ML20142A394

From kanterella
Jump to navigation Jump to search
Environmental, Inc. Midwest Laboratory, Monthly Progress Report for January Through December 2019
ML20142A394
Person / Time
Site: Davis Besse 
(NPF-003)
Issue date: 02/12/2020
From:
ATI Environmental Midwest Lab, Environmental
To:
Office of Nuclear Reactor Regulation
Shared Package
ML20142A392 List:
References
PROJECT8003, L-20-093
Download: ML20142A394 (60)


Text

i* ATI 1d tmLigai

./00 Landwehr Road* Northbrook, IL 60062-2310 ph (847) 564-0700

  • fax (847) 564-4517 MONTHLY PROGRESS REPORT RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM Reviewed and Approved DAVIS-BESSE NUCLEAR POWER STATION OAK HARBOR, OHIO Reporting Period: January-December, 2019 A. Banavali, PhD.

Laboratory Manager Prepared and Submitted by ENVIRONMENTAL, INC,

MIDWEST LABORATORY Project Number: 8003 Date Distribution: K. Filar, Davis-Besse (2 copies and Original Raw Data)

P. Hintz, Ohio Department of Health

TABLE OF CONTENTS Section Page List of Tables............................................................................................................... iii

1.0 INTRODUCTION

.......................................................................................................... V 2.0 LISTING OF MISSED SAMPLES................................................................................. vi 3.0 DATA TABULATIONS................................................................................................. vii Appendices A

lnterlaboratory Comparison Program Results........................................................... A-1 B

Data Reporting Conventions..................................................................................... B-1 C

Supplemental Analyses............................................................................................ C-1 ii

LIST OF TABLES No.

Title Page 1

2 3

4 5

6 7

8 9

10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 Airborne particulates and iodine, analysis for gross beta and iodine-131 Location T-1 Location T-2.................................................................................................................

Location T-3.................................................................................

Location T-4 Location T-7 Location T-9..............................

Location T-11 Location T-12 Location T-27 Airborne particulate data, gross beta analysis, monthly averages, 1-1 2-1 3-1 4-1 5-1 6-1 7-1 8-1 9-1 minima and maxima.......................................................................................................... 10-1 Airborne particulate samples, quarterly composites, analyses for strontium-89 and strontium-90............................................................................. 11-1 Area monitors (TLD), quarterly............................................................................................... 12-1 Milk, analyses for strontium-89, strontium-90, iodine-131, gamma-emitting isotopes, calcium, and stable potassium....

13-1 Ground water, analyses for gross beta, tritium, strontium-89 and strontium-90 and gamma-emitting isotopes.......................... 14-1 Domestic meat, analysis for gamma-emitting isotopes................................................................

15-1 Wild meat, analysis for gamma-emitting isotopes...........................................................

16-1 Green leafy vegetables, analyses for strontium-89, strontium-90, iodine-131 and gamma-emitting isotopes.....................

17-1

Fruit, analyses for strontium-89, strontium-90, iodine-131 and gamma-emitting isotopes........................

18-1 Animal-wildlife feed, analysis for gamma-emitting isotopes..........................................................

19-1 Soil, analysis for gamma-emitting isotopes............................................................................... 20-1 Treated surface water, analysis for gross beta..........................................................................

21-1 Treated surface water, analyses for tritium, strontium-89, strontium-90 and gamma-emitting isotopes...............................................

22-1 Untreated surface water, analyses for gross beta, tritium and gamma-emitting isotopes....................................................................

23-1 Untreated surface water, analyses for strontium-89 and strontium-90...........................................

24-1 Fish, analyses for gross beta and gamma-emitting isotopes........................................................

25-1 Shoreline sediment, analysis for gamma-emitting isotopes..........................................................

26-1 iii

LIST OF TABLES (continued)

The following tables are in the Appendices:

Appendix A Attachment A: Acceptance criteria for spiked samples.............................................................. A-2 A-1 lnterlaboratory Comparison Program Results......................................................................... A1-1 A-2 lnterlaboratory Comparison Program Results, thermoluminescent dosimeters (TLDs)..................................................................................................... A2-1 A-3 Results of the analyses on in-house spiked samples.............................................................. A3-1 A-4 Results of the analyses on in-house "blank" samples.............................................................. A4-1 A-5 Results of the analyses on in-house "duplicate" samples........................................................ A5-1 A-6 Mixed Analyte Performance Evaluation Program (MAPEP)..................................................... A6-1 A-7 Environmental Resources Associates, Crosscheck Program Results (EML study replacement).............................................................................................................. A 7-1 Appendix B B-1 Data Reporting Conventions...................................................................................................... B-2 iv

1.0 INTRODUCTION

The following constitutes the current 2019 Monthly Progress Report for the Radiological Environmental Monitoring Program conducted at the Davis-Besse Nuclear Power Station in Oak Harbor, Ohio. Results of completed analyses are presented in the attached tables.

All activities, except gross alpha and gross beta, are decay corrected to the time of collection.

All samples were collected within the scheduled period unless noted otherwise in the Listing of Missed Samples.

V

Sample Type Location AP/Al T-12 AP/Al T-12 AP T-07 VE T-37 2.0 LISTING OF MISSED SAMPLES Expected Collection Date 02-05-19 08-27-19 10-22-19 10-30-19 vi Reason Pump lost power due to severe winter conditions.

Samples not collected due to multiple pump failures.

Sample discarded per station request..

No vegetation available.

3.0 DATA TABULATIONS vii

Table 1. Airborne particulates and charcoal canisters, analyses for gross beta and iodine-1318 Location: T-1 Units: pCi/m3 Collection: Continuous, weekly exchange.

Date Collected Required LLD 01-08-19 01-15-19 01-22-19 01-29-19 02-05-19 02-12-19 02-19-19 02-26-19 03-05-19 03-12-19 03-19-19 03-26-19 04-02-19 Volume (mW) 218 275 303 268 126 122 252 258 315 325 285 281 294 1st Quarter Mean +/- s.d.

04-09-19 277 04-16-19 287 04-23-19 278 04-30-19 282 05-07-19 293 05-14-19 307 05-21-19 324 05-28-19 314 06-04-19 312 06-11-19 318 06-18-19 301 06-25-19 305 07-02-19 308 2nd Quarter Mean +/- s.d.

Gross Beta 0.010 0.030 +/- 0.005 0.022 +/- 0.004 0.018 +/- 0.003 0.028 +/- 0.004 0.073 +/- 0.009 b 0.043 +/- 0.008 b 0.028 +/- 0.004 0.038 +/- 0.005 0.028 +/- 0.004 0.035 +/- 0.004 0.028 +/- 0.004 0.017 +/- 0.004 0.012 +/- 0.003 0.031 +/- 0.015 0.020 +/- 0.004 0.012 +/- 0.003 0.010 +/- 0.003 0.015 +/- 0.004 0.013 +/- 0.003 0.008 +/- 0.003 0.015 +/- 0.003 0.014 +/- 0.003 0.012 +/- 0.003 0.014 +/- 0.003 0.007 +/- 0.003 0.011 +/- 0.003 0.021 +/- 0.003 0.013 +/- 0.004 Date Collected Required LLD 07-09-19 07-16-19 07-23-19 07-30-19 08-06-19 08-13-19 08-20-19 08-27-19 09-03-19 09-10-19 09-17-19 09-24-19 10-01-19 Volume (mW) 302 289 267 205 284 316 290 389 351 280 397 333 288 3rd Quarter Mean +/- s.d.

10-08-19 283 10-15-19 324 10-22-19 304 10-29-19 306 11-05-19 305 11-12-19 304 11-19-19 301 11-26-19 291 12-03-19 289 12-10-19 287 12-17-19 292 12-23-19 251 12-31-19 321 4th Quarter Mean+/- s.d.

Cumulative Average a lodine-131 concentrations are < 0.07 pCi/m3 unless noted otherwise.

b Pump lost power due to severe weather conditions.

1-1 Gross Beta 0.010 0.019 +/- 0.003 0.017 +/- 0.003 0.013 +/- 0.004 0.034 +/- 0.005 0.027 +/- 0.004 0.032 +/- 0.004 0.032 +/- 0.004 0.017 +/- 0.003 0.027 +/- 0.003 0.028 +/- 0.004 0.045 +/- 0.004 0.053 +/- 0.004 0.031 +/- 0.004 0.029 +/- 0.011 0.018 +/- 0.004 0.021 +/- 0.003 0.026 +/- 0.004 0.018 +/- 0.003 0.015 +/- 0.003 0.020 +/- 0.004 0.026 +/- 0.004 0.026 +/- 0.004 0.014 +/- 0.003 0.024 +/- 0.004 0.033 +/- 0.004 0.035 +/- 0.005 0.030 +/- 0.004 0.024 +/- 0.007 0.024

Table 2. Airborne particulates and charcoal canisters, analyses for gross beta and iodine-1318 Location: T-2 Units: pCi/m3 Collection: Continuous, weekly exchange.

Date Collected Required LLD 01-08-19 01-15-19 01-22-19 01-29-19 02-05-19 02-12-19 02-19-19 02-26-19 03-05-19 03-12-19 03-19-19 03-26-19 04-02-19 Volume (mV) 248 302 268 279 296 250 278 304 299 295 302 265 357 1st Quarter Mean +/- s.d.

04-09-19 345 04-16-19 296 04-23-19 306 04-30-19 308 05-07-19 286 05-14-19 272 05-21-19 262 05-28-19 284 06-04-19 283 06-11-19 292 06-18-19 287 06-25-19 298 07-02-19 292 2nd Quarter Mean +/- s.d.

Gross Beta 0.010 0.026 +/- 0.004 0.018 +/- 0.004 0.020 +/- 0.004 b

0.027 +/- 0.004 0.032 +/- 0.004 0.012 +/- 0.004 0.025 +/- 0.004 0.028 +/- 0.004 0.026 +/- 0.004 0.029 +/- 0.004 0.023 +/- 0.004 0.015 +/- 0.004 0.013 +/- 0.003 0.023 +/- 0.006 0.016 +/- 0.003 0.011 +/- 0.003 0.009 +/- 0.003 0.012 +/- 0.003 0.011 +/- 0.003 0.008 +/- 0.003 0.012 +/- 0.004 0.010 +/- 0.003 0.011 +/- 0.003 0.014 +/- 0.003 0.011 +/- 0.003 0.010 +/- 0.003 0.012 +/- 0.003 0.011 +/- 0.002 Date Volume Collected (mW) 07-09-19 219 07-16-19 285 07-23-19 274 07-30-19 288 08-06-19 157 08-13-19 266 08-20-19 292 08-27-19 314 09-03-19 419 09-10-19 262 09-17-19 297 09-24-19 314 10-01-19 317 3rd Quarter Mean +/- s.d.

10-08-19 299 10-15-19 337 10-22-19 321 10-29-19 329 11-05-19 330 11-12-19 318 11-19-19 321 11-26-19 313 12-03-19 309 12-10-19 311 12-17-19 312 12-23-19 267 12-31-19 350 4th Quarter Mean +/- s.d.

Cumulative Average a lodine-131 concentrations are < 0.07 pCi/m3 unless noted otherwise.

b Pump found not working during the collection.

c Lower volume due to the pump malfunction.

2-1 Gross Beta 0.010 0.008 +/- 0.004 0.011 +/- 0.003 0.016 +/- 0.004 0.029 +/- 0.004 0.036 +/- 0.007 0.027 +/- 0.004 0.032 +/- 0.004 0.016 +/- 0.003 0.024 +/- 0.003 0.013 +/- 0.004 0.026 +/- 0.004 0.032 +/- 0.004 0.023 +/- 0.004 0.023 +/- 0.009 0.016 +/- 0.003 0.019 +/- 0.003 0.020 +/- 0.003 0.014 +/- 0.003 0.012 +/- 0.003 0.020 +/- 0.003 0.023 +/- 0.003 0.028 +/- 0.004 0.016 +/- 0.003 0.020 +/- 0.003 0.025 +/- 0.004 0.032 +/- 0.004 0.026 +/- 0.004 0.021 +/- 0.006 0.019 C

Table 3. Airborne particulates and charcoal canisters, analyses for gross beta and iodine-1318 Location: T-3 Units: pCi/m3 Collection: Continuous, weekly exchange.

Date Collected Required LLD 01-08-19 01-15-19 01-22-19 01-29-19 02-05-19 02-12-19 02-19-19 02-26-19 03-05-19 03-12-19 03-19-19 03-26-19 04-02-19 Volume (mj) 250 224 306 309 338 270 246 264 271 356 263 284 285 1st Quarter Mean +/- s.d.

04-09-19 297 04-16-19 292 04-23-19 298 04-30-19 242 05-07-19 299 05-14-19 284 05-21-19 302 05-28-19 453 06-04-19 450 06-11-19 302 06-18-19 293 06-25-19 286 07-02-19 257 2nd Quarter Mean +/- s.d.

Gross Beta 0.010 0.024 +/- 0.004 0.017 +/- 0.004 0.019 +/- 0.003 0.024 +/- 0.004 0.026 +/- 0.003 0.017 +/- 0.004 0.025 +/- 0.004 0.031 +/- 0.004 0.020 +/- 0.004 0.033 +/- 0.004 0.024 +/- 0.004 0.015 +/- 0.003 0.013 +/- 0.004 0.022 +/- 0.006 0.016 +/- 0.003 0.011 +/- 0.003 0.008 +/- 0.003 0.016 +/- 0.004 0.010 +/- 0.003 0.009 +/- 0.003 0.018 +/- 0.004 0.016 +/- 0.002 0.018 +/- 0.003 0.022 +/- 0.004 0.015 +/- 0.003 0.018 +/- 0.003 0.030 +/- 0.004 0.016 +/- 0.006 Date Volume Collected (mj) 07-09-19 259 07-16-19 245 07-23-19 316 07-30-19 317 08-06-19 281 08-13-19 285 08-20-19 289 08-27-19 287 09-03-19 277 09-10-19 276 09-17-19 277 09-24-19 274 10-01-19 269 3rd Quarter Mean+/- s.d.

10-08-19 269 10-15-19 265 10-22-19 249 10-29-19 253 11-05-19 253 11-12-19 255 11-19-19 251 11-26-19 276 12-03-19 270 12-10-19 268 12-17-19 272 12-23-19 237 12-31-19 310 4th Quarter Mean +/- s.d.

Cumulative Average a lodine-131 concentrations are< 0.07 pCi/m3 unless noted otherwise.

3-1 Gross Beta 0.010 0.025 +/- 0.004 0.024 +/- 0.004 0.014 +/- 0.003 0.026 +/- 0.004 0.020 +/- 0.004 0.018 +/- 0.004 0.017 +/- 0.004 0.011 +/- 0.003 0.017 +/- 0.004 0.015 +/- 0.004 0.028 +/- 0.004 0.026 +/- 0.004 0.020 +/- 0.004 0.020 +/- 0.005 0.014 +/- 0.004 0.016 +/- 0.004 0.014 +/- 0.004 0.018 +/- 0.004 0.011 +/- 0.004 0.015 +/- 0.004 0.022 +/- 0.004 0.030 +/- 0.004 0.015 +/- 0.004 0.022 +/- 0.004 0.027 +/- 0.004 0.037 +/- 0.005 0.026 +/- 0.004 0.021 +/- 0.008 0.020

Table 4. Airborne particulates and charcoal canisters, analyses for gross beta and iodine-1318 Location: T-4 Units: pCi/m3 Collection: Continuous, weekly exchange.

Date Collected Required LLD 01-08-19 01-15-19 01-22-19 01-29-19 02-05-19 02-12-19 02-19-19 02-26-19 03-05-19 03-12-19 03-19-19 03-26-19 04-02-19 Volume (mU) 252 339 223 245 300 288 319 143 273 305 298 262 287 1st Quarter Mean+/- s.d.

04-09-19 273 04-16-19 282 04-23-19 259 04-30-19 298 05-07-19 265 05-14-19 263 05-21-19 263 05-28-19 276 06-04-19 276 06-11-19 289 06-18-19 287 06-25-19 286 07-02-19 299 2nd Quarter Mean +/- s.d.

Gross Beta 0.010 0.034 +/- 0.005 0.015 +/- 0.003 0.021 +/- 0.005 0.032 +/- 0.005 0.029 +/- 0.004 0.017 +/- 0.003 ° 0.035 +/- 0.004 0.053 +/- 0.008 0.031 +/- 0.005 0.032 +/- 0.004 0.030 +/- 0.004 0.023 +/- 0.004 0.016 +/- 0.004 0.028 +/- 0.010 0.024 +/- 0.004 0.015 +/- 0.003 0.012 +/- 0.003 0.018 +/- 0.004 0.017 +/- 0.004 0.013 +/- 0.003 0.025 +/- 0.004 0.016 +/- 0.003 0.021 +/- 0.004 0.024 +/- 0.004 0.018 +/- 0.004 0.018 +/- 0.003 0.026 +/- 0.004 0.019 +/- 0.005 Date Volume Collected (mV) 07-09-19 298 07-16-19 302 07-23-19 300 07-30-19 303 08-06-19 295 08-13-19 323 08-20-19 363 08-27-19 294 09-03-19 271 09-10-19 267 09-17-19 254 09-24-19 269 10-01-19 255 3rd Quarter Mean +/- s.d.

10-08-19 353 10-15-19 308 10-22-19 289 10-29-19 300 11-05-19 295 11-12-19 291 11-19-19 279 11-26-19 268 12-03-19 267 12-10-19 259 12-17-19 262 12-23-19 251 12-31-19 324 4th Quarter Mean +/- s.d.

Cumulative Average a lodine-131 concentrations are< 0.07 pCi/m3 unless noted otherwise.

b Flow meter failure. Volume based on pump run time.

c Pump lost power due to severe weather conditions.

4-1 Gross Beta 0.010 0.023 +/- 0.004 0.019 +/- 0.003 0.015 +/- 0.003 0.030 +/- 0.004 0.027 +/- 0.004 0.016 +/- 0.003 0.017 +/- 0.003 0.013 +/- 0.003 0.013 +/- 0.003 0.012 +/- 0.004 0.025 +/- 0.004 0.026 +/- 0.004 0.017 +/- 0.004 0.019 +/- 0.006 0.010 +/- 0.003 0.014 +/- 0.003 0.013 +/- 0.003 0.012 +/- 0.003 0.010 +/- 0.003 0.013 +/- 0.003 0.016 +/- 0.003 0.019 +/- 0.004 0.009 +/- 0.003 0.018 +/- 0.004 0.018 +/- 0.004 0.046 +/- 0.005 0.038 +/- 0.004 0.018 +/- 0.011 0.021 C

Table 5. Airborne particulates and charcoal canisters, analyses for gross beta and iodine-131 a.

Location: T-7 Units: pCi/m3 Collection: Continuous, weekly exchange.

Date Collected Required LLD 01-08-19 01-15-19 01-22-19 01-29-19 02-05-19 02-12-19 02-19-19 02-26-19 03-05-19 03-12-19 03-19-19 03-26-19 04-02-19 Volume (m3)

Gross Beta 0.010 218 0.026 +/- 0.005 341 0.020 +/- 0.003 307 0.024 +/- 0.004 232 0.027 +/- 0.005 212 0.040 +/- 0.005 b

271 0.018 +/- 0.004 319 0.023 +/- 0.003 272 0.030 +/- 0.004 280 0.022 +/- 0.004 217 0.034 +/- 0.005 268 0.030 +/- 0.004 266 0.017 +/- 0.004 267 0.014 +/- 0.004 Date Volume Collected (m3) 07-09-19 251 07-16-19 342 07-23-19 351 07-30-19 271 08-06-19 306 08-13-19 276 08-20-19 260 08-27-19 240 09-03-19 290 09-10-19 292 09-17-19 353 09-24-19 302 10-01-19 295 1st Quarter Mean+/- s.d.

0.025 +/- 0.007 3rd Quarter Mean +/- s.d.

04-09-19 262 0.023 +/- 0.004 10-08-19 314 04-16-19 256 0.012 +/- 0.003 10-15-19 285 04-23-19 250 0.005 +/- 0.003 10-22-19 04-30-19 285 0.015 +/- 0.004 10-29-19 321 05-07-19 282 0.014 +/- 0.003 11-05-19 321 05-14-19 272 0.009 +/- 0.003 11-12-19 279 05-21-19 291 0.013 +/- 0.003 11-19-19 259 05-28-19 272 0.013 +/- 0.003 11-26-19 262 12-03-19 258 06-04-19 263 0.015 +/- 0.003 06-11-19 260 0.026 +/- 0.004 12-10-19 259 06-18-19 273 0.016 +/- 0.004 12-17-19 271 06-25-19 279 0.014 +/- 0.003 12-23-19 248 07-02-19 280 0.025 +/- 0.004 12-31-19 305 2nd Quarter Mean +/- s.d.

