L-08-117, Monthly Progress Report, Radiological Environmental Monitoring Program for Reporting Period: January - December, 2007

From kanterella
Jump to navigation Jump to search
Monthly Progress Report, Radiological Environmental Monitoring Program for Reporting Period: January - December, 2007
ML081290444
Person / Time
Site: Davis Besse Cleveland Electric icon.png
Issue date: 02/13/2008
From:
Environmental
To:
Office of Nuclear Reactor Regulation
References
FOIA/PA-2010-0209, L-08-117, Project No. 8003
Download: ML081290444 (84)


Text

- .. Environmental, Inc.

Midwest Laboratory an Allegheny Technologies Co.

700 Landwehr Road o Northbrook, IL 60062-2310 ph. (847) 564-0700 tfax (847) 564-4517 MONTHLY PROGRESS REPORT RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM DAVIS-BESSE NUCLEAR POWER STATION OAK HARBOR, OHIO Reporting Period: January - December, 2007 Prepared and Submitted by ENVIRONMENTAL, INC.,

MIDWEST LABORATORY Project Number: 8003 Reviewed and, Approved Date 02 2C08 Distribution: A. Percival, Davis-Besse (2 copies and Original Raw Data)

TABLE OF CONTENTS Section Page List of Tables ............................. I.................................................................................. iii

1.0 INTRODUCTION

................................................................................................... vi 2.0 LISTING OF MISSED SAM PLES .............................................................................. vii

-J 3.0 DATA TABULATIONS ................................................................................................ viii Appendices A Interlaboratory Com parison Program Results ....... ........... .......................... A-1 B Data Reporting Conventions ............................................................................... B-I C Supplemental Analyses ....................................................................................... C-1 ii

LIST OF TABLES No. Title Page 1 Airborne particulates and iodine collected at Location T-1, analyses for gross beta and iodine-1 31 .................................................................................... 1-1 2 Airborne particulates and iodine collected at Location T-2, analyses for gross beta and iodine-1 31 .................................................................................... 2-1 3 Airborne particulates and iodine collected at Location T-3, analyses for gross beta and iodine-131 ........................................ 3-1 4 Airborne particulates and iodine collected at Location T-4, analyses for gross beta and iodine-1 31 .............................................. ................................... 4-1 5 Airborne particulates and iodine collected at Location T-7, analyses for gross beta and iod ine-13 1 ......................................................................................... 5-1 6 Airborne particulates and iodine collected at Location T-8, analyses for gross beta and iodine-131 ........................................ 6-1 7 Airborne particulates and iodine collected at Location T-9, analyses for gross beta and iodine-131 .................................................................................... 7-1 8 Airborne particulates and iodine collected at Location T-11, analyses for gross beta and iodine-1 31 .................................... 8-1 9 Airborne particulates and iodine collected at Location T-1 2, analyses for gross beta and iodine-131 ...... ........................................................................ 9-1 10 Airborne particulates and iodine collected at Location T-27, analyses for gross beta and iodine-1 31 ............................................................................. 10-1 11 Airborne particulate data, gross beta analysis, monthly averages, minima and maxima ................................................................... 11-1 12 Airborne particulate samples, quarterly composites by location, analyses for strontium-89, strontium-90 and gamma-emitting isotopes ............................ 12-1 13 A rea m onitors (TLD ), quarterly ................................................................................... 13-1 14 A rea m onitors (T Lb ), annual ...................................................................................... 14-1 15 Milk, analyses for strontium-89, strontium-90, iodine-131, gamma-emitting isotopes, calcium, stable potassium, and ratios of strontium-90 (pCi) per gram of calcium and cesium-1 37 (pCi) per gram of potassium .............. 15-1 iii

LIST OF TABLES (continued)

No. Title Paqe 16 Ground water, analyses for gross beta, tritium, strontium-89 and strontium-90 and gamma-emitting isotopes, quarterly collections ..................................... 16-1 17 Domestic meat, analysis for gamma-emitting isotopes .............................................. 17-1 18 Wild meat, analysis for gamma-emitting isotopes ...................................................... 18-1 19 Green leafy vegetable, analyses for strontium-89, strontium-90, iodine-131 and gamma-emitting isotopes ................................ 19-1 20 Fruit, analyses, for strontium-89, strontium-90,. iodine-131 and gamma-e m itting isotopes ........................................................................................... 20-1 21 Animal-wildlife feed, analysis for gamma-emitting isotopes ....................................... 21-1 22 Soil, analysis for gam ma-em itting isotopes ................................................................ 22-1 23 Treated surface water, monthly composites of weekly grab samples, analysis fo r gross beta ................................................................................................. 23-1 24 Treated surface water, quarterly composites of weekly grab samples, analyses for tritium, strontium-89, strontium-90 and gamma-emitting isotopes .................................... ........... 24-1 25 Untreated surface water, monthly composites of weekly grab samples, analyses for gross beta, tritium and gamma-emitting isotopes ..................... 25-1 26 Untreated surface water, quarterly composites of weekly grab samples, analyses for strontium-89 and strontium-90 ................................................. 26-1 27 Untreated lakewater, monthly collection, analyses for gross beta, tritium and gam m a-em itting isotopes .............................................................................. 27-1 28 Fish, analyses for gross beta and gamma-emitting isotopes ..................................... 28-1 29 Shoreline sediment, analysis for gamma-emitting isotopes ....................................... 29-1 30 Eggs, analysis for gamma-emitting isotopes ............................................................. 30-1 iv

LIST OF TABLES (continued)

The following tables are in the Appendices:

Appendix A Attachment A: Acceptance criteria for spiked samples ................................................ A-2 A-1 Interlaboratory Comparison Program Results ....................................................... Al-1 A-2 Interlaboratory Comparison Program Results, thermoluminescent dosim eters (TLD s) ................. ..................................................................... A2-1 A-3 Results of the analyses on in-house spiked samples ...................... A3-1 A-4 Results of the analyses on in-house "blank" samples ................................................ A4-1 A-5 Results of the analyses on in-house "duplicate" samples ................... A5-1 A-6 Mixed Analyte Performance Evaluation Program (MAPEP) ....................................... A6-1 Appendix B B-1 D ata Reporting C onventions ....................................................................................... B -2 Appendix C C-1 Air Particulates, duplicate analyses for gross beta ....................................................... C-2 C-2 D uplicate A nalyses ....................................................................................................... C -3 C-3 P rogram D eviations ...................................................................................................... C -4 V

1.0 INTRODUCTION

The following constitutes the current 2007 Monthly Progress Report for the Radiological Environmental Monitoring Program conducted at the Davis-Besse Nuclear Power Station in Oak Harbor, Ohio. Results of completed analyses are presented in the attached tables. Missing entries indicate analyses that are not yet completed.

All activities, except gross alpha and gross beta, are decay corrected to the time of collection.

All samples were collected within the scheduled period unless noted otherwise in the Listing of Missed Samples.

vi

2.0 LISTING OF MISSED SAMPLES Expected Sample Type Location Collection Reason

-- Date TLD T-53 2nd Qtr. 2007 TLD lost in the field.

TLD T-49 4th Qtr. 2007 TLD lost in the field.

TLD T-49 Annual 2007 TLD lost in the field.

TLD T-53 Annual 2007 TLD lost in the field.

'U vii

3.0 DATA TABULATIONS viii

Table 1. Airborne particulates and charcoal canisters, analyses for gross beta and iodine-131'.

Location: T-1 3

Units: pCi/m Collection: Continuous, weekly exchange.

Date Volume Date Volume Collected (me) Gross Beta Collected (m") Gross Beta Required LLD 0.010 0.010 01-09-07 281 0.016 + 0.004 07-10-07 285 0.029 +/- 0.004 01-16-07 280 0.016 +/- 0.003 07-17-07 281 0.018 +/- 0.004 01-23-07 280 0.023 .+/- 0.004 07-24-07 280 0.018 +/- 0.004 01-30-07 281 0.031 +/- 0.004 07-31-07 280 0.029 +/- 0.004 02-06-07 281 0.032 +/- 0.004 08-07-07 281 0.040 +/- 0.005 02-13-07 281 0.024 +/- 0.004 08-14-07 276 0.023 +/- 0.004 02-20-07 279 0.022 +/- 0.004 08-21-07 284 0.021 +/- 0.004 02-27-07 281 0.022 +/- 0.004 08-28-07 284 0.021 +/- 0.003 03-06-07 289 0.041 +/- 0.005 09-04-07 284 0.033 +/- 0.004 03-13-07 277 0.024 + 0.004 09-11-07 284 0.044 + 0.005 03-20-07 281 0.025 + 0.004 09-18-07 284 0.018 +/- 0.003 03-27-07 280 0.022 +/- 0.004 09-25-07 285 0.047 +/- 0.005 04-03-07 280 0.021 +/- 0.004 10-02-07 285 0.027 + 0.004 1st Quarter Mean +/- s.d. 0.025 +/- 0.007 3rd Quarter Mean +/- s.d. 0.028 +/- 0.010 04-10-07 281 0.010 +/- 0.004 10-09-07 283 0.036 +/- 0.004 04-17-07 280 0.021 +/- 0.004 10-16-07 286 0.020 +/- 0.003 04-24-07 280 0.016 +/- 0.004 10-23-07 283 0.036 +/- 0.004 05-01-07 280 0.010 +/- 0.003 10-30-07 285 0.019 +/- 0.004 05-08-07 281 0.016 +/- 0.004 11-06-07 285 0.025 +/- 0.004 05-15-07 280 0.024 +/- 0.004 11-13-07 284 0.031 +/- 0.004 05-22-07 281 0.018 +/- 0.004 11-20-07 284 0.023 +/- 0.004 05-29-07 280 0.035 +/- 0.004 11-27-07 280 0.033 +/- 0.004 06-05-07 281 0.031 +/- 0.004 12-04-07 280 0.030 +/- 0.004 06-12-07 280 0.020 +/- 0.004 12-11-07 281 0.031 +/- 0.004 06-19-07 281 0.030 +/- 0.004 12-18-07 280 0.034 +/- 0.004 06-26-07 280 0.024 +/- 0.004 12-26-07 320 0.048 +/- 0.004 07-03-07 278 0.017-+/- 0.004 01-02-08 283 0.040 +/- 0.004 2nd Quarter Mean +/- s.d. 0.021 +/- 0.008 4th Quarter Mean +/- s.d. 0.031 +/- 0.008 Cumulative Average 0.026 Previous Annual Average 0.024 a lodine-1 31 concentrations are < 0.07 pCi/m 3 unless noted otherwise in Appendix C.

1-1

Table 2. Airborne particulates and charcoal canisters, analyses for gross beta and iodine-131".

Location: T-2 3

Units: pCi/m Collection: Continuous, weekly exchange.

Date Volume Date Volume Collected (mn) Gross Beta Collected (mi) Gross Beta Required LLD 0.010 0.010 01-09-07 281 0.017 +/- 0.004 07-10-07 290 0.033 +/- 0.004 01-16-07 281 0.015 +/- 0.003 07-1 7-07 286 0.019 +/- 0.004 01-23-07 280 0.030 +/- 0.004 07-24-07 285 0.021 +/- 0.004 01-30-07 281 0.034 +/- 0.004 07-31-07 '285 0.032 +/- 0.004 02-06-07 283 0.031 +/- 0.004 08-07-07 286 0.041 +/- 0.005 02-13-07 280 0.025 +/- 0.004 08-14-07 286 0.025 +/- 0.004 02-20-07 280 0.026 00.004 08-21-07 286 0.027 +/- 0.004 02-27-07 281 0.018 + 0.003 08-28-07 291 0.021 +/- 0.003 03-06-07 285 0.018 +/- 0.004 09-04-07 289 0.030 +/- 0.004 03-13-07 278 0.022 +/- 0.004 09-11-07 291 0.039 +/- 0.004 03-20-07 281 0.025 +/- 0.004 09-18-07 290 0.019 +/- 0.004 03-27-07 272 0.023 +/- 0.004 09-25-07 292 0.044 +/- 0.005 04-03-07 280 0.020 +/- 0.004 10-02-07 290 0.025 +/- 0.003 1st Quarter Mean +/- s.d. 0.023 +/- 0.006 3rd Quarter Mean +/- s.d. 0.029 +/- 0.008 04-10-07 281 0.015 +/- 0.004 10-09-07 290 0.033 +/- 0.004 04-17-07 280 0.017 +/- 0.003 10-16-07 290 0.023 +/- 0.003 04-24-07 281 0.017 +/- 0.004 10-23-07 290 0.033 +/- 0.004 05-01-07 281 0.014 +/- 0.004 10-30-07 311 0.020 +/- 0.003 05-08-07 286 0.016 +/- 0.004 11-06-07 291 0.029 +/- 0.004 05-15-07 285 0.026 +/- 0.004 11-13-07 291 0.035 +/- 0.004 05-22-07 277 0.015 +/- 0.004 11-20-07 291 0.024 +/- 0,004 05-29-07 285 0.034 +/- 0.004 11-27-07 290 0.029 +/- 0.004 06-05-07 286 0.027 +/- 0.004 12-04-07 291 0.030 +/- 0.004 06-12-07 285 0.018 +/- 0.003 12-11-07 292 0.025 +/- 0.004 06-19-07 286 0.030 +/- 0.004 12-18-07 290 0.030 + 0.004 06-26-07 285 0.024 +/- 0.004 12-26-07 333 0.049 + 0.004 07-03-07 284 0.013 +/- 0.003 01-02-08 286 0.037 +/- 0.004 2nd Quarter Mean +/- s.d. 0.020 +/- 0.007 4th Quarter Mean +/- s.d. 0.031 +/- 0.007 Cumulative Average 0.026 Previous Annual Average 0.023 lodine-131 concentrations are < 0.07 pCi/m3 unless noted otherwise in Appendix C.

2-1

Table 3. Airborne particulates and charcoal canisters, analyses for gross beta and iodine-1312 .

Location: T-3 3

Units: pCi/m Collection: Continuous, weekly exchange.

Date Volume Date Volume Collected (m") Gross Beta Collected (ma) Gross Beta Required LLD 0.010 0.010 01-09-07 287 0.017 +/- 0.004 07-10-07 288 0.034 +/- 0.004 01-16-07 287 0.016 +/- 0.003 07-17-07 285 0.020 +/- 0.004 01-23-07 286 0.020 +/- 0.004 07-24-07 283 0.020 +/- 0.004 01-30-07 287 0.028 +/- 0.004 07-31-07 284 0.029 +/- 0.004 02-06-07 289 0.031 +/- 0.004 08-07-07 284 0.041 +/- 0.005 02-13-07 286 0.024 +/- 0.004 08-14-07 284 0.023 +/- 0.004 02-20-07 286 0.027 +/- 0.004 08-21-07 284 0.026 +/- 0.004 02-27-07 287 0.015 +/- 0.003 08-28-07 285 0.018 +/- 0.003 03-06-07 287 0.016 +/- 0.004 09-04-07 283 0.033 +/- 0.004

.03-13-07 284 0.029 +/- 0.004. 09-11-07 287 0.045 +/- 0.005 03-20-07 287 0.022 +/- 0.004 09-18-07 289 0.019 +/- 0.004 03-27-07 287 0.016 +/- 0.003 09-25-07 287 0.041 +/- 0.005 04-03-07 287 0.020 +/- 0.004 10-02-07 285 0.028 +/- 0.004 1st Quarter Mean : s.d. 0.022 +/- 0.006 3rd Quarter Mean +/- s.d. 0.029 +/- 0.009 04-10-07 317 0.011 +/- 0.003 .10-09-07 286 0.032 +/- 0.004 04-17-07 286 0.021 +/- 0.004 10-16-07 285 0.019 +/- 0.003 04-24-07 287 0.016 +/- 0.004 10-23-07 285 0.032 +/- 0.004 05-01-07 287 0.014 +/- 0.004 10-30-07 287 0.016 +/- 0.003 05-08-07 287 0.017 +/- 0.004 11-06-07 286 0.027 +/- 0.004 05-15-07 286 0.028 +/- 0.004 11-13-07 286 0.030 +/- 0.004 05-22-07 287 0.016 +/- 0.004 11-20-07 286 0.025 +/- 0.004 05-29-07 286 0.034 +/- 0.004 11-27-07 285 0.026 +/- 0.004 06-05-07 225 0.029 +/- 0.005 12-04-07 286 0.029 +/- 0.004 06-12-07 283 0.018 +/- 0.004 12-11-07 287 0.027 +/- 0.004 06-19-07 284 0.031 +/- 0.004 12-18-07 286 0.035 +/- 0.004 06-26-07 283 0.021 +/- 0.004 12-26-07 325 0.049 +/- 0.004 07-03-07 282 0.015 +/- 0.004 01-02-08 286 0.039 +/- 0.004 2nd Quarter Mean +/- s.d. 0.021 +/- 0.007 4th Quarter Mean +/- s.d. 0.030 +/- 0.008 Cumulative Average 0.025 Previous Annual Averaqe 0.022 2 Iodine-1 31 concentrations are < 0.07 pCi/m 3 unless noted otherwise in Appendix C.

3-1

Table 4. Airborne particulates and charcoal canisters, analyses for gross beta and iodine-131a.

Location: T-4 3

Units: pCi/mr Collection: Continuous, weekly exchange.

Date Volume Date Volume Collected (min) Gross Beta Collected (me) Gross Beta Required LLD 0.010 0.010 01-09-07 281 0.019 +/- 0.004 07-10-07 291 0.028 +/- 0.004 01-16-07 280 0.016 +/- 0.003 07-17-07 287 0.019 +/- 0.004 01-23-07 279 0.022 +/- 0.004 07-24-07 286 0.021 +/- 0.004 01-30-07 281 0.033 +/- 0.004 07-31-07 288 0.026 +/- 0.004 02-06-07 288 0.028 +/- 0.004 08-07-07 282 0.042 +/- 0.005 02-13-07 286 0.029 +/- 0.004 08-14-07 277 0.028 +/- 0.004 02-20-07 286 0.027 +/- 0.004 08-21-07 276 0:023 +/- 0.004 02-27-07 286 0.018 +/- 0.003 08-28-07 278 0.023 +/- 0.004 03-06-07 287 0.018 +/- 0.004 09-04-07 276 0.044 +/- 0.005 03-13-07 284 0.026 +/- 0.004 09-11-07 277 0.045 +/- 0.005 03-20-07 287 0.020 +/- 0.004 09-18-07 282 0.021 +/- 0.004 03-27-07 283 0.017 +/- 0.004 09-25-07 283 0.049 +/- 0.005 04-03-07 286 0.021 +/- 0.004 10-02-07 283 0.031 +/- 0.004 1st Quarter Mean +/- s.d. 0.023 +/- 0.005 3rd Quarter Mean +/- s.d. 0.031 +/- 0.011 04-10-07 288 0.014 +/- 0.004 10-09-07 286 0.033 +/- 0.004 04-17-07 286 0.020 +/- 0.004 10-16-07 285 0.017 +/- 0.003 04-24-07 287 0.015 +/- 0.004 10-23-07 285 0.035 +/- 0.004 05-01-07 287 0.010 +/- 0.003 10-30-07 287 0.022 +/- 0.004 05-08-07 287 0.016 +/- 0.004 11-06-07 287 0.029 +/- 0.004 05-15-07 286 0.024 +/- 0.004 11-13 285 0.037 +/- 0.004 05-22-07 283 0.017 +/- 0.004 11-20-07 286 0.025 +/- 0.004 05-29-07 287 0.035 +/- 0.004 11-27-07 286 0.025 +/- 0.004 06-05-07 287 0.031 +/- 0.004 12-04-07 307 0.027 +/- 0.004 06-12-07 286 0.018 +/- 0.004 12-11-07 284 0.029 +/- 0.004 06-19-07 287 0.032 +/- 0.004 12-18&-07 285 0.037 +/- 0.004 06-26-07 285 0.024 +/- 0.004 12-26-07 321 0.050 +/- 0.005 07-03-07 285 0.014 +/- 0.003 01-02-08 284 0.043 +/- 0.005 2nd Quarter Mean +/- s.d. 0.021 +/- 0.008 4th Quarter Mean +/- s.d. 0.031 +/- 0.009 Cumulative Average 0.026 Previous Annual Average 0.023 3

Iodine-1 31 concentrations are < 0.07 pCi/m unless noted otherwise in Appendix C.

4-1

Table 5. Airborne particulates and charcoal canisters, analyses for gross beta and iodine-1 31a Location: T-7 3

Units: pCi/m Collection: Continuous, weekly exchange.

Date Volume Date Volume Collected (M3) Gross Beta. Collected (mi) Gross Beta Required LLD 0.010 0.010 01-09-07 284 0.013 +/- 0.003 07-1 0-07 283 0.034 +/- 0.004 01-16-07 284 0.015 +/- 0.003 07-17-07 282 0.018 +/- 0.004 01-23-07 283 0.023 +/- 0.004 07-24-07 278 0.021 +/- 0.004 01-30-07 285 0.033 +/- 0.004 07-31-07 278 0.033 +/- 0.004 02-06-07 296 0.031 +/- 0.004 08-07-07 282 0.041 +/- 0.005 02-13-07 284 0.024 +/- 0.004 08-14-07 285 0.026 +/- 0.004 02-20-07 283 0.026 +/- 0.004 08-21-07 276 0.024 +/- 0.004 02-27-07 284 0.017 +/- 0.003 08-28-07 282 0.018 +/- 0.003 03-06-07 284 0.014 +/- 0.004 09-04-07 287 0.036 +/- 0.004 03-13-07 275 0.024 +/-.0.004 09-11-07 278 0.044 +/- 0.005 03-20-07 276 0.023 +/- 0.004 09-18-07 282 0.015 +/- 0.003 03-27-07 272 0.020 +/- 0.004 09-25-07 279 0.045 +/- 0.005 04-03-07 277 0.021 +/- 0.004 10-02-07 282 0.028 +/- 0.004 1st Quarter Mean +/- s.d. 0.022 +/- 0.006 3rd Quarter Mean +/- s.d. 0.029 +/- 0.010 04-10-07 277 0.011 +/- 0.004 10-09-07 275 0.037 +/- 0.005 04-17-07 276 0.018 +/- 0.004 10-16-07 279 0.016 +/- 0.003 04-24-07 281 0.015 +/- 0.004 10-23-07 279 0.038 +/- 0.005 05-01-07 272 0.013 +/- 0.004 10-30-07 279 0.018 +/- 0.004 05-08-07 279 0.014 +/- 0.004 11-06-07 280 0:032 +/- 0.004 05-15-07 282 0.024 +/- 0.004 11-13-07 280 0.037 +/- 0.005 05-22-07 282 0.015 +/- 0.004 11-20-07 278 0.029 +/- 0.004

.05-29-07 282 0.034 +/- 0.004 11-27-07 278 0.022 +/- 0.004 06-05-07 282 0.031 +/- 0.004 12-04-07 279 0.030 +/- 0.004 06-12-07 282 0.020 +/- 0.004 12-11-07 280 0.031 +/- 0.004 06-19-07 282 0.030 +/- 0.004 12-18-07 278 0.025 +/- 0.004 06-26-07 282 0.022 +/- 0.004 12-26-07 318 0.042 +/- 0.004 07-03-07 283 0.015 +/- 0.004 01-02-08 279 0.041 +/- 0.004 2nd Quarter Mean +/- s.d. .0.020 +/- 0.008 4th Quarter Mean +/- s~d. 0.031 +/- 0.008 Cumulative Average 0.025 I 3 n0ote us Average innual u.uC.,5 lodine-1 31 concentrations are < 0.07 pCi/m3 unless noted otherwise in Appendix C.

5-1

Table 6. Airborne particulates and charcoal canisters, analyses for gross beta and iodine-131a.

Location: T-8 3

Units: pCi/m Collection: Continuous, Weekly exchange.

Date Volume Date Volume Collected (M3) Gross Beta Collected (M 3). Gross Beta Required LLD 0.010 0.010 01-09-07 261 0.017 +/- 0.004 07-10-07 289 0.030 +/- 0.004 01-16-07 261 0.017 +/- 0.004 07-17-07 284 0.019 +/- 0.004 01-23-07 261 0.026 +/- 0.004 07-24-07 284 0.021 +/- 0.004 01-30-07 285 0.035 +/- 0.004 07-31 -07 283 0.030 +/- 0.004 02-06-07 285 0.028 +/- 0.004 08-07-07 .284 0.040 +/- 0.005 02-13-07 283 0.022 +/- 0.004 08-14-07 284 0.024 +/- 0.004 02-20-07 282 0.027 +/- 0.004 08-21-07 283 0.019 +/- 0.004 02-27-07 284 0.020 +/- 0.004 08-28-07 284 0.021 +/- 0.003 03-06-07 284 0.017 +/- 0.004 09-04-07 282 0.038 +/- 0.004 03-13-07 273 0.027 +/- 0.004 09-11-07 285 0.040 +/- 0.005 03-20-07 285 0.021 +/- 0.004 09-18-07 284 0.020 +/- 0.004 03-27-07 279 0.020 +/- 0.004 09-25-07 282 0.049 +/- 0.005 04-03-07 283 0.022 +/- 0.004 10-02-07 285 0.030 +/- 0.004 1st Quarter Mean +/- s.d. 0.023 +/- 0.005 3rd Quarter Mean +/- s.d. 0.029 +/- 0.010 04-10-07 286 0.012 +/- 0.004 10-09-07 282 0.040 +/- 0.005 04-17-07 282 0.019 +/- 9.004 10-16-07 283 0.018 +/- 0.003 04-24-07 286 0.015 +/- 0.004 10-23-07 285 0.041 +/- 0.005 05-01-07 284 0.009 +/- 0.003 10-30-07 286 0.018 +/- 0.004 05-08-07 284 0.016 +/- 0.004 11-06-07 284 0.027 +/- 0.004 05-15-07 .284 0.027 +/- 0.004 11-13-07 284 0.035 +/- 0.004 05-22-07 284 0.016 +/- 0.004 11-20-07 283 0.025 +/- 0.004 05-29-07 284 0.037 +/- 0.004 11-27-07 275 0.031 +/- 0.004 06-05-07 233 0.033 +/- 0.005 12-04-07 284 0.027 +/- 0.004 06-12-07 284 0.018 +/- 0.004 12-11-07 292 0.027 +/- 0.004 06-19-07 283 0.032 +/- 0.004 12-18-07 279 0.033 +/- 0.004 06-26-07 282 0.020 +/- 0.004 12-26-07 309 0.046 +/- 0.004 07-03-07 282 0.014 1 0.003 01-02-08 298 0.039 +/- 0.004 2nd Quarter Mean +/- s.d. 0.021 +/- 0.009 4th Quarter Mean +/- s.d. 0.031 +/- 0.009 Cumulative Average 0.026 Previous Annual Average 0.023 B Iodine-I 31 concentrations are < 0.07 pCi/mr3 unless noted otherwise in Appendix C.

6-_1

Table 7. Airborne particulates and charcoal canisters, analyses for gross beta and iodine-131 a.

Location: T-9 (C) 3 Units: pCi/mr Collection: Continuous, weekly exchange.

