Text
Florida Power & Light Company, 6501 S. Ocean Drive, Jensen Beach, FL 34957 0 November 28, 2005 FPL L-2005-237 10 CFR 50.55a 10 CFR 50.36 U. S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, DC 20555 Re: St. Lucie Unit 2 Docket No. 50-389 Refueling Outage SL2-15 Steam Generator Tube Inservice Inspection Special Report Attached is the Steam Generator Tube Inservice Inspection Special Report required by sections 4.4.5.5.b and 6.9.2 of the St Lucie Unit 2 Technical Specifications for the January 2005 refueling outage (SL2-15). The report is to be submitted within one year of completing the refueling outage steam generator inservice inspection.
Should there be any questions, please contact us.
Willia effe rb Vice President St. Lucie Plant WJ/GRM Enclosure A -1(-
an FPL Group company
St. Lucie Unit 2 Docket No. 50-389 L-2005-237 Enclosure Enclosure Steam Generator Tube Inservice Inspection Special Report (98 pages)
FORM NIS-BB Attachment Title Pages 1 S/G 2A - Tubes with bobbin indications 40-100% TW and RPC 23 repairable 2 S/G 2A - Tubes with bobbin indications 20-39% TW 6 3 S/G 2A - Tubes with bobbin indications 1-19 % TW 8 4 S/G 2B - Tubes with bobbin indications 40-100% TW and RPC 24 repairable 5 S/G 2B - Tubes with bobbin indications 20-39% TW 4 6 S/G 2B - Tubes with bobbin indications 1-19 % TW 7 7 S/G 2A - Tubes with bobbin indications 1-39% TW left in service 14 8 S/G 2B - Tubes with bobbin indications 1-39% TW left in service 10 Through Wall (TW) Rotating Pancake Coil (RPC)
St. Lucie Unit 2 Docket No. 50-389 L-2005-237 Enclosure In accordance with Plant Technical Specification Section 4.4.5.5 (b), the attached information provides a summary of the results for the inservice examination of steam generator (S/G) tubing, and is to be submitted to the Commission within 12 months of the examination completion date.
- 1. Inservice examination and plugging of the St. Lucie Unit 2 steam generators was completed between January 11, 2005 and January 29, 2005. The specific scope of examination for all techniques is provided below. This is also shown under Total Tubes Inspected on the attached FORM NIS-BB, Owners' Data Report For Eddy Current Examination Results.
Planned Examination Scope Bobbin colt examination:
- 100% full-length in Rows 3 and higher. Row 1 and 2 examinations were limited to the hot leg and cold leg straight sections.
- Screening of dings/dents <5 volts in straight lengths (including horizontal runs).
+PoinT rotating probe examination:
- 100% of active hot leg tubes +3 inches/-13 inches as referenced from the top of tubesheet
- All cold leg tubes in peripheral high flow regions for foreign object wear +3 inches/-2 inches as referenced from the top of tubesheet
- Full depth tubesheet inspection of all hot & cold leg tubes with no tube expansion
- 35% of Row 1 and 2 U-bends
- All wear indications at the hot leg (H/L) diagonal support structures
- All wear indications at horizontal eggcrate tube supports
- 20% of wear indications at vertical supports in the U-bend region
- 20% of wear indications at the cold leg (C/L) diagonal supports
- Dings/Dents
- All dings/dents between TSH +0.00 inches and 01 H +1.00 inch
- All dings/dents >= 5.00 volts between 01H +1.00 inch and DHB -0.01 inches
- All dings/dents in the H/L and C/L square bends for Rows 19 - 140 e All dings/dents >= 5.00 volts in the horizontal runs of tubes in Rows 19 - 140
- All dings/dents in the U-bend region for tubes in Rows 1 - 18
- 20% of dings/dents > 5.00 volts in the cold leg straight sections Visual Examination
- 100% of all previously installed tube plugs
St. Lucie Unit 2 Docket No. 50-389 L-2005-237 Enclosure
- 5. The attached listings for SIGs 2A and 2B are included as source documents for the preparation of FORM NIS-BB.
- S/G 2A - Tubes with Bobbin Indications 40 - 100% TW and rotating pancake coil (RPC) repairable codes (Attachment 1 )
- S/G 2A - Tubes with Bobbin Indications 20 - 39% TW (Attachment 2)
- S/G 2A - Tubes with Bobbin Indications 1 - 19% TW (Attachment 3)
- S/G 2B - Tubes with Bobbin Indications 40 - 100% TW and RPC repairable codes (Attachment 4)
- S/G 2B - Tubes with Bobbin Indications 20 - 39% TW (Attachment 5)
- S/G 2B - Tubes with Bobbin Indications 1 - 19% TW (Attachment 6)
- S/G 2A - Tubes with Bobbin Indications 1 - 39% TW Left in service (Attachment 7)
- S/G 2B - Tubes with Bobbin Indications 1 - 39% TW Left in service (Attachment 8)
St. Lucie Unit 2 Docket No. 50-389 L-2005-237 Enclosure
.ZJ EWDY,'URREN-TECAMIN'ATitl;N;EsULTS::
Planl: St. Lucle Unit 2 Exam Dalts: January 11. 2005 to January 29. 2005 Total Tues _Total Tubs Tubes as Tubes Tot P*ugged Steam Total Tubes 20%-39% T.W. Preventie Pu~ ue nec Genrerator Inspected TThises TtlTue es ~ ~ Puge ue SInGac (5) C~ro. & Mxal Malnienance (PTP) OutageSG A 7740 233 798(ip 0 798 1489 7539 B 144 35 2 837(4) 1709 4, 00%.C, ,;r&~fA1
,,,......................PthX ,, ,, .,gg r r, Partial U BENDS EGGCRATES Supports Top of Tube Shoot to Total Total Indications Stearn DHB to I to 7 8 and 9 #1 EGGOCRATE Indications >=40% T.W.
Generator DOB (7) (7) (7) 20%-39% Cirh. & Axil 7)(8 _-W _--(5) (7 W-L' CIL. MR Cit. HL CIL.
2 1181 2 1 0 22 0 1208 307 1 3 5 I O O 317 9 1247 9 7 3 15 0 1291M B 176 4 4 2 0 0 0 1868 Total EGOCRATES PaSial Top of Tube Sheet to Indications Total Indications Steatr U 7 Supports #1 EGGCRATE M119' 1%439% Left In U BENDS I to 7 8 a id 9 Sevice for Cycle MM to HIL CIL _ CIL WIL CIL (A (5)
A 383 30 10 10 7 0 1 421 701 B 267 30 21 a 0 0 330 490 Refer to ghe Remarks Section on the Following Page
St. Lucie Uni( 2 Docket No. 5!'-389 L-2005-237 Enclosure zFp, NIS-BB OWNErS EDATA E T FOR DY fENT EXAMINATION RESULt+".
' ' ... M blh provslbnd of the AkMECOD30 b-'toAs RULES - ' ..
' .':,.GURRENT,EXAINATINESUL&' *' . --. .
Plant: St. Lucie Unit 2 Exam Dates: January 11, 2005 to January 29, 2005 Remarks:
(1) Six (6)tubes were plugged due to circumferential hdications at the hot leg expansion ransition hi SG 2A.
(2) Ten (10) tubes were plugged due to circumferential Indications at the hot leg expansion transition in SG 28.
(3) Two (2)tubes were preventalively plugged. One (1)due to the presence of wear (WAR) associated with a PUP at the 1I hot leg eggcrate support. One (1)due to a non-quantiflable Indication (NO) Inthe froespan ragian between the cold leg expansion transition and 1 eggcrate Inwhich RPC results were inconclusive.
(4) The total number of tubes plugged excludes tube R50L132 that was do-plugged and rn-plugged with a Long Poll Plug in both egs as well as t-length tsabilization during this outage.
(5) Percent through-wall penetration Isgivenponly for mechanical wear Indications at structures. (SA) Numbers are cumulative and Include indications In tubes that are plugged for other reasons.
(6) This total Includes One (1) tube, R491L67 that has a SCI indication at TEH +0.32. and Is not counted In any of the categories listed In this section.
(7) The upper number In these live columns represents the number of non-wear type or 3-41%TW Indications reported (SAi, MAI, SCI, etc). The lower number represents the number of mechanical wear Indications reported at the structures that ranged from 20-39% throughwall.
(6) In SG 2A, One (1)tube R47iL77 was reported with a cold leg diagonal strap (DCT) wear Indication measuring 42%
throughwall by bobbin coil and was plugged and One (1)tube was Identified with a single axial Indication (SAI) at the hot leg diagonal top (DHT) and was plugged.
In SG 2B. Nlne () single axial IndIcations (SAt) were reported at the edges of (7)hot leg and (2) cold leg diagonal straps.
Acronyms: SM- Single Axial Indication SCI - Single Circumferential Indication, PP - Preventative Tube Plug. TSH - Hot leg tubesheet Expansion, TSC -Cold leg Tubesheet expanslon VOL - Volumsetrc Indication. PLP - Possitbe Lwse Part. TEH - Tube End Hot, TEC - Tube End Cold
Framatome ANP Inc. 1/22/2005 14:30 Attachm nt I CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 1 of 23 Tubes with Bobbin 40-100% TWD and +Point Vol, Circ and Axial Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 6 4 0.28 81 P 6 SAI 03H -0.17 03H 03H 173 HOT 5803P 0.20 98 P 6 SAI 03H +0.80 03H 03H 173 HOT 5803P 8 4 0.16 81 P 6 SAI 03H -0.42 03H 03H 173 HOT 5803P 0.15 70 P 6 SAI 03H +0.81 03H 03H 173 HOT 5803P 12 4 0.22 109 P 6 SAI 01H +0.88 01H 01H 95 HOT 5803P 22 4 0.43 102 P 6 SAI 02H +0.28 02H 02H 63 HOT 5803P 0.13 92 P 6 SAI 02H +0.89 02H 02H 63 HOT 5803P 12 6 0.50 105 P 6 SAI 03H +0.68 03H 03H 63 HOT 5803P 16 6 0.23 114 P 6 SAI 03H +0.80 03H 03H 63 HOT 5803P 32 6 0.27 105 P 6 SAI 03H +0.81 03H 03H 63 HOT 5803P 7 7 0.19 112 P 6 SAI 03H -0.35 03H 03H 173 HOT 5803P 2 8 0.27 90 P 6 SAI 03H +0.73 03H 03H 69 HOT 5803P 6 8 0.17 57 P 6 SAI 03H -0.35 03H 03H 173 HOT 5803P 0.44 107 P 6 MAI 03H +0.55 03H 03H 173 HOT 5803P 10 8 0.17 77 P 6 SAI 03H +0.86 03H 03H 173 HOT 5803P 7 9 0.18 86 P 6 SAI 01H +0.88 01H 01H 173 HOT 5803P 0.33 117 P 6 MAI 03H +0.87 03H 03H 173 HOT 5803P 0.15 94 P 6 SAI 05H +0.77 05H 05H 173 HOT 5803P 13 9 0.14 64 P 6 SAI 05H -0.17 05H 05H 129 HOT 5803P 0.52 99 P 6 SAI 03H +0.06 03H 03H 63 HOT 5803P 12 10 0.33 102 P 6 SAI 03H +0.42 03H 03H 95 HOT 5803P 0.35 101 P 6 SAI 04H +0.79 04H 04H 63 HOT 5803P 1 11 0.14 64 P 6 SAI 03H +0.85 03H 03H 69 HOT 5803P 9 11 0.32 90 P 6 MAI 03H -0.13 03H 03H 173 HOT 5803P 0.15 46 P 6 SAI 05H +0.54 05H 05H 173 HOT 5803P 13 11 0.22 86 P 6 MAI 03H +0.73 03H 03H 63 HOT 5803P 45 11 0.37 79 P 6 SAI 02H -0.49 02H 02H 63 HOT 5803P 0.29 83 P 6 SAI 04H -0.49 04H 04H 63 HOT 5803P 8 12 0.16 71 P 6 SAI 02H -0.74 02H 02H 173 HOT 5803P 10 12 0.27 83 P 6 SAI 05H -0.50 05H 05H 173 HOT 5803P 7 13 0.16 59 P 6 MAI 03H +0.90 03H 03H 173 HOT 5803P 0.34 85 P 6 SAI 04H +0.75 04H 04H 173 HOT 5803P 13 13 0.21 60 P 6 SAI 07H +0.53 DCB 07H 171 HOT 5602 P 10 14 0.19 79 P 6 SAI 03H +0.64 03H 03H 173 HOT 5803P 7 15 0.17 68 P 6 SAI 02H -0.75 02H 02H 173 HOT 5803P 9 15 0.50 103 P 6 SAI 02H +0.56 02H 02H 173 HOT 5803P 6 16 0.15 100 P 6 SAI 01H +0.87 01H 01H 173 HOT 5803P 0.17 95 P 6 SAI 03H +0.67 03H 03H 173 HOT 5803P 14 16 0.22 109 P 6 SAI 03H +0.83 03H 03H 95 HOT 5803P 0.27 76 P 6 SAI 04H -0.75 04H 04H 63 HOT 5803P 34 16 0.30 83 P 6 SAI 02H +0.89 02H 02H 63 HOT 5803P 66 16 0.36 91 P 6 SAI 03H +0.33 03H 03H 63 HOT 5803P 5 17 0.31 93 P 6 SAI 05H -0.23 05H 05H 173 HOT 5803P 7 17 0.36 106 P 6 MAI 01H +0.45 01H 01H 173 HOT 5803P 0.27 112 P 6 SAI 05H +0.68 05H 05H 173 HOT 5803P 9 17 0.55 112 P 6 SAI 01H +0.31 01H 01H 173 HOT 5803P 0.38 92 P 6 SAI 03H -0.95 03H 03H 173 HOT 5803P 0.41 88 P 6 SAI 03H +0.07 03H 03H 173 HOT 5803P 65 17 0.17 96 P 6 SAI 04H -0.38 04H 04H 63 HOT 5803P 0.23 105 P 6 SAI 02H -0.35 02H 02H 95 HOT 5803P 6 18 0.23 116 P 6 SAI 01H +0.79 01H 01H 173 HOT 5803P 0.17 100 P 6 SAI 02H -0.90 02H 02H 173 HOT 5803P 0.29 101 P 6 SAI 02H +0.33 02H 02H 173 HOT 5803P 8 18 0.25 78 P 6 SAI 02H -0.65 02H 02H 173 HOT 5803P
Framatome ANP Inc. 1/22/2005 14:30 Attachment I CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 2 of 23 Tubes with Bobbin 40-100% TWD and +Point Vol, Circ and Axial Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 10 18 0.28 88 P 6 SAI 01H -0.46 01H 01H 173 HOT 5803=P 0.16 182 P 6 SAI 03H -0.51 03H 03H 173 HOT 5803P 0.20 80 P 6 SAI 03H +0.86 03H 03H 173 HOT 5803P 7 19 0.17 61 P 6 SAI 01H +0.24 01H 01H 173 HOT 5803P 0.21 69 P 6 SAI 02H +0.60 02H 02H 173 HOT 5803P 13 19 0.19 113 P 6 KAI 03H +0.80 03H 03H 155 HOT 5803P 6 20 0.23 94 P 6 SAI 01H +0.21 01H 01H 173 HOT 5803P 0.18 96 P 6 SAI 03H -0.64 03H 03H 173 HOT 5803P 0.37 106 P 6 SAI 03H +0.49 03H 03H 173 HOT 5803P 0.21 111 P 6 SAT 05H +0.69 05H 05H 173 HOT 5803P 10 20 0.32 93 P 6 SAI 03H +0.79 03H 03H 173 HOT 5803P 0.10 85 P 6 SAI 04H -0.92 04H 04H 173 HOT 5803P 8 22 0.18 68 P 6 MAI 02H -0.41 02H 02H 173 HOT 5803P 0.17 93 P 6 SAI 03H +0.78 03H 03H 173 HOT 5803P 0.08 86 P 6 SAI 04H -0.56 04H 04H 173 HOT 5803P 44 22 0.24 84 P 6 SAI 04H -0.85 04H 04H 63 HOT 5803P 0.21 123 P 6 SAI 03H -0.94 03H 03H 95 HOT 5803P 66 22 0.27 102 P 6 SAI 02H -0.46 02H 02H 95 HOT 5803P 0.23 61 P 6 SAI 04H -0.80 04H 04H 95 HOT 5803P 0.20 83 P 6 SAI 06H +0.79 06H 06H 95 HOT 5803P 5 23 0.30 70 P 6 SAI 02H -0.61 02H 02H 173 HOT 5803P 0.26 97 P 6 SAI 03H +0.86 03H 03H 173 HOT 5803P 0.38 95 P 6 SAI 05H +0.69 05H 05H 173 HOT 5803P 7 23 0.15 83 P 6 SAI 01H -0.92 01H 01H 173 HOT 5803P 0.19 63 P 6 SAI 03H +0.84 03H 03H 173 HOT 5803P 0.29 90 P 6 SAI 05H +0.43 05H 05H 173 HOT 5803P 13 23 0.23 139 P 6 MAI 03H +0.71 03H 03H 155 HOT 5803P 47 23 0.31 99 P 6 SAI 03H +0.83 03H 03H 63 HOT 5803P 6 24 0.33 104 P 6 SAI 03H +0.61 03H 03H 173 HOT 5803P 8 24 0.24 80 P 6 MAI 01H -0.97 01H 01H 173 HOT 5803P 0.16 81 P 6 SAI 02H +0.95 02H 02H 173 HOT 5803P 0.13 45 P 6 SAI 03H -0.29 03H 03H 173 HOT 5803P 10 24 0.32 84 P 6 MAI 02H +0.55 02H 02H 173 HOT 5803P 0.14 79 P 6 SAI 05H +0.07 05H 05H 173 HOT 5803P 0.17 86 P 6 SAI 05H +0.54 05H 05H 173 HOT 5803P 0.38 94 P 6 SAI 07H +0.25 07H DHT 173 HOT 5803P 12 24 0.21 72 P 6 SAI 02H -0.70 02H 02H 95 HOT 5803P 0.14 79 P 6 SAI 03H +0.84 03H 03H 63 HOT 5803P 44 24 0.21 108 P 6 SAI 01H -0.61 01H 01H 63 HOT 5803P 46 24 0.29 108 P 6 SAI 03H +0.71 03H 03H 63 HOT 5803P 0.18 88 P 6 SAI 01H +0.83 01H 01H 95 HOT 5803P 7 25 0.15 64 P 6 SAI 01H -0.77 01H 01H 173 HOT 5803P 0.20 93 P 6 SAI 03H +0.87 03H 03H 173 HOT 5803P 0.13 66 P 6 SAI 05H +0.78 05H 05H 173 HOT 5803P 65 25 0.19 76 P 6 SAI 02H -0.82 02H 02H 63 HOT 5803P 0.18 102 P 6 SAI 01H -0.66 01H 01H 95 HOT 5803P 8 26 0.23 53 P 6 SAI 01H -0.69 01H 01H 173 HOT 5803P 0.19 104 P 6 SAI 05H +0.65 05H 05H 173 HOT 5803P 0.16 53 P 6 SAI 07H -0.07 07H DHT 173 HOT 5803P 10 26 0.16 61 P 6 SAI 01H -0.59 01H 01H 173 HOT 5803P 0.25 120 P 6 SAI 03H +0.77 03H 03H 173 HOT 5803P 12 26 0.24 62 P 6 SAI 02H +0.49 02H 02H 95 HOT 5803P 0.39 103 P 6 SAI 03H +0.67 03H 03H 63 HOT 5803P 24 26 0.18 114 P 6 SAI 03H -0.94 03H 03H 95 HOT 5803P
Framatome ANP Inc. 1/22/2005 14:30 Attach-ent I CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 3 of 23 Tubes with Bobbin 40-100% TWD and +Point Vol, Circ and Axial Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 0.18 101 P 6 MAI 05H +0.77 05H 05H 63 HOT 5803P 0.16 80 P 6 SAI 03H -0.16 03H 03H 95 HOT 5803P 0.09 68 P 6 SAI 03H +0.89 03H 03H 95 HOT 5803P 64 26 0.41 103 P 6 SAI 02H +0.59 02H 02H 63 HOT 5803P 0.21 100 P 6 SAI 06H +0.71 06H 06H 63 HOT 5803P 66 26 0.24 93 P 6 SAI 03H +0.84 03H 03H 63 HOT 5803P 0.32 100 P 6 SAI 02H +0.04 02H 02H 95 HOT 5803P 0.20 88 P 6 SAI 02H +0.75 02H 02H 95 HOT 5803P 7 27 0.31 96 P 6 SAI 03H +0.57 03H 03H 173 HOT 5803P 9 27 0.18 108 P 6 SAI 03H +0.87 03H 03H 173 HOT 5803P 15 27 0.36 85 P 6 SAI DHT -0.15 07C 07H 165 HOT 5602P 0.37 105 P 6 MAI 05H +0.64 05H 05H 63 HOT 5803P 61 27 0.24 84 P 6 SAI 04H +0.83 04H 04H 63 HOT 5803P 65 27 0.19 84 P 6 SAI 02H +0.85 02H 02H 63 HOT 5803P 0.31 63 P 6 SAI 03H +0.48 03H 03H 63 HOT 5803P 67 27 0.26 85 P 6 SAI 03H +0.59 03H 03H 63 HOT 5803P 0.24 99 P 6 SAI 02H -0.78 02H 02H 95 HOT 5803P 83 27 0.24 85 P 6 SAI 02H +0.70 02H 02H 129 HOT 5803P 0.33 269 P 6 SAI 02H -0.80 02H 02H 129 HOT 5803P 6 28 0.14 87 P 6 SAI 01H +0.19 01H 01H 173 HOT 5803P 8 28 0.14 149 P 6 SAI 07H +0.90 07H DHT 173 HOT 5803P 10 28 0.34 101 P 6 SAI 01H -0.37 01H 01H 173 HOT 5803P 14 28 0.16 61 P 6 SAI 02H +0.19 02H 02H 95 HOT 5803P 0.38 104 P 6 SAI 03H +0.32 03H 03H 63 HOT 5803P 30 28 0.37 104 P 6 SAI 02H -0.51 02H 02H 155 HOT 5803P 66 28 0.44 99 P 6 MAI 03H +0.90 03H 03H 63 HOT 5803P 0.31 60 P 6 SAI 02H -0.57 02H 02H 95 HOT 5803P 68 28 0.23 85 P 6 SAI 02H +0.81 02H 02H 63 HOT 5803P 76 28 0.28 94 P 6 SAI 02H -0.65 02H 02H 63 HOT 5803P 0.27 106 P 6 SAI 02H +0.81 02H 02H 63 HOT 5803P 0.18 49 P 6 SAI 03H -0.25 03H 03H 63 HOT 5803P 0.17 70 P 6 SAI 04H +0.85 04H 04H 63 HOT 5803P 15 29 0.29 109 P 6 SAI 03H +0.82 03H 03H 63 HOT 5803P 21 29 0.58 101 P 6 SAI 03H +0.63 03H 03H 63 HOT 5803P 0.18 91 P 6 SAI 04H +0.81 04H 04H 63 HOT 5803P 39 29 0.19 97 P 6 SAI 01H -0.69 01H 01H 63 HOT 5803P 69 29 0.28 83 P 6 SAI 02H +0.78 02H 02H 63 HOT 5803P 0.32 79 P 6 SAI 03H +0.73 03H 03H 63 HOT 5803P 87 29 0.22 77 P 6 SAI 03H +0.82 03H 03H 129 HOT 5803P 6 30 0.31 89 P 6 SAI 03H +0.85 03H 03H 173 HOT 5803P 8 30 0.25 105 P 6 SAI 03H +0.79 03H 03H 173 HOT 5803P 10 30 0.24 94 P 6 SAI 01H +0.85 01H 01H 173 HOT 5803P 24 30 0.27 104 P 6 SAI 03H +0.80 03H 03H 63 HOT 5803P 0.36 86 P 6 MAI 05H +0.81 05H 05H 63 HOT 5803P 28 30 0.17 116 P 6 SAI 02H -0.75 02H 02H 63 HOT 5803P 54 30 0.32 83 P 6 SAI 04H +0.71 04H 04H 63 HOT 5803P 0.19 81 P 6 SAI 01H +0.52 01H 01H 95 HOT 5803P 0.17 82 P 6 SAI 02H +0.85 02H 02H 95 HOT 5803P 66 30 0.36 94 P 6 SAI 01H +0.44 01H 01H 63 HOT 5803P 78 30 0.14 89 P 6 SAI 01H +0.82 01H 01H 63 HOT 5803P 9 31 0.14 70 P 6 SAI 03H +0.79 03H 03H 173 HOT 5803P 23 31 0.29 92 P 6 SAI 03H +0.40 03H 03H 63 HOT 5803P 55 31 0.28 104 P 6 SAI 01H -0.34 01H 01H 63 HOT 5803P 67 31 0.28 81 P 6 SAI 02H +0.89 02H 02H 63 HOT 5803P
Framatome ANP Inc. 1/22/2005 14:30 Attacbment I CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 4 of 23 Tubes with Bobbin 40-100% TWD and +Point Vol, Circ and Axial Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 71 31 0.17 68 P 6 SM= 04H +0.80 04H 04H 63 HOT 5803P 24 32 0.16 92 P 6 SAI 01H -0.55 01H 01H 95 HOT 5803P 0.17 58 P 6 SAI 03H +0.93 03H 03H 63 HOT 5803P 32 32 0.23 140 2 SAI 03H -0.35 03H 03H 63 HOT 5803P 66 32 0.41 91 P 6 SAI 05H +0.72 05H 05H 63 HOT 5803P 80 32 0.30 76 P 6 SAI 03H +0.81 03H 03H 63 HOT 5803P 0.17 68 P 6 SAI 02H -0.45 02H 02H 95 HOT 5803P 0.22 78 P 6 SAI 02H +0.63 02H 02H 95 HOT 5803P 82 32 0.29 93 P 6 SAI 02H +0.77 02H 02H 129 HOT 5803P 0.21 71 P 6 SAI 03H +0.93 03H 03H 129 HOT 5803P 11 33 0.16 85 P 6 SAI 01H -0.58 01H 01H 155 HOT 5803P 15 33 0.46 80 P 6 SAI 01H +0.40 01H 01H 63 HOT 5803P 37 33 0.23 68 P 6 SAI 03H +0.65 03H 03H 63 HOT 5803P 71 33 0.25 82 P 6 SAI 02H +0.90 02H 02H 63 HOT 5803P 10 34 0.82 104 P 6 SAI 01H +0.58 01H 01H 173 HOT 5803P 0.17 73 P 6 SAI 07H +0.88 07H DHT 173 HOT 5803P 32 34 0.23 77 P 6 SAI 01H -0.41 01H 01H 95 HOT 5803P 0.34 110 P 6 SAI 03H -0.14 03H 03H 63 HOT 5803P 58 34 0.45 93 P 6 SAI 02H +0.87 02H 02H 129 HOT 5803P 66 34 0.18 86 P 6 SAI 04H +0.74 04H 04H 66 HOT 5803P 76 34 0.54 102 P 6 SAI 03H +0.35 03H 03H 66 HOT 5803P 0.25 101 P 6 SAI 02H -0.70 02H 02H 95 HOT 5803P 0.28 105 P 6 SAI 02H +0.56 02H 02H 95 HOT 5803P 37 35 0.27 68 P 6 SAI 01H +0.80 01H 01H 95 HOT 5803P 0.28 106 P 6 SAI 03H +0.51 03H 03H 63 HOT 5803P 71 35 0.18 76 P 6 SAI 01H -0.82 01H1 01H 66 HOT 5803P 83 35 0.42 96 P 6 SAI 03H -0.12 03H 03H 129 HOT 5803P 0.16 109 P 6 SAI 04H -0.51 04H 04H 129 HOT 5803P 0.21 66 P 6 SAI 04H +0.90 04H 04H 129 HOT 5803P 87 35 0.44 103 P 6 SAI 05H -0.29 05H 05H 129 HOT 5803P 0.25 89 P 6 SAI 06H +0.84 06H 06H 129 HOT 5803P 4 36 0.21 93 P 6 SAI 07H +0.72 07H DHT 173 HOT 5803P 8 36 0.16 90 P 6 SAI 01H +0.68 01H 01H 173 HOT 5803P 24 36 0.16 102 P 6 SAI 05H -0.24 05H 05H 129 HOT 5803P 30 36 0.48 100 P 6 SAI 01H +0.67 01H 01H 63 HOT 5803P 58 36 0.27 80 P 6 SAI 02H +0.79 02H 02H 66 HOT 5803P 76 36 0.14 62 P 6 SAI 01H -0.63 01H 01H 66 HOT 5803P 0.13 108 P 6 SAI 01H -0.38 01H 01H 66 HOT 5803P 0.25 83 P 6 SAI 01H +0.70 01H 01H 66 HOT 5803P 9 37 0.15 72 P 6 SAI 01H +0.27 01H 01H 69 HOT 5803P 65 37 0.17 69 P 6 SAI 02H -0.13 02H 02H 66 HOT 5803P 0.24 78 P 6 SAI 02H +0.78 02H 02H 66 HOT 5803P 0.20 73 P 6 SAI 01H -0.57 01H 01H 95 HOT 5803P 32 38 0.11 85 P 6 SAI 02H -0.67 02H 02H 95 HOT 5803P 0.13 71 P 6 SAI 02H +0.72 02H 02H 95 HOT 5803P 0.32 111 P 6 SAI 03H +0.30 03H 03H 63 HOT 5803P 0.20 92 P 6 SAI 04H -0.16 04H 04H 63 HOT 5803P 0.20 90 P 6 SAI 04H +0.76 04H 04H 63 HOT 5803P 54 38 0.19 93 P 6 SAI 02H +0.79 02H 02H 95 HOT 5803P 0.25 77 P 6 SAI 05H +0.98 05H 05H 95 HOT 5803P 64 38 0.33 102 P 6 SAI 01H -0.52 01H 01H 66 HOT 5803P 76 38 0.27 78 P 6 SAI 03H +0.51 03H 03H 66 HOT 5803P 88 38 0.18 88 P 6 SAI 02H +0.91 02H 02H 129 HOT 5803P 3 39 0.29 61 P 6 MAI 07H +0.25 07H DHT 155 HOT 5803P
Framatome ANP Inc. 1/22/2005 14:30 Attacbment 1 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 5 of 23 Tubes with Bobbin 40-100% TWD and +Point Vol. Circ and Axial Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 71 39 0.41 87 P 6 SAI 03H +0.58 03H 03H 66 HOT 5803P 0.23 72 P 6 SAI 04H +0.79 04H 04H 66 HOT 5803P 0.22 77 P 6 SAI 02H +0.86 02H 02H 95 HOT 5803P 105 39 0.20 72 P 6 SAI 03H +0.94 03H 03H 129 HOT 5803P 10 40 0.14 81 P 6 SAI 01H +0.36 01H 01H 155 HOT 5803P 30 40 0.38 95 P 6 SAI 03H +0.65 03H 03H 63 HOT 5803P 58 40 0.37 100 P 6 MAI 01H -0.69 01H 01H 66 HOT 5803P 74 40 0.24 85 P 6 SAI 03H +0.65 03H 03H 95 HOT 5803P 78 40 0.18 74 P 6 SAI 03H +0.50 03H 03H 66 HOT 5803P 82 40 0.32 98 P 6 SAI 01H -0.36 01H 01H 129 HOT 5803P 0.23 65 P 6 SAI 03H -0.10 03H 03H 129 HOT 5803P 0.27 96 P 6 SAI 03H +0.98 03H 03H 129 HOT 5803P 7 41 0.16 68 P 6 SAI 01H -0.39 01H 01H 155 HOT 5803P 15 41 0.75 100 P 6 SAI 03H +0.71 03H 03H 63 HOT 5803P 17 41 0.21 98 P 6 SAI 07C +0.86 07C 07C 85 COLD 5803P 25 41 0.34 282 P 6 SAI 03H -0.39 03H 03H 63 HOT 5803P 37 41 0.27 103 P 6 SAI 02H +0.13 02H 02H 95 HOT 5803P 0.22 94 P 6 SAI 01H -0.45 01H 01H 63 HOT 5803P 0.28 79 P 6 SAI 03H +0.75 03H 03H 63 HOT 5803P 0.25 108 P 6 MAI 03H -0.24 03H 03H 63 HOT 5803P 41 41 0.34 86 P 6 SAI 01H -0.52 01H 01H 63 HOT 5803P 61 41 0.38 85 P 6 SAI 02H +0.57 02H 02H 66 HOT 5803P 83 41 0.18 80 P 6 SAI 01H -0.74 01H 01H 129 HOT 5803P 6 42 0.34 99 P 6 SAI 01H -0.66 01H 01H 155 HOT 5803P 42 42 0.17 92 P 6 SAI 01H +0.44 01H 01H 63 HOT 5803P 72 42 0.18 92 P 6 SAI 03H +0.41 03H 03H 66 HOT 5803P 76 42 0.26 75 P 6 MAI 03H +0.66 03H 03H 66 HOT 5803P 9 43 0.15 109 P 6 SAI 03H +0.85 03H 03H 155 HOT 5803P 15 43 0.12 31 P 6 SAI 03H -0.22 03H 03H 63 HOT 5803P 37 43 0.43 90 P 6 SAI 02H +0.53 02H 02H 63 HOT 5803P 71 43 0.20 78 P 6 MAI 02H +0.68 02H 02H 66 HOT 5803P 0.14 74 P 6 SAI 04H +0.75 04H 04H 66 HOT 5803P 0.19 66 P 6 SAI 01H +0.09 01H 01H 95 HOT 5803P 0.13 77 P 6 SAI 01H +0.60 01H 01H 95 HOT 5803P 0.21 51 P 6 SAI 03H +0.73 03H 03H 95 HOT 5803P 103 43 0.21 102 P 6 SAI 01H -0.45 01H 01H 129 HOT 5803P 0.29 123 P 6 SAI 01H +0.81 01H 01H 129 HOT 5803P 0.20 71 P 6 SAI 02H -0.41 02H 02H 129 HOT 5803P 4 44 0.18 71 P 6 SAI 06H -0.15 06H 06H 69 HOT 5803P 8 44 0.26 117 P 6 SAI 01H +0.69 01H 01H 155 HOT 5803P 0.16 88 P 6 SAI 01H -0.77 01H 01H 155 HOT 5803P 12 44 0.70 102 P 6 SAI 01H +0.65 01H 01H 63 HOT 5803P 0.22 86 P 6 SAI 01H -0.45 01H 01H 63 HOT 5803P 14 44 0.32 92 P 6 SAI 01H +0.62 01H 01H 95 HOT 5803P 0.13 68 P 6 SAI 03H +0.87 03H 03H 63 HOT 5803P 24 44 0.33 106 P 6 SAI 01H +0.39 01H 01H 63 HOT 5803P 40 44 0.36 100 P 6 SAI 04H +0.86 04H 04H 127 HOT 5803P 0.68 102 P 6 SAI 01H -0.59 01H 01H 63 HOT 5803P 0.30 111 P 6 SAI 01H +0.78 01H 01H 63 HOT 5803P 0.29 96 P 6 MAI 02H +0.71 02H 02H 63 HOT 5803P 0.40 85 P 6 SAI 03H +0.84 03H 03H 63 HOT 5803P 46 44 0.20 77 P 6 SAI 01H -0.41 01H 01H 63 HOT 5803P 0.21 64 P 6 SAI 02H +0.89 02H 02H 63 HOT 5803P 0.30 87 P 6 SAI 03H -0.34 03H 03H 63 HOT 5803P
Framatome ANP Inc. 1/22/2005 14:30 Attachment 1 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 6 of 23 Tubes with Bobbin 40-100% TWD and +Point Vol, Circ and Axial Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 54 44 0.50 92 P 6 SA= 01H -0.45 01H 01H 63 HOT 5803=P 80 44 0.27 83 P 6 SAI 01H +0.03 01H 01H 95 HOT 5803P 0.20 77 P 6 SAI 02H +0.80 02H 02H 66 HOT 5803P 104 44 0.25 89 P 6 SAI 01H -0.20 01H 01H 129 HOT 5803P 7 45 0.25 86 P 6 SAI 07H +0.86 07H DHT 155 HOT 5803P 15 45 0.17 74 P 6 SAI 01H +0.63 01H 01H 95 HOT 5803P 0.24 91 P 6 SAI 02H +0.92 02H 02H 63 HOT 5803P 19 45 0.16 107 P 6 SAI 03H -0.68 03H 03H 63 HOT 5803P 41 45 0.51 90 P 6 SAI 02H +0.56 02H 02H 63 HOT 5803P 55 45 0.29 89 P 6 SAI 01H -0.47 01H 01H 63 HOT 5803P 67 45 0.41 102 P 6 SAI 01H -0.38 01H 01H 66 HOT 5803P 0.18 95 P 6 SAI 01H +0.74 01H 01H 66 HOT 5803P 71 45 0.14 33 P 6 SAI 03H +0.86 03H 03H 66 HOT 5803P 73 45 0.28 82 P 6 SAI 01H -0.56 01H 01H 66 HOT 5803P 103 45 0.21 91 P 6 SAI 02H -0.89 02H 02H 129 HOT 5803P 113 45 0.31 76 P 6 SAI 03H +0.54 03H 03H 129 HOT 5803P 0.13 64 P 6 SAI 03H -0.26 03H 03H 129 HOT 5803P 10 46 0.40 106 P 6 SAI 01H +0.92 01H 01H 155 HOT 5803P 54 46 0.56 104 P 6 SAI 02H +0.35 02H 02H 63 HOT 5803P 27 47 0.42 88 P 6 SAI 01H +0.23 01H 01H 63 HOT 5803P 37 47 0.18 92 P 6 SAI 05H +0.90 05H 05H 63 HOT 5803P 67 47 0.43 106 P 6 SAI 01H -0.14 01H 01H 66 HOT 5803P 75 47 0.31 79 P 6 MAI 05H -0.16 05H 05H 66 HOT 5803P 105 47 0.24 81 P 6 SAI 02H +0.84 02H 02H 129 HOT 5803P 0.29 69 P 6 SAI 03H +0.76 03H 03H 129 HOT 5803P 32 48 0.35 75 P 6 SAI 01H +0.71 01H 01H 63 HOT 5803P 36 48 0.21 76 P 6 MAI 01H +0.80 01H 01H 63 HOT 5803P 35 49 0.26 82 P 6 SAI 02H +0.89 02H 02H 63 HOT 5803P 71 49 0.16 81 P 6 SAI 01H -0.25 01H 01H 95 HOT 5803P 73 49 0.25 89 P 6 SAI 01H -0.63 01H 01H 95 HOT 5803P 8 50 0.68 108 P 6 MAI 02H +0.04 02H 02H 155 HOT 5803P 0.20 114 P 6 SAI 02H -0.81 02H 02H 155 HOT 5803P 82 50 0.27 86 P 6 SAI 02H +0.92 02H 02H 129 HOT 5803P 110 50 0.21 95 P 6 SAI 01H +0.47 01H 01H 129 HOT 5803P 0.18 106 P 6 SAI 01H +0.28 01H 01H 129 HOT 5803P 122 50 0.34 98 P 6 SAI 02H +0.82 02H 02H 129 HOT 5803P 13 51 0.27 115 P 6 SAI 07H +0.97 07H 07H 162 HOT 5602P 41 51 0.24 85 P 6 SAI O1H +0.75 01H 01H 95 HOT 5803P 0.18 115 P 6 SAI 02H +0.91 02H 02H 63 HOT 5803P 69 51 0.12 127 P 6 SAI 03H +0.94 03H 03H 66 HOT 5803P 97 51 0.33 113 P 6 SAI 02H -0.96 02H 02H 129 HOT 5803P 113 51 0.27 104 P 6 SAI 01H -0.54 01H 01H 129 HOT 5803P 8 52 0.17 77 P 6 SAI 05H +0.80 05H 05H 155 HOT 5803P 32 52 0.32 92 P 6 SAI 01H +0.45 01H 01H 63 HOT 5803P 38 52 0.30 72 P 6 SAI 02H +0.90 02H 02H 63 HOT 5803P 82 52 0.42 95 P 6 SAI 01H -0.62 01H 01H 129 HOT 5803P 118 52 0.33 112 P 6 SAI 01H -0.80 01H 01H 129 HOT 5803P 15 53 0.20 115 P 6 SAI 07H -0.32 07H 07H 162 HOT 5602P 43 53 0.79 105 P 1 SCI TSH -0.14 TSH TSH 123 HOT 5803P 97 53 0.25 74 P 6 SAI 01H -0.52 01H 01H 129 HOT 5803P 0.25 98 P 6 SAI 01H +0.84 01H 01H 129 HOT 5803P 8 54 0.24 101 P 6 SAI 05H +0.80 05H 05H 155 HOT 5803P 14 54 0.31 94 P 6 SAI 01H +0.78 01H 01H 63 HOT 5803P 16 54 0.27 121 P 6 SAI 07H +0.22 07C 07H 162 HOT 5602P
Framatome ANP Inc. 1/22/2005 14:30 Attachment 1 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 7 of 23 Tubes with Bobbin 40-100% TWD and +Point Vol. Circ and Axial Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL LEG PROBE 66 54 0.62 94 P 6 SAI 01H -0.31 01H 01H 66 HOT 5803P 96 54 0.22 80 P 6 SAI 01H -0.69 01H 01H 129 HOT 5803P 102 54 0.21 98 P 6 SAI 02H +0.88 02H 02H 129 HOT 5803P 106 54 0.24 102 P 6 SAI 02H +0.87 02H 02H 129 HOT 5803P 67 55 0.54 99 P 6 SAI 01H -0.72 01H 01H 66 HOT 5803P 75 55 0.40 80 P 6 SAI 02H +0.31 02H 02H 66 HOT 5803P 111 55 0.32 100 P 6 SAI 02H +0.74 02H 02H 129 HOT 5803P 6 56 0.23 129 P 6 SAI 07C -0.92 07C 07C 85 COLD 5803P 8 56 0.19 109 P 6 SAI 07H -0.13 07H DHT 155 HOT 5803P 0.30 88 P 6 MAI 07H +0.87 07H DHT 155 HOT 5803P 14 56 0.40 91 P 6 SAI 02H +0.89 02H 02H 63 HOT 5803P 44 56 0.11 141 P 6 SAI TSH +0.22 TSH TSH 123 HOT 5803P 70 56 0.54 82 P 6 SAI 01H -0.60 01H O1H 95 HOT 5803P 80 56 0.37 94 P 6 SAI 02H +0.57 02H 02H 66 HOT 5803P 0.27 89 P 6 SAI 01H -0.78 01H 01H 95 HOT 5803P 82 56 0.29 ill P 6 SAI 04H +0.91 04H 04H 129 HOT 5803P 102 56 0.52 113 P 6 SAI 02H -0.70 02H 02H 129 HOT 5803P 0.14 62 P 6 SAI 02H +0.61 02H 02H 129 HOT 5803P 0.19 70 P 6 SAI 03H -0.04 03H 03H 129 HOT 5803P 106 56 0.31 92 P 6 MAI 01H -0.34 01H 01H 129 HOT 5803P 75 57 0.59 127 P 6 SAI 01H -0.33 01H 01H 95 HOT 5803P 93 57 0.33 103 P 6 MAI 01H -0.47 01H 01H 129 HOT 5803P 103 57 0.35 85 P 6 SAI 05H +0.83 05H 05H 129 HOT 5803P 113 57 0.23 93 P 6 SAI 01H -0.69 01H 01H 129 HOT 5803P 0.34 82 P 6 SAI 03H +0.14 03H 03H 129 HOT 5803P 8 58 0.26 109 P 6 SAI 02H -0.48 02H 02H 155 HOT 5803P 12 58 0.13 87 P 6 SAI 02H +0.84 02H 02H 63 HOT 5803P 16 58 0.17 82 P 6 SAI 02H +0.91 02H 02H 95 HOT 5803P 0.21 77 P 6 SAI 05H -0.18 05H 05H 95 HOT 5803P 0.15 81 P 6 SAI 07H -0.06 07H 07H 63 HOT 5803P 0.30 91 P 6 SAI 07H +0.88 07H 07H 63 HOT 5803P 64 58 0.19 111 P 6 SAI 03H -0.41 03H 03H 66 HOT 5803P 0.18 68 P 6 MAI 03H +0.21 03H 03H 66 HOT 5803P 0.40 104 P 6 SAI 03H +0.82 03H 03H 66 HOT 5803P 102 58 0.18 62 P 6 SAI 01H +0.91 01H 01H 129 HOT 5803P 0.29 98 P 6 SAI 03H +0.64 03H 03H 129 HOT 5803P 0.15 55 P 6 SAI 03H -0.43 03H 03H 129 HOT 5803P 110 58 0.34 97 P 6 SAI 02H +0.70 02H 02H 129 HOT 5803P 0.36 110 P 6 SAI 03H +0.53 03H 03H 129 HOT 5803P 0.27 112 P 6 SAI 03H -0.85 03H 03H 129 HOT 5803P 126 58 0.23 85 P 6 SAI 02H +0.62 02H 02H 179 HOT 5803P 71 59 0.26 92 P 6 SAI 01H +0.92 01H 01H 69 HOT 5803P 101 59 0.27 79 P 6 SAI 04H +0.95 04H 04H 129 HOT 5803P 103 59 0.41 86 P 6 SAI 02H +0.79 02H 02H 129 HOT 5803P 8 60 0.26 106 P 6 SAI 01H +0.89 01H 01H 155 HOT 5803P 0.19 66 P 6 SAI 02H +0.83 02H 02H 155 HOT 5803P 40 60 0.42 92 P 6 SAI 01H -0.12 01H 01H 127 HOT 5803P 0.32 98 P 6 SAI 06H +0.79 06H 06H 127 HOT 5803P 44 60 0.59 98 P 6 MAI 02H -0.63 02H 02H 127 HOT 5803P 110 60 0.36 95 P 6 SAI 02H +0.58 02H 02H 129 HOT 5803P 27 61 0.43 94 P 6 SAI 02H +0.79 02H 02H 127 HOT 5803P 43 61 0.23 79 P 6 SAI 02H +0.76 02H 02H 127 HOT 5803P 103 61 0.63 96 P 6 SAI 01H -0.51 01H 01H 129 HOT 5803P 111 61 0.30 65 P 6 SAI 02H +0.26 02H 02H 129 HOT 5803P
Framatome ANP Inc. 1/22/2005 14:30 Attacbment 1 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 8 of 23 Tubes with Bobbin 40-100% TWD and +Point Vol. Circ and Axial Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 30 62 0.27 80 P 6 SA= 02H +0.81 02H 02H 127 HOT 5803P 40 62 0.30 94 P 6 SAI 01H -0.76 01H 01H 127 HOT 5803P 0.40 89 P 6 SAI 01H +0.36 01H 01H 127 HOT 5803P 0.54 97 P 6 SAI 02H -0.33 02H 02H 127 HOT 5803P 0.33 99 P 6 SAI 02H +0.72 02H 02H 127 HOT 5803P 0.30 92 P 6 SAI 03H +0.41 03H 03H 127 HOT 5803P 70 62 0.25 94 P 6 SAI 02H +0.84 02H 02H 69 HOT 5803P 82 62 0.15 106 P 6 SAI TSH +0.54 TSH TSH 83 HOT 5803P 88 62 0.36 93 P 6 SAI 05H +0.19 05H 05H 129 HOT 5803P 0.19 94 P 6 SAI 05H +0.94 05H 05H 129 HOT 5803P 106 62 0.42 94 P 6 MAI 01H +0.49 01H 01H 129 HOT 5803P 21 63 0.33 97 P 6 SAI 02H +0.52 02H 02H 127 HOT 5803P 0.22 80 P 6 SAI 03H -0.66 03H 03H 127 HOT 5803P 41 63 0.20 82 P 6 SAI 02H +0.81 02H 02H 179 HOT 5803P 43 63 0.18 86 P 6 SAI 01H +0.83 01H 01H 127 HOT 5803P 109 63 0.34 95 P 6 SAI 02H +0.55 02H 02H 129 HOT 5803P 0.16 44 P 6 SAI 02H -0.82 02H 02H 129 HOT 5803P 111 63 0.35 79 P 6 SAI 05H -0.26 05H 05H 129 HOT 5803P 0.14 63 P 6 SAI 05H +0.39 05H 05H 129 HOT 5803P 121 63 0.28 84 P 6 SAI 02H +0.37 02H 02H 129 HOT 5803P 133 63 0.08 98 P 6 SAI 01H -0.99 01H 01H 149 HOT 5803P 34 64 0.24 142 P 6 SAI 02H +0.31 02H 02H 127 HOT 5803P 40 64 0.34 266 P 6 SAI 06H +0.82 06H 06H 127 HOT 5803P 70 64 0.10 75 P 6 SAI 03H -0.01 03H 03H 69 HOT 5803P 0.21 58 P 6 SAI 03H +0.76 03H 03H 69 HOT 5803P 80 64 0.57 95 P 6 SAI 01H +0.02 01H 01H 69 HOT 5803P 88 64 0.28 89 P 6 SAI 01H +0.44 01H 01H 129 HOT 5803P 0.27 80 P 6 SAI 02H +0.89 02H 02H 129 HOT 5803P 50 66 0.37 106 P 6 SAI 01H -0.10 01H 01H 127 HOT 5803P 66 66 0.26 126 P 6 SAI 01H -0.90 O1H 01H 69 HOT 5803P 0.21 86 P 6 SAI 07H +0.76 07H 07H 69 HOT 5803P 88 66 0.22 96 P 6 SAI 02H +0.91 02H 02H 129 HOT 5803P 0.17 49 P 6 SAI 02H -0.69 02H 02H 129 HOT 5803P 0.54 104 P 6 SAI 03H +0.90 03H 03H 129 HOT 5803P 0.38 91 P 6 SAI 01H -0.28 01H 01H 173 HOT 5803P 110 66 0.52 104 P 6 SAI 03H +0.76 03H 03H 129 HOT 5803P 0.37 102 P 6 SAI 05H +0.81 05H 05H 129 HOT 5803P 93 67 0.25 77 P 6 SAI 03H +0.84 03H 03H 129 HOT 5803P 105 67 0.30 78 P 6 SAI 02H -0.94 02H 02H 129 HOT 5803P 0.27 89 P 6 SAI 05H +0.85 05H 05H 129 HOT 5803P 66 68 0.39 109 P 6 SAI 03H -0.48 03H 03H 69 HOT 5803P 0.13 93 P 6 SAI 03H +0.22 03H 03H 69 HOT 5803P 0.17 80 P 6 SAI 03H +0.58 03H 03H 69 HOT 5803P 0.51 110 P 6 SAI 05H +0.27 05H 05H 69 HOT 5803P 88 68 0.37 103 P 6 MAI 01H -0.81 01H 01H 129 HOT 5803P 110 68 0.26 70 P 6 SAI 03H +0.84 03H 03H 129 HOT 5803P 0.27 83 P 6 SAI 05H +0.44 05H 05H 129 HOT 5803P 118 68 0.27 94 P 6 SAI 03H +0.97 03H 03H 129 HOT 5803P 122 68 0.41 78 P 6 SAI 02H +0.69 02H 02H 129 HOT 5803P 0.22 73 P 6 SAI 02H -0.77 02H 02H 129 HOT 5803P 123 69 0.40 102 P 6 SAI 02H +0.81 02H 02H 129 HOT 5803P 0.18 46 P 6 SAI 02H -0.91 02H 02H 129 HOT 5803P 135 69 0.18 142 P 6 SAI 01H -0.75 01H 01H 149 HOT 5803P 70 70 0.18 59 P 6 SAI 05H -0.29 05H 05H 69 HOT 5803P
Framatome ANP Inc. 1/22/2005 14:30 Attachment 1 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 9 of 23 Tubes with Bobbin 40-100% TWD and +Point Vol, Circ and Axial Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL LEG PROBE 0.15 96 P 6 SAI 05H +0.73 05H 05H 69 HOT 5803P 124 70 0.47 89 P 6 MAI 02H +0.63 02H 02H 129 HOT 5803P 55 71 0.47 104 P 6 SAI 01H +0.11 01H 01H 69 HOT 5803P 93 71 0.21 90 P 6 SAI 05H +0.90 05H 05H 153 HOT 5803P 103 71 0.25 31 P 6 SAI 02H +0.71 02H 02H 153 HOT 5803P 72 72 0.19 54 P 6 SAI 02H -0.29 02H 02H 69 HOT 5803P 96 72 0.21 117 P 6 SAI 01H +0.94 01H 01H 153 HOT 5803P 85 73 0.20 41 P 6 SAI 02H +0.85 02H 02H 153 HOT 5803P 103 73 0.30 91 P 6 SAI 01H -0.45 01H 01H 153 HOT 5803P 0.26 91 P 6 SAI 05H +0.98 05H 05H 153 HOT 5803P 50 74 0.26 85 P 6 SAI 05H +0.74 05H 05H 69 HOT 5803P 66 74 0.14 54 P 6 SAI 01H -0.72 01H 01H 69 HOT 5803P 0.38 85 P 6 SAI 01H -0.26 01H 01H 69 HOT 5803P 0.23 112 P 6 SAI 03H -0.71 03H 03H 69 HOT 5803P 0.33 83 P 6 SAI 03H +0.70 03H 03H 69 HOT 5803P 80 74 0.18 52 P 6 SAI 03H -0.88 03H 03H 69 HOT 5803P 0.16 53 P 6 SAI 03H -0.17 03H 03H 69 HOT 5803P 88 74 0.10 102 P 6 SAI TSH +1.11 TSH TSH 72 HOT 5803P 69 75 0.26 102 P 6 SAI 01H +0.80 01H 01H 69 HOT 5803P 0.35 106 P 6 SAI 02H -0.90 02H 02H 69 HOT 5803P 0.57 82 P 6 SAI 02H +0.61 02H 02H 69 HOT 5803P 0.24 76 P 6 SAI 03H +0.78 03H 03H 69 HOT 5803P 85 75 0.22 98 P 6 SAI 05H +0.91 05H 05H 153 HOT 5803P 123 75 0.21 72 P 6 SAI 02H -0.53 02H 02H 129 HOT 5803P 0.36 99 P 6 SAI 03H -0.53 03H 03H 129 HOT 5803P 54 76 0.31 80 P 6 SAI 02H +0.76 02H 02H 69 HOT 5803P 104 76 0.25 82 P 6 SAI 02H +0.84 02H 02H 153 HOT 5803P 110 76 0.21 79 P 6 SAI 03H +0.89 03H 03H 153 HOT 5803P 0.13 77 P 6 SAI 05H +0.80 05H 05H 153 HOT 5803P 124 76 0.25 82 P 6 SAI 02H -0.15 02H 02H 129 HOT 5803P 0.20 77 P 6 SAI 02H +0.79 02H 02H 129 HOT 5803P 132 76 0.20 97 P 6 SAI 02H +0.54 02H 02H 149 HOT 5803P 47 77 1.71 89 P 4 TWD 42 DCT +0.00 TEC TEH 3 HOT 60OUL 65 77 0.22 76 P 6 SAI 04H +0.02 04H 04H 69 HOT 5803P 97 77 0.23 100 P 6 SAI 01H -0.68 01H 01H 153 HOT 5803P 105 77 0.28 105 P 6 SAI 02H +0.77 02H 02H 153 HOT 5803P 0.35 90 P 6 SAI 05H +0.21 05H 05H 153 HOT 5803P 72 78 0.16 87 P 6 SAI TSH +0.50 TSH TSH 60 HOT 5803P 78 78 0.17 108 P 6 SAI TSH +0.16 TSH TSH 59 HOT 5803P 82 78 0.27 94 P 6 SAI 01H -0.85 01H 01H 153 HOT 5803P 106 78 0.19 74 P 6 SAI 01H +0.13 01H 01H 153 HOT 5803P 118 78 0.21 81 P 6 SAI 01H -0.73 01H 01H 132 HOT 5803P 0.14 77 P 6 SAI 01H +0.93 01H 01H 132 HOT 5803P 122 78 0.33 85 P 6 SAI 01H +0.07 01H 01H 129 HOT 5803P 65 79 0.15 67 P 6 SAI TSH +0.52 TSH TSH 60 HOT 5803P 83 79 0.24 84 P 6 SAI 06H +0.83 06H 06H 153 HOT 5803P 87 79 0.38 88 P 6 SAI 01H +0.42 01H 01H 153 HOT 5803P 111 79 0.16 56 P 6 SAI 02H +0.88 02H 02H 153 HOT 5803P 133 79 0.22 108 P 6 SAI 01H +0.50 01H 01H 149 HOT 5803P 54 80 0.24 89 P 6 MAI 05H -0.47 05H 05H 69 HOT 5803P 0.25 106 P 6 SAI 05H +0.77 05H 05H 69 HOT 5803P 74 80 0.15 95 P 6 SAI TSH +0.52 TSH TSH 60 HOT 5803P 98 80 0.35 112 P 6 SAI 05H +0.58 05H 05H 153 HOT 5803P 102 80 0.46 100 P 6 SAI 01H -0.53 01H 01H 170 HOT 5803P