0.015 +/- 0.006 4th Quarter Mean +/- s.d.

Cumulative Average a lodine-131 concentrations are< 0.07 pCi/m3 unless noted otherwise.

b Lower volume possibly due to severe weather conditions.

c No sample collected. See table 2.0, Listing Of Missed Samples.

5-1 Gross Beta 0.010 0.026 +/- 0.004 0.027 +/- 0.004 0.021 +/- 0.003 0.038 +/- 0.004 0.033 +/- 0.004 0.032 +/- 0.004 0.030 +/- 0.004 0.025 +/- 0.004 0.033 +/- 0.004 0.030 +/- 0.004 0.048 +/- 0.004 0.055 +/- 0.005 0.040 +/- 0.004 0.034 +/- 0.010 0.034 +/- 0.004 0.044 +/- 0.005 NSC 0.024 +/- 0.004 0.018 +/- 0.003 0.024 +/- 0.004 0.039 +/- 0.005 0.053 +/- 0.005 0.020 +/- 0.004 0.034 +/- 0.005 0.046 +/- 0.005 0.044 +/- 0.005 0.040 +/- 0.004 0.035 +/- 0.011 0.027

Table 6. Airborne particulates and charcoal canisters, analyses for gross beta and iodine-131a.

Location: T-9 (C)

Units: pCi/m3 Collection: Continuous, weekly exchange.

Date Collected Required LLD 01-08-19 01-15-19 01-22-19 01-29-19 02-05-19 02-12-19 02-19-19 02-26-19 03-05-19 03-12-19 03-19-19 03-26-19 04-02-19 Volume (mV) 224 336 318 281 261 302 277 286 312 304 274 284 312 1st Quarter Mean +/- s.d.

04-09-19 325 04-16-19 231 04-23-19 256 04-30-19 349 05-07-19 284 05-14-19 446 05-21-19 223 05-28-19 372 06-04-19 281 06-11-19 304 06-18-19 314 06-25-19 272 07-02-19 311 2nd Quarter Mean +/- s.d.

Gross Beta 0.010 0.029 +/- 0.005 0.019 +/- 0.003 0.020 +/- 0.003 0.024 +/- 0.004 0.034 +/- 0.004 0.015 +/- 0.003 0.026 +/- 0.004 0.035 +/- 0.004 0.021 +/- 0.004 0.031 +/- 0.004 0.029 +/- 0.004 0.019 +/- 0.004 0.022 +/- 0.004 0.025 +/- 0.006 0.023 +/- 0.004 0.014 +/- 0.004 0.013 +/- 0.003 0.016 +/- 0.003 0.016 +/- 0.003 0.009 +/- 0.002 0.024 +/- 0.005 0.013 +/- 0.003 0.013 +/- 0.003 0.017 +/- 0.003 0.012 +/- 0.003 0.016 +/- 0.003 0.024 +/- 0.004 0.016 +/- 0.005 Date Volume Collected (mW) 07-09-19 303 07-16-19 308 07-23-19 305 07-30-19 307 08-06-19 286 08-13-19 08-20-19 98 08-27-19 223 09-03-19 310 09-10-19 310 09-17-19 329 09-24-19 307 10-01-19 286 3rd Quarter Mean +/- s.d.

10-08-19 277 10-15-19 298 10-22-19 287 10-29-19 312 11-05-19 300 11-12-19 296 11-19-19 294 11-26-19 280 12-03-19 301 12-10-19 292 12-17-19 292 12-23-19 244 12-31-19 325 4th Quarter Mean +/- s.d.

Cumulative Average a lodine-131 concentrations are < 0.07 pCi/m3 unless noted otherwise.

b Very low volume due to the pump malfunction; sample discarded per station request.

c Low volume due to the pump malfunction.

6-1 Gross Beta 0.010 0.013 +/- 0.003 0.015 +/- 0.003 0.010 +/- 0.003 0.022 +/- 0.003 0.019 +/- 0.004 NDb 0.028 +/- 0.009 C

0.022 +/- 0.005 0.026 +/- 0.004 0.019 +/- 0.004 0.036 +/- 0.004 0.040 +/- 0.004 0.026 +/- 0.004 0.023 +/- 0.009 0.022 +/- 0.004 0.029 +/- 0.004 0.027 +/- 0.004 0.024 +/- 0.004 0.019 +/- 0.004 0.023 +/- 0.004 0.034 +/- 0.004 0.034 +/- 0.004 0.017 +/- 0.004 0.029 +/- 0.004 0.042 +/- 0.005 0.043 +/- 0.005 0.036 +/- 0.004 0.029 +/- 0.008 0.023

Table 7. Airborne particulates and charcoal canisters, analyses for gross beta and iodine-1318 Location: T-11 (C)

Units: pCi/m3 Collection: Continuous, weekly exchange.

Date Collected Required LLD 01-08-19 01-15-19 01-22-19 01-29-19 02-05-19 02-12-19 02-19-19 02-26-19 03-05-19 03-12-19 03-19-19 03-26-19 04-02-19 Volume (m.j) 260 353 248 262 43 381 262 278 321 291 313 302 287 1st Quarter Mean +/- s.d.

04-09-19 319 04-16-19 197 04-23-19 310 04-30-19 205 05-07-19 337 05-14-19 191 05-21-19 353 05-28-19 314 06-04-19 270 06-11-19 244 06-18-19 346 06-25-19 329 07-02-19 230 2nd Quarter Mean +/- s.d.

Gross Beta 0.010 0.037 +/- 0.005 0.023 +/- 0.003 0.021 +/- 0.004 0.031 +/- 0.004 0.050 +/- 0.019 ° 0.012 +/- 0.003 0.019 +/- 0.004 0.027 +/- 0.004 0.021 +/- 0.004 0.028 +/- 0.004 0.022 +/- 0.003 0.014 +/- 0.003 0.016 +/- 0.004 0.025 +/- 0.010 0.024 +/- 0.004 0.010 +/- 0.004 C

0.011 +/- 0.003 0.017 +/- 0.005 0.013 +/- 0.003 0.015 +/- 0.005 0.014 +/- 0.003 0.012 +/- 0.003 0.017 +/- 0.004 0.021 +/- 0.004 0.012 +/- 0.003 0.012 +/- 0.003 0.023 +/- 0.004 0.015 +/- 0.005 Date Volume Collected (m.j) 07-09-19 288 07-16-19 303 07-23-19 241 07-30-19 242 08-06-19 279 08-13-19 290 08-20-19 282 08-27-19 263 09-03-19 270 09-10-19 279 09-17-19 265 09-24-19 275 10-01-19 311 3rd Quarter Mean +/- s.d.

10-08-19 309 10-15-19 309 10-22-19 302 10-29-19 302 11-05-19 302 11-12-19 296 11-19-19 290 11-26-19 283 12-03-19 274 12-10-19 274 12-17-19 272 12-23-19 238 12-31-19 306 4th Quarter Mean +/- s.d.

Cumulative Average a lodine-131 concentrations are< 0.07 pCi/m3 unless noted otherwise.

b Low volume due to the power outage. 1-131 result< 0.07 pCi/m3.

c Pump found off.

7-1 Gross Beta 0.010 0.015 +/- 0.003 0.013 +/- 0.003 0.018 +/- 0.004 0.031 +/- 0.005 0.025 +/- 0.004 0.027 +/- 0.004 0.033 +/- 0.004 0.019 +/- 0.004 0.026 +/- 0.004 0.024 +/- 0.004 0.040 +/- 0.005 0.041 +/- 0.005 0.026 +/- 0.004 0.026 +/- 0.009 0.024 +/- 0.004 0.025 +/- 0.004 0.026 +/- 0.004 0.023 +/- 0.004 0.020 +/- 0.004 0.024 +/- 0.004 0.032 +/- 0.004 0.035 +/- 0.004 0.017 +/- 0.004 0.035 +/- 0.005 0.041 +/- 0.005 0.041 +/- 0.005 0.038 +/- 0.004 0.029 +/- 0.008 0.024

Table 8. Airborne particulates and charcoal canisters, analyses for gross beta and iodine-131".

Location: T-12 (C)

Units: pCi/m3 Collection: Continuous, weekly exchange.

Date Collected Required LLD 01-08-19 01-15-19 01-22-19 01-29-19 02-05-19 02-12-19 02-19-19 02-26-19 03-05-19 03-12-19 03-19-19 03-26-19 04-02-19 Volume (m")

264 295 304 245 124 259 308 280 296 283 305 273 Gross Beta 0.010 0.023 +/- 0.004 0.013 +/- 0.003 0.017 +/- 0.003 0.028 +/- 0.005 ° NSC 0.017 +/- 0.007 a 0.037 +/- 0.005 0.033 +/- 0.004 0.027 +/- 0.004 0.030 +/- 0.004 0.034 +/- 0.004 0.020 +/- 0.003 0.017 +/- 0.004 Date Volume Collected (m")

07-09-19 324 07-16-19 281 07-23-19 277 07-30-19 273 08-06-19 301 08-13-19 363 08-20-19 262 08-27-19 09-03-19 353 09-10-19 330 09-17-19 292 09-24-19 351 10-01-19 342 1st Quarter Mean +/- s.d.

0.025 +/- 0.008 3rd Quarter Mean +/- s.d.

04-09-19 295 0.023 +/- 0.004 10-08-19 343 04-16-19 304 0.011 +/- 0.003 10-15-19 285 04-23-19 266 0.015 +/- 0.003 10-22-19 293 04-30-19 401 0.015 +/- 0.003 10-29-19 301 05-07-19 274 0.018 +/- 0.004 11-05-19 299 05-14-19 325 0.009 +/- 0.003 11-12-19 302 05-21-19 245 0.012 +/- 0.004 11-19-19 304 05-28-19 351 0.012 +/- 0.003 11-26-19 295 12-03-19 294 06-04-19 286 0.003 +/- 0.003 e 06-11-19 239 0.022 +/- 0.004 12-10-19 294 06-18-19 315 0.014 +/- 0.003 12-17-19 296 06-25-19 320 0.018 +/- 0.003 12-23-19 256 07-02-19 239 0.025 +/- 0.004 12-31-19 338 2nd Quarter Mean +/- s.d.

0.015 +/- 0.006 4th Quarter Mean +/- s.d.

Cumulative Average a lodine-131 concentrations are< 0.07 pCi/m3 unless noted otherwise.

0 Pump found not working during the collection.

c Power failure due to severe weather conditions. Indicated volume 12.1 f.

0 Lower volume due to severe weather conditons.

e Low activity possibly caused by the pomp failure.

' No sample collected. See table 2.0, Listing Of Missed Samples.

8-1 Gross Beta 0.010 0.024 +/- 0.004 0.023 +/- 0.004 0.018 +/- 0.004 0.028 +/- 0.004 0.029 +/- 0.004 0.023 +/- 0.003 0.025 +/- 0.004 NSr 0.027 +/- 0.003 0.022 +/- 0.004 0.037 +/- 0.004 0.041 +/- 0.004 0.025 +/- 0.003 0.027 +/- 0.006 0.016 +/- 0.003 0.024 +/- 0.004 0.029 +/- 0.004 0.022 +/- 0.004 0.020 +/- 0.004 0.024 +/- 0.004 0.032 +/- 0.004 0.033 +/- 0.004 0.016 +/- 0.004 0.028 +/- 0.004 0.037 +/- 0.004 0.049 +/- 0.005 0.046 +/- 0.004 0.029 +/- 0.010 0.024

Table 9. Airborne particulates and charcoal canisters, analyses for gross beta and iodine-131a.

Location: T-27 (C)

Units: pCi/m3 Collection: Continuous, weekly exchange.

Date Collected Required LLD 01-08-19 01-15-19 01-22-19 01-29-19 02-05-19 02-12-19 02-19-19 02-26-19 03-05-19 03-12-19 03-19-19 03-26-19 04-02-19 Volume (mJ) 243 274 265 291 302 284 283 256 279 282 282 284 291 1st Quarter Mean +/- s.d.

04-09-19 276 04-16-19 264 04-23-19 268 04-30-19 282 05-07-19 284 05-14-19 268 05-21-19 225 05-28-19 423 06-04-19 291 06-11-19 230 06-18-19 319 06-25-19 278 07-02-19 274 2nd Quarter Mean +/- s.d.

Gross Beta 0.010 0.033 +/- 0.005 0.027 +/- 0.004 0.028 +/- 0.004 0.037 +/- 0.004 0.038 +/- 0.004 0.019 +/- 0.004 0.034 +/- 0.004 0.045 +/- 0.005 0.031 +/- 0.004 0.035 +/- 0.004 0.033 +/- 0.004 0.022 +/- 0.004 0.018 +/- 0.004 0.031 +/- 0.008 0.027 +/- 0.004 0.017 +/- 0.004 0.016 +/- 0.003 0.016 +/- 0.004 0.013 +/- 0.003 0.012 +/- 0.003 0.024 +/- 0.005 0.014 +/- 0.002 0.012 +/- 0.003 0.020 +/- 0.004 0.018 +/- 0.003 0.016 +/- 0.003 0.031 +/- 0.004 0.018 +/- 0.006 Date Volume Collected (mJ) 07-09-19 301 07-16-19 294 07-23-19 324 07-30-19 283 08-06-19 378 08-13-19 08-20-19 340 08-27-19 371 09-03-19 315 09-10-19 328 09-17-19 339 09-24-19 300 10-01-19 292 3rd Quarter Mean +/- s.d.

10-08-19 290 10-15-19 286 10-22-19 268 10-29-19 272 11-05-19 268 11-12-19 264 11-19-19 257 11-26-19 257 12-03-19 251 12-10-19 284 12-17-19 283 12-23-19 241 12-31-19 325 4th Quarter Mean +/- s.d.

Cumulative Average a lodine-131 concentrations are< 0.07 pCi/m3 unless noted otherwise.

b Very low volume due to the pump failure. Sample discarded per station request.

9-1 Gross Beta 0.010 0.017 +/- 0.003 0.019 +/- 0.004 0.014 +/- 0.003 0.024 +/- 0.004 0.024 +/- 0.003 NSb 0.023 +/- 0.003 0.012 +/- 0.003 0.018 +/- 0.003 0.020 +/- 0.003 0.033 +/- 0.004 0.031 +/- 0.004 0.019 +/- 0.004 0.021 +/- 0.006 0.015 +/- 0.003 0.021 +/- 0.004 0.016 +/- 0.004 0.017 +/- 0.004 0.013 +/- 0.004 0.018 +/- 0.004 0.030 +/- 0.004 0.029 +/- 0.004 0.015 +/- 0.004 0.026 +/- 0.004 0.029 +/- 0.004 0.036 +/- 0.005 0.028 +/- 0.004 0.023 +/- 0.007 0.023

Table 10-1. Airborne particulate data.gross beta analyses, monthly averages, minima and maxima.

January April Location Average Minima Maxima Location Average Minima Maxima T-9 0.023 0.019 0.029 T-9 0.017 0.013 0.023 T-11 0.028 0.021 0.037 T-11 0.016 0.010 0.024 T-12 0.020 0.013 0.028 T-12 0.016 0.011 0.023 T-27 0.031 0.027 0.037 T-27 0.019 0.016 0.027 Controls 0.026 0.013 0.037 Controls 0.017 0.010 0.027 T-1 0.025 0.018 0.030 T-1 0.014 0.010 0.020 T-2 0.023 0.018 0.027 T-2 0.012 0.009 0.016 T-3 0.021 0.017 0.024 T-3 0.013 0.008 0.016 T-4 0.026 0.015 0.034 T-4 0.017 0.012 0.024 T-7 0.024 0.020 0.027 T-7 0.014 0.005 0.023 Indicators 0.024 0.015 0.034 Indicators 0.014 0.005 0.024 February May Location Average Minima Maxima Location Average Minima Maxima T-9 0.028 0.015 0.035 T-9 0.016 0.009 0.024 T-11 0.027 0.012 0.050 T-11 0.014 0.012 0.015 T-12 0.029 0.017 0.037 T-12 0.013 0.009 0.018 T-27 0.034 0.019 0.045 T-27 0.016 0.012 0.024 Controls 0.030 0.012 0.050 Controls 0.015 0.009 0.024 T-1 0.046 0.028 0.073 T-1 0.013 0.008 0.015 T-2 0.024 0.012 0.032 T-2 0.010 0.008 0.012 T-3 0.025 0.017 0.031 T-3 0.013 0.009 0.018 T-4 0.034 0.017 0.053 T-4 0.018 0.013 0.025 T-7 0.028 0.018 0.040 T-7 0.012 0.009 0.014 Indicators 0.031 0.012 0.073 Indicators 0.013 0.008 0.025 March June Location Average Minima Maxima Location Average Minima Maxima T-9 0.024 0.019 0.031 T-9 0.016 0.012 0.024 T-11 0.020 0.014 0.028 T-11 0.017 0.012 0.023 T-12 0.026 0.017 0.034 T-12 0.016 0.003 0.025 T-27 0.028 0.018 0.035 T-27 0.019 0.012 0.031 Controls 0.025 0.014 0.035 Controls 0.017 0.003 0.031 T-1 0.024 0.012 0.035 T-1 0.013 0.007 0.021 T-2 0.021 0.013 0.029 T-2 0.012 0.010 0.014 T-3 0.021 0.013 0.033 T-3 0.021 0.015 0.030 T-4 0.026 0.016 0.032 T-4 0.021 0.018 0.026 T-7 0.023 0.014 0.034 T-7 0.019 0.014 0.026 Indicators 0.023 0.012 0.035 Indicators 0.017 0.007 0.030 Note: Unless otherwise specified, samples collected on the first, second or third day of the month are grouped with data from the previous month.

10- 1

Table 10-1. Airborne particulate data.gross beta analyses, monthly averages, minima and maxima.

July October Location Average Minima Maxima Location Average Minima Maxima T-9 0.015 0.010 0.022 T-9 0.026 0.022 0.029 T-11 0.019 0.013 0.031 T-11 0.025 0.023 0.026 T-12 0.023 0.018 0.028 T-12 0.023 0.016 0.029 T-27 0.019 0.014 0.024 T-27 0.017 0.015 0.021 Controls 0.019 0.010 0.031 Controls 0.023 0.015 0.029 T-1 0.021 0.013 0.034 T-1 0.021 0.018 0.026 T-2 0.016 0.008 0.029 T-2 0.017 0.014 0.020 T-3 0.022 0.014 0.026 T-3 0.016 0.014 0.018 T-4 0.022 0.015 0.030 T-4 0.012 0.010 0.014 T-7 0.028 0.021 0.038 T-7 0.034 0.024 0.044 Indicators 0.022 0.008 0.038 Indicators 0.020 0.010 0.044 August November Location Average Minima Maxima Location Average Minima Maxima T-9 0.024 0.019 0.028 T-9 0.025 0.017 0.034 T-11 0.026 0.019 0.033 T-11 0.026 0.017 0.035 T-12 0.026 0.023 0.029 T-12 0.025 0.016 0.033 T-27 0.019 0.012 0.024 T-27 0.021 0.013 0.030 Controls 0.024 0.012 0.033 Controls 0.024 0.013 0.035 T-1 0.027 0.017 0.032 T-1 0.020 0.014 0.026 T-2 0.027 0.016 0.036 T-2 0.020 0.012 0.028 T-3 0.017 0.011 0.020 T-3 0.019 0.011 0.030 T-4 0.017 0.013 0.027 T-4 0.013 0.009 0.019 T-7 0.031 0.025 0.033 T-7 0.031 0.018 0.053 Indicators 0.024 0.011 0.036 Indicators 0.021 0.009 0.053 September December Location Average Minima Maxima Location Average Minima Maxima T-9 0.030 0.019 0.040 T-9 0.038 0.029 0.043 T-11 0.033 0.024 0.041 T-11 0.039 0.035 0.041 T-12 0.031 0.022 0.041 T-12 0.040 0.028 0.049 T-27 0.026 0.019 0.033 T-27 0.030 0.026 0.036 Controls 0.030 0.019 0.041 Controls 0.037 0.026 0.049 T-1 0.039 0.028 0.053 T-1 0.031 0.024 0.035 T-2 0.024 0.013 0.032 T-2 0.026 0.020 0.032 T-3 0.022 0.015 0.028 T-3 0.028 0.022 0.037 T-4 0.020 0.012 0.026 T-4 0.030 0.018 0.046 T-7 0.043 0.030 0.055 T-7 0.041 0.034 0.046 Indicators 0.030 0.012 0.055 Indicators 0.031 0.018 0.046 Note: Unless otherwise specified, samples collected on the first, second or third day of the month are grouped with data from the previous month.

