ATI Environmental, Inc.
1"\\1 Midwest Laboratory Reviewed and Approved MONTHLY PROGRESS REPORT RADIOLO G I CAL ENVIRONMENTAL MON ITORIN G PROGRAM DAVIS-BESS E NUCLEAR POWER STATION OAK HARBOR, OHIO Rep orti ng Pe ri od: Ja nua ry Dece mbe r, 201 1 Prepared and Submitted by ENVIRONMENTAL, INC" MIDWEST LABORATORY Project Number: 8003 Da te 02-15-20 (2 Distribution:
A. Percival, Davis-Besse (2 copies and Original Raw Data)
T ABL E OF C ONT ENTS S ecti on P age List of T abl es
............................................................................................................... iii 1.0 INTR ODUCTI ON......................................................................................................... vi 2.0 LISTING OF M ISS ED S AM P L ES................................................................................ vii 3.0 DAT A T ABUL ATI ON S................................................................................................ viii Appendi ces A
I nt erl abor at ory C om p aris on Pr ogr am R es ults........................................................... A-1 B
Dat a R ep orti ng C onv enti ons.
................................................................................ B-1 C
S uppl em ent al Analys es......................................................................................... C-1 ii
L IST OF T ABL ES Airborne particulates and iodine collected at Location T-1, analyses for gross beta and iodine-131............................................................................................................. 1-1 2
Airborne particulates and iodine collected at Location T-2, analyses for gross beta and iodine-131............................................................................................................. 2-1 3
Airborne particulates and iodine collected at Location T-3, analyses for gross beta and iodine-131............................................................................................................. 3-1 4
Airborne particulates and iodine collected at Location T-4, analyses for gross beta and iodine-131............................................................................................................. 4-1 5
Airborne particulates and iodine collected at Location T -7, analyses for gross beta and iodine-131............................................................................................................. 5-1 6
Airborne particulates and iodine collected at Location T-8, analyses for gross beta and iodine-131............................................................................................................. 6-1 7
Airborne particulates and iodine collected at Location T-9, analyses for gross beta and iodine-131............................................................................................................. 7-1 8
Airborne particulates and iodine collected at Location T-11, analyses for gross beta and iodine-131............................................................................................................. 8-1 9
Airborne particulates and iodine collected at Location T-12, analyses for gross beta and iodine-131............................................................................................................. 9-1 10 Airborne particulates and iodine collected at Location T-27, analyses for gross beta and iodine-131........................................................................................................... 10-1 11 Airborne particulate data, gross beta analysis, monthly averages, minima and maxima...................................................................................................................... 11-1 12 Airborne particulate
- samples, quarterly composites by location, analyses for strontium-89, strontium-90 and gamma-emitting isotopes......................................... 12-1 13 Area monitors (TLD), quarterly................................................................................................. 13-1 14 Area monitors (TLD), annual.................................................................................................... 14-1 15 Milk, analyses for strontium-89, strontium-90, iodine-131, gamma-emitting isotopes, calcium, stable potassium, and ratios of strontium-90 (pCi) per gram of calcium and cesium-137 (pCi) per gram of potassium................................................................................. 15-1 16 Ground water, analyses for gross beta, tritium, strontium-89 and strontium-90 and gamma-emitting isotopes, quarterly collections,...................................................................... 16-1 17 Domestic meat, analysis for gamma-emitting isotopes............................................................ 17-1 18 Wild meat, analysis for gamma-emitting isotopes.................................................................... 18-1 iii
L IST OF T ABL ES ( conti nued )
19 Green leafy vegetable, analyses for strontium-89, strontium-90, iodine-131 and gamma-emitting isotopes......................................................................................................... 19-1 20
- Fruit, analyses for strontium-89, strontium-90, iodine-131 and gamma-emitting isotopes.................................................................................................................................... 20-1 21 Animal-wildlife feed, analysis for gamma-emitting isotopes..................................................... 21-1 22 Soil, analysis for gamma-emitting isotopes.............................................................................. 22-1 23 Treated surface water, monthly composites of weekly grab samples, analysis for gross beta................................................................................................................................ 23-1 24 Treated surface water, quarterly composites of weekly grab samples, analyses for tritium, strontium-89, strontium-90 and gamma-emitting isotopes........................................... 24-1 25 Untreated surface water, monthly composites of weekly grab samples, analyses for gross beta, tritium and gamma-emitting isotopes.................................................................... 25-1 26 Untreated surface water, quarterly composites of weekly grab samples, analyses for strontium-89 and strontium-90................................................................................................. 26-1 27 Fish, analyses for gross beta and gamma-emitting isotopes................................................... 28-1 28 Shoreline sediment, analysis for gamma-emitting isotopes..................................................... 29-1 iv
LIST OF TABLES (continued)
The following tables are in the Appendices:
Appendix A Attachment A: Acceptance criteria for spiked samples.............................................................. A-2 A-1 Interlaboratory Comparison Program Results.......................................................................... A1-1 A-2 Interlaboratory Comparison Program Results, thermoluminescent dosimeters (TLDs)..................................................................................................... A2-1 A-3 Results of the analyses on in-house spiked samples.............................................................. A3-1 A-4 Results of the analyses on in-house "blank" A4-1 A-5 Results of the analyses on in-house "duplicate" samples........................................................ A5-1 A-6 Mixed Analyte Performance Evaluation Program (MAPEP)..................................................... A6-1 A-7 Environmental Resources Associates, Crosscheck Program Results (EML study replacement).............................................................................................................. A7-1 Appendix B B-1 Data Reporting Conventions...................................................................................................... B-2 v
1.0 INTR ODUCTI ON T h e f oll owi ng constitut es th e fi nal 201 1 M onthly Pr ogr ess R ep ort f or th e R ad i ol ogi cal Envir onm ent al M onit ori ng Pr ogr am cond u ct ed at th e Davis-Bess e N u cl ear P ow er St ati on i n Oak Har bor, Ohi o.
R esults of com pl et ed analys es ar e pr es ent ed i n th e att ach ed t abl es.
All activiti es, ex cept gr oss alph a and gr oss bet a, ar e d ecay corr ect ed t o th e tim e of coll ecti on.
All s am pl es w er e coll ect ed withi n th e s ch edul ed p eri od u nl ess not ed oth erwis e i n th e Listi ng of M iss ed S am pl es.
vi
Sample Type Location AP T-1 1 WL T-2 1 0 TLD T-1 1 4 TLD T-1 24 TLD T-1 1 4 TLD T-1 24 WW T-27A WW T-1 4 1 WW T-225 WW T-225 WW T-226 2.0 LISTING OF MISSED SAMPLES Expected Collection Date 09-06-1 1 1 2-08-1 1 0 1 -1 1-12 0 1 -1 1-12 0 1 -1 1 -1 2 0 1 -1 1 -1 2 1 st Qtr, 201 1 1 st Qtr, 201 1 1 st Qtr, 201 1 2nd Qtr, 201 1 1 st Qtr, 201 1 Reason Sampler pump not running; open fuse.
No sample available.
Quarterly, TLD lost in the field.
Quarterly, TLD lost in the field.
Annual, TLD lost in the field.
Annual, TLD lost in the field.
No sample available.
No sample available.
No sample available.
No sample available.
No sample available.
vii
3.0 DATA TABULATIONS viii
Table 1. Airborne particulates and charcoal canisters, analyses for gross beta and iodine-131 a.
Location: T-1 Units: pCi/m3 Collection: Continuous, weekly exchange.
Date Collected Required LLD 01-04-11 01-11-11 01-18-11 01-25-11 01-31-11 02-08-11 02-15-11 02-22-11 03-01-11 03-08-11 03-15-11 03-22-11 b 03-29-11 b Volume (m) 304 302 295 303 262 345 303 304 303 303 302 304 302 1st Quarter Mean +/- s.d.
04-05-11 0 305 04-12-11 b 302 04-19-11 304 04-26-11 304 05-03-11 303 05-10-11 303 05-17-11 303 05-24-11 286 05-31-11 282 06-07-11 286 06-14-11 286 06-21-11 286 06-29-11 328 2nd Quarter Mean +/- s.d.
Gross Beta 0.010 0.031 +/- 0.004 0.041 +/- 0.004 0.027 +/- 0.004 0.030 +/- 0.004 0.036 +/- 0.004 0.026 +/- 0.003 0.030 +/- 0.003 0.024 +/- 0.003 0.026 +/- 0.003 0.022 +/- 0.003 0.019 +/- 0.003 0.031 +/- 0.004 0.024 +/- 0.004 0.028 +/- 0.006 0.043 +/- 0.004 0.018 +/- 0.003 0.026 +/- 0.003 0.015 +/- 0.003 0.017 +/- 0.003 0.017 +/- 0.003 0.016 +/- 0.003 0.011 +/- 0.003 0.013 +/- 0.003 0.028 +/- 0.004 0.019 +/- 0.003 0.016 +/- 0.003 0.015 +/- 0.003 0.020 +/- 0.008 Date Volume Collected (mü)
07-06-11 286 07-12-11 244 07-19-11 286 07-26-11 287 08-02-11 286 08-09-11 286 08-16-11 286 08-23-11 282 08-30-11 286 09-06-11 286 09-13-11 286 09-20-11 287 09-27-11 285 3rd Quarter Mean +/- s.d.
10-04-11 286 10-11-11 287 10-18-11 282 10-25-11 280 11-01-11 281 11-08-11 284 11-15-11 279 11-22-11 281 11-29-11 281 12-06-11 281 12-13-11 281 12-20-11 288 12-28-11 328 01-03-12 247 4th Quarter Mean +/- s.d.
Cumulative Average a lodine-131 concentrations are < 0.07 pCi/m3 unless noted otherwise.
b lodine-131 activity detected, refer to Appendix C, "Supplementary Analyses".
1 - 1 Gross Beta 0.010 0.027 +/- 0.004 0.029 +/- 0.004 0.028 +/- 0.004 0.032 +/- 0.004 0.034 +/- 0.004 0.031 +/- 0.004 0.021 +/- 0.003 0.036 +/- 0.004 0.024 +/- 0.003 0.047 +/- 0.004 0.016 +/- 0.003 0.018 +/- 0.003 0.024 +/- 0.003 0.028 +/- 0.008 0.014 +/- 0.003 0.043 +/- 0.005 0.028 +/- 0.004 0.022 +/- 0.003 0.022 +/- 0.003 0.030 +/- 0.004 0.031 +/- 0.004 0.027 +/- 0.004 0.017 +/- 0.003 0.017 +/- 0.003 0.035 +/- 0.004 0.035 +/- 0.004 0.023 +/- 0.003 0.015 +/- 0.003 0.026 +/- 0.009 0.025
Table 2. Airborne particulates and charcoal canisters, analyses for gross beta and iodine-131a.
Location: T-2 Units: pCilm3 Collection: Continuous, weekly exchange.
Date Collected Required LLD 01-04-11 01-11-11 01-18-11 01-25-11 01-31-11 02-08-11 02-15-11 02-22-11 03-01-11 03-08-11 03-15-11 03-22-11 b 03-29-11 b Volume (mü)
286 285 286 286 247 326 286 287 289 283 286 286 275 1 st Quarter Mean +/- s.d.
04-05-11 b 287 04-12-11 285 04-19-11 286 04-26-11 287 05-03-11 285 05-10-11 285 05-17-11 286 05-24-11 286 05-31-11 287 06-07-11 286 06-14-11 285 06-21-11 286 06-29-11 328 2nd Quarter Mean +/- s.d.
Gross Beta 0.010 0.037 +/- 0.004 0.043 +/- 0.004 0.028 +/- 0.004 0.033 +/- 0.004 0.036 +/- 0.004 0.023 +/- 0.003 0.024 +/- 0.003 0.021 +/- 0.003 0.011 +/- 0.003 0.023 +/- 0.003 0.021 +/- 0.003 0.033 +/- 0.004 0.028 +/- 0.004 0.028 +/- 0.009 0.045 +/- 0.004 0.017 +/- 0.003 0.027 +/- 0.003 0.017 +/- 0.003 0.015 +/- 0.003 0.016 +/- 0.003 0.021 +/- 0.003 0.015 +/- 0.003 0.015 +/- 0.003 0.025 +/- 0.003 0.022 +/- 0.003 0.015 +/- 0.003 0.015 +/- 0.003 0.020 +/- 0.008 Date Volume Collected (mü)
07-06-11 285 07-12-11 244 07-19-11 287 07-26-11 286 08-02-11 286 08-09-11 285 08-16-11 286 08-23-11 296 08-30-11 286 09-06-11 285 09-13-11 286 09-20-11 282 09-27-11 285 3rd Quarter Mean +/- s.d.
10-04-11 286 10-11-11 287 10-18-11 286 10-25-11 284 11-01-11 286 11-08-11 288 11-15-11 284 11-22-11 286 11-29-11 286 12-06-11 285 12-13-11 285 12-20-11 286 12-28-11 328 01-03-12 247 4th Quarter Mean +/- s.d.
Cumulative Average a lodine-131 concentrations are < 0.07 pCilm3 unless noted otherwise.
b lodine-131 activity detected, refer to Appendix C, "Supplementary Analyses".
2-1 Gross Beta 0.010 0.024 +/- 0.003 0.023 +/- 0.004 0.026 +/- 0.003 0.046 +/- 0.004 0.028 +/- 0.003 0.031 +/- 0.004 0.019 +/- 0.003 0.032 +/- 0.004 0.021 +/- 0.003 0.046 +/- 0.004 0.016 +/- 0.003 0.018 +/- 0.003 0.026 +/- 0.003 0.027 +/- 0.010 0.016 +/- 0.003 0.048 +/- 0.005 0.028 +/- 0.004 0.022 +/- 0.003 0.024 +/- 0.003 0.026 +/- 0.003 0.032 +/- 0.004 0.024 +/- 0.003 0.021 +/- 0.003 0.019 +/- 0.003 0.036 +/- 0.004 0.038 +/- 0.005 0.021 +/- 0.003 0.024 +/- 0.004 0.027 +/- 0.009 0.026
Table 3. Airborne particulates and charcoal canisters, analyses for gross beta and iodine-131 a.
Location: T-3 Units: pCi/m3 Collection: Continuous, weekly exchange.
Date Collected Required LLD 01-04-1 1 01-1 1-1 1 01-18-1 1 01-25-1 1 01-31 -1 1 02-08-1 1 02-15-1 1 02-22-1 1 03-01-1 1 03-08-1 1 03-15-1 1 03-22-1 1 b 03-29-1 1 b Volume (m6) 277 286 286 286 248 325 286 286 288 283 291 288 285 1 st Quarter Mean +/- s.d.
04-05-1 1 b 287 04-1 2-1 1 285 04-1 9-1 1 286 04-26-1 1 281 05-03-1 1 277 05-1 0-1 1 277 05-1 7-1 1 275 05-24-1 1 275 05-31-1 1 276 06-07-1 1 284 06-14-1 1 283 06-21-1 1 284 06-29-1 1 326 2nd Quarter Mean +/- s.d.
Gross Beta 0.010 0.036 +/- 0.004 0.038 +/- 0.004 0.025 +/- 0.003 0.032 +/- 0.004 0.035 +/- 0.004 0.028 +/- 0.003 0.026 +/- 0.003 0.024 +/- 0.003 0.023 +/- 0.003 0.023 +/- 0.003 0.016 +/- 0.003 0.026 +/- 0.003 0.029 +/- 0.004 0.028 +/- 0.006 0.040 +/- 0.004 0.022 +/- 0.003 0.032 +/- 0.004 0.017 +/- 0.003 0.029 +/- 0.004 0.013 +/- 0.003 0.019 +/- 0.003 0.014 +/- 0.003 0.013 +/- 0.003 0.026 +/- 0.004 0.022 +/- 0.003 0.016 +/- 0.003 0.015 +/- 0.003 0.021 +/- 0.008 Date Volume Collected (m6) 07-06-1 1 284 07-12-1 1 242 07-19-1 1 285 07-26-1 1 284 08-02-1 1 284 08-09-1 1 283 08-1 6-1 1 295 08-23-1 1 297 08-30-1 1 289 09-06-1 1 284 09-1 3-1 1 286 09-20-1 1 286 09-27-1 1 284 3rd Quarter Mean +/- s.d.
1 0-04-1 1 286 1 0-1 1-1 1 287 1 0-18-1 1 291 1 0-25-1 1 292 1 1 1 1 291 1 1 1 1 294 1 1 1 1 288 1 1 1 1 291 1 1 1 1 291 12-06-1 1 290 12-13-1 1 290 12-20-1 1 291 12-28-1 1 331 01-03-12 259 4th Quarter Mean +/- s.d.
Cumulative Average a lodine-131 concentrations are < 0.07 pCi/m3 unless noted otherwise.
b lodine-131 activity detected, refer to Appendix C, "Supplementary Analyses".
3-1 Gross Beta 0.0 1 0 0.023 +/- 0.003 0.029 +/- 0.004 0.023 +/- 0.003 0.041 +/- 0.004 0.027 +/- 0.003 0.033 +/- 0.004 0.022 +/- 0.003 0.033 +/- 0.004 0.022 +/- 0.003 0.045 +/- 0.004 0.020 +/- 0.003 0.018 +/- 0.003 0.024 +/- 0.003 0.028 +/- 0.008 0.016 +/- 0.003 0.040 +/- 0.004 0.027 +/- 0.004 0.021 +/- 0.003 0.021 +/- 0.003 0.027 +/- 0.003 0.029 +/- 0.004 0.025 +/- 0.003 0.019 +/- 0.003 0.022 +/- 0.003 0.033 +/- 0.004 0.037 +/- 0.004 0.020 +/- 0.003 0.025 +/- 0.004 0.026 +/- 0.007 0.026
Table 4. Airborne particulates and charcoal canisters, analyses for gross beta and iodine-131a.
