7/17/2006 10:47:22 AM Core shroud tie rod upper support cracking-informationr request July 17, 2006 To Ram Subbaratnam:

Core shroud tie rod upper support cracking:

Please email to us the GE August 21, 2006 and October 9, 2006 when received by the NRC/Pilgrim; and explain how this specifically is'being dealt with in the re-licensing review and outcome.

Thank-you, Mary Lampert Pilgrim Watch/Duxbury Nuclear Advisory Committee General Information or Other Event Number: 42573 Rep Org: GENERAL ELECTRIC COMPANY Licensee: GENERAL ELECTRIC COMPANY Region: 1 City: WILMINGTON State: NC County:

License #:

Agreement: Y Docket:

NRC Notified By: JASON POST HQ OPS Officer: MIKE RIPLEY Notification Date: 05/12/2006

  • ent.-i-ward_- Core shroud tie rod upper support cracking-informationr request Page_21 Notification Time: 22:36 [ET]

Event Date: 04/24/2006 Event Time: [EDT] -

Last Update Date: 05/12/2006 Emergency Class: NON EMERGENCY 10 CFR Section:

21.21 - UNSPECIFIED PARAGRAPH Person (Organization):

ANTHONY DIMITRIADIS (R1)

JAMES MOORMAN (R2)

RICHARD SKOKOWSKI (R3)

OMID TABATABAI-EMAIL (NRR)

JACK FOSTER (EMAIL) (NRR)

Event Text PART 21 NOTIFICATION - BWR CORE SHROUD TIE ROD UPPER SUPPORT CRACKING "Summary:

GE Energy, Nuclear (GE) has provided core shroud repairs using tie rods to the US BWR plants identified in Attachment 1 [of the Part 21 notification]. Recently it was discovered during an in-vessel visual inspection (IVVI) that tie rod upper supports at Hatch Unit 1 experienced cracking. The apparent root cause is Intergranular Stress Corrosion Cracking (IGSCC) in the Alloy X-750 tie rod upper support material. Alloy X-750 material is susceptible to IGSCC if subjected to sustained, large peak stress conditions. GE opened an internal evaluation to determine if the potential IGSCC in the X-750 tie rod structural components of other BWR shroud repairs designed by GE could be a reportable condition under 10CFR21.

"GE used the criterion provided in the BWR Vessels & Internals Project (BWRVIP-84) for the IGSCC susceptibility assessment of the X-750 components in the tie rod vertical load path. GE has concluded that it is not a reportable condition for the plants that were found to be within or not significantly exceed the BWRVIP-84 criterion. These US plants are identified as 'NR' in Attachment 2 [of the Part 21 notification].

GE determined that two US plants exceed the BWRVIP-84 criterion for the upper supports (in addition to the Hatch Unit 1 as-found condition). GE has not completed the evaluation for these plants to assess if a substantial safety hazard (SSH) exists. These plants have been provided a 60-Day Interim Report Notification under §21.21 (a)(2) and are identified as '60-Day' in Attachment 2 [of the Part 21 notification].

"Safety Basis:

Cracking in the tie rod components made of X-750 may render the tie rod ineffective in maintaining core shroud configuration integrity during postulated accident conditions. Loss of core shroud integrity could impact the ability to maintain adequate core cooling for postulated design basis accident conditions.

This condition would be reportable under 10 CFR 21 as a substantial safety hazard.

"Corrective Action:

The corrective action which has been, is being, or will be taken; the name of the individual or organization responsible for the action; and the length of time that has been or will be taken to complete the action (note, these are actions specifically associated with the identified deviation or failure to comply):

1. A preliminary cause evaluation has been performed. The apparent cause of the cracking is Intergranular Stress Corrosion Cracking (IGSCC). A material sample is being shipped to the GE Vallecitos Nuclear Center for examination to confirm the apparent cause. GE will report the results of the examination by August 21, 2006.
2. The issue has been communicated to the industry through the BWR Owners' Group and the Electric Power Research Institute (EPRI)/BWR Vessel and Internals Project (BWRVIP). The NRC was informed in a NRC management meeting with EPRI and the BWRVIP Executive Oversight Committee at the NRC

I', KentHoward - Core shroud tie rod upper suppoýj st Page 3 Kent ~-Ioward - Core shroud tie rod upper support cracking-informationr request Page 311 offices, Rockville, on March 15, 2006.

