlife Feed Be-7 0.19 0.72 (1/2)

T-31, Onsite 0.72(1/1) 0.27 (1/1) 0 (pCi/g wet)

Roving location K-40 0.10 3.08 (2/2)

T-31, Onsite 3.76(1/1) 2.13 (1/1) 0 (2.40-3.76)

Roving location Nb-95 0.018

< LLD

< LLD 0

Zr-95 0.023

< LLD

< LLD 0

Ru-103 0.019

<LLD

< LLD 0

Ru-106 0.14

< LLD

< LLD 0

Cs-134 0.015

< LLD

< LLD 0

Cs-137 0.016

< LLD

< LLD 0

Ce-141 0.039

< LLD

< LLD 0

Ce-144 0.12

< LLD

< LLD 0

Soil GS 10 (pCi/g dry)

Be-7 0.39 1.04 (4/6)

T-8, Farm 2.28(1/1) 0.52 (1/4) 0 (0.56-2.28) 2.7 mi. WSW K-40 0.10 12.82 (6/6)

T-9, Oak Harbor 22.55 (1/1) 16.54 (4/4) 0 (5.33-19.92) 6.8 mi. SW (9.32-22.55)

Nb-95 0.046

< LLD

< LLD 0

Zr-95 0.061

< LLD

< LLD 0

Ru-103 0.047

< LLD

< LLD 0

Ru-106 0.22

< LLD

< LLD 0

Cs-134 0.026

< LLD

< LLD 0

Cs-137 0.022 0.13(5/6)

T-8, Farm 0.27(1/1) 0.12 (3/4)

(0.048-0.27) 2.7 mi. WSW (0.070-0.15) 0 Ce-141 0.084

< LLD

< LLD 0

Ce-144 0.17

< LLD

< LLD 0

169

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Table 4.5 Radiological Environmental Monitoring Program Summary Name of Facility Location of Facility Davis-Besse Nuclear Power Station Docket No.

Reporting Period 50-346 January-December, 2008 Ottawa, Ohio

( County, State)

Indicator Location with Highest Control Number Sample Type and Locations Annual Mean Locations Non-Type Number of LLDb Mean (F)C Mean (F)c Mean (F)c Routine Results (Units)

Analysesa Rangec Locationd Rangec Range' 2.1 Treated GB (TR) 43 1.0 (23/24)

T-22, Carroll Twp.

2.2 (12/12) 1.9 (20/24) 0 Surface Water (0.9-4.5)

WTP, 3.0 mi. NW (0.9-4.5)

(1.0-3.1)

(pCi/L)

H-3 16 330

< LLD

< LLD 0

Sr-89 16 1.1

< LLD

< LLD 0

Sr-90 16 0.6

< LLD

< LLD 0

GS 16 Mn-54 15

< LLD

< LLD 0

Fe-59 30

< LLD

< LLD 0

Co-58 15

< LLD

< LLD 0

Co-60 15

< LLD

< LLD 0

Zn-65 30

< LLD

< LLD 0

Zr-Nb-95 15

< LLD

< LLD 0

Cs-134 10

< LLD

< LLD 0

Cs-137 10

< LLD

< LLD 0

Ba-La-140 15

< LLD

< LLD 0

2.2 T-3, Site Untreated GB (TR) 60 1.0 (33/36)

Boundary 3.0(12/12) 1.9 (23/24) 0 Surface Water (0.9-4.5) 1.4 mi. ESE (1.5'4.5)

(0.9-3.5)

(pCi/L)

H-3 60 330

< LLD

< LLD 0

Sr-89 20 1.6

< LLD

< LLD 0

Sr-90 20 0.9

< LLD

< LLD 0

GS 60 Mn-54 15

< LLD LLD 0

Fe-59 30

< LLD

< LLD 0

Co-58 15

< LLD

< LLD 0

Co-60 15

< LLD LLD 0

Zn-65 30

< LLD

< LLD 0

Zr-Nb-95 15

< LLD

< LLD 0

Cs-134 10

< LLD

< LLD 0

Cs-137 10

< LLD

< LLD 0

Ba-La-140 15

< LLD LLD 0

170

Davis-Besse Nuclear Power Station 2008 Annual Radiological Environmental Operating Report Table 4.5 Radiological Environmental Monitoring Program Summary Name of Facility Location of Facility Davis-Besse Nuclear Power Station Ottawa, Ohio Docket No.

Reporting Period 50-346 January-December, 2008

( County, State)

Indicator Location with Highest Control Number Sample Type and Locations Annual Mean Locations Non-Type Number of LLDb Mean (F)c Mean (F)c Mean (F)c Routine Results (Units)

Analysesa Rangec Locationd Rangec Rangec Fish GB 6

0.10 4.12 (3/3)

T-33, Lake Erie 4.12 (3/3) 4.10 (3/3) 0 (pCi/g wet)

(3.53-4.76) 1.5 mi. NE (3.53-4.76)

(3.37-5.32)

GS 6

K-40 0.10 3.08 (3/3)

T-33, Lake Erie 3.08 (3/3) 2.88 (3/3) 0 (3.05-3.12) 1.5 mi. NE (3.05-3.12)

(2.56-3.22)

Mn-54 0.024

< LLD

< LLD 0

Fe-59 0.082

< LLD

< LLD 0

Co-58 0.021

< LLD

< LLD 0

Co-60 0.023

< LLD

< LLD 0

Zn-65 0.043

< LLD

< LLD 0

Cs-134 0.024

< LLD

< LLD 0

Cs-137 0.017

< LLD

< LLD 0

Shoreline GS 8

T-4, Site Sediments K-40 0.10 12.85 (6/6)

Boundary 15.11 (2/2) 10.87 (2/2) 0 (10.12-(pCi/g dry) 19.69) 0.8 mi. S (10.52-19.69)

(9.89-11.85)

Mn-54 0.038

< LLD

< LLD 0

Co-58 0.039

< LLD

< LLD 0

Co-60 0.02

< LLD

< LLD 0

Cs-134 0.023

< LLD

< LLD 0

Cs-137 0.025

< LLD

<LLD 0

a GB = gross beta, GS = gamma scan.

b LLD = nominal lower limit of detection based on a 4.66 sigma counting error for background sample.

Mean and range are based on detectable measurements only (i.e., >LLD) Fraction of detectable measurements at specified locations is indicated in parentheses (F).

d Locations are specified by station code (Table 4.1) and distance (miles) and direction relative to reactor site.

Non-routine results are those which exceed ten times the control station value.

171