Location: T-4 Units: pCi/m3 Collection:
Continuous, weekly exchange.
Date Volume Date Volume Collected (mO)
Gross Beta Collected (mO)
Gross Beta Reguired LLD 0.010 0.010 01-04-11 287 0.037 +/- 0.004 07-06-11 286 0.025 +/- 0.004 01-11-11 287 0.040 +/- 0.004 07-12-11 244 0.028 +/- 0.004 01-18-11 287 0.029 +/- 0.004 07-19-11 287 0.025 +/- 0.003 01-25-11 296 0.038 +/- 0.004 07-26-11 276 0.031 +/- 0.004 01-31-11 248 0.035 +/- 0.004 08-02-11 275 0.031 +/- 0.004 02-08-11 315 0.026 +/- 0.003 08-09-11 275 0.030 +/- 0.004 02-15-11 290 0.027 +/- 0.003 08-16-11 275 0.023 +/- 0.003 02-22-11 288 0.022 +/- 0.003 08-23-11 277 0.037 +/- 0.004 03-01-11 291 0.027 +/- 0.004 08-30-11 276 0.024 +/- 0.003 03-08-11 291 0.025 +/- 0.003 09-06-11 274 0.048 +/- 0.004 03-15-11 291 0.018 +/- 0.003 09-13-11 275 0.019 +/- 0.003 03-22-11 b 289 0.027 +/- 0.004 09-20-11 276 0.017 +/-0.003 03-29-11 b 284 0.029 +/- 0.004 09-27-11 274 0.026 +/- 0.004 1 st Quarter Mean +/- s.d.
0.029 +/- 0.007 3rd Quarter Mean +/- s.d.
0.028 +/- 0.008 04-05-11 b 292 0.046 +/- 0.004 10-04-11 275 0.017 +/- 0.004 04-12-11 289 0.021 +/- 0.003 10-11-11 277 0.049 +/- 0.005 04-19-11 291 0.030 +/- 0.003 10-18-11 276 0.027 +/- 0.004 04-26-11 292 0.019 +/- 0.003 10-25-11 274 0.022 +/- 0.003 05-03-11 290 0.024 +/- 0.003 11-01-11 275 0.022 +/- 0.003 05-10-11 291 0.018 +/- 0.003 11-08-11 279 0.030 +/- 0.004 05-17-11 291 0.017 +/- 0.003 11-15-11 274 0.029 +/- 0.004 05-24-11 291 0.013 +/- 0.003 11-22-11 276 0.024 +/- 0.004 05-31-11 285 0.016 +/- 0.003 11-29-11 275 0.019 +/- 0.003 06-07-11 286 0.026 +/- 0.004 12-06-11 275 0.022 +/- 0.003 06-14-11 285 0.021 +/- 0.003 12-13-11 274 0.041 +/- 0.004 06-21-11 286 0.019 +/- 0.003 12-20-11 276 0.045 +/- 0.005 06-29-11 328 0.015 +/- 0.003 12-28-11 327 0.025 +/- 0.003 01-03-12 249 0.025 +/- 0.004 2nd Quarter Mean +/- s.d.
0.022 +/- 0.009 4th Quarter Mean +/- s.d.
0.028 +/- 0.010 Cumulative Average 0.027 a lodine-131 concentrations are < 0.07 pCi/m3 unless noted otherwise.
b lodine-131 activity detected, refer to Appendix C, "Supplementary Analyses".
4-1
Table 5.
Airborne particulates and charcoal canisters, analyses for gross beta and iodine-1318*
Location: T-7 Units: pCi/m3 Collection:
Continuous, weekly exchange.
Date Collected Required LLD 01-04-11 01-11-11 01-18-11 01-25-11 01-31-11 02-08-11 02-15-11 02-22-11 03-01-11 03-08-11 03-15-11 03-22-11 b 03-29-11 b Volume (m3) 286 285 286 286 247 325 286 285 275 285 284 286 285 1 st Quarter Mean +/- s.d.
04-05-11 b 287 04-12-11 b 286 04-19-11 286 04-26-11 286 05-03-11 286 05-10-11 285 05-17-11 282 05-24-11 282 05-31-11 284 06-07-11 282 06-14-11 281 06-21-11 282 06-29-11 322 2nd Quarter Mean +/- s.d.
Gross Beta 0.010 0.049 +/- 0.004 0.046 +/- 0.004 0.025 +/- 0.004 0.036 +/- 0.004 0.038 +/- 0.004 0.025 +/- 0.003 0.027 +/- 0. 003 0.021 +/- 0.003 0.027 +/- 0.004 0.021 +/- 0.003 0.020 +/- 0.003 0.028 +/- 0. 004 0.027 +/- 0.004 0.030 +/- 0.009 0.049 +/- 0.004 0.020 +/- 0.003 0.030 +/- 0.004 0.018 +/- 0.003 0.015 +/- 0. 003 0.016 +/- 0.003 0.019 +/- 0.003 0.014 +/- 0.003 0.014 +/- 0.003 0.029 +/- 0.004 0.023 +/- 0.003 0.015 +/- 0.003 0.015 +/- 0.003 0.021 +/- 0.010 Date Volume Collected (m3) 07-06-11 282 07-12-11 244 07-19-11 284 07-26-11 284 08-02-11 288 08-09-11 287 08-16-11 283 08-23-11 288 08-30-11 281 09-06-11 284 09-13-11 284 09-20-11 283 09-27-11 285 3rd Quarter Mean +/- s.d.
10-04-11 288 10-11-11 282 10-18-11 281 10-25-11 283 11-01-11 284 11-08-11 285 11-15-11 284 11-22-11 287 11-29-11 285 12-06-11 289 12-13-11 291 12-20-11 292 12-28-11 338 01-03-12 245 4th Quarter Mean +/- s.d.
Cumulative Average 8 lodine-131 concentrations are < 0.07 pCilm3 unless noted otherwise.
b lodine-131 activity detected, refer to Appendix C, "Supplementary Analyses".
5-1 Gross Beta 0.010 0.024 +/- 0.004 0.032 +/- 0.004 0.022 +/- 0.003 0.031 +/- 0.004 0.032 +/- 0.004 0.031 +/- 0.004 0.024 +/- 0. 003 0.034 +/- 0.004 0.025 +/- 0.003 0.050 +/- 0.004 0.025 +/- 0.003 0.018 +/- 0.003 0.024 +/- 0.003 0.029 +/- 0.008 0.015 +/- 0.003 0.047 +/- 0.005 0.029 +/- 0.004 0.021 +/- 0.003 0.022 +/- 0.003 0.034 +/- 0.004 0.031 +/- 0.004 0.025 +/- 0.003 0.016 +/- 0.003 0.019 +/- 0.003 0.036 +/- 0.004 0.042 +/- 0.005 0.020 +/- 0.003 0.024 +/- 0.004 0.027 +/- 0.010 0.027
Table 6. Airborne particulates and charcoal canisters, analyses for gross beta and iodine-131 a.
Location: T-8 Units: pCi/m3 Collection:
Continuous, weekly exchange.
Date Collected Required LLD 01-04-11 01-11-11 01-18-11 01-25-11 01-31-11 02-08-11 02-15-11 02-22-11 03-01-11 03-08-11 03-15-11 03-22-11 b 03-29-11 b Volume (m3) 298 274 275 277 255 328 289 294 288 278 287 289 288 1 st Quarter Mean +/- s.d.
04-05-11 b 289 04-12-11 b 289 04-19-11 288 04-26-11 b 291 05-03-11 298 05-10-11 297 05-17-11 280 05-24-11 288 05-31-11 288 06-07-11 289 06-14-11 288 06-21-11 285 06-29-11 330 2nd Quarter Mean +/- s.d.
Gross Beta 0.010 0.041 +/- 0.004 0.043 +/- 0.004 0.025 +/- 0.004 0.037 +/- 0.004 0.032 +/- 0.004 0.028 +/- 0.003 0.016 +/- 0.003 0.022 +/- 0.003 0.024 +/- 0.003 0.020 +/- 0.003 0.017 +/- 0.003 0.030 +/- 0.004 0.028 +/- 0.004 0.028 +/- 0.009 0.041 +/- 0.004 0.019 +/- 0.003 0.039 +/- 0.004 0.015 +/- 0.003 0.014 +/- 0.003 0.014 +/- 0.003 0.018 +/- 0.003 0.011 +/- 0.003 0.012 +/- 0.003 0.026 +/- 0.003 0.023 +/- 0.003 0.017 +/- 0.003 0.017 +/- 0.003 0.020 +/- 0.010 Date Volume Collected (m3) 07-06-11 275 07-12-11 238 07-19-11 277 07-26-11 277 08-02-11 277 08-09-11 287 08-16-11 275 08-23-11 297 08-30-11 275 09-06-11 286 09-13-11 277 09-20-11 281 09-27-11 284 3rd Quarter Mean +/- s.d.
10-04-11 278 10-11-11 293 10-18-11 279 10-25-11 285 11-01-11 286 11-08-11 302 11-15-11 281 11-22-11 286 11-29-11 268 12-06-11 286 12-13-11 286 12-20-11 286 12-28-11 330 01-03-12 239 4th Quarter Mean +/- s.d.
Cumulative Average a lodine-131 concentrations are < 0.07 pCilm3 unless noted otherwise.
b lodine-131 activity detected, refer to Appendix C, "Supplementary Analyses".
6-1 Gross Beta 0.010 0.024 +/- 0.004 0.030 +/- 0.004 0.029 +/- 0.004 0.032 +/- 0.004 0.031 +/- 0.004 0.034 +/- 0.004 0.024 +/- 0.004 0.035 +/- 0.004 0.022 +/- 0.003 0.050 +/- 0.004 0.021 +/- 0.003 0.020 +/- 0.003 0.024 +/- 0.003 0.029 +/- 0.008 0.017 +/- 0.004 0.046 +/- 0.005 0.031 +/- 0.004 0.022 +/- 0.003 0.025 +/- 0.003 0.029 +/- 0.003 0.028 +/- 0.004 0.026 +/- 0.004 0.019 +/- 0.003 0.019 +/- 0.003 0.036 +/- 0.004 0.042 +/- 0.005 0.020 +/- 0.003 0.023 +/- 0.004 0.027 +/- 0.009 0.026
Table 7. Airborne particulates and charcoal canisters, analyses for gross beta and iodine-131 a.
Location: T-9 (C)
Units: pCi/m3 Collection:
Continuous, weekly exchange.
Date Collected Required LLD 01-04-11 01-11-11 01-18-11 01-25-11 01-31-11 02-08-11 02-15-11 02-22-11 03-01-11 03-08-11 03-15-11 03-22-11 b 03-29-11 b Volume (m")
266 289 286 287 244 332 292 291 286 283 286 289 289 1 st Quarter Mean +/- s.d.
04-05-11 b 279 04-12-11 294 04-19-11 284 04-26-11 278 05-03-11 292 05-10-11 292 05-17-11 285 05-24-11 286 05-31-11 287 06-07-11 286 06-14-11 284 06-21-11 278 06-29-11 337 2nd Quarter Mean +/- s.d.
Gross Beta 0.010 0.035 +/- 0.004 0.045 +/- 0.004 0.027 +/- 0.004 0.037 +/- 0.004 0.036 +/- 0.004
- 0. 027 +/- 0.003
- 0. 027 +/- 0. 003 0.024 +/- 0.003 0.025 +/- 0.003 0.021 +/- 0.003 0.020 +/- 0.003
- 0. 028 +/- 0. 004 0.028 +/- 0.004 0.029 +/- 0.007 0.043 +/- 0.004 0.017 +/- 0. 003 0.025 +/- 0.003 0.018 +/- 0.003 0.018 +/- 0.003 0.016 +/- 0.003 0.020 +/- 0.003 0.015 +/- 0.003 0.014 +/- 0.003 0.025 +/- 0.003 0.027 +/- 0. 003 0.020 +/- 0.003 0.018 +/- 0.003 0.021 +/- 0.008 Date Volume Collected (m")
07-06-11 274 07-12-11 253 07-19-11 287 07-26-11 277 08-02-11 286 08-09-11 295 08-16-11 276 08-23-11 296 08-30-11 276 09-06-11 291 09-13-11 286 09-20-11 289 09-27-11 289 3rd Quarter Mean +/- s.d.
10-04-11 273 10-11-11 297 10-18-11 285 10-25-11 275 11-01-11 287 11-08-11 289 11-15-11 287 11-22-11 287 11-29-11 287 12-06-11 287 12-13-11 294 12-20-11 288 12-28-11 327 01-03-12 235 4th Quarter Mean +/- s.d.
Cumulative Average a lodine-131 concentrations are < 0.07 pCi/m3 unless noted otherwise.
D lodine-131 activity detected, refer to Appendix C, "Supplementary Analyses".
7-1 Gross Beta 0.010 0.025 +/- 0.004 0.028 +/- 0.004 0.025 +/- 0.003 0.033 +/- 0.004 0.036 +/- 0.004 0.034 +/- 0.004
- 0. 023 +/- 0.003 0.036 +/- 0.004 0.021 +/- 0.003 0.051 +/- 0.004 0.022 +/- 0.003 0.022 +/- 0.003 0.025 +/- 0.003 0.029 +/- 0.009 0.017 +/- 0.004 0.042 +/- 0.004 0.030 +/- 0.004 0.021 +/- 0.003 0.024 +/- 0.003 0.034 +/- 0.004 0.024 +/- 0.003 0.024 +/- 0.003 0.018 +/- 0.003 0.022 +/- 0.003 0.039 +/- 0.004 0.041 +/- 0.005 0.022 +/- 0.003 0.022 +/- 0.004 0.027 +/- 0.009 0.027
Table 8. Airborne particulates and charcoal canisters, analyses for gross beta and iodine-131 a.
Location: T-1 1 (C)
Units: pCilm3 Collection: Continuous, weekly exchange.
Date Collected Required LLD 0 1 1 1 0 1 -1 1-1 1 01-1 8-1 1 0 1 1 1 01-31 -1 1 02-08-1 1 02-1 5-1 1 02-22-1 1 03-01-1 1 03-08-1 1 03-1 5-1 1 03-22-1 1 b 03-29-1 1 b Volume (m0) 287 286 286 275 245 323 284 284 284 285 282 284 283 1 st Quarter Mean +/- s.d.
04-05-1 1 b 285 04-1 2-1 1 284 04-1 9-1 1 284 04-26-1 1 284 05-03-1 1 284 05-1 0-1 1 284 05-1 7-1 1 285 05-24-1 1 284 05-31 -1 1 284 06-07-1 1 284 06-1 4-1 1 284 06-2 1 -1 1 283 06-29-1 1 324 2nd Quarter Mean +/- s.d.
Gross Beta 0.0 1 0 0.032 +/- 0.004 0.041 +/- 0.004 0.025 +/- 0.004 0.033 +/- 0.004 0.036 +/- 0.004 0.025 +/- 0.003 0.027 +/- 0.003 0.0 1 8 +/- 0.003 0.036 +/- 0.004 0.023 +/- 0.003 0.0 1 8 +/- 0.003 0.029 +/- 0.004 0.026 +/- 0.004 0.028 +/- 0.007 0.046 +/- 0.004 0.021 +/- 0.003 0.028 +/- 0.003 0.01 7 +/- 0.003 0.01 6 +/- 0.003 0.01 7 +/- 0.003 0.021 +/- 0.003 0.029 +/- 0.004 0.01 2 +/- 0.003 0.026 +/- 0.004 0.01 9 +/- 0.003 0.01 9 +/- 0.003 0.01 7 +/- 0.003 0.022 +/- 0.009 Date Volume Collected (m0) 07-06-1 1 283 07-12-1 1 243 07-1 9-1 1 284 07-26-1 1 283 08-02-1 1 265 08-09-1 1 274 08-1 6-1 1 284 08-23-1 1 284 08-30-1 1 284 09-06-1 1 09-1 3-1 1 283 09-20-1 1 283 09-27-1 1 283 3rd Quarter Mean +/- s.d.
1 0-04-1 1 284 1 0-1 1-1 1 284 1 0-1 8-1 1 283 1 0-25-1 1 284 1 1 1 1 283 1 1 1 1 304 1 1 -1 5-1 1 279 1 1 1 1 282 1 1 1 1 282 1 2-06-1 1 282 1 2-13-1 1 281 1 2-20-1 1 282 1 2-28-1 1 322 01 1 2 248 4th Quarter Mean +/- s.d.
Cumulative Average a lodine-1 31 concentrations are < 0.07 pCi/m3 unless noted otherwise.
D lodine-1 31 activity detected, refer to Appendix C, "Supplementary Analyses".
C No Sample; Pump not running due to open fuse.
8-1 Gross Beta 0.0 1 0 0.025 +/- 0.004 0.029 +/- 0.004 0.027 +/- 0.004 0.033 +/- 0.004 0.035 +/- 0.004 0.037 +/- 0.004 0.020 +/- 0.003 0.038 +/- 0.004 0.024 +/- 0.003 NSc 0.020 +/- 0.003 0.020 +/- 0.003 0.029 +/- 0.004 0.028 +/- 0.007 0.01 9 +/- 0.004 0.050 +/- 0.005 0.027 +/- 0.004 0.01 8 +/- 0.003 0.020 +/- 0.003 0.028 +/- 0.003 0.026 +/- 0.004 0.026 +/- 0.004 0.01 7 +/- 0.003 0.022 +/- 0.003 0.036 +/- 0.004 0.046 +/- 0.005 0.023 +/- 0.003 0.020 +/- 0.004 0.027 +/- 0.01 0 0.026
Table 9. Airborne particulates and charcoal canisters, analyses for gross beta and iodine-131a.