Framatome ANP Inc. 1/22/2005 14:30 Attachbmnt 1 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 10 of 23 Tubes with Bobbin 40-100% TWD and +Point Vol, Circ and Axial Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 0.34 100 P=6 SAI 03H +0.33 03H 03H 153 HOT 5803P 0.35 99 P 6 MAI 05H +0.15 05H 05H 153 HOT 5803P 67 81 0.13 83 P 6 SAI TSH +0.59 TSH TSH 59 HOT 5803P 81 81 0.21 52 P 6 SAI 06H +0.85 06H 06H 153 HOT 5803P 83 81 0.25 79 P 6 SAI 03H -0.51 03H 03H 153 HOT 5803P 95 81 0.25 75 P 6 SAI 01H -0.22 01H 01H 153 HOT 5803P 103 81 0.54 107 P 6 SAI 01H -0.50 01H O1H 153 HOT 5803P 115 81 0.44 104 P 6 SAI 01H -0.71 01H 01H 153 HOT 5803P 0.29 106 P 6 SAI 03H +0.90 03H 03H 153 HOT 5803P 133 81 0.20 42 P 6 SAI 01H -0.95 01H 01H 180 HOT 5803P 0.12 71 P 6 SAI 02H -0.76 02H 02H 180 HOT 5803P 0.19 53 P 6 SAI 02H +0.58 02H 02H 180 HOT 5803P 0.21 79 P 6 SAI 03H +0.83 03H 03H 180 HOT 5803P 66 82 0.16 107 P 6 SAI 06H +0.84 06H 06H 69 HOT 5803P 0.44 96 P 6 SAI 07H -0.62 07H 07H 69 HOT 5803P 0.15 91 P 6 SAI 07H +0.33 07H 07H 69 HOT 5803P 116 82 0.24 117 P 6 SAI 01H +0.83 01H 01H 153 HOT 5803P 0.15 127 P 6 SAI 02H +0.92 02H 02H 153 HOT 5803P 0.19 94 P 6 SAI 03H +0.94 03H 03H 153 HOT 5803P 79 83 0.17 65 P 6 SAI 02H +0.79 02H 02H 69 HOT 5803P 89 83 0.24 103 P 6 SAI 01H +0.56 01H 01H 153 HOT 5803P 131 83 0.29 97 P 6 SAI 01H +0.16 01H 01H 149 HOT 5803P 139 83 0.17 103 P 6 SAI 01H +0.91 01H 01H 149 HOT 5803P 66 84 0.32 93 P 6 SAI 02H -0.27 02H 02H 69 HOT 5803P 0.22 82 P 6 SAI 02H -0.54 02H 02H 69 HOT 5803P 70 84 0.34 106 P 6 SAI 03H -0.11 03H 03H 69 HOT 5803P 0.20 104 P 6 SAI TSH +0.53 TSH TSH 59 HOT 5803P 82 84 0.14 64 P 6 SAI 02H +0.81 02H 02H 153 HOT 5803P 110 84 0.32 94 P 6 SAI 01H -0.30 01H 01H 153 HOT 5803P 114 84 0.24 87 P 6 SAI 01H -0.84 01H 01H 153 HOT 5803P 91 85 0.26 103 P 6 SAI 01H -0.45 01H 01H 178 HOT 5803P 121 85 0.16 78 P 6 SAI 03H -0.29 03H 03H 132 HOT 5803P 123 85 0.31 98 P 6 SAI 01H -0.58 01H 01H 132 HOT 5803P 68 86 0.45 93 P 6 SAI 03H +0.56 03H 03H 69 HOT 5803P 0.20 66 P 6 SAI 04H +0.88 04H 04H 69 HOT 5803P 72 86 0.11 114 P 6 SAI TSH +0.40 TSH TSH 60 HOT 5803P 110 86 0.39 89 P 6 MAI 01H +0.34 01H 01H 149 HOT 5803P 124 86 0.29 81 P 6 SAI 01H -0.32 01H 01H 132 HOT 5803P 103 87 0.31 92 P 6 SAI 01H +0.24 01H 01H 149 HOT 5803P 121 87 0.54 91 P 6 SAI 01H -0.63 01H 01H 153 HOT 5803P 0.21 110 P 6 SAI 01H +0.61 01H 01H 153 HOT 5803P 129 87 0.54 106 P 6 SAI 01H +0.52 01H 01H 153 HOT 5803P 0.17 60 P 6 SAI 05H +0.73 05H 05H 153 HOT 5803P 80 88 0.20 68 P 6 SAI 01H -0.59 01H 01H 69 HOT 5803P 0.52 87 P 6 MAI 01H +0.72 01H O1H 69 HOT 5803P 0.22 64 P 6 SAI 07H +0.67 07H 07H 69 HOT 5803P 114 88 0.36 78 P 6 MAI 01H -0.84 01H 01H 149 HOT 5803P 122 88 0.24 98 P 6 SAI 01H -0.54 01H 01H 153 HOT 5803P 0.16 60 P 6 SAI 01H +0.66 01H 01H 153 HOT 5803P 77 89 0.08 97 P 6 SAI TSH +0.34 TSH TSH 60 HOT 5803P 58 90 0.21 86 P 6 SAI 01H -0.67 01H 01H 69 HOT 5803P 0.20 102 P 6 SAI 01H +0.78 01H 01H 69 HOT 5803P 70 90 0.21 78 P 6 SAI 03H +0.86 03H 03H 69 HOT 5803P 0.25 86 P 6 SAI 05H +0.83 05H 05H 69 HOT 5803P
Framatome ANP Inc. 1/22/2005 14:30 Attachment I CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 11 of 23 Tubes with Bobbin 40-100% TWD and +Point Vol, Circ and Axial Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 80 90 0.26 63 P6 SAI 02H +0.79 02H 02H 69 HOT 5803P 0.33 55 P6 SAI 03H +0.78 03H 03H 69 HOT 5803P 114 90 0.24 86 P6 MAI 01H +0.39 01H 01H 149 HOT 5803P 122 90 0.29 81 P6 SAI 03H +0.83 03H 03H 153 HOT 5803P 49 91 0.39 84 P6 SAI 02H +0.53 02H 02H 69 HOT 5803P 69 91 0.19 74 P6 SAI 01H +0.81 01H 01H 140 HOT 5803P 0.16 75 P6 SAI 01H -0.31 01H 01H 140 HOT 5803P 123 91 0.31 88 P6 SAI 02H +0.92 02H 02H 153 HOT 5803P 52 92 0.26 97 P6 SAI 06H -0.39 06H 06H 69 HOT 5803P 76 92 0.19 84 P6 SAI 05H +0.72 05H 05H 69 HOT 5803P 82 92 0.16 80 P6 SAI 05H +0.89 05H 05H 153 HOT 5803P 86 92 0.28 95 P6 SAI 01H -0.87 01H 01H 153 HOT 5803P 0.27 108 P6 MAI 02H -0.80 TO+1.00 02H 02H 153 HOT 5803P 122 92 0.21 84 P6 MAI 01H -0.77 01H 01H 153 HOT 5803P 49 93 0.28 103 P6 SAI 02H +0.84 02H 02H 69 HOT 5803P 0.45 79 P6 SAI 03H +0.54 03H 03H 69 HOT 5803P 71 93 0.27 105 P6 SAI 03H +0.84 03H 03H 69 HOT 5803P 105 93 0.37 79 P6 SAI 01H +0.44 01H 01H 149 HOT 5803P 121 93 0.29 77 P6 SAI 01H -0.12 01H 01H 149 HOT 5803P 133 93 0.29 104 P6 SAI 01H +0.63 01H 01H 149 HOT 5803P 60 94 0.28 141 P6 SAI 03H -0.21 03H 03H 69 HOT 5803P 92 94 0.33 68 P6 SAI 01H -0.25 01H 01H 153 HOT 5803P 102 94 0.35 92 P6 SAI 02H +0.74 02H 02H 149 HOT 5803P 0.27 84 P6 SAI 02H -0.28 02H 02H 149 HOT 5803P 118 94 0.16 92 P6 SAI 01H -0.04 01H 01H 149 HOT 5803P 0.19 93 P6 MAI 01H +0.85 01H 01H 149 HOT 5803P 124 94 0.30 99 P6 SAI 01H -0.15 01H 01H 149 HOT 5803P 61 95 0.31 82 P6 SAI 05H +0.84 05H 05H 69 HOT 5803P 69 95 0.26 60 P6 SAI 01H -0.80 01H 01H 69 HOT 5803P 103 95 0.41 92 P6 MAI 01H +0.51 01H 01H 149 HOT 5803P 133 95 0.39 98 P6 SAI 02H -0.65 02H 02H 149 HOT 5803P 86 96 0.14 142 P6 SAI 02H +0.78 02H 02H 153 HOT 5803P 116 96 0.25 103 P6 MAI 01H +0.52 01H 01H 149 HOT 5803P 65 97 0.31 98 P6 SAI 01H -0.50 01H 01H 69 HOT 5803P 0.20 82 P6 SAI 01H +0.17 01H 01H 69 HOT 5803P 0.22 92 P6 SAI 01H +0.77 01H 01H 69 HOT 5803P 0.26 95 P6 SAI 06H -0.74 06H 06H 69 HOT 5803P 0.52 88 P6 SAI 06H +0.59 06H 06H 69 HOT 5803P 69 97 0.22 87 P6 SAI 01H -0.38 01H 01H 69 HOT 5803P 0.35 100 P6 SAI 01H +0.76 01H 01H 69 HOT 5803P 0.18 68 P6 SAI 06H -0.91 06H 06H 69 HOT 5803P 77 97 0.15 87 P6 SAI 05H +0.85 05H 05H 69 HOT 5803P 81 97 0.13 122 P6 SAI 04H -0.62 04H 04H 153 HOT 5803P 89 97 0.15 78 P6 SAI 02H +0.91 02H 02H 153 HOT 5803P 103 97 0.47 97 P6 SAI 01H -0.75 01H 01H 149 HOT 5803P 109 97 0.30 102 P6 SAI 02H +0.86 02H 02H 149 HOT 5803P 129 97 0.27 69 P6 MAI 03H +0.91 03H 03H 149 HOT 5803P 133 97 0.22 103 P6 MAI 01H +0.76 01H 01H 149 HOT 5803P 40 98 0.18 114 P6 SAI 06H +0.94 06H 06H 155 HOT 5803P 0.16 97 P6 SAI 06H -0.47 06H 06H 155 HOT 5803P 0.24 62 P6 SAI 07H -0.50 07H 07H 155 HOT 5803P 102 98 0.25 62 P6 SAI 02H +0.07 02H 02H 149 HOT 5803P 59 99 0.29 78 P6 SAI 01H +0.78 01H 01H 69 HOT 5803P 0.14 89 P6 SAI 01H -0.56 01H 01H 69 HOT 5803P
Framatome ANP Inc. 1/22/2005 14:30 Attacbment 1 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 12 of 23 Tubes with Bobbin 40-100% TWD and +Point Vol, Circ and Axial Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 75 99 0.17 68 P 6 SAI 02H = 0.56 02H 02H 69 HOT 5803=P 0.40 101 P 6 SAI 02H +0.83 02H 02H 69 HOT 5803P 0.23 77 P 6 SAI 05H +0.83 05H 05H 69 HOT 5803P 111 99 0.24 83 P 6 SAI 01H +0.29 01H 01H 149 HOT 5803P 133 99 0.43 105 P 6 SAI 01H +0.84 01H 01H 149 HOT 5803P 52 100 0.19 80 P 6 SAI 02H +0.93 02H 02H 150 HOT 5803P 62 100 0.10 110 P 1 SCI TSH +0.08 TSH TSH 97 HOT 5803P 68 100 0.21 86 P 6 SAI 05H +0.77 05H 05H 151 HOT 5803P 86 100 0.18 80 P 6 SAI 05H +0.72 05H 05H 133 HOT 5803P 88 100 0.23 252 P 6 SAI 05H +0.71 05H 05H 133 HOT 5803P 92 100 0.35 90 P 6 SAI 01H +0.59 01H 01H 133 HOT 5803P 98 100 0.28 102 P 6 SAI 01H -0.15 01H 01H 133 HOT 5803P 108 100 0.21 83 P 6 SAI 01H +0.81 01H 01H 136 HOT 5803P 110 100 0.21 52 P 6 SAI 01H -0.66 01H 01H 136 HOT 5803P 118 100 0.21 84 P 6 SAI 01H -0.40 01H 01H 136 HOT 5803P 124 100 0.27 97 P 6 SAI 01H +0.67 01H 01H 136 HOT 5803P 53 101 0.34 96 P 6 SAI 02H +0.71 02H 02H 150 HOT 5803P 0.31 91 P 6 SAI 03H -0.54 03H 03H 150 HOT 5803P 0.30 102 P 6 SAI 04H +0.47 04H 04H 150 HOT 5803P 61 101 0.32 95 P 6 SAI 02H +0.39 02H 02H 151 HOT 5803P 0.20 66 P 6 SAI 07H +0.25 07H 07H 151 HOT 5803P 0.37 85 P 6 SAI 06H +0.61 06H 06H 170 HOT 5803P 65 101 0.35 110 P 6 SAI 01H -0.38 01H 01H 151 HOT 5803P 0.24 103 P 6 SAI 02H +0.64 02H 02H 151 HOT 5803P 0.29 104 P 6 SAI 03H +0.54 03H 03H 151 HOT 5803P 0.15 80 P 6 SAI 03H -0.54 03H 03H 151 HOT 5803P 67 101 0.20 53 P 6 SAI O1H -0.76 01H 01H 151 HOT 5803P 0.24 69 P 6 SAI 02H +0.82 02H 02H 151 HOT 5803P 69 101 0.23 109 P 6 SAI 03H +0.93 03H 151 HOT 03H 5803P 0.57 95 P 6 SAI 04H +0.53 04H 04H 151 HOT 5803P 71 101 0.21 90 P 6 SAI 05H +1.00 05H 05H 151 HOT 5803P 75 101 0.18 65 P 6 SAI 01H -0.44 01H 01H 151 HOT 5803P 0.14 82 P 6 SAI 01H -0.02 01H 01H 151 HOT 5803P 83 101 0.28 67 P 6 SAI 02H +0.88 02H 02H 135 HOT 5803P 30 102 0.28 87 P 6 SAI 03H +0.05 03H 03H 150 HOT 5803P 52 102 0.18 57 P 6 SAI 01H -0.23 01H 01H 150 HOT 5803P 0.30 94 P 6 SAI 02H +0.74 02H 02H 150 HOT 5803P 0.21 83 P 6 SAI 05H +0.69 05H 05H 150 HOT 5803P 54 102 0.18 73 P 6 SAI 03H +0.02 03H 03H 150 HOT 5803P 62 102 0.16 84 P 6 SAI 01H +0.88 01H 01H 151 HOT 5803P 66 102 0.26 110 P 6 SAI 02H +0.67 02H 02H 151 HOT 5803P 68 102 0.37 114 P 6 SAI 01H -0.33 01H 01H 151 HOT 5803P 0.18 70 P 6 SAI 02H +0.90 02H 02H 151 HOT 5803P 70 102 0.49 106 P 6 SAI 02H +0.59 02H 02H 151 HOT 5803P 74 102 0.13 77 P 6 SAI 02H +1.00 02H 02H 151 HOT 5803P 94 102 0.29 98 P 6 SAI 01H +0.11 01H 01H 133 HOT 5803P 106 102 0.12 59 P 6 SAI 01H -0.82 01H 01H 136 HOT 5803P 108 102 0.24 85 P 6 SAI 01H -0.17 01H 01H 136 HOT 5803P 122 102 0.12 67 P 6 MAI 01H +0.24 01H 01H 136 HOT 5803P 29 103 0.24 12 2 SAI TSH -1.43 TSH TSH 97 HOT 5803P 51 103 0.21 54 P 6 SAI 03H +0.84 03H 03H 150 HOT 5803P 53 103 0.21 64 P 6 SAI 01H -0.25 01H 01H 150 HOT 5803P 55 103 0.17 60 P 6 SAI 04H +0.53 04H 04H 150 HOT 5803P 61 103 0.58 85 P 6 SAI 02H +0.81 02H 02H 151 HOT 5803P
Framatome ANP Inc. 1/22/2005 14:30 Attacbment 1 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 13 of 23 Tubes with Bobbin 40-100% TWD and +Point Vol. Circ and Axial Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 0.30 87 P 6 SAI 05H +0.83 05H 05H 151 HOT 5803P 65 103 0.22 85 P 6 SAI 01H +0.23 01H 01H 151 HOT 5803P 67 103 0.31 104 P 6 SAI 01H -0.12 01H 01H 151 HOT 5803P 109 103 0.26 86 P 6 SAI 01H -0.24 01H 01H 136 HOT 5803P 113 103 0.18 101 P 6 SAI 01H -0.28 01H 01H 136 HOT 5803P 24 104 0.20 81 P 6 SAI 04H +0.51 04H 04H 150 HOT 5803P 32 104 0.28 99 P 6 SAI O1H +0.34 01H 01N 150 HOT 5803P 0.17 62 P 6 SAI 03H +0.69 03H 03H 150 HOT 5803P 52 104 0.24 78 P 6 SAI 05H +1.12 05H 05H 150 HOT 5803P 96 104 0.12 108 P 6 SAI 01H +0.57 01H 01H 135 HOT 5803P 0.14 90 P 6 SAI 01H +0.16 01H 01H 135 HOT 5803P 114 104 0.59 108 P 6 SAI 01H -0.36 01H 01H 136 HOT 5803P 118 104 0.69 101 P 6 SAI 01H -0.48 01H 01H 136 HOT 5803P 49 105 0.37 103 P 6 SAI 01H +0.65 01H 01H 150 HOT 5803P 57 105 0.10 76 P 1 SCI TSH -0.07 TSH TSH 97 HOT 5803P 65 105 0.43 107 P 6 SAI 01H +0.92 01H 01H 150 HOT 5803P 0.22 82 P 6 SAI 02H +0.89 02H 02H 150 HOT 5803P 0.41 73 P 6 MAI 05H +0.82 05H 05H 150 HOT 5803P 81 105 0.16 82 P 6 SAI 01H +0.29 01H 01H 133 HOT 5803P 0.20 71 P 6 SAI 02H +0.15 02H 02H 133 HOT 5803P 103 105 0.21 91 P 6 SAI 01H -0.77 01H 01H 136 HOT 5803P 113 105 0.15 74 P 6 SAI 01H -0.69 01H 01H 136 HOT 5803P 18 106 0.31 59 P 6 SAI 01H -0.60 01H 01H 148 HOT 5803P 0.29 257 P 6 MAI 02H -0.53 02H 02H 148 HOT 5803P 0.33 92 P 6 SAI 03H +0.79 03H 03H 148 HOT 5803P 0.30 91 P 6 MAI 04H -0.38 04H 04H 148 HOT 5803P 0.23 86 P 6 SAI 05H +0.17 05H 05H 148 HOT 5803P 40 106 0.34 89 P 6 SAI 01H -0.24 01H 01H 150 HOT 5803P 0.40 91 P 6 SAI 02H +0.76 02H 02H 150 HOT 5803P 0.15 65 P 6 SAI 02H +0.02 02H 02H 150 HOT 5803P 0.26 101 P 6 SAI 05H +0.14 05H 05H 150 HOT 5803P 50 106 0.21 80 P 6 SAI 01H +0.61 01H 01H 178 HOT 5803P 52 106 0.33 110 P 6 MAI 02H +0.52 02H 02H 150 HOT 5803P 108 106 0.19 91 P 6 SAI 02H +0.75 02H 02H 135 HOT 5803P 0.12 51 P 6 SAI 02H -0.79 02H 02H 135 HOT 5803P 110 106 0.35 97 P 6 MAI 02H +0.76 02H 02H 135 HOT 5803P 118 106 0.18 73 P 6 SAI 02H +0.81 02H 02H 135 HOT 5803P 7 107 0.37 105 P 6 SAI 01H +0.20 01H 01H 148 HOT 5803P 13 107 0.18 59 P 6 SAI 02H +0.56 02H 02H 148 HOT 5803P 0.14 85 P 6 SAI 03H -0.81 03H 03H 148 HOT 5803P 19 107 0.27 74 P 6 SAI 04H +0.86 04H 04H 148 HOT 5803P 21 107 0.26 272 P 6 SAI 01H +0.32 01H 01H 148 HOT 5803P 0.22 96 P 6 SAI 01H -0.66 01H 01H 148 HOT 5803P 35 107 0.15 48 P 6 SAI 04H +0.88 04H 04H 150 HOT 5803P 55 107 0.25 79 P 6 SAI 01H -0.18 01H 01H 150 HOT 5803P 0.19 81 P 6 SAI 01H +0.91 01H 01H 150 HOT 5803P 0.19 71 P 6 SAI 02H +0.37 02H 02H 150 HOT 5803P 0.08 69 P 1 SCI TSH -0.10 TSH TSH 96 HOT 5803P 0.12 131 P 1 SCI TSH +0.08 TSH TSH 96 HOT 5803P 57 107 0.17 67 P 6 SAI 01H -0.34 01H 01H 150 HOT 5803P 0.16 74 P 6 SAI 01H +0.86 01H 01H 150 HOT 5803P 0.18 122 P 6 SAI 02H -0.20 02H 02H 150 HOT 5803P 0.14 92 P 6 SAI 04H +1.15 04H 04H 150 HOT 5803P 59 107 0.19 156 P 6 SAI TSH +0.18 TSH TSH 96 HOT 5803P
Framatome ANP Inc. 1/22/2005 14:30 Attachment 1 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 14 of 23 Tubes with Bobbin 40-100% TWD and +Point Vol. Circ and Axial Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 63 107 0.56 106 P 6 SA= 01H +0.27 01H 01H 150 HOT 5803P 0.34 109 P 6 SAI 03H +0.77 03H 03H 150 HOT 5803P 0.26 89 P 6 SAI 05H -0.49 05H 05H 150 HOT 5803P 0.25 57 P 6 SAI 05H +0.86 05H 05H 150 HOT 5803P 65 107 0.20 69 P 6 SAI 04H +1.01 04H 04H 150 HOT 5803P 71 107 0.29 97 P 6 SAI 01H +0.57 01H 01H 140 HOT 5803P 87 107 0.15 76 P 6 SAI 04H +0.80 04H 04H 135 HOT 5803P 129 107 0.30 67 P 6 SAI 01H -0.75 01H 01H 135 HOT 5803P 8 108 0.25 87 P 6 SAI 02H -0.46 02H 02H 148 HOT 5803P 12 108 0.68 89 P 6 MAI 01H -0.38 01H 01H 148 HOT 5803P 16 108 0.18 67 P 6 SAI 01H +0.85 01H 01H 148 HOT 5803P 0.41 109 P 6 SAI 06H +0.70 06H 06H 148 HOT 5803P 24 108 0.24 88 P 6 SAI 04H +0.91 04H 04H 148 HOT 5803P 0.40 88 P 6 SAI 05H +0.75 05H 05H 148 HOT 5803P 40 108 0.39 102 P 6 SAT 01H +0.83 01H 01H 150 HOT 5803P 0.26 84 P 6 MAI 06H -0.50 06H 06H 150 HOT 5803P 54 108 0.15 73 P 6 SAI TSH +0.13 TSH TSH 97 HOT 5803P 56 108 0.24 105 P 6 SAI 02H +0.56 02H 02H 150 HOT 5803P 0.10 133 P 6 SAI TSH +0.23 TSH TSH 96 HOT 5803P 60 108 0.18 74 P 6 SAI 03H +0.79 03H 03H 150 HOT 5803P 68 108 0.26 103 P 6 SAI 01H +0.88 01H 01H 150 HOT 5803P 84 108 0.14 100 P 6 SAI 02H +0.79 02H 02H 135 HOT 5803P 86 108 0.22 83 P 6 SAI 02H -0.41 02H 02H 135 HOT 5803P 90 108 0.38 82 P 6 MAI 01H -0.97 01H 01H 135 HOT 5803P 0.14 63 P 6 SAI 03H +0.85 03H 03H 135 HOT 5803P 104 108 0.38 78 P 6 SAI 01H +0.62 01H 01H 135 HOT 5803P 116 108 0.16 95 P 6 SAI 01H +0.75 01H 01H 135 HOT 5803P 118 108 0.36 106 P 6 SAI 01H -0.53 01H 01H 135 HOT 5803P 1 109 0.17 111 P 6 SAI 01H -0.81 TSH 01H 164 HOT 5803P 9 109 0.32 97 P 6 SAI 02H +0.87 02H 02H 148 HOT 5803P 23 109 0.58 88 P 6 SAI 02H +0.78 02H 02H 148 HOT 5803P 27 109 0.22 77 P 6 MAI 02H +0.79 02H 02H 148 HOT 5803P 31 109 0.22 63 P 6 SAI 02H +0.87 02H 02H 148 HOT 5803P 43 109 0.16 75 P 6 SAI 02H +0.90 02H 02H 150 HOT 5803P 49 109 0.34 105 P 6 SAI 01H +0.48 01H 01H 150 HOT 5803P 51 109 0.09 41 P 6 SAI 04H +0.68 04H 04H 150 HOT 5803P 67 109 0.16 80 P 6 SAI 02H +0.97 02H 02H 150 HOT 5803P 71 109 0.18 65 P 6 SAI 02H +0.83 02H 02H 150 HOT 5803P 97 109 0.18 87 P 6 SAI 01H -0.18 01H 01H 135 HOT 5803P 103 109 0.35 77 P 6 SAI 02H +0.33 02H 02H 135 HOT 5803P 0.19 46 P 6 SAI 02H -0.48 02H 02H 135 HOT 5803P 121 109 0.22 86 P 6 SAI 02H +0.83 02H 02H 135 HOT 5803P 10 110 0.25 104 P 6 MAI 05H +0.46 05H 05H 148 HOT 5803P 0.22 94 P 6 SAI 06H +0.11 06H 06H 148 HOT 5803P 0.19 87 P 6 SAI 06H -0.86 06H 06H 148 HOT 5803P 12 110 0.18 54 P 6 SAI 02H +0.92 02H 02H 148 HOT 5803P 0.23 60 P 6 SAI 04H +0.92 04H 04H 148 HOT 5803P 14 110 0.24 74 P 6 SAI 02H -0.36 02H 02H 148 HOT 5803P 0.27 90 P 6 SAI 04H +0.82 04H 04H 148 HOT 5803P 18 110 0.26 100 P 6 SAI 01H -0.90 TO+1.00 01H 01H 148 HOT 5803P 24 110 0.30 87 P 6 SAI 01H -0.45 01H 01H 148 HOT 5803P 0.27 100 P 6 SAI 02H +0.55 02H 02H 148 HOT 5803P 0.36 85 P 6 SAI 04H +0.71 04H 04H 148 HOT 5803P 0.29 105 P 6 SAI 06H +0.93 06H 06H 148 HOT 5803P
Framatome ANP Inc. 1/22/2005 14:30 Attachment 1 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 15 of 23 Tubes with Bobbin 40-100% TWD and +Point Vol. Circ and Axial Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL LEG PROBE 0.16 80 P 6 SA= 06H -0.76 06H 06H 148 HOT 5803P 30 110 0.12 65 P 6 SAI 03H +0.93 03H 03H 148 HOT 5803P 0.30 88 P 6 MAI 04H +0.15 04H 04H 148 HOT 5803P 36 110 0.28 41 P 6 SAI 02H +0.80 02H 02H 148 HOT 5803P 46 110 0.17 83 P 6 SAI 02H +0.79 02H 02H 148 HOT 5803P 62 110 0.64 99 P 6 SAI 04H +0.47 04H 04H 148 HOT 5803P 0.42 90 P 6 SAI 08H +0.82 08H 08H 148 HOT 5803P 64 110 0.20 88 P 6 SAI 06H -0.18 06H 06H 148 HOT 5803P 70 110 0.43 96 P 6 SAI 04H +0.79 04H 04H 148 HOT 5803P 110 110 0.37 92 P 6 SAI 02H +0.63 02H 02H 135 HOT 5803P 9 111 0.51 113 P 6 SAI 06H -0.39 06H 06H 147 HOT 5803P 15 lll 0.39 84 P 6 MAI 01H -0.26 01H 01H 147 HOT 5803P 17 111 0.37 110 P 6 SAI 01H -0.65 01H 01H 147 HOT 5803P 0.39 97 P 6 SAI 02H +0.68 02H 02H 147 HOT 5803P 23 111 0.18 74 P 6 SAI 01H +0.24 01H 01H 147 HOT 5803P 27 111 0.36 84 P 6 SAI 01H +0.88 01H 01H 147 HOT 5803P 0.28 85 P 6 SAI 04H +0.23 04H 04H 147 HOT 5803P 35 111 0.20 59 P 6 SAI 06H +0.83 06H 06H 147 HOT 5803P 37 111 0.25 60 P 6 SAI 02H +0.33 02H 02H 170 HOT 5803P 39 111 0.49 94 P 6 SAI 01H -0.03 01H 01H 147 HOT 5803P 43 111 0.37 102 P 6 SAI 02H +0.16 02H 02H 147 HOT 5803P 0.22 104 P 6 SAI 04H +0.22 04H 04H 147 HOT 5803P 47 111 0.18 79 P 6 SAI 06H +0.93 06H 06H 148 HOT 5803P 57 111 0.33 88 P 6 SAI 02H +0.97 02H 02H 148 HOT 5803P 59 111 0.22 38 P 6 SAI 04H +0.47 04H 04H 148 HOT 5803P 63 111 0.23 78 P 6 SAI 06H +0.79 06H 06H 148 HOT 5803P 65 111 0.35 74 P 6 SAI 04H +0.75 04H 04H 148 HOT 5803P 71 111 0.35 104 P 6 SAI 01H -0.49 01H 01H 148 HOT 5803P 0.22 86 P 6 SAI 02H +0.89 02H 02H 148 HOT 5803P lll 111 0.35 87 P 6 SAI 01H +0.77 01H 01H 135 HOT 5803P 0.17 48 P 6 SAI 03H +0.69 03H 03H 135 HOT 5803P 6 112 0.27 110 P 6 SAI 05H -0.31 05H 05H 147 HOT 5803P 8 112 0.39 85 P 6 SAI 02H -0.62 02H 02H 147 HOT 5803P 14 112 0.23 99 P 6 SAI 01H +0.38 01H 01H 147 HOT 5803P 0.21 48 P 6 SAI 02H +0.97 02H 02H 147 HOT 5803P 0.24 55 P 6 SAI 04H +1.00 04H 04H 147 HOT 5803P 28 112 0.19 69 P 6 SAI 04H -0.30 04H 04H 147 HOT 5803P 40 112 0.31 102 P 6 SAI 01H +0.71 01H 01H 147 HOT 5803P 0.20 107 P 6 SAI 07H +0.96 07H 07H 147 HOT 5803P 44 112 0.22 62 P 6 MAI 02H +0.35 02H 02H 147 HOT 5803P 48 112 0.16 257 P 6 SAI 02H +0.71 02H 02H 147 HOT 5803P 58 112 0.20 71 P 6 SAI 02H +0.97 02H 02H 147 HOT 5803P 64 112 0.14 51 P 6 SAI 02H +0.93 02H 02H 147 HOT 5803P 70 112 0.32 82 P 6 SAI 02H +0.68 02H 02H 147 HOT 5803P 80 112 0.31 96 P 6 SAI 01H +0.55 01H 01H 147 HOT 5803P 0.24 81 P 6 SAI 01H -0.72 01H 01H 147 HOT 5803P 118 112 0.29 89 P 6 SAI 02H -0.46 02H 02H 135 HOT 5803P 0.24 98 P 6 SAI 02H +0.63 02H 02H 135 HOT 5803P 9 113 0.18 101 P 6 SAI 01H +0.73 01H 01H 147 HOT 5803P 11 113 0.15 88 P 6 SAI 01H -0.57 01H 01H 147 HOT 5803P 0.49 104 P 6 SAI 01H +0.40 01H 01H 147 HOT 5803P 0.30 87 P 6 SAI 03H +0.82 03H 03H 147 HOT 5803P 59 113 0.11 65 P 6 SAI 02H +0.84 02H 02H 147 HOT 5803P 61 113 0.20 73 P 6 SAI 02H +0.34 02H 02H 147 HOT 5803P
Framatome ANP Inc. 1/22/2005 14:30 Attacbhent 1 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 16 of 23 Tubes with Bobbin 40-100% TWD and +Point Vol. Circ and Axial Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 69 113 0.34 109 P 6 SAI 01H -0.74 01H 01H 147 HOT 5803 P 97 113 0.23 108 P 6 SAI 01H -0.72 01H 01H 135 HOT 5803P 0.18 73 P 6 MAI 02H -0.21 02H 02H 135 HOT 5803P 0.16 90 P 6 MAI 04H +0.86 04H 04H 135 HOT 5803P 121 113 0.25 96 P 6 SAI 02H +0.75 02H 02H 135 HOT 5803P 129 113 0.19 106 P 6 MAI 01H +0.65 01H 01H 135 HOT 5803P 6 114 0.19 86 P 6 SAI 01H +0.87 01H 01H 147 HOT 5803P 10 114 0.36 93 P 6 SAI 03H -0.17 03H 03H 170 HOT 5803P 14 114 0.20 100 P 6 SAI 01H -0.11 01H 01H 147 HOT 5803P 0.18 117 P 6 SAI 01H +0.71 01H 01H 147 HOT 5803P 20 114 0.25 104 P 6 SAI 01H +0.78 01H 01H 178 HOT 5803P 24 114 0.26 80 P 6 SAI 01H -0.53 01H 01H 147 HOT 5803P 0.42 104 P 6 SAI 01H +0.89 01H 01H 147 HOT 5803P 0.25 91 P 6 SAI 03H +0.83 03H 03H 147 HOT 5803P 0.34 87 P 6 SAI 04H +0.98 04H 04H 147 HOT 5803P 44 114 0.36 164 P 1 SCI TSH -0.04 TSH TSH 91 HOT 5803P 64 114 0.13 72 P 6 SAI 02H +0.99 02H 02H 147 HOT 5803P 70 114 0.36 108 P 6 SAI 02H +0.86 02H 02H 147 HOT 5803P 0.22 90 P 6 SAI 04H +0.86 04H 04H 147 HOT 5803P 82 114 0.18 96 P 6 SAI 01H -0.28 01H 01H 170 HOT 5803P 106 114 0.34 105 P 6 SAI 01H -0.52 01H 01H 135 HOT 5803P 118 114 0.19 77 P 6 SAI 01H +0.83 01H 01H 133 HOT 5803P 0.21 74 P 6 SAI 02H -0.21 02H 02H 133 HOT 5803P 0.17 94 P 6 SAI 02H +0.20 02H 02H 133 HOT 5803P 120 114 0.33 111 P 6 SAI 02H -0.60 02H 02H 133 HOT 5803P 0.21 86 P 6 SAI 02H +0.64 02H 02H 133 HOT 5803P 9 115 0.28 71 P 6 MAI 02H +0.65 02H 02H 146 HOT 5803P 11 115 0.16 72 P 6 SAI 03H -0.22 03H 03H 146 HOT 5803P 0.26 93 P 6 SAI 05H +0.71 05H 05H 146 HOT 5803P 15 115 0.29 105 P 6 SAI 01H -0.69 01H 01H 146 HOT 5803P 0.14 118 P 6 SAI 01H +0.43 01H 01H 146 HOT 5803P 29 115 0.16 38 P 6 SAI 02H +0.19 02H 02H 146 HOT 5803P 39 115 0.28 52 P 1 SCI TSH -0.06 TSH TSH 92 HOT 5803P 59 115 0.40 87 P 6 SAI 02H +0.33 02H 02H 146 HOT 5803P 0.37 84 P 6 SAI 04H +0.33 04H 04H 146 HOT 5803P 0.22 42 P 6 SAI 05H +0.77 05H 05H 146 HOT 5803P 63 115 0.23 86 P 6 SAI 01H +0.77 01H 01H 146 HOT 5803P 0.20 54 P 6 SAI 01H +0.07 01H 01H 146 HOT 5803P 0.18 62 P 6 SAI 03H +0.76 03H 03H 146 HOT 5803P 65 115 0.18 66 P 6 SAI 04H +0.37 04H 04H 146 HOT 5803P 67 115 0.36 88 P 6 SAI 01H +0.33 01H 01H 146 HOT 5803P 0.12 81 P 6 SAI 03H +0.25 03H 03H 146 HOT 5803P 0.15 57 P 6 SAI 03H +0.69 03H 03H 146 HOT 5803P 93 115 0.15 77 P 6 SAI 01H -0.72 01H 01H 135 HOT 5803P 103 115 0.53 92 P 6 SAI 02H -0.34 02H 02H 135 HOT 5803P 121 115 0.95 96 P 6 SAI 02H -0.66 02H 02H 133 HOT 5803P 0.37 91 P 6 SAI 02H +0.73 02H 02H 133 HOT 5803P 16 116 0.19 59 P 6 SAI 01H -0.18 01H 01H 146 HOT 5803P 18 116 0.36 112 P 6 SAI 01H +0.24 01H 01H 146 HOT 5803P 46 116 0.25 105 P 6 SAI 02H +0.66 02H 02H 146 HOT 5803P 48 116 0.14 52 P 6 SAI 01H -0.03 01H 01H 146 HOT 5803P 0.17 84 P 6 SAI 01H +0.70 01H 01H 146 HOT 5803P 0.09 35 P 6 SAI 02H +0.22 02H 02H 146 HOT 5803P 0.15 46 P 6 SAI 02H +0.82 02H 02H 146 HOT 5803P
Framatome ANP Inc. 1/22/2005 14:30 Attachment .
CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 17 of 23 Tubes with Bobbin 40-100% TWD and +Point Vol, Circ and Axial Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 52 116 0.18 49 P 6 SAI 01H +0.74 01H 01H 146 HOT 5803P 116 116 0.13 95 P 6 SAI 01H +0.68 01H 01H 133 HOT 5803P 0.27 91 P 6 SAI 02H -0.53 02H 02H 133 HOT 5803P 0.14 98 P 6 SAI 02H +0.28 02H 02H 133 HOT 5803P 120 116 0.15 88 P 6 SAI 01H +0.73 01H 01H 133 HOT 5803P 9 117 0.23 94 P 6 SAI 01H +0.56 01H 01H 146 HOT 5803P 0.45 103 P 6 SAI 02H -0.91 02H 02H 146 HOT 5803P 21 117 0.25 86 P 6 SAI 01H -0.70 01H 01H 146 HOT 5803P 0.24 83 P 6 SAI 01H +0.70 01H 01H 146 HOT 5803P 27 117 0.19 129 P 6 SAI 01H -0.81 01H 01H 146 HOT 5803P 45 117 0.17 59 P 6 SAI 03H +0.66 03H 03H 146 HOT 5803P 47 117 0.17 113 P 6 SAI 01H -0.24 01H 01H 146 HOT 5803P 0.31 78 P 6 SAI 02H +0.34 02H 02H 146 HOT 5803P 49 117 0.26 70 P 6 SAI 02H -0.34 02H 02H 146 HOT 5803P 0.30 99 P 6 SAI 03H +0.50 03H 03H 146 HOT 5803P 0.16 55 P 6 SAI 05H +0.93 05H 05H 146 HOT 5803P 63 117 0.20 82 P 6 SAI 02H +0.85 02H 02H 146 HOT 5803P 65 117 0.25 95 P 6 SAI 01H -0.15 01H 01H 146 HOT 5803P 0.26 101 P 6 SAI 01H +0.45 O1H 01H 146 HOT 5803P 71 117 0.23 89 P 6 SAI 02H +0.77 02H 02H 146 HOT 5803P 79 117 0.16 130 P 6 SAI 02H +0.23 02H 02H 146 HOT 5803P 115 117 0.61 98 P 6 SAI 02H +0.82 02H 02H 133 HOT 5803P 0.30 80 P 6 SAI 02H -0.16 02H 02H 133 HOT 5803P 10 118 0.20 110 P 6 SAI 04H +0.20 04H 04H 146 HOT 5803P 0.24 69 P 6 SAI 07H +0.44 07H 07H 146 HOT 5803P 12 118 0.34 106 P 6 SAI 03H -0.17 03H 03H 146 HOT 5803P 16 118 0.29 86 P 6 SAI 07H +0.17 07H 07H 146 HOT 5803P 38 118 0.13 72 P 6 SAI 01H +0.70 01H 01H 146 HOT 5803P 0.32 102 P 6 MAI 02H +0.26 02H 02H 146 HOT 5803P 46 118 0.47 94 P 6 SAI 01H +0.28 01H 01H 146 HOT 5803P 0.24 91 P 6 SAI 05H +0.72 04H 05H 146 HOT 5803P 48 118 0.17 43 P 6 SAI 02H +0.53 02H 02H 146 HOT 5803P 0.16 62 P 6 SAI 05H +0.46 05H 05H 146 HOT 5803P 56 118 0.35 79 P 6 SAI 01H -0.45 01H 01H 146 HOT 5803P 58 118 0.42 101 P 6 SAI 01H +0.57 01H 01H 146 HOT 5803P 64 118 0.19 82 P 6 SAI 03H +0.77 03H 03H 146 HOT 5803P 70 118 0.21 56 P 6 SAI 06H +0.75 06H 06H 146 HOT 5803P 84 118 0.21 114 P 6 SAI 01H -0.86 01H 01H 135 HOT 5803P 114 118 0.21 104 P 6 SAI 02H -0.05 02H 02H 178 HOT 5803P 118 118 0.18 96 P 6 SAI 01H +0.77 01H 01H 133 HOT 5803P 9 119 0.19 95 P 6 SAI 01H -0.19 01H 01H 145 HOT 5803P 0.16 55 P 6 SAI 02H +0.77 02H 02H 145 HOT 5803P 11 119 0.36 92 P 6 SAI 03H +0.85 03H 03H 145 HOT 5803P 15 119 0.23 88 P 6 SAI 05H +0.53 05H 05H 145 HOT 5803P 43 119 0.25 73 P 6 SAI 01H +0.79 01H 01H 145 HOT 5803P 47 119 0.37 90 P 6 SAI 04H +0.70 04H 04H 146 HOT 5803P 0.17 62 P 6 SAI 05H -0.14 05H 05H 146 HOT 5803P 0.24 73 P 6 SAI 05H +0.70 05H 05H 146 HOT 5803P 49 119 0.55 93 P 6 SAI 02H +0.59 02H 02H 146 HOT 5803P 57 119 0.21 55 P 6 SAI 02H +0.76 02H 02H 146 HOT 5803P 67 119 0.43 99 P 6 SAI 01H +0.19 01H 01H 146 HOT 5803P 75 119 0.20 83 P 6 SAI 01H -0.34 01H 01H 146 HOT 5803P 93 119 0.27 79 P 6 SAI 02H +0.80 02H 02H 135 HOT 5803P 0.21 62 P 6 MAI 02H -0.48 02H 02H 135 HOT 5803P
Framatome ANP Inc. 1/22/2005 14:30 Attachment .
CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 18 of 23 Tubes with Bobbin 40-100% TWD and +Point Vol. Circ and Axial Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 121 119 0.47 95 P 6 SAI 02H +0.52 02H 02H 133 HOT 5803P 0.26 93 P 6 SAI 04H +0.66 04H 04H 133 HOT 5803P 8 120 0.27 122 P 6 SAI 02H -0.67 02H 02H 145 HOT 5803P 0.23 82 P 6 SAI 06H +0.81 06H 06H 145 HOT 5803P 0.37 93 P 6 SAI 03H -0.39 03H 03H 170 HOT 5803P 36 120 0.24 85 P 6 SAI 05H +0.44 05H 05H 145 HOT 5803P 40 120 0.25 86 P 6 SAI 03H +0.64 03H 03H 145 HOT 5803P 0.21 72 P 6 SAI 05H +0.56 05H 05H 145 HOT 5803P 48 120 0.18 56 P 6 SAI 01H +0.83 01H 01H 145 HOT 5803P 0.20 90 P 6 SAI 04H +0.70 04H 04H 145 HOT 5803P 112 120 0.22 118 P 6 SAI 01H +0.51 01H 01H 133 HOT 5803P 0.23 86 P 6 SAI 02H -0.14 02H 02H 133 HOT 5803P 13 121 0.38 93 P 6 SAI 03H -0.27 03H 03H 145 HOT 5803P 0.20 55 P 6 SAI 07H -0.30 07H 07H 145 HOT 5803P 27 121 0.13 77 P 6 SAI 02H +0.87 02H 02H 145 HOT 5803P 49 121 0.46 96 P 6 SAI 01H +0.10 01H 01H 145 HOT 5803P 0.23 68 P 6 SAI 05H +0.67 05H 05H 145 HOT 5803P 0.35 83 P 6 SAI 06H +0.71 06H 06H 145 HOT 5803P 55 121 0.56 97 P 6 SAI 01H +0.77 01H 01H 145 HOT 5803P 57 121 0.22 83 P 6 SAI 02H -0.16 02H 02H 145 HOT 5803P 67 121 0.26 101 P 6 SAI 01H -0.24 01H 01H 145 HOT 5803P 0.20 65 P 6 SAI 02H +0.42 02H 02H 145 HOT 5803P 69 121 0.20 64 P 6 SAI 02H +0.69 02H 02H 145 HOT 5803P 101 121 0.19 70 P 6 SAI 01H +0.77 01H 01H 133 HOT 5803P 0.46 96 P 6 SAI 02H -0.37 02H 02H 133 HOT 5803P 121 121 0.38 93 P 6 MAI 02H -0.37 02H 02H 133 HOT 5803P 8 122 0.30 72 P 6 SAI 02H +0.51 02H 02H 145 HOT 5803P 14 122 0.18 81 P 6 SAI 04H +0.74 04H 04H 145 HOT 5803P 18 122 0.24 89 P 6 SAI O1H +0.69 01H 01H 145 HOT 5803P 0.26 91 P 6 SAI 05H +0.72 05H 05H 145 HOT 5803P 20 122 0.20 84 P 6 SAI 02H +0.72 02H 02H 145 HOT 5803P 0.32 72 P 6 SAI 03H -0.68 03H 03H 145 HOT 5803P 24 122 0.21 61 P 6 SAI 01H +0.60 01H 01H 145 HOT 5803P 30 122 0.26 68 P 6 SAI 03H +0.59 03H 03H 145 HOT 5803P 40 122 0.23 78 P 6 SAI 01H +0.55 01H 01H 145 HOT 5803P 0.19 135 P 6 SAI 04H +0.18 04H 04H 145 HOT 5803P 46 122 0.19 88 P 6 SAI 01H +0.10 01H 01H 145 HOT 5803P 58 122 0.19 51 P 6 SAI 03H +0.85 03H 03H 145 HOT 5803P 70 122 0.27 92 P 6 MAI 01H +0.48 01H 01H 145 HOT 5803P 88 122 0.15 87 P 6 SAI 02H +0.90 02H 02H 135 HOT 5803P 116 122 0.21 84 P 6 SAI 04H +0.81 04H 04H 133 HOT 5803P 9 123 0.19 65 P 6 SAI 01H -0.15 01H 01H 144 HOT 5803P 11 123 0.21 111 P 6 SAI 02H -0.20 02H 02H 144 HOT 5803P 19 123 0.21 47 P 6 SAI 05H +0.32 05H 05H 144 HOT 5803P 29 123 0.12 54 P 6 SAI 01H -0.03 01H 01H 144 HOT 5803P 37 123 0.28 69 P 6 SAI 02H +0.76 02H 02H 144 HOT 5803P 41 123 0.19 63 P 6 SAI 02H +0.90 02H 02H 144 HOT 5803P 49 123 0.21 45 P 6 SAI 01H -0.64 01H 01H 144 HOT 5803P 0.19 66 P 6 SAI 02H +0.72 02H 02H 144 HOT 5803P 0.25 90 P 6 SAI 03H -0.35 03H 03H 144 HOT 5803P 63 123 0.18 53 P 6 SAI 02H -0.14 02H 02H 144 HOT 5803P 0.22 121 P 6 SAI 03H +0.88 03H 03H 144 HOT 5803P 65 123 0.21 59 P 6 SAI 02H -0.39 02H 02H 144 HOT 5803P 0.19 56 P 6 SAI 02H +0.33 02H 02H 144 HOT 5803P
Framatome ANP Inc. 1/22/2005 14:30 Attachzxmt I CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 19 of 23 Tubes with Bobbin 40-100% TWD and +Point Vol. Circ and Axial Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 79 123 0.19 92 P 6 SA= 01H +0.91 01H 01H 144 HOT 5803P 81 123 0.24 84 P 6 SAI 02H +0.68 02H 02H 133 HOT 5803P 93 123 0.24 92 P 6 SAI 01H -0.74 01H 01H 133 HOT 5803P 18 124 0.33 92 P 6 SAI 05H -0.27 05H 05H 144 HOT 5803P 24 124 0.34 92 P 6 SAI 01H +0.34 01H 01H 144 HOT 5803P 0.17 95 P 6 SAI 03H -0.19 03H 03H 144 HOT 5803P 0.39 97 P 6 SAI 05H -0.14 05H 05H 144 HOT 5803P 0.13 84 P 6 SAI 05H +0.75 05H 05H 144 HOT 5803P 46 124 0.30 89 P 6 SAI 01H -0.47 01H 01H 144 HOT 5803P 0.21 78 P 6 SAI 02H +0.55 02H 02H 144 HOT 5803P 0.25 93 P 6 SAI 04H +0.82 04H 04H 144 HOT 5803P 0.63 93 P 6 SAI 05H +0.63 05H 05H 144 HOT 5803P 0.23 71 P 6 SAI 05H -0.65 05H 05H 144 HOT 5803P 48 124 0.22 57 P 6 SAI 03H +0.87 03H 03H 144 HOT 5803P 0.37 86 P 6 SAI 04H +0.70 04H 04H 144 HOT 5803P 50 124 0.24 89 P 6 SAI 01H -0.39 01H 01H 144 HOT 5803P 56 124 0.24 90 P 6 MAI 01H +0.46 01H 01H 144 HOT 5803P 62 124 0.22 77 P 6 MAI 01H -0.62 01H 01H 144 HOT 5803P 70 124 0.21 88 P 6 SAI 01H -0.27 01H 01H 144 HOT 5803P 0.36 86 P 6 SAI 02H +0.85 02H 02H 144 HOT 5803P 78 124 0.51 97 P 6 SAI 01H -0.71 01H 01H 144 HOT 5803P 9 125 0.20 74 P 6 SAI 01H +0.65 01H 01H 144 HOT 5803P 0.26 82 P 6 MAI 05H +0.81 05H 05H 144 HOT 5803P 11 125 0.22 99 P 6 MAI 01H -0.24 01H 01H 144 HOT 5803P 17 125 0.22 87 P 6 SAI 04H +0.25 04H 04H 144 HOT 5803P 19 125 0.15 35 P 6 SAI 02H -0.58 02H 02H 144 HOT 5803P 0.45 87 P 6 SAI 02H +0.40 02H 02H 144 HOT 5803P 25 125 0.18 86 P 6 SAI 03H -0.26 03H 03H 144 HOT 5803P 0.13 75 P 6 SAI 03H +0.82 03H 03H 144 HOT 5803P 33 125 0.18 72 P 6 SAI 05H +0.07 05H 05H 144 HOT 5803P 45 125 0.24 71 P 6 SAI 04H +0.58 04H 04H 144 HOT 5803P 49 125 0.20 80 P 6 SAI 01H +0.84 01H 01H 144 HOT 5803P 51 125 0.20 93 P 6 SAI 02H -0.49 02H 02H 144 HOT 5803P 0.18 62 P 6 SAI 02H +0.95 02H 02H 144 HOT 5803P 55 125 0.23 84 P 6 SAI 01H -0.38 01H 01H 144 HOT 5803P 0.39 95 P 6 SAI 01H +0.82 01H 01H 144 HOT 5803P 57 125 0.35 89 P 6 SAI 02H +0.44 02H 02H 144 HOT 5803P 63 125 0.26 76 P 6 SAI 02H +0.74 02H 02H 144 HOT 5803P 67 125 0.26 84 P 6 SAI 01H -0.61 01H 01H 144 HOT 5803P 0.31 95 P 6 SAI 01H +0.29 01H 01H 144 HOT 5803P 71 125 0.29 98 P 6 SAI 01H -0.68 01H 01H 144 HOT 5803P 79 125 0.33 82 P 6 SAI 01H -0.62 01H 01H 144 HOT 5803P 81 125 0.50 89 P 6 SAI 02H -0.02 02H 02H 133 HOT 5803P 0.31 94 P 6 SAI 03H +0.21 03H 03H 133 HOT 5803P 0.23 83 P 6 SAI 04H +0.62 04H 04H 133 HOT 5803P 6 126 0.25 88 P 6 SAI 01H +0.79 01H 01H 144 HOT 5803P 0.25 83 P 6 SAI 07H +0.51 07H 07H 144 HOT 5803P 10 126 0.18 90 P 6 SAI 01H +0.27 01H 01H 144 HOT 5803P 30 126 0.15 55 P 6 SAI 03H +0.48 03H 03H 144 HOT 5803P 0.18 92 P 6 SAI 07H -0.24 07H 07H 144 HOT 5803P 40 126 0.27 84 P 6 SAI 02H +0.86 02H 02H 144 HOT 5803P 0.12 171 P 6 SAI 02H -0.40 02H 02H 144 HOT 5803P 46 126 0.19 82 P 6 SAI 01H +0.69 01H 01H 144 HOT 5803P 0.25 70 P 6 SAI 03H +0.78 03H 03H 144 HOT 5803P
Framatome ANP Inc. 1/22/2005 14:30 Attacbment I CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 20 of 23 Tubes with Bobbin 40-100% TWD and +Point Vol, Circ and Axial Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 0.44 95 P 6 SAI 04H +0.50 04H 04H 144 HOT 5803P 0.18 84 P 6 SAI 05H +0.95 05H 05H 144 HOT 5803P 0.29 79 P 6 SAI 06H -0.21 06H 06H 144 HOT 5803P 58 126 0.30 99 P 6 SAI 01H +0.53 01H 01H 143 HOT 5803P 0.14 66 P 6 SAI 02H +0.78 02H 02H 143 HOT 5803P 0.16 60 P 6 SAI 04H +0.80 04H 04H 143 HOT 5803P 66 126 0.39 94 P 6 MAI 01H +0.06 01H 01H 143 HOT 5803P 0.22 63 P 6 MAI 02H -0.06 02H 02H 143 HOT 5803P 70 126 0.43 114 P 6 SAI 01H +0.56 01H 01H 143 HOT 5803P 0.22 45 P 6 SAI 02H -0.37 02H 02H 143 HOT 5803P 0.31 96 P 6 SAI 03H +0.85 03H 03H 143 HOT 5803P 92 126 0.29 101 P 6 SAI 02H +0.85 02H 02H 133 HOT 5803P 118 126 0.22 121 P 6 SAI 01H +0.71 01H 01H 133 HOT 5803P 11 127 0.13 117 P 6 SAI 02H -0.86 02H 02H 143 HOT 5803P 0.16 39 P 6 SAI 02H -0.50 02H 02H 143 HOT 5803P 13 127 0.20 70 P 6 SAI 01H -0.24 01H 01H 143 HOT 5803P 0.23 78 P 6 SAI 04H +0.78 04H 04H 143 HOT 5803P 37 127 0.19 65 P 6 SAI 01H -0.38 01H 01H 143 HOT 5803P 39 127 0.14 63 P 6 SAI 02H -0.44 02H 02H 143 HOT 5803P 0.18 115 P 6 SAI 02H +0.55 02H 02H 143 HOT 5803P 0.19 39 P 6 SAI 03H +0.54 03H 03H 143 HOT 5803P 49 127 0.16 61 P 6 SAI 01H -0.85 01H 01H 143 HOT 5803P 55 127 0.14 88 P 6 SAI 01H -0.78 01H 01H 143 HOT 5803P 59 127 0.19 95 P 6 SAI 02H +0.53 02H 02H 143 HOT 5803P 63 127 0.34 103 P 6 MAI 01H +0.19 01H 01H 143 HOT 5803P 65 127 0.31 85 P 6 SAI 02H +0.63 02H 02H 143 HOT 5803P 71 127 0.19 66 P 6 SAI 06H +0.86 06H 06H 143 HOT 5803P 85 127 0.25 85 P 6 SAI 02H +0.70 02H 02H 133 HOT 5803P 101 127 0.17 98 P 6 SAI 02H +0.22 02H 02H 133 HOT 5803P 6 128 0.40 84 P 6 SAI 03H -0.44 03H 03H 143 HOT 5803P 12 128 0.28 94 P 6 SAI 03H +0.69 03H 03H 178 HOT 5803P 14 128 0.14 56 P 6 SAI 03H -0.32 03H 03H 143 HOT 5803P 0.16 69 P 6 SAI 04H +0.75 04H 04H 143 HOT 5803P 0.14 65 P 6 SAI 05H -0.94 05H 05H 143 HOT 5803P 20 128 0.10 87 P 6 SAI 03H +0.87 03H 03H 143 HOT 5803P 40 128 0.24 75 P 6 SAI 01H -0.29 01H 01H 143 HOT 5803P 0.34 81 P 6 SAI 02H -0.42 02H 02H 143 HOT 5803P 0.28 92 P 6 SAI 04H +0.81 04H 04H 143 HOT 5803P 0.16 79 P 6 SAI 05H +0.91 05H 05H 143 HOT 5803P 46 128 0.14 103 P 6 SAI 01H +0.08 01H 01H 143 HOT 5803P 0.47 90 P 6 SAI 02H +0.87 02H 02H 143 HOT 5803P 60 128 0.19 110 P 6 SAI 01H +0.35 01H 01H 143 HOT 5803P 62 128 0.18 86 P 6 SAI 01H -0.44 01H 01H 143 HOT 5803P 74 128 0.16 89 P 6 SAI 01H -0.92 01H 01H 143 HOT 5803P 78 128 0.32 105 P 6 SAI 01H -0.75 01H 01H 143 HOT 5803P 0.16 99 P 6 MAI 02H +0.25 02H 02H 143 HOT 5803P 86 128 0.24 125 P 6 SAI 03H -0.30 03H 03H 131 HOT 5803P 5 129 0.20 74 P 6 SAI 02H -0.68 02H 02H 143 HOT 5803P 41 129 0.25 95 P 6 SAI 01H -0.20 01H 01H 143 HOT 5803P 47 129 0.13 58 P 6 SAI 02H +0.85 02H 02H 143 HOT 5803P 51 129 0.22 83 P 6 SAI 01H -0.46 01H 01H 143 HOT 5803P 81 129 0.26 76 P 6 MAI 02H -0.29 02H 02H 131 HOT 5803P 0.26 66 P 6 SAI 03H +0.83 03H 03H 131 HOT 5803P 83 129 0.29 107 P 6 SAI 01H -0.34 01H 01H 131 HOT 5803P
Framatome ANP Inc. 1/22/2005 14:30 Attachment I CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 21 of 23 Tubes with Bobbin 40-100% TWD and +Point Vol, Circ and Axial Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 0.20 112 P 61SA 01H +0.42 01H 01H 131 HOT 5803P 0.16 55 P 6 SAI 02H -0.79 02H 02H 131 HOT 5803P 0.19 90 P 6 SAI 02H +0.92 02H 02H 131 HOT 5803P 6 130 0.27 79 P 6 SAI 01H -0.17 01H 01H 128 HOT 5803P 8 130 0.24 92 P 6 SAI 01H -0.90 01H 01H 128 HOT 5803P 0.24 87 P 6 SAI 02H +0.92 02H 02H 128 HOT 5803P 16 130 0.61 94 P 6 SAI 01H -0.35 01H 01H 152 HOT 5803P 0.21 58 P 6 SAI 01H +0.45 01H 01H 152 HOT 5803P 56 130 0.25 90 P 6 SAI 01H -0.87 01H 01H 131 HOT 5803P 66 130 0.67 98 P 6 SAI 01H -0.71 01H 01H 131 HOT 5803P 13 131 0.33 118 P 6 SAI 01H -0.32 01H 01H 152 HOT 5803P 0.29 111 P 6 SAI 02H +0.51 02H 02H 152 HOT 5803P 23 131 0.20 86 P 6 SAI 01H +0.40 01H 01H 128 HOT 5803P 31 131 0.45 97 P 6 MAI 01H +0.49 01H 01H 152 HOT 5803P 91 131 0.23 98 P 6 SAI 01H +0.74 01H 01H 131 HOT 5803P 12 132 0.42 96 P 6 SAI 01H +0.12 01H 01H 128 HOT 5803P 0.16 60 P 6 SAI 01H -0.40 01H 01H 128 HOT 5803P 14 132 0.20 63 P 6 SAI 01H +0.93 01H 01H 140 HOT 5803P 66 132 0.28 101 P 6 SAI 01H -0.78 01H 01H 131 HOT 5803P 88 132 0.22 117 P 6 SAI 01H +0.86 01H 01H 131 HOT 5803P 11 133 0.24 171 P 6 SAI 03H -0.38 03H 03H 128 HOT 5803P 13 133 0.18 58 P 6 MAI 07H +0.36 DCB 07H 159 HOT 5602P 0.10 57 P 6 SAI 07H -0.83 DCB 07H 159 HOT 5602P 0.51 88 P 6 SAI 05H +0.78 05H 05H 128 HOT 5803P 67 133 0.30 95 P 6 SAI 01H +0.64 01H 01H 131 HOT 5803P 79 133 0.23 100 P 6 SAI 01H -0.43 01H 01H 131 HOT 5803P 0.17 65 P 6 SAI 01H +0.49 01H 01H 131 HOT 5803P 85 133 0.31 94 P 6 SAI 02H -0.44 02H 02H 131 HOT 5803P 8 134 0.28 82 P 6 SAI 01H -0.64 01H 01H 128 HOT 5803P 10 134 0.34 102 P 6 SAI 01H +0.66 01H 01H 128 HOT 5803P 40 134 0.28 92 P 6 SAI 01H -0.46 01H 01H 131 HOT 5803P 0.17 90 P 6 SAI 01H +0.21 01H 01H 131 HOT 5803P 86 134 0.23 67 P 6 SAI 03H +0.82 03H 03H 131 HOT 5803P 7 135 0.14 87 P 6 SAI 02H -0.38 02H 02H 128 HOT 5803P 15 135 0.19 102 P 6 SAI 03H +0.79 03H 03H 152 HOT 5803P 49 135 0.45 100 P 6 SAI 01H -0.70 01H 01H 131 HOT 5803P 79 135 0.40 113 P 6 SAI 01H +0.46 01H 01H 131 HOT 5803P 46 136 0.25 87 P 6 MAI 02H -0.86 02H 02H 152 HOT 5803P 0.26 80 P 6 MAI 01H -0.81 01H 01H 170 HOT 5803P 66 136 0.24 106 P 6 MAI 01H -0.32 01H 01H 131 HOT 5803P 78 136 0.25 108 P 6 SAI 01H -0.76 01H 01H 131 HOT 5803P 86 136 0.20 88 P 6 SAI 02H -0.13 02H 02H 131 HOT 5803P 0.35 97 P 6 SAI 02H +0.28 02H 02H 131 HOT 5803P 7 137 0.19 99 P 6 SAI 02H -0.86 02H 02H 128 HOT 5803P 23 137 0.22 74 P 6 MAI 02H +0.79 02H 02H 130 HOT 5803P 6 138 0.18 80 P 6 SAI 01H +0.48 01H 01H 128 HOT 5803P 0.27 88 P 6 SAI 04H +0.84 04H 04H 128 HOT 5803P 10 138 0.15 49 P 6 SAI 02H -0.16 02H 02H 128 HOT 5803P 0.17 44 P 6 SAI 03H +0.90 03H 03H 128 HOT 5803P 18 138 0.20 79 P 6 SAI 01H +0.68 01H 01H 152 HOT 5803P 0.37 103 P 6 SAI 03H +0.76 03H 03H 152 HOT 5803P 0.21 67 P 6 SAI 05H +0.79 05H 05H 152 HOT 5803P 0.24 75 P 6 SAI 07H -0.17 07H 07H 152 HOT 5803P 94 138 0.18 102 P 6 SAI 01H +0.50 01H 01H 133 HOT 5803P
