.... v..';:;;.;.

..";..L-;....
X Environmental, Inc.

Midwest Laboratory an Allegheny Technologies Co.

700 Landwehr Road - Northbrook, IL 60062-2310 (847) 564-0700 fax (847) 564-4517 FINAL MONTHLY PROGRESS REPORT RADIOLOGICAL ENVIRONMENTAL MONITORING PROGRAM (REMP)

FOR THE DAVIS-BESSE NUCLEAR POWER STATION OAK HARBOR, OHIO Reporting Period: January - December, 2006 PREPARED AND SUBMITTED BY ENVIRONMENTAL, INC.,

MIDWEST LABORATORY Project Number: 8003 Reviewed and Approved Date 02,-(16-007

19. (ob, M.S.

Lar ry Manager Distribution:

Percival, A., Davis-Besse (2 copies and Original Raw Data)

TABLE OF CONTENTS Section 1.0 2.0 3.0 Appendices A

B C

Page List of Tables.........................................................................................................

iii INTRODUCTION....................................................................................................

vi LISTING OF M ISSED SAMPLES...............................................................................

vii DATA TABULATIONS...........

viii Interlaboratory Com parison Program Results.....................................................

A-1 Data Reporting Conventions.................................................................................

B-1 Program Deviations............................................................................................

C-1 ii

LIST OF TABLES No.

Title Page 1

Airborne particulates and iodine collected at Location T-1, analyses for gross beta and iodine-13 1.........................................................................................

1-1 2

Airborne particulates and iodine collected at Location T-2, analyses for gross beta a nd iod ine-13 1.........................................................................................

2-1 3

Airborne particulates and iodine collected at Location T-3, analyses for gross beta and iodine-13 1.........................................................................................

3-1 4

Airborne particulates and iodine collected at Location T-4, analyses for gross beta and iodine-13 1.........................................................................................

4-1 5

Airborne particulates and iodine collected at Location T-7, analyses for gross beta and iodine-13 1.........................................................................................

5-1 6

Airborne particulates and iodine collected at Location T-8, analyses for gross beta and iod ine-13 1.........................................................................................

6-1 7

Airborne particulates and iodine collected at Location T-9, analyses for gross beta and iodine-131.........................................................................................

7-1 8

Airborne particulates and iodine collected at Location T-1 1, analyses for gross beta and iodine-131...............................................................................

8-1 9

Airborne particulates and iodine collected at Location T-12, analyses for gross beta and iodine-131...............................................................................

9-1 10 Airborne particulates and iodine collected at Location T-27, analyses for gross beta and iodine-131.............................................................................

10-1 11 Airborne particulate data, gross beta analysis, monthly averages, minima and m a x im a..........................................................................................................

1 1 -1 12 Airborne particulate samples, quarterly composites by location, analyses for strontium-89, strontium-90 and gamma-emitting isotopes............................

12-1 13 Area monitors (TLD), quarterly...................................................................................

13-1 14 Area monitors (TLD), annual......................................................................................

14-1 15 Milk, analyses for strontium-89, strontium-90, iodine-131, gamma-emitting isotopes, calcium, stable potassium, and ratios of strontium-90 (pCi) per gram of calcium and cesium-137 (pCi) per gram of potassium.............. 15-1 iii

LIST OF TABLES (continued)

No.

Title Paqe 16 Ground water, analyses for gross beta, tritium, strontium-89 and strontium-90 and gamma-emitting isotopes, quarterly collections......................................

16-1 17 Domestic meat, analysis for gamma-emitting isotopes..............................................

17-1 18 Wild meat, analysis for gamma-emitting isotopes......................................................

18-1 19 Green leafy vegetable, analyses for strontium-89, strontium-90, iodine-131 and gamma-emitting isotopes.......................................................................

19-1 20 Fruit, analyses for strontium-89, strontium-90, iodine-131 and gamma-em itting isotopes............................................................................................

20-1 21 Animal-wildlife feed, analysis for gamma-emitting isotopes.......................................

21-1 22 Soil, analysis for gamma-emitting isotopes................................................................

22-1 23 Treated surface water, monthly composites of weekly grab samples, analysis for gross beta.................................................................................................

23-1 24 Treated surface water, quarterly composites of weekly grab samples, analyses for tritium, strontium-89, strontium-90 and gamma-emitting iso to p e s.........................................................................................................

2 4 -1 25 Untreated surface water, monthly composites of weekly grab samples, analyses for gross beta, tritium and gamma-emitting isotopes..................... 25-1 26 Untreated surface water, quarterly composites of weekly grab samples, analyses for strontium-89 and strontium-90.................................................

26-1 27 Untreated lakewater, monthly collection, analyses for gross beta, tritium and gamma-emitting isotopes..............................................................................

27-1 28 Fish, analyses for gross beta and gamma-emitting isotopes.....................................

28-1 29 Shoreline sediment, analysis for gamma-emitting isotopes.......................................

29-1 30 Eggs, analysis for gamma-emitting isotopes..............................................................

30-1 iv

LIST OF TABLES (continued)

The following tables are in the Appendices:

Appendix A Attachment A: Acceptance criteria for spiked samples................................................

A-2 A-i Interlaboratory Comparison Program Results............................................................

Al-1 A-2 Interlaboratory Comparison Program Results, thermoluminescent dosim eters (T LD 's)...................................................

.................................... A 2-1 A-3 Results of the analyses on in-house spiked samples.................................................

A3-1 A-4 Results of the analyses on in-house "blank" samples................................................

A4-1 A-5 Results of the analyses on in-house "duplicate" samples..........................................

A5-1 A-6 Mixed Analyte Performance Evaluation Program (MAPEP).......................................

A6-1 Appendix B B-1 Data Reporting Conventions.........................................................................................

B-2 Appendix C C -1 Program D eviations......................................................................................................

C -2 v

1.0 INTRODUCTION

The following constitutes the final 2006 Monthly Progress Report for the Radiological Environmental Monitoring Program conducted at the Davis-Besse Nuclear Power Station in Oak Harbor, Ohio. Results of completed analyses are presented in the attached tables. Missing entries indicate analyses that are not yet completed.

All activities, except gross alpha and gross beta, are decay corrected to the time of collection.

All samples were collected within the scheduled period unless noted otherwise in the Listing of Missed Samples.

vi

2.0 LISTING OF MISSED SAMPLES Expected Sample Type Location Collection Reason Date TLD TLD TLD TLD T-92 T-155 T-155 T-205 1st Qtr.

3rd Qtr.

Annual'06 Annual '06 TLD lost in the field.

TLD lost in the field.

TLD lost in the field.

TLD lost in the field.

vii

3.0 DATA TABULATIONS viii

Table 1. Airborne particulates and charcoal canisters, analyses for gross beta and iodine-131a.

Location: T-1 Units: pCi/m 3

Collection: Continuous, weekly exchange.

Date Volume Date Volume Collected (mi)

Gross Beta Collected (mi)

Gross Beta Required LLD 0.010 0.010 01-10-06 01-17-06 01-24-06 01-31-06 02-07-06 02-14-06 02-21-06 02-28-06 03-07-06 03-14-06 03-21-06 03-28-06 276 273 276 273 276 275 276 279 279 279 278 272 0.018 +/- 0.004 0.019 +/- 0.004 0.025 +/- 0.004 0.027 +/- 0.004 0.019 +/- 0.004 0.020 +/- 0.004 0.024 +/- 0.004 0.029 +/- 0.004 0.014 +/- 0.003 0.020 +/- 0.004 0.024 +/- 0.004 0.016 +/- 0.003 07-05-06 07-11-06 07-18-06 07-25-06 08-01-06 08-08-06 08-15-06 08-22-06 08-29-06 09-05-06 09-12-06 09-19-06 09-26-06 10-03-06 320 240 278 279 278 281 285 286 288 284 286 285 287 286 0.028 +/- 0.004 0.021 +/- 0.004 0.030 +/- 0.004 0.022 +/- 0.004 0.031 +/- 0.004 0.026 +/- 0.004 0.022 +/- 0.004 0.027 +/- 0.004 0.038 +/- 0.004 0.019 +/- 0.004 0.033 +/- 0.004 0.023 +/- 0.004 0.019 +/- 0.004 0.021 +/- 0.004 1st Quarter Mean +/- s.d.

04-04-06 04-11-06 04-18-06 04-25-06 05-02-06 05-09-06 05-16-06 05-23-06 05-30-06 06-06-06 06-13-06 06-20-06 06-27-06 277 278 279 273 278 281 278 279 279 278 281 284 278 0.021 +/- 0.005 0.018 +/- 0.004 0.021 +/- 0.004 0.020 +/- 0.004 0.012 +/- 0.004 0.017 +/- 0.004 0.020 +/- 0.004 0.015 +/- 0.003 0.009 +/- 0.003 0.020 +/- 0.004 0.025 +/- 0.004 0.017 +/- 0.004 0.024 +/- 0.004 0.018 +/- 0.003 3rd Quarter Mean +/- s.d.

10-10-06 10-17-06 10-24-06 10-31-06 11-07-06 11-14-06 11-21-06 11-28-06 12-05-06 12-12-06 12-19-06 12-26-06 01-02-07 286 285 286 286 286 286 285 289 285 287 279 281 280 0.026 +/- 0.006 0.027 +/- 0.004 0.021 +/- 0.004 0.018 +/- 0.004 0.018 +/- 0.004 0.034 +/- 0.004 0.021 +/- 0.004 0.024 +/- 0.004 0.029 +/- 0.004 0.029 +/- 0.004 0.035 +/- 0.004 0.042 +/- 0.005 0.027 +/- 0.004 0.053 +/- 0.005 2nd Quarter Mean +/- s.d.

0.018 +/- 0.004 4th Quarter Mean +/- s.d.

Cumulative Average Previous Annual Average 0.029 +/- 0.010 0.024 0.025 a lodine-131 concentrations are < 0.07 pCi/m 3 unless noted otherwise in Appendix C.

1-1

Table 2. Airborne particulates and charcoal canisters, analyses for gross beta and iodine-131a.

Location: T-2 Units: pCi/m 3

Collection: Continuous, weekly exchange.

Date Volume Date Volume Collected (me)

Gross Beta Collected (ma)

Gross Beta Required LLD 0.010 0.010 01-10-06 01-17-06 01-24-06 01-31-06 02-07-06 02-14-06 02-21-06 02-28-06 03-07-06 03-14-06 03-21-06 03-28-06 282 278 282 282 283 282 274 275 275 275 274 270 0.019 +/- 0.004 0.020 +/- 0.004 0.022 +/- 0.004 0.027 +/- 0.004 0.018 +/- 0.004 0.017 +/- 0.004 0.026 +/- 0.004 0.028 +/- 0.004 0.016 +/- 0.003 0.024 +/- 0.004 0.023 +/- 0.004 0.007 +/- 0.003 07-05-06 07-11-06 07-18-06 07-25-06 08-01-06 08-08-06 08-15-06 08-22-06 08-29-06 09-05-06 09-12-06 09-19-06 09-26-06 10-03-06 322 228 277 275 278 280 279 279 281 277 279 278 280 279 0.025 +/- 0.004 0.023 +/- 0.005 0.030 +/- 0.004 0.024 +/- 0.004 0.030 +/- 0.004 0.022 +/- 0.004 0.023 +/- 0.004 0.027 + 0.004 0.040 + 0.005 0.017 +/- 0.004 0.030 + 0.004 0.028 + 0.004 0.017 +/- 0.004 0.021 +/- 0.004 0.026 +/- 0.006 1st Quarter Mean +/- s.d.

04-04-06 04-11-06 04-18-06 04-25-06 05-02-06 05-09-06 05-16-06 05-23-06 05-30-06 06-06-06 06-13-06 06-20-06 06-27-06 273 274 275 275 291 343 273 277 266 274 281 273 270 0.021 +/- 0.006 0.019 +/- 0.004 0.022 +/- 0.004 0.023 +/- 0.004 0.014 +/- 0.004 0.018 +/- 0.004 0.020 +/- 0.003 0.019 +/- 0.004 0.008 +/- 0.003 0.025 +/- 0.004 0.022 +/- 0.004 0.014 +/- 0.003 0.026 +/- 0.004 0.020 +/- 0.004 3rd Quarter Mean +/- s.d.

10-10-06 10-17-06 10-24-06 10-31-06 11-07-06 11-14-06 11-21-06 11-28-06 12-05-06 12-12-06 12-19-06 12-26-06 01-02-07 279 278 279 279 279 279 278 279 280 282 280 281 280 0.021 +/- 0.004 0.020 +/- 0.004 0.021 + 0.004 0.018 + 0.004 0.033 _ 0.004 0.018 + 0.003 0.026 + 0.004 0.027 +/- 0.004 0.032 +/- 0.004 0.036 +/- 0.005 0.042 +/- 0.005 0.030 +/- 0.004 0.032 +/- 0.004 2nd Quarter Mean +/- s.d.

0.019 +/- 0.005 4th Quarter Mean +/- s.d.

Cumulative Average Previous Annual Average 0.027 +/- 0.008 0.023 0.024 a Iodine-131 concentrations are < 0.07 pCi/m3 unless noted otherwise in Appendix C.

2-1

Table 3. Airborne particulates and charcoal canisters, analyses for gross beta and iodine-131a.

Location: T-3 Units: pCi/m 3

Collection: Continuous, weekly exchange.

Date Volume Date Volume Collected (ms)

Gross Beta Collected (m")

Gross Beta Req~uired LLD 0.010 01-10-06 01-17-06 01-24-06 01-31-06 02-07-06 02-14-06 02-21-06 02-28-06 03-07-06 03-14-06 03-21-06 03-28-06 286 266 224 278 281 280 280 281 280 281 280 275 0.018 0.021 0.021 0.025 0.019 0.016 0.027 0.031 0.018 0.019 0.020 0.010

+/- 0.004

+/- 0.004

+/- 0.004

+/- 0.004

+/- 0.004

+/- 0.003

+/- 0.004

+/- 0.004

+/- 0.004

+/- 0.004

+/- 0.004

+/- 0.003 07-05-06 07-11-06 07-18-06 07-25-06 08-01 -06 08-08-06 08-15-06 08-22-06 08-29-06 09-05-06 09-12-06 09-19-06 09-26-06 10-03-06 320 240 277 280 285 270 279 279 281 277 279 278 280 279 0.010 0.026 +/- 0.004 0.018 +/- 0.004 0.029 +/- 0.004 0.019 +/- 0.004 0.033 +/- 0.004 0.023 +/- 0.004 0.022 +/- 0.004 0.028 +/- 0.004 0.039 +/- 0.005 0.019 +/- 0.004 0.030 +/- 0.004 0.027 +/- 0.004 0.020 +/- 0.004 0.020 +/- 0.004 1st Quarter Mean +/- s.d.

04-04-06 04-11 -06 04-18-06 04-25-06 05-02-06 05-09-06 05-16-06 05-23-06 05-30-06 06-06-06 06-13-06 06-20-06 06-27-06 279 280 281 281 280 283 279 278 281 280 276 278 278 0.020 +/- 0.005 0.021 +/- 0.004 0.021 +/- 0.004 0.019 +/- 0.004 0.013 +/- 0.003 0.018 +/- 0.004 0.017 +/- 0.004 0.015 +/- 0.003 0.007 +/- 0.003 0.023 +/- 0.004 0.024 +/- 0.004 0.015 +/- 0.004 0.020 +/- 0.004 0.017 +/- 0.003 3rd Quarter Mean +/- s.d.

10-10-06 10-17-06 10-24-06 10-31-06 11-07-06 11-14-06 11-21-06 11-28-06 12-05-06 12-12-06 12-19-06 12-26-06 01-02-07 279 278 279 279 279 281 280 281 280 282 286 287 287 0.025 +/- 0.006 0.019 +/- 0.004 0.018 +/- 0.004 0.017 +/- 0.004 0.019 +/- 0.004 0.032 0.021 0.022 0.029 0.031 0.038 0.037 0.025 0.027

+/- 0.004

+/- 0.004

+/- 0.004

+/- 0.004

+/- 0.004

+/- 0.005

+/- 0.004

+/- 0.004

+/- 0.004 2nd Quarter Mean +/- s.d.

0.018 +/- 0.005 4th Quarter Mean +/- s.d.

Cumulative Average Previous Annual Averaqe 0.026 +/- 0.007 0.022 0.025 a Iodine-1 31 concentrations are < 0.07 pCi/m 3 unless noted otherwise in Appendix C.

3-1

Table 4. Airborne particulates and charcoal canisters, analyses for gross beta and iodine-131 a.

Location: T-4 Units: pCi/m 3

Collection: Continuous, weekly exchange.

Date Volume Date Volume Collected (m")

Gross Beta Collected (mi)

Gross Beta Required LLD 01-10-06 01-17-06 01-24-06 01-31-06 02-07-06 02-14-06 02-21-06 02-28-06 03-07-06 03-14-06 03-21-06 03-28-06 284 281 284 284 285 284 283 285 284 284 283 285 0.010 0.023 +/- 0.004 0.020 +/- 0.004 0.022 +/- 0.004 0.027 +/- 0.004 0.019 +/- 0.004 0.019 +/- 0.004 0.031 +/- 0.004 0.029 +/- 0.004 0.018 +/- 0.003 0.020 +/- 0.004 0.026 +/- 0.004 0.009 +/- 0.003 07-05-06 07-11-06 07-18-06 07-25-06 08-01-06 08-08-06 08-15-06 08-22-06 08-29-06 09-05-06 09-12-06 09-19-06 09-26-06 10-03-06 323 243 280 283 281 287 281 281 239 280 282 281 277 282 0.010 0.025 +/- 0.004 0.021 +/- 0.004 0.027 +/- 0.004 0.024 +/- 0.004 0.036 +/- 0.004 0.024 +/- 0.004 0.021 +/- 0.004 0.027 +/- 0.004 0.051 +/- 0.006 0.015 +/- 0.003 0.029 +/- 0.004 0.025 +/- 0.004 0.021 +/- 0.004 0.024 +/- 0.004 1st Quarter Mean +/- s.d.

0.022 +/- 0.006 3rd Quarter Mean +/- s.d.

04-04-06 04-11-06 04-18-06 04-25-06 05-02-06 05-09-06 05-16-06 05-23-06 05-30-06 06-06-06 06-13-06 06-20-06 06-27-06 283 283 284 282 283 287 282 288 278 281 284 281 281 0.021 0.025 0.018 0.012 0.018 0.016 0.015 0.009 0.026 0.022 0.013 0.016 0.023

+/- 0.004

+/- 0.004

+/- 0.004

+/- 0.003

+ 0.004

+ 0.004

+ 0.003

+ 0.003

+ 0.004

+ 0.004

+ 0.003

+ 0.004

+ 0.004 10-10-06 10-17-06 10-24-06 10-31-06 11-07-06 11-14-06 11-21-06 11-28-06 12-05-06 12-12-06 12-19-06 12-26-06 01-02-07 281 280 282 281 282 281 279 281 280 282 279 281 280 0.026 +/- 0.009 0.024 +/- 0.004 0.021 +/- 0.004 0.020 +/- 0.004 0.017 +/- 0.004 0.035 +/- 0.005 0.021 +/- 0.004 0.022 +/- 0.004 0.024 +/- 0.004 0.028 +/- 0.004 0.033 +/- 0.004 0.043 +/- 0.005 0.026 +/- 0.004 0.029 +/- 0.004 2nd Quarter Mean +/- s.d.

0.018 +/- 0.005 4th Quarter Mean +/- s.d.

Cumulative Average Previous Annual Average 0.026 +/- 0.007 0.023 0.025 a Iodine-131 concentrations are < 0.07 pCi/m3 unless noted otherwise in Appendix C.

4-1

Table 5. Airborne particulates and charcoal canisters, analyses for gross beta and iodine-131a.

Location: T-7 Units: pCi/m 3

Collection: Continuous, weekly exchange.

Date Volume Date Volume Collected (M3)

Gross Beta Collected (M3)

Gross Beta Required LLD 0.010 0.010 01-10-06 01-17-06 01-24-06 01-31-06 02-07-06 02-14-06 02-21-06

'02-28-06 03-07-06 03-14-06 03-21-06 03-28-06 279 282 281 278 285 277 280 281 281 279 280 281 0.020 +/- 0.004 0.018 +/- 0.004 0.022 +/- 0.004 0.025 +/- 0.004 0.018 +/- 0.004 0.017 +/- 0.004 0.029 +/- 0.004 0.029 +/- 0.004 0.015 +/- 0.003 0.019 +/- 0.004 0.024 +/- 0.004 0.011 +/- 0.003 07-05-06 07-11-06 07-18-06 07-25-06 08-01-06 08-08-06 08-15-06 08-22-06 08-29-06 09-05-06 09-12-06 09-19-06 09-26-06 10-03-06 320 238 282 283 282 283 282 282 283 282 282 282 283 282 0.024 +/- 0.004 0.018 +/- 0.004 0.030 +/- 0.004 0.022 +/- 0.004 0.034 +/- 0.004 0.023 +/- 0.004 0.021 +/- 0.004 0.025 +/- 0.004 0.042 +/- 0.005 0.017 +/- 0.004 0.033 +/- 0.004 0.024 +/- 0.004 0.021 +/- 0.004 0.023 +/- 0.004 1st Quarter Mean +/- s.d.

04-04-06 04-11-06 04-18-06 04-25-06 05-02-06 05-09-06 05-16-06 05-23-06 05-30-06 06-06-06 06-13-06 06-20-06 06-27-06 279 280 281 281 281 308 275 288 281 290 281 280 281 0.021 +/- 0.005 0.019 +/- 0..004 0.023 +/- 0.004 0.019 +/- 0.004 0.009 +/- 0.003 0.016 +/- 0.004 0.019 +/- 0.004 0.013 +/- 0.003 0.009 +/- 0.003 0.026 +/- 0.004 0.029 +/- 0.004 0.015 +/- 0.004 0.022 +/- 0.004 0.017 +/- 0.003 3rd Quarter Mean +/- s.d.

10-10-06 10-17-06 10-24-06 10-31 -06 11-07-06 11-14-06 11-21-06 11-28-06 12-05-06 12-12-06 12-19-06 12-26-06 01-02-07 282 281 286 279 282 284 283 284 282 287 284 287 281 0.026 +/- 0.007 0.021 +/- 0.004 0.022 +/- 0.004 0.018 +/- 0.004 0.018 +/- 0.004 0.035 +/- 0.005 0.020 +/- 0.004 0.025 +/- 0.004 0.026 +/- 0.004 0.029 +/- 0.004 0.037 +/- 0.004 0.040 +/- 0.005 0.023 +/- 0.004 0.029 +/- 0.004 2nd Quarter Mean +/- s.d.

0.018 +/- 0.006 4th Quarter Mean +/- s.d.

Cumulative Average Previous Annual Averaqe 0.026 +/- 0.007 0.023 0.024 a Iodine-1 31 concentrations are < 0.07 pCi/m3 unless noted otherwise in Appendix C.

5-1

Table 6. Airborne particulates and charcoal canisters, analyses for gross beta and iodine-131a.

Location: T-8 Units: pCi/m 3

Collection: Continuous, weekly exchange.

Date Volume Date Volume Collected (m3)

Gross Beta Collected (m 3)

Gross Beta Required LLD 0.010 0.010 01-10-06 01-17-06 01-24-06 01-31-06 02-07-06 02-14-06 02-21-06 02-28-06 03-07-06 03-14-06 03-21-06 03-28-06 299 295 285 293 286 283 284 281 284 279 283 285 0.022 +/- 0.004 0.020 +/- 0.004 0.021 +/- 0.004 0.025 +/- 0.004 0.022 +/- 0.004 0.025 +/- 0.004 0.026 +/- 0.004 0.029 +/- 0.004 0.015 +/- 0.003 0.019 +/- 0.004 0.024 +/- 0.004 0.009 +/- 0.003 07-05-06 07-11-06 07-18-06 07-25-06 08-01-06 08-08-06 08-15-06 08-22-06 08-29-06 09-05-06 09-12-06 09-19-06 09-26-06 10-03-06 325 243 352 287 282 286 281 283 289 280 285 281 285 284 0.024 +/- 0.004 0.018 +/- 0.004 0.026 +/- 0.003 0.022 +/- 0.004 0.031 +/- 0.004 0.020 +/- 0.004 0.020 +/- 0.004 0.026 +/- 0.004 0.035 +/- 0.004 0.019 0.027 0.025 0.020 0.019

+/- 0.004

+/- 0.004

+ 0.004

+ 0.004

+/- 0.004 1st Quarter Mean +/- s.d.

04-04-06 04-11-06 04-18-06 04-25-06 05-02-06 05-09-06 05-16-06 05-23-06 05-30-06 06-06-06 06-13-06 06-20-06 06-27-06 281 281 283 284 282 287 279 283 275 282 286 281 283 0.021 +/- 0.005 0.021 +/- 0.004 0.025 +/- 0.004 0.019 +/- 0.004 0.013 +/- 0.003 0.019 +/- 0.004 0.028 +/- 0.004 0.012 +/- 0.003 0.010 +/- 0.003 0.023 +/- 0.004 0.022 +/- 0.004 0.017 +/- 0.004 0.020 +/- 0.004 0.015 +/- 0.003 3rd Quarter Mean +/- s.d.

10-10-06 10-17-06 10-24-06 10-31-06 11-07-06 11-14-06 11-21-06 11-28-06 12-05-06 12-12-06 12-19-06 12-26-06 01-02-07 282 281 284 283 283 261 262 260 262 263 260 262 263 0.024 +/- 0.005 0.021 +/- 0.004 0.022 +/- 0.004 0.017 +/- 0.003 0.017 +/- 0.003 0.032 +/- 0.004 0.020 +/- 0.004 0.024 +/- 0.004 0.032 +/- 0.005 0.032 +/- 0.004 0.041 +/- 0.005 0.047 +/- 0.005 0.032 +/- 0.004 0.027 +/- 0.004 2nd Quarter Mean +/- s.d.

0.019 +/- 0.005 4th Quarter Mean +/- s.d.

Cumulative Average Previous Annual Average 0.028 +/- 0.009 0.023 0.025 a Iodine-131 concentrations are < 0.07 pCi/m 3 unless noted otherwise in Appendix C.

6-1

Table 7. Airborne particulates and charcoal canisters, analyses for gross beta and iodine-131a.

Location: T-9 (C)

Units: pCi/m 3

Collection: Continuous, weekly exchange.

Date Volume Date Volume Collected (m")

Gross Beta Collected (m")

Gross Beta Required LLD 0.010 0.010 01-10-06 01-17-06 01-24-06 01-31-06 02-07-06 02-14-06 02-21-06 02-28-06 03-07-06 03-14-06 03-21-06 03-28-06 275 273 284 283 286 282 283 279 283 281 281 283 0.020 +/- 0.004 0.022 +/- 0.004 0.022 +/- 0.004 0.029 +/- 0.004 0.019 +/- 0.004 0.020 +/- 0.004 0.028 +/- 0.004 0.030 +/- 0.004 0.018 +/- 0.003 0.019 +/- 0.004 0.020 +/- 0.004 0.008 +/- 0.003 07-05-06 07-11-06 07-18-06 07-25-06 08-01-06 08-08-06 08-15-06 08-22-06 08-29-06 323 242 280 282 279 282 279 280 284 0.031 +/- 0.004 0.028 +/- 0.005 0.029 +/- 0.004 0.021 +/- 0.004 0.035 +/- 0.004 09-05-06 277 09-12-06 282 09-19-06 279 09-26-06 283 10-03-06 281 3rd Quarter Mean +/- s.d.

0.025 0.020 0.026 0.037 0.021 0.029 0.025 0.019 0.021 0.026

+/- 0.004

+/- 0.004

+/- 0.004

+/- 0.005

+/- 0.004

+/- 0.004

+/- 0.004

+/- 0.004

+/- 0.004

+/- 0.006 1st Quarter Mean +/- s.d.