Date Volume Date Volume Collected (mi) Gross Beta. Collected (mj) Gross Beta Required LLD 0.010 0.010 01-09-07 276 0.020 +/- 0.004 07-10-07 285 0.037 +/- 0.004 01-16-07 280 0.018 +/- 0.004 07-17-07 283 0.020 +/- 0.004 01-23-07 276 0.026 +/- 0.004 07-24-07 284 0.020 +/- 0.004 01-30-07 278 0.026 +/- 0.004 07-31-07 283, 0.033 +/- 0.004 02-06-07 277 0.032 +/- 0.004 08-07-07 284 0.044 +/- 0.005 02-13-07 279 0.023 +/- 0.004 08-14-07 284 0.030 +/- 0.004 02-20-07 279 0.030 +/- 0.004 08-21-07 283 0.024 +/- 0.004 02-27-07 281 0.018 +/- 0.003 08-28-07 284 0.020 +/- 0.003 03-06-07 281 0.016 +/- 0.004 09-04-07 281 0.038 +/- 0.004 03-13-07 278 0.029 +/- 0.004 09-11-07 284 0.043 +/- 0.005 03-20-07 295 0.025 +/- 0.004 09-18-07 283 0.018 +/- 0.004 03-27-07 275 0.025 +/- 0.004 09-25-07 284 0.044 +/- 0.005 04-03-07 280 0.023 +/- 0.004 10-02-07 284 0.032 +/- 0.004 1st Quarter Mean +/- s.d. 0.024 +/- 0.005 3rd Quarter Mean +/- s.d. 0.031 +/- 0.010 04-10-07 282 0.014 +/- 0.004 10-09-07 281 0.029 +/- 0.004 0417-07 279 0.021 +/- 0.004 10-16-07 282 0.021 +/- 0.003 04-24-07 282 0.015 +/- 0.004 10-23-07 284 0.038 +/- 0.005 05-01-07 280 0.013 +/- 0.004

.10-30-07 285 0.020 +/- 0.004 05-08-07 260 0.016 +/- 0.004 11-06-07 287 0.028 +/- 0.004 05-15-07 280 0.030 +/- 0.004 11-13-07 287 0.034 +/- 0.004 05-22-07 276 0.017 +/- 0.004 11-20-07 286 0.022 +/- 0.004 05-29-07 281 0.035 +/- 0.004 11-27-07 287 0.030 +/- 0.004 06-05-07 312 0.030 +/- 0.004 12-04-07 287 0.028 +/- 0.004 06-12-07 266 0.022 +/- 0.004 12-11-07 289 0.027 +/- 0.004 06-19-07 294 0.033 +/- 0.004 12-18-07 286 0.034 +/- 0.004 06-26-07 270 0.024 +/- 0.004 12-26-07 322 0.044 +/- 0.004 07-03-07 279 0.019 +/- 0.004 01-02-08 206 0.034 +/- 0.005 2nd Quarter Mean +/- s.d. 0.022 +/- 0.008 4th Quarter Mean +/- s.d. 0.030 +/- 0.007 Cumulative Average 0.027 Previous Annual Average 0.024 lodine-131 concentrations are < 0.07 pCi/mr3 unless noted otherwise in Appendix C.

7-.1

Table 8. Airborne particulates and charcoal canisters, analyses for gross beta and iodine-1 31".

Location: T-1 1 (C) 3 Units: pCi/m Collection: Continuous, weekly exchange.

Date Volume Date Volume Collected (m6) Gross Beta Collected (m") Gross Beta Required LLD 0.010 0.010 01-09-07 288 0.018 +/- 0.004 07-10-07 280 0.039 +/- 0.004 01-16-07 287 0.016 +/- 0.003 07-17-07 287 0.020 +/- 0.004 01-23-07 287 0.027 +/- 0.004 07-24-07 287 0.023 +/- 0.004 01-30-07 285 0.027 +/- 0.004 07-31-07 287 0.032 +/- 0.004 02-06-07 285 0.029 +/- 0.004 08-07-07 293 0.038 +/- 0.004 02-13-07 284 0.024 +/- 0.004 08-14-07 280 0.025 +/- 0.004 02-20-07 283 0.045 +/- 0.005 08-21-07 292 0.021 +/- 0.004 02-27-07 285 0.017 +/- 0.003 08-28-07 290 0.021 +/- 0.003 03-06-07 291 0.016 +/- 0.004 09-04-07 289 0.034 +/- 0.004 03-13-07 282 0.026 +/- 0.004 09-11-07 291 0.041 +/- 0.005 03-20-07 284 0.022 +/- 0.004 09-18-07 291 0.022 +/- 0.004 03-27-07 277 0.021 +/- 0.004 09-25-07 291 0.049 +/- 0.005 04-03-07 284 0.018 +/- 0.004 10-02-07 291 0.027 +/- 0.004 1st Quarter Mean +/- s.d. 0.024 +/- 0.008 3rd Quarter Mean +/- s.d. 0.030 +/- 0.009 04-10-07 284 0.012 +/- 0.004 10-09-07 290 0.037 +/- 0.004 04-17-07 284 0.017 +/- 0.003 10-16-07 290 0.021 +/- 0.003 04-24-07 284 0.016 +/- 0.004 10-23-07 291 0.037 +/- 0.004 05-01-07 284 0.013 +/- 0.004 10-30-07 290 0.019 +/- 0.004 05-08-07 284 0.015 +/- 0.003 11-06-07 292 0.025 +/- 0.004 05-15-07 284 0.027 +/- 0.004 11-13-07 291 0.031 +/- 0.004 05-22-07 284 0.015 +/- 0.004 11-20-07 291 0.025 +/- 0.004 05-29-07 284 0.042 +/- 0.005 11-27-07 290 0.026 +/- 0.004 06-05-07 243 0.034 +/- 0.005. 12-04-07 291 0.029 +/- 0.004 06-12-07 288 0.019 +/- 0.004 12-11-07 285 0.029 +/- 0:004 06-19-07 287 0.031 +/- 0.004 12-18-07 284 0.040 +/- 0.005 06-26-07 299 0.024 +/- 0.004 12-26-07 323 0.046 +/- 0.004 07-03-07 284 0.013 +/- 0.003 01-02-08 279 0.039 +/- 0.004 2nd Quarter Mean +/- s.d. 0.021 +/- 0.009 4th Quarter Mean +/- s.d. 0.031 +/- 0.008 Cumulative Average 0.026 Previous Annual Average 0.023 3

a Iodine-131 concentrations are < 0.07 pCi/m unless noted otherwise in Appendix C.

8-1

Table 9. Airborne particulates and charcoal canisters, analyses for gross beta and iodine-131a.

Location: T-12 (C) 3 Units: pCi/m Collection: Continuous, weekly exchange.

Date Volume Date Volume Collected (m") Gross Beta Collected (ms) Gross Beta Required LLD 0.010 0.010 01-09-07 281 0.015 +/- 0.004 07-10-07 283 0.035 +/- 0.004 01-16-07 281 0.015 +/- 0.003 07-17-07 280 0.021 +/- 0.004 01-23-07 280 0.024 +/- 0.004 07-24-07 277 0.019 +/- 0.004 01-30-07 283 0.034 +/- 0.004 07-31-07 280 0.034 +/- 0.004 02-06-07 281 0.033 +/- 0.004 08-07-07 280 0.040 +/- 0.005 02-13-07 280 0.022 +/- 0.004 08-14-07 279 0.027 +/- 0.004 02-20-07 280 0.022 +/- 0.004 08-21-07 287 0.023 +/- 0.004 02-27-07 281 0.017 +/- 0.003 08-28-07 287 0.019 +/- 0.003 03-06-07 281 0.014 +/- 0.004 09-04-07 285 0.036 +/- 0.004 03-13-07 272 0.026 +/- 0.004 09-11-07 288 0.036 +/- 0.004 03-20-07 283 0.023 +/- 0.004 09-18-07 288 0.018 +/- 0.003 03-27-07 270 0.019 +/- 0.004 09-25-07 289 0.042 +/- 0.005 04-03-07 284 0.019 +/- 0.004 10-02-07 289 0.030 +/- 0.004 1st Quarter Mean +/- s.d. 0.022 +/- 0.006 3rd Quarter Mean +/- s.d. 0.029 +/- 0.009 04-10-07 286 0.011 +/- 0.004 10-09-07 285 0.034 +/- 0.004 04-17-07 283 0.019 +/- 0.004 10-16-07 287 0.017 +/- 0.003 04-24-07 281 0.018 +/- 0.004 10-23-07 288 0.035 +/- 0.004 05-01-07 279 0.017 +/- 0.004 10-30-07 288 0.018 +/- 0.004 05-08-07 279 0.016 +/- 0.004. 11-06-07 289 0.023 +/- 0.004-05-15-07 279 0.024 +/- 0.004 11-13-07 288 0.032 +/- 0.004 05-22-07 278 0.017 +/- 0.004 11-20-07 287 0.024 +/- 0.004 05-29-07 280 0.035 +/- 0.004 11-27-07 288 0.028 +/- 0.004 06-05-07 290 0.034 +/- 0.004 12-04-07 289 0.027 +/- 0.004 06-12-07 278 0.019 +/- 0.004 12-11-07 291 0.023 +/- 0.004 06-19-07 279 0.026 +/- 0.004 12-18-07 282 0.039 +/- 0.005 06-26-07 278 0.017 +/- 0.004' 12-26-07 320 0.046 +/- 0.004 07-03-07 277 0.012 +/- 0.003 01-02-08 291 0.038 +/- 0.004 2nd Quarter Mean +/- s.d. 0.020 +/- 0.007 4th Quarter Mean +/- s.d. 0.030 +/- 0.009 Cumulative Average 0.025 Previous Annual Average 0.023 a lodine-131 concentrations are < 0.07 pCi/m 3 unless noted otherwise.

9-1

Table 10. Airborne particulates and charcoal canisters, analyses for gross beta and iodine-1 31'.

Location: T-27 (C) 3 Units: pCi/m Collection: Continuous, weekly exchange.

Date Volume Date Volume Collected (m") Gross Beta Collected (m") Gross Beta Required LLD 0.010 0.010 01-09-07 284 0.017 +/- 0.004 07-10-07 285 0.034 +/- 0.004 01-16-07 284 0.020 +/- 0.004 07-17-07 285 0.016 +/- 0.003 01-23-07 283 0.022 +/- 0.004 07-24-07 284 0.019 +/- 0.004 01-30-07 285 0.030 +/- 0.004 07-31-07 285 0.031 +/- 0.004 02-06-07 285 0.030 +/- 0.004 08-07-07 283 0.042 +/- 0.005 02-13-07 291 0.026 +/- 0.004 08-14-07 285 0.028 +/- 0.004 02-20-07 279 0.025 +/- 0.004 08-21-07 278 0.023 +/- 0.004 02-27-07 272 0.016 +/- 0.003 08-28-07 284 0.020 +/- 0.003 03-06-07 280 0.017 +/- 0.004 09-04-07 289 0.033 +/- 0.004 03-13-07 270 0.026 +/- 0.004 09-11-07 284 0.040 +/- 0.005 03-20-07 281 0.022 +/- 0.004 09-18-07 285 0.018 +/- 0.004 03-27-07 277 0.021 +/- 0.004 09-25-07 279 0.045 +/- 0.005 04-03-07 282 0.019 +/- 0.004 10-02-07 292 0.026 +/- 0.004 1 st Quarter Mean +/- s.d. 0.022 +/- 0.005 3rd Quarter Mean +/- s.d. 0.029 +/- 0.010 04-10-07 282 0.011 +/- 0.004 10-09-07 275 0.034 +/- 0.004 04-17-07 281 0.018 +/- 0.004 10-16-07 284 0.015 +/- 0.003 04-24-07 283 0.013 +/- 0.004 10-23-07 289 0.035 +/- 0.004 05-01-07 281 0.013 +/- 0.004 10-30-07 285 0.020 +/- 0.004 05-08-07 282 0.024 +/- 0.004 11-06-07 285 0.029 +/- 0.004 05-15-07 280 0.028 +/- 0.004 11-13-07 284 0.032 +/- 0.004 05-22-07 283 0.004 +/- 0.003 11-20-07 279 0.022 +/- 0.004' 05-29-07 282 0.030 +/- 0.004 11-27-07 281 0.029 +/- 0.004 06-05-07 290 0.030 +/- 0.004 12-04-07 287 0.034 +/- 0.004 06-12-07 281 0.016 +/- 0.003 12-11-07 293 0.027 +/- 0.004 06-19-07 282 0.031 +/- 0.004 12-18-07 280 0.034 +/- 0.004 06-26-07 280 0.022 +/- 0.004 12-26-07 327 0.049 +/- 0.004 07-03-07 281 0.017 +/- 0.004 01-02-08 292 0.041 +/- 0.004 2nd Quarter Mean +/- s.d. 0.020 +/- 0.009 4th Quarter Mean +/- s.d. 0.031 +/- 0.009 Cumulative Average 0.025 Previous Annual Average 0.023 3

a Iodine-1 31 concentrations are < 0.07 pCi/m unless noted otherwise in Appendix C.

b Filter light.

10-1

Table 11-1. Airborne particulate data,gross beta analyses, monthly averages, minima and maxima.

January April Location Average Minima Maxima Location Average Minima Maxima Janua* April T-9 0.023 0.018 0.026 T-9 0.016 0.013 0.021 T-1 1 0.022 0.016 0.027 T-1 1 0.015 0.012 0.017 T-12 0.022 0.015 0.034 T-12 0.016 0.011 0.019 T-27 0.022 0.017 0.030 T-27 0.014 0.011 0.018 Controls 0.022 0.015 0.034 Controls +P 0.015 0.011 0.021 T-1 0.022 0.016 0.031 T-1 0.014 0.010 0.021 T-2 0.024 0.015 0.034 T-2 0.016 0.014 0.017 T-3 0.020 0.016 0.028 T-3 0.016 0.011 0.021 T-4 0.023 0.016 0.033 T-4 0.015 0.010 0.020 T-7 0.021 0.013 0:033 T-7 0.014 0.011 0.018 T-8 0.024 0.017 0.035 T-8 0.014 0.009 0.019 Indicators 0.022 0.013 0.035 Indicators 0.015 0.009 0.021 February May Location Average Minima Maxima Location Average Minima Maxima T-9 0.026 0.018 0.032 T-9 0.025 0.016 0.035 T-11 0.029 0.017 0.045 T-11 0.025 0.015 0.042 T-12 0.024 0.017 0.033 T-12 0.023 0.016 0.035 T-27 0.024 0.016 0.030 T-27 0.022 0.004 0.030 Controls 0.026 0.016 0.045 Controls 0.024 0.004 0.042 T-1 0.025 0.022 0.032 T-1 0.023 0.016 0.035 T-2 0.025 0.018 0.031 T-2 0.023 0.015 0.034 T-3 0.024 0.015 0.031 T-3 0.024 0.016 0.034 T-4 0.026 0.018 0.029 T-4 0.023 0.016 0.035 T-7 0.025 0.017 0.031 T-7 0.022 0.014 0.034 T-8 0.024 0.020 0.028 T-8 0.024 0.016 0.037 Indicators 0.025 0.015 0.032 Indicators 0.023 0.014 0.037 March June Location Average Minima Maxima Location Average Minima Maxima T-9 0.024 0.016 0.029 T-9 0.026 0.019 0.033 T-1 1 0.021 0.016 0.026 T-1 1 0.024 0.013 0.034 T-12 0.020 0.014 0.026 T-12 0.022 0.012 0.034 T-27 0.021 0.017 0.026 T-27 0.023 0.016 0.031 Controls 0.022 0.014 0.029 Controls 0.024 0.012 0.034 T-1 0.027 0.021 0.041 T-1 0.024 0.017 0.031 T-2 0.022 0.018 0.025 T-2 0.022 0.013 0.030 T-3 0.021 0.016 0.029 T-3 0.023 0.015 0.031 T-4 0.020 0.017 0.026 T-4 0.024 0.014 0.032 T-7 0.020 0.014 0.024 T-7 0.024 0.015 0.031 T-8 0.021 0.017 0.027 T-8 0.023 0.014 0.033 Indicators 0.022 0.014 0.041 Indicators 0.023 0.013 0.033 Note: Unless otherwise specified, samples collected on the first, second or third day of the month are grouped with data of the previous month.

11-1

Table 11-1. Airborne particulate data,gross beta analyses, monthly averages, minima and maxima.

July October Location Average Minima Maxima Location Average Minima Maxima T-9 0.028 0.020 0.037 T-9 0.027 0.020 0.038 T-1 1 0.029 0.020 0.039 T-1 1 0.029 0.019 0.037 T-12 0.027 0.019 0.035 T-12 0.026 0.017 0.035 T-27 0.025 0.016 0.034 T-27 0.026 0.015 0.035 Controls 0.027 0.016 0.039 Controls 0.027 0.015 0.038 T-1 0.024 0.018 0.029 T-1 0.028 0.019 0.036 T-2 0.026, 0.019 0.033 T-2 0.027 0,020 0.033 T-3 0.026 0.020 0.034 T-3 0.025 0.016 0.032 T-4 0.024 0.019 0.028 T-4 0.027 0.017 0.035 T-7 0.027 0.018 0.034 T-7 0.027 0.016 0.038 T-8 0.025 .0.019 0.030 T-8 0.029 0.018 0.041 Indicators 0,025 0.018 0.034 Indicators 0.027 0.016 0.041 August November Location Average Minima Maxima Location Average Minima Maxima T-9 0.030 0.020 0.044 T-9 0.029 0.022 0.034 T-11 0.026 0.021 0.038 T-11 0.027 0.025 0.031 T-12 0.027 0.019 0.040 T-12 0.027 0.023 0.032 T-27 0.028 0.020 0.042 T-27 0.028 0.022 0.032 Controls 0.028 0.019 0.044 Controls 0.028 0.022 0.034 T-1 0.026 0.021 0.040 T-1 0.028 0.023 0.033 T-2 0.029 0.021 0.041 T-2 0.029 0.024 0.035 T-3 0.027 0.018 0.041 T-3 0.027 0.025 0.030 T-4 0.029 0.023 0.042 T-4 0.029 0.025 0.037 T-7 0.027 0.018 0.041 T-7 0.030 0.022 0.037 T-8 0.026 0.019 0.040 T-8 0.030 0.025 0.035 Indicators 0.027 0.018 0.042 Indicators 0.029 0.022 0.037 September December Location Average Minima Maxima Location Average Minima Maxima T-9 0.035 0.018 0.044 T-9 0.033 0.027 .0.044 T-11 0.035 0.022 0.049 T-11 0.037 0.029 0.046 T-12 0.032 0,018 0.042 T-12 0.035 0.023 0.046 T-27 0.032 0.018 0.045 T-27 0.037 0.027 0.049 Controls 0.034 0.018 0.049 Controls 0.036 0.023 0.049 T-1 0.034 0.018 0.047 T-1 0.037 0.030 0.048 T-2 0.031 0,019 0.044 T-2 0.034 0.025 0.049 T-3 0.033 0.01'9 0.045 T-3 0.036 0.027 0.049 T-4 0.038 0.021 0.049 T-4 0.037 0.027 0.050 T-7 0.034 0.015 0.045 T-7 0,034 0.025 0.042 T-m8 0.035 0.020 0.049 T-8 0.034 0.027 0.046 Indicators 0.034 0.015 0.049 Indicators 0.035 0.025 0.050 Note: Unless otherwise specified, samples collected on the first, second or third day of the month are grouped with data of the previous month.

11-2

TOLEDO Table 12. Airborne particulates, analyses for strontium-89, strontium-90 and gamma-emitting isotopes.

Collection: Quarterly 3

Composite Units: pCi/m Location T-1 Quarter 1 st Quarter 2nd Quarter 3rd Quarter 4th Quarter Lab Code TAP- 2190 TAP- 4422 TAP- 6971 TAP- 8808 Volume (m3 ) 3651 3643 3673 3714 Sr-89 < 0.0007 < 0.0005 < 0.0007 < 0.0005 Sr-90 < 0.0004 < 0.0003 < 0.0004 < 0.0004 Be-7 0.063 + 0.011 0.107 + 0.020 0.090 +/- 0.014 0.069 +/- 0.013 K-40 0.021 0.027 0.023 < 0.024 Nb-95 0.0007 0.0011 0.0008 < 0.0006 Zr-95 0.0013 0.0010 0.0015 < 0.0013 Ru-I 03 0.0007 0.0009 0.0007 < 0.0007 Ru-1 06 0.0057 0.0056 0.0068 < 0.0030 Cs-1 34 0.0010 0.0005 0.0008 < 0.0007 Cs-1 37 0.0006 0.0004 0.0005 < 0.0004 Ce-1 41 0.0015 0.0018 0.0016 < 0.0016 Ce-1 44 0.0035 0.0030 0.0036 < 0.0035 Location T-2

  • Quarter 1st Quarter 2nd Quarter 3rd Quarter 4th Quarter a Lab Code TAP- 2191 TAP- 4423 - TAP- 6972 TAP- 8809 Volume (in 3) 3643 3682 3747 3836 Sr-89 < 0.0007 < 0.0006 < 0.0006 < 0.0011 Sr-90 < 0.0004 < 0.0003 < 0.0003 < 0.0009 Be-7 0.084 r 0.016 0.114 +/- 0.021 0.089 +/- 0.014 0.062 + 0.016 K-40 0.023 0.027 0.025 0.023 Nb-95 0.0007 0.0011 0.0011 0.0008 Zr-95 0.0008 0.0016 0.0016 0.0010 Ru-1 03 0.0006 0.0009 0.0004 0.0006 Ru-1 06 0.0074 0.0074 0.0035 0.0026 Cs-1 34 0.0008 0.0008 0.0006 0.0007 Cs-1 37 0.0009 0.0006 0.0004 0.0004 Ce-141 0.0015 0.0011 0.0012 0.0010 Ce-144 0.0043 0.0054 0.0035 0.0028 a Duplicate analysis, refer to Appendix C.

12-1

TOLEDO Table 12. Airborne particulates, analyses for strontium-89, strontium-90 and gamma-emitting isotopes.

Collection: Quarterly 3

Composite Units: pCi/m Location T-3 Quarter 1st Quarter 2nd Quarter 3rd Quarter 4th Quarter Lab Code TAP- 2192 TAP- 4424 TAP- 6973 TAP- 8811 Volume (M 3) 3727 3680 3708 3756 Sr-89 < 0.0005 < 0.0005 < 0.0007 < 0.0005 Sr-90 < 0.0003 < 0.0003 < 0.0004 < 0.0004 Be-7 0.087 + 0.013 0.107 + 0.018 0.084 + 0.013 0.062 +/- 0.014 K-40 0.021 0.027 0.022 0.024 Nb-95 0.0007 0.0010 0.0008 0.0009 Zr-95 0.0009 0.0016 0.0019 0.0014 Ru-1 03 0.0009 0.0008 0.0007 0.0008 Ru-1 06 0.0059 0.0087 0.0050 0.0021 Cs-1 34 0.0008 0.0005 0.0005 0.0005 Cs-1 37 0.0007 0.0006 0.0004 0.0005 Ce-141 0.0009 0.0016 0.0010 0.0016 Ce-144 0.0026 0.0041 0.0048 0.0028 Location T-4 Quarter 1st Quarter 2nd Quarter 3rd Quarter 4th Quarter Lab Code TAP- 2193---- -- TAP-4425--_ TAP- 6974 TAP- 8812 Volume (M 3 ) 3694 3721 3666 3768 Sr-89 < 0.0006 < 0.0005 < 0.0007 < 0.0006 Sr-90 < 0.0003 < 0.0002 < 0.0003 < 0.0004 Be-7 0.082 +/- 0.014 0.105 +/- 0.016 0.086 +/- 0.014 0.052 +/- 0.013 K-40 0.021 0.026 < 0.022 < 0.024 Nb-95 0.0006 0.0009 < 0.0008 < 0.0012 Zr-95 0.0013 0.0010 < 0.0013 < 0.0007 Ru-103 0.0008 0.0004 < 0.0006 < 0;0010 Ru-106 0.0066 0.0056 < 0.0053 < 0.0054 Cs-134 0.0009 0.0006 < 0.0005 < 0.0004 Cs-1 37 0.0007 0.0007 < 0.0006 < 0.0004 Ce- 141 0.0013 0.0013 < 0.0013 < 0.0010 Ce-1 44 0.0037 0.0052 < 0.0047 < 0.0036 12-2

TOLEDO Table 12. Airborne particulates, analyses for strontium-89, strontium-90 and gamma-emitting isotopes.

Collection: Quarterly 3

Composite Units: pCi/m Location T-7 Quarter 1st Quarter 2nd Quarter 3rd Quarter a 4th Quarter Lab Code TAP- 2194 TAP- 4426 TAP- 6975 TAP- 8813 Volume(m') 3667 3642 3654 3662 Sr-89 < 0.0006 < 0.0005 < 0.0013 < 0.0007 Sr-90 < 0.0003 < 0.0003 < 0.0007 < 0.0006 Be-7 0.077 +/- 0.014 0.108 +/- 0.018 0.086 +/-.0.015 0.060 +/- 0.014 K-40 < 0.023 < 0.034 < 0.023 < 0.025 Nb-95 < 0.0008 < 0.0008 < 0.0007 < 0.0009 Zr-95 < 0.0009 < 0.0016 < 0.0011 < 0.0015 Ru-1 03 < 0.0009 < 0.0006 < 0.0006 < 0.0006 Ru-1 06 < 0.0064 * < 0.0075 < 0.0047 < 0.0030 Cs-1 34 < 0.0009 < 0.0008 < 0.0007 < 0.0006 Cs-137 < 0.0007 < 0.0006 < 0.0008 < 0.0003 Ce-1 41 < 0.0011 < 0.0017 ,< 0.0013 < 0.0011 Ce-144 < 0.0047 < 0.0036 < 0.0042 < 0.0044 Location T-8 Quarter 1st Quarter 2nd Quarter a 3rd Quarter 4th Quarter Lab Code TAP- 2195 TAP- 4427 TAP- 6977 TAP- 8814 Volume (m') 3606 - - 3638 3693 3724 Sr-89 < 0.0006 < 0.0010 < 0.0006 < 0.0005 Sr-90 < 0.0004 < 0.0006 < 0.0004 < 0.0005 Be-7 0.077 +/- 0.013 1 0.127 + 0.020 0.094 +/- 0.015 0.057 +/- 0.015 K-40 0.022 0.027 < 0.023 0.028 Nb-95 0.0007 0.0009 < 0.0005 0.0011 Zr-95 0.0013 0.0022 < 0.0009 0.0007 Ru-103 0.0006 0.0005 < 0.0007 0.0003 Ru-106 0.0076 0.0075 < 0.0045 0.0060 Cs-134 0.0009 0.0004 < 0.0006 0.0006 Cs-137 0.0008 0.0006 < 0.0004 0.0005 Ce-141 0.0017 0.0017 < 0.0013 0.0016 Ce-144 0.0043 0.0031 < 0.0045 0.0037 a Duplicate analysis, refer to Appendix C.

12-3

TOLEDO Table 12. Airborne particulates, analyses for strontium-89, strontium-90 and gamma-emitting isotopes.

Collection: Quarterly Composite Units: pCi/m3 Location T-9 (C)

Quarter 1st Quarter 2nd Quarter 3rd Quarter 4th Quarter Lab Code TAP- 2196 TAP- 4429 TAP- 6978 TAP- 8815 Volume (m') 3635 3641 3686 3669 Sr-89 < 0.0003 < 0.0005 < 0.0007 < 0.0005 Sr-90 < 0.0002 < 0.0003 < 0.0003 < 0.0004 Be-7 0.080 +/- 0.015 0.110 +/- 0.020 0.081 +/- 0.014 0.069 +/- 0.012 K-40 0.022 +/- 0.012 0.027 0.022 0.024 Nb-95 0.0007 0.0008 0.0004 0.0008 Zr-95 0.0010 0.0010 0.0006 0.0007 Ru-103 0.0008 0.0008 0.0004 0.0006 Ru-1 06 0.0071 0.0057 0.0043 0.0076 Cs-1 34 0.0009 0.0006 0.0004 0.0008 Cs-1 37 0.0006 0.0004 0.0005 0.0006 Ce-I 41 0.0008 0.0015 0.0011 0.0015 Ce-1 44 0.0042 0.0046 0.0032 0.0051 Location T-11 (C)

Quarter 1st Quarter a 2nd Quarter 3rd Quarter 4th Quarter Lab Code TAP- 2197 TAP- 4430 -TAP- 6979 TAP- 8816 Volume (ma) 3702 3673 3749 3787 Sr-89 < 0.0010 < 0.0005 < 0.0006 < 0.0005 Sr-90 < 0.0007 < 0.0003 < 0.0003 < 0.0005 Be-7 0.075 +/- 0.015 0.119 +/- 0.019 0.093 +/- 0.013 0.053 +/- 0.012 K-40 < 0.021 < 0.030 < 0.024 < 0.024 Nb-95 < 0.0007 < 0.0010 < 0.0008 < 0.0012 Zr-95 < 0.0014 < 0.0018 < 0.0012 < 0.0011 Ru-1 03 < 0.0010 < 0.0009 < 0.0007 < 0.0009 Ru-1 06 < 0.0051 < 0.0068 < 0.0039 < 0.0025 Cs-1 34 < 0.0008 < 0.0003 < 0.0006 < 0.0006 Cs-137 < 0.0006 < 0.0006 < 0.0006 <.0.0006 Ce-141 < 0.0009 < 0.0019 < 0.0007 < 0.0014 Ce-1 44 < 0.0023 < 0.0033 < 0.0044 < 0.0023 a Duplicate analysis, refer to Appendix C.