Framatome ANP Inc. 1/22J2005 14:30 Attachment 1 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 22 of 23 Tubes with Bobbin 40-100% TWD and +Point Vol. Circ and Axial Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 4 140 0.21 89 P6 SA= 03H +0.65 03H 03H 128 HOT 5803P 24 140 0.37 96 P6 SAI 02H -0.74 02H 02H 130 HOT 5803P 84 140 0.26 122 P6 SAI 01H +0.74 01H 01H 131 HOT 5803P 5 141 0.35 109 P6 SAI 02H -0.43 02H 02H 128 HOT 5803P 6 142 0.13 61 P6 SAI 03H +0.31 03H 03H 128 HOT 5803P 10 142 0.17 77 P6 SAI 03H +0.49 03H 03H 181 HOT 5803P 26 142 0.28 93 P6 SAI 03H +0.75 03H 03H 130 HOT 5803P 58 142 0.20 97 P6 SAI 01H +0.32 01H 01H 131 HOT 5803P 70 142 0.19 106 P6 SAI 01H +0.92 01H 01H 131 HOT 5803P 78 142 0.16 109 P6 SAI 01H +0.83 01H 01H 131 HOT 5803P 0.22 109 P6 SAI 01H +0.34 01H 01H 131 HOT 5803P 92 142 0.39 99 P6 SAI 01H -0.25 01H 01H 133 HOT 5803P 7 143 0.34 77 P6 SAI 02H +0.50 02H 02H 128 HOT 5803P 0.36 96 P6 SAI 03H +0.57 03H 03H 128 HOT 5803P 19 143 0.38 92 P6 SAI 01H +0.89 01H 01H 128 HOT 5803P 0.22 82 P6 SAI 01H -0.19 01H 01H 128 HOT 5803P 23 143 0.30 74 P6 SAI 02H -0.78 02H 02H 128 HOT 5803P 27 143 0.26 79 P6 SAI 02H +0.83 02H 02H 170 HOT 5803P 0.14 65 P6 SAI 02H -0.47 02H 02H 170 HOT 5803P 4 144 0.29 79 P6 SAI 03H +0.53 03H 03H 128 HOT 5803P 10 144 0.11 72 P6 SAI 02H -0.56 02H 02H 181 HOT 5803P 0.19 84 P6 SAI 02H +0.84 02H 02H 181 HOT 5803P 0.15 98 P6 SAI 03H +0.68 03H 03H 181 HOT 5803P 24 144 0.28 98 P6 SAI 01H +0.81 01H 01H 128 HOT 5803P 0.36 107 P6 SAI 04H +0.61 04H 04H 128 HOT 5803P 36 144 0.43 102 P6 SAI 02H -0.53 02H 02H 130 HOT 5803P 5 145 0.08 53 P6 SAI 02H -0.90 02H 02H 128 HOT 5803P 13 145 0.14 67 P6 SAI 07H -0.53 07C 07H 157 HOT 5602P 15 145 0.29 82 P6 SAI 02H +0.86 02H 02H 128 HOT 5803P 18 146 0.41 94 P6 SAI 04H +0.64 04H 04H 128 HOT 5803P 34 146 0.25 69 P6 SAI 03H +0.92 03H 03H 130 HOT 5803P 54 146 0.29 90 P6 SAI 01H -0.61 01H 01H 131 HOT 5803P 9 147 0.24 47 P6 SAI 02H +0.49 02H 02H 128 HOT 5803P 13 147 0.26 85 P6 SAI 04H +0.92 04H 04H 128 HOT 5803P 17 147 0.76 101 P6 SAI 02H +0.57 02H 02H 128 HOT 5803P 6 148 0.20 54 P6 SAI 02H +0.52 02H 02H 128 HOT 5803P 16 148 0.32 88 P6 SAI 05H +0.75 05H 05H 128 HOT 5803P 7 149 0.22 75 P6 SAI 02H +0.85 02H 02H 128 HOT 5803P 0.25 84 P6 SAI 04H +0.82 04H 04H 128 HOT 5803P 9 149 0.38 87 P6 SAI 01H +0.60 01H 01H 128 HOT 5803P 11 149 0.15 254 P6 SAI 02H -0.71 02H 02H 128 HOT 5803P 0.38 101 P6 SAI 03H -0.71 03H 03H 128 HOT 5803P 0.20 71 P6 SAI 02H +0.49 02H 02H 128 HOT 5803P 2 150 0.31 106 P6 SAI 03H +0.83 03H 03H 130 HOT 5803P 6 150 0.18 82 P6 SAI 03H +0.82 03H 03H 130 HOT 5803P 8 150 0.25 83 P6 SAI 01H -0.58 01H 01H 130 HOT 5803P 0.28 67 P6 MAI 07H -0.48 07H 07H 130 HOT 5803P 10 150 0.17 81 P6 SAI 05H +0.77 05H 05H 130 HOT 5803P 14 150 0.80 103 P6 SAI 03H +0.12 03H 03H 128 HOT 5803P 5 151 0.19 65 P6 MAI 04H +0.89 04H 04H 128 HOT 5803P 15 151 0.22 102 P6 SAI 01H +0.80 01H 01H 130 HOT 5803P 6 152 0.20 82 P6 SAI 02H +0.93 02H 02H 130 HOT 5803P 8 152 0.20 82 P6 SAI 01H +0.79 01H 01H 130 HOT 5803P 0.29 89 P6 SAI 02H -0.56 02H 02H 130 HOT 5803P
Framatome ANP Inc. 1/22/2005 14:30 Attachment 1 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 23 of 23 Tubes with Bobbin 40-100% TWD and +Point Vol. Circ and Axial Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 0.20 82 P 6 SAI 03H +0.40 03H 03H 130 HOT 5803P 5 153 0.13 83 P 6 SAI 01H +0.92 01H 01H 128 HOT 5803P 7 153 0.53 99 P 6 SAI 02H +0.49 02H 02H 130 HOT 5803P 9 153 0.47 106 P 6 SAI 04H -0.01 04H 04H 130 HOT 5803P 0.21 102 P 6 SAI 04H -0.89 04H 04H 130 HOT 5803P 11 153 0.64 106 P 6 SAI 02H +0.79 02H 02H 130 HOT 5803P 8 154 0.32 85 P 6 SAI 03H -0.20 03H 03H 130 HOT 5803P 0.28 115 P 6 SAI 04H +0.88 04H 04H 130 HOT 5803P 10 154 0.17 48 P 6 SAI 03H -0.58 03H 03H 130 HOT 5803P 0.24 66 P 6 MAI 04H -0.55 04H 04H 130 HOT 5803P 16 154 0.22 89 P 6 SAI 04H +1.01 04H 04H 130 HOT 5803P 8 156 0.19 80 P 6 SAI 02H -0.78 02H 02H 130 HOT 5803P 10 156 0.22 74 P 6 SAI 02H +0.39 02H 02H 130 HOT 5803P 19 157 0.28 72 P 6 SAI 02H +0.82 02H 02H 130 HOT 5803P 10 158 0.19 81 P 6 MAI 02H -0.76 02H 02H 130 HOT 5803P 7 159 0.23 109 P 6 SAI 03H +0.76 03H 03H 130 HOT 5803P 17 159 0.47 103 P 6 SAI 02H +0.28 02H 02H 130 HOT 5803P 8 160 0.15 79 P 6 SAI 03H +0.74 03H 03H 130 HOT 5803P 23 161 0.28 105 P 6 SAI 02H +0.77 02H 02H 130 HOT 5803P 7 165 0.17 78 P 6 SAI 03H -0. 19 03H 03H 131 HOT 5803P Total Tubes : 798 Total Records: 1208
Framatome ANP Inc. 1/22/2005 14:30 Attacbment 2 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 1 of 6 Tubes with Bobbin 20-39% TWD Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 72 20 0.37 130 P 2 TWD 25 V=2 -0.49 TEC TEH 20 HOT 600UL 88 20 0.46 123 P 2 IWD 28 VS2 -0.89 TEH TEC 63 COLD 600UL 87 21 0.50 114 P 2 TWD 20 VS2 +0.90 TEH TEC 13 COLD 600UL 89 21 0.39 61 P 2 TWD 26 VS2 +0.73 TEH TEC 14 COLD 600UL 86 22 1.00 84 P 2 TWD 34 VS2 +0.86 TEH TEC 13 COLD 60OUL 1.19 122 P 4 TWD 35 VS3 -0.88 TEH TEC 13 COLD 60OUL 90 24 0.64 134 P 2 TWD 29 VS3 -0.78 TEH TEC 13 COLD 60OUL 61 25 0.44 153 P 2 TWD 27 VS4 +0.78 TEC TEH 30 HOT 60OUL 92 26 0.39 137 P 2 TWD 22 VS4 -0.80 TEH TEC 13 COLD 60OUL 0.58 122 P 2 TND 28 VS4 +0.45 TEH TEC 13 COLD 600UL 88 28 0.44 79 P 2 IWD 24 VS4 -0.84 TEH TEC 13 COLD 60OUL 0.42 42 P 2 TWD 23 VS4 -0.25 TEH TEC 13 COLD 60OUL 98 28 0.61 116 P 2 TWD 32 VS4 +0.57 TEH TEC 14 COLD 60OUL 81 29 0.74 115 P 2 IWD 27 VS4 -0.90 TEH TEC 13 COLD 60OUL 0.42 58 P 2 TWD 23 VS3 -0.97 TEH TEC 13 COLD 600UL 0.75 99 P 2 TWD 31 VS3 -0.21 TEH TEC 13 COLD 60OUL 0.85 104 P 2 TWD 33 VS3 +0.68 TEH TEC 13 COLD 60OUL 96 30 0.29 146 P 2 TWD 21 VS2 +0.91 TEH TEC 14 COLD 600UL 0.44 16 P 2 TWD 27 DCT +0.00 TEH TEC 14 COLD 60OUL 97 31 0.45 151 P 2 TWD 24 VS2 +0.86 TEH TEC 13 COLD 600UL 105 33 0.33 92 P 2 TWD 20 VS2 +0.10 TEH TEC 13 COLD 600UL 94 34 0.35 145 P 2 TWD 21 VS2 -0.94 TEH TEC 13 COLD 600UL 96 34 0.64 136 P 2 TWD 29 VS2 -0.84 TEH TEC 13 COLD 60OUL 51 35 0.41 124 P 2 TWD 25 VS3 -0.92 TEC TEN 35 HOT 600UL 82 40 0.37 142 P 2 TWD 24 VS3 -0.82 TEH TEC 17 COLD 600UL 0.29 151 P 2 TWD 21 VS4 -0.84 TEH TEC 17 COLD 600UL 0.28 144 P 2 TWD 21 VS4 +0.54 TEH TEC 17 COLD 600UL 43 41 0.32 129 P 2 TWD 20 VS3 +0.71 TEH TEC 5 COLD 600UL 95 41 0.47 28 P 2 TWD 26 DHT -0.24 TEH TEC 16 COLD 60OUL 82 44 1.04 94 P 2 TWD 31 VS2 +0.68 TEH TEC 15 COLD 60OUL 94 44 0.35 160 P 2 TWD 22 DCT +0.00 TEH TEC 16 COLD 600UL 122 44 0.41 147 P 2 TWD 24 DCT +0.00 TEH TEC 16 COLD 60OUL 3 49 0.37 59 P 2 TWD 25 02C -0.71 07H TEC 67 COLD 580SF 48 50 0.51 114 P 2 TWD 25 VS3 -0.76 TEH TEC 9 COLD 600UL 124 50 0.42 154 P 2 TWD 24 VS1 +0.78 TEH TEC 16 COLD 600UL 0.67 90 P 2 TWD 30 VS2 -0.92 TEH TEC 16 COLD 600UL 125 51 0.44 23 P 2 TWD 25 DHB +2.13 TEH TEC 16 COLD 60OUL 78 52 0.45 138 P 2 TWD 26 VS4 +0.77 TEH TEC 10 COLD 60OUL 84 52 0.91 100 P 2 TWD 29 VS3 +0.06 TEH TEC 15 COLD 600UL 85 53 0.54 51 P 2 TWD 28 08H +0.61 TEH TEC 16 COLD 600UL 49 55 0.34 156 P 2 TWD 20 VS3 -0.92 TEH TEC 9 COLD 600UL 95 57 0.24 100 P 2 TWD 20 VS2 +0.92 TEH TEC 20 COLD 600UL 129 57 0.51 74 P 2 TWD 30 DCT +0.00 TEH TEC 20 COLD 600UL 90 58 0.28 84 P 2 TWD 21 VS3 -0.69 TEH TEC 17 COLD 600UL 130 58 0.36 119 P 2 TWD 24 DCB +0.16 TEH TEC 17 COLD 600UL 132 58 0.36 151 P 2 TWD 27 DCB +0.28 TEH TEC 53 COLD 600UL 0.45 98 P 2 TWD 29 DHB +0.08 TEH TEC 53 COLD 600UL 93 59 0.38 136 P 2 TWD 27 VS4 +0.70 TEH TEC 18 COLD 600UL 95 59 0.35 108 P 2 TWD 23 VS2 +0.87 TEH TEC 17 COLD 60OUL 0.40 131 P 2 TWD 25 VS3 +0.57 TEH TEC 17 COLD 600UL 127 59 0.32 81 P 2 TWD 24 VS1 +0.81 TEH TEC 18 COLD 60OUL 82 60 0.27 146 P 2 TWD 21 VS3 -0.79 TEH TEC 18 COLD 600UL 128 60 0.31 120 P 2 TWD 22 DHB +0.02 TEH TEC 17 COLD 600UL 130 60 0.40 38 P 2 TWD 25 DHT -0.06 TEH TEC 17 COLD 600UL
Framatome ANP Inc. 1/22/2005 14:30 Attachment 2 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 2 of 6 Tubes with Bobbin 20-39% TWD Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 129 61 0.33 17 P 2 TWD 23 DHT +0.00 TEN TEC 17 COLD 60.UL 78 62 0.61 106 P 2 TWD 28 VS2 +0.65 TEH TEC 11 COLD 600UL 96 62 0.33 103 P 2 TWD 23 VS3 -0.69 TEH TEC 17 COLD 60OUL 134 62 0.21 149 P 2 TWD 20 VS3 +0.68 TEH TEC 53 COLD 60OUL 0.22 138 P 2 TWD 21 DHT +0.00 TEH TEC 53 COLD 60OUL 19 63 0.56 41 P 2 TWD 27 VS3 -0.90 TEH TEC 11 COLD 60OUL 133 63 0.46 93 P 2 TWD 25 VS1 +0.74 TEH TEC 52 COLD 60OUL 135 63 0.47 128 P 2 TWD 30 09H +0.73 TEH TEC 53 COLD 600UL 0.35 85 P 2 TWD 26 DHB +0.00 TEH TEC 53 COLD 600UL 0.95 61 P 2 TWD 37 VS1 -0.90 TEH TEC 53 COLD 600UL 0.37 87 P 2 TWD 27 VS1 +0.86 TEH TEC 53 COLD 600UL 94 64 0.80 70 P 2 TWD 29 VS2 +0.76 TEH TEC 19 COLD 60OUL 128 64 0.53 125 P 2 IWD 23 VS1 +0.69 TEH TEC 19 COLD 60OUL 132 64 0.43 97 P 2 TWD 24 DHT +0.00 TEH TEC 52 COLD 600UL 31 67 0.57 91 P 2 TWD 27 DCB +0.00 TEH TEC 11 COLD 600UL 79 67 0.31 128 P 2 TD 20 VS2 -0.83 TEH TEC 11 COLD 60OUL 0.44 121 P 2 TWD 24 VS4 +0.63 TEH TEC 11 COLD 60OUL 133 67 0.35 79 P 2 TKD 26 VS1 +0.62 TEH TEC 53 COLD 60OUL 34 68 0.35 117 P 2 TWD 21 DHB +0.00 TEH TEC 12 COLD 60OUL 35 69 0.79 86 P 2 TWD 34 DCB +0.67 TEH TEC 64 COLD 60OUL 0.50 120 P 2 TWD 27 DHB +0.25 TEH TEC 64 COLD 60OUL 37 69 0.40 124 P 2 TWD 26 DHB +0.37 TEH TEC 64 COLD 60OUL 0.83 101 P 2 IWD 35 DCB +0.47 TEH TEC 64 COLD 60OUL 40 70 0.27 70 P 2 TWD 21 DHB +0.43 TEH TEC 64 COLD 60OUL 42 70 0.83 108 P 2 TWD 35 DCB +0.28 TEH TEC 64 COLD 60OUL 44 70 0.54 112 P 2 TWD 28 DCB +0.00 TEC TEN 4 HOT 600UL 50 70 0.30 98 P 2 TWD 21 DCB +0.00 TEC TEH 4 HOT 60OUL 84 70 0.28 150 P 2 TW@D 20 07H +0.89 TEN TEC 21 COLD 60OUL 136 70 0.74 142 P 2 TWD 31 VS1 -0.84 TEH TEC 52 COLD 60OUL 0.62 104 P 2 TWD 29 VS3 -0.74 TEH TEC 52 COLD 60OUL 39 71 0.39 126 P 2 TWD 24 DCB +0.35 TEH TEC 64 COLD 60OUL 43 71 0.41 43 P 2 TWD 25 DCB +0.00 TEC TEN 4 NOT 60OUL 45 71 0.55 132 P 2 TWD 27 DCB +0.47 TEC TEH 3 HOT 60OUL 51 71 0.26 65 P 2 TWD 20 DCT +0.00 TEC TEH 4 HOT 60OUL 42 72 0.71 101 P 2 TWD 31 DCT +0.00 TEC TEH 4 HOT 60OUL 1.07 84 P 2 TWD 35 DHB +0.00 TEC TEH 4 HOT 600UL 44 72 0.41 134 P 2 TWD 23 DHB +0.35 TEC TEH 3 HOT 60OUL 50 72 0.49 101 P 2 TWD 27 DCB +0.00 TEC TEH 4 HOT 60OUL 126 72 0.35 64 P 2 TWD 21 08H +0.90 TEN TEC 22 COLD 600UL 134 72 0.40 49 P 2 TWD 23 VS1 +0.82 TEH TEC 52 COLD 60OUL 43 73 0.47 81 P 2 TWD 25 DHB +0.37 TEC TEN 3 HOT 600UL 49 73 0.51 121 P 2 TWD 28 DCB +0.00 TEC TEH 4 NOT 60OUL 51 73 0.32 96 P 2 TWD 20 DCB +0.21 TEC TEH 3 HOT 60OUL 53 73 0.33 51 P 2 TWD 22 DCB +0.00 TEC TEH 4 HOT 60OUL 135 73 0.81 59 P 2 TWD 32 VS1 +0.80 TEN TEC 52 COLD 600UL 0.32 121 P 2 TWD 20 VS2 +0.66 TEH TEC 52 COLD 60OUL 0.61 24 P 2 TD 28 VS3 +0.70 TEH TEC 52 COLD 60OUL 1.11 132 P 2 TD 35 VS4 +0.78 TEH TEC 52 COLD 60OUL 46 74 0.40 71 P 2 TWD 25 DHB +0.00 TEC TEH 4 HOT 60OUL 48 74 0.33 105 P 2 TWD 20 DCT -0.25 TEC TEH 3 HOT 60OUL 54 74 0.30 154 P 2 TWD 21 DCT +0.00 TEC TEH 4 HOT 60OUL 82 74 0.50 124 P 2 TWD 27 VS2 -0.76 TEH TEC 21 COLD 60OUL 45 75 0.37 118 P 2 TWD 23 DCT +0.00 TEC TEH 3 HOT 60OUL 0.58 101 P 2 TWD 29 DHT +0.00 TEC TEH 3 HOT 60OUL
Framatome ANP Inc. 1/22/2005 14:30 Attacm^ent 2 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 3 of 6 Tubes with Bobbin 20-39% TWD Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 57 75 0.44 89 P 2 TWD 25 VS3 -0.60 TEC TEH 3 HOT )= = 60 OUL 93 75 0.48 81 P 2 TWD 27 VS2 -0.39 TEH TEC 21 COLI 60OUL 133 75 0.32 123 P 2 TWD 25 VS1 +0.66 TEH TEC 53 COLI 60OUL 46 76 0.48 116 P 2 TWD 27 DCT +0.00 TEC TEH 4 HOT 60OUL 0.72 71 P 2 TWD 32 DHT +0.00 TEC TEH 4 HOT 600UL 0.83 94 P 2 TWD 33 DHB +0.00 TEC TEH 4 HOT 60OUL 48 76 0.34 86 P 2 TD 22 DCB +0.00 TEC TEH 3 HOT 60OUL 0.35 87 P 2 TWD 21 DHB +0.19 TEC TEH 3 HOT 60OUL 58 76 0.37 104 P 2 TWD 24 DCB +0.00 TEC TEH 4 HOT 60OUL 136 76 0.31 134 P 2 TWD 20 DCT +0.00 TEH TEC 52 COLI 60OUL 47 77 0.52 11 P 2 TWD 27 DHT +0.00 TEC TEH 3 HOT 60OUL 0.55 97 P 2 TWD 28 DHB +0.00 TEC TEH 3 HOT 60OUL 51 77 1.25 97 P 2 TWD 37 DCT +0.00 TEC TEH 4 HOT 60OUL 53 77 1.34 19 P 2 TWD 38 DHT +0.00 TEC TEH 3 HOT 60OUL 0.91 93 P 2 TWD 34 DHB +0.00 TEC TEH 3 HOT 60OUL 0.37 115 P 2 TWD 21 DCT +0.00 TEC TEH 3 HOT 60OUL 57 77 0.43 123 P 2 TWD 25 DCT +0.00 TEC TEH 3 HOT 60OUL 73 77 0.30 82 P 2 TWD 21 VS2 -0.86 TEC TEH 4 HOT 60OUL 93 77 0.31 86 P 2 TWD 20 DCB +0.46 TEH TEC 54 COLD 60OUL 133 77 0.20 138 P 2 TWD 20 VS5 +0.77 TEH TEC 53 COLD 600UL 48 78 0.54 29 P 2 TWID 28 DHB +0.00 TEC TEH 3 HOT 60OUL 56 78 1.05 90 P 2 TWD 35 DCB +0.00 TEC TEH 4 HOT 60OUL 72 78 0.52 128 P 2 TWD 28 VS4 +0.85 TEC TEH 4 HOT 60OUL 96 78 0.79 86 P 2 TWD 33 VS3 -0.83 TEH TEC 54 COLE 60OUL 49 79 0.76 103 P 2 TWD 32 DCT +0.00 TEC TEH 5 HOT 60OUL 1.12 81 P 2 TWD 36 VS3 +0.97 TEC TEH 5 HOT 60OUL 0.77 56 P 2 TWD 32 VS3 -0.10 TEC TEH 5 HOT 60OUL 0.86 82 P 2 TWD 33 DHT +0.00 TEC TEH 5 HOT 60OUL 51 79 0.95 104 P 2 TWD 34 DCT +0.00 TEC TEH 6 HOT 600UL 0.44 152 P 2 TWD 26 DHT +0.00 TEC TEH 6 HOT 600UL 53 79 0.35 117 P 2 TWD 21 DCT +0.00 TEC TEH 5 HOT 60OUL 61 79 0.91 102 P 2 TWD 34 DCB +0.00 TEC TEH 6 HOT 60OUL 54 80 0.36 101 P 2 TWD 22 DCB +0.00 TEC TEH 5 HOT 60OUL 0.43 150 P 2 TWD 24 DCT +0.00 TEC TEH 5 HOT 600UL 0.44 130 P 2 TWD 24 DHT +0.00 TEC TEH 5 HOT 60OUL 0.37 112 P 2 TWD 22 DHB +0.00 TEC TEH 5 HOT 60OUL 62 80 0.94 69 P 2 TWD 34 DCB +0.00 TEC TEH 5 HOT 60OUL 53 81 0.77 75 P 2 TWD 32 DCT +0.00 TEC TEH 5 HOT 60OUL 0.31 159 P 2 TWD 20 DHT +0.00 TEC TEH 5 HOT 60OUL 0.53 50 P 2 TWD 27 DHB +0.00 TEC TEH 5 HOT 600UL 59 81 0.38 110 P 2 TWD 23 DCB +0.00 TEC TEH 5 HOT 60OUL 50 82 0.57 79 P 2 TWD 28 DCB +0.00 TEC TEH 5 HOT 600UL 56 82 0.40 46 P 2 TWD 24 DCT +0.00 TEC TEH 6 HOT 60OUL 60 82 0.65 119 P 2 TWD 30 DHB +0.00 TEC TEH 6 HOT 60OUL 51 83 0.46 112 P 2 TWD 25 DCB +0.00 TEC TEH 5 HOT 60OUL 0.56 108 P 2 TWD 28 DHB +0.00 TEC TEH 5 HOT 60OUL 85 83 0.34 89 P 2 TWD 22 VS2 -1.38 TEH TEC 25 COLD 60OUL 135 83 0.21 137 P 2 TWD 20 VS1 -0.77 TEH TEC 53 COLD 60OUL 52 84 0.54 107 P 2 TWD 27 DCT +0.00 TEC TEH 5 HOT 60OUL 56 84 0.51 77 P 2 TWD 27 DCB +0.00 TEC TEH 6 HOT 60OUL 61 85 0.37 95 P 2 TWD 24 DCB +0.00 TEC TEH 6 HOT 60OUL 77 85 0.27 33 P 2 TWD 20 VS4 +0.82 TEC TEH 6 HOT 600UL 54 86 0.33 121 P 2 TWD 22 DCT +0.00 TEC TEH 6 HOT 600UL 0.60 83 P 2 TWD 29 VS3 -0.69 TEC TEH 6 HOT 60OUL
Framatome ANP Inc. 1/22/2005 14:30 Attachment 2 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: SIG A Page 4 of 6 Tubes with Bobbin 20-39% TWD Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 0.31 79 P2 TWD 21 DHB +0.00 TEC TEH 6 HOT 60 OUL 56 86 1.11 110 P2 TWD 36 DCB +0.00 TEC TEH 5 HOT 60OUL 58 86 0.93 125 P2 TWD 34 DCB +0.00 TEC TEH 6 HOT 600UL 60 86 0.33 84 P2 TWD 21 DHB +0.00 TEC TEH 5 HOT 60OUL 62 86 0.34 152 P2 TWD 22 DCB +0.00 TEC TEH 6 HOT 60OUL 92 86 0.56 135 P2 TWD 28 VS2 +0.88 TEC TEC 25 COLD 600UL 1.19 130 P2 TWD 36 VS3 -0.84 TEH TEC 25 COLD 60OUL P2 TEC 600UL 0.30 149 TWD 20 VS4 -0.86 TEH 25 COLD 49 87 1.36 107 P2 TWD 37 DCT +0.00 TEC TEH 6 HOT 600UL 0.49 82 P2 TWD 27 DHB +0.00 TEC TEH 6 HOT 60OUL 51 87 0.85 55 P2 TWD 33 DCT +0.00 TEC TEH 5 HOT 60OUL 0.59 136 P2 TWD 28 DHB +0.00 TEC TEH 5 HOT 600UL 55 87 0.49 55 P2 TWD 26 DCT +0.00 TEC TEH 5 HOT 600UL 0.49 125 P2 TWD 26 VS3 -0.85 TEC TEH 5 HOT 60OUL 0.51 80 P2 TWD 27 DHB +0.00 TEC TEH 5 HOT 60OUL 57 87 0.68 119 P2 TWD 31 DCB +0.00 TEC TEH 6 HOT 600UL 59 87 0.47 103 P2 TWD 25 DHB +0.00 TEC TEH 5 HOT 600UL 93 87 0.40 47 P2 TWD 24 VS2 -0.98 TEH TEC 25 COLD 60OUL 0.29 134 P2 TWD 20 VS4 +1.00 TEH TEC 25 COLD 60OUL 97 87 0.38 82 P2 TWD 23 VS2 -0.66 TEH TEC 25 COLD 600UL 0.31 124 P2 TWD 21 VS3 +0.78 TEH TEC 25 COLD 600UL 50 88 0.97 87 P2 TWD 34 DCB +0.00 TEC TEC 6 HOT 600UL 0.89 99 P2 TWD 34 DHT +0.00 TEC TEH 6 HOT 60OUL 52 88 0.54 99 P2 TWD 27 DCB +0.00 TEC TEH 5 HOT 60OUL 0.59 139 P2 TWD 28 DCT +0.00 TEC TEH 5 HOT 60OUL 56 88 0.48 138 P2 TWD 26 DCT +0.00 TEC TEH 5 HOT 60OUL 94 88 0.28 106 P2 TWD 20 VS2 -0.80 TEC TEC 26 COLD 60OUL 0.35 117 P2 TWD 23 VS4 +0.74 TEH TEC 26 COLD 600UL 53 89 0.56 131 P2 TWD 28 DHB +0.00 TEC TEN 5 NOT 60OUL 95 89 0.41 118 P2 TWD 24 VS4 -0.60 TEH TEC 25 COLD 60OUL 46 90 0.30 143 P2 TWD 21 DCB +0.00 TEC TEH 6 HOT 60OUL 0.58 118 P2 TWD 29 DCT +0.00 TEC TEC 6 HOT 60OUL 0.34 85 P2 TWD 22 DHT +0.00 TEC TEH 6 HOT 60OUL 48 90 0.33 139 P2 TWD 21 DCT +0.00 TEC TEH 5 HOT 600UL 0.35 122 P2 TWD 22 DCB +0.00 TEC TEH 5 HOT 60OUL 50 90 0.29 96 P2 TWD 21 DCB +0.00 TEC TEH 6 HOT 60OUL 82 90 0.32 75 P2 TWD 21 VS3 -0.64 TEH TEC 25 COLD 60OUL 45 91 0.75 86 P2 TWD 31 DHB +0.04 TEC TEH 5 HOT 60OUL 0.36 60 P2 TWD) 22 DCT +0.00 TEC TEC 5 HOT 60OUL 0.66 173 P2 TWD 30 DHT +0.00 TEC TEH 5 HOT 60OUL 47 91 0.53 57 P2 TWD 28 DHB +0.00 TEC TEH 6 HOT 60OUL 51 91 0.40 78 P2 TWD 24 DHB +0.00 TEC TEH 6 HOT 600UL 139 91 0.26 133 P2 TWD 23 VS5 +0.72 TEH TEC 56 COLD 60OUL 0.75 95 P2 TWD 35 DHT +0.00 TEN TEC 56 COLD 60OUL 1.25 17 P2 TWD 39 DCT +0.00 TEH TEC 56 COLD 60OUL 52 92 0.72 20 P2 TWD 31 DCT +0.00 TEC TEN 6 HOT 600UL 0.65 157 P2 TWD 30 VS3 +0.99 TEC TEN 6 HOT 60OUL 56 92 0.62 8 P2 TWD 30 DHT +0.00 TEC TEH 6 HOT 60OUL 58 92 0.38 102 P2 TWD 23 DCB +0.00 TEC TEH 5 HOT 600UL 132 92 0.36 127 P2 TWD 22 VS1 +0.98 TEH TEC 55 COLD 600UL 43 93 0.32 93 P2 TWD 20 DHB +0.00 TEC TEH 5 HOT 60OUL 0.61 131 P2 TWD 29 DCB +0.00 TEC TEH 5 HOT 60OUL 45 93 0.38 85 P2 TWD 24 DCB +0.00 TEC TEH 6 HOT 60OUL 97 93 0.37 137 P2 TWD 26 VS3 +0.67 TEH TEC 28 COLD 60OUL
Framatome ANP Inc. 1/22/2005 14:30 Attachment 2 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 5 of 6 Tubes with Bobbin 20-39% TWD Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 44 94 0.50 114 P 2 TWD 27 DHB +0.00 TEC TEH 6 HOT 60=OUL 43 95 0.28 92 P 2 TWD 20 VS3 +1.04 TEC TEH 6 HOT 60OUL 49 95 0.39 50 P 2 TWD 23 DCT -0.06 TEC TEH 5 HOT 60OUL 0.49 125 P 2 TWD 26 VS3 -0.60 TEC TEH 5 HOT 600UL 38 96 1.00 99 P 2 TWD 35 DCB +0.00 TEC TEH 6 HOT 600UL 0.37 122 P 2 TWD 24 DCT +0.00 TEC TEH 6 HOT 60OUL 0.65 84 P 2 TWD 30 DHT +0.00 TEC TEH 6 HOT 60OUL 42 96 0.84 94 P 2 TWD 33 DHT +0.00 TEC TEH 6 HOT 60OUL 48 96 0.44 130 P 2 TWD 25 VS3 -0.99 TEC TEH 5 HOT 60OUL 0.37 132 P 2 TWD 22 VS3 +0.77 TEC TEH 5 HOT 60OUL 54 96 0.42 97 P 2 TWD 25 VS3 -0.70 TEC TEH 6 HOT 60OUL 94 96 0.73 82 P 2 TWD 31 VS2 -0.90 TEH TEC 27 COLE 60OUL 0.47 153 P 2 TWD 26 VS4 +0.68 TEH TEC 27 COLE 60OUL 41 97 0.27 106 P 2 TWD 20 DHB +0.00 TEC TEH 6 HOT 60OUL 43 97 0.39 144 P 2 TWD 23 DCB +0.00 TEC TEH 5 HOT 60OUL 45 97 0.39 90 P 2 TWD 24 DCT +0.00 TEC TEH 6 HOT 60OUL 47 97 0.40 112 P 2 TWD 23 DCB +0.00 TEC TEH 5 HOT 60OUL 0.59 129 P 2 TWD 28 VS3 +1.07 TEC TEH 5 HOT 60OUL 135 97 0.48 48 P 2 TWD 25 VS1 -0.82 TEH TEC 55 COLE 600UL 0.60 63 P 2 TWD 28 VS3 +0.94 TEH TEC 55 COLE 60OUL 0.41 107 P 2 TWD 23 VS5 +0.04 TEH TEC 55 COLE 60OUL 42 98 0.31 91 P 2 TWD 22 DCB +0.00 TEH TEC 62 COLE 60OUL 50 98 0.31 82 P 2 TWD 20 VS3 -0.78 TEC TEH 5 HOT 60OUL 134 98 0.45 109 P 2 TWD 30 VS3 -0.54 TEH TEC 56 COLE 60OUL 138 98 0.96 121 P 2 TWD 37 DHT +0.06 TEH TEC 56 COLEI 60OUL 37 99 0.35 114 P 2 TWD 23 DCB +0.00 TEH TEC 62 COLEI 60OUL 39 99 0.19 100 P 2 TWD 20 DCB +0.00 TEH TEC 62 COLEI 60OUL 45 99 0.39 71 P 2 TWD 25 VS3 +0.85 TEH TEC 62 COLEI 60OUL 137 99 0.29 101 P 2 TWD 24 VS5 -0.82 TEH TEC 56 COLEI 60OUL 46 100 0.60 41 P 2 TWD 28 VS3 +0.71 TEH TEC 43 COLDI 600UL 54 100 0.46 67 P 2 TWD 24 VS3 +0.77 TEH TEC 43 COLDI 600UL 137 101 0.51 45 P 2 TWD 31 09H +1.00 TEH TEC 56 COLD 60OUL 0.29 156 P 2 TWD 25 DHT +0.00 TEH TEC 56 COLDI 600UL 40 102 0.22 163 P 2 TWD 22 VS3 -0.93 TEH TEC 44 COLDI 60OUL 48 102 0.20 72 P 2 TWD 22 DCB +0.12 TEH TEC 44 COLDI 60OUL 134 102 0.54 140 P 2 TWD 32 DCT +0.00 TEH TEC 56 COLDI 60OUL 91 103 0.43 130 P 2 TWD 25 VS4 -0.99 TEH TEC 35 COLDI 60OUL 129 103 0.32 47 P 2 TWD 21 VS5 -0.96 TEH TEC 35 COLDI 600UL 95 105 0.46 90 P 2 TWD 26 VS3 +0.76 TEH TEC 35 COLDI 60OUL 126 106 0.27 97 P 2 TWD 20 VS1 -0.86 TEH TEC 35 COLDI 60OUL 96 108 0.46 122 P 2 TWD 28 VS2 -0.72 TEH TEC 36 COLDI 60OUL 0.65 114 P 2 TWD 33 VS3 -0.68 TEH TEC 36 COLD 60OUL 0.34 101 P 2 TWD 23 VS4 +0.68 TEH TEC 36 COLD 60OUL 132 108 0.34 34 P 2 TWD 21 DCB +0.00 TEH TEC 55 COLDI 60OUL 133 109 0.21 145 P 2 TWD 21 DHT +0.00 TEH TEC 56 COLDI 600UL 46 112 0.31 59 P 2 TWD 24 VS3 +0.67 TEH TEC 42 COLD 60OUL 82 112 0.28 140 P 2 TWD 24 VS4 +0.62 TEH TEC 34 COLDI 600UL 51 113 0.32 111 P 2 TWD 24 VS3 +0.87 TEH TEC 41 COLD 60OUL 53 113 0.23 132 P 2 TWD 20 VS3 +0.99 TEH TEC 41 COLD 60OUL 123 113 0.29 50 P 2 TWD 24 VS1 -0.74 TEH TEC 34 COLD 60OUL 0.26 138 P 2 TWD 23 VS3 +0.78 TEH TEC 34 COLD 60OUL 0.31 147 P 2 TWD 25 VS4 +1.02 TEH TEC 34 COLD 600UL 84 114 0.34 77 P 2 TWD 21 VS4 -0.88 TEH TEC 33 COLD 60OUL 47 115 0.30 118 P 2 TWD 23 VS3 +0.97 TEH TEC 41 COLD 60OUL
Framatome ANP Inc. 1/22/2005 14:30 Attachment 2 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 6 of 6 Tubes with Bobbin 20-39% TWD Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 0.41 154 P2 =WD 26 VS3 -0.79 TEH TEC 41 COLD 60=OUL 92 116 0.22 131 P2 TWD 21 VS2 -0.68 TEH TEC 34 COLD 600UL 94 116 0.34 37 P2 TWD 21 VS4 -0.88 TEH TEC 33 COLD 60OUL 127 117 0.38 66 P2 TWD 23 VS1 +0.74 TEH TEC 31 COLD 600UL 86 118 0.24 142 P2 TWD 20 VS3 -0.74 TEH TEC 32 COLD 60OUL 37 119 0.32 88 P2 TWD 21 VS3 +0.97 TEH TEC 39 COLD 60OUL 51 119 0.26 34 P2 TWD 20 VS3 +0.83 TEH TEC 40 COLD 60OUL 84 120 0.38 128 P2 TWD 23 VS4 -0.88 TEH TEC 31 COLD 60OUL 94 120 0.57 112 P2 TWD 32 VS2 +0.62 TEH TEC 32 COLD 60OUL 0.27 147 P2 TWD 22 VS3 -0.88 TEH TEC 32 COLD 60OUL 0.30 99 P2 TWD 24 VS4 -0.90 TEH TEC 32 COLD 60OUL 102 120 0.26 98 P2 IWD 22 VS3 -0.77 TEH TEC 32 COLD 60OUL 126 120 0.50 62 P2 TWD 26 08H -0.95 TEH TEC 31 COLD 60OUL 97 121 0.41 85 P2 TWD 28 08C +0.88 TEH TEC 32 COLD 600UL 125 121 0.39 40 P2 TWD 27 DCT +0.08 TEH TEC 32 COLD 60OUL 38 124 0.24 115 P2 TqD 23 VS3 +0.73 TEH TEC 37 COLD 60OUL 42 124 0.26 124 P2 TWD 24 VS3 -0.67 TEH TEC 37 COLD 60OUL 38 126 0.20 144 P2 TWD 21 VS3 +0.75 TEH TEC 37 COLD 60OUL 44 126 0.24 160 P2 TWD 21 VS3 -0.73 TEH TEC 38 COLD 60OUL 94 126 0.24 125 P2 TWD 20 VS2 -0.90 TEH TEC 32 COLD 60OUL 53 127 0.74 81 P2 TWD 30 VS3 -0.77 TEH TEC 47 COLD 60OUL 57 127 0.33 54 P2 TWD 20 VS3 -0.72 TEH TEC 47 COLD 60OUL 97 127 0.67 72 P2 TWD 30 VS3 +0.92 TEH TEC 31 COLD 60OUL 54 128 0.32 148 P2 TWD 20 VS3 -0.94 TEH TEC 47 COLD 60OUL 96 128 0.23 101 P2 TWD 20 VS2 -0.94 TEH TEC 32 COLD 600UL 53 129 0.20 150 P2 TWD 21 VS3 -0.77 TEH TEC 37 COLD 60OUL 91 131 0.20 164 P2 TWD 21 VS3 +1.26 TEH TEC 30 COLD 60OUL 93 131 0.20 86 P2 TWD 21 VS2 -0.80 TEH TEC 30 COLD 60OUL 0.72 48 P2 TWD 35 VS2 +0.72 TEH TEC 30 COLD 60OUL 92 132 0.26 49 P2 TWD 24 VS2 +0.70 TEH TEC 30 COLD 60OUL 57 133 0.56 139 P2 TWD 29 VS3 +0.78 TEC TEN 25 HOT 600UL 93 133 0.27 153 P2 TWD 25 VS2 +0.80 TEH TEC 30 COLD 60OUL 97 133 0.48 80 P2 TWD 31 VS2 -0.68 TEH TEC 30 COLD 60OUL 0.26 e8 P2 TWD 24 VS4 -0.60 TEH TEC 30 COLD 60OUL 96 134 0.24 142 P2 TWD 23 VS2 +0.92 TEH TEC 30 COLD 600UL 0.31 74 P2 TWD 26 VS3 -0.86 TEH TEC 30 COLD 600UL 96 138 0.49 110 P2 TWD 30 VS3 -0.60 TEH TEC 28 COLD 60OUL 97 139 0.50 51 P2 TWD 26 VS2 -0.92 TEH TEC 27 COLD 60OUL 85 141 0.33 106 P2 TWD 21 VS3 +0.64 TEH TEC 27 COLD 60OUL 87 143 0.40 32 P2 TWD 24 VS2 -0.98 TEH TEC 27 COLD 60OUL 0.63 52 P2 TWD 29 VS3 +0.38 TEH TEC 27 COLD 60OUL 56 152 0.75 127 P2 TWD 26 VS3 -0.65 TEC TEN 44 HOT 600UL 44 156 0.30 91 P2 TWD 20 VS3 -0.83 TEC TEH 48 HOT 60OUL 51 157 0.48 103 P2 TWD 26 VS3 +0.84 TEC TEH 48 HOT 60OUL 0.67 91 P2 TWD 30 VS3 -0.55 TEC TEH 48 HOT 60OUL 2 166 0.34 83 P2 TWD 23 01C -0.84 07C TEC 59 COLD 600UL 14 166 0.39 55 P2 TWD 24 01C -1.04 TEC TEH 47 HOT 60OUL Total Tubes : 233 Total Records: 317
Framatome ANP Inc. 1/22/2005 14:30 Attachment 3 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 1 of 8 Tubes with Bobbin 1-19% TWD Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 16 4 0.08 14 P 2 TWD 9 05H -1.02 TEC TEH 10 HOT 60OUL 27 5 0.11 148 P 2 TWD 12 01H +0.81 TEC TEH 9 HOT 60OUL 35 5 0.17 140 P 2 TWD 17 01H -1.00 TEC TEH 9 HOT 600UL 55 9 0.18 20 P 2 TWD 16 01H -0.83 TEC TEH 10 HOT 60OUL 41 15 0.10 125 P 2 TWD 10 VS3 +0.83 TEC TEH 10 HOT 60OUL 74 16 0.09 121 P 2 TWD 11 VS2 +0.27 TEC TEH 9 HOT 60OUL 86 20 0.18 123 P 2 TWD 16 VS2 -0.84 TEH TEC 63 COLD 60OUL 87 21 0.32 149 P 2 TWD 14 VS2 -0.92 TEH TEC 13 COLD 60OUL 86 22 0.43 100 P 2 TWD 18 VS3 +0.68 TEH TEC 13 COLD 60OUL 0.32 116 P 2 TWD 14 VS4 +0.86 TEH TEC 13 COLD 600UL 72 24 0.19 118 P 2 TWD 17 VS4 -0.52 TEC TEH 30 HOT 600UL 90 24 0.29 150 P 2 TWD 18 VS2 -0.92 TEH TEC 13 COLD 60OUL 92 26 0.32 114 P 2 TWD 14 VS3 -0.84 TEH TEC 13 COLD 600UL 0.27 92 P 2 TWD 17 VS2 +0.84 TEH TEC 13 COLD 60OUL 98 26 0.17 13 P 2 TWD 15 08H -0.94 TEH TEC 14 COLD 60OUL 37 27 0.17 141 P 2 TWD 16 VS3 -0.97 TEC TEH 30 HOT 600UL 91 27 0.16 151 P 2 TWD 14 VS2 -0.71 TEH TEC 14 COLD 60OUL 0.18 24 P 2 TWD 15 VS4 -0.91 TEH TEC 14 COLD 60OUL 99 27 0.28 149 P 2 TWD 18 VS1 -0.55 TEH TEC 13 COLD 60OUL 101 27 0.24 78 P 2 TWD 19 02H +0.00 TEH TEC 14 COLD 60OUL 88 28 0.31 101 P 2 TWD 19 VS3 -0.94 TEH TEC 13 COLD 60OUL 98 28 0.13 143 P 2 TWD 12 VS2 +0.83 TEH TEC 14 COLD 60OUL 81 29 0.08 143 P 2 TWD 6 VS4 +0.86 TEH TEC 13 COLD 60OUL 96 30 0.17 165 P 2 TWD 15 VS3 +0.79 TEH TEC 14 COLD 60OUL 98 30 0.29 44 P 2 TWD 18 VS2 +0.51 TEH TEC 13 COLD 60OUL 0.21 130 P 2 TWD 15 VS3 +0.94 TEH TEC 13 COLD 60OUL 47 31 0.08 22 P 2 TWD 10 DHT +0.00 TEC TEH 36 HOT 60OUL 95 31 0.08 22 P 2 TWD 9 VS2 +0.87 TEH TEC 14 COLD 60OUL 24 32 0.17 122 P 2 TWD 17 VS3 +0.65 TEC TEH 36 HOT 60OUL 92 32 0.24 162 P 2 TWD 19 VS2 -0.79 TEH TEC 14 COLD 600UL 108 32 0.09 148 P 2 TWD 9 VS2 +0.82 TEH TEC 14 COLD 600UL 91 33 0.12 168 P 2 TWD 12 VS4 +0.93 TEH TEC 14 COLD 60OUL 5 35 0.09 9 P 2 TWD 9 04H +0.90 TEH TEC 68 COLD 600UL 93 35 0.25 153 P 2 TWD 16 05H -1.02 TEH TEC 13 COLD 60OUL 111 35 0.19 40 P 2 TWD 16 07H -0.93 TEH TEC 14 COLD 600UL 88 36 0.17 143 P 2 TWD 15 VS4 +0.79 TEH TEC 14 COLD 600UL 103 37 0.23 97 P 2 TWD 18 DCB +0.00 TEH TEC 14 COLD 60OUL 85 39 0.25 126 P 2 TWD 16 VS2 -0.94 TEH TEC 13 COLD 60OUL 103 39 0.19 171 P 2 TWD 16 DCB +0.00 TEH TEC 14 COLD 60OUL 40 40 0.19 147 P 2 TWD 14 VS3 +0.69 TEH TEC 5 COLD 60OUL 9 41 0.12 169 P 2 TWD 11 04H +0.87 TEH TEC 68 COLD 600UL 63 41 0.26 97 P 2 TWD 17 VS2 +0.70 TEH TEC 5 COLD 60OUL 119 41 0.17 44 P 2 TWD 13 VS1 -0.63 TEH TEC 16 COLD 60OUL 44 42 0.18 29 P 2 TWD 13 VS3 +0.14 TEH TEC 5 COLD 600UL 0.17 46 P 2 TWD 13 VS3 +0.64 TEH TEC 5 COLD 60OUL 72 42 0.27 125 P 2 TWD 18 VS3 +0.73 TEH TEC 5 COLD 600UL 75 43 0.21 122 P 2 TWD 15 VS2 +0.82 TEH TEC 5 COLD 60OUL 0.23 87 P 2 TWD 16 VS4 -1.04 TEH TEC 5 COLD 60OUL 117 43 0.17 159 P 2 TWD 13 VS4 +0.92 TEH TEC 16 COLD 60OUL 64 44 0.13 117 P 2 TWD 11 VS3 +0.89 TEH TEC 5 COLD 60OUL 82 44 0.36 126 P 2 TWD 15 VS3 -0.88 TEH TEC 15 COLD 60OUL 94 44 0.26 140 P 2 TWD 18 VS2 -0.95 TEH TEC 16 COLD 60OUL 0.23 64 P 2 TWD 17 VS2 +0.54 TEH TEC 16 COLD 60OUL 102 44 0.20 69 P 2 TWD 15 DCB +0.00 TEH TEC 16 COLD 60OUL
Framatome ANP Inc. 1/22/2005 14:30 Attachment 3 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 2 of 8 Tubes with Bobbin 1-19% TWD Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 122 44 0.13 12 P 2 TWD 11 DCB +0.00 TEH TEC 16 COLD 60OUL 66 46 0.24 108 P 2 TWD 19 03H +0.97 TEH TEC 6 COLD 60OUL 124 46 0.21 160 P 2 TWD 9 DCT -0.04 TEH TEC 15 COLD 600UL 49 47 0.18 156 P 2 TWD 15 VS3 -0.63 TEH TEC 6 COLD 600UL 123 47 0.18 118 P 2 TWD 8 VS2 +0.56 TEH TEC 15 COLD 60OUL 125 47 0.30 80 P 2 TWD 13 DCT +0.00 TEH TEC 15 COLD 60OUL 41 49 0.23 125 P 2 TWD 18 VS3 -0.88 TEH TEC 10 COLD 60OUL 75 49 0.16 102 P 2 TWD 13 VS2 -0.72 TEH TEC 7 COLD 600UL 0.30 118 P 2 TWD 19 VS3 -0.16 TEH TEC 7 COLD 60OUL 121 49 0.25 170 P 2 TWD 18 DCT +0.00 TEH TEC 16 COLD 600UL 123 49 0.19 161 P 2 TWD 9 VS1 +0.74 TEH TEC 15 COLD 600UL 125 49 0.16 72 P 2 TWD 7 VS1 +0.85 TEH TEC 15 COLD 60OUL 48 50 0.23 28 P 2 TWD 16 VS3 -0.04 TEH TEC 9 COLD 60OUL 122 50 0.23 33 P 2 TWD 10 DHT -0.24 TEH TEC 15 COLD 60OUL 124 50 0.25 54 P 2 TWD 18 DHT +0.00 TEH TEC 16 COLD 60OUL 126 50 0.36 134 P 2 TWD 15 08H -0.14 TEH TEC 15 COLD 600UL 0.46 117 P 2 TWD 18 VS1 +0.85 TEN TEC 15 COLD 60OUL 39 51 0.24 149 P 2 TWD 16 VS3 +0.72 TEH TEC 9 COLD 60OUL 61 51 0.12 92 P 2 TWD 11 VS2 -0.28 TEH TEC 10 COLD 60OUL 77 51 0.15 152 P 2 TWD 13 VS4 +0.75 TEH TEC 10 COLD 600UL 127 51 0.15 36 P 2 TWD 7 09H +0.85 TEH TEC 15 COLD 60OUL 0.13 130 P 2 TWD 6 04H -0.92 TEN TEC 15 COLD 60OUL 46 52 0.16 152 P 2 TWD 14 VS3 -1.00 TEH TEC 10 COLD 600UL 78 52 0.14 159 P 2 TWD 12 VS4 -0.51 TEH TEC 10 COLD 600UL 84 52 0.20 154 P 2 TWD 9 VS2 -0.97 TEH TEC 15 COLD 60OUL 0.45 135 P 2 TWD 18 VS4 +0.49 TEH TEC 15 COLD 60OUL 128 52 0.43 22 P 2 TWD 17 DHT +0.14 TEH TEC 15 COLD 60OUL 126 54 0.20 99 P 2 TWD 18 VS1 +0.22 TEH TEC 20 COLD 600UL 0.20 142 P 2 TWD 18 VS1 +1.29 TEH TEC 20 COLD 60OUL 128 54 0.37 105 P 2 TWD 17 DHT +0.00 TEH TEC 19 COLD 600UL 51 55 0.06 120 P 2 TWD 6 07C -0.06 TEH TEC 10 COLD 600UL 117 55 0.14 28 P 2 TWD 14 VS1 +0.74 TEH TEC 20 COLD 600UL 123 55 0.27 134 P 2 TWD 14 VS1 -0.95 TEH TEC 19 COLD 60OUL 129 55 0.16 127 P 2 TWD 15 DCB +0.00 TEH TEC 20 COLD 600UL 78 56 0.20 99 P 2 TWD 15 VS3 +0.77 TEH TEC 11 COLD 60OUL 0.20 159 P 2 TWD 15 VS4 +0.97 TEH TEC 11 COLD 60OUL 83 57 0.16 143 P 2 TWD 14 VS2 +0.91 TEH TEC 17 COLD 60OUL 87 57 0.17 72 P 2 TWD 14 VS2 +0.85 TEH TEC 17 COLD 60OUL 89 57 0.20 18 P 2 TWD 11 VS2 +0.95 TEH TEC 19 COLD 60OUL 93 57 0.21 12 P 2 TWD 11 DHT +0.00 TEH TEC 19 COLD 60OUL 0.12 166 P 2 TWD 7 VS4 -0.83 TEH TEC 19 COLD 60OUL 95 57 0.22 95 P 2 TWD 19 DHT +0.00 TEH TEC 20 COLD 60OUL 123 57 0.22 151 P 2 TWD 12 VS1 +0.66 TEH TEC 19 COLD 600UL 127 57 0.22 49 P 2 TWD 11 VS1 +0.76 TEH TEC 19 COLD 60OUL 24 58 0.10 161 P 2 TWD 8 VS3 -0.70 TEH TEC 12 COLD 600UL 90 58 0.15 140 P 2 TWD 13 DHT +0.00 TEH TEC 17 COLD 600UL 96 58 0.20 64 P 2 TWD 16 VS3 -0.70 TEH TEC 18 COLD 600UL 0.12 101 P 2 TWD 6 VS3 +0.92 TEH TEC 18 COLD 600UL 0.18 97 P 2 TWD 13 VS4 -0.14 TEH TEC 18 COLD 60tUL 126 58 0.11 139 P 2 TWD 10 09H +0.97 TEH TEC 17 COLD 60OUL 95 59 0.08 149 P 2 TWD 7 VS3 -0.83 TEH TEC 17 COLD 60OUL 125 59 0.11 18 P 2 TWD 10 VS1 +0.88 TEH TEC 17 COLD 60OUL 0.17 13 P 2 TWD 14 DCT +0. 00 TEH TEC 17 COLD 60OUL 127 59 0.23 66 P 2 TWD 18 VS1 -0.27 TEH TEC 18 COLD 600UL
Framatome ANP Inc. 1/22/2005 14:30 Attacloint 3 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 3 of 8 Tubes with Bobbin 1-19% TWD Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 0.19 90 P 2 ==D 15 DCT +0.00 TEH TEC 18 COLD 60=OUL 24 60 0.17 30 P 2 TWD 13 VS3 -0.68 TEH TEC 11 COLD 600UL 96 60 0.16 9 P 2 TWD 14 DHB +3.36 TEH TEC 17 COLD 600UL 128 60 0.11 164 P 2 TWD 10 VS5 -0.90 TEH TEC 17 COLD 60OUL 41 61 0.17 130 P 2 TWD 13 VS3 -0.85 TEH TEC 11 COLD 60OUL 24 62 0.21 153 P 2 TWD 15 VS3 +0.98 TEH TEC 12 COLD 60OUL 36 62 0.17 136 P 2 TWD 13 VS3 -0.94 TEH TEC 12 COLD 600UL 44 62 0.11 164 P 2 TWD 9 VS3 +0.80 TEH TEC 12 COLD 60OUL 50 62 0.20 69 P 2 TWD 9 VS3 -0.51 TEH TEC 11 COLD 60OUL 78 62 0.17 339 P 2 TWD 13 VS3 -0.75 TEH TEC 11 COLD 60OUL 0.16 172 P 2 TWD 12 VS4 +0.73 TEH TEC 11 COLD 600UL 134 62 0.15 113 P 2 TWD 16 08H -0.99 TEH TEC 53 COLD 60OUL 0.16 33 P 2 TWD 17 DCT +0.00 TEH TEC 53 COLD 60OUL 0.17 157 P 2 TWD 18 07H +0.78 TEH TEC 53 COLD 600UL 21 63 0.30 87 P 2 TND 19 VS3 -0.87 TEH TEC 12 COLD 600UL 39 63 0.24 143 P 2 TWD 17 VS3 -0.93 TEH TEC 11 COLD 60OUL 79 63 0.15 114 P 2 TWD 12 VS2 +0.89 TEH TEC 11 COLD 600UL 0.18 26 P 2 TWD 14 VS3 -0.74 TEH TEC 11 COLD 600UL 0.15 42 P 2 TWD 12 VS4 +0.89 TEH TEC 11 COLD 60OUL 129 63 0.20 58 P 2 TWD 18 VS1 +0.65 TEH TEC 20 COLD 600UL 20 64 0.23 58 P 2 TWD 19 VS3 -0.81 TEH TEC 63 COLD 600UL 24 64 0.12 50 P 2 TWD 10 VS3 -0.62 TEH TEC 12 COLD 600UL 94 64 0.31 142 P 2 TWD 15 VS2 -0.89 TEH TEC 19 COLD 600UL 0.40 154 P 2 TWD 19 VS3 +0.82 TEH TEC 19 COLD 60OUL 0.36 92 P 2 TWD 17 VS4 -0.87 TEH TEC 19 COLD 60OUL 0.34 90 P 2 TWD 17 VS4 -0.36 TEH TEC 19 COLD 60OUL 130 64 0.18 99 P 2 TWD 16 VS1 +0.70 TEH TEC 20 COLD 60OUL 132 64 0.14 160 P 2 TWD 10 07H +0.57 TEH TEC 52 COLD 600UL 27 65 0.30 109 P 2 TWD 19 DHB +0.02 TEH TEC 11 COLD 60OUL 47 65 0.24 155 P 2 TWD 17 VS3 -0.70 TEH TEC 12 COLD 600UL 38 66 0.19 114 P 2 TWD 14 VS3 +0.74 TEH TEC 11 COLD 600UL 52 66 0.15 17 P 2 TWD 12 VS3 -0.90 TEH TEC 11 COLD 60OUL 124 66 0.17 165 P 2 TWD 9 VS1 +0.79 TEH TEC 19 COLD 600UL 33 67 0.23 98 P 2 TWD 16 DCB +0.00 TEH TEC 12 COLD 60OUL 37 67 0.10 121 P 2 TWD 8 VS3 +0.73 TEH TEC 12 COLD 600UL 0.17 152 P 2 TWD 13 DCB +0.00 TEH TEC 12 COLD 600UL 57 67 0.10 150 P 2 TWD 8 VS3 +0.82 TEH TEC 12 COLD 600UL 89 67 0.18 160 P 2 TWD 10 VS4 +0.99 TEH TEC 19 COLD 60OUL 91 67 0.18 64 P 2 TWD 17 VS2 +0.73 TEH TEC 20 COLD 60OUL 93 67 0.20 146 P 2 TWD 11 VS3 -0.89 TEH TEC 19 COLD 60OUL 64 68 0.11 156 P 2 TWD 9 VS3 +0.83 TEH TEC 11 COLD 60OUL 80 68 0.08 10 P 2 TWD 7 VS4 +0.89 TEH TEC 11 COLD 60OUL 88 68 0.19 35 P 2 TWD 17 VS2 -0.87 TEH TEC 20 COLD 600UL 132 68 0.17 135 P 2 TWD 13 VS2 -1.00 TEH TEC 52 COLD 60OUL 35 69 0.17 23 P 2 TWD 13 DHT -0.18 TEH TEC 64 COLD 60OUL 137 69 0.19 164 P 2 TWD 19 07H +0.65 TEH TEC 53 COLD 600UL 40 70 0.23 120 P 2 TWD 19 DCT -0.24 TEH TEC 64 COLD 60OUL 42 70 0.23 22 P 2 TWD 19 DCT -0.14 TEH TEC 64 COLD 60OUL 50 70 0.25 119 P 2 TWD 19 VS3 -0.71 TEC TEC 4 HOT 60OUL 136 70 0.21 139 P 2 TWD 15 VS2 +0.92 TEH TEC 52 COLD 60OUL 0.14 165 P 2 TWD 11 VS5 -0.90 TEH TEC 52 COLD 600UL 41 71 0.20 122 P 2 TWD 17 DCB +0.57 TEH TEC 64 COLD 60OUL 89 71 0.22 118 P 2 TWD 16 VS2 +0.98 TEH TEC 21 COLD 600UL 95 71 0.31 39 P 2 TWD 19 VS2 +0.79 TEH TEC 22 COLD 60OUL