04-04-06 04-11-06 04-18-06 04-25-06 05-02-06 05-09-06 05-16-06 05-23-06 05-30-06 06-06-06 06-13-06 06-20-06 06-27-06 280 282 279 282 280 285 280 281 282 281 285 279 281 0.021 +/- 0.006 0.019 +/- 0.004 0.023 +/- 0.004 0.020 +/- 0.004 0.014 +/- 0.004 0.016 +/- 0.004 0.018 +/- 0.004 0.014 +/- 0.003 0.011 +/- 0.003 0.023 +/- 0.004 0.023 +/- 0.004 0.017 +/- 0.004 0.023 +/- 0.004 0.023 +/- 0.004 10-10-06 10-17-06 10-24-06 10-31-06 11-07-06 11-14-06 11-21-06 11-28-06 12-05-06 12-12-06 12-19-06 12-26-06 01-02-07 280 278 282 280 281 280 281 274 277 278 275 277 278 0.022 +/- 0.004 0.024 +/- 0.004 0.020 +/- 0.004 0.018 +/- 0.004 0.033 +/- 0.004 0.019 +/- 0.004 0.020 +/- 0.004 0.027 +/- 0.004 0.027 0.037 0.045 0.031 0.037

+/- 0.004

+/- 0.005

+/- 0.005

+/- 0.004

+/- 0.005 2nd Quarter Mean +/- s.d.

0.019 +/- 0.004 4th Quarter Mean +/- s.d.

Cumulative Average Previous Annual Average 0.028 +/- 0.008 0.024 0.025 a lodine-131 concentrations are < 0.07 pCi/m 3 unless noted otherwise in Appendix C.

7-1

Table 8. Airborne particulates and charcoal canisters, analyses for gross beta and iodine-131a.

Location: T-1 1 (C)

Units: pCi/m 3 Collection:

Continuous, weekly exchange.

Date Volume Date Volume Collected (m")

Gross Beta Collected (m")

Gross Beta Required LLD 0.010 01-10-06 01-17-06 01-24-06 01-31-06 02-07-06 02-14-06 02-21-06 02-28-06 03-07-06 03-14-06 03-21-06 03-28-06 283 281 284 283 284 283 283 283 283 283 283 280 0.021 0.024 0.022 0.022 0.025 0.018 0.031 0.028

+ 0.004

+ 0.004

+/- 0.004

+/- 0.004

+ 0.004

+ 0.004

+ 0.004

+ 0.004 07-05-06 07-11-06 07-18-06 07-25-06 08-01-06 08-08-06 08-15-06 08-22-06 08-29-06 09-05-06 09-12-06 09-19-06 09-26-06 10-03-06 329 247 287 288 287 287 287 287 280 287 287 287 288 287 0.010 0.026 +/- 0.004 0.021 +/- 0.004 0.029 +/- 0.004 0.023 +/- 0.004 0.036 +/- 0.004 0.024 +/- 0.004 0.021 +/- 0.004 0.031 +/- 0.004 0.039 +/- 0.005 0.018 +/- 0.004 0.030 +/- 0.004 0.025 +/- 0.004 0.018 +/- 0.004 0.021 +/- 0.004 0.015 +/- 0.003 0.021 +/- 0.004 0.024 +/- 0.004 0.012 +/- 0.003 1st Quarter Mean +/- s.d.

04-04-06 04-11-06 04-18-06 04-25-06 05-02-06 05-09-06 05-16-06 05-23-06 05-30-06 06-06-06 06-13-06 06-20-06 06-27-06 281 283 281 284 283 284 282 292 288 287 287 288 287 0.022 +/- 0.005 0.020 +/- 0.004 0.023 +/- 0.004 0.022 +/- 0.004 0.013 +/- 0.003 0.019 +/- 0.004 0.018 +/- 0.004 0.013 +/- 0.003 0.009 +/- 0.003 0.025 +/- 0.004 0.024 +/- 0.004 0.017 +/- 0.004 0.021 +/- 0.004 0.018 +/- 0.003 3rd Quarter Mean +/- s.d.

0.026 +/- 0.006 10-10-06 10-17-06 10-24-06 10-31 -06 11-07-06 11-14-06 11-21-06 11-28-06 12-05-06 12-12-06 12-19-06 12-26-06 01-02-07 288 287 288 287 287 287 287 285 287 288 287 288 287 0.022 0.019 0.019 0.018 0.031 0.021 0.023 0.029

+/- 0.004

+/- 0.004

+/- 0.004

+/- 0.004

+/- 0.004

+/- 0.004

+/- 0.004

+/- 0.004 0.033 +/- 0.004 0.033 +/- 0.004 0.041 + 0.005 0.028 +/- 0.004 0.034 + 0.004 2nd Quarter Mean +/- s.d.

0.019 +/- 0.005 4th Quarter Mean +/- s.d.

Cumulative Average Previous Annual Average 0.027 +/- 0.007 0.023 0.024 a Iodine-1 31 concentrations are < 0.07 pCi/m 3 unless noted otherwise in Appendix C.

8-1

Table 9. Airborne particulates and charcoal canisters, analyses for gross beta and iodine-131a.

Location: T-12 (C)

Units: pCi/m 3

Collection: Continuous, weekly exchange.

Date Volume Date Volume Collected (me)

Gross Beta Collected (m")

Gross Beta Required LLD 0.010 0.010 01-10-06 01-17-06 01-24-06 01-31-06 02-07-06 02-14-06 02-21-06 02-28-06 03-07-06 03-14-06 03-21-06 03-28-06 284 330 266 293 262 329 277 299 284 284 283 278 0.017 +/- 0.004 0.023 +/- 0.003 0.018 +/- 0.004 0.024 +/- 0.004 0.019 +/- 0.004 0.020 +/- 0.003 0.026 +/- 0.004 0.035 +/- 0.004 0.011 +/- 0.003 0.019 +/- 0.004 0.023 +/- 0.004 0.011 +/- 0.003 07-05-06 07-11-06 07-18-06 07-25-06 08-01-06 08-08-06 08-15-06 08-22-06 08-29-06 09-05-06 09-12-06 09-19-06 09-26-06 10-03-06 327 244 282 286 283 285 275 281 284 279 282 280 283 282 0.027 +/- 0.004 0.022 +/- 0.004 0.027 +/- 0.004 0.021 +/- 0.004 0.039 +/- 0.005 0.023 +/- 0.004 0.017 +/- 0.004 0.029 +/- 0.004 0.038 +/- 0.005 0.021 +/- 0.004 0.032 +/- 0.004 0.023 +/- 0.004 0.019 +/- 0.004 0.023 +/- 0.004 1st Quarter Mean +/- s.d.

04-04-06 04-11-06 04-18-06 04-25-06 05-02-06 05-09-06 05-16-06 05-23-06 05-30-06 06-06.06 06-13-06 06-20-06 06-27-06 283 283 284 285 282 287 282 283 285 282 287 282 283 0.021 +/- 0.007 0.018 +/- 0.004 0.023 +/- 0.004 0.023 +/- 0.004 0.012 +/- 0.003 0.015 + 0.004 0.019 +/- 0.004 0.014 +/- 0.003 0.009 +/- 0.003 0.026 0 0.004 0.022 + 0.004 0.015 +/- 0.003 0.025 +/- 0.004 0.020 +/- 0.004 3rd Quarter Mean +/- s.d.

10-10-06 10-17-06 10-24-06 10-31-06 11-07-06 11-14-06 11-21-06 11-28-06 12-05-06 12-12-06 12-19-06 12-26-06 01-02-07 281 280 283 281 281 281 280 280 281 282 279 281 281 0.026 +/- 0.007 0.021 +/- 0.004 0.021 +/- 0.004 0.019 +/- 0.004 0.019 +/- 0.004 0.032 +/- 0.004 0.015 +/- 0.003 0.024 +/- 0.004 0.025 +/- 0.004 0.027 +/- 0.004 0.034 +/- 0.004 0.041 +/- 0.005 0.028 +/- 0.004 0.029 +/- 0.004 2nd Quarter Mean +/- s.d.

0.019 +/- 0.005 4th Quarter Mean +/- s.d.

Cumulative Average Previous Annual Average 0.026 +/- 0.007 0.023 0.025 a Iodine-1 31 concentrations are < 0.07 pCi/mi3 unless noted otherwise.

9-1

Table 10. Airborne particulates and charcoal canisters, analyses for gross beta and iodine-131a.

Location: T-27 (C)

Units: pCi/m 3 Collection: Continuous, weekly exchange.

Date Volume Date Volume Collected (mi)

Gross Beta Collected (mi)

Gross Beta Required LLD 0.010 0.010 01-10-06 01-17-06 01-24-06 01-31-06 02-07-06 02-14-06 02-21-06 02-28-06 03-07-06 03-14-06 03-21-06 03-28-06 285 290 286 286 287 285 285 286 286 286 285 286 0.022 +/- 0.004 0.023 +/- 0.004 0.016 +/- 0.003 0.025 +/- 0.004 0.023 +/- 0.004 0.021 +/- 0.004 0.027 +/- 0.004 0.027 +/- 0.004 0.017 +/- 0.003 0.024 +/- 0.004 0.020 +/- 0.004 0.010 +/- 0.003 07-05-06 07-11-06 07-18-06 07-25-06 08-01-06 08-08-06 08-15-06 08-22-06 08-29-06 09-05-06 09-12-06 09-19-06 09-26-06 10-03-06 325 243 281 284 282 284 282 283 285 281 285 283 286 284 0.027 +/- 0.004 0.021 +/- 0.004 0.028 +/- 0.004 0.019 +/- 0.003 0.035 +/- 0.003 0.023 0.022 0.025 0.043

+/- 0.004

+/- 0.004

+/- 0.004

+/- 0.005 0.015 +/- 0.004 0.031 +/- 0.004 0.022 +/- 0.004 0.020 +/- 0.004 0.019 +/- 0.004 1st Quarter Mean +/- s.d.

04-04-06 04-11-06 04-18-06 04-25-06 05-02-06 05-09-06 05-16-06 05-23-06 05-30-06 06-06-06 06-13-06 06-20-06 06-27-06 284 285 283 284 282 286 281 282 284 282 286 281 282 0.021 +/- 0.005 0.018 +/- 0.004 0.022 +/- 0.004 0.017 +/- 0.004 0.014 +/- 0.003 0.014 +/- 0.004 0.015 +/- 0.004 0.012 +/- 0.003 0.009 +/- 0.003 0.024 +/- 0.004 0.026 +/- 0.004 0.016 +/- 0.004 0.024 +/- 0.004 0.020 +/- 0.004 3rd Quarter Mean +/- s.d.

10-10-06 10-17-06 10-24-06 10-31 -06 11-07-06 11-14-06 11-21-06 11-28-06 12-05-06 12-12-06 12-19-06 12-26-06 01-02-07 284 287 281 283 284 284 283 284 284 286 283 285 284 0.025 +/- 0.007 0.023 +/- 0.004 0.024 +/- 0.004 0.021 +/- 0.004 0.021 +/- 0.004 0.037 +/- 0.005 0.019 +/- 0.003 0.023 +/- 0.004 0.026 +/- 0.004 0.029 +/- 0.004 0.036 +/- 0.004 0.046 +/- 0.005 0.027 +/- 0.004 0.030 +/- 0.004 2nd Quarter Mean +/- s.d.

0.018 +/- 0.005 4th Quarter Mean +/- s.d.

Cumulative Average Previous Annual Averaqe 0.028 +/- 0.008 0.023 0.026 a Iodine-1 31 concentrations are < 0.07 pCi/m 3 unless noted otherwise in Appendix C.

10-1

Table 11-1. Airborne particulate data,gross beta analyses, monthly averages, minima and maxima.

Location T-9 T-1 I T-12 T-27 Controls T-1 T-2 T-3 T-4 T-7 T-8 Indicators January Average Minima Maxima 0.023 0.020 0.029 0.022 0.021 0.024 0.021 0.017 0.024 0.022 0.016 0.025 0.022 0.016 0.029 0.022 0.018 0.027 0.022 0.019 0.027 0.021 0.018 0.025 0.023 0.020 0.027 0.021 0.018 0.025 0.022 0.020 0.025 0.022 0.018 0.027 Location T-9 T-11 T-12 T-27 Controls T-1 T-2 T-3 T-4 T-7 T-8 Indicators April Average Minima Maxima 0.018 0.014 0.023 0.019 0.013 0.023 0.018 0.012 0.023 0.017 0.014 0.022 0.018 0.012 0.023 0.018 0.012 0.021 0.019 0.014 0.023 0.018 0.013 0.021 0.019 0.012 0.025 0.017 0.009 0.023 0.019 0.013 0.025 0.018 0.009 0.025 Location T-9 T-1 1 T-12 T-27 February Average Minima Maxima 0.024 0.019 0.030 0.026 0.018 0.031 0.025 0.019 0.035 0.025 0.021 0.027 Location T-9 T-11 T-12 T-27 May Average Minima Maxima 0.017 0.011 0.023 0.016 0.009 0.025 0.017 0.009 0.026 0.015 0.009 0.024 Controls T-1 T-2 T-3 T-4 T-7 T-8 Indicators 0.025 0.018 0.035 0.023 0.019 0.029 0.022 0.017 0.028 0.023 0.016 0.031 0.025 0.019 0.031 0.023 0.017 0.029 0.026 0.022 0.029 0.024 0.016 0.031 Controls T-1 T-2 T-3 T-4 T-7 T-8 Indicators 0.016 0.009 0.026 0.016 0.009 0.020 0.018 0.008 0.025 0.016 0.007 0.023 0,017 0.009 0.026 0.017 0.009 0.026 0.018 0.010 0.028 0,017 0.007 0.028 March Location Average Minima Maxima T-9 0.016 0.008 0.020 T-11 0.018 0.012 0.024 T-12 0.016 0.011 0.023 T-27 0.018 0.010 0.024 Controls 0.017 0.008 0.024 T-1 0.019 0.014 0.024 T-2 0.018 0.007 0.024 T-3 0.017 0.010 0.020 T-4 0.018 0.009 0.026 T-7 0.017 0.011 0.024 T-8 0.017 0.009 0.024 Indicators 0.018 0.007 0.026 June Location Average Minima Maxima T-9 0.022 0.017 0.023 T-11 0.020 0.017 0.024 T-12 0.021 0.015 0.025 T-27 0.022 0.016 0.026 Controls 0.021 0.015 0.026 T-1 0.021 0.017 0.025 T-2 0.021 0.014 0.026 T-3 0.019 0.015 0.024 T-4 0.019 0.013 0.023 T-7 0.021 0.015 0.029 T-8 0.019 0.015 0.022 Indicators 0.020 0.013 0.029 Note: Unless otherwise specified, samples collected on the first, second or third day of the month are grouped with data of the previous month.

11-1

Table 11-1. Airborne particulate data,gross beta analyses, monthly averages, minima and maxima.

Location T-9 T-1 1 T-1 2 T-27 Controls July Average Minima Maxima 0.029 0.021 0.035 0.027 0.021 0.036 0.027 0.021 0.039 0.026 0.019 0.035 0.027 0.019 0.039 Location T-9 T-11 T-12 T-27 Controls October Average Minima Maxima 0.021 0.018 0.024 0.020 0.018 0.022 0.020 0.019 0.021 0.022 0.021 0.024 0.021 0.018 0.024 T-1 0.026 0.021 0.031 T-2 0.026 0.023 0.030 T-3 0.025 0.018 0.033 T-4 0.027 0.021 0.036 T-7 0.026 0.018 0.034 T-8 0.024 0.018 0.031 T-1 0.021 0.018 0.027 T-2 0.020 0.018 0.021 T-3 0.018 0.017 0.019 T-4 0.021 0.017 0.024 T-7 0.020 0.018 0.022 T-8 0.019 0.017 0.022 Indicators 0.026 0.018 0.036 Indicators 0.020 0.017 0.027 August Location T-9 T-11 T-1 2 T-27 Controls T-1 T-2 T-3 T-4 T-7 T-8 Indicators Average Minima Maxima 0.027 0.020 0.037 0.029 0.021 0.039 0.027 0.017 0.038 0.028 0.022 0.043 0.028 0.017 0.043 0.028 0.022 0.038 0.028 0.022 0.040 0.028 0.022 0.039 0.031 0.021 0.051 0.028 0.021 0.042 0.025 0.020 0.035 0.028 0.020 0.051 Location T-9 T-1 1 T-12 T-27 Controls T-1 T-2 T-3 T-4 T-7 T-8 Indicators November Average Minima Maxima 0.025 0.019 0.033 0.026 0.021 0.031 0.024 0.015 0.032 0.026 0.019 0.037 0.025 0.015 0.037 0.027 0.021 0.034 0.026 0.018 0.033 0.026 0.021 0.032 0.026 0.021 0.035 0.027 0.020 0.035 0.027 0.020 0.032 0.026 0.018 0.035 Location T-9 T-11 T-12 T-27 Controls T-1 T-2 T-3 T-4 T-7 T-8 Indicators September Average Minima Maxima 0.023 0.019 0.029 0.022 0.018 0.030 0.024 0.019 0.032 0.021 0.015 0.031 0.023 0.015 0.032 0.023 0.019 0.033 0.023 0.017 0.030 0.023 0.019 0.030 0.023 0.015 0.029 0.024 0.017 0.033 0.022 0.019 0.027 0.023 0.015 0.033 Location T-9 T-1 1 T-12 T-27 Controls T-1 T-2 T-3 T-4 T-7 T-8 Indicators December Average Minima Maxima 0.035 0.027 0.045 0.034 0.028 0.041 0.032 0.027 0.041 0.034 0.027 0.046 0.034 0.027 0.046 0.037 0.027 0.053 0.034 0.030 0.042 0.032 0.025 0.038 0.032 0.026 0.043 0,032 0.023 0.040 0.036 0.027 0.047 0.034 0.023 0.053 Note: Unless otherwise specified, samples collected on the first, second or third day of the month are grouped with data of the previous month.

11-2

TOLEDO Table 12.

Airborne particulates, analyses for strontium-89, strontium-90 and gamma-emitting isotopes.

Collection: Quarterly Composite Units: pCi/m 3 Location T-1 Quarter 1st Quarter 2nd Quarter 3rd Quarter 4th Quarter Lab Code TAP-2524 TAP-4893 TAP-7537 TAP-9653 Volume (m3) 3312 3623 3963 3701 Sr-89

< 0.0008

< 0.0010

< 0.0006

< 0.0005 Sr-90

< 0.0005

< 0.0006

< 0.0004

< 0.0004 Be-7 0.073 +/- 0.015 0.095 +/- 0.023 0.077 +/- 0.013 0.063 +/- 0.016 K-40

< 0.033

< 0.019

< 0.020

< 0.023 Nb-95

< 0.0008

< 0.0020

< 0.0008

< 0.0007 Zr-95

< 0.0016

< 0.0024

< 0.0010

< 0.0011 Ru-103

< 0.0012

< 0.0010

< 0.0008

< 0.0008 Ru-1 06

< 0.0078

< 0.0063

< 0.0078

< 0.0057 Cs-134

< 0.0011

< 0.0008

< 0.0007

< 0.0007 Cs-137

< 0.0003

< 0.0010

< 0.0007

< 0.0005 Ce-141

< 0.0008

< 0.0013

< 0.0014

< 0.0010 Ce-144

< 0.0043

< 0.0057

< 0.0049

< 0.0039 Location T-2 Quarter 1st Quarter 2nd Quarter 3rd Quarter 4th Quarter Lab Code TAP-2525 TAP-4894 TAP-7538 TAP-9654 Volume (m3 )

3332 3645 3892 3633 Sr-89

< 0.0009

< 0.0010

< 0.0007

< 0.0006 Sr-90

< 0.0005

< 0.0005

< 0.0004

< 0.0004 Be-7 0.066 +/- 0.014 0.10 +/- 0.020 0.093 +/- 0.015 0.066 +/- 0.015 K-40

< 0.016

< 0.028

< 0.024

< 0.024 Nb-95

< 0.0019

< 0.0006

< 0.0008

< 0.0009 Zr-95

< 0.0012

< 0.0013

< 0.0011

< 0.0012 Ru-103

< 0.0007

< 0.0017

< 0.0007

< 0.0012 Ru-106

< 0.0072

< 0.0057

< 0.0065

< 0.0053 Cs-134

< 0.0006

< 0.0010

< 0.0009

< 0.0004 Cs-137

< 0.0007

< 0.0005

< 0.0006

< 0.0006 Ce-141

< 0.0011

< 0.0024

< 0.0011

< 0.0020 Ce-144

< 0.0048

< 0.0039

< 0.0036

< 0.0035 12-1

TOLEDO Table 12.

Airborne particulates, analyses for strontium-89, strontium-90 and gamma-emitting isotopes.

Collection: Quarterly Composite Units: pCi/m 3 Location T-3 Quarter Lab Code Volume (M 3)

Sr-89 Sr-90 1 st Quarter TAP-2526 3292

< 0.0008

< 0.0006 Be-7 K-40 Nb-95 Zr-95 Ru-1 03 Ru-1 06 Cs-134 Cs-137 Ce-141 Ce-144 0.061 +/- 0.013

< 0.015

< 0.0010

< 0.0018

< 0.0009

< 0.0064

< 0.0008

< 0.0007

< 0.0010

< 0.0038 2nd Quarter TAP-4895 3634

< 0.0009

< 0.0006 0.095 +/- 0.019

< 0.028

< 0.0011

< 0.0020

< 0.0010

< 0.0061

< 0.0007

< 0.0006

< 0.0018

< 0.0043 3rd Quarter TAP-7539 3904

< 0.0006

< 0.0004 0.076 +/- 0.012

< 0.022

< 0.0008

< 0.0011

< 0.0007

< 0.0058

< 0.0004

< 0.0004

< 0.0009

< 0.0039 4th Quarter TAP-9655 3658

< 0.0006

< 0.0004 0.066 +/- 0.018

< 0.023

< 0.0009

< 0.0015

< 0.0010

< 0.0067

< 0.0007

< 0.0007

< 0.0019

< 0.0047 Location T-4 Quarter Lab Code Volume (M3)

Sr-89 Sr-90 Be-7 K-40 Nb-95 Zr-95 Ru-103 Ru-106 Cs-134 Cs-137 Ce-141 Ce-144 1 st Quarter TAP-2527 3406

< 0.0004

< 0.0003 0.071 +/- 0.014

< 0.032

< 0.0008

< 0.0016

< 0.0011

< 0.0093

< 0.0011

< 0.0003

< 0.0008

< 0.0042 2nd Quarter TAP-4896 3677

< 0.0009

< 0.0005 0.104 +/- 0.020

< 0.026

< 0.0011

< 0.0014

< 0.0010

< 0.0050

< 0.0008

< 0.0005

< 0.0017

< 0.0037 3rd Quarter TAP-7540 3900

< 0.0006

< 0.0003 0.085 +/- 0.015

< 0.022

< 0.0009

< 0.0013

< 0.0009

< 0.0051

< 0.0007

< 0.0009

< 0.0016

< 0.0029 4th Quarter TAP-9656 3649

< 0.0005

< 0.0003 0.072 +/- 0.016

< 0.019

< 0.0011

< 0.0019

< 0.0008

< 0.0050

< 0.0009

< 0.0009

< 0.0019

< 0.0043 12-2

TOLEDO Table 12.

Airborne particulates, analyses for strontium-89, strontium-90 and gamma-emitting isotopes.

Collection: Quarterly Composite Units: pCi/m 3

Location T-7 Quarter 1 st Quarter 2nd Quarter Lab Code Volume (m')

Sr-89 Sr-90 3rd Quarter TAP-7541 3946 4th Quarter TAP-9657 3682 Be-7 K-40 Nb-95 Zr-95 Ru-1 03 Ru-1 06 Cs-134 Cs-137 Ce-141 Ce-144 TAP-2528 3364

< 0.0008

< 0.0005 0.055 +/- 0.018

< 0.020

< 0.0017

< 0.0016

< 0.0014

< 0.0090

< 0.0009

< 0.0012

< 0.0026

< 0.0066 TAP-4897 3686

< 0.0009

< 0.0004 0.100 +/- 0.019

< 0.028

< 0.0009

< 0.0012

< 0.0009

< 0.0060

< 0.0008

< 0.0007

< 0.0024

< 0.0051

< 0.0007

< 0.0004

< 0.0005

< 0.0003 0.074 +/- 0.013

< 0.022

< 0.0009

< 0.0013

< 0.0007

< 0.0058

< 0.0007

< 0.0005

< 0.0021

< 0.0036 0.050 +/- 0.012

< 0.023

< 0.0007

< 0.0013

< 0.0007

< 0.0057

< 0.0009

< 0.0005

< 0.0013

< 0.0056 Location T-8 Quarter 1 st Quarter TAP-2529 3437 Lab Code Volume (mi)

Sr-89 Sr-90

< 0.0008

< 0.0006 Be-7 K-40 Nb-95 Zr-95 Ru-103 Ru-106 Cs-1 34 Cs-137 Ce-141 Ce-144 0.065 +/- 0.014

< 0.019

< 0.0008

< 0.0012

< 0.0011

< 0.0063

< 0.0007

< 0.0006

< 0.0018

< 0.0039 2nd Quarter TAP-4898 3667

< 0.0009

< 0.0005 0.084 +/- 0.017

< 0.026

< 0.0009

< 0.0014

< 0.0011

< 0.0074

< 0.0007

< 0.0005

< 0.0019

< 0.0042 3rd Quarter TAP-7542 4043

< 0.0006

< 0.0004 0.083 +/- 0.014

< 0.027

< 0.0009

< 0.0013

< 0.0008

< 0.0047

< 0.0006

< 0.0005

< 0.0015

< 0.0040 4th Quarter TAP-9658 3506

< 0.0006

< 0.0004 0.073 +/- 0.016

< 0.024

< 0.0012

< 0.0016

< 0.0012

< 0.0066

< 0.0005

< 0.0008

< 0.0021

< 0.0043 12-3

TOLEDO Table 12.

Airborne particulates, analyses for strontium-89, strontium-90 and gamma-emitting isotopes.

Collection: Quarterly Composite Units: pCi/m 3 Location T-9 (C)

Quarter 1st Quarter Lab Code Volume (mi)

Sr-89 Sr-90 Be-7 K-40 Nb-95 Zr-95 Ru-1 03 Ru-1 06 Cs-1 34 Cs-1 37 Ce-141 Ce-144 TAP-2530 3373

< 0.0008

< 0.0005 0.036 +/- 0.011

< 0.020

< 0.0022

< 0.0023

< 0.0009

< 0.0085

< 0.0006

< 0.0008

< 0.0025

< 0.0030 2nd Quarter TAP-4899 3657

< 0.0011

< 0.0006 0.110 +/- 0.023

< 0.028

< 0.0007

< 0.0014

< 0.0015

< 0.0066

< 0.0008

< 0.0006

< 0.0021

< 0.0039 3rd Quarter TAP-7543 3933

< 0.0007

< 0.0004 0.069 +/- 0.015

< 0.022

< 0.0008

< 0.0012

< 0.0005

< 0.0047

< 0.0007

< 0.0005

< 0.0009

< 0.0022 4th Quarter TAP-9659 3621

< 0.0005

< 0.0004 0.073 +/- 0.019

< 0.024

< 0.0009

< 0.0018

< 0.0011

< 0.0048

< 0.0006

< 0.0005

< 0.0020

< 0.0047 Location T-11 (C)

Quarter 1st Quarter 2nd Quarter 3rd Quarter 4th Quarter Lab Code TAP-2531 TAP-4900 TAP-7544 TAP-9660 Volume (m')

3393 3707 4015 3733 Sr-89

< 0.0008

< 0.0009

< 0.0006

< 0.0005 Sr-90

< 0.0006

< 0.0005

< 0.0004

< 0.0004 Be-7 0.089 +/- 0.020 0.076 +/- 0.020 0.069 +/- 0.016 0.051 +/- 0.012 K-40

< 0.033

< 0.028

< 0.021

< 0.026 Nb-95

< 0.0012

< 0.0014

< 0.0008

< 0.0008 Zr-95

< 0.0021

< 0.0013

< 0.0016

< 0.0012 Ru-1 03

< 0.0016

< 0.0010

< 0.0006

< 0.0007 Ru-106

< 0.0055

< 0.0061

< 0.0069

< 0.0066 Cs-134

< 0.0010

< 0.0008

< 0.0008

< 0.0004 Cs-137

< 0.0011

< 0.0008

< 0.0005

< 0.0006 Ce-141

< 0.0015

< 0.0010

< 0.0007

< 0.0009 Ce-144

< 0.0041

< 0.0034

< 0.0044

< 0.0026 12-4

TOLEDO Table 12.