12-4

TOLEDO Table 12. Airborne particulates, analyses for strontium-89, strontium-90 and gamma-emitting isotopes.

Collection: Quarterly Composite 3

Units: pCi/m Location T-1 2 (C)

Quarter 1st Quarter 2nd Quarter 3rd Quarter 4th Quarter Lab Code TAP- 2199 TAP- 4431 TAP- 6980 TAP- 8817 Volume (me) 3637 3647 3692 3773 Sr-89 < 0.0006 < 0.0005 < 0.0009 < 0.0005 Sr-90 < 0.0003 < 0.0003 < 0.0004 < 0.0004 Be-7 0.077 +/- 0.014 0.119 + 0.018 0.084 + 0.015 0.067 + 0.014 K-40 < 0.022 0.030 0.022 0.024 Nb-95 < 0.0010 0.0007 0.0005 0.0007 Zr-95 < 0.0011 0.0015 0.0011 0.0020 Ru-1 03 < 0.0007 0.0007 0.0005 0.0008 Ru-1 06 < 0.0060 0.0069 0.0043 0.0046 Cs-I 34 < 0.0009 0.0005 0.0007 0.0007 Cs-137. < 0.0005 0.0008 0.0003 0.0009 Ce-1 41 < 0.0015 0.0018 0.0014 0.0015 Ce-i 44 < 0.0046 0.0055 0.0034 0.0029 Location T-27 (C)

Quarter 1st Quarter 2nd Quarter 3rd Quarter 4th Quarter Lab Code TAP- 2200 TAP- 4432 TAP- 6981 TAP- 8818 Voldime (mrn- 3653 3668 3698 3741 Sr-89 < 0.0006 < 0.0005 < 0.0007 < 0.0005 Sr-90 < 0.0004 < 0.0003 < 0.0004 < 0.0004 Be-7 0.087 +/- 0.017 0.113 +/- 0.017 0.074 +/- 0.016 0.065 +/- 0.014 K-40 < 0.026 < 0.027 < 0.025 < 0.024 Nb-95 < 0.0009 < 0.0009 < 0.0005 < 0.0005 Zr-95 < 0.0007 < 0.0022 < 0.0011 < 0.0010 Ru-1 03 < 0.0007 < 0.0006 < 0.0008 < 0.0010 Ru-1 06 < 0.0056 < 0.0086 < 0.0018 < 0.0042 Cs-1 34 < 0.0009 < 0.0005 < 0.0009 < 0.0005 Cs-1 37 < 0.0007 < 0.0006 < 0.0004 < 0.0006 Ce-141 < 0.0014 < 0.0013 < 0.0010 < 0.0014 Ce-144 < 0.0034 < 0.004 < 0.0020 < 0.0022 12-5

TOLEDO Table 13. Area monitors (TLD), Quarterly.

Units: mR/91 days 1st Qtr. 2nd Qtr. 3rd Qtr. 4th Qtr.

Indicator T-1 11.1 +/-0.6 8.7 +/- 1.9 11.6 +/- 1.0 12.5 +/- 1.2 T-2 13.2 +/- 0.5 10.8 +/- 1.9 13.5 +/- 0.9 14.3.4- 0.5 T-3 13.6 +/- 0.9 10.6 +/-+2.0 14.5 +/- 1.0 '14.4 +/- 1.0 T-4 12.9 +/- 0.6 10.3 +/- 1.9 13.5 +/- 0.6 13.5 +/- 0.5 T-5 14.6 +/- 0.7 12.3 +/- 1.9 15.4 +/- 0.8 16.0 +/- 0.5 T-6 12.6 +/- 0.6 10.4 +/- 2.0 13.7 +/- 1.0 13.5 +/- 0.5 T-7 18.4 +/- 0.5 15.4 +/- 2.0 20.6 +/- 1.0 19.9 +/- 0.7 T-8 23.3 +/- 1.2 19.2 +/- 1.9 26.1 +/- 1.4 24.5 +/- 0.6 T-10 15.7 +/-0.6 13.4 +/- 1.9 16.8 +/-0.8 17.5 +/-0.8 T-38 11.5 +/-0.5 10.6 +/-2.1 12.5 +/-0.8 14.2 +/- 1.0 T-39 12.7 +/- 0.8 10.5 +/- 1.9 13.7 +/- 1.0 13.1 +/- 0.5 T-40 15.2 +/- 0.5 13.5 +/- 2.1 16.6 +/- 0.6, 16.6 +/- 0.5 T-41 9.6 +/- 0.6 10.9 +/- 1.9 11.3 +/- 1.0 14.3 +/-0.5 T-42 13.2 +/- 0.9 10.7 +/- 2.0 14.5 +/- 1.2 1317 +/- 0.9 T-43 17.0 +/- 0.9 14.1 +/- 2.0 18.7 +/- 1.0 17.6 +/- 0.6 T-44 19.1 +/- 0.9 16.4 +/- 2.0 21.0 +/- 1.2 20.1 +/- 0.8 T-45 21.7 +/- 0.6 19.6 +/- 2.0 24.7 +/- 0.7 24.0 +/- 0.6 T-46 13.9 +/- 0.8 11.7 +/- 2.0 15.1+/- 1.0 14.8 +/- 0.8 T-47 11.4 +/-0.9 7.7 +/- 1.9 14.4 +/- 1.4 10.8 +/--0.6 T-48 12.5 +/-0.4 11.5 +/-2.9 14.1 +/-0.6 13.5 +/-0.4 T-49 13.0 +/- 0.6 10.8 +/- 1.9 14.8 +/- 0.8 ND a T-50 13.5 +/- 0.6 14.8 +/- 2.2 15.4 +/- 0.8 18.3 +/- 1.3 T-51 17.8 +/- 1.6 17.3 +/- 2.5 20.6 +/- 2.1 22.3 +/- 1.1 T-52 18.1 +/- 1.1 16.1 +/- 2.0 21.2 +/- 1.3 19.8 +/- 0.7 T-53 16.2 +/- 0.4 ND a 19.2 +/- 0.7, 16.5 +/- 1.3 T-54 17.4 +/- 0.6 - - --- 16.2 +/- 2.1 - 20.4 +/- 0.7 20.2 +/- 0.7 T-55 14.1 +/- 1.0 13.7 +/- 2.0 16.2 +/- 1.4 17.0 +/- 0.5 T-60 11.0 +/- 0.6 10.7 +/- 1.5 14.1 +/-+1.8 12.7 +/- 1.1 T-62 12.2 +/-0.6 11.1 +/-0.9 12.8 +/-0.6 11.9 +/-0.7 T-65 .18.6 +/-0.4 17.1 +/-0.7 19.6 +/-0.9 18.1 +/-0.7 T-66 20.6 +/- 0.6 19.3 +/- 1.0 21.9 +/- 0.7 21.4 +/- 1.0 T-67 22.1 +/- 0.7 18.0 +/- 0.8 23.1 +/- 0.6 20.5 +/- 0.8 T-68 18.7 +/- 0.5 17.7 +/- 2.0 18.4 +/- 0.8 17.4 +/- 0.9 T-69 18.7 +/- 0.5 17.0 +/- 0.5 19.9 +/- 0.7 18.7 +/- 0.6 T-71 19.4 +/- 0.4 17.4 +/- 1.3 19.6 +/- 0.4 15.8 +/- 0.9 T-73 15.7 +/- 1.3 13.0 +/- 0.7 15.8 +/- 1.4 14.3 +/- 0.8 T-74 17.4 +/- 0.5 15.9 +/- 0.9 17.7 +/- 0.7 17.4 +/- 1.1 T-75 16.3 +/- 0.4 14.3 +/- 0.6 17.7 +/- 0.5 16.3 +/- 0.6 T-76 13.1 +/- 0.5 10.8 +/- 0.6 13.0 +/- 0.5 12.0 +/- 0.7 T-91 19.6 +/- 1.3 18.0 +/- 1.0 21.0 +/- 1.1 18.2 +/- 1.1 T-92 11.5 +/-0.3 13.8 +/-0.6 12.1 +/-0.5 15.6 +/-0.8 a ND = No Data, TLD lost in the field.

13-1

TOLEDO Table 13. Area monitors (TLD), Quarterly.

Units: mRI91 days 1st Qtr. 2nd Qtr. 3rd Qtr. 4th Qtr.

Indicator T-93 16.0 +/- 0.4 14.3 +/- 0.7 16.6 +/- 0.7 15.8 +/- 0.8 T-94 17.4 +/- 0.8 16.0 +/- 1.1 19.2 +/- 1.2 18.4 +/- 1.2 T-112 13.9 +/- 0.9 15.2 +/-0.6 a 15.9 +/- 0.6 12.0 +/- 0.7 T-121 19.0 +/- 1.2 19.7 + 0.9 21.1 +/- 1.6 20.6 +/- 0.9 T-122 15.4 +/-1.6 15.4 +/-0.6 16.9 +/- 1.6 16.4 +/- 0.6 T-123 17.5 +/- 1.2 17.7 +/- 0.7 19.7 +/- 1.4 19.1 +/- 0.8 T-125 15.9 +/- 0.9 16.5 +/- 0.6 18.4 +/- 0.9 17.7 +/- 0.6 T-1 26 16.6 +/- 0.4 15.7 +/-0.9 18.7 +/- 0.9 17.2 +/- 1.0 T-1 27 17.9 +/- 0.4 19.0 + 1.0 20.6 +/- 0.5 20.2 + 1.0 T-1 28 18.9 +/- 1.6 18.7 +/- 0.7 20.8 +/- 2.0 19.9 +/- 0.6 T-1 42 12.1 +/- 0.5 11.3 +/- 0.6 13.1 +/- 0.6 12.6 +/- 0.6 T-1 50 13.2 +/- 0.9 13.0 +/- 1.0 14.6 +/- 0.9 14.6 +/- 0.9 T-151 16.5 +/- 0.6 17.4 + 0.7 19.0 +/--0.7 19.7 +/- 1.2 T-153 17.6 +/- 0.4 15.5 +/- 0.6 19.5 +/- 0.5 16.8 +/- 0.7 T-154( 15.2 +/- 0.8 17.6 +/-0.6 15.7 +/- 0.8 15.5 +/-0.8 T-201 12.6 +/- 0.9 11.8 +/-0.3 13.2 +/- 1.1 13.2 +/-0.5 T-202 15.0 +/-1.2 13.2 +/-0.5 14.4 +/- 1.3 14.7 +/- 1.0 T-203 14.9 +/- 1.1 13.8 + 0.9 14.5 +/- 1.1 15.7 +/- 1.0 T-204 12.8 +/- 1.1 11.4 +/-0.7 12.9 +/- 1.1 13.2 +/- 1.0 T-205 11.4 +/- 1.1 9.7 +/- 0.3 10.8 1.1 11.2 +/- 0.6 T-206 10.5 +/- 1.0 9.9 +/-0.3 10.4 +/- 1.1 11.5 +/- 0.6 T-207 9.7 +/- 1.2 6.9 +/- 0.4 9.6 +/- 1.4 8.1 +/- 0.6 T-208 11.0 +/- 1.8 9.8 +/- 0.4 11.4 +/- 2.0 11.2 +/-0.7 T-211 12.8 +/- 0.7 10.5 +/-2.7 12.2 +/- 0.7 11.0 +/-0.3 T-212 11.8 +/- 0.4 10.6 + 0.7 11.6 +/- 0.5 12.5 +/- 0.7 T-213 18.7 +/- 0.6 18.0 +/- 3.3 20.1 +/- 0.7 19.3 +/- 0.5 T-214 18.7 +/- 0.8 10.1 +/-0.7 20.9 +/- 0.6 20.5 +/- 0.6 T-2 15 20.3 +/- 0.8 15.9 + 0.7 20.5 +/- 0.9 18.5 +/- 0.7 T-216 19.1 +/- 0.7 16.1 +/-1.1 20.3 +/- 1.2 18.0 +/- 1.2 T-217 20.5 +/- 0.6 18.4 +/- 1.5 22.5 +/- 0.8 20.9 +/- 1.3 T-218 20.8 +/- 1.1 18.4 +/- 0.7 22.8 +/- 1.0 21.0 +/- 0.8 T-219 17.0 +/- 1.2 15.4 +/- 1.4 18.4 +/- 1.2 18.6 +/- 0.8 T-220 19.8 +/- 1.1 18.4 +/- 1.4 21.8 +/- 1.2 20.7 +/- 1.8 T-222 12.7 +/- 0.9 11.1 +/-0.6 13.5 +/- 0.9 12.8 +/- 0.7 T-223 13.6 +/- 0.7 13.4 +/- 0.4 14.0 +/- 0.7 15.4 +/- 0.5 T-224 16.2 +/- 0.6 13.1 +/-0.4 17.2 +/- 0.7 15.2 +/- 0.6 Mean +/- s.d. 15.6 +/- 3.3 14.1 +/- 3.3 16.9 +/- 3.8 16.4 +/- 3.4 a A duplicate sample was received from this location; second dosimeter reading, 15.5 +/- 0.6.

13-2

TOLEDO Table 13. Area monitors (TLD), Quarterly.

Units: mRJ91 days 1st Qtr. 2nd Qtr. 3rd Qtr. 4th Qtr.

Control T-9 13.5 +/- 0.5 11.7 +/- 1.9 15.1 +/- 0.9 15.5 +/- 0.8 T-1 1 13.4 +/- 0.5 10.5 +/- 1.9 13.9 +/- 0.6 13.9 +/- 0.7 T-1 2 19.6 +/- 0.6 16.7 +/- 2.0 22.2 +/- 1.5 20.8 +/- 0.7 T-24 17.7 +/- 0.8 15.4 +/- 1.9 19.8 +/- 0.9 19.5 +/- 0.4 T-27 18.9 +/- 0.7 16.4 +/- 1.9 20.5 +/- 0.9 20.5 +/- 0.6 Mean +/- s.d. 16.6 +/- 3.0 14.1 +/- 2.8 18.3 +/- 3.6 18.0 +/- 3.1 T-95 17.2 +/- 0.5 15.7 +/- 0.7 18.6 +/- 0.8 17.2 +/- 0.8 T-100 16.8 +/- 1.5 15.5 +/- 0.9 18.0 +/- 1.7 16.1 +/- 1.1 T-111 17.5 +/- 2.0 17.5 +/- 0.6 19.3 +/- 2.1 18.9 +/- 0.8 T-1 24 16.0 +/- 0.9 15.1 +/- 1.6 17.3 +/- 0.8 16.1 +/- 1.6 T-155 12.4 +/- 0.7 12.4 +/- 0.7 13.2 +/- 0.8 13.7 +/- 0.8 T-221 16.6 +/- 0.9 16.5 +/- 1.1 18.0 +/- 1.0 18.8 +/- 1.2 Mean +/- s.d. 16.1 +/- 1.9 15.5 +/- 1.7 17.4 +/- 2.2 16.8 +/- 2.0 QC T-80 .10.2 +/- 0.5 9.2 +/- 0.5 .10.4 +/-0.7 10.2 +/- 0.6 T-81 *.17.7 +/- 0.5 16.0 +/- 0.6 18.4 +/- 0.8 17.7 +/- 0.7 T-82 10.6 +/- 0.4 9.4 +/- 0.6 10.2 +/- 0.5 10.4 +/- 0.7 T-83 9.4 +/- 0.5 -10.0 +/-0.9 10.0 +/- 0.6 11.4 +/- 1.0 T-84 12.2 +/- 0.9 -10.3 +/-0.6 .11.9 +/-1.0 11.6 +/- 0.7 T-85 14.6 +/- 0.5 12.9+/- 0.9 14.4 +/- 0.6 14.1 +/- 0.9 T-86 21.4 +/- 1.0 .19.4 +/- 0.8 22.4 +/- 1.0 21.6 +/- 1.0 T-88 14.8 +/- 0.9 .18.5 +/- 0.8 15.8 +/- 1.2 18.4 +/- 0.9 T-89 +/-

17.90.6 .16.3 +/- 0.8 19.9 +/- 0.5 18.7 +/- 0.9 T-113 15.0 +/-0.5 ,15.3 +/-0.8 -16.6 +/- 1.0 15.7 +/- 0.8 T-114 13.5 +/- 0.6 13.4 +/- 0.9 14.5 +/- 0.6 13.8 +/- 0.8 T-115 "12.5 +/-0.8 9.6 +/- 0.5 13.2 +/- 0.9 16.1 +/- 0.6 T-116; 15.8 +/- 0.6 16.6 +/- 1.1 16.8 +/- 0.7 17.5 +/- 0.9 T-117 13.4 +/- 1.2 16.0 +/- 3.6 14.5 +/- 1.0 14.6 +/- 1.8 T-118 14.7 +/-0.8 15.1 +/- 1.0 16.1 +/- 1.1 15.7 +/- 1.1 T-119 13.3 +/-+0.6 13.0 +/- 0.7 15.0 +/- 0.7 13.7 +/- 0.6 10.8 +/- 0.6 12.7 +/- 0.7 11.8 +/- 0.8 T-120 11.7 +/- 0.5 T-200. 12.1 +/- 1.0 11.2 +/--2.3 13.7 +/- 1.1 13.7 +/-0.9 Mean +/- s.d. 13.9 +/- 3.0 13.5 +3.3 14.8 +/- 3.3 14.8 +/- 3.2 Shield T-87 7.9 +/- 0.7 7.2 +u.8 7.5 +/- 0.7 7.6 +/- 0.8 13-3

TOLEDO Table 14. Area monitors (TLD), Annual.

Units: mRI365 days Indicator 2007 T-1 42.0 +/- 1.0 T-2 52.7 +/- 1.4 T-3 51.6 +/- 1.8 T-4 45.1 +/- 1.5 T-5 56.8 +/- 1.4 T-6 48.1 +/- 1.1 T-7 68.3 +/- 4.8 T-8 89.9 +/- 2.1 T-1 0 63.1 +/- 2.8 T-38 47.6 +/- 1.3 T-39 46.6 +/- 1.6 T-40 61.7 +/- 1.7 T-41 42.8 +/- 1.3 T-42 49.4 +/- 2.0 T-43 64.5 +/- 1.7 T-44 75.2 +/- 3.2 T-45 87.2 +/- 3.9 T-46 54.7 +/- 2.7 T-47 36.5 +/- 1.2 T-48 45.5 +/- 1.4 T-49 NDa T-50 65.8 +/- 2.1 T-51 78.9 +/- 1.4 T-52 72.8 +/- 2.7 T-53 NDa T-54 78.4 +/- 2.2 T-55 62.7 +/- 4.8 T-60 53.8 +/- 3.8 T-62 47.4 +/- 3.0 T-65 75.3 +/- 5.1 T-66 79.5 +/- 2.4 T-67 79.8 +/- 2.2 T-68 66.2 +/- 1.4 T-69 71.7 +/-2.0 T-71 68.0 +/-2.1 T-73 55.6 +/- 1.3 T-74 65.7 +/- 2.2 T-75 64.6 +/- 3.7 T-76 49.9 +/- 2.0 T-91 75.6 +/- 1.5 T-92 50.5 +/- 1.9 a "ND" = No data; TLD missing in field.

14-1

TOLEDO Table 14. Area monitors (TLD), Annual.

Units: mR/365 days Indicator 2007 T-93 62.3 +/- 1.6 T-94 7.2.0 +/- 2.0 T-112 54.4 +/- 1.7 T-121 78.0 +/- 1.9 T-122 60.2 +/- 2.2 T-123 .69.8 +/- 2.2 T-125 64.0 +/- 1.7 T-126 61.9 +/- 1.7 T-127 73.7 +/- 1.8 T-128 75.2 +/- 6.2 T-142 42.2 +/- 1.6 T-150 53.8 +/- 1.8 T-151 71.5 +/- 1.6 T-153 73.4 +/- 1.8 T-154 61.7 +/- 1.7 T-201 53.6 +/- 2.6 T-202 54.7 +/- 2.9 T-203 56.2 +/- 2.7 T-204 44.7 +/- 2.8 T-205 42.4 +/- 2.9 T-206 41.6 +/- 2.6 T-207 39.6 +/- 2.5 T-208 43.3+/- 2.6 T-211 38.4 +/- 2.6 T-212 37.7 +/- 1.2 T-213 .. 61.6 +/- 2.6 T-214 40.3 +/- 1.8 T-215 65.0 +/- 2.3 T-216 59.3 +/- 2.8 T-217 68.4 +/- 1.5 T-218 72.6 +/- 2.1 T-219 54.5 +/- 2.2 T-220 66.2 +/- 2.6 T-222 45.1 +/- 1.6 T-223 47.8 +/- 1.6 T-224 50.7 +/-2.7 Mean +/- s.d. 59.3 +/- 13.1 14-2

TOLEDO Table 14. Area monitors (TLD), Annual.

Units: mRJ365 days Control 2007 T-9 54.8 +/- 1.0 T-11, 46.6 +/- 0.9 T-1 2 78.7 +/- 2.1 T-24 75.5 +/- 2.1 T-27 81.9 +/- 1.8 Mean + s.d. 67.5 +/- 15.8 T-95 68.9 +/- 3.2 T-100 62.1 +/- 2.1 T-111 64.7 +/- 2.7 T-124 59.1 +/- 4.6 T-155 52.1 +/- 2.2 T-221 60.2 _2.1 Mean + s.d. 61.2 +/- 5.7 QC T-80 44.9 +/- 1.6 T-81 69.8 +/- 1.4 T-82 44.3 +/- 1.2 T-83 41.7 +/- 1.6 T-84 49.2 +/- 1.8 T-85 53.8 +/- 2.9 T-86 82.1 +/- 4.3 T-88' 66.7 +/- 2.2 T-89 50.2 +/- 4*3 T-113 59.8 +/- 2.4 T-114 54.6 +/- 2.0 T-115 40.8 +/- 1.6 T-116 67.4 +/- 1.3 T-117 56.8 +/- 1.3 T-118 63.0 +/- 1.3 1-119 54.5 +/- 2.2 T-120 46.0 +/- 1.3 T-200 49.8 +/- 2.6 Mean +/- s.d. 55.3 +/- 11.1 Shield T-87 27.1 +/- 1.2 14-3

Table 15. Milk, analyses for strontium-89, strontium-90, iodine-131, gamma emitting isotopes, calcium and stable potassium.

Monthly collections, location T-24 Units: pCi/L Date Collected 01-31-07 02-28-07 03-28-07 04-25-07 Lab Code TMI- 642 TMI- 1116 TMI- 1719 TMI- 2321 1-131 < 0.3 < 0.2 < 0.3 < 0.2 Sr-89 < 0.5 < 0.5 < 0.6 < 0.7 Sr-90 0.7 +/- 0.3 0.9 +/- 0.3 0.7 +/- 0.4 0.9 +/- 0.4 K-40 1315 +/- 105 1341 +/- 112 1415 +/- 108 1397 +/- 126 Cs-134 < 3.0 < 2.3 < 2.6 <3.6 Cs-137 < 4.3 < 3.4 < 3.0 < 4.2 Ba-La-1 40 < 3.1 < 2.2 < 1.9 < 3.5 Ca (g/L) 1.42 1.04 1.27 1.26 Sr-90/g Ca 0.49 0.87 0.55 0.71 K (g/L) 1.52 +/- 0.12 1.55 +/- 0.13 1.64 +/- 0.12 1.62 +/- 0.15 Cs-137/g K < 2.83 < 2.19 < 1.83 < 2.59 Date Collected 05-30-07 06-27-07 08-01-07 08-29-07 Lab Code TMI- 3225 TMI- 3966 TMI- 5016 TMI- 5774 1-131 < 0.4 < 0.4 < 0.3 < 0.3" Sr-89 < 0.6 < 0.7 < 0.5 < 0.6 Sr-90 0.7 +/- 0.3 < 0.7 1.0 +/- 0.4 0.9 +/- 0.4 K-40 1342 +/- 113 1401 +/- 128 1449 +/- 113 1461 +/- 110 Cs-1 34 < 3.3 < 4.2 < 2.7 < 2.8 Cs-137 <4.3 < 3.9 <3.1 < 2.5 Ba-La-140 < 2.5 < 2.3 < 3.3 < 4.7 Ca (g/L) 1.25 1.21 1.32 1.30 Sr-90/g Ca 0.56 - - <0.58 0.76 0.69 K (g/L) 1.55 +/- 0.13 1.62 +/- 0.15 1.68 +/- 0.13 1.69 +/- 0.13 Cs-1 37/g K < 2.77 < 2.41 < 1.85 < 1.48 09-26-07 Date Collected 10-31-07 11-28-07 12-27-07 Lab Code TMI- 6541 TMI- 7621 TMI- 8112 TMI- 8623 1-131 < 0.2 < 0.3 < 0.4 < 0.4 Sr-89 < 0.7 < 1.0 < 0.8 < 0.7 Sr-90 0.9 + 0.4 0.8 +/- 0.4 < 0.5 0.9 +/-.0.4 K-40 1394 + 120 1338 +/- 111 1314 +/- 104 1331 +/- 119 Cs-134 < 2.6 < 2.9 < 3.5 < 2.3 Cs-137 < 2.9 < 2.7 < 4.3 < 4.5 Ba-La-140 < 5.5 < 4.8 < 4.6, < 1.8 Ca (g/L) 1.54 1.16 1.62 .1.40 Sr-90/g Ca 0.58 0.69 < 0.31 0.64 K (g/L) 1.61 +/- 0.14 1.55 +/- 0.13 1.52 +/- 0.12 1.54 +/- 0.14 Cs-137/g K < 1.80 < 1.74 < 2.83 < 2.92 15-1

Table 16. Ground water samples, analyses for gross beta, tritium, strontium-89, strontium-90 and gamma-emitting isotopes.

Collection: Quarterly Units: pCi/L Period 1st Qtr. 2nd Qtr. 3rd Qtr. 4th Qtr.

Location T-27 (C)

Lab Code ND TWW- 3345 TWW- 5118, TWW- 6835 Req. LLD Date Collected 05-31-07 07-13-07 10-05-07 Gross beta < 1.8. < 1.8 3.6 +/- 1.2 4.0 H-3 <330 <330 < 330 330 Sr-89 - < 0.7 < 1.1 < 0.8 Sr-90 -< 0.6 < 0.5 < 0.5 Mn-54 -< 4.5 < 2.8 < 3.4 15

  • Fe-59 -< 9.1 < 5.6 <3.2 30 Co-58 -< 4.1 < 2.2 < 4.4 15 Co-60 -< 3.0 < 2.1 < 2.1 15 Zn-65 - < 7.3 < 3.9 < 6.9 30 Zr-Nb-95 - < 4.4 < 3.7 < 6.2 15 Cs-134 - < 3.4 < 2.8 < 4.6 15 Cs-137 - < 4.1 < 1.7 < 6.1 18 Ba-La-140 - < 6.3 < 8.9 < 8.5 15 Location T-226 (I)

Lab Code TWW- 1749 TWW- 3347 TWW- 5120 TWW- 6837 Req. LLD Date Collected 03-28-07 05-31-07 07-13-07 10-05-07 Gross beta 3.3 +/- 1.2 < 1.9 < 1.7 3.0 +/- 1.2 4.0 H-3 < 330 < 330 < 330 <330 330 Sr-89 < 0.5 < 0.9 < 1.4 < 0.8 Sr-90 < 0.6 < 0.5 < 0.6 < 0.5 Mn-54 <2.2 < 2.2 < 2.4 < 3.2 15 Fe-59 <2.8 < 7.2 < 4.8 < 5.2 30 Co-58 < 2.2 < 3.3 < 2.9 < 2.0 15 Co-60 < 2.6 < 2.6 < 2.2 < 1.6 15 Zn-65 < 5.8 < 6.1 < 2.0 < 5.0 30 Zr-Nb-95 < 2.8 < 4.3 < 3.2 < 2.8 15 Cs-134 < 3.9 < 3.1 < 2.2 < 2.9 15 Cs-137 < 3.0 < 3.6 < 3.9 < 3.9 18 Ba-La-140 < 3.9 < 2.7 < 6.1 < 2.8 15 16-1

Table 16. Ground water samples, analyses for gross beta, tritium, strontium--89, strontium-90 and gamma-emitting isotopes.