Framatome ANP Inc. 1/22/2005 14:30 Attacbment 3 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 4 of 8 Tubes with Bobbin 1-19% TWD Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 135 71 0.27 47 P=2 TWD 18 VS1 -0.90 TEH TEC 52 COLD 60 OUL 42 72 0.20 115 P 2 TWD 16 VS3 +0.75 TEC TEH 4 HOT 60OUL 0.16 104 P 2 TWD 14 VS3 -0.83 TEC TEH 4 HOT 600UL 46 72 0.20 85 P 2 TWD 17 DCB +0.00 TEC TEH 4 HOT 60OUL 48 72 0.21 28 P 2 TWD 16 DCT +0.00 TEC TEH 3 HOT 60OUL 0.22 137 P 2 TWD 17 VS3 +0.66 TEC TEH 3 HOT 60OUL 52 72 0.15 147 P 2 TWD 7 DCT +0.00 TEC TEH 3 HOT 60OUL 54 72 0.19 160 P 2 TWD 16 VS3 +0.88 TEC TEH 4 HOT 60OUL 64 72 0.19 140 P 2 TWD 13 VS4 -0.82 TEC TEH 3 HOT 60OUL 82 72 0.23 161 P 2 TWD 17 VS3 -0.78 TEH TEC 21 COLD 600UL 94 72 0.11 171 P 2 TWD 8 VS2 +0.86 TEH TEC 22 COLD 600UL 0.12 168 P 2 TWD 9 VS4 +0.92 TEH TEC 22 COLD 60OUL 126 72 0.18 31 P 2 TWD 13 09H +0.10 TEH TEC 22 COLD 600UL 43 73 0.20 43 P 2 TWD 15 DHT +0.00 TEC TEH 3 HOT 600UL 0.31 93 P 2 TWD 19 DCB +0.26 TEC TEH 3 HOT 600UL 49 73 0.18 76 P 2 TWD 15 DCT +0.00 TEC TEH 4 HOT 60OUL 55 73 0.16 156 P 2 TWD 12 DCB +0.35 TEC TEH 3 HOT 600UL 0.20 109 P 2 TWD 14 VS3 -0.12 TEC TEH 3 HOT 60OUL 75 73 0.16 156 P 2 TWD 13 VS3 +0.83 TEC TEH 3 HOT 60OUL 83 73 0.18 163 P 2 TWD 15 05H +1.02 TEH TEC 21 COLD 60OUL 133 73 0.14 149 P 2 TWD 15 VS1 -0.56 TEH TEC 53 COLD 60OUL 135 73 0.15 19 P 2 TWD 12 VS5 +0.80 TEH TEC 52 COLD 60OUL 0.20 62 P 2 TWD 15 VS1 -0.76 TEH TEC 52 COLD 600UL 52 74 0.22 66 P 2 TWD 17 DCT +0.00 TEC TEH 3 HOT 600UL 54 74 0.20 118 P 2 TWD 17 VS3 -0.92 TEC TEH 4 HOT 600UL 56 74 0.19 163 P 2 TWD 15 VS3 +0.70 TEC TEH 3 HOT 60OUL 62 74 0.24 62 P 2 TWD 18 VS4 -0.71 TEC TEH 4 HOT 600UL 126 74 0.13 36 P 2 TWD 9 VS2 +0.89 TEN TEC 22 COLD 60OUL 45 75 0.18 137 P 2 TWD 14 DCB +0.00 TEC TEH 3 HOT 60OUL 0.24 104 P 2 TWD 17 DHB +0.00 TEC TEH 3 HOT 60OUL 49 75 0.16 162 P 2 TWD 13 DHB +0.00 TEC TEH 3 HOT 60OUL 54 76 0.19 135 P 2 TWD 16 DCB +0.00 TEC TEH 4 HOT 60OUL 94 76 0.23 25 P 2 TWD 18 VS3 -0.42 TEC TEC 21 COLD 60OUL 112 76 0.13 65 P 2 TWD 9 VS2 -0.67 TEH TEC 22 COLD 60OUL 134 76 0.11 56 P 2 TWD 9 VS5 -1.00 TEH TEC 52 COLD 600UL 73 77 0.25 150 P 2 TWD 19 VS2 +0.84 TEC TEH 4 HOT 600UL 79 77 0.12 156 P 2 TWD 10 VS2 -0.79 TEC TEH 3 HOT 600UL 48 78 0.15 120 P 2 TWD 12 DHT +0.00 TEC TEH 3 HOT 60OUL P 2 600UL 52 78 0.25 108 TWD 17 DHB +0.23 TEC TEH 3 HOT 56 78 0.15 147 P 2 TWD 14 VS3 +0.77 TEC TEH 4 HOT 60OUL 60 78 0.10 132 P 2 TWD 9 VS4 -0.66 TEC TEH 4 HOT 600UL 0.15 142 P 2 TWD 13 VS3 +0.78 TEC TEH 4 HOT 60OUL 116 78 0.17 157 P 2 TWD 12 VS1 -0.73 TEH TEC 23 COLD 600UL TWD 63 79 0.16 60 P 2 13 DCB +0.00 TEC TEH 5 HOT 600UL P 2 TWD 125 79 0.22 108 14 VS1 -0.85 TEH TEC 23 COLD 600UL TWD 131 79 0.15 159 P 2 9 VS4 -0.90 TEH TEC 54 COLD 600UL P 2 TWD 61 81 0.19 139 15 DCB +0.00 TEC TEH 6 HOT 60OUL P 2 TWD 95 81 0.13 78 11 VS2 +0.77 TEH TEC 26 COLD 60OUL TWD 50 82 0.16 97 P 2 13 DCT +0.00 TEC TEH 5 HOT 60OUL TWD 0.21 20 P 2 16 DHT +0.00 TEC TEH 5 HOT 60OUL P 2 TWD 0.21 101 16 DHB +0.00 TEC TEH 5 HOT 60OUL TWD 60 82 0.16 71 P 2 13 DCB +0.00 TEC TEH 6 HOT 60OUL 51 83 0.19 151 P 2 TWD 15 DCT +0.00 TEC TEH 5 HOT 60OUL 61 83 0.12 14 P 2 TWD 10 DCB +0.00 TEC TEH 6 HOT 60OUL
Framatome ANP Inc. 1/22/2005 14:30 Attachment 3 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 5 of 8 Tubes with Bobbin 1-19% TWD Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 79 83 0.16 128 P2 TWD 13 VS2 -0.77 TEC TEH 5 HOT 60=OUL 85 83 0.21 137 P2 TWD 16 VS3 +0.63 TEH TEC 25 COLD 60OUL 76 84 0.28 142 P2 TWD 19 VS3 +0.81 TEC TEH 5 HOT 60OUL 82 84 0.20 122 P2 TWD 16 VS4 -0.67 TEH TEC 25 COLD 600UL 75 85 0.29 128 P2 TWD 19 VS3 +0.75 TEC TEH 5 HOT 60OUL 54 86 0.24 159 P2 TWD 18 VS3 +1.04 TEC TEH 6 HOT 60OUL 62 86 0.24 98 P2 TWD 18 VS3 -0.80 TEC TEH 6 HOT 60OUL 92 86 0.24 51 P2 TWD 18 VS4 +0.82 TEH TEC 25 COLD 60OUL 126 86 0.12 152 P2 TWD 10 09H -0.84 TEH TEC 26 COLD 60OUL 51 87 0.17 150 P2 TWD 13 DCB +0.00 TEC TEH 5 HOT 60OUL 55 87 0.26 157 P2 TWD 18 DCB +0.00 TEC TEH 5 HOT 60OUL 93 87 0.24 170 P2 TWD 18 VS2 +0.58 TEH TEC 25 COLD 60OUL 111 87 0.11 55 P2 TWD 10 VS2 -0.93 TEH TEC 25 COLD 60OUL 50 88 0.14 109 P2 TWD 12 DCT +0.00 TEC TEH 6 HOT 600UL 54 88 0.22 51 P2 TWD 17 DCB +0.00 TEC TEH 6 HOT 60OUL TWD 94 88 0.12 139 P2 10 VS3 -0.96 TEH TEC 26 COLD 60OUL TWD 49 89 0.27 114 P2 19 DCB +0.00 TEC TEH 5 HOT 60OUL TWD 51 89 0.21 45 P2 17 DCB +0.00 TEC TEH 6 HOT 600UL TWD 53 89 0.24 102 P2 17 DCT +0.00 TEC TEH 5 HOT 600UL TWD 57 89 0.14 122 P2 11 04H +0.93 TEC TEH 5 HOT 60OUL TWD 73 89 0.18 88 P2 14 VS3 +0.65 TEC TEH 5 HOT 60OUL TWD 83 89 0.22 86 P2 17 VS2 +0.74 TEH TEC 25 COLD 600UL TWD 0.17 83 P2 14 VS3 -0.90 TEH TEC 25 COLD 60OUL TWD 0.23 115 P2 17 VS4 -0.68 TEH TEC 25 COLD 600UL TWD 0.24 130 P2 18 VS3 +0.92 TEH TEC 25 COLD 60OUL TWD 95 89 0.21 93 P2 16 VS2 -0.94 TEH TEC 25 COLD 60OUL TWD 0.26 22 P2 19 VS2 +0.50 TEH TEC 25 COLD 60OUL TWD 50 90 0.13 90 P2 11 05H +0.96 TEC TEH 6 HOT 60OUL TWD 54 90 0.24 130 P2 18 DCB +0.00 TEC TEH 6 HOT 600UL TWD 0.23 76 P2 18 VS3 -0.62 TEC TEH 6 HOT 60OUL TWD 92 90 0.22 144 P2 17 VS2 +0.80 TEH TEC 25 COLD 600UL TWD 114 90 0.16 54 P2 13 VS1 +0.59 TEH TEC 26 COLD 60OUL TWD 57 91 0.29 107 P2 19 DHB +0.00 TEC TEH 5 HOT 60OUL TWD 43 93 0.19 63 P2 14 VS3 +1.00 TEC TEH 5 HOT 60OUL TWD 49 93 0.18 145 P2 15 VS3 -0.85 TEC TEH 6 HOT 60OUL TWD 55 93 0.23 132 P2 16 DCB +0.06 TEC TEH 5 HOT 600UL TWD 97 93 0.21 157 P2 18 VS2 -0.81 TEH TEC 28 COLD 600UL TWD 0.19 62 P2 17 VS4 +0.63 TEH TEC 28 COLD 60OUL TWD 0.12 91 P2 12 VS2 +0.22 TEH TEC 28 COLD 60OUL TWD 44 94 0.10 141 P2 TWD~ 9 DCB +0.00 TEC TEH 6 HOT 60OUL TWD 48 94 0.15 125 P2 13 VS3 -0.87 TEC TEH 6 HOT 60OUL TWD 52 94 0.17 104 P2 14 VS3 +0.00 TEC TEH 6 HOT 60OUL TWD 82 94 0.15 154 P2 12 VS2 +0.97 TEH TEC 55 COLD 60OUL TWD 0.16 140 P2 13 VS4 +0.93 TEH TEC 55 COLD 60OUL TWD 86 94 0.13 35 P2 11 VS4 +0.84 TEH TEC 27 COLD 60OUL TWD 49 95 0.27 137 P2 18 VS3 +1.09 TEC TEH 5 HOT 600UL TWD 51 95 0.16 154 P2 13 DCB +0.00 TEC TEH 6 HOT 60OUL TWD 53 95 0.14 123 P2 11 DCB -0.19 TEC TEH 5 HOT 60OUL TWD 135 95 0.26 140 P2 17 VS1 -0.94 TEH TEC 55 COLD 60OUL TWD 38 96 0.17 90 P2 14 DHB +0.00 TEC TEH 6 HOT 60OUL TWD 42 96 0.19 155 P2 15 VS3 -0.87 TEC TEH 6 HOT 60OUL TWD 44 96 0.22 80 P2 17 DCT +0.00 TEC TEH 5 HOT 60OUL TWD 94 96 0.26 113 P2 18 VS3 -0.54 TEH TEC 27 COLD 60OUL TWD 41 97 0.26 108 P2 19 DCB +0.00 TEC TEH 6 HOT 60OUL
Framatome ANP Inc. 1/22/2005 14:30 Attac1nent 3 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 6 of 8 Tubes with Bobbin 1-19% TWD Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 43 97 0.20 108 P 2 TWD 15 DCT +0.00 TEC TEH 5 HOT 600UL 45 97 0.15 121 P 2 TWD 13 DCB +0.00 TEC TEH 6 HOT 60OUL 0.25 125 P 2 TWD 19 VS3 +0.85 TEC TEH 6 HOT 600UL 57 97 0.12 146 P 2 TWD 10 VS3 +0.68 TEC TEH 6 HOT 60OUL 87 97 0.13 15 P 2 TWD 13 VS4 -0.56 TEH TEC 28 COLD 60OUL 137 97 0.06 142 P 2 TWD 9 DCB +0.40 TEH TEC 56 COLD 600UL 48 98 0.09 42 P 2 TWD 8 DHB +0.10 TEC TEH 6 HOT 60OUL 64 98 0.19 62 P 2 TWD 15 VS4 -0.90 TEC TEH 6 HOT 60OUL 106 98 0.23 142 P 2 TWD 17 VS4 -0.85 TEH TEC 27 COLD 60OUL 136 98 0.13 160 P 2 TWD 10 VS1 -0.84 TEH TEC 55 COLD 600UL 43 99 0.22 45 P 2 TWD 17 DHB +0.00 TEH TEC 62 COLD 60OUL 57 99 0.23 84 P 2 TWD 18 VS3 +0.56 TEC TEH 6 HOT 60OUL 0.11 154 P 2 TWD 10 VS3 -0.75 TEC TEH 6 HOT 60OUL 125 99 0.17 170 P 2 TWD 18 09C -0.88 TEH TEC 56 COLD 60OUL 133 99 0.06 74 P 2 TWD 9 TSC +2.15 TEH TEC 56 COLD 60OUL 135 99 0.17 165 P 2 TWD 13 VS5 -0.82 TEH TEC 55 COLD 60OUL 0.11 121 P 2 TWD 9 DCB +0.30 TEH TEC 55 COLD 60OUL 38 100 0.18 79 P 2 TWD 13 VS3 +0.87 TEH TEC 43 COLD 60OUL 46 100 0.20 118 P 2 TWD 14 VS3 -0.83 TEH TEC 43 COLD 60OUL 48 100 0.35 51 P 2 TWD 19 DCB +0.02 TEH TEC 44 COLD 60OUL 50 100 0.24 63 P 2 TWD 16 VS3 -0.81 TEH TEC 43 COLD 60OUL 54 100 0.27 49 P 2 TWD 18 DHT +0.00 TEH TEC 43 COLD 600UL 78 100 0.15 29 P 2 TWD 18 VS2 -0.06 TEH TEC 44 COLD 60OUL 134 100 0.17 154 P 2 TWD 19 VS4 -0.76 TEH TEC 56 COLD 60OUL 41 101 0.20 119 P 2 TWD 14 DCT +0.00 TEH TEC 43 COLD 600UL 51 101 0.23 121 P 2 TWD 14 VS3 +0.85 TEH TEC 44 COLD 60OUL 87 101 0.17 141 P 2 TWD 19 VS4 -0.58 TEH TEC 37 COLD 60OUL 91 101 0.15 129 P 2 TWD 17 08C +0.90 TEH TEC 37 COLD 60OUL 115 101 0.06 18 P 2 TWD 8 05H +0.86 TEH TEC 37 COLD 60OUL 92 102 0.24 138 P 2 TWD 19 VS2 +0.91 TEH TEC 36 COLD 60OUL 132 102 0.15 120 P 2 TWD 12 DCT +0.00 TEH TEC 55 COLD 60OUL 136 102 0.17 156 P 2 TWD 18 VS1 -0.78 TEH TEC 56 COLD 60OUL 91 103 0.13 124 P 2 TWD 12 VS2 -0.95 TEH TEC 35 COLD 60OUL 24 104 0.26 126 P 2 TWD 15 VS3 +0.89 TEH TEC 44 COLD 60OUL 126 104 0.20 147 P 2 TWD 16 VS2 +0.90 TEH TEC 36 COLD 600UL 134 104 0.19 36 P 2 TWD 14 05H +0.86 TEH TEC 55 COLD 60OUL 47 105 0.15 161 P 2 TWD 19 VS3 -0.81 TEH TEC 44 COLD 60OUL 0.13 12 P 2 TWD 18 VS3 +0.26 TEH TEC 44 COLD 60OUL 119 105 0.22 93 P 2 TWD 13 03H +0.92 TEH TEC 36 COLD 600UL 125 105 0.10 70 P 2 TWD 10 08C +0.70 TEH TEC 35 COLD 60OUL 32 106 0.09 168 P 2 TWD 14 VS3 +0.56 TEH TEC 44 COLD 60OUL 82 106 0.15 161 P 2 TWD 13 VS3 +0.76 TEH TEC 36 COLD 60OUL 94 106 0.11 146 P 2 TWD 10 VS2 +0.95 TEH TEC 36 COLD 60OUL 53 107 0.26 110 P 2 TWD 15 VS3 +0.79 TEH TEC 44 COLD 60OUL 125 107 0.20 82 P 2 TWD 16 VS1 +0.94 TEH TEC 35 COLD 60OUL 127 107 0.20 17 P 2 TWD 17 DCT -0.02 TEH TEC 36 COLD 60OUL 42 108 0.13 157 P 2 TWD 14 VS3 +0.10 TEH TEC 41 COLD 60OUL 48 108 0.13 164 P 2 TWD 14 VS3 -0.83 TEH TEC 42 COLD 60OUL 84 108 0.14 150 P 2 TWD 12 VS3 +0.99 TEH TEC 36 COLD 60OUL 96 108 0.22 157 P 2 TWD 18 VS2 +0.81 TEH TEC 36 COLD 60OUL 100 108 0.13 144 P 2 TWD 12 DCT +0.00 TEH TEC 36 COLD 60OUL 39 109 0.09 111 P 2 TWD 11 VS3 +0.93 TEH TEC 41 COLD 60OUL 101 109 0.24 33 P 2 TWD 17 VS3 +0.87 TEH TEC 33 COLD 60OUL 129 109 0.23 153 P 2 TWD 17 VS1 -0.88 TEH TEC 33 COLD 60OUL
Framatome ANP Inc. 1/22/2005 14:30 Attacbment 3 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 7 of 8 Tubes with Bobbin 1-19% TWD Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 133 109 0.13 166 P 2 TWD 15 07C -0.94 TEN TEC 56 COLD 60=OUL 8 110 0.16 41 P 2 TWD 13 06H +0.69 TEH TEC 50 COLD 600UL 78 110 0.10 11 P 2 TWD 10 06H +0.96 TEH TEC 46 COLD 60OUL 132 110 0.15 161 P 2 TWD 17 VS5 -0.87 TEH TEC 56 COLD 600UL 33 111 0.20 77 P 2 TWD 18 VS3 +0.85 TEH TEC 42 COLD 600UL 45 111 0.13 20 P 2 TWD 13 VS3 +0.89 TEH TEC 42 COLD 600UL 87 111 0.27 156 P 2 TWD 18 VS3 -0.86 TEH TEC 33 COLD 600UL 40 112 0.10 167 P 2 TWD 11 VS3 +0.91 TEH TEC 41 COLD 60OUL 82 112 0.15 100 P 2 TWD 17 VS2 -0.02 TEH TEC 34 COLD 60OUL 0.15 161 P 2 TWD 16 VS2 +0.76 TEH TEC 34 COLD 60OUL 88 112 0.16 28 P 2 TWD 13 VS4 -0.93 TEH TEC 55 COLD 60OUL 0.26 155 P 2 TWD 18 VS3 -0.95 TEH TEC 55 COLD 600UL 0.18 160 P 2 TWD 14 VS2 +0.87 TEH TEC 55 COLD 60OUL 92 112 0.12 116 P 2 TWD 10 VS3 -1.00 TEH TEC 33 COLD 600UL 31 113 0.13 18 P 2 TWD 14 VS3 -0.34 TEH TEC 42 COLD 600UL 123 113 0.09 28 P 2 TWD 12 VS5 +1.00 TEH TEC 34 COLD 60OUL 41 115 0.10 167 P 2 TWD 11 VS3 +0.99 TEH TEC 41 COLD 600UL 125 115 0.12 166 P 2 TWD 14 VS1 +0.98 TEH TEC 34 COLD 60OUL 54 116 0.08 194 P 2 TWD 9 VS3 -0.73 TEH TEC 40 COLD 60OUL 76 116 0.07 155 P 2 TWD 9 VS3 +0.63 TEH TEC 45 COLD 60OUL 0.10 168 P 2 TWD 12 08C +0.88 TEH TEC 45 COLD 60OUL 92 116 0.09 156 P 2 TWD 12 08C +1.15 TEH TEC 34 COLD 60OUL 128 116 0.11 145 P 2 TWD 14 VS2 +1.04 TEH TEC 34 COLD 60OUL 41 117 0.10 168 P 2 TWD 12 VS3 +0.81 TEH TEC 40 COLD 60OUL 53 117 0.11 17 P 2 TWD 12 VS3 +0.95 TEH TEC 40 COLD 600UL 77 117 0.15 159 P 2 1WD 14 VS3 +0.98 TEH TEC 46 COLD 600UL 93 117 0.13 46 P 2 TWD 13 VS3 +0.62 TEH TEC 32 COLD 600UL 40 118 0.13 119 P 2 TWD 11 VS3 +0.87 TEH TEC 39 COLD 600UL 88 118 0.29 134 P 2 TWD 19 08H +0.89 TEH TEC 31 COLD 60OUL 53 119 0.14 25 P 2 TWD 12 VS3 +0.83 TEH TEC 39 COLD 60OUL 123 119 0.10 161 P 2 TWD 11 VS4 -0.96 TEH TEC 32 COLD 60OUL 84 120 0.27 132 P 2 TWD 19 VS2 -0.74 TEH TEC 31 COLD 60OUL 37 121 0.12 156 P 2 TWD 10 VS3 +0.81 TEH TEC 39 COLD 600UL 53 121 0.14 44 P 2 TWD 12 VS3 -0.85 TEH TEC 39 COLD 600UL 125 121 0.14 37 P 2 TWD 14 07H +0.77 TEH TEC 32 COLD 600UL 37 123 0.17 171 P 2 TWD 19 VS3 -0.52 TEH TEC 37 COLD 600UL 39 123 0.12 60 P 2 TWD 13 VS3 +0.91 TEH TEC 38 COLD 60OUL 41 123 0.12 140 P 2 TWD 14 VS3 +1.00 TEH TEC 37 COLD 60OUL 53 123 0.21 44 P 2 TWD 15 VS3 +0.92 TEH TEC 48 COLD 60OUL 37 125 0.12 59 P 2 TWD 15 VS3 -0.70 TEH TEC 37 COLD 60OUL 41 125 0.17 24 P 2 TWD 19 VS3 -0.62 TEH TEC 37 COLD 60OUL 54 126 0.13 96 P 2 TWD 10 VS3 -0.86 TEH TEC 47 COLD 60OUL 21 127 0.15 92 P 2 TWD 17 VS3 +0.89 TEH TEC 37 COLD 60OUL 41 127 0.16 73 P 2 TWD 18 VS3 -0.73 TEH TEC 37 COLD 600UL 79 127 0.14 123 P 2 TWD 13 VS2 -0.77 TEH TEC 47 COLD 60OUL 87 127 0.17 147 P 2 TWD 16 VS2 +0.52 TEH TEC 32 COLD 60OUL 91 127 0.18 153 P 2 TD 17 VS2 -0.84 TEH TEC 32 COLD 60OUL 95 127 0.16 155 P 2 TD 16 VS2 -0.88 TEH TEC 32 COLD 60OUL 97 127 0.17 29 P 2 TWD 13 VS4 +0.90 TEH TEC 31 COLD 60OUL 0.24 130 P 2 TWD 17 VS2 -0.64 TEH TEC 31 COLD 600UL 80 128 0.20 32 P 2 TWD 15 VS4 -0.95 TEH TEC 47 COLD 600UL 96 128 0.19 154 P 2 TWD 18 VS4 -0.82 TEH TEC 32 COLD 600UL 41 129 0.16 32 P 2 TWD 18 VS3 -0.69 TEH TEC 37 COLD 60OUL 45 129 0.14 40 P 2 TWD 16 VS3 -0.61 TEH TEC 37 COLD 60OUL
Framatome ANP Inc. 1/22/2005 14:30 Attacbment 3 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 8 of 8 Tubes with Bobbin 1-19% TWD Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 89 129 0.23 69 P 2 TWD VS2 +0.91 TEH TEC 31 COLD 60=OUL 91 129 0.27 131 P 2 TWD 18 VS2 -0.78 TEH TEC 31 COLD 60OUL 45 133 0.28 139 P 2 TWD 19 VS3 +0.78 TEC TEH 27 HOT 600UL 91 133 0.31 146 P 2 TWD 15 08C +1.34 TEH TEC 29 COLD 60OUL 42 134 0.16 47 P 2 TWD 13 VS3 -0.92 TEC TEH 27 HOT 600UL 50 134 0.14 23 P 2 TWD 12 DCT +0.00 TEC TEH 27 HOT 60OUL 6 138 0.14 38 P 2 TWD 9 07C -0.57 TEH TEC 50 COLD 60OUL 42 138 0.28 107 P 2 TWD 16 05H +0.92 TEC TEH 37 HOT 60OUL 46 138 0.14 157 P 2 TWD 9 VS3 -0.63 TEC TEH 37 HOT 60OUL 96 138 0.19 151 P 2 TWD 17 VS2 +0.84 TEH TEC 28 COLD 600UL 102 138 0.22 153 P 2 TWD 16 VS2 -0.96 TEH TEC 27 COLD 60OUL 104 138 0.15 13 P 2 TWD 14 08H +0.79 TEH TEC 28 COLD 60OUL 53 139 0.22 106 P 2 TWD 15 VS3 -0.55 TEC TEH 37 HOT 60OUL 81 139 0.21 158 P 2 TWD 16 06C +0.83 TEH TEC 27 COLD 60OUL 95 139 0.15 131 P 2 'ND 15 VS2 -0.90 TEH TEC 28 COLD 60OUL 101 139 0.10 133 P 2 'WD 9 VS2 -0.95 TEH TEC 27 COLD 60OUL 48 140 0.27 135 P 2 'ND 18 VS3 +0.80 TEC TEH 37 HOT 600UL 102 140 0.18 20 P 2 TWD 17 09H -0.95 TEH TEC 28 COLD 600UL 97 141 0.22 71 P 2 TWD 16 07C -0.26 TEH TEC 27 COLD 600UL 66 142 0.06 170 P 2 TWD 5 VS2 +1.12 TEC TEH 41 HOT 600UL 86 142 0.17 169 P 2 TWD 14 VS4 -0.88 TEH TEC 27 COLD 60OUL 0.14 150 P 2 TWD 12 VS3 +1.06 TEH TEC 27 COLD 60OUL 96 142 0.09 166 P 2 TWD 10 VS4 -0.88 TEH TEC 28 COLD 60OUL 81 143 0.19 103 P 2 TWD 14 08C +0.86 TEH TEC 27 COLD 60OUL 87 143 0.15 38 P 2 TWD 12 VS4 +0.66 TEH TEC 27 COLD 60OUL 95 143 0.23 78 P 2 TWD 17 VS2 -0.92 TEH TEC 27 COLD 60OUL 94 144 0.12 163 P 2 TWD 10 01C +0.95 TEH TEC 27 COLD 60OUL 46 146 0.12 65 P 2 TWD 11 VS3 +0.61 TEH TEC 62 COLD 60OUL 85 147 0.18 120 P 2 TWD 17 VS2 +0.92 TEH TEC 28 COLD 60OUL 53 151 0.22 141 P 2 TWD 10 VS3 -0.85 TEC TEH 44 HOT 60OUL 47 155 0.26 129 P 2 TWD 19 VS3 -0.73 TEC TEH 47 HOT 60OUL 57 155 0.23 143 P 2 T'D 17 VS3 +0.80 TEC TEH 48 HOT 60OUL 49 161 0.24 102 P 2 TWD 18 VS3 -0.79 TEC TEH 48 HOT 60OUL 38 162 0.12 139 P 2 TWD 11 01H +1.07 TEC TEH 47 HOT 600UL 29 163 0.06 156 P 2 TWD 7 01C -1.00 TEC TEH 48 HOT 600UL 30 164 0.16 32 P 2 TWD 13 01H -0.92 TEC TEH 47 HOT 600UL 32 164 0.20 158 P 2 TWD 16 01C +0.92 TEC TEH 48 HOT 60OUL 36 164 0.11 7 P 2 TWD 10 01H +0.94 TEC TEH 47 HOT 60OUL 15 165 0.21 32 P 2 TWD 17 01H -0.78 TEC TEH 48 HOT 60OUL 27 165 0.22 133 P 2 TWD 17 01C -0.93 TEC TEH 48 HOT 60OUL 29 165 0.12 149 P 2 TWD 11 01C -0.99 TEC TEH 47 HOT 60OUL 0.18 154 P 2 TWD 15 01H -1.03 TEC TEH 47 HOT 60OUL 20 166 0.13 142 P 2 TWD 12 01H +0.93 TEC TEH 47 HOT 600UL Total Tubes : 364 Total Records: 421
Framatome ANP Inc. 1/22/2005 14:30 Attachment 4 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G B Page 1 of 24 Tubes with Bobbin 40-100% TWD and +Point Vol, Circ and Axial Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 4 2 0.22 84 P 6 MAI 01H +0.86 01H 01H 161 HOT 5803P 0.21 100 P 6 SAI 03H +0.79 03H 03H 161 HOT 5803P 12 2 0.15 100 P 6 SAI 01H +0.83 01H 01H 118 HOT 5803P 15 3 0.15 96 P 6 SAI 01H +0.78 01H 01H 118 HOT 5803P 12 4 0.16 125 P 6 SAI 01H +0.84 01H 01H 118 HOT 5803P 7 5 0.30 97 P 6 SAI 03H +0.69 03H 03H 161 HOT 5803P 9 5 0.19 128 P 6 SAI 03H -0.11 03H 03H 161 HOT 5803P 4 8 0.17 143 P 6 SAI 03H -0.14 03H 03H 161 HOT 5803P 0.31 106 P 6 SAI 04H +0.81 04H 04H 161 HOT 5803P 7 9 0.35 105 P 6 SAI 01H -0.57 01H 01H 160 HOT 5803P 9 9 0.19 90 P 6 SAI 01H +0.35 01H 01H 173 HOT 5803P 0.14 47 P 6 SAI 05H -0.17 05H 05H 160 HOT 5803P 0.32 82 P 6 SAI 07H +0.56 07H DHT 160 HOT 5803P 12 10 0.32 114 P 6 SAI 03H +0.64 03H 03H 118 HOT 5803P 1 11 0.38 103 P 6 MAI 03H +0.81 03H 03H 160 HOT 5803P 15 11 0.29 93 P 6 SAI 03H +0.73 03H 03H 118 HOT 5803P 43 11 0.10 77 P 6 SAI 01H +0.47 01H 01H 118 HOT 5803P 4 12 0.14 99 P 6 SAI 03H +0.67 03H 03H 173 HOT 5803P 6 12 0.27 106 P 6 MAI 03H +0.39 03H 03H 157 HOT 5803P 12 12 0.28 115 P 6 SAI 02H -0.77 02H 02H 118 HOT 5803P 3 13 0.58 101 P 6 MAI 03H +0.84 03H 03H 157 HOT 5803P 5 13 0.28 58 P 6 SAI 02H -0.29 02H 02H 157 HOT 5803P 0.50 45 P 6 SAI 05H +1.33 05H 05H 157 HOT 5803P 7 13 0.17 91 P 6 MAI 05H +0.92 05H 05H 157 HOT 5803P 0.24 54 P 6 SAI 06H -0.90 06H 06H 157 HOT 5803P 0.45 110 P 6 SAI 03H +0.72 03H 03H 173 HOT 5803P 0.24 88 P 6 SAI 01H +0.22 01H 01H 157 HOT 5803P 4 14 0.17 91 P 6 SAI 01H +0.78 01H 01H 157 HOT 5803P 0.15 89 P 6 SAI 03H +0.81 03H 03H 157 HOT 5803P 0.13 135 P 6 SAI 03H +0.50 03H 03H 157 HOT 5803P 0.33 103 P 6 SAI 05H +1.08 05H 05H 157 HOT 5803P 6 14 0.30 87 P 6 SAI 01H -0.13 01H 01H 157 HOT 5803P 16 14 0.28 102 P 6 SAI 03H +0.70 03H 03H 118 HOT 5803P 5 15 0.28 104 P 6 MAI 03H +0.81 03H 03H 157 HOT 5803P 0.25 108 P 6 SAI 03H -0.34 03H 03H 157 HOT 5803P 9 15 0.42 101 P 6 SAI 01H +0.38 01H 01H 157 HOT 5803P 0.16 67 P 6 SAI 02H -0.60 02H 02H 157 HOT 5803P 0.19 73 P 6 MAI 05H +0.91 05H 05H 157 HOT 5803P 21 15 0.20 107 P 6 SAI 05H +0.56 05H 05H 118 HOT 5803P 6 16 0.20 113 P 6 SAI 03H +0.46 03H 03H 173 HOT 5803P 5 17 0.15 96 P 6 SAI 01H +0.27 01H 01H 157 HOT 5803P 0.39 91 P 6 MAI 05H +0.20 05H 05H 157 HOT 5803P 15 17 0.69 106 P 6 SAI 03H -0.10 03H 03H 118 HOT 5803P 29 17 0.27 96 P 6 SAI 05H -0.12 05H 05H 118 HOT 5803P 7 19 0.26 105 P 6 SAI 01H +0.37 01H 01H 157 HOT 5803P 0.24 104 P 6 SAI 05H +0.84 05H 05H 157 HOT 5803P 0.16 73 P 6 SAI 05H -0.23 05H 05H 157 HOT 5803P 0.30 94 P 6 SAI DCB +0.20 07C DCT 73 COLD 5803P 9 19 0.57 96 P 6 SAI 01H +0.57 01H 01H 157 HOT 5803P 0.16 82 P 6 SAI 03H +0.70 03H 03H 157 HOT 5803P 0.23 91 P 6 SAI 05H +0.29 05H 05H 157 HOT 5803P 0.22 99 P 6 SAI 05H +0.76 05H 05H 157 HOT 5803P 13 19 0.29 100 P 6 SAI 01H +0.17 01H 01H 118 HOT 5803P 71 19 0.24 108 P 6 SAI 02H +0.87 02H 02H 118 HOT 5803P
Framatome ANP Inc. 1/22/2005 14:30 Attacbment 4 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G B Page 2 of 24 Tubes with Bobbin 40-100% TWD and +Point Vol, Circ and Axial Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 75 19 0.35 102 P 6 SAI 02H -0.77 02H 02H 118 HOT 5803P 10 20 0.26 92 P 6 MAI 03H +0.66 03H 03H 157 HOT 5803P 0.32 100 P 6 SAI 07H +0.72 07H 07H 157 HOT 5803P 22 20 0.32 62 P 6 SAI 02H -0.47 02H 02H 118 HOT 5803P 26 20 0.37 92 P 6 SAI 03H +0.72 03H 03H 118 HOT 5803P 28 20 0.35 80 P 6 SAI 01H -0.75 01H 01H 178 HOT 5803P 0.28 89 P 6 SAI 03H +0.76 03H 03H 118 HOT 5803P 30 20 0.31 105 P 6 SAI 01H +0.42 01H 01H 118 HOT 5803P 0.20 63 P 6 MAI 03H +0.87 03H 03H 118 HOT 5803P 34 20 0.41 94 P 6 SAI 02H -0.29 02H 02H 118 HOT 5803P 48 20 0.26 91 P 6 SAI 01H -0.70 01H 01H 118 HOT 5803P 60 20 0.36 92 P 6 SAI 06H +0.74 06H 06H 118 HOT 5803P 12 22 0.38 107 P 6 SAI 01H +0.28 01H 01H 118 HOT 5803P 28 22 0.36 65 P 6 SAI 03H +0.66 03H 03H 118 HOT 5803P 68 22 0.20 86 P 6 SAI 04H +0.69 04H 04H 47 HOT 5803P 5 23 0.21 90 P 6 SAI 01H -0.62 01H 01H 173 HOT 5803P 7 23 0.17 85 P 6 SAI 03H +0.82 03H 03H 181 HOT 5803P 0.12 47 P 6 SAI 03H -0.39 03H 03H 181 HOT 5803P 0.34 94 P 6 SAI 05H +0.77 05H 05H 161 HOT 5803P 9 23 0.31 108 P 6 SAI 03H +0.67 03H 03H 157 HOT 5803P 15 23 0.37 99 P 6 SAI 03H +0.86 03H 03H 118 HOT 5803P 45 23 0.25 79 P 6 MAI 02H +0.70 02H 02H 47 HOT 5803P 4 24 0.34 104 P 6 SAI 05H +0.80 05H 05H 161 HOT 5803P 68 24 0.22 102 P 6 SAI 04H +0.74 04H 04H 47 HOT 5803P 0.15 118 P 6 SAI 01H -0.78 01H 01H 77 HOT 5803P 0.20 90 P 6 SAI 01H +0.73 01H 01H 77 HOT 5803P 3 25 0.38 80 P 6 SAI 01H +0.45 01H 01H 161 HOT 5803P 9 25 0.22 93 P 6 SAI 05H +0.73 05H 05H 161 HOT 5803P 49 25 0.18 99 P 6 SAI 01H +0.32 01H 01H 47 HOT 5803P 4 26 0.30 91 P 6 SAI 02H +0.49 02H 02H 161 HOT 5803P 0.27 94 P 6 SAI 03H +0.77 03H 03H 161 HOT 5803P 10 26 0.21 75 P 6 SAI 05H +0.45 05H 05H 157 HOT 5803P 26 26 0.20 89 P 6 SAI 05H -0.51 05H 05H 118 HOT 5803P 0.48 105 P 6 SAI 05H +0.90 05H 05H 118 HOT 5803P 52 26 0.43 99 P 6 SAI 01H -0.33 01H 01H 47 HOT 5803P 7 27 0.18 101 P 6 SAI 01H +0.30 01H 01H 161 HOT 5803P 37 27 0.30 97 P 6 SAI 01H -0.68 01H 01H 47 HOT 5803P 75 27 0.26 106 P 6 SAI 02H -0.76 02H 02H 50 HOT 5803P 0.23 68 P 6 SAI 02H +0.25 02H 02H 50 HOT 5803P 0.28 100 P 6 SAI 03H +0.17 03H 03H 50 HOT 5803P 4 28 0.24 80 P 6 SAI 06H +0.83 06H 06H 161 HOT 5803P 10 28 0.18 89 P 6 SAI 05H +0.81 05H 05H 161 HOT 5803P 0.26 99 P 6 SAI 07H +0.85 07H 07H 161 HOT 5803P 7 29 0.24 91 P 6 SAI 05H +0.82 05H 05H 161 HOT 5803P 61 29 0.29 97 P 6 MAI 01H +0.47 01H 01H 47 HOT 5803P 6 30 0.24 109 P 6 SAI 05C +0.72 05C 05C 73 COLD 5803P 10 30 0.41 100 P 6 SAI 01H -0.25 01H 01H 161 HOT 5803P 0.45 113 P 6 SAI 04H +0.51 04H 04H 161 HOT 5803P 30 30 0.17 94 P 6 SAI 03H +0.76 03H 03H 47 HOT 5803P 38 30 0.29 106 P 6 MAI 01H +0.19 01H 01H 47 HOT 5803P 17 31 0.28 101 P 6 SAI 05H +0.67 05H 05H 47 HOT 5803P 41 31 0.32 119 P 6 SAI 01H -0.77 01H 01H 47 HOT 5803P 67 31 0.20 99 P 6 SAI 04H +0.63 04H 04H 47 HOT 5803P 8 32 0.29 53 P 6 SAI 01H -0.48 01H 01H 161 HOT 5803P
Framatome ANP Inc. 1/22/2005 14:30 Attacbment 4 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G B Page 3 of 24 Tubes with Bobbin 40-100% TWD and +Point Vol, Circ and Axial Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 10 32 0.26 120 P 6=SA 01H +0.52 01H 01H 161 HOT 5803P 22 32 0.26 77 P 6 SAI 05H +0.14 05H 05H 118 HOT 5803P 0.21 110 P 6 SAI 05H +0.79 05H 05H 118 HOT 5803P 34 32 0.46 101 P 6 MAI 05H +0.54 05H 05H 47 HOT 5803P 0.22 85 P 6 SAI 07H +0.55 07H 07H 47 HOT 5803P 0.17 80 P 6 SAI 01H -0.62 01H 01H 77 HOT 5803P 0.18 91 P 6 SAI 01H +0.39 01H 01H 77 HOT 5803P 0.17 75 P 6 SAI 02H +0.73 02H 02H 77 HOT 5803P 0.45 102 P 6 SAI 03H +0.37 03H 03H 77 HOT 5803P 0.47 40 P 6 SAI 04H +0.62 04H 04H 77 HOT 5803P 62 32 0.18 132 P 6 SAI 03H -0.60 03H 03H 47 HOT 5803P 0.11 67 P 6 SAI 03H +0.18 03H 03H 47 HOT 5803P 0.24 99 P 6 SAI 03H +0.46 03H 03H 47 HOT 5803P 0.32 93 P 6 SAI 04H +0.69 04H 04H 47 HOT 5803P 64 32 0.23 77 P 6 SAI 02H +0.78 02H 02H 47 HOT 5803P 88 32 0.43 91 P 6 SAI 02H +0.78 02H 02H 122 HOT 5803P 7 33 0.44 106 P 6 MAI 01H -0.23 01H 01H 161 HOT 5803P 21 33 0.15 77 P 6 SAI 01H -0.86 01H 01H 118 HOT 5803P 27 33 0.20 74 P 6 SAI 03H +0.69 03H 03H 118 HOT 5803P 41 33 0.26 104 P 6 SAI 01H +0.08 01H 01H 47 HOT 5803P 0.13 76 P 6 SAI 01H -0.38 01H 01H 47 HOT 5803P 45 33 0.21 77 P 6 SAI 02H +0.64 02H 02H 77 HOT 5803P 59 33 0.85 100 P 6 SAI 02H +0.45 02H 02H 47 HOT 5803P 61 33 0.26 76 P 6 SAI 03H +0.11 03H 03H 47 HOT 5803P 75 33 0.20 73 P 6 SAI 04H +0.91 04H 04H 50 HOT 5803P 0.10 60 P 6 SAI 04H -0.66 04H 04H 50 HOT 5803P 87 33 0.19 92 P 6 SAI 02H +0.89 02H 02H 122 HOT 5803P 26 34 0.30 80 P 6 SAI 01H -0.61 01H 01H 47 HOT 5803P 0.32 106 P 6 SAI 01H +0.06 01H 01H 47 HOT 5803P 0.51 105 P 6 MAI 04H +0.64 04H 04H 47 HOT 5803P 0.14 88 P 6 MAI 02H -0.73 02H 02H 77 HOT 5803P 0.21 88 P 6 SAI 02H +0.45 02H 02H 77 HOT 5803P 0.30 91 P 6 SAI 03H +0.97 03H 03H 77 HOT 5803P 30 34 0.38 122 P 6 SAI 05H +0.53 05H 05H 47 HOT 5803P 0.16 83 P 6 SAI 05H -0.25 05H 05H 47 HOT 5803P 0.20 76 P 6 SAI 01H +0.66 01H 01H 77 HOT 5803P 0.43 93 P 6 MAI 04H +0.78 04H 04H 100 HOT 5803P 68 34 0.21 88 P 6 SAI 05H +0.66 05H 05H 47 HOT 5803P 39 35 0.18 98 P 6 SAI 01H -0.69 01H 01H 47 HOT 5803P 0.25 100 P 6 SAI 01H +0.34 01H 01H 47 HOT 5803P 87 35 0.16 93 P 6 SAI 02H -0.23 02H 02H 124 HOT 5803P 4 36 0.21 104 P 6 SAI 07H -0.22 07H DHT 161 HOT 5803P 0.25 89 P 6 SAI 07H +0.82 07H DHT 161 HOT 5803P 30 36 0.53 104 P 6 SAI 06H -0.50 06H 06H 47 HOT 5803P 0.19 56 P 6 SAI 01H -0.82 01H 01H 77 HOT 5803P 0.18 95 P 6 SAI 01H +0.78 01H 01H 77 HOT 5803P 0.13 31 P 6 SAI 02H -0.70 02H 02H 77 HOT 5803P 0.21 82 P 6 SAI 02H +0.88 02H 02H 77 HOT 5803P 0.24 76 P 6 SAI 03H +0.92 03H 03H 77 HOT 5803P 0.35 102 P 6 MAI 04H -0.10 04H 04H 77 HOT 5803P 56 36 0.46 92 P 6 SAI 01H -0.21 01H 01H 47 HOT 5803P 0.29 87 P 6 SAI 02H +0.60 02H 02H 47 HOT 5803P 60 36 0.31 98 P 6 SAI 01H -0.65 01H 01H 47 HOT 5803P 0.14 74 P 6 SAI 02H -0.52 02H 02H 47 HOT 5803P
Framatome ANP Inc. 1/22/2005 14:30 Attacbment 4 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G B Page 4 of 24 Tubes with Bobbin 40-100% TWD and +Point Vol. Circ and Axial Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 0.48 99 P 6 SAI 02H +0.14 02H 02H 47 HOT 5803P 62 36 0.24 86 P 6 SAI 04H +0.63 04H 04H 47 HOT 5803P 0.18 79 P 6 SAI 05H +0.74 05H 05H 47 HOT 5803P 7 37 0.25 88 P6 SAI 01H +0.78 01H 01H 161 HOT 5803P 0.41 105 P 6 SAI 03H +0.86 03H 03H 161 HOT 5803P 0.31 89 P 6 MAI 06H +0.11 06H 06H 161 HOT 5803P 0.29 76 P 6 SAI 07H -0.78 07H DHT 161 HOT 5803P 0.58 110 P 6 SAI 07H +0.88 07H DHT 161 HOT 5803P 0.33 111 P 6 SAI 07C -0.36 07C DCT 73 COLD 5803P 23 37 0.19 73 P 6 SAI 05H +0.34 05H 05H 47 HOT 5803P 0.24 107 P 6 SAI 05H +0.70 05H 05H 47 HOT 5803P 0.19 43 P 6 SAI 03H -0.73 03H 03H 77 HOT 5803P 0.13 75 P 6 SAI 03H +0.71 03H 03H 77 HOT 5803P 27 37 0.37 78 P 6 SAI 03H +0.65 03H 03H 47 HOT 5803P 53 37 0.14 98 P 6 SAI 01H +0.30 01H 01H 47 HOT 5803P 0.13 75 P 6 SAI 01H -0.15 01H 01H 47 HOT 5803P 61 37 0.13 102 P 6 SAI 01H -0.68 01H 01H 47 HOT 5803P 71 37 0.19 73 P 6 SAI 02H +0.85 02H 02H 47 HOT 5803P 75 37 0.22 86 P 6 SAI 02H +0.87 02H 02H 47 HOT 5803P 83 37 0.13 91 P 6 SAI 05H +0.81 05H 05H 124 HOT 5803P 4 38 0.30 97 P 6 SAI 05H +0.87 05H 05H 161 HOT 5803P 56 38 0.25 73 P 6 SAI 02H +0.72 02H 02H 47 HOT 5803P 0.20 56 P 6 SAI 02H -0.67 02H 02H 47 HOT 5803P 60 38 0.24 110 P 6 SAI 01H -0.37 01H 01H 47 HOT 5803P 0.40 85 P 6 SAI 01H +0.40 01H 01H 47 HOT 5803P 68 38 0.26 111 P6 SAI 01H -0.67 01H 01H 47 HOT 5803P 0.52 97 P 6 SAI 01H +0.44 01H 01H 47 HOT 5803P 7 39 0.41 111 P 6 SAI 01H +0.56 01H 01H 161 HOT 5803P 0.26 71 P 6 SAI 04H +0.56 04H 04H 161 HOT 5803P 0.37 117 P 6 SAI 06H +0.87 06H 06H 161 HOT 5803P 9 39 0.30 78 P 6MAI 06H -0.17 06H 06H 161 HOT 5803P 17 39 0.20 67 P6 SAI 03H +0.72 03H 03H 47 HOT 5803P 87 39 0.22 114 P 6 SAI 01H -0.83 01H 01H 161 HOT 5803P 2 40 0.29 88 P6 SAI 06H -0.46 06H 06H 161 HOT 5803P 20 40 0.14 74 P6 SAI 01H +0.80 01H 01H 47 HOT 5803P 56 40 0.83 90 P 6 MAI 01H -0.73 01H 01H 47 HOT 5803P 62 40 0.42 103 P 6 SAI 01H -0.16 01H 01H 47 HOT 5803P 0.35 117 P 6 SAI 01H +0.33 O1H 01H 47 HOT 5803P 9 41 0.17 91 P 6 SAI 06H +0.87 06H 06H 161 HOT 5803P 11 41 0.21 103 P 6 SAI 02H +0.78 02H 02H 47 HOT 5803P 0.21 79 P 6 SAI 05H -0.23 05H 05H 47 HOT 5803P 0.10 73 P 6 SAI 05H +0.66 05H 05H 47 HOT 5803P 33 41 0.33 84 P6 SAI 06H +0.68 06H 06H 47 HOT 5803P 0.15 59 P 6 SAI 01H -0.31 01H 01H 77 HOT 5803P 0.09 47 P 6 SAI 01H +0.65 01H 01H 77 HOT 5803P 81 41 0.23 101 P 6 SAI 01H +0.44 01H 01H 124 HOT 5803P 14 42 0.24 82 P 6 SAI 02H +0.33 02H 02H 47 HOT 5803P 0.25 69 P 6 SAI 01H -0.37 01H 01H 77 HOT 5803P 0.22 63 P 6 SAI 01H +0.53 01H 01H 77 HOT 5803P 20 42 0.16 162 P 6 SAI 01H -0.26 01H 01H 47 HOT 5803P 56 42 0.30 103 P 6 SAI 01H +0.27 01H 01H 50 HOT 5803P 58 42 0.27 66 P 6 SAI 01H +0.20 01H 01H 50 HOT 5803P 0.19 68 P 6 SAI 01H -0.92 01H 01H 50 HOT 5803P 66 42 0.34 100 P 6 SAI 01H -0.30 01H 01H 50 HOT 5803P
Framatome ANP Inc. 1/22/2005 14:30 Attachment 4 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G B Page 5 of 24 Tubes with Bobbin 40-100% TWD and +Point Vol. Circ and Axial Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 10 44 0.22 81 P 6 SAX 03H +0.93 03H 03H 157 HOT 5803P 0.23 97 P 6 MAI 05H +0.63 05H 05H 157 HOT 5803P 28 44 0.29 85 P 6 SAX 01H +0.65 01H 01H 47 HOT 5803P 48 44 0.29 254 P 6 SAX 02H +0.79 02H 02H 50 HOT 5803P 56 44 0.34 90 P 6 SAX 01H -0.27 01H 01H 50 HOT 5803P 0.37 86 P 6 SAX 02H +0.90 02H 02H 50 HOT 5803P 90 44 0.17 79 P 6 SAX 05H +0.85 05H 05H 125 HOT 5803P 7 45 0.19 99 P 6 SAX 04H +0.39 04H 04H 157 HOT 5803P 0.22 109 P 6 SAX 06H +0.68 06H 06H 157 HOT 5803P 0.58 89 P 6 SAI 06H -0.72 06H 06H 157 HOT 5803P 61 45 0.11 138 P 6 SAX 08C -1.02 08C 08C 73 COLD 5803P 69 45 0.41 100 P 6 MAI 01H +0.41 01H 01H 50 HOT 5803P 0.28 50 P 6 SAl 08C -0.55 08C 08C 73 COLD 5803P 10 46 0.31 96 P 6 MAI 05H +0.43 05H 05H 161 HOT 5803P 54 46 0.64 106 P 6 SAX 01H +0.85 01H 01H 50 HOT 5803P 96 46 0.10 65 P 6 SAI 03H -0.71 03H 03H 125 HOT 5803P 102 46 0.20 81 P 6 SAX 04H +0.88 04H 04H 125 HOT 5803P 7 47 0.28 92 P 6 MAI 06H +0.77 06H 06H 161 HOT 5803P 0.17 80 P 6 SAX 06H -0.30 06H 06H 161 HOT 5803P 0.38 116 P 6 MAI 05H -0.30 05H 05H 161 HOT 5803P 9 47 0.34 84 P 6 SAl 05H +0.56 05H 05H 161 HOT 5803P 11 47 0.32 101 P 6 SAl 01H +0.43 01H 01H 47 HOT 5803P 13 47 0.20 65 P 6 SAI DHB +0.52 07C 07H 149 HOT 5602P 0.14 75 P 6 SAl 07H +0.23 07C 07H 149 HOT 5602P 0.10 48 P 6 SAl 03H -0.59 03H 03H 47 HOT 5803P 17 47 0.23 127 P 6 SAl 03H -0.64 03H 03H 47 HOT 5803P 0.26 106 P 6 SAl 03H -0.42 03H 03H 47 HOT 5803P 0.22 113 P 6 SAl 03H +0.50 03H 03H 47 HOT 5803P 0.26 83 P 6 SAl 06H -0.33 06H 06H 47 HOT 5803P 0.23 110 P 6 SAl 06H +0.56 06H 06H 47 HOT 5803P 69 47 0.34 95 P 6 MAI 01H +0.52 01H 01H 50 HOT 5803P 79 47 0.62 102 P 6 SAl 01H -0.09 01H 01H 50 HOT 5803P 20 48 0.08 110 P 6 SAX 07H +0.09 07H 07H 47 HOT 5803P 0.31 98 P 6 SAl 07H +0.42 07H 07H 47 HOT 5803P 0.19 64 P 6 MAI 01H -0.01 01H 01H 77 HOT 5803P 0.18 105 P 6 SAl 06H +0.48 06H 06H 77 HOT 5803P 28 48 0.33 96 P 6 SAl 02H +0.50 02H 02H 161 HOT 5803P 42 48 0.31 119 P 6 SAX 01H -0.43 01H 01H 161 HOT 5803P 56 48 0.22 101 P 6 MAI 01H +0.88 01H 01H 161 HOT 5803P 120 48 0.12 86 P 6 SAl 01H +0.21 01H 01H 125 HOT 5803P 9 49 0.35 83 P 6 SAl 06H +0.78 06H 06H 161 HOT 5803P 63 49 0.38 90 P 6 SAl 05H +0.78 05H 05H 160 HOT 5803P 4 50 0.33 95 P 6 SAI 05H +0.75 05H 05H 161 HOT 5803P 0.39 91 P 6 SAI 06H -0.84 06H 06H 161 HOT 5803P 10 50 0.19 66 P 6 SAl 01H +0.19 01H 01H 161 HOT 5803P 0.32 99 P 6 SAl 06H +0.86 06H 06H 161 HOT 5803P 16 50 0.15 57 P 6 SAl 01H -0.25 01H 01H 47 HOT 5803P 46 50 0.62 93 P 6 SAl 02H +0.52 02H 02H 161 HOT 5803P 86 50 0.20 117 P 6 SAl 01H -0.83 01H 01H 125 HOT 5803P 126 50 0.37 85 P 6 SAX 02H -0.85 02H 02H 125 HOT 5803P 7 51 0.30 86 P 6 SAl 05H -0.24 05H 05H 161 HOT 5803P 9 51 0.15 87 P 6 SAl 07H -0.23 07C 07H 149 HOT 5602P 17 51 0.30 101 P 6 SAX 06H +0.64 DHT 06H 149 HOT 5602P 0.20 66 P 6 SAl 06H -0.52 DHT 06H 149 HOT 5602P
Framatome ANP Inc. 1/22/2005 14:30 Attachment 4 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G B Page 6 of 24 Tubes with Bobbin 40-100% TWD and +Point Vol. Circ and Axial Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 53 51 0.24 94 P 6 SAI 01H +0.59 01H 01H 161 HOT 5803P 0.18 53 P 6 SAI 01H -0.38 01H 01H 161 HOT 5803P 99 51 0.16 81 P 6 SAI 01H -0.48 O1H 01H 125 HOT 5803P 101 51 0.22 91 P 6 SAI 01H -0.77 01H 01H 125 HOT 5803P 10 52 0.23 103 P 6 SAI 05H +0.78 05H 05H 161 HOT 5803P 28 52 0.28 79 P 6 SAI 01H +0.77 01H 01H 161 HOT 5803P 54 52 0.10 71 P 6 SAI 01H -0.40 01H 01H 161 HOT 5803P 60 52 0.48 86 P 6 SAI 07H +0.75 07H 07H 161 HOT 5803P 88 52 0.16 99 P 6 SAI 01H +0.77 01H 01H 127 HOT 5803P 23 53 0.53 104 P 6 SAI 05H +0.85 HOT 05H 05H 161 5803P 49 53 0.23 89 P 6 SAI 02H +0.09 02H 02H 161 HOT 5803P 59 53 0.22 59 P 6 SAI 02H +0.83 02H 02H 161 HOT 5803P 0.19 58 P 6 SAI 05H +0.82 05H 05H 161 HOT 5803P 73 53 0.28 SAI 01H -0.04 50 HOT 80 P 6 01H 01H 5803P 87 53 0.32 93 P 6 SAI 01H -0.74 01H 01H 127 HOT 5803P 0.19 94 P 6 SAI 06H +0.88 06H 06H 127 HOT 5803P 0.27 60 P 6 SAI 07H +0.63 07H 07H 127 HOT 5803P 101 53 0.18 80 P 6 MAI 02H -0.34 02H 02H 127 HOT 5803P 117 53 0.23 93 P 6 SAI 01H -0.59 01H 01H 127 HOT 5803P 4 54 0.59 108 P 6 MAI 03H -0.25 03H 03H 161 HOT 5803P 0.54 102 P 6 MAI 05H +0.41 05H 05H 161 HOT 5803P 58 54 0.33 98 P 6 SAI 02H +0.84 02H 02H 161 HOT 5803P 94 54 0.24 79 P 6 MAI 01H +0.43 01H 01H 127 HOT 5803P 98 54 0.14 69 P 6 SAI 01H -0.64 01H 01H 127 HOT 5803P 118 54 0.24 80 P 6 SAI 02H +0.84 02H 02H 127 HOT 5803P 122 54 0.38 81 P 6 SAI 02H +0.69 02H 02H 127 HOT 5803P 7 55 0.30 115 P 6 SAI 04H -0.33 04H 04H 161 HOT 5803P 0.41 114 P 6 SAI 06H +0.15 06H 06H 161 HOT 5803P 9 55 0.23 87 P 6 SAI 05H +0.76 05H 05H 161 HOT 5803P 17 55 0.32 97 P 6 MAI 05H +0.73 05H 05H 50 HOT 5803P 47 55 0.18 71 P 1 SCI TSH -0.06 TSH TSH 102 HOT 5803P 53 55 0.23 123 P 6 SAI 01H -0.41 01H 01H 161 HOT 5803P 0.39 88 P 6 SAI 04H +0.61 04H 04H 161 HOT 5803P 55 55 0.22 65 P 6 SAI 06H +0.80 06H 06H 161 HOT 5803P 59 55 0.27 111 P 6 SAI 02H +0.79 02H 02H 161 HOT 5803P 61 55 0.31 105 P 6 SAI DHB +2.26 DHT 08H 151 HOT 5602P 0.23 77 P 6 SAI 01H -0.30 01H 01H 50 HOT 5803P 0.43 69 P 6 SAI 05H -0.36 05H 05H 50 HOT 5803P 0.20 93 P 6 MAI 05H +0.79 05H 05H 50 HOT 5803P 65 55 0.48 92 P 6 SAI 01H -0.25 01H 01H 50 HOT 5803P 69 55 0.30 92 P 6 SAI 01H -0.48 01H 01H 50 HOT 5803P 85 55 0.26 93 P 6 SAI 01H -0.55 01H 01H 127 HOT 5803P 97 55 0.35 106 P 6 SAI 01H -0.79 01H 01H 127 HOT 5803P 101 55 0.19 104 P 6 SAI 01H +0.39 01H 01H 178 HOT 5803P 0.13 99 P 6 SAI 01H -0.35 01H 01H 178 HOT 5803P 107 55 0.38 114 P 6 SAI 01H +0.87 01H 01H 127 HOT 5803P 14 56 0.29 83 P 6 SAI 05H -0.48 05H 05H 50 HOT 5803P 0.20 75 P 6 SAI 05H +0.54 05H 05H 50 HOT 5803P 16 56 0.24 85 P 6 SAI 02H +0.85 02H 02H 50 HOT 5803P 0.33 97 P 6 MAI 07H +0.68 07H 07H 50 HOT 5803P 0.26 89 P 6 SAI 07H -0.31 07H 07H 50 HOT 5803P 18 56 0.29 96 P 6 SAI 07H +0.63 07H 07H 50 HOT 5803P 0.15 60 P 6 MAI 07H -0.49 07H 07H 50 HOT 5803P 20 56 0.48 111 P 6 SAI 07H +0.22 07H 07H 50 HOT 5803P
Framatome ANP Inc. 1/22/2005 14:30 Attacbment 4 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G B Page 7 of 24 Tubes with Bobbin 40-100% TWD and +Point Vol. Circ and Axial Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL LEG PROBE 98 56 0.20 88 P 6 SAI 01H +0.50 01H 01H 127 HOT 5803 P 100 56 0.51 101 P 6 SAI 01H +0.92 01H 01H 127 HOT 5803P 0.18 81 P 6 SAI 01H -0.74 01H 01H 127 HOT 5803P 0.17 74 P 6 MAI 03H +0.28 03H 03H 127 HOT 5803P 0.23 78 P 6 SAI 08H +0.77 08H 08H 127 HOT 5803P 120 56 0.23 89 P 6 SAI 02H +0.66 02H 02H 127 HOT 5803P 0.18 68 P 6 SAI 02H -0.55 02H 02H 127 HOT 5803P 9 57 0.27 91 P 6 MAI 07H +0.43 07H DHT 173 HOT 5803P 17 57 0.57 99 P 6 SAI 07H 07 07H 07H 50 HOT 5803P 53 57 0.54 105 P 6 SAI 02H +0.03 02H 02H 161 HOT 5803P 87 57 0.14 127 P 6 SAI 01H -0.68 01H 01H 128 HOT 5803P 97 57 0.82 103 P 6 SAI 01H -0.04 01H 01H 128 HOT 5803P 101 57 0.16 98 P 6 MAI 01H -0.29 01H 01H 128 HOT 5803P 0.43 112 P 6 SAI 04H +0.85 04H 04H 128 HOT 5803P 105 57 0.30 64 P 6 SAI 01H -0.46 01H 01H 128 HOT 5803P 10 58 0.20 79 P 6 MAI 01H +0.79 01H 01H 161 HOT 5803P 20 58 0.43 103 P 6 SAI 03H -0.20 03H 03H 161 HOT 5803P 0.22 87 P 6 SAI 04H +0.71 04H 04H 161 HOT 5803P 22 58 0.21 59 P 6 SAI 02H +0.91 02H 02H 161 HOT 5803P 54 58 0.46 101 P 6 SAI 02H +0.38 02H 02H 161 HOT 5803P 60 58 0.17 57 P 6 SAI 02H +0.91 02H 02H 50 HOT 5803P 62 58 0.30 96 P 6 SAI 01H -0.23 01H 01H 50 HOT 5803P 0.27 44 P 6 SAI 01H +0.83 01H 01H 50 HOT 5803P 0.27 77 P 6 SAI 02H +0.80 02H 02H 50 HOT 5803P 66 58 0.51 99 P 6 SAI 01H +0.70 01H 01H 50 HOT 5803P 0.33 106 P 6 SAI 01H -0.42 01H 01H 50 HOT 5803P 68 58 0.55 104 P 6 SAI 01H -0.46 01H 01H 50 HOT 5803P 94 58 0.22 78 P 6 SAI 02H +0.79 02H 02H 128 HOT 5803P 124 58 0.21 51 P 6 SAI 01H +0.43 01H 01H 128 HOT 5803P 7 59 0.22 93 P 6 SAI 03H +0.87 03H 03H 161 HOT 5803P 0.23 81 P 6 SAI 05H 93 05H 05H 161 HOT 5803P 0.22 101 P 6 SAI 05H +0.31 05H 05H 161 HOT 5803P 0.58 102 P 6 MAI 07H +0.53 07H 07H 161 HOT 5803P 9 59 0.27 79 P 6 SAI 06H +0.10 06H 06H 161 HOT 5803P 29 59 0.28 70 P 6 SAI 01H +0.84 01H 01H 161 HOT 5803P 0.23 65 P 6 MAI 02H +0.83 02H 02H 161 HOT 5803P 31 59 0.15 103 P 6 MAI 01H +0.69 01H 01H 161 HOT 5803P 0.39 104 P 6 SAI 02H +0.83 02H 02H 161 HOT 5803P 59 59 0.55 104 P 6 SAI 01H +0.79 01H 01H 161 HOT 5803P 69 59 0.19 91 P 6 SAI 05H +0.76 05H 05H 50 HOT 5803P 83 59 0.29 98 P 6 SAI 01H -0.48 01H 01H 128 HOT 5803P 0.16 98 P 6 SAI 01H +0.30 01H 01H 128 HOT 5803P 101 59 0.27 124 P 6 SAI 01H -0.45 01H 01H 128 HOT 5803P 103 59 0.34 81 P 6 SAI 01H +0.09 01H 01H 128 HOT 5803P 0.17 84 P 6 SAI 01H +0.89 01H 01H 128 HOT 5803P 105 59 0.47 101 P 6 SAI 01H +0.47 01H 01H 128 HOT 5803P 0.16 96 P 6 SAI 01H -0.24 01H 01H 128 HOT 5803P 111 59 0.23 54 P 6 SAI 02H +0.64 02H 02H 128 HOT 5803P 6 60 0.24 96 P 6 SAI 03H +0.84 03H 03H 161 HOT 5803P 26 60 0.19 109 P 6 SAI 02H +0.79 02H 02H 161 HOT 5803P 28 60 0.33 86 P 6 SAI 03H +0.88 03H 03H 161 HOT 5803P 40 60 0.17 65 P 6 SAI 02H +0.70 02H 02H 161 HOT 5803P 60 60 0.32 98 P 6 SAI 02H +0.85 02H 02H 161 HOT 5803P 84 60 0.19 88 P 6 SAI 01H -0.40 01H 01H 128 HOT 5803P