Airborne particulates, analyses for strontium-89, strontium-90 and gamma-emitting isotopes.

Collection: Quarterly Composite Units: pCi/m 3

Location T-12 (C)

Quarter Lab Code Volume (m")

Sr-89 Sr-90 1 st Quarter TAP-2532 3469

< 0.0007

< 0.0004 Be-7 K-40 Nb-95 Zr-95 Ru-1 03 Ru-106 Cs-1 34 Cs-1 37 Ce-141 Ce-144 0.079 +/- 0.026

< 0.043

< 0.0044

< 0.0048

< 0.0028

< 0.0083

< 0.0015

< 0.0014

< 0.0033

< 0.0069 2nd Quarter TAP-4901 3688

< 0.0009

< 0.0005 0.089 +/- 0.019

< 0.028

< 0.0008

< 0.0016

< 0.0010

< 0.0036

< 0.0007

< 0.0006

< 0.0025

< 0.0035 3rd Quarter TAP-7545 3953

< 0.0006

< 0.0003 0.085 +/- 0.015

< 0.031

< 0.0009

< 0.0013

< 0.0009

< 0.0048

< 0.0006

< 0.0005

< 0.0015

< 0.0021 4th Quarter TAP-9661 3651

< 0.0005

< 0.0003 0.057 +/- 0.014

< 0.023

< 0.0012

< 0.0016

< 0.0007

< 0.0088

< 0.0007

< 0.0006

< 0.0022

< 0.0051 Location T-27 (C)

Quarter 1 st Quarter TAP-2533 3433 Lab Code Volume (m')

Sr-89 Sr-90

< 0.0007

< 0.0005 Be-7 K-40 Nb-95 Zr-95 Ru-103 Ru-106 Cs-1 34 Cs-137 Ce-141 Ce-144 0.051 +/- 0.018

< 0.024

< 0.0021

< 0.0021

< 0.0017

< 0.0096

< 0.0009

< 0.0008

< 0.0028

< 0.0069 2nd Quarter TAP-4902 3682

< 0.0009

< 0.0005 0.069 +/- 0.020

< 0.027

< 0.0007

< 0.0011

< 0.0010

< 0.0062

< 0.0008

< 0.0006

< 0.0021

< 0.0025 3rd Quarter TAP-7546 3968

< 0.0006

< 0.0003 0.083 +/- 0.013

< 0.022

< 0.0009

< 0.0012

< 0.0008

< 0.0056

< 0.0005

< 0.0003

< 0.0018

< 0.0037 4th Quarter TAP-9662 3692

< 0.0005

< 0.0003 0.071 +/- 0.014

< 0.024

< 0.0008

< 0.0020

< 0.0011

< 0.0053

< 0.0007

< 0.0005

< 0.0009

< 0.0040 12-5

TOLEDO Table 13. Area monitors (TLD), Quarterly.

Units: mR/91 days Indicator T-1 T-2 T-3 T-4 T-5 T-6 T-7 T-8 T-1 0 T-38 T-39 T-40 T-41 T-42 T-43 T-44 T-45 T-46 T-47 T-48 T-49 T-50 T-51 T-52 T-53 T-54 T-55 T-60 T-62 T-65 T-66 T-67 T-68 T-69 T-71 T-73 T-74 T-75 T-76 T-91 T-92 1st Qtr.

10.5 +/- 0.8 12.5 +/- 0.7 12.8 +/- 0.9 11.7 +/-0.7 13.9 +/- 1.0 11.5 +/-0.9 16.8 +/- 0.7 22.6 +/- 1.3 15.4 +/- 0.9 10.9 +/- 0.7 11.6 +/- 0.9 14.4 +/- 0.7 9.3 +/- 0.8 12.2 +/- 1.0 16.5 +/- 0.9 18.3 +/- 1.1 20.0 +/- 0.8 12.4 +/- 1.0 10.4 +/- 1.0 11.5 +/- 0.7 12.4 +/- 0.8 13.2 +/- 0.9 16.0 +/- 1.6 17.6 +/- 1.1 15.7 +/- 0.7 17.2 +/- 0.7 13.6 +/- 1.0 10.9 +/- 0.6 10.8 +/- 0.4 16.6 +/- 0.5 19.3 +/- 0.5 19.3 +/- 0.6 16.8 +/- 0.6 17.1 +/- 0.5 15.3 +/- 0.4 14.2 +/- 1.1 15.0 +/-0.4 14.8 +/- 0.4 11.8 +/-0.3 18.3 +/- 1.0 ND a 2nd Qtr.

11.0 +/- 1.0 12.3 +/- 0.5 12.0 +/-0.7 11.0 +/- 0.5 13.1 +/- 0.4 10.8 +/- 0.5 16.7 +/- 0.6 20.9 +/- 0.6 14.5 +/- 0.5 11.7 +/- 0.9 11.7 +/-0.5 14.7 +/-0.5 11.9 +/-0.6 11.8 +/-0.7 15.5 +/-0.8 18.3 + 0.7 21.1 +/-0.8 12.4 +/- 0.7 8.7 +/- 0.5 11.4 +/-0.5 11.6 +/-0.5 15.8 +/-1.1 17.6 +/-0.9 17.4 +/- 0.6 18.1 +/- 1.4 18.2 +/- 0.8 14.6 +/- 0.6 10.9 +/- 0.9 11.0 +/-0.5 16.9 +/-0.4 19.6 +/- 1.2 19.0 +/-0.6 16.9 +/-0.8 17.2 +/-0.5 15.7 +/-0.7 13.5 +/-0.5 15.3 +/-0.6 14.1 +/-0.3 10.8 +/- 0.4 17.3 +/-0.8 13.5 + 0.4 3rd Qtr.

11.0 +/- 0.6 13.3 +/- 0.4 13.4 +/- 0.7 12.6 +/- 0.5 15.2 +/- 0.7 12.1 +/- 0.7 17.7 +/- 0.6 23.7 +/- 1.8 15.6 +/- 0.6 12.9 +/- 0.9 11.4 +/-0.5 15.2 +/- 0.5 10.6 +/- 0.6 12.8 +/- 1.0 17.1 +/- 0.9 19.1 +/- 1.0 21.9 +/- 0.7 13.6 +/- 0.9 11.2 +/-0.8 12.4 +/- 0.4 13.4 +/- 0.6 13.9 +/- 0.5 18.5 +/- 1.6 19.0 +/- 1.1 17.1 +/- 0.5 18.6 +/- 0.5 14.6 +/- 1.1 11.9 +/-0.8 12.0 +/- 0.4 19.3 +/- 1.0 20.4 +/- 0.5 21.9 +/- 0.9 19.2 +/- 0.8 19.0 +/- 0.5 17.3 +/- 0.4 15.2 +/- 1.1 17.1 +/- 0.5 16.8 +/-0.4 12.6 +/- 0.3 20.8 +/- 1.0 12.1 +0.4 4th Qtr.

11.5 +/- 0.6 14.3 +/- 1.0 13.7 +/- 0.7 13.0 +/- 1.2 15.8 +/- 0.5 12.2 +/- 0.4 18.6 +/- 0.6 23.3 +/- 0.5 16.0 +/- 0.6 13.0 +/- 1.0 12.7 +/- 0.4 15.8 +/- 0.5 13.1 +/- 0.4 13.0 +/- 0.7 16.7 +/- 0.6 19.3 +/- 0.7 22.2 +/- 0.5 13.8 +/- 0.9 9.6 +/- 0.4 12.0 +/- 0.4 12.6 +/- 0.4 17.1 +/- 1.1 20.2 +/- 1.6 18.6 +/- 0.5 18.5 +/- 0.5 18.9 +/- 0.9 15.4 +/- 0.6 12.3 +/- 1.0 12.4 +/- 0.6 19.2 +/- 0.5 22.0 +/- 0.7 20.7 +/- 0.7 19.1 +/- 0.9 19.0 +/- 0.5 19.0 +/- 1.1 15.2 +/- 0.6 17.8 +/- 1.0 16.6 +/- 0.4 13.0 +/- 0.5 19.9 +/- 0.9 15.7 +/- 0.5 a ND = No Data, TLD lost in the field.

13-1

TOLEDO Table 13. Area monitors (TLD), Quarterly.

Units: mR/91 days 1st Qtr.

2nd Qtr.

3rd Qtr.

4th Qtr.

Indicator T-93 14.6 +/- 0.6 13.9 +/- 0.6 16.3 +/- 0.5 16.0 +/- 0.7 T-94 17.1 +/- 1.0 15.5 +/- 0.9 18.4 +/- 0.8 17.6 +/- 1.0 T-1i12 13.9 +/-0.4 12.9 +/-0.5 15.6 +/-0.4 15.0 +/-0.7 T-121 17.3 +/- 1.1 17.4 +/- 0.8 20.1 +/- 1.5 19.9 +/- 0.8 T-122 14.7 +/- 1.1 14.0 +/- 0.6 16.5 +/- 1.4 16.3 +/- 0.6 T-123 16.3 +/- 0.8 16.4 +/- 0.4 18.4 +/- 1.1 18.0 +/- 0.6 T-125 15.3 +/- 0.9 15.3 + 0.4 17.5 +/- 1.1 16.8 +/- 0.5 T-126 15.5 +/- 0.5 14.7 +/- 0.7 17.6 +/- 0.6 16.0 +/- 0.6 T-127 18.0 +/- 0.5 17.8 +/- 0.8 20.5 +/- 0.4 19.5 +/- 0.9 T-128 17.7 +/- 1.4 17.4 +/- 0.4 20.4 +/- 1.8 18.6 +/- 0.4 T-142 11.0 +/- 0.4 10.6 +/- 0.4 12.5 +/- 0.3 12.0 +/- 0.4 T-150 12.4 +/- 0.8 12.4 +/- 0.7 13.8 +/- 0.9 13.7 +/- 0.7 T-151 16.8 +/-0.6 17.0 +/-0.4 18.8 +/-0.8 18.6 +/-0.6 T-153 16.8 +/-0.4 15.2 +/-0.4 19.2 +/-0.4 16.4 +/-0.5 T-154 14.0 +/-0.8 13.7 +/-0.5 15.5 +/-0.7 15.1 +/-0.8 T-201 13.0 +/- 0.7 12.3 +/- 0.4 13.5 +/- 0.9 12.7 +/- 0.3 T-202 13.3 +/- 0.9 13.6 +/- 0.7 14.2 +/- 1.0 14.0 +/- 0.8 T-203 13.2 +/- 0.7 14.2 +/- 0.8 13.9 +/- 0.9 14.8 +/- 0.8 T-204 12.2 +/- 0.7 14.0 +/- 1.1 12.8 +/- 0.9 12.5 +/- 0.7 T-205 10.3 +/- 0.7 10.2 +/- 0.4 10.5 +/- 1.0 10.9 +/- 0.3 T-206 9.4 +/- 0.9 10.1 +/- 0.3 10.3 +/- 0.9 10.8 +/- 0.4 T-207 9.0 +/- 0.8 7.5 +/- 0.5 9.4 +/- 1.0 8.2 +/- 0.7 T-208 9.8 +/- 1.3 10.2 +/- 0.4 10.7 +/- 1.6 10.6 +/- 0.3 T-211 10.6 +/- 1.0 9.1 +/-0.4 11.8 +/-0.6 9.9 +/-0.3 T-212 9.8 +/-0.9 10.3 +/-0.5 11.1 +/-0.4 11.4 +/-0.6 T-213 17.1 +/- 1.0 15.7 +/- 0.4 18.3 +/- 0.6 16.7 +/- 0.5 T-214 17.0 +/- 0.9 15.9 +/- 0.5 18.1 +/- 0.6 16.9 +/- 0.5 T-215 18.2 +/- 1.2 15.9 +/- 0.7 19.6 +/- 0.7 16.8 +/- 0.6 T-216 16.7 +/- 1.2 16.0 +/- 1.0 18.3 +/- 0.6 16.4 +/- 0.9 T-217 18.6 +/- 1.2 17.6 +/- 1.3 20.1 +/- 0.8 18.5 +/- 1.4 T-218 19.2 +/- 1.2 18.7 +/-0.8 20.6 +/-0.9 19.1 +/-0.8 T-219 15.0 +/- 1.1 15.9 +/- 0.5 16.0 +/- 0.9 16.0 +/- 1.2 T-220 18.3 +/- 1.4 18.4 +/- 1.4 19.8 +/- 0.9 19.8 +/- 1.5 T-222 11.6 +/- 0.9 11.0 +/- 0.5 12.4 +/- 0.7 12.3 +/- 0.6 T-223 12.2 +/- 1.0 13.2 +/- 0.5 13.3 +/- 0.5 14.6 +/- 0.5 T-224 16.1 +/- 0.9 14.1 +/- 0.6 16.9 +/- 0.5 14.5 +/- 0.5 Mean +/- s.d.

14.5 +/- 3.1 14.3 +/- 3.0 15.8 +/- 3.4 15.7 +/- 3.3 13-2

TOLEDO Table 13. Area monitors (TLD), Quarterly.

Units: mR/91 days 1 st Qtr.

Control T-9 T-1 1 T-1 2 T-24 T-27 12.8 +/- 0.7 12.7 +/- 0.7 18.7 +/- 0.8 17.2 +/- 0.9 18.3 +/- 1.0 2nd Qtr.

12.4 +/- 0.7 12.0 +/- 0.5 18.5 +/- 0.6 17.2 +/- 0.5 18.8 +/- 0.6 3rd Qtr.

13.4 +/- 0.5 13.1 +/- 0.5 19.8 +/- 0.7 18.4 +/- 0.8 18.9 +/- 0.9 4th Qtr.

13.9 +/- 0.6 13.4 +/- 0.5 20.0 +/- 0.6 18.5 +/- 0.3 19.9 +/- 0.5 Mean +/- s.d.

15.9 +/- 3.0 T-95 T-100 T-111 T-124 T-155 T-221 16.6 +/- 0.6 15.4 +/- 1.2 16.3 +/- 1.5 15.0 +/- 0.7 12.7 +/- 0.6 14.9 +/- 1.2 15.8 +/- 3.3 15.1 +/--0.3 15.5 +/- 0.8 16.5 +/- 0.5 13.6 +/- 1.2 12.4 +/- 0.6 16.2 +/- 1.0 14.9 +/- 1.6 16.7 +/- 3.2 18.5 +/- 0.7 17.6 +/- 1.6 18.8 +/- 1.9 17.0 +/- 0.8 ND a 16.3 +/- 0.8 17.6 +/- 1.0 17.1 +/- 3.2 17.4 +/- 0.4 17.4 +/- 0.8 19.0 +/- 0.6 15.5 +/- 1.3 13.8 +/- 0.7 17.3 +/- 1.1 16.7 +/- 1.8 Mean +/- s.d.

15.2 +/- 1.4 0C T-80 T-81 T-82 T-83 T-84 T-85 T-86 T-88 T-89 T-113 T-1 14 T-1 15 T-116 T-117.

T-118 T-119 T-120 T-200 9.6 +/- 0.5 16.7 +/- 0.7 9.7 +/- 0.4 9.7 +/- 0.4 10.7 +/- 0.7

.13.1 +/- 0.7 19.0 +/- 0.8 13.5 +/- 0.6 15.8 +/- 0.4 14.4 +/- 0.4 13.5 +/- 0.5 12.5 +/- 0.7 15.0 +/- 0.4 12.8 +/- 0.6 15.3 +/- 0.6 13.3 +/- 0.6 11.5 +/-_0.7 11.4 +/-_0.7 i

9.0 +/- 0.3 16.2 +/- 0.5 9.3 +/- 0.5 10.0 +/- 0.8 10.3 +/- 0.4 13.6 +/- 0.7 19.3 +/- 0.8 15.8 +/- 0.6 17.1 +/- 0.8 13.8 +/- 0.4 12.3 +/- 0.5 13.9 +/- 0.4 15.9 +/- 0.5 12.3 +/- 1.0 14.0 +/- 0.7 12.1 +/- 0.4 10.0 +/- 0.5 12.3 +/- 0.7 10.6 +/- 0.8 18.4 +/- 0.7 10.7 +/- 0.3 10.6 +/- 0.5 11.7 +/- 0.8 14.2 +/- 0.5 22.2 +/- 1.1 15.6 +/- 0.8 18.3 +/- 0.5 16.5 +/- 0.3 14.9 +/- 0.6 13.8 +/- 0.9 16.9 +/- 0.5 14.4 +/- 0.7 16.6 +/- 0.5 14.8 +/- 0.6 12.2 +/- 0.6 12.5 +/- 0.9 10.6 +/- 0.4 18.4 +/- 0.5 11.1 +/- 0.5 12.6 +/- 0.8 12.0 +/- 0.6 15.3 +/- 0.8 21.9 +/- 0.9 18.6 +/- 0.6 19.8 +/- 0.7 16.0 +/- 0.5.

14.1 +/- 0.6 14.9 +/- 0.4 18.2 +/- 0.7 13.8 +/- 1.0 15.7 +/- 0.6 13.9 +/- 0.5 11.8 +/- 0.5 12.7 +/- 0.7 Mean +/- s.d.

13.2 +/- 2.6 13.2 +/- 2.9 14.7 +/- 3.1 15.1 +/-3.2 Shield T-87 6.9 +/- 0.5 6.8 +/- 0.5 7.3 +/- 0.5 8.6 +/- 0.6 a ND = No Data, TLD lost in the field.

13-3

TOLEDO Table 14. Area monitors (TLD), Annual.

Units: mR/365 days Indicator 2006 T-1 39.5 +/- 2.0 T-2 44.1 +/- 1.5 T-3 47.8 +/- 2.9 T-4 44.4 +/- 1.5 T-5 53.8 +/- 1.6 T-6 42.1 +/- 1.5 T-7 71.0 +/- 3.1 T-8 90.1 +/- 6.5 T-10 59.4 +/- 1.5 T-38 47.5 +/- 1.4 T-39 49.0 +/- 1.3 T-40 61.7 +/- 2.6 T-41 49.4 +/- 1.7 T-42 50.1 +/- 1.7 T-43 62.6 +/- 2.3 T-44 75.2 +/- 2.5 T-45 78.4 +/- 2.3 T-46 46.9 +/- 2.0 T-47 40.6 +/- 1.5 T-48 49.7 +/- 1.8 T-49 53.9 +/- 2.1 T-50 54.3 +/- 2.2 T-51 68.4 +/- 2.7 T-52 68.9 +/- 2.1 T-53 64.1 +/- 3.1 T-54 71.1 +/- 2.2 T-55 57.3 +/- 2.3 T-60 40.7 +/- 1.6 T-62 38.7 +/- 1.2 T-65 66.3 +/- 4.4 T-66 72.5 +/- 4.2 T-67 70.4 +/- 2.1 T-68 63.0 +/- 1.3 T-69 63.6 +/- 1.5 T-71 58.2 +/- 1.6 T-73 49.8 +/- 1.4 T-74 54.9 +/- 2.3 T-75 55.2 +/- 1.6 T-76 42.5 +/- 1.5 T-91 67.5 +/- 5.4 T-92 38.6 +/- 2.3 a "ND" = No data; TLD missing in field.

14-1

TOLEDO Table 14. Area monitors (TLD), Annual.

Units: mR/365 days Indicator 2006 T-93 T-94 T-1 12 T-121 T-122 T-1 23 T-125 T-126 T-127 T-128 T-1 42 T-150 T-151 T-153 T-154 T-201 T-202 T-203 T-204 T-205 T-206 T-207 T-208 T-211 Tý-212 T-213 T-214 T-215 T-216 T-217 T-218 T-219 T,220 T-222 T-223 T-224 50.0 +/- 1.1 60.1 +/- 1.3 53.6 +/- 4.5 66.6 +/- 2.8 51.9 +/- 1.5 66.9 +/- 2.4 69.6 +/- 2.9 57.1 +/- 3.0 79.7 +/- 3.4 74.7 +/- 2.3 43.9 +/- 1.2 52.1 +/-1.6 74.3 +/- 4.4 74.9 +/- 3.3 58.9 +/- 2.5 49.8 +/- 4.0 52.0 +/- 3.1 53.7 +/- 4.4 49.3 +/- 3.9 NDa 39.5 +/- 3.5 35.7 +/- 3.2 43.0 +/- 3.6 42.6 +/- 2.9 40.7 +/- 1.1 70.0 +/- 4.1 66.1 +/- 4.5 70.7 +/- 1.9 65.0 +/- 2.4 73.4 +/- 1.3 70.9 +/- 2.2 61.7 +/- 2.7 70.6 +/- 2.8 51.2 +/- 1.5 49.5 +/- 2.0 68.1 +/- 2.3 Mean +/- s.d.

57.6 +/- 12.2 a "ND" No data; TLD missing in field.

14-2

TOLEDO Table 14. Area monitors (TLD), Annuai.

Units: mRI365 days Control T-9 T-11 T-1 2 T-24 T-27 Mean +/- s.d.

T-95 T-100 T-111 T-124 T-155 T-221 Mean +/- s.d.

QC 2006 49.2 +/- 1.8 52.0 +/- 4.0 75.9 +/- 1.9 76.2 +/- 1.7 81.2 +/- 1.9 66.9 +/- 15.1 60.5 +/- 1.6 58.8 +/- 4.1 64.6 +/- 2.0 54.7 +/- 1.8 NDa 63.0 +/- 2.7 60.3 +/- 3.9 39.0 +/- 2.1 65.9 +/- 2.1 37.9 +/- 2.9 38.5 +/- 1.8 40.1 +/- 2.4 48.6 +/- 1.1 75.8 +/- 2.9 51.6 +/- 1.6 58.8 +/- 1.6 55.8 +/- 1.1 49.6 +/- 1.4 54.6 +/- 3.2 59.5 +/- 1.8 46.7 +/- 1.3 56.3 +/- 1.9 49.7 +/- 2.5 39.8 +/- 1.5 49.0 +/- 4.0 51.0 +/- 10.2 T-80 T-81 T-82 T-83 T-84 T-85 T-86 T-88 T-89 T-113 T-1 14 T-1 15 T-116 T-117 T-1 18 T-1 19 T-120 T-200 Mean +/- s.d.

Shield T-87 25.4 +/- 1.4 3N"= No data; TLD missing in field.

14-3

Table 15. Milk, analyses for strontium-89, strontium-90, iodine-131, gamma emitting isotopes, calcium and stable potassium.

Monthly collections, location T-24 Units: pCi/L Date Collected Lab Code 1-131 Sr-89 Sr-90 K-40 Cs-134 Cs-1 37 Ba-La-140 Ca (g/L)

Sr-90/g Ca K (g/L)

Cs-137/g K Date Collected Lab Code 1-131 Sr-89 Sr-90 K-40 Cs-134 Cs-137 Ba-La-1 40 Ca (g/L)

Sr-90/g Ca K (g/L)

Cs-137/g K 02-01-06 TMI-517

< 0.2

< 0.6 1.0 +/- 0.4 1257 +/- 117

< 3.8

< 2.5

< 1.4 1.09 0.92 1.45 +/- 0.14

< 1.72 05-31-06 TMI-3584

< 0.3

< 0.6 0.8 +/- 0.3 1328 +/- 118

< 4.2

< 2.6

< 1.8 1.16 0.69 1.54 +/- 0.14

< 1.69 09-27-06 TM 1-6617

< 0.4

< 0.6 0.6 +/- 0.3 1398 +/- 117

< 3.5

< 4.8

< 2.0 1.26 0.48 1.62 +/- 0.14

< 2.97 03-01-06 TMI-1078, 9

< 0.4

< 0.4 1.4 +/- 0.4 1265 +/- 166

< 5.2

< 6.5

< 3.5 0.75 1.87 1.46 +/- 0.19

< 4.45 06-28-06 TMI-4307

< 0.2

< 0.7

< 0.6 1405 +/- 107

< 2.7

< 2.3

< 2.8 1.16

< 0.52 1.62 +/- 0.12

< 1.42 11-01-06 TMI-8070

< 0.4

< 0.8

< 0.5 1251 +/- 168

<3.1

< 4.0

< 7.8 1.22

< 0.41 1.45 +/- 0.19

< 2.77 03-29-06 TM1-1760, 1

< 0.4

< 0.5 0.8 +/- 0.4 1325 +/- 72

< 2.6

<2.1

< 2.9 1.15 0.70 1.53 +/- 0.08

< 1.37 07-26-06 TMI-5123

< 0.3

< 0.7 0.8 +/- 0.3 1301 +/- 117

< 3.6

< 4.9

< 1.5 1.09 0.73 1.50 +/- 0.14

< 3.26 11-29-06 TMI-8572

< 0.2

< 0.8 0.9 +/- 0.4 1229 +/- 146

<4.1

< 4.9

< 2.5 0.85 1.06 1.42 +/- 0.17

< 3.45 04-26-06 TMI-2852

< 0.3

< 0.5 1.0 +/- 0.3 1321 +/- 44

< 1.6

<2.1

< 1.1 1.14 0.88 1.53 +/- 0.05

< 1.38 08-30-06 TMI-5963

< 0.4

< 0.5 1.0 +/- 0.3 1304 +/- 132

< 3.6

< 5.9

< 2.7 1.31 0.76 1.51 +/- 0.15

< 3.91 12-27-06 TMI-9397

< 0.4

< 0.6 0.6 +/- 0.3 1414 +/- 108

< 3.3

< 3.6

< 3.2 1.51 0.40 1.63 +/- 0.12

< 2.20 Date Collected Lab Code 1-131 Sr-89 Sr-90 K-40 Cs-134 Cs-137 Ba-La-140 Ca (g/L)

Sr-90/g Ca K (g/L)

Cs-137/g K 15-1

Table 16. Ground water samples, analyses for gross beta, tritium, strontium-89, strontium-90 and gamma-emitting isotopes.

Collection: Quarterly Units: pCi/L Period 1st Qtr.

2nd Qtr.

3rd Qtr.

4th Qtr.

Location T-27 (C)

Lab Code TWW-600 TWW-3453 TWW-5245 TWW-8186 Req. LLD Date Collected 01-30-06 05-24-06 07-12-06 10-05-06 Gross beta

< 2.2

< 2.2 2.0 +/- 1.2 4.1 +/- 1.4 4.0 H-3

< 330

< 330

< 330

< 330 330 Sr-89

< 0.6

< 0.7

< 0.7

< 0.9 Sr-90

< 0.5

< 0.5

< 0.5

< 0.5 Mn-54

< 3.1

< 3.9

< 3.7

< 2.2 15 Fe-59

< 7.4

< 2.4

< 7.9

< 6.2 30 Co-58

< 2.7

< 3.1

< 5.4

< 2.3 15 Co-60

< 2.2

< 2.3

< 3.3

< 2.5 15 Zn-65

< 3.9

< 4.6

< 10.4

< 4.1 30 Zr-Nb-95

< 3.4

< 3.2

< 7.9

< 4.1 15 Cs-134

< 3.7

< 2.8

< 5.5

< 2.0 15 Cs-137

< 2.7

< 3.4

< 3.7

< 2.7 18 Ba-La-140

< 6.4

< 1.8

< 11.6

< 11.1 15 Location T-226 (I)

Lab Code TWW-602 TWW-3455 TWW-5247 TWW-8188 Req. LLD Date Collected 01-30-06 05-24-06 07-14-06 10-05-06 Gross beta 2.5 +/- 1.1

< 1.9

< 1.6 2.5 +/- 1.2 4.0 H-3

< 330

< 330

< 330

< 330 330 Sr-89

< 0.5

< 0.7

< 0.7

< 0.8 Sr-90

< 0.5

< 0.5

< 0.4

< 0.5 Mn-54

< 2.4

< 4.8

< 2.0

< 2.3 15 Fe-59

< 3.5

< 4.6

< 3.9

< 6.8 30 Co-58

< 3.1

< 4.1

< 8.1

< 2.4 15 Co-60

< 3.1

< 4.7

< 1.2

< 2.1 15 Zn-65

< 5.0

< 6.2

< 4.5

< 3.5 30 Zr-Nb-95

< 3.7

< 5.3

< 4.4

< 4.2 15 Cs-134

< 3.3

< 4.4

< 2.3

< 2.1 15 Cs-137

< 3.8

< 7.0

< 2.6

< 2.3 18 Ba-La-140

< 1.6

< 3.1

< 6.9

< 14.5 15 16-1

Table 16. Ground water samples, analyses for gross beta, tritium, strontium-89, strontium-90 and gamma-emitting isotopes.