10- 2

Table 11. Airborne particulates, analyses for strontium-89, strontium-90 and gamma-emitting isotopes.

Location Quarter Lab Code Volume (m3)

Sr-89 Sr-90 Be-7 K-40 Nb-95 Zr-95 Ru-103 Ru-106 Cs-134 Cs-137 Ce-141 Ce-144 Location Quarter Lab Code Volume (m3)

Sr-89 Sr-90 Be-7 K-40 Nb-95 Zr-95 Ru-103 Ru-106 Cs-134 Cs-137 Ce-141 Ce-144 Collection: Quarterly Composite Units: pCi/m3 1st Quarter TAP-1238 3322

< 0.0014

< 0.0009 2nd Quarter TAP-2656 3906

< 0.0008

< 0.0006 0.107 +/- 0.017 0.069 +/- 0.011

< 0.023

< 0.025

< 0.0009

< 0.0010

< 0.0007

< 0.0014

< 0.0006

< 0.0009

< 0.0065

< 0.0065

< 0.0010

< 0.0008

< 0.0007

< 0.0006

< 0.0014

< 0.0015

< 0.0043

< 0.0055 1st Quarter 2nd Quarter TAP-1239 TAP-2657 3743 3811

< 0.0012

< 0.0010

< 0.0008

< 0.0008 0.075 +/- 0.014 0.059 +/- 0.016

< 0.017

< 0.015

< 0.0006

< 0.0006

< 0.0009

< 0.0009

< 0.0004

< 0.0009

< 0.0066

< 0.0051

< 0.0009

< 0.0007

< 0.0008

< 0.0005

< 0.0008

< 0.0008

< 0.0043

< 0.0039 11-1 T-1 3rd Quarter 4th Quarter TAP-3903 TAP-5027 3991 3858

< 0.0005

< 0.0005

< 0.0003

< 0.0004 0.113 +/- 0.017 0.046 +/- 0.011

< 0.018

< 0.015

< 0.0008

< 0.0022

< 0.0011

< 0.0020

< 0.0010

< 0.0010

< 0.0053

< 0.0041

< 0.0008

< 0.0011

< 0.0007

< 0.0005

< 0.0010

< 0.0012

< 0.0034

< 0.0048 T-2 3rd Quarter 4th Quarter TAP-3904 TAP-5028 3704 4117

< 0.0008

< 0.0005

< 0.0004

< 0.0004 0.086 +/- 0.017 0.059 +/- 0.013

< 0.019

< 0.018

< 0.0007

< 0.0009

< 0.0016

< 0.0013

< 0.0011

< 0.0011

< 0.0057

< 0.0073

< 0.0010

< 0.0008

< 0.0008

< 0.0005

< 0.0017

< 0.0015

< 0.0029

< 0.0041

Table 11. Airborne particulates, analyses for strontium-89, strontium-90 and gamma-emitting isotopes.

Location Quarter Lab Code Volume (m3)

Sr-89 Sr-90 Be-7 K-40 Nb-95 Zr-95 Ru-103 Ru-106 Cs-134 Cs-137 Ce-141 Ce-144 Location Quarter Lab Code Volume (m3)

Sr-89 Sr-90 Be-7 K-40 Nb-95 Zr-95 Ru-103 Ru-106 Cs-134 Cs-137 Ce-141 Ce-144 Collection: Quarterly Composite Units: pCi/m3 1st Quarter TAP-1240 3666

< 0.0010

< 0.0007 2nd Quarter TAP-2658 4055

< 0.0008

< 0.0006 0.076 +/- 0.012 0.091 +/- 0.017

< 0.021

< 0.017

< 0.0013

< 0.0012

< 0.0011

< 0.0015

< 0.0010

< 0.0006

< 0.0077

< 0.0070

< 0.0008

< 0.0010

< 0.0007

< 0.0008

< 0.0016

< 0.0017

< 0.0032

< 0.0045 1st Quarter 2nd Quarter TAP-1241 TAP-2659 3534 3616

< 0.0020

< 0.0009

< 0.0013

< 0.0006 0.108 +/- 0.020 0.095 +/- 0.018

< 0.030

< 0.023

< 0.0028

< 0.0013

< 0.0035

< 0.0013

< 0.0010

< 0.0007

< 0.0100

< 0.0073

< 0.0016

< 0.0011

< 0.0018

< 0.0011

< 0.0023

< 0.0020

< 0.0057

< 0.0040 11-2 T-3 3rd Quarter 4th Quarter TAP-3905 TAP-5029 3652 3428

< 0.0005

< 0.0005

< 0.0004

< 0.0004 0.066 +/- 0.015 0.060 +/- 0.014 0.026 +/- 0.009

< 0.028

< 0.0007

< 0.0013

< 0.0009

< 0.0015

< 0.0011

< 0.0005

< 0.0068

< 0.0078

< 0.0009

< 0.0010

< 0.0006

< 0.0011

< 0.0012

< 0.0020

< 0.0046

< 0.0036 T-4 3rd Quarter 4th Quarter TAP-3906 TAP-5030 3794 3746

< 0.0005

< 0.0005

< 0.0003

< 0.0003 0.072 +/- 0.013 0.064 +/- 0.027

< 0.015

< 0.032

< 0.0003

< 0.0040

< 0.0011

< 0.0033

< 0.0008

< 0.0021

< 0.0066

< 0.0141

< 0.0008

< 0.0018

< 0.0004

< 0.0018

< 0.0012

< 0.0035

< 0.0034

< 0.0078

Table 11. Airborne particulates, analyses for strontium-89, strontium-90 and gamma-emitting isotopes.

Location Quarter Lab Code Volume (m;i)

Sr-89 Sr-90 Be-7 K-40 Nb-95 Zr-95 Ru-103 Ru-106 Cs-134 Cs-137 Ce-141 Ce-144 Location Quarter Lab Code Volume (m3)

Sr-89 Sr-90 Be-7 K-40 Nb-95 Zr-95 Ru-103 Ru-106 Cs-134 Cs-137 Ce-141 Ce-144 Collection: Quarterly Composite Units: pCi/m3 1st Quarter TAP-1243 3470

< 0.0011

< 0.0008 2nd Quarter TAP-2660 3525

< 0.0009

< 0.0008 0.088 +/- 0.018 0.087 +/- 0.014

< 0.019

< 0.024

< 0.0008

< 0.0009

< 0.0013

< 0.0011

< 0.0008

< 0.0012

< 0.0078

< 0.0064

< 0.0012

< 0.0009

< 0.0006

< 0.0009

< 0.0010

< 0.0017

< 0.0030

< 0.0041 1st Quarter 2nd Quarter TAP-1244 TAP-2661 3771 3968

< 0.0012

< 0.0010

< 0.0008

< 0.0008 0.095 +/- 0.017 0.084 +/- 0.013

< 0.023

< 0.020

< 0.0008

< 0.0008

< 0.0012

< 0.0013

< 0.0010

< 0.0009

< 0.0089

< 0.0069

< 0.0012

< 0.0008

< 0.0011

< 0.0006

< 0.0014

< 0.0015

< 0.0041

< 0.0043 11-3 T-7 3rd Quarter 4th Quarter TAP-3907 TAP-5031 3829 3382

< 0.0004

< 0.0005

< 0.0003

< 0.0004 0.126 +/- 0.018 0.098 +/- 0.016

< 0.019

< 0.023

< 0.0009

< 0.0010

< 0.0011

< 0.0019

< 0.0009

< 0.0012

< 0.0076

< 0.0065

< 0.0010

< 0.0010

< 0.0011

< 0.0005

< 0.0014

< 0.0022

< 0.0046

< 0.0056 T-9 (C) 3rd Quarter 4th Quarter TAP-3908 TAP-5032 3372 3798

< 0.0005

< 0.0005

< 0.0004

< 0.0004 0.091 +/- 0.017 0.080 +/- 0.015

< 0.028

< 0.015

< 0.0010

< 0.0014

< 0.0016

< 0.0012

< 0.0014

< 0.0011

< 0.0056

< 0.0056

< 0.0011

< 0.0008

< 0.0008

< 0.0007

< 0.0013

< 0.0019

< 0.0063

< 0.0044

Table 11. Airborne particulates, analyses for strontium-89, strontium-90 and gamma-emitting isotopes.

Location Quarter Lab Code Volume (m3)

Sr-89 Sr-90 Be-7 K-40 Nb-95 Zr-95 Ru-103 Ru-106 Cs-134 Cs-137 Ce-141 Ce-144 Location Quarter Lab Code Volume (m;j)

Sr-89 Sr-90 Be-7 K-40 Nb-95 Zr-95 Ru-103 Ru-106 Cs-134 Cs-137 Ce-141 Ce-144 Collection: Quarterly Composite Units: pCi/m3 1st Quarter TAP-1245 3601

< 0.0011

< 0.0008 2nd Quarter TAP-2662 3645

< 0.0010

< 0.0008 0.089 +/- 0.015 0.077 +/- 0.015

< 0.023

< 0.017

< 0.0008

< 0.0007

< 0.0008

< 0.0011

< 0.0010

< 0.0007

< 0.0076

< 0.0038

< 0.0009

< 0.0009

< 0.0008

< 0.0009

< 0.0017

< 0.0016

< 0.0046

< 0.0032 1st Quarter 2nd Quarter TAP-1246 TAP-2663 3236 3860

< 0.0011

< 0.0009

< 0.0007

< 0.0007 0.101 +/- 0.017 0.097 +/- 0.017

< 0.021

< 0.018

< 0.0009

< 0.0014

< 0.0019

< 0.0019

< 0.0010

< 0.0010

< 0.0069

< 0.0085

< 0.0010

< 0.0010

< 0.0005

< 0.0008

< 0.0010

< 0.0018

< 0.0050

< 0.0032 11-4 T-11 (C) 3rd Quarter 4th Quarter TAP-3909 TAP-5033 3588 3757

< 0.0005

< 0.0006

< 0.0004

< 0.0004 0.089 +/- 0.018 0.079 +/- 0.014 0.030 +/- 0.016

< 0.021

< 0.0010

< 0.0007

< 0.0012

< 0.0013

< 0.0006

< 0.0011

< 0.0044

< 0.0050

< 0.0009

< 0.0010

< 0.0007

< 0.0011

< 0.0011

< 0.0017

< 0.0038

< 0.0056 T-12 (C) 3rd Quarter 4th Quarter TAP-3910 TAP-5034 3749 3900

< 0.0005

< 0.0004

< 0.0004

< 0.0003 0.094 +/- 0.013 0.076 +/- 0.017

< 0.015

< 0.024

< 0.0007

< 0.0021

< 0.0014

< 0.0014

< 0.0007

< 0.0009

< 0.0033

< 0.0071

< 0.0007

< 0.0013

< 0.0004

< 0.0010

< 0.0010

< 0.0017

< 0.0027

< 0.0053

Table 11.

Airborne particulates, analyses for strontium-89, strontium-90 and gamma-emitting isotopes.

Location Quarter Lab Code Volume (mG)

Sr-89 Sr-90 Be-7 K-40 Nb-95 Zr-95 Ru-103 Ru-106 Cs-134 Cs-137 Ce-141 Ce-144 Collection: Quarterly Composite Units: pCi/m3 1st Quarter TAP-1247 3616

< 0.0009

< 0.0007 2nd Quarter TAP-2664 3682

< 0.0008

< 0.0006 0.110 +/- 0.022 0.091 +/- 0.015

< 0.029

< 0.024

< 0.0022

< 0.0011

< 0.0015

< 0.0013

< 0.0012

< 0.0008

< 0.0088

< 0.0054

< 0.0014

< 0.0007

< 0.0011

< 0.0009

< 0.0032

< 0.0018

< 0.0061

< 0.0029 11-5 T-27 (C) 3rd Quarter 4th Quarter TAP-3911 TAP-5035 3865 3546

< 0.0005

< 0.0004

< 0.0004

< 0.0003 0.075 +/- 0.015 0.065 +/- 0.016

< 0.021

< 0.020

< 0.0010

< 0.0009

< 0.0013

< 0.0017

< 0.0010

< 0.0011

< 0.0073

< 0.0075

< 0.0009

< 0.0011

< 0.0009

< 0.0008

< 0.0015

< 0.0020

< 0.0045

< 0.0048

Table 12. Area monitors (TLD), Quarterly.

Units: mR/91 days 1st Qtr.

2nd Qtr.

3rd Qtr.

4th Qtr.

Indicator T-1 12.1 +/- 1.2 10.6 +/- 0.8 10.7+/-1.1 12.8 +/- 0.8 T-2 10.5 +/- 0.7 11.4 +/- 0.8 10.2 +/- 0.8 12.9 +/- 0.8 T-3 10.6 +/- 1.2 10.3 +/- 0.9 10.1 +/- 1.2 12.3 +/- 1.0 T-4 11.3+/-0.7 12.4 +/- 0.6 11.2+/-0.7 14.1 +/- 0.7 T-5 12.9 +/- 0.8 14.1 +/- 1.1 12.7 +/- 0.6 16.1 +/- 0.9 T-6 10.8+/-1.0 9.9 +/- 0.6 11.4 +/- 1.3 12.2 +/- 0.7 T-7 16.6 +/- 0.7 16.6 +/- 0.6 16.6 +/- 0.9 17.0 +/- 1.0 T-10 14.6 +/- 0.8 14.9 +/- 0.7 15.3 +/- 0.8 16.9 +/- 0.9 T-38 10.7 +/- 0.8 11.4 +/- 1.3 11.2 +/- 0.8 12.6+/-1.4 T-40 9.8 +/- 0.8 11.3 +/- 1.0 9.7 +/- 0.6 12.7+/-1.0 T-41 10.0 +/- 0.9 9.8 +/- 0.6 10.7+/-1.0 11.7 +/-0.7 T-42 10.6+/-1.0 10.9 +/- 0.9 11.1 +/- 1.3 12.6 +/- 1.0 T-43 13.7 +/- 1.8 13.8 +/- 0.8 13.6 +/- 1.1 15.7 +/- 0.8 T-44 17.9+/-0.9 18.9+/-1.2 20.1 +/- 1.3 22.0 +/- 1.1 T-45 17.1 +/- 0.6 17.0+/-1.2 17.9 +/- 0.8 19.5 +/- 1.5 T-46 11.4+/-0.7 12.0 +/- 0.8 11.9+/-1.2 13.6 +/- 0.9 T-47 9.2+/-1.0 8.8 +/- 0.8 9.7 +/- 1.1 10.3 +/- 0.9 T-48 10.3+/-1.0 11.0 +/- 0.8 10.8 +/- 0.6 12.6 +/- 0.8 T-49 8.9 +/- 0.8 10.2+/-1.2 9.2 +/- 0.8 10.3+/-1.4 T-51 18.5 +/- 1.3 17.6+/-1.4 19.3+/-1.3 19.2 +/- 1.4 T-52 16.8 +/- 1.7 17.3 +/- 0.7 17.9 +/- 2.0 18.6 +/- 0.8 T-54 18.0 +/- 1.3 18.4 +/- 1.2 19.1 +/- 1.1 21.1 +/- 1.3 T-55 11.6 +/- 1.4 10.9 +/- 1.1 11.6 +/- 1.4 11.9+/-1.1 T-60 12.9+/-1.1 13.0 +/- 1.5 15.2+/-1.4 14.9 +/- 1.6 T-62 8.8 +/- 0.4 9.0 +/- 0.9 10.5 +/- 0.3 10.2 +/- 0.9 T-67 15.3+/-1.0 16.5+/-1.1 17.8 +/- 0.8 19.4+/-1.2 T-68 14.0+/-1.3 13.3 +/- 0.9 17.3 +/-0.5 15.1+/-0.8 T-69 15.1 +/- 0.7 19.7+/-1.3 17.9 +/- 0.8 18.4 +/- 0.8 T-71 8.7 +/- 0.3 10.4 +/- 0.9 11.7 +/- 0.2 12.0 +/- 1.0 T-73 14.8 +/- 1.1 16.8+/-1.2 17.4+/-0.8 18.3+/-1.4 T-74 13.8 +/- 0.5 14.4 +/- 0.9 16.3 +/- 0.6 15.9+/-1.4 12-1

Table 12. Area monitors (TLD), Quarterly.

Units: mR/91 days 1st Qtr.

2nd Qtr.

3rd Qtr.

4th Qtr.

Indicator T-125 15.8 +/- 0.9 14.5 +/- 0.9 18.6 +/- 1.0 14.6 +/- 1.0 T-126 14.6 +/- 0.7 17.2 +/-1.0 17.8 +/- 0.8 17.4 +/-1.0 T-127 17.8 +/- 1.0 17.6+/-1.2 21.3 +/- 0.8 20.8 +/- 1.5 T-128 15.4 +/- 1.5 16.7 +/- 0.9 18.3 +/- 1.6 20.6 +/- 1.2 T-142 41.7 +/- 0.7 10.4 +/- 1.2 10.8 +/- 0.8 11.6 +/- 1.3 T-150 12.2 +/- 0.9 12.3 +/- 1.2 12.9 +/- 0.8 15.0+/-1.2 T-154 16.5 +/- 0.6 20.4 +/- 1.5 20.2 +/- 0.6 23.4 +/- 1.7 T-201 12.6 +/- 0.6 13.9 +/- 0.5 13.2 +/- 0.5 14.5 +/- 0.5 T-203 14.4 +/- 0.6 15.6 +/- 1.5 17.2 +/- 0.8 13.9+/-1.0 T-206 9.9 +/- 0.6 11.2 +/- 0.4 9.8 +/- 0.5 11.4 +/- 0.6 T-208 8.3 +/- 0.7 10.8 +/- 0.8 9.6 +/- 0.7 11.6 +/- 0.8 T-211 8.2 +/- 0.6 7.2 +/- 0.7 9.9 +/- 0.9 7.8 +/- 1.0 T-212 8.4 +/- 0.7 9.9 +/- 0.8 9.6 +/- 0.4 10.5 +/- 1.1 T-217 15.2 +/- 1.6 15.3 +/- 1.3 18.2 +/- 1.3 16.5+/-1.6 T-218 17.7 +/- 0.8 18.4 +/- 1.3 21.1 +/- 0.8 19.9+/-1.4 T-219 12.5 +/- 1.1 14.6 +/- 1.4 14.8 +/- 1.0 15.8 +/- 1.6 T-220 15.1 +/- 1.1 14.0+/-1.1 15.6 +/- 0.7 16.5+/-1.3 T-222 8.3 +/- 0.8 11.4 +/- 1.2 12.4 +/- 0.7 13.6 +/- 1.6 T-224 7.6 +/- 0.9 9.9 +/- 0.8 11.9 +/- 0.5 10.5 +/- 1.0 Mean+/- s.d.

13.4 +/- 5.2 13.5 +/- 3.3 14.2 +/- 3.7 15.0 +/- 3.6 12-2

Table 12. Area monitors (TLD), Quarterly.

Units: mR/91 days 1st Qtr.

2n d Qtr.

3rd Qtr.

4th Qtr.

Con trol T-9 13.4 +/- 1.4 12.7 +/- 0.8 13.4+/-0.8 14.4 +/- 0.8 T-11 12.6 +/- 0.6 12.7 +/- 0.8 11.8+/-0.7 14.1 +/- 0.7 T-12 15.6 +/- 1.0 16.1+/-1.2 16.0 +/- 0.9 18.7+/-1.5 T-27 17.0+/-1.3 18.6 +/- 1.2 18.0 +/- 1.3 20.8 +/- 0.9 Mean+/- s.d.

14.7 +/- 2.0 15.0 +/- 2.9 14.8 +/- 2.7 17.0 +/- 3.3 T-100 13.8 +/- 1.5 14.5 +/- 1.2 16.5 +/- 1.0 16.9 +/- 1.4 T-124 17.7+/-1.2 19.3 +/- 1.0 20.5+/-1.1 19.8+/-1.0 T-155 14.3 +/- 0.7 14.0+/-1.0 16.3 +/- 0.7 16.4 +/- 1.4 T-221 14.7 +/- 0.8 18.4 +/- 1.0 20.6 +/- 0.8 19.9 +/- 0.9 Mean+/- s.d.