Framatome ANP Inc. 1/22/2005 14:30 Attachment 4 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G B Page 8 of 24 Tubes with Bobbin 40-100% TWD and +Point Vol, Circ and Axial Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 106 60 0.18 86 P 6 SAI 01H -0.43 01H 01H 128 HOT 5803P 0.36 89 P 6 SAI 02H +0.43 02H 02H 128 HOT 5803P 0.19 79 P 6 SAI 02H -0.32 02H 02H 128 HOT 5803P 17 61 0.29 105 P 6 SAI 07H +0.69 07H 07H 161 HOT 5803P 83 61 0.22 85 P 6 SAI O1H -0.89 01H 01H 128 HOT 5803P 95 61 0.71 103 P 6 SAI O1H -0.53 01H 01H 128 HOT 5803P 22 62 0.29 105 P 6 SAI 02H +0.79 02H 02H 161 HOT 5803P 104 62 0.26 115 P 6 SAI 01H +0.33 01H 01H 128 HOT 5803P 29 63 0.20 51 P 6 SAI 01H +0.74 01H 01H 161 HOT 5803P 49 63 0.30 51 P 6 SAI 01H +0.63 01H 01H 161 HOT 5803P 59 63 0.55 100 P 6 MAI 07H +0.16 07H 07H 50 HOT 5803P 61 63 0.52 101 P 6 SAI 01H -0.53 01H 01H 50 HOT 5803P 0.23 113 P 6 SAI 03H +0.38 03H 03H 50 HOT 5803P 0.18 75 P 6 SAI 03H +0.81 03H 03H 50 HOT 5803P 69 63 0.32 56 P 6 SAI 01H -0.29 01H 01H 50 HOT 5803P 101 63 0.26 93 P 6 SAI 01H -0.47 01H 01H 128 HOT 5803P 129 63 0.17 65 P 6 SAI 02H -0.65 02H 02H 128 HOT 5803P 40 64 0.40 102 P 6 MAI 01H -0.46 01H 01H 161 HOT 5803P 0.39 112 P 6 SAI 02H +0.64 02H 02H 161 HOT 5803P 124 64 0.17 77 P 6 SAI 02H +0.72 02H 02H 130 HOT 5803P 35 65 0.31 91 P 6 SAI 02H +0.73 02H 02H 161 HOT 5803P 83 65 0.23 76 P 6 SAI 01H -0.69 01H 01H 130 HOT 5803P 0.18 87 P 6 SAI 01H +0.33 01H 01H 130 HOT 5803P 95 65 0.30 105 P 6 SAI 01H -0.36 01H 01H 130 HOT 5803P 82 66 0.21 91 P 6 SAI 01H -0.23 01H 01H 130 HOT 5803P 106 66 0.33 90 P 6 SAI 01H +0.39 01H 01H 130 HOT 5803P 0.22 69 P 6 SAI 02H +0.88 02H 02H 130 HOT 5803P 118 66 0.19 103 P 6 MAI O1H -0.32 01H 01H 130 HOT 5803P 49 67 1.49 22 P 1 SCI TEH +0.32 TEH TSH 173 HOT 5803P 0.51 96 P 6 MAI 01H -0.15 01H 01H 161 HOT 5803P 65 67 0.25 97 P 6 MAI 05H +0.72 05H 05H 50 HOT 5803P 101 67 0.38 106 P 6 SAI 01H -0.31 01H 01H 130 HOT 5803P 111 67 0.22 86 P 6 SAI 02H +0.81 02H 02H 130 HOT 5803P 137 67 0.68 41 P 6 SAI TSH +0.89 TSH TSH 117 HOT 5803P 66 68 0.28 274 P 6 MAI 05H +0.19 05H 05H 50 HOT 5803P 74 68 0.19 73 P 6 SAI 08H +0.32 08H 08H 161 HOT 5803P 98 68 0.16 68 P 6 SAI 01H -0.88 01H 01H 130 HOT 5803P 104 68 0.25 94 P 6 SAI 01H -0.27 01H 01H 130 HOT 5803P 110 68 0.25 48 P 6 SAI 04H +0.65 04H 04H 130 HOT 5803P 118 68 0.19 68 P 6 SAI 01H -0.78 01H 01H 130 HOT 5803P 0.15 63 P 6 SAI 02H +0.86 02H 02H 130 HOT 5803P 47 69 0.14 45 P 6 SAI 03H +0.79 03H 03H 163 HOT 5803P 0.14 58 P 6 SAI 03H -0.53 03H 03H 163 HOT 5803P 61 69 0.19 81 P 6 SAI 05H +0.64 05H 05H 148 HOT 5803P 67 69 0.41 292 P 6 SAI 03H +0.74 03H 03H 50 HOT 5803P 83 69 0.33 105 P 6 SAI 01H -0.48 01H 01H 130 HOT 5803P 95 69 0.29 92 P 6 SAI 01H -0.27 01H 01H 130 HOT 5803P 99 69 0.24 92 P 6 SAI 01H -0.82 01H 01H 130 HOT 5803P 0.30 71 P 6 SAI 01H +0.74 01H 01H 130 HOT 5803P 101 69 0.24 96 P 6 SAI 01H -0.80 01H 01H 130 HOT 5803P 105 69 0.24 103 P 6 MAI 01H -0.32 01H 01H 130 HOT 5803P 48 70 0.33 75 P 6 SAI 01H -0.70 01H 01H 163 HOT 5803P 0.19 58 P 6 SAI 04H -0.32 04H 04H 163 HOT 5803P 68 70 0.34 94 P 6 MAI 03H -0.07 03H 03H 50 HOT 5803P
Framatome ANP Inc. 1/22/2005 14:30 Attacbment 4 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G B Page 9 of 24 Tubes with Bobbin 40-100% TWD and +Point Vol, Circ and Axial Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL LEG PROBE 80 70 0.25 88 P 6 SAI 01H -0.49 01H 01H 50 HOT 5803P 94 70 0.13 73 P 6 SAI 01H +0.34 01H 01H 171 HOT 5803P 102 70 0.20 67 P 6 SAI 01H -0.72 01H 01H 130 HOT 5803P 59 71 0.41 78 P 6 SAI 05H -0.75 05H 05H 148 HOT 5803P 65 71 0.17 76 P 6 SAI 02H +0.70 02H 02H 148 HOT 5803P 69 71 0.26 258 P 6 SAI 03H -0.07 03H 03H 50 HOT 5803P 0.18 66 P 6 SAI 03H +0.91 03H 03H 50 HOT 5803P 101 71 0.19 98 P 6 SAI 01H -0.82 01H 01H 130 HOT 5803P 70 72 0.16 74 P 6 SAI 08H -0.08 08H 08H 50 HOT 5803P 0.23 76 P 6 NAI 08H +0.91 08H 08H 50 HOT 5803P 94 72 0.22 74 P 6 NAI 01H -0.40 01H 01H 130 HOT 5803P 100 72 0.34 86 P 6 SAI 01H +0.09 01H 01H 130 HOT 5803P 59 73 0.35 80 P 6 MAI 01H +0.19 01H 01H 148 HOT 5803P 89 73 0.16 113 P 6 SAI 01H -0.37 01H 01H 130 HOT 5803P 101 73 0.43 101 P 6 MAI 01H +0.35 01H 01H 130 HOT 5803P 58 74 0.16 67 P 6 SAI 04H -0.54 04H 04H 148 HOT 5803P 68 74 0.42 268 P 6 SAI 03H +0.30 03H 03H 50 HOT 5803P 94 74 0.27 85 P 6 SAI 02H +0.86 02H 02H 130 HOT 5803P 100 74 0.36 83 P 6 SAI 01H -0.82 01H 01H 130 HOT 5803P 116 74 0.29 1.07 P 6 SAI 01H -0.43 01H 01H 130 HOT 5803P 49 75 0.37 106 P 6 SAI 01H +0.34 01H 01H 163 HOT 5803P 0.26 96 P 6 SAI 06H -0.29 06H 06H 163 HOT 5803P 0.29 96 P 6 SAI 06H +0.49 06H 06H 163 HOT 5803P 53 75 0.22 69 P 6 SAI 03H -0.51 03H 03H 163 HOT 5803P 61 75 0.18 72 P 6 SAI 01H +0.51 01H 01H 148 HOT 5803P 0.39 86 P 6 NAI 07H +0.11 07H 07H 148 HOT 5803P 117 75 0.25 102 P 6 SAI 01H -0.23 01H 01H 130 HOT 5803P 108 76 0.18 63 P 6 SAI 02H +0.77 02H 02H 130 HOT 5803P 112 76 0.61 97 P 6 SAI 01H -0.30 01H 01H 130 HOT 5803P 77 77 0.19 134 P 1 SCI TSH -0.18 TSH TSH 39 HOT 5803P 105 77 0.40 99 P 6 SAI 01H -0.23 01H 01H 131 HOT 5803P 109 77 0.33 78 P 6 SAI 02H +0.65 02H 02H 131 HOT 5803P 94 78 0.43 118 P 6 MAI 01H -0.64 01H 01H 131 HOT 5803P 116 78 0.14 73 P 6 SAI 01H +0.43 01H 01H 131 HOT 5803P 120 78 0.32 83 P 6 MAI 02H +0.87 02H 02H 131 HOT 5803P 122 78 0.14 90 P 6 SAI 01H +0.30 01H 01H 131 HOT 5803P 124 78 0.39 89 P 6 SAI 03H +0.86 03H 03H 131 HOT 5803P 0.27 99 P 6 SAI 04H +0.78 04H 04H 131 HOT 5803P 0.68 107 P 6 MAI 05H +0.29 05H 05H 131 HOT 5803P 59 79 0.18 77 P 6 SAI 08C -0.99 DCT 08C 87 COLD 5602P 0.72 98 P 6 SAI 07H +0.70 07H 07H 148 HOT 5803P 105 79 0.50 110 P 6 MAI 01H -0.55 01H 01H 131 HOT 5803P 68 80 0.20 77 P 6 SAI 04H +0.79 04H 04H 148 HOT 5803P 102 80 0.19 98 P 6 SAI 01H +0.79 01H 01H 131 HOT 5803P 0.19 76 P 6 SAI 01H +0.00 01H 01H 131 HOT 5803P 108 80 0.21 78 P 6 MAI 01H +0.95 01H 01H 131 HOT 5803P 0.15 42 P 6 SAI 02H +0.85 02H 02H 131 HOT 5803P 110 80 0.24 65 P 6 MAI 01H -0.34 01H 01H 131 HOT 5803P 114 80 0.33 103 P 6 SAI 01H -0.57 01H 01H 131 HOT 5803P 122 80 0.69 98 P 6 SAI 02H -0.69 02H 02H 131 HOT 5803P 0.18 99 P 6 SAI 03H +0.90 03H 03H 131 HOT 5803P 0.25 84 P 6 MAI 05H +0.75 05H 05H 131 HOT 5803P 124 80 0.35 79 P 6 SAI 02H +0.85 02H 02H 131 HOT 5803P 134 80 0.33 73 P 6 SAI 02H -0.68 02H 02H 146 HOT 5803P
Framatome ANP Inc. 1/22/2005 14:30 Attacbment 4 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G B Page 10 of 24 Tubes with Bobbin 40-100% TWD and +Point Vol, Circ and Axial Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 59 81 0.28 104 P=6 SAI 01H -0.75 01H 01H 148 HOT 5803P 61 81 0.26 95 P 6 SAI 03H -0.45 03H 03H 148 HOT 5803P 0.23 98 P 6 SAI 07H +0.54 07H 07H 148 HOT 5803P 67 81 0.24 138 P 6 SAI 01H -0.30 01H 01H 148 HOT 5803P 69 81 0.17 85 P 6 SAI 07H +0.44 07H 07H 148 HOT 5803P 103 81 0.36 96 P 6 SAI 01H -0.70 01H 01H 131 HOT 5803P 105 81 0.33 102 P 6 SAI 02H +0.86 02H 02H 131 HOT 5803P 133 81 0.09 88 P 6 SAI 01H -0.70 01H 01H 146 HOT 5803P 0.14 87 P 6 SAI 02H +0.82 02H 02H 146 HOT 5803P 0.10 68 P 6 SAI 02H -0.59 02H 02H 146 HOT 5803P 96 82 0.17 44 P 6 SAI 01H -0.62 01H 01H 131 HOT 5803P 98 82 0.29 86 P 6 SAI 02H +0.89 02H 02H 131 HOT 5803P 130 82 0.22 79 P 6 SAI 01H +0.85 01H 01H 131 HOT 5803P 109 83 0.36 105 P 6 SAI 02H -0.57 02H 02H 131 HOT 5803P 117 83 0.44 107 P 6 SAI 01H -0.45 01H 01H 131 HOT 5803P 100 84 0.42 99 P 6 SAI 01H +0.05 01H 01H 131 HOT 5803P 102 84 0.38 106 P 6 SAI 01H -0.65 01H 01H 131 HOT 5803P 0.37 82 P 6 SAI 01H +0.52 01H 01H 131 HOT 5803P 118 84 0.17 81 P 6 SAI 01H -0.75 01H 01H 131 HOT 5803P 61 85 0.19 270 P 6 MAI 07H -0.66 07H 07H 148 HOT 5803P 81 85 0.51 99 P 6 SAI 01H +0.26 01H 01H 131 HOT 5803P 85 85 0.17 36 P 6 SAI 02H +0.48 02H 02H 133 HOT 5803P 103 85 0.62 103 P 6 SAI 01H -0.41 01H 01H 133 HOT 5803P 0.19 86 P 6 SAI 05H +0.87 05H 05H 133 HOT 5803P 115 85 0.17 85 P 6 SAI 01H +0.81 01H 01H 171 HOT 5803P 139 85 0.24 106 P 6 SAI 01H +0.19 01H 01H 146 HOT 5803P 58 86 0.23 90 P 6 SAI 06H +0.70 06H 06H 148 HOT 5803P 0.17 65 P 6 SAI 06H +0.18 06H 06H 148 HOT 5803P 0.31 71 P 6 SAI 08H +1.49 DHT 08H 162 HOT 5402P 84 86 0.13 76 P 6 SAI 02H +0.72 02H 02H 133 HOT 5803P 86 86 0.17 88 P 6 SAI 01H -0.43 01H 01H 171 HOT 5803P 0.17 70 P 6 SAI 02H +0.46 02H 02H 171 HOT 5803P 108 86 0.32 69 P 6 MAI 01H -0.68 01H 01H 133 HOT 5803P 124 86 0.18 53 P 6 MAI 01H -0.96 01H 01H 133 HOT 5803P 53 87 0.30 93 P 6 SAI 06H -0.27 06H 06H 148 HOT 5803P 0.20 98 P 6 SAI 06H +0.39 06H 06H 148 HOT 5803P 61 87 0.26 67 P 6 SAI 01H +0.62 01H 01H 148 HOT 5803P 0.30 89 P 6 SAI 05H -0.23 05H 05H 148 HOT 5803P 0.22 78 P 6 SAI 05H +0.60 05H 05H 148 HOT 5803P 65 87 0.25 77 P 6 SAI 01H +0.59 01H 01H 148 HOT 5803P 103 87 0.65 97 P 6 SAI 01H -0.31 01H 01H 133 HOT 5803P 109 87 0.26 89 P 6 SAI 01H -0.22 01H 01H 133 HOT 5803P 0.18 71 P 6 SAI 01H +0.92 01H 01H 133 HOT 5803P 98 88 0.26 80 P 6 MAI 01H -0.56 01H 01H 133 HOT 5803P 106 88 0.39 91 P 6 SAI 01H -0.33 01H 01H 133 HOT 5803P 122 88 1.04 89 P 6 MAI 01H -0.37 01H 01H 133 HOT 5803P 126 88 0.29 68 P 6 MAI 01H -0.66 01H 01H 133 HOT 5803P 53 89 0.38 99 P 6 MAI 07H +0.20 07H 07H 148 HOT 5803P 87 89 0.26 97 P 6 SAI 04H +0.92 04H 04H 133 HOT 5803P 58 90 0.51 103 P 6 MAI 04H +0.49 04H 04H 148 HOT 5803P 122 90 0.41 112 P 6 SAI 01H -0.32 01H 01H 133 HOT 5803P 0.57 99 P 6 SAI 02H +0.65 02H 02H 133 HOT 5803P 126 90 0.37 99 P 6 MAI 01H +0.47 01H 01H 133 HOT 5803P 134 90 0.23 88 P 6 SAI 02H +0.34 02H 02H 146 HOT 5803P
Framatome ANP Inc. 1/22/2005 14:30 Attacbment 4 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G B Page 11 of 24 Tubes with Bobbin 40-100% TWD and +Point Vol. Circ and Axial Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL LEG PROBE 47 91 0.45 98 P 6 SAI 01H +0.77 01H 01H 148 HOT 5803P 77 91 0.25 92 P 6 SAI 04H +0.46 04H 04H 148 HOT 5803P 103 91 0.36 87 P 6 SAI 02H +0.62 02H 02H 133 HOT 5803P 107 91 0.23 90 P 6 SAI 01H +0.82 01H 01H 133 HOT 5803P 135 91 0.15 102 P 6 SAI 01H +0.84 01H 01H 146 HOT 5803P 0.24 92 P 6 SAI 02H +0.79 02H 02H 146 HOT 5803P 0.10 72 P 6 SAI 02H -0.26 02H 02H 146 HOT 5803P 58 92 0.29 117 P 6 SAI 02H +0.93 02H 02H 148 HOT 5803P 0.24 96 P 6 SAI 05H +0.88 05H 05H 148 HOT 5803P 60 92 0.23 80 P 6 SAI 05H -0.13 05H 05H 148 HOT 5803P 0.23 65 P 6 SAI 05H +0.72 05H 05H 148 HOT 5803P 66 92 0.36 118 P 6 SAI 03H -0.71 03H 03H 148 HOT 5803P 98 92 0.28 93 P 6 SAI 01H +0.00 01H 01H 133 HOT 5803P 0.28 74 P 6 SAI 01H -0.76 01H 01H 133 HOT 5803P 114 92 0.14 56 P 6 SAI 04H +1.00 04H 04H 133 HOT 5803P 122 92 0.32 112 P 6 MAI 01H -0.62 01H 01H 133 HOT 5803P 0.12 89 P 6 SAI 02H +0.23 02H 02H 133 HOT 5803P 134 92 0.16 98 P 6 SAI 02H -0.73 02H 02H 146 HOT 5803P 0.20 103 P 6 SAI 02H +0.26 02H 02H 146 HOT 5803P 53 93 0.30 98 P 6 MAI 02H +0.47 02H 02H 148 HOT 5803P 0.31 87 P 6 SAI 03H +0.90 03H 03H 148 HOT 5803P 55 93 0.27 100 P 6 SAI 02H +0.94 02H 02H 148 HOT 5803P 0.37 89 P 6 SAI 04H +0.91 04H 04H 148 HOT 5803P 57 93 0.37 103 P 6 SAI 03H +0.65 03H 03H 148 HOT 5803P 65 93 0.43 96 P 6 SAI 06H +0.68 06H 06H 148 HOT 5803P 01H +0.75 01H 01H 148 HOT 5803P 77 93 0.29 113 P 6 SAI 102 P 6 SAI 07H +0.76 07H 07H 148 HOT 5803P 0.32 117 93 0.36 99 P 6 SAI 02H +0.25 02H 02H 133 HOT 5803P 62 94 0.43 94 P 6 MAI 01H -0.13 01H 01H 148 HOT 5803P 0.51 111 P 6 SAI 02H +0.78 02H 02H 148 HOT 5803P
-0.10 04H 04H HOT 0.26 92 P 6 MAI 04H 148 5803P 01H +0.41 01H 01H 148 HOT 66 94 0.30 95 P 6 SAI 5803P 0.28 97 P 6 MAI 06H +0.44 06H 06H 148 HOT 5803P 0.24 94 P 6 SAI 08H -0.16 08H 08H 148 HOT 5803P 0.23 81 P 6 MAI 08H +0.81 08H 08H 148 HOT 5803P 86 94 0.54 98 P 6 SAI 01H -0.20 01H 01H 133 HOT 5803P 102 94 0.41 276 P 6 SAI 01H -0.36 01H 01H 133 HOT 5803P 0.27 94 P 6 SAI 01H +0.46 01H 01H 133 HOT 5803P 0.27 97 P 6 SAI 02H +0.83 02H 02H 133 HOT 5803P 118 94 0.23 104 P 6 SAI 01H +0.60 01H 01H 133 HOT 5803P 122 94 0.32 89 P 6 SAI 01H +0.80 01H 01H 133 HOT 5803P 134 94 0.18 90 P 6 SAI 02H +0.68 02H 02H 146 HOT 5803P 47 95 0.42 100 P 6 SAI 02H +0.73 02H 02H 148 HOT 5803P 0.37 102 P 6 SAI 02H -0.33 02H 02H 148 HOT 5803P 49 95 0.31 92 P 6 SAI 02H +0.92 02H 02H 148 HOT 5803P 69 95 0.21 68 P 6 MAI 02H +0.88 02H 02H 148 HOT 5803P 81 95 0.46 101 P 6 SAI 01H +0.02 01H 01H 133 HOT 5803P 87 95 0.33 107 P 6 SAI 01H -0.32 01H 01H 133 HOT 5803P 103 95 0.46 99 P 6 SAI 01H -0.86 01H 01H 133 HOT 5803P 0.35 78 P 6 SAI 01H +0.81 01H 01H 133 HOT 5803P 0.26 91 P 6 SAI 02H +0.52 02H 02H 133 HOT 5803P 0.21 92 P 6 SAI 04H +0.86 04H 04H 133 HOT 5803P 0.41 87 P 6 MAI 07H +0.37 07H 07H 133 HOT 5803P 105 95 0.32 99 P 6 SAI 01H -0.39 01H 01H 133 HOT 5803P
Framatome ANP Inc. 1/22/2005 14:30 Attacbment 4 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G B Page 12 of 24 Tubes with Bobbin 40-100% TWD and +Point Vol. Circ and Axial Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL
- LEG PROBE 0.27 74 P 6 SAX 02H +0.69 02H 02H 133 HOT 5803P 107 95 0.19 62 P 6 SAX 06H -0.44 06H 06H 133 HOT 5803P 40 96 0.47 96 P 6 SAX 04H +0.73 04H 04H 148 HOT 5803P 0.27 107 P 6 SAX 06H +0.93 06H 06H 148 HOT 5803P 48 96 0.35 109 P 6 SAI 01H +0.23 01H 01H 148 HOT 5803P 0.39 88 P 6 SAI 02H -0.67 02H 02H 148 HOT 5803P 0.43 95 P 6 SAI 04H +0.74 04H 04H 148 HOT 5803P 0.44 105 P 6 SAI 05H -0.37 05H 05H 148 HOT 5803P 0.36 101 P 6 SAI 05H +0.78 05H 05H 148 HOT 5803P 58 96 0.25 75 P 6 SAI 03H +0.96 03H 03H 148 HOT 5803P 64 96 0.26 110 P 6 SAI 02H +0.63 02H 02H 148 HOT 5803P 86 96 0.14 69 P 6 SAI O1H -0.86 01H 01H 135 HOT 5803P 90 96 0.21 111 P 6 SAI 01H -0.48 01H 01H 135 HOT 5803P 98 96 0.30 116 P 6 SAI 04H +0.81 04H 04H 135 HOT 5803P 102 96 0.28 70 P 6 SAI 01H -0.75 01H 01H 163 HOT 5803P 104 96 0.31 90 P 6 SAI 01H +0.66 01H 01H 135 HOT 5803P 108 96 0.15 75 P 6 MAI 01H +0.83 01H 01H 135 HOT 5803P 0.19 89 P 6 SAI 02H +0.64 02H 02H 135 HOT 5803P 122 96 0.35 98 P 6 SAI 01H -0.21 01H 01H 135 HOT 5803P 124 96 0.25 60 P 6 SAI 02H -0.75 02H 02H 135 HOT 5803P 0.26 74 P 6 MAI 02H +0.48 02H 02H 135 HOT 5803P 59 97 0.55 98 P 6 SAI 01H -0.75 01H 01H 148 HOT 5803P 61 97 0.44 93 P 6 SAI 02H +0.48 02H 02H 163 HOT 5803P 0.34 96 P 6 SAI 01H +0.02 01H 01H 148 HOT 5803P 0.29 105 P 6 SAI 05H -0.31 05H 05H 148 HOT 5803P 97 97 0.26 84 P 6 SAI 02H +0.47 02H 02H 135 HOT 5803P 103 97 0.42 95 P 6 SAI 01H -0.16 01H 01H 135 HOT 5803P 0.38 95 P 6 SAI 01H +0.87 01H 01H 135 HOT 5803P 0.32 113 P 6 SAI 04H +0.46 04H 04H 135 HOT 5803P 0.22 75 P 6 SAI 05H +0.82 05H 05H 135 HOT 5803P 119 97 0.28 86 P 6 SAI 02H +0.53 02H 02H 135 HOT 5803P 74 98 0.29 82 P 6 SAI 05H +0.80 05H 05H 148 HOT 5803P 90 98 0.23 92 P 6 SAI 01H +0.86 01H 01H 135 HOT 5803P 98 98 0.20 66 P 6 SAI 05H +0.85 05H 05H 135 HOT 5803P 108 98 0.18 77 P 6 SAI 02H +0.91 02H 02H 135 HOT 5803P 110 98 0.20 47 P 6 SAI 03H +0.45 03H 03H 135 HOT 5803P 116 98 0.24 39 P 6 SAI 02H +0.82 02H 02H 135 HOT 5803P 122 98 0.45 77 P 6 SAI 02H -0.22 02H 02H 135 HOT 5803P 61 99 0.44 98 P 6 SAI 02H +0.61 02H 02H 148 HOT 5803P 87 99 0.27 87 P 6 SAI 02H +0.52 02H 02H 135 HOT 5803P 93 99 0.20 78 P 6 SAI 01H +0.90 01H 01H 135 HOT 5803P 105 99 0.18 75 P 6 SAI 01H -0.49 01H 01H 171 HOT 5803P 0.15 55 P 6 SAI 01H +0.30 01H 01H 171 HOT 5803P 107 99 0.18 93 P 6 SAI 01H -0.15 01H 01H 135 HOT 5803P 60 100 0.27 64 P 6 SAI 01H +0.91 01H 01H 140 HOT 5803P 64 100 0.21 73 P 6 SAI 01H -0.20 01H 01H 171 HOT 5803P 0.31 80 P 6 SAI 01H +0.65 01H 01H 171 HOT 5803P 66 100 0.21 131 P 6 SAI 02H +0.82 02H 02H 140 HOT 5803P 68 100 0.69 96 P 6 MAI 01H +0.60 01H 01H 140 HOT 5803P 0.17 72 P 6 MAI 03H +0.76 03H 03H 140 HOT 5803P 72 100 0.20 83 P 6 SAI 01H +0.76 01H 01H 140 HOT 5803P 98 100 0.26 101 P 6 SAI 01H -0.85 01H 01H 145 HOT 5803P 108 100 0.32 104 P 6 SAI 01H +0.20 01H 01H 145 HOT 5803P 116 100 0.13 67 P 6 MAI 03H +0.90 03H 03H 145 HOT 5803P
Framatome ANP Inc. 1/22/2005 14:30 Attachment 4 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G B Page 13 of 24 Tubes with Bobbin 40-100% TWD and +Point Vol. Circ and Axial Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL I LEG PROBE 49 101 0.31 96 P 6 MAI 01H +0.79 01H 01H 140 HOT 5803P 53 101 0.37 84 P 6 SAI 01H +0.22 01H 01H 140 HOT 5803P 0.28 74 P 6 SAI 07H +0.31 07H 07H 140 HOT 5803P 69 101 0.18 82 P 6 SAI 01H +0.88 01H 01H 140 HOT 5803P 81 101 0.21 133 P 6 SAI 02H +0.86 02H 02H 145 HOT 5803P 89 101 0.24 103 P 6 MAI 01H -0.22 01H 01H 171 HOT 5803P 0.18 59 P 6 SAI 02H +0.80 02H 02H 171 HOT 5803P 0.20 77 P 6 SAI 04H +0.70 04H 04H 171 HOT 5803P 97 101 0.32 93 P 6 SAI 01H -0.50 01H 01H 145 HOT 5803P 103 101 0.36 111 P 6 SAI 01H -0.43 01H 01H 145 HOT 5803P 0.40 111 P 6 SAI 01H +0.33 01H 01H 145 HOT 5803P 36 102 0.69 96 P 6 SAI 05H +0.26 05H 05H 140 HOT 5803P 64 102 0.24 76 P 6 SAI 01H +0.84 01H 01H 140 HOT 5803P 68 102 0.24 112 P 6 SAI 02H +0.83 02H 02H 140 HOT 5803P 74 102 0.27 75 P 6 SAI 04H +0.69 04H 04H 140 HOT 5803P 0.40 102 P 6 MAI 01H -0.09 01H 01H 165 HOT 5803P 84 102 0.32 86 P 6 SAI 01H -0.62 01H 01H 145 HOT 5803P 120 102 0.27 88 P 6 SAI 02H +0.96 02H 02H 145 HOT 5803P 134 102 0.25 74 P 6 SAI 02H -0.95 02H 02H 146 HOT 5803P 53 103 0.32 77 P 6 SAI 06H -0.21 06H 06H 140 HOT 5803P 0.50 110 P 6 SAI 01H -0.44 01H 01H 165 HOT 5803P 69 103 0.34 83 P 6 SAI 01H +0.78 01H 01H 140 HOT 5803P 89 103 0.16 69 P 6 SAI 05H +0.88 05H 05H 145 HOT 5803P 119 103 0.15 58 P 6 SAI 02H -0.48 02H 02H 145 HOT 5803P 121 103 0.53 100 P 6 SAI 02H +0.68 02H 02H 145 HOT 5803P 48 104 0.34 95 P 6 MAI 01H +0.43 01H 01H 140 HOT 5803P 0.25 76 P 6 SAI 02H +0.64 02H 02H 140 HOT 5803P 68 104 0.38 87 P 6 SAI 01H +0.82 01H 01H 140 HOT 5803P 27 105 0.26 95 P 6 SAI 07H -0.41 07H 07H 129 HOT 5803P 53 105 0.24 66 P 6 SAI 01H +0.25 01H 01H 140 HOT 5803P 57 105 0.39 89 P 6 SAI 01H -0.23 01H 01H 140 HOT 5803P 0.20 98 P 1 SCI TSH -0.22 TSH TSH 82 HOT 5803P 89 105 0.25 106 P 6 SAI 01H -0.42 01H 01H 145 HOT 5803P 48 106 0.41 86 P 6 SAI 02H -0.48 02H 02H 140 HOT 5803P 60 106 0.28 87 P 1 SCI TSH +0.08 TSH TSH 83 HOT 5803P 0.26 107 P 1 SCI TSH -0.12 TSH TSH 83 HOT 5803P 64 106 0.21 56 P 6 SAI 02H +0.91 02H 02H 140 HOT 5803P 82 106 0.55 87 P 6 SAI 01H +0.68 01H 01H 145 HOT 5803P 110 106 0.34 85 P 6 MAI 02H +0.37 02H 02H 145 HOT 5803P 7 107 0.57 103 P 6 MAI 01H -0.40 01H 01H 123 HOT 5803P 0.11 84 P 6 SAI DHB +0.00 07H DHT 123 HOT 5803P 0.25 98 P 6 MAI 07H +0.45 07H DHT 123 HOT 5803P 13 107 0.18 80 P 6 SAI 06H -0.06 06H 06H 129 HOT 5803P 37 107 0.18 74 P 6 SAI 07H -0.77 07H 07H 129 HOT 5803P 0.22 78 P 6 SAI 07H +0.67 07H 07H 129 HOT 5803P 61 107 0.30 90 P 6 SAI 02H +0.83 02H 02H 140 HOT 5803P 8 108 0.34 107 P 6 SAI 06H +0.46 06H 06H 123 HOT 5803P 48 108 0.34 96 P 6 SAI 02H +0.72 02H 02H 140 HOT 5803P 50 108 0.19 60 P 6 SAI 02H +0.95 02H 02H 140 HOT 5803P 60 108 0.60 26 2 SAI TSH -0.14 TSH TSH 81 HOT 5803P 66 108 0.31 81 P 6 SAI 01H -0.44 01H 01H 140 HOT 5803P 110 108 0.30 95 P 6 MAI 01H -0.50 01H 01H 145 HOT 5803P 126 108 0.38 77 P 6 SAI 02H +0.89 02H 02H 143 HOT 5803P 5 109 0.19 86 P 6 SAI 01H -0.71 01H 01H 123 HOT 5803P
Framatome ANP Inc. 1/22/2005 14:30 Attacbment 4 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G B Page 14 of 24 Tubes with Bobbin 40-100% TWD and +Point Vol, Circ and Axial Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL LEG PROBE 0.17 91 P 6 SAI 01H +0.58 01H 01H 123 HOT 5803P 7 109 0.16 76 P 6 SAI 03H -0.64 03H 03H 123 HOT 5803P 0.23 97 P 6 SAI 03H +0.80 03H 03H 123 HOT 5803P 0.27 68 P 6 SAI 06H -0.72 06H 06H 123 HOT 5803P 0.43 90 P 6 SAI 06H +0.10 06H 06H 123 HOT 5803P 9 109 0.42 110 P 6 MAI 06H +0.38 06H 06H 123 HOT 5803P 0.42 91 P 6 MAI 07H -0.26 07H DHT 123 HOT 5803P 47 109 0.15 86 P 6 SAI DHB +0.41 DHB DHB 159 HOT 5402P 8 110 0.38 103 P 6 MAI 06H -0.21 06H 06H 123 HOT 5803P 38 110 0.31 101 P 6 SAI 04H +0.58 04H 04H 129 HOT 5803P 54 110 0.28 76 P 6 SAI 01H +0.59 01H 01H 140 HOT 5803P 102 110 0.32 87 P 6 MAI 04H +0.78 04H 04H 145 HOT 5803P 114 110 0.20 63 P 6 MAI 02H -0.39 02H 02H 145 HOT 5803P 126 110 0.22 108 P 6 SAI 01H +0.72 01H 01H 143 HOT 5803P 1 111 0.38 88 P 6 SAI 06H +0.73 06H 06H 165 HOT 5803P 17 111 0.33 88 P 6 SAI 02H +0.87 02H 02H 129 HOT 5803P 23 111 0.30 96 P 6 SAI 07H -0.36 07H 07H 129 HOT 5803P 25 111 0.39 78 P 6 SAI 02H +0.54 02H 02H 129 HOT 5803P 49 111 0.15 22 P 1 SCI TSH -0.22 TSH TSH 75 HOT 5803P 57 111 0.12 63 P 6 SAI 01H -0.47 01H 01H 140 HOT 5803P 0.35 81 P 6 SAI 01H +0.83 01H 01H 140 HOT 5803P 63 111 0.26 84 P 6 SAI 03H +0.71 03H 03H 129 HOT 5803P 101 111 0.29 112 P 6 SAI 01H +0.35 01H 01H 145 HOT 5803P 4 112 0.29 96 P 6 SAI 01H -0.82 01H 01H 123 HOT 5803P 0.14 86 P 6 SAI 01H +0.69 01H 01H 123 HOT 5803P 6 112 0.36 94 P 6 SAI 05H -0.69 05H 05H 123 HOT 5803P 0.31 99 P 6 SAI 05H +0.86 05H 05H 123 HOT 5803P 0.27 100 P 6 SAI 06H -0.30 06H 06H 123 HOT 5803P 0.38 99 P 6 SAI 06H +0.36 06H 06H 123 HOT 5803P 44 112 0.38 95 P 6 MAI 01H +0.64 01H 01H 129 HOT 5803P 56 112 0.35 91 P 6 MAI 01H -0.25 01H 01H 129 HOT 5803P 88 112 0.32 96 P 6 SAI 01H +0.65 01H 01H 145 HOT 5803P 102 112 0.27 99 P 6 MAI 01H -0.61 01H 01H 145 HOT 5803P 112 112 0.16 64 P 6 MAI 02H +0.81 02H 02H 145 HOT 5803P 0.17 80 P 6 MAI 04H +0.81 04H 04H 145 HOT 5803P 120 112 0.18 70 P 6 SAI 01H +0.87 01H 01H 145 HOT 5803P 5 113 0.36 100 P 6 SAI 01H -0.52 01H 01H 123 HOT 5803P 7 113 0.53 95 P 6 SAI 06H +0.67 06H 06H 123 HOT 5803P 9 113 0.31 62 P 6 MAI 01H -0.28 01H 01H 123 HOT 5803P 0.14 72 P 6 SAI 05H -0.56 05H 05H 123 HOT 5803P 0.26 83 P 6 MAI 05H +0.30 05H 05H 123 HOT 5803P 0.23 86 P 6 SAI 07H -0.90 07C 07H 155 HOT 5602P 0.16 263 P 6 MAI 07H +0.20 07C 07H 155 HOT 5602P 17 113 0.14 41 P 6 SAI 02H -0.28 02H 02H 129 HOT 5803P 0.19 75 P 6 SAI 05H +0.19 05H 05H 129 HOT 5803P 0.16 73 P 6 SAI 06H +0.79 06H 06H 129 HOT 5803P 0.21 79 P 6 HAI 07H -0.11 07H 07H 129 HOT 5803P 0.22 57 P 6 SAI 07H +0.82 07H 07H 129 HOT 5803P 27 113 0.18 63 P 6 SAI 01H +0.83 01H 01H 129 HOT 5803P 29 113 0.37 109 P 6 SAI 01H -0.58 01H 01H 129 HOT 5803P 43 113 0.11 125 P 1 SCI TSH -0.08 TSH TSH 75 HOT 5803P 47 113 0.16 87 P 1 SCI TSH -0.05 TSH TSH 76 HOT 5803P 49 113 0.35 54 2 SAI TSH -0.22 TSH TSH 75 HOT 5803P 0.08 39 P 6 SAI 01H -0.27 01H 01H 129 HOT 5803P
Framatome ANP Inc. 1/22/2005 14:30 Attachment 4 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G B Page 15 of 24 Tubes with Bobbin 40-100% TWD and +Point Vol, Circ and Axial Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 0.23 117 P6 MAI 01H +0.81 01H 01H 129 HOT 5803P 53 113 0.69 100 P6 SAI 02H +0.51 02H 02H 129 HOT 5803P 69 113 0.27 82 P6 SAI 02H +0.47 02H 02H 129 HOT 5803P 0.20 155 P6 SAI 03H -0.86 03H 03H 129 HOT 5803P 0.31 122 P6 SAI 03H -0.34 03H 03H 129 HOT 5803P 71 113 0.10 126 P6 SAI 02H -0.87 02H 02H 129 HOT 5803P 0.20 38 P6 SAI 02H +0.89 02H 02H 129 HOT 5803P 103 113 0.15 47 P6 SAI 02H -0.31 02H 02H 145 HOT 5803P 0.13 98 P6 SAI 02H +0.91 02H 02H 145 HOT 5803P 6 114 0.56 102 P6 SAI 01H -0.84 01H 01H 123 HOT 5803P 0.33 105 P6 SAI 01H +0.72 01H 01H 123 HOT 5803P 0.22 79 P6 SAI 03H +0.73 03H 03H 123 HOT 5803P 0.31 97 P6 MAI 05H +0.65 05H 05H 123 HOT 5803P 0.36 112 P6 SAI 07H -0.07 07H DHT 123 HOT 5803P 0.29 105 P6 SAI 07H +0.84 07H DHT 123 HOT 5803P 8 114 0.38 86 P6 SAI 05H +0.63 05H 05H 123 HOT 5803P 16 114 0.20 114 P6 MAI 07H -0.54 07H 07H 129 HOT 5803P 28 114 0.19 82 P6 SAI 02H +0.92 02H 02H 129 HOT 5803P 68 114 0.31 95 P6 MAI 01H -0.73 01H 01H 129 HOT 5803P 104 114 0.25 106 P6 MAI 04H +0.68 04H 04H 145 HOT 5803P 108 114 0.17 101 P6 MAI 02H +0.80 02H 02H 145 HOT 5803P 0.18 75 P6 SAI 04H -0.42 04H 04H 145 HOT 5803P 118 114 0.16 89 P6 MAI 01H +0.79 01H 01H 143 HOT 5803P 120 114 0.30 102 P6 MAI 02H +0.54 02H 02H 143 HOT 5803P 122 114 0.20 82 P6 SAI 01H +0.71 01H 01H 143 HOT 5803P 0.30 88 P6 MAI 02H +0.91 02H 02H 143 HOT 5803P 7 115 0.20 80 P6 SAI 01H +0.31 01H 01H 123 HOT 5803P 9 115 0.19 86 P6 SAI 01H +0.64 01H 01H 123 HOT 5803P 0.37 78 P6 MAI 04H -0.16 04H 04H 123 HOT 5803P 0.22 76 P6 SAI 06H -0.22 06H 06H 123 HOT 5803P 17 115 0.18 92 P6 SAI 01H -0.54 01H 01H 129 HOT 5803P 0.41 81 P6 SAI 01H +0.39 01H 01H 129 HOT 5803P 21 115 0.14 90 P6 SAI 07H -0.60 07H 07H 129 HOT 5803P 23 115 0.49 103 P6 MAI 04H +0.11 04H 04H 165 HOT 5803P 0.21 92 P6 SAI 06H +0.17 06H 06H 129 HOT 5803P 0.17 91 P6 SAI DHB +0.93 DHT DHB 155 HOT 5602P 53 115 0.15 29 P6 SAI 02H -0.35 02H 02H 129 HOT 5803P 0.23 114 P6 SAI 02H +0.42 02H 02H 129 HOT 5803P 57 115 0.30 76 P6 SAI 01H +0.77 01H 01H 129 HOT 5803P 61 115 0.16 65 P6 SAI 01H -0.36 01H 01H 129 HOT 5803P 0.47 90 P6 SAI 01H +0.64 01H 01H 129 HOT 5803P 63 115 0.18 53 P6 SAI 02H -0.39 02H 02H 129 HOT 5803P 69 115 0.27 108 P6 SAI 02H +0.83 02H 02H 129 HOT 5803P 71 115 0.49 108 P6 SAI 01H +0.38 01H 01H 129 HOT 5803P 99 115 0.30 99 P6 SAI 01H -0.32 01H 01H 145 HOT 5803P 105 115 0.32 98 P6 SAI 04H -0.57 04H 04H 145 HOT 5803P 0.12 60 P6 SAI 04H +0.78 04H 04H 145 HOT 5803P 107 115 0.31 91 P6 SAI 02H +0.78 02H 02H 145 HOT 5803P 109 115 0.27 86 P6 SAI 02H +0.86 02H 02H 145 HOT 5803P 4 116 0.52 88 P6 SAI 06H +0.21 06H 06H 123 HOT 5803P 6 116 0.22 108 P6 SAI 01H -0.86 01H 01H 123 HOT 5803P 0.13 50 P6 SAI 02H -0.90 02H 02H 123 HOT 5803P 0.16 66 P6 SAI 05H -0.88 05H 05H 123 HOT 5803P 0.32 73 P6 SAI 05H +0.27 05H 05H 123 HOT 5803P
Framatome ANP Inc. 1/22/2005 14:30 Attacbment 4 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G B Page 16 of 24 Tubes with Bobbin 40-100% TWD and +Point Vol, Circ and Axial Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 10 116 0.26 104 P 6 MAI 06H -0.40 06H 06H 123 HOT 5803P 30 116 0.27 84 P 6 MAI 07H -0.69 07H 07H 136 HOT 5803P 48 116 0.44 91 P 6 SAI 01H +0.71 01H 01H 136 HOT 5803P 0.61 98 P 6 SAI 02H +0.69 02H 02H 136 HOT 5803P 0.35 96 P 6 SAI 06H +0.76 06H 06H 136 HOT 5803P 62 116 0.32 63 P 6 SAI 01H -0.57 01H 01H 129 HOT 5803P 104 116 0.70 101 P 6 SAI 01H -0.04 01H 01H 165 HOT 5803P 114 116 0.47 90 P 6 MAI 02H +0.75 02H 02H 143 HOT 5803P 0.17 66 P 6 MAI 04H +0.66 04H 04H 143 HOT 5803P 124 116 0.27 93 P 6 SAI 02H +0.57 02H 02H 143 HOT 5803P 9 117 0.14 72 P 6 SAI 07C -0.06 07C 07H 158 HOT 5602P 0.14 85 P 6 SAI 05H +0.33 05H 05H 123 HOT 5803P 0.39 71 P 6 SAI 06H -0.44 06H 06H 123 HOT 5803P 0.33 86 P 6 SAI 06H +0.63 06H 06H 123 HOT 5803P 29 117 0.37 77 P 6 SAI 03H -0.34 03H 03H 136 HOT 5803P 0.18 50 P 6 SAI 03H +0.34 03H 03H 136 HOT 5803P 41 117 0.18 101 P 6 SAI 02H -0.23 02H 02H 136 HOT 5803P 45 117 0.24 142 P 1 MCI TSH -0.14 TSH TSH 75 HOT 5803P 53 117 0.30 103 P 6 MAI 02H -0.59 02H 02H 129 HOT 5803P 0.17 100 P 6 SAI 02H +0.46 02H 02H 129 HOT 5803P 0.19 79 P 6 SAI 06H -0.59 06H 06H 129 HOT 5803P 0.63 90 P 6 SAI 06H +0.75 06H 06H 129 HOT 5803P 57 117 0.27 58 P 6 MAI 01H +0.71 01H 01H 129 HOT 5803P 59 117 0.25 89 P 6 SAI 02H +0.70 02H 02H 129 HOT 5803P 101 117 0.22 79 P 6 MAI 02H +0.79 02H 02H 145 HOT 5803P 103 117 0.20 66 P 6 SAI 02H +0.49 02H 02H 145 HOT 5803P 0.40 97 P 6 SAI 04H +0.56 04H 04H 145 HOT 5803P 107 117 0.16 76 P 6 SAI 04H +0.80 04H 04H 145 HOT 5803P 6 118 0.11 74 P 6 SAI 03H +0.76 03H 03H 123 HOT 5803P 0.23 104 P 6 SAI 05H +0.51 05H 05H 123 HOT 5803P 10 118 0.29 105 P 6 MAI 05H +0.85 05H 05H 123 HOT 5803P 12 118 0.20 79 P 6 SAI 01H -0.79 01H 01H 136 HOT 5803P 0.47 85 P 6 SAI 01H +0.70 01H 01H 136 HOT 5803P 0.24 94 P 6 SAI 05H +1.00 05H 05H 136 HOT 5803P 28 118 0.58 77 P 6 MAI 07H -0.30 07H 07H 136 HOT 5803P 34 118 0.23 95 P 6 MAI 01H +0.63 01H 01H 136 HOT 5803P 42 118 0.08 116 P 1 SCI TSH +0.06 TSH TSH 75 HOT 5803P 66 118 0.25 84 P 6 SAI 02H +0.48 02H 02H 129 HOT 5803P 72 118 0.27 74 P 6 SAI 01H -0.53 01H 01H 129 HOT 5803P 108 118 0.17 109 P 6 SAI 01H +0.90 01H 01H 145 HOT 5803P 7 119 0.30 100 P 6 SAI 01H +0.88 01H 01H 123 HOT 5803P 0.24 72 P 6 MAI 03H +0.79 03H 03H 123 HOT 5803P 0.25 74 P 6 SAI 06H +0.17 06H 06H 123 HOT 5803P 29 119 0.27 82 P 6 MAI 02H +0.85 02H 02H 136 HOT 5803P 37 119 0.15 132 P 1 SCI TSH +0.01 TSH TSH 75 HOT 5803P 0.21 83 P 6 SAI 02H +0.86 02H 02H 136 HOT 5803P 0.35 100 P 6 SAI 04H +0.80 04H 04H 136 HOT 5803P 49 119 0.23 44 P 6 SAI 02H +0.45 02H 02H 136 HOT 5803P 57 119 0.33 74 P 6 SAI 06H +0.43 06H 06H 132 HOT 5803P 0.16 94 P 6 SAI 06H -0.23 06H 06H 132 HOT 5803P 63 119 0.52 95 P 6 MAI 01H -0.19 01H 01H 129 HOT 5803P 69 119 0.18 50 P 6 SAI 01H -0.33 01H 01H 165 HOT 5803P 0.51 98 P 6 SAI 01H +0.66 01H 01H 165 HOT 5803P 0.35 111 P 6 SAI 02H +0.65 02H 02H 129 HOT 5803P
Framatome ANP Inc. 1/22/2005 14:30 Attacbment 4 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G B Page 17 of 24 Tubes with Bobbin 40-100% TWD and +Point Vol, Circ and Axial Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 93 119 0.19 99 P 6 SAI 02H +0.63 02H 02H 143 HOT 5803=P 101 119 0.29 108 P 6 SAI 02H +0.42 02H 02H 143 HOT 5803P 121 119 0.17 120 P 6 SAI O1H +0.38 01H 01H 143 HOT 5803P 4 120 0.35 89 P 6 MAI 05H +0.25 05H 05H 165 HOT 5803P 0.31 91 P 6 SAI 06H -0.47 06H 06H 123 HOT 5803P 0.19 52 P 6 SAI 06H +0.78 06H 06H 123 HOT 5803P 10 120 0.27 130 P 6 SAI 02H -0.30 02H 02H 123 HOT 5803P 0.14 39 P 6 SAI 02H +0.78 02H 02H 123 HOT 5803P 16 120 0.34 77 P 6 SAI 03H +0.75 03H 03H 165 HOT 5803P 0.23 73 P 6 SAI 01H -0.03 01H 01H 136 HOT 5803P 0.20 53 P 6 SAI 04H -0.71 04H 04H 136 HOT 5803P 42 120 0.58 105 P 6 SAI 02H -0.11 02H 02H 136 HOT 5803P 0.18 72 P 6 SAI 02H +0.54 02H 02H 136 HOT 5803P 62 120 0.21 79 P 6 MAI 01H -0.86 01H 01H 129 HOT 5803P 64 120 0.39 87 P 6 SAI 01H -0.06 01H 01H 129 HOT 5803P 0.33 97 P 6 SAI 01H +0.79 01H 01H 129 HOT 5803P 88 120 0.18 73 P 6 SAI 01H +0.74 01H 01H 143 HOT 5803P 0.24 102 P 6 SAI 01H +0.20 01H 01H 143 HOT 5803P 104 120 0.55 93 P 6 SAI 01H +0.44 01H 01H 143 HOT 5803P 0.27 107 P 6 SAI 02H +0.74 02H 02H 143 HOT 5803P 0.32 113 P 6 SAI 04H +0.38 04H 04H 143 HOT 5803P 110 120 0.18 75 P 6 MAI 02H +0.15 02H 02H 143 HOT 5803P 1 121 0.18 101 P 6 SAI DHB +0.39 07H 07C 84 COLD 7 121 0.26 73 P 6 SAI 02H -0.46 02H 02H 123 HOT 5803P 0.22 85 P 6 SAI 03H -0.55 03H 03H 123 HOT 5803P 0.13 69 P 6 SAI 03H +0.79 03H 03H 123 HOT 5803P 0.49 98 P 6 MAI 05H +0.44 05H 05H 123 HOT 5803P 0.24 94 P 6 SAI 06H +0.12 06H 06H 123 HOT 5803P 0.22 80 P 6 SAI 06H +0.83 06H 06H 123 HOT 5803P 9 121 0.17 93 P 6 SAI 01H +0.75 01H 01H 123 HOT 5803P 0.19 87 P 6 SAI 03H +0.77 03H 03H 123 HOT 5803P 27 121 0.48 79 P 6 SAI 01H +0.61 01H 01H 136 HOT 5803P 29 121 0.20 97 P 6 SAI 03H +0.74 03H 03H 136 HOT 5803P 37 121 0.26 86 P 6 MAI 02H +0.18 02H 02H 165 HOT 5803P 0.27 81 P 6 SAI 01H +0.18 01H 01H 136 HOT 5803P 39 121 0.28 69 P 6 SAI 01H +0.60 01H 01H 136 HOT 5803P 53 121 0.58 99 P 6 SAI 01H -0.58 01H 01H 136 HOT 5803P 0.30 108 P 6 MAI 02H -0.39 02H 02H 136 HOT 5803P 57 121 0.37 64 P 6 SAI 01H -0.11 01H 01H 136 HOT 5803P 59 121 0.48 86 P 6 SAI 01H -0.34 01H 01H 136 HOT 5803P 0.48 97 P 6 SAI 01H +0.62 01H 01H 136 HOT 5803P 0.30 94 P 6 SAI 02H +0.96 02H 02H 136 HOT 5803P 61 121 0.58 93 P 6 SAI 01H -0.61 01H 01H 136 HOT 5803P 103 121 0.45 109 P 6 SAI 02H +0.36 02H 02H 143 HOT 5803P 0.36 103 P 6 SAI 04H +0.79 04H 04H 143 HOT 5803P 6 122 0.17 96 P 6 SAI 01H +0.71 01H 01H 123 HOT 5803P 0.19 97 P 6 MAI 05H -0.23 05H 05H 123 HOT 5803P 12 122 0.34 108 P 6 SAI 01H +0.49 01H 01H 136 HOT 5803P 14 122 0.46 85 P 6 SAI 01H +0.78 01H 01H 136 HOT 5803P 0.17 59 P 6 SAI 01H -0.13 01H 01H 136 HOT 5803P 0.25 67 P 6 SAI 04H +0.78 04H 04H 136 HOT 5803P 16 122 0.54 81 P 6 SAI 07H -0.78 07H 07H 136 HOT 5803P 40 122 0.16 79 P 6 SAI 02H +0.92 02H 02H 136 HOT 5803P 48 122 0.25 91 P 6 SAI 01H -0.77 01H 01H 136 HOT 5803P
Framatome ANP Inc. 1/22/2005 14:30 Attachment 4 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G B Page 18 of 24 Tubes with Bobbin 40-100% TWD and +Point Vol. Circ and Ax:ial Indiccations ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL LEG PROBE 56 122 0.14 90 P6 SAI 02H +0.81 02H 02H 136 HOT 5803P 64 122 0.36 94 P6 SAI 01H -0.62 01H 01H 165 HOT 5803P 0.33 80 P6 MAI 02H +0.59 02H 02H 129 HOT 5803P 66 122 0.14 79 P6 SAI 01H -0.11 01H 01H 129 HOT 5803P 0.22 70 P6 SAI 01H +0.91 01H 01H 129 HOT 5803P 68 122 0.26 88 P6 SAI 01H -0.77 01H 01H 129 HOT 5803P 110 122 0.42 105 P6 MAI 02H -0.48 02H 02H 143 HOT 5803P 1 123 0.21 105 P6 SAI DCB +1.33 07H 07C 84 COLD 5601P 5 123 0.23 81 P6 SAI 06H +0.75 06H 06H 123 HOT 5803P 15 123 0.27 73 P6 SAI 04H +0.07 04H 04H 136 HOT 5803P 27 123 0.40 105 P6 SAI 03H +0.60 03H 03H 136 HOT 5803P 29 123 0.24 66 P6 SAI 04H +0.69 04H 04H 136 HOT 5803P 41 123 0.54 103 P6 SAI 01H +0.68 01H 01H 136 HOT 5803P 59 123 0.19 67 P6 SAI 02H -0.13 02H 02H 136 HOT 5803P 61 123 0.56 102 P6 SAI 01H +0.55 01H 01H 136 HOT 5803P 0.42 84 P6 SAI 05H +0.69 05H 05H 136 HOT 5803P 69 123 0.34 85 P6 SAI 01H -0.32 01H 01H 129 HOT 5803P 0.43 93 P6 SAI 01H +0.50 01H 01H 129 HOT 5803P 83 123 0.11 57 P6 MAI 02H +0.15 02H 02H 143 HOT 5803P 0.36 105 P6 SAI 03H +0.74 03H 03H 143 HOT 5803P 6 124 0.41 104 P6 SAI 01H -0.74 01H 01H 123 HOT 5803P 0.31 110 P6 SAI 01H -0.20 01H 01H 123 HOT 5803P 0.14 80 P6 SAI 01H +0.75 01H 01H 123 HOT 5803P 0.25 85 P6 SAI 03H -0.46 03H 03H 123 HOT 5803P 0.15 67 P6 SAI 03H +0.69 03H 03H 123 HOT 5803P 16 124 0.28 84 P6 SAI 04H +0.72 04H 04H 136 HOT 5803P 30 124 0.46 96 P6 SAI 05H +0.65 05H 05H 136 HOT 5803P 0.20 82 P6 SAI 05H -0.64 05H 05H 136 HOT 5803P 34 124 0.36 101 P6 MAI 02H +0.60 02H 02H 136 HOT 5803P 56 124 0.41 89 P6 MAI 01H +0.40 01H 01H 136 HOT 5803P 64 124 0.61 89 P6 MAI 01H +0.44 01H 01H 136 HOT 5803P 74 124 0.44 103 P6 SAI 01H -0.34 01H 01H 129 HOT 5803P 80 124 0.20 91 P6 SAI 01H +0.71 01H 01H 129 HOT 5803P 114 124 0.17 85 P6 SAI 02H -0.34 02H 02H 143 HOT 5803P 0.18 78 P6 SAI 02H +0.28 02H 02H 143 HOT 5803P 7 125 0.21 85 P6 SAI 01H -0.63 01H 01H 123 HOT 5803P 0.18 102 P6 SAI 01H +0.70 01H 01H 123 HOT 5803P 0.26 72 P6 SAI 02H +0.08 02H 02H 123 HOT 5803P 0.19 64 P6 SAI 02H +0.77 02H 02H 123 HOT 5803P 9 125 0.41 101 P6 MAI 03H -0.27 03H 03H 123 HOT 5803P 19 125 0.13 73 P6 SAI 01H +0.80 01H 01H 136 HOT 5803P 23 125 0.29 68 P6 SAI 02H +0.73 02H 02H 136 HOT 5803P 25 125 0.20 91 P6 SAI 03H +0.66 03H 03H 136 HOT 5803P 47 125 0.47 95 P6 SAI 01H +0.44 01H 01H 136 HOT 5803P 0.35 91 P6 SAI 01H -0.48 01H 01H 136 HOT 5803P 59 125 0.30 99 P6 SAI 01H +0.79 01H 01H 136 HOT 5803P 69 125 0.41 97 P6 MAI 01H -0.24 01H 01H 129 HOT 5803P 99 125 0.14 61 P6 SAI 02H -0.22 02H 02H 143 HOT 5803P 0.29 110 P6 SAI 02H +0.45 02H 02H 143 HOT 5803P 20 126 0.21 63 P6 SAI 02H +0.84 02H 02H 136 HOT 5803P 38 126 0.60 104 P6 SAI 03H -0.25 03H 03H 136 HOT 5803P 46 126 0.17 75 P6 SAI 01H +0.88 01H 01H 136 HOT 5803P 64 126 0.73 99 P6 SAI 02H +0.63 02H 02H 136 HOT 5803P 74 126 0.27 94 P6 SAI 01H -0.11 01H 01H 129 HOT 5803P