Collection: Quarterly Units: pCi/L Period 1st Qtr.

2nd Qtr.

3rd Qtr.

4th Qtr.

Location T-141 (QC)

Lab Code TWW-601 TWW-3454 TWW-5246 TWW-8187 Req. LLD Date Collected 01-30-06 05-24-06 07-14-06 10-05-06 Gross beta 2.1 +/- 1.0

< 2.0 2.8 +/- 1.1 3.7 +/- 1.3 4.0 H-3

< 330

< 330

< 330

< 330 330 Sr-89

< 0.7

< 0.8

< 0.7

< 1.0 Sr-90

< 0.5

< 0.4

< 0.5

< 0.5 Mn-54

< 3.3

< 3.5

< 2.6

< 2.3 15 Fe-59

< 6.8

< 3.4

< 4.2

< 5.5 30 Co-58

< 2.1

< 2.5

< 4.2

< 1.6 15 Co-60

< 2.5

< 2.7

< 3.5

< 2.0 15 Zn-65

< 2.9

< 3.7

< 3.6

< 4.5 30 Zr-Nb-95

< 3.2

< 2.8

< 5.3

< 5.0 15 Cs-134

< 3.3

< 3.3

< 4.0

< 2.5 15 Cs-137

< 3.4

< 3.2

< 4.8

< 2.2 18 Ba-La-140

< 2.9

< 2.4

< 12.4

< 15.0 15 16-2

Table 18. Wild meat, analyses for gamma-emitting isotopes.

Collection: Annually Units:

pCi/g wet Location T-31(1)

T-210 (C)

Lab Code TWL-9398 TWL-9399 Date Collected 12/11/2006 12/13/2007 Sample Type Muskrat Muskrat Be-7

< 0.052

< 0.11 K-40 2.28 +/- 0.16 2.69 +/- 0.17 Nb-95

< 0.013

< 0.016 Zr-95

< 0.014

< 0.018 Ru-103

< 0.007

< 0.015 Ru-106

< 0.054

< 0.061 Cs-134

< 0.005

< 0.006 Cs-137

< 0.004

< 0.005 Ce-141

< 0.026

< 0.019 Ce-144

< 0.046

< 0.069 18-1

Table 19. Green leafy vegetables, analyses for strontium-89, strontium-90, iodine-131 and other gamma-emitting isotopes.

Collection:

Monthly, in season Units: pCi/g wet Location Lab Code Date Collected Sample Type Sr-89 Sr-90 1-131 K-40 Nb-95 Zr-95 Cs-134 Cs-137 Ce-141 Ce-144 T-227 (I)

TVE-5966 8/28/2006 Cabbage

< 0.003

< 0.001

< 0.023 2.17 +/- 0.34

< 0.021

< 0.036

< 0.011

< 0.012

< 0.024

< 0.14 TVE-6622 9/27/2006 Cabbage

< 0.003

< 0.002

< 0.008 2.06 +/- 0.18

< 0.007

< 0.009

< 0.004

< 0.006

< 0.010

< 0.05 Location Lab Code Date Collected Sample Type Sr-89 Sr-90 1-131 K-40 Nb-95 Zr-95 Cs-134 Cs-1 37 Ce-141 Ce-144 T-19 (1)

TVE-5121 7/26/2006 Cabbage

< 0.003

< 0.001

< 0.009 2.00 t 0.24

< 0.009

< 0.019

< 0.006

< 0.011

< 0.015

< 0.067 TVE-5964 8/29/2006 Cabbage

< 0.004

< 0.002

< 0.025 1.91 +/- 0.29

< 0.008

< 0.023

< 0.008

< 0.008

< 0.024

< 0.076 TVE-6620 9/27/2006 Cabbage

< 0.002 0.002 +/- 0.001

< 0.013 1.96 +/- 0.25

< 0.010

< 0.017

< 0.007

< 0.007

< 0.018

< 0.076 TVE-8072 10/31/2006 Cabbage

< 0.003

< 0.001

< 0.015 2.12 +/- 0.19

< 0.005

< 0.016

< 0.008

< 0.007

< 0.017

< 0.067 Location Lab Code Date Collected Sample Type Sr-89 Sr-90 1-131 K-40 Nb-95 Zr-95 Cs-134 Cs-1 37 Ce-141 Ce-144 T-37 (C)

TVE-5122 7/26/2006 Cabbage

< 0.003

< 0.001

< 0.016 1.71 +/- 0.27

< 0.009

< 0.017

< 0.009

< 0.008

< 0.021

< 0.059 TVE-5965 8/29/2006 Cabbage

< 0.002 0.001 +/- 0.001

< 0.016 1.85 +/- 0.31

< 0.013

< 0.023

< 0.009

< 0.011

< 0.018

< 0.074 TVE-6621 9/26/2006 Cabbage

< 0.002

< 0.001

< 0.016 1.75 +/- 0.25

< 0.007

< 0.023

< 0.008

< 0.008

< 0.024

< 0.081 19-1

Table 20. Fruit, analyses for strontium-89, strontium-90, iodine-131 and other gamma-emitting isotopes.

Collection: Monthly, in season Units: pCi/g wet Location T-8 (I)

T-25 (I)

Lab Code TVE-6441 TVE-6368 Date Collected 9/13/2006 9/13/2006 Sample Type Apples Apples Sr-89

< 0.004

< 0.002 Sr-90

< 0.002

< 0.001 1-131

< 0.017

< 0.009 K-40 1.31 +/- 0.14 1.37 +/- 0.12 Nb-95

< 0.009

< 0.006 Zr-95

< 0.014

< 0.011 Cs-1 34

< 0.004

< 0.005 Cs-1 37

< 0.006

< 0.004 Ce-141

< 0.017

< 0.009 Ce-144

< 0.058

< 0.037 Location T-209 (C)

Lab Code TVE-6442 Date Collected 9/13/2006 Sample Type Apples Sr-89

< 0.002 Sr-90 0.003 +/- 0.001 1-131

< 0.033 K-40 0.95 +/- 0.21 Nb-95

< 0.011 Zr-95

< 0.016 Cs-1 34

< 0.007 Cs-1 37

< 0.009 Ce-141

< 0.029 Ce-144

< 0.091 20-1

Table 21. Animal - wildlife feed, analyses for gamma-emitting isotopes.

Collection:

Monthly, in season Units:

pCi/g wet Indicators Location Lab Code Date Collected Sample Type T-31 TCF-6366 9/14/2006 Cattails T-198 TCF-6440 9/13/2006 Cattails Be-7 K-40 Nb-95 Zr-95 Ru-103 Ru-1 06 Cs-134 Cs-137 Ce-141 Ce-144 0.30 +/- 0.17 2.74 +/- 0.27

< 0.017

< 0.029

< 0.024

< 0.088

< 0.007

< 0.007

< 0.047

< 0.072

< 0.27 1.55 +/- 0.26

< 0.014

< 0.038

< 0.030

< 0.13

< 0.011

< 0.015

< 0.078

< 0.13 Control Location Lab Code Date Collected Sample Type Be-7 K-40 Nb-95 Zr-95 Ru-103 Ru-106 Cs-1 34 Cs-137 Ce-141 Ce-144 T-32 TCF-6367 9/14/2006 Cattails

< 0.25 1.48 +/- 0.27

< 0.033

< 0.033

< 0.024

< 0.12

< 0.017

< 0.013

< 0.056

< 0.094 21-1

Table 22. Soil samples, analyses for gamma-emitting isotopes.

Collection: Annual Units: pCi/g dry Location Lab Code Date Collected T-1 TSO-3108 4/5/2006 T-2 TSO-3109 4/5/2006 T-3 TSO-31 10 4/5/2006 T-4 TSO-3111 4/5/2006 Be-7 K-40 Mn-54 Nb-95 Zr-95 Ru-1 03 Ru-106 Cs-1 34 Cs-1 37 Ce-141 Ce-1 44 11.20 +

0.13+/-

0.38 0.88 0.029 0.040 0.056 0.044 0.27 0.042 0.039 0.12 0.20

< 0.55 6.17 +/- 0.76

< 0.030

< 0.079

< 0.073

< 0.042

< 0.30

< 0.038 0.076 +/- 0.035

< 0.099

< 0.17

< 0.48 9.20 +/- 0.92

< 0.045

< 0.090

< 0.080

< 0.059

< 0.33

< 0.045

< 0.031

< 0.11

< 0.21 1.09 +/- 0.58 17.34 +/- 1.28

< 0.057

< 0.11

< 0.13

< 0.086

< 0.23

< 0.063 0.13 +/- 0.051

< 0.14

< 0.32 Location Lab Code Date Collected Be-7 K-40 Mn-54 Nb-95 Zr-95 Ru-1 03 Ru-106 Cs-i 34 Cs-1 37 Ce-141 Ce-144 T-7 TSO-3112 4/5/2006 T-8 TSO-3113 4/5/2006 10.91 _

0.34 0.95 0.034 0.059 0.068 0.024 0.25 0.027 0.014 0.078 0.17

< 0.53 25.26 +/- 1.40

< 0.062

< 0.092

< 0.13

< 0.10

< 0.30

< 0.071 0.19 +/- 0.068

< 0.17

< 0.23 Location Lab Code Date Collected Be-7 K-40 Mn-54 Nb-95 Zr-95 Ru-103 Ru-1 06 Cs-134 Cs-1 37 Ce-141 Ce-144 T-9 TSO-3114 4/5/2006

< 0.46 14.64 +/- 1.18

< 0.024

< 0.096

< 0.060

< 0.041

< 0.37

< 0.046

< 0.096

< 0.094

< 0.14 T-11 TSO-3115 4/5/2006

< 0.44 10.53 +/- 0.90

< 0.035

< 0.053

< 0.098

< 0.039

< 0.29

< 0.045

< 0.031

<0.11

< 0.20 T-12 TSO-3116 4/5/2006

< 0.39 19.32 +/- 0.85

< 0.027

< 0.073

< 0.048

< 0.043

< 0.24

< 0.041 0.22 +/- 0.038

< 0.10

< 0.11 T-27 TSO-3117 4/5/2006

< 0.67 22.45 +/- 1.48

< 0.054

< 0.077

< 0.12

< 0.089

< 0.41

< 0.072 0.21 +/- 0.051

< 0.15

< 0.29 22-1

Table 23. Treated surface water samples, analyses for gross beta.

Collection: Monthly composites of weekly grab samples Units: pCi/L Location T-11 (C)

Mean+/- s.d.

Lab Code TSWT-573 TSWT-1091 TSWT-2000 1st Quarter Date Collected 01-31-06 02-28-06 03-28-06 Gross beta 2.2 +/- 0.6 2.6 +/- 0.4 1.4 +/- 0.4 2.1 +/- 0.6 Lab Code TSWT-2853 TSWT-3612 TSWT-4475 2nd Quarter Date Collected 04-25-06 05-30-06 06-27-06 Gross beta 2.3 +/- 0.6 1.5 +/- 0.4 1.9 +/- 0.4 1.9 +/- 0.4 Lab Code TSWT-5289 TSWT-6140 TSWT-6712 3rd Quarter Date Collected 07-25-06 08-29-06 09-26-06 Gross beta 2.5 +/- 0.6 1.7 + 0.4 1.1 +/- 0.3 1.8 +/- 0.7 Lab Code TSWT-8177 TSWT-8637 TSWT-9433 4th Quarter Date Collected 10-31-06 11-28-06 12-26-06 Gross beta 1.4 +/- 0.6 1.3 +/- 0.3 2.4 +/- 0.6 1.7 +/- 0.6 Location T-12 (C)

Mean+/- s.d.

Lab Code TSWT-574 TSWT-1092 TSWT-2001 1 st Quarter Date Collected 01-31-06 02-28-06 03-28-06 Gross beta 2.8 +/- 0.6 0.8 +/- 0.3 1.3 +/- 0.3 1.6 +/- 1.0 Lab Code TSWT-2854 TSWT-3613 TSWT-4476 2nd Quarter Date Collected 04-25-06 05-30-06 06-27-06 Gross beta 2.3 +/- 0.5 1.4 +/- 0.3 1.3 +/- 0.3 1.7 +/- 0.6 Lab Code TSWT-5290 TSWT-6141 TSWT-6713 3rd Quarter Date Collected 07-25-06 08-29-06 09-26-06 Gross beta 2.7 +/- 0.6 1.3 +/- 0.3 1.7 +/- 0.4 1.9 +/- 0.7 Lab Code TSWT-8178 TSWT-8638 TSWT-9434 4th Quarter Date Collected 10-31-06 11-28-06 12-26-06 Gross beta 2.2 +/- 0.5 1.4 +/- 0.3 3.1 +/- 0.6 2.2 +/- 0.9 23-1

Table 23. Treated surface water samples, analyses for gross beta.

Collection:

Monthly composites of weekly grab samples Units: pCi/L Location T-22 Mean+/- s.d.

Lab Code TSWT-575 TSWT-1093 TSWT-2002 1 st Quarter Date Collected 01-31-06 02-28-06 03-28-06 Gross beta 2.7 + 0.6 1.3 +/- 0.3 2.1 +/- 0.4 2.0 +/- 0.7 Lab Code TSWT-2855 TSWT-3614 TSWT-4477 2nd Quarter Date Collected 04-25-06 05-30-06 06-27-06 Gross beta 2.7 +/- 0.6 1.7 +/- 0.4 1.2 +/- 0.3 1.9 +/- 0.8 Lab Code TSWT-5291 TSWT-6142 TSWT-6714 3rd Quarter Date Collected 07-25-06 08-29-06 09-26-06 Gross beta 2.4 +/- 0.6 1.4 +/- 0.3 1.1 +/- 0.3 1.6 +/- 0.7 Lab Code TSWT-8179 TSWT-8639 TSWT-9435 4th Quarter Date Collected 10-31-06 11-28-06 12-26-06 Gross beta 1.7 +/- 0.6 2.7 +/- 0.4 4.3 +/- 0.7 2.9 +/- 1.3 Location T-50 Mean+/- s.d.

Lab Code TSWT-576 TSWT-1094 TSWT-2003 1st Quarter Date Collected 01-31-06 02-28-06 03-28-06 Gross beta 2.7 +/- 0.6 1.2 +/- 0.3 1.4 +/- 0.4 1.8 +/- 0.8 Lab Code TSWT-2856 TSWT-3615 TSWT-4478 2nd Quarter Date Collected 04-25-06 05-30-06 06-27-06 Gross beta 2.2 +/- 0.6 1.5 +/- 0.4 1.3 +/- 0.3 1.7 +/- 0.5 Lab Code TSWT-5292 TSWT-6143 TSWT-6715 3rd Quarter Date Collected 07-25-06 08-29-06 09-26-06 Gross beta 1.7 +/- 0.6 1.6 +/- 0.4 1.3 +/- 0.3 1.5 +/- 0.2 Lab Code TSWT-8180 TSWT-8640 TSWT-9436, 7 4th Quarter Date Collected 10-31-06 11-28-06 12-26-06 Gross beta 1.8 +/- 0.6 1.4 +/- 0.4 2.3 +/- 0.4 1.8 +/- 0.5 23-2

Table 23. Treated surface water samples, analyses for gross beta.

Collection:

Monthly composites of weekly grab samples Units: pCi/L Location T-143 (QC)

Mean+/- s.d.

Lab Code TSWT-577, 8 TSWT-1095 TSWT-2004 1st Quarter Date Collected 01-31-06 02-28-06 03-28-06 Gross beta 3.4 +/- 0.5 1.1 +/- 0.3 1.8 +/- 0.4 2.1 +/- 1.2 Lab Code TSWT-2857 TSWT-3616 TSWT-4479 2nd Quarter Date Collected 04-25-06 05-30-06 06-27-06 Gross beta 2.0 +/- 0.6 1.6 +/- 0.4 1.8 +/- 0.6 1.8 +/- 0.2 Lab Code TSWT-5293 TSWT-6144 TSWT-6716 3rd Quarter Date Collected 07-25-06 08-29-06 09-26-06 Gross beta 1.1 +/- 0.3 1.3 +/- 0.3 1.5 +/- 0.4 1.3 +/- 0.2 Lab Code TSWT-8181 TSWT-8641, 2 TSWT-9438 4th Quarter Date Collected 10-31-06 11-28-06 12-26-06 Gross beta 2.1 +/- 0.6 2.9 +/- 0.3 3.0 +/- 0.6 2.7 +/- 0.5 23-3

Table 24.

Treated surface water samples, analyses for tritium, strontium-89, strontium-90 and gamma-emitting isotopes.

Collection: Quarterly composites of weekly grab samples Units: pCi/L Location Period Lab Code H-3 Sr-89 Sr-90 Mn-54 Fe-59 Co-58 Co-60 Zn-65 Zr-Nb-95 Cs-134 Cs-1 37 Ba-La-140 T-11 (C) 1 st Qtr.

TSWT-2005

< 330

< 0.7

< 0.5

< 2.7

< 5.7

< 3.2

< 5.1

< 3.4

< 4.3

<5.1

< 4.6

< 4.4 2nd Qtr.

TSWT-4975

< 330

< 1.4

< 0.5

< 3.4

< 6.9

< 5.4

< 2.9

< 3.8

< 7.4

< 3.4

< 4.9

< 15.0 3rd Qtr.

TSWT-7625

< 330

< 0.9

< 0.5

< 2.1

< 8.8

< 2.4

< 3.8

< 5.1

< 4.5

< 2.4

< 3.0

< 8.8 4th Qtr.

TSWT-9504

< 330

< 0.7

< 0.5

< 3.3

< 7.0

< 4.5

< 4.9

< 3.4

< 3.6

< 4.4

< 5.3

< 4.9 Rea. LLD 330 15 30 15 15 30 15 15 18 15 Location Period Lab Code T-12 (C)

H-3 Sr-89 Sr-90 Mn-54 Fe-59 Co-58 Co-60 Zn-65 Zr-Nb-95 Cs-134 Cs-i 37 Ba-La-140 1 st Qtr.

TSWT-2006

< 330

< 0.8

< 0.5

< 6.3

< 18.1

< 11.0

< 6.8

< 16.6

< 12.1

< 6.3

< 7.8

< 13.6 2nd Qtr.

TSWT-4976

< 330

< 1.0

< 0.6

< 6.1

< 12.7

< 4.6

< 3.0

< 6.6

< 7.2

< 5.4

< 2.8

< 13.7 3rd Qtr.

TSWT-7626

< 330

< 0.8

< 0.5

< 1.9

< 5.7

< 3.6

< 2.6

<8.1

< 3.6

< 3.0

< 3.2

< 6.6 4th Qtr.

TSWT-9505

< 330

< 0.8

< 0.5

< 2.6

< 9.8

< 4.8

< 5.1

< 5.1

< 6.1

< 5.0

< 5.2

< 9.3 Reg. LLD 330 15 30 15 15 30 15 15 18 15 24-1

Table 24.

Treated surface water samples, analyses for tritium, strontium-89, strontium-90 and gamma-emitting isotopes.

Collection: Quarterly composites of weekly grab samples.

Units: pCi/L Location Period Lab Code H-3 Sr-89 Sr-90 Mn-54 Fe-59 Co-58 Co-60 Zn-65 Zr-Nb-95 Cs-1 34 Cs-137 Ba-La-140 T-22 TSWT-2007

< 330

< 0.6

< 0.4

< 2.2

< 5.7

< 2.5

< 1.7

< 4.0

< 3.5

< 1.4

< 2.1

< 8.2 2nd Qtr.

TSWT-4977

< 330

< 1.0

< 0.6

< 4.2

< 7.5

< 3.7

< 2.8

< 2.3

< 8.0

< 2.8

<3.7

< 12.7 3rd Qtr.

TSWT-7627

< 330

< 1.0

< 0.6

< 1.9

< 6.2

< 3.0

< 2.2

< 3.1

< 3.6

< 2.1

< 1.8

< 6.6 4th Qtr.

TSWT-9506

< 330

< 0.7

< 0.5

< 3.1

< 8.7

< 4.4

< 5.7

< 4.0

< 6.6

< 3.5

< 6.2

< 5.6 Req. LLD 330 15 30 15 15 30 15 15 18 15 Location Period Lab Code T-50 H-3 Sr-89 Sr-90 Mn-54 Fe-59 Co-58 Co-60 Zn-65 Zr-Nb-95 Cs-134 Cs-1 37 Ba-La-140 1 st Qtr.

TSWT-2008

< 330

< 0.7

< 0.4

< 4.2

< 4.6

< 2.8

< 4.2

< 3.6

< 5.4

< 4.4

< 4.2

< 5.3 2nd Qtr.

TSWT-4978

< 330

< 1.0

< 0.6

< 4.6

< 18.6

< 2.0

< 5.0

< 11.3

< 6.7

< 4.7

< 3.4

< 10.7 3rd Qtr.

TSWT-7628

< 330

< 0.8

< 0.5

< 3.0

< 10.4

< 4.8

< 3.9

< 5.7

< 6.5

< 2.8

< 3.4

< 12.3 4th Qtr.

TSWT-9507

< 330

< 0.7

< 0.4

< 2.6

< 7.6

<4.3

< 3.0

< 5.8

< 6.4

< 3.4

< 3.8

< 7.8 Reg. LLD 330 15 30 15 15 30 15 15 18 15 24-2

Table 25. Untreated surface water, analyses for gross beta, tritium and gamma emitting isotopes.

Location: T-3 Collection:

Monthly composites of weekly grab samples Units: pCi/L Lab Code Date Collected Gross beta H-3 Mn-54 Fe-59 Co-58 Co-60 Zn-65 Zr-Nb-95 Cs-134 Cs-1 37 Ba-La-140 Lab Code Date Collected Gross beta H-3 Mn-54 Fe-59 Co-58 Co-60 Zn-65 Zr-Nb-95 Cs-134 Cs-1 37 Ba-La-140 Lab Code Date Collected Gross beta H-3 Mn-54 Fe-59 Co-58 Co-60 Zn-65 Zr-Nb-95 Cs-134 Cs-1 37 Ba-La-140 TSWU-591 1/31/2006 5.5 +/- 0.8

< 330

< 4.2

< 12.4

< 4.4

< 2.2

< 6.3

< 5.6

< 5.1

< 6.4

< 6.5 TSWU-3776 5/30/2006 3.1 +/- 0.5

< 330

< 2.8

< 6.4

< 3.1

< 5.9

< 8.1

< 5.0

< 4.8

< 4.7

< 6.1 TSWU-6717 9/26/2006 2.2 +/- 0.4

< 330

<2.1

< 4.6

< 3.2

< 1.8

< 4.0

< 4.3

< 3.0

< 3.2

< 3.8 TSWU-1096 2/28/2006 3.1 +/- 0.5

< 330

< 2.3

< 3.7

< 1.4

< 1.9

< 2.2

< 4.2

< 3.1

< 3.0

< 2.0 TSWU-4483 6/27/2006 2.3 +/- 0.4

< 330

< 1.8

< 2.8

< 2.2

< 2.2

< 3.6

< 3.2

< 2.3

< 2.8

< 3.1 TSWU-8189 10/31/2006 2.2 +/- 0.3

< 330

< 4.1

< 8.8

< 4.8

< 4.1

< 6.8

< 5.3

< 3.8

< 6.1

< 8.8 TSWU-2009 3/28/2006 2.9 +/- 0.5

< 330

< 4.0

< 7.8

< 4.0

<4.1

< 6.0

< 2.2

< 3.6

< 2.4

< 3.1 TSWU-5294 7/25/2006 2.6 +/- 0.4

< 330

< 4.8

< 6.6

< 3.4

< 4.8

< 5.9

< 3.9

< 4.5

< 3.7

< 3.8 TSWU-8643 11/28/2006 2.6 +/- 0.4

< 330

< 4.8

< 4.3

< 3.4

< 3.9

< 8.4

< 3.9

< 4.4

< 3.7

< 4.2 TSWU-2859 4/25/2006 2.5 +/- 0.4

< 330

< 2.5

< 2.0

< 2.3

< 2.3

< 3.3

< 1.9

< 1.6

< 1.7

< 3.6 TSWU-6145 8/29/2006 2.3 +/- 0.3

< 330

< 6.3

< 13.5

< 5.0

< 5.5

< 10.3

< 7.6

< 5.1

< 7.5

< 7.3 TSWU-9439 12/26/2006 3.4 +/- 0.7

< 330

< 3.7

< 9.0

< 4.1

< 4.2

< 7.9

< 5.0

< 4.3

< 5.9

< 11.7 Req. LLD 4.0 330 15 30 15 15 30 15 15 18 15 4.0 330 15 30 15 15 30 15 15 18 15 4.0 330 15 30 15 15 30 15 15 18 15 25-1

Table 25. Untreated surface water, analyses for gross beta, tritium and gamma emitting isotopes.

Location: T-1 1 (C)

Collection: Monthly composites of weekly grab samples Units: pCi/L Lab Code Date Collected Gross beta H-3 Mn-54 Fe-59 Co-58 Co-60 Zn-65 Zr-Nb-95 Cs-1 34 Cs-1 37 Ba-La-140 Lab Code Date Collected Gross beta H-3 Mn-54 Fe-59 Co-58 Co-60 Zn-65 Zr-Nb-95 Cs-134 Cs-137 Ba-La-140 Lab Code Date Collected Gross beta H-3 Mn-54 Fe-59 Co-58 Co-60 Zn-65 Zr-Nb-95 Cs-134 Cs-1 37 Ba-La-140 TSWU-593 1/31/2006 2.1 +/- 0.4

< 330

< 4.1

< 6.6

< 4.8

< 2.3

< 5.6

< 4.0

< 4.2

< 3.7

< 4.5 TSWU-3778 5/30/2006 2.5 +/- 0.4

< 330

< 5.1

< 7.9

< 4.0

< 4.2

!< 7.2

< 9.2

< 2.4

< 5.9

< 5.2 TSWU-6720 9/26/2006 1.3 +/- 0.3

< 330

< 2.0

< 2.0

< 1.7

< 1.6

< 4.2

< 3.7

< 2.3

< 2.4

< 2.8 TSWU-1 098 2/28/2006 2.2 +/- 0.4

< 330

< 4.1

< 3.9

< 4.3

< 3.1

< 8.0

< 3.9

< 2.0

< 3.7

< 7.0 TSWU-4485 6/27/2006 2.3 +/- 0.4

< 330

< 4.7

< 6.5

< 3.3

< 2.5

< 7.8

< 5.8

< 3.4

< 4.5

< 9.3 TSWU-8191 10/31/2006 1.4 +/- 0.3

< 330

< 6.7

< 5.1

< 3.8

< 5.3

< 4.0

< 5.6

< 5.9

< 5.5

< 11.5 TSWU-2011 3/28/2006 2.0 +/- 0.4

< 330

< 2.8

< 5.4

< 2.8

< 2.8

< 4.1

< 3.2

< 1.6

< 2.6

< 7.9 TSWU-5296 7/25/2006 1.6 +/- 0.4

< 330

< 3.1

< 8.2

< 2.7

< 3.6

< 6.1

< 5.0

< 3.9

< 3.0

< 3.9 TSWU-8645 11/28/2006 2.1 +/- 0.4

< 330

< 2.7

< 5.7

< 3.2

< 2.8

< 3.7

< 2.7

< 3.2

< 3.9

< 1.8 TSWU-2861 4/25/2006 2.5 +/- 0.4

< 330

< 1.1

< 2.0

< 1.0

< 0.8

< 1.6

< 1.3

< 0.9

< 1.0

< 2.1 TSWU-6147 8/29/2006 1.9 +/- 0.3

< 330

< 1.7

< 2.0

< 2.2

< 1.6

< 5.3

< 3.6

< 2.4

< 1.7

< 5.0 TSWU-9441 12/26/2006 3.3 +/- 0.7

< 330

< 2.5

< 6.7

  • 3.6

< 5.2

< 10.0

< 10.4

< 2.6

<4.1

< 7.7 Req. LLD 4.0 330 15 30 15 15 30 15 15 18 15 4.0 330 15 30 15 15 30 15 15 18 15 4.0 330 15 30 15 15 30 15 15 18 15 25-2

Table 25. Untreated surface water, analyses for gross beta, tritium and gamma emitting isotopes.