Collection: Quarterly Units: pCi/L Period 1st Qtr. 2nd Qtr. 3rd Qtr. 4th Qtr.

Location T-141 (QC)

Lab Code TWW- 1748 TWW- 3346 TWW- 5119 TWW- 6836 Req. LLD Date Collected 03-28-07 05-31-07 07-13-07 10-05-07 Gross beta < 1.7 < 2.1 < 1.6 2.2 +/- 1.0 4.0 H-3 < 330 < 330 < 330 < 330 330 Sr-89 < 0.6 < 0.5 < 1.1 < 0.9 Sr-90 1.1 +/- 0.4 <0.5 < 0.4 < 0.5 Mn-54 < 3.7 < 2.0 < 2.5 < 3.6 15 Fe-59 < 2.6 < 5.3 < 5.2 < 4.2 30 Co-58 < 3.1 < 1.6 < 2.3 < 2.2 15 Co-60 < 0.9 < 2.9 < 2.6 < 5.8 15 Zn-65 < 3.7 < 4.0 < 4.9 < 4.8 30 Zr-Nb-95 < 3.0 < 3.1 < 3.8 < 4.0 15 Cs-134 < 1.7 < 3.5, < 2.7 < 2.9 15 Cs-137 < 3.0 < 3.6 < 3.2 < 4.4 18 Ba-La-140 < 2.3 < 3.1 < 4.6 < 7.6 15 16-2

This Page Intentionally Left Blank 17-1

Table 18. Wild meat, analyses for gamma-emitting isotopes.

Collection: Annually.

Units: pCi/g wet Location T-31 (I) T-210 (C)

Lab Code TWL- 8720 TWL- 7922 Date Collected 12-30-07 11-14-07 Sample Type Muskrat Muskrat Be-7 < 0.14 < 0.048 K-40 2.35 +/- 0.28 2.25 +/- 0.15 Nb-95 < 0.012 < 0.004 Zr-95 < 0.015 < 0.009 Ru-1 03 < 0.026 <-0.005 Ru-106 < 0.062 < 0.049 Cs-1 34 < 0.008 < 0.005 Cs-1 37 < 0.010 < 0.005 Ce-141 < 0.034 < 0.013 Ce-144 < 0.079 < 0.047 18-1

Table 19. Green leafy vegetables, analyses for strontium-89, strontium-90, iodine-131 and other gamma-emitting isotopes.

Collection: Monthly, in season Units: pCi/g wet Location T-227 (I)

Lab Code TVE- 5021 TVE- 5773 Date Collected 07-25-07 08-28-07 Sample Type Cabbage Cabbage Sr-89 < 0.003 < 0.002 Sr-90 <0.002 < 0.001 1-131 < 0.026 < 0.016 K-40 2.42 +/- 0.26 1.67 +/- 0.24 Nb-95 < 0.008 < 0.011 Zr-95 < 0.016 < 0.012 Cs-1 34 < 0.004 < 0.005 Cs-1 37 < 0.006 < 0.010 Ce-1 41 < 0.031 < 0.016 Ce-144 < 0.091 < 0.046 Location T-19 (I)

Lab Code TVE- 5019 TVE- 5771 TVE- 6542 TVE- '7622 Date Collected 07-25-07 08-28-07 09-25-07 10-30-07 Sample Type Cabbage Cabbage Vegetation Cabbage Sr-89 < 0.003 < 0.002 < 0.002 < 0.003 Sr-90 < 0.002 < 0.001 0.004 +/- 0.001 0.008.+/- 0.001 1-131 < 0.026 < 0.024 < 0.016 < 0.017 K-40 2.16 +/- 0.24 1.90 +/- 0.24 2.10 +/- 0.21 2.71 +/- 0.24 Nb-95 < 0.011 < 0.006 < 0.009 < 0.009 Zr-95 < 0.010 < 0.014 < 0.018 < 0.010 Cs-134 < 0.006 < 0.008 < 0.008 < 0.009 Cs-137 < 0.008 < 0.006 < 0.008 < 0.009 Ce-141 < 0.012 < 0.020 < 0.017 < 0.016 Ce-144 < 0.061 < 0.071 < 0.036 < 0.069 Location T-37 (C)

Lab Code TVE- 5020 TVE- 5772 TVE- 6543 TVE- 7623 Date Collected 07-24-07 08-28-07 09-25-07 10-30-07 Sample Type Cabbage Cabbage Vegetation Cabbage Sr-89 < 0.002 < 0.002 < 0.002 < 0.002 Sr-90 < 0.001 < 0.001 0.001 +/- 0.001 < 0.001 1-131 < 0.028 < 0.023 < 0.022 < 0.010 K-40 2.43 +/- 0.26 1.44 +/- 0.32 1.59 +/- 0.26 1.68 +/- 0.20 Nb-95 < 0.011 < 0.006 < 0.008 < 0.006 Zr-95 < 0.027 < 0.021 < 0.018 < 0.009 Cs-134 < 0.008 < 0.011, < 0.013 < 0.006 Cs-137 < 0.011 < 0.013 < 0.011 < 0.005 Ce-141 < 0.019 < 0.029 < 0.024 < 0.015 Ce-144 < 0.073 < 0.054 < 0.079 < 0.060 19-1

Table 20. Fruit, analyses for strontium-89, strontium-90, iodine-1 31 and other gamma-emitting isotopes.

Collection: Monthly, in season Units: pCi/g wet Location T-8 (I) T-25 (I)

Lab Code TVE- 6174 TVE- 6175 Date Collected 09-12-07 09-12-07 Sample Type Apples Apples Sr-89 < 0.004 < 0.003 Sr-90 < 0.002 0.002 +/- 0.001 1-131 < 0.057 < 0.044 K-40 1.38 +/- 0.18 1.22 +/- 0.17 Nb-95 < 0.010 < 0.009 Zr-95 < 0.012 < 0.011 Cs-1 34 < 0.009 < 0.006 Cs-1 37 < 0.008 < 0.007 Ce-141 < 0.022 < 0.018 Ce-144 < 0.067 < 0.036 Location T-209 (C)

Lab Code TVE- 6176 Date Collected 09-12-07 Sample Type Apples Sr-89 < 0.004 Sr-90 < 0.002 1-131 < 0.031 K-40 1.24 0.17 Nb-95 < 0.010 -- -

Zr-95 < 0.008 Cs-134 < 0.007 Cs-1 37 <0.008 Ce-141 < 0.013 Ce-144 < 0.045 20-1

Table 21. Animal - wildlife feed, analyses for gamma-emitting isotopes.

Collection-- Monthly, in season Units: pCi/g wet Indicators Location T-31 T-1 98 Lab Code TCF- 5928 TCF- 5930 Date Collected 09-05-07 09-05-07 Sample Type Cattails Cattails Be-7 1.13 +/- 0.09 0.30 +/- 0.09 K-40 4.14 +/- 0.16 4.05 +/- 0.17 Nb-95 < 0.010 < 0.006 Zr-95 < 0.012 < 0.015 Ru-103 < 0.006 < 0.005 Ru- 106 < 0.034 < 0.058 Cs-134 < 0.005 < 0.005 Cs-137  : 0.007 < 0.005 Ce-141 <0.022 < 0.015 Ce-144 < 0.057 < 0:049 Control Location T-32 Lab Code TCF- 5929 Date Collected 09-05-07 Sample Type Cattails Be-7 0.41 +/- 0.17 K-40 _ 2.90 +/- 0.36 Nb-95 < 0.015 Zr-95 < 0.020 Ru-1 03 < 0.014 Ru-1 06 < 0.125 Cs-134 < 0.011 Cs- 137 < 0.014 Ce-141 < 0.028 Ce-144 < 0.074 21-1

Table 22. Soil samples, analyses for gamma-emitting isotopes.

Collection: Annual Units: pCi/g dry Location T-1 T-2 T-3 T-4 Lab Code TSO- 2588 TSO- 2589 TSO- 2590 TSO- 2591 Date Collected 04-24-07 04-24-07 04-24-07 04-24-07 Be-7 < 0.27 < 0.55 < 0.34 < 0.37 K-40 10.87 +/- 0.63 4.88 +/- 0.62 6.61 +/- 0.54 16.35 +/- 1.06 Mn-54 < 0.026 < 0.030 < 0.022 < 0.037, Nb-95 < 0.033 < 0.085 < 0.050 < 0.099 Zr-95 < 0.042 < 0.074 < 0.030 < 0.099 Ru-1 03 < 0.026 < 0.065 < 0.045 < 0.077 Ru-1 06 < 0.124 < 0.225 < 0.105 < 0.279 Cs-1 34 < 0.017 < 0.030 < 0.017 < 0.043 Cs-137 0.10 +/- 0.030 0,055 +/- 0.030 < 0.020 < 0.022 Ce-141 < 0.055 < 0.173 < 0.101 < 0.161 Ce-1 44 < 0.126 < 0.211 < 0.127 <0.199 Location T-7 T-8 Lab Code TSO- 2592 TSO- 2593 Date Collected 04-24-07 04-24-07 Be-7 < 0.46 < 0.60 K-40 6.12 +/- 0.61 23.36 +/- 1.03 Mn-54 < 0.022 < 0.036 Nb-95 < 0.063 < 0.141 Zr-95 < 0.054 < 0.085 Ru-1 03 < 0.076 < 0.081 Ru-106 < 0.171 < 0.369 Cs-1 34 < 0.030 < 0.046 Cs-1 37 < 0.023 0.206 +/- 0.057 Ce-1 41 < 0.128 < 0.212 Ce-144 < 0.156 < 0.255 Location . T-9 T-11 T-12 . T-27 Lab Code TSO- 2594 TSO- 2595 TSO- 2596 TSO- 2597 Date Collected 04-24-07 04-24-07 04-24-07 04-24-07 Be-7 1.09 +/- 0.63 < 0.37 0.33 < 0.68 K-40 20.18 +/- 1.04 17.29 +/- 0.82 18.16 +/- 0.85 20.42 +/- 1.21 Mn-54 < 0.029 < 0.029 0.032 < 0.052 Nb-95 < 0.053 < 0.055 0.081 < 0.151 Zr-95 < 0.045 < 0.058 0.066 < 0.110 Ru-103 < 0.057 < 0.023 0.052 < 0.069 Ru-1 06 < 0.176 < 0.155 0.126 < 0.303 Cs-1 34 < 0.018 < 0.019 0.041 < 0.053 Cs-1 37 0.26 +/- 0.042 0.096 + 0.029 0.198 +/- 0.036 0.185 +/- 0.068 Ce-141 < 0.135 < 0.128 0.134 < 0.179 Ce-144 < 0.162 < 0.182 0.163 < 0.235 22-1

Table 23. Treated surface water samples, analyses for gross beta.

Collection: Monthly composites of weekly grab samples Units: pCi/L T-11 (C) T-12 (C)

Lab Code Date Collected Gross Beta Lab Code Date Collected Gross Beta TSWT- 664 01-30-07 2:2 +/- 0.6 TSWT- 665 01-30-07 3.6 +/- 0.6 TSWT- 1152 02-27-07 2.5 +/- 0.4 .TSWT- 1153 02-27-07 2.0 +/- 0.4 TSWT- 1727 03-27-07 1'.8 +/- 0.4 TSWT- 1728 03-27-07 1.9 +/- 0.4 TSWT- 2464 04-24-07 2.2 +/- 0.4 TSWT- 2465 04-24-07 1.3 +/- 0.3 TSWT- 3253 05-29-07 1.5 +/- 0.4 TSWT- 3254 05-29-07 1.6 +/-0.3 TSWT- 4260 06-26-07 1.3 +/-0.2 .TSWT- 4261 06-26-07 0.9 +/- 0.2 TSWT- 5113 07-31-07 1.4 +/-0.5 TSWT- 5114 07-31-07 1.2 +/-0.6 TSWT- 5788 08-28-07 2.3 + 1.0 TSWT- 5789 08-28-07 1.8 +/- 1.1 TSWT- 6546 09-25-07 2.7 + 1.1 TSWT- 6547 09-25-07 2.1 +/-0.9 TSWT- 7705 10-30-07 3.3 + 1.1 TSWT- 7706 10-30-07 1.4 +/-0.9 TSWT- 8113 11-27-07 1.5 +/- 0.4 TSWT- 8114 11-27-07 1.0 +/-0.4 TSWT- 8651 12-26-07 1.5 +/- 0.6 TSWT- 8652 12-26-07 1.6 +/-0.6 T-22 T-50 TSWT- 666 01-30-07 3.4 +/- 0.7 TSWT- 667 01-30-07 2.3 +/- 0.6 TSWT- 1154 02-27-07 2.6 +/- 0.4 TSWT- 1155 02-27-07 2.0 +/- 0.4 TSWT- 1729 03-27-07 2.4 +/- 0.4 TSWT- 1730 03-27-07 2.3 +/- 0.4 TSWT- 2466 04-24-07 1.9 +/-0.4 TSWT- 2467 04-24-07 2.3 +/- 0.4 TSWT- 3255 05-29-07 1.3 +/-0.3 TSWT- 3256 05-29-07 1.4 +/-0.4 TSWT- 4262 06-26-07 1.5 +/-0.3 TSWT- 4263 06-26-07 1.4 +/- 0.3 TSWT- 5115 07-31-07 1.2 +/-0.6 TSWT- 5116 07-31-07 2.6 +/- 1.1 TSWT- 5790 08-28-07 1.7 +/- 1.0 TSWT- 5791 08-28-07 2.8 +/- 1.0a TSWT- 6549 09-25-07 4.5 +/- 1.1 TSWT- 6550 09-25-07 2.3 +/- 1.0 TSWT- 7707 10-30-07 2.1 +/-1.0 TSWT- 7708 10-30-07 2.4 +/- 0.6 TSWT- 8115 11-27-07 1.4 +/-0.4 TSWT- 8116 11-27-07 1.4 +/- 0.4 TSWT- 8653 12-26-07 2.4 +/- 1.1 TSWT- 8654 12-26-07 1.4 +/- 0.6 T-143 (QC)

TSWT- 668 01-30-07 2.1 +/-0.6 TSWT- 1156 02-27-07 1.8 +/-0.4 TSWT- 1731 03-27-07 1.7 +/-0.4 TSWT- 2468 04-24-07 2.3 +/- 0.6 TSWT- 3257 05-29-07 1.2 +/- 0.3 TSWT- 4264 06-26-07 1.3 +/-0.2 TSWT- 5117 07-31-07 1.9 +/-0.6 TSWT- 5792 08-28-07 2.2 +/- 1.0 TSWT- 6551 09-25-07 2.6 +/- 0.6 TSWT- 7709 10-30-07 1.4 +/- 1.1 TSWT- 8117 11-27-07 1.1 +/-0.4 TSWT- 8655 12-26-07 2.9 +/- 1.0 a Result of reanalysis.

b Analysis was run in duplicate (TSWT-8656). Result, 3.3+/- 1.1 pCi/L.

23-1

Table 24. Treated surface water samples, analyses for tritium, strontium-89, strontium-90 and gamma-emitting isotopes.

Collection: Quarterly composites of weekly grab samples Units: pCi/L Location T-11.(C)

Period 1st Qtr. 2nd Qtr. .3rd Qtr. 4th Qtr.

Lab Code TSWT- 2217 TSWT- 4530 TSWT- 7141 TSWT- 8676 Rea. LLD H-3 <330 < 330 < 330 < 330 330 Sr-89 < 0.9 < 0.9 < 1.4 < 0.8 Sr-90 < 0.5 < 0.6 <0.5 < 0.7 Mn-54 < 2.8 < 1.9 < 2.8 < 3.0 15 Fe-59 < 9.5 < 9.1 < 5.1 < 4.9 30 Co-58 < 4.0 < 2.5 < 2.8 < 1.9 15 Co-60 < 2.0 < 2.1 < 1.3 < 2.3 15 Zn-65 < 2.5 < 5.3 < 2.9 < 3.7 30 Zr-Nb-95 < 5.2 < 4.5 < 2.2 < 3.4 15 Cs-1 34 < 2.3 < 2.5 < 2.5 < 2.2 15 Cs-1 37 < 2.8 < 3.5 < 3.0 < 2.7 18 Ba-La-140 < 12.9 < 8.0 < 5.5 < 4.5 15 Location T-1 2 (C)

Period 1st Qtr. 2nd Qtr. 3rd Qtr. 4th Qtr.

Lab Code TSWT- 2218 S TSWT- 4531 TSWT- 7142 TSWT- 8677 Reg. LLD H-3 < 330 < 330 < 330 < 330 330 Sr-89 < 1.0 < 1.5 < 1.1 < 0.6 Sr-90 < 0.4 < 1.0 < 0.6 < 0.6 Mn-54 < 2.8 < 3.2 < 2.2 < 1.7 15 Fe-59 < 7.1 < 5.6 <4.1 < 5.0 30 Co-58 <2.1 < 3.2 < 2.2 < 2.5 15 Co-60 < 1.3 < 2.3 < 2.2 < 2.1 15 Zn-65 < 3.5 < 4.2 < 3.8 < 4.3 30 Zr-Nb-95 < 4.7 < 3.3 < 2.8 < 4.6 15 Cs-1 34 < 2.9 < 2.8 < 2.0 < 3.0 15 Cs-137 < 3.4 < 2.4 <2.7 < 2.9 18 Ba-La-1 40 < 10.7 < 7.6 < 5.4 < 5.5 15 a Duplicate analysis, refer to Appendix C.

24-1

Table 24. Treated surface water samples, analyses for tritium, strontium-89, strontium-90 and gamma-emitting isotopes.

Collection: Quarterly composites of weekly grab samples.

Units: pCi/L Location T-22 Period 1st Qtr. 2nd Qtr. 3rd Qtr. 4th Qtr.

Lab Code TSWT- 2220 TSWT- 4532 TSWT- 7143 TSWT- 8678 Reg. LLD H-3 < 330 < 330 < 330 < 330 330 Sr-89 < 0.9 < 0.9 < 1.2 < 0.7 Sr-90 < 0.4 < 0.5 0.6 +/- 0.3 < 0.6 Mn-54 <2.1 < 1.9 < 2.3 < 4.2 15 Fe-59 < 6.0 < 7.3 < 3.2 < 6.8 30 Co-58 < 2.9 < 2.2 < 2.9 < 6.5 15 Co-60 < 2.1 < 3.3 < 2.4 < 3.7 15 Zn-65 < 4.9 < 3.0 < 2.6 < 7.8 30 Zr-Nb-95 < 3.6 < 3.6 < 4.4 < 4.0 15 Cs-1 34 < 3.2 < 3.1 < 1.8 < 5.0 15 Cs-1 37 < 2.3 < 2.4 < 2.4 < 7.8 18 Ba-La-1 40 < 6.1 < 6.7 < 6.6 < 9.5 15 Location T-50 4th Qtr.

1st Qtr. 2nd Qtr. 3rd Qtr.

Period 1st Qtr. 2nd Qtr. 3rd Qtr. 4th Qtr.

Lab Code TSWT- 2221 TSWT- 4533 TSWT- 7144 TSWT- 8679 Reg. LLD H-3 < 330 < 330 < 330 < 330 330 Sr-89 < 0.9 < 1.0 < 1.0 < 0.6 Sr-90 0.4 +/- 0.2 < 0.6 < 0.6 1.0 +/- 0.4 Mn-54 < 3.2 < 2.6 < 1.7 < 4.1 15 Fe-59 < 6.7 < 7.0 < 3.0 < 4.1 30 Co-58 < 2.7 < 1.8 < 2.4 < 3.7 15 Co-60 < 2.3 < 1.9 < 2.2 < 4.7 15 Zn-65 < 4.8 < 4.6 < 3.0 < 4.6 30 Zr-Nb-95 < 5.2 < 4.0 < 4.0 < 4.9 15 Cs-134 < 2.2 < 2.4 < 1.9 < 4.7 15 Cs-137 < 2.7 < 3.2 < 1.8 < 5.9 18 Ba-La-140 < 7.8 < 10.2 < 9.2 < 10.6 15 24-2

Table 25. Untreated surface water, analyses for gross beta, tritium and gamma emitting isotopes.

Location: T-3 Collection: Monthly composites of weekly grab samples Units: pCi/L Lab Code TSWU- 669 TSWU- 1157 TSWU- 1736 TSWU- 2469 Date Collected 01-30-07 02-27-07 03-27-07 04-24-07 Req. LLD Gross beta 5.6 +/- 0.8 3.6 +/- 0.7 3.1 +/- 0.5 3.6 +/- 0.5 4.0 H-3 < 330 < 330 < 330 < 330 330 Mn-54 < 3.5 < 2.1 < 4.8 < 2.2 15 Fe-59 < 8.6 < 4.9 < 6.2. < 3.8 30 Co-58 < 3.9 < 1.7 < 3.7 < 2.4 15 Co-60 < 3.6 < 2.5 < 3.2 < 1.0 15 Zn-65 < 6.3 <3.1 < 5.2 < 4.4 30 Zr-Nb-95 < 5.9,. < 2.6 < 4.7 <.2.9 15 Cs-134 <,5.2 <2.7 < 4.8 < 2.3 15 Cs-1 37 < 5.8 < 3.0 < 5.7 < 3.6 18 Ba-La-140 < 4.1 < 2.3 < 5.8 <4.1 15 Lab Code TSWU- 3258 TSWU- 4265 TSWU- 5125 TSWU- 5793 Date Collected 05-29-07 06-26-07 07-31-07 08-28-07 Req. LLD Gross beta 2.5 +/- 0.4 1.8 +/- 0.3 2.0 +/- 1.0 2.9 +/- 1.2 4.0 H-3 < 330 < 330 < 330 < 330 330 Mn-54

  • 4.5 < 3.3 < 6.1 < 3.9 15 Fe-59 < 5.7 < 3.5 < 7.5 <6.4 30 Co-58 < 6.0 *<2.3 < 3.1 < 4.3 15 Co-60 < 3.8 < 3.0 < 3.5  :< 3.3 15 Zn-65 < 9.4 < 4.7 < 4.7 < 6.7 30 Zr-Nb-95 < 6.0 < 4.0 < 3.5 < 3.5 15 Cs-134 < 4.6 < 2.9 < 4.2 < 5.9 '15 Cs-137 < 4.9 < 2.2 < 5.8 < 5.4 18 Ba-La-140 < 3.9 < 5.9 < 6.6 <7.9 15 Lab Code TSWU- 6552 TSWU- 7732 TSWU- 8118 TSWU- 8657 Date Collected 09-25-07 10-30-07 11-27-07 12-26-07 Req. LLD Gross beta 1.8 +/- 0.3 2.4 +/- 0.6 3.4 +/- 0:5 3.3 +/- 0.7 4.0 H-3 < 330 < 330 < 330 < 330 330 15 Mn-54 < 3.5 < 2.3 < 2.6 < 2.8 Fe-59 < 7.2 < 5:7 < 9.2 < 5.9 30 Co-58 < 3.9 < 2.4 < 3.5 < 5.3 15 Co-60 < 3.4 < 2.4 < 3.6 < 3.0 15 Zn-65 < 2.6 < 2.0 < 5.4 < 4.7 30 Zr-Nb-95 < 3.3 < 3.0 < 4.6 < 3.9 15 Cs-134 < 4.5 < 2.0 < 4.2 < 3.7 15 Cs-137 < 5.0 < 2.4 <4.1 < 5.3 18 Ba-La-140 < 6.9 < 2.8 < 8.8 < 7.5 15 25-1

Table 25. Untreated surface water, analyses for gross beta, tritium and gamma emitting isotopes.

Location: T-11 (C)

Collection: Monthly composites of weekly grab samples Units: pCi/L Lab Code TSWU- 671 TSWU- 1159 TSWU- 1738 TSWU- 2471

.Date Collected 01-30-07 02-27-07 *03-27-07 04-24-07 Req. LLD Gross beta 5.5 + 1.2 3.8 +/- 0.6 2.0 +/- 0.4 1.8 +/- 0.4 4.0 H-3 < 330 < 330 < 330 < 330 330.

Mn-54 < 2.5 < 3.0 < 2.9 < 3.2 15 Fe-59 < 5.6 < 2.4 < 2.4 < 7.8 30 Co-58 < 2.7 < 2.2 < 2.5 < 5.4 15 Co-60 < 3.2 < 2.2 < 2.3 <4.1 15 Zn-65 < 3.3 < 3.7 < 3.2 < 3.4 30 Zr-Nb-95 <4.1 < 3.7 < 3.8 < 5.1 15 Cs-1 34 < 2.8 < 3.0 < 2.7 < 4.3 15 Cs-1 37 < 2.5 < 2.9 < 3.4 < 3.8 18 Ba-La-140 < 6.2 < 2.2 < 1.7 < 3.7 15 Lab Code TSWU- 3260 TSWU- 4267 TSWU- 5127 a TSWU- 5795 Date Collected 05-29-07 06-26-07 07-:31-07 08-28-07 Req. LLD Gross beta 1.4 +/- 0.3 1.6 +/- 0.3 1.7 +/- 0.6 1.7+/- 1.1 4.0 H-3 < 330 < 330 < 330 < 330 330 Mn-54 < 3.5 < 1.7 < 2.6 < 2.9 15 Fe-59 < 8.6 < 5.0 < 8.7 < 6.5 30 Co-58 < 3.9 < 2.0 < 4.3 < 2.4 15 Co-60 < 2.5 .< 2.6 < 3.0 < 1.7 15 Zn-65 < 3.1 < 3.5 < 3.8 < 2.7 30 Zr-Nb-95 < 2.3 < 4.0 < 6.0 < 3.3 15 Cs-134 < 3.5 < 3.1 < 2.8 < 3.2 15 Cs-137 < 3.7 < 2.9 < 5.3 < 2.7 18 Ba-La-1 40 < 2.2 < 3.8 < 7.7 < 3.6 15 Lab Code TSWU- 6554 TSWU- 7735 TSWU- 8121 TSWU- 8659 Date Collected 09-25-07 10-30-07 11-27-07 12-26-07 Req.. LLD Gross beta 1.5 +/- 0.3 1.2 +/- 0.6 1.7 +/- 0.7 2.8 +/- 0.7 4.0 H-3 < 330 < 330 < 330 555 +/- 103 b 330 Mn-54 < 5.2 < 2.0 < 1.9 < 3.9 15 Fe-59 < 6.7 < 2.2 < 5.4 < 9.6 30 Co-58 <2.9 < 1.7 < 2.2 <4.1 15 Co-60 < 3.5 < 1.8 < 1.9 < 2.4 15 Zn-65 < 10.1 < 4.5 < 6.9  ; 5.8 30 Zr-Nb-95 < 2.3 < 1.8 < 1.9 < 4.5 15 Cs-134 < 3.7 < 2.0 < 3.2 < 4.0 15 Cs-137 < 6.3 <2.3 < 2.6 < 5.6 18 Ba-La-140 < 7.5 < 5.1 < 3.1 < 7.8 15 a Duplicate analysis, refer to Appendix C.

b Analysis was repeated; result of reanalysis, 416 +/- 105 pCi/L.