Framatome ANP Inc. 1/22/2005 14:30 Attachment 4 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: SIG B Page 19 of 24 Tubes with Bobbin 40-100% TWD and +Point Vol, Circ and Axial Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 0.22 107 P=6 SAI 01H +0.71 01H 01H 129 HOT 5803P 108 126 0.26 90 P 6 SAI 02H +0.80 02H 02H 143 HOT 5803P 7 127 0.54 100 P 6 SAI 01H +0.65 01H 01H 123 HOT 5803P 0.29 79 P 6 SAI 02H +0.37 02H 02H 123 HOT 5803P 0.80 102 P 6 SAI 03H -0.40 03H 03H 123 HOT 5803P 0.31 86 P 6 SAI 03H +0.84 03H 03H 123 HOT 5803P 0.26 96 P 6 SAI 07C +0.44 07C 07C 73 COLD 5803P 19 127 0.14 88 P 6 SAI 02H +0.62 02H 02H 136 HOT 5803P 25 127 0.21 90 P 6 SAI 02H +0.70 02H 02H 136 HOT 5803P 45 127 0.41 105 P 6 SAI 01H +0.83 01H 01H 136 HOT 5803P 0.18 71 P 6 SAI 01H -0.30 01H 01H 136 HOT 5803P 47 127 0.66 90 P 6 SAI 02H -0.49 02H 02H 136 HOT 5803P 57 127 0.23 84 P 6 SAI 01H -0.19 01H 01H 136 HOT 5803P 0.19 79 P 6 SAI 01H +0.82 01H 01H 136 HOT 5803P 61 127 0.42 92 P 6 SAI 01H -0.78 01H 01H 136 HOT 5803P 0.53 101 P 6 SAI 01H +0.55 01H 01H 136 HOT 5803P 0.34 80 P 6 SAI 02H +0.49 02H 02H 136 HOT 5803P 101 127 0.11 89 P 6 SAI 02H -0.71 02H 02H 143 HOT 5803P 107 127 0.19 66 P 6 SAI 02H +0.84 02H 02H 143 HOT 5803P 6 128 0.32 98 P 6 SAI 02H +0.44 02H 02H 123 HOT 5803P 0.39 96 P 6 SAI 03H -0.33 03H 03H 123 HOT 5803P 0.31 103 P 6 SAI 03H +0.42 03H 03H 123 HOT 5803P 0.32 78 P 6 SAI 05H -0.83 05H 05H 123 HOT 5803P 0.34 96 P 6 SAI 05H +0.49 05H 05H 123 HOT 5803P 16 128 0.31 98 P 6 SAI 03H -0.46 03H 03H 165 HOT 5803P 0.20 106 P 6 MAI 03H +0.80 03H 03H 165 HOT 5803P 24 128 0.19 76 P 6 SAI 02H +0.42 02H 02H 165 HOT 5803P 34 128 0.15 66 P 6 SAI 03H -0.68 03H 03H 165 HOT 5803P 0.47 99 P 6 SAI 03H +0.73 03H 03H 165 HOT 5803P 38 128 0.21 83 P 6 SAI 01H -0.44 01H 01H 165 HOT 5803P 58 128 0.19 75 P 6 SAI 01H -0.61 01H 01H 165 HOT 5803P 0.45 106 P 6 SAI 04H +0.64 04H 04H 165 HOT 5803P 84 128 0.35 103 P 6 SAI 02H +0.13 02H 02H 143 HOT 5803P 100 128 0.27 85 P 6 SAI 01H +0.48 01H 01H 143 HOT 5803P 5 129 0.18 45 P 6 SAI 03H -0.50 03H 03H 123 HOT 5803P 0.25 84 P 6 SAI 03H +0.81 03H 03H 123 HOT 5803P 0.11 68 P 6 SAI 04H +0.85 04H 04H 123 HOT 5803P 23 129 0.20 101 P 6 SAI 02H +0.82 02H 02H 165 HOT 5803P 35 129 0.41 79 P 6 SAI 02H +0.78 02H 02H 165 HOT 5803P 45 129 0.47 99 P 6 MAI 01H +0.34 01H 01H 165 HOT 5803P 53 129 0.36 84 P 6 MAI 01H -0.38 01H 01H 165 HOT 5803P 0.23 96 P 6 MAI 02H +0.01 02H 02H 165 HOT 5803P 61 129 0.71 92 P 6 SAI 01H -0.74 01H 01H 165 HOT 5803P 63 129 0.29 86 P 6 SAI 01H +0.83 01H 01H 165 HOT 5803P 75 129 0.32 106 P 6 SAI 01H +0.25 01H 01H 129 HOT 5803P 0.17 67 P 6 SAI 01H +0.97 01H 01H 129 HOT 5803P 87 129 0.21 118 P 6 SAI 02H +0.44 02H 02H 143 HOT 5803P 99 129 0.27 121 P 6 SAI 01H +0.48 01H 01H 143 HOT 5803P 10 130 0.23 96 P 6 SAI 01H +0.48 01H 01H 123 HOT 5803P 0.22 152 P 6 SAI 02H -0.60 02H 02H 123 HOT 5803P 16 130 0.25 78 P 6 SAI 04H -0.75 04H 04H 139 HOT 5803P 0.18 66 P 6 SAI 04H +0.64 04H 04H 139 HOT 5803P 0.34 89 P 6 SAI 05H +0.86 05H 05H 139 HOT 5803P 0.35 79 P 6 SAI 05H -0.51 05H 05H 139 HOT 5803P
Framatome ANP Inc. 1/22/2005 14:30 Attacbment 4 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G B Page 20 of 24 Tubes with Bobbin 40-100% TWD and +Point Vol. Circ and Axial Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 22 130 0.15 82 P 6 SAI O1H +0.81 01H 01H 139 HOT 5803P 40 130 0.14 62 P 6 SAI 02H +0.75 02H 02H 139 HOT 5803P 0.18 75 P 6 SAI 04H +0.48 04H 04H 139 HOT 5803P 44 130 0.76 81 P 6 SAI DHT +0.66 VS3 DHB 155 HOT 5602P 48 130 0.36 102 P 6 MAX 01H -0.18 01H 01H 139 HOT 5803P 0.35 109 P 6 MAI 02H +0.70 02H 02H 139 HOT 5803P 0.35 107 P 6 SAl 03H -0.70 03H 03H 139 HOT 5803P 0.32 98 P 6 SAX 04H +0.95 04H 04H 139 HOT 5803P 54 130 0.23 100 P 6 SAX 01H +0.30 01H 01H 139 HOT 5803P 0.25 105 P 6 SAX 01H -0.82 01H O1H 139 HOT 5803P 62 130 0.38 102 P 6 SAX 01H +0.60 01H O1H 139 HOT 5803P 0.25 96 P 6 SAX 01H +0.02 01H O1H 139 HOT 5803P 68 130 0.40 95 P 6 MAI 02H +0.60 02H 02H 139 'HOT 5803P 72 130 0.35 99 P 6 MAI 01H -0.32 01H 01H 129 HOT 5803P 3 131 0.26 79 P 6 SAX 03H +0.84 03H 03H 123 HOT 5803P 5 131 0.22 45 P 6 SAI 03H -0.40 03H 03H 123 HOT 5803P 0.13 56 P 6 SAI 03H +0.89 03H 03H 123 HOT 5803P 11 131 0.33 94 P 6 SAl 04H +0.43 04H 04H 139 HOT 5803P 13 131 0.17 257 P 6 SAI 02H +0.95 02H 02H 139 HOT 5803P 0.60 101 P 6 MAI 01H -0.69 01H 01H 165 HOT 5803P 53 131 0.66 98 P 6 SAl 01H +0.83 01H 01H 140 HOT 5803P 0.59 102 P 6 SAl 02H +0.82 02H 02H 140 HOT 5803P 57 131 0.18 115 P 6 SAl 01H +0.29 01H 01H 140 HOT 5803P 0.68 98 P 6 SAl 01H -0.77 O1H 01H 140 HOT 5803P 6 132 0.39 114 P 6 SAl 07C -0.32 07C DCT 73 COLD 5803P 0.22 98 P 6 SAl 07C +0.59 07C DCT 73 COLD 5803P 30 132 0.29 95 P 6 SAl 04H +1.00 04H 04H 139 HOT 5803P 0.63 280 P 6 SAX 05H +0.77 05H 05H 139 HOT 5803P 0.22 84 P 6 SAX 05H -0.58 05H 05H 139 HOT 5803P 34 132 0.22 72 P 6 SAX 02H +0.90 02H 02H 139 HOT 5803P 48 132 0.39 104 P 6 SAl 01H -0.62 O1H 01H 140 HOT 5803P 0.45 93 P 6 SAI 01H +0.62 O1H O1H 140 HOT 5803P 58 132 0.29 75 P 6 SAI O1H -0.45 01H 01H 140 HOT 5803P 0.45 91 P 6 SAX 02H -0.24 02H 02H 140 HOT 5803P 7 133 0.43 92 P6 SAX 06H -0.20 06H 06H 123 HOT 5803P 0.66 96 P 6 SAl 06H +0.66 06H 06H 123 HOT 5803P 23 133 0.14 51 P 6 SAl 02H +0.90 02H 02H 139 HOT 5803P 51 133 0.15 85 P 6 SAX O1H -0.81 01H 01H 140 HOT 5803P 63 133 0.18 114 P 6 SAX O1H +0.30 O1H O1H 171 HOT 5803P 67 133 0.29 112 P 6 SAX 01H +0.36 01H O1H 140 HOT 5803P 95 133 0.14 54 P6 SAl 02H +0.39 02H 02H 143 HOT 5803P 6 134 0.18 99 P6 SAX 01H +0.83 01H 01H 123 HOT 5803P 0.30 91 P 6 SAl 03H -0.60 03H 03H 123 HOT 5803P 0.13 68 P 6 SAX 03H +0.86 03H 03H 123 HOT 5803P 0.29 78 P 6 MAI 05H +0.08 05H 05H 123 HOT 5803P 10 134 0.29 67 P 6 SAl 03H -0.18 03H 03H 123 HOT 5803P 12 134 0.23 68 P 6 SAl 01H +1.01 01H 01H 139 HOT 5803P 30 134 0.34 93 P 6 SAl 02H +0.32 02H 02H 139 HOT 5803P 0.33 80 P 6 MAI 03H +0.52 03H 03H 139 HOT 5803P 32 134 0.19 39 P6 SAI 03H +0.42 03H 03H 139 HOT 5803P 50 134 0.36 100 P 6 SAX 03H -0.30 03H 03H 140 HOT 5803P 15 135 0.17 62 P 6 SAI 03H -0.16 03H 03H 139 HOT 5803P 61 135 0.21 45 P 6 SAl 02H -0.56 02H 02H 140 HOT 5803P 0.26 89 P 6 SAl 02H +0.91 02H 02H 140 HOT 5803P
Framatome ANP Inc. 1/22/2005 14:30 Attachment 4 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G B Page 21 of 24 Tubes with Bobbin 40-100% TWD and +Point Vol. Circ and Axial Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE
=== === === ======
69 135 0.30 86 P 6 SAI 02H +0.93 02H 02H 140 HOT 5803P 50 136 0.20 79 P 6 SAI 02H +0.62 02H 02H 140 HOT 5803P 82 136 0.27 78 P 6 SAI 02H +0.55 02H 02H 143 HOT 5803P 7 137 0.20 86 P 6 SAI 01H +0.75 01H 01H 123 HOT 5803P 0.32 72 P 6 SAI 02H +0.89 02H 02H 123 HOT 5803P 0.32 86 P 6 SAI 03H -0.38 03H 03H 123 HOT 5803P 0.37 97 P 6 SAI 03H +0.74 03H 03H 123 HOT 5803P 9 137 0.57 92 P 6 SAI 02H +0.62 02H 02H 123 HOT 5803P 13 137 0.27 67 P 6 SAI 07H +0.27 07H 07H 139 HOT 5803P 87 137 0.18 90 P 6 SAI 01H -0.61 01H 01H 143 HOT 5803P 2 138 0.23 100 P 6 SAI 06H +0.81 06H 06H 123 HOT 5803P 12 138 0.26 72 P 6 SAI 02H +0.93 02H 02H 139 HOT 5803P 52 138 0.25 72 P 6 SAI 01H -0.85 01H 01H 140 HOT 5803P 0.15 93 P 6 SAI 01H +0.58 01H 01H 140 HOT 5803P 94 138 0.16 81 P 6 SAI 01H +0.69 01H 01H 143 HOT 5803P 5 139 0.17 81 P 6 SAI 05H +0.75 05H 05H 123 HOT 5803P 11 139 0.16 52 P 6 SAI 02H +0.86 02H 02H 139 HOT 5803P 0.38 101 P 6 MAI 03H -0.22 03H 03H 139 HOT 5803P 0.16 66 P 6 SAT 04H +0.76 04H 04H 139 HOT 5803P 21 139 0.15 48 P 6 SAI 04H +0.39 04H 04H 139 HOT 5803P 0.34 90 P 6 MAI 05H -0.30 05H 05H 139 HOT 5803P 43 139 0.34 99 P 6 SAI 02H +0.72 02H 02H 140 HOT 5803P 10 140 0.13 55 P 6 SAI 02H +0.75 02H 02H 123 HOT 5803P 12 140 0.28 97 P 6 SAI 02H +0.26 02H 02H 139 HOT 5803P 0.28 120 P 6 SAI 02H -0.62 02H 02H 139 HOT 5803P 40 140 0.16 31 P 6 MAI 02H -0.59 02H 02H 171 HOT 5803P 42 140 0.19 87 P 6 SAI 02H +0.79 02H 02H 139 HOT 5803P 74 140 0.36 94 P 6 SAI 02H +0.79 02H 02H 140 HOT 5803P 13 141 0.25 87 P 6 SAI 03H +0.66 03H 03H 139 HOT 5803P 15 141 0.22 90 P 6 SAI 07H +0.66 DCB 07H 158 HOT 5602P 0.26 54 P 6 SAI 03H +0.88 03H 03H 139 HOT 5803P 23 141 0.17 75 P 6 SAI 02H -0.05 02H 02H 139 HOT 5803P 25 141 0.29 76 P 6 MAI 02H +0.46 02H 02H 139 HOT 5803P 0.14 61 P 6 SAI 02H -0.45 02H 02H 139 HOT 5803P 35 141 0.37 79 P 6 SAI 02H +0.86 02H 02H 139 HOT 5803P 45 141 0.15 53 P 6 SAI 02H +0.72 02H 02H 119 HOT 5803P 47 141 0.23 71 P 6 SAI 02H +0.98 02H 02H 140 HOT 5803P 61 141 0.28 91 P 6 SAI 02H -0.10 02H 02H 140 HOT 5803P 63 141 0.20 105 P 6 SAI 01H +0.85 01H 01H 140 HOT 5803P 10 142 0.23 66 P 6 SAI 04H -0.21 04H 04H 123 HOT 5803P 12 142 0.22 101 P 6 SAI 02H +0.94 02H 02H 139 HOT 5803P 0.20 149 P 6 SAI 02H -0.33 02H 02H 139 HOT 5803P 16 142 0.50 104 P 6 SAI 02H +0.77 02H 02H 139 HOT 5803P 28 142 0.23 60 P 6 SAI 03H +0.82 03H 03H 139 HOT 5803P 0.19 74 P 6 SAI 04H +0.89 04H 04H 139 HOT 5803P 30 142 0.18 57 P 6 MAI 02H -0.52 02H 02H 139 HOT 5803P 0.12 83 P 6 SAI 02H +0.48 02H 02H 139 HOT 5803P 0.41 97 P 6 SAI 03H +0.87 03H 03H 139 HOT 5803P 0.34 103 P 6 MAI 03H -0.42 03H 03H 139 HOT 5803P 0.57 98 P 6 SAI 04H +0.53 04H 04H 139 HOT 5803P 34 142 0.18 49 P 6 MAI 02H -0.47 02H 02H 139 HOT 5803P 48 142 0.26 86 P 6 SAI 01H -0.85 01H 01H 140 HOT 5803P 66 142 0.23 50 P 6 SAI 02H -0.62 02H 02H 140 HOT 5803P 13 143 0.24 101 P 6 SAI 03H +1.00 03H 03H 139 HOT 5803P
Framatome ANP Inc. 1/22/2005 14:30 Attacmoent 4 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G B Page 22 of 24 Tubes with Bobbin 40-100% TWD and +Point Vol, Circ and Axial Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL LEG PROBE 15 143 0.25 63 P 6 SAI 02H +0.87 02H 02H 139 HOT 5803P 47 143 0.31 91 P 6 SAI 02H -0.28 02H 02H 140 HOT 5803P 0.15 50 P 6 SAI 03H -0.27 03H 03H 140 HOT 5803P 0.27 76 P 6 SAI 05H +0.70 05H 05H 140 HOT 5803P 49 143 0.22 88 P 6 SAI 02H +0.09 02H 02H 140 HOT 5803P 0.15 87 P 6 SAI 03H -0.60 03H 03H 140 HOT 5803P 4 144 0.28 97 P 6 SAI 03H +0.66 03H 03H 126 HOT 5803P 10 144 0.17 81 P 6 SAI 02H +0.78 02H 02H 126 HOT 5803P 12 144 0.48 103 P 6 SAI 02H +0.02 02H 02H 139 HOT 5803P 0.21 71 P 6 SAI 02H -0.83 02H 02H 139 HOT 5803P 20 144 0.21 114 P 6 SAI 03H -0.24 03H 03H 139 HOT 5803P 0.18 84 P 6 SAI 03H +0.91 03H 03H 139 HOT 5803P 22 144 0.49 96 P 6 SAI 03H +0.84 03H 03H 139 HOT 5803P 0.29 85 P 6 SAI 04H +0.85 04H 04H 139 HOT 5803P 0.37 109 P 6 SAI 05H -0.20 05H 05H 139 HOT 5803P 0.15 76 P 6 SAI 05H +0.48 05H 05H 139 HOT 5803P 42 144 0.13 75 P 6 SAI 02H +0.79 02H 02H 139 HOT 5803P 50 144 0.36 85 P 6 SAI 02H -0.33 02H 02H 140 HOT 5803P 60 144 0.13 74 P 6 SAI 03H -0.39 03H 03H 140 HOT 5803P 62 144 0.21 49 P 6 SAI 02H +0.58 02H 02H 140 HOT 5803P 7 145 0.26 99 P 6 SAI 07C +0.91 07C 07C 158 HOT 5602P 47 145 0.38 101 P 6 SAr 02H +0.76 02H 02H 139 HOT 5803P 0.12 84 P 6 SAI 02H -0.18 02H 02H 139 HOT 5803P 69 145 0.27 93 P 6 SAI 04H -0.29 04H 04H 140 HOT 5803P 75 145 0.17 86 P 6 SAI 02H +0.46 02H 02H 139 HOT 5803P 12 146 0.31 78 P 6 SAI 05H +0.93 05H 05H 139 HOT 5803P 16 146 0.43 111 P 6 SAI 02H +0.95 02H 02H 139 HOT 5803P 0.41 107 P 6 SAI 04H +0.81 04H 04H 139 HOT 5803P 7 147 0.39 104 P 6 SAI 02H -0.77 02H 02H 126 HOT 5803P 0.44 109 P 6 MAI 05H +0.73 05H 05H 126 HOT 5803P 0.54 103 P 6 SAI 07C +0.36 07C 07C 74 COLD 5803P 9 147 0.15 90 P 6 SAI 04H +0.70 04H 04H 126 HOT 5803P 49 147 0.12 90 P 6 SAI 01H +0.54 01H 01H 139 HOT 5803P 0.23 73 P 6 MAI 02H +0.94 02H 02H 139 HOT 5803P 6 148 0.27 101 P 6 SAI 02H +0.61 02H 02H 126 HOT 5803P 0.40 86 P 6 SAI 03H +0.37 03H 03H 126 HOT 5803P 0.16 91 P 6 SAI 03H -0.23 03H 03H 126 HOT 5803P 0.47 279 P 6 SAI 06H +0.37 06H 06H 126 HOT 5803P 50 148 0.36 93 P 6 SAI 02H +0.91 02H 02H 139 HOT 5803P 62 148 0.38 93 P 6 SAI 02H +0.73 02H 02H 140 HOT 5803P 64 148 0.19 56 P 6 SAI 02H +0.57 02H 02H 140 HOT 5803P 82 148 0.40 112 P 6 SAI 01H +0.83 01H 01H 143 HOT 5803P 5 149 0.54 102 P 6 MAI 03H +0.33 03H 03H 126 HOT 5803P 21 149 0.34 280 P 6 SAI 02H -0.48 02H 02H 139 HOT 5803P 41 149 0.42 101 P 6 SAI 03H +0.60 03H 03H 139 HOT 5803P 43 149 0.18 91 P 6 SAI 02H +0.93 02H 02H 139 HOT 5803P 2 150 0.46 94 P 6 MAI 05H +0.74 05H 05H 126 HOT 5803P 0.26 116 P 6 SAI 07H +0.28 07H DHT 126 HOT 5803P 8 150 0.34 81 P 6 SAI 05H -0.41 05H 05H 126 HOT 5803P 12 150 0.38 98 P 6 SAI 05H -0.45 05H 05H 139 HOT 5803P 14 150 0.22 92 P 6 SAI 02H -0.26 02H 02H 139 HOT 5803P 18 150 0.31 83 P 6 SAI 02H +0.79 02H 02H 139 HOT 5803P 0.12 92 P 6 SAI 03H +0.91 03H 03H 139 HOT 5803P 0.24 100 P 6 SAI 03H -0.21 03H 03H 139 HOT 5803P
Framatome ANP Inc. 1/22/2005 14:30 Attacbment 4 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G B Page 23 of 24 Tubes with Bobbin 40-100% TWD and +Point Vol. Circ and Axial Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 32 150 0.29 83 P 6 SAI 03H -0.51 03H 03H 139 HOT 5803P 0.19 79 P 6 SAI 03H +0.60 03H 03H 139 HOT 5803P 0.46 105 P 6 SAI 05H -0.57 05H 05H 139 HOT 5803P 52 150 0.14 67 P 6 SAI 02H +0.49 02H 02H 139 HOT 5803P 0.24 77 P 6 SAI 04H +0.66 04H 04H 139 HOT 5803P 56 150 0.32 98 P 6 SAI 02H +0.51 02H 02H 139 HOT 5803P 82 150 0.19 105 P 6 MAI 03H +0.68 03H 03H 143 HOT 5803P 5 151 0.25 276 P 6 MAI 02H +0.84 02H 02H 126 HOT 5803P 0.17 78 P 6 SAI 03H -0.67 03H 03H 126 HOT 5803P 7 151 0.65 93 P 6 SAI 02H +0.65 02H 02H 126 HOT 5803P 0.42 105 P 6 MAI 03H +0.34 03H 03H 126 HOT 5803P 0.26 108 P 6 SAI 04H -0.33 04H 04H 126 HOT 5803P 15 151 0.31 83 P 6 SAI 04H +0.73 04H 04H 139 HOT 5803P 0.18 80 P 6 SAI 05H +0.86 05H 05H 139 HOT 5803P 31 151 0.31 108 P 6 SAI 03H +0.63 03H 03H 139 HOT 5803P 49 151 0.16 76 P 6 SAI 04H +0.69 04H 04H 139 HOT 5803P 8 152 0.18 98 P 6 SAI 02H +0.05 02H 02H 126 HOT 5803P 0.11 76 P 6 SAI 02H -0.85 02H 02H 126 HOT 5803P 0.50 108 P 6 SAI 03H +0.03 03H 03H HOT 126 5803P 0.50 106 P 6 SAI 05H +0.06 05H 05H 126 HOT 5803P 28 152 0.49 83 P 6 SAI 03H +0.58 03H 03H 139 HOT 5803P 38 152 0.12 63 P 6 SAI 03H -0.51 03H 03H 119 HOT 5803P 9 153 0.41 94 P 6 SAI 02H +0.03 02H 02H 126 HOT 5803P 0.31 117 P 6 SAI 04H -0.94 04H 04H 126 HOT 5803P 23 153 0.31 110 P 6 MAI 02H +0.66 02H 02H 134 HOT 5803P 47 153 0.39 108 P 6 SAI 04H -0.18 04H 04H 139 HOT 5803P 0.24 88 P 6 SAT 04H +0.55 04H 04H 139 HOT 5803P 59 153 0.23 101 P 6 SAI 02H +0.71 02H 02H 139 HOT 5803P 0.17 92 P 6 SAI 04H +0.54 04H 04H 139 HOT 5803P 10 154 0.34 94 P 6 SAI 02H -0.61 02H 02H 126 HOT 5803P 0.45 102 P 6 MAI 03H +0.36 03H 03H 126 HOT 5803P 12 154 0.27 102 P 6 SAI 02H -0.31 02H 02H 134 HOT 5803P 0.22 67 P 6 SAI 02H +0.65 02H 02H 134 HOT 5803P 32 154 0.19 109 P 6 SAI 02H -0.26 02H 02H 134 HOT 5803P 0.22 100 P 6 SAI 02H +0.84 02H 02H 134 HOT 5803P 34 154 0.24 83 P 6 MAI 02H -0.75 02H 02H 134 HOT 5803P 52 154 0.45 109 P 6 SAI 02H +0.78 02H 02H 134 HOT 5803P 5 155 0.30 89 P 6 SAI 02H +0.80 02H 02H 126 HOT 5803P 7 155 0.28 92 P 6 MAI 02H +0.41 02H 02H 126 HOT 5803P 0.27 97 P 6 MAI 03H +0.48 03H 03H 126 HOT 5803P 0.45 89 P 6 SAI 04H +0.39 04H 04H 126 HOT 5803P 0.57 104 P 6 SAI 05H +0.43 05H 05H 126 HOT 5803P 13 155 0.40 97 P 6 MAI 03H -0.53 03H 03H 134 HOT 5803P 19 155 0.49 113 P 6 MAI 02H -0.43 02H 02H 134 HOT 5803P 21 155 0.26 97 P 6 MAI 02H +0.76 02H 02H 134 HOT 5803P 41 155 0.75 99 P 6 MAI 02H +0.34 02H 02H 165 HOT 5803P 0.21 77 P 6 MAI 04H +0.51 04H 04H 134 HOT 5803P 43 155 0.18 71 P 6 MAI 02H -0.81 02H 02H 134 HOT 5803P 47 155 0.18 73 P 6 SAI TSH +4.91 TSH TSH 134 HOT 5803P 49 155 0.31 107 P 6 MAI 02H +0.52 02H 02H 134 HOT 5803P 0.14 77 P 6 SAI 02H -0.52 02H 02H 134 HOT 5803P 0.15 63 P 6 SAI 04H +0.37 04H 04H 134 HOT 5803P 4 156 0.44 94 P 6 SAI 05H +0.44 05H 05H 126 HOT 5803P 0.17 78 P 6 SAI 05H -0.32 05H 05H 126 HOT 5803P
Framatome ANP Inc. 1/22/2005 14:30 Attachment 4 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G B Page 24 of 24 Tubes with Bobbin 40-100% TWD and +Point Vol. Circ and Axial Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 0.30 108 P6 SAI 07H -0.43 07H DHT 126 HOT 5803P 16 156 0.29 86 P6 MAI 02H -0.49 02H 02H 134 HOT 5803P 28 156 0.48 88 P6 MAI 02H +0.73 02H 02H 134 HOT 5803P 52 156 0.20 106 P6 SAI 03H +0.89 03H 03H 134 HOT 5803P 7 157 0.56 93 P6 MAI 02H +0.53 02H 02H 126 HOT 5803P 0.36 118 P6 SAI 03H -0.79 03H 03H 126 HOT 5803P 0.19 64 P6 SAI 03H +0.51 03H 03H 126 HOT 5803P 0.56 99 P6 SAI 04H +0.59 04H 04H 126 HOT 5803P 0.46 98 P6 SAI 05H -0.77 05H 05H 126 HOT 5803P 8 158 0.17 86 P6 SAI 03H -0.80 03H 03H 126 HOT 5803P 0.23 96 P6 SAI 04H +0.86 04H 04H 126 HOT 5803P 12 158 0.26 53 P6 SAI 02H -0.38 02H 02H 134 HOT 5803P 0.42 78 P6 SAI 02H +0.73 02H 02H 134 HOT 5803P 28 158 0.41 75 P6 SAI 02H +0.26 02H 02H 134 HOT 5803P 7 159 0.33 112 P6 SAI 03H +0.84 03H 03H 126 HOT 5803P 0.23 69 P6 MM 04H -0.48 04H 04H 126 HOT 5803P 0.18 80 P6 SAI 06H +0.85 06H 06H 126 HOT 5803P 9 159 0.26 118 P6 SAI 03H -0.36 03H 03H 126 HOT 5803P 11 159 0.74 94 P6 MAI 02H +0.30 02H 02H 134 HOT 5803P 0.14 78 P6 SAI 03H +0.32 03H 03H 134 HOT 5803P 0.30 106 P6 SAI 03H +0.87 03H 03H 134 HOT 5803P 0.85 101 P6 SAI 04H -0.01 04H 04H 134 HOT 5803P 0.10 59 P6 SAI 05H +0.51 05H 05H 134 HOT 5803P 0.11 77 P6 SAI 05H -0.68 05H 05H 134 HOT 5803P 43 159 0.25 84 P6 MAI 02H -0.66 02H 02H 134 HOT 5803P 12 160 0.24 92 P6 SAI 02H -0.21 02H 02H 134 HOT 5803P 0.32 111 P6 SAI 02H +0.85 02H 02H 134 HOT 5803P 30 160 0.27 77 P6 SAI 02H +0.28 02H 02H 134 HOT 5803P 34 160 0.65 105 P6 SAI 02H -0.50 02H 02H 134 HOT 5803P 0.43 93 P6 SAI 02H +0.43 02H 02H 134 HOT 5803P 1 161 0.20 61 P6 SAI 07C +0.32 07H 07C 84 COLD 5601P 0.52 101 P6 MAI 03H +0.69 03H 03H 126 HOT 5803P 0.20 114 P6 SAI 04H -0.88 04H 04H 126 HOT 5803P 5 161 0.37 114 P6 SAI 02H -0.42 02H 02H 126 HOT 5803P 7 161 0.26 90 P6 SAI 02H +0.32 02H 02H 126 HOT 5803P 0.24 92 P6 SAI 02H +0.78 02H 02H 126 HOT 5803P 0.42 103 P6 SAI 03H -0.69 03H 03H 126 HOT 5803P 0.22 84 P6 SAI 05H -0.39 05H 05H 126 HOT 5803P 9 161 0.29 101 P6 SAI 03H +0.68 03H 03H 126 HOT 5803P 15 161 0.48 103 P6 MAI 02H +0.28 02H 02H 134 HOT 5803P 17 161 0.16 100 P6 SAI 02H -0.81 02H 02H 134 HOT 5803P 0.25 75 P6 SAI 02H +0.23 02H 02H 134 HOT 5803P 0.14 84 P6 SAI 04H -0.83 04H 04H 134 HOT 5803P 43 161 0.85 105 P6 SAI 02H +0.29 02H 02H 134 HOT 5803P 12 162 0.20 81 P6 SAI 04H +0.26 04H 04H 134 HOT 5803P 24 162 0.17 97 P6 SAI 02H +0.24 02H 02H 134 HOT 5803P 16 164 0.30 98 P6 SAI 02H +0.76 02H 02H 134 HOT 5803P 7 165 0.25 81 P6 SAI 03H -0.24 03H 03H 126 HOT 5803P 9 165 0.10 71 P6 SAI 03H +0.85 03H 03H 126 HOT 5803P Total Tubes : 835 Total Records: 1291
Framatome ANP Inc. 1/22/2005 14:30 Attacbment 5 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G B Page 1 of 4 Tubes with Bobbin 20-39% TWD Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 37 5 0.31 74 P 2 TWD 23 02H +0.80 TEC TEH 10 HOT 60 OUL 52 8 0.36 146 P 2 TWD 25 01C -0.98 TEC TEH 10 HOT 60OUL 47 21 0.29 124 P 2 TWD 23 VS3 -0.70 TEC TEN 17 HOT 600UL 48 22 0.24 43 P 2 TWD 21 VS3 +0.74 TEC TEH 17 HOT 600UL 54 22 0.38 98 P 2 TWD 26 VS3 -0.66 TEC TEH 18 HOT 60OUL 87 23 0.43 111 P 2 TWD 21 VS2 +0.83 TEH TEC 48 COLD 60OUL 96 24 0.36 146 P 2 TWD 21 07H -0.22 TEH TEC 50 COLD 600UL 0.58 60 P 2 TWD 27 08H -0.92 TEH TEC 50 COLD 600UL 0.36 107 P 2 TWD 20 VS4 +0.79 TEH TEC 50 COLD 60OUL 0.48 128 P 2 TWD 24 DCB +0.00 TEH TEC 50 COLD 60OUL 45 25 0.35 67 P 2 TWD 25 VS3 -0.88 TEC TEH 17 HOT 60OUL 96 26 0.49 33 P 2 TWD 25 VS4 +0.16 TEH TEC 50 COLD 60OUL 0.34 29 P 2 TWD 20 DHT +0.00 TEH TEC 50 COLD 60OUL 99 27 0.43 143 P 2 TWD 22 08H -0.26 TEH TEC 49 COLD 60OUL 101 27 0.68 115 P 2 TWD 29 DCT +0.00 TEH TEC 50 COLD 60OUL 100 28 0.81 114 P 2 TWD 31 DCT +0.00 TEH TEC 50 COLD 60OUL 95 29 0.50 78 P 2 TWD 25 DCT +0.00 TEH TEC 50 COLD 60OUL 43 33 0.26 100 P 2 TWD 20 VS3 +0.93 TEC TEH 25 HOT 60OUL 64 34 0.46 63 P 2 TWD 29 VS4 -0.24 TEC TEH 24 HOT 600UL 96 34 0.92 109 P 2 TWD 32 VS2 -0.41 TEH TEC 49 COLD 600UL 50 36 0.30 99 P 2 TWD 21 VS3 +0.76 TEC TEH 25 HOT 600UL 95 41 0.38 114 P 2 TWD 20 VS2 +0.97 TEH TEC 52 COLD 60OUL 97 41 0.87 102 P 2 TWD 31 VS2 +0.63 TEH TEC 51 COLD 60OUL 0.70 121 P 2 TWD 28 VS4 +0.55 TEH TEC 51 COLD 60OUL 43 47 0.50 126 P 2 TWD 26 VS3 -0.78 TEH TEC 4 COLD 60OUL 126 48 0.50 48 P 2 TWD 23 DHT +0.25 TEH TEC 52 COLD 600UL 93 49 0.39 101 P 2 TWD 24 VS2 -0.87 TEH TEC 54 COLD 600UL 68 50 0.48 122 P 2 TWD 22 VS3 -1.02 TEH TEC 7 COLD 60OUL 57 51 0.95 83 P 2 TWD 32 VS3 -0.80 TEH TEC 7 COLD 60OUL 41 55 0.36 61 P 2 TWD 20 VS3 +0.95 TEH TEC 14 COLD 60OUL 131 55 0.73 115 P 2 TWD 26 DCB +0.00 TEH TEC 58 COLD 600UL 130 58 0.48 107 P 2 TWD 23 DCT +0.00 TEH TEC 55 COLD 60OUL 132 58 0.69 71 P 2 TWD 25 VS1 -0.80 TEH TEC 58 COLD 60OUL 0.50 106 P 2 TWD 21 DCB +0.21 TEH TEC 58 COLD 60OUL 49 59 0.46 140 P 2 TWD 22 VS3 -0.89 TEH TEC 12 COLD 60OUL 131 59 0.81 64 P 2 TWD 28 DCT +0.00 TEH TEC 57 COLD 600UL 133 59 0.50 70 P 2 TWD 21 DCB +0.00 TEH TEC 58 COLD 60OUL 134 60 0.58 91 P 2 TWD 23 DHB +0.76 TEH TEC 58 COLD 60OUL 43 61 0.52 86 P 2 TWD 25 VS3 +0.67 TEH TEC 13 COLD 60OUL 135 63 0.52 69 P 2 TWD 21 DHT +0.00 TEH TEC 58 COLD 60OUL 39 65 0.38 25 P 2 TWD 20 VS3 -1.01 TEH TEC 10 COLD 60OUL 137 67 1.01 119 P 2 TWD 31 DHT -0.06 TEH TEC 58 COLD 60OUL 34 68 0.41 36 P 2 TWD 21 DHB +0.00 TEH TEC 10 COLD 600UL 1.18 98 P 2 TWD 35 DCB +0.16 TEH TEC 10 COLD 60OUL 0.80 112 P 2 TWD 30 DCT -0.08 TEH TEC 10 COLD 600UL 36 68 0.52 53 P 2 TWD 26 VS3 +0.57 TEH TEC 11 COLD 60OUL 39 69 0.62 121 P 2 TWD 27 VS3 +0.51 TEC TEH 12 HOT 60OUL 0.61 148 P 2 TWD 27 DHT +0.00 TEC TEH 12 HOT 60OUL 41 69 0.36 156 P 2 TWD 20 07C -0.89 TEC TEH 11 HOT 60OUL 36 70 0.82 130 P 2 TWD 30 DCB +0.00 TEC TEH 12 HOT 60OUL 0.43 146 P 2 TWD 22 DHB +0.00 TEC TEH 12 HOT 600UL 46 70 0.82 141 P 2 TWD 30 VS3 +0.84 TEC TEH 12 HOT 60OUL 48 70 0.46 91 P 2 TWD 24 VS3 +0.68 TEC TEH 11 HOT 600UL 35 71 0.72 113 P 2 TWD 29 DCB +0.00 TEC TEH 12 HOT 60OUL
Framatome ANP Inc. 1J22/2005 14:30 Attacbment 5 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G B Page 2 of 4 Tubes with Bobbin 20-39% TWD Indications ROW LINE VOLTS DEG CNN IND %TW LOCATION EXT EXT CAL # LEG PROBE 0.51 52 P2 TWD 24 D=T +0.00 TEC TEH 12 HOT 60_OUL 37 71 0.83 84 P2 TWD 30 DHT +0.00 TEC TEH 11 HOT 60OUL 45 71 0.69 82 P2 TWD 28 DCT +0.00 TEC TEH 11 HOT 60OUL 0.49 145 P2 TWD 24 VS3 -0.77 TEC TEH 11 HOT 600UL 97 71 0.62 55 P2 TWD 28 VS4 +0.64 TEH TEC 42 COLD 60OUL 48 72 0.48 91 P2 TWD 24 VS3 -0.74 TEC TEH 11 HOT 60OUL 43 75 0.43 75 P2 TWD 22 DCB +0.34 TEC TEH 12 HOT 600UL 45 75 0.42 114 P2 TWD 22 DCB +0.00 TEC TEH 11 HOT 60OUL 44 76 1.12 94 P2 TWD 34 DHB +0.00 TEC TEH 12 HOT 60OUL 46 76 0.38 70 P2 TWD 21 DHB +0.00 TEC TEH 11 HOT 60OUL 52 76 0.67 78 P2 TWD 28 VS3 +0.75 TEC TEH 12 HOT 60OUL 54 76 0.49 152 P2 TWD 24 VS3 -0.81 TEC TEH 11 HOT 600UL 0.45 141 P2 TWD 23 VS3 +0.77 TEC TEH 11 HOT 600UL 56 76 0.88 103 P2 TWD 32 VS3 +0.68 TEC TEH 12 HOT 60OUL 0.46 145 P2 TWD 23 VS3 -0.81 TEC TEH 12 HOT 60OUL 55 77 1.02 148 P2 TWD 31 DCB +0.00 TEC TEH 5 HOT 60OUL 107 77 0.33 26 P2 TWD 22 04H -0.42 TEH TEC 39 COLD 60OUL 52 78 0.58 127 P2 TWD 25 DCT +0.00 TEC TEH 6 HOT 600UL 0.39 139 P2 TWD 21 DCB +0.00 TEC TEH 6 HOT 60OUL 1.46 144 P2 TWD 29 VS3 +0.85 TEC TEH 6 HOT 60OUL 54 78 0.76 132 P2 TWD 28 DCB +0.00 TEC TEH 5 HOT 60OUL 0.76 84 P2 TWD 28 DHB +0.00 TEC TEH 5 HOT 600UL 88 78 0.64 34 P2 TWD 25 VS2 +0.76 TEH TEC 44 COLD 60OUL 96 78 0.40 43 P2 TWD 25 VS4 +0.74 TEH TEC 39 COLD 60OUL 0.78 87 P2 TWD 33 VS2 -0.76 TEH TEC 39 COLD 60OUL 0.33 31 P2 TWD 22 VS3 +0.36 TEH TEC 39 COLD 60OUL 51 79 0.51 94 P2 TWD 23 DCB +0.00 TEC TEH 5 NOT 60OUL 0.56 150 P2 TWD 24 DHT +0.00 TEC TEH 5 HOT 600UL 50 80 0.37 138 P2 TWD 20 DCT +0.00 TEC TEH 6 HOT 60OUL 0.74 108 P2 TWD 29 DHB +0.00 TEC TEH 6 HOT 60OUL 52 80 0.44 88 P2 TWD 21 DCT +0.00 TEC TEH 5 HOT 600UL 0.64 145 P2 TWD 26 VS3 +0.92 TEC TEH 5 HOT 60OUL 0.47 126 P2 TWD 22 VS3 -0.63 TEC TEH 5 HOT 60OUL 1.47 100 P2 TWD 35 DHB +0.00 TEC TEN 5 HOT 60OUL 60 80 0.45 87 P2 TWD 22 DCB +0.00 TEC TEH 5 HOT 60OUL 51 81 0.63 129 P2 TWD 27 DCB +0.00 TEC TEH 6 HOT 600UL 53 81 1.25 26 P2 TWD 33 DHT +0.00 TEC TEH 5 HOT 600UL 48 82 0.68 37 P2 TWD 27 DHT +0.00 TEC TEH 5 HOT 60OUL 50 82 0.42 74 P2 TWD 21 DCB +0.00 TEC TEH 6 HOT 60OUL 98 82 0.44 22 P2 TWD 26 VS3 +0.91 TEH TEC 39 COLD 60OUL 51 83 0.78 100 P2 TWD 29 DCT +0.00 TEC TEH 6 HOT 60OUL 87 83 0.35 104 P2 TWD 23 VS3 -0.93 TEH TEC 39 COLD 60OUL 89 83 1.75 112 P2 TWD 32 VS3 -0.87 TEH TEC 41 COLD 60OUL 48 84 1.69 110 P2 TWD 36 DHB +0.00 TEC TEH 5 HOT 60OUL TWD 1.08 103 P2 32 DCT +0.00 TEC TEH 5 HOT 60OUL TWID 50 84 1.02 118 P2 33 DCT +0.00 TEC TEH 6 NOT 60OUL TWD 52 84 1.88 111 P2 37 DCT -0.25 TEC TEH 5 HOT 60OUL TWD 57 85 0.57 125 P2 25 DCB +0.00 TEC TEH 5 HOT 60OUL TWD 54 86 0.42 43 P2 21 DCT +0.00 TEC TEH 5 HOT 60OUL TWD 88 86 0.58 64 P2 27 VS3 +0.74 TEH TEC 38 COLD 60OUL TWD 53 87 0.42 98 P2 23 DCB +0.00 TEC TEH 3 HOT 60OUL TWD 55 87 1.20 93 P2 34 DCT +0.00 TEC TEH 4 HOT 60OUL TWD 52 88 0.87 108 P2 30 VS3 +0.89 TEC TEH 4 HOT 60OUL TWD 0.52 79 P2 24 DCB +0.39 TEC TEH 4 HOT 60OUL
Framatome ANP Inc. 1/22/2005 14:30 Attacbment 5 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G B Page 3 of 4 Tubes with Bobbin 20-39% TWD Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 54 88 0.48 88 P2 TWD 22 VS3 +0.90 TEC TEN 3 HOT 60=OUL 62 88 0.42 92 P2 TWD 21 VS3 -0.77 TEC TEH 4 HOT 60OUL TWD 51 89 0.73 117 P2 28 DHB +0.00 TEC TEH 4 HOT 60OUL TWD 54 90 0.43 63 P2 21 DCB +0.00 TEC TEH 4 HOT 60OUL TWD 56 90 0.52 57 P2 23 DCT +0.02 TEC TEH 3 HOT 60OUL TWD 44 92 0.51 104 P2 23 DHB +0.00 TEC TEH 3 HOT 60OUL TWD 48 92 0.45 125 P2 21 DHB +0.00 TEC TEH 3 HOT 60OUL TWD 54 92 0.75 97 P2 T.WD 28 VS3 +0.70 TEC TEH 4 HOT 600UL 60 92 0.40 70 P,2 20 VS3 +0.78 TEC TEH 3 HOT 60OUL 43 93 0.60 128 P2 TWD 27 DCB +0.00 TEC TEH 3 HOT 60OUL 1.05 51 P2 TWD 32 DHT +0.00 TEC TEH 3 HOT 600UL 42 94 0.99 77 P2 TWD 32 DCB +0.63 TEC TEH 3 HOT 60OUL 46 94 0.82 123 P2 TWD 30 VS3 -0.94 TEC TEH 3 HOT 600UL 1.03 130 P2 TWD 32 DCB +0.00 TEC TEH 3 HOT 600UL 50 94 0.47 115 P2 TWD 24 VS3 -0.92 TEC TEH 3 HOT 60OUL 51 95 0.37 144 P2 TWD 21 07H +0.87 TEC TEH 3 HOT 60OUL 35 97 0.59 137 P2 TWD 25 DHB +0.00 TEC TEH 4 HOT 60OUL 71 97 0.62 149 P2 TWD 27 VS4 -0.73 TEC TEH 3 HOT 600UL 93 97 0.39 144 P2 TWD 20 VS2 +0.68 TEH TEC 35 COLD 60OUL 34 98 0.47 78 P2 TWD 24 VS3 +0.83 TEC TEN 3 HOT 600UL 0.78 127 P2 TWD 29 VS3 -0.90 TEC TEN 3 HOT 60OUL 0.60 123 P2 TWD 27 DHB +0.00 TEC TEH 3 HOT 600UL 0.51 97 P2 TWD 25 DCB +0.09 TEC TEH 3 HOT 60OUL 1.02 57 P2 TWD 27 DHT -0.25 TEC TEH 3 HOT 60OUL 33 99 0.42 31 P2 TWD 21 DCB +0.00 TEC TEH 4 HOT 600UL 37 99 0.69 40 P2 TWD 27 DCB +0.00 TEC TEH 4 HOT 60OUL 0.64 67 P2 TWD 26 VS3 -0.07 TEC TEH 4 HOT 60OUL 0.91 130 P2 TWD 31 VS3 -0.69 TEC TEH 4 HOT 60OUL 0.54 48 P2 TWD 24 DHB +0.00 TEC TEH 4 HOT 60OUL 34 100 0.62 76 P2 TWD 27 DHB +0.27 TEH TEC 16 COLD 600UL 0.88 78 P2 TWD 32 DHT -0.16 TEH TEC 16 COLD 600UL 94 100 0.86 119 P2 TWD 31 VS2 -0.79 TEH TEC 26 COLD 600UL 0.69 54 P2 TWD 28 VS2 +0.79 TEH TEC 26 COLD 600UL 33 101 0.37 139 P2 TWD 21 DCT +0.00 TEH TEC 17 COLD 60OUL 35 101 0.52 69 P2 TWD 25 VS3 -0.99 TEH TEC 16 COLD 60OUL TWD 47 101 0.36 46 P2 20 VS3 +0.86 TEH TEC 16 COLD 60OUL TWD 93 101 0.55 94 P2 25 VS2 -0.94 TEH TEC 26 COLD 60OUL TWD 135 101 0.90 82 P2 29 VS1 +0.74 TEH TEC 58 COLD 60OUL TWD 34 102 0.49 73 P2 24 VS3 +0.64 TEH TEC 16 COLD 600UL TWD 29 103 0.36 29 P2 20 VS3 -0.81 TEH TEC 17 COLD 60OUL TWD 34 104 0.46 27 P2 24 VS3 -0.96 TEH TEC 17 COLD 600UL TWD 40 104 0.55 151 P2 25 VS3 -0.87 TEH TEC 16 COLD 60OUL TWD 47 105 0.39 19 P2 21 VS3 +0.77 TEH TEC 17 COLD 600UL TWD 32 106 0.48 69 P2 22 VS3 -1.01 TEH TEC 18 COLD 60OUL TWD 50 106 0.45 93 P2 23 VS3 +0.91 TEH TEC 19 COLD 600UL TWD 34 108 0.47 61 P2 23 VS3 -0.89 TEH TEC 19 COLD 60OUL TWD 96 108 0.66 119 P2 30 VS2 -0.86 TEH TEC 28 COLD 60OUL TWD 97 109 0.28 113 P2 20 VS2 -0.97 TEH TEC 28 COLD 60OUL TWD 89 111 0.66 101 P2 29 VS4 -0.71 TEH TEC 35 COLD 60OUL TWD 126 112 0.54 36 P2 24 VS1 -0.84 TEH TEC 36 COLD 60OUL TWD 96 114 1.10 127 P2 36 VS2 -0.81 TEH TEC 35 COLD 60OUL TWD 1.01 99 P2 35 VS2 -0.14 TEH TEC 35 COLD 60OUL TWD 0.68 69 P2 29 VS2 +0.52 TER TEC 35 COLD 600UL TWD 0.44 140 P2 22 VS3 -0.89 TEH TEC 35 COLD 600UL
Framatome ANP Inc. 1/22/2005 14:30 Attachment 5 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G B Page 4 of 4 Tubes with Bobbin 20-39% TWD Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 0.74 69 P=2 TWD 30 VS3 +0.18 TEH TEC 35 COLD 60 OUL 0.59 147 P 2 TWD 27 VS4 +0.89 TEH TEC 35 COLD 60OUL 89 117 0.63 52 P 2 TWD 28 VS2 -0.85 TEH TEC 36 COLD 60OUL 88 120 0.69 39 P 2 TWD 29 VS4 -0.76 TEH TEC 33 COLD 60OUL 96 120 0.38 152 P 2 TWD 20 VS3 -0.89 TEH TEC 33 COLD 600UL 51 121 0.33 54 P 2 TWD 21 VS3 +0.71 TEH TEC 22 COLD 60OUL 54 124 0.87 25 P 2 TWD 30 VS3 +0.00 TEH TEC 20 COLD 60OUL 94 124 0.39 61 P 2 TWD 20 VS2 -0.80 TEH TEC 34 COLD 60OUL 55 125 0.90 113 P 2 TWD 31 VS3 -0.99 TEH TEC 20 COLD 60OUL 94 126 0.39 80 P 2 TWD 21 VS2 -0.98 TEH TEC 33 COLD 60OUL 95 131 0.38 83 P 2 TWD 21 VS2 -0.51 TEH TEC 33 COLD 60OUL 60 134 0.43 74 P 2 TWD 23 VS3 -0.69 TEC TEH 23 HOT 60OUL 89 135 0.37 114 P 2 TWD 22 DCB +0.00 TEH TEC 31 COLD 60OUL 94 136 0.39 132 P 2 TWD 21 VS4 +0.91 TEH TEC 32 COLD 60OUL 108 136 0.60 126 P 2 TWD 28 02C -0.85 TEH TEC 31 COLD 600UL TWD 35 137 0.34 102 P 2 21 VS3 -0.87 TEC TEC 23 HOT 60OUL TWD 70 138 0.56 133 P 2 26 VS3 +0.91 TEC TEH 23 HOT 60OUL TWD 55 139 0.88 85 P 2 31 VS3 +0.98 TEC TEH 23 HOT 60OUL TWD 92 142 0.36 99 P 2 21 VS2 +0.62 TEH TEC 31 COLD 600UL TWD 95 143 0.60 148 P 2 25 VS2 -0.65 TEH TEC 27 COLD 60OUL TWD 82 150 0.45 152 P 2 21 VS3 +0.87 TEH TEC 27 COLD 60OUL TWD 64 152 0.39 92 P 2 21 VS2 -0.53 TEC TEN 29 HOT 600UL TWD 42 162 0.41 98 P 2 20 01C +0.91 TEC TEH 32 HOT 600UL TWD 27 163 0.49 62 P 2 22 VS3 +0.61 TEC TEH 33 HOT 60OUL Total Tubes : 144 Total Records: 186
Framatome ANP Inc. 1/22/2005 14:30 Attachment 6 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G B Page 1 of 7 Tubes with Bobbin 1-19% TWD Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 1 3 0.11 161 P 2 TWD 8 01C -0.96 07C TEC 46 COLD 60OUL 32 4 0.25 140 P 2 TWD 13 02H +0.99 TEH TEC 47 COLD 600UL 34 4 0.24 153 P 2 TWD 14 02H -0.99 TEH TEC 48 COLD 60OUL 31 5 0.35 48 P 2 TWD 18 01C -0.93 TEC TEH 9 HOT 600UL 60 10 0.08 155 P 2 TWD 9 02H +0.88 TEC TEH 9 HOT 60OUL 62 12 0.17 109 P 2 TWD 15 01H -0.94 TEC TEH 10 HOT 60OUL 39 15 0.09 171 P 2 TWD 9 04H +0.80 TEC TEH 14 HOT 60OUL 55 15 0.07 168 P 2 TWD 8 04H +0.86 TEC TEH 14 HOT 600UL 40 18 0.17 55 P 2 TWD 15 VS3 -0.96 TEC TEH 14 HOT 600UL 62 18 0.16 93 P 2 TWD 14 VS3 -0.87 TEC TEH 14 HOT 600UL 46 22 0.14 33 P 2 TWD 14 VS3 +0.97 TEC TEH 18 HOT 600UL 48 22 0.13 51 P 2 TWD 14 VS3 -1.00 TEC TEH 17 HOT 600UL 93 23 0.24 93 P 2 TWD 13 DCT +0.00 TEH TEC 47 COLD 600UL 88 24 0.32 58 P 2 TWD 17 VS2 +0.89 TEH TEC 49 COLD 60OUL 0.19 140 P 2 TWD 12 VS3 +0.58 TEH TEC 49 COLD 600UL 92 24 0.30 58 P 2 TWD 17 DCB +0.00 TEH TEC 49 COLD 600UL 94 24 0.25 72 P 2 TWD 16 DCB +0.00 TEH TEC 50 COLD 60OUL 96 24 0.26 135 P 2 TWD 9 06H +0.87 TEH TEC 50 COLD 600UL 81 25 0.30 63 P 2 TWD 18 DCT +0.00 TEH TEC 50 COLD 600UL 91 25 0.31 122 P 2 TWD 18 DCT -0.12 TEH TEC 49 COLD 600UL 95 25 0.35 130 P 2 TWD 19 VS4 -0.89 TEH TEC 49 COLD 600UL 0.08 16 P 2 TWD 3 05H +0.67 TEH TEC 49 COLD 600UL 44 26 0.11 15 P 2 TWD 12 VS3 -0.88 TEC TEN 19 HOT 60OUL 94 26 0.32 110 P 2 TWD 17 VS2 -1.01 TEH TEC 49 COLD 60OUL 0.28 149 P 2 TWD 15 VS2 +0.95 TEH TEC 49 COLD 600UL 0.37 133 P 2 TWD 18 DHT +0.00 TEH TEC 49 COLD 60OUL 91 27 0.30 98 P 2 TWD 17 VS4 -0.99 TEH TEC 49 COLD 60OUL 95 27 0.20 81 P 2 TWD 12 VS4 -0.93 TEH TEC 49 COLD 60OUL 97 27 0.21 40 P 2 TWD 14 VS3 -0.93 TEH TEC 50 COLD 60OUL 34 28 0.08 163 P 2 TWD 8 VS3 -1.13 TEC TEH 20 HOT 600UL 92 28 0.16 30 P 2 TWD 12 VS2 -0.59 TEH TEC 50 COLD 600UL 0.13 121 P 2 TWD 9 VS2 +0.83 TEH TEC 50 COLD 60OUL 98 28 0.17 110 P 2 TWD 10 VS2 +0.81 TEH TEC 49 COLD 600UL 100 28 0.21 120 P 2 TWD 14 02H +0.94 TEH TEC 50 COLD 60OUL 53 29 0.17 119 P 2 TWD 17 VS3 +0.92 TEC TEC 19 HOT 600UL 67 29 0.17 136 P 2 TWD 17 VS2 -0.69 TEC TEH 19 HOT 600UL 89 29 0.27 11 P 2 TWD 17 DHT +0.00 TEH TEC 50 COLD 600UL 91 29 0.28 98 P 2 TWD 15 DCT +0.00 TEH TEC 49 COLD 600UL 95 29 0.19 49 P 2 TWD 13 VS2 +0.81 TEH TEC 50 COLD 600UL 0.13 35 P 2 TWD 10 06H +0.95 TEH TEC 50 COLD 60OUL 42 30 0.24 28 P 2 TWD 19 VS3 -0.86 TEC TEH 20 HOT 600UL 92 30 0.30 139 P 2 TWD 16 VS2 +0.65 TEH TEC 49 COLD 600UL 0.28 152 P 2 TWD 16 VS4 -0.91 TEH TEC 49 COLD 600UL 0.15 121 P 2 TWD 9 07H +0.88 TEH TEC 49 COLD 600UL 96 30 0.21 26 P 2 TWD 13 VS4 +0.40 TEH TEC 49 COLD 60OUL 104 30 0.19 56 P 2 TWD 10 VS3 -1.33 TEH TEC 49 COLD 600UL 107 31 0.24 51 P 2 TWD 15 02H +0.76 TEH TEC 49 COLD 60OUL 0.28 70 P 2 TWD 16 04C -1.02 TEH TEC 49 COLD 600UL 108 32 0.25 149 P 2 TWD 15 02H -0.86 TEH TEC 49 COLD 600UL 27 33 0.12 33 P 2 TWD 11 VS3 +0.76 TEC TEN 25 HOT 600UL 105 33 0.28 78 P 2 TWD 10 02H -0.12 TEH TEC 49 COLD 600UL 30 34 0.18 165 P 2 TWD 19 VS3 -0.98 TEC TEH 24 HOT 600UL 82 34 0.28 87 P 2 TWD 10 VS4 -0.61 TEH TEC 50 COLD 600UL 92 34 0.18 63 P 2 TWD 11 08H +1.02 TEH TEC 49 COLD 600UL
Framatome ANP Inc. 1/22/2005 14:30 Attaclheznt 6 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G B Page 2 of 7 Tubes with Bobbin 1-19% TWD Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 96 34 0.24 86 P2 TWD 15 VS3 +0.32 TEH TEC 49 COLD 60=OUL 108 34 0.15 100 P2 TWD 10 03C -0.88 TEH TEC 52 COLD 60OUL 94 36 0.25 148 P2 TWD 15 VS2 -0.95 TEH TEC 51 COLD 60OUL 96 36 0.35 106 P2 TWD 19 VS2 -0.79 TEH TEC 52 COLD 600UL 100 36 0.29 12 P2 T.D 17 08H +0.89 TEH TEC 52 COLD 600UL 87 37 0.13 20 P2 TWD 9 VS2 -0.65 TEH TEC 51 COLD 60OUL 0.17 167 P2 TWD 11 VS2 +0.75 TEH TEC 51 COLD 600UL 68 38 0.21 90 P2 TWD 14 VS2 -0.54 TEH TEC 3 COLD 600UL 92 38 0.22 102 P2 TWD 13 08H -0.78 TEH TEC 52 COLD 600UL 112 38 0.23 97 P2 TWD 14 VS4 -0.87 TEH TEC 52 COLD 600UL 116 38 0.33 52 P2 TWD 18 VS3 +0.87 TEH TEC 52 COLD 60OUL 81 39 0.23 22 P2 TWD 14 VS4 +0.63 TEH TEC 51 COLD 60OUL 83 39 0.15 105 P2 TWD 10 VS2 +0.65 TEH TEC 51 COLD 600UL 0.19 14 P2 TWD 12 VS4 +0.75 TEH TEC 51 COLD 600UL 117 39 0.29 44 P2 TWD 16 DCT -0.25 TEH TEC 52 COLD 60O0UL 81 41 0.33 86 P2 TWD 18 VS3 -0.95 TEH TEC 51 COLD 60OUL 85 41 0.16 152 P2 TWD 10 VS4 -0.77 TEH TEC 51 COLD 60OUL 95 41 0.22 63 P2 TWD 13 VS4 +0.89 TEH TEC 52 COLD 60OUL 97 41 0.36 57 P2 TWD 19 VS3 -0.97 TEH TEC 51 COLD 600UL 0.22 138 P2 TWD 14 VS4 -0.81 TEH TEC 51 COLD 60OUL 116 42 0.15 114 P2 TWD 10 05C +0.86 TEH TEC 52 COLD 60OUL 121 43 0.19 10 P2 TWD 12 DCT +0.00 TEH TEC 51 COLD 600UL 46 44 0.13 20 P2 TWD 9 VS3 +0.82 TEH TEC 4 COLD 60OUL 94 44 0.20 162 P2 TWD 12 VS2 -0.69 TEH TEC 52 COLD 60OUL 0.25 52 P2 TWD 15 VS4 -1.20 TEH TEC 52 COLD 600UL 120 44 0.17 138 P2 TWD 11 04H +0.92 TEH TEC 51 COLD 600UL 29 45 0.29 69 P2 TWD 17 VS3 -0.62 TEH TEC 3 COLD 60OUL 123 45 0.32 41 P2 TWD 17 DHT +0.00 TEH TEC 52 COLD 60OUL 62 46 0.27 50 P2 TWD 16 VS2 +0.85 TEH TEC 3 COLD 60OUL 124 46 0.15 29 P2 TWD 10 DCT +0.00 TEH TEC 52 COLD 60OUL 600UL 125 47 0.31 108 P2 TWD 17 09C +0.88 TEH TEC 52 COLD 86 48 0.24 47 P2 TWD 14 VS2 +1.08 TEH TEC 51 COLD 60OUL 126 48 0.14 149 P2 TWD 9 07H -1.00 TEH TEC 52 COLD 60OUL 68 50 0.28 45 P2 TWD 15 VS2 +0.85 TEH TEC 7 COLD 60OUL 107 51 0.13 65 P2 TWD 10 07C +0.95 TEH TEC 54 COLD 60OUL 113 51 0.35 104 P2 TWD 19 02H -0.08 TEH TEC 53 COLD 60OUL 121 51 0.27 161 P2 TWD 16 05H +0.89 TEH TEC 53 COLD 60OUL 127 53 0.30 75 P2 TWD 18 DCB -0.16 TEH TEC 53 COLD 600UL 0.30 132 P2 TWD 17 07H +0.85 TEH TEC 53 COLD 60OUL 0.18 156 P2 TWD 12 06H -0.56 TEH TEC 53 COLD 60OUL 94 54 0.31 162 P2 TWD 17 VS3 +0.83 TEH TEC 55 COLD 60OUL 83 55 0.21 60 P2 TWD 13 VS4 +0.64 TEH TEC 56 COLD 60OUL 600UL 0.27 43 P2 TWD 16 VS3 -0.73 TEH TEC 56 COLD P2 TWD 600UL 95 55 0.24 48 14 DHB +0.30 TEH TEC 55 COLD TWD 131 55 0.20 103 P2 10 05H -0.97 TEH TEC 58 COLD 60OUL TWD 28 56 0.15 15 P2 11 VS3 -0.82 TEH TEC 15 COLD 600UL TWD 81 57 0.29 56 P2 17 VS4 -0.71 TEH TEC 55 COLD 60OUL TWD 121 57 0.14 63 P2 11 VS1 +0.90 TEH TEC 54 COLD 60OUL TWD 48 58 0.10 143 P2 7 VS3 +0.87 TEH TEC 13 COLD 600UL TWD 49 59 0.25 25 P2 14 VS3 +0.85 TEH TEC 12 COLD 60OUL TWD 127 59 0.35 220 P2 19 09H +0.96 TEH TEC 55 COLD 60OUL TWD 129 59 0.27 14 P2 16 DCT +0.25 TEH TEC 56 COLD 600UL TWD 102 60 0.21 99 P2 13 VS4 -0.66 TEH TEC 56 COLD 60OUL TWD 132 60 0.40 101 P2 18 DCT +0.00 TEH TEC 57 COLD 60OUL