Location: T-12 (C)

Collection: Monthly composites of weekly grab samples Units: pCi/L Lab Code Date Collected Gross beta H-3 Mn-54 Fe-59 Co-58 Co-60 Zn-65 Zr-Nb-95 Cs-i 34 Cs-137 Ba-La-140 Lab Code Date Collected Gross beta H-3 Mn-54 Fe-59 Co-58 Co-60 Zn-65 Zr-Nb-95 Cs-1 34 Cs-137 Ba-La-140 Lab Code Date Collected Gross beta H-3 Mn-54 Fe-59 Co-58 Co-60 Zn-65 Zr-Nb-95 Cs-1 34 Cs-137 Ba-La-140 TSWU-594 1/31/2006 4.3 +/- 0.5

< 330

< 2.7

< 10.4

< 2.9

< 3.5

<4.7

< 7.0

< 3.8

< 5.2

< 6.9 TSWU-3779 5/30/2006 2.4 +/- 0.4

< 330

< 4.0

< 8.0

< 3.0

< 2.8

< 6.1

< 4.3

< 2.8

< 3.8

< 3.2 TSWU-6721 9/26/2006 1.5 +/- 0.4

< 330

< 2.4

< 3.4

< 5.8

< 1.9

< 3.4

< 5.2

< 3.9

< 4.6

< 7.0 TSWU-1099 2/28/2006 1.5 +/- 0.4

< 330

< 4.3

< 13.7

< 7.7

< 5.1

< 8.7

< 4.0

< 5.7

< 4.3

< 5.7 TSWU-4486 6/27/2006 1.9 +/- 0.4

< 330

< 2.3

< 4.0

< 2.2

< 1.7

< 1.7

< 1.6

< 1.9

< 2.7

< 2.8 TSWU-8192 10/31/2006 1.7 +/- 0.3

< 330

< 4.1

< 10.9

< 4.3

< 5.9

< 10.8

< 6.8

< 4.1

< 4.9

< 8.4 TSWU-2012 3/28/2006 1.7 +/- 0.4

< 330

< 5.5

< 5.9

< 5.4

< 3.5

< 4.7

< 4.4

< 5.8

< 5.3

< 4.7 TSWU-5297 7/25/2006 2.9 +/- 0.6

< 330

< 1.2

<4.1

< 2.0

< 1.4

< 4.7

< 2.4

< 3.3

< 4.0

< 5.7 TSWU-8646 11/28/2006 1.8 +/- 0.4

< 330

< 3.4

< 3.1

< 2.2

< 2.0

< 3.3

< 3.7

< 3.0

< 3.4

< 4.4 TSWU-2862 4/25/2006 1.7 +/- 0.4

< 330

  • 2.6

< 5.5

< 1.7

< 1.7

< 1.6

< 2.2

< 2.4

< 3.2

< 2.5 TSWU-6148 8/29/2006 1.9 +/- 0.3

< 330

< 2.9

< 5.2

< 2.4

< 2.5

< 3.4

< 4.0

< 3.0

< 2.8

< 5.6 TSWU-9442 12/26/2006 3.7 +/- 0.7

< 330

< 1.7

< 8.4

< 3.1

< 2.7

< 3.1

< 4.0

< 2.9

< 3.9

< 3.4 Req. LLD 4.0 330 15 30 15 15 30 15 15 18 15 4.0 330 15 30 15 15 30 15 15 18 15 4.0 330 15 30 15 15 30 15 15 18 15 25-3

Table 25. Untreated surface water, analyses for gross beta, tritium and gamma emitting isotopes.

Location: T-22 Collection:

Monthly composites of weekly grab samples Units: pCi/L Lab Code Date Collected Gross beta H-3 Mn-54 Fe-59 Co-58 Co-60 Zn-65 Zr-Nb-95 Cs-1 34 Cs-137 Ba-La-140 Lab Code Date Collected Gross beta H-3 Mn-54 Fe-59 Co-58 Co-60 Zn-65 Zr-Nb-95 Cs-1 34 Cs-137 Ba-La-140 Lab Code Date Collected Gross beta H-3 Mn-54 Fe-59 Co-58 Co-60 Zn-65 Zr-Nb-95 Cs-134 Cs-137 Ba-La-140 TSWU-596 1/31/2006 2.6 +/- 0.4

< 330

< 4.3

< 8.6

< 2.9

< 2.7

< 7.8

< 5.8

< 4.1

< 3.1

< 5.0 TSWU-3781 5/30/2006 2.1 +/- 0.4

< 330

< 2.8

< 7.1

< 2.6

< 1.9

< 2.3

< 3.8

< 2.6

< 2.3

< 2.9 TSWU-1101 2/28/2006 3.1 +/- 0.5

< 330

<5.1

< 6.4

< 4.0

< 4.6

< 5.4

< 4.4

< 6.8

< 5.2

< 3.5 TSWU-4488 6/27/2006 1.8 +/- 0.4

< 330

< 2.1

< 5.6

< 2.5

< 2.1

< 2.8

< 4.6

< 2.3

< 2.1

< 4.5 TSWU-2014 3/28/2006 2.3 +/- 0.4

< 330

< 5.7

< 10.9

< 3.5

< 4.5

< 8.5

< 4.0

< 4.6

< 5.8

< 5.5 TSWU-2865 4/25/2006 1.9 t 0.4

< 330

< 1.5

< 4.8

< 2.3

< 1.8

< 4.6

< 3.0

< 3.2

< 2.2

< 4.4 Req. LLD 4.0 330 15 30 15 15 30 15 15 18 15 TSWU-5299 TSWU-6150, 1 7/25/2006 8/29/2006 TSWU-6723 TSWU-8194, 5 9/26/2006 10/31/2006 2.8 +/- 0.6

< 330

< 2.5

< 6.2

< 2.5

< 2.1

< 2.8

< 4.6

< 3.9

< 3.7

< 5.1 TSWU-8648 11/28/2006 3.6 +/- 0.5

< 330

< 3.1

< 4.7

< 1.7

< 2.3

< 3.0

< 3.1

< 3.0

< 2.7

< 3.9 1.8 +/- 0.3

< 330

< 2.5

< 3.2

< 2.0

< 1.1

< 3.8

< 3.2

< 2.3

< 2.1

< 3.0 4.0 330 15 30 15 15 30 15 15 18 15 1.1 +/- 0.3

< 330

< 2.8

< 2.7

< 2.0

< 2.1

< 4.6

< 3.6

< 2.4

< 3.0

< 3.3 1.6 +/- 0.2

< 330

< 1.6

< 4.5

< 2.0

< 2.5

< 4.0

< 2.2

< 2.6

< 2.0

< 2.7 TSWU-9444 12/26/2006 5.1 +/- 0.7

< 330

< 2.7

< 8.4

< 5.8

< 4.4

< 10.9

< 6.3

< 4.8

< 3.9

< 10.7 4.0 330 15 30 15 15 30 15 15 18 15 25-4

Table 25. Untreated surface water, analyses for gross beta, tritium and gamma emitting isotopes.

Location: T-50 Collection:

Monthly composites of weekly grab samples Units: pCi/L Lab Code Date Collected Gross beta H-3 Mn-54 Fe-59 Co-58 Co-60 Zn-65 Zr-Nb-95 Cs-134 Cs-1 37 Ba-La-140 Lab Code Date Collected Gross beta H-3 Mn-54 Fe-59 Co-58 Co-60 Zn-65 Zr-Nb-95 Cs-1 34 Cs-137 Ba-La-140 Lab Code Date Collected Gross beta H-3 Mn-54 Fe-59 Co-58 Co-60 Zn-65 Zr-Nb-95 Cs-1 34 Cs-137 Ba-La-140 TSWU-597 1/31/2006 2.4 +/- 0.4

< 330

< 3.2

< 4.7

< 2.5

< 2.8

< 6.0

< 4.7

< 4.6

< 4.3

< 3.9 TSWU-3782 5/30/2006 1.7 +/- 0.4

< 330

< 4.3

< 6.0

< 4.6

< 3.2

< 6.6

< 5.8

< 5.2

< 4.8

< 5.3 TSWU-6724 9/26/2006 1.5 +/- 0.4

< 330

< 3.2

< 4.4

< 3.4

< 2.5

< 2.8

< 3.5

< 3.8

< 2.3

< 2.0 TSWU-1102, 3 2/28/2006 1.6 +/- 0.3

< 330

< 3.4

< 5.0

< 2.4

< 2.4

< 2.4

< 2.4

< 2.4

< 2.7

< 2.1 TSWU-4489, 90 6/27/2006 1.8 +/- 0.3

< 330

< 1.6

< 2.1

< 1.4

< 1.4

< 2.8

< 1.5

< 1.4

< 1.4

< 1.1 TSWU-2015 3/28/2006 1.6 +/- 0.4

< 330

< 2.6

< 4.6

< 2.7

< 2.6

< 2.9

<4.1

< 3.9

< 4.4

< 2.4 TSWU-5300 7/25/2006 2.4 +/- 0.6

< 330

< 3.7

< 4.8

< 3.3

< 3.6

< 5.8

< 4.7

< 3.4

< 3.9

< 2.2 TSWU-8649 11/28/2006 2.2 +/- 0.4

< 330

< 4.5

< 8.2

< 4.5

< 4.9

< 8.7

< 4.8

< 4.7

< 3.6

< 2.5 TSWU-2866 4/25/2006 1.8 +/- 0.4

< 330

< 3.3

< 4.5

< 1.5

< 1.9

< 5.2

< 4.3

< 2.8

< 3.2

< 3.6 TSWU-6152 8/29/2006 2.0 +/- 0.3

< 330

< 4.3

< 9.6

< 3.4

< 4.8

< 4.2

< 4.9

< 4.3

< 6.0

< 3.8 TSWU-9445 12/26/2006 1.9 +/- 0.4

< 330

< 3.0

< 9.5

< 3.8

< 5.7

< 6.1

< 6.2

< 2.8

< 3.5

< 6.4 Req. LLD 4.0 330 15 30 15 15 30 15 15 18 15 4.0 330 15 30 15 15 30 15 15 18 15 TSWU-8196 10/31/2006 1.6 +/- 0.3

< 330

< 4.1

< 3.8

< 7.6

< 6.1

< 5.2

< 4.7

< 4.3

< 5.7

< 13.1 4.0 330 15 30 15 15 30 15 15 18 15 25-5

Table 25. Untreated surface water, analyses for gross beta, tritium and gamma emitting isotopes.

Location: T-145 (QC)

Collection: Monthly composites of weekly grab samples Units: pCi/L Lab Code Date Collected Gross beta H-3 Mn-54 Fe-59 Co-58 Co-60 Zn-65 Zr-Nb-95 Cs-1 34 Cs-1 37 Ba-La-140 Lab Code Date Collected Gross beta H-3 Mn-54 Fe-59 Co-58 Co-60 Zn-65 Zr-Nb-95 Cs-i 34 Cs-1 37 Ba-La-140 Lab Code Date Collected Gross beta H-3 Mn-54 Fe-59 Co-58 Co-60 Zn-65 Zr-Nb-95 Cs-1 34 Cs-1 37 Ba-La-140 TSWU-598, 9 1/31/2006 2.0 +/- 0.3

< 330

< 1.8

< 4.9

< 2.3

< 2.8

< 3.2

< 3.8

< 3.5

< 2.7

< 4.2 TSWU-3783 5/30/2006 3.4 +/- 0.5

< 330

< 4.5

< 9.7

< 4.3

< 5.4

< 3.8

< 7.0

< 5.3

< 2.4

< 9.4 TSWU-6725 9/26/2006 2.1 +/- 0.4

< 330

< 4.4

< 6.5

< 2.4

< 2.1

< 3.4

< 3.4

< 2.9

< 3.8

< 2.2 TSWU-I 104 2/28/2006 4.7 +/- 0.8a

< 330

< 3.9

< 3.4

< 3.1

< 2.7

< 3.5

< 3.8

< 4.4

< 3.9

< 3.7 TSWU-4491 6/27/2006 1.9 +/- 0.4

< 330

< 2.9

< 5.3

< 1.2

< 2.1

< 4.0

< 4.3

< 2.4

< 3.3

< 2.7 TSWU-8197 10/31/2006 1.5 +/- 0.3

< 330

< 4.6

< 9.7

< 4.4

< 7.2

< 8.4

< 6.3

< 5.8

< 5.5

< 6.2 TSWU-2016 3/28/2006 2.3 t 0.4

< 330

< 4.7

< 10.2

< 3.3

< 4.5

< 10.6

< 5.9

< 4.9

< 6.3

< 5.6 TSWU-5301 7/25/2006.

1.8 +/- 0.4

< 330

< 5.4

< 10.0

<4.1

< 5.5

< 3.6

< 7.3

< 5.2

< 3.4

< 6.6 TSWU-8650 11/28/2006 3.2 +/- 0.7

< 330

< 2.3

< 9.7

< 2.5

< 4.5

< 7.2

< 5.2

< 4.0

< 3.4

< 3.5 TSWU-2867 4/25/2006 2.8 +/- 0.6

< 330

< 2.7

< 5.3

< 1.6

< 0.9

< 3.5

< 3.6

< 1.9

< 2.6

< 2.8 TSWU-6153 8/29/2006 2.4 +/- 0.4

< 330

< 5.5

< 4.3

< 2.8

< 4.7

< 4.8

< 3.9

< 3.4

< 5.2

< 4.7 TSWU-9446 12/26/2006 2.8 +/- 0.4

< 330

< 5.8

< 6.6

< 6.6

< 4.3

< 5.4

< 9.6

< 2.2

< 2.8

< 7.2 Req. LLD 4.0 330 15 30 15 15 30 15 15 18 15 4.0 330 15 30 15 15 30 15 15 18 15 4.0 330 15 30 15 15 30 15

.15 18 15 a Result of reanalysis.

25-6

Table 26. Untreated surface water samples, analyses for strontium-89 and strontium-90.

Collection: Quarterly composites of weekly grab samples Units:

pCi/L Location T-3 Period 1st Qtr.

2nd Qtr.

3rd Qtr.

4th Qtr.

Lab Code TSWU-2220 TSWU-4681 TSWU-7429 TSWU-9592 Sr-89

< 0.6

< 0.8

< 0.7

< 0.7 Sr-90

< 0.5

< 0.5

< 0.5

< 0.4 Location T-11 (C)

Period 1st Qtr.

2nd Qtr.

3rd Qtr.

4th Qtr.

Lab Code TSWU-2221 TSWU-4979 TSWU-7430 TSWU-9593 Sr-89

< 0.7

< 0.8

< 0.8

< 0.7 Sr-90

< 0.5

< 0.5

< 0.5

< 0.6 Location T-12 (C)

Period 1st Qtr.

2nd Qtr.

3rd Qtr.

4th Qtr.

Lab Code TSWU-2222 TSWU-4682 TSWU-7431 TSWU-9594 Sr-89

< 0.7

< 0.7

< 0.7

< 0.9 Sr-90

< 0.5

< 0.5

< 0.4

< 0.6 Location T-22 Period 1st Qtr.

2nd Qtr.

3rd Qtr.

4th Qtr.

Lab Code TSWU-2223 TSWU-4683 TSWU-7432 TSWU-9595 Sr-89

< 0.5

< 1.0

< 1.1

< 0.6 Sr-90

< 0.5

< 0.4

< 0.7

< 0.5 Location T-50 Period 1st Qtr.

2nd Qtr.

3rd Qtr.

4th Qtr.

Lab Code TSWU-2224 TSWU-4684 TSWU-7433 TSWU-9596 Sr-89

< 0.6

< 0.8

< 1.0

< 0.7 Sr-90

< 0.4 0.5 t 0.3

< 0.6

< 0.4 26-1

Table 28. Fish samples, analyses for gross beta and gamma-emitting isotopes.

Collection: Annually Units: pCi/g wet Location T-33 (Lake Erie, 1.5 mi. NE of Station)

Lab Code Date Collected Sample Type TF-3307 5/4/2006 Carp TF-3308 5/4/2006 White Bass / Perch TF-3309 4/26/2006 Walleye Gross Beta K-40 Mn-54 Fe-59 Co-58 Co-60 Zn-65 Cs-1 34 Cs-1 37 3.61 +/- 0.08 3.28 +/- 0.49

< 0.024

< 0.061

< 0.024

< 0.027

< 0.044

< 0.022

< 0.020 4.10 + 0.19 2.74 + 0.40

< 0.011

< 0.019

< 0.016

< 0.013

< 0.022

< 0.019

< 0.017 3.99 +/- 0.12 3.75 +/- 0.53

< 0.017

< 0.041

< 0.021

< 0.027

< 0.031

< 0.050

< 0.012 Location T-35 Lab Code Date Collected Sample Type TF-331 0 5/11/2006 Carp TF-3311, 12 2/9/2006 White Bass / Perch TF-3313 2/9/2006 Walleye Gross Beta K-40 Mn-54 Fe-59 Co-58 Co-60 Zn-65 Cs-134 Cs-137 3.39 +/- 0.08 2.99 +/- 0.38

< 0.016

< 0.027

< 0.012

< 0.016

< 0.018

< 0.013

< 0.013 3.97 +/- 0.10 2.72 +/- 0.27

< 0.023

<0.11

< 0.027

< 0.015

< 0.032

< 0.018

< 0.014 2.16 + 0.07 2.97 +/- 0.47

< 0.029

< 0.23

< 0.050

< 0.017

< 0.034

< 0.021

< 0.020 28-1

Table 29. Shoreline sediment samples, analyses for gamma-emitting isotopes.

Collection: Semiannually Units: pCi/g dry Location T-3 T-4 T-4P T-27B T-132 Lab Code TSS-4024 TSS-4025 TSS-4026 TSS-4027 TSS-4028 Date Collected 6/13/2006 6/13/2006 6/13/2006 6/13/2006 6/13/2006 K-40 8.95 +/- 0.66 10.57 +/- 0.89 14.44 +/- 0.97 9.31 +/- 0.69 12.93 +/- 0.84 Mn-54

< 0.009

< 0.013

< 0.021

< 0.026

< 0.013 Co-58

< 0.010

< 0.010

< 0.008

< 0.015

< 0.022 Co-60

< 0.009

< 0.015

< 0.018

< 0.014

< 0.019 Cs-1 34

< 0.010

< 0.026

< 0.029

< 0.020

< 0.020 Cs-1 37

< 0.012

< 0.019

< 0.019

< 0.023

< 0.020 Lab Code TSS-8667 TSS-8668 TSS-8669 TSS-8670 TSS-8671 Date Collected 11/2212006 11/22/2006 11/22/2006 11/22/2006 11/22/2006 K-40 11.89 +/- 0.59 12.56 +/- 0.81 22.02 +/- 1.07 10.13 +/- 0.54 6.73 +/- 0.59 Mn-54

< 0.012

< 0.021

< 0.037

< 0.018

< 0.020 Co-58

< 0.013

< 0.023

< 0.023

< 0.016

< 0.022 Co-60

< 0.014

< 0.019

< 0.016

< 0.011

< 0.013 Cs-1 34

< 0.011

< 0.034

< 0.020

< 0.018

< 0.027 Cs-137

< 0.012

< 0.019

< 0.032

< 0.013

< 0.019 29-1

Environmental, Inc.

Midwest Laboratory an Allegheny Technologies Co.

700 Landwehr Road - Northbrook, IL 60062-2310 ph. (847) 564-0700 - fax (847) 564-4517 APPENDIX A INTERLABORATORY COMPARISON PROGRAM RESULTS NOTE:

Environmental Inc., Midwest Laboratory participates in intercomparison studies administered by Environmental Resources Associates, and serves as a replacement for studies conducted previously by the U.S. EPA Environmental Monitoring Systems Laboratory, Las Vegas, Nevada. Results are reported in Appendix A. TLD Intercomparison results, in-house spikes, blanks, duplicates and mixed analyte performance evaluation program results are also reported. Appendix A is updated four times a year; the complete Appendix is included in March, June, September and December monthly progress reports only.

January, 2006 through December, 2006

Appendix A Interlaboratory Comparison Program Results Environmental, Inc., Midwest Laboratory has participated in interlaboratory comparison (crosscheck) programs since the formulation of it's quality control program in December 1971. These programs are operated by agencies which supply environmental type samples containing concentrations of radionuclides known to the issuing agency but not to participant laboratories. The purpose of such a program is to provide an independent check on a laboratory's analytical procedures and to alert it of any possible problems.

Participant laboratories measure the concentration of specified radionuclides and report them to the issuing agency. Several months later, the agency reports the known values to the participant laboratories and specifies control limits. Results consistently higher or lower than the known values or outside the control limits indicate a need to check the instruments or procedures used.

Results in Table A-1 were obtained through participation in the environmental sample crosscheck program administered by Environmental Resources Associates, serving as a replacement for studies conducted previously by the U.S. EPA Environmental Monitoring Systems Laboratory, Las Vegas, Nevada.

The results in Table A-2 list results for thermoluminescent dosimeters (TLDs), via International Intercomparison of Environmental Dosimeters, when available, and internal laboratory testing.

Table A-3 lists results of the analyses on in-house "spiked" samples for the past twelve months. All samples are prepared using NIST traceable sources. Data for previous years available upon request.

Table A-4 lists results of the analyses on in-house "blank" samples for the past twelve months. Data for previous years available upon request.

Table A-5 list results of the in-house "duplicate" program for the past twelve months. Acceptance is based on the difference of the results being less than the sum of the errors. Data for previous years available upon request.

The results in Table A-6 were obtained through participation in the Mixed Analyte Performance Evaluation Program.

Attachment A lists acceptance criteria for "spiked" samples.

Out-of-limit results are explained directly below the result.

Al

Attachment A ACCEPTANCE CRITERIA FOR "SPIKED" SAMPLES LABORATORY PRECISION: ONE STANDARD DEVIATION VALUES FOR VARIOUS ANALYSESa One standard deviation Analysis Level for single determination Gamma Emitters 5 to 100 pCi/liter or kg 5.0 pCi/liter

> 100 pCi/liter or kg 5% of known value Strontium-89b 5 to 50 pCi/liter or kg 5.0 pCi/liter

> 50 pCi/liter or kg 10% of known value Strontium-90b 2 to 30 pCi/liter or kg 5.0 pCi/liter

> 30 pCi/liter or kg 10% of known value Potassium-40

> 0.1 g/Iiter or kg 5% of known value Gross alpha

< 20 pCi/liter 5.0 pCi/liter

> 20 pCi/liter 25% of known value Gross beta

< 100 pCi/liter 5.0 pCi/liter

> 100 pCi/liter 5% of known value Tritium

< 4,000 pCi/liter lo = (pCi/liter) =

169.85 x (known)00 933

> 4,000 pCi/liter 10% of known value Radium-226,-228

> 0.1 pCi/liter 15% of known value Plutonium

> 0.1 pCi/liter, gram, or sample 10% of known value Iodine-131,

< 55 pCi/liter 6.0 pCi/liter Iodine-129b

> 55 pCi/liter 10% of known value Uranium-238,

< 35 pCi/liter 6.0 pCi/liter Nickel-63b

> 35 pCi/liter 15% of known value Technetium-99b Iron-55b 50 to 100 pCi/liter 10 pCi/liter

> 100 pCi/liter 10% of known value Othersb 20% of known value a From EPA publication, "Environmental Radioactivity Laboratory Intercomparison Studies Program, Fiscal Year, 1981-1982, EPA-600/4-81-004, b Laboratory limit.

A2

TABLE A-1. Interlaboratory Comparison Crosscheck program, Environmental Resource Associates (ERA)a.

Concentration (pCi/L)

Lab Code Date Analysis Laboratory ERA Control Resultb Resultc Limits Acceptance STW-1078 01/16/06 Sr-89 49.9 +/- 3.5 50.2 41.5 -58.9 Pass STW-1078 01/16/06 Sr-90 31.5 +/- 1.5 30.7 22.0 -39.4 Pass STW-1079 01/16/06 Ba-133 86.5 +/- 4.1 95.0 78.6 -111.0 Pass STW-1079 01/16/06 Co-60 96.3 +/- 4.1 95.3 86.6 - 104.0 Pass STW-1079 01/16/06 Cs-134 22.6 +/- 3.0 23.1 14.4 -31.8 Pass STW-1079 01/16/06 Cs-137 109.0 +/- 5.9 111.0 101.0 -121.0 Pass STW-1079 01/16/06 Zn-65 198.0 +/- 11.2 192.0 159.0 - 225.0 Pass STW-1080 01/16/06 Gr. Alpha 10.8 +/- 1.4 9.6 1.0 - 18.3 Pass STW-1080 01/16/06 Gr. Beta 56.9 +/- 1.9 61.9 44.6 -79.2 Pass STW-1081 01/16/06 Ra-226 4.3 +/- 0.4 4.6 3.4 - 5.8 Pass STW-1081 01/16/06 Ra-228 7.1 +/- 1.8 6.6 3.7 -9.5 Pass STW-1 081 01/16/06 Uranium 20.7 +/- 0.5 22.1 16.9 -27.3 Pass STW-1088 04/10/06 Sr-89 29.0 +/- 1.8 32.4 23.7 -41.1 Pass STW-1088 04/10/06 Sr-90 8.7 +/- 1.0 9.0 0.3 - 17.7 Pass STW-1089 04/10/06 Ba-133 10.3 +/- 0.4 10.0 1.3 - 18.7 Pass STW-1089 04/10/06 Co-60 114.0 +/- 2.8 113.0 103.0 - 123.0 Pass STW-1089 04/10/06 Cs-134 41.9 +/- 1.4 43.4 34.7 -52.1 Pass STW-1089 04/10/06 Cs-137 208.0 +/- 1.1 214.0 195.0 -233.0 Pass STW-1089 04/10/06 Zn-65 154.0 +/- 0.8 152.0 126.0 - 178.0 Pass STW-1090 04/10/06 Gr. Alpha 13.4 +/- 1.1 21.3 12.1 -30.5 Pass STW-1090 04/10/06 Gr. Beta 27.7 +/- 2.1 23.0 14.3 -31.7 Pass STW-1091 04/10/06 1-131 22.0 +/- 0.3 19.1 13.9 -24.3 Pass STW-1092 04/10/06 H-3 7960.0 +/- 57.0 8130.0 6720.0 - 9540.0 Pass STW-1092 04/10/06 Ra-226 2.9 +/- 0.4 3.0 2.2 - 3.8 Pass STW-1092 04/10/06 Ra-228 20.9 +/- 1.2 19.1 10.8 -27.4 Pass STW-1092 04/10/06 Uranium 68.6 +/- 3.4 69.1 57.1 -81.1 Pass STW-1094 07/10/06 Sr-89 15.9 +/- 0.7 19.7 11.0 -28.4 Pass STW-1094 07/10/06 Sr-90 24.3 +/- 0.4 25.9 17.2 - 34.6 Pass STW-1095 07/10/06 Ba-1 33 94.9 +/- 8.9 88.1 72.9 - 103.0 Pass STW-1095 07/10/06 Co-60 104.0 +/- 1.8 99.7 91.0 - 108.0 Pass STW-1095 07/10/06 Cs-134 48.7 +/- 1.3 54.1 45.4 -62.8 Pass STW-1095 07/10/06 Cs-1 37 236.0 +/- 3.0 238.0 217.0 - 259.0 Pass STW-1 095 07/10/06 Zn-65 126.0 +/- 8.0 121.0 100.0 - 142.0 Pass STW-1096 07/10/06 Gr. Alpha 10.9 +/- 1.0 10.0 1.3 -18.6 Pass STW-1096 07/10/06 Gr. Beta 9.7 +/- 0.4 8.9 0.2 - 17.5 Pass STW-1097 07/10/06 Ra-226 11.0 +/- 0.5 10.7 7.9 -13.5 Pass STW-1097 07/10/06 Ra-228 12.2 +/- 0.8 10.7 6.1 - 15.3 Pass STW-1097 07/10/06 Uranium 43.4 +/- 0.1 40.3 33.3 -47.3 Pass Al-I

TABLE A-1. Interlaboratory Comparison Crosscheck program, Environmental Resource Associates (ERA)a.