Location: T-12 (C)
Units: pCilm3 Collection:
Continuous, weekly exchange.
Date Collected Required LLD 01-04-11 01-11-11 01-18-11 01-25-11 01-31-11 02-08-11 02-15-11 02-22-11 03-01-11 03-08-11 03-15-11 03-22-11 03-29-11 b Volume (m) 297 295 296 297 257 338 297 296 296 294 296 297 293 1 st Quarter Mean +/- s.d.
04-05-11 b 301 04-12-11 b 292 04-19-11 297 04-26-11 286 05-03-11 290 05-10-11 283 05-17-11 283 05-24-11 284 05-31-11 284 06-07-11 284 06-14-11 282 06-21-11 284 06-29-11 333 2nd Quarter Mean +/- s.d.
Gross Beta 0.010 0.036 +/- 0.004 0.043 +/- 0.004
- 0. 029 +/- 0.004 0.038 +/- 0.004
- 0. 033 +/- 0.004
- 0. 025 +/- 0.003
- 0. 031 +/- 0.003
- 0. 023 +/- 0.003
- 0. 023 +/- 0.003 0.023 +/- 0.003
- 0. 016 +/- 0.003 0.030 +/- 0.004 0.024 +/- 0.004
- 0. 029 +/- 0.007 0.048 +/- 0.004 0.022 +/- 0.003 0.028 +/- 0.003 0.018 +/- 0.003 0.013 +/- 0.003 0.016 +/- 0.003 0.020 +/- 0.003 0.020 +/- 0. 003 0.017 +/- 0.003 0.030 +/- 0. 004 0.025 +/- 0. 003 0.019 +/- 0. 003 0.016 +/- 0. 003 0.022 +/- 0.009 Date Volume Collected (m) 07-06-11 286 07-12-11 237 07-19-11 280 07-26-11 280 08-02-11 280 08-09-11 278 08-16-11 286 08-23-11 281 08-30-11 284 09-06-11 283 09-13-11 282 09-20-11 285 09-27-11 289 3rd Quarter Mean +/- s.d.
10-04-11 287 10-11-11 287 10-18-11 286 10-25-11 286 11-01-11 289 11-08-11 288 11-15-11 285 11-22-11 272 11-29-11 286 12-06-11 288 12-13-11 282 12-20-11 287 12-28-11 327 01-03-12 246 4th Quarter Mean +/- s.d.
Cumulative Average a lodine-131 concentrations are < 0.07 pCi/m3 unless noted otherwise.
o lodine-131 activity detected, refer to Appendix C, "Supplementary Analyses".
9-1 Gross Beta 0.010 0.025 +/- 0.003 0.033 +/- 0.004 0.028 +/- 0. 004 0.035 +/- 0.004 0.031 +/- 0.004 0.035 +/- 0.004 0.023 +/- 0.003 0.036 +/- 0.004 0.026 +/- 0.003 0.050 +/- 0.004 0.023 +/- 0.003 0.018 +/- 0.003 0.022 +/- 0.003 0.030 +/- 0.008 0.022 +/- 0.004 0.047 +/- 0.005 0.029 +/- 0.004 0.021 +/- 0.003 0.026 +/- 0.003 0.033 +/- 0.004 0.033 +/- 0.004 0.025 +/- 0.004 0.020 +/- 0.003
- 0. 025 +/- 0. 003 0.042 +/- 0.004 0.041 +/- 0.005 0.022 +/- 0.003
- 0. 027 +/- 0.004 0.030 +/- 0.009 0.028
Table 10. Airborne particulates and charcoal canisters, analyses for gross beta and iodine-1 31 a.
Location: T -27 (C)
Units: pCi/m3 Collection: Continuous, weekly exchange.
Date Collected Required LLD 01 1 1 01-1 1-1 1 01-18-1 1 01 1 1 01-31-1 1 02-08-1 1 02-15-1 1 02-22-1 1 03-01-1 1 03-08-1 1 03-1 5-1 1 03-22-1 1 b 03-29-1 1 b Volume (m")
277 291 286 286 247 325 285 286 286 279 284 286 285 1 st Quarter Mean +/- s,d, 04-05-1 1 b 292 04-12-1 1 280 04-19-1 1 291 04-26-1 1 287 05-03-1 1 286 05-10-1 1 285 05-1 7-1 1 281 05-24-1 1 286 05-31-1 1 286 06-07-1 1 286 06-14-1 1 285 06-21-1 1 290 06-29-1 1 329 2nd Quarter Mean +/- s.d.
Gross Beta 0.0 1 0 0.034 +/- 0.004 0.040 +/- 0.004 0.026 +/- 0.004 0.035 +/- 0.004 0.035 +/- 0.004 0.024 +/- 0.003 0.028 +/- 0.003 0.023 +/- 0.003 0.026 +/- 0.004 0.023 +/- 0.003 0,018 +/- 0,003 0,025 +/- 0,004 0,030 +/- 0,004 0,028 +/- 0,006 0,044 +/- 0,004 0,020 +/- 0,003 0,028 +/- 0,003 0,01 8 +/- 0,003 0,016 +/- 0,003 0,016 +/- 0.003 0.020 +/- 0,003 0.01 5 +/- 0.003 0,01 5 +/- 0,003 0.027 +/- 0,004 0,025 +/- 0,003 0,0 1 9 +/- 0,003 0.0 1 6 +/- 0.003 0.021 +/- 0.008 Date Volume Collected (m")
07-06-1 1 285 07-1 2-1 1 238 07-19-1 1 286 07-26-1 1 285 08-02-1 1 284 08-09-1 1 292 08-16-1 1 279 08-23-1 1 297 08-30-1 1 286 09-06-1 1 285 09-1 3-1 1 286 09-20-1 1 279 09-27-1 1 292 3rd Quarter Mean +/- s,d, 1 0-04-1 1 285 1 0-1 1-1 1 288 1 0-18-1 1 286 1 0-25-1 1 279 1 1-01-1 1 292 1 1-08-1 1 286 1 1-1 5-1 1 282 1 1-22-1 1 286 1 1 1 1 288 1 2-06-1 1 285 1 2-1 3-1 1 280 1 2-20-1 1 287 1 2-28-1 1 332 01-03-1 2 248 4th Quarter Mean +/- s.d, Cumulative Average a lodine-131 concentrations are < 0,07 pCilm3 unless noted otherwise, b lodine-1 31 activity detected, refer to Appendix C, "Supplementary Analyses",
10- 1 Gross Beta 0.01 0 0.024 +/- 0.003 0.030 +/- 0.004 0.031 +/- 0.004 0.033 +/- 0.004 0.031 +/- 0.004 0.033 +/- 0.004 0.025 +/- 0.004 0.036 +/- 0.004 0.025 +/- 0.003 0.047 +/- 0,004 0,022 +/- 0,003 0,01 8 +/- 0,003 0.025 +/- 0,003 0,029 +/- 0,007 0.0 1 6 +/- 0,003 0,047 +/- 0,005 0,027 +/- 0,004 0,022 +/- 0,003 0.023 +/- 0,003 0,030 +/- 0,004 0.030 +/- 0,004 0,027 +/- 0,004 0,022 +/- 0,003 0,022 +/- 0.003 0,033 +/- 0,004 0,046 +/- 0.005 0,022 +/- 0.003 0.024 +/- 0.004 0,028 +/- 0.009 0,027
Table 1 1-1. Airborne particulate data,gross beta analyses, monthly averages, minima and maxima.
Location T-9 T-1 1 T-1 2 T-27 Controls T-1 T-2 T-3 T-4 T-7 T-8 Indicators Location T-9 T-1 1 T-1 2 T-27 Controls T-1 T-2 T-3 T-4 T-7 T-8 Indicators Location T-9 T-1 1 T-1 2 T-27 Controls T-1 T-2 T-3 T-4 T-7 T-8 Indicators January Average Minima 0.036 0.027 0.033 0.025 0.036 0.029 0.034 0.026 0.035 0.025 0.033 0.027 0.035 0.028 0.033 0.025 0.036 0.029 0.039 0.025 0.036 0.025 0.035 0.025 February Average Minima 0.026 0.024 0.027 0.01 8 0.026 0.023 0.025 0.023 0.026 0.0 1 8 0.027 0.024 0.020 0.01 1 0.025 0.023 0.026 0.022 0.025 0.021 0.023 0.01 6 0.024 0.01 1 March Average 0.024 0.024 0.023 0.024 0.024 0.024 0.026 0.024 0.025 0.024 0.024 0.025 Minima 0.020 0.01 8 0.01 6 0.01 8 0.01 6 0.0 1 9 0.021 0.01 6 0.0 1 8 0.020 0.0 1 7 0.01 6 Maxima 0.045 0.041 0.043 0.040 0.045 0.041 0.043 0.038 0.040 0.049 0.043 0.049 Maxima 0.027 0.036 0.031 0.028 0.036 0.030 0.024 0.028 0.027 0.027 0.028 0.030 Maxima 0.028 0.029 0.030 0.030 0.030 0.031 0.033 0.029 0.029 0.028 0.030 0.033 Location T-9 T-1 1 T-1 2 T-27 Controls T-1 T-2 T-3 T-4 T-7 T-8 Indicators Location T-9 T-1 1 T-1 2 T-27 Controls T-1 T-2 T-3 T-4 T-7 T-8 Indicators Location T-9 T-1 1 T-1 2 T-27 Controls T-1 T-2 T-3 T-4 T-7 T-8 Indicators April Average Minima 0.024 0.01 7 0.026 0.0 1 6 0.026 0.01 3 0.025 0.01 6 0.025 0.01 3 0.024 0.01 5 0.024 0.01 5 0.028 0.0 1 7 0.028 0.01 9 0.026 0.01 5 0.026 0.014 0.026 0.01 4 May Average Minima 0.01 6 0.01 4 0.020 0.01 2 0.01 8 0.01 6 0.01 7 0.01 5 0.0 1 8 0.01 2 0.0 1 4 0.01 1 0.0 1 7 0.0 1 5 0.0 1 5 0.0 1 3 0.0 1 6 0.0 1 3 0.01 6 0.014 0.014 0.01 1 0.01 5 0.01 1 June Average Minima 0.023 0.0 1 8 0.020 0.01 7 0.023 0.01 6 0.022 0.01 6 0.022 0.01 6 0.020 0.01 5 0.01 9 0.01 5 0.020 0.01 5 0.020 0.0 1 5 0.021 0.01 5 0.021 0.01 7 0.020 0.01 5 Note: U nless otherwise specified, samples collected on the first, second or third day of the month are grouped with data of the previous month.
1 1 - 1 Maxima 0.043 0.046 0.048 0.044 0.048 0.043 0.045 0.040 0.046 0.049 0.041 0.049 Maxima 0.020 0.029 0.020 0.020 0.029 0.01 7 0.021 0.01 9 0.01 8 0.0 1 9 0.01 8 0.021 Maxima 0.027 0.026 0.030 0.027 0.030 0.028 0.025 0.026 0.026 0.029 0.026 0.029
Table 1 1 -1. Airborne particulate data,gross beta analyses, monthly averages, minima and maxima.
Location T-9 T-1 1 T-1 2 T-27 Controls T-1 T-2 T-3 T-4 T-7 T-8 Indicators Location T-9 T-1 1 T-1 2 T-27 Controls T-1 T-2 T-3 T-4 T-7 T-8 Indicators Location T-9 T-1 1 T-1 2 T-27 Controls T-1 T-2 T-3 T-4 T-7 T-8 Indicators July Average Minima Maxima 0.029 0.025 0.036 0.030 0.025 0.035 0.030 0.025 0.035 0.030 0.024 0.033 0.030 0.024 0.036 0.030 0.027 0.034 0.029 0.023 0.046 0.029 0.023 0.041 0.028 0.025 0.031 0.028 0.022 0.032 0.029 0.024 0.032 0.029 0.022 0.046 August Average 0.029 0.030 0.030 0.030 0.030 0.028 0.026 0.028 0.029 0.029 0.029 0.028 Minima 0.021 0.020 0.023 0.025 0.020 0.021 0.01 9 0.022 0.023 0.024 0.022 0.019 September Maxima 0.036 0.038 0.036 0.036 0.038 0.036 0.032 0.033 0.037 0.034 0.035 0.037 Average Minima Maxima 0.030 0.022 0.051 0.023 0.020 0.029 0.028 0.0 1 8 0.050 0.028 0.0 1 8 0.047 0.027 0.0 1 8 0.051 0.026 0.0 1 6 0.047 0.027 0.0 1 6 0.046 0.027 0.0 1 8 0.045 0.028 0.0 1 7 0.048 0.029 0.0 1 8 0.050 0.029 0.020 0.050 0.028 0.01 6 0.050 Location T-9 T-1 1 T-1 2 T-27 Controls T-1 T-2 T-3 T-4 T-7 T-8 Indicators Location T-9 T-1 1 T-1 2 T-27 Controls T-1 T-2 T-3 T-4 T-7 T-8 Indicators Location T-9 T-1 1 T-1 2 T-27 Controls T-1 T-2 T-3 T-4 T-7 T-8 Indicators October Average Minima Maxima 0.027 0.01 7 0.042 0.027 0.01 8 0.050 0.029 0.021 0.047 0.027 0.01 6 0.047 0.028 0.01 6 0.050 0.026 0.0 1 4 0.043 0.028 0.01 6 0.048 0.025 0.01 6 0.040 0.027 0.0 1 7 0.049 0.027 0.01 5 0.047 0.028 0.0 1 7 0.046 0.027 0.0 1 4 0.049 November Average Minima 0.025 0.0 1 8 0.024 0.0 1 7 0.028 0.020 0.027 0.022 0.026 0.0 1 7 0.026 0.01 7 0.026 0.021 0.025 0.019 0.026 0.019 0.027 0.01 6 0.026 0.019 0.026 0.01 6 December Average Minima 0.029 0.022 0.029 0.020 0.031 0.022 0.029 0.022 0.030 0.020 0.025 0.01 5 0.028 0.019 0.027 0.020 0.032 0.022 0.028 0.019 0.028 0.019 0.028 0.01 5 Maxima 0.034 0.028 0.033 0.030 0.034 0.031 0.032 0.029 0.030 0.034 0.029 0.034 Maxima 0.041 0.046 0.042 0.046 0.046 0.035 0.038 0.037 0.045 0.042 0.042 0.045 Note: Unless otherwise specified, samples collected on the first, second or third day of the month are grouped with data of the previous month.
1 1 - 2
Table 1 2. Airborne particulates, analyses for strontium-89, strontium-90 and gamma-emitting isotopes.
Location Quarter Lab Code Volume (m3)
Sr-89 S r-90 8e-7 K-40 Nb-95 Zr-95 Ru-1 03 Ru-1 06 Cs-1 34 Cs-1 37 Ce-1 41 Ce-1 44 Location Quarter Lab Code Volume (m3)
Sr-89 Sr-90 8e-7 K-40 Nb-95 Zr-95 Ru-1 03 Ru-1 06 Cs-1 34 Cs-1 37 Ce-1 41 Ce-1 44 Collection: Quarterly Composite Units: pCilm3 1 st Quarter TAP-1 8 1 9 3932
< 0.0004
< 0.0003 0.066 +/- 0.0 1 2
< 0.023
< 0.0006
< 0.00 1 0
< 0.0008
< 0.0044
< 0.0005
< 0.0005
< 0.00 1 3
< 0.0041 1 st Quarter TAP-1 820 3708
< 0.0005
< 0.0003 0.073 +/- 0.01 4
< 0.024
< 0.0005
< 0.001 1
< 0.0009
< 0.0044
< 0.0006
< 0.0004
< 0.00 1 2
< 0.0040 2nd Quarter TAP-481 1 3878
< 0.0005
< 0.0004 0.072 +/- 0.0 1 5
< 0.021
< 0.00 1 3
< 0.0008
< 0.001 1
< 0.0075
< 0.001 1
< 0.001 1
< 0.00 1 2
< 0.0044 2nd Quarter TAP-481 2 3759
< 0.0005
< 0.0003 0.076 +/- 0.01 5
< 0.0 1 9
< 0.001 4
< 0.001 7
< 0.0007
< 0.0070
< 0.0008
< 0.0008
< 0.001 4
< 0.0051 1 2-1 T-1 3rd Quarter 4th Quarter TAP-701 0 TAP-9 1 53 3673 3966
< 0.0008
< 0.0004
< 0.0004
< 0.0003 0.078 +/- 0.0 1 7 0.074 +/- 0.0 1 3
< 0.023
< 0.027
< 0.0006
< 0.0009
< 0.0007
< 0.00 1 4
< 0.0009
< 0.0007
< 0.0046
< 0.0034
< 0.001 0
< 0.0007
< 0.001 0
< 0.0007
< 0.0020
< 0.0009
< 0.0038
< 0.0042 T-2 3rd Quarter 4th Quarter TAP-701 1 TAP-9 1 54 3679 4004
< 0.0006
< 0.0009
< 0.0003
< 0.0006 0.082 +/- 0.0 1 6 0.066 +/- 0.0 1 4
< 0.023
< 0.022
< 0.0004
< 0.0005
< 0.0007
< 0.001 1
< 0.0009
< 0.0006
< 0.0028
< 0.0046
< 0.0007
< 0.0008
< 0.0006
< 0.0005
< 0.001 8
< 0.0008
< 0.0044
< 0.0044
Table 1 2.