25-2

Table 25. Untreated surface water, analyses for gross beta, tritium and gamma emitting isotopes.

Location: T-12 (C)

Collection: Monthly composites of weekly grab samples Units: pCi/L Lab Code TSWU- 672 TSWU- 1160 TSWU- 1739 TSWU- 2472 Date Collected 01-30-07 02-27-07 03-27-07 04-24-07 Req. LLD Gross beta 4.5 +/- 0.7 3.7 +/- 0.7 1.9 +/- 0.4 2.1 +/- 0.4 4.0 H-3 < 330 < 330 < 330 < 330 330

< 5.3 15 Mn-54 < 4.0 < 1.9 < 2.2 Fe-59 < 9.2 < 3.5 <2.1 < 6.8 30 Co-58 < 2.9 < 2-.6 < 1.6 < 3.7 15 Co-60 < 1.7 < 1.4 < 0.8 < 5.0 15 Zn-65 < 5.0 < 3.2 < 2.1 < 5.7 30 Zr-Nb-95 < 3.6 < 1.9 < 2.4 < 4.3 .15 Cs-134 < 3.7 < 2.5 < 2.2 < 1.5 15 Cs-137 < 3.9 < 3.2 < 2.9 < 4.5 18 Ba-La- 140 < 4.2 < 2.8 < 2.3 < 5.3 15 Lab Code TSWU- 3261 TSWU- 4268 TSWU- 5129 TSWU- 5796 Date Collected 05-29-07 06-26-07 07-31-07 08-28-07 Req. LLD Gross beta 2.4 +/- 0.6 2.8 +/- 0.6 2.5 +/- 1.1 3.2 +/- 1.2 4.0 H-3 < 330 < 330 < 330 < 330 330 Mn-54 < 3.7 < 2.1 < 5.3 < 3.0 15 Fe-59

  • 8.4 < 5.0 < 10.4 < 4.2 30 Co-58 < 3.1 <2.2 < 4.4 < 2.8 15 Co-60 *< 2.9 < 2.7 < 4.9 < 4.2 15 Zn-65 < 4.8 < 1.9 < 7.8 < 4.0 30 Zr-Nb-95 < 5.9 < 5.5 < 4.8 < 5.8 15 Cs-1 34 < 5.9 < 3.8 < 5.3 < 3.8 15 Cs-137 < 4.3 < 3.1 < 5.0 <3.9 18 Ba-La-140 < 7.8 < 4.0 < 7.8 < 7.9 15 Lab Code TSWU- 6555 TSWU- 7736 TSWU- 8122 TSWU- 8660 Date Collected 09-25-07 10-30-07 11-27-07 12-26-07 Req. LLD Gross beta 1.5 + 0.3 2.2 + 0.6 2.9 +/- 0.6 2.8 +/--1.1 4.0 H-3 < 330 < 330 < 330 < 330 330 Mn-54 < 1.6 < 2.2 < 4.4 < 1.7 15 Fe-59 < 5.1 < 2.3 < 4.3 < 4.4 30 Co-58 < 1.8 < 2.6 < 4.6 < 2.3 15 Co-60 < 1.5 < 1.9 < 3.3 < 2.8 15 Zn-65 < 3.6 <6.1 <4.9 < 6.5 30 Zr-Nb-95 < 2.4 < 2.3 < 5.3 < 3.6 15 Cs-134 < 2.8 < 2.2 < 4.9 < 2.5 15 Cs-1 37 < 1.7 < 2.2 < 4.9 < 2.3 18 Ba-La-140 < 1.4 < 3.1 < 9.1 < 5.2 15 25-3

Table 25. Untreated surface water, analyses for gross beta, tritium and gamma emitting isotopes.

Location: T-22 Collection: Monthly composites of weekly grab samples Units: pCi/L a TSWU- 2474 Lab Code TSWU- 674 TSWU- 1162 TSWU- 1741 Date Collected 01-30-07 02-27-07 03-27-07 04-24-07 Req. LLD Gross beta 2.6 +/- 0.4 3.6 + 0.7 1.9 +/- 0.4 3.3 +/- 0.7 4.0 H-3

  • 330 < 330 < 330 < 330 330 Mn-54 < 1.0 < 1.9 <3.1 < 1.2 15 Fe-59 < 3.4 < 2.0 < 4.8 < 3.1 30 Co-58 < 1.9 < 2.6 < 4.2 < 2.9 15 Co-60
  • 0.9 < 2.9 < 5.4 .< 1.4 15 Zn-65 *< 2.4 < 3.8 < 5.1 < 2.4 30 Zr-Nb-95 < 3.1 < 2.7 < 4.2 < 2.4 15 Cs-1 34 < 2.8 < 1.7 < 5.7 < 2.1 15 Cs-1 37 < 3.4 < 2.7 < 4.5 < 2.5 18 Ba-La- 140 < 3.2 < 2.6 < 4.6 < 3.7 15 Lab Code TSWU- 3263 a TSWU- 4270 TSWU- 5131 TSWU- 5798 Date Collected 05-29-07 06-26-07 07-31-07 08-28-07 Req. LLD Gross beta 2.6 +/- 0.6 2.6 +/- 0.6 1.5 +/- 1.0 3.2 +/- 1.1 4.0 H-3 435 +/- 92 < 330 < 330 < 330 330 Mn-54 < 4.3 < 1.7 < 2.4 < 5.1 15 Fe-59 < 6.7 < 6.3 < 4.7 < 5.2 30 Co-58 < 5.6 < 2.9 < 2.9 < 2.5 15 Co-60 < 2.9 < 2.5 < 2.2 < 4.0 15 Zn-65 < 8.5 < 5.5 < 2.0 < 3.7 30 Zr-Nb-95 < 6.5 < 3.7 < 2.7 < 5.7 15 Cs-1 34 < 4.7 < 2.6 < 2.9 < 4.9 15 Cs-1 37 < 6.1 < 3.0 < 2.2 < 2.7 18 Ba-La-140 < 7.5 - < 4.0 <2.1 < 8.4 15 Lab Code TSWU- 6557 TSWU- 7738 TSWU- 8124 TSWU- 8662 Date Collected 09-25-07 10-30-07 11-27-07 12-26-07 Req. LLD Gross beta 1.6 +/- 0.3 2.0 +/- 0.6 2.6 + 0.6 3.1 +/- 0.7 4.0 H-3 < 330 < 330 736 + 122 b 578 +/- 119c 330 Mn-54 < 2.9 < 3.1 < 4.1 < 3.7 15 Fe-59 < 4.9 < 4.7 < 6.6 < 6.1 30 Co-58 < 3.1 < 1.1 < 3.2 < 4.4 15 Co-60 < 3.0 < 3.0 < 3.0 < 2.6 15 Zn-65 < 5.0 < 5.4 < 6.5 < 5.2 30 Zr-Nb-95 < 4.6 <4.3 < 6.2 < 2.6 15 Cs-134 < 2.2 < 2.6 < 4.8 < 4.4 15 Cs-137 < 1.8 < 2.9 < 3.7 <. 5.4 18 Ba-La-140 < 6.0 < 3.4 < 7.6 < 7.7 15 a Duplicate analysis, refer to Appendix C.

b Analysis was repeated; result of reanalysis, 835 +/- 125 pCi/L.

c Analysis was repeated; result of reanalysis, 658 +/- 114 pCi/L.

25-4

Table 25. Untreated surface water, analyses for gross beta, tritium and gamma emitting isotopes.

Location: T-50 Collection: Monthly composites of weekly grab samples Units: pCi/L Lab Code TSWU- 675 TSWU- 1164 TSWU- 1742 TSWU- 2475 Date Collected 01-30-07 02-27-07 03-27-07 04-24-07 Req. LLD.

Gross beta 2.1 +/- 0.4 2.2 +/- 0.4 2.3 +/- 0.4 3.0 +/- 0.6 4.0 H-3 < 330 < 330 < 330 < 330 330 Mn-54 < 4.5 < 2.2 < 2.5 < 2.8 15 Fe-59 < 7.1 < 4.2 < 9.1 < 5.4 30 Co-58 < 4.0 < 2.8 < 2.9 < 2.3 15 Co-60 < 4.4 < 2.6 < 4.5 < 1.8 15 Zn-65 < 8.4 < 5.5 < 2.6 < 4.5 30

< 3.5 < 3.7 15 Zr-Nb-95 < 3.4 < 2.0 Cs-134 < 3.9 < 3.4 < 3.9 < 3.7 15 Cs-137 < 4.2 < 2.9 < 5.7 < 3.5 18 Ba-La-140 < 6.2 < 2.5 < 6.1 < 3.1 15 Lab Code TSWU- 3265 TSWU- 4271 TSWU- 5132 TSWU- 5799 a Date Collected 05-29-07 06-26-07 07-31-07 08-28-07 Req. LLD Gross beta 2.0 +/- 0.6 2.6 +/- 0.6 1.8 +/- 1.1 2.6 +/- 1.2 4.0 H-3 < 330 < 330 < 330 < 330 330 Mn-54 < 6.3 < 1.6 < 6.3 < 4.2 15 Fe-59 < 6.7 < 8.4 < 7.6 < 5.0 30 Co-58 < 4.4 < 2.8 < 4.2 < 3.0 15.

Co-60 < 3.4 < 2.1 < 2.1 < 4.1 15 Zn-65 < 6.9 < 3.8 < 6.9 < 3.6 30 Zr-Nb-95 < 6.8 < 3.5 < 3.9 < 4.0 15 Cs-1 34 < 5.1 < 4.1 < 5.1 <4.1 15

< 4.6 - < 2.1 - < 4.3 < 4.1 18 Cs-137 Ba-La-140 < 5.4 < 4.7 < 6.8 < 7.5 15 Lab Code TSWU- 6558 TSWU- 7739 TSWU- 8125 TSWU- 8663 Date Collected 09-25-07 10-30-07 11-27-07 12-26-07 Req. LLD Gross beta 1.3 - 0.3 1.2 +/- 0.6 2.3 +/- 0.5 3.1 +/- 0.7 4.0 H-3 < 330 < 330 < 330 < 330 330 Mn-54 < 2.7 < 2.3 '<5.1 < 2.5 15 Fe-59 < 4.7 < 3.0 < 8.2 < 6.3 30 Co-58 < 1.8 < 2.1 < 6.5 < 3.1 15 Co-60 <2.1 < 2.3 <3.1 < 2.5 15 Zn-65 < 5.3 < 3.8 < 9.5 < 5.5 30 Zr-Nb-95 < 2.9 < 3.3 < 3.8 < 3.0 15 Cs-134 < 4.0 < 2.7 < 3.9 <3.1 15 Cs-137 < 2.8 < 3.3 < 4.7 < 3.4 18 Ba-La-1 40 < 3.8 < 4.2 < 8.3 < 5.4 15 a Duplicate analysis, refer to Appendix C.

25-5

Table 25. Untreated surface water, analyses for gross beta, tritium and gamma emitting isotopes.

Location: T-145 (QC)

Collection: Monthly composites of weekly grab samples Units: pCi/L Lab Code TSWU- 676 TSWU- 1165 TSWU- 1743 TSWU- 2476 Date Collected 01-30-07 02-27-07 03-27-07 04-24-07 Req. LLD Gross beta 1.9 + 0.3 2.0 +/- 0.4 3.0 +/- .0.5 2.9 _ 0.7 4.0 H-3 < 330 < 330 < 330 < 330 330 Mn-54 < 4.9 < 1.6 < 3.1 < 2.8 15 Fe-59 < 8.0 < 5.0 < 2.6 < 9.2 30 Co-58 < 3.3 < 2.7 < 2.4 < 2.7 15 Co-60 < 4.3 < 2.0 < 3.0 < 3.8 15 Zn-65 < 4.6 < 3.9 < 3.2 < 4.9 30 Zr-Nb-95 < 5.7 < 2.2 < 3.6 < 4.7 15 Cs-134 <4.1 < 3.3 < 3.2 < 5.0 15 Cs-1 37 < 5.3 < 3.2 < 2.9 < 3.7 18 Ba-La-140 < 2.9 < 2.3 < 2.4 < 5.3 15 Lab Code TSWU- 3266 .TSWU- 4272 TSWU- 5133 TSWU- 5801 Date Collected 05-29-07 06-26-07 07-31-07 08-28-07 Req. LLD Gross beta 3.6 +/- 0.7 1.8 +/- 0.3 1.9 +/- 1.0 1.6 +/- 1.2 4.0 H-3 < 330 < 330 < 330 < 330 330 Mn-54 < 2.9 < 1.9 < 2.8 < 6.0 15 Fe-59 < 5.8 < 4.7 < 12.7 < 11.4 30 Co-58 < 2.1 < 1.8 < 4.9 < 5.7 15 Co-60 < 2.3 < 3.3 < 3.0 < 4.0 15 Zn-65 < 6.7 < 5.1 < 4.9 < 9.9 30 Zr-Nb-95 < 1.9 < 3.6 < 5:5 < 5.6 15 Cs-134 < 2.7 < 3.5 < 5.4 <6.0 15 Cs-137 < 3:2 < 2.3 -- < 4.8 < 4.9 18 -

Ba-La- 140 < 2.8 < 5.4 < 8.0 < 9.5 15 Lab Code TSWU- 6559 TSWU- 7740 TSWU- 8126 TSWU- 8664 Date Collected 09-25-07 10-30-07 11-27-07 12-26-07 Req. LLD Gross beta 3.0 +/- 0.6 2.7 +/- 1.9 3.9 +/- 0.5 3.7 +/- 1.0 4.0 H-3 < 330 < 330 < 330 < 330 330 Mn-54 < 5.1 < 2.3 < 1.7

  • 2.5 15 Fe-59 < 4.9 < 4.7 < 4.4
  • 5.4 30 Co-58 < 3.0 < 2.2 <'1.3 < 2.7 15 Co-60 < 4.0 < 2.3 < 2.3 < 2.7 15 Zn-65 < 2.8. < 4.2 < 2.6 < 3.4 30 Zr-Nb-95 < 5.0 < 3.9 < 3.2 < 1.9 15 Cs-134 < 3.2 < 2.3 <3.1 < 3.3 15 Cs-137 < 2.9 < 2.6 < 2.6 < 3.7 18 Ba-La-140
  • 6.4 < 1.9 < 4.3 < 2.2 15 a Duplicate analysis, refer to Appendix C.

25-6

Table 26. Untreated surface water samples, analyses for strontium-89 and strontium-90.

Collection: Quarterly composites of weekly grab samples Units: pCi/L Location T-3 Period 1st Qtr. 2nd Qtr. 3rd Qtr. 4th Qtr.

Lab Code TSWU-2212 TSWU-4618 TSWU-7145 TSWU-8705 Sr-89 < 0.9 < 0.9 < 1.4 < 0.8 Sr-90 < 0.5 < 0.6 < 0.7 < 0.8 Location T-11 (C)

Period 1st Qtr. 2nd Qtr. 3rd Qtr. 4th Qtr.

Lab Code TSWU-2213 TSWU-4619 TSWU-7146 TSWU-8706 Sr-89 < 1.0 < 1.0 < 1.1 < 0.7 Sr-90 < 0.5 < 0.6 < 0.6 < 0.6 Location T-12 (C)

Period 1st Qtr. 2nd Qtr. 3rd Qtr. 4th Qtr.

Lab Code TSWU-2214 TSWU-4620 TSWU-7147 TSWU-8707 Sr-89 < 0.8 < 0.9 < 1.1 < 0.6 Sr-90 < 0.5 < 0.6 < 0.5 < 0.6 Location T-22 Period 1st Qtr. 2nd Qtr. 3rd Qtr. 4th Qtr.

Lab Code TSWU-2215 TSWU-4621 ____TSWU-7148 TSWU-8708" Sr-89 < 0.8 < 1.0 < 1.2 < 0.6 Sr-90 < 0.5 < 0.6 < 0.6 < 0.5 Location T-50 Period 1st Qtr. 2nd Qtr. 3rd Qtr. 4th Qtr.

Lab Code TSWU-2216 TSWU-4622 TSWU-7149 TSWU-8710 Sr-89 < 0.9 ' < 0.9 < 1.3 < 0.6 Sr-90 < 0.5 < 0.5 < 0.7 < 0.6 a Analysis performed in duplicate result of duplicate analysis (TSWU-8709): Sr-89, < 0.6 Sr-90, < 0.6pCi/L.

26-1

This Page Intentionally Left Blank 27-1

Table 28. Fish samples, analyses for gross beta and gamma-emitting isotopes.

Collection: Annually Units: pCi/g wet Location T-33 (Lake Erie, 1.5 mi. NE of Station)

Lab Code TF- 3358 TF- 3359 TF- 3360 TF- 3361 Date Collected 05-08-07 05-08-07 05-08-07 05-23-07 Sample Type Walleye Perch Carp White Bass Gross Beta 4.74 +/- 0.13 3.62 +/- 0.21 4.73 + 0.13 3.51 +/- 0.11 K-40 3.12 +/- 0.51 2.66 +/- 0.47 3.18 + 0.53 2.48 +/- 0.47 Mn-54 < 0.017 < 0.021 0.017 < 0.012 Fe-59 < 0.084 < 0.046 0.078 < 0.060 Co-58 < 0.030 < 0.021 0.034 < 0.025 Co-60 < 0.019 < 0.022 0.016 <. 0.020 Zn-65 < 0.036 < 0.018 0.019 < 0.037 Cs-1 34 < 0.013 < 0.012 0.015 < 0.018 Cs-1 37 < 0.023 < 0.014 0.019 < 0.021 Location T-35 Lab Code TF- 3362 TF- 3363 Date Collected 03-05-07 04-04-07 Sample Type Walleye Perch / Bass Gross Beta 4.64 +/- 0.13 3.24 +/- 0.12 K-40 3.19 +/- 0.47 2.88 +/- 0.39 Mn-54 < 0.019 < 0.011 Fe-59 < 0.177 < 0.081 Co-58 < 0.041 < 0.020 Co-60 < 0.022 < 0.014 Zn-65 < 0.041 < 0.010 Cs-1 34 < 0.020 < 0.011 Cs-1 37 < 0.015 < 0.012 28-1

Table 29. Shoreline sediment samples, analyses for gamma-emitting isotopes.

Collection: Semiannually Units: pCi/g dry Location. T-3 T-4 T-4P T-27B T-132 Lab Code TSS- 3348 TSS- 3349 TSS- 3350 TSS- 3351 TSS- 3352 Date Collected 05-31-07 05-31-07 05-31-07 05-31-07 05-31-07 K-40 8.71 + 0.68 11.78 +/- 0.87. 18.32 +/- 0.96 10.61 +/- 0.75 9.74 +/- 0.72 Mn-54 < 0.018 < 0.031 < 0.023 < 0.021 < 0.019 Co-58 < 0.026 < 0.027 < 0.027 < 0.024 < 0.024 Co-60 < 0.019 < 0.024 < 0.018 < 0.022 < 0.019 Cs-1 34 < 0.030 < 0.038 < 0.045 <'0.027 < 0.025 Cs-1 37 < 0.019 < 0.026 < 0.029 < 0.012 < 0.017 Lab Code TSS- 7931 TSS- 7932 TSS- 7933 TSS- 7934 TSS- 7935 Date Collected 11-07-07 11-07-07 11-07-07 11-07-07 11-07-07 K-40 11.95 +/- 0.55 11.07 +/- 0.55 17.55 +/- 0.93 9.61 +/- 0.60 9.95 +/- 0.51 Mn-54 < 0.012 < 0.014 < 0.034 < 0.018 < 0.007 Co-58 < 0.020 < 0.013 < 0.026 < 0.018 < 0.019 Co-60 < 0.010 < 0.009 < 0.017 < 0.011 < 0.008 Cs-134 < 0.010 < 0.011 <.0.021 < 0.013 < 0.012 Cs-1 37 < 0.007 < 0.012 < 0.027 < 0.018 < 0.015 29-1

-Environmental, Inc.

Midwest Laboratory an Ailegheny Technologies Co.

700 Landwehr Road Northbrook, IL 60062-2310 ph. (847) 564-0700 - fax (847) 564-4517

/-

APPENDIX A INTERLABORATORY COMPARISON PROGRAM RESULTS NOTE: Environmental Inc., Midwest Laboratory participates in intercomparison studies administered by Environmental Resources Associates, and serves as a replacement for studies conducted previously by the U.S. EPA Environmental Monitoring Systems Laboratory, Las Vegas, Nevada. Results are reported in Appendix A. TLD Intercomparison results, in-house spikes, blanks, duplicates and mixed analyte performance evaluation program results are also reported. Appendix A is updated four times a year; the complete Appendix is included in March, June, September and December monthly progress reports only.

January through December, 2007

Appendix A Interlaboratory Comparison Proqram Results Environmental, Inc., Midwest Laboratory has participated in interlaboratory comparison (crosscheck) programs since the formulation' of it's quality control program in December 1971. These programs are operated by agencies which supply environmental type samples containing concentrations of radionuclides known to the issuing agency butnot to participant laboratories. The purpose of such a program is to provide an independent check on a laboratory's analytical procedures and to alert it of any possible problems.

Participant laboratories measure the concentration of specified radionuclides and report them to the issuing agency. Several months later, the agency reports the known values to the participant laboratories and specifies control limits. Results consistently higher or lower than the known values or outside the control limits indicate a need to check the instruments or procedures used.

Results in Table A-1 were obtained through participation in the environmental sample crosscheck program administered by Environmental Resources Associates, serving as a replacement for studies conducted previously by the U.S. EPA Environmental Monitoring Systems Laboratory, Las Vegas, Nevada.

The results in Table A-2 list results for thermoluminescent dosimeters (TLDs), via International Intercomparison of Environmental Dosimeters, when available, and internal laboratory testing.

Table A-3 lists results of the analyses on in-house "spiked" samples for the past twelve months. All samples are prepared using NIST traceable sources. Data for previous years available upon request.

Table A-4 lists results of the analyses on in-house "blank" samples for the past twelve months. Data for previous years available upon request.

Table A-5 lists REMP specific analytical results from the in-house "duplicate" program for the past twelve month, Acceptance is based on the difference of the results being less than the sum of the errors.

Complete analytical data for duplicate analyses is available upon request.

The results in Table A-6 were obtained through participation in the Mixed Analyte Performance Evaluation Program.

Results in Table A-7 were obtained through participation in the environmental sample crosscheck program administered by Environmental Resources Associates, serving as a replacement for studies conducted previously by the Environmental Measurement Laboratory Quality Assessment Program (EML).

Attachment A lists acceptance criteria for "spiked" samples.

Out-of-limit results are explained directly below the result.

Al

Attachment A

/ ACCEPTANCE CRITERIA FOR "SPIKED" SAMPLES LABORATORY PRECISION: ONE STANDARD DEVIATION VALUES FOR VARIOUS ANALYSESa One standard deviation Analysis Level for single determination Gamma Emitters 5 to 100 pCi/liter or kg 5.0 pCi/liter

> 100 pCi/liter or kg 5% of known value Strontium-89b 5 to 50.pCi/liter or kg 5.0 pCi/liter

> 50 pCi/liter or kg 10% of known value 5.0 pCi/liter Strontium-90b 2 to 30 pCi/liter or kg

> 30 pCi/liter or kg 10% of known value Potassium-40 > 0.1 g/liter or kg 5% of known value Gross alpha < 20 pCi/liter 5.0 pCi/liter

> 20 pCi/liter 25% of known value Gross beta < 100 pCi/liter 5.0 pCi/liter

> 100 pCi/liter 5% of known value Tritium 5 4,000 pCi/liter 0 0 33 169.85 x (known) 9

> 4,000 pCi/liter 10% of known value Radium-226,-228 > 0.1 pCi/liter 15% of known value Plutonium > 0.1 pCi/liter, gram, or sample 10% of known value Iodine-1 31, 5 55 pCi/liter 6.0 pCi/liter Iodine_129b > 55 pCi/liter 10% of known value Uranium-238, -535 pCi/liter 6.0 pCi/liter Nickel-63b > 35 pCi/liter 15% of known value Technetium-99b Iron-55b 50 to 100 pCi/liter 10 pCi/liter

> 100 pCi/liter 10% of known value Othersb 20% of known value

" From EPA publication, 'Environmental Radioactivity Laboratory Intercomparison Studies Program, Fiscal Year, 1981-1982, EPA-600/4-81-004.

b Laboratory limit.

A2

TABLE A-1. Interlaboratory Comparison Crosscheck program, Environmental Resource Associates (ERA)a.

Concentration (pCi/L)

Lab Code Date Analysis Laboratory ERA Control Resultb Resultc Limits Acceptance STW-1 121 0'4/09/07 Sr-89 30.7 +/- 4.3 35.4 26.7 -44.1 Pass STW-1 121 04/09/07 Sr-90 39.3 +/- 1.8 42.1 33.4 - 50.8 Pass STW-1 122 04/09/07 Ba-133 30.0 +/- 2.4 29.3 20.6 - 38.0 Pass STW-1 122 04/09/07 Co-60 118.5 +/- 3.9 119.0 109.0 - 129.0 Pass STW-1 122 04/09/07 Cs-134 52.6 +/- 2.3 54.3 45.6 - 63.0 Pass STW-1 122 04/09/07 Cs-1 37 49.5 +/- 3.8 50.3 41.6 - 59.0 Pass STW-1 122 04/09/07 Zn-65 91.7 +/- 6.3 88.6 73.3 - 104.0 Pass STW-1 123 04/09/07 Gr. Alpha 33.8 +/- 3.5 56.5 32.0 -81.0 Pass STW-1 123 04/09/07 Gr. Beta 24.2 +/- 2.3 25.3 16.6 -34.0 Pass STW-1 124 04/09/07 1-131 19.2 +/- 1.2 18.9 13.7 -24.1 Pass STW-1 125 04/09/07 H-3 7540.0 +/- 255.0 8060.0 6660.0 -9450.0 Pass STW-1 125 04/09/07 Ra-226 13.0 +/- 0.6 13.4 9.9 -16.9 Pass STW-1 125 04/09/07 Ra-228 19.9 +/- 2.7 18.2 10.3 -26.1 Pass STW-1 125 04/09/07 Uranium 4.5 +/- 0.2 4.6 0.0 - 9.8 Pass STW-1 127 07/09/07 Sr-89 51.7 +/- 5.0 58.2 49.5 - 66.9 Pass STW-1 127 07/09/07 Sr-90 21.4 +/- 2.3 19.0 10.3 -27.7 Pass STW-1 128 07/09/07 Ba-133 19.4 +/- 2.2 19.4 10.7 -28.1 Pass STW-1128 07/09/07 Co-60 32.8 +/- 2.0 33.5 24.8 - 42.2 Pass STW-1 128 07/09/07 Cs-134 67.0 +/- 2.9 68.9 60.2 - 77.6 Pass STW-1 128 07/09/07 Cs-137 61.6 +/- 3.8 61.3 52.6 - 70.0 Pass STW-1 128 07/09/07 Zn-65 55.6 +/- 7.5 54.6 45.2 - 64.0 Pass STW-1 129 07/09/07 Gr. Alpha 19.2 +/- 1.6 27.1 15.4 -38.8 Pass STW-1129 07/09/07 Gr. Beta 9.1 +/- 0.9 11.5 2.8,-20.2 Pass STW-1 130 07/09/07 Ra-226 7.0 +/- 0.5 7.7 5.7 - 9.7 Pass STW-1 130 07/09/07 Ra-228 9.2 +/- 2.3 9.1 5.2 - 13.1 Pass STW-1130 07/09/07 Uranium 23.9 +/- 1.1 25.1 19.9 -30.3 Pass STW-1 131 10/05/07 Sr-89 27.3 +/- 3.3 27.4 19.3 - 33.9 Pass STW-1 131 10/05/07 Sr-90 17.7 +/- 1.2 18.2 .12.9 -21.6 Pass STW-1132 10/05/07 Ba-1 33 12.2 +/- 3.3 12.6 8.6 -15.5 Pass STW-1132 10/05/07 Co-60 23.8 +/- 1.4 23.2 19.9 -28.3 Pass STW-1132 10/05/07 Cs-134 70.5 +/- 4.2 71.1 58.0 - 78.2 Pass STW-1132 10/05/07 Cs-1 37 178.2 +/- 3.3 180.0 162.0 - 200.0 Pass STW-1 132 10/05/07 Zn-65 263.9 +/- 6.9 251.0 226.0 -294.0 Pass STW-1 133 10/05/07 Gr. Alpha 54.7 +/- 2.1 58.6 30.6 - 72.9 Pass STW-1133 10/05/07 Gr. Beta 11.9 +/- 0.9 9.7 4.3 - 18.2 Pass STW-1 134 10/05/07 1-131 33.0 +/- 1.5 28.9 ,24.0 - 33.8 Pass STW-1135 10/05/07 H-3 9965.0 +/- 250.0 9700.0 8430.0 - 10700.0 Pass STW-1135 10/05/07 Ra-226 12.7. +/- 0.2 12.9 9.6 - 14.9 Pass STW-1 135 10/05/07 Ra-228 19.6 +/- 2.4 17.9 12.0 -21.5 Pass STW-1 135 10/05/07 Uranium 27.3 +/- 1.1 27.5 22.1 -30.8 Pass Results obtained.by Environmental, Inc., Midwest Laboratory as a participant in the crosscheck program for proficiency testing in drinking water conducted by Environmental Resources Associates (ERA).

b Unless otherwise indicated, the laboratory result is given as the mean +/- standard deviation for three determinations.

c Results are presented as the known values, expected laboratory precision (1 sigma, 1 determination) and control limits as provided by ERA.