Concentration (pCiIL)

Lab Code Date Analysis Laboratory ERA Control Resultb Resultc Limits Acceptance STW-1104 STW-1 104 STW-1105 STW-1 105 STW-1105 STW-1 105 STW-1 105 STW-1 106 STW-1 106 STW-1107 d STW-1108 STW-1 108 STW-1 108 STW-1 109 10/06/06 10/06/06 10/06/06 10/06/06 10/06/06 10/06/06 10/06/06 10/06/06 10/06/06 10/06/06 10/06/06 10/06/06 10/06/06 10/06/06 Sr-89 Sr-90 Ba-133 Co-60 Cs-134 Cs-1 37 Zn-65 Gr. Alpha Gr. Beta 1-131 Ra-226 Ra-228 Uranium H-3 38.4 +/- 1.3 15.5 +/- 0.5 64.9 +/- 2.8 61.6 +/- 1.0 29.0 +/- 0.9 77.8 +/- 2.4 293.0 +/- 2.4 23.9 +/- 2.5 23.7 +/- 1.4 28.4 +/- 1.2 14.5 +/- 0.5 6.6 +/- 0.4 2.9 +/- 0.1 3000.0 +/- 142.0 39.9 16.0 70.2 62.3 29.9 78.2 277.0 28.7 20.9 22.1 14.4 5.9 3.2 3050.0 31.2 -45.7 7.3 - 24.7 58.1 - 82.3 53.6 - 71.0 21.2 -38.6 69.5 - 86.9 229.0 - 325.0 16.3 -41.1 12.2 -29.6 16.9 -27.3 10.7 - 18.1 3.3 - 8.4 0.0 - 8.4 2430.0 - 3670.0 Pass Pass Pass Pass Pass Pass Pass Pass Pass Fail Pass Pass Pass Pass a Results obtained by Environmental, Inc., Midwest Laboratory as a participant in the crosscheck program for proficiency testing in drinking water conducted by Environmental Resources Associates (ERA).

b Unless otherwise indicated, the laboratory result is given as the mean +/- standard deviation for three determinations.

c Results are presented as the known values, expected laboratory precision (1 sigma, 1 determination) and control limits as provided by ERA.

d The reported result was an average of three analyses, results ranged from 25.36 to 29.23 pCi/L.

A fourth analysis was performed, result of analysis, 24.89 pCi/L.

Al -2

TABLE A-2. Crosscheck program results; Thermoluminescent Dosimetry, (TLD, CaSO4: Dy Cards).

mR Lab Code Date Known Lab Result Control Description Value

+/- 2 sigma Limits Acceptance Environmental, Inc.

2006-1 6/5/2006 2006-1 6/5/2006 2006-1 6/5/2006 2006-1 6/5/2006 2006-1 6/5/2006 2006-1 6/5/2006 2006-1 6/5/2006 2006-1 6/5/2006 2006-1 6/5/2006 Environmental, Inc.

30 cm 60 cm 60 cm 90 cm 120 cm 120 cm 150 cm 150 cm 180 cm 30 cm.

40 cm.

50 cm.

60 cm.

75 cm.

90 cm.

120 cm.

150 cm.

180 cm.

54.81 13.70 13.70 6.09 3.43 3.43 2.19 2.19 1.52 55.61 31.28 20.02 13.90 8.90 6.18 3.48 2.22 1.54 70.73 +/- 0.69 16.71 +/- 1.89 16.69 +/- 0.94 6.57 +/- 0.82 3.65 +/- 0.22 3.09 +/- 0.33 2.35 +/- 0.38 1.98 +/- 0.10 1.56 +/- 0.26 60.79 +/- 1.32 35.93 +/- 3.70 21.55 +/- 1.20 14.90 +/- 1.42 8.03 + 0.51 6.88 +/- 0.68 2.90 +/- 0.20 1.99 +/- 0.07 1.79 +/- 0.94 38.37 -71.25 9.59 - 17.81 9.59 - 17.81 4.26 - 7.92 2.40 - 4.46 2.40 -4.46 1.53 -2.85 1.53 - 2.85 1.06 -1.98 38.93 - 72.29 21.90 -40.66 14.01 -26.03 9.73 - 18.07 6.23 -11.57 4.33 - 8.03 2.44 - 4.52 1.55 -2.89 1.08 - 2.00 Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass 2006-2 2006-2 2006-2 2006-2 2006-2 2006-2 2006-2 2006-2 2006-2 11/6/2006 11/6/2006 11/6/2006 11/6/2006 11/6/2006 11/6/2006 11/6/2006 11/6/2006 11/6/2006 A2-1

TABLE A-3. In-House "Spike" Samples Concentration (pCi/L)a Lab Code b Date Analysis Laboratory results Known Control 2s, n=1 c Activity Limits d Acceptance SPW-301 SPAP-1224 SPAP-1224 SPAP-1224 SPW-1228 SPW-1230 SPW-1230 SPMI-1 232 SPMI-1232 W-30906 W-30906 SPW-2750 SPW-2869 SPAP-2871 SPAP-2871' SPW-2875 STSO-3155 STSO-3155 STSO-3155 SPAP-2873 SPF-3183 SPF-3183 SPW-3460 W-60606 W-60606 SPW-3988 SPW-3988 SPW-3988 SPW-3988 SPW-3988 SPMI-3990 SPMI-3990 SPMI-3990 SPMI-3991 SPW-4356 W-90506 W-90506 SPAP-6950 SPAP-6950 SPAP-6952 1/2012006 3/7/2006 3/7/2006 3/7/2006 3/7/2006 3/7/2006 3/7/2006 3/7/2006 3/7/2006 3/9/2006 3/9/2006 4/27/2006 5/1/2006 5/1/2006 5/1/2006 5/1/2006 5/1/2006 5/1/2006 5/1/2006 5/2/2006 5/10/2006 5/10/2006 5/26/2006 6/6/2006 6/6/2006 6/16/2006 6/16/2006 6/16/2006 6/16/2006 6/16/2006 6/16/2006 6/1612006 6/16/2006 6/16/2006 7/5/2006 9/5/2006 9/5/2006 9/30/2006 9/30/2006 9/30/2006 Fe-55 Cs-1 34 Cs-137 Gr. Beta H-3 Cs-134 Cs-137 Cs-134 Cs-137 Gr. Alpha Gr. Beta Ni-63 Fe-55 Cs-1 34 Cs-137 H-3 Co-60 Cs-1 34 Cs-1 37 Gr. Beta Cs-137 Cs-1 34 C-14 Gr. Alpha Gr. Beta Cs-1 34 Cs-1 37 1-131(G)

Sr-89 Sr-90 Cs-1 34 Cs-137 1-131(G) 1-131 1-131 Gr. Alpha Gr. Beta Cs-1 34 Cs-1 37 Gr. Beta 2700.10 +/- 70.00 37.13 +3.70 118.25 + 8.97 520.32 + 7.42 70891.00 +/- 719.00 38.58 + 2.10 59.44 + 4.51 41.20 +/- 1.33 57.82 + 3.96 24.24 +/- 0.47 63.79 + 0.48 116.00 +/- 2.49 19473.00 + 188.00 33.97 +/- 1.10 114.44 +/- 2.81 71057.00 +/- 730.20 7950.80 +/- 67.29 12.49 +/- 0.13 14.10 +/- 0.12 1724.80 +/- 4.51 2.47 +/- 0.03 0.73 +/- 0.01 4009.60 +/- 14.43 21.94 +/- 0.46 58.17 +/-+0.49 35.56 +/- 1.40 60.23 _ 2.72 94.01 + 4.38 52.40 +/-4.23 45.35 +/- 1.95 35.52 +/- 5.05 56.78 +/- 3.86 95.04 _ 5.05 96.55 +/- 0.87 80.88 - 1.09 23.11 +/-+0.45 65.01 +/- 0.51 28.93 +/- 1.56 116.62 +/- 2.97 52.96 +/- 0.14 2502.50 39.52 119.30 455.00 75394.00 39.51 59.65 39.51 59,65 20.08 65.73 100.00 23332.00 37.50 118.90 75394.00 7750.00 11.59 11.63 1744.00 2.38 0.74 4741.00 20.08 65.73 36.00 59.27 99.30 58.16 41.21 36.00 59.27 99.30 99.30 77.23 20.08 65.73 32.65 117.75 53.50 2002.00 - 3003.00 29.52 - 49.52 107.37 - 131.23 364.00 - 637.00 60315.20 - 90472.80 29.51 - 49.51 49.65 - 69.65 29.51 -49.51 49.65 - 69.65 10.04 -30.12 55.73 - 75.73 60.00 - 140.00 18665.60 -27998.40 27.50 - 47.50 107.01 - 130.79 60315.20 - 90472.80 6975.00 - 8525.00 1.59 -21.59 1.63 -21.63 1395.20 -2441.60 1.43 -3.33 0.44-1.04 2844.60 - 6637.40 10.04 -30.12 55.73 - 75.73 26.00 - 46.00 49.27 - 69.27 89.30 - 109.30 46.53 - 69.79 32.97 - 49.45 26.00 - 46.00 49.27 - 69.27 89.30 - 109.30 79.44 -119.16 61.78 - 92.68 10.04 -30.12 55.73 - 75.73 22.65 - 42.65 105.98 - 129.53 42.80 - 74.90 Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass A3-1

TABLE A-3. In-House "Spike" Samples Concentration (pCi/L)

Lab Code Date Analysis Laboratory results Known Control 2s, n=lb Activity Limitsc Acceptance SPW-6954 SPW-6954 SPMI-6956 SPMI-6956 W-120106 W-1 20106 SPAP-9476 SPAP-9478 SPAP-9478 SPW-9480 SPW-9483 SPW-9488 SPW-9488 SPMI-9490 SPMI-9490 SPF-9492 SPF-9492 9/30/2006 9/30/2006 9/30/2006 9/30/2006 12/1/2006 12/1/2006 12/29/2006 12/29/2006 12/29/2006 12/29/2006 12/29/2006 12/29/2006 12/29/2006 12/29/2006 12/29/2006 12/29/2006 12/29/2006 Cs-1 34 Cs-137 Cs-1 34 Cs-1 37 Gr. Alpha Gr. Beta Gr. Beta Cs-134 Cs-1 37 H-3 Tc-99 Cs-134 Cs-137 Cs-1 34 Cs-137 Cs-1 34 Cs-1 37 63.29 +/- 8.24 60.41 +/- 7.53 69.26 +/- 4.85 61.35 +/- 7.62 22.40 +/- 1.03 63.70 +/- 1.14 57.51 +/- 0.14 26.84 +/- 1.23 110.54 +/- 3.12 68972.20 +/- 748.00 29.43 +/- 0.84 61.35 +/- 1.65 60.30 +/- 2.76 58.99 +/- 5.43 54.16 +/- 7.85 0.64 +/- 0.01 2.61 +/- 0.03 65.30 58.87 65.31 58.87 20.08 65.73 53.16 30.06 117.10 72051.60 32.98 60.10 56.80 60.10 56.80 0.60 2.34 55.30 - 75.30 48.87 - 68.87 55.31 - 75.31 48.87 - 68.87 10.04 - 30.12 55.73 - 75.73 42.53 - 74.42 20.06 -40.06 105.39 - 128.81 57641.28 -86461.92 20.98 -44.98 50.10 -70.10 46.80 - 66.80 50.10 -70.10 46.80 - 66.80 0.36 - 0.84 1.40 -3.28 Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass a Liquid sample results are reported in pCi/Liter, air filters( pCi/filter), charcoal (pCi/m 3), and solid samples (pCi/g).

b Laboratory codes as follows: W (water), MI (milk), AP (air filter), SO (soil), VE (vegetation),

CH (charcoal canister), F (fish).

c Results are based on single determinations.

d Control limits are based on Attachment A, Page A2 of this report.

NOTE: For fish, Jello is used for the Spike matrix. For Vegetation, cabbage is used for the Spike matrix.

A3-2

TABLE A-4. In-House "Blank" Samples Concentration (pCi/L)a Lab Code Sample Date Analysisb Laboratory results (4.66cy)

Acceptance Type LLD Activityc Criteria (4.66 a)

SPW-302 SPAP-1225 SPW-1231 SPW-1231 W-30906 W-30906 SPW-2751 SPW-2868 SPW-2874 SPAP-2872 SPF-3154 SPF-3154 SPW-3461 W-60606 W-60606 SPW-3989 SPW-3989 SPW-3989 SPW-3989 SPW-3989 SPW-3989 SPMI-3991 SPMI-3991 SPMI-3991 SPMI-3991 SPMI-3991 SPMI-3991 W-90506 W-90506 SPMI-6383 SPMI-6383 d SPAP-6949 SPAP-6949 SPAP-6951 SPW-6953 SPW-6953 SPW-6953 SPW-6953 water Air Filter water water water water water water water Air Filter Fish Fish water water water water water water water water water Milk Milk Milk Milk Milk Milk water water Milk Milk Air Filter Air Filter Air Filter water water water water 1/20/2006 3/7/2006 3/7/2006 3/7/2006 3/9/2006 3/9/2006 4/27/2006 5/1/2006 5/1/2006 5/2/2006 5/10/2006 5/10/2006 5/26/2006 6/6/2006 6/6/2006 6/16/2006 6/16/2006 6/16/2006 6/16/2006 6/16/2006 6/16/2006 6/16/2006 6/16/2006 6/16/2006 6/16/2006 6/16/2006 6/16/2006 9/5/2006 9/5/2006 9/14/2006 9/14/2006 9/30/2006 9/30/2006 9/30/2006 9/30/2006 9/30/2006 9/30/2006 9/30/2006 Fe-55 Gr. Beta Cs-134 Cs-1 37 Gr. Alpha Gr. Beta Ni-63 Fe-55 H-3 Gr. Beta Cs-134 Cs-137 C-14 Gr. Alpha Gr. Beta Cs-134 Cs-1 37 1-131 1-131(G)

Sr-89 Sr-90 Cs-1 34 Cs-137 1-131 1-131(G)

Sr-89 Sr-90 Gr. Alpha Gr. Beta Sr-89 Sr-90 Cs-1 34 Cs-137 Gr. Beta Cs-1 34 Cs-137 Sr-89 Sr-90 1061 1.16 2.71 2.05 0.037 0.076 1.48 18.07 166.00 1.18 16.4 13.7 10.20 0.05 0.16 3.00 3.65 0.21 8.34 0.54 0.58 4.42 3.88 0.28 3.76 0.61 0.52

-91 +/- 637

-0.512 +/- 51.20 0.005 +/- 0.026

-0.016 +/- 0.052 0.37 +/- 0.91 4.33 +/- 11.27

-8.3 +/- 86.9

-3.65 +/- 0.64

-7.9 + 5.20 0.013 + 0.037

-0.044 +/- 0.11 0.045 +/- 0.14 0.005 +/- 0.45

-0.079 +/- 0.26

-0.22 +/- 0.19

-0.25 +/- 0.76 0.88 +/- 0.34 0.00 +/- 0.04 0.05 +/- 0.11

-0.18 +/- 0.92 0.65 +/- 0.33

-0.54 +/- 0.64

-0.14 +/- 0.64 0.11 +/-0.29 1000 3.2 10 10 1

3.2 20 1000 200 3.2 100 100 200 1

3.2 10 10 0.5 20 5

1 10 10 0.5 20 5

1 0.06 0.16 0.97 0.57 0.89 0.91 1.12 3.91 5.61 0.79 0.60 1

3.2 5

1 100 100 3.2 10 10 5

1 A4-1

TABLE A-4. In-House "Blank" Samples Concentration (pCi/L)2 Lab Code Sample Date Analysisb Laboratory results (4.66a)

Acceptance Type LLD Activityc Criteria (4.66 c)

SPMI-6955 SPMI-6955 SPMI-6955 W-1 20106 W-120106 SPAP-9477 SPAP-9479 SPW-9481 SPW-9483 SPW-9489 SPMI-9491 SPMI-9491 SPMI-9491 SPF-9493 SPF-9493 Milk Milk Milk water water Air Filter Air Filter water water water Milk Milk Milk Fish Fish 9/30/2006 9/30/2006 9/30/2006 12/1/2006 12/1/2006 12/29/2006 12/29/2006 12/29/2006 12/29/2006 12/29/2006 12/29/2006 12/29/2006 12/29/2006 12/29/2006 12/29/2006 Cs-1 34 Cs-1 37 1-131(G)

Gr. Alpha Gr. Beta Gr. Beta Cs-137 H-3 Tc-99 Cs-1 34 Cs-134 Cs-1 37 1-131 (G)

Cs-134 Cs-1 37 2.86 2.39 9.98 0.11 0.30 1.13 0.87 146.2 0.95 2.30 3.10 2.90 8.00 7.6 7.9 0.066 +/- 0.072 0.093 +/- 0.16

-0.37 +/- 0.66 63.2 +/- 80.1

-1.20 +/- 0.56 10 10 0.5 1

3.2 3.2 100 200 10 10 10 10 20 100 100 a Liquid sample results are reported in pCi/Liter, air filters( pCi/filter), charcoal (pCi/charcoal canister), and solid samples (pCi/kg).

b 1-131 (G); iodine-1 31 as analyzed by gamma spectroscopy.

c Activity reported is a net activity result. For gamma spectroscopic analysis, activity detected below the LLD value is not reported d Low levels of Sr-90 are still detected in the environment. A concentration of (1-5 pCi/L) in milk is not unusual.

A4-2

TABLE A-5. In-House "Duplicate" Samples Concentration (pCi/L)"

Averaged Lab Code Date Analysis First Result Second Result Result Acceptance AP-7466, 7467 AP-7513, 7514 AP-7555, 7556 MI-154, 155 MI-217, 218 MI-217, 218 MI-287, 288 MI-287, 288 WW-314, 315 WW-314, 315 SWT-577, 578 SWU-598, 599 SWU-598, 599 F-3311, 3312 b F-3311, 3312 SW-780, 781 SW-780, 781 DW-934, 935 DW-1024, 1025 MI-1078, 1079 F-1357, 1358 F-1357, 1358 MI-1469, 1470 CF-1538, 1539 WW-1 583, 1584 DW-1955, 1956 MI-1760, 1761 AP-2603, 2604 E-1997, 1998 E-1997, 1998 AP-2818, 2819 SWU-2863, 2864 SS-2389, 2390 SS-2389, 2390 DW-2773, 2774 SL-2932, 2933 SL-2932, 2933 SL-2932, 2933 BS-3103, 3104 BS-3103, 3104 MI-3037, 3038 MI-3037, 3038 1/3/2006 1/3/2006 1/3/2006 1/10/2006 1/11/2006 1/11/2006 1/17/2006 1/17/2006 1/19/2006 1/19/2006 1/31/2006 1/31/2006 1/31/2006 2/9/2006 2/9/2006 2/14/2006 2/14/2006 2/17/2006 2/24/2006 3/1/2006 3/10/2006 3/10/2006 3/14/2006 3/21/2006 3/22/2006 3/27/2006 3/29/2006 3/29/2006 4/3/2006 4/3/2006 4/3/2006 4/3/2006 4/11/2006 4/11/2006 4/21/2006 5/1/2006 5/1/2006 5/1/2006 5/1/2006 5/1/2006 5/2/2006 5/2/2006 Be-7 Be-7 Be-7 K-40 K-40 Sr-90 K-40 Sr-90 Gr. Beta H-3 Gr. Beta Gr. Beta H-3 Gr. Beta K-40 Gr. Alpha Gr. Beta 1-131 1-131 Sr-90 Gr. Beta K-40 K-40 K-40 Gr. Beta Gr. Beta K-40 Be-7 Gr. Beta K-40 Be-7 Gr. Beta Gr. Beta K-40 1-131 Be-7 Gr. Beta K-40 Gr. Beta K-40 K-40 Sr-90 0.053 +/- 0.015 0.033 +/- 0.008 0.053 +/- 0.007 1254.20 +/- 87.75 1258.00 +/- 118.00 1.27 +/- 0.37 1383.10 +/- 110.90 0.74 +/- 0.38 9.21 + 1.72 168.64 _ 94.94 3.06 _ 0.66 2.03 +/- 0.39 260.10 + 98.20 4.12 + 0.14 2.68 +/- 0.37 4.09 _ 1.52 5.91 + 0.90 0.35 + 0.22 0.24 + 0.26 1.42 + 0.39 3.77 + 0.07 2.46 +/- 0.32 1396.30 + 120.80 13.66 + 0.81 7.66 _ 0.73 2.25 + 0.60 1271.00 + 89.00 0.067 + 0.015 0.057 +/- 0.011 0.036 +/- 0.008 0.054 +/- 0.008 1369.60 +/- 102.80 1313.00 +/- 98.00 0.92 +/- 0.33 1457.80 +/- 119.10 0.94 +/- 0.37 11.52 +/- 1.93 210.12 + 96.51 3.68 + 0.64 1.97 +/- 0.40 134.10 +/-93.50 3.82 +/- 0.13 2.76 +/- 0.39 3.22 +/- 1.37 5.89 +/- 0.92 0.31 +/- 0.25 0.53 +/- 0.24 1.30 +/- 0.62 3.71 +/- 0.07 2.32 +/- 0.44 1335.60 +/- 113.80 13.97 +/- 0.68 8.87 +/- 0.75 3.15 +/- 0.59 1378.00 +/- 113.00 0.056 +/- 0.010 1.87 +/- 0.07 1.24 +/- 0.21 0.06 +/- 0.01 4.77 +/- 1.30 9.38 + 0.84 5.79 _ 0.40 0.53 +/- 0.40 1.27 + 0.17 5.65 +/- 0.31 3.09 +/- 0.36 9.03 +/- 1.59 5643.70 +/- 599.80 1301.00 +/- 103.90 1.48 +/- 0.42 0.055 +/- 0.009 0.035 +/- 0.006 0.053 +/- 0.005 1311.90 +/- 67.58 1285.50 +/- 76.69 1.10 +/- 0.25 1420.45 +/- 81.37 0.84 +/- 0.27 10.37 +/- 1.29 189.38 +/- 67.69 3.37 +/- 0.46 2.00 +/- 0.28 197.10 +/- 67.80 3.97 +/- 0.10 2.72 +/- 0.27 3.66 +/- 1.03 5.90 +/- 0.64 0.33 +/- 0.16 0.39 +/- 0.18 1.36 +/- 0.37 3.74 +/- 0.05 2.39 +/- 0.27 1365.95 +/- 82.98 13.81 +/- 0.53 8.26 +/- 0.52 2.70 +/- 0.42 1324.50 +/- 71.92 0.062 +/- 0.009 Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Fail Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass 1.82 1.28 0.06 3.20 10.53 5.51 0.74 1.28 6.09 3.13 8.27 6288.20 1238.90 1.76

+ 0.07

+/-0.15

+ 0.01

+ 1.26

+ 0.96

+ 0.42

+ 0.23

+0.19

_+ 0.33

+ 0.41

+ 1.46

+ 585.20

+ 98.59

+ 0.42 1.85 1.26 0.06 3.99 9.96 5.65 0.63 1.28 5.87 3.11 8.65 5965.95 1269.95 1.62

+/- 0.05

+/- 0.13

+/- 0.01

+/- 0.91

+/- 0.64

+/- 0.29

+/- 0.23

+/- 0.13

+/- 0.23

+/- 0.27

+/- 1.08

+/- 418.99

+/- 71.62

+/- 0.29 A5-1

TABLE A-5. In-House "Duplicate" Samples Concentration (pCi/L)a Averaged Lab Code Date Analysis First Result Second Result Result Acceptance MI-3124, 3125 SW-3145, 3146 SW-3145, 3146 MI-3236, 3237 F-3422, 3423 G-3491, 3492 G-3491, 3492 SO-3539, 3540 SO-3539, 3540 WW-3751, 3752 F-3617, 3618 SL-3641, 3642 SL-3641, 3642 SL-3641, 3642 MI-3886, 3887 VE-3949, 3950 VE-3949, 3950 VE-3949, 3950 BS-4016, 4017 BS-4016, 4017 BS-4016, 4017 MI-3992, 3993 LW-4175, 4176 W-4130, 4131 AV-4330, 4331 SWU-4489, 4490 AP-4909, 4910 AP-4952, 4953 AP-4930, 4931 E-4399, 4400 E-4399, 4400 G-4420, 4421 G-4420, 4421 G-4420, 4421 5/9/2006 5/9/2006 5/9/2006 5/10/2006 5/19/2006 5/24/2006 5/24/2006 5/24/2006 5/24/2006 5/25/2006 5/30/2006 6/1/2006 6/1/2006 6/1/2006 6/12/2006 6/13/2006 6/13/2006 6/13/2006 6/13/2006 6/13/2006 6/13/2006 6/14/2006 6/16/2006 6/21/2006 6/26/2006 6/27/2006 6/29/2006 6/29/2006 7/3/2006 7/5/2006 7/5/2006 7/5/2006 7/5/2006 7/5/2006 K-40 Gr. Alpha Gr. Beta K-40 H-3 Gr. Beta K-40 Gr. Beta K-40 Gr. Beta K-40 Be-7 Gr. Beta K-40 K-40 Gr. Alpha Gr. Beta K-40 Co-60 Cs-1 37 K-40 K-40 H-3 H-3 K-40 Gr. Beta Be-7 Be-7 Be-7 Gr. Beta K-40 Be-7 Gr. Beta K-40 Gr. Alpha Gr. Alpha Gr. Alpha K-40 Sr-90 K-40 Gr. Beta 1032.30 +/- 91.12 4.85 +/- 1.68 8.94 +/- 1.46 1412.40 +/- 119.10 8175.00 +/- 252.00 8.89 +/- 0.18 5.60 +/- 0.71 19.57 +/- 1.99 12.55 +/- 0.89 9.85 +/- 0.79 2.42 +/- 0.38 1.41 +/- 0.19 5.03 +/- 0.18 2.21 +/- 0.26 1424.20 +/- 118.20 0.13 +/- 0.06 4.53 +/- 0.19 6.02 +/- 0.66 0.18 +/- 0.03 1.97 +/- 0.09 11.03 +/- 0.76 1358.50 +/- 166.40 482.11 +/- 90.25 401.50 +/- 87.85 1717.10 +/- 244.30 1.70 +/- 0.38 0.11 +/- 0.01 0.08 +/- 0.02 0.08 +/- 0.02 1.85 +/- 0.05 1.25 +/- 0.19 0.82 +/- 0.20 13.20 +/- 0.40 9.96 +/- 0.44 3.24 +/- 1.35 3.70 +/- 1.12 6.87 +/- 1.26 1403.50 +/- 118.80 0.59 +/- 0.34 1286.60 +/- 92.62 1.75 +/- 0.60 1103.60 +/- 120.50 4.12 +/- 1.62 9.14 +/- 1.36 1427.90 +/- 127.70 8268.00 +/- 253.00 9.03 +/- 0.19 6.30 +/- 0.78 18.98 +/- 1.91 11.49 +/- 0.59 8.96 +/- 0.74 2.53 +/- 0.37 1.31 +/- 0.27 5.30 +/- 0.19 2.14 +/- 0.37 1318.80 +/- 110.50 0.16 +/- 0.07 4.47 +/- 0.18 5.33 +/- 0.66 0.15 +/- 0.03 2.01 +/- 0.09 10.45 +/- 0.78 1395.80 +/- 122.70 397.50 +/- 86.88 236.28 +/- 80.89 1893.10 +/- 223.30 1.93 +/- 0.38 0.11 +/-0.02 0.10 +/- 0.02 0.07 +/- 0.01 1.85 +/- 0.05 1.24 +/- 0.18 0.61 +/- 0.14 14.00 +/- 0.40 10.06 +/- 0.82 2.49 +/- 1.33 3.09 +/- 1.16 4.77 +/- 1.09 1330.40 +/- 116.50 0.70 +/- 0.35 1358.60 +/- 158.40 2.51 +/- 0.59 1067.95 +/- 75.54 4.48 +/- 1.17 9.04 +/- 1.00 1420.15 +/- 87.31 8221.50 +/- 178.54 8.96 +/- 0.13 5.95 +/- 0.53 19.27 +/- 1.38 12.02 +/- 0.53 9.41 +/- 0.54 2.47 +/- 0.27 1.36 +/- 0.17 5.17 +/- 0.13 2.18 +/- 0.23 1371.50 +/- 80.90 0.15 +/- 0.05 4.50 +/- 0.13 5.67 +/- 0.47 0.16 +/- 0.02 1.99 +/- 0.06 10.74 +/- 0.54 1377.15 +/- 103.37 439.81 +/- 62.63 318.89 +/- 59.71 1805.10 +/- 165.49 1.82 +/- 0.27 0.11 +/- 0.01 0.09 +/- 0.01 0.08 +/- 0.01 1.85 +/- 0.04 1.25 +/- 0.13 0.72 +/- 0.12 13.60 +/- 0.28 10.01 +/- 0.47 2.87 +/- 0.95 3.40 +/- 0.81 5.82 +/- 0.83 1366.95 +/- 83.20 0.65 +/- 0.24 1322.60 +/- 91.75 2.13 +/- 0.42 Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass DW-60432, 60433 7/6/2006 DW-60514, 60515 7/10/2006 DW-60449, 60450 7/11/2006 MI-4599, 4600 7/12/2006 MI-4599, 4600 7/12/2006 MI-4667, 4668 7/12/2006 LW-4823, 4824 7/14/2006 A5-2

TABLE A-5. In-House "Duplicate" Samples Concentration (pCi/L)a Averaged Lab Code Date Analysis First Result Second Result Result Acceptance DW-60502, 60503 7/19/2006 DW-60526, 60527 7/21/2006 DW-60539, 60540 7/21/2006 MI-5125, 5126 7/25/2006 DW-60609, 60610 7/26/2006 DW-60621, 60622 7/31/2006 SL-5265, 5266 SL-5265, 5266 SL-5265, 5266 SL-5265, 5266 VE-5286, 5287 VE-5286, 5287 VE-5286, 5287 SW-5383, 5384 SW-5383, 5384 SW-5971, 5972 VE-5404, 5405 VE-5404, 5405 DW-5480, 5481 8/1/2006.