Airborne particulates, analyses for strontium-89, strontium-90 and gamma-emitting isotopes.
Location Quarter Lab Code Volume (m3)
Sr-89 Sr-90 8e-7 K-40 Nb-95 Zr-95 Ru-1 03 Ru-106 Cs-1 34 Cs-1 37 Ce-1 41 Ce-1 44 Location Quarter Lab Code Volume (m3)
Sr-89 Sr-90 8e-7 K-40 Nb-95 Zr-95 Ru-1 03 Ru-1 06 Cs-134 Cs-137 Ce-141 Ce-1 44 Collection: Quarterly Composite Units: pCi/m3 1 st Quarter TAP-1 821 371 5
< 0.0005
< 0.0003 0.062 +/- 0.0 1 3
< 0.022
< 0.001 1
< 0.001 3
< 0.001 2
< 0.0078
< 0.0008
< 0.0006
< 0.001 4
< 0.0034 1 st Quarter TAP-1 822 3744
< 0.0004
< 0.0003 0.078 +/- 0.0 1 4
< 0.022
< 0.0007
< 0.0009
< 0.001 1
< 0.0076
< 0.0008
< 0.001 1
< 0.001 3
< 0.0053 2nd Quarter TAP-481 3 3696
< 0.0005
< 0.0003 0.075 +/- 0.01 3
< 0.0 1 5
< 0.0009
< 0.001 1
< 0.0009
< 0.0072
< 0.0007
< 0.0009
< 0.0009
< 0.0024 2nd Quarter TAP-481 4 3797
< 0.0005
< 0.0004 0.082 +/- 0.01 7
< 0.021
< 0.001 1
< 0.0020
< 0.001 1
< 0.0051
< 0.0008
< 0.0009
< 0.0020
< 0.0049 1 2-2 T-3 3rd Quarter 4th Quarter TAP-7012 TAP-9 1 56 3683 4072
< 0.0005
< 0.0005
< 0.0003
< 0.0003 0.076 +/- 0.01 5 0.059 +/- 0.01 5
< 0.024
< 0.01 8
< 0.0009
< 0.0009
< 0.0022
< 0.00 1 0
< 0.001 3
< 0.0007
< 0.0089
< 0.0065
< 0.0007
< 0.0009
< 0.0009
< 0.0009
< 0.00 1 3
< 0.00 1 6
< 0.0044
< 0.0030 T-4 3rd Quarter 4th Quarter TAP-701 3 TAP-9 1 57 3570 3882
< 0.0005
< 0.0004
< 0.0003
< 0.0003 0.088 +/- 0.01 7 0.067 +/- 0.0 1 2
< 0.020
< 0.021
< 0.001 0
< 0.00 1 0
< 0.001 6
< 0.00 1 8
< 0.0009
< 0.001 1
< 0.0046
< 0.0046
< 0.001 0
< 0.0006
< 0.0008
< 0.0005
< 0.001 3
< 0.001 1
< 0.0034
< 0.0040
Table 12.
Airborne particulates, analyses for strontium-89, strontium-90 and gamma-emitting isotopes.
Location Quarter Lab Code Volume (m)
Sr-89 Sr-90 Be-7 K-40 Nb-95 Zr-95 Ru-1 03 Ru-1 06 Cs-1 34 Cs-1 37 Ce-1 41 Ce-1 44 Location Quarter Lab Code Volume (m3)
Sr-89 S r-90 Be-7 K-40 Nb-95 Zr-95 Ru-1 03 Ru-1 06 Cs-1 34 Cs-1 37 Ce-1 41 Ce-1 44 Collection: Quarterly Composite Units: pCi/m3 1 st Quarter TAP-1 823 3701
< 0.0004
< 0.0003 0.090 +/- 0.01 6
< 0.024
< 0.0006
< 0.0020
< 0.0007
< 0.0088
< 0.0007
< 0.0006
< 0.001 1
< 0.0026 1 st Quarter TAP-1 824 3720
< 0.0004
< 0.0003 0.079 +/- 0.01 4
< 0.020
< 0.0009
< 0.001 1
< 0.0006
< 0.0071 2nd Quarter TAP-481 5 3731
< 0.0004
< 0.0003 0.076 +/- 0.0 1 5
< 0.021
< 0.00 1 3
< 0.00 1 3
< 0.0009
< 0.0069
< 0.0008
< 0.0009
< 0.00 1 7
< 0.0043 2nd Quarter TAP-481 6 3800
< 0.0005
< 0.0004 0.072 +/- 0.0 1 3 0.01 6 +/- 0.009
< 0.0007
< 0.0009
< 0.0008
< 0.0050
< 0.0006 0.001 0 +/- 0.0006
< 0.0009 0.001 2 +/- 0.0007
< 0.00 1 4
< 0.00 1 2
< 0.0031
< 0.0037 T-7 3rd Quarter TAP-701 4 3657
< 0.001 1
< 0.0008 0.090 +/- 0.01 6
< 0.023
< 0.0009
< 0.00 1 6
< 0.001 1
< 0.0083
< 0.001 1
< 0.0008
< 0.001 5
< 0.0059 T-8 3rd Quarter TAP-701 6 3606
< 0.0006
< 0.0004 0.089 +/- 0.01 6
< 0.023
< 0.001 1
< 0.001 1
< 0.00 1 4
< 0.0053 a
< 0.0007 a
< 0.0007
< 0.00 1 9
< 0.0050 a Activity observed in second quarter air samples most likely attributable to Fukushima Daiichi accident.
1 2-3 4th Quarter TAP-91 58 401 4
< 0.0005
< 0.0003 0.059 +/- 0.01 1
< 0.022
< 0.0007
< 0.00 1 2
< 0.0009
< 0.0066
< 0.0007
< 0.0007
< 0.00 1 6
< 0.0043 4th Quarter TAP-91 59 3985
< 0.0005
< 0.0003 0.073 +/- 0.0 1 2
< 0.023
< 0.0004
< 0.00 1 8
< 0.001 1
< 0.0060
< 0.0005
< 0.0007
< 0.00 1 0
< 0.0036
Table 1 2.
Airborne particulates, analyses for strontium-89, strontium-90 and gamma-emitting isotopes.
Location Quarter Lab Code Volume (m3)
Sr-89 Sr-90 8e-7 K-40 Nb-95 Zr-95 Ru-1 03 Ru-1 06 Cs-1 34 Cs-1 37 Ce-1 41 Ce-1 44 Location Quarter Lab Code Volume (mj)
Sr-89 Sr-90 8e-7 K-40 Nb-95 Zr-95 Ru-1 03 Ru-1 06 Cs-1 34 Cs-1 37 Ce-1 41 Ce-1 44 Collection: Quarterly Composite Units: pCi/m3 1 st Quarter TAP-1 825 3720
< 0.0005
< 0.0003 0.069 +/- 0.0 1 6
< 0.023
< 0.0006
< 0.0009
< 0.001 1
< 0.0085
< 0.0009
< 0.0007
< 0.001 4
< 0.0060 1 st Quarter TAP-1 826 3688
< 0.0004
< 0.0003 0.065 +/- 0.01 5
< 0.025
< 0.0004
< 0.001 6
< 0.0005
< 0.0065
< 0.0006 2nd Quarter TAP-481 7 3762
< 0.0006
< 0.0004 0.088 +/- 0.0 1 7
< 0.024
< 0.001 2
< 0.001 9
< 0.0008
< 0.0060
< 0.0009
< 0.001 0
< 0.001 5
< 0.0047 2nd Quarter TAP-481 8 3733
< 0.0005
< 0.0004 0.083 +/- 0.01 5
< 0.0 1 9
< 0.001 1
< 0.001 4
< 0.001 1
< 0.0039
< 0.0007
< 0.0006 0.001 5 +/- 0.0009
< 0.0007
< 0.001 7
< 0.0034
< 0.0032 T-9 (C) 3rd Quarter TAP-701 7 3675
< 0.0006
< 0.0004 0.091 +/- 0.0 1 8
< 0.023
< 0.0004
< 0.001 4
< 0.0009
< 0.0076
< 0.0006
< 0.0008
< 0.00 1 7
< 0.0047 T-1 1 (C) 3rd Quarter TAP-701 8 3333
< 0.0006
< 0.0004 0.089 +/- 0.01 7 0.027 +/- 0.0 1 5
< 0.001 2
< 0.001 2
< 0.0007
< 0.0039
< 0.0006 a
< 0.0007
< 0.001 3
< 0.0033 a Activity observed in second quarter air samples most likely attributable to Fukushima Daiichi accident.
1 2-4 4th Quarter TAP-9 1 60 3998
< 0.0004
< 0.0003 0.066 +/- 0.0 1 3
< 0.020
< 0.001 0
< 0.0009
< 0.001 0
< 0.0068
< 0.0007
< 0.0007
< 0.001 6
< 0.0042 4th Quarter TAP-9 1 61 3980
< 0.0004
< 0.0003 0.062 +/- 0.0 1 3
< 0.021
< 0.0008
< 0.001 0
< 0.0007
< 0.0071
< 0.0008
< 0.0008
< 0.001 9
< 0.0035
Table 12, Airborne particulates, analyses for strontium-89, strontium-90 and gamma-emitting isotopes, Collection: Quarterly Composite U nits: pCilm3 Location T-1 2 (C)
Quarter 1 st Quarter 2nd Quarter 3rd Quarter 4th Quarter Lab Code TAP-1 827 TAP-481 9 TAP-701 9 TAP-91 62 Volume (mj) 3849 3783 3631 3996 Sr-89
< 0,0004
< 0,0009
< 0,0005
< 0,0004 Sr-90
< 0,0003
< 0,0006
< 0,0003
< 0,0003 Be-7 0,079 +/- 0,01 2 0,066 +/- 0,0 1 2 0,088 +/- 0,0 1 8 0,069 +/- 0,01 4 K-40
< 0,020 0,01 9 +/- 0,009
< 0,023
< 0,022 Nb-95
< 0,001 2
< 0,0007
< 0,0005
< 0,0004 Zr-95
< 0,001 9
< 0,00 1 2
< 0,0009
< 0,0006 Ru-1 03
< 0,001 0
< 0,0006
< 0,00 1 1
< 0,0006 Ru-1 06
< 0,0068
< 0,0054
< 0,0035
< 0,0064 Cs-1 34
< 0,0006
< 0,0008
< 0,0008
< 0,0004 Cs-137
< 0,001 0
< 0,0005
< 0,0006
< 0,0004 Ce-1 41
< 0,001 3
< 0,00 1 3
< 0,00 1 5
< 0,00 1 4 Ce-1 44
< 0,0058
< 0,0037
< 0,0048
< 0,0036 Location T-27 (C)
Quarter 1 st Quarter 2nd Quarter 3rd Quarter 4th Quarter Lab Code TAP-1 828 TAP-4820 TAP-7020 TAP-9 1 63 Volume (mj) 3703 3764 3674 4004 Sr-89
< 0,0004
< 0,0005
< 0,0005
< 0,0004 Sr-90
< 0,0003
< 0,0004
< 0,0003
< 0,0003 Be-7 0,089 +/- 0,0 1 6 0,079 +/- 0,01 5 0,094 +/- 0,01 6 0,081 +/- 0,0 1 4 K-40
< 0,022
< 0,022
< 0,023
< 0,0 1 8 Nb-95
< 0,0008
< 0,0021
< 0,0008
< 0,00 1 0 Zr-95
< 0,001 2
< 0,001 7
< 0,0009
< 0,00 1 0 Ru-1 03
< 0,001 1
< 0,00 1 2
< 0,0007
< 0,0009 Ru-1 06
< 0,0073
< 0,0083
< 0,0041
< 0,0055 Cs-1 34
< 0,0007
< 0,001 1
< 0,0006
< 0,0008 Cs-1 37
< 0,001 0
< 0,00 1 3
< 0,0006
< 0,0006 Ce-1 41
< 0,001 3
< 0,00 1 2
< 0,001 1
< 0,00 1 2 Ce-1 44
< 0,0048
< 0,0053
< 0,0041
< 0,0029 1 2-5
Table 13. Area monitors (TLD), Quarterly.
Units: mR/91 days 1 st Qtr.
2nd Qtr.
3rd Qtr.
4th Qtr.
Indicator T-1 12.3 +/- 1.1 12.0 +/- 0.6 12.3 +/- 0.8 12.5 +/- 0.8 T-2 14.2 +/- 0.9 14.8 +/- 0.7 14.4 +/- 0.6 15.4 +/- 0.8 T-3 14.5 +/- 1.0 14.2 +/- 0.9 15.3 +/- 1.0 15.5 +/- 1.1 T-4 14.2 +/- 0.6 14.0 +/- 0.8 14.5 +/- 0.6 14.9 +/- 0.8 T-5 16.7 +/- 1.2 16.6 +/- 0.6 16.6 +/- 0.9 18.3 +/- 0.8 T-6 14.8 +/- 1.3 12.4 +/- 0.6 14.9 +/- 1.2 14.2 +/- 0.9 T-7 19.9 +/- 0.6 20.5 +/- 0.7 21.5 +/- 0.5 21.8 +/- 0.8 T-8 23.8 +/- 1.4 25.9 +/- 2.1 25.6 +/- 1.8 23.7 +/- 1.6 T-10 16.5 +/- 0.7 17.9 +/- 0.8 17.7 +/- 0.9 18.8 +/- 0.9 T-38 11.8 +/- 0.7 13.4 +/- 1.1 14.1 +/- 0.8 14.2 +/- 1.3 T-39 12.8 +/- 1.1 13.0 +/- 0.7 14.8 +/- 1.4 13.8 +/- 0.8 T-40 15.8 +/- 0.5 16.3 +/- 0.7 17.9 +/- 0.6 17.0 +/- 0.8 T-41 11.5 +/- 0.7 13.5 +/- 0.7 13.1 +/- 0.7 14.3 +/- 0.7 T-42 13.6 +/- 0.9 13.8 +/- 0.9 15.5 +/- 1.0 15.1 +/- 1.3 T-43 17.5 +/- 0.9 18.1 +/- 0.7 21.2 +/- 1.0 18.7 +/- 0.9 T-44 19.9 +/- 1.0 20.2 +/- 0.9 23.1 +/- 1.3 21.3 +/- 1.2 T-45 23.4 +/- 0.9 24.8 +/- 0.7 27.2 +/- 0.5 25.4 +/- 0.8 T-46 15.4 +/- 0.8 15.5 +/- 0.8 17.2 +/- 1.2 16.8 +/- 1.1 T-47 13.2 +/- 1.0 10.9 +/- 0.7 14.5 +/- 1.3 12.5 +/- 1.1 T-48 14.3 +/- 0.5 14.6 +/- 0.8 15.7 +/- 0.6 15.6 +/- 0.8 T-49 12.7 +/- 0.8 11.7 +/- 1.2 14.3 +/- 0.7 13.0 +/- 1.4 T-50 16.0 +/- 0.5 19.6 +/- 1.5 18.4 +/- 0.6 19.9 +/- 2.1 T-51 18.9 +/- 1.7 23.4 +/- 0.9 22.4 +/- 2.1 22.3 +/- 1.1 T-52 19.2 +/- 1.1 21.1 +/- 0.6 22.7 +/- 1.5 19.5 +/- 0.8 T-53 18.0 +/- 0.5 18.5 +/- 1.8 20.9 +/- 0.7 16.3 +/- 2.1 T-54 17.9 +/- 0.5 20.4 +/- 0.8 20.2 +/- 0.6 18.2 +/- 1.0 T-55 14.7 +/- 1.2 17.7 +/- 0.9 16.9 +/- 1.3 16.9 +/- 1.2 T-60 12.2 +/- 1.2 12.7 +/- 1.2 12.2 +/- 0.8 12.8 +/- 1.5 T-62 12.7 +/- 0.6 12.1 +/- 0.9 13.1 +/- 0.6 12.8 +/- 1.3 T-65 19.8 +/- 0.9 19.5 +/- 0.9 21.2 +/- 1.1 19.8 +/- 0.8 T-66 22.7 +/- 0.8 22.7 +/- 2.1 23.3 +/- 0.9 22.0 +/- 0.7 T-67 22.3 +/- 1.4 21.7 +/- 1.2 24.0 +/- 1.3 22.1 +/- 0.9 T-68 17.1 +/- 1.3 17.4 +/- 1.4 18.1 +/- 0.9 18.5 +/- 0.9 T-69 20.9 +/- 0.8 19.2 +/- 0.8 21.7 +/- 0.6 19.7 +/- 0.7 T-71 19.2 +/- 0.6 18.6 +/- 1.1 19.4 +/- 0.5 16.6 +/- 0.8 T-73 15.4 +/- 1.1 14.8 +/- 1.1 17.5 +/- 1.7 15.4 +/- 1.3 T-74 18.2 +/- 0.8 18.7 +/- 1.4 19.4 +/- 0.8 19.4 +/- 1.5 T-75 17.8 +/- 0.7 17.1 +/- 0.9 19.0 +/- 0.5 17.3 +/- 0.7 T-76 13.6 +/- 0.7 13.1 +/- 1.0 15.3 +/- 0.6 13.3 +/- 0.8 T-91 19.9 +/- 1.2 21.8 +/- 1.8 21.9 +/- 1.3 21.8 +/- 1.8 T-92 13.9 +/- 0.6 15.9 +/- 0.8 16.3 +/- 0.8 16.3 +/- 0.8 1 3-1
Table 13. Area monitors (TLO), Quarterly.