15.1 +/- 1.8 16.6 +/- 2.7 18.5 +/- 2.4 18.3 +/- 1.9 QC T-80 8.0 +/- 0.8 9.7 +/- 1.0 10.8 +/- 0.7 11.0 +/- 0.9 T-83 8.6 +/- 0.7 9.9 +/- 1.5 10.9 +/- 0.7 10.6 +/- 1.2 T-84 11.0 +/- 0.8 11.7+/-0.9 11.8+/-0.7 12.2 +/- 0.8 T-113 17.0 +/- 0.4 17.6+/-1.1 20.6 +/- 0.5 18.4+/-1.1 T-200 8.7 +/- 0.6 11.4 +/- 0.9 10.2 +/- 0.6 12.2 +/- 0.7 Mean+/- s.d.

10.7 +/- 3.7 12.1 +/- 3.2 12.9 +/- 4.4 12.9 +/- 3.2 Shield T-87 5.7 +/- 0.9 8.1 +/- 1.1 6.8 +/- 0.5 6.7 +/- 0.9 12-3

Table 13. Milk, analyses for strontium-89, strontium-90, iodine-131, gamma emitting isotopes, calcium and stable potassium.

Monthly collections, location T-24 Units: pCi/L Date Collected 01-29-19 02-26-19 04-03-19 Lab Code TMI-286 TMI-536 TMI-1006 1-131

< 0.5

< 0.3

< 0.5 Sr-89

< 0.6

< 0.7

< 0.7 Sr-90

< 0.6

< 0.7

< 0.6 K-40 1311 +/- 119 1363 +/- 120 1290 +/- 120 Cs-134

< 4.6

< 3.7

< 4.0 Cs-137

< 2.4

< 2.9

< 2.1 Ba-La-140

< 3.0

< 2.9

< 2.1 Ca (g/L) 1.06 1.08 0.96 Sr-90/g Ca

< 0.57

< 0.65

< 0.63 K (g/L) 1.60 +/- 0.15 1.66+/-0.15 1.57 +/- 0.15 Cs-137/g K

< 1.50

< 1.75

< 1.34 Milk Sampling Discontinued 13-1 05-01-19 TMI-1489

< 0.3

< 0.5

< 0.5 1333 +/- 110

< 4.1

< 2.9

< 2.1 0.92

< 0.54 1.63 +/- 0.13

< 1.78

Table 14. Ground water samples, analyses for gross beta, tritium, strontium-89, strontium-90 and gamma-emitting isotopes.

Collection: Quarterly Units: pCi/L Period 1st Qtr.

2nd Qtr.

3rd Qtr.

4th Qtr.

Location T-27A (C)

Lab Code TWW-1010 TWW-2847 TWW-3912 Req. LLD Date Collected 03-13-19 NSa 07-11-19 10-08-19 Gross beta 2.8 +/- 1.3

< 3.8 3.8 4.0 H-3

< 330

< 330

< 330 330 Sr-89

< 0.8

< 1.6

< 0.6 Sr-90

< 0.5

< 0.9

< 0.5 Mn-54

< 3.5

< 3.3

< 2.2 15 Fe-59

< 6.7

< 6.4

< 5.3 30 Co-58

< 2.0

< 1.8

< 2.0 15 Co-60

< 1.7

< 1.7

< 1.5 15 Zn-65

< 3.5

< 3.7

< 3.3 30 Zr-Nb-95

< 5.6

< 3.8

< 4.3 15 Cs-134

< 4.2

< 3.8

< 3.1 15 Cs-137

< 3.4

< 3.5

< 3.1 18 Ba-La-140

< 5.2

< 8.2

< 5.4 15 a No sample sent.

14-1

Table 17. Green leafy vegetables, analyses for strontium-89, strontium-90, iodine-131 and other gamma-emitting isotopes.

Collection: Monthly, in season Units: pCi/g wet Location T-17(1)

Lab Code TYE-3643 TYE-4163 TYE-4562 Date Collected 09-25-19 10-30-19 11-27-19 Sample Type Cabbage Cabbage Cabbage Sr-89

< 0.011

< 0.011

< 0.005 Sr-90

< 0.007

< 0.008

< 0.004 1-131

< 0.026

< 0.023

< 0.018 K-40 2.78 +/- 0.29 2.91 +/- 0.31 2.28 +/- 0.24 Nb-95

< 0.009

< 0.008

< 0.007 Zr-95

< 0.014

< 0.022

< 0.008 Cs-134

< 0.010

< 0.009

< 0.008 Cs-137

< 0.011

< 0.011

< 0.009 Ce-141

< 0.019

< 0.012

< 0.018 Ce-144

< 0.053

< 0.055

< 0.049 Location T-19 (I) 19C Lab Code TYE-3281 TYE-3644 TYE-4164 TYE-4564 Date Collected 08-28-19 09-25-19 10-30-19 11-27-19 Sample Type Cabbage Cabbage Cabbage Cabbage Sr-89

< 0.005

< 0.007

< 0.004

< 0.004 Sr-90

< 0.003

< 0.004

< 0.002

< 0.003 1-131

< 0.021

< 0.029

< 0.026

< 0.027 K-40 2.44 +/- 0.24 2.07 +/- 0.27 2.17 +/- 0.29 2.51 +/- 0.29 Nb-95

< 0.007

< 0.011

< 0.020

< 0.020 Zr-95

< 0.008

< 0.017

< 0.021

< 0.013 Cs-134

< 0.008

< 0.012

< 0.017

< 0.011 Cs-137

< 0.007

< 0.008

< 0.013

< 0.013 Ce-141

< 0.019

< 0.016

< 0.034

< 0.027 Ce-144

< 0.068

< 0.079

< 0.119

< 0.077 Location T-19(1) 19K Lab Code TYE-2840 TYE-3282 TYE-3646 TYE-4165 TYE-4563 Date Collected 07-31-19 08-28-19 09-25-19 10-30-19 11-27-19 Sample Type Kale Kale Kale Kale Kale Sr-89

< 0.028

< 0.025

< 0.032

< 0.019

< 0.015 Sr-90

< 0.022

< 0.015

< 0.020

< 0.015

< 0.010 1-131

< 0.042

< 0.042

< 0.024

< 0.024

< 0.028 K-40 3.99 +/- 0.47 3.86 +/- 0.35 4.57 +/- 0.39 2.77 +/- 0.33 5.00 +/- 0.45 Nb-95

< 0.019

< 0.011

< 0.016

< 0.013

< 0.018 Zr-95

< 0.033

< 0.015

< 0.017

< 0.017

< 0.029 Cs-134

< 0.021

< 0.012

< 0.011

< 0.013

< 0.015 Cs-137

< 0.018

< 0.013

< 0.009

< 0.014

< 0.013 Ce-141

< 0.044

< 0.031

< 0.014

< 0.024

< 0.021 Ce-144

< 0.104

< 0.083

< 0.075

< 0.075

< 0.096 17-1

Table 17. Green leafy vegetables, analyses for strontium-89, strontium-90, iodine-131 and other gamma-emitting isotopes.

Collection: Monthly, in season Units: pCi/g wet Location T-30 Lab Code TVE-2842 TVE-3283 TVE-3647 Date Collected 07-31-19 08-28-19 09-25-19 Sample Type Kale Kale Kale Sr-89

< 0.030

< 0.019

< 0.039 Sr-90

< 0.023

< 0.012

< 0.026 1-131

< 0.018

< 0.035

< 0.036 K-40 4.51 +/- 0.43 3.25 +/- 0.37 4.64 +/- 0.39 Nb-95

< 0.009

< 0.010

< 0.009 Zr-95

< 0.014

< 0.014

< 0.021 Cs-134

< 0.015

< 0.012

< 0.014 Cs-137

< 0.018

< 0.011

< 0.008 Ce-141

< 0.032

< 0.021

< 0.027 Ce-144

< 0.122

< 0.075

< 0.099 Location T-37 (C)

Lab Code TVE-3284 TVE-3648 Date Collected 08-28-19 09-24-19 10-29-19 Sample Type Cabbage Cabbage Sr-89

< 0.006

< 0.006 NSa Sr-90

< 0.004

< 0.004 1-131

< 0.034

< 0.019 K-40 1.89 +/- 0.24 1.67 +/- 0.21 Nb-95

< 0.015

< 0.009 Zr-95

< 0.022

< 0.018 Cs-134

< 0.012

< 0.009 Cs-137

< 0.006

< 0.008 Ce-141

< 0.027

< 0.012 Ce-144

< 0.079

< 0.043 NS - No sample collected. See table 2.0, Listing Of Missed Samples 17-2 TVE-3647 09-25-19 Kale

< 0.039

< 0.026

< 0.036 4.64 +/- 0.39

< 0.009

< 0.021

< 0.014

< 0.008

< 0.027

< 0.099

Table 17. Green leafy vegetables, analyses for strontium-89, strontium-90, iodine-131 and other gamma-emitting isotopes.

Collection: Monthly, in season Units: pCi/g wet Location T-227 (I)

Lab Code TVE-3285 TVE-3649 TVE-4167 Date Collected 08-28-19 09-25-19 10-30-19 Sample Type Cabbage Cabbage Cabbage Sr-89

< 0.006

< 0.013

< 0.004 Sr-90

< 0.005

< 0.007

< 0.004 1-131

< 0.023

< 0.040

< 0.031 K-40 1.87 +/- 0.23 2.26 +/- 0.28 2.34 +/- 0.27 Nb-95

< 0.012

< 0.008

< 0.007 Zr-95

< 0.008

< 0.016

< 0.017 Cs-134

< 0.009

< 0.010

< 0.010 Cs-137

< 0.007

< 0.010

< 0.013 Ce-141

< 0.016

< 0.024

< 0.021 Ce-144

< 0.059

< 0.068

< 0.081 17-3 TVE-4565 11-27-19 Cabbage

< 0.003

< 0.002

< 0.022 2.31 +/- 0.27

< 0.013

< 0.020

< 0.012

< 0.008

< 0.017

< 0.094

Table 21. Treated surface water samples, analyses for gross beta.

Collection: Monthly composites of weekly grab samples Units: pCi/L T-11 (C)

Lab Code Date Collected Gross Beta Lab Code TSWT-298 01-29-19 1.8 +/- 0.6 TSWT-299 TSWT-537 02-26-19

< 0.9 TSWT-538 TSWT-1007 04-02-19 1.3 +/- 0.6 TSWT-1008 TSWT-1492 04-30-19 1.0 +/- 0.5 TSWT-1493 TSWT-1882 05-28-19

< 0.9 TSWT-1883 TSWT-2353 06-25-19 1.7 +/- 0.6 TSWT-2354 TSWT-2837 07-30-19

< 0.9 TSWT-2838 TSWT-3286 09-03-19 1.0 +/- 0.5 TSWT-3287 TSWT-3650 10-01-19 1.4+/- 0.6 TSWT-3651 TSWT-4168 10-29-19

< 0.8 TSWT-4169 TSWT-4597 11-26-19 1.9 +/- 0.6 TSWT-4598 TSWT-4890 12-31-19 1.1 +/- 0.6 TSWT-4892 T-143 (QC)

Lab Code Date Collected Gross Beta TSWT-300 01-29-19

< 0.9 TSWT-539 02-26-19 1.5 +/- 0.6 TSWT-1009 04-02-19 1.9 +/- 0.6 TSWT-1494 04-30-19 1.0+/-0.5 TSWT-1884 05-28-19 1.3 +/- 0.6 TSWT-2355 06-25-19 1.2 +/- 0.6 TSWT-2839 07-30-19 1.4 +/- 0.6 TSWT-3288 09-03-19 1.7+/-0.6 TSWT-3652 10-01-19

< 0.9 TSWT-4170 10-29-19 1.2+/-0.5 TSWT-4600 11-26-19 1.0 +/- 0.5 TSWT-4893 12-31-19

< 0.9 21-1 T-22 Date Collected Gross Beta 01-29-19 1.3 +/- 0.6 02-26-19 1.1 +/- 0.5 04-02-19 1.4 +/- 0.6 04-30-19 1.4 +/- 0.6 05-28-19

< 0.9 06-25-19 1.7 +/- 0.6 07-30-19 1.4 +/- 0.6 09-03-19 0.9 +/- 0.5 10-01-19 1.0+/- 0.5 10-29-19

< 0.9 11-26-19 1.1 +/- 0.5 12-31-19 2.3 +/- 0.6

Table 22.

Location Period Lab Code H-3 Sr-89 Sr-90 Mn-54 Fe-59 Co-58 Co-60 Zn-65 Zr-Nb-95 Cs-134 Cs-137 Ba-La-140 Location Period Lab Code H-3 Sr-89 Sr-90 Mn-54 Fe-59 Co-58 Co-60 Zn-65 Zr-Nb-95 Cs-134 Cs-137 Ba-La-140 Treated surface water samples, analyses for tritium, strontium-89, strontium-90 and gamma-emitting isotopes.

Collection: Quarterly composites of weekly grab samples Units: pCi/L T-11 (C) 1st Qtr.

2nd Qtr.

3rd Qtr.

TSWT-1011 TSWT-2374 TSWT-3689

< 330

< 330

< 330

< 0.7

< 0.6

< 0.6

< 0.5

< 0.4

< 0.5

< 2.2

< 2.6

< 2.4

< 3.6

< 6.4

< 5.4

< 2.1

< 2.2

< 3.2

< 1.8

< 2.5

< 2.0

< 1.8

< 7.3

< 7.4

< 4.5

< 4.9

< 4.7

< 4.2

< 3.9

< 4.1

< 2.3

< 3.3

< 2.5

< 2.6

< 8.0

< 2.3 T-22 1st Qtr.

2nd Qtr.

3rd Qtr.

TSWT-1012 TSWT-2375 TSWT-3690

< 330

< 330

< 330

< 0.6

< 0.6

< 0.6

< 0.5

< 0.4

< 0.5

< 3.2

< 3.8

< 2.6

< 4.0

< 7.5

< 5.4

< 1.5

< 3.5

< 2.4

< 1.5

< 2.6

< 2.0

< 6.4

< 5.5

< 4.2

< 3.4

< 5.5

< 2.0

< 3.8

< 3.4

< 3.6

< 2.5

< 3.3

< 3.9

< 2.6

< 10.4

< 2.8 22-1 4th Qtr.

TSWT-4910

< 330

< 0.7

< 0.5

< 3.0

< 4.4

< 3.0

< 3.0

< 1.8

< 3.3

< 3.9

< 2.1

< 3.5 4th Qtr.

TSWT-4911 336 +/- 91

< 0.8

< 0.5

< 2.8

< 3.1

< 1.4

< 2.0

< 2.7

< 4.6

< 3.8

< 2.2

< 4.2 Reg. LLD 330 15 30 15 15 30 15 10 18 15 Reg. LLD 330 15 30 15 15 30 15 10 18 15

Table 23. Untreated surface water, analyses for gross beta, tritium and gamma emitting isotopes.

Location: T-3 Collection: Monthly composites of weekly grab samples Units: pCi/L Lab Code TSWU-301 TSWU-540 TSWU-1013 TSWU-1495 Date Collected 01-29-19 02-26-19 04-02-19 04-30-19 Req. LLD Gross beta 2.9 +/- 0.7 1.7 +/- 0.6 2.8 +/- 0.7 2.4 +/- 0.7 4.0 H-3

< 330

< 330

< 330

< 330 330 Mn-54

< 2.7

< 2.7

< 2.6

< 2.2 15 Fe-59

< 4.0

< 4.6

< 2.0

< 3.6 30 Co-58

< 1.9

< 2.5

< 3.7

< 2.6 15 Co-60

< 2.4

< 2.5

< 1.3

< 1.2 15 Zn-65

< 7.9

< 2.9

< 4.5

< 5.5 30 Zr-Nb-95

< 3.3

< 1.7

< 2.7

< 4.5 15 Cs-134

< 4.1

< 3.2

< 3.8

< 3.9 10 Cs-137

< 3.5

< 2.9

< 3.2

< 3.0 18 Ba-La-140

< 5.1

< 3.5

< 3.1

< 4.4 15 Lab Code TSWU-1885 TSWU-2358 TSWU-2843 TSWU-3289 Date Collected 05-28-19 06-25-19 07-30-19 09-03-19 Req. LLD Gross beta 2.3 +/- 0.7 2.4 +/- 1.1 1.6 +/- 0.6 2.3 +/- 0.6 4.0 H-3

< 330

< 330

< 330 430 +/- 95 330 Mn-54

< 4.1

< 2.9

< 4.1

< 2.6 15 Fe-59

< 5.9

< 5.2

< 8.3

< 4.2 30 Co-58

< 3.6

< 2.8

< 2.4

< 3.8 15 Co-60

< 4.7

< 2.3

< 1.7

< 2.8 15 Zn-65

< 10.4

< 1.9

< 5.6

< 6.1 30 Zr-Nb-95

< 6.7

< 3.5

< 5.0

< 3.0 15 Cs-134

< 5.4

< 4.1

< 4.8

< 3.1 10 Cs-137

< 5.7

< 4.5

< 3.6

< 1.5 18 Ba-La-140

< 9.3

< 7.3

< 7.4

< 2.5 15 Lab Code TSWU-3653 TSWU-4171 TSWU-4591 TSWU-4894 Date Collected 10-01-19 10-29-19 11-26-19 12-31-19 Req. LLD Gross beta 1.1 +/- 0.5 2.0 +/- 0.6 1.7 +/- 0.6 2.8 +/- 0.7 4.0 H-3 515 +/- 98 431 +/- 94

< 330

< 330 330 Mn-54 3.1

< 6.6

< 3.9

< 2.7 15 Fe-59 6.0

< 10.0

< 7.5

< 3.0 30 Co-58 3.6

< 4.8

< 5.2

< 1.6 15 Co-60 1.9

< 5.9

< 4.5

< 2.6 15 Zn-65 4.5

< 17.3

< 3.8

< 3.2 30 Zr-Nb-95 2.7

< 9.6

< 7.0

< 2.8 15 Cs-134 4.4

< 6.2

< 6.6

< 3.4 10 Cs-137 4.9

< 6.0

< 3.4

< 2.1 18 Ba-La-140 3.1

< 7.7

< 8.0

< 3.1 15 23-1

Table 23. Untreated surface water, analyses for gross beta, tritium and gamma emitting isotopes.

Location: T-11 (C)

Collection: Monthly composites of weekly grab samples Units: pCi/L Lab Code TSWU-302 TSWU-541 TSWU-1014 TSWU-1496 Date Collected 01-29-19 02-26-19 04-02-19 04-30-19 Req. LLD Gross beta 1.7 +/- 0.6 1.5 +/- 0.6 1.2 +/- 0.6 1.5 +/- 0.6 4.0 H-3

< 330

< 330

< 330

< 330 330 Mn-54

< 3.7

< 3.4

< 2.7

< 3.3 15 Fe-59

< 6.2

< 4.3

< 5.0

< 3.2 30 Co-58

< 2.7

< 2.4

< 3.6

< 2.1 15 Co-60

< 1.1

< 2.1

< 1.3

< 2.7 15 Zn-65

< 3.8

< 5.5

< 2.8

< 4.5 30 Zr-Nb-95

< 4.2

< 2.8

< 2.7

< 3.3 15 Cs-134

< 4.4

< 4.5

< 3.9

< 3.2 10 Cs-137

< 3.8

< 2.4

< 3.8

< 3.6 18 Ba-La-140

< 2.9

< 1.8

< 2.1

< 5.5 15 Lab Code TSWU-1886 TSWU-2359 TSWU-2844 TSWU-3290 Date Collected 05-28-19 06-25-19 07-30-19 09-03-19 Req. LLD Gross beta 1.2+/-0.6 1.8 +/- 0.6 1.3 +/- 0.5 1.5 +/- 0.6 4.0 H-3

< 330

< 330

< 330

< 330 330 Mn-54

< 4.0

< 2.2

< 2.9

< 2.8 15 Fe-59

< 7.5

< 5.7

< 5.0

< 3.7 30 Co-58

< 3.9

< 3.0

< 4.3

< 3.3 15 Co-60

< 4.7

< 1.7

< 1.2

< 1.6 15 Zn-65

< 3.7

< 2.6

< 3.0

< 3.3 30 Zr-Nb-95

< 6.4

< 2.5

< 4.6

< 2.4 15 Cs-134

< 4.5

< 3.7

< 4.7

< 3.1 10 Cs-137

< 5.2

< 2.7

< 3.3

< 3.2 18 Ba-La-140

< 3.1

< 4.0

< 6.1

< 4.3 15 Lab Code TSWU-3655 TSWU-4172 TSWU-4592 TSWU-4895 Date Collected 10-01-19 10-29-19 11-26-19 12-31-19 Req. LLD Gross beta 0.9 +/- 0.5 0.9 +/- 0.5

< 1.8 1.2 +/- 0.6 4.0 H-3

< 330

< 330 367 +/- 91

< 330 330 Mn-54

< 4.5

< 4.2

< 3.5

< 2.7 15 Fe-59

< 4.6

< 6.2

< 3.5

< 5.2 30 Co-58

< 3.9

< 3.5

< 2.7

< 2.2 15 Co-60

< 3.9

< 3.6

< 3.3

< 2.2 15 Zn-65

< 8.1

< 5.5

< 5.2

< 3.5 30 Zr-Nb-95

< 4.3

< 3.0

< 4.3

< 3.0 15 Cs-134

< 5.1

< 4.7

< 3.2

< 3.3 10 Cs-137

< 4.0

< 4.3

< 3.3

< 3.7 18 Ba-La-140

< 4.1

< 3.5

< 6.7

< 3.9 15 23-2

Table 23. Untreated surface water, analyses for gross beta, tritium and gamma emitting isotopes.