8/1/2006 8/1/2006 8/1/2006 8/1/2006 8/1/2006 8/1/2006 8/8/2006 8/8/2006 8/8/2006 8/10/2006 8/10/2006 8/11/2006 DW-60645, 60646 8/15/2006 W-5602, 5603 8/16/2006 DW-60634, 60635 8/18/2006 DW-60634, 60635 8/18/2006 MI-5793, 5794 8/22/2006 SWU-6150, 6151 8/29/2006 DW-60657, 60658 8/29/2006 CF-7450, 7451 9/5/2006 SL-6085, 6086 9/5/2006 SL-6085, 6086 9/5/2006 SL-6085, 6086 9/5/2006 DW-60695, 60696 9/11/2006 LW-6266, 6267 9/1312006 MI-6424, 6425 9/19/2006 DW-60715, 60716 9/19/2006 SO-6597, 6598 9/22/2006 SO-6597, 6598 9/22/2006 SWU-6718, 6719 9/26/2006 SO-6668, 6669 9/27/2006 SO-6668, 6669 9/27/2006 Gr. Alpha Gr. Alpha Gr. Alpha K-40 Gr. Alpha Gr. Alpha Be-7 Sr-90 Gr. Beta K-40 Be-7 Gr. Beta K-40 Gr. Alpha Gr. Beta H-3 Be-7 K-40 H-3 Gr. Alpha H-3 Gr. Alpha Gr. Beta K-40 Gr. Beta Gr. Alpha Be-7 Co-60 Gr. Beta K-40 Gr. Alpha Gr. Beta Sr-90 Gr. Alpha Cs-1 37 K-40 Gr. Beta Cs-1 37 K-40 16.27 +/- 2.49 14.06 +/- 1.82 5.09 +/- 0.95 1480.60 +/- 118.30 1.00 +/- 1.10 3.70 +/- 1.00 1.10 +/- 0.46 0.10 +/- 0.03 4.41 +/- 0.41 1.19 +/- 0.52 1.21 +/- 0.30 9.67 +/- 0.35 6.25 +/- 0.81 3.24 +/- 1.35 4.86 +/- 0.86 119.90 +/- 78.14 0.77 +/- 0.24 4.71 +/- 0.63 169.08 +/- 85.52 10.41 +/- 1.78 2118.79 +/- 151.55 12.99 +/- 1.84 10.51 +/- 1.33 1264.00 +/- 115.00 1.84 +/- 0.28 2.33 +/- 0.80 0.78 +/- 0.45 0.22 +/- 0.03 5.47 +/- 0.69 1.91 +/- 0.28 3.93 +/- 1.17 3.09 +/- 0.48 0.78 +/- 0.38 1.30 +/- 1.00 0.18 +/- 0.04 10.25 +/- 0.66 3.45 +/- 1.21 0.13 +/- 0.04 13.04 +/- 0.90 21.41 +/- 3.21 15.57 +/- 1.77 6.23 +/- 1.05 1402.60 +/- 120.80 2.70 +/- 1.30 1.90 +/- 0.80 1.38 +/- 0.52 0.16 +/- 0.03 3.46 +/- 0.57 0.87 +/- 0.52 1.32 +/- 0.20 9.37 +/- 0.35 6.50 +/- 0.48 2.94 +/- 1.35 5.46 +/- 0.87 144.41 +/- 79.23 1.01 +/- 0.26 4.01 +/- 0.58 133.65 +/- 83.96 10.97 +/- 1.85 2181.82 +/- 153.09 9.67 +/- 1.61 8.61 +/- 1.18 1377.00 +/- 121.00 1.81 +/- 0.28 2.90 +/- 0.78 0.78 +/- 0.27 0.21 +/- 0.02 4.63 +/- 0.58 2.06 +/- 0.41 4.62 +/- 1.12 2.98 +/- 0.48 1.11 +/- 0.37 2.23 +/- 1.01 0.18 +/- 0.04 10.11 +/- 0.64 2.78 +/- 1.19 0.13 +/- 0.02 12.41 +/- 0.54 18.84 +/- 2.03 14.82 +/- 1.27 5.66 +/- 0.71 1441.60 +/- 84.54 1.85 +/- 0.85 2.80 +/- 0.64 1.24 +/- 0.35 0.13 +/- 0.02 3.94 +/- 0.35 1.03 +/- 0.37 1.27 +/- 0.18 9.52 +/- 0.25 6.38 +/- 0.47 3.09 +/- 0.96 5.16 +/- 0.61 132.15 +/- 55.64 0.89 +/- 0.18 4.36 +/- 0.43 151.36 +/- 59.92 10.69 +/- 1.28 2150.30 +/- 107.71 11.33 +/- 1.22 9.56 +/- 0.89 1320.50 +/- 83.47 1.82 +/- 0.20 2.62 +/- 0.56 0.78 +/- 0.26 0.22 +/- 0.02 5.05 +/- 0.45 1.99 +/- 0.25 4.28 +/- 0.81 3.03 +/- 0.34 0.95 +/- 0.27 1.77 +/- 0.71 0.18 +/- 0.03 10.18 +/- 0.46 3.12 +/- 0.85 0.13 +0.02 12.72 +/- 0.53 Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass A5-3

TABLE A-5. In-House "Duplicate" Samples Concentration (pCi/L)a Averaged Lab Code Date Analysis First Result Second Result Result Acceptance MI-6760, 6761 G-6797, 6798 G-6797, 6798 G-6797, 6798 b AP-7531, 7532 AP-7552, 7553 AP-7573, 7574 SO-7103, 7104 SO-7103, 7104 DW-60759, 60760 MI-7037, 7038 VE-7058, 7059 VE-7058, 7059 VE-7058, 7059 SS-7079, 7080 SS-7079, 7080 SS-7079, 7080 MI-7208, 7209 CF-7450, 7451 LW-7945, 7946 F-7971, 7972 SWU-8194, 8195 BS-8017, 8018 BS-8017, 8018 LW-8215, 8216 F-8345, 8346 BS-8366, 8367 MI-8083, 8084 WW-8259, 8260 MI-8484, 8485 SO-8619, 8620 SO-8619, 8620 SO-8619, 8620 SO-8619, 8620 SWT-8641, 8642 SWT-9436, 9437 10/2/2006 10/2/2006 10/2/2006 10/2/2006 10/3/2006 10/3/2006 10/3/2006 10/4/2006 10/4/2006 10/5/2006 10/10/2006 10/10/2006 10/10/2006 10/10/2006 10/10/2006 10/10/2006 10/10/2006 10/11/2006 10/18/2006 10/26/2006 10/29/2006 10/31/2006 11/1/2006 11/1/2006 11/1/2006 11/2/2006 11/2/2006 11/6/2006 11/7/2006 11/22/2006 11/27/2006 11/27/2006 11/27/2006 11/27/2006 11/29/2006 12/26/2006 K-40 Be-7 Gr. Beta K-40 Be-7 Be-7 Be-7 Cs-137 K-40 Gr. Alpha K-40 Gr. Alpha Gr. Beta K-40 Cs-137 Gr. Beta K-40 K-40 K-40 Gr. Beta K-40 Gr. Beta Gr. Beta K-40 Gr. Beta K-40 K-40 K-40 H-3 K-40 Cs-137 Gr. Alpha Gr. Beta K-40 Gr. Beta Gr. Beta 1413.10 + 113.20 4.70 + 0.31 6.89 + 0.26 5.39 + 0.35 0.07 +/- 0.01 0.08 + 0.02 0.08 +/- 0.02 0.25 + 0.05 12.95 _ 1.12 4.93 +/- 0.97 1326.10 +/- 115.20 0.18 + 0.11 9.21 + 0.34 10.90 + 0.65 0.04 + 0.01 12.23 + 2.46 7.23 + 0.36 1295.20 + 116.90 20.40 +/- 0.84 1.30 +/- 0.37 3.63 +/- 0.54 1.84 +/- 0.28 10.54 +/- 1.72 10.00 + 0.53 2.23 +/- 0.61 2.84 + 0.42 13.69 + 0.66 1295.00 + 121.20 337.00 4 95.00 1405.80 + 87.06 0.74 _ 0.08 16.54 + 5.65 24.99 + 3.88 12.21 + 1.11 2.83 + 0.47 2.39 _ 0.64 1187.30 +/- 155.20 4.56 +/- 0.41 7.04 +/- 0.24 4.36 +/- 0.47 0.08 +/- 0.01 0.08 +/- 0.01 0.08 +/- 0.01 0.27 +/- 0.06 12.22 +/- 1.07 5.04 +/- 1.03 1251.40 +/- 115.70 0.32 +/- 0.14 8.83 +/- 0.36 10.42 +/- 0.80 0.04 +/- 0.02 11.76 +/- 2.23 7.37 +/- 0.40 1386.90 +/- 119.10 19.54 +/- 0.99 1.44 +/- 0.36 3.33 +/- 0.43 1.43 +/- 0.28 10.17 +/- 1.73 9.60 +/- 0.69 1.64 +/- 0.37 2.89 +/- 0.40 13.61 +/- 0.78 1374.80 +/- 162.80 295.00 +/- 93.00 1390.70 +/- 103.60 0.69 +/- 0.06 12.24 +/- 4.90 28.66 +/- 3.95 12.92 +/- 0.83 2.89 +/- 0.45 2.25 +/- 0.60 1300.20 +/- 96.05 4.63 +/- 0.26 6.97 +/- 0.18 4.88 +/- 0.29 0.08 +/- 0.01 0.08 +/- 0.01 0.08 +/- 0.01 0.26 +/- 0.04 12.58 +/- 0.77 4.99 +/- 0.71 1288.75 +/- 81.64 0.25 +/- 0.09 9.02 +/- 0.25 10.66 +/- 0.52 0.04 +/- 0.01 11.99 +/- 1.66 7.30 +/- 0.27 1341.05 +/- 83.44 19.97 +/- 0.65 1.37 +/- 0.26 3.48 +/- 0.34 1.64 +/- 0.20 10.36 +/- 1.22 9.80 +/- 0.44 1.93 +/- 0.35 2.86 +/- 0.29 13.65 +/- 0.51 1334.90 +/- 101.48 316.00 +/- 66.47 1398.25 +/- 67.66 0.71 +/- 0.05 14.39 +/- 3.74 26.82 +/- 2.77 12.57 +/- 0.69 2.86 +/- 0.33 2.32 +/- 0.44 Pass Pass Pass Fail Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Note: Duplicate analyses are performed on every twentieth sample received in-house. Results are not listed for those analyses with activities that measure below the LLD.

a Results are reported in units of pCi/L, except for air filters (pCi/Filter), food products, vegetation, soil, sediment (pCi/g).

b 200 minute count time or longer, resulting in lower error.

A5-4

TABLE A-6. Department of Energy's Mixed Analyte Performance Evaluation Program (MAPEP)a.

Concentration b Known Control Lab Codec Date Analysis Laboratory result Activity Limits d Acceptance STVE-1082 STVE-1082 STVE-1082 STVE-1082 e STVE-1082 STVE-1082 STVE-1082 STVE-1082 STVE-1 082 STVE-1082 STVE-1082 STVE-1082 STSO-1083 STSO-1 083 STSO-1 083 STSO-1083 e STSO-1083 STSO-1 083 STSO-1 083 STSO-1 083 STSO-1 083 STSO-1083 STSO-1083 STSO-1 083 STSO-1 083 01/01/06 01/01/06 01/01/06 01/01/06 01/01/06 01/01/06 01/01/06 01/01/06 01/01/06 01/01/06 01/01/06 01/01/06 01/01/06 01/01/06 01/01/06 01/01/06 01/01/06 01/01/06 01/01/06 01/01/06 01/01/06 01/01/06 01/01/06 01/01/06 01/01/06 Am-241 Co-57 Co-60 Cs-1 34 Cs-137 Mn-54 Pu-238 Pu-239/40 Sr-90 U-233/4 U-238 Zn-65 Am-241 Co-57 Co-60 Cs-1 34 Cs-137 K-40 Mn-54 Ni-63 Pu-238 Pu-239/40 U-233/4 U-238 Zn-65 0.16 +/- 0.06 10.40 +/- 0.20 5.00 +/- 0.20

< 0.20 3.40 +/- 0.20 6.90 +/- 0.20 0.08 +/- 0.03 0.17 +/- 0.03 1.40 +/- 0.20 0.24 +/- 0.05 0.19 +/- 0.04 11.10 +/- 0.50 54.60 +/- 5.50 762.90 +/- 12.70 504.90 +/- 3.10

< 1.70 406.50 +/- 3.70 719.20 +/- 18.40 415.60 +/- 4.80 261.40 +/- 14.70 14.60 +/- 2.90 14.60 +/- 2.40 13.50 +/- 1.70 15.40 +/- 1.80 783.40 +/- 7.00 0.16 8.58 4.52 0.00 3.07 6.25 0.14 0.16 1.56 0.21 0.22 9.80 57.08 656.29 447.10 0.00 339.69 604.00 346.77 323.51 61.15 45.85 37.00 38.85 657.36 0.11 -0.20 6.00 -11.15 3.16 -5.88 2.15 -4.00 4.37 -8.12 0.10 -0.18 0.11 -0.21 1.09 -2.03 0.15 -0.27 0.15 -0.28 6.86 - 12.74 39.96 - 74.20 459.40 -853.18 312.97 -581.23 237.78 -441.60 422.80 - 785.20 242.74 - 450.80 226.46 - 420.56 42.81 -79.50 32.09 - 59.61 25.90 -48.10 27.20 - 50.50 460.15 - 854.57 Pass Pass Pass Pass Pass Pass Fail Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Fail Fail Fail Fail Pass Pass Pass Pass Pass Pass Pass Pass Fail Pass Pass Pass Pass Pass STAP-1084 01/01/06 Gr. Alpha STAP-1084 01/01/06 Gr. Beta STAP-1 085 STAP-1 085 STAP-1 085 STAP-1085 STAP-1 085 STAP-1085 STAP-1 085 e STAP-1085 STAP-1085 STAP-1085 STAP-1 085 01/01/06 01/01/06 01/01/06 01/01/06 01/01/06 01/01/06 01/01/06 01/01/06 01/01/06 01/01/06 01/01/06 Am-241 Co-57 Co-60 Cs-134 Cs-1 37 Pu-238 Pu-239/40 Sr-90 U-233/4 U-238 Zn-65 0.26 +/- 0.02 0.51 +/- 0.03 0.12 +/- 0.02 4.32 +/- 0.10 2.24 +/- 0.16 2.96 +/- 0.19 2.64 +/- 0.20 0.03 +/- 0.01

< 0.01 0.77 +/- 0.21 0.03 +/- 0.01 0.02 +/- 0.01 3.94 +/- 0.44 0.36 0.48 0.09 4.10 2.19 2.93 2.53 0.07 0.00 0.79 0.02 0.02 3.42 0.00 - 0.72 0.24 - 0.72 0.07 -0.12 2.87 - 5.32 1.53 -2.84 2.05 - 3.81 1.77 - 3.29 0.05 - 0.09 0.55 - 1.03 0.01 - 0.03 0.01 - 0.03 2.40 -4.45 A6-1

TABLE A-6. Department of Energy's Mixed Analyte Performance Evaluation Program (MAPEP)a.

Concentration b Known Control Lab Codec Date Analysis Laboratory result Activity Limits d Acceptance STW-1086 STW-1086 STW-1086 STW-1 086 STW-1086 e STW-1086 STW-1086 STW-1086 STW-1 086 STW-1 086 STW-1 086 e STW-1 086 STW-1086 STW-1 086 STW-1086 STW-1086 STW-1087 STW-1 087 STVE-1098 e STVE-1098 g 8TVE-1098 STVE-1 098 STVE-1098 STVE-1098 STSO-1099 STSO-1099 STSO-1099 STSO-1099 STSO-1099 STSO-1099 STSO-1 099 STSO-1099 STSO-1 099 STSO-1099 STSO-1099 STSO-1 099 STSO-1099 STAP-1 100 STAP-1 100 STAP-i 100 STAP-1 100 01/01/06 01/01/06 01/01/06 01/01/06 01/01/06 01/01/06 01/01/06 01/01/06 01/01/06 01/01/06 01/01/06 01/01/06 01/01/06 01/01/06 01/01/06 01/01/06 01/01/06 01/01/06 07/01/06 07/01/06 07/01/06 07/01/06 07/01/06 07/01/06 07/01/06 07/01/06 07/01/06 07/01/06 07/01/06 07/01/06 07/01/06 07/01/06 07/01/06 07/01/06 07/01/06 07/01/06 07/01/06 07/01/06 07/01/06 07/01/06 07/01/06 Am-241 Co-57 Co-60 Cs-134 Cs-137 Fe-55 H-3 Mn-54 Ni-63 Pu-238 Pu-239/40 Sr-90 Tc-99 U-233/4 U-238 Zn-65 Gr, Alpha Gr. Beta Co-57 Co-60 Cs-134 Cs-1 37 Mn-54 Zn-65 1.29 +/- 0.05 177.10 +/- 1.00 158.30 +/- 1.00 96.40 +/- 1.50

< 0.80 102.50 +/- 18.10 956.60 +/- 16.50 335.30 +/- 2.20 62.90 +/- 3.60 0.96 +/- 0.07

< 0.20 12.80 +/- 1.60 22.30 +/- 1.20 2.02 +/- 0.12 2.03 +/- 0.12 249.50 +/- 3.40 0.59 +/- 0.10 1.69 +/- 0.07

<0.14 6.89 +/- 0.17 8.46 +/- 0.16 6.87 +/- 0.29 10.36 +/- 0.29 7.46 +/- 0.50 130.00 +/- 11.60 784.90 +/- 3.80 2.10 +/- 0.90 500.70 +/- 7.40 624.20 +/- 4.90 701.30 +/- 3.40 699.20 +/- 5.20 614.40 +/- 17.10 79.90 +/- 5.80

< 0.70 150.50 +/- 5.90 151.60 +/- 6.00 1021.90 +/- 9.20 0.16 +/- 0.03 2.17 +/- 0.06 1.38 +/- 0.07 2.52 +/- 0.13 1.30 166.12 153.50 95.10 0.00 129.60 952.01 315.00 60.34 0.91 0.00 13.16 23.38 2.09 2.17 228.16 0.58 1.13 0.91 - 1.69 116.28 -215.96 107.45 - 199.55 66.57 -123.63 90.72 - 168.48 666.41 -1238.00 220.50 -409.50 42.24 - 78.44 0.70 - 1.30 9.21 -17.11 16.37 -30.39 1.46 -2.72 1.52 -2.82 159.71 -296.61 0.00 -1.16 0.56 -1.70 0.00 5.81 7.49 5.50 8.35 5.98 4.06 - 7.55 5.24 - 9.73 3.85 -7.14 5.85 - 10.86 4.19 -7.78 Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Am-241 Co-57 Co-60 Cs-134 Cs-137 K-40 Mn-54 Ni-63 Pu-238 Pu-239/40 U-233/4 U-238 Zn-65 Am-241 Co-57 Co-60 Cs-1 34 105.47 676.33 1.98 452.13 525.73 604.00 594.25 672.30 82.00 0.00 152.44 158.73 903.61 0.14 2.58 1.58 3.15 73.83 -137.11 473.43 - 879.23 0.00 - 5.00 316.49 - 587.77 368.01 -683.45 423.00 - 785.00 415.98 -772.52 470.60 -874.00 57.00 - 107.00 106.71 -198.17 111.11 -206.35 632.53 - 1175.00 0.10 -0.19 1.81 -3.36 1.10 -2.05 2.20 -4.09 A6-2

TABLE A-6. Department of Energy's Mixed Analyte Performance Evaluation Program (MAPEP)a.

Concentration b Known Control Lab Codec Date Analysis Laboratory result Activity Limits d Acceptance STAP-1 100 STAP-1100 STAP-1100 STAP-1 100 STAP-1 100 STAP-1 100 STAP-1100 e STAP-1101 STAP-1101 STW-1 102 STW-1102 STW-1103 STW-1103 STW-1103 STW-1103 STW-1103 STW-1 103 STW-1103 STW-1103 e STW-1 103 STW-1 103 STW-1 103 STW-1 103 STW-1103 STW-1103 STW-1103 STW-1103 07/01/06 07/01/06 07/01/06 07/01/06 07/01/06 07/01/06 07/01/06 07/01/06 07/01/06 07/01/06 07/01/06 07/01/06 07/01/06 07/01/06 07/01/06 07/01/06 07/01/06 07/01/06 07/01/06 07/01/06 07/01/06 07/01/06 07/01/06 07/01/06 07/01/06 07/01/06 07/01/06 Cs-1 37 Mn-54 Pu-238 Sr-90 U-233/4 U-238 Zn-65 Gr. Alpha Gr. Beta Gr. Alpha Gr. Beta Am-241 Co-57 Co-60 Cs-1 34 Cs-1 37 Fe-55 H-3 Mn-54 Ni-63 Pu-238 Pu-239/40 Sr-90 Tc-99 U-233/4 U-238 Zn-65 1.64 +/- 0.08 1.76 +/- 0.18 0.09 +/- 0.02 0.66 +/- 0.21 0.15 +/- 0.02 0.13 +/- 0.02

< 0.07 0.08 +/- 0.03 0.41 +/- 0.05 1.81 1.92 0.12 0.62 0.13 0.14 0.00 0.29 0.36 1.26 - 2.35 1.34 - 2.50 0.08 -0.15 0.43 - 0.81 0.09 -0.17 0.10 -0.18 0.00 - 0.58 0.18 -0.54 0.76 +/- 0.07 1.23 +/- 0.06 1.86 +/- 0.09 224.10 +/- 1.20 49.40 +/- 0.50 112.70 +/- 0.90 206.60 +/- 1.40 138.40 +/- 5.40 446.50 +/- 11.80

< 0.30 116.70 +/- 3.60 1.27 +/- 0.07 1.67 +/- 0.08 16.40 +/- 1.90 29.40 +/- 1.10 1.97 +/- 0.08 1.97 +/- 0.08 192.50 +/- 2.40 1.03 1.03 2.31 213.08 47.50 112.82 196.14 165.40 428.85 0.00 118.62 1.39 1.94 15.69 27.15 2.15 2.22 176.37 0.00 -2.07 0.52 -1.54 1.62 -3.00 149.16 -277.00 33.20 -61.80 78.97 - 146.66 137.30 -254.98 115.80 -215.00 300.20 -557.50 83.03 -154.21 0.97 -1.81 1.36 -2.52 10.98 -20.40 19.00 -35.29 1.50 -2.80 1.55 -2.89 123.46 -229.28 Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass 8 Results obtained by Environmental, Inc., Midwest Laboratory as a participant in the Department of Energy's Mixed Analyte Performance Evaluation Program, Idaho Operations office, Idaho Falls, Idaho Results are reported in units of Bq/kg (soil), Bq/L (water) or Bq/total sample (filters, vegetation).

Laboratory codes as follows: STW (water), STAP (air filter), STSO (soil), STVE (vegetation).

d MAPEP results are presented as the known values and expected laboratory precision (1 sigma, I determination) and control limits as defined by the MAPEP.

e Included in the MAPEP as a false positive.

f Difficulties with the analyses for transuranics isotopes in solid samples (Filters, Soil and vegetation),

were attributed to incomplete dissolution of the samples. Soil samples were repeated, results of reanalyses:

Pu-238, 53.1 +/- 5.3 bq/kg. Pu-239/240, 42.4 +/- 4.7 bq/kg. U-233/4, 33.3 +/- 3.5 bq/kg. U-238, 35.5 +/- 3.6 bq/kg.

The July vegetation sample was provided in two separate geometries, (100 ml. and 500 ml.). Results reported here used the 500 ml. standard size geometry. Results for the 100 ml. geometry showed approximately a 15% higher bias.

A6-3

APPENDIX B DATA REPORTING CONVENTIONS B-1

APPENDIX B DATA REPORTING CONVENTIONS B-1

Data Reportina Conventions 1.0. All activities, except gross alpha and gross beta, are decay corrected to collection time or the end of the collection period.

2.0. Single Measurements Each single measurement is reported as follows:

x +/- s where:

x = value of the measurement; s = 2a counting uncertainty (corresponding to the 95% confidence level).

In cases where the activity is less than the lower limit of detection L, it is reported as: < L, where L = the lower limit of detection based on 4.66a uncertainty for a background sample.

3.0. Duplicate analyses 3.1 Individual results: For two analysis results; x, +/- si and x2 +/-"S2 Reported result:

x +/- s; where x = (1/2) (x1 + x2) and s = (1/2)

+S2 3.2.

Individual results:

< L1, < L2 Reported result: < L, where L = lower of Li and L2 3.3.

Individual results:

x +/- s, < L Reported result:

x +/- s if x ? L; < otherwise.

4.0. Computation of Averages and Standard Deviations 4.1 Averages and standard deviations listed in the tables are computed from all of the individual measurements over the period averaged; for example, an annual standard deviation would not be the average of quarterly standard deviations. The average x and standard deviation s of a set of n numbers xi, x2... xn are defined as follows:

1x-x 2

n~.

n-i 4.2 Values below the highest lower limit of detection are not included in the average.

4.3 If all values in the averaging group are less than the highest LLD, the highest LLD is reported.

4.4 If all but one of the values are less than the highest LLD, the single value x and associated two sigma error is reported.

4.5 In rounding off, the following rules are followed:

4.5.1. If the number following those to be retained is less than 5, the number is dropped, and the retained number s are kept unchanged. As an example, 11.443 is rounded off to 11.44.

4.5.2. If the number following those to be retained is equal to or greater than 5, the number is dropped and the last retained number is raised by 1. As an example, 11.445 is rounded off to 11.45.

B-2

Table 4.5 Radiological Environmental Monitoring Program Summary Name of Facility Location of Facility Davis-Besse Nuclear Power Station Ottawa, Ohio

( County, State)

Docket No.