Units: mR/91 days 1 st Qtr.
2nd Qtr.
3rd Qtr.
4th Qtr.
Indicator T-93 17.5 +/- 0.9 15.6 +/- 0.9 19.9 +/- 1.4 16.2 +/- 0.8 T-94 18.3 +/- 1.1 17.7 +/- 1.0 20.4 +/- 1.0 18.4 +/- 1.3 T-112 15.4 +/- 0.8 11.7 +/- 0.8 16.6 +/- 0.7 12.0 +/- 0.8 T-121 19.4 +/- 1.7 20.8 +/- 1.3 21.1 +/- 1.0 20.4 +/- 1.2 T-122 17.1 +/- 1.2 16.1 +/- 0.8 18.6 +/- 1.4 18.1 +/- 0.7 T-123 19.6 +/- 1.2 19.1 +/- 0.7 20.4 +/- 1.4 19.7 +/- 0.7 T-125 18.7 +/- 0.9 17.4 +/- 0.8 19.0 +/- 0.8 17.7 +/- 0.8 T-126 18.5 +/- 0.8 17.5 +/- 1.0 19.2 +/- 0.5 17.9 +/- 1.0 T-127 20.0 +/- 0.8 20.5 +/- 1.0 22.5 +/- 0.7 20.1 +/- 1.1 T-128 20.6 +/- 1.9 19.7 +/- 0.8 21.5 +/- 2.0 19.6 +/- 0.7 T-142 13.7 +/- 0.9 11.9 +/- 0.8 14.2 +/- 0.7 12.6 +/- 0.7 T-150 14.9 +/- 0.9 14.2 +/- 1.4 15.5 +/- 0.9 14.1 +/- 1.5 T-151 18.5 +/- 0.9 18.9 +/- 0.9 20.0 +/- 0.8 18.2 +/- 0.9 T-153 18.2 +/- 0.7 17.3 +/- 0.8 19.6 +/- 0.7 16.7 +/- 0.8 T-154 15.5 +/- 0.9 15.2 +/- 0.9 16.1 +/- 1.1 14.9 +/- 1.0 T-201 13.0 +/- 1.1 8.3 +/- 0.8 14.0 +/- 1.0 14.0 +/- 0.3 T-202 13.1 +/- 1.1 4.2 +/- 0.6 13.6 +/- 1.1 14.4 +/- 0.6 T-203 13.1 +/- 1.1 3.8 +/- 0.4 13.6 +/- 1.2 14.8 +/- 1.2 T-204 11.2 +/- 1.1 13.9 +/- 1.4 11.8 +/- 1.0 11.3 +/- 0.6 T-205 10.0 +/- 1.1 11.0 +/- 0.5 10.2 +/- 1.1 13.5 +/- 1.2 T-206 9.4 +/- 1.2 11.2 +/- 0.3 9.4 +/- 1.3 11.7 +/- 0.4 T-207 9.2 +/- 1.5 7.9 +/- 0.4 9.0 +/- 1.3 8.1 +/- 0.5 T-208 9.7 +/- 1.6 10.7 +/- 0.7 10.0 +/- 1.7 11.1 +/- O.4 T-211 12.1 +/- 0.9 10.9 +/- 0.6 13.1 +/- 1.2 11.7 +/- 0.6 T-212 11.7 +/- 0.6 12.3 +/- 0.8 13.0 +/- 0.8 13.2 +/- 0.8 T-213 18.1 +/- 0.6 18.6 +/- 0.8 19.7 +/- 0.6 18.8 +/- 0.9 T-214 18.7 +/- 0.7 21.2 +/- 0.7 20.8 +/- 0.7 20.6 +/- 0.8 T-215 18.9 +/- 1.2 19.7 +/- 1.0 21.3 +/- 1.0 19.9 +/- 0.9 T-216 17.8 +/- 0.7 18.2 +/- 1.1 18.7 +/- 0.9 18.2 +/- 1.4 T-217 19.5 +/- 0.9 21.9 +/- 1.7 21.9 +/- 1.1 22.0 +/- 1.7 T-218 19.4 +/- 1.0 23.1 +/- 0.9 21.2 +/- 0.8 21.7 +/- 0.9 T-219 15.2 +/- 0.8 18.2 +/- 1.3 16.2 +/- 0.8 17.8 +/- 1.6 T-220 17.8 +/- 0.9 22.3 +/- 1.6 19.9 +/- 0.8 21.8 +/- 1.8 T-222 11.3 +/- 0.8 13.7 +/- 0.7 11.8 +/- 0.8 13.7 +/- 0.7 T-223 12.7 +/- 0.7 13.6 +/- 0.8 13.5 +/- 0.7 13.8 +/- 0.9 T-224 15.3 +/- 1.1 16.3 +/- 0.8 16.7 +/- 1.0 15.7 +/- 0.6 Mean +/- s.d.
16.1 +/- 3.4 16.3 +/- 4.4 17.5 +/- 4.0 16.9 +/- 3.5 1 3-2
Table 13. Area monitors (TLO), Quarterly.
Units: mR/91 days 1 st Qtr.
2nd Qtr.
3rd Qtr.
4th Qtr.
Control T-9 15.1 +/- 0.7 16.3 +/- 0.9 16.0 +/- 0.6 17.1 +/- 1.0 T-11 14.4 +/- 0.6 15.0 +/- 0.8 15.4 +/- 0.7 16.0 +/- 1.1 T-12 22.1 +/- 0.6 24.6 +/- 1.2 24.1 +/- 0.6 24.7 +/- 1.0 T-24 17.9 +/- 1.0 20.2 +/- 0.7 19.6 +/- 1.1 19.9 +/- 0.8 T-27 18.7 +/- 1.1 20.9 +/- 0.9 22.7 +/- 1.2 21.3 +/- 1.0 Mean +/- s.d.
17.6 +/- 3.1 19.4 +/- 3.8 19.6 +/- 3.9 19.8 +/- 3.5 T-95 16.7 +/- 1.5 17.8 +/- 0.9 18.7 +/- 1.4 16.8 +/- 0.9 T-100 15.5 +/- 1.9 16.5 +/- 1.0 16.6 +/- 2.0 16.0 +/- 1.2 T-111 19.2 +/- 1.8 18.8 +/- 1.1 21.0 +/- 1.9 18.9 +/- 0.9 T-124 16.9 +/- 1.7 16.3 +/- 1.6 17.6 +/- 1.5 NO a T-155 13.3 +/- 0.8 13.9 +/- 1.1 13.6 +/- 0.6 13.5 +/- 1.3 T-221 14.8 +/- 1.4 19.7 +/- 1.3 16.3 +/- 0.8 19.2 +/- 1.2 Mean +/- s.d.
16.1 +/- 2.0 17.2 +/- 2.1 17.3 +/- 2.5 16.9 +/- 2.3 QC T-80 10.2 +/- 0.9 10.0 +/- 0.8 10.4 +/- 0.8 10.2 +/- 0.8 T-81 18.3 +/- 1.0 17.9 +/- 0.8 19.5 +/- 1.1 17.7 +/- 0.7 T-82 10.5 +/- 0.7 10.7 +/- 0.8 11.5 +/- 0.8 10.7 +/- 0.7 T-83 9.8 +/- 0.7 11.0 +/- 1.3 10.5 +/- 0.9 10.8 +/- 1.7 T-84 11.5 +/- 0.9 11.4 +/- 0.8 12.7 +/- 1.0 11.3 +/- 0.8 T-85 13.6 +/- 0.9 13.9 +/- 1.0 15.3 +/- 1.0 14.2 +/- 1.2 T-86 21.7 +/- 1.1 21.7 +/- 1.1 24.1 +/- 1.0 21.8 +/- 1.3 T-88 16.6 +/- 1.3 19.1 +/- 0.9 18.9 +/- 1.4 19.1 +/- 1.1 T-89 18.1 +/- 1.0 19.3 +/- 0.8 20.1 +/- 1.1 19.8 +/- 0.9 T-113 15.0 +/- 0.9 15.5 +/- 1.0 16.7 +/- 1.1 15.6 +/- 0.9 T-114 14.7 +/- 0.9 13.4 +/- 1.0 15.5 +/- 0.8 NO a T-115 13.0 +/- 1.0 15.7 +/- 0.9 14.7 +/- 0.9 16.2 +/- 0.8 T-116 16.0 +/- 0.7 17.2 +/- 1.1 16.8 +/- 0.8 17.2 +/- 1.3 T-117 13.7 +/- 1.0 14.1 +/- 1.2 14.6 +/- 1.1 13.9 +/- 1.5 T-118 16.1 +/- 1.1 16.5 +/- 1.1 17.1 +/- 0.9 16.4 +/- 1.3 T-119 15.1 +/- 0.7 13.8 +/- 0.8 15.7 +/- 0.8 14.7 +/- 0.9 T-120 13.0 +/- 1.0 11.1 +/- 1.0 13.3 +/- 0.7 12.1 +/- 0.8 T-200 11.6 +/- 1.2 11.9 +/- 0.6 12.4 +/- 1.0 13.6 +/- 0.8 Mean +/- s.d.
14.4 +/- 3.2 14.7 +/- 3.4 15.5 +/- 3.6 15.0 +/- 3.4 Shield T-87 8.2 +/- 0.7 8.1 +/- 0.8 9.4 +/- 0.6 7.9 +/- 1.0 a NO = No Data, TLO lost in the field.
1 3-3
Table 1 4. Area monitors (TLO), Annual.
Units: mR/365 days Indicator 201 1 T-1 47.2 +/- 1.4 T-2 61. 5 +/- 1.7 T-3 59.9 +/- 2.9 T-4
- 52. 1 +/- 1.9 T-5 67.7 +/- 2.9 T-6 54.3 +/- 1.5 T-7 8 1.3 +/- 6.3 T-8 1 04.6 +/- 2.0 T-1 0 72.0 +/- 3.4 T-38 53.5 +/- 2.0 T-39 50.6 +/- 1.8 T-40 67.5 +/- 2.3 T-41 47.7 +/- 1.7 T-42 55.3 +/- 2.1 T-43 7 1.2 +/- 2.1 T-44 82.3 +/- 3.8 T-45 95.4 +/- 4.6 T-46 59.7 +/- 3.7 T-47 38.6 +/- 1.2 T-48 49.6 +/- 1.7 T-49 39.0 +/- 1.6 T-50 74.6 +/- 2.5 T-51 83.6 +/- 2.1 T-52 77.3 +/- 1.9 T-53 70.9 +/- 1.3 T-54 80.9 +/- 3.3 T-55 66.9 +/- 5.7 T-60 53.3 +/- 2.5 T-62 49.0 +/- 3.4 T-65 77.5 +/- 4.8 T-66 79.0 +/- 2.7 T-67 77.7 +/- 3.1 T-68 62.5 +/- 1.9 T-69 7 1.6 +/- 1.8 T-71 64.1 +/- 1.0 T-73 55.2 +/- 1.4 T-74 65.4 +/- 2.0 T-75 63.6 +/- 4.5 T-76 47.3 +/- 1.7 T-91 70.4 +/- 1.2 T-92 50.6 +/- 1.8 1 4-1
Table 1 4. Area monitors (TLD), Annual.
Indicator T-93 T-94 T-1 1 2 T-1 2 1 T-1 22 T-1 23 T-1 25 T-1 26 T-1 27 T-1 28 T-1 42 T-1 50 T-1 51 T-1 53 T-1 54 T-201 T-202 T-203 T-204 T-205 T-206 T-207 T-208 T-2 1 1 T-2 1 2 T-21 3 T-2 1 4 T-2 1 5 T-2 1 6 T-2 1 7 T-2 1 8 T-2 1 9 T-220 T-222 T-223 T-224 Units: mR/365 days Mean +/- s.d.
a NO = No Data, TLD lost in the field.
201 1
- 55. 1 +/- 1.2 64.5 +/- 1.6 51.9 +/- 1.4 75.7 +/- 2.7 59.8 +/- 1.7 68.7 +/- 1.9 63.2 +/- 1.3 62.1 +/- 1.0 72.4 +/- 1.6 72.5 +/- 5.8 41.9 +/- 1.3 55.0 +/- 4.2 69.6 +/- 1.4 71.0 +/- 2.6 58.5 +/- 1.2 54.2 +/- 2.7 51.5 +/- 2.7 53.3 +/- 2.7 44.1 +/- 2.9 41. 1 +/- 2.8 41.9 +/- 2.6 39.3 +/- 2.7 42.0 +/- 2.7 42.1 +/- 3.0 42.8 +/- 1.9 66.6 +/- 3.2 63.3 +/- 1.9 72.1 +/- 2.2 62.2 +/- 3.0 74.1 +/- 2.1 8 1. 1 +/- 1.6 57.8 +/- 2.4 68.7 +/- 2.1 48.7 +/- 1.5 53.2 +/- 2.0 56.0 +/- 2.7 61.7 +/- 1 3.7 1 4-2
Table 1 4. Area monitors (TLO), Annual.
T-9 T-1 1 T-1 2 T-24 T-27 Units: mRl365 days Mean +/- s.d.
T-95 T-1 00 T-1 1 1 T-1 24 T-1 55 T-221 Mean +/- s.d.
T-80 T-81 T-82 T-83 T-84 T-85 T-86 T-88 T-89 T-1 1 3 T-1 1 4 T-1 1 5 T-1 1 6 T-1 1 7 T-1 1 8 T-1 1 9 T-1 20 T-200 Mean +/- s.d.
T-87 a NO = No Oata, TLO lost in the field.
201 1 62.7 +/- 1.4 55.1 +/- 1.7 1 0 1.6 +/- 2.4 83.3 +/- 3.1 90.1 +/- 2.0 78.6 +/- 1 9.3 62.0 +/- 2.5 56.4 +/- 2.0 63.0 +/- 3.1 NO a 48.8 +/- 1.8 63.9 +/- 1.9 58.8 +/- 6.3 42.8 +/- 1.3 60.1 +/- 1.4 41.4 +/- 2. 1 37.7 +/- 1.3 46.5 +/- 1.5 48.5 +/- 2.5 76.4 +/- 4.3 63.2 +/- 1.6 49.1 +/- 1.2 58.8 +/- 1.9 NO a 56.0 +/- 1.8 64.4 +/- 1.3 55.9 +/- 1.5 58.6 +/- 1.3 55.2 +/- 2.8 44.5 +/- 1.3 47.3 +/- 3.1 53.3 +/- 9.9 26.8 +/- 1.0 1 4-3
Table 1 5. Milk, analyses for strontium-89, strontium-90, iodine-1 31, gamma emitting isotopes, calcium and stable potassium.
Monthly collections, location T-24 Units: pC ilL Date Collected 01-31-1 1 02-28-1 1 03-30-1 1 05-04-1 1 Lab Code TMI-441 TMI-829 TMI-1450 TMI-271 6 1-1 31
< 0.3
< 0.3
< 0.4
< 0.4 Sr-89
< 0.5
< 0.6
< 0.5
< 0.5 Sr-90 0.6 +/- 0.3 0.9 +/- 0.4 0.7 +/- 0.3 0.5 +/- 0.3 K-40 1 392 +/- 1 1 8 1 341 +/- 1 1 0 1 4 1 0 +/- 1 1 5 1 286 +/- 1 1 0 Cs-1 34
< 2.9
< 3.3
< 3.8
< 3.5 Cs-137
< 4.5
< 3.5
< 4.5
< 3.9 Ba-La-140
< 3.3
< 2.2
< 3.2
< 2.1 Ca (giL) 1.22 1.29 1.26 1. 1 0 Sr-90/g Ca 0.49 0.70 0.56 0.45 K (giL) 1.70 +/- 0. 1 4 1.64 +/- 0. 1 3 1.72 +/- 0.14 1.57 +/- 0. 1 3 Cs-1 37/g K
< 2.65
< 2. 1 3
< 2.62
< 2.48 Date Collected 05-31-1 1 06-29-1 1 08-02-1 1 08-31-1 1 Lab Code TMI-3352 TMI-4067 TMI-5248 TMI-5849 1-1 31
< 0.4
< 0.5
< 0.4
< 0.4 Sr-89
< 0.5
< 0.6
< 0.6
< 0.7 Sr-90 0.5 +/- 0.3
< 0.5
< 0.6
< 0.6 K-40 1 297 +/- 1 1 4 1 3 1 4 +/- 1 23 1 350 +/- 1 1 9 1 387 +/- 1 1 5 Cs-134
< 3.6
< 3.4
< 3.1
< 3.0 Cs-1 37
< 4.4
< 4.5
< 2.9
< 3.7 Ba-La-1 40
< 1.7
< 2.9
< 2.1
< 1.9 Ca (giL) 1.29 0.93 1.05 0.97 Sr-90/g Ca 0.39
< 0.54
< 0.57
< 0.62 K (giL) 1.58 +/- 0.14 1.60 +/- 0. 1 5 1.65 +/- 0.15 1.69 +/- 0.14 Cs-1 37/g K
< 2.78
< 2.81
< 1.76
< 2.19 Date Collected 09-28-1 1 1 0-31-1 1 1 1-29-1 1 01-04-1 2 Lab Code TMI-6493 TMI-761 9 TMI-8393 TMI-91 00 1-1 31
< 0.2
< 0.3
< 0.2
< 0.3 Sr-89
< 0.6
< 0.6
< 0.5
< 0.6 Sr-90
< 0.5 0.6 +/- 0.3 0.6 +/- 0.3 0.6 +/- 0.3 K-40 1 346 +/- 1 1 7 1 388 +/- 1 00 1 391 +/- 1 1 7 1 362 +/- 1 1 5 Cs-134
< 3.3
< 3.2
< 3.7
< 3.0 Cs-1 37
< 3.4
< 3.1
< 2.1
< 3.3 Ba-La-1 40
< 3.2
< 3.1
< 2.3
< 1.9 Ca (giL) 1.1 3 1.20 1.01 1.22 Sr-90/g Ca
< 0.44 0.50 0.59 0.49 K (giL) 1.64 +/- 0.14 1.69 +/- 0.12 1.70 +/- 0.1 4 1.66 +/- 0. 1 4 Cs-1 37/g K
< 2.07
< 1.83
< 1.24
< 1.99 a Corrected value.