Location: T-22 Collection: Monthly composites of weekly grab samples Units: pCi/L Lab Code TSWU-303 8 TSWU-542 TSWU-1015 TSWU-1497 Date Collected 01-29-19 02-26-19 04-02-19 04-30-19 Req. LLD Gross beta 2.3 +/- 0.7 1.7 +/- 0.6 1.6 +/- 0.6 1.9 +/- 0.6 4.0 H-3

< 330

< 330

< 330

< 330 330 Mn-54

< 4.4

< 4.7

< 2.4

< 2.5 15 Fe-59

< 7.1

< 8.5

< 3.9

< 6.2 30 Co-58

< 3.8

< 5.5

< 1.9

< 1.4 15 Co-60

< 2.1

< 3.2

< 2.1

< 2.6 15 Zn-65

< 4.5

< 14.9

< 4.1

< 1.7 30 Zr-Nb-95

< 4.5

< 9.5

< 3.0

< 4.1 15 Cs-134

< 3.6

< 6.6

< 2.9

< 3.0 10 Cs-137

< 4.1

< 5.5

< 3.3

< 2.3 18 Ba-La-140

< 1.9

< 6.8

< 3.7

< 4.8 15 Lab Code TSWU-1887 TSWU-2360 TSWU-2845 TSWU-3291 Date Collected 05-28-19 06-25-19 07-30-19 09-03-19 Req. LLD Gross beta 1.9 +/- 0.6 1.9 +/- 0.6 1.4 +/- 0.6 1.3 +/- 0.6 4.0 H-3

< 330

< 330

< 330

< 330 330 Mn-54

< 2.9

< 3.0

< 3.3

< 3.3 15 Fe-59

< 4.2

< 4.3

< 9.3

< 4.4 30 Co-58

< 2.9

< 2.0

< 4.0

< 2.5 15 Co-60

< 2.7

< 3.2

< 1.3

< 2.4 15 Zn-65

< 4.0

< 4.0

< 4.6

< 4.5 30 Zr-Nb-95

< 3.1

< 4.1

< 3.7

< 2.9 15 Cs-134

< 3.3

< 3.3

< 5.1

< 3.9 10 Cs-137

< 4.0

< 1.7

< 3.3

< 2.1 18 Ba-La-140

< 5.4

< 5.9

< 4.3

< 7.9 15 Lab Code TSWU-3657 TSWU-4173 TSWU-4593 TSWU-4896 Date Collected 10-01-19 10-29-19 11-26-19 12-31-19 Req. LLD Gross beta 1.0 +/- 0.5 1.1 +/- 0.6 1.5 +/- 0.6 1.3 +/- 0.6 4.0 H-3 546 +/- 99 480 +/- 96

< 330

< 330 330 Mn-54

< 1.6

< 3.1

< 2.8

< 2.6 15 Fe-59

< 4.4

< 3.2

< 4.4

< 4.2 30 Co-58

< 1.2

< 2.8

< 1.2

< 2.7 15 Co-60

< 1.9

< 2.0

< 2.8

< 1.7 15 Zn-65

< 3.6

< 3.4

< 5.8

< 2.3 30 Zr-Nb-95

< 2.3

< 2.4

< 2.6

< 2.9 15 Cs-134

< 3.5

< 3.0

< 3.4

< 2.9 10 Cs-137

< 3.0

< 3.1

< 3.5

< 2.0 18 Ba-La-140

< 3.1

< 2.8

< 4.4

< 3.9 15 a Sample leaked during transportation. Only 1 liter tested for gamma.

23-3

Table 23. Untreated surface water, analyses for gross beta, tritium and gamma emitting isotopes.

Location: T-145 (QC)

Collection: Monthly composites of weekly grab samples Units: pCi/L Lab Code TSWU-305 TSWU-543 TSWU-1016 TSWU-1498 Date Collected 01-29-19 02-26-19 04-02-19 04-30-19 Req. LLD Gross beta 1.6 +/- 0.6 1.4 +/- 0.6 1.2 +/- 0.5 2.0 +/- 0.6 4.0 H-3

< 330

< 330

< 330

< 330 330 Mn-54

< 2.0

< 2.1

< 1.8

< 2.7 15 Fe-59

< 3.7

< 4.6

< 2.7

< 5.1 30 Co-58

< 2.4

< 1.8

< 2.4

< 2.1 15 Co-60

< 2.5

< 1.4

< 2.7

< 2.7 15 Zn-65

< 7.2

< 2.7

< 4.1

< 4.2 30 Zr-Nb-95

< 2.5

< 2.9

< 1.9

< 1.8 15 Cs-134

< 3.2

< 3.3

< 2.2

< 3.3 10 Cs-137

< 3.4

< 3.9

< 3.0

< 3.6 18 Ba-La-140

< 1.6

< 2.7

< 2.0

< 3.0 15 Lab Code TSWU-1888 TSWU-2361 TSWU-2846 TSWU-3292 Date Collected 05-28-19 06-25-19 07-30-19 09-03-19 Req. LLD Gross beta 1.1 +/- 0.5 1.8 +/- 0.6 1.1 +/- 0.5

< 0.8 4.0 H-3

< 330

< 330

< 330

< 330 330 Mn-54

< 2.3

< 2.8

< 3.4

< 2.0 15 Fe-59

< 4.8

< 7.1

< 7.0

< 6.6 30 Co-58

< 1.9

< 2.1

< 4.3

< 3.7 15 Co-60

< 3.7

< 1.9

< 2.6

< 1.9 15 Zn-65

< 3.5

< 1.8

< 4.3

< 4.5 30 Zr-Nb-95

< 4.8

< 2.1

< 3.0

< 5.2 15 Cs-134

< 3.6

< 2.8

< 4.7

< 3.3 10 Cs-137

< 2.7

< 2.5

< 5.6

< 3.7 18 Ba-La-140

< 8.1

< 6.7

< 4.2

< 3.2 15 Lab Code TSWU-3658 TSWU-4174 TSWU-4594 TSWU-4897 Date Collected 10-01-19 10-29-19 11-26-19 12-31-19 Req. LLD Gross beta 1.4+/-0.6 1.2 +/- 0.5

< 1.7 1.1 +/- 0.5 4.0 H-3

< 330 561 +/- 100

< 330

< 330 330 Mn-54

< 3.4

< 2.6

< 2.7

< 2.0 15 Fe-59

< 4.8

< 3.9

< 5.9

< 2.6 30 Co-58

< 2.7

< 1.6

< 2.8

< 2.3 15 Co-60

< 2.0

< 2.5

< 3.4

< 2.5 15 Zn-65

< 6.1

< 7.9

< 8.0

< 5.1 30 Zr-Nb-95

< 4.0

< 2.7

< 4.6

< 2.4 15 Cs-134

< 3.0

< 3.6

< 4.4

< 2.9 10 Cs-137

< 4.1

< 3.0

< 2.8

< 3.3 18 Ba-La-140

< 4.2

< 2.8

< 4.3

< 1.5 15 23-4

Table 24. Untreated surface water samples, analyses for strontium-89 and strontium-90.

Collection: Quarterly composites of weekly grab samples Units: pCi/L Location T-3 Period 1st Qtr.

2nd Qtr.

3rd Qtr.

4th Qtr.

Lab Code TSWU-1137 TSWU-2566 TSWU-3854 TSWU-4923 Sr-89

< 0.6

< 0.7

< 0.7

< 0.6 Sr-90

< 0.5

< 0.5

< 0.6

< 0.5 Location T-11 (C)

Period 1st Qtr.

2nd Qtr.

3rd Qtr.

4th Qtr.

Lab Code TSWU-1138 TSWU-2567 TSWU-3855 TSWU-4924 Sr-89

< 0.6

< 0.8

< 0.7

< 0.6 Sr-90

< 0.5

< 0.5

< 0.6

< 0.5 Location T-22 Period 1st Qtr.

2nd Qtr.

3rd Qtr.

4th Qtr.

Lab Code TSWU-1139 TSWU-2568 TSWU-3856 TSWU-4925 Sr-89

< 0.5

< 0.6

< 0.6

< 0.6 Sr-90

< 0.5

< 0.4

< 0.5

< 0.5 24-1

Table 25. Fish samples, analyses for gross beta and gamma-emitting isotopes.

Collection: Annually Units: pCi/g wet Location Lab Code TF-3381 Date Collected 04-07-19 Sample Type Walleye Gross Beta 3.52 +/- 0.11 K-40 3.65 +/- 0.31 Mn-54

< 0.011 Fe-59

< 0.242 Co-58

< 0.034 Co-60

< 0.013 Zn-65

< 0.031 Cs-134

< 0.014 Cs-137

< 0.016 Location Lab Code TF-3383 Date Collected 04-07-19 Sample Type Walleye Gross Beta 4.38+/-0.12 K-40 4.02 +/- 0.33 Mn-54

< 0.018 Fe-59

< 0.254 Co-58

< 0.035 Co-60

< 0.008 Zn-65

< 0.045 Cs-134

< 0.016 Cs-137

< 0.012 T-33 (Lake Erie, 1.5 mi. NE of Station)

TF-3382 05-25-19 White Perch; White Bass 3.33 +/- 0.11 3.22 +/- 0.52

< 0.028

< 0.136

< 0.069

< 0.016

< 0.073

< 0.025

< 0.021 T-35 TF-3384 06-10-19 White Perch; White Bass 3.80+/-0.12 3.78 +/- 0.68

< 0.040

< 0.229

< 0.062

< 0.027

< 0.073

< 0.036

< 0.032 25-1

Table 26. Shoreline sediment samples, analyses for gamma-emitting isotopes.

Collection: Semiannually Units: pCi/g dry Location T-3 Lab Code TSS-1490 Date Collected 04-03-19 K-40 9.44 +/- 0.46 Mn-54

< 0.016 Co-58

< 0.019 Co-60

< 0.009 Cs-134

< 0.011 Cs-137

< 0.009 Lab Code TSS-3900 Date Collected 10-15-19 K-40 12.06 +/- 0.57 Mn-54

< 0.014 Co-58

< 0.010 Co-60

< 0.018 Cs-134

< 0.010 Cs-137

< 0.013 T-11 TSS-1491 04-03-19 12.19 +/- 0.55

< 0.015

< 0.017

< 0.012

< 0.011

< 0.010 TSS-3902 10-15-19 11.67 +/- 0.56

< 0.017

< 0.023

< 0.018

< 0.012

< 0.013 26-1

NOTE:

Appendix A is updated four times a year. The complete appendix is included in March, June, September and December monthly progress reports only.

October, 2018 through September, 2019 APPENDIX A INTERLABORATORY AND INTRALABORATORY COMPARISON PROGRAM RESULTS

~L. ATI E~vironmental, Inc.

,.~r"\\.I Midwest Laboratory 700 Landwehr Road* Northbrook, IL 60062-2310 phone /847) 564-0700

  • fax /847) 564-4517

A-1 Environmental, Inc., Midwest Laboratory has participated in interlaboratory comparison (crosscheck) programs since the formulation of its quality control program in December 1971. These programs are operated by agencies which supply environmental type samples containing concentrations of radionuclides known to the issuing agency but not to participant laboratories. The purpose of such a program is to provide an independent check on a laboratorys analytical procedures and to alert it of any possible problems.

Participant laboratories measure the concentration of specified radionuclides and report them to the issuing agency. Several months later, the agency reports the known values to the participant laboratories and specifies control limits. Results consistently higher or lower than the known values or outside the control limits indicate a need to check the instruments or procedures used.

Results in Table A-1 were obtained through participation in the RAD PT Study Proficiency Testing Program administered by Environmental Resource Associates, serving as a replacement for studies conducted previously by the U.S. EPA Environmental Monitoring Systems Laboratory, Las Vegas, Nevada.

Table A-2 lists results for thermoluminescent dosimeters (TLDs), via irradiation and evaluation by the University of Wisconsin-Madison Radiation Calibration Laboratory at the University of Wisconsin Medical Radiation Research Center.

Table A-3 lists results of the analyses on in-house spiked samples for the past twelve months. All samples are prepared using NIST traceable sources. Data for previous years available upon request.

Table A-4 lists results of the analyses on in-house blank samples for the past twelve months. Data for previous years available upon request.

Table A-5 lists analytical results from the in-house duplicate program for the past twelve months. Acceptance is based on the difference of the results being less than the sum of the errors.

Complete analytical data for duplicate analyses is available upon request.

The results in Table A-6 were obtained through participation in the Mixed Analyte Performance Evaluation Program.

Results in Table A-7 were obtained through participation in the MRAD PT Study Proficiency Testing Program administered by Environmental Resource Associates, serving as a replacement for studies conducted previously by the Environmental Measurement Laboratory Quality Assessment Program (EML).

Attachment A lists the laboratory acceptance criteria for various analyses.

Out-of-limit results are explained directly below the result.

Appendix A Interlaboratory/ Intralaboratory Comparison Program Results

A-2 Analysis Ratio of lab result to known value.

Gamma Emitters 0.8 to 1.2 Strontium-89, 0.8 to 1.2 Strontium-90 Potassium-40 0.8 to 1.2 Gross alpha 0.5 to 1.5 Gross beta 0.8 to 1.2 Tritium 0.8 to 1.2 Radium-226, 0.7 to 1.3 Radium-228 Plutonium 0.8 to 1.2 Iodine-129, 0.8 to 1.2 Iodine-131 Nickel-63, 0.7 to 1.3 Technetium-99, Uranium-238 Iron-55 0.8 to 1.2 Other Analyses 0.8 to 1.2 Attachment A ACCEPTANCE CRITERIA FOR SPIKED SAMPLES

A-3 TABLE A-1. Interlaboratory Comparison Crosscheck program, Environmental Resource Associates (ERA)a.

RAD study Lab Code Date Analysis ERA Result Acceptance ERW-71 1/7/2019 Ba-133 97.9 +/- 4.5 99.5 84.1 - 109 Pass ERW-71 1/7/2019 Cs-134 45.4 +/- 3.1 49.1 39.5 - 54.0 Pass ERW-71 1/7/2019 Cs-137 129 +/- 6 125 112 - 140 Pass ERW-71 1/7/2019 Co-60 98.1 +/- 4.1 96.4 86.8 - 108 Pass ERW-71 1/7/2019 Zn-65 80.4 +/- 7.8 77.4 69.5 +/- 93.2 Pass ERW-73 1/7/2019 Gr. Alpha 22.2 +/- 1.6 21.8 10.9 - 29.5 Pass ERW-73 1/7/2019 Gr. Beta 46.4 +/- 1.4 55.7 38.1 - 62.6 Pass ERW-75 1/7/2019 Ra-226 7.19 +/- 0.30 7.37 5.55 +/- 8.72 Pass ERW-75 1/7/2019 Ra-228 4.02 +/- 0.70 4.28 2.48 - 5.89 Pass ERW-75 1/7/2019 Uranium 50.2 +/- 2.9 68.2 55.7 - 75.0 Failb ERW-77 1/7/2019 H-3 2,129 +/- 158 2,110 1,740 - 2,340 Pass ERW-397 2/11/2019 I-131 27.2 +/- 1.0 25.9 25.1 - 30.6 Pass ERW-1141 4/8/2019 Ra-226 7.58 +/- 0.53 7.15 5.39 - 8.48 Pass ERW-1141 4/8/2019 Ra-228 2.64 +/- 0.79 2.94 1.54 - 4.35 Pass ERW-1141 4/8/2019 Uranium 67.0 +/- 0.9 55.9 45.6 - 61.5 Failc ERW-2471 7/8/2019 Ba-133 66.5 +/- 4.0 66.9 55.8 - 73.6 Pass ERW-2471 7/8/2019 Cs-134 29.6 +/- 2.6 32.0 25.1 - 35.2 Pass ERW-2471 7/8/2019 Cs-137 21.3 +/- 3.6 21.4 17.6 - 26.7 Pass ERW-2471 7/8/2019 Co-60 99.9 +/- 4.4 95.1 85.6 - 107.0 Pass ERW-2471 7/8/2019 Zn-65 43.7 +/- 6.2 41.2 35.3 - 51.4 Pass ERW-2473 7/8/2019 Gr. Alpha 41.7 +/- 2.1 70.6 37.1 - 87.1 Pass ERW-2473 7/8/2019 Gr. Beta 57.0 +/- 1.6 63.9 44.2 - 70.5 Pass ERW-2477 7/8/2019 Ra-226 16.2 +/- 0.5 18.5 13.8 - 21.1 Pass ERW-2477 7/8/2019 Ra-228 6.2 +/- 0.8 8.2 5.2 - 10.3 Pass ERW-2477 7/8/2019 Uranium 63.8 +/- 3.6 68.3 55.8 - 75.1 Pass ERW-2479 7/8/2019 H-3 8,630 +/- 200 16,700 14,600 - 18,400 Faild ERW-2475 7/8/2019 I-131 33.6 +/- 1.3 29.6 24.6 - 34.6 Pass a Results obtained by Environmental, Inc., Midwest Laboratory as a participant in the crosscheck program for proficiency testing in drinking water conducted by Environmental Resource Associates (ERA).

b In order to get to the root cause of the above "Fail" resolution the U-232 tracer was standardized using a known concentration of NIST U-238 solution. A duplicate analysis was performed and the results obtained were well within the acceptance range (Known value for Total Uranium=68.2 pCi/L, acceptance range of (55.7-75 pCi/L). The results obtained were 63.3 pCi/L and 66.0 pCi/L respectively.

c The standardized U-232 value utilized on ERA sample ERW-75 (see footnote "b" above was found to be estimated high due to interferences in the U-238 solution causing the ERW-1141 Uranium PT failure above. After performing U-isotopic chemistry on the NIST-Uranium solution to remove interferences a more accurate U-232 tracer concentration was obtained. The subsequent ERA PT study was acceptable. See ERW-2477 Uranium result above.

d H-3 analysis was performed using the ERA provided blank sample. Pairing the ERA supplied blank and the lab routine blank with standard vials created confusion and resulted in the standard total count time being mistallied by half.

The resulting batch efficiency was overstated by a factor of two and the reported ERA results were understated by half.

The result of reanalysis, (17,400 pCi/L), is within the control limits for the study.

Concentration (pCi/L)

Laboratory Control Result Limits

A-4 TABLE A-2. Thermoluminescent Dosimetry, (TLD, CaSO4: Dy Cards).a Lab Code Irradiation Delivered Reportedb Date Description Dose Dose Environmental, Inc.

Group 1 2018-1 11/15/2018 Spike 1 97.0 81.6

-0.16 2018-1 11/15/2018 Spike 2 97.0 88.5

-0.09 2018-1 11/15/2018 Spike 3 97.0 87.9

-0.09 2018-1 11/15/2018 Spike 4 97.0 85.6

-0.12 2018-1 11/15/2018 Spike 5 97.0 86.5

-0.11 2018-1 11/15/2018 Spike 6 97.0 89.0

-0.08 2018-1 11/15/2018 Spike 7 97.0 85.1

-0.12 2018-1 11/15/2018 Spike 8 97.0 90.6

-0.07 2018-1 11/15/2018 Spike 9 97.0 91.3

-0.06 2018-1 11/15/2018 Spike 10 97.0 84.5

-0.13 2018-1 11/15/2018 Spike 11 97.0 90.8

-0.06 2018-1 11/15/2018 Spike 12 97.0 93.8

-0.03 2018-1 11/15/2018 Spike 13 97.0 85.3

-0.12 2018-1 11/15/2018 Spike 14 97.0 85.5

-0.12 2018-1 11/15/2018 Spike 15 97.0 86.9

-0.10 2018-1 11/15/2018 Spike 16 97.0 88.6

-0.09 2018-1 11/15/2018 Spike 17 97.0 83.1

-0.14 2018-1 11/15/2018 Spike 18 97.0 85.4

-0.12 2018-1 11/15/2018 Spike 19 97.0 83.3

-0.14 2018-1 11/15/2018 Spike 20 97.0 85.5

-0.12 Mean (Spike 1-20) 86.9

-0.10 Passd Standard Deviation (Spike 1-20) 3.1 0.03 Passd a TLD's were irradiated by the University of Wisconsin-Madison Radiation Calibration Laboratory following ANSI N13.37 protocol from a known air kerma rate. TLD's were read and the results were submitted by Environmental Inc. to the University of Wisconsin-Madison Radiation Calibration Laboratory for comparison to the delivered dose.

b Reported dose was converted from exposure (R) to Air Kerma (cGy) using a conversion of 0.876. Conversion from air kerma to ambient dose equivalent for Cs-137 at the reference dose point H*(10)Ka = 1.20. mrem/cGy = 1000.

c Performance Quotient (P) is calculated as ((reported dose - conventially true value) ÷ conventially true value) where the conventially true value is the delivered dose.

d Acceptance is achieved when neither the absolute value of mean of the P values, nor the standard deviation of the P values exceed 0.15.

mrem Performancec Quotient (P)

A-5 TABLE A-2. Thermoluminescent Dosimetry, (TLD, CaSO4: Dy Cards).a Lab Code Irradiation Delivered Reportedb Date Description Dose Dose Environmental, Inc.