Al-1

TABLE A-1. Interlaboratory Comparison Crosscheck program, Environmental Resource Associates (ERA)a.

Concentration (pCi/L)

Lab Code Date Analysis Laboratory ERA Control Resultb Resultf Limits Acceptance Results obtained by Environmental, Inc., Midwest Laboratory as a participant in the crosscheck program for proficiency testing in drinking water conducted by Environmental Resources Associates (ERA).

b Unless otherwise indicated, the laboratory result is given as the mean +/- standard deviation for three determinations.

c Results are presented as the known values, expected laboratory precision (1 sigma, 1 determination) and control limits as provided by ERA.

d The reported result was an average of three analyses, results ranged from 25.36 to 29.23 pCi/L.

A fourth analysis was performed, result of analysis, 24.89 pCi/L.

Al -2

TABLE A-2. Crosscheck program results; Thermoluminescent Dosimetry, (TLD, CaSO 4 : Dy Cards).

mR Lab Code Date Known Lab Result Control Description Value + 2 sigma Limits Acceptance Environmental, Inc.

2007-1 7/13/2007 30 cm. 54.25 60.56 +/- 5.54 37.98 - 70.53 Pass 2007-1 7/13/2007 40 cm. 30.51 34.23 +/- 0.96 21.36 - 39.66 Pass 2007-1 7/13/2007 50 cm. 19.53 17.95 +/- 1.86 13.67 - 25.39 Pass 2007-1 7/13/2007 60 cm. 13.56 16.61 +/- 0.60 9.49 - 17.63 Pass 2007-1 7/13/2007 70 cm. 9.96 9.72 +/- 0.90 6.97 - 12.95 Pass 2007-1 7/13/2007 80 cm. 7.63 7.79 +/- 0.33 5.34 - 9.92 Pass 2007-1 7/13/2007 90 cm. 6.03 5.53 +/- 0.72 4.22 - 7.84 Pass 2007-1 7/13/2007 100 cm. 4.88 5.32 .+/- 0.17 3.42 -6.34 Pass 2007-1 7/13/2007 110 cm. 4.03 3.49 +/- 0.14 2.82 - 5.24 Pass 2007-1 7/13/2007 120 cm. 3.39 2.64 +/- 0.14 2.37 - 4.41 Pass 2007-1 7/13/2007 150 cm. 2.17 2.13 +/- 0.87 1.52 -2.82 Pass Environmental, Inc.

2007-2 11/12/2007 30 cm. 54.37 65.47 +/- 5.25 38.06 - 70.68 Pass 2007-2 11/12/2007 40 cm. 30.59 37.43 +/- 2.18 21.41 -39.77 Pass 2007-2 11/12/2007 60 cm. 13.59 15.18 +/- 0.50 9.51 - 17.67 Pass 2007-2 11/12/2007 70 cm. 9.99 12.18 +/- 0.46 6.99 - 12.99 Pass 2007-2 11/12/2007 80 cm. 7.65 8.74 +/- 0.39 5.36 - 9.95 Pass 2007-2 11/12/2007 90 cm. 6.04- 5.89 +/- 0.25 4.23 - 7.85 Pass 2007-2 11/12/2007 110 cm. 4.04 4.13 +/- 0.41 2.83 - 5.25 Pass 2007-2 11/12/2007 120 cm. 3.4 2.92 +/- 0.13 2.38 - 4.42 Pass 2007-2 11/12/2007 120 cm. 3.4 2.91 +/- 0.31 2.38 - 4.42 Pass 2007-2 11/12/2007 150 cm. 2.17 1.95 +/- 0.72 1.52 -2.82 Pass 2007-2 11/12/2007 180 cm. 1.51 1.38 +/- 0.05 1.06 -1.96 Pass A2-1

TABLE A-3. In-House "Spike" Samples Concentration (pCi/L)a Lab Code b Date Analysis Laboratory results Known Control 2s, n=1 C Activity Limits d Acceptance W-30707 3/7/2007 Gr. Alpha 19.51 +/- 0.40 20.08 10.04 - 30.12 Pass 67.45 +/- 0.49 W-30707 3/7/2007 Gr. Beta 65.73 55.73 - 75.73 Pass SPAP-1566 3/23/2007 Cs-1 34 25.35.+/- 1.31 27.82 17.82 - 37.82 Pass SPAP-1566 3/23/2007 Cs-1 37 107.52 +/- 3.02 116.48 104.83 - 128.13 Pass SPW-1 568 3/23/2007 H-3 65595.00 +/- 672.00 71118.00 56894.40 - 85341.60 Pass SPW-1678 3/28/2007 Tc-99 28.44 +/- 1.12 32.35 20.35 - 44.35 Pass SPW-1595 4/5/2007 Cs-1 34 54.48 +/- 2.12 54.99 44.99 - 64.99 Pass SPW-1595 4/5/2007 Cs-1 37 59.03 +/- 2.94 58.19 48.19 - 68.19 Pass SPW-1595 4/5/2007 1-131(G). 83.11 +/- 3.51 82.07 72.07 - 92.07 Pass SPW-1595A 4/5/2007 1-131 78.40 +/- 1.10 82.07 65.66 - 98.48 Pass SPW-1595B 4/5/2007 1-131 78.97 +/- 1.10 82.07 65.66 - 98.48 Pass SPM1-1597 *4/5/2007 Cs-1 34 54.03 +/- 2.15 54.99 44.99 - 64.99 Pass SPMI-1597 4/5/2007 Cs-1 37 59.81 +/- 4.75 58.19 48.19 - 68.19 Pass SPM1-1597 4/5/2007 1-131(G) 83.97 +/- 4.07 82.07 72.07 - 92.07 Pass SPMI-1597A 4/5/2007 1-131 79.53 +/- 1.03 / 82.07 65.66 - 98.48 Pass SPMI-1597B 4/5/2007 1-131 83.51 +/- 1.05 82.07 65.66 - 98.48 Pass SPCH-2839 5/17/2007 1-131(G) 78.70 +/- 7.36 70.40 60.40 - 80.40 Pass SPW-2847 5/17/2007 Cs-134 55.43 +/- 1.68 52.85 42.85 - 62.85 Pass SPW-2847 5/17/2007 Cs-1 37 59.86 +/- 2.71 58.03 48.03 - 68.03 Pass SPW-2847 5/17/2007 1-131(G) 63.95 +/- 2.69 70.87 60.87 - 80.87 Pass SPMI-2849 5/17/2007 Cs-1 34 51.37 +/- 1.65 52.85 42.85 - 62.85 Pass SPMI-2849 5/17/2007 Cs-1 37 60.42 +/- 4.31 58.03 48.03 - 68.03 Pass SPMI-2849 5/17/2007 1-131(G) 62.44 +/- 3.14 70.87 60.87 - 80.87 Pass SPCH-2922 5/17/2007 1-131(G) 80.00 +/- 6.40 70.40 41.60 -99.20 Pass SPW-2847 5/18/2007 1-131 60.14 +/- 0.89 70.87 56.70 - 85.04 Pass SPW-2847 5/18/2007 Sr-89 104.93 +/- 6.64 121.90 97.52 - 146.28 Pass SPW-2847 5/18/2007 Sr-89 46.72 +/- 1.97 46.08 36.08 - 56.08 Pass SPMI-2849 5/18/2007 1-131 67.97 +/- 0.88 70.87 56.70 - 85.04 Pass SPW-2909 e 5/22/2007 Fe-55 11137.00 +/- 316.00 14271.50 11417.20 -17125.80 Fail SPW-2911 5/22/2007 H-3 65023.00 +/- 679.00 70485.00 56388.00 - 84582.00 Pass SPAP-2913 5/22/2007 Gr. Beta 55.27 +/- 8.51 52.65 42.12 -73.71 Pass SPAP-2915 5/22/2007 Cs-1 34 22.53 +/-.1.12 26.42 16.42 -36.42 Pass SPAP-2915 5/22/2007 Cs-1 37 111.14 +/- 3.57 116.06 104.45 - 127.67 Pass SPF-2922 5/22/2007 Cs-1 34 0.52 +/- 0.03 0.53 0.32 - 0.74 Pass SPF-2922 5/22/2007 Cs-1 37 2.58 +/- 0.07 2.32 1.39 - 3.25 Pass SPW-3223 5/24/2007 Ni-63 2233.10 +/- 10.32 2135.90 1281.54 -2990.26 Pass W-60507 6/5/2007 Gr. Alpha 20.93 +/- 0.42 20.08 10.04 - 30.12 Pass W-60507 6/5/2007 Gr. Beta 60.50 +/- 0.46 65.73 55.73 - 75.73 Pass SPW-4327 7/18/2007 Tc-99 25.58 +/- 1.11 32.35 20.35 -44.35 Pass SPW-5476 8/17/2007 Ni-63 1925.18 +/- 9.62 2135.90 1281.54 - 2990.26 Pass W-92107 9/21/2007 Gr. Alpha 23.02 +/- 0.44 20.08 10.04 - 30.12 Pass W-92107 9/21/2007 Gr. Beta 61.48 +/- 0.47 65.73 55.73 - 75.73 Pass A3-1

TABLE A-3. In-House "Spike" Samples Concentration (pCi/L)a Lab Code Date Analysis Laboratory results Known Control 2s, n=1 b Activity Limitsc Acceptance SPW-6880 10/10/2007 Tc-99 30.97 +/- 1.21 32.35 20.35 - 44.35 Pass w-111007 11/10/2007 Gr. Alpha 22.43 +/- 0.42 20.08 10.04 - 30.12 Pass w-111007 11/10/2007 Gr. Beta 64.49 +/- 0.48 65.73 55.73 - 75.73 Pass SPAP-7742 11/13/2007 Cs-134 21.18 +/- 1.29 22.41 12.41 - 32.41 Pass SPAP-7742 11/13/2007 Cs-137 113.61 +/- 3.16 114.76 103.28 - 126.24 Pass SPAP-7744 11/13/2007 Gr. Beta 53.41 +/- 0.13 52.03 41.62 - 72.84 Pass SPMI-7746 11/13/2007 Cs-134 42.20 +/- 1.48 44.83 34.83 - 54.83 Pass SPMI-7746 11/13/2007 Cs-1 37 56.05 +/- 2.83 57.40 47.40 - 67.40 Pass SPMI-7746 11/13/2007 Sr-90 41.02 +/- 1.61 45.54 36.43 - 54.65 Pass SPW-7748 11/13/2007 Cs-1 34 43.11 +/- 1.52 44.80 34.80 - 54.80 Pass SPW-7748 11/13/2007 CsT137 59.28 +/- 3.50 57.40 47.40 - 67.40 Pass SPW-7748 11/13/2007 Sr-90 37.23 +/- 1.51 45.54 36.43 - 54.65 Pass SPW-7752 11/13/2007 Fe-55 12935.10 +/- 357.00 12640.50 10112.40 - 15168.60 Pass SPW-7758 11/13/2007 H-3 65405.00 +/- 712.50 68618.00 54894.40 - 82341.60 Pass SPF-7760 11/13/2007 Cs-1 34 0.45 +/- 0.02 0.45 0.27 - 0.63 Pass SPF-7760 11/13/2007 Cs-1 37 2.45 +/- 0.07. 2.29 1.37 -3.21 Pass SPW-8034 11/13/2007 Ni-63 2194.06 +/- 10.77 2129.03 1277.42 -2980.64 Pass a Liquid sample results are reported in pCi/Liter, air filters( pCi/filter), charcoal (pCi/m 3), and solid samples (pCi/g).

b Laboratory codes as follows: W (water), Ml (milk), AP (air filter), SO (soil), VE (vegetation),

CH (charcoal canister), F (fish).

CResults are based on single determinations.

d Control limits are based on Attachment A, Page A2 of this report.

e Sample recount: 12557 +/- 335.

NOTE: For fish, Jello is used for the Spike matrix. For Vegetation, cabbage is used for the Spike matrix.

A3-2

TABLE A-4. In-House "Blank" Samples Concentration (pCi/L)a Lab Code Sample Date Analysisb Laboratoryresults (4.66o) Acceptance Type LLD Activityc Criteria (4.66 a)

W-30707 water 3/7/2007 Gr. Alpha 0.40 0.01 +/- 0.28 .2 W-30707 water 3/7/2007 Gr. Beta 0.75 0.06 +/- 0.53 4 SPAP-1 567 Air Filter 3/23/2007 Cs-1 34 .0.79 100

,100 SPW-1 567 Air Filter 3/23/2007 Cs-137 1.01 SPW-1 568 water 3/23/2007 H-3 176.10 -26.16 +/- 91.62 200 SPW-1 596 water 4/5/2007 Cs-1 34 3.28 10' SPW-1 596 water 4/5/2007 Cs-1 37 3.45 10 SPW-1596 water 4/5/2007 1-131 0.27 0.02 +/- 0.18 0.5 SPW-1596 water 4/5/2007 1-131(G) 2.91 20 SPMI-1 598 Milk 4/5/2007 Cs-134 3.30 10 SPMI-1 598 Milk 4/5/2007 Cs-137 5.08 10 SPMI-1598 Milk 4/5/2007 1-131 0.26 -0.10 +/- 0.17. 0.5 SPMI-1598 Milk 4/5/2007 1-131(G) 4.10 '20 SPCH-2839 Charcoal Canister 5/17/2007 1-131(G) 2.24 9.6 SPW-2848 water 5/17/2007 Cs-1 34 3.14 10 10 SPW-2848 water 5/17/2007 Cs-1 37 1.37 SPW-2848 water 5/17/2007 1-131(G). 5.34 20 SPMI-2850 Milk 5/17/2007 Cs-1 34 3.32 10 SPMI-2850 Milk 5/17/2007 Cs-137 2.60 10 SPMI-2850 Milk. 5/17/2007 1-131(G) 4.77 20 SPW-2848 water 5/18/2007 1-131 0.34 -0.06 +/- 0.19 0.5 SPW-2848 water 5/18/2007 Sr-89 0.81 -0.02 +/- 0.65 5 SPW-2848 water 5/18/2007 Sr-90 0.53 0.01 +/- 0.25 1 SPMI-2850 Milk 5/18/2007 1-131 0.45 0.20 +/- 0.26 0.5 SPMI-2850 Milk 5/18/2007 Sr-89 0.96 -0.73+,+/-1.02 5 SPMI-2850 d Milk 5/18/2007 Sr-90 0.58 0.96 +/- 0.38 1 SPAP-2914 Air Filter 5/22/2007 Gr. Beta 0.004 -0.002 +/- 0.002 0.01 SPAP-2916 Air Filter 5/22/2007 Cs-1 34 2.84 100 SPAP-2916 Air Filter 5/22/2007 Cs-1 37 2.24 100 SPF-2923 Fish 5/22/2007 Cs-1 34 8.71 100 SPF-2923 Fish 5/22/2007 .8.35 100 Cs-1 37 SPW-3224 water. 5/24/2007 Ni-63 1.61 -0.30 +/- 0.84 20 W-60507 water 6/5/2007 Gr. Alpha 0.43 -0.01 +/- 0.30 2 W-60507 water 6/5/2007 Gr. Beta 0.77 0.01 +/- 0.54 4 SPW-4328 water 7/18/2007 Tc-99 6.41 -3.12 +/- 3.84 10 SPW-5477 water 8/17/2007 Ni-63 1.48 4.38 +/- 1.01 20 W-92107 water 9/21/2007 Gr. Alpha 0.41 0.09 +/- 0.29 2 W-92107 water 9/21/2007 Gr. Beta 0.75 -0.26 +/- 0.51 4 A4-1

TABLE A-4. In-House "Blank" Samples Concentration (pCi/L)a Lab Code Sample Date Analysisb Laboratory results (4.66a) Acceptance Type LLD Activityc Criteria (4.66 a)

SPW-6881 water 10/10/2007 Tc-99 6.82 -6.58 +/- 4.04 10 SPAP-7743 Air Filter 11/13/2007 Gr. Beta 0.003 -0.002 +/- 0.002 0.01 SPMI-7745 Milk 11/13/2007 Cs-134 2.16 10 SPMI-7745 Milk 11/1312007 Cs-137 3.46 10 SPMI-7745 Milk 11/13/2007 1-131(G) 5.89 20 SPMI-7745 Milk 11/13/2007 Sr-90 0.59 0.73 +/- 0.35 1 SPW-7747 water 11/13/2007 Cs-134 2.39 10 SPW-7747 water 11/13/2007 Cs-137 3.53 10 SPW-7747 water 11/13/2007 1-131(G) 12.51 20 SPW-7747 water 11/13/2007 Sr-90 0.71 -0.04 + 0.32 1 SPW-7751 water 11/13/2007 Fe-55 15.50 -4.18 +/- 9.20 1000 SPW-7757 water 11/13/2007 H-3 151.35 -14.98 _ 78.85 200 SPF-7759 Fish 11/13/2007 Cs-134 5.50 100 SPF-7759- Fish 11/13/2007 Cs-137 5.10 100 SPW-8033 water 11/13/2007 Ni-63 1.45 -0.19 + 0.87 20 W-120607 water 12/6/2007 Gr. Alpha 0.40 0.02 + 0.28 2 W-120607 water 12/6/2007 Gr. Beta 0.77- -0.70 +/- 0.51 4 Liquid sample results are reported in pCi/Liter, air filters( pCi/filter), charcoal (pCi/charcoal canister), and solid samples (pCi/kg).

b 1-131(G); iodine-131 as analyzed by gamma spectroscopy.

Activity reported is a net activity result. For gamma spectroscopic analysis, activity detected below the LLD value is not reported.

d Low levels of Sr-90 are still detected in the environment. A concentration of (1-5 pCi/L) in milk is not unusual.

A4-2

TABLE A-5. In-House "Duplicate" Samples Concentration .(pCi/L)8 Averaged Lab Code Date Analysis First Result Second Result Result Acceptance E-20, 21 1/2/2007 Gr. Beta 1.76 +/- 0.07 1.70 +/- 0.06 1.73 +/- 0.05 Pass E-20, 21 1/2/2007 K-40 1.49 +/- 0.24 1.57 +/- 0.27 1.53 +/- 0.18 Pass CF-41, 42 1/2/2007 Gr. Beta 18.02 +/- 0.41 18.81 +/- 0.42 18.42 +/- 0.29 Pass CF-41, 42 1/2/2007 K-40 11.68 +/- 1.12 12.67 +/- 0.97 12.18 +/- 0.74 Pass CF-41, 42 1/2/2007 Sr-90 0.039 +/- 0.011 0.026 +/- 0.010 0.033 +/- 0.007 Pass P-9516, 9517 1/3/2007 H-3 270.78 +/- 91.74 301.18 +9299 285.98 +/- 65.31 Pass LW-9579, 9580 1/4/2007 Gr. Beta 0.91 +/- 0.31 0.93 +/- 0.30 0.92 +/- 0.22 Pass DW-70085, 70086 1/9/2007 Gr.: Alpha 7.95 +/- 1.20 7.92 +/- 1.42 7.94 +/- 0.93 Pass DW-70037, 70038 1/11/2007 Gr. Alpha 55.47 +/- 3.99 52.87 +/- 4.02 54.17 +/- 2.83 Pass DW-70054, 70055 1/18/2007 Gr. Alpha 2.68 +/- 0.88 1.88 +/- 0.78 2.28 +/- 0.59 Pass DW-70122, 70123 1/18/2007 Gr. Alpha 4.30 +/- 1.14 6.25 +/- 1.16 5.28 +/- 0.81 Pass DW-70122, 70123 1/18/2007 Gr. Beta 4.22 +/-0.70 5.33 +/- 0.75 4.78 +/- 0.51 Pass DW-70098, 70099 1/25/2007 Gr. Alpha 3.27 +/- 0.90 1.97 +/- 0.92 2.62 +/- 0.64 Pass DW-70110, 70111 1/25/2007 Gr. Alpha 2.19 +/- 0.92 1.69 +/- 0.79 1.94 +/- 0.61 Pass SWU-676, 677 1/30/2007 Gr. Beta 1.77 +/- 0.39 2.11 +/- 0.39 1.94 +/- 0.28 Pass DW-70148, 70149 1/30/2007 Gr. Alpha 4.65 +/- 1.37 5.20+/- 1.81 4.93 +/- 1.14 Pass SW-600, 601 2/1/2007 K-40 1.24 +/- 0.12 1.20 +/- 0.12 1.22 +/- 0.08 Pass SW-601, 602 2/1/2007 Gr. Beta 0.89 +/- 0.37 1.02 +/- 0.25 0.96 +/- 0.22 Pass DW-1138, 1139 2/9/2007 H-3 2707.00 +/- 161.00 2700.00 +/- 161.00 2703.50 +/- 113.84 Pass MI-721, 722 2/13/2007 K-40 1330.40 +/- 117.60 1316.40 +/- 116.50 1323.40 +/- 82.77 Pass SW-847, 848 2/13/2007 Gr. Alpha 3.82 +/- 1.67 2.61 +/- 1.24 3.22 +/- 1.04 Pass SW-847, 848 2/13/2007 Gr. Beta 7.33 +/- 1.37 5.89 +/- 0.90 6.61 +/- 0.82 Pass DW-70175, 70176 2/14/2007 Gr. Alpha 11.72 +/- 1.68 8.84 +/- 1.32 10.28 +/- 1.07 Pass DW-70187, 70188 2/14/2007 Gr. Alpha 6.79 +/- 1.18 6.47 +/- 1.08 6.63 +/- 0.80 Pass SWU-1162, 1163 2/27/2007 Gr. Beta 3.63 +/- 0.69 2.61 +/-0.44 3.12 +/- 0.41 Pass DW-70205, 70206 2/28/2007 Gr. Alpha 0.88 +/- 0.80 1.31 +/-0.79 1.10 +/- 0.56 Pass PW-1117, 1118 3/1/2007 Gr. Alpha 3.79 +/- 1.91 3.62 +/- 2.09 3.71 +/- 1.42 Pass PW-1117, 1118 3/1/2007 Gr. Beta 7.12 +/- 1.40 7.20 +/- 1.39 7.16 +/- 0.99 Pass W-2122, 2123 3/5/2007 Gr. Alpha 6.10 +/-4.16 3.80 +/- 4.30 4.95 +/- 2.99 Pass W-2122, 2123 3/5/2007 Gr. Beta 10.65 +/- 2.15 13.11 +/-2.42 11.88 +/- 1.62 Pass W-2085, 2086 3/6/2007 Gr. Alpha 2.51 +/- 2.29 1.10 +/- 2.78 1.81 +/- 1.80 Pass W-2085, 2086 3/6/2007 Gr. Beta 11.02 +/- 1.85 9.50 +/- 2.01 10.26 +/- 1.37 Pass DW-70232, 70233 3/8/2007 Gr. Alpha 4.75 1.28 5.98 +/-1.31 5.37 +/- 0.92 Pass WW-1477, 1478 3/12/2007 Gr. Beta 6.41 +/- 1.48 4.10 +/- 1.25 5.26 +/- 0.97 Pass WW-1498, 1499 3/15/2007 Gr. Beta 0.83 +/- 0.31 0.97 +/- 0.33 0.90 +/- 0.22 Pass W-2140, 2141 3/19/2007 Gr. Alpha 2.31 +/- 1.57 1.33 +/- 1.64 1.82 +/- 1.14 Pass W-2140, 2141 3/19/2007 Gr. Beta 4.26 +/- 1.00 .5.58 +/- 1.02 4.92 +/- 0.71 Pass DW-1626, 1627 3/21/2007 H-3 4973.00 +/- 209.00 5190.00 +/- 213.00 5081.50 +/-,149.21 Pass MI-1647, 1648 3/21/2007 K-40 1448.80 +/- 120.20 1439.30 +/- 126.00 1444.05 +/- 87.07 Pass DW-70248, 70249 3/21/2007 Gr. Alpha 11.10 +/- 1.18 9.90 +/- 1.16 10.50 +/- 0.83 Pass W-2150, 2151 3/26/2007 Gr. Alpha 3.56 +/- 2.20 3.30 +/- 1.81 3.43 +/- 1.42 Pass W-2150, 2151 3/26/2007 Gr. Beta 9.26 +/- 1.00 10.17 +/- 1.90 9.72 +/- 1.07 Pass LW-1941, 1942 3/31/2007 Gr. Beta 1.35 +/- 0.43 1.36 +/- 0.41 1.36 +/- 0.30 Pass A5-1