1 5-1
Table 1 6. Ground water samples, analyses for gross beta, tritium, strontium-89, strontium-90 and gamma-emitting isotopes.
Collection: Quarterly Units: pCi/L Period 1 st Qtr.
2nd Qtr.
3rd Qtr.
4th Qtr.
Location T-27A (C)
Lab Code NO TWW-3431 TWW-5981 TWW-7663 Req. LLD Date Collected 04-1 9-1 1 08-24-1 1 1 0-25-1 1 Gross beta
< 1.6 1.7 +/- 0.8 3.2 +/- 1.3 4.0 H-3
< 330
< 330
< 330 330 Sr-89
< 1.5
< 0.8
< 0.8 Sr-90
< 0.5
< 0.4
< 0.5 Mn-54
< 1.2
< 2.2
< 2.6 1 5 Fe-59
< 4.5
< 4.1
< 5.7 30 Co-58
< 1.2
< 1.8
< 2.4 1 5 Co-60
< 1.0
< 1.6
< 2.0 1 5 Zn-65
< 2.0
< 3.3
< 1.8 30 Zr-Nb-95
< 2.1
< 2.6
< 4.3 1 5 Cs-1 34
< 0.9
< 3.2
< 2.7 1 5 Cs-1 37
< 1.2
< 3.6
< 2.1 1 8 Ba-La-1 40
< 23.3
< 6.7
< 3.3 1 5 Location T-225 (I)
Lab Code NO NO TWW-5983 TWW-7665 Req. LLD Date Collected 08-24-1 1 1 0-25-1 1 Gross beta 1.7 +/- 0.3 1.3 +/- 0.6 4.0 H-3
< 330
< 330 330 Sr-89
< 0.9
< 0.8 Sr-90
< 0.5
< 0.5 Mn-54
< 2.4
< 2.5 1 5 Fe-59
< 7.1
< 5.5 30 Co-58
< 2.7
< 2.4 1 5 Co-60
< 1.6
< 2.6 1 5 Zn-65
< 1.9
< 3.3 30 Zr-Nb-95
< 3.1
< 3.1 1 5 Cs-134
< 2.4
< 2.0 1 5 Cs-137
< 2.0
< 2.5 1 8 Ba-La-1 40
< 3.6
< 3.7 1 5 NO = No Data, Sample not received.
1 6-1
Table 1 6. Ground water samples, analyses for gross beta, tritium, strontium-89, strontium-90 and gamma-emitting isotopes.
Collection: Quarterly U nits: pCi/L Period 1 st Qtr.
2nd Qtr.
3rd Qtr.
4th Qtr.
Location T-226 (I)
Lab Code NO TWW-3433 TWW-5984 TWW-7666 Req. LLD Date Collected 05-3 1 -1 1 08-24-1 1 1 0-25-1 1 Gross beta 1.6 +/- 0.4 1.3 +/- 0.3 1.5 +/- 0.7 4.0 H-3
< 330
< 330
< 330 330 Sr-89
< 0.9
< 0.9
< 0.8 Sr-90
< 0.5
< 0.5
< 0.5 Mn-54
< 1.9
< 2.1
< 1.8 1 5 Fe-59
< 5.2
< 5.6
< 3.0 30 Co-58
< 2.3
< 2.3
< 1.6 1 5 Co-60
< 1.9
< 1.7
< 1.1 1 5 Zn-65
< 2.9
< 5.0
< 2.0 30 Zr-Nb-95
< 2.0
< 2.7
< 2.5 1 5 Cs-1 34
< 2.5
< 2.7
< 1.8 1 5 Cs-1 37
< 3.1
< 3.7
< 2.7 1 8 Ba-La-1 40
< 1.8
< 5.4
< 1.6 1 5 Location T-141 (QC)
Lab Code NO TWW-3432 TWW-5982 TWW-7664 Req. LLD Date Collected 04-1 9-1 1 08-24-1 1 1 0-25-1 1 Gross beta
< 1.6 1.1 +/- 0.3 1.8 +/- 1.3 4.0 H-3
< 330
< 330
< 330 330 Sr-89
< 1.6
< 0.9
< 0.7 Sr-90
< 0.5
< 0.5
< 0.5 Mn-54
< 1.1
< 2.0
< 2.5 1 5 Fe-59
< 3.7
< 2. 1
< 5.8 30 Co-58
< 1.7
< 1.5
< 2.0 1 5 Co-60
< 0.8
< 2. 1
< 1.7 1 5 Zn-65
< 2.2
< 3.4
< 2.9 30 Zr-Nb-95
< 2.1
< 3.8
< 3.5 1 5 Cs-134
< 0.8
< 2.4
< 1.9 1 5 Cs-1 37
< 1.2
< 2.7
< 1.8 1 8 Ba-La-1 40
< 22.7
< 5.9
< 3.4 1 5 NO = No Data, Sample not received.
1 6-2
Table 1 8. Wild meat, analyses for gamma-emitting isotopes.
Location Lab Code Collection: Annually Units: pCi/g wet Date Collected Sample Type Be-7 K-40 Nb-95 Zr-95 Ru-1 03 Ru-106 Cs-134 Cs-137 Ce-141 Ce-144 NO = No Data, Sample not received.
T -31 (I)
TWL-9 1 05 1 2-08-1 1 Muskrat
< 0.062 2.72 +/- 0.1 97
< 0.0068
< 0.0096
< 0.0052
< 0.0435
< 0.0036
< 0.0056
< 0.01 79
< 0.0279 1 8-1 T-2 1 0 (C)
NO
Table 1 9. Green leafy vegetables, analyses for strontium-89, strontium-90, iodine-131 and other gamma-emitting isotopes.
Collection: Monthly, in season Units: pCi/g wet Location T-227 (I)
Lab Code TVE-5750 TVE-6496 TVE-7244 Date Collected 08-24-1 1 09-27-1 1 1 0-18-1 1 Sample Type Cabbage Cabbage Cabbage Sr-89
< 0.002
< 0.002
< 0.004 Sr-90
< 0.002
< 0.001
< 0.002 1-1 31
< 0.009
< 0.013
< 0.006 K-40 2.95 +/- 0.22 2.21 +/- 0.21 1.71 +/- 0. 12 Nb-95
< 0.004
< 0.006
< 0.005 Zr-95
< 0.01 1
< 0.01 0
< 0.007 Cs-1 34
< 0.006
< 0.005
< 0.004 Cs-137
< 0.008
< 0.006
< 0.004 Ce-141
< 0.01 1
< 0.01 1
< 0.008 Ce-1 44
< 0.059
< 0.048
< 0.025 Location T-1 9 ( I)
Lab Code TVE-5748 TVE-6494 TVE-7242 Date Collected 08-24-1 1 09-27-1 1 1 0-18-1 1 Sample Type Cabbage Cabbage Cabbage Sr-89
< 0.002
< 0.003
< 0.003 Sr-90
< 0.002
< 0.002
< 0.001 1-1 31
< 0.007
< 0.014
< 0.014 K-40 1.98 +/- 0.06 1.97 +/- 0.20 2.12 +/- 0. 1 9 Nb-95
< 0.003
< 0.005
< 0.005 Zr-95
< 0.003
< 0.012
< 0.010 Cs-1 34
< 0.002
< 0.007
< 0.007 Cs-1 37
< 0.002
< 0.004
< 0.005 Ce-141
< 0.004
< 0.01 1
< 0.016 Ce-1 44
< 0.01 8
< 0.054
< 0.049 Location T-37 (C)
Lab Code TVE-5749 TVE-6495 TVE-7243 Date Collected 08-23-1 1 09-27-1 1 1 0-18-1 1 Sample Type Cabbage Cabbage Cabbage Sr-89
< 0.002
< 0.003
< 0.004 Sr-90
< 0.001
< 0.002
< 0.002 1-1 31
< 0.007
< 0.014
< 0.012 K-40 2.02 +/- 0.18 2.1 0 +/- 0.19
- 3. 1 0 +/- 0.25 Nb-95
< 0.005
< 0.005
< 0.009 Zr-95
< 0.007
< 0.009
< 0.010 Cs-134
< 0.007
< 0.007
< 0.006 Cs-137
< 0.006
< 0.005
< 0.007 Ce-141
< 0.0 1 4
< 0.013
< 0.009 Ce-1 44
< 0.048
< 0.038
< 0.053 1 9-1
Table 20. Fruit, analyses for strontiu m-89, strontium-90, iodine-1 31 and other gamma-emitting isotopes.
Collection: Annual Units: pCi/g wet Location T -8 (I)
T-25 (I)
Lab Code TVE-6497 TVE-6498 Date Collected 09-27-1 1 09-27-1 1 Sample Type Apples Apples Sr-89
< 0.002
< 0.002 Sr-90
< 0.001
< 0.002 1-1 31
< 0.0 1 0
< 0.009 K-40 1.03 +/- 0.1 3 1.60 +/- 0.1 6 Nb-95
< 0.006
< 0.004 Zr-95
< 0.006
< 0.0 1 0 Cs-1 34
< 0.004
< 0.005 Cs-1 37
< 0.008
< 0.007 Ce-1 41
< 0.01 1
< 0.01 3 Ce-1 44
< 0.042
< 0.044 Location T-209 (C)
Lab Code TVE-6499 Date Collected 09-27-1 1 Sample Type Apples Sr-89
< 0.003 Sr-90
< 0.002 1-1 31
< 0.008 K-40 1.28 +/- 0. 1 2 Nb-95
< 0.006 Zr-95
< 0.007 Cs-1 34
< 0.003 Cs-1 37
< 0.006 Ce-141
< 0.008 Ce-1 44
< 0.029 20-1
Table 21. Animal - wildlife feed, analyses for gamma-emitting isotopes.
Location Collection: Annual Units: pCi/g wet Lab Code Date Collected Sample Type 8e-7 K-40 Nb-95 Zr-95 Ru-1 03 Ru-1 06 Cs-134 Cs-137 Ce-141 Ce-144 Location Lab Code Date Collected Sample Type 8e-7 K-40 Nb-95 Zr-95 Ru-1 03 Ru-1 06 Cs-134 Cs-137 Ce-141 Ce-144 Indicators T-31 TCF-7259 10-18-1 1 Cattails 1.09 +/- 0.36 2.45 +/- 0.59
< 0.016
< 0.052
< 0.025
< 0.1 72
< 0.020
< 0.028
< 0.047
< 0.205 T-32 TCF-7260 10-18-1 1 Cattails 0.66 +/- 0.22 0.91 +/- 0.31
< 0.01 5
< 0.024
< 0.025
< 0. 1 30
< 0.017
< 0.022
< 0.042
< 0.21 1 21-1 Control T-198 TCF-7261 10-18-1 1 Cattails 0.96 +/- 0.21 2.00 +/- 0.35
< 0.020
< 0.025
< 0.014
< 0.077
< 0.01 7
< 0.021
< 0.035
< 0.162
Table 22. Soil samples, analyses for gamma-emitting isotopes.
Collection: Annual Units: pCi/g dry Location T-1 T-2 T-3 T-4 Lab Code TSO-2954 TSO-2955 TSO-2956 TSO-2957 Date Collected 04-27-11 04-27-11 04-27-11 04-27-11 Be-7 0.95 +/- 0.22
< 0.21 0.58 +/- 0.28
< 0.32 K-40 7.74 +/- 0.57 12.11 +/- 0.74 9.45 +/- 0.70 19.42 +/- 0.94 Mn-54
< 0.018
< 0.026
< 0.026
< 0.036 Nb-95
< 0.019
< 0.023
< 0.017
< 0.030 Zr-95
< 0.020
< 0.036
< 0.021
< 0.025 Ru-103
< 0.023
< 0.019
< 0.025
< 0.023 Ru-106
< 0.127
< 0.139
< 0.169
< 0.176 Cs-134
< 0.016
< 0.015
< 0.016
< 0.018 Cs-137 0.059 +/- 0.018 0.24 +/- 0.044
< 0.029 0.106 +/- 0.039 Ce-141
< 0.041
< 0.052
< 0.058
< 0.072 Ce-144
< 0.106
< 0.113
< 0.110
< 0.105 Location T-7 T-8 Lab Code TSO-2958 TSO-2959 Date Collected 04-27-11 04-27-11 Be-7 0.37 +/- 0.21 0.84 +/- 0.22 K-40 10.47 +/- 0.61 23.52 +/- 1.05 Mn-54
< 0.024
< 0.026 Nb-95
< 0.019
< 0.034 Zr-95
< 0.032
< 0.022 Ru-103
< 0.012
< 0.028 Ru-106
< 0.074
< 0.147 Cs-134
< 0.014
< 0.022 Cs-137
< 0.014 0.21 +/- 0.037 Ce-141
< 0.041
< 0.036 Ce-144
< 0.097
< 0.144 Location T-9 T-11 T-12 T-27 Lab Code TSO-2960 TSO-2962 TSO-2963 TSO-2964 Date Collected 04-27-11 04-27-11 04-27-11 04-27-11 Be-7
< 0.36
< 0.24 0.55 +/- 0.28
< 0.33 K-40 22.90 +/- 0.96 14.70 +/- 0.76 12.84 +/- 0.71 23.98 +/- 1.05 Mn-54
< 0.028
< 0.028
< 0.023
< 0.032 Nb-95
< 0.036
< 0.032
< 0.014
< 0.053 Zr-95
< 0.048
< 0.042
< 0.040
< 0.047 Ru-103
< 0.026
< 0.025
< 0.030
< 0.029 Ru-106
< 0.127
< 0.093
< 0.180
< 0.141 Cs-134
< 0.023
< 0.016
< 0.020
< 0.019 Cs-137
< 0.029 0.048 +/- 0.022 0.109 +/- 0.028 0.169 +/- 0.044 Ce-141
< 0.061
< 0.047
< 0.057
< 0.076 Ce-144
< 0.141
< 0.132
< 0.076
< 0.094 22-1
Table 23. Treated surface water samples, analyses for gross beta.
Collection: Monthly composites of weekly grab samples Units: pCifL T-1 1 (C)
Lab Code Date Collected Gross Beta Lab Code TSWT-442 01 -3 1 -1 1 1.8 +/- 0.8 TSWT-443 TSWT-844 03-0 1 -1 1 0.9 +/- 0.4 TSWT-845 TSWT-1 454 03-29-1 1 2.0 +/- 0.8 TSWT-1 456 TSWT-2943 04-26-1 1 2.9 +/- 0.9 TSWT-2944 TSWT-3427 05-31 -1 1 2.1 +/- 0.6 TSWT-3428 TSWT-4353 06-29-1 1 2.6 +/- 1. 1 TSWT-4354 TSWT-5324 08-02-1 1 1.1 +/- 0.5 TSWT-5325 TSWT-5882 08-30-1 1 1.7 +/- 0.6 TSWT-5883 TSWT-6586 09-27-1 1 2.8 +/- 0.7 TSWT-6587 TSWT-7651 1 1 -0 1 -1 1 1.2 +/- 0.5 TSWT-7652 TSWT-8394 1 1 1 1 1.6 +/- 0.6 TSWT-8395 TSWT-9080 01 1 2 3.4 +/- 0.9 TSWT-9081 T-22 TSWT-444 0 1 1 1 2.8 +/- 0.8 TSWT-445 TSWT-846 03-0 1 -1 1 1.1 +/- 0.4 TSWT-848 TSWT-1 457 03-28-1 1 3.1 +/- 0.8 TSWT-1 458 TSWT-2945 04-26-1 1 2.1 +/- 0.8 TSWT-2946 TSWT-3429 05-31 -1 1 2.1 +/- 0.6 TSWT-3430 TSWT-4355 06-29-1 1 2.6 +/- 1.0 TSWT-4356 TSWT-5326 08-02-1 1 1.4 +/- 0.6 TSWT-5327 TSWT-5884 08-30-1 1
< 0.9 TSWT-5885 TSWT-6588 09-27-1 1 2.7 +/- 0.7 TSWT-6589 TSWT-7653 1 1 -0 1 -1 1 1.4 +/- 0.6 TSWT-7654 TSWT-8396 1 1 1 1 2.0 +/- 0.6 TSWT-8397 TSWT-9082 0 1 1 2 3.0 +/- 0.8 TSWT-9083 23-1 T-1 2 (C)
Date Collected Gross Beta 0 1 1 1 1.7 +/- 0.7 03-0 1 -1 1 1.0 +/- 0.4 03-29-1 1 2.7 +/- 0.8 04-26-1 1 2.0 +/- 0.7 05-3 1 -1 1 1.5 +/- 0.6 06-29-1 1 2.5 +/- 0.9 08-02-1 1
< 0.8 08-30-1 1 1.3 +/- 0.6 09-27-1 1 2.4 +/- 0.8 1 1 -0 1 -1 1 1.5 +/- 0.6 1 1 1 1 1.2 +/- 0.5 01-03-1 2 2.6 +/- 0.7 T-1 43 (QC) 0 1 -3 1 -1 1 2.2 +/- 0.8 03-0 1 -1 1 0.9 +/- 0.4 03-29-1 1 1.9 +/- 0.8 04-26-1 1 2.4 +/- 0.8 05-31 -1 1 1.7 +/- 0.6 06-29-1 1 2.7 +/- 0.9 08-02-1 1 1.0 +/- 0.5 08-30-1 1 1.2 +/- 0.5 09-27 -1 1 1.9 +/- 0.7 1 1 -0 1 -1 1 1. 1 +/- 0.6 1 1 1 1
< 0.8 0 1 1 2 2.7 +/- 0.8
Table 24.