Group 2 2018-2 11/15/2018 Spike 21 143.0 130.3

-0.09 2018-2 11/15/2018 Spike 22 143.0 128.1

-0.10 2018-2 11/15/2018 Spike 23 143.0 134.4

-0.06 2018-2 11/15/2018 Spike 24 143.0 129.0

-0.10 2018-2 11/15/2018 Spike 25 143.0 132.5

-0.07 2018-2 11/15/2018 Spike 26 143.0 126.1

-0.12 2018-2 11/15/2018 Spike 27 143.0 126.2

-0.12 2018-2 11/15/2018 Spike 28 143.0 122.4

-0.14 2018-2 11/15/2018 Spike 29 143.0 118.8

-0.17 2018-2 11/15/2018 Spike 30 143.0 123.2

-0.14 2018-2 11/15/2018 Spike 31 143.0 137.2

-0.04 2018-2 11/15/2018 Spike 32 143.0 144.4 0.01 2018-2 11/15/2018 Spike 33 143.0 137.8

-0.04 2018-2 11/15/2018 Spike 34 143.0 140.2

-0.02 2018-2 11/15/2018 Spike 35 143.0 143.8 0.01 2018-2 11/15/2018 Spike 36 143.0 146.7 0.03 2018-2 11/15/2018 Spike 37 143.0 150.0 0.05 2018-2 11/15/2018 Spike 38 143.0 126.1

-0.12 2018-2 11/15/2018 Spike 39 143.0 136.2

-0.05 2018-2 11/15/2018 Spike 40 143.0 144.8 0.01 Mean (Spike 21-40) 133.9

-0.06 Passd Standard Deviation (Spike 21-40) 9.0 0.06 Passd a TLD's were irradiated by the University of Wisconsin-Madison Radiation Calibration Laboratory following ANSI N13.37 protocol from a known air kerma rate. TLD's were read and the results were submitted by Environmental Inc. to the University of Wisconsin-Madison Radiation Calibration Laboratory for comparison to the delivered dose.

b Reported dose was converted from exposure (R) to Air Kerma (cGy) using a conversion of 0.876. Conversion from air kerma to ambient dose equivalent for Cs-137 at the reference dose point H*(10)Ka = 1.20. mrem/cGy = 1000.

c Performance Quotient (P) is calculated as ((reported dose - conventially true value) ÷ conventially true value) where the conventially true value is the delivered dose.

d Acceptance is achieved when neither the absolute value of mean of the P values, nor the standard deviation of the P values exceed 0.15.

mrem Performancec Quotient (P)

A-6 TABLE A-3. In-House "Spiked" Samples Lab Codeb Date Analysis Known Ratio Activity Acceptance Lab/Known SPW-3991 10/1/2018 H-3 15,614 +/- 369 16,507 13,206 - 19,808 Pass 0.95 SPW-4105 10/5/2018 H-3 15,669 +/- 370 16,507 13,206 - 19,808 Pass 0.95 W-101118 4/29/2016 Cs-134 33.5 +/- 3.1 36.2 29.0 - 43.4 Pass 0.92 W-101118 4/29/2016 Cs-137 79.7 +/- 3.2 71.9 57.5 - 86.3 Pass 1.11 SPW-4205 10/12/2018 H-3 15,821 +/- 372 16,507 13,206 - 19,808 Pass 0.96 SPW-4274 10/17/2018 H-3 15,575 +/- 369 16,507 11,555 - 21,459 Pass 0.94 SPW-4596 10/31/2018 H-3 15,650 +/- 369 16,507 13,206 - 19,808 Pass 0.95 SPW-4682 11/1/2018 H-3 15,742 +/- 371 16,507 13,206 - 19,808 Pass 0.95 SPW-4684 11/1/2018 Sr-90 19.1 +/- 1.2 17.9 14.3 - 21.5 Pass 1.07 SPW-4790 11/9/2018 H-3 15,887 +/- 373 16,507 13,206 - 19,808 Pass 0.96 SPW-4839 11/13/2018 Ni-63 381 +/- 43 465 326 - 605 Pass 0.82 SPW-4863 11/16/2018 H-3 15,610 +/- 370 16,507 13,206 - 19,808 Pass 0.95 W-111618 4/29/2016 Cs-134 38.0 +/- 12.4 36.2 25.3 - 47.1 Pass 1.05 W-111618 4/29/2016 Cs-137 83.8 +/- 13.8 71.9 57.5 - 86.3 Pass 1.17 SPW-5049 11/30/2018 H-3 15,370 +/- 366 16,507 13,206 - 19,808 Pass 0.93 SPW-5148 12/7/2018 H-3 15,522 +/- 368 16,507 13,206 - 19,808 Pass 0.94 W-121118 4/29/2016 Cs-134 39.4 +/- 7.9 36.2 29.0 - 43.4 Pass 1.09 W-121118 4/29/2016 Cs-137 78.5 +/- 7.7 71.9 57.5 - 86.3 Pass 1.09 W-121218 4/29/2016 Cs-134 42.0 +/- 13.8 36.2 25.3 - 47.1 Pass 1.16 W-121218 4/29/2016 Cs-137 79.2 +/- 13.1 71.9 57.5 - 86.3 Pass 1.10 W-121318 4/29/2016 Cs-134 35.1 +/- 7.8 36.2 25.3 - 47.1 Pass 0.97 W-121318 4/29/2016 Cs-137 77.5 +/- 8.4 71.9 50.3 - 93.5 Pass 1.08 SPW-5279 12/14/2018 H-3 15,686 +/- 370 16,507 13,206 - 19,808 Pass 0.95 W-121418 4/29/2016 Cs-134 34.5 +/- 8.2 36.2 29.0 - 43.4 Pass 0.95 W-121418 4/29/2016 Cs-137 82.7 +/- 8.0 71.9 57.5 - 86.3 Pass 1.15 W-121718 4/29/2016 Cs-134 34.9 +/- 10.5 36.2 29.0 - 43.4 Pass 0.96 W-121718 4/29/2016 Cs-137 80.3 +/- 8.1 71.9 57.5 - 86.3 Pass 1.12 SPW-5351 12/19/2018 H-3 15,855 +/- 375 16,507 13,206 - 19,808 Pass 0.96 SPW-5404 12/31/2018 H-3 15,179 +/- 365 16,507 13,206 - 19,808 Pass 0.92 SPW-5450 12/31/2018 Gr. Alpha 56.5 +/- 2.6 72.4 36.2 - 108.6 Pass 0.78 SPW-5450 12/31/2018 Gr. Beta 45.1 +/- 1.4 54.8 43.8 - 65.8 Pass 0.82 SPW-5615 12/31/2018 Fe-55 831.0 +/- 43.5 732.6 586.0 - 879.1 Pass 1.13 SPW-5619 12/31/2018 Tc-99 99.0 +/- 1.7 107.8 86.2 - 129.4 Pass 0.92 SPW-61 11/5/2018 Ra-226 13.4 +/- 0.4 12.3 8.6 - 16.0 Pass 1.09 SPW-118 1/14/2019 H-3 15,463 +/- 369 16,507 13,206 - 19,808 Pass 0.94 SPW-178 1/16/2019 Ra-228 17.7 +/- 2.1 15.1 10.58 - 19.66 Pass 1.17 SPW-199 1/18/2019 Sr-90 17.6 +/- 1.2 17.9 14.3 - 21.5 Pass 0.98 SPW-250 1/24/2019 Ni-63 356.3 +/- 44.5 465 326 - 605 Pass 0.77 SPW-256 1/15/2019 Ra-226 12.0 +/- 0.4 12.3 8.6 - 16.0 Pass 0.98 SPW-271 3/18/2019 H-3 22,035 +/- 450 21,700 17,360 - 26,040 Pass 1.02 SPW-281 1/25/2019 Ra-226 11.6 +/- 0.4 12.3 8.6 - 16.0 Pass 0.94 W-012119 4/29/2016 Cs-134 37.3 +/- 10.6 36.2 29.0 - 43.4 Pass 1.03 W-012119 4/29/2016 Cs-137 82.7 +/- 8.0 71.9 57.5 - 86.3 Pass 1.15 W-012319 4/29/2016 Cs-134 33.4 +/- 10.1 36.2 25.3 - 47.1 Pass 0.92 W-012319 4/29/2016 Cs-137 79.1 +/- 9.6 71.9 57.5 - 86.3 Pass 1.10 W-012519 4/29/2016 Cs-134 35.0 +/- 7.7 36.2 29.0 - 43.4 Pass 0.97 W-012519 4/29/2016 Cs-137 79.2 +/- 7.9 71.9 57.5 - 86.3 Pass 1.10 W-012919 4/29/2016 Cs-134 32.3 +/- 8.3 36.2 29.0 - 43.4 Pass 0.89 W-012919 4/29/2016 Cs-137 82.3 +/- 8.3 71.9 57.5 - 86.3 Pass 1.14 Concentrationa Laboratory results Control 2s, n=1c Limitsd

A-7 TABLE A-3. In-House "Spiked" Samples Lab Codeb Date Analysis Known Ratio Activity Acceptance Lab/Known SPW-370 3/19/2019 H-3 21,689 +/- 444 21,700 17,360 - 26,040 Pass 1.00 SPW-400 1/31/2019 Ra-226 11.6 +/- 0.4 12.3 8.6 - 16.0 Pass 0.95 SPW-461 2/12/2019 Ra-226 11.1 +/- 0.4 12.3 8.6 - 16.0 Pass 0.90 W-020619 4/26/2016 Cs-134 35.0 +/- 14.9 36.2 29.0 - 43.4 Pass 0.97 W-020619 4/29/2016 Cs-137 72.8 +/- 8.9 71.9 57.5 - 86.3 Pass 1.01 W-020819 4/26/2016 Cs-134 36.7 +/- 8.6 36.2 29.0 - 43.4 Pass 1.01 W-020819 4/29/2016 Cs-137 76.7 +/- 8.7 71.9 57.5 - 86.3 Pass 1.07 SPW-568 2/21/2019 Ra-226 10.3 +/- 0.3 12.3 8.6 - 16.0 Pass 0.84 W-021319 4/29/2016 Cs-134 37.7 +/- 11.5 36.2 29.0 - 43.4 Pass 1.04 W-021319 4/26/2016 Cs-137 75.8 +/- 9.6 71.9 57.5 - 86.3 Pass 1.05 SPW-469 3/19/2019 H-3 21,696 +/- 447 21,700 17,360 - 26,040 Pass 1.00 SPW-600 3/6/2019 H-3 20,710 +/- 425 21,700 17,360 - 26,040 Pass 0.95 SPW-837 3/21/2019 Ra-228 11.7 +/- 1.5 15.1 10.58 - 19.66 Pass 0.78 SPW-709 3/19/2019 H-3 20,369 +/- 421 21,700 17,360 - 26,040 Pass 0.94 SPW-818 3/19/2019 H-3 20,457 +/- 424 21,700 17,360 - 26,040 Pass 0.94 SPW-844 3/22/2019 U-234 15.1 +/- 0.5 13.6 9.5 - 17.7 Pass 1.11 SPW-844 3/22/2019 U-238 15.3 +/- 0.5 13.1 9.2 - 17.0 Pass 1.17 SPW-934 3/19/2019 H-3 20,487 +/- 421 21,700 17,360 - 26,040 Pass 0.94 SPW-1061 3/1/2019 Ra-226 10.6 +/- 0.3 12.3 8.6 - 16.0 Pass 0.86 SPW-1091 4/10/2019 H-3 20,323 +/- 421 21,700 17,360 - 26,040 Pass 0.94 SPW-1093 4/8/2019 Ra-228 14.9 +/- 1.9 15.1 10.6 - 19.6 Pass 0.98 SPW-1267 4/16/2019 H-3 20,302 +/- 421 21,700 17,360 - 26,040 Pass 0.94 SPW-1339 4/18/2019 H-3 19,924 +/- 417 21,700 17,360 - 26,040 Pass 0.92 SPW-1403e 4/25/2019 Gr. Alpha 56.7 +/- 2.6 72.4 36.2 - 108.6 Pass 0.78 SPW-1403e 4/25/2019 Gr. Beta 43.2 +/- 1.4 54.8 43.8 - 65.8 Fail 0.79 SPW-1427 4/26/2019 H-3 20,119 +/- 418 21,700 15,190 - 28,210 Pass 0.93 SPW-1537 5/6/2019 Sr-90 19.9 +/- 1.2 17.9 14.3 - 21.5 Pass 1.11 W-050719 4/29/2016 Cs-134 38.5 +/- 9.0 36.2 29.0 - 43.4 Pass 1.06 W-050719 4/26/2016 Cs-137 85.2 +/- 8.5 71.9 57.5 - 86.3 Pass 1.18 SPW-1582 5/9/2019 H-3 20,492 +/- 423 21,700 15,190 - 28,210 Pass 0.94 W-050919 4/29/2016 Cs-134 37.4 +/- 8.9 36.2 29.0 - 43.4 Pass 1.03 W-050919 4/26/2016 Cs-137 81.5 +/- 7.8 71.9 57.5 - 86.3 Pass 1.13 SPW-1596 5/8/2019 Ra-228 14.1 +/- 1.7 15.1 10.6 - 19.6 Pass 0.94 W-051419 4/29/2016 Cs-134 36.2 +/- 11.7 36.2 29.0 - 43.4 Pass 1.00 W-051419 4/26/2016 Cs-137 75.8 +/- 10.0 71.9 57.5 - 86.3 Pass 1.05 SPW-1676 5/17/2019 H-3 20,233 +/- 420 21,700 15,190 - 28,210 Pass 0.93 SPW-1799 5/20/2019 H-3 20,428 +/- 422 21,700 15,190 - 28,210 Pass 0.94 SPW-1858 5/28/2019 H-3 20,367 +/- 522 21,700 15,190 - 28,210 Pass 0.94 SPW-1890 5/30/2019 H-3 20,206 +/- 419 21,700 15,190 - 28,210 Pass 0.93 SPW-2014 5/31/2019 Ra-226 11.9 +/- 0.3 12.3 8.6 - 16.0 Pass 0.97 SPW-2030 6/12/2019 Ni-63 377 +/- 45 464.8 325 - 604 Pass 0.81 SPW-2093 6/18/2019 H-3 20,158 +/- 418 21,700 15,190 - 28,210 Pass 0.93 W-062419 4/29/2016 Cs-134 33.0 +/- 12.4 36.2 29.0 - 43.4 Pass 0.91 W-062419 4/26/2016 Cs-137 66.0 +/- 10.4 71.9 57.5 - 86.3 Pass 0.92 SPW-2338 6/26/2019 H-3 20,032 +/- 417 21,700 15,190 - 28,210 Pass 0.92 Laboratory results Control 2s, n=1c Limitsd Concentrationa

A-8 TABLE A-3. In-House "Spiked" Samples Lab Codeb Date Analysis Known Ratio Activity Acceptance Lab/Known W-072619 4/29/2016 Cs-134 36.3 +/- 9.2 36.2 29.0 - 43.4 Pass 1.00 W-072619 4/26/2016 Cs-137 79.7 +/- 7.6 71.9 57.5 - 86.3 Pass 1.11 SPW-3188 7/30/2019 Ra-226 11.9 +/- 0.3 12.3 8.6 - 16.0 Pass 0.97 SPW-2925 8/6/2019 Sr-90 10.7 +/- 1.0 SPW-2947 8/9/2019 H-3 20,128 +/- 425 21,700 15,190 - 28,210 Pass 0.93 SPW-3003 8/14/2019 H-3 20,588 +/- 435 21,700 15,190 - 28,210 Pass 0.95 W-081519 4/26/2019 Cs-134 36.2 +/- 9.2 36.2 29.0 - 43.4 Pass 1.00 W-081519 4/26/2019 Cs-137 78.1 +/- 8.4 71.9 57.5 - 86.3 Pass 1.09 W-082119 4/26/2019 Cs-134 32.8 +/- 9.1 36.2 29.0 - 43.4 Pass 0.91 W-082119 4/26/2019 Cs-137 79.1 +/- 7.9 71.9 57.5 - 86.3 Pass 1.10 SPW-3151 8/26/2019 H-3 20,329 +/- 428 21,700 15,190 - 28,210 Pass 0.94 W-082619 4/26/2019 Cs-134 33.3 +/- 17.8 36.2 29.0 - 43.4 Pass 0.92 W-082619 4/26/2019 Cs-137 82.6 +/- 13.2 71.9 57.5 - 86.3 Pass 1.15 W-082719 4/26/2019 Cs-134 33.9 +/- 7.0 36.2 29.0 - 43.4 Pass 0.94 W-082719 4/26/2019 Cs-137 81.4 +/- 6.0 71.9 57.5 - 86.3 Pass 1.13 SPW-3359 8/30/2019 Gr. Alpha 54.2 +/- 0.3 72.4 36.2 - 108.6 Pass 0.75 SPW-3359 8/30/2019 Gr. Beta 59.7 +/- 0.2 54.8 43.8 - 65.8 Pass 1.09 SPW-3323 9/6/2019 Ra-228 12.7 +/- 1.8 15.1 10.6 - 19.6 Pass 0.84 W-091019 4/26/2019 Cs-134 31.0 +/- 11.3 36.2 29.0 - 43.4 Pass 0.86 W-091019 4/26/2019 Cs-137 80.5 +/- 10.0 71.9 57.5 - 86.3 Pass 1.12 SPW-3349 9/10/2019 H-3 19,851 +/- 422 21,700 15,190 - 28,210 Pass 0.91 SPW-3410 9/13/2019 H-3 20,267 +/- 431 21,700 15,190 - 28,210 Pass 0.93 W-091719 4/26/2019 Cs-134 39.3 +/- 12.6 36.2 29.0 - 43.4 Pass 1.09 W-091719 4/26/2019 Cs-137 81.1 +/- 9.9 71.9 57.5 - 86.3 Pass 1.13 SPW-3450 9/17/2019 H-3 20,036 +/- 427 21,700 15,190 - 28,210 Pass 0.92 W-091919 9/19/2019 Cs-134 40.0 +/- 10.7 36.2 29.0 - 43.4 Pass 1.10 W-091919 9/19/2019 Cs-137 71.0 +/- 8.7 71.9 57.5 - 86.3 Pass 0.99 SPW-3569 8/28/2019 Ra-226 11.9 +/- 0.3 12.3 8.6 - 16.0 Pass 0.97 SPW-3571 9/27/2019 H-3 21,026 +/- 440 21,700 15,190 - 28,210 Pass 0.97 a Liquid sample results are reported in pCi/Liter, air filters ( pCi/m3), charcoal (pCi/charcoal canister), and solid samples (pCi/kg).

b Laboratory codes : W & SPW (Water), MI (milk), AP (air filter), SO (soil), VE (vegetation), CH (charcoal canister), F (fish), U (urine).

c Results are based on single determinations.

d Control limits are listed in Attachment A of this report.

e The LCS sample was prepared from an Environmental Resource Associates (ERA) sample of known activity. While the analysis did satisfy the acceptance criteria of the ERA study from which it was sourced, it did not satisfy EIML's internal LCS acceptance criteria. All of the original solution had been consumed in the analysis. Subsequent gross alpha and beta PT and LCS sample results were acceptable.

NOTE: For fish, gelatin is used for the spike matrix. For vegetation, cabbage is used for the spike matrix.