TABLE A-5. In-House "Duplicate" Samples Concentration (pCi/L)a Averaged Lab Code Date Analysis First Result Second Result Result Acceptance MI-1824, 1825 4/2/2007 K-40 1316.10 +/- 110.60 1229.80 +/- 110.50 1272.95 +/- 78.17 Pass MI-1824, 1825 4/2/2007 Sr-90 1.20 +/- 0.50 1.10 +/- 0.36 1.15 +/- 0.31 Pass AP-2170, 2171 4/2/2007 Be-7 0.08 +/- 0.01 0.08 +/- 0.01 0.08 +/- 0.01 Pass WW-1850, 1851 4/3/2007 H-3 -5.83 +/- 102.29 150.05 +/- 80.14 72.11 +/- 64.97 Pass AP-2198, 2199 4/3/2007 Be-7 0.08 +/- 0.01 0.08 +/- 0.01 0.08 +/- 0.01 Pass AP-2370, 2371 4/3/2007 Be-7 0.07 +/- 0.01 0.07 +/- 0.01 0.07 +/- 0.01 Pass DW-70300, 70301 4/4/2007 Gr. Alpha 3.78 +/- 0.89 3.66 +/- 0.96 3.72 +/- 0.65 Pass DW-70300, 70301 4/4/2007 Gr. Beta 2.93 +/- 0.61 2.91 +/- 0.64 2.92 +/- 0.44 Pass DW-70335, 70336 4/5/2007 Gr. Alpha 24.37 +/- 2.89 22.72 +/- 2.91, 23.55 +/- 2.05 Pass DW-70335, 70336 4/5/2007 Gr. Beta 20.26 +/- 1.37 18.33 +/- 1.34 19.30 +/- 0.96 Pass SW-1898, 1899 4/10/2007 Gr. Alpha 3.86 +/- 1.40 4.78 +/- 1.51 4.32 +/- 1.03 Pass SW-1898, 1899 4/10/2007 Gr. Beta 6.31 +/- 1.36 7.03 +/- 1.42 6.67 +/- 0.98 Pass SW-1898, 1899 *4/10/2007 H-3 241.99 +/- 93.35 318.10 +/- 96.48 280.04 +/- 67.12 Pass DW-70346, 70347 4/11/2007 Gr. Alpha 1.83 +/- 1.08 2.54 +/- 1.04 2.19 +/- 0.75 Pass DW-70346, 70347 4/11/2007 Gr. Beta 4.62 +/- 0.72 4.01 +/- 0.71 4.32 +/- 0.51 Pass DW-70376, 70377 4/11/2007 Gr. Alpha 1.81 +/- 0.80 1.66 +/- 0.86 1.74 +/- 0.59 Pass DW-70376, 70377 4/11/2007 Gr. Beta 1.84 + 0.62 2.24 +/- 0.61 2.04 +/- 0.44 Pass DW-70311, 70312 4/12/2007 Gr. Alpha 10.82 +/- 1.50 13.20 +/- 1.56 12.01 +/- 1.08 Pass WW-2349, 2350 4/17/2007 Gr. Alpha 0.71 +/- 0.56 0.62 +/- 0.52 0.66 +/- 0.38 Pass WW-2461, 2462 4/25/2007 H-3 190.30 + 100.31 115.95 +/- 97.65 153.13 +/- 70.00 Pass LW-2437, 2438 4/26/2007 Gr. Beta 2.71 + 0.50 2.15 +/- 0.45 2.43 +/- 0.34 Pass LW-2917, 2918 4/30/2007 Gr. Beta 1.97 +/- 0.79 2.78 +/- 0.81 2.38 +/- 0.57 Pass SO-2583, 2584 5/1/2007 Be-7 544.99 +/- 247.70 601.13 +/- 192.20 573.06 +/- 156.76 Pass SO-2583, 2584 5/1/2007 Cs-1 37 119.22 +/- 36.61 87.46 +/- 23.97 103.34 +/- 21.88 Pass SO-2583, 2584 - 5/1/2007 K-40 17825.00 +/- 749.90- 17672.00 +/- 724.30- 17748.50 +/- 521.29 - Pass SO-2583, 2584 5/1/2007 Gr. Alpha 11.49 +/- 3.96 8.04 +/- 3.88 9.77 +/- 2.77 Pass SO-2583, 2584 5/1/2007 Gr. Beta 31.02 +/- 3.74 26.10 +/- 3.40 28.56 +/- 2.53 Pass SO-2583, 2584 5/1/2007 Sr-90 0.086 +/- 0.024 0.068 +/- 0.025 0.077 +/- 0.017 Pass S-2620, 2621 5/2/2007 H-3 277.90 +/- 126.70 304.40 +/- 101.00 291.15 +/- 81.02 Pass MI-2610, 2611 5/3/2007 K-40 1549.20 +/- 184.20 1388.80 +/- 128.20 1469.00 +/- 112.21 Pass W-4469, 4470 5/7/2007 Gr. Beta 10.60 +/- 1.90 11.10 +/- 1.80 10.85 +/- 1.31 Pass SS-2697, 2698 5/8/2007 Cs-1 37 0.06 +/- 0.02 0.05 +/- 0.03 0.05 +/- 0.02 Pass SS-2697, 2698 5/8/2007 K-40 8.03 +/- 0.57 7.36 +/- 0.68 7.70 +/- 0.44 Pass MI-2790, 2791 5/14/2007 K-40 1694.30 +/- 126.20 1627.60 +/- 128.80 1660.95 +/- 90.16 Pass W-4505, 4506 5/14/2007 Gr. Beta 3.30 +/- 1.70 3.90 +/- 1.50 3.60 +/- 1.13 Pass DW-3219, 3220 5/26/2007 1-131 0.62 +/- 0.32 0.69 +/- 0.31 0.66 +/- 0.22 Pass SO-3416, 3417 5/31/2007 Cs-137 0.15 +/- 0.03 0.15 +/- 0.03 0.15 +/- 0.02 Pass SO-3416, 3417 5/31/2007 Gr. Beta 22.88 +/- 2.33 22.46 +/- 2.37 22.67 +/- 1.66 Pass SO-3416, 3417 5/31/2007 K-40 12.26 +/- 0.80 12.36 +/- 0.65 12.31 +/- 0.52 Pass F-3561, 3562 5/31/2007 K-40 3.06 +/- 0.39 3.37 +/- 0.45 3.21 +/- 0.30 Pass SL-3311, 3312 6/4/2007 Be-7 0.61 +/- 0.29 0.55 +/- 0.25 0.58 +/- 0.19 Pass SL-3311, 3312 6/4/2007 K-40 5.78 +/- 0.67 4.87 +/- 0.25 5.33 +/- 0.36 Pass A5-2

TABLE A-5. In-House "Duplicate" Samples Concentration (pCi/L)B Averaged Lab Code Date Analysis First Result Second Result Result Acceptance SL-3992, 3993 6/4/2007 Be-7 0.75 +/- 0.19 0.74 +/- 0.32 0.75 +/- 0.19 Pass SL-3992, 3993 6/4/2007 Gr. Beta 13.61 +/- 1.12 14.06 +/- 1.08 13.84 +/- 0.78 Pass SL-3992, 3993 6/4/2007 K-40 2.43 +/- 0.36 2.29 +/- 0.40 2.36 +/- 0.27 Pass W-5087, 5088 6/11/2007 Gr. Beta, 8.70 +/- 1.90 7.70 +/- 1.90 8.20 +/- 1.34 Pass SW-3710, 3711 6/14/2007 H-3 9571.51 +/- 287.22 9879.21 +/- 291.42 9725.36 +/- 204.59 Pass W-4062, 4063 6/28/2007 Gr. Alpha 0.76 +/- 0.63 0.32 +/- 0.66 0.54 +/- 0.45 Pass W-4062, 4063 6/28/2007 Gr. Beta 0.97 +/- 0.53 0.58 +/- 0.57' 0.78 +/- 0.39 Pass AP-4448, 4449 6/28/2007 Be-7 0.10 +/- 0.02 0.09 +/- 0.02 0.10 +/- 0.01 Pass SG-3735, 3736 6/30/2007 Be-7 0.84 +/- 0.12 0.82 +/- 0.18 0.83 +/- 0.11 Pass SG-3735, 3736 6/30/2007 Cs-137 0.07 +/- 0.01 0.07 +/- 0.01 0.07 +/- 0.01, Pass-SG-3735, 3736 6/30/2007 Gr. Beta 29.51 +/- 2.22 30.81 +/- 2.22 30.16 +/- 1.57 Pass SG-3735, 3736 6/30/2007 K-40 9.41 +/- 0.31 8.90 +/- 0.48 9.16 +/- 0.29 Pass LW-4175, 4176 6/30/2007 Gr. Beta 2.18 +/- 0.60 1.93 +/- 0.68 2.06 +/- 0.45 Pass SG-5422, 5423 7/2/2007 Gr. Alpha 10.31 +/- 1.98 10.57 +/- 1.99 10.44 +/-1.40 Pass SG-5422, 5423 7/2/2007 Gr. Beta 18.59 +/- 1.46 20.97 +/- 1.49 19.78 +/- 1.04 Pass AP-4656, 4657 7/3/2007 Be-7 0.09 +/- 0.02 0.10 +/- 0.02 0.10 +/- 0.01 Pass AP-4763, 4764 7/3/2007 Be-7 0.11 +/-0.02 0.10 +/- 0.02 0.11 +/- 0.01 Pass SG-5430, 5431 7/11/2007 Be-7 10.17 +/- 0.48 10.06 +/- 0.51 10.12 +/- 0.35 Pass SG-5430, 5431 7/11/2007 Cs-137 0.050 +/- 0.010 0.059 +/- 0.011 0.055 +/- 0.007 Pass SG-5430, 5431 7/11/2007 Gr. Alpha 17.86 t 2.78 15.74 +/- 2.70 16.80 +/- 1.94 Pass SG-5430, 5431 .7/11/2007 Gr. Beta 25.04 +/- 1.86 26.19 +/- 1.74 25.62 +/- 1.27 Pass SG-5430, 5431 7/11/2007 K-40 7.69 +/- 0.30 7.65 +/- 0.28 7.67 +/- 0.21 Pass WW-4298, 4299 7/12/2007 Gr. Beta 1.74 +/- 0.74 2.22 +/- 0.80 1.98 +/- 0.55 Pass DW-70612, 70613 7/23/2007 Gr. Alpha 4.54 +/- V11I 4.19 +/- 0.97 4.37 +/- 0.74 Pass WW-4918, 4919 7/25/2007 H-3 240.43 +/- 111.12 216.68 +/- 110.27 228.56 +/- 78.27 Pass MI-4742, 4743 7/26/2007 K-40 1820.30 +/- 134.10 1802.90 +/- 199.50 1811.60 +/- 120.19 Pass VE-4939, 4940 8/1/2007 Be-7 0.39 +/- 0.21 0.45 +/- 0.20 0.42 +/- 0.15 Pass VE-4939, 4940 8/1/2007 Gr. Beta 5.50 +/- 0.14 5.76 +/- 0.13 5.63 +/- 0.10 Pass VE-4939, 4940 8/1/2007 K-40 3.36 +/- 0.45 3.36 +/- 0.21 3.36 +/- 0.25 Pass SG-6274, 6275 8/6/2007 Gr. Alpha 16.68 +/- 3.29 19.26 +/- 3.39 17.97 +/- 2.36 Pass SG-6274, 6275 8/6/2007 Gr. Beta 40.93 +/- 2.74 42.42 +/- 2.66 41.68 +/- 1.91 Pass SW-5218, 5219 8/7/2007 1-131 1.31 +/- 0.24 1.42 +/- 0.24 1.37 +/- 0.17 Pass SG-6284, 6285 8/8/2007 Cs-1 37 0.043 +/- 0.006 0.051 +/- 0.007 0.047 +/- 0.005 Pass SG-6284, 6285 8/8/2007 Gr. Alpha 9.38 +/- 2.93 13.61 +/- 3.38 11.50 +/- 2.24 Pass SG-6284, 6285 8/8/2007 Gr. Beta 33.46 +/- 2.84 32.87 +/- 2.93 33.17 +/- 2.04 Pass SG-6284, 6285 8/8/2007 K-40 16.15 +/- 0.24 16.23 +/- 0.25 .16.19 +/- 0.17 Pass WW-5310, 5311 8/9/2007 H-3 644.00 +/- 106.00 831.00 +/- 113.00 737.50 +/- 77.47 Pass SW-5393, 5394 8/14/2007 Gr. Beta 2.32 +/- 1.31 1.71 +/- 1.27 2.02 +/- 0.92 Pass SW-5393, 5394 8/14/2007 H-3 190.06 +/- 86.80 69.05 +/- 80.88 129.55 +/- 59.32 Pass W-5468, 5469 8/15/2007 H-3 262.58 +/- 108.43 346.53 +/- 111.42 304.55 +/- 77.74 Pass A5-3

TABLE A-5. In-House "Duplicate" Samples Concentration (pCi/L)a Averaged Lab Code Date Analysis First Result Second Result Result Acceptance VE-5553, 5554 8/22/2007 K-40 1.89 +/- 0.33 1.89 +/- 0.22 1.89 +/- 0.20 Pass WW-5643, 5644 8/22/2007 H-3 259.00 +/- 110.00 266.00 +/- 110.00 262.50 +/- 77.78 Pass SWU-5799, 5800 8/28/2007 Gr. Beta 2.64 +/- 1.18 3.62 +/- 1.06 3.13 +/- 0.79 Pass DW-70752, 70753 8/31/2007 Gr. Alpha 14.41 +/- 1.48 12.90 +/- 1.50 13.66 +/- 1.05 Pass VE-5917, 5918 9/4/2007 Be-7 0.94 +/- 0.17 0.83 +/- 0.20 0.89 +/- 0.13 Pass VE-5917, 5918 9/4/2007 K-40 3.73 +/- 0.37 3.58 +/- 0.36 3.66 +/- 0.26 Pass VE-5917, 5918 9/4/2007 Gr. Beta 2.71 +/- 0.10 2.69 +/- 0.10 2.70 +/- 0.07 Pass MI-6009, 6010 9/11/2007 K-40 1348.90 +/- 113.40 1388.10 +/- 116.40 1368.50 +/- 81.25 Pass MI-6030, 6031 9/12/2007 K-40 1242.70 +/- 118.00 1475.60 +/- 119.60 1359.15 +/- 84.01 Pass MI-6030, 6031 9/12/2007 Sr-90 1.00 +/- 0.38 0.90 +/- 0.34 0.95 +/- 0.26 Pass DW-70718, 70719 9/12/2007 Gr. Alpha 23.04 +/- 3.71 23.22 +/- 3.61 23.13 +/- 2.59 Pass DW-70718, 70719 9/12/2007 Gr. Beta 16.13 +/- 1.59 17.36 +/- 1.69 16.75 +/- 1.16 Pass SO-6156, 6157 9/14/2007 H-3 181.99 +/- 90.67 232.19 +/- 92.95 207.09 +/- 64.92 Pass SO-6484, 6485 9/17/2007 Cs-1 37 0.01 +/- 0.00 0.01 +/- 0.00 0.01 +/- 0.00 Pass SO-6484, 6485 9/17/2007 Gr. Beta 24.20 +/- 2.60 23.30 +/- 2.30 23.75 +/- 1.74 Pass SO-6484, 6485 9/17/2007 K-40 11.52 +/- 1.16 10.89 +/- 1.10 11.20 +/- 0.80 Pass WW-6469, 6470 9/21/2007 Gr. Beta 27.19 +/- 2.51 24.23 +/- 2.29 25.71 +/- 1.70 Pass E-6647, 6648 10/1/2007 Gr. Beta 1.82 + 0.10 1.93 +/- 0.11 1.88 +/- 0.07 Pass E-6647, 6648 10/1/2007 K-40 1.48 + 0.24 1.31 +/- 0.23 1.40 +/- 0.17 Pass WW-6656, 6657 10/1/2007. Gr. Beta 2.80 +/- 0.97 1.95 +/- 0.87 2.38 +/- 0.65 Pass TD-7080, 7081 10/2/2007 H-3 332.00 +/- 229.00 383.00 +/- 191.00 357.50 +/- 149.10 Pass SG-6891, 6892 10/3/2007 Gr. Alpha 12.93 +/- 2.12 1'3.52 +/- 2.07 13.23 +/- 1.48 Pass SG-6891, 6892 10/3/2007 Gr. Beta 18.08 + 1.41 18.27 +/- 1.36 18.18 +/- 0.98 Pass AP-7191, 7192 10/3/2007 Be-7 0.09 + 0.01 0.09 +/- 0.01 0.09 +/- 0.01 Pass WW-6786, 6787 10/8/2007 H-3 --13333 +/-322 13532 +/-324 13433 +/-228 Pass WW-6786, 6787 10/8/2007 H-3 13188 +/- 322 13556 +/- 326 13372 +/- 229 Pass VE-6828, 6829 10/8/2007 Gr.Alpha 0.06 +/- 0.04 0.06 +/- 0.05 0.06 +/- 0.03 Pass VE-6828, 6829 10/8/2007 Gr. Beta 5.55 +/- 0.21 5.20 +/- 0.22 5.38 +/- 0.10 Pass VE-6828, 6829 10/8/2007 K-40 5.45 +/- 0.43 5.20 +/- 0.49 5.32 +/- 0.33 Pass SS-6870, 6871 10/9/2007 Gr. Beta 18.10 +/- 2.08 21.71 +/- 2.19 19.90 +/- 1.51 Pass SS-6870, 6871 10/9/2007 K-40 10.19 +/- 0.66 9.72 +/- 0.68 9.95 +/- 0.47 Pass LW-7507, 7508 10/11/2007 Gr. Beta 1.40 +/- 0.56 1.44 +/- 0.54 1.42 +/- 0.39 Pass MI-6933, 6934 10/16/2007 K-40 1386.60 +/- 104.70 1331.20 +/- 106.70 1358.90 +/- 74.74 Pass MI-6933, 6934 10/16/2007 Sr-90 1.73 +/- 0.52 2.17 +/- 0.57 1.95 +/- 0.39 Pass MI-7059, 7060 10/17/2007 K-40 1424.80 +/- 106.60 1448.60 +/- 115.30 1436.70 +/- 78.51 Pass F-7213, 7214 10/24/2007 H-3 6.83 +/- 0.22 7.24 +/- 0.22 7.03 +/- 0.16 Pass F-7213, 7214 10/24/2007 K-40 3.13 +/- 0.51 3.16 +/- 0.48 3.15 +/- 0.35 Pass WW-7408, 7409 10/24/2007 H-3 340.71 +/- 90.45 346.22 +/- 90.67 343.46 +/- 64.03 Pass DW-70856, 70857 10/24/2007 Gr. Alpha 11.03 +/- 1.66 10.71 +/- 1.34 10.87 +/- 1.07 Pass SO-7508, 7509 10/26/2007 Cs-137 0.30 +/- 0.04 0.29 +/- 0.05 0.29 +/- 0.03 Pass SO-7508, 7509 10/26/2007 Gr. Beta 34.43 +/- 2.72 37.25 +/- 3.07 35.84 +/- 2.05 Pass SO-7508, 7509 10/26/2007 K-40 16.84 +/- 0.84 17.43 +/- 1.05 17.14 +/- 0.67 Pass A5-4

TABLE A-5. In-House "Duplicate" Samples Concentration (pCi/L)a Averaged Lab Code Date Analysis First Result Second Result Result Acceptance SS-7529, 7530 10/29/2007 Cs-1 37 0.12 +/- 0.03 0.12 +/- 0.02 0.12 +/- 0.02 Pass SS-7529, 7530 10/29/2007 K-40 11.85 +/- 0.68 11.75 +/- 0.58 11.80 +/- 0.45 Pass SW-7589, 7590 10/30/2007 Gr. Beta 1.75 +/- 0.29 1.24 +/- 0.26 1.50+0.19 Pass SWU-7733, 7734 10/30/2007 Gr. Beta 1.66 +/- 1.01 2.43 +/- 1.13 2.05 +/- 0.76 Pass MI-7618, 7619. 10/31/2007 K-40 1376.80 +/- 114.30 1426.70 +/- 128.80 1401.75 +/- 86.10 Pass VE-7666,7667 11/5/2007 Gr. Alpha 0.07 +/- 0.04 0.16 +/-0.05 0.11 +/-+0.03 Pass VE-7666, 7667 11/5/2007 Gr. Beta 6.03 +/- 0.15 6.13 +/- 0.15 6.08 +/- 0.10 Pass VE-7666, 7667 11/5/2007 K-40 .5.82 +/- 0.36 5.74 +/- 0.36 5.78 +/- 0.25 Pass DW-7853, 7854 11/9/2007 1-131 1.61 +/- 0.40 1.08 +/- 0.39 1.35 +/- 0.28 Pass MI-7874, 7875 11/14/2007 K-40 1407.70 +/- 101.30 1362.60 +/- 114.50 1385.15 +/- 76.44 Pass WW-8142, 8143 11/28/2007 Gr. Beta 9.51 +/- 2.21 7.86 +/- 2.01 8.68 +/- 1.49 Pass DW-8094, 8095 11/29/2007 Gr. Beta 1.60 +/- 0.58 1.25 +/- 0.54 1.43 + 0.40 Pass F-8328, 8329 12/11/2007 Gr. Beta 3.97 +/- 0.08 4.00 +/- 0.08 3.99 + 0.05 Pass WW-8378, 8379 12/11/2007 H-3 296.00 +/- 103.00 407.00 +/- 107.00 351.50 + 74.26 Pass Note: Duplicate analyses are performed on every twentieth sample received in-house. Results are not listed for those analyses with activities that measure below the LLD.

a Results are reported in units of pCi/L, except for air filters (pCi/Filter), food products, vegetation, soil, sediment (pCi/g).

A5-5

TABLE A-6. Department of Energy's Mixed Analyte Performance Evaluation Program (MAPEP)8 .

Concentration b Known Control Lab Codec Date Analysis Laboratory, result Activity Limits d Acceptance STW-1110 0.1/01/07 Gr. Alpha 0.45 +/- 0.08 0.33 0.00 - 0.65 Pass STW-1110 01/01/07 Gr. Beta 0.90 +/- 0.14 0.85 0.43 -1.28 Pass STW-1111 e 01/01/07 Am-241 2.80 +/- 0.21 1.71 1.20 -2.22 Fail STW-1111 01/01/07 Co-57 151.60 +/- 10.00 143.70 100.60 -186.80 Pass STW-1111 01/01/07 Cs-1 34 79.20 +/- 8.00 83:50 58.50 -108.60 Pass STW-1 111 01/01/07 Cs-137 168.70 +/- 12.10 163.00 114.10 -211.90 Pass STW-1111 01/01/07 Fe-55 130.30 +/- 19.90 129.30 90.50 -168.10 Pass STW-1111 01/01/07 H-3 262.20 +/- 9.10 283.00 198.10 -367.90 Pass STW-1111 01/01/07 Mn-54 130.60 +/- 11.50 123.80 86.70 -160.90 Pass STW-1111 01/01/07 Ni-63 127.80 +/- 3.60 130.40 91.30 - 169.50 Pass STW-1111 01/01/07 Ni-63 127.80 +/- 3.60 130.40 91.30 -169.50 Pass STW-1111 01/01/07 Pu-238 2.03 +/- 0.17 2.25 1.58 -2.93 Pass STW-1111 01/01/07 Pu-239/40 2.27 +/- 0.17 2.22 1.55 -2.89 Pass STW-1111 01/01/07 Sr-90 9.60 +/- 1.40 8.87 6.21 -11.53 Pass STW-1111 01/01/07 Tc-99 8.80 +/- 1.50 88.00 7.40 -13.70 Pass STW-1111 01/01/07 U-233/4 2.44 +/- 0.21 2.49 1.74 -3.24 Pass STW-1111 01/01/07 U-238 2.44 +/- 0.21 2.48 1.74 -3.22 Pass STW-1111 01/0'1/07 Zn-65 123.70 +/- 17.00 114.80 80.40 -149.20 Pass STSO-1112' 01/01/07 Am-241 46.40 +/- 9.00 34.80 24.40 - 45.20 Fail STSO-1 112 01/01/07 Co-57 501.20 +/- 2.90 471.20 329.80 -612.60 Pass STSO-1 112 01/01/07 Co-60 285.90 +/- 2.10 274.70 192.30 -357.10 Pass STSO-1 112 01/01/07 Cs-1 34 325.90 +/- 7.40 327.40 229.20 -425.60 Pass STSO-1 112 01/01/07 Cs-137 855.70 +/-+4.60 799.70 559.80 - 1039.60 Pass STSO-1 112 01/01/07 Mn-54 750.90 +/- 4.70 _.. 685.20 479.60 -8.90.80 Pass STAP-1113 01/01/07 Gr. Alpha 0.27 +/- 0.04 0.60 0.00 -1.20 Pass STAP-1113 01/01/07 Gr. Beta 0.57 +/- 0.05 0.44 0.22 - 0.66 Pass STAP-1 114 01/01/07 Am-241 0.10 +/- 0.03 0.10 0.07 -0.13 Pass STAP-1 114 01/01/07 Co-57 3.51 +/- 0.07 2.89 2.02 - 3.75 Pass STAP-1 114 01/01/07 Co-60 2.98 +/- 0.10 2.91 2.03 - 3.78 Pass STAP-1 114 01/01/07 Cs-1 34 4.02 +/- 0.16 4.20 2.94 - 5.45 Pass STAP-1 114 01/01/07 Cs-137 2.75 +/- 0.12 2.57 1.80 -3.34 Pass STAP-1 114 01/01/07 Mn-54 3.94 +/- 0.12 3.52 2.46 - 4.57 Pass STAP-1114 01/01/07 Pu-238 0.07 +/- 0.01 0.07 0.05 - 0.09 Pass STAP-1 114 01/01/07 Pu-239/40 0.08 +/- 0.01 0.08 0.06 -0.11 Pass STAP-1 114 01/01/07 Sr-90 0.58 +/- 0.18 0.61 0.43 - 0.79 Pass STAP-1114 01/01/07 U-233/4 0.09 +/- 0.01 0.10 0.07 -0.13 Pass STAP-1 114 01/01/07 U-238 0.09 +/- 0.01 0.10 0.07 - 0.13 Pass STAP-1114 01/01/07 Zn-65 2.70 +/- 0.10 2.68 1.88-3.49 Pass A6-1

TABLE A-6. Department of Energy's Mixed Analyte Performance Evaluation Program (MAPEP)a.

b Concentration Known Control Lab Coder Date Analysis Laboratory result Activity Limits d Acceptance STVE-1115 01/01/07 Co-57 8.90 +/- 0.20 8.19 5.73 - 10.64 Pass STVE-1 115 01/01/07 Co-60 6.50 +/- 0.20 5.82 4.08 - 7.57 Pass STVE-1115 01/01/07 Cs-1 34 6.90 +/- 0.30 6.21 4.35 - 8.07 Pass STVE-1115 01/01/07 Cs-137 8.20 +/- 0.30 6.99 4.90 - 9.09 Pass STVE-1115 01/01/07, Mn-54 10.10 + 0.30 8.46 5.91 - 10.98 Pass a Results obtained by Environmental, Inc., Midwest Laboratory as a participant in the Department of Energy's Mixed Analyte Performance Evaluation Program, Idaho Operations office, Idaho Falls, Idaho b Results are reported in units of Bq/kg (soil), Bq/L (water) or Bq/total sample (filters, vegetation).

Laboratory codes as follows: STW (water), STAP (air filter), STSO (soil), STVE (vegetation).

d MAPEP results are presented as the known values and expected laboratory precision (1 sigma, 1 determination) and control limits as defined by the MAPEP.

e Result of reanalysis, 2.08 +/- 0.13 pCi/L.

f The test samples were recounted on lower background detectors. Result of the recounts: 41.4 +/- 6.3 Bq/kg.

A6-2

TABLE A-7. Interlaboratory Comparison Crosscheck program, Environmental Resource Associates (ERA)'.