Location Period Lab Code H-3 Sr-89 Sr-90 Mn-54 Fe-59 Co-58 Co-60 Zn-65 Zr-Nb-95 Cs-1 34 Cs-1 37 Ba-La-1 40 Location Period Lab Code H-3 Sr-89 Sr-90 Mn-54 Fe-59 Co-58 Co-60 Zn-65 Zr-Nb-95 Cs-1 34 Cs-1 37 Ba-La-1 40 Treated surface water samples, analyses for tritium, strontium-89, strontium-90 and gamma-emitting isotopes.
Collection: Quarterly composites of weekly grab samples Units: pCi/L T-1 1 (C) 1 st Qtr.
2nd Qtr.
3rd Qtr.
TSWT-1 574 TSWT-451 1 TSWT-6651
< 330
< 330
< 330
< 0.6
< 0.8
< 0.9 0.4 +/- 0.3
< 0.5
< 0.5
< 2.5
< 2.9
< 2.6
< 3.8
< 4.9
< 2.0
< 1.7
< 1.9
< 2.0
< 1.9
< 1.6
< 2.2
< 4.3
< 2.9
< 3.7
< 3.4
< 3.4
< 3.1
< 3.4
< 2.1
< 2.7
< 1.6
< 2.1
< 2.6
< 2. 1
< 6.8
< 3.9 T-1 2 (C) 1 st Qtr.
2nd Qtr.
3rd Qtr.
TSWT-1 575 TSWT-451 2 TSWT-6652
< 330
< 330
< 330
< 0.9
< 0.8
< 1.0
< 0.6
< 0.5
< 0.5
< 1.9
< 2.5
< 1.9
< 5.4
< 4.4
< 5.6
< 2.5
< 2.1
< 1.8
< 2.9
< 1.6
< 1.4
< 3.1
< 2.5
< 3.9
< 2.3
< 3.4
< 2.6
< 2.3
< 2.6
< 3.4
< 2.6
< 1.7
< 2.6
< 4.6
< 5.6
< 4.1 24-1 4th Qtr.
TSWT-9097
< 330
< 0.7
< 0.5
< 3.4
< 5.2
< 2.3
< 2.5
< 2.6
< 4.3
< 2.4
< 4.0
< 3.0 4th Qtr.
TSWT-9098
< 330
< 0.9
< 0.7
< 2.7
< 6.6
< 2.3
< 2.5
< 4.9
< 2.2
< 2. 1
< 3.2
< 1.9 Reg. LLD 330 1 5 30 1 5 1 5 30 1 5 1 0 1 8 1 5 Reg. LLD 330 1 5 30 1 5 1 5 30 1 5 1 0 1 8 1 5
Table 24.
Location Period Lab Code H-3 Sr-89 Sr-90 Mn-54 Fe-59 Co-58 Co-60 Zn-65 Zr-Nb-95 Cs-1 34 Cs-1 37 Ba-La-1 40 Treated surface water samples, analyses for tritium, strontium-89, strontium-90 and gamma-emitting isotopes.
Collection: Quarterly composites of weekly grab samples.
Units: pCi/L T-22 1 st Qtr.
2nd Qtr.
3rd Qtr.
TSWT-1 576 TSWT-451 3 TSWT-6653
< 330
< 330
< 330
< 0.8
< 0.7
< 0.8
< 0.5
< 0.4
< 0.5
< 2.9
< 1.6
< 2.0
< 2.0
< 5.0
< 3.3
< 2.4
< 1.5
< 1.9
< 1.6
< 2.4
< 1.9
< 3.2
< 3.4
< 5.5
< 3.4
< 2.2
< 3.1
< 2.3
< 2.5
< 2.3
< 2.0
< 2.6
< 3.3
< 4.1
< 3.2
< 4.3 24-2 4th Qtr.
TSWT-9099
< 330
< 0.6
< 0.4
< 3.0
< 5.5
< 3.1
< 2.4
< 6.2
< 3.6
< 2.9
< 2.5
< 4.1 Reg. LLD 330 1 5 30 1 5 1 5 30 1 5 1 0 1 8 1 5
Table 25. Untreated surface water, analyses for gross beta, tritium and gamma emitting isotopes.
Location: T-3 Collection: Monthly composites of weekly grab samples Units: pC ilL Lab Code TSWU-446 TSWU-849 TSWU-1518 TSWU-2947 Date Collected 01-31-1 1 03-01-1 1 03-29-1 1 04-26-1 1 Req. LLD Gross beta 1.4 +/- 0.4 4.8 +/- 0.9 2.4 +/- 0.8 2.9 +/- 0.7 4.0 H-3 620 +/- 1 19
< 330
< 330
< 330 330 Mn-54
< 2.3
< 2.9
< 2.9
< 2.1 15 Fe-59
< 4.0
< 4.6
< 4.3
< 3.5 30 Co-58
< 2.7
< 3.0
< 2.6
< 2.6 1 5 Co-60
< 0.9
< 3.4
< 3.7
< 2.0 1 5 Zn-65
< 4.0
< 3.8
< 4.0
< 2.3 30 Zr-Nb-95
< 2.1
< 2.6
< 2.7
< 3.1 1 5 Cs-134
< 2.7
< 3.0
< 4.1
< 1.8 10 Cs-137
< 3.6
< 4.0
< 2.8
< 2.7 18 Ba-La-140
< 2.4
< 5.1
< 2.4
< 4.7 1 5 Lab Code TSWU-3420 TSWU-4357 TSWU-5328 TSWU-5887 Date Collected 05-31 -1 1 06-29-1 1 08-02-1 1 08-30-1 1 Req. LLD Gross Beta 2.7 +/- 0.7 2.8 +/- 0.8 2.3 +/- 0.8 2.4 +/- 0.7 4.0 H-3
< 330
< 330
< 330
< 330 330 Mn-54
< 2.2
< 3.5
< 2.8
< 2.4 1 5 Fe-59
< 6.4
< 7.3
< 4.7
< 5.6 30 Co-58
< 1.7
< 2.7
< 1.8
< 1. 1 1 5 Co-60
< 1.7
< 1.4
< 2.0
< 1.7 1 5 Zn-65
< 3.9
< 6.1
< 5.0
< 2.8 30 Zr-Nb-95
< 3.8
< 2.8
< 2.8
< 3.0 1 5 Cs-1 34
< 1.9
< 3. 1
< 2.1
< 2.6 10 Cs-1 37
< 3.4
< 3.5
< 2.8
< 2.5 18 Ba-La-140
< 2.1
< 4.7
< 9.0
< 2.7 1 5 Lab Code TSWU-6590 TSWU-7655 TSWU-8385 TSWU-9084 Date Collected 09-27-1 1 1 1-01 -1 1 1 1 1 1 01 12 Req. LLD Gross Beta 3.1 +/- 0.5 3.2 +/- 0.9 1.3 +/- 0.6 4.1 +/- 0.8 4.0 H-3
< 330
< 330
< 330
< 330 330 Mn-54
< 1.6
< 2.0
< 2.9
< 2.3 1 5 Fe-59
< 5.0
< 3.6
< 4.1
< 3.4 30 Co-58
< 2.0
< 1.2
< 2.8
< 2.4 1 5 Co-60
< 1.7
< 0.9
< 1.9
< 1.9 1 5 Zn-65
< 3.9
< 1.9
< 4.1
< 3.7 30 Zr-Nb-95
< 3.0
< 1.9
< 2.2
< 3.5 1 5 Cs-134
< 2.5
< 2.4
< 2.3
< 2.4 10 Cs-137
< 2.6
< 2.7
< 2.3
< 3.3 1 8 Ba-La-140
< 2.4
< 3.7
< 1.5
< 2.7 1 5 25-1
Table 25. Untreated surface water, analyses for gross beta, tritium and gamma emitting isotopes.
Location: T-1 1 (C)
Collection: Monthly composites of weekly grab samples Units: pC ilL Lab Code TSWU-449 TSWU-851 TSWU-1 520 TSWU-2949 Date Collected 01-31 -1 1 03-01-1 1 03-29-1 1 04-26-1 1 Req. LLD Gross beta 1.0 +/- 0.4 2.0 +/- 0.8 1.3 +/- 0.8 2.4 +/- 0.7 4.0 H-3
< 330
< 330
< 330
< 330 330 Mn-54
< 4.1
< 2.6
< 2.1
< 2.0 1 5 Fe-59
< 7.4
< 6.1
< 5.3
< 3.9 30 Co-58
< 3.2
< 2.9
< 3.1
< 2.5 1 5 Co-60
< 3.3
< 2.4
< 3.1
< 1.3 1 5 Zn-65
< 4.4
< 2.9
< 5.0
< 4.0 30 Zr-Nb-95
< 2.1
< 4.2
< 3.3
< 3.2 1 5 Cs-134
< 3.1
< 2.9
< 3.2
< 1.8 10 Cs-1 37
< 4.4
< 2.4
< 2.1
< 2.7 18 Ba-La-140
< 2.9
< 2.4
< 2.7
< 7.4 1 5 Lab Code TSWU-3422 TSWU-4359 TSWU-5330 TSWU-5889 Date Collected 05-31-1 1 06-29-1 1 08-02-1 1 08-30-1 1 Req. LLD Gross Beta 1.9 +/- 0.6 3.4 +/- 0.8 1.8 +/- 0.8
< 0.9 4.0 H-3
< 330
< 330
< 330
< 330 330 Mn-54
< 2.1
< 2.0
< 2.4
< 3.1 15 Fe-59
< 6.1
< 5.4
< 6.5
< 2.8 30 Co-58
< 1.7
< 2.6
< 1.6
< 2.3 1 5 Co-60
< 3.0
< 1.8
< 2.4
< 1.9 1 5 Zn-65
< 4.1
< 4.9
< 2.6
< 4.8 30 Zr-Nb-95
< 2.3
< 4.9
< 4.2
< 2.0 1 5 Cs-1 34
< 2.7
< 2.7
< 2.6
< 2.3 10 Cs-137
< 3.4
< 2.8
< 2.1
< 2.5 18 Ba-La-1 40
< 3.4
< 4.6
< 4.6
< 3.9 1 5 Lab Code TSWU-6592 TSWU-7657 TSWU-8387 TSWU-9086 Date Collected 09-27-1 1 1 1-01-1 1 1 1 1 1 01-03-12 Req. LLD Gross Beta 1.7 +/- 0.4 3.1 +/- 0.8 1.3 +/- 0.6 1.7 +/- 0.6 4.0 H-3
< 330
< 330
< 330
< 330 330 Mn-54
< 3.3
< 3.3
< 4.2
< 2.7 1 5 Fe-59
< 6.6
< 6.6
< 8.6
< 3.3 30 Co-58
< 4.4
< 2.3
< 3.8
< 2.2 1 5 Co-60
< 2.1
< 2.8
< 4.4
< 1.5 1 5 Zn-65
< 6.8
< 4.1
< 1 1.7
< 4.9 30 Zr-Nb-95
< 4.2
< 3.0
< 8.4
< 3.3 1 5 Cs-134
< 3.8
< 2.4
< 4.1
< 2.3 10 Cs-137
< 4.0
< 3.5
< 5.4
< 3.3 18 Ba-La-140
< 7.2
< 4.8
< 4.8
< 2.1 1 5 25-2
Table 25, Untreated surface water, analyses for gross beta, tritium and gamma emitting isotopes, Location: T-12 (C)
Collection: Monthly composites of weekly grab samples Units: pCi/L Lab Code TSWU-450 TSWU-852 TSWU-1 521 TSWU-2950 Date Collected 01-31-1 1 03-01-1 1 03-29-1 1 04-26-1 1 Req, LLD Gross beta 1,0 +/- 0.4 2,1 +/- 0,7 1,8 +/- 0,8 1,7 +/- 0,6 4,0 H-3
< 330
< 330
< 330
< 330 330 Mn-54
< 2,7
< 2,0
< 3,6
< 2,0 15 Fe-59
< 3,2
< 6,9
< 3,1
< 4,5 30 Co-58
< 2,6
< 2,8
< 3,1
< 1,6 1 5 Co-60
< 1.4
< 2.4
< 2,5
< 1,3 1 5 Zn-65
< 2,3
< 4,3
< 2.4
< 4,0 30 Zr-Nb-95
< 1,9
< 3,3
< 2,2
< 2,3 1 5 Cs-1 34
< 2,5
< 3,0
< 2,7
< 2,0 10 Cs-1 37
< 3,1
< 3,7
< 4,0
< 2,7 18 Ba-La-140
< 1,7
< 3,8
< 4,1
< 6,9 1 5 Lab Code TSWU-3423 TSWU-4360 TSWU-5331 TSWU-5890 Date Collected 05-31-1 1 06-29-1 1 08-02-1 1 08-30-1 1 Req, LLD Gross Beta 2,1 +/- 0,6 3,5 +/- 0,7 2,5 +/- 0.7 1,6 +/- 0,6 4,0 H-3
< 330
< 330
< 330
< 330 330 Mn-54
< 1,7
< 3,2
< 2,6
< 1,6 1 5 Fe-59
< 4,1
< 2,8
< 4,2
< 4,3 30 Co-58
< 2,1
< 1,8
< 1.4
< 1,9 1 5 Co-60
< 1,3
< 2,5
< 1,6
< 1,6 1 5 Zn-65
< 3,9
< 5.4
< 4,1
< 4,6 30 Zr-Nb-95
< 2,6
< 4,0
< 3,9
< 3,1 1 5 Cs-134
< 2,3
< 3,1
< 2,1
< 2,6 10 Cs-137
< 3.4
< 2,3
< 2,2
< 3,0 18 Ba-La-140
< 4,3
< 5,7
< 7,3
< 2,3 1 5 Lab Code TSWU-6593 TSWU-7658 TSWU-8388 TSWU-9087 Date Collected 09-27-1 1 1 1 1 1 1 1-29-1 1 01-03-12 Req, LLD Gross Beta 1,9 +/- 0.4 2,9 +/- 0,7 1,7 +/- 0,6 2,3 +/- 0,7 4,0 H-3
< 330
< 330
< 330
< 330 330 Mn-54
< 2,8
< 4,5
< 2,0
< 3,3 1 5 Fe-59
< 3,3
< 7,3
< 4,1
< 4,1 30 Co-58
< 1,9
< 4,8
< 1,6
< 1,3 1 5 Co-60
< 1,8
< 5,6
< 2.4
< 2,7 1 5 Zn-65
< 2,6
< 5.4
< 3.4
< 6,7 30 Zr-Nb-95
< 1,8
< 5,3
< 2,8
< 3,0 1 5 Cs-1 34
< 2,3
< 3.4
< 2,0
< 2,5 10 Cs-137
< 2.4
< 5,8
< 3,1
< 3.4 18 Ba-La-1 40
< 2,0
< 4.4
< 1,8
< 1,6 1 5 25-3
Table 25. Untreated surface water, analyses for gross beta, tritium and gamma emitting isotopes, Location: T-22 Collection: Monthly composites of weekly grab samples Units: pCi/L Lab Code TSWU-452 TSWU-854 TSWU-1 524 TSWU-2952 Date Collected 01-31-1 1 03-01-1 1 03-29-1 1 04-26-1 1 Req. LLD Gross beta 2.7 +/- 0.8 1,8 +/- 0.8 1,6 +/- 0.8 1.7 +/- 0,6 4,0 H-3 351 +/- 1 09
< 330
< 330
< 330 330 Mn-54
< 2.9
< 1.9
< 2,2
< 1.7 1 5 Fe-59
< 2,6
< 4.4
< 5,5
< 3,1 30 Co-58
< 1.8
< 3,0
< 2. 1
< 2.4 1 5 Co-60
< 2,5
< 1.4
< 1.8
< 1,6 1 5 Zn-65
< 3,6
< 2,6
< 2.2
< 2.4 30 Zr-Nb-95
< 3,9
< 2.8
< 3.2
< 2.9 1 5 Cs-134
< 2.6
< 3.2
< 2.5
< 2.3 1 0 Cs-137
< 2.8
< 2.4
< 3.4
< 2,1 18 Ba-La-140
< 2.4
< 2.4
< 4.1
< 4,2 1 5 Lab Code TSWU-3425 TSWU-4362 TSWU-5333 TSWU-5892 Date Collected 05-31-1 1 06-29-1 1 08-02-1 1 08-30-1 1 Req. LLD Gross Beta 1.5 +/- 0.6 2.1 +/- 0,8 2,1 +/- 0.8 1,5 +/- 0.6 4.0 H-3
< 330
< 330
< 330
< 330 330 Mn-54
< 2,6
< 5.5
< 1,9
< 1. 1 1 5 Fe-59
< 6.2
< 9,0
< 5.7
< 3.3 30 Co-58
< 2.5
< 2,9
< 3.2
< 1,7 1 5 Co-60
< 1.8
< 3,7
< 2.0
< 1.4 1 5 Zn-65
< 4,3
< 6,0
< 2,0
< 3,5 30 Zr-Nb-95
< 3,5
< 5.6
< 3.8
< 2,1 15 Cs-134
< 2.9
< 3,8
< 2.0
< 2.5 1 0 Cs-137
< 2,5
< 2.7
< 2.4
< 2,6 18 Ba-La-140
< 2,7
< 6,6
< 5.5
< 4,0 1 5 Lab Code TSWU-6595 TSWU-7660 TSWU-8391 TSWU-9089 Date Collected 09-27-1 1 1 1 1 1 1 1 1 1 01-03-12 Req, LLD Gross Beta 1.9 +/- 0.5 3.4 +/- 0,8
< 0.9 3,5 +/- 0,7 4.0 H-3
< 330
< 330
< 330
< 330 330 Mn-54
< 3.2
< 2.9
< 3,2
< 3.9 1 5 Fe-59
< 7.0
< 6.5
< 5.1
< 7.5 30 Co-58
< 2.9
< 3.5
< 3.1
< 4,2 1 5 Co-60
< 1,9
< 4.6
< 2.1
< 2.3 1 5 Zn-65
< 5.6
< 6.8
< 7.1
< 5.7 30 Zr-Nb-95
< 2,6
< 5,0
< 3.0
< 4.5 1 5 Cs-134
< 2,8
< 3,8
< 3,5
< 2.0 1 0 Cs-137
< 3,7
< 4.1
< 4.4
< 4.5 1 8 Ba-La-140
< 4,0
< 2.2
< 4,8
< 4.3 1 5 25-4
Table 25. Untreated surface water, analyses for gross beta, tritium and gamma emitting isotopes.