2s, n=1c Limitsd Concentrationa Laboratory results Control

A-9 TABLE A-4. In-House "Blank" Samples Lab Codeb Sample Date Analysisc Type LLD SPW-3990 Water 10/1/2018 H-3 153

-6 +/- 71 200 SPW-4105 Water 10/5/2018 H-3 150 7 +/- 71 200 SPW-4565 Water 10/11/2018 Ra-228 0.86

-0.26 +/- 0.36 2

SPW-4205 Water 10/12/2018 H-3 154

-9 +/- 71 200 SPW-4273 Water 10/17/2018 H-3 153 67 +/- 76 200 SPW-4595 Water 10/30/2018 H-3 150 75 +/- 74 200 SPW-4681 Water 11/1/2018 H-3 152 19 +/- 72 200 SPW-4683 Water 11/1/2018 Sr-89 0.64 0.25 +/- 0.45 5

SPW-4683 Water 11/1/2018 Sr-90 0.51

-0.10 +/- 0.22 1

SPW-4789 Water 11/9/2018 H-3 148 27 +/- 73 200 SPW-4799 Water 11/9/2018 I-131 0.43

-0.01 +/- 0.20 1

SPW-4838 Water 11/13/2018 Ni-63 62 34 +/- 38 200 SPW-4862 Water 11/16/2018 H-3 154 15 +/- 77 200 SPW-5028 Water 11/19/2018 Ra-226 0.04

-0.14 +/- 0.03 2

SPW-5028 Water 11/19/2018 Ra-228 0.96

-0.11 +/- 0.43 2

SPW-5048 Water 11/30/2018 H-3 151

-6 +/- 69 200 SPW-5147 Water 12/7/2018 H-3 151 14 +/- 71 200 SPW-5278 Water 12/14/2018 H-3 153 83 +/- 76 200 SPW-5350 Water 12/19/2018 H-3 153 71 +/- 75 200 SPW-5403 Water 12/31/2018 H-3 156 51 +/- 75 200 SPW-5614 Water 12/31/2018 Fe-55 612

-68 +/- 368 1000 SPW-5618 Water 12/31/2018 Tc-99 11 7 +/- 7 100 SPW-34 Water 1/7/2019 I-131 0.36 0.13 +/- 0.18 1

SPW-60 Water 11/5/2019 Ra-226 0.03 0.15 +/- 0.03 2

SPW-119 Water 1/14/2019 H-3 148 42 +/- 80 200 SPW-177 Water 1/16/2019 Ra-228 0.93

-0.10 +/- 0.42 2

SPW-198 Water 1/18/2019 Sr-89 0.67 0.25 +/- 0.50 5

SPW-198 Water 1/18/2019 Sr-90 0.67

-0.16 +/- 0.29 1

SPW-249 Water 1/24/2019 Ni-63 67 31 +/- 41 200 SPW-255 Water 1/15/2019 Ra-226 0.04 0.16 +/- 0.03 2

SPW-280 Water 1/25/2019 Ra-226 0.06

-0.09 +/- 0.14 2

SPW-399 Water 1/31/2019 Ra-226 0.03 0.15 +/- 0.03 2

SPW-460 Water 2/12/2019 Ra-226 0.03 0.15 +/- 0.02 2

SPW-567 Water 2/21/2019 Ra-226 0.03 0.13 +/- 0.02 2

SPW-844 Water 3/22/2019 U-234 0.19 0.04 +/- 0.14 1

SPW-844 Water 3/22/2019 U-238 0.19 0.00 +/- 0.11 1

SPW-836 Water 3/21/2019 Ra-228 0.74 0.53 +/- 0.41 2

SPW-1060 Water 3/31/2019 Ra-226 0.04

-0.02 +/- 0.03 2

a Liquid sample results are reported in pCi/Liter, air filters ( pCi/m3), charcoal (pCi/charcoal canister), and solid samples (pCi/g).

b Laboratory codes : W & SPW (Water), MI (milk), AP (air filter), SO (soil), VE (vegetation), CH (charcoal canister), F (fish), U (urine).

c I-131(G); iodine-131 as analyzed by gamma spectroscopy.

d Activity reported is a net activity result.

Concentrationa Laboratory results (4.66s)

Acceptance Activityd Criteria (4.66 s)

A-10 TABLE A-4. In-House "Blank" Samples Lab Codeb Sample Date Analysisc Type LLD SPW-1090 Water 4/10/2019 H-3 155

-14 +/- 72 200 SPW-1092 Water 4/8/2019 Ra-228 0.82 0.75 +/- 0.46 2

SPW-1266 Water 4/16/2019 H-3 152 67 +/- 74 200 SPW-1338 Water 4/18/2019 H-3 152 66 +/- 79 200 SPW-1386 Water 4/8/2019 Ra-226 0.03 0.09 +/- 0.03 2

SPW-1426 Water 4/26/2019 H-3 156 34 +/- 75 200 SPW-1536 Water 5/6/2019 Sr-89 0.66

-0.07 +/- 0.45 5

SPW-1536 Water 5/6/2019 Sr-90 0.59

-0.10 +/- 0.26 1

SPW-1581 Water 5/9/2019 H-3 147 73 +/- 77 200 SPW-1644 Water 4/22/2019 Ra-226 0.02 0.15 +/- 0.02 2

SPW-1675 Water 5/17/2019 H-3 154

-30 +/- 71 200 SPW-1798 Water 5/20/2019 H-3 149 24 +/- 73 200 SPW-1857 Water 5/28/2019 H-3 150 54 +/- 74 200 SPW-1889 Water 5/30/2019 H-3 152 45 +/- 73 200 SPW-2013 Water 5/31/2019 Ra-226 0.01 0.13 +/- 0.02 2

SPW-2029 Water 6/12/2019 Ni-63 66 10 +/- 40 200 SPW-2092 Water 6/18/2019 H-3 154

-42 +/- 70 200 SPW-2237 Water 6/26/2019 H-3 150

-9 +/- 69 200 SPW-2107 Water 6/18/2019 I-131 0.16 0.04 +/- 0.09 1

SPW-2152 Water 6/19/2019 I-131 0.16 0.04 +/- 0.09 1

SPW-3187 Water 7/30/2019 Ra-226 0.02 0.17 +/- 0.02 2

SPW-2924 Water 8/6/2019 Sr-89 0.71

-0.06 +/- 0.57 5

SPW-2924 Water 8/6/2019 Sr-90 0.59 0.08 +/- 0.28 1

SPW-2946 Water 8/9/2019 H-3 152 33 +/- 72 200 SPW-3002 Water 8/14/2019 H-3 152

-22 +/- 74 200 SPW-3150 Water 8/26/2019 H-3 151 115 +/- 77 200 SPW-3358 Water 8/30/2019 Gr. Alpha 0.44

-0.08 +/- 0.30 2

SPW-3358 Water 8/30/2019 Gr. Beta 0.72

-0.31 +/- 0.49 4

SPW-3568 Water 8/28/2019 Ra-226 0.03 0.16 +/- 0.03 2

SPW-3348 Water 9/10/2019 H-3 150 107 +/- 76 200 SPW-3409 Water 9/13/2019 H-3 154 133 +/- 79 200 SPW-3449 Water 9/17/2019 H-3 147 102 +/- 79 200 SPW-3570 Water 9/27/2019 H-3 151 70 +/- 77 200 a Liquid sample results are reported in pCi/Liter, air filters ( pCi/m3), charcoal (pCi/charcoal canister), and solid samples (pCi/g).

b Laboratory codes : W & SPW (Water), MI (milk), AP (air filter), SO (soil), VE (vegetation), CH (charcoal canister), F (fish), U (urine).

c I-131(G); iodine-131 as analyzed by gamma spectroscopy.

d Activity reported is a net activity result.

Concentrationa Laboratory results (4.66s)

Acceptance Activityd Criteria (4.66 s)

A-11 TABLE A-5. In-House "Duplicate" Samples Lab Codeb Date Analysis Acceptance DW-90173,90174 10/24/2018 Ra-226 1.13 +/- 0.15 1.38 +/- 0.17 1.26 +/- 0.11 Pass DW-90173,90174 10/24/2018 Ra-228 5.09 +/- 0.84 6.59 +/- 0.89 5.84 +/- 0.61 Pass SW-4782,4783 11/7/2018 H-3 192 +/- 82 238 +/- 84 215 +/- 59 Pass WW-4959,4960 11/13/2018 H-3 330 +/- 88 286 +/- 86 308 +/- 61 Pass SG-4850,4851 11/14/2018 Pb-214 15.0 +/- 0.4 14.7 +/- 0.4 14.9 +/- 0.3 Pass SG-4850,4851 11/14/2018 Ac-228 17.5 +/- 0.7 16.7 +/- 0.6 17.1 +/- 0.5 Pass VE-4917,4918 11/20/2018 K-40 4.54 +/- 0.45 4.05 +/- 0.46 4.30 +/- 0.32 Pass VE-4917,4918 11/20/2018 Be-7 9.42 +/- 0.45 9.42 +/- 0.46 9.42 +/- 0.32 Pass SO-5024,5025 11/14/2018 K-40 6.60 +/- 0.54 6.26 +/- 0.58 6.43 +/- 0.40 Pass SG-5046,5047 11/21/2018 K-40 8.65 +/- 1.18 9.12 +/- 1.02 8.88 +/- 0.78 Pass SG-5046,5047 11/21/2018 Cs-137 0.18 +/- 0.06 0.10 +/- 0.05 0.14 +/- 0.04 Pass SG-5046,5047 11/21/2018 Gr. Alpha 22.8 +/- 5.6 17.5 +/- 4.8 20.2 +/- 3.7 Pass SG-5046,5047 11/21/2018 Gr. Beta 31.8 +/- 3.5 26.8 +/- 3.1 29.3 +/- 2.4 Pass SG-6286,6287 12/1/2018 Pb-214 11.3 +/- 0.4 10.7 +/- 0.5 11.0 +/- 0.3 Pass SG-6286,6287 12/1/2018 Ac-228 13.5 +/- 0.9 13.2 +/- 1.0 13.4 +/- 0.7 Pass SWU-5132,5133 12/4/2018 H-3 159 +/- 82 204 +/- 80 181 +/- 57 Pass SWU-5132,5133 12/4/2018 Gr. Beta 1.32 +/- 0.56 1.33 +/- 0.57 1.32 +/- 0.40 Pass AP-5499,5500 1/2/2019 Fe-55 941 +/- 220 1027 +/- 226 984 +/- 158 Pass AP-5499,5500 1/2/2019 Sr-89 20.2 +/- 7.3 14.9 +/- 5.7 17.5 +/- 4.7 Pass AP-5499,5500 1/2/2019 Ni-63 12.1 +/- 8.5 15.6 +/- 8.5 13.8 +/- 6.0 Pass CF-20,21 1/2/2019 Gr. Beta 10.0 +/- 0.2 10.7 +/- 0.2 10.3 +/- 0.2 Pass CF-20,21 1/2/2019 Sr-90 0.005 +/- 0.002 0.005 +/- 0.002 0.005 +/- 0.001 Pass CF-20,21 1/2/2019 Be-7 0.27 +/- 0.09 0.29 +/- 0.08 0.28 +/- 0.06 Pass CF-20,21 1/2/2019 K-40 6.69 +/- 0.34 6.83 +/- 0.34 6.76 +/- 0.24 Pass SG-211,212 1/21/2019 Ra-226 7.94 +/- 1.15 8.50 +/- 1.11 9.79 +/- 0.19 Pass SG-211,212 1/21/2019 Ac-228 4.46 +/- 0.37 4.63 +/- 0.43 4.55 +/- 0.28 Pass WW-324,325 2/4/2019 Gr. Alpha 0.68 +/- 0.44 0.49 +/- 0.46 0.59 +/- 0.32 Pass WW-324,325 2/4/2019 Gr. Beta 1.80 +/- 0.55 2.95 +/- 0.63 2.37 +/- 0.42 Pass W-345,346 2/4/2019 H-3 245 +/- 84 277 +/- 85 261 +/- 60 Pass WW-797,798 3/5/2019 H-3 165 +/- 80 222 +/- 83 193 +/- 58 Pass WW-648,649 3/8/2019 H-3 587 +/- 101 630 +/- 102 608 +/- 72 Pass SW-713,714 3/14/2019 H-3 326 +/- 90 254 +/- 86 290 +/- 62 Pass AP-1241,1242 4/2/2019 Be-7 0.097 +/- 0.018 0.108 +/- 0.020 0.103 +/- 0.013 Pass AP-1285,1286 4/3/2019 Be-7 0.080 +/- 0.014 0.078 +/- 0.012 0.079 +/- 0.009 Pass AP-1306,1307 4/3/2019 Be-7 0.085 +/- 0.009 0.096 +/- 0.011 0.090 +/- 0.007 Pass AP-1327,1328 4/3/2019 Be-7 0.078 +/- 0.010 0.079 +/- 0.011 0.078 +/- 0.007 Pass AP-1327,1328 4/3/2019 K-40 0.012 +/- 0.007 0.021 +/- 0.010 0.017 +/- 0.006 Pass AP-2119,2120 4/3/2019 Be-7 0.276 +/- 0.098 0.265 +/- 0.116 0.270 +/- 0.076 Pass Concentrationa Averaged First Result Second Result Result

A-12 TABLE A-5. In-House "Duplicate" Samples Lab Codeb Date Analysis Acceptance AP-2225,2226 4/3/2019 Be-7 0.231 +/- 0.128 0.208 +/- 0.123 0.220 +/- 0.089 Pass CF-820,821 4/3/2019 K-40 6.39 +/- 0.30 6.63 +/- 0.37 6.51 +/- 0.24 Pass WW-648,649 4/5/2019 H-3 587 +/- 101 630 +/- 102 608 +/- 72 Pass WW-1043,1044 4/5/2019 H-3 666 +/- 121 662 +/- 121 664 +/- 86 Pass SW-1087,1088 4/8/2019 H-3 9,997 +/- 300 10,330 +/- 305 10,164 +/- 214 Pass WW-1198,1199 4/9/2019 H-3 562 +/- 99 640 +/- 102 601 +/- 71 Pass LW-1503,1504 4/25/2019 Gr. Beta 1.09 +/- 0.55 1.46 +/- 0.57 1.27 +/- 0.39 Pass WW-1789,1790 5/7/2019 H-3 366 +/- 90 400 +/- 92 383 +/- 64 Pass SG-2269,2270 5/7/2019 Pb-214 39.1 +/- 0.5 40.3 +/- 0.5 39.7 +/- 0.4 Pass SG-2269,2270 5/7/2019 Ac-228 53.2 +/- 1.0 57.1 +/- 1.0 55.2 +/- 0.7 Pass DW-10049,10050 5/7/2019 Ra-226 1.31 +/- 0.13 1.66 +/- 0.15 1.49 +/- 0.10 Pass DW-10049,10050 5/7/2019 Ra-228 1.24 +/- 0.52 1.33 +/- 0.53 1.29 +/- 0.37 Pass WW-1690A,B 5/8/2019 H-3 325 +/- 89 303 +/- 93 314 +/- 64 Pass S-1812,1813 5/16/2019 K-40 21.95 +/- 0.92 23.26 +/- 0.95 22.61 +/- 0.66 Pass S-1812,1813 5/16/2019 Cs-137 0.05 +/- 0.03 0.07 +/- 0.04 0.06 +/- 0.02 Pass DW-10053,10054 5/22/2019 Gr. Alpha 0.93 +/- 0.63 1.14 +/- 0.72 1.04 +/- 0.48 Pass DW-10053,10054 5/22/2019 Gr. Beta 1.43 +/- 0.62 1.13 +/- 0.59 1.28 +/- 0.43 Pass W-2053,2054 5/29/2019 H-3 1572 +/- 135 1470 +/- 131 1521 +/- 94 Pass G-1989,1990 6/3/2019 Be-7 0.80 +/- 0.18 0.72 +/- 0.15 0.76 +/- 0.12 Pass G-1989,1990 6/3/2019 K-40 6.15 +/- 0.51 5.98 +/- 0.46 6.065 +/- 0.34 Pass G-1989,1990 6/3/2019 Gr. Beta 7.24 +/- 0.19 7.00 +/- 0.19 7.12 +/- 0.13 Pass WW-2204,2205 6/6/2019 H-3 3861 +/- 194 3722 +/- 191 3792 +/- 136 Pass S-2031,2032 6/10/2019 Pb-214 5.16 +/- 0.19 4.75 +/- 0.22 4.96 +/- 0.15 Pass S-2031,2032 6/10/2019 Ac-228 3.81 +/- 0.31 3.63 +/- 0.33 3.72 +/- 0.23 Pass S-2010,2011 6/10/2019 Pb-214 1.48 +/- 0.10 1.05 +/- 0.11 1.27 +/- 0.07 Pass F-2140,2141 6/12/2019 K-40 1.01 +/- 0.28 1.39 +/- 0.32 1.20 +/- 0.21 Pass S-2162,2163 6/12/2019 Pb-214 0.65 +/- 0.06 0.54 +/- 0.05 0.60 +/- 0.04 Pass S-2162,2163 6/12/2019 Ac-228 0.46 +/- 0.10 0.44 +/- 0.08 0.45 +/- 0.07 Pass S-2162,2163 6/12/2019 K-40 4.22 +/- 0.49 3.81 +/- 0.41 4.02 +/- 0.32 Pass S-2162,2163 6/12/2019 Tl-208 0.09 +/- 0.02 0.10 +/- 0.02 0.09 +/- 0.01 Pass S-2162,2163 6/12/2019 Pb-212 0.34 +/- 0.03 0.26 +/- 0.03 0.30 +/- 0.02 Pass SWT-2355,2356 6/25/2019 Gr. Beta 1.12 +/- 0.57 1.24 +/- 0.56 1.18 +/- 0.40 Pass AP-2689,2690 6/28/2019 Be-7 0.089 +/- 0.020 0.075 +/- 0.018 0.082 +/- 0.013 Pass AP-2710,2711 7/1/2019 Be-7 0.091 +/- 0.010 0.097 +/- 0.010 0.094 +/- 0.007 Pass AP-2731,2732 7/2/2019 Be-7 0.073 +/- 0.013 0.072 +/- 0.011 0.072 +/- 0.009 Pass DW-10062,10063 7/5/2019 Ra-226 4.10 +/- 0.30 4.03 +/- 0.30 4.07 +/- 0.21 Pass DW-10062,10063 7/5/2019 Ra-228 1.95 +/- 0.60 2.31 +/- 0.62 2.13 +/- 0.43 Pass AP-70818,70819 7/8/2019 Gr. Beta 0.021 +/- 0.004 0.023 +/- 0.004 0.022 +/- 0.003 Pass XW-2459,2460 7/10/2019 H-3 304 +/- 92 234 +/- 89 269 +/- 64 Pass VE-2516,2517 7/10/2019 Be-7 0.63 +/- 0.16 0.52 +/- 0.19 0.58 +/- 0.12 Pass Concentrationa Averaged First Result Second Result Result