3. GE has completed an evaluation of the susceptibility to IGSCC using the BWRVIP-84 criterion.

Determination of whether any possible cracking could lead to a substantial safety hazard (i.e., loss of core shroud configuration integrity during a design basis accident condition) depends upon many factors, including the actual extent of cracking in the repair components. Until inspections are completed, the actual extent of cracking is not known. GE is developing a model to predict the postulated extent of tie rod upper support cracking for tie rods with upper supports made of Alloy X-750. For upper supports that exceed the BWRVIP-84 criteria significantly, the model will be used to postulate the extent of cracking.

This prediction will be used to determine if a substantial safety hazard could exist. GE will report the results of the evaluation by October 9, 2006.

4. The original design basis stress reports will be reviewed to assess the available margin in the primary membrane + bending stress intensities of the upper supports with respect to ASME code allowable values. Where reasonable margin exists in the original design basis code evaluation (an existing margin of approximately 25 % will beconsidered as reasonable margin), the existing margin is deemed adequate to offset any engineering assumptions or judgments used in the original analysis. Where the original margin is less than 25%, further review will be performed (including finite element analysis, if necessary) to confirm that the upper support remains qualified. This review will be completed by October 9, 2006."

Affected US Plants per Attachments 1 and 2 of the Part 21 notification: Clinton, Nine Mile Point 1, Pilgrim, Dresden 2 & 3, Quad Cities 1 & 2, Hatch 1 & 2.

CC:

"Millie Morriison" <millie.morrison@verizon.net>, "Mary Leach" <mldux@adelphia.net>,

"Kevin Craig" <kwcraig@adelphia.net>, "Henry Chang" <tigerami@adelphia.net>, "Barbara Pye"

<bapye @ msn.com>, "Becky Chin" <rebeccajchin @ hotmail.com>, "Sheila Hollis(PlyAttorney)"

<sshollis@duanemorris.com>, "David Lochbaum" <dlochbaum @ucsusa.org>, "Paul Gunter"

<pgunter@nirs.org>, "Molly Bartlett" <mollyhbartlett@hotmail.com>

11 c:\\ternp\\GW}O0001.TMP Mail Envelope Properties (44BBA2EC.6E9: 14 : 42729)

Pagel J1

Subject:

Creation Date From:

Created By:

Core shroud tie rod upper support cracking-informationr request 7/17/2006 10:46:50 AM "lampert" <lampert@ adelphia.net>

lampert @ adelphia.net Recipients nrc.gov TWGWPO02.HQGWDOO1 RXS2 (Ram Subbaratnam) hotmail.com mollyhbartlett CC (Molly Bartlett) rebeccajchin CC (Becky Chin) nirs.org pgunter CC (Paul Gunter) ucsusa.org dlochbaum CC (David Lochbaum) duanemorris.com sshollis CC (Sheila Hollis(PlyAttorney))

msn.com bapye CC (Barbara Pye) adelphia.net tigerami CC (Henry Chang) kwcraig CC (Kevin Craig) mldux CC (Mary Leach) verizon.net millie.morrison CC (Millie Morriison)

Post Office TWGWPO02.HQGWDO01 Route nrc.gov hotmail.com nirs.org ucsusa.org duanemorris.com msn.com

F&A-t(iFIýKGW

ý0006-1--Twff--P-

-P*6e-231 c:\\tem.... GWI....

Q1 TM P..

a,"ge-'+- I7 adelphia.net verizon.net Files Size Date & Time MESSAGE 6071 7/17/2006 10:46:50 AM TEXT.htm 16558 Mime.822 1

Options Expiration Date:

None Priority:

Standard ReplyRequested:

No Return Notification:

None Concealed

Subject:

No Security:

Standard Junk Mail Handling Evaluation Results Message is eligible for Junk Mail handling This message was not classified as Junk Mail Junk Mail settings when this message was delivered Junk Mail handling disabled by User Junk Mail handling disabled by Administrator Junk List is not enabled Junk Mail using personal address books is not enabled Block List is not enabled