50-346 Reporting Period January-December, 2006 Indicator Location with Highest Control Number Sample Type and Locations Annual Mean Locations Non-Type Number of LLDb Mean (F)c Mean (F)c Mean (F)c Routine (Units)

Analyses' Rangec Locationd Range' Rangec Results' Airborne GB 520 0.005 0.023 (312/312)

Site Boundary 0.024 (52/52) 0.023 (208/208) 0 Particulates (0,007-0.053) 0.6 mi. ENE (0.009-0.053)

(0.008-0.046)

(pCi/m 3)

Sr-89 0.0011

< LLD

< LLD 0

Sr-90 0.0006

< LLD

< LLD 0

GS 40 Be-7 0.015 0.077 (24/24)

T-4, Site Boundary 0.083 (4/4) 0.072 (16/16) 0 (0.050-0.104) 0.8 mi. S (0.071-0.104)

(0.036-0.110)

K-40 0.043

< LLD

< LLD 0

Nb-95 0.0044

< LLD

< LLD 0

Zr-95 0.0048

< LLD

<- LLD 0

Ru-103 0.0028

< LLD

< LLD 0

Ru-106 0.0096

< LLD

< LLD 0

Cs-134 0.0015

< LLD

< LLD 0

Cs-137 0.0014

< LLD

< LLD 0

Ce-141 0.0033

< LLD

< LLD 0

Ce-144 0.0069

< LLD

< LLD 0

Airborne Iodine 1-131 520 0.07

< LLD

< LLD 0

(pCi/m 3)

TLD (Quarterly)

Gamma 350 1.0 15.1 (307/307)

T-8, Farm 22.6 (4/4) 16.2 (43/43) 0 (mR/91 days)

(7.5-23.7) 2.7 mi. WSW (20.9-23.7)

(12.0-20.0)

TLD (Quarterly)

Gamma 4

1.0 7.4 (4/4)

None 0

(mRJ91 days)

(6.8-8.6)

(Shield)

TLD (Annual)

Gamma 86 1.0 57.6 (76/76)

T-8, Farm 90.1 (1/1) 63.6 (10/10) 0 (mR/365 days)

(35.7-90.1) 2.7 mi. WSW (49.2-81.2)

TLD (Annual)

Gamma 1

1.0 25.4(1/1)

None 0

(mR/365 days)

(Shield)

Table 4.5 Radiological Environmental Monitoring Program Summary Name of Facility Location of Facility Davis-Besse Nuclear Power Station Ottawa, Ohio Docket No.

50-346 Reporting Period January-December, 2006

( County, State )

Indicator Location with Highest Control Number Sample Type and Locations Annual Mean Locations Non-Type Number of LLDb Mean (F)c Mean (F)c Mean (F)

Routine (Units)

Analyses' Rangec Locationd Rangec RangeC Results' Treated GB (TR) 48 1.0 2.0 (24/24)

T-22, Carroll Twp.

2.1 (12112) 1.9 (24/24) 0 Surface Water (1.1-4.3)

WTP, 3.0 mi. NW (1.1-4.3)

(0.8-3.1)

(pCi/L)

H-3 16 330

< LLD

< LLD 0

Sr-89 16 1.4

< LLD

< LLD 0

Sr-90 16 0.6

< LLD

< LLD 0

GS 16 Mn-54 15

< LLD

< LLD 0

Fe-59 30

< LLD

< LLD 0

Co-58 15

< LLD

< LLD 0

Co-60 15

< LLD

< LLD 0

Zn-65 30

< LLD

< LLD 0

Zr-Nb-95 15

< LLD

< LLD 0

Cs-134 10

< LLD

< LLD 0

Cs-137 10

< LLD

< LLD 0

Ba-La-140 15

< LLD

< LLD 0

Untreated GB (TR) 60 1.0 2.4 (36/36)

T-3, Site Boundary 2.9 (12/12) 2.2 (24/24) 0 Surface Water (1.1-5.5) 1.4 mi. ESE (2.2-5.5)

(1.3-4.3)

(pCi/L)

H-3 60 330

< LLD

< LLD 0

Sr-89 20 1.1

< LLD

< LLD 0

Sr-90 20 0.7

< LLD

< LLD 0

GS 60 Mn-54 15

< LLD

< LLD 0

Fe-59 30

< LLD

< LLD 0

Co-58 15

< LLD

< LLD 0

Co-60 15

< LLD

< LLD 0

Zn-65 30

< LLD

< LLD 0

Zr-Nb-95 15

< LLD

< LLD 0

Cs-134 10

< LLD

< LLD 0

Cs-137 10

< LLD

< LLD 0

Ba-La-140 15

< LLD

< LLD 0

Table 4.5 Radiological Environmental Monitoring Program Summary Name of Facility Location of Facility Davis-Besse Nuclear Power Station Ottawa. Ohio Docket No.

50-346 Reporting Period January-December, 2006

( County, State )

Indicator Location with Highest Control Number Sample Type and Locations Annual Mean Locations Non-Type Number of LLDb Mean (F)c Mean (F)c Mean (F)c Routine (Units)

Analysesa Rangec Location" Rangec Rangec Resultse Airborne GB 520 0.005 0.023 (312/312)

Site Boundary 0.024 (52/52) 0.023 (208/208) 0 Particulates (0.007-0.053) 0.6 mi. ENE (0.009-0.053)

(0.008-0.046)

(pCi/m 3 )

Sr-89 0.0011

< LLD

< LLD 0

Sr-90 0.0006

< LLD

< LLD 0

GS 40 Be-7 0.015 0.077 (24/24)

T-4, Site Boundary 0.083(4/4) 0.072 (16/16) 0 (0.050-0.104) 0.8 mi. S (0.071-0.104)

(0.036-0.110)

K-40 0.043

< LLD

< LLD 0

Nb-95 0.0044

< LLD

< LLD 0

Zr-95 0.0048

< LLD

< LLD 0

Ru-103 0.0028

< LLD

< LLD 0

Ru-1 06 0.0096

< LLD

< LLD 0

Cs-134 0.0015

< LLD

< LLD 0

Cs-137 0.0014

< LLD

< LLD 0

Ce-141 0.0033

< LLD

< LLD 0

Ce-144 0.0069

< LLD

< LLD 0

Airborne Iodine 1-131 520 0.07

< LLD

< LLD 0

(pCi/m 3 )

TLD (Quarterly) Gamma 350 1.0 15.1 (307/307)

T-8, Farm 22.6 (4/4) 16.2 (43143) 0 (mR/91 days)

(7.5-23.7) 2.7 mi. WSW (20.9-23.7)

(12.0-20.0)

TLD (Quarterly)

Gamma 4

1.0 7.4 (4/4)

None 0

(mRJ91 days)

(6.8-8.6)

(Shield)

TLD (Annual)

Gamma 86 1.0 57.6 (76/76)

T-8, Farm 90.1 (1/1) 63.6 (10/10) 0 (mRI365 days)

(35.7-90.1) 2.7 mi. WSW (49.2-81.2)

TLD (Annual)

Gamma 1

1.0 25.4(1/1)

None 0

(mR/365 days)

(Shield)

Table 4.5 Radiological Environmental Monitoring Program Summary Name of Facility Location of Facility Davis-Besse Nuclear Power Station Ottawa, Ohio

( County, State)

Docket No.

50-346 Reporting Period January-December, 2006 Indicator Location with Highest Control Number Sample Type and Locations Annual Mean Locations Non-Type Number of LLDb Mean (F)c Mean (F)c Mean (F)c Routine (Units)

Analyses' Rangec Locationd Rangec Range' Results' Milk (pCi/L) 1-131 12 0.4 none

< LLD 0

Sr-89 12 0.8 rfone

< LLD 0

Sr-90 12 0.5 none T-24, Sandusky 1.0 (8/12) 1.0 (8/12) 0 21.0 mi. SE (0.8-1.4)

(0.8-1.4)

GS 12 K-40 100 none T-24, Sandusky 1316 (12/12) 1316 (12/12) 0 21.0 mi. SE (1229-1414)

(1229-1414)

Cs-134 5.2 Cs-137 6.5 none

< LLD 0

Ba-La-140 7.8 none

< LLD 0

(g/L)

Ca 12 0.50 none T-24, Sandusky 1.14 (12/12) 1.14 (12/12) 0 21.0 mi. SE (0.75-1.51)

(0.75-1.51)

(g/L)

K (stable) 12 none T-24, Sandusky 1.52 (12/12) 1.52 (12/12) 0 21.0 mi. SE (1.42-1.63)

(1.42-1.63)

(pCi/g)

Sr-90/Ca 12 none T-24, Sandusky 0.85 (10/12) 0.85 (10/12) 0 21.0 mi. SE (0.40-1.87)

(0.40-1.87)

(pCi/g)

Cs-137/K 12 none

< LLD 0

Ground Water GB (TR) 8 2.2 2.5 (2/4)

T-27, Crane Creek 4.1 (1/4) 4.1 (1/4)

(pCi/L)

(2.5-2.5)

S.P., 5.8 mi. WNW H-3 8

330

< LLD

< LLD 0

Sr-89 8

0.9

< LLD

< LLD 0

Sr-90 8

0.5

< LLD

< LLD 0

GS Mn-54 15

< LLD

< LLD 0

Fe-59 30

< LLD

< LLD 0

Co-58 15

< LLD

< LLD 0

Co-60 15

< LLD

< LLD 0

Zn-65 30

< LLD

< LLD 0

Zr-95 15

< LLD

< LLD 0

Cs-134 10

< LLD

< LLD 0

Cs-137 10

< LLD

< LLD 0

Ba-La-140 15

< LLD

< LLD 0

Table 4.5 Radiological Environmental Monitoring Program Summary Name of Facility Location of Facility Davis-Besse Nuclear Power Station Ottawa, Ohio Docket No.

50-346 Reporting Period January-December, 2006

( County, State )

Indicator Location with Highest Control Number Sample Type and Locations Annual Mean Locations Non-Type Number of LLDb Mean (F)c Mean (F)c Mean (F)c Routine (Units)

Analyses' Range' Locationd Rangec Rangec Resultse Meat (Wild)

GS 2

(pCi/g wet)

K-40 0.10 2.28 (1/1)

T-210, roving 2.69 (1/1) 2.69 (1/1) 0 offsite location Nb-95 0.016

< LLD

< LLD 0

Zr-95 0.018

< LLD

< LLD 0

Ru-103 0.015

< LLD

< LLD 0

Ru-106 0.061

< LLD

< LLD 0

Cs-134 0.006

< LLD

< LLD 0

Cs-137 0.005

< LLD

< LLD 0

Ce-141 0.026

< LLD

< LLD 0

Ce-144 0.069

< LLD

< LLD 0

Fruits and Sr-89 3

0.004

< LLD

< LLD 0

Vegetables Sr-90 3

0.002

< LLD T-209, Roving 0.003 (1/2) 0.003 (1/2) 0 (pCi/g wet)

Off-site location 1-131 3

0.033

< LLD

< LLD 0

GS 3

K-40 0.50 1.34 (2/2)

T-25, Residence 1.37 (1/1) 0.95 (1/1) 0 (1.31 - 1.37) 1.6 mi. S Nb-95 0.011

< LLD

< LLD 0

Zr-95 0.016

< LLD

< LLD 0

Cs-134 0.007

< LLD

< LLD 0

Cs-137 0.009

< LLD

< LLD 0

Ce-1 41 0.029

< LLD

< LLD 0

Ce-144 0.091

< LLD

< LLD 0

Broad Leaf Sr-89 9

0.004

< LLD

< LLD 0

Vegetation Sr-90 9

0.002 0.002 (1/6)

T-19, Farm 0.002 (1/4)

< LLD 0

(pCi/g wet) 0.68 mi. W 1-131 9

0.025

< LLD

< LLD 0

GS 9

K-40 0.50 2.04 (6/6)

T-227, Roving 2.12 (2/2) 1.77 (3/3) 0 (1.91-2.17)

Off-site location (2.06-2.17)

(1.71-1.85)

Nb-95 0.021

< LLD

< LLD 0

Zr-95 0.036

< LLD

< LLD 0

Cs-134 0.011

< LLD

< LLD 0

Cs-137 0.012

< LLD

< LLD 0

Ce-141 0.024

< LLD

< LLD 0

Ce-144 0.14

< LLD

< LLD 0

Table 4.5 Radiological Environmental Monitoring Program Summary Name of Facility Location of Facility Davis-Besse Nuclear Power Station Ottawa, Ohio Docket No.

50-346 Reporting Period January-December, 2006

( County, State )

Indicator Location with Highest Control Number Sample Type and Locations Annual Mean Locations Non-Type Number of LLD' Mean (F)c Mean (F)c Mean (F)c Routine (Units)

Analyses' Range' Locationd Ranglec Range' Resultse Animal /

GS 3

Wildlife Feed Be-7 0.27 0.30 (1/2)

T-31, Roving 0.30(1/1)

< LLD 0

(pCi/g wet)

On-site location K-40 0.10 2.15 (2/2)

T-31, Roving 2.74(1/1) 1.48(1/1) 0 (1.55-2.74)

On-site location Nb-95 0.033

< LLD

< LLD 0

Zr-95 0.038

< LLD

< LLD 0

Ru-103 0.030

< LLD

< LLD 0

Ru-106 0.13

< LLD

< LLD 0

Cs-134 0.017

< LLD

< LLD 0

Cs-137 0.015

< LLD

< LLD 0

Ce-141 0.078

< LLD

< LLD 0

Ce-144 0.13

< LLD

< LLD 0

Soil GS 10 (pCi/g dry)

Be-7 0.67 1.09 (1/6)

T-4, Site Boundary 1.09(1/1)

< LLD 0

0.8 mi. S K-40 0.10 13.35 (6/6)

T-8, Farm 25.26(1/1) 16.74 (4/4) 0 (6.17-25.26) 2.7 mi. WSW (10.53-22.45)

Nb-95 0.11

< LLD

< LLD 0

Zr-95 0.13

< LLD

< LLD 0

Ru-103 0.10

< LLD

< LLD 0

Ru-106 0.41

< LLD

< LLD 0

Cs-1 34 0.072

< LLD

< LLD 0

Cs-137 0.096 0.15 (3/6)

T-12, Water Treatment 0.22 (1/1) 0.22 (2/4)

(0.13-0.19)

Plant, 23.5 mi. WNW (0.21-0.22) 0 Ce-141 0.17

< LLD

< LLD 0

Ce-144 0.32

< LLD

< LLD 0

Table 4.5 Radiological Environmental Monitoring Program Summary Name of Facility Location of Facility Davis-Besse Nuclear Power Station Ottawa, Ohio

( County, State)

Docket No.

50-346 Reporting Period January-December, 2006 Indicator Location with Highest Control Number Sample Type and Locations Annual Mean Locations Non-Type Number of LLDb Mean (F)'

Mean (F)'

Mean (F)'

Routine (Units)

Analyses" Ranger Locationd Rangec Range' Results' Milk (pCi/L) 1-131 12 0.4 none

< LLD 0

Sr-89 12 0.8 none

< LLD 0

Sr-90 12 0.5 none T-24, Sandusky 1.0(8/12) 1.0 (8/12) 0 21.0 mi. SE (0.8-1.4)

(0.8-1.4)

GS 12 K-40 100 none T-24, Sandusky 1316 (12/12) 1316 (12/12) 0 21.0 mi. SE (1229-1414)

(1229-1414)

Cs-134 5.2 Cs-137 6.5 none

< LLD 0

Ba-La-140 7.8 none

< LLD 0

(g/L)

Ca 12 0.50 none T-24, Sandusky 1.14 (12/12) 1.14 (12/12) 0 21.0 mi. SE (0.75-1.51)

(0.75-1.51)

(g/L)

K (stable) 12 none T-24, Sandusky 1.52 (12/12) 1.52 (12/12) 0 21.0 mi. SE (1.42-1.63)

(1.42-1.63)

(pCi/g)

Sr-90/Ca 12 none T-24, Sandusky 0.85 (10/12) 0.85 (10/12) 0 21.0 mi. SE (0.40-1.87)

(0.40-1.87)

(pCi/g)

Cs-137/K 12 none

< LLD 0

Ground Water GB (TR) 8 2.2 2.5 (2/4)

T-27, Crane Creek 4.1 (1/4) 4.1 (1/4)

(pCi/L)

(2.5-2.5)

S.P., 5.8 mi. WNW H-3 8

330

< LLD

< LLD 0

Sr-89 8

0.9

< LLD

< LLD 0

Sr-90 8

0.5

< LLD

< LLD 0

GS Mn-54 15

< LLD

< LLD 0

Fe-59 30

< LLD

< LLD 0

Co-58 15

< LLD

< LLD 0

Co-60 15

< LLD

< LLD 0

Zn-65 30

< LLD

< LLD 0

Zr-95 15

< LLD

< LLD 0

Cs-134 10

< LLD LLD 0

Cs-137 10

< LLD

< LLD 0

Ba-La-140 15

< LLD

< LLD 0

Table 4.5 Radiological Environmental Monitoring Program Summary Name of Facility Location of Facility Davis-Besse Nuclear Power Station Ottawa, Ohio

( County, State)

Docket No.

50-346 Reporting Period January-December, 2006 Indicator Location with Highest Control Number Sample Type and Locations Annual Mean Locations Non-Type Number of LLDb Mean (F)'

Mean (F)c Mean (F)f Routine (Units)

Analyses" Rangec Locationd Range' Rangec Results' Meat (Wild)

GS 2

(pCi/g wet)

K-40 0.10 2.28 (1/1)

T-210, roving 2.69 (1/1) 2.69 (1/1) 0 offsite location Nb-95 0.016

< LLD

< LLD 0

Zr-95 0.018

< LLD

< LLD 0

Ru-103 0.015

< LLD

< LLD 0

Ru-1 06 0.061

< LLD LLD 0

Cs-134 0.006

< LLD

< LLD 0

Cs-137 0.005

< LLD

< LLD 0

Ce-141 0.026

< LLD

< LLD 0

Ce-144 0.069

< LLD

< LLD 0

Fruits and Sr-89 3

0.004

< LLD

< LLD 0

Vegetables Sr-90 3

0.002

< LLD T-209, Roving 0.003 (1/2) 0.003 (1/2) 0 (pCi/g wet)

Off-site location 1-131 3

0.033

< LLD

< LLD 0

GS 3

K-40 0.50 1.34 (2/2)

T-25, Residence 1.37(1/1) 0.95(1/1) 0 (1.31 - 1.37) 1.6 mi. S Nb-95 0.011

< LLD

< LLD 0

Zr-95 0.016

< LLD

< LLD 0

Cs-1 34 0.007

< LLD

< LLD 0

Cs-1 37 0.009

< LLD

< LLD 0

Ce-141 0.029

< LLD

< LLD 0

Ce-144 0.091

< LLD

< LLD 0

Broad Leaf Sr-89 9

0.004

< LLD

< LLD 0

Vegetation Sr-90 9

0.002 0.002 (1/6)

T-19, Farm 0.002 (1/4)

< LLD 0

(pCi/g wet) 0.68 mi. W 1-131 9

0.025

< LLD

< LLD 0

GS 9

K-40 0.50 2.04 (6/6)

T-227, Roving 2.12 (2/2) 1.77 (3/3) 0 (1.91-2.17)

Off-site location (2.06-2.17)

(1.71-1.85)

Nb-95 0.021

< LLD

< LLD 0

Zr-95 0.036

< LLD

< LLD 0

Cs-134 0.011

< LLD

< LLD 0

Cs-137 0.012

< LLD

< LLD 0

Ce-141 0.024

< LLD

< LLD 0

Ce-144 0.14

< LLD

< LLD 0

Table 4.5 Radiological Environmental Monitoring Program Summary Name of Facility Location of Facility Davis-Besse Nuclear Power Station Ottawa, Ohio

( County, State)

Docket No.

50-346 Reporting Period January-December, 2006 Indicator Location with Highest Control Number Sample Type and Locations Annual Mean Locations Non-Type Number of LLDb Mean (F)c Mean (F)c Mean (F)'

Routine (Units)

Analyses' Rangec Locationd Rangec Rangec Resultse Animal /

GS 3

Wildlife Feed Be-7 0.27 0.30 (1/2)

T-31, Roving 0.30(1/1)

< LLD 0

(pCi/g wet)

On-site location K-40 0.10 2.15(2/2)

T-31, Roving 2.74 (1/1) 1.48 (1/1) 0 (1.55-2.74)

On-site location Nb-95 0.033

< LLD

<LLD 0

Zr-95 0.038

< LLD

< LLD 0

Ru-103 0.030

< LLD

< LLD 0

Ru-106 0.13

< LLD

< LLD 0

Cs-134 0.017

< LLD

< LLD 0

Cs-137 0.015

< LLD

< LLD 0

Ce-141 0.078

< LLD

< LLD 0

Ce-144 0.13

< LLD

< LLD 0

Soil GS 10 (pCi/g dry)

Be-7 0.67 1.09 (1/6)

T-4, Site Boundary 1.09(1/1)

< LLD 0

0.8 mi. S K-40 0.10 13.35 (6/6)

T-8, Farm 25.26(1/1) 16.74 (4/4) 0 (6.17-25.26) 2.7 mi. WSW (10.53-22.45)

Nb-95 0.11

< LLD

< LLD 0

Zr-95 0.13

< LLD

< LLD 0

Ru-103 0.10

< LLD

< LLD 0

Ru-106 0.41

< LLD

< LLD 0

Cs-1 34 0.072

< LLD

< LLD 0

Cs-137 0.096 0.15 (3/6)

T-12, Water Treatment 0.22(1/1) 0.22 (2/4)

(0.13-0.19)

Plant, 23.5 mi. WNW (0.21-0.22) 0 Ce-141 0.17

< LLD

< LLD 0

Ce-144 0.32

< LLD

< LLD 0

Table 4.5 Radiological Environmental Monitoring Program Summary Name of Facility Location of Facility Davis-Besse Nuclear Power Station Ottawa, Ohio Docket No.

50-346 Reporting Period January-December, 2006

( County, State )

Indicator Location with Highest Control Number Sample Type and Locations Annual Mean Locations Non-Type Number of LLDb Mean (F)'

Mean (F)c Mean (F)0 Routine (Units)

Analyses' Range' Locationd Range' Rangec Results' Treated GB (TR) 48 1.0 2.0 (24/24)

T-22, Carroll Twp.

2.1 (12/12) 1.9 (24/24) 0 Surface Water (1.1-4.3)

WTP, 3.0 mi. NW (1.1-4.3)

(0.8-3.1)

(pCi/L)

H-3 16 330

< LLD

< LLD 0

Sr-89 16 1.4

< LLD

< LLD 0

Sr-90 16 0.6

< LLD

< LLD 0

GS 16 Mn-54 15

< LLD

< LLD 0

Fe-59 30

< LLD

< LLD 0

Co-58 15

< LLD

< LLD 0

Co-60 15

< LLD

< LLD 0

Zn-65 30

< LLD

< LLD 0

Zr-Nb-95 15

< LLD

< LLD 0

Cs-134 10

< LLD

< LLD 0

Cs-137 10

< LLD

< LLD 0

Ba-La-140 15

< LLD

< LLD 0

Untreated GB (TR) 60 1.0 2.4 (36/36)

T-3, Site Boundary 2.9 (12/12) 2.2 (24/24) 0 Surface Water (1.1-5.5) 1.4 mi. ESE (2.2-5.5)

(1.3-4.3)

(pCi/L)

H-3 60 330

< LLD

< LLD 0

Sr-89 20 1.1

< LLD

< LLD 0

Sr-90 20 0.7

< LLD

< LLD 0

GS 60 Mn-54 15

< LLD

< LLD 0

Fe-59 30

< LLD

< LLD 0

Co-58 15

< LLD

< LLD 0

Co-60 15

< LLD

< LLD 0

Zn-65 30

< LLD

< LLD 0

Zr-Nb-95 15

< LLD

< LLD 0

Cs-134 10

< LLD

< LLD 0

Cs-137 10

< LLD

< LLD 0

Ba-La-140 15

< LLD

< LLD 0

Table 4.5 Radiological Environmental Monitoring Program Summary Name of Facility Location of Facility Davis-Besse Nuclear Power Station Docket No.

50-346 Reporting Period January-December, 2006 Ottawa, Ohio

( County, State )

Indicator Location with Highest Control Number Sample Type and Locations Annual Mean Locations Non-Type Number of LLDb Mean (F)c Mean (F)c Mean (F)c Routine (Units)

Analyses' Rangec Locationd Rangec Range' Resultso Fish GB 6

0.10 3.90 (3/3)

T-33, Lake Erie 3.90 (3/3) 3.17 (3/3) 0 (pCi/g wet)

(3.61-4.10) 1.5 mi. NE (3.61-4.10)

(2.16-3.97)

GS 6

K-40 0.10 3.26 (3/3)

T-33, Lake Erie 3.26 (3/3) 2.89 (3/3) 0 (2.74-3.75) 1.5 mi. NE (2.74-3.75)

(2.72-2.99)

Mn-54 0.029

<LLD

< LLD 0

Fe-59 0.23

< LLD

< LLD 0

Co-58 0.050

< LLD

< LLD 0

Co-60 0.027

< LLD

< LLD 0

Zn-65 0.044

< LLD

< LLD 0

Cs-134 0.050

< LLD

< LLD 0

Cs-1 37 0.020

< LLD

< LLD 0

Shoreline GS 8

Sediments K-40 0.10 10.61 (6/6)

T-4, Site Boundary 11.57 (2/2) 9.72 (2/2) 0 (pCi/g dry)

(6.73-12.93) 0.8 mi. S (10.57-12.56)

(9.31-10.13)

Mn-54 0.026

< LLD

< LLD 0

Co-58 0.037

< LLD

< LLD 0

Co-60 0.023

< LLD

< LLD 0

Cs-134 0.029

< LLD

< LLD 0

Cs-137 0.034

< LLD

< LLD 0

2 GB = gross beta, GS = gamma scan.

LLD = nominal lower limit of detection based on a 4.66 sigma counting error for background sample.

c Mean and range are based on detectable measurements only (i.e., >LLD) Fraction of detectable measurements at specified locations is indicated in parentheses (F).

d Locations are specified by station code (Table 4.1) and distance (miles) and direction relative to reactor site..

e Non-routine results are those which exceed ten times the control station value.

4 Table 4.5 Radiological Environmental Monitoring Program Summary Name of Facility Location of Facility Davis-Besse Nuclear Power Station Ottawa, Ohio Docket No.

50-346 Reporting Period January-December, 2006

( County, State )

Indicator Location with Highest Control Number Sample Type and Locations Annual Mean Locations Non-Type Number of LLDb Mean (F)r Mean (F)f Mean (F)

Routine (Units)

Analyses Rangec Locationd Rangec Rangec Results0 Fish GB 6

0.10 3.90 (3/3)

T-33, Lake Erie 3.90 (3/3) 3.17 (3/3) 0 (pCi/g wet)

(3.61-4.10) 1.5 mi. NE (3.61-4.10)

(2.16-3.97)

GS 6

K-40 0.10 3.26 (3/3)

T-33, Lake Erie 3.26 (3/3) 2.89 (3/3) 0 (2.74-3.75) 1.5 mi. NE (2.74-3.75)

(2.72-2.99)

Mn-54 0.029

< LLD

< LLD 0

Fe-59 0.23

< LLD

< LLD 0

Co-58 0.050

< LLD

< LLD 0

Co-60 0.027

< LLD

< LLD 0

Zn-65 0.044

< LLD

< LLD 0

Cs-1 34 0.050

< LLD

< LLD 0

Cs-1 37 0.020

< LLD

< LLD 0

Shoreline GS 8

Sediments K-40 0.10 10.61 (6/6)

T-4, Site Boundary 11.57 (2/2) 9.72 (2/2) 0 (pCi/g dry)

(6.73-12.93) 0.8 mi. S (10.57-12.56)

(9.31-10.13)

Mn-54 0.026

< LLD

< LLD 0

Co-58 0.037

< LLD

< LLD 0

Co-60 0.023

< LLD

< LLD 0

Cs-134 0.029

< LLD

< LLD 0

Cs-137 0.034

< LLD

< LLD 0

GB = gross beta, GS gamma scan.

b LLD = nominal lower limit of detection based on a 4.66 sigma counting error for background sample.

Mean and range are based on detectable measurements only (i.e., >LLD) Fraction of detectable measurements at specified locations is indicated in parentheses (F).

Locations are specified by station code (Table 4.1) and distance (miles) and direction relative to reactor site..

e Non-routine results are those which exceed ten times the control station value.