A-13 TABLE A-5. In-House "Duplicate" Samples Lab Codeb Date Analysis Acceptance VE-2516,2517 7/10/2019 K-40 6.50 +/- 0.47 6.81 +/- 0.54 6.66 +/- 0.36 Pass AP-71518A,B 7/15/2019 Gr. Beta 0.022 +/- 0.004 0.025 +/- 0.004 0.023 +/- 0.003 Pass VE-2668,2669 7/16/2019 K-40 3.84 +/- 0.27 3.74 +/- 0.26 3.79 +/- 0.19 Pass DW-10076,10077 7/16/2019 Gr. Alpha 3.01 +/- 0.92 4.13 +/- 0.91 3.57 +/- 0.65 Pass DW-10073,10074 7/16/2019 Ra-226 1.57 +/- 0.18 1.51 +/- 0.21 1.54 +/- 0.14 Pass DW-10073,10074 7/16/2019 Ra-228 1.29 +/- 0.56 1.48 +/- 0.57 1.385 +/- 0.40 Pass AP-72218A,B 7/22/2019 Gr. Beta 0.013 +/- 0.004 0.016 +/- 0.004 0.015 +/- 0.003 Pass G-2752,2753 7/23/2019 K-40 4.53 +/- 0.42 4.47 +/- 0.46 4.50 +/- 0.31 Pass G-2752,2753 7/23/2019 Be-7 1.98 +/- 0.29 1.96 +/- 0.29 1.97 +/- 0.20 Pass AP-2800,2801 7/25/2019 Be-7 0.208 +/- 0.090 0.321 +/- 0.147 0.264 +/- 0.086 Pass AP-72918A,B 7/29/2019 Gr. Beta 0.026 +/- 0.005 0.025 +/- 0.005 0.025 +/- 0.003 Pass VE-2840,2841 7/31/2019 K-40 3.94 +/- 0.38 3.99 +/- 0.47 3.96 +/- 0.30 Pass AP-2903,2904 8/1/2019 Be-7 0.198 +/- 0.102 0.228 +/- 0.102 0.213 +/- 0.072 Pass P-2882,2983 8/1/2019 H-3 265 +/- 85 327 +/- 88 296 +/- 61 Pass SG-2926,2927 8/5/2019 Pb-214 9.07 +/- 0.39 8.82 +/- 0.39 8.95 +/- 0.28 Pass SG-2926,2927 8/5/2019 Ac-228 9.00 +/- 0.76 8.58 +/- 0.72 8.79 +/- 0.52 Pass AV-2993,2994 8/9/2019 Gr. Beta 1.22 +/- 0.19 1.28 +/- 0.21 1.25 +/- 0.14 Pass AV-2993,2994 8/9/2019 K-40 3.12 +/- 0.36 3.14 +/- 0.35 3.13 +/- 0.25 Pass DW-10088,10089 8/9/2019 Ra-228 0.60 +/- 0.50 1.20 +/- 0.50 0.90 +/- 0.35 Pass DW-10088,10089 8/9/2019 Ra-226 1.40 +/- 0.20 0.94 +/- 0.20 1.17 +/- 0.14 Pass VE-3016,3017 8/12/2019 Be-7 0.39 +/- 0.12 0.47 0.28 0.43 0.15 Pass VE-3016,3017 8/12/2019 K-40 6.13 +/- 0.41 6.24 0.64 6.18 0.38 Pass G-3600,3601 8/12/2019 Be-7 4.42 +/- 0.33 4.35 0.27 4.39 0.21 Pass WW-3100,3101 8/14/2019 H-3 480 +/- 96 401 +/- 92 441 +/- 66 Pass MI-3211,3212 8/27/2019 K-40 1862 +/- 131 1923 +/- 136 1893 +/- 94 Pass MI-3211,3212 8/27/2019 Sr-90 0.90 +/- 0.33 0.56 +/- 0.29 0.73 +/- 0.22 Pass LW-3512,3513 8/30/2019 Gr. Beta 0.79 +/- 0.50 1.39 +/- 0.58 1.09 +/- 0.38 Pass F-3379,3380 9/3/2019 K-40 2.98 +/- 0.40 3.04 +/- 0.37 3.01 +/- 0.27 Pass P-3278,3279 9/3/2019 H-3 1110 +/- 123 1076 +/- 121 1093 +/- 86 Pass VE-3309,3310 9/4/2019 K-40 2.23 +/- 0.26 1.72 +/- 0.25 1.98 +/- 0.18 Pass DW-10100,10101 9/5/2019 Ra-226 0.50 +/- 0.11 0.57 0.12 0.54 +/- 0.08 Pass DW-10100,10101 9/5/2019 Ra-228 3.38 +/- 0.82 2.54 1.03 2.96 +/- 0.66 Pass VE-3400,3401 9/10/2019 Be-7 1.68 +/- 0.22 1.45 +/- 0.41 1.57 +/- 0.24 Pass VE-3400,3401 9/12/2019 K-40 4.63 +/- 0.42 5.09 +/- 0.41 4.86 +/- 0.30 Pass VE-3488,3489 9/17/2019 K-40 22.9 +/- 0.8 24.1 +/- 1.4 23.5 +/- 0.8 Pass VE-3488,3489 9/17/2019 Be-7 4.33 +/- 0.35 4.09 +/- 0.50 4.21 +/- 0.31 Pass WW-3467,3468 9/18/2019 H-3 211 +/- 85 209 +/- 85 210 +/- 60 Pass WW-3730,3731 9/18/2019 H-3 229 +/- 83 256 +/- 85 242 +/- 59 Pass AP-3533,3534 9/19/2019 Be-7 0.217 +/- 0.093 0.261 +/- 0.112 0.239 +/- 0.073 Pass WW-3554,3555 9/23/2019 Gr. Beta 1.62 +/- 1.10 1.93 +/- 1.07 1.77 +/- 0.77 Pass Concentrationa Averaged First Result Second Result Result

A-14 TABLE A-5. In-House "Duplicate" Samples Lab Codeb Date Analysis Acceptance DW-10111,10112 9/23/2019 Gr. Alpha 1.72 +/- 0.73 1.41 +/- 0.68 1.57 +/- 0.50 Pass DW-10115,10116 9/25/2019 Ra-228 3.65 +/- 0.80 2.76 +/- 0.68 3.21 +/- 0.52 Pass DW-10115,10116 9/25/2019 Ra-226 2.99 +/- 0.23 2.74 +/- 0.25 2.87 +/- 0.17 Pass G-3600,3601 9/26/2019 K-40 5.19 +/- 0.46 5.48 +/- 0.41 5.33 +/- 0.31 Pass AP-3921,3922 10/1/2019 Be-7 0.074 +/- 0.011 0.070 +/- 0.012 0.072 +/- 0.008 Pass AP-3986,3987 10/2/2019 Be-7 0.060 +/- 0.009 0.066 +/- 0.011 0.063 +/- 0.007 Pass WW-3793,3794 10/8/2019 Gr. Beta 3.75 +/- 1.18 4.34 1.20 4.05 +/- 0.84 Pass Note: Duplicate analyses are performed on every twentieth sample received in-house. Results are not listed for those analyses with activities that measure below the LLD.

a Results are reported in units of pCi/L, except for air filters (pCi/Filter or pCi/m3), food products, vegetation, soil and sediment (pCi/g).

b Laboratory codes: AP (Air Particulate), AV (Aquatic Vegetation), BS (Bottom Sediment), CF (Cattle Feed),

CH (Charcoal Canister), DW (Drinking Water), E (Egg), F (Fish), G (Grass), LW (Lake Water), P (Precipitation),

PM (Powdered Milk), S, (Solid), SG (Sludge), SO (Soil), SS (Shoreline Sediment), SW (Surface Water),

SWT (Surface Water Treated), SWU (Surface Water Untreated), VE (Vegetation), W Water (Water), WW (Well Water).

Concentrationa Averaged First Result Second Result Result

A-15 TABLE A-6. Department of Energy's Mixed Analyte Performance Evaluation Program (MAPEP).

Reference Known Lab Code b Date Analysis Activity Acceptance MASO-3638 8/1/2018 Cs-134 688.7 +/- 26.2 781 547 - 1015 Pass MASO-3638 8/1/2018 Cs-137 605.9 +/- 22.7 572 400 - 744 Pass MASO-3638 8/1/2018 Co-57 976.7 +/- 37.6 958 671 - 1245 Pass MASO-3638 8/1/2018 Co-60 604.5 +/- 24.9 608 426 - 790 Pass MASO-3638 8/1/2018 Mn-54 5.2 +/- 5.2 0

NA c Pass MASO-3638 8/1/2018 K-40 630 +/- 31 566 396 - 736 Pass MASO-3638 8/1/2018 Zn-65 556.4 +/- 26.8 500 350 - 650 Pass MAAP-3636 8/1/2018 Cs-134 0.37 +/- 0.04 0.444 0.311 - 0.577 Pass MAAP-3636 8/1/2018 Cs-137 0.34 +/- 0.05 0.345 0.242 - 0.449 Pass MAAP-3636 8/1/2018 Co-57 0.56 +/- 0.04 0.592 0.414 - 0.770 Pass MAAP-3636 8/1/2018 Co-60 0.28 +/- 0.03 0.294 0.206 - 0.382 Pass MAAP-3636 8/1/2018 Mn-54 0.26 +/- 0.05 0.266 0.186 - 0.346 Pass MAAP-3636 8/1/2018 Zn-65 0.22 +/- 0.07 0.201 NA d Pass MAVE-3640 8/1/2018 Cs-134 1.87 +/- 0.10 1.94 1.36 - 2.52 Pass MAVE-3640 8/1/2018 Cs-137 2.69 +/- 0.15 2.36 1.65 - 3.07 Pass MAVE-3640 8/1/2018 Co-57 3.90 +/- 0.12 3.31 2.32 - 4.30 Pass MAVE-3640 8/1/2018 Co-60 1.76 +/- 0.09 1.68 1.18 - 2.18 Pass MAVE-3640 8/1/2018 Mn-54 2.91 +/- 0.16 2.53 1.77 - 3.29 Pass MAVE-3640 8/1/2018 Zn-65 1.53 +/- 0.21 1.37 0.96 - 1.78 Pass MAW-3480 8/1/2018 H-3 336.0 +/- 10.7 338 237 - 439 Pass MAW-3480 8/1/2018 Cs-134 7.86 +/- 0.31 8.7 6.1 - 11.3 Pass MAW-3480 8/1/2018 Cs-137 7.55 +/- 0.33 6.9 4.8 - 9.0 Pass MAW-3480 8/1/2018 Co-57 15.67 +/- 0.36 14.9 10.4 - 19.4 Pass MAW-3480 8/1/2018 Co-60 0.12 +/- 0.12 0

NA c Pass MAW-3480 8/1/2018 Mn-54 13.38 +/- 0.44 12.5 8.8 - 16.3 Pass MAW-3480 8/1/2018 Zn-65 7.80 +/- 0.53 7.53 5.27 - 9.79 Pass MAW-3634 8/1/2018 I-129 1.32 +/- 0.08 1.62 1.13 - 2.11 Pass MAAP-609 2/1/2019 Gross Alpha 0.16 +/- 0.03 0.528 0.158 - 0.898 Pass MAAP-609 2/1/2019 Gross Beta 1.09 +/- 0.07 0.948 0.474 - 1.422 Pass MAW-550 2/1/2019 Gross Alpha 0.73 +/- 0.06 0.84 0.25 - 1.43 Pass MAW-550 2/1/2019 Gross Beta 2.26 +/- 0.06 2.33 1.17 - 3.50 Pass MASO-605 2/1/2019 Am-241 38.89 +/- 5.92 49.9 34.9 +/- 64.9 Pass MASO-605 2/1/2019 Cs-134 0.45 +/- 2.52 0.0 NA c Pass MASO-605 2/1/2019 Cs-137 1273.1 +/- 13.0 1164 815 - 1513 Pass MASO-605 2/1/2019 Co-57 0.46 +/- 1.1 0.0 NA c Pass MASO-605 2/1/2019 Co-60 857.96 +/- 8.52 855.0 599 - 1112 Pass MASO-605 2/1/2019 Mn-54 1,138.0 +/- 13.5 1027 719 - 1335 Pass MASO-605 2/1/2019 Zn-65 730.92 +/- 16.48 668 468 - 868 Pass MASO-605 2/1/2019 K-40 676 +/- 47 585 410 - 761 Pass MASO-605 2/1/2019 Sr-90 0.0007 +/- 0.0007 0.000 NA c Pass Concentrationa Control Laboratory result Limits c

A-16 TABLE A-6. Department of Energy's Mixed Analyte Performance Evaluation Program (MAPEP).

Reference Known Lab Code b Date Analysis Activity Acceptance MASO-605 2/1/2019 Pu-238 78.15 +/- 6.11 71.0 49.7 - 92.3 Pass MASO-605 2/1/2019 Pu-239/240 65.00 +/- 5.4 59.8 41.9 - 77.7 Pass MASO-605 2/1/2019 U-234 65 +/- 13 56 39 - 73 Pass MASO-605 2/1/2019 U-238 237 +/- 23 205 144 - 267 Pass MAW-613 2/1/2019 Am-241 0.46 +/- 0.03 0.582 0.407 - 0.757 Pass MAW-613 2/1/2019 Cs-134 5.49 +/- 0.18 5.99 4.19 - 7.79 Pass MAW-613 2/1/2019 Cs-137 0.089 +/- 0.080 0

NA c Pass MAW-613 2/1/2019 Co-57 10.87 +/- 0.24 10.00 7.0 - 13.0 Pass MAW-613 2/1/2019 Co-60 6.78 +/- 0.19 6.7 4.7 - 8.7 Pass MAW-613 2/1/2019 Mn-54 8.98 +/- 0.17 8.4 5.9 - 10.9 Pass MAW-613 2/1/2019 Zn-65 0.096 +/- 0.141 0

NA c Pass MAW-613 2/1/2019 Fe-55 0.004 +/- 4.00 0

NA c Pass MAW-613 2/1/2019 Ni-63 5.54 +/- 1.52 5.8 4.1 - 7.5 Pass MAW-613 2/1/2019 Sr-90 6.02 +/- 0.53 6.35 4.45 +/- 8.26 Pass MAW-613 2/1/2019 Pu-238 0.315 +/- 0.088 0.451 0.316 - 0.586 Faile MAW-613 2/1/2019 Pu-239/240 0.07 +/- 0.07 0.005 NA d Pass MAW-613 2/1/2019 U-234 0.96 +/- 0.07 0.800 0.56 +/- 1.04 Pass MAW-613 2/1/2019 U-238 0.94 +/- 0.07 0.810 0.57 +/- 1.05 Pass MAAP-611 2/1/2019 Cs-134 0.185 +/- 0.025 0.216 0.151 - 0.281 Pass MAAP-611 2/1/2019 Cs-137 0.288 +/- 0.045 0.290 0.203 - 0.377 Pass MAAP-611 2/1/2019 Co-57 0.369 +/- 0.033 0.411 0.288 - 0.534 Pass MAAP-611 2/1/2019 Co-60 0.333 +/- 0.045 0.340 0.238 - 0.442 Pass MAAP-611 2/1/2019 Mn-54 0.546 +/- 0.058 0.547 0.383 - 0.711 Pass MAAP-611 2/1/2019 Zn-65 0.025 +/- 0.0348 0

NA c Pass MAAP-611 2/1/2019 Sr-90 1.34 +/- 0.13 0.662 0.463 - 0.861 Failf MAAP-611 2/1/2019 U-234/233 4.14 +/- 0.97 0.106 0.074 - 0.138 Failf MAAP-611 2/1/2019 U-238 3.89 +/- 0.94 0.110 0.077 - 0.143 Failf MAVE-607 2/1/2019 Cs-134 2.33 +/- 0.10 2.44 1.71 - 3.17 Pass MAVE-607 2/1/2019 Cs-137 2.62 +/- 0.13 2.30 1.61 - 2.99 Pass MAVE-607 2/1/2019 Co-57 2.39 +/- 0.11 2.07 1.45 - 2.69 Pass MAVE-607 2/1/2019 Co-60 0.046 +/- 0.04 0

NA c Pass MAVE-607 2/1/2019 Mn-54 0.031 +/- 0.04 0

NA c Pass MAVE-607 2/1/2019 Sr-90 0.013 +/- 0.022 0

NA c Pass MAW-601 2/1/2019 I-129 0.56 +/- 0.08 0.616 0.431 - 0.801 Pass a Results are reported in units of Bq/kg (soil), Bq/L (water) or Bq/total sample (filters, vegetation).

b Laboratory codes as follows: MAW (water), MAAP (air filter), MASO (soil) and MAVE (vegetation).

c MAPEP results are presented as the known values and expected laboratory precision (1 sigma, 1 determination) and control limits as defined by the MAPEP. A known value of "zero" indicates an analysis was included in the testing series as a "false positive". MAPEP does not provide control limits.

d Provided in the series for "sensitivity evaluation". MAPEP does not provide control limits.

e An investigation is in progress to determine the reason for the failure of the Pu-239 study.

f An erroneous volume conversion caused some incorrect values to be submitted. If the conversion had been performed properly the results in Bq/sample would have been (Sr-90: 0.671 +/- 0.066 ) and (U-234: 0.153 +/- 0.036) and (U-238: 0.144 +/- 0.035).

This result had been included in the Uranium investigation. See footnote "C" on Table A-1.

Concentrationa Control Laboratory result Limits c

A-17 TABLE A-7. Interlaboratory Comparison Crosscheck Program, Environmental Resource Associates (ERA)a.

MRAD-30 Study Lab Code b Date Analysis ERA Value c Acceptance ERAP-846 3/18/2019 Am-241 19.1 18.7 13.3 - 24.9 Pass ERAP-846 3/18/2019 Cs-134 612 721 468 - 884 Pass ERAP-846 3/18/2019 Cs-137 679 634 521 - 832 Pass ERAP-846 3/18/2019 Co-60 93.7 93.8 79.7 - 119 Pass ERAP-846 3/18/2019 Fe-55 612 718 262 - 1150 Pass ERAP-846 3/18/2019 Mn-54

< 0.5

< 50.0 0.00 - 50.0 Pass ERAP-846 3/18/2019 Zn-65 1500 1380 1130 - 2110 Pass ERAP-846 3/18/2019 Pu-238 34.0 33.8 25.5 - 41.5 Pass ERAP-846 3/18/2019 Pu-239 64.9 67.0 50.1 - 80.8 Pass ERAP-846 3/18/2019 Sr-90 199 181 114 - 246 Pass ERAP-846 3/18/2019 U-234e 29.0 18.2 13.5 - 21.3 Fail ERAP-846 3/18/2019 U-238e 28.6 18.1 13.7 - 21.6 Fail ERAP-848 3/18/2019 Gross Alpha 48.4 50.3 26.3 - 82.9 Pass ERAP-848 3/18/2019 Gross Beta 95.5 78.6 47.7 - 119 Pass a Results obtained by Environmental, Inc., Midwest Laboratory (EIML) as a participant in the crosscheck program for proficiency testing administered by Environmental Resource Associates, serving as a replacement for studies conducted previously by the Environmental Measurements Laboratory Quality Assessment Program (EML).

b Laboratory code ERAP (air filter). Results are reported in units of (pCi/Filter).

c The ERA Assigned values for the air filter standards are equal to 100% of the parameter present in the standard as determined by the gravimetric and/or volumetric measurements made during standard preparation as applicable. The acceptance limits are established per the guidelines contained in the Department of Energy (DOE) d The acceptance limits are established per the guidelines contained in the Department of Energy (DOE) report EML-564, Analysis of Environmental Measurements Laboratory (EML) Quality Assessment Program (QAP)Data Determination of Operational Criteria and Control Limits for Performance Evaluation Purposes or ERA's SOP for the generation of Performance Acceptance Limits.

e Failure due to an over-estimated U-232 tracer value. Tracer has been re-standardized. (See footnote "c" on Table A-1.

Concentration a Laboratory Control Result Limits d

APPENDIX B DATA REPORTING CONVENTIONS

Data RepQOlng Conventions 1.0. All actM!les, except gross alpha and gross beta, are decay corracted to collsction time or the end of the collection period.

2.0. Single Measurements Each slngle measurement is reported as follows:

x ts where:

x "' value of the measurement; s = 2o counting uncertainty {corresponding to the 96% confidence level).

In cases where the activity is less than the lower llmft of detedlon L, ii is reported as: < L, where L c the lower limit of detectlon based on 4.660" uncertainty for a background sample.

3.0. Duplicate anatyses If dupllcate analyse$ are reported, the canventlon is ~s follows.:

3.1 lngjyjdual rruJUfts: For two analysls resul~; x1 t s1 and X:r :t s~

RePQr1ed result; ic :ts: where 1i' = (1,;2) (x, + "2) ands= (1/'l).J$12 + s; 3.2.

3.3.

Individual rasuits:

< l.1 * < L:z l[Jdividual results:

x :t s. < L 4.0. Comgµtallpn of AveraBes end Sl§ndard Qevlaljon~

Repprted,resuft; < J.., whe~ L"' lower of L1 and1/2 Req_orted rnsuit; x :t s if x ~ L; < L otherwise.

4.1 Averages and standard deviations listed In the tables are computed from all of the Individual measurements

~ver the period averaged; for exa~ple, an annual stand1:1rd devletlcm would not be the average of quarterly standard deviations. Th,;, average x and 1;1~ndard deviation *5* of a set of n number& x1* ~.,

  • xn ere defined as follows:

1 X "'n I:x 4.2 Values below the highest lower llmit of detection are not Included in the average.

4.3 If all values in the ave111ging group are less than the highest LLD, the highest LLD is reported.

4.4 If all but one of the values are les:1 than th~ highe~t LLD, the single \\'aluo 1e and associated two sigma error is reported.

4.6 In rounding off, the following nJles are followed:

4.5.1. If the number followlng tho~e to be r&t~inf,ld If! le$!> than 5. the number is dropped, and the retained numbers are kept unchanged. As an axe mp le, 11.-414~ Is rounded off to 11.44.

4.5.2. If lhe number followln9 th~se to be ret~ined is equal to or greater than 5, the number is dropped end the last retained number is raised by 1. As an example, 11.445 is rounded off to 11.45.

8-,2