Location: T-145 (QC)
Collection: Monthly composites of weekly grab samples Units: pC ilL Lab Code TSWU-453 TSWU-855 TSWU-1525 TSWU-2953 Date Collected 01-31-11 03-01-11 03-29-11 04-26-11 Req. LLD Gross beta 3.2 +/- 0.8 2.7 +/- 0.7 1.8 +/- 0.8 2.0 +/- 0.7 4.0 H-3
< 330
< 330
< 330
< 330 330 Mn-54
< 4.1
< 5.0
< 2.5
< 2.4 15 Fe-59
< 5.4
< 6.2
< 2.5
< 4.7 30 Co-58
< 4.8
< 2.5
< 1.7
< 3.4 15 Co-60
< 2.7
< 3.6
< 1.5
< 1.6 15 Zn-65
< 6.1
< 3.9
< 4.5
< 1.0 30 Zr-Nb-95
< 5.0
< 3.5
< 3.9
< 2.2 15 Cs-134
< 3.8
< 4.5
< 3.1
< 1.9 10 Cs-137
< 4.1
< 3.9
< 2.7
< 1.6 18 Ba-La-140
< 6.9
< 3.4
< 3.4
< 6.8 15 Lab Code TSWU-3426 TSWU-4363 TSWU-5334 TSWU-5893 Date Collected 05-31-11 06-29-11 08-02-11 08-30-11 Req. LLD Gross Beta 2.9 +/- 1.1 3.5 +/- 0.9 2.3 +/- 0.8 4.1 +/- 1.0 4.0 H-3
< 330
< 330
< 330
< 330 330 Mn-54
< 2.5
< 2.5
< 2.4
< 4.0 15 Fe-59
< 2.8
< 5.8
< 4.7
< 8.6 30 Co-58
< 2.2
< 4.6
< 1.7
< 4.0 15 Co-60
< 1.8
< 3.5
< 1.6
< 2.3 15 Zn-65
< 2.1
< 5.7
< 2.9
< 6.3 30 Zr-Nb-95
< 1.8
< 4.0
< 3.5
< 3.9 15 Cs-134
< 2.7
< 2.2
< 2.6
< 2.6 10 Cs-137
< 2.1
< 3.7
< 2.9
< 3.6 18 Ba-La-140
< 4.0
< 5.8
< 5.9
< 5.6 15 Lab Code TSWU-6596 TSWU-7661 TSWU-8392 TSWU-9090 Date Collected 09-27-11 11-01-11 11-29-11 01-03-12 Req. LLD Gross Beta 3.3 +/- 0.8 1.5 +/- 0.6 1.3 +/- 0.6 3.3 +/- 0.7 4.0 H-3
< 330
< 330
< 330
< 330 330 Mn-54
< 2.5
< 2.2
< 1.9
< 2.9 15 Fe-59
< 2.8
< 6.9
< 4.2
< 3.5 30 Co-58
< 3.2
< 3.0
< 1.8
< 1.7 15 Co-60
< 1.3
< 2.0
< 2.3
< 2.1 15 Zn-65
< 4.1
< 7.7
< 4.9
< 6.0 30 Zr-Nb-95
< 2.8
< 3.6
< 2.0
< 2.8 15 Cs-134
< 1.5
< 3.9
< 1.8
< 2.5 10 Cs-137
< 2.1
< 3.6
< 3.2
< 3.3 18 Ba-La-140
< 3.8
< 5.3
< 2.6
< 2.0 15 25-5
Table 26. Untreated surface water samples, analyses for strontium-89 and strontium-90.
Collection: Ouarterly composites of weekly grab samples Units: pC ilL Location T-3 Period 1 st Otr.
2nd Otr.
3rd Otr.
4th Otr.
Lab Code TSWU-1 835 TSWU-451 4 TSWU-6749 TSWU-91 1 8 Sr-89
< 1. 1
< 0.7
< 1.0
< 0.7 Sr-90
< 0.7
< 0.4
< 0.6
< 0.5 Location T-1 1 (C)
Period 1 st Otr.
2nd Otr.
3rd Otr.
4th Otr.
Lab Code TSWU-1 836 TSWU-451 5 TSWU-6750 TSWU-91 1 9 Sr-89
< 0.8
< 0.7
< 1.1
< 0.7 Sr-90
< 0.5
< 0.7
< 0.6
< 0.5 Location T-1 2 Period 1 st Otr.
2nd Otr.
3rd Otr.
4th Otr.
Lab Code TSWU-1 837 TSWU-451 6 TSWU-6751 TSWU-9 1 20 Sr-89
< 0.7
< 0.8
< 0.9
< 0.7 Sr-90
< 0.5
< 0.5
< 0.5
< 0.5 Location T-22 Period 1 st Otr.
2nd Otr.
3rd Otr.
4th Otr.
Lab Code TSWU-1 838 TSWU-451 7 TSWU-6752 TSWU-9121 Sr-89
< 0.6
< 0.7
< 0.8
< 0.7 Sr-90
< 0.4
< 0.5
< 0.4
< 0.5 26-1
Table 27. Fish samples, analyses for gross beta and gamma-emitting isotopes.
Collection: Annually U nits: pCi/g wet Location Lab Code TF-5242 Date Collected 06-07-1 1 Sample Type Commercial sp.
Gross Beta 2.9 +/- 0.1 K-40 3.23 +/- 0.43 Mn-54
< 0.01 4 Fe-59
< 0.066 Co-58
< 0.027 Co-60
< 0.01 2 Zn-65
< 0.01 8 Cs-1 34
< 0.01 6 Cs-1 37
< 0.01 2 Location Lab Code TF-5245 Date Collected 05-1 4-1 1 Sample Type Commercial sp.
Gross Beta 3.0 +/- 0.1 K-40 2.54 +/- 0.37 Mn-54
< 0.01 2 Fe-59
< 0.091 Co-58
< 0.01 8 Co-60
< 0.01 2 Zn-65
< 0.020 Cs-1 34
< 0.009 Cs-1 37
< 0.01 5 T-33 (Lake Erie, 1.5 mi. NE of Station)
TF-5243 TF-5244 05-24-1 1 04-1 3-1 1 Carp Walleye 2.9 +/- 0.1 4.4 +/- 0.1 1.47 +/- 0.31 3.30 +/- 0.43
< 0.01 6
< 0.0 1 3
< 0.060
< 0.1 1 8
< 0.0 1 8
< 0.024
< 0.0 1 1
< 0.0 1 2
< 0.01 7
< 0.039
< 0.01 1
< 0.01 4
< 0.01 0
< 0.0 1 7 T-35 TF-5246 TF-5247 07-27-1 1 04-01-1 1 Carp Walleye 3.5 +/- 0.1 4.6 +/- 0.1 2.83 +/- 0.36 3.26 +/- 0.43
< 0.01 2
< 0.0 1 5
< 0.023
< 0.2 1 3
< 0.007
< 0.034
< 0.01 0
< 0.0 1 0
< 0.01 1
< 0.0 1 5
< 0.0 1 0
< 0.008
< 0.009
< 0.01 1 27-1
Table 28. Shoreline sediment samples, analyses for gamma-emitting isotopes.
Collection: Semiannually Units: pCi/g dry Location T-3 T-4 T-4P T-27B T-1 32 Lab Code TSS-3434 TSS-3436 TSS-3437 TSS-3438 TSS-3439 Date Collected 05-25-1 1 05-25-1 1 05-25-1 1 05-25-1 1 05-25-1 1 K-40 1 1.53 +/- 0.56 1 6.69 +/- 0.93 1 8.25 +/- 0.94 9.57 +/- 0.54 8.86 +/- 0.49 Mn-54
< 0.0 1 8
< 0.034
< 0.023
< 0.0 1 4
< 0.0 1 5 Co-58
< 0.0 1 9
< 0.038
< 0.01 2
< 0.01 0
< 0.0 1 4 Co-60
< 0.0 1 3
< 0.036
< 0.0 1 0
< 0.0 1 8
< 0.01 1 Cs-1 34
< 0.01 1
< 0.026
< 0.021
< 0.01 2
< 0.0 1 2 Cs-1 37
< 0.01 1
< 0.034
< 0.026
< 0.01 4
< 0.01 1 Lab Code TSS-8 1 04 TSS-8 1 05 TSS-8 1 06 TSS-81 07 TSS-8 1 08 Date Collected 1 1 1 1 1 1 -1 6-1 1 1 1 -1 6-1 1 1 1 1 1 1 1 -1 6-1 1 K-40 7.67 +/- 0.46 1 2.00 +/- 0.67 1 7. 1 2 +/- 0.92 1 0.69 +/- 0.55 1 0.21 +/- 0.64 Mn-54
< 0.0 1 3
< 0.021
< 0.034
< 0.01 7
< 0.020 Co-58
< 0.008
< 0.0 1 2
< 0.020
< 0.025
< 0.029 Co-60
< 0.009
< 0.0 1 2
< 0.023
< 0.01 5
< 0.0 1 3 Cs-1 34
< 0.0 1 0
< 0.01 2
< 0.023
< 0.0 1 5
< 0.01 6 Cs-1 37
< 0.0 1 0
< 0.01 7
< 0.027
< 0.01 4
< 0.01 4 28-1
APPENDIX B DATA REPORT I N G CONVENTIONS B-1
Data Reporting Conventions 1.0. All activities, except gross alpha and gross beta, are decay corrected to collection time or the end of the collection period.
2.0. Single Measurements Each single measurement is reported as follows:
x +/- s where:
x = value of the measurement; s = 20 counting uncertainty (corresponding to the 95% confidence level).
In cases where the activity is less than the lower limit of detection L, it is reported as: < L, where L = the lower limit of detection based on 4.660 uncertainty for a background sample.
3.0. Duplicate analyses If duplicate analyses are reported, the convention is as follows. :
3.1 Individual results: For two analysis results; x1 +/- S1 and x2 +/- S2 3.2.
3.3.
Reported result:
Individual results:
Individual results:
x +/- s; where x =
< Ll, < L2 x +/- s, < L 4.0. Computation of Averages and Standard Deviations (1/2) (Xl + xJ and s = (1/2)
Reported result: < L. where L = lower of L1 and L2 x +/- s if x ;::: L; < L otherwise.
4.1 Averages and standard deviations listed in the tables are computed from all of the individual measurements over the period averaged; for exar::!ple, an annual standard deviation would not be the average of quarterly standard deviations. The average x and standard deviation "s" of a set of n numbers x1 ' x2... xn are defined as follows:
1 x = i1 L X s = L (x-x )2 n-1 4.2 Values below the highest lower limit of detection are not inciuded in the average.
4.3 If all values in the averaging group are less than the highest LLD, the highest LLD is reported.
4.4 If all but one of the values are less than the highest LLD, the single value x and associated two sigma error is reported.
4.5 In rounding off, the following rules are followed:
4.5.1. If the number following those to be retained is less than 5, the number is dropped, and the retained numbers are kept unchanged. As an example, 1 1.443 is rounded off to 1 1.44.
4.5.2. If the number following those to be retained is equal to or greater than 5, the number is dropped and the last retained number is raised by 1. As an example, 1 1.445 is rounded off to 1 1.45.
B-2
APPENDIX C SUPPLEMENTAL ANALYSES C-1
C-1, Airborne iodine-1 31, as measured in activated charcoal canisters, Location T-1 T-2 T-3 T-4 T-7 T-8 T-9 T-1 1 T-1 2 T-27 T-1 T-2 T-3 T-4 T-7 T-8 T-9 T-1 1 T-1 2 T-27 T-1 T-2 T-3 T-4 T-7 T-8 T-9 T-1 1 T-1 2 T-27 T-1 T-2 T-3 T-4 T-7 T-8 T-9 T-1 1 T-1 2 T-27 U nits: pCilm3 Required LLD: 0,070 Collection: Continuous, weekly exchange, Date Collected 03-22-1 1 03-22-1 1 03-22-1 1 03-22-1 1 03-22-1 1 03-22-1 1 03-22-1 1 03-22-1 1 03-22-1 1 03-22-1 1 03-29-1 1 03-29-1 1 03-29-1 1 03-29-1 1 03-29-1 1 03-29-1 1 03-29-1 1 03-29-1 1 03-29-1 1 03-29-1 1 04-05-1 1 04-05-1 1 04-05-1 1 04-05-1 1 04-05-1 1 04-05-1 1 04-05-1 1 04-05-1 1 04-05-1 1 04-05-1 1 04-1 2-1 1 04-1 2-1 1 04-1 2-1 1 04-1 2-1 1 04-1 2-1 1 04-1 2-1 1 04-1 2-1 1 04-1 2-1 1 04-1 2-1 1 04-1 2-1 1 C-2 304 286 288 289 286 289 289 284 297 286 302 275 285 284 285 288 289 283 293 285 305 287 287 292 287 289 279 285 301 292 302 285 285 289 286 289 294 284 292 280 Concentration 1-1 31 (pCilm3) 0,043 +/- 0,022 0,047 +/- 0,023 0,046 +/- 0,020 0,040 +/- 0,0 1 8 0,033 +/- 0,0 1 5 0,034 +/- 0,020 0,056 +/- 0,024 0,044 +/- 0,0 1 5 0,060 +/- 0,022 0,049 +/- 0,022 0,080 +/- 0,020 0,076 +/- 0,020 0,070 +/- 0,01 6 0,065 +/- 0,023 0,081 +/- 0,021 0,061 +/- 0,027 0,074 +/- 0,025 0,083 +/- 0,021 0,075 +/- 0,025 0,057 +/- 0,025 0,1 34 +/- 0,023 0,1 39 +/- 0,025 0, 1 32 +/- 0,020 0,1 60 +/- 0,033 0,140 +/- 0,022 0,148 +/- 0,029 0, 1 40 +/- 0,020 0, 1 40 +/- 0,022 0, 1 66 +/- 0,031 0, 1 55 +/- 0,026 0,066 +/- 0,024
< 0,031
< 0,026
< 0,032 0,053 +/- 0,026 0,056 +/- 0,032
< 0,030
< 0,033 0,064 +/- 0,031
< 0,026
C-1. Airborne iodine-1 31, as measured in activated charcoal canisters.
U nits: pCilm3 Required LLD: 0.070 Collection: Continuous, weekly exchange.
Date Volume Concentration Location Collected (m3) 1-1 31 (pCi/m3)
T-1 04-1 9-1 1 304
< 0.01 5 T-2 04-1 9-1 1 286
< 0.01 7 T-3 04-1 9-1 1 286
< 0.0 1 8 T-4 04-1 9-1 1 291
< 0.020 T-7 04-1 9-1 1 286
< 0.01 5 T-8 04-1 9-1 1 288
< 0.022 T-9 04-1 9-1 1 284
< 0.0 1 8 T-1 1 04-1 9-1 1 284
< 0.0 1 7 T-1 2 04-1 9-1 1 297
< 0.01 8 T-27 04-1 9-1 1 291
< 0.01 7 T-1 04-26-1 1 304
< 0.01 7 T-2 04-26-1 1 287
< 0.01 6 T-3 04-26-1 1 281
< 0.0 1 7 T-4 04-26-1 1 292
< 0.01 5 T-7 04-26-1 1 286
< 0.0 1 4 T-8 04-26-1 1 291 0.034 +/- 0.0 1 9 T-9 04-26-1 1 278
< 0.024 T-1 1 04-26-1 1 284
< 0.0 1 9 T-1 2 04-26-1 1 286
< 0.01 6 T-27 04-26-1 1 287
< 0.01 6 C-3