Framatome ANP Inc. 1/22/2005 14:30 Attacbment 6 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G B Page 3 of 7 Tubes with Bobbin 1-19% TWD Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 134 60 0.26 61 P 2 TWD 13 DCT +0.00 TEN TEC 58 COLD 60===L 133 61 0.45 146 P 2 TWD 19 DHT -0.25 TEH TEC 58 COLD 600UL 24 62 0.28 49 P 2 TWD 17 VS3 +0.82 TEH TEC 13 COLD 600UL 98 62 0.10 41 P 2 TWD 7 VS2 -0.89 TEH TEC 55 COLD 600UL 106 62 0.20 136 P 2 TWD 12 VS1 +0.12 TEH TEC 55 COLD 600UL 53 63 0.17 73 P 2 TWD 12 VS3 -0.61 TEH TEC 11 COLD 600UL 22 64 0.17 93 P 2 TWD 11 VS3 +0.72 TEH TEC 10 COLD 600UL 25 65 0.22 36 P 2 TWD 15 VS3 +0.68 TEH TEC 11 COLD 600uL 46 66 0.20 107 P 2 TWD 14 VS3 +0.79 TEH TEC 11 COLD 600UL 96 66 0.23 98 P 2 TWD 14 VS4 +0.88 TEH TEC 56 COLD 600UL 36 68 0.32 29 P 2 TWD 19 VS3 -0.80 TEH TEC 11 COLD 600UL 38 68 0.29 159 P 2 TWD 16 VS3 -0.78 TEH TEC 10 COLD 600UL 46 68 0.16 124 P 2 TWD 10 VS3 +0.93 TEH TEC 10 COLD 600UL 0.11 7 P 2 TWD 7 DCT +0.00 TEH TEC 10 COLD 600UL 64 68 0.18 96 P 2 TWD 11 VS2 +0.79 TEH TEC 10 COLD 600UL 134 68 0.34 143 P 2 TWD 16 DHB +0.00 TEH TEC 58 COLD 600UL 35 69 0.35 140 P 2 TWD 19 DCT -0.21 TEC TEH 12 HOT 600UL 39 69 0.17 136 P 2 TWD 11 VS3 -0.61 TEC TEH 12 HOT 600UL 50 72 0.27 104 P 2 TWD 16 VS3 -0.70 TEC TEH 12 HOT 600UL 48 74 0.13 94 P 2 TWD 9 DHB +0.11 TEC TEH 12 HOT 600UL 52 74 0.26 165 P 2 TWD 16 VS3 +0.97 TEC TEH 12 HOT 600UL 103 75 0.22 51 P 2 TWD 12 VS2 +1.00 TEH TEC 43 COLD 600UL 137 75 0.23 147 P 2 TWD 11 05H .0.90 TEH TEC 57 COLD 600UL 53 77 0.24 111 P 2 TWD 15 DCB +0.00 TEC TEH 6 HOT 600UL 57 77 0.33 130 P 2 TWD 18 VS3 -0.87 TEC TEH 6 HOT 600UL 0.16 130 P 2 TWD 11 VS3 +0.71 TEC TEH 6 HOT 600UL 0.31 158 P 2 TWD 18 DCB +0.51 TEC TEH 6 HOT 600UL 52 78 0.46 58 P 2 TWD 14 VS3 -0.96 TEC TEH 6 HOT 600UL 54 78 0.29 102 P 2 TWD 17 DCT +0.00 TEC TEH 5 HOT 600UL 88 78 0.31 104 P 2 TWD 15 VS2 -0.90 TEH TEC 44 COLD 600UL 96 78 0.17 28 P 2 TWD 15 DCT -0.25 TEH TEC 39 COLD 600UL 59 79 0.30 87 P 2 TWD 17 DCB +0.00 TEC TEH 6 HOT 600UL 61 79 0.26 112 P 2 TWD 15 DCB +0.00 TEC TEH 5 HOT 600UL 63 79 0.25 136 P 2 TWD 15 DCB +0.00 TEC TEH 5 HOT 600UL 132 80 0.18 153 P 2 TWD 9 VS1 +0.62 TEH TEC 57 COLD 600UL 51 81 0.31 141 P 2 TWD 17 DCT +0.00 TEC TEH 6 HOT 600UL 53 81 0.30 26 P 2 TWD 17 DCT +0.00 TEC TEH 5 HOT 600UL 116 82 0.16 113 P 2 TWD 8 VS4 -0.91 TEH TEC 41 COLD 600UL 51 83 0.33 32 P 2 TWD 18 DCB +0.00 TEC TEH 6 HOT 600UL 53 83 0.24 28 P 2 TWD 14 DCB +2.99 TEC TEH 5 HOT 600UL 50 84 0.23 23 P 2 TWD 14 DHB +0.00 TEC TEH 6 HOT 600UL 54 84 0.17 108 P 2 TWD 12 DCT +0.00 TEC TEH 6 HOT 600UL 64 84 0.28 165 P 2 TWD 16 VS3 -0.73 TEC TEH 5 HOT 600UL 88 84 0.31 159 P 2 TWD 17 VS2 +0.85 TEH TEC 59 COLD 600UL 98 84 0.11 39 P 2 TWD 11 VS5 -0.92 TEH TEC 39 COLD 600UL 61 85 0.25 67 P 2 TWD 15 DCB +0.00 TEC TEH 6 HOT 600UL 95 85 0.25 102 P 2 TWD 19 VS2 -0.75 TEH TEC 39 COLD 600UL 60 86 0.14 168 P 2 TWD 9 VS3 -0.67 TEC TEH 3 HOT 600UL 122 86 0.13 79 P 2 TWD 9 06H +0.87 TEH TEC 37 COLD 600UL 50 88 0.31 157 P 2 TWD 19 DHB +0.00 TEC TEH 3 HOT 600UL 52 88 0.33 42 P 2 TWD 18 DHT +0.07 TEC TEH 4 HOT 600UL 54 88 0.28 149 P 2 TWD 16 VS3 -0.79 TEC TEH 3 HOT 600UL 100 88 0.32 163 P 2 TWD 17 08C -0.93 TEH TEC 37 COLD 600UL 122 88 0.20 101 P 2 TWD 14 VS1 +0.50 TEH TEC 38 COLD 600UL
Framatome ANP Inc. 1/22/2005 14:30 Attacbment 6 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G B Page 4 of 7 Tubes with Bobbin 1-19% TWD Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 55 89 0.15 160 P 2 TWD 10 DHB -0.05 TEC TEH 4 HOT 600UL 89 89 0.24 129 P 2 TWD 14 VS2 -0.69 TEH TEC 37 COLD 600UL 48 90 0.38 84 P 2 TWD 14 DHB +0.00 TEC TEH 3 HOT 600UL 52 90 0.35 51 P 2 TWD 18 DCB +0.00 TEC TER 3 HOT 600UL 56 90 0.34 38 P 2 TWD 18 VS3 -0.27 TEC TEH 3 HOT 600UL 100 90 0.42 30 P 2 TWD 15 06C +0.04 TEN TEC 38 COLD 600UL 53 91 0.17 168 P 2 TWD 11 DCT +0.00 TEC TEH 3 HOT 600UL 44 92 0.32 17 P 2 TWD 17 DCT +0.00 TEC TEN 3 HOT 600UL 50 92 0.32 19 P 2 TWD 17 DHB +0.00 TEC TEN 4 HOT 600UL 60 92 0.33 140 P 2 TWD 18 VS4 -0.93 TEC TEN 3 HOT 600UL 96 92 0.16 166 P 2 TWD 10 05C +0.84 TER TEC 37 COLD 600UL 102 92 0.19 40 P 2 TWD 13 VS4 -0.65 TEN TEC 38 COLD 600UL 110 92 0.12 155 P 2 TWD 9 07C -0.14 TEN TEC 38 COLD 600UL 87 93 0.33 97 P 2 TWD 17 VS3 -1.00 TEN TEC 37 COLD 600UL 44 94 0.35 33 P 2 TWD 18 DCB +0.00 TEC TEH 4 HOT 600UL 66 94 0.20 159 P 2 TWD 14 VS3 +0.69 TEC TEN 3 HOT 600UL 39 95 0.31 62 P 2 TWD 17 DCT +0.00 TEC TER 4 HOT 600UL 95 95 0.22 143 P 2 TWD 15 VS2 +1.01 TEN TEC 38 COLD 600UL 0.23 134 P 2 TWD 15 VS4 -0.64 TEN TEC 38 COLD 600UL 46 96 0.37 160 P 2 TWD 19 DHB +0.00 TEC TEH 4 HOT 600UL 45 97 0.30 341 P 2 TWD 19 VS3 -1.02 TEC TER 3 HOT 600UL 71 97 0.21 163 P 2 TWD 15 VS2 +0.86 TEC TEH 3 HOT 600UL 89 97 0.35 70 P 2 TWD 18 VS4 -0.88 TEH TEC 35 COLD 600UL 93 97 0.29 60 P 2 TWD 14 VS4 +0.74 TEH TEC 35 COLD 600UL 34 98 0.27 32 P 2 TWD 15 DCT -0.11 TEC TEH 3 HOT 600UL 56 98 0.24 152 P 2 TWD 16 VS3 +0.99 TEC TEH 3 HOT 600UL 62 98 0.20 147 P 2 TWD 15 VS3 -0.82 TEC TEH 3 HOT 600UL 88 98 0.40 60 P 2 TWD 15 06C +0.85 TEN TEC 35 COLD 600UL 94 98 0.29 43 P 2 TWD 16 VS2 +0.67 TEN TEC 36 COLD 600UL 47 99 0.31 151 P 2 TWD 17 VS3 -0.83 TEC TEH 4 HOT 600uL 55 99 0.13 161 P 2 TWD 9 VS3 +1.19 TEC TEN 4 HOT 600UL 95 99 0.15 148 P 2 TWD 8 08C +0.82 TEH TEC 36 COLD 600UL 137 99 0.27 129 P 2 TWD 13 VS1 +0.80 TER TEC 58 COLD 600UL 34 100 0.18 97 P 2 TWD 12 DCB +0.47 TEN TEC 16 COLD 600UL 94 100 0.27 29 P 2 TWD 15 VS4 +0.87 TEN TEC 26 COLD 600UL 37 101 0.18 77 P 2 TWD 12 VS3 -0.87 TEN TEC 17 COLD 600UL 51 101 0.41 86 P 2 TWD 14 VS3 +0.80 TEN TEC 16 COLD 600UL 89 101 0.22 86 P 2 TWD 13 06H +0.99 TEH TEC 26 COLD 600UL 91 101 0.18 117 P 2 TWD 9 VS2 -0.79 TEH TEC 25 COLD 600UL 93 101 0.28 30 P 2 TWD 15 VS3 -0.50 TEH TEC 26 COLD 600UL 97 101 0.31 70 P 2 TWD 11 05C -0.20 TEN TEC 26 COLD 600UL 30 102 0.28 137 P 2 TWD 17 VS3 +0.88 TEN TEC 16 COLD 600UL 34 102 0.17 158 P 2 TWD 12 VS3 -0.84 TEN TEC 16 COLD 600UL 92 102 0.18 34 P 2 TWD 11 VS2 +0.83 TEH TEC 26 COLD 600UL 94 102 0.24 11 P 2 TWD 12 VS3 -0.80 TEH TEC 25 COLD 600UL 98 102 0.14 169 P 2 TWD 8 VS4 -0.97 TER TEC 25 COLD 600UL 27 103 0.24 153 P 2 TWD 15 VS3 -0.76 TEN TEC 16 COLD 600UL 31 103 0.26 138 P 2 TWD 16 VS3 -0.74 TEH TEC 16 COLD 600UL 35 103 0.27 62 P 2 TWD 17 VS3 -0.66 TER TEC 16 COLD 600UL 53 103 0.25 12 P 2 TWD 16 DCT +0.00 TEN TEC 17 COLD 600UL 87 103 0.16 22 P 2 TWD 8 VS2 -0.92 TER TEC 25 COLD 600UL 89 103 0.35 111 P 2 TWD 18 VS2 -0.79 TER TEC 26 COLD 600UL 97 103 0.30 174 P 2 TWD 16 DHB +3.71 TEH TEC 26 COLD 600UL 20 104 0.20 142 P 2 TWD 13 VS3 +0.90 TEH TEC 17 COLD 600UL
Framatome ANP Inc. 1/22/2005 14:30 kttacbment 6 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G B Page 5 of 7 Tubes with Bobbin 1-19% TWD Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 24 104 0.27 116 P 2 TWD 17 VS3 +0.72 TEH TEC 16 COLD 60OUL 26 104 0,34 44 P 2 TWD 19 VS3 +0.80 TEH TEC 17 COLD 60OUL 28 104 0.20 138 P 2 TWD 14 VS3 +0.80 TEH TEC 16 COLD 60OUL 38 104 0.26 38 P 2 TWD 16 VS3 +0.74 TEH TEC 17 COLD 600UL 94 104 0.21 21 P 2 TWD 11 08C +0.80 TEH TEC 25 COLD 60OUL 126 104 0.42 109 P 2 TWD 14 VS1 -0.83 TEH TEC 25 COLD 60OUL 47 105 0.33 59 P 2 TWD 19 VS3 -0.60 TEH TEC 17 COLD 60OUL 24 106 0.30 137 P 2 TWD 16 VS3 +0.72 TEH TEC 18 COLD 60OUL 28 106 0.29 60 P 2 TWD 16 VS3 +0.82 TEH TEC 18 COLD 60OUL 42 106 0.18 113 P 2 TWD 11 VS3 -0.32 TEH TEC 19 COLD 600UL 29 107 0.29 31 P 2 TWD 16 VS3 +0.68 TEH TEC 18 COLD 600UL 50 108 0.18 153 P 2 TWD 12 VS3 -0.81 TEH TEC 19 COLD 600UL 88 108 0.19 145 P 2 TWD 16 05H +0.93 TEH TEC 28 COLD 60OUL TWD TEH TEC 96 108 0.22 51 P 2 18 VS4 +0.86 28 COLD 60OUL TWD TEH TEC 93 109 0.14 140 P 2 13 VS2 -0.92 28 COLD 60OUL TWD TEH TEC 97 109 0.21 28 P 2 17 VS2 +0.85 28 COLD 600UL TWD TEH TEC 133 109 0.23 74 P 2 12 08H +0.73 58 COLD 600UL TWD TEH TEC COLD 0.21 104 P 2 11 08H -0.75 58 60OUL TWD TEH TEC COLD 50 110 0.22 135 P 2 13 VS3 -0.89 18 600UL TWD 0.21 133 P 2 12 VS3 +0.66 TEH TEC 18 COLD 60OUL TWD TEH TEC 132 110 0.31 103 P 2 15 VS5 +0.85 58 COLD 60OUL TWD 35 111 0.16 148 P 2 11 VS3 -0.79 TEH TEC 19 COLD 60OUL TWD 34 112 0.17 157 P 2 11 VS3 -0.73 TEH TEC 24 COLD 600UL TWD COLD 90 112 0.11 138 P 2 6 06H +0.87 TEH TEC 36 60OUL TWD TEH TEC COLD 122 112 0.29 57 P 2 15 VS4 -0.88 36 60OUL TWD TEH TEC 128 112 0.36 93 P 2 19 DCT -0.10 35 COLD 60OUL TWD 25 113 0.21 129 P 2 10 VS3 -0.72 TEH TEC 23 COLD 60OUL TWD TEH TEC COLD 51 115 0.20 121 P 2 12 VS3 +0.85 24 60OUL TWD 52 116 0.20 152 P 2 10 VS3 +0.92 TEH TEC 23 COLD 60OUL P 2 TWD TEH TEC COLD 0.10 17 4 VS3 -0.92 23 60OUL TWD 54 116 0.15 32 P 2 10 VS3 +1.00 TEH TEC 24 COLD 60OUL P 2 TWD TEH TEC 19 117 0.28 24 14 VS3 +0.82 23 COLD 60OUL TWD TEH TEC COLD 89 117 0.36 106 P 2 12 07H -0.88 36 60OUL P 2 TWD TEH TEC 32 118 0.22 138 13 VS3 +0.04 24 COLD 60OUL TWD 54 118 0.24 37 P 2 14 VS3 +0.97 TEH TEC 24 COLD 600UL P 2 TWD TEH TEC 112 118 0.18 19 10 VS1 +0.60 36 COLD 60OUL TWD 121 119 0.10 43 P 2 7 VS4 -0.76 TEH TEC 33 COLD 600UL P 2 TWD TEH TEC COLD 96 120 0.22 79 14 VS3 +0.77 33 60OUL P 2 TWD 5 121 0.10 125 7 04C +0.96 TEH TEC 61 COLD 60OUL TWD 51 121 0.24 12 P 2 TWD 17 VS3 -0.83 TEH TEC 22 COLD 600UL 97 121 0.19 13 P 2 TWD 11 VS2 -0.80 TEH TEC 34 COLD 600UL 94 122 0.28 65 P 2 TWD 16 VS2 -0.95 TEH TEC 34 COLD 600UL 102 122 0.21 72 P 2 TWD 12 VS1 -0.65 TEH TEC 34 COLD 60OUL 52 124 0.26 87 P 2 TWD 18 VS3 -0.95 TEH TEC 22 COLD 600UL 62 124 0.11 157 P 2 TWD 7 05C +0.98 TEH TEC 20 COLD 600UL 94 124 0.36 71 P 2 TWD 19 VS3 -0.96 TEH TEC 34 COLD 60OUL 36 126 0.14 148 P 2 TWD 12 VS3 -0.93 TEH TEC 22 COLD 60OUL 46 126 0.34 52 P 2 TWD 18 VS3 -0.74 TEH TEC 20 COLD 60OUL 94 126 0.29 155 P 2 17 VS3 -0.84 TEH TEC 33 COLD 60OUL 0.19 22 P 2 TWD 12 VS4 +0.80 TEH TEC 33 COLD 60OUL 93 127 0.12 76 P 2 TWD 8 VS3 +0.60 TEH TEC 34 COLD 600UL 95 127 0.34 69 P 2 TWD 19 VS2 -0.43 TEH TEC 33 COLD 60OUL P 2 TWD TEH TEC 88 128 0.27 61 15 08C -0.72 34 COLD 60OUL P 2 TWD TEH TEC 75 129 0.19 58 11 DHB +0.00 18 COLD 600UL
Framatome ANP Inc. 1/22/2005 14:30 Attacbment 6 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G B Page 6 of 7 Tubes with Bobbin 1-19% TWD Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 85 129 0.21 65 P 2 TWD 12 DHB +0.00 TEH TEC 34 COLI 60 OUL 95 129 0.11 52 P 2 TWD 8 VS2 +0.77 TEH TEC 33 COLE 60OUL 1 131 0.12 171 P 2 TWD 8 04H +0.91 07H TEH 16 HOT 60OUL 87 131 0.21 157 P 2 TWD 13 VS2 -0.67 TEH TEC 33 COLE) 60OUL 39 133 0.18 8 P 2 TWD 12 VS3 -0.99 TEC TEH 22 HOT 60OUL 111 133 0.24 32 P 2 TWD 16 05C +0.14 TEH TEC 31 COLE) 60OUL 54 134 0.25 45 P 2 TWD 15 VS3 -0.88 TEC TEH 22 HOT 60OUL 0.27 106 P 2 TWD 16 DCB +3.72 TEC TEH 22 HOT 60OUL 88 134 0.15 27 P 2 TWD 10 VS2 -0.83 TEH TEC 32 COLE) 60OUL 104 134 0.26 130 P 2 TWD 16 VS1 +0.70 TEH TEC 32 COLE) 60OUL 55 135 0.21 30 P 2 TWD 13 DCT +0.00 TEC TEH 22 HOT 600UL 87 135 0.28 124 P 2 TWD 17 VS2 -0.89 TEH TEC 32 COLD 60OUL 0.15 72 P 2 TWD 10 VS3 -0.73 TEH TEC 32 COLE) 60OUL 89 135 0.14 15 P 2 TWD 10 VS2 +0.86 TEH TEC 31 COLE) 600UL 0.15 147 P 2 TWD 11 VS2 -0.64 TEH TEC 31 COLD 60OUL 42 136 0.27 40 P 2 TWD 18 VS3 -0.71 TEC TEH 23 HOT 60OUL 94 136 0.15 51 P 2 TWD 10 VS4 -0.28 TEH TEC 32 COLE 600UL 35 137 0.25 34 P 2 TWD 17 DHB +0.78 TEC TEH 23 HOT 60OUL 57 137 0.17 55 P 2 TWD 11 VS3 +0.67 TEC TEH 22 HOT 60OUL 103 137 0.14 14 P 2 TWD 10 VS2 +0.60 TEH TEC 31 COLD 60OUL 56 138 0.20 151 P 2 TWD 13 VS3 -0.61 TEC TEH 22 HOT 60OUL 0.19 164 P 2 TWD 12 VS3 +0.94 TEC TEH 22 HOT 60OUL 80 138 0.22 143 P 2 TWD 15 08C -1.08 TEC TEH 23 HOT 60OUL 88 138 0.29 139 P 2 TWD 19 DCB +0.00 TEH TEC 31 COLE 60OUL 92 138 0.18 24 P 2 TWD 13 VS2 +0.83 TEH TEC 31 COLE 60OUL 94 140 0.18 15 P 2 TWD 12 VS2 +1.38 TEH TEC 32 COLE 60OUL 39 141 0.40 159 P 2 TWD 19 VS3 +0.87 TEC TEH 26 HOT 60OUL 77 141 0.29 30 P 2 TWD 17 DCT +0.07 TEC TEH 27 HOT 600UL 44 142 0.27 125 P 2 TWD 16 07C -1.03 TEC TEH 27 HOT 60OUL 56 142 0.38 156 P 2 TWD 19 07C -1.00 TEC TEH 26 HOT 60OUL 63 143 0.22 147 P 2 TWD 13 VS3 -0.77 TEC TEH 26 HOT 60OUL 54 144 0.22 63 P 2 TWD 13 DCT +0.00 TEC TEH 26 HOT 60OUL 94 144 0.37 130 P 2 TWD 18 VS2 -0.87 TEH TEC 27 COLE 600UL 0.13 156 P 2 TWD 7 VS3 -0.98 TEH TEC 27 COLE 60OUL 0.30 25 P 2 TWD 16 VS4 +0.81 TEH TEC 27 COLD 60OUL 53 145 0.15 162 P 2 TWD 10 DCB +1.93 TEC TEH 26 HOT 60OUL 69 145 0.23 115 P 2 TWD 15 VS2 +0.76 TEC TEH 27 HOT 60OUL 52 146 0.13 32 P 2 TWD 9 07C -0.91 TEC TEH 27 HOT 60OUL 0.14 66 P 2 TWD 10 VS3 +0.79 TEC TEH 27 HOT 600UL 0.34 28 P 2 TWD 19 VS3 -0.76 TEC TEH 27 HOT 600UL 0.15 168 P 2 TWD 10 06C +0.16 TEC TEH 27 HOT 60OUL 76 146 0.21 16 P 2 TWD 14 VS3 +0.80 TEC TEH 27 HOT 60OUL 0.34 59 P 2 TWD 19 VS2 +0.85 TEC TEH 27 HOT 600UL 0.15 137 P 2 TWD 10 VS4 -0.98 TEC TEH 27 HOT 60OUL 85 147 0.27 69 P 2 TWD 14 VS2 -0.99 TEH TEC 27 COLD 600UL 33 151 0.11 53 P 2 TWD 8 VS3 +1.08 TEC TEH 29 HOT 600UL 53 151 0.16 22 P 2 TWD 11 DCB +0.00 TEC TEH 29 HOT 60OUL 60 152 0.24 25 P 2 TWD 15 VS3 +0.50 TEC TEH 29 HOT 60OUL 0.16 36 P 2 TWD 11 VS4 -0.91 TEC TEH 29 HOT 600UL 64 152 0.21 39 P 2 TWD 14 VS4 -0.67 TEC TEH 29 HOT 60OUL 69 153 0.26 28 P 2 TWD 16 VS4 -0.87 TEC TEH 29 HOT 600UL 54 154 0.37 30 P 2 TWD 11 VS3 +0.02 TEC TEH 29 HOT 60OUL 61 155 0.10 8 P 2 TWD 8 VS2 +0.64 TEC TEH 29 HOT 60OUL 62 158 0.10 68 P 2 TWD 7 VS3 -0.96 TEC TEH 28 HOT 60OUL
Framatome ANP Inc. 1/22/2005 14:30 Attacbment 6 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G B Page 7 of 7 Tubes with Bobbin 1-19% TWD Indications ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 55 159 0.31 25 P=2 =WD 18 DHT +0.00 TEC TEH 29 HOT 60=OUL 36 162 0.15 152 P 2 TWD 10 01H +0.83 TEC TEH 33 HOT 60OUL 40 162 0.35 116 P 2 TWD 17 01C -0.93 TEC TEH 33 HOT 60OUL 35 163 0.17 9 P 2 TWD 10 01H +0.78 TEC TEH 33 HOT 60OUL TWD 36 164 0.35 85 P 2 18 01C +0.02 TEC TEH 32 HOT 600UL TWD 12 166 0.31 112 P 2 16 01C -0.98 TEC TEH 33 HOT 60OUL Total Tubes : 294 Total Records: 330
Framatome ANP Inc. 1/23/2005 08:32 Attachment 7 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 1 of 14 Total Number of Bobbin 1-39% TWD Indications left in service for Cycle 15 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 16 4 0.08 14 P2 TWD 9 05H -1.02 TEC TEN 10 HOT 60=OUL 27 5 0.11 148 P2 TWD 12 01H +0.81 TEC TEH 9 HOT 60OUL 35 5 0.17 140 P2 TWD 17 01H -1.00 TEC TEH 9 HOT 60OUL HOT 55 9 0.18 20 P2 TWD 16 01H -0.83 TEC TEH 10 600UL 41 15 0.10 125 P2 TWD 10 VS3 +0.83 TEC TEH 10 HOT 60OUL 74 16 0.09 121 P2 TWD 11 VS2 +0.27 TEC TEH 9 HOT 60OUL 72 20 0.37 130 P2 TWD 25 VS2 -0.49 TEC TEH 20 HOT 600UL TWD 86 20 0.18 123 P2 16 VS2 -0.84 TEH TEC 63 COLD 60OUL TWD 88 20 0.46 123 P2 28 VS2 -0.89 TEH TEC 63 COLD 600UL TWD 87 21 0.50 114 P2 20 VS2 +0.90 TEH TEC 13 COLD 60OUL TWD 0.32 149 P2 14 VS2 -0.92 TEH TEC 13 COLD 60OUL TWD 89 21 0.39 61 P2 26 VS2 +0.73 TEH TEC 14 COLD 60OUL TWD 86 22 1.00 84 P2 34 VS2 +0.86 TEH TEC 13 COLD 60OUL TWD 0.43 100 P2 18 VS3 +0.68 TEH TEC 13 COLD 60OUL TWD 0.32 116 P2 14 VS4 +0.86 TEH TEC 13 COLD 600UL TWD 1.19 122 P4 35 VS3 -0.88 TEH TEC 13 COLD 600UL TWD 72 24 0.19 118 P2 17 VS4 -0.52 TEC TEH 30 HOT 60OUL TWD 90 24 0.29 150 P2 18 VS2 -0.92 TEH TEC 13 COLD 600UL TWD 0.64 134 P2 29 VS3 -0.78 TEH TEC 13 COLD 60OUL TWD 61 25 0.44 153 P2 27 VS4 +0.78 TEC TEN 30 HOT 60OUL TWD 92 26 0.32 114 P2 14 VS3 -0.84 TEH TEC 13 COLD 60OUL TWD 0.27 92 P2 17 VS2 +0.84 TEH TEC 13 COLD 600UL TWD 0.39 137 P2 22 VS4 -0.80 TEH TEC 13 COLD 600UL TWD 0.58 122 P2 28 VS4 +0.45 TEH TEC 13 COLD 60OUL TWD 98 26 0.17 13 P2 15 08H -0.94 TEH TEC 14 COLD 60OUL TWD 37 27 0.17 141 P2 16 VS3 -0.97 TEC TEC 30 HOT 60OUL TWD 91 27 0.16 151 P2 TWD 14 VS2 -0.71 TEH TEC 14 COLD 600UL 0.18 24 P2 TWD 15 VS4 -0.91 TEH TEC 14 COLD 600UL 99 27 0.28 149 P2 TWD 18 VS1 -0.55 TEH TEC 13 COLD 600UL 101 27 0.24 78 P2 TWD 19 02H +0.00 TEH TEC 14 COLD 60OUL 88 28 0.31 101 P2 TWD 19 VS3 -0.94 TEH TEC 13 COLD 60OUL 0.44 79 P2 TWD 24 VS4 -0.84 TEH TEC 13 COLD 60OUL 0.42 42 P2 TWD 23 VS4 -0.25 TEH TEC 13 COLD 60OUL 98 28 0.13 143 P2 TWD 12 VS2 +0.83 TEH TEC 14 COLD 60OUL 0.61 116 P2 TWD 32 VS4 +0.57 TEH TEC 14 COLD 60OUL 81 29 0.74 115 P2 TWD 27 VS4 -0.90 TEH TEC 13 COLD 60OUL 0.42 58 P2 TWD 23 VS3 -0.97 TEH TEC 13 COLD 600UL 0.75 99 P2 TWD 31 VS3 -0.21 TEH TEC 13 COLD 60OUL 0.85 104 P2 TWD 33 VS3 +0.68 TEH TEC 13 COLD 60OUL 0.08 143 P2 TWD 6 VS4 +0.86 TEH TEC 13 COLD 600UL 96 30 0.29 146 P2 TWD 21 VS2 +0.91 TEH TEC 14 COLD 60OUL 0.17 165 P2 TWD 15 VS3 +0.79 TEH TEC 14 COLD 60OUL 0.44 16 P2 TWD 27 DCT +0.00 TEH TEC 14 COLD 60OUL 98 30 0.29 44 P2 18 VS2 +0.51 TEH TEC 13 COLD 600UL 0.21 130 P2 TWD 15 VS3 +0.94 TEH TEC 13 COLD 60OUL 47 31 0.08 22 P2 TWD 10 DHT +0.00 TEC TEN 36 HOT 60OUL 95 31 0.08 22 P2 TWD 9 VS2 +0.87 TEH TEC 14 COLD 60OUL 97 31 0.45 151 P2 TWD 24 VS2 +0.86 TEH TEC 13 COLD 60OUL 92 32 0.24 162 P2 TWD 19 VS2 -0.79 TEH TEC 14 COLD 60OUL 108 32 0.09 148 P2 TWD 9 VS2 +0.82 TEH TEC 14 COLD 60OUL 91 33 0.12 168 P2 TWD 12 VS4 +0.93 TEH TEC 14 COLD 60OUL 105 33 0.33 92 P2 TWD 20 VS2 +0.10 TEH TEC 13 COLD 60OUL TWD 94 34 0.35 145 P2 21 VS2 -0.94 TEH TEC 13 COLD 600UL TWD 96 34 0.64 136 P2 29 VS2 -0.84 TEH TEC 13 COLD 600UL
Framatome ANP Inc. 1/23/2005 08:32 Attachment 7 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 2 of 14 Total Number of Bobbin 1-39% TWD Indications left in service for Cycle 15 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 5 35 0.09 9 P 2 TWD 9 04H +0.90 TEH TEC 68 COLD 60=OUL 51 35 0.41 124 P 2 TWD 25 VS3 -0.92 TEC TEH 35 HOT 600UL 93 35 0.25 153 P 2 TWD 16 05H -1.02 TEH TEC 13 COLD 60OUL 111 35 0.19 40 P 2 TWD 16 07H -0.93 TEH TEC 14 COLD 60OUL 88 36 0.17 143 P 2 TWD 15 VS4 +0.79 TEH TEC 14 COLD 60OUL 103 37 0.23 97 P 2 TWD 18 DCB +0.00 TEH TEC 14 COLD 60OUL 85 39 0.25 126 P 2 TWD 16 VS2 -0.94 TEH TEC 13 COLD 60OUL 103 39 0.19 171 P 2 TWD 16 DCB +0.00 TEH TEC 14 COLD 60OUL 40 40 0.19 147 P 2 TWD 14 VS3 +0.69 TEH TEC 5 COLD 60OUL 9 41 0.12 169 P 2 TWD 11 04H +0.87 TEH TEC 68 COLD 60OUL 43 41 0.32 129 P 2 TWD 20 VS3 +0.71 TEH TEC 5 COLD 60OUL 63 41 0.26 97 P 2 TWD 17 VS2 +0.70 TEH TEC 5 COLD 60OUL 95 41 0.47 28 P 2 TWD 26 DHT -0.24 TEH TEC 16 COLD 60OUL 119 41 0.17 44 P 2 TWD 13 VS1 -0.63 TEH TEC 16 COLD 60OUL 44 42 0.18 29 P 2 TWD 13 VS3 +0.14 TEH TEC 5 COLD 60OUL 0.17 46 P 2 TWD 13 VS3 +0.64 TEH TEC 5 COLD 60OUL 75 43 0.21 122 P 2 TWD 15 VS2 +0.82 TEH TEC 5 COLD 60OUL 0.23 87 P 2 TWD 16 VS4 -1.04 TEH TEC 5 COLD 600UL 117 43 0.17 159 P 2 TWD 13 VS4 +0.92 TEH TEC 16 COLD 60OUL 64 44 0.13 117 P 2 TWD 11 VS3 +0.89 TEH TEC 5 COLD 60OUL 82 44 1.04 94 P 2 TWD 31 VS2 +0.68 TEH TEC 15 COLD 600UL 0.36 126 P 2 TWD 15 VS3 -0.88 TEH TEC 15 COLD 60OUL 94 44 0.26 140 P 2 TWD 18 VS2 -0.95 TEH TEC 16 COLD 60OUL 0.23 64 P 2 TWD 17 VS2 +0.54 TEH TEC 16 COLD 60OUL 0.35 160 P 2 TWD 22 DCT +0.00 TEH TEC 16 COLD 60OUL 102 44 0.20 69 P 2 TWD 15 DCB +0.00 TEH TEC 16 COLD 60OUL 122 44 0.41 147 P 2 TWD 24 DCT +0.00 TEH TEC 16 COLD 60OUL 0.13 12 P 2 TWD 11 DCB +0.00 TEH TEC 16 COLD 600UL 66 46 0.24 108 P 2 TWD 19 03H +0.97 TEH TEC 6 COLD 60OUL 600UL 124 46 0.21 160 P 2 TWD 9 DCT -0.04 TEH TEC 15 COLD 49 47 0.18 156 P 2 TWD 15 VS3 -0.63 TEH TEC 6 COLD 60OUL 123 47 0.18 118 P 2 TWD 8 VS2 +0.56 TEH TEC 15 COLD 60OUL 125 47 0.30 80 P 2 TWD 13 DCT +0.00 TEH TEC 15 COLD 600UL 3 49 0.37 59 P 2 TWD 25 02C -0.71 07H TEC 67 COLD 580SF 41 49 0.23 125 P 2 TWD 18 VS3 -0.88 TEH TEC 10 COLD 60OUL 75 49 0.16 102 P 2 TWD 13 VS2 -0.72 TEH TEC 7 COLD 60OUL 0.30 118 P 2 TWD 19 VS3 -0.16 TEH TEC 7 COLD 60OUL 121 49 0.25 170 P 2 TWD 18 DCT +0.00 TEH TEC 16 COLD 60OUL 123 49 0.19 161 P 2 TWD 9 VS1 +0.74 TEH TEC 15 COLD 60OUL 125 49 0.16 72 P 2 TWD 7 VS1 +0.85 TEH TEC 15 COLD 60OUL 48 50 0.51 114 P 2 TWD 25 VS3 -0.76 TEH TEC 9 COLD 600UL 0.23 28 P 2 TWD 16 VS3 -0.04 TEH TEC 9 COLD 60OUL 124 50 0.42 154 P 2 TWD 24 VS1 +0.78 TEH TEC 16 COLD 60OUL 0.67 90 P 2 TWD 30 VS2 -0.92 TEH TEC 16 COLD 60OUL 0.25 54 P 2 TWD 18 DHT +0.00 TEH TEC 16 COLD 600UL 126 50 0.36 134 P 2 TWD 15 08H -0.14 TEH TEC 15 COLD 60OUL 0.46 117 P 2 TWD 18 VS1 +0.85 TEH TEC 15 COLD 60OUL 39 51 0.24 149 P 2 TWD 16 VS3 +0.72 TEH TEC 9 COLD 60OUL 61 51 0.12 92 P 2 TWD 11 VS2 -0.28 TEH TEC 10 COLD 60OUL 77 51 0.15 152 P 2 TWD 13 VS4 +0.75 TEH TEC 10 COLD 600UL 125 51 0.44 23 P 2 TWD 25 DHB +2.13 TEH TEC 16 COLD 600UL 127 51 0.15 36 P 2 TWD 7 09H +0.85 TEH TEC 15 COLD 600UL 0.13 130 P 2 TWD 6 04H -0.92 TEH TEC 15 COLD 600UL 46 52 0.16 152 P 2 TWD 14 VS3 -1.00 TEH TEC 10 COLD 60OUL
Framatome ANP Inc. 1/23/2005 08:32 Attachment 7 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 3 of 14 Total Number of Bobbin 1-39% TWD Indications left in service for Cycle 15 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 78 52 0.14 159 P2 TWD 12 VS4 -0.51 TE= TEC 10 COLD 60:==L 0.45 138 P2 TWD 26 VS4 +0.77 TEH TEC 10 COLD 60OUL 84 52 0.20 154 P2 TWD 9 VS2 -0.97 TEH TEC 15 COLD 60OUL 0.91 100 P2 TWD 29 VS3 +0.06 TEH TEC 15 COLD 600UL 0.45 135 P2 TWD 18 VS4 +0.49 TEH TEC 15 COLD 600UL 128 52 0.43 22 P2 TWD 17 DHT +0.14 TEH TEC 15 COLD 600UL 85 53 0.54 51 P2 TWD 28 08H +0.61 TEH TEC 16 COLD 600UL 126 54 0.20 99 P2 TWD 18 VS1 +0.22 TEH TEC 20 COLD 600UL 0.20 142 P2 TWD 18 VS1 +1.29 TEH TEC 20 COLD 600UL 128 54 0.37 105 P2 TWD 17 DHT +0.00 TEH TEC 19 COLD 600UL 49 55 0.34 156 P2 TWD 20 VS3 -0.92 TEH TEC 9 COLD 600UL 51 55 0.06 120 P2 TWD 6 07C -0.06 TEH TEC 10 COLD 600UL 117 55 0.14 28 P2 TWD 14 VS1 +0.74 TEH TEC 20 COLD 600UL 123 55 0.27 134 P2 TWD 14 VS1 -0.95 TEH TEC 19 COLD 600UL 129 55 0.16 127 P2 TWD 15 DCB +0.00 TEB TEC 20 COLD 600UL 78 56 0.20 99 P2 TWD 15 VS3 +0.77 TEH TEC 11 COLD 600UL 0.20 159 P2 TWD 15 VS4 +0.97 TEH TEC 11 COLD 600UL 83 57 0.16 143 P2 TWD 14 VS2 +0.91 TEH TEC 17 COLD 600UL 87 57 0.17 72 P2 TWD 14 VS2 +0.85 TEH TEC 17 COLD 600UL 89 57 0.20 18 P2 TWD 11 VS2 +0.95 TEH TEC 19 COLD 600UL 95 57 0.24 100 P2 TWD 20 VS2 +0.92 TEH TEC 20 COLD 600UL 0.22 95 P2 TWD 19 DHT +0.00 TEH TEC 20 COLD 600UL 123 57 0.22 151 P2 TWD 12 VS1 +0.66 TEH TEC 19 COLD 600UL 127 57 0.22 49 P2 TWD 11 VS1 +0.76 TEH TEC 19 COLD 600UL 129 57 0.51 74 P2 TWD 30 DCT +0.00 TEH TEC 20 COLD 600UL 24 58 0.10 161 P2 TWD 8 VS3 -0.70 TEH TEC 12 COLD 600UL 90 58 0.15 140 P2 TWD 13 DHT +0.00 TEH TEC 17 COLD 600UL 0.28 84 P2 TWD 21 VS3 -0.69 TEH TEC 17 COLD 600UL TWD 96 58 0.20 64 P2 16 VS3 -0.70 TEH TEC 18 COLD 600UL TWD 0.12 101 P2 6 VS3 +0.92 TEH TEC 18 COLD 600UL TWD 0.18 97 P2 13 VS4 -0.14 TEH TEC 18 COLD 600UL TWD 130 58 0.36 119 P2 24 DCB +0.16 TEH TEC 17 COLD 60OUL TWD 132 58 0.36 151 P2 27 DCB +0.28 TEH TEC 53 COLD 600UL TWD 0.45 98 P2 29 DEB +0.08 TEH TEC 53 COLD 600UL TWD COLD 93 59 0.38 136 P2 27 VS4 +0.70 TEH TEC 18 600UL TWD 95 59 0.35 108 P2 23 VS2 +0.87 TEH TEC 17 COLD 600UL TWD 0.08 149 P2 7 VS3 -0.83 TEH TEC 17 COLD 600UL TWD 0.40 131 P2 25 VS3 +0.57 TEH TEC 17 COLD 600UL TWD 125 59 0.11 18 P2 10 VS1 +0.88 TEH TEC 17 COLD 600UL TWD 0.17 13 P2 14 DCT +0.00 TEH TEC 17 COLD 600UL TWD 127 59 0.23 66 P2 18 VS1 -0.27 TEH TEC 18 COLD 600UL TWD 0.32 81 P2 24 VS1 +0.81 TEH TEC 18 COLD 600UL TWD 0.19 90 P2 15 DCT +0.00 TEH TEC 18 COLD 600UL TWD 24 60 0.17 30 P2 13 VS3 -0.68 TEH TEC 11 COLD 600UL TWD 82 60 0.27 146 P2 21 VS3 -0.79 TEH TEC 18 COLD 600UL TWD 96 60 0.16 9 P2 14 DHB +3.36 TEH TEC 17 COLD 600UL TW3D 128 60 0.31 120 P2 22 DHB +0.02 TEE TEC 17 COLD 600UL TWD 0.11 164 P2 10 VS5 -0.90 TEH TEC 17 COLD 60OUL TWD 130 60 0.40 38 P2 25 DHT -0.06 TEH TEC 17 COLD 600UL TWD 41 61 0.17 130 P2 13 VS3 -0.85 TEH TEC 11 COLD 600UL TWD 129 61 0.33 17 P2 23 DHT +0.00 TEH TEC 17 COLD 600UL 24 62 0.21 153 P2 TWD 15 VS3 +0.98 TEE TEC 12 COLD 600UL 36 62 0.17 136 P2 TWD 13 VS3 -0.94 TEH TEC 12 COLD 600UL 44 62 0.11 164 P2 TWD 9 VS3 +0.80 TEH TEC 12 COLD 600UL
Framatome ANP Inc. 1/23/2005 08:32 Attacbment 7 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 4 of 14 Total Number of Bobbin 1-39% TWD Indications left in service for Cycle 15 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 50 62 0.20 69 P 2 TWD 9 VS3 -0.51 TEH TEC 11 COLD 60=UL 78 62 0.61 106 P 2 TWD 28 VS2 +0.65 TEH TEC 11 COLD 60OUL 0.17 339 P 2 TWD 13 VS3 -0.75 TEH TEC 11 COLD 60OUL 0.16 172 P 2 TWD 12 VS4 +0.73 TEH TEC 11 COLD 60OUL 96 62 0.33 103 P 2 TWD 23 VS3 -0.69 TEH TEC 17 COLD 60OUL 134 62 0.15 113 P 2 TWD 16 08H -0.99 TEH TEC 53 COLD 60OUL 0.21 149 P 2 TWD 20 VS3 +0.68 TEH TEC 53 COLD 60OUL 0.22 138 P 2 TWD 21 DHT +0.00 TEH TEC 53 COLD 600UL 0.16 33 P 2 TWD 17 DCT +0.00 TEH TEC 53 COLD 600UL 0.17 157 P 2 TWD 18 07H +0.78 TEH TEC 53 COLD 60OUL 19 63 0.56 41 P 2 TWD 27 VS3 -0.90 TEH TEC 11 COLD 600UL 39 63 0.24 143 P 2 TWD 17 VS3 -0.93 TEH TEC 11 COLD 60OUL 79 63 0.15 114 P 2 TWD 12 VS2 +0.89 TEH TEC 11 COLD 60OUL 0.18 26 P 2 TWD 14 VS3 -0.74 TEH TEC 11 COLD 60OUL 0.15 42 P 2 TWD 12 VS4 +0.89 TEH TEC 11 COLD 600UL 129 63 0.20 58 P 2 TWD 18 VS1 +0.65 TEH TEC 20 COLD 600UL 135 63 0.47 128 P 2 TWD 30 09H +0.73 TEH TEC 53 COLD 60OUL 0.35 85 P 2 TWD 26 DHB +0.00 TEH TEC 53 COLD 60OUL 0.95 61 P 2 TWD 37 VS1 -0.90 TEH TEC 53 COLD 60OUL 0.37 87 P 2 TWD 27 VS1 +0.86 TEH TEC 53 COLD 60OUL 20 64 0.23 58 P 2 TWD 19 VS3 -0.81 TEH TEC 63 COLD 600UL 24 64 0.12 50 P 2 TWD 10 VS3 -0.62 TEH TEC 12 COLD 60OUL 94 64 0.80 70 P 2 TWD 29 VS2 +0.76 TEH TEC 19 COLD 60OUL 0.31 142 P 2 TWD 15 VS2 -0.89 TEH TEC 19 COLD 600UL 0.40 154 P 2 TWD 19 VS3 +0.82 TEH TEC 19 COLD 60OUL 0.36 92 P 2 TWD 17 VS4 -0.87 TEH TEC 19 COLD 60OUL 0.34 90 P 2 TWD 17 VS4 -0.36 TEH TEC 19 COLD 60OUL 128 64 0.53 125 P 2 TWD 23 VS1 +0.69 TEH TEC 19 COLD 600UL 130 64 0.18 99 P 2 TWD 16 VS1 +0.70 TEH TEC 20 COLD 60OUL 132 64 0.14 160 P 2 TWD 10 07H +0.57 TEH TEC 52 COLD 60OUL 0.43 97 P 2 TWD 24 DHT +0.00 TEH TEC 52 COLD 60OUL 27 65 0.30 109 P 2 TWD 19 DHB +0.02 TEH TEC 11 COLD 60OUL 47 65 0.24 155 P 2 TWD 17 VS3 -0.70 TEH TEC 12 COLD 60OUL 38 66 0.19 114 P 2 TWD 14 VS3 +0.74 TEH TEC 11 COLD 60OUL 52 66 0.15 17 P 2 TWD 12 VS3 -0.90 TEH TEC 11 COLD 600UL 124 66 0.17 165 P 2 TWD 9 VS1 +0.79 TEH TEC 19 COLD 60OUL 31 67 0.57 91 P 2 TWD 27 DCB +0.00 TEH TEC 11 COLD 60OUL 33 67 0.23 98 P 2 TWD 16 DCB +0.00 TEH TEC 12 COLD 60OUL 37 67 0.10 121 P 2 TWD 8 VS3 +0.73 TEH TEC 12 COLD 600UL 0.17 152 P 2 TWD 13 DCB +0.00 TEH TEC 12 COLD 60OUL 57 67 0.10 150 P 2 TWD 8 VS3 +0.82 TEH TEC 12 COLD 60OUL 79 67 0.31 128 P 2 TWD 20 VS2 -0.83 TEH TEC 11 COLD 600UL 0.44 121 P 2 TWD 24 VS4 +0.63 TEH TEC 11 COLD 60OUL 89 67 0.18 160 P 2 TWD 10 VS4 +0.99 TEH TEC 19 COLD 600UL 91 67 0.18 64 P 2 TWD 17 VS2 +0.73 TEH TEC 20 COLD 60OUL 133 67 0.35 79 P 2 TWD 26 VS1 +0.62 TEH TEC 53 COLD 60OUL 34 68 0.35 117 P 2 TWD 21 DHB +0.00 TEH TEC 12 COLD 60OUL 64 68 0.11 156 P 2 TWD 9 VS3 +0.83 TEH TEC 11 COLD 600UL 80 68 0.08 10 P 2 TWD 7 VS4 +0.89 TEH TEC 11 COLD 600UL 132 68 0.17 135 P 2 TWD 13 VS2 -1.00 TEH TEC 52 COLD 60OUL 35 69 0.17 23 P 2 TWD 13 DHT -0.18 TEH TEC 64 COLD 60OUL 0.79 86 P 2 TWD 34 DCB +0.67 TEH TEC 64 COLD 60OUL 0.50 120 P 2 TWD 27 DHB +0.25 TEH TEC 64 COLD 60OUL 37 69 0.40 124 P 2 TWD 26 DHB +0.37 TEH TEC 64 COLD 60OUL
Framatome ANP Inc. 1/23/2005 08:32 Attachment 7 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: SIG A Page 5 of 14 Total Number of Bobbin 1-39% TWD Indications left in service for Cycle 15 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL t LEG PROBE 0.83 101 P2 T== 35 DCB +0.47 TEH TEC 64 COLD 60.UL 137 69 0.19 164 P2 TWD 19 07H +0.65 TEH TEC 53 COLD 60OUL 40 70 0.27 70 P2 TWD 21 DHB +0.43 TEH TEC 64 COLD 60OUL 0.23 120 P2 TWD 19 DCT -0.24 TEH TEC 64 COLD 600UL 42 70 0.23 22 P2 TWD 19 DCT -0.14 TEH TEC 64 COLD 60OUL 0.83 108 P2 TWD 35 DCB +0.28 TEH TEC 64 COLD 600UL 44 70 0.54 112 P2 TWD 28 DCB +0.00 TEC TEN 4 HOT 600UL 50 70 0.30 98 P2 TWD 21 DCB +0.00 TEC TEH 4 HOT 600UL 0.25 119 P2 TWD 19 VS3 -0.71 TEC TEH 4 HOT 60OUL 84 70 0.28 150 P2 TWD 20 07H +0.89 TEH TEC 21 COLD 60OUL 136 70 0.74 142 P2 TWD 31 VS1 -0.84 TEH TEC 52 COLD 60OUL 0.21 139 P2 TWD 15 VS2 +0.92 TEH TEC 52 COLD 60OUL 0.62 104 P2 TWD 29 VS3 -0.74 TEH TEC 52 COLD 600UL 0.14 165 P2 TWD 11 VS5 -0.90 TEH TEC 52 COLD 600UL 39 71 0.39 126 P2 TWD 24 DCB +0.35 TEH TEC 64 COLD 60OUL 41 71 0.20 122 P2 TWD 17 DCB +0.57 TEH TEC 64 COLD 60O0UL 43 71 0.41 43 P2 TWD 25 DCB +0.00 TEC TEH 4 HOT 60OUL 45 71 0.55 132 P2 TWD 27 DCB +0.47 TEC TEH 3 HOT 60OUL 51 71 0.26 65 P2 TWD 20 DCT +0.00 TEC TEH 4 HOT 60OUL 89 71 0.22 118 P2 TWD 16 VS2 +0.98 TEH TEC 21 COLD 60OUL 95 71 0.31 39 P2 TWD 19 VS2 +0.79 TEH TEC 22 COLD 600UL 135 71 0.27 47 P2 TWD 18 VS1 -0.90 TEH TEC 52 COLD 60OUL 42 72 0.71 101 P2 TWD 31 DCT +0.00 TEC TEN 4 HOT 600UL 1.07 84 P2 TWD 35 DHB +0.00 TEC TEH 4 HOT 60OUL TWD 0.20 115 P2 16 VS3 +0.75 TEC TEH 4 HOT 600UL TWD 0.16 104 P2 14 VS3 -0.83 TEC TEH 4 HOT 600UL TWD 44 72 0.41 134 P2 23 DHB +0.35 TEC TEH 3 HOT 600UL TWD 46 72 0.20 85 P2 17 DCB +0.00 TEC TEH 4 HOT 60OUL TWD 48 72 0.21 28 P2 16 DCT +0.00 TEC TEH 3 HOT 60OUL TWD 0.22 137 P2 17 VS3 +0.66 TEC TEH 3 HOT 600UL TWD 50 72 0.49 101 P2 27 DCB +0.00 TEC TEH 4 HOT 600UL TWD 52 72 0.15 147 P2 7 DCT +0.00 TEC TEH 3 HOT 60OUL TWD 54 72 0.19 160 P2 16 VS3 +0.88 TEC TEH 4 HOT 600UL TWD 64 72 0.19 140 P2 13 VS4 -0.82 TEC TEH 3 HOT 60OUL TWD 82 72 0.23 161 P2 TWD 17 VS3 -0.78 TEH TEC 21 COLD 60O0UL 94 72 0.11 171 P2 TWD 8 VS2 +0.86 TEH TEC 22 COLD 60OUL 0.12 168 P2 TWD 9 VS4 +0.92 TEN TEC 22 COLD 600UL 126 72 0.35 64 P2 TWD 21 08H +0.90 TEH TEC 22 COLD 60OUL 0.18 31 P2 TWD 13 09H +0.10 TEH TEC 22 COLD 60OUL 134 72 0.40 49 P2 TWD 23 VS1 +0.82 TEH TEC 52 COLD 60OUL 43 73 0.20 43 P2 TWD 15 DHT +0.00 TEC TEC 3 HOT 60OUL 0.31 93 P2 TWD 19 DCB +0.26 TEC TEH 3 HOT 60OUL 0.47 81 P2 TWD 25 DHB +0.37 TEC TEH 3 HOT 60OUL 49 73 0.51 121 P2 TWD 28 DCB +0.00 TEC TEH 4 HOT 60OUL 0.18 76 P2 TWD 15 DCT +0.00 TEC TEH 4 HOT 60OUL 51 73 0.32 96 P2 TWD 20 DCB +0.21 TEC TEH 3 HOT 60OUL 53 73 0.33 51 P2 TWD 22 DCB +0.00 TEC TEH 4 HOT 60OUL 55 73 0.16 156 P2 TWD 12 DCB +0.35 TEC TEH 3 HOT 60OUL 0.20 109 P2 TWD 14 VS3 -0.12 TEC TEH 3 HOT 60OUL 75 73 0.16 156 P2 TWD 13 VS3 +0.83 TEC TEH 3 HOT 60OUL 83 73 0.18 163 P2 15 05H +1.02 TEH TEC 21 COLD 600UL 133 73 0.14 149 P2 TWD 15 VS1 -0.56 TEH TEC 53 COLD 60OUL TWD 135 73 0.81 59 P2 32 VS1 +0.80 TEH TEC 52 COLD 60OUL TWD 0.32 121 P2 20 VS2 +0.66 TEH TEC 52 COLD 60OUL
Framatome ANP Inc. 1/23/2005 08:32 AttacS-ent 7 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: SIG A Page 6 of 14 Total Number of Bobbin 1-39% TWD Indications left in service for Cycle 15 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 0.61 24 P2 TWD 28 VS3 +0.70 TEH TEC 52 COLD 60=OUL 1.11 132 P2 TWD 35 VS4 +0.78 TEH TEC 52 COLD 600UL 0.15 19 P2 TWD 12 VS5 +0.80 TEH TEC 52 COLD 600VL 0.20 62 P2 TWD 15 VS1 -0.76 TEH TEC 52 COLD 600UL 46 74 0.40 71 P2 TWD 25 DHB +0.00 TEC TEC 4 HOT 60OUL 48 74 0.33 105 P2 TWD 20 DCT -0.25 TEC TEH 3 HOT 60OUL 52 74 0.22 66 P2 TWD 17 DCT +0.00 TEC TEH 3 HOT 60OUL 54 74 0.30 154 P2 TWD 21 DCT +0.00 TEC TEH 4 HOT 600UL 0.20 118 P2 TWD 17 VS3 -0.92 TEC TEH 4 HOT 60OUL 56 74 0.19 163 P2 TWD 15 VS3 +0.70 TEC TEH 3 HOT 60OUL 62 74 0.24 62 P2 TWD 18 VS4 -0.71 TEC TEH 4 HOT 60OUL 82 74 0.50 124 P2 TWD 27 VS2 -0.76 TEH TEC 21 COLD 600UL 126 74 0.13 36 P2 TWD 9 VS2 +0.89 TEH TEC 22 COLD 60OUL 45 75 0.18 137 P2 TWD 14 DCB +0.00 TEC TEN 3 NOT 60OUL 0.37 118 P2 TWD 23 DCT +0.00 TEC TEH 3 HOT 60OUL 0.58 101 P2 TWD 29 DHT +0.00 TEC TEH 3 HOT 600UL 0.24 104 P2 TWD 17 DHB +0.00 TEC TEH 3 HOT 60OUL 49 75 0.16 162 P2 TWD 13 DHB +0.00 TEC TEH 3 HOT 60OUL 57 75 0.44 89 P2 TWD 25 VS3 -0.60 TEC TEH 3 HOT 600UL 93 75 0.48 81 P2 TWD 27 VS2 -0.39 TEH TEC 21 COLD 60OUL 133 75 0.32 123 P2 TWD 25 VS1 +0.66 TEH TEC 53 COLD 60OUL 46 76 0.48 116 P2 TWD 27 DCT +0.00 TEC TEC 4 HOT 600UL 0.72 71 P2 TWD 32 DHT +0.00 TEC TEH 4 HOT 60OUL 0.83 94 P2 TWD 33 DHB +0.00 TEC TEH 4 HOT 60OUL 48 76 0.34 86 P2 TWD 22 DCB +0.00 TEC TEH 3 HOT 60OUL 0.35 87 P2 TWD 21 DHB +0.19 TEC TEH 3 HOT 60OUL 58 76 0.37 104 P2 TWD 24 DCB +0.00 TEC TEH 4 HOT 60OUL 94 76 0.23 25 P2 TWD 18 VS3 -0.42 TEH TEC 21 COLD 600UL 112 76 0.13 65 P2 TWD 9 VS2 -0.67 TEH TEC 22 COLD 600UL 134 76 0.11 56 P2 TWD 9 VS5 -1.00 TEH TEC 52 COLD 600UL 136 76 0.31 134 P2 TWD 20 DCT +0.00 TEH TEC 52 COLD 60OUL 51 77 1.25 97 P2 TWD 37 DCT +0.00 TEC TEN 4 HOT 60OUL 53 77 1.34 19 P2 TWD 38 DHT +0.00 TEC TEH 3 HOT 600UL 0.91 93 P2 TWD 34 DHB +0.00 TEC TEH 3 HOT 60OUL 0.37 115 P2 TWD 21 DCT +0.00 TEC TEH 3 HOT 60OUL 57 77 0.43 123 P2 TWD 25 DCT +0.00 TEC TEH 3 HOT 600UL 73 77 0.25 150 P2 TWD 19 VS2 +0.84 TEC TEH 4 HOT 60OUL TWD 0.30 82 P2 21 VS2 -0.86 TEC TEH 4 HOT 600UL TWD 79 77 0.12 156 P2 10 VS2 -0.79 TEC TEH 3 HOT 600UL TWD 93 77 0.31 86 P2 20 DCB +0.46 TEH TEC 54 COLD 60OUL TWD 133 77 0.20 138 P2 20 VS5 +0.77 TEH TEC 53 COLD 60OUL TWD 48 78 0.15 120 P2 12 DHT +0.00 TEC TEC 3 NOT 60OUL TWD 0.54 29 P2 28 DHB +0.00 TEC TEH 3 HOT 600UL TWD 52 78 0.25 108 P2 17 DHB +0.23 TEC TEH 3 HOT 600UL TWD 56 78 1.05 90 P2 35 DCB +0.00 TEC TEH 4 HOT 60OUL TWD 0.15 147 P2 14 VS3 +0.77 TEC TEH 4 HOT 60OUL TWD 60 78 0.10 132 P2 9 VS4 -0.66 TEC TEH 4 HOT 60OUL TWD 0.15 142 P2 13 VS3 +0.78 TEC TEH 4 HOT 60OUL TWD 96 78 0.79 86 P2 33 VS3 -0.83 TEH TEC 54 COLD 60OUL TWD 116 78 0.17 157 P2 12 VS1 -0.73 TEH TEC 23 COLD 60OUL TWD 49 79 0.76 103 P2 32 DCT +0.00 TEC TEH 5 HOT 600UL TWD 1.12 81 P2 36 VS3 +0.97 TEC TEH 5 HOT 60OUL TWD 0.77 56 P2 32 VS3 -0.10 TEC TEH 5 HOT 60OUL TWD 0.86 82 P2 33 DHT +0.00 TEC TEH 5 HOT 60OUL
Framatome ANP Inc. 1/23/2005 08:32 Attacbment 7 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 7 of 14 Total Number of Bobbin 1-39% TWD Indications left in service for Cycle 15 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 51 79 0.95 104 P2 TWD 34 DCT +0.00 TEC TEH 6 HOT 60OOUL 0.44 152 P2 TWD 26 DHT +0.00 TEC TEH 6 HOT 60OUL 53 79 0.35 117 P2 TWD 21 DCT +0.00 TEC TEH 5 HOT 600UL 61 79 0.91 102 P2 TWD 34 DCB +0.00 TEC TEH 6 HOT 60OUL 63 79 0.16 60 P2 TWD 13 DCB +0.00 TEC TEH 5 HOT 600UL 125 79 0.22 108 P2 TWD 14 VS1 -0.85 TEH TEC 23 COLD 60OUL 131 79 0.15 159 P2 TWD 9 VS4 -0.90 TEH TEC 54 COLD 60OUL 62 80 0.94 69 P2 TWD 34 DCB +0.00 TEC TEH 5 NOT 600UL 53 81 0.77 75 P2 TWD 32 DCT +0.00 TEC TEH 5 HOT 60OUL 0.31 159 P2 TWD 20 DHT +0.00 TEC TEH 5 HOT 600UL 0.53 50 P2 TWD 27 DHB +0.00 TEC TEH 5 HOT 60OUL 59 81 0.38 110 P2 TWD 23 DCB +0.00 TEC TEH 5 HOT 600UL 61 81 0.19 139 P2 TWD 15 DCB +0.00 TEC TEH 6 HOT 60OUL 50 82 0.57 79 P2 TWD 28 DCB +0.00 TEC TEH 5 HOT 600UL 0.16 97 P2 TWD 13 DCT +0.00 TEC TEB 5 HOT 600UL 0.21 20 P2 TWD 16 DHT +0.00 TEC TEH 5 HOT 60OUL 0.21 101 P2 TWD 16 DHB +0.00 TEC TEH 5 HOT 60OUL 56 82 0.40 46 P2 TWD 24 DCT +0.00 TEC TEH 6 HOT 60OUL 60 82 0.16 71 P2 TWD 13 DCB +0.00 TEC TEH 6 HOT 60OUL 0.65 119 P2 TWD 30 DHB +0.00 TEC TEH 6 HOT 600UL 51 83 0.46 112 P2 TWD 25 DCB +0.00 TEC TEH 5 HOT 600UL 0.19 151 P2 TWD 15 DCT +0.00 TEC TEH 5 HOT 600UL 0.56 108 P2 TWD 28 DHB +0.00 TEC TEH 5 HOT 60OUL 61 83 0.12 14 P2 TWD 10 DCB +0.00 TEC TEH 6 HOT 60OUL 85 83 0.34 89 P2 TWD 22 VS2 -1.38 TEH TEC 25 COLD 60OUL 0.21 137 P2 TWD 16 VS3 +0.63 TEH TEC 25 COLD 60OUL 135 83 0.21 137 P2 TWD 20 VS1 -0.77 TEH TEC 53 COLD 600UL 52 84 0.54 107 P2 TWD 27 DCT +0.00 TEC TEN 5 HOT 60OUL 56 84 0.51 77 P2 TWD 27 DCB +0.00 TEC TEH 6 HOT 600UL 600UL 76 84 0.28 142 P2 TWD 19 VS3 +0.81 TEC TEH 5 HOT 61 85 0.37 95 P2 TWD 24 DCB +0.00 TEC TEH 6 HOT 60OUL 75 85 0.29 128 P2 TWD 19 VS3 +0.75 TEC TEH 5 HOT 60OUL 77 85 0.27 33 P2 TWD 20 VS4 +0.82 TEC TEH 6 HOT 60OUL 54 86 0.33 121 P2 TWD 22 DCT +0.00 TEC TEH 6 HOT 60OUL 0.24 159 P2 TWD 18 VS3 +1.04 TEC TEH 6 HOT 60OUL TWD 0.60 83 P2 29 VS3 -0.69 TEC TEH 6 HOT 60OUL TWD 0.31 79 P2 21 DHB +0.00 TEC TEH 6 HOT 60OUL TWD 56 86 1.11 110 P2 36 DCB +0.00 TEC TEH 5 HOT 60OUL TWD 58 86 0.93 125 P2 34 DCB +0.00 TEC TEH 6 HOT 60OUL TWD 60 86 0.33 84 P2 21 DHB +0.00 TEC TEH 5 HOT 600UL TWD 62 86 0.34 152 P2 22 DCB +0.00 TEC TEH 6 HOT 60OUL TWD 0.24 98 P2 18 VS3 -0.80 TEC TEH 6 HOT 60OUL TWD 92 86 0.56 135 P2 28 VS2 +0.88 TEH TEC 25 COLD 60OUL TWD 1.19 130 P2 36 VS3 -0.84 TEH TEC 25 COLD 60OUL TWD 0.30 149 P2 20 VS4 -0.86 TEH TEC 25 COLD 60OUL TWD 0.24 51 P2 18 VS4 +0.82 TEH TEC 25 COLD 600UL TWD 126 86 0.12 152 P2 10 09H -0.84 TEH TEC 26 COLD 60OUL TWD 49 87 1.36 107 P2 37 DCT +0.00 TEC TEN 6 HOT 600UL TWD 0.49 82 P2 27 DHB +0.00 TEC TEH 6 HOT 600UL TWD 51 87 0.85 55 P2 33 DCT +0.00 TEC TEH 5 HOT 60OUL TWD 0.17 150 P2 13 DCB +0.00 TEC TEH 5 HOT 600UL TWD 0.59 136 P2 28 DHB +0.00 TEC TEH 5 HOT 600UL TWD 55 87 0.26 157 P2 18 DCB +0.00 TEC TEH 5 HOT 600UL TWD 0.49 55 P2 26 DCT +0.00 TEC TEH 5 HOT 600UL