Concentration (pCi/L)

Lab Code b Date Analysis Laboratory ERA Control

  • Result c Result d Limits Acceptance STAP-1 116 03/19/07 Gr. Alpha 34.64 +/- 2.56 25.8 12.4 -39 Pass STAP-1116 03/19/07 Gr. Beta 93.41 +/- 3.20 79.5 48.8-116 Pass STAP-1 117 03/19/07 Am-241 56.04 +/- 3.90 57.5 33.1 -80 Pass STAP-1 117 03/19/07 Co-60 1610.00 +/- 8.40 1300.0 1010M - 1620 Pass STAP-1 117 03/19/07 Cs-134 1340.40 +/- 48.84 1120.0 732.0 -1380 Pass STAP-1117 e 03/19/07 Cs-1 37 345.30.+/- 8.20 255.0 192.0 -336 Fail STAP-1117' 03/19/07 Fe-55 < 134.0 0.0 Pass STAP-1117 03/19/07 Mn-54 < 5.0 0.0 Pass STAP-1 117 03/19/07 Pu-238 43.32 +/- 2.28 37.4 25.7 -49 Pass STAP-1 117 03/19/07 Pu-239/40 35.23 +/- 2.24 31.6 22.9 -41 Pass STAP-1 117 03/19/07 Sr-90 156.10 +/- 6.60 156.0 66.6 -246 Pass STAP-1 117 03/19/07 U-233/4 42.22 +/- 1.84 47.8 30.1 -71 Pass STAP-1117 03/19/07 U-238 42.00 +/- 1.84 47.4 30.2 -68 Pass STAP-1 117 03/19/07 Uranium 85.79 +/- 3.60 97.3 49.5 -155 Pass STAP-1 117 03/19/07 Zn-65 363.80 +/- 11.90 245.0 208.0 -412 Pass STSO-1 118 03/19/07 Ac-228 3097.77 +/- 94.96 2790.0 1790.0 -3930 Pass STSO-1118 03/19/07 Am-241 1000.70 +/- 156.10 927.0 548.0 -1200 Pass STSO-1118 03/19/07 Bi-212 2467.87 +/- 114.33 2500.0 658.0 -3730 Pass STSO-1 118 03/19/07 Co-60 7847.40 +/-86.60 7330.0 5340.0 -9820 Pass STSO-1 118 03/19/07 Cs-134 7910.60 +/- 356.88 7560.0 4850.0 - 9070 Pass STSO-1 118 03/19/07 Cs-1 37 4635.00 +/- 99.10 4300.0 3290.0 -5580 Pass STSO-1 118 03/19/07 K-40 12201.60 +/- 423.20 11100.0 8050.0 -15000 Pass STSO-1118' 03/19/07 Mn-54 < 34.0 0.0 Pass STSO-1 118 03/19/07 Pb-212 2046.80 +/- 127.20 1730.0 1120.0 -2430 Pass STSO-1 118 03/19/07 Pb-214- 4142.80+/- 110.40 3330.0 1980.0 -4980 Pass STSO-1 118 03/19/07 Pu-238 1099.20 +/- 73.10 857.0 490.0 -1200 Pass STSO-1 118 03/19/07 Pu-239/40 1586.10 +/- 82.00 1360.0 928.0 -1810 Pass STSO-1 118 03/19/07 Sr-90 6163.30 +/- 791.60 7500.0 2610.0 -12400 Pass STSO-1118 03/19/07 Th-234 4329.40 +/- 569.10 3590.0 2190.0 -4560 Pass STSO-1118 03/19/07 U-233/4 3236.70 +/- 106.00 3620.0 2280.0 - 4520 Pass STSO-1 118 03/19/07 U-238 3425.20 +/- 134.00 3590.0 2190.0 -4560 Pass STSO-1118 03/19/07 Uranium 6787.80 +/- 240.00 7380.0 4210.0 -9930 Pass STSO-1 118 03/19/07 Uranium 6787.80 +/- 240.00 7380.0 4210.0 -9930 Pass STSO-1118' 03/19/07 Zn-65 0.00 +/- 0.00 0.0 0.0-0 Pass A7-1

TABLE A-7. Interlaboratory Comparison Crosscheck program, Environmental Resource Associates (ERA)a.

Concentration (pCi/L)

Lab Code b Date Analysis Laboratory ERA Control Result c Result d Limits Acceptance STVE-1 119 03/19/07 Am-241 3249.60 +/- 150.30 3550.0 2020.0 - 4890 Pass STVE-1119 03/19/07 Cm-244 1860.70 +/- 91.50 1840.0 905.0 -2870 Pass STVE-1 119 03/19/07 Co-60 2827.90 +/- 62.40 2600.0 1760.0 -3720 Pass STVE-1119 03/19/07 Cs-1 34 654.80 +/- 48.40 579.0 308.0 -822 Pass STVE-1 119 03/19/07 Cs-137 3307.30 +/- 58.80 2920.0 2150.0 -4060 Pass STVE-1 119 03/19/07 K-40 40814.20 +/- 618.80 37900.0 27200.0 - 53600 Pass STVE-1 119 03/19/07 Mn-54 <27.6 0.0 Pass STVE-1 119 03/19/07 Pu-238 2762.00 +/- 251.10 2430.0 1250.0 - 3600 Pass STVE-1119 03/19/07 Pu-239/40. 2156.60 +/- 83.40 1900.0 1180.0 -2600 Pass STVE-1119 03/19/07 Sr-90 8999.70 +/- 580.90 8890.0 4900.0 -11800 Pass STVE- 1119 03/19/07 U-233/4 2821.90 +/- 73.50 2940.0 1930.0 -3920 Pass STVE-1 119 03/19/07 U-238 2896.10 +/- 50.70 2910.0 2090.0 -3610 Pass STVE-1 119 03/19/07 Uranium 5718.00 +/- 124.15 5980.0 4110.0 - 7770 Pass STVE-1 119 03/19/07 Zn-65 474.30 + 45.70 366.0 267.0 -500 Pass STW-1 120 03/19/07 Am-241 133.50 +/- 10.60 179.0 123.0-243 Pass STW-1 120 03/19/07 Co-60 541.40 +/- 9.00 536.0 467.0 -631 Pass STW-1 120 03/19/07 Cs-1 34 1623.80 +/- 66.10 1750.0 1290.0 - 2020 Pass STW-1 120 03/19/07 Cs-137 1839.10 +/- 17.90 1850.0 1570.0 -2220 Pass STW-1 120 03/19/07 Fe-55 829.50 + 226.80 671.0 392.0 -896 Pass STW-1120' 03/19/07 Mn-54 <8.1 0.0 Pass STW-1 120 03/ 19/07 Pu-238 123.30 + 4.30 116.0 87.6 -144 Pass STW-1 120 03/19/07 Pu-239/40 95.10 + 3.80 90.9 70.3 -113 Pass STW-1 120 03/19/07 Sr-90 949.40 + 16.70 989.0 630.0 -1320 Pass STW-1 120 03/19/07 U-233/4 164.20 +/- 6.58 192.0 145.0 -247 Pass STW-1120 03/19/07 U-238 169.20 +/- 8.22 190.0 145.0 -236 Pass STW-1 120 03/19/07 Uranium 339.60 +/- 10.66 - 391.0 282.0 -521 Pass STW-1 120 03/19/07 Zn-65 2009.00 +/- 36.40 1910.0 1600.0 -2410 Pass B Results obtained by Environmental, Inc., Midwest Laboratory as a participant in the crosscheck program for proficiency testing administered by Environmental Resources Associates, serving as a replacement for studies conducted previously by the Environmental Measurements Laboratory Quality Assessment Program (EML).

b Laboratory codes as follows: STW (water), STAP (air filter), STSO (soil), STVE (vegetation).

C Unless otherwise indicated, the laboratory result is given as the mean +/- standard deviation for three determinations.

d Results are presented as the known values, expected laboratory precision (1 sigma, 1 determination) and control limits as provided by ERA.

e A high bias (- 20%) was observed in gamma results for air filters. A composite filter geometry was used in the calculations vs. a single filter geometry. Result of recalculation. Cs-1 37, 305.8 +/- 6.0 pCi/filter.

f Included in the testing series as a "false positive". No activity expected.

A7-2

APPENDIX B DATA REPORTING CONVENTIONS B-1

Data Reporting Conventions 1.0. All. activities, except gross alpha and gross beta, are decay corrected to collection time or the end of the

  • collection period.

2.0. Single Measurements

  • Each single measurement is reported as follows: x+S where: x = value of the measurement; s =.2a counting uncertainty (corresponding to the 95% confidence level):

In cases where the activity is less than the lower limit of detection L, it is reported as: < L, where L = the lower limit of detection based on 4.66a uncertainty for a background sample.

3.0. Duplicate analyses

\3.1 Individual results: For two analysis results; x 1 + s, and x2 s2 Reported result: +/-x.s; Where x= (1/2)(x 1+x 2 )ands= (1/2) Js+S2 3.2. Individual results: < L1 <. L2 Reported result: < L, where L = lower of L1 and L2 3.3. Individual results: x +/- s, <L Reported result: x +/- s if x --L; <L otherwise.

4.0. Computation of Averages and Standard Deviations 4.1 Averages and standard deviations listed in the tables are computed from all of the individual measurements over the period averaged; for example, an annual standard deviation would not be the average of quarterly standard deviations. The average x and standard deviation s of a set of n numbers x1, x2,.., x are defined as follows:--------------- . .

x =n Ex , S=n-4.2 Values below the highest lower limit of detection are not included in the average.

4.3 If all values inthe averaging group are less than the highest LLD, the highest LLD is reported.

4.4 If all but one of the values are less than the highest LLD, the single value x and associated two sigma error is reported.

4.5 In rounding off, the following rules are followed:

4.5.1. If the number following those to be retained is less than 5, the number is dropped, and the retained number s are kept unchanged. As an example, 11.443 is rounded off to 11.44.

  • 4.5.2. If-the number following those to be retained is equal to or greater than 5, the number is dropped and the last retained number is raised by 1. As an example, 11.445 is rounded off to 11.45.

B-2

APPENDIX C SUPPLEMENTAL ANALYSES C-1

C-1. Airborne particulate filters, duplicate analyses for gross beta.

Units: pCi/m 3 Required LLD: 0.010 Collection: Continuous, weekly exchange.

Date Volume Location Collected (M3) Gross Beta T-1 2 01-09-07 281 0.015 +/- 0.004 T-11 01-16-07 287 0.015 +/- 0.003 T-07 01-23-07 283 0.020 +/- 0.004 T-27 02-06-07 285 0.026 +/- 0.004 T-09 02-13-07 279 0.028 +/- 0.004 T-11 02-20-07 283 0.043 +/- 0.005 T-08 02-27-07 284 0.018 +/- 0,003 T-04 03-06-07 287 0.016 +/- 0.004 T-09 04-03-07 280 0.020 +/- 0.004 T-01 04-17-07 280 0.022 +/- 0.004 T-27 05-01-07 281 0.012 +/- 0.004 T-27 05-15-07 280 0.029 +/- 0.004 T-07 05-29-07 282 0.031 +/- 0.004 T-27 06-12-07 281 0.020 +/- 0.004 T-11 07-03-07 284 0.013 +/- 0.003 T-02 07-10-07 290 0.031 +/- 0.004 T-04 07-17-07 287 0.021 +/- 0.004 T-03 08-07-07 280 0.044 +/- 0.005 T-27 08-28-07 280 0.020 +/- 0.003 T-27 09-11-07 284 0.042 +/- 0.005 T-04 09-18-07 282 0.022 +/- 0.004 T-09 ... 09-25 284 0.046 +/- 0.005 T-01 10-02-07 285 0.029 +/- 0.004 T-08 11-27-07 275 0.031 +/- 0.004 T-03 12-04-07 286 0.030 +/- 0.004 T-02 12-26-07 333 0.045 +/- 0.004 C-2

C-2. Duplicate Analyses Surface Water Location T-145 (QC) T-22 T-1 2 Lab Code TSWU- 677 TSWU- 1163 TSWT- 2219 Date Collected 01-30-07 02-27-07 03-27-07 Gross beta 1.9 +/- 0.3 3.6 +/- 0.7 NA H-3 < 330 < 330 < 330 Sr-89 NA NA < 0.9 Sr-90 NA NA < 0.4 Mn-54 < 1.7 < 2.3 < 2.0 Fe-59 < 5.8 < 4.7 < 7.8 Co-58 < 2.1 < 2.8 < 1.8 Co-60 < 2.6 < 2.0 < 1.7 Zn-65 < 3.0 < 4.6 < 5.0 Zr-Nb-95 < 3.0 < 3.5 < 6.4 Cs-1 34 < 2.7 < 2.5 < 2.9 Cs-1 37 < 3.0 < 3.8 < 3.5 Ba-La-1 40 < 5.5 < 4.6 < 12.1 Location T-22 T-11 T-50 Lab Code TSWU- 3264 TSWU- 5128 TSWU- 5800 Date Collected 05-29-07 07-31-07 08-28-07 Gross beta < 1.7 3.6 +/- 1.1 H-3 441 +/- 92 < 330 < 330 Mn-54 < 2.3 < 3.7 < 3.8 Fe-59 < 4.0 < 11.5 <7.1 Co-58 < 3.2 < 3.1 < 4.7 Co-60 < 2.3 < 2.6 < 2.1 Zn-65 < 2.4 < 7.5 < 5.3 Zr-Nb-95 < 3.4 < 4.7 < 2.7 Cs-134 < '4.1 < 4.3 < 4.4 Cs-137 < 3.2 < 6.8 < 3.2 Ba-La-140 < 5.0 < 6.9 < 8.5 Location T-3 Lab Code TSWU- 8119 Date Collected 11-27-07 Gross beta 3.3 +/- 0.5 H-3 < 330 Mn-54 < 3.8 Fe-59 < 5.6 Co-58 < 3.7 Co-60 < 3.4 Zn-65 < 8.8 Zr-Nb-95 < 5.5 Cs-134 < 2.0 Cs-137 < 3.0 Ba-La-1 40 < 7.9 NA = Not analyzed, analysis not required.

C-3

C-2. Duplicate Analyses Air Particulates (Quarterly composites)

Location T-11 T-8 T-7 Lab Code TAP- 2198 TAP- 4428 TAP- 6976' Sr-89 < 0.0010 < 0.0011 < 0.0013 Sr-90 < 0.0006 < 0.0007 < 0.0008 Be-7 0.078 +/- 0.013 0.109 +/- 0.020 0.081 +/- 0.013 K-40 < 0.018 < 0.027 < 0.019 Nb-95 < 0.0007 < 0.0014 < 0.0010 Zr-95 < 0.0011 < 0.0010 .< 0.0021 Ru-1 03 < 0.0009 < 0.0008 < 0.0010 Ru-1 06 < 0.0038 < 0.0075 <. 0.0063 Cs-134 < 0.0006 < 0.0004 < 0.0008 Cs-137 < 0.0006 < 0.0007 < 0.0006 Ce-1 41 < 0.0010 < 0.0013 < 0.0011 Ce-144 < 0.0033 < 0.0034 < 0.0045 Location T-2 Lab Code TAP- 8810 Sr-89 < 0.0010 Sr-90 < 0.0009 Be-7 0.057 +/- 0.013 K-40 < 0.033 Nb-95 < 0.0005 Zr-95 < 0.0009 Ru-1 03 < 0.0004 Ru-i 06 < 0.0055 Cs-1 34 < 0.0006.

Cs-1 37 < 0.0005 Ce-1 41 < 0.0009 Ce-144 < 0.0028 C-4

Table 4.5 Radiological Environmental Monitoring Program Summary Name of Facility Davis-Besse Nuclear Power Station Docket No. 50-346 Location of Facility Ottawa, Ohio Reporting Period January-December, 2007

( County, State )

Indicator Location with Highest Control Number Sample Type and Locations Annual Mean Locations Non-Type Number of LLDb Mean (F)c Mean (F)c Mean (F)c Routine (Units) Analysesa Rangec Lodationd Rangec Rangec Results' Treated GB (TR) 48 1.0 2.2 (24/24) T-22, Carroll Twp. 2.2 (12/12) 1.9 (24/24) 0 Surface Water (1.2-4.5) WTP, 3.0 mi. NW (1.2-4.5) (0.9-3.6)

(pCi/L) H-3 16 330 < LLD - < LLD 0 Sr-89 16 1.5 < LLD < LLD 0 Sr-90 16 1.0 < LLD T-50, Erie Indus. Pk. 1.0 (1/4) < LLD 0 WTP, 4.5 mi. SE GS 16 Mn-54 .15 < LLD - - < LLD 0 Fe-59 30 < LLD. - < LLD 0 Co-58 15 < LLD - < LLD 0 Co-60 15 < LLD - < LLD 0 Zn-65 30 < LLD - < LLD 0 Zr-Nb-95 15 < LLD .- < LLD 0 Cs-134 10 < LLD < LLD 0 Cs-137 10 < LLD < LLD 0 Ba-La-140 15 < LLD < LLD 0 Untreated GB (TR) 60 1.0 2.6 (36/36) T-3, Site Boundary 3.0 (12112) 2.5 (24/24) 0 Surface Water (1.2-5.6) 1.4 mi. ESE (1.8-5.6) (1.2-5.5)

(pCi/L) H-3 60 330 583 (3/36) T-22, Carroll Twp' 583 (3/12) 555 (1/24) 0 (435-736) - WTP, 3.0 mi. NW (435-736)

Sr-89 20 1.4 < LLD < LLD 0 Sr-90 20 0.8 < LLD < LLD 0 GS 60 Mn-54 15 < LLD - < LLD 0 Fe-59 30 < LLD - < LLD 0 Co-58 15 < LLD - < LLD 0 Co-60 15 < LLD - < LLD 0 Zn-65 30 < LLD < LLD 0 Zr-Nb-95 15 < LLD < LLD 0 Cs-134 10 < LLD < LLD 0 Cs-137 10 < LLD < LLD 0 Ba-La-140 15 < LLD < LLD 0

Table 4.5 Radiological Environmental Monitoring Program Summary Name of Facility Davis-Besse Nuclear Power Station Docket No. 50-346 Location of Facility Ottawa, Ohio Reporting Period January-December, 2007

( County, State Indicator Location with Highest Control Number Sample Type and Locations Annual Mean Locations Non-Type Number of LLDb Mean (F)c Mean (F)c Mean (F)c Routine (Units) Analysesa Rangec Locationd Ranlec Rangec Resultse Fish GB 6 0.10 4.15(4/4) T-33, Lake Erie 4.15 (4/4) 3.94 (2/2) 0 (pCi/g wet) (3.51-4.74)- 1.5 mi. NE (3.51-4.74) (3.24-4.64)

GS 6 K-40 0.10 2.86(4/4) T-35, Lake Erie 3.04 (2/2) 3.04(2/2) 0 (2.48-3.18) > 10 mi. (2.88-3.19) (2.88-3.19)

Mn-54 0.021 < LLD - < LLD 0 Fe-59 0.177 < LLD < LLD 0 Co-58 0.041 < LLD < LLD 0 Co-60 0.022 < LLD < LLD 0 Zn-65 0.041 < LLD < LLD 0 Cs-1 34 0.020 < LLD < LLD 0 Cs-1 37 0.023 < LLD < LLD 0 Shoreline GS 8 Sediments K-40 0.10 10.54 (6/6) T-4, Site Boundary 11.43 (2/2) 10.11 (2/2) 0 (pCi/g dry) (8.71-11.95) 0.8 mi. S (11.07-11.78) (9.61-10.61)

Mn-54 0.034 < LLD < LLD 0 Co-58 0.027 < LLD "- < LLD 0 Co-60 0.024 < LLD - < LLD 0 Cs-134 0.045 < LLD < LLD 0 Cs-137 0.029 < LLD . -<LLD < 0 o GB = gross beta, GS = gamma scan.

b LLD = nominal lower limit of detection based on a 4.66\sigma counting error for background sample.

Mean and range are based on detectable measurements only (i.e., >LLD) Fraction of detectable measurements at specified locations is indicated in parentheses (F).

d Locations are specified by station code (Table 4.1) and distance (miles) and direction relative to reactor site..

e Non-routine results are those which exceed ten times the control station value.

Table 4.5 Radiological Environmental Monitoring Prograrm Summary Name of Facility Davis-Besse Nuclear Power Station Docket No. 50-346 Location of Facility Ottawa, Ohio Reporting Period January-December, 2007

( County, State )

I Indicator Location with Highest Control Number Sample Type and Locations Annual Mean Locations Non-Type Number of LLDb Mean (F)c Mean (F)c Mean (F)c Routine (Units) Analysesa Rangec Locationd Rangec Rangec Resultse' Airborne GB 520 0.005 0.026 (312/312) T-9, Oak Harbor 0.027 (52/52) 0.026 (208/208) 0 Particulates (0.009-0.050) 6.8 mi. SW (0.013-0.044) (0.004-0.049) 3 (pCi/m )

Sr-89 0.0013 < LLD < LLD 0 Sr-90 0.0009 < LLD < LLD 0 GS 40 Be-7 0.015 0.085 (24/24) T-8, Farm 0.089(4/4) 0.086 (16/16) 0 (0.052-0.127) 2.7 mi. WSW (0.057-0.127) (0.053-0.119)

K-40 0.034 < LLD < LLD 0 Nb-95 0.0012 < LLD < LLD . 0 Zr-95 0.0022 < LLD < LLD 0 Ru-103 0.0010 < LLD < LLD 0 Ru-106 0,0087 < LLD < LLD 0 Cs-134 0.0010 < LLD .- < LLD 0 Cs-137 0.0009 < LLD < LLD 0 Ce-141 0.0019 < LLD < LLD 0 Ce-144 0.0054 < LLD < LLD 0 Airborne Iodine 1-131 520 0.07 < LLD < LLD 0 3

(pCi/m )

TLD (Quarterly) Gamma 350 1.0 15.7 (306/306) T-8, Farm 23.3(4/4) 16.6 (44/44) 0 (mR/91 days) (6.9-26.1) 2.7 mi. WSW .(19.2-26.1) (10.5-22.2)

TLD (Quarterly) Gamma 4 1.0 7.6 (4/4) None 0 (mR/91 days) (7.2-7.9)

(Shield)

TLD (Annual) Gamma 86 1.0 59.3 (75/75) T-8, Farm 89.9 (1/1) 64.1 (11/11) 0 (mR/365 days) (36.5-89.9) 2.7 mi. WSW (46.6-81.9)

TLD (Annual) Gamma 1.0 27.1 (1/1) None 0 (mR/365 days)

(Shield)

Table 4.5 Radiological Environmental Monitoring Program Summary Name of Facility Davis-Besse Nuclear Power Station Docket No. 50-346 Location of Facility Ottawa. Ohio Reporting Period January-December, 2007

( County, State )

Indicator Location with Highest Control Number Sample Type and Locations Annual Mean Locations Non-Type Number of LLDb Mean (F)c Mean (F)c Mean (F)c Routine (Units) Analyseso Rangec Locationd Rangec Rangec Results' Milk (pCi/L) 1-131 12 0.4 none < LLD 0 Sr-89 12 1.0 none < LLD 0 Sr-90. 12 0.7 none T-24, Sandusky 0.8 (10/12) 0.8 (10/12) 0 21.0 mi. SE (0.7-1.0) (0.7-1.0)

GS 12 K-40 100 none T-24, Sandusky 1375 (12/12) 1375 (12112) 0 21.0 mi. SE (1314-1461) (1314-1461)

Cs-1 34 4.2 Cs-1 37 4.5 none. < LLD 0 Ba-La-140 5.5 none < LLD 0 (g/L) Ca 12 0.50 none T-24, Sandusky 1.32 (12/12) 1.32 (12/12) 0 21.0 mi. SE (1.04-1.62) (1.04-1.62)

(g/L) K (stable) 12 none T-24, Sandusky 1.59 (12/12) 1.59 (12/12) 0 21.0 mi. SE (1.52-1.69) (1.52-1.69)

(pCi/g) . Sr-90/Ca 12 none T-24, Sandusky 0.65 (10/12) 0.65 (10/12) 0 21.0 mi. SE (0.49-0.87) (0.49-0.87)

(pCi/g) Cs-1 37/K 12 none "-< LLD 0 Ground Water GB (TR)-- 7 -1.9 3,2 (2/4) - - T-27, Crane Creek 3.6 (1/3) 3.6 (1/3)

(pCi/L) (3.0-3.3) 5.3 mi. WNW H-3 7 330 < LLD < LLD 0 Sr-89 7 1.4 < LLD < LLD 0 Sr-90 7 0.6 < LLD < LLD 0 GS Mn-54 15 < LLD < LLD 0 Fe-59 30 < LLD -< LLD 0 Co-58 15 < LLD < LLD 0 Co-60 15 < LLD < LLD 0 Zn-65 30 < LLD < LLD 0 Zr-95 15 < LLD -< LLD 0 Cs-134 10 < LLD < LLD 0 Cs-137 10 < LLD. < LLD 0 Ba-La-140 15 < LLD - < LLD 0

Table 4.5 Radiological Environmental Monitoring Program Summary Name of Facility Davis-Besse Nuclear Power Station Docket No. 50-346 Location of Facility Ottawa, Ohio Reporting Period January-December, 2007 County, State Indicator Location with Highest Control Number Sample Type and Locations Annual Mean . Locations Non-Type Number of LLDb Mean (F)c Mean (F)c Mean (F)c Routine (Units) Analyses' Rangec Location d Rangec Rangec Results8 Wild Meat GS 2 (pCi/g wet) K-40 0.10 2.35(1/1) T-31, On-site 2.35(1/1) 2.25(1/1) 0 Roving location Nb-95 0.012 < LLD < LLD 0 Zr-95 0.015 < LLD < LLD 0 Ru-103 0.026 < LLD < LLD 0 Ru-106 0.062 < LLD - . - < LLD 0 Cs-1 34 0.008 < LLD < LLD 0 Cs-137 0.010 < LLD. < LLD 0 Ce-141 0.034 < LLD < LLD 0 Ce-144 0.079 < LLD < LLD 0 Fruits and Sr-89 3 0.004 < LLD < LLD 0 Vegetables Sr-90 3 0.002 0.002 (1/2) T-25, Farm. 0.002 (1/2) < LLD

  • 0 (pCi/g wet) 1.6 mi. S 1-131 3 0.057 < LLD < LLD 0 GS 3 K-40 0.50 1.30 (2/2) T-8, Farm 1.38(1/1) 1.24(1/1) 0 (1.22-1.38) 2.7 mi. WSW Nb-95 0.010 < LLD < LLD 0 Zr-95 0.012 < LLD -, < LLD 0 Cs-1 34 0.009 < LLD < LLD 0 Cs-137 0.008 < LLD - < LLD 0 Ce-141 0.022 < LLD < LL.D 0 Ce-144 0.067 < LLD < LLD . 0 Broad Leaf Srr89 10 0.003 < LLD - < LLD 0 Vegetation Sr-90 10 0.002 0.006 (2/6) T-19, Farm 0.006 (2/4) < LLD 0 (pCi/g wet) (0.004-0.008) 0.68 mi. W (0.004-0.008) 1-131 10 0.028 < LLD < LLD 0 GS 10 K-40 0.50 2.16 (6/6) T-19, Farm 2.22 (4/4) 1.79 (4/4) 0 (1.67-2.71) 0.68 mi. W (1.90-2.71) (1.44-2.43)

Nb-95 0.011 < LLD < LLD 0 Zr-95 0.027 < LLD < LLD 0 Cs-134 0.013 < LLD < LLD 0 Cs-137 0.013 < LLD < LLD 0 Ce-141 0.031 < LLD < LLD 0 Ce-144 0.091 < LLD < LLD 0

Table 4.5 Radiological Environmental Monitoring Program Summary Name of Facility Davis-Besse Nuclear Power Station Docket No. 50-346 Location of Facility Ottawa, Ohio Reporting Period January-December, 2007 County, State)

Indicator Location with Highest Control Number Sample Type and Locations Annual Mean Locations Non-Type Number of LLDb Mean (F)c Mean (F)' Mean (F)c Routine (Units) Analyses" Rangec Locationd Rangec Rangec Resultse Animal I GS 3 Wildlife Feed Be-7 0.10 0.72 (2/2) T-31, On-site 1.13(1/1) 0.41 (1/1) 0 (pCi/g wet) (0.30-1.13) Roving location K-40 0.10 4.10 (2/2) T-31, On-site 4.14(1/1) 2.90 (1/1) 0 (4.05-4.14) Roving location Nb-95 0.015 < LLD < LLD 0 Zr-95 0.020 < LLD < LLD 0 Ru-103 0.014 < LLD < LLD 0 Ru-106 0.13 < LLD < LLD 0 Cs-134 0.011 < LLD < LLD 0 Cs-137 0.014 < LLD < LLD 0 Ce-141 0.028 < LLD < LLD 0 Ce-144 0.074 < LLD < LLD 0 Soil GS 10 (pCi/g dry) Be-7 0.68 < LLD T-9, Oak Harbor 1.09(1/1) 1.09(1/4) 0 6.8 mi. SW K-40 0.10 11.37 (6/6) T-8, Farm 23.36(1/1) 19.01 (4/4) 0 (4.88-23.36) 2.7 mi. WSW (17.29-20.42)

Nb-95 0.15 < LLD < LLD 0 Zr-95 0.11 < LLD < LLD 0 Ru-103 0.081 < LLD < LLD 0 Ru-106 0.37 < LLD -< LLD 0 Cs-134 0.053 < LLD < LLD 0 Cs-1 37 0.023 0.12 (3/6) T-9, Oak Harbor 0.26 (1/1) 0.19(4/4)

(0.055-0.21) 6.8 mi. SW (0,10-0.26) -0 Ce-141 0.21 < LLD < LLD 0 Ce-144 0.26 < LLD < LLD 0