Framatome ANP Inc. 1/23/2005 08:32 Attachment 7 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 8 of 14 Total Number of Bobbin 1-39% TWD Indications left in service for Cycle 15 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 0.49 125 P2 TWD 26 VS3 -0.85 TEC TEH 5 HOT 60:UL 0.51 80 P2 TWD 27 DHB +0.00 TEC TEH 5 HOT 60OUL 57 87 0.68 119 P2 TWD 31 DCB +0.00 TEC TEH 6 HOT 60OUL 59 87 0.47 103 P2 TWD 25 DHB +0.00 TEC TEH 5 HOT 60OUL 93 87 0.40 47 P2 TWD 24 VS2 -0.98 TEC TEC 25 COLD 600UL 0.24 170 P2 TWD 18 VS2 +0.58 TEH TEC 25 COLD 60OUL 0.29 134 P2 TWD 20 VS4 +1.00 TEH TEC 25 COLD 60OUL 97 87 0.38 82 P2 TWD 23 VS2 -0.66 TEH TEC 25 COLD 60OUL 0.31 124 P2 TWD 21 VS3 +0.78 TEH TEC 25 COLD 600UL 111 87 0.11 55 P2 TWD 10 VS2 -0.93 TEH TEC 25 COLD 60OUL 50 88 0.97 87 P2 TWD 34 DCB +0.00 TEC TEC 6 HOT 600UL 0.14 109 P2 TWD 12 DCT +0.00 TEC TEH 6 HOT 60OUL 600UL 0.89 99 P2 TWD 34 DHT +0.00 TEC TEH 6 HOT 52 88 0.54 99 P2 TWD 27 DCB +0.00 TEC TEH 5 HOT 60OUL 0.59 139 P2 TWD 28 DCT +0.00 TEC TEH 5 HOT 600UL 54 88 0.22 51 P2 TWD 17 DCB +0.00 TEC TEH 6 HOT 60OUL 56 88 0.48 138 P2 TWD 26 DCT +0.00 TEC TEH 5 HOT 600UL 94 88 0.28 106 P2 TWD 20 VS2 -0.80 TEN TEC 26 COLD 600UL 0.12 139 P2 TWD 10 VS3 -0.96 TEH TEC 26 COLD 60OUL 0.35 117 P2 TWD 23 VS4 +0.74 TEH TEC 26 COLD 600UL 49 89 0.27 114 P2 TWD 19 DCB +0.00 TEC TEN 5 HOT 60OUL 51 89 0.21 45 P2 TWD 17 DCB +0.00 TEC TEH 6 HOT 60OUL 53 89 0.24 102 P2 TWD 17 DCT +0.00 TEC TEH 5 HOT 60OUL 0.56 131 P2 TWD 28 DHB +0.00 TEC TEH 5 HOT 60OUL 57 89 0.14 122 P2 TWD 11 04H +0.93 TEC TEH 5 HOT 600UL 73 89 0.18 88 P2 TWD 14 VS3 +0.65 TEC TEH 5 HOT 60OUL 83 89 0.22 86 P2 TWD 17 VS2 +0.74 TEN TEC 25 COLD 60OUL 0.17 83 P2 TWD 14 VS3 -0.90 TEH TEC 25 COLD 60OUL 0.23 115 P2 TWD 17 VS4 -0.68 TEH TEC 25 COLD 60OUL 0.24 130 P2 TWD 18 VS3 +0.92 TEH TEC 25 COLD 600UL 95 89 0.21 93 P2 TnD 16 VS2 -0.94 TEH TEC 25 COLD 60OUL 0.26 22 P2 TWD 19 VS2 +0.50 TEH TEC 25 COLD 600UL 0.41 118 P2 TWD 24 VS4 -0.60 TEH TEC 25 COLD 60OUL 600UL 46 90 0.30 143 P2 TWD 21 DCB +0.00 TEC TEH 6 HOT 0.58 118 P2 TWD 29 DCT +0.00 TEC TEH 6 HOT 60OUL 0.34 85 P2 TWD 22 DHT +0.00 TEC TEH 6 HOT 600UL 48 90 0.33 139 P2 TWD 21 DCT +0.00 TEC TEH 5 HOT 600UL 0.35 122 P2 TWD 22 DCB +0.00 TEC TEH 5 HOT 60OUL 50 90 0.29 96 P2 TWD 21 DCB +0.00 TEC TEH 6 HOT 60OUL 0.13 90 P2 TWD 11 05H +0.96 TEC TEH 6 HOT 60OUL 54 90 0.24 130 P2 TWD 18 DCB +0.00 TEC TEH 6 HOT 600UL 0.23 76 P2 TWD 18 VS3 -0.62 TEC TEH 6 HOT 600UL 82 90 0.32 75 P2 TWD 21 VS3 -0.64 TEC TEC 25 COLD 60OUL 92 90 0.22 144 P2 TWD 17 VS2 +0.80 TEH TEC 25 COLD 600UL TWD 45 91 0.75 86 P2 31 DHB +0.04 TEC TEH 5 HOT 60OUL TWD 0.36 60 P2 22 DCT +0.00 TEC TEH 5 HOT 600UL TWD 0.66 173 P2 30 DHT +0.00 TEC TEH 5 HOT 60OUL TWD 47 91 0.53 57 P2 28 DHB +0.00 TEC TEH 6 HOT 60OUL TWD 51 91 0.40 78 P2 24 DHB +0.00 TEC TEH 6 HOT 60OUL TWD 57 91 0.29 107 P2 19 DHB +0.00 TEC TEH 5 HOT 6QOUL TWD 139 91 0.26 133 P2 23 VS5 +0.72 TEH TEC 56 COLD 60OUL TWD 0.75 95 P2 35 DHT +0.00 TEH TEC 56 COLD 60OUL TWD 1.25 17 P2 39 DCT +0.00 TEH TEC 56 COLD 60OUL TWD 56 92 0.62 8 P2 30 DHT +0.00 TEC TEH 6 HOT 60OUL
Framatome ANP Inc. 1/23/2005 08:32 Attac}ment 7 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 9 of 14 Total Number of Bobbin 1-39% TWD Indications left in service for Cycle 15 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 58 92 0.38 102 P 2 TWD 23 DCB +0.00 TEC TEH 5 HOT 60OOUL 132 92 0.36 127 P 2 TWD 22 VS1 +0.98 TEH TEC 55 COLD 60OUL 43 93 0.19 63 P 2 TWD 14 VS3 +1.00 TEC TEH 5 HOT 600UL 0.32 93 P 2 TWD 20 DHB +0.00 TEC TEH 5 HOT 60OUL 0.61 131 P 2 TWD 29 DCB +0.00 TEC TEH 5 HOT 60OUL 45 93 0.38 85 P 2 TWD 24 DCB +0.00 TEC TEH 6 HOT 60OUL 55 93 0.23 132 P 2 TWD 16 DCB +0.06 TEC TEH 5 HOT 60OUL 97 93 0.21 157 P 2 TWD 18 VS2 -0.81 TEH TEC 28 COLD 60OUL 0.37 137 P 2 TWD 26 VS3 +0.67 TEH TEC 28 COLD 60OUL 0.19 62 P 2 TWD 17 VS4 +0.63 TEH TEC 28 COLD 600UL 0.12 91 P 2 TWD 12 VS2 +0.22 TEH TEC 28 COLD 60OUL 44 94 0.10 141 P 2 TWD 9 DCB +0.00 TEC TEH 6 HOT 600UL 0.50 114 P 2 TWD 27 DHB +0.00 TEC TEH 6 HOT 60OUL 48 94 0.15 125 P 2 TWD 13 VS3 -0.87 TEC TEH 6 HOT 600UL 52 94 0.17 104 P 2 TWD 14 VS3 +0.00 TEC TEH 6 HOT 60OUL 82 94 0.15 154 P 2 TWD 12 VS2 +0.97 TEH TEC 55 COLD 60OUL 0.16 140 P 2 TWD 13 VS4 +0.93 TEH TEC 55 COLD 60OUL 86 94 0.13 35 P 2 TWD 11 VS4 +0.84 TEH TEC 27 COLD 600UL 43 95 0.28 92 P 2 TWD 20 VS3 +1.04 TEC TEH 6 HOT 60OUL 49 95 0.39 50 P 2 TWD 23 DCT -0.06 TEC TEH 5 HOT 60OUL 0.27 137 P 2 TWD 18 VS3 +1.09 TEC TEH 5 HOT 60OUL 0.49 125 P 2 TWD 26 VS3 -0.60 TEC TEH 5 HOT 60OUL 51 95 0.16 154 P 2 TWD 13 DCB +0.00 TEC TEH 6 HOT 60OUL 53 95 0.14 123 P 2 TWD 11 DCB -0.19 TEC TEH 5 HOT 60OUL 135 95 0.26 140 P 2 TWD 17 VS1 -0.94 TEH TEC 55 COLD 60OUL 38 96 1.00 99 P 2 TWD 35 DCB +0.00 TEC TEH 6 HOT 60OUL 0.37 122 P 2 TWD 24 DCT +0.00 TEC TEH 6 HOT 60OUL 600UL 0.17 90 P 2 TWD 14 DHB +0.00 TEC TEH 6 HOT 0.65 84 P 2 TWD 30 DHT +0.00 TEC TEH 6 HOT 60OUL 42 96 0.19 155 P 2 TWD 15 VS3 -0.87 TEC TEH 6 HOT 60O0UL 0.84 94 P 2 TWD 33 DHT +0.00 TEC TEH 6 HOT 60OUL 44 96 0.22 80 P 2 TWD 17 DCT +0.00 TEC TEH 5 HOT 60OUL 48 96 0.44 130 P 2 TWD 25 VS3 -0.99 TEC TEH 5 HOT 60OUL 0.37 132 P 2 TWD 22 VS3 +0.77 TEC TEH 5 HOT 60OUL 54 96 0.42 97 P 2 TWD 25 VS3 -0.70 TEC TEH 6 HOT 600UL 94 96 0.73 82 P 2 TWD 31 VS2 -0.90 TEH TEC 27 COLD 60OUL 0.26 113 P 2 TWD 18 VS3 -0.54 TEH TEC 27 COLD 600UL 0.47 153 P 2 TWD 26 VS4 +0.68 TEN TEC 27 COLD 600UL 41 97 0.26 108 P 2 TWD 19 DCB +0.00 TEC TEH 6 HOT 600UL 0.27 106 P 2 TWD 20 DHB +0.00 TEC TEH 6 HOT 60OUL 43 97 0.20 108 P 2 TWD 15 DCT +0.00 TEC TEH 5 HOT 60OUL 0.39 144 P 2 TWD 23 DCB +0.00 TEC TEH 5 HOT 60OUL 45 97 0.15 121 P 2 TWD 13 DCB +0.00 TEC TEH 6 HOT 60OUL 0.39 90 P 2 TWD 24 DCT +0.00 TEC TEH 6 HOT 60OUL 0.25 125 P 2 TWD 19 VS3 +0.85 TEC TEH 6 HOT 60OUL 47 97 0.40 112 P 2 TWD 23 DCB +0.00 TEC TEH 5 HOT 60OUL 0.59 129 P 2 TWD 28 VS3 +1.07 TEC TEH 5 HOT 60OUL 57 97 0.12 146 P 2 TWD 10 VS3 +0.68 TEC TEH 6 HOT 60OUL 87 97 0.13 15 P 2 TWD 13 VS4 -0.56 TEN TEC 28 COLD 60OUL 135 97 0.48 48 P 2 TWD 25 VS1 -0.82 TEH TEC 55 COLD 60OUL 0.60 63 P 2 TWD 28 VS3 +0.94 TEH TEC 55 COLD 60OUL 0.41 107 P 2 TWD 23 VS5 +0.04 TEH TEC 55 COLD 600UL 137 97 0.06 142 P 2 TWD 9 DCB +0.40 TEH TEC 56 COLD 60OUL 42 98 0.31 91 P 2 TWD 22 DCB +0.00 TEH TEC 62 COLD 600UL
Pramatome ANP Inc. 1/23/2005 08:32 Attachment 7 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 11 of 14 Total Number of Bobbin 1-39% TWD Indications left in service for Cycle 15 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 125 107 0.20 82 P 2 TWD 16 VS1 +0.94 TE= TEC 35 COLD 60:UL 127 107 0.20 17 P 2 TWD 17 DCT -0.02 TEH TEC 36 COLD 60OUL 42 108 0.13 157 P 2 TWD 14 VS3 +0.10 TEH TEC 41 COLD 600UL 48 108 0.13 164 P 2 TWD 14 VS3 -0.83 TEH TEC 42 COLD 60OUL 96 108 0.46 122 P 2 TWD 28 VS2 -0.72 TEH TEC 36 COLD 600UL 0.22 157 P 2 TWD 18 VS2 +0.81 TEH TEC 36 COLD 60OUL 0.65 114 P 2 TWD 33 VS3 -0.68 TEH TEC 36 COLD 60OUL TWD 0.34 101 P 2 23 VS4 +0.68 TEH TEC 36 COLD 60OUL 100 108 0.13 144 P 2 IWD 12 DCT +0.00 TEH TEC 36 COLD 60OUL 132 108 0.34 34 P 2 TWD 21 DCB +0.00 TEH TEC 55 COLD 60OUL 39 109 0.09 111 P 2 TWD 11 VS3 +0.93 TEH TEC 41 COLD 60OUL 101 109 0.24 33 P 2 TWD 17 VS3 +0.87 TEH TEC 33 COLD 60OUL 129 109 0.23 153 P 2 TWD 17 VS1 -0.88 TEH TEC 33 COLD 600UL 133 109 0.21 145 P 2 TWD 21 DHT +0.00 TEH TEC 56 COLD 60OUL 0.13 166 P 2 TWD 15 07C -0.94 TEH TEC 56 COLD 600UL TWD 8 110 0.16 41 P 2 13 06H +0.69 TEH TEC 50 COLD 600UL TWD 78 110 0.10 11 P 2 10 06H +0.96 TEH TEC 46 COLD 60OUL TWD 132 110 0.15 161 P 2 17 VS5 -0.87 TEH TEC 56 COLD 60OUL TWD 33 111 0.20 77 P 2 18 VS3 +0.85 TEH TEC 42 COLD 60OUL TWD 45 111 0.13 20 P 2 13 VS3 +0.89 TEH TEC 42 COLD 60OUL TWD 87 111 0.27 156 P 2 18 VS3 -0.86 TEH TEC 33 COLD 60OUL TWD 46 112 0.31 59 P 2 24 VS3 +0.67 TEH TEC 42 COLD 60OUL TWD 82 112 0.15 100 P 2 17 VS2 -0.02 TEH TEC 34 COLD 60OUL TWD 0.15 161 P 2 16 VS2 +0.76 TEH TEC 34 COLD 60OUL TWD 0.28 140 P 2 24 VS4 +0.62 TEH TEC 34 COLD 60OUL TWD 88 112 0.16 28 P 2 13 VS4 -0.93 TEH TEC 55 COLD 60OUL TWD 0.26 155 P 2 18 VS3 -0.95 TEH TEC 55 COLD 600UL TWD 0.18 160 P 2 14 VS2 +0.87 TEH TEC 55 COLD 600UL TWD 92 112 0.12 116 P 2 10 VS3 -1.00 TEH TEC 33 COLD 600UL P 2 TWD TEC 31 113 0.13 18 14 VS3 -0.34 TEH 42 COLD 60OUL TWD 51 113 0.32 111 P 2 TWD 24 VS3 +0.87 TEH TEC 41 COLD 60OUL 53 113 0.23 132 P 2 TWD 20 VS3 +0.99 TEH TEC 41 COLD 60OUL 123 113 0.29 50 P 2 TWD 24 VS1 -0.74 TEH TEC 34 COLD 60OUL 0.26 138 P 2 TWD 23 VS3 +0.78 TEH TEC 34 COLD 60OUL 0.31 147 P 2 TWD 25 VS4 +1.02 TEH TEC 34 COLD 600UL 0.09 28 P 2 TWD 12 VS5 +1.00 TEH TEC 34 COLD 600UL 84 114 0.34 77 P 2 TWD 21 VS4 -0.88 TEH TEC 33 COLD 600UL 41 115 0.10 167 P 2 TWD 11 VS3 +0.99 TEH TEC 41 COLD 600UL 47 115 0.30 118 P 2 TWD 23 VS3 +0.97 TEH TEC 41 COLD 60OUL 0.41 154 P 2 TWD 26 VS3 -0.79 TEH TEC 41 COLD 60OUL 125 115 0.12 166 P 2 TWD 14 VS1 +0.98 TEN TEC 34 COLD 60OUL 54 116 0.08 194 P 2 TWD 9 VS3 -0.73 TEH TEC 40 COLD 600UL 76 116 0.07 155 P 2 TWD 9 VS3 +0.63 TEH TEC 45 COLD 60OUL 0.10 168 P 2 TWD 12 08C +0.88 TEH TEC 45 COLD 600UL 92 116 0.09 156 P 2 12 08C +1.15 TEH TEC 34 COLD 600UL 0.22 131 P 2 TWD 21 VS2 -0.68 TEH TEC 34 COLD 600UL TWD 94 116 0.34 37 P 2 21 VS4 -0.88 TEH TEC 33 COLD 60OUL 128 116 0.11 145 P 2 TWD 14 VS2 +1.04 TEH TEC 34 COLD 60OUL 41 117 0.10 168 P 2 TWD 12 VS3 +0.81 TEH TEC 40 COLD 60OUL 53 117 0.11 17 P 2 TWD 12 VS3 +0.95 TEH TEC 40 COLD 60OUL 77 117 0.15 159 P 2 TWD 14 VS3 +0.98 TEH TEC 46 COLD 60OUL 93 117 0.13 46 P 2 TWD 13 VS3 +0.62 TEH TEC 32 COLD 60OUL TWD 127 117 0.38 66 P 2 23 VS1 +0.74 TEH TEC 31 COLD 60OUL TWD 40 118 0.13 119 P 2 11 VS3 +0.87 TEH TEC 39 COLD 600UL
Framatome ANP Inc. 1/23/2005 08:32 Attacbment 7 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: SIG A Page 12 of 14 Total Number of Bobbin 1-39% TWD Indications left in service for Cycle 15 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 86 118 0.24 142 P 2 ==D 20 VS3 -0.74 TEH TEC 32 COLD 60=OUL 88 118 0.29 134 P 2 TWD 19 08H +0.89 TEH TEC 31 COLD 60OUL 37 119 0.32 88 P 2 TWD 21 VS3 +0.97 TEH TEC 39 COLD 60OUL 51 119 0.26 34 P 2 TWD 20 VS3 +0.83 TEH TEC 40 COLD 60OUL 53 119 0.14 25 P 2 TWD 12 VS3 +0.83 TEH TEC 39 COLD 60OUL 123 119 0.10 161 P 2 TWD 11 VS4 -0.96 TEH TEC 32 COLD 60OUL 84 120 0.38 128 P 2 TWD 23 VS4 -0.88 TEH TEC 31 COLD 60OUL 0.27 132 P 2 TWD 19 VS2 -0.74 TEH TEC 31 COLD 60OUL 94 120 0.57 112 P 2 TWD 32 VS2 +0.62 TEH TEC 32 COLD 60OUL 0.27 147 P 2 TWD 22 VS3 -0.88 TEH TEC 32 COLD 60OUL 0.30 99 P 2 TWD 24 VS4 -0.90 TEH TEC 32 COLD 60OUL TWD 102 120 0.26 98 P 2 22 VS3 -0.77 TEH TEC 32 COLD 60OUL TWD 126 120 0.50 62 P 2 26 08H -0.95 TEH TEC 31 COLD 60OUL TWD 37 121 0.12 156 P 2 10 VS3 +0.81 TEH TEC 39 COLD 60OUL TWD 53 121 0.14 44 P 2 12 VS3 -0.85 TEH TEC 39 COLD 60OUL TWD 97 121 0.41 85 P 2 28 08C +0.88 TEH TEC 32 COLD 600UL TWD 125 121 0.14 37 P 2 14 07H +0.77 TEH TEC 32 COLD 60OUL TWD 0.39 40 P 2 27 DCT +0.08 TEH TEC 32 COLD 60OUL TWD 39 123 0.12 60 P 2 13 VS3 +0.91 TEH TEC 38 COLD 60OUL TWD 53 123 0.21 44 P 2 15 VS3 +0.92 TEH TEC 48 COLD 60OUL TWD 38 124 0.24 115 P 2 23 VS3 +0.73 TEH TEC 37 COLD 60OUL TWD 42 124 0.26 124 P 2 24 VS3 -0.67 TEH TEC 37 COLD 60OUL TWD 37 125 0.12 59 P 2 15 VS3 -0.70 TEH TEC 37 COLD 600UL TWD 41 125 0.17 24 P 2 19 VS3 -0.62 TEH TEC 37 COLD 60OUL TWD 38 126 0.20 144 P 2 21 VS3 +0.75 TEH TEC 37 COLD 600UL TWD 44 126 0.24 160 P 2 21 VS3 -0.73 TEH TEC 38 COLD 60OUL TWD 54 126 0.13 96 P 2 10 VS3 -0.86 TEH TEC 47 COLD 60OUL TWD 94 126 0.24 125 P 2 20 VS2 -0.90 TEH TEC 32 COLD 600UL TWD 21 127 0.15 92 P 2 17 VS3 +0.89 TEH TEC 37 COLD 60OUL TWD 41 127 0.16 73 P 2 TWD 18 VS3 -0.73 TEH TEC 37 COLD 60OUL 53 127 0.74 81 P 2 TWD 30 VS3 -0.77 TEH TEC 47 COLD 60OUL 57 127 0.33 54 P 2 TWD 20 VS3 -0.72 TEH TEC 47 COLD 60OUL 79 127 0.14 123 P 2 TWD 13 VS2 -0.77 TEH TEC 47 COLD 60OUL 87 127 0.17 147 P 2 TWD 16 VS2 +0.52 TEH TEC 32 COLD 60OUL 91 127 0.18 153 P 2 TWD 17 VS2 -0.84 TEH TEC 32 COLD 600UL 95 127 0.16 155 P 2 TWD 16 VS2 -0.88 TEH TEC 32 COLD 60OUL 600UL 97 127 0.67 72 P 2 TWD 30 VS3 +0.92 TEH TEC 31 COLD 0.17 29 P 2 TWD 13 VS4 +0.90 TEH TEC 31 COLD 60OUL 0.24 130 P 2 TWD 17 VS2 -0.64 TEH TEC 31 COLD 60OUL 54 128 0.32 148 P 2 TWD 20 VS3 -0.94 TEH TEC 47 COLD 60OUL 80 128 0.20 32 P 2 TWD 15 VS4 -0.95 TEH TEC 47 COLD 60OUL 96 128 0.23 101 P 2 TWD 20 VS2 -0.94 TEH TEC 32 COLD 60OUL 0.19 154 P 2 18 VS4 -0.82 TEH TEC 32 COLD 60OUL 45 129 0.14 40 P 2 TWD 16 VS3 -0.61 TEH TEC 37 COLD 60OUL 53 129 0.20 150 P 2 TWD 21 VS3 -0.77 TEH TEC 37 COLD 60OUL 89 129 0.23 69 P 2 TWD 17 VS2 +0.91 TEH TEC 31 COLD 60OUL 91 129 0.27 131 P 2 TWD 18 VS2 -0.78 TEH TEC 31 COLD 60OUL 93 131 0.20 86 P 2 TWD 21 VS2 -0.80 TEH TEC 30 COLD 600UL 0.72 48 P 2 TWD 35 VS2 +0.72 TEH TEC 30 COLD 60OUL 92 132 0.26 49 P 2 TWD 24 VS2 +0.70 TEH TEC 30 COLD 60OUL 45 133 0.28 139 P 2 TWD 19 VS3 +0.78 TEC TEH 27 HOT 60OUL 57 133 0.56 139 P 2 TWD 29 VS3 +0.78 TEC TEH 25 HOT 600UL TWD 91 133 0.31 146 P 2 15 08C +1.34 TEH TEC 29 COLD 60OUL TWD 93 133 0.27 153 P 2 25 VS2 +0.80 TEH TEC 30 COLD 60OUL
Framatome ANP Inc. 1/23/2005 08:32 Attach-mnt 7 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 13 of 14 Total Number of Bobbin 1-39% TWD Indications left in service for Cycle 15 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 97 133 0.48 80 P 2 TWD 31 VS2 -0.68 TEH TEC 30 COLD 60OUL 0.26 88 P 2 TWD 24 VS4 -0.60 TEH TEC 30 COLD 60OUL 42 134 0.16 47 P 2 TWD 13 VS3 -0.92 TEC TEH 27 HOT 60OUL 50 134 0.14 23 P 2 TWD 12 DCT +0.00 TEC TEH 27 HOT 60OUL 96 134 0.24 142 P 2 TWD 23 VS2 +0.92 TEH TEC 30 COLD 60OUL 0.31 74 P 2 TWD 26 VS3 -0.86 TEH TEC 30 COLD 600UL 42 138 0.28 107 P 2 TWD 16 05H +0.92 TEC TEH 37 HOT 60OUL 46 138 0.14 157 P 2 TWD 9 VS3 -0.63 TEC TEH 37 HOT 600UL 96 138 0.49 110 P 2 TWD 30 VS3 -0.60 TEH TEC 28 COLD 600UL 0.19 151 P 2 TWD 17 VS2 +0.84 TEH TEC 28 COLD 600UL 102 138 0.22 153 P 2 TWD 16 VS2 -0.96 TEH TEC 27 COLD 600UL 104 138 0.15 13 P 2 TWD 14 08H +0.79 TEH TEC 28 COLD 600UL 53 139 0.22 106 P 2 TWD 15 VS3 -0.55 TEC TEH 37 HOT 600UL 81 139 0.21 158 P 2 1WD 16 06C +0.83 TEH TEC 27 COLD 60OUL 95 139 0.15 131 P 2 1WD 15 VS2 -0.90 TEH TEC 28 COLD 60OUL 97 139 0.50 51 P 2 TWD 26 VS2 -0.92 TEH TEC 27 COLD 60OUL 101 139 0.10 133 P 2 TWD 9 VS2 -0.95 TEH TEC 27 COLD 60OUL 48 140 0.27 135 P 2 TWD 18 VS3 +0.80 TEC TEH 37 HOT 60OUL 102 140 0.18 20 P 2 TWD 17 09H -0.95 TEH TEC 28 COLD 60OUL 85 141 0.33 106 P 2 TWD 21 VS3 +0.64 TEH TEC 27 COLD 60OUL 97 141 0.22 71 P 2 TWD 16 07C -0.26 TEH TEC 27 COLD 600UL 66 142 0.06 170 P 2 TWD 5 VS2 +1.12 TEC TEH 41 HOT 60OUL 86 142 0.17 169 P 2 TWD 14 VS4 -0.88 TEH TEC 27 COLD 60OUL 0.14 150 P 2 TWD 12 VS3 +1.06 TEH TEC 27 COLD 60OUL 96 142 0.09 166 P 2 TWD 10 VS4 -0.88 TEH TEC 28 COLD 60OUL 81 143 0.19 103 P 2 TWD 14 08C +0.86 TEH TEC 27 COLD 600UL 87 143 0.40 32 P 2 TWD 24 VS2 -0.98 TEH TEC 27 COLD 60OUL 0.63 52 P 2 TWD 29 VS3 +0.38 TEH TEC 27 COLD 60OUL 0.15 38 P 2 TWD 12 VS4 +0.66 TEH TEC 27 COLD 600UL 95 143 0.23 78 P 2 TWD 17 VS2 -0.92 TEH TEC 27 COLD 60OUL 94 144 0.12 163 P 2 TWD 10 01C +0.95 TEH TEC 27 COLD 60OUL 46 146 0.12 65 P 2 TWD 11 VS3 +0.61 TEH TEC 62 COLD 60OUL 85 147 0.18 120 P 2 TWD 17 VS2 +0.92 TEH TEC 28 COLD 60OUL 53 151 0.22 141 P 2 TWD 10 VS3 -0.85 TEC TEH 44 HOT 600UL 56 152 0.75 127 P 2 TWD 26 VS3 -0.65 TEC TEH 44 HOT 60OUL 47 155 0.26 129 P 2 TWD 19 VS3 -0.73 TEC TEH 47 HOT 60OUL 57 155 0.23 143 P 2 TWD 17 VS3 +0.80 TEC TEN 48 HOT 60OUL 44 156 0.30 91 P 2 TWD 20 VS3 -0.83 TEC TEH 48 HOT 60OUL 51 157 0.48 103 P 2 TWD 26 VS3 +0.84 TEC TEH 48 HOT 60OUL 0.67 91 P 2 TWD 30 VS3 -0.55 TEC TEH 48 HOT 60OUL 49 161 0.24 102 P 2 TWD 18 VS3 -0.79 TEC TEH 48 HOT 60OUL 38 162 0.12 139 P 2 TWD 11 01H +1.07 TEC TEH 47 HOT 600UL 29 163 0.06 156 P 2 TWD 7 01C -1.00 TEC TEH 48 HOT 60OUL 30 164 0.16 32 P 2 TWD 13 01H -0.92 TEC TEH 47 HOT 600UL 32 164 0.20 158 P 2 TWD 16 01C +0.92 TEC TEH 48 HOT 600UL 36 164 0.11 7 P 2 TWD 10 01H +0.94 TEC TEH 47 HOT 60OUL 15 165 0.21 32 P 2 TWD 17 01H -0.78 TEC TEH 48 HOT 60OUL 27 165 0.22 133 P 2 TWD 17 01C -0.93 TEC TEH 48 HOT 60OUL 29 165 0.12 149 P 2 TWD 11 01C -0.99 TEC TEH 47 HOT 60OUL 0.18 154 P 2 TWD 15 01H -1.03 TEC TEH 47 HOT 60OUL 2 166 0.34 83 P 2 TWD 23 01C -0.84 07C TEC 59 COLD 60OUL 14 166 0.39 55 P 2 TWD 24 01C -1.04 TEC TEH 47 HOT 60OUL 20 166 0.13 142 P 2 TWD 12 01H +0.93 TEC TEH 47 HOT 60OUL
Framatome ANP Inc. 1/23/2005 08:32 Attachment 7 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G A Page 14 of 14 Total Number of Bobbin 1-39% TWD Indications left in service for Cycle 15 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE Total Tubes : 490 Total Records: 701
Framatome ANP Inc. 1/23/2005 08:32 Attachment 8 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G B Page 1 of 10 Total Number of Bobbin 1-39% TWD Indications left in service for Cycle 15 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 1 3 0.11 161 P 2 TWD 8 01C -0.96 07C TEC 46 COLD 60OUL 32 4 0.25 140 P 2 TWD 13 02H +0.99 TEH TEC 47 COLD 60OUL 34 4 0.24 153 P 2 TWD 14 02H -0.99 TEH TEC 48 COLD 60OUL 31 5 0.35 48 P 2 TWD 18 01C -0.93 TEC TEN 9 HOT 37 5 0.31 74 P 2 TWD 23 02H +0.80 TEC TEH 10 HOT 60OUL 52 8 0.36 146 P 2 TWD 25 01C -0.98 TEC TEH 10 HOT 60OUL 60 10 0.08 155 P 2 TWD 9 02H +0.88 TEC TEH 9 HOT 60OUL 62 12 0.17 109 P 2 TWD 15 01H -0.94 TEC TEH 10 HOT 60OUL 39 15 0.09 171 P 2 TWD 9 04H +0.80 TEC TEH 14 HOT 60OUL 55 15 0.07 168 P 2 TWD 8 04H +0.86 TEC TEH 14 HOT 60OUL 40 18 0.17 55 P 2 TWD 15 VS3 -0.96 TEC TEH 14 HOT 60OUL 62 18 0.16 93 P 2 TWD 14 VS3 -0.87 TEC TEH 14 HOT 60OUL 47 21 0.29 124 P 2 TWD 23 VS3 -0.70 TEC TEH 17 HOT 60OUL 46 22 0.14 33 P 2 TWD 14 VS3 +0.97 TEC TEH 18 HOT 600UL 48 22 0.24 43 P 2 TWD 21 VS3 +0.74 TEC TEH 17 HOT 60OUL 0.13 51 P 2 TWD 14 VS3 -1.00 TEC TEH 17 HOT 60OUL 54 22 0.38 98 P 2 TWD 26 VS3 -0.66 TEC TEH 18 HOT 600UL 87 23 0.43 111 P 2 TWD 21 VS2 +0.83 TEH TEC 48 COLD 60OUL 93 23 0.24 93 P 2 TWD 13 DCT +0.00 TEH TEC 47 COLD 60OUL 88 24 0.32 58 P 2 TWD 17 VS2 +0.89 TEH TEC 49 COLD 60OUL 0.19 140 P 2 TWD 12 VS3 +0.58 TEH TEC 49 COLD 60OUL 92 24 0.30 58 P 2 TWD 17 DCB +0.00 TEH TEC 49 COLD 60OUL 94 24 0.25 72 P 2 TWD 16 DCB +0.00 TEH TEC 50 COLD 600UL 96 24 0.36 146 P 2 TWD 21 07H -0.22 TEH TEC 50 COLD 60OUL 0.58 60 P 2 TWD 27 08H -0.92 TEH TEC 50 COLD 60OUL 0.36 107 P 2 TWD 20 VS4 +0.79 TEH TEC 50 COLD 60OUL 0.48 128 P 2 TWD 24 DCB +0.00 TEH TEC 50 COLD 60OUL 0.26 135 P 2 TWD 9 06H +0.87 TEH TEC 50 COLD 60OUL 45 25 0.35 67 P 2 TWD 25 VS3 -0.88 TEC TEN 17 HOT 60OUL 81 25 0.30 63 P 2 TWD 18 DCT +0.00 TEH TEC 50 COLD 60OUL 91 25 0.31 122 P 2 TWD 18 DCT -0.12 TEH TEC 49 COLD 60OUL 95 25 0.35 130 P 2 TWD 19 VS4 -0.89 TEH TEC 49 COLD 60OUL 0.08 16 P 2 TWD 3 05H +0.67 TEH TEC 49 COLD 600UL 44 26 0.11 15 P 2 TWD 12 VS3 -0.88 TEC TEN 19 HOT 60OUL 94 26 0.32 110 P 2 TWD 17 VS2 -1.01 TEH TEC 49 COLD 60OUL 0.28 149 P 2 TWD 15 VS2 +0.95 TEH TEC 49 COLD 60OUL 0.37 133 P 2 TWD 18 DHT +0.00 TEH TEC 49 COLD 60OUL 96 26 0.49 33 P 2 TWD 25 VS4 +0.16 TEH TEC 50 COLD 60OUL 0.34 29 P 2 TWD 20 DHT +0.00 TEH TEC 50 COLD 60OUL TWD 91 27 0.30 98 P 2 17 VS4 -0.99 TEH TEC 49 COLD 600UL TWD 95 27 0.20 81 P 2 12 VS4 -0.93 TEH TEC 49 COLD 600UL TWD 97 27 0.21 40 P 2 14 VS3 -0.93 TEH TEC 50 COLD 60OUL TWD 99 27 0.43 143 P 2 22 O0H -0.26 TEH TEC 49 COLD 60OUL TWD 101 27 0.68 115 P 2 29 DCT +0.00 TEH TEC 50 COLD 60OUL TWD 34 28 0.08 163 P 2 8 VS3 -1.13 TEC TEN 20 HOT 60OUL TWD 92 28 0.16 30 P 2 12 VS2 -0.59 TEH TEC 50 COLD 60OUL TWD 0.13 121 P 2 9 VS2 +0.83 TEH TEC 50 COLD 60OUL TWD 98 28 0.17 110 P 2 10 VS2 +0.81 TEH TEC 49 COLD 60OUL TWD 100 28 0.81 114 P 2 31 DCT +0.00 TEH TEC 50 COLD 60OUL TWD 0.21 120 P 2 14 02H +0.94 TEH TEC 50 COLD 60OUL TWD 53 29 0.17 119 P 2 17 VS3 +0.92 TEC TEH 19 HOT 60OUL TWD 67 29 0.17 136 P 2 17 VS2 -0.69 TEC TEH 19 HOT 60OUL TWD 89 29 0.27 11 P 2 17 DHT +0.00 TEH TEC 50 COLD 60OUL TWD 91 29 0.28 98 P 2 15 DCT +0.00 TEH TEC 49 COLD 600UL
Framatome ANP Inc. 1/23/2005 08:32 Attachment 8 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: SIG B Page 2 of 10 Total Number of Bobbin 1-39% TWD Indications left in service for Cycle 15 ROW LINE VOLTS DEG CNN IND %TW LOCATION EXT EXT CAL # LEG PROBE 95 29 0.19 49 P 2 TWD 13 VS2 +0.81 TEN TEC 50 COLD 60 OUL 0.50 78 P 2 TWD 25 DCT +0.00 TEH TEC 50 COLD 60OUL 0.13 35 P 2 TWD 10 06H +0.95 TEN TEC 50 COLD 60OUL 42 30 0.24 28 P 2 TWD 19 VS3 -0.86 TEC TEN 20 HOT 60OUL 92 30 0.30 139 P 2 TWD 16 VS2 +0.65 TEN TEC 49 COLD 60OUL 0.28 152 P 2 TWD 16 VS4 -0.91 TEN TEC 49 COLD 60OUL 0.15 121 P 2 TWD 9 07H +0.88 TEN TEC 49 COLD 600UL 96 30 0.21 26 P 2 TWD 13 VS4 +0.40 TEN TEC 49 COLD 60OUL 104 30 0.19 56 P 2 TWD 10 VS3 -1.33 TEH TEC 49 COLD 600UL 107 31 0.24 51 P 2 TWD 15 02H +0.76 TEN TEC 49 COLD 60OUL 0.28 70 P 2 TWD 16 04C -1.02 TEH TEC 49 COLD 60OUL 108 32 0.25 149 P 2 TWD 15 02H -0.86 TEN TEC 49 COLD 60OUL 43 33 0.26 100 P 2 TWD 20 VS3 +0.93 TEC TEN 25 HOT 60OUL 105 33 0.28 78 P 2 TWD 10 02H -0.12 TEN TEC 49 COLD 600UL 64 34 0.46 63 P 2 TWD 29 VS4 -0.24 TEC TEN 24 HOT 60OUL 82 34 0.28 87 P 2 TWD 10 VS4 -0.61 TEN TEC 50 COLD 60OUL 92 34 0.18 63 P 2 TWD 11 08H +1.02 TEN TEC 49 COLD 60OUL 96 34 0.92 109 P 2 TWD 32 VS2 -0.41 TEN TEC 49 COLD 600UL 0.24 86 P 2 TWD 15 VS3 +0.32 TEN TEC 49 COLD 60OUL 108 34 0.15 100 P 2 TWD 10 03C -0.88 TEN TEC 52 COLD 60OUL 50 36 0.30 99 P 2 TWD 21 VS3 +0.76 TEC TEN 25 HOT 60OUL 94 36 0.25 148 P 2 TWD 15 VS2 -0.95 TEN TEC 51 COLD 60OUL 96 36 0.35 106 P 2 TWD 19 VS2 -0.79 TEH TEC 52 COLD 60OUL 100 36 0.29 12 P 2 TWD 17 08H +0.89 TEN TEC 52 COLD 60OUL 87 37 0.13 20 P 2 TWD 9 VS2 -0.65 TEN TEC 51 COLD 600UL 0.17 167 P 2 TWD 11 VS2 +0.75 TEN TEC 51 COLD 60OUL 92 38 0.22 102 P 2 TWD 13 08H -0.78 TEN TEC 52 COLD 60OUL 112 38 0.23 97 P 2 TWD 14 VS4 -0.87 TEN TEC 52 COLD 60OUL 116 38 0.33 52 P 2 TWD 18 VS3 +0.87 TEH TEC 52 COLD 60OUL 81 39 0.23 22 P 2 TWD 14 VS4 +0.63 TEN TEC 51 COLD 60OUL 83 39 0.15 105 P 2 TWD 10 VS2 +0.65 TEN TEC 51 COLD 60OUL 0.19 14 P 2 TWD 12 VS4 +0.75 TEN TEC 51 COLD 60OUL 117 39 0.29 44 P 2 TWD 16 DCT -0.25 TEN TEC 52 COLD 60OUL TWD 85 41 0.16 152 P 2 10 VS4 -0.77 TEN TEC 51 COLD 600UL TWD 95 41 0.38 114 P 2 20 VS2 +0.97 TEN TEC 52 COLD 60OUL TWD 0.22 63 P 2 13 VS4 +0.89 TEN TEC 52 COLD 600UL TWD 97 41 0.87 102 P 2 31 VS2 +0.63 TEN TEC 51 COLD 60OUL TWD 0.36 57 P 2 19 VS3 -0.97 TEN TEC 51 COLD 60OUL TWD 0.70 121 P 2 28 VS4 +0.55 TEN TEC 51 COLD 600UL TWD 0.22 138 P 2 14 VS4 -0.81 TEN TEC 51 COLD 60OUL TWD 116 42 0.15 114 P 2 10 05C +0.86 TEN TEC 52 COLD 600UL TWD 121 43 0.19 10 P 2 12 DCT +0.00 TEN TEC 51 COLD 600UL TWD 46 44 0.13 20 P 2 9 VS3 +0.82 TEN TEC 4 COLD 600UL P 2 TWD 94 44 0.20 162 12 VS2 -0.69 TEN TEC 52 COLD 600UL TWD 0.25 52 P 2 15 VS4 -1.20 TEN TEC 52 COLD 60OUL TWD 120 44 0.17 138 P 2 11 04H +0.92 TEN TEC 51 COLD 60OUL TWD 29 45 0.29 69 P 2 17 VS3 -0.62 TEN TEC 3 COLD 60OUL TWD 123 45 0.32 41 P 2 17 DHT +0.00 TEN TEC 52 COLD 60OUL TWD 62 46 0.27 50 P 2 16 VS2 +0.85 TEN TEC 3 COLD 600UL P 2 TWD 124 46 0.15 29 10 DCT +0.00 TEN TEC 52 COLD 600UL TWD 43 47 0.50 126 P 2 26 VS3 -0.78 TEN TEC 4 COLD 600UL TWD 125 47 0.31 108 P 2 17 09C +0.88 TEN TEC 52 COLD 600UL TWD 86 48 0.24 47 P 2 14 VS2 +1.08 TEN TEC 51 COLD 60OUL TWD 126 48 0.14 149 P 2 9 07H -1.00 TEN TEC 52 COLD 60OUL
Framatome ANP Inc. 1/23/2005 08:32 Attacbhent 8 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: SIG B Page 3 of 10 Total Number of Bobbin 1-39% TWD Indications left in service for Cycle 15 ROW LINE VOLTS DEG CH} IND %TW LOCATION EXT EXT CAL # LEG PROBE 0.50 48 P 2 TWD 23 DHT +0.25 TEH TEC 52 COLD 600UL 93 49 0.39 101 P 2 TWD 24 VS2 -0.87 TEH TEC 54 COLD 60 OUL 68 50 0.28 45 P 2 TWD 15 VS2 +0.85 TEH TEC 7 COLD 60OUL 0.48 122 P 2 TWD 22 VS3 -1.02 TEH TEC 7 COLD 60OUL 57 51 0.95 83 P 2 TWD 32 VS3 -0.80 TEH TEC 7 COLD 60OUL 107 51 0.13 65 P 2 TWD 10 07C +0.95 TEH TEC 54 COLD 600UL 113 51 0.35 104 P 2 TWD 19 02H -0.08 TEH TEC 53 COLD 60OUL 121 51 0.27 161 P 2 TWD 16 05H +0.89 TEH TEC 53 COLD 60OUL 127 53 0.30 75 P 2 TWD 18 DCB -0.16 TEH TEC 53 COLD 60OUL 0.30 132 P 2 TWD 17 07H +0.85 TEH TEC 53 COLD 600UL 0.18 156 P 2 TWD 12 06H -0.56 TEH TEC 53 COLD 600UL 41 55 0.36 61 P 2 TWD 20 VS3 +0.95 TEH TEC 14 COLD 600UL 83 55 0.21 60 P 2 TWD 13 VS4 +0.64 TEH TEC 56 COLD 60OUL 0.27 43 P 2 TWD 16 VS3 -0.73 TEH TEC 56 COLD 600UL 95 55 0.24 48 P 2 TWD 14 DHB +0.30 TEH TEC 55 COLD 60OUL 131 55 0.20 103 P 2 TWD 10 05H -0.97 TEH TEC 58 COLD 60OUL 0.73 115 P 2 TWD 26 DCB +0.00 TEH TEC 58 COLD 60OUL 28 56 0.15 15 P 2 TWD 11 VS3 -0.82 TEH TEC 15 COLD 600UL 81 57 0.29 56 P 2 TWD 17 VS4 -0.71 TEH TEC 55 COLD 60OUL 121 57 0.14 63 P 2 TWD 11 VS1 +0.90 TEH TEC 54 COLD 60OUL 48 58 0.10 143 P 2 TWD 7 VS3 +0.87 TEH TEC 13 COLD 60OUL 130 58 0.48 107 P 2 TWD 23 DCT +0.00 TEH TEC 55 COLD 60OUL 132 58 0.69 71 P 2 TWD 25 VS1 -0.80 TEH TEC 58 COLD 60OUL 0.50 106 P 2 TWD 21 DCB +0.21 TEH TEC 58 COLD 60OUL 49 59 0.46 140 P 2 TWD 22 VS3 -0.89 TEH TEC 12 COLD 60OUL 0.25 25 P 2 TWD 14 VS3 +0.85 TEH TEC 12 COLD 60OUL 127 59 0.35 220 P 2 TWD 19 09H +0.96 TEH TEC 55 COLD 60OUL 129 59 0.27 14 P 2 TWD 16 DCT +0.25 TEH TEC 56 COLD 60OUL 131 59 0.81 64 P 2 TWD 28 DCT +0.00 TEH TEC 57 COLD 60OUL 133 59 0.50 70 P 2 TWD 21 DCB +0.00 TEH TEC 58 COLD 600UL 102 60 0.21 99 P 2 TWD 13 VS4 -0.66 TEH TEC 56 COLD 60OUL 132 60 0.40 101 P 2 TWD 18 DCT +0.00 TEH TEC 57 COLD 60OUL 134 60 0.26 61 P 2 TWD 13 DCT +0.00 TEH TEC 58 COLD 60OUL 0.58 91 P 2 TWD 23 DHB +0.76 TEH TEC 58 COLD 60OUL 43 61 0.52 86 P 2 TWD 25 VS3 +0.67 TEH TEC 13 COLD 600UL 133 61 0.45 146 P 2 TWD 19 DHT -0.25 TEH TEC 58 COLD 600UL 24 62 0.28 49 P 2 TWD 17 VS3 +0.82 TEH TEC 13 COLD 60OUL 98 62 0.10 41 P 2 TWD 7 VS2 -0.89 TEH TEC 55 COLD 60OUL 106 62 0.20 136 P 2 TWD 12 VS1 +0.12 TEH TEC 55 COLD 60OUL 53 63 0.17 73 P 2 TWD 12 VS3 -0.61 TEH TEC 11 COLD 60OUL 135 63 0.52 69 P 2 TWD 21 DHT +0.00 TEH TEC 58 COLD 60OUL 22 64 0.17 93 P 2 TWD 11 VS3 +0.72 TEH TEC 10 COLD 60OUL 25 65 0.22 36 P 2 TWD 15 VS3 +0.68 TEH TEC 11 COLD 600UL 39 65 0.38 25 P 2 TWD 20 VS3 -1.01 TEH TEC 10 COLD 60OUL 46 66 0.20 107 P 2 TWD 14 VS3 +0.79 TEH TEC 11 COLD 60OUL 96 66 0.23 98 P 2 TWD 14 VS4 +0.88 TEH TEC 56 COLD 60OUL 34 68 0.41 36 P 2 TWD 21 DHB +0.00 TEH TEC 10 COLD 60OUL 1.18 98 P 2 TWD 35 DCB +0.16 TEH TEC 10 COLD 60OUL 0.80 112 P 2 TWD 30 DCT -0.08 TEH TEC 10 COLD 600UL 36 68 0.32 29 P 2 TWD 19 VS3 -0.80 TEH TEC 11 COLD 600UL 0.52 53 P 2 TWD 26 VS3 +0.57 TEH TEC 11 COLD 60OUL 38 68 0.29 159 P 2 TWD 16 VS3 -0.78 TEH TEC 10 COLD 600UL 46 68 0.16 124 P 2 TWD 10 VS3 +0.93 TEH TEC 10 COLD 600UL 0.11 7 P 2 TWD 7 DCT +0.00 TEH TEC 10 COLD 60OUL
Framatome ANP Inc. 1/23/2005 08:32 Attacbment 8 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G B Page 4 of 10 Total Number of Bobbin 1-39% TWD Indications left in service for Cycle 15 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 64 68 0.18 96 P 2 TWD 11 VS2 +0.79 TEH TEC 10 COLD 6=OUL 134 68 0.34 143 P 2 TWD 16 DHB +0.00 TEH TEC 58 COLD 600UL 35 69 0.35 140 P 2 TWD 19 DCT -0.21 TEC TEN 12 COT 600UL 39 69 0.62 121 P 2 TWD 27 VS3 +0.51 TEC TEH 12 HOT 60OUL 0.17 136 P 2 TWD 11 VS3 -0.61 TEC TEH 12 HOT 60OUL 0.61 148 P 2 TWD 27 DHT +0.00 TEC TEH 12 HOT 60OUL 41 69 0.36 156 P 2 TWD 20 07C -0.89 TEC TEH 11 HOT 600UL 36 70 0.82 130 P 2 TWD 30 DCB +0.00 TEC TEH 12 HOT 600UL 0.43 146 P 2 TWD 22 DHB +0.00 TEC TEH 12 HOT 600UL 46 70 0.82 141 P 2 TWD 30 VS3 +0.84 TEC TEH 12 HOT 60OUL 35 71 0.72 113 P 2 TWD 29 DCB +0.00 TEC TEH 12 HOT 60OUL 0.51 52 P 2 TWD 24 DHT +0.00 TEC TEH 12 HOT 60OUL 37 71 0.83 84 P 2 TWD 30 DHT +0.00 TEC TEH 11 HOT 60OUL 45 71 0.69 82 P 2 TWD 28 DCT +0.00 TEC TEH 11 HOT 60OUL 0.49 145 P 2 TWD 24 VS3 -0.77 TEC TEH 11 HOT 600UL 97 71 0.62 55 P 2 TWD 28 VS4 +0.64 TEH TEC 42 COLD 60OUL 48 72 0.48 91 P 2 TWD 24 VS3 -0.74 TEC TEC 11 HOT 600UL 50 72 0.27 104 P 2 TWD 16 VS3 -0.70 TEC TEH 12 HOT 600UL 48 74 0.13 94 P 2 TWD 9 DHB +0.11 TEC TEH 12 HOT 600UL 52 74 0.26 165 P 2 TWD 16 VS3 +0.97 TEC TEH 12 HOT 600UL 43 75 0.43 75 P 2 TWD 22 DCB +0.34 TEC TEH 12 HOT 600UL 45 75 0.42 114 P 2 TWD 22 DCB +0.00 TEC TEH 11 HOT 60OUL 103 75 0.22 51 P 2 TWD 12 VS2 +1.00 TEH TEC 43 COLD 600UL 137 75 0.23 147 P 2 TWD 11 05H +0.90 TEH TEC 57 COLD 60OUL 44 76 1.12 94 P 2 TWD 34 DHB +0.00 TEC TEN 12 HOT 60OUL 46 76 0.38 70 P 2 TWD 21 DHB +0.00 TEC TEH 11 HOT 60OUL 52 76 0.67 78 P 2 TWD 28 VS3 +0.75 TEC TEH 12 HOT 600UL 54 76 0.49 152 P 2 TWD 24 VS3 -0.81 TEC TEH 11 HOT 600UL 0.45 141 P 2 TWD 23 VS3 +0.77 TEC TEH 11 HOT 600UL 56 76 0.88 103 P 2 TWD 32 VS3 +0.68 TEC TEH 12 HOT 600UL 0.46 145 P 2 TWD 23 VS3 -0.81 TEC TEH 12 HOT 60OUL 53 77 0.24 111 P 2 TWD 15 DCB +0.00 TEC TEH 6 HOT 60OUL 55 77 1.02 148 P 2 TWD 31 DCB +0.00 TEC TEH 5 HOT 60OUL 57 77 0.33 130 P 2 TWD 18 VS3 -0.87 TEC TEH 6 HOT 60OUL 0.16 130 P 2 TWD 11 VS3 +0.71 TEC TEH 6 HOT 60OUL 0.31 158 P 2 TWD 18 DCB +0.51 TEC TEH 6 HOT 60OUL 107 77 0.33 26 P 2 TWD 22 04H -0.42 TEH TEC 39 COLD 600UL 52 78 0.58 127 P 2 TWD 25 DCT +0.00 TEC TEN 6 HOT 60OUL 0.39 139 P 2 TWD 21 DCB +0.00 TEC TEH 6 HOT 60OUL 1.46 144 P 2 TWD 29 VS3 +0.85 TEC TEH 6 HOT 60OUL 0.46 58 P 2 TWD 14 VS3 -0.96 TEC TEH 6 HOT 60OUL 54 78 0.76 132 P 2 TWD 28 DCB +0.00 TEC TEH 5 HOT 60OUL 0.76 84 P 2 TWD 28 DHB +0.00 TEC TEH 5 HOT 60OUL 0.29 102 P 2 TWD 17 DCT +0.00 TEC TEH 5 HOT 60OUL 88 78 0.31 104 P 2 TWD 15 VS2 -0.90 TEH TEC 44 COLD 60OUL 0.64 34 P 2 TWD 25 VS2 +0.76 TEH TEC 44 COLD 60OUL 96 78 0.40 43 P 2 TWD 25 VS4 +0.74 TEH TEC 39 COLD 60OUL 0.17 28 P 2 TWD 15 DCT -0.25 TEH TEC 39 COLD 60OUL 0.78 87 P 2 TWD 33 VS2 -0.76 TEH TEC 39 COLD 60OUL 0.33 31 P 2 TWD 22 VS3 +0.36 TEH TEC 39 COLD 60OUL 51 79 0.51 94 P 2 IWD 23 DCB +0.00 TEC TEN 5 HOT 600UL 0.56 150 P 2 TWD 24 DHT +0.00 TEC TEH 5 HOT 60OUL 61 79 0.26 112 P 2 TWD 15 DCB +0.00 TEC TEH 5 HOT 60OUL 63 79 0.25 136 P 2 TWD 15 DCB +0.00 TEC TEH 5 HOT 60OUL
Framatome ANP Inc. 1/23/2005 08:32 Attacbment 8 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G B Page 5 of 10 Total Number of Bobbin 1-39% TWD Indications left in service for Cycle 15 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 50 80 0.37 138 P2 TWD 20 DCT +0.00 TEC TEH 6 HOT 600UL 0.74 108 P2 TWD 29 DHB +0.00 TEC TEH 6 HOT 60OOUL 52 80 0.44 88 P2 TWD 21 DCT +0.00 TEC TEH 5 HOT 60OUL 0.64 145 P2 TWD 26 VS3 +0.92 TEC TEH 5 HOT 60OUL 0.47 126 P2 TWD 22 VS3 -0.63 TEC TEH 5 NOT 600UL 1.47 100 P2 TWD 35 DHB +0.00 TEC TEH 5 HOT 60OUL 600UL 60 80 0.45 87 P2 TWD 22 DCB +0.00 TEC TEH 5 HOT 132 80 0.18 153 P2 TWD 9 VS1 +0.62 TEC TEC 57 COLD 600UL 51 81 0.31 141 P2 TWD 17 DCT +0.00 TEC TEC 6 HOT 600UL 0.63 129 P2 TWD 27 DCB +0.00 TEC TEH 6 HOT 600UL 53 81 1.25 26 P2 TWD 33 DHT +0.00 TEC TEH 5 HOT 60OUL 0.30 26 P2 TWD 17 DCT +0.00 TEC TEH 5 HOT 600UL 48 82 0.68 37 P2 TWD 27 DHT +0.00 TEC TEH 5 HOT 600UL 50 82 0.42 74 P2 TWD 21 DCB +0.00 TEC TEH 6 HOT 60OUL 116 82 0.16 113 P2 TWD 8 VS4 -0.91 TEH TEC 41 COLD 60OUL 51 83 0.33 32 P2 TWD 18 DCB +0.00 TEC TEH 6 HOT 600UL 0.78 100 P2 TWD 29 DCT +0.00 TEC TEH 6 HOT 60OUL 53 83 0.24 28 P2 TWD 14 DCB +2.99 TEC TEH 5 HOT 600UL 87 83 0.35 104 P2 TWD 23 VS3 -0.93 TEC TEC 39 COLD 60OUL 89 83 1.75 112 P2 TWD 32 VS3 -0.87 TEH TEC 41 COLD 60OUL 48 84 1.69 110 P2 TWD 36 DHB +0.00 TEC TEH 5 HOT 600UL 1.08 103 P2 TWD 32 DCT +0.00 TEC TEH 5 HOT 60OUL TWD 50 84 1.02 118 P2 33 DCT +0.00 TEC TEH 6 HOT 60OUL TWD TEC 60OUL 0.23 23 P2 14 DHB +0.00 TEH 6 NOT TWD TEC 60OUL 52 84 1.88 111 P2 37 DCT -0.25 TEH 5 HOT TWD 54 84 0.17 108 P2 12 DCT +0.00 TEC TEH 6 HOT 60OUL TWD TEC HOT 60OUL 64 84 0.28 165 P2 16 VS3 -0.73 TEH 5 TWD TEH COLD 60OUL 88 84 0.31 159 P2 17 VS2 +0.85 TEC 59 TWD TEH COLD 60OUL 98 84 0.11 39 P2 11 VS5 -0.92 TEC 39 TWD HOT 600UL 57 85 0.57 125 P2 25 DCB +0.00 TEC TEH 5 TWD 95 85 0.25 102 P2 19 VS2 -0.75 TEH TEC 39 COLD 60OUL TWD 54 86 0.42 43 P2 21 DCT +0.00 TEC TEH 5 HOT 600UL TWD 60OUL 60 86 0.14 168 P2 9 VS3 -0.67 TEC TEH 3 HOT TWD 88 86 0.58 64 P2 27 VS3 +0.74 TEH TEC 38 COLD 600UL TWD 60OUL 122 86 0.13 79 P2 9 06H +0.87 TEH TEC 37 COLD TWD HOT 55 87 1.20 93 P2 34 DCT +0.00 TEC TEH 4 60OUL TWD HOT 60OUL 50 88 0.31 157 P2 19 DHB +0.00 TEC TEH 3 TWD HOT 60OUL 52 88 0.87 108 P2 30 VS3 +0.89 TEC TEH 4 TWD HOT 60OUL 0.52 79 P2 24 DCB +0.39 TEC TEH 4 TWD HOT 0.33 42 P2 TWD 18 DHT +0.07 TEC TEH 4 60OUL 54 88 0.48 88 P2 22 VS3 +0.90 TEC TEH 3 HOT 60OUL 0.28 149 P2 TWD 16 VS3 -0.79 TEC TEH 3 HOT 60OUL 62 88 0.42 92 P2 TWD 21 VS3 -0.77 TEC TEH 4 HOT 60OUL 100 88 0.32 163 P2 TWD 17 08C -0.93 TEH TEC 37 COLD 60OUL 51 89 0.73 117 P2 TWD 28 DHB +0.00 TEC TEH 4 HOT 60OUL 55 89 0.15 160 P2 TWD 10 DHB -0.05 TEC TEH 4 HOT 60OUL 89 89 0.24 129 P2 TWD 14 VS2 -0.69 TEH TEC 37 COLD 60OUL 48 90 0.38 84 P2 TWD 14 DHB +0.00 TEC TEH 3 HOT 60OUL 52 90 0.35 51 P2 TWD 18 DCB +0.00 TEC TEH 3 HOT 60OUL 54 90 0.43 63 P2 TWD 21 DCB +0.00 TEC TEH 4 HOT 60OUL 56 90 0.34 38 P2 TWD 18 VS3 -0.27 TEC TEH 3 HOT 60OUL 0.52 57 P2 TWD 23 DCT +0.02 TEC TEH 3 NOT 60OUL TWD COLD 60OUL 100 90 0.42 30 P2 15 06C +0.04 TEH TEC 38 TWD HOT 600UL 53 91 0.17 168 P2 11 DCT +0.00 TEC TEH 3
Framatome ANP Inc. 1/23/2005 08:32 Attacb ent 8 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G B Page 6 of 10 Total Number of Bobbin 1-39% TWD Indications left in service for Cycle 15 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 44 92 0.51 104 P2 TWD 23 DHB +0.00 TEC TEH 3 HOT 60OOUL 0.32 17 P2 TWD 17 DCT +0.00 TEC TEH 3 HOT 60OUL TEC TEB 3 HOT 600UL 48 92 0.45 125 P2 TWD 21 DHB +0.00 TEH 4 600UL 50 92 0.32 19 P2 TWD 17 DHB +0.00 TEC HOT TEC TEH 4 HOT 600UL 54 92 0.75 97 P2 TWD 28 VS3 +0.78 TEN TEC COLD 600UL 96 92 0.16 166 P2 TWD 10 05C +0.84 37 TEC COLD 600UL 102 92 0.19 40 P2 TWD 13 VS4 -0.65 TEH 38 TEH TEC COLD 600UL 110 92 0.12 155 P2 TWD 9 07C -0.14 38 NOT 600UL 43 93 0.60 128 P2 TWD 27 DCB +0.00 TEC TEH 3 TWD HOT 600UL 1.05 51 P2 32 DHT +0.00 TEC TEH 3 600UL 87 93 0.33 97 P2 TWD, 17 VS3 -1.00 TEH TEC 37 HOT 600UL 42 94 0.99 77 P2 TWD 32 DCB +0.63 TEC TEH 3 HOT 600UL 44 94 0.35 33 P2 TWD 18 DCB +0.00 TEC TEH 4 HOT 600UL 46 94 0.82 123 P2 TWD 30 VS3 -0.94 TEC TEH 3 HOT 600UL 1.03 130 P2 TWD 32 DCB +0.00 TEC TEH 3 HOT 600UL 50 94 0.47 115 P2 TWD 24 VS3 -0.92 TEC TEH 3 HOT 600UL 39 95 0.31 62 P2 TWD 17 DCT +0.00 TEC TEH 4 HOT 600UL 51 95 0.37 144 P2 TWD 21 07H +0.87 TEC TEH 3 600UL 95 95 0.22 143 P2 TWD 15 VS2 +1.01 TEH TEC 38 COLD 600UL 0.23 134 P2 TWD 15 VS4 -0.64 TEH TEC 38 COLD 600UL 46 96 0.37 160 P2 TWD 19 DHB +0.00 TEC TEH 4 HOT 600UL 35 97 0.59 137 P2 TWD 25 DHB +0.00 TEC TEH 4 HOT 600UL 45 97 0.30 341 P2 TWD 19 VS3 -1.02 TEC TEH 3 HOT 600UL 71 97 0.62 149 P2 TWD 27 VS4 -0.73 TEC TEH 3 HOT 600UL 0.21 163 P2 TWD 15 VS2 +0.86 TEC TEH 3 HOT 600UL 89 97 0.35 70 P2 TWD 18 VS4 -0.88 TEH TEC 35 COLD 600UL 93 97 0.39 144 P2 TWD 20 VS2 +0.68 TEH TEC 35 COLD 600UL 0.29 60 P2 TWD 14 VS4 +0.74 TEH TEC 35 COLD 600UL 34 98 0.47 78 P2 TWD 24 VS3 +0.83 TEC TEH 3 HOT 60O0UL 600UL 0.78 127 P2 TWD 29 VS3 -0.90 TEC TEH 3 HOT 600UL 0.60 123 P2 TWD 27 DHB +0.00 TEC TEH 3 HOT 600UL 0.51 97 P2 TWD 25 DCB +0.09 TEC TEH 3 HOT 600UL 0.27 32 P2 TWD 15 DCT -0.11 TEC TEH 3 HOT 600UL 1.02 57 P2 TWD 27 DHT -0.25 TEC TEH 3 HOT 600UL 56 98 0.24 152 P2 TWD 16 VS3 +0.99 TEC TEH 3 HOT 600UL 62 98 0.20 147 P2 TWD 15 VS3 -0.82 TEC TEH 3 HOT 600UL 88 98 0.40 60 P2 TWD 15 06C +0.85 TEH TEC 35 COLD 600UL 94 98 0.29 43 P2 TWD 16 VS2 +0.67 TEH TEC 36 COLD 600UL 33 99 0.42 31 P2 TWD 21 DCB +0.00 TEC TEH 4 HOT 600UL 37 99 0.69 40 P2 TWD 27 DCB +0.00 TEC TEH 4 HOT TWD 600UL 0.64 67 P2 26 VS3 -0.07 TEC TEH 4 HOT TWD 600UL 0.91 130 P2 31 VS3 -0.69 TEC TEH 4 HOT TWD 600UL 0.54 48 P2 24 DHB +0.00 TEC TEH 4 HOT TWD 600UL 47 99 0.31 151 P2 17 VS3 -0.83 TEC TEH 4 HOT TWD 600UL 55 99 0.13 161 P2 9 VS3 +1.19 TEC TEH 4 HOT TWD 600UL 95 99 0.15 148 P2 8 08C +0.82 TEH TEC 36 COLD TWD 600UL 137 99 0.27 129 P2 13 VS1 +0.80 TEH TEC 58 COLD TWD 600UL 34 100 0.62 76 P2 27 DHB +0.27 TEH TEC 16 COLD TWD 600UL 0.88 78 P2 32 DHT -0.16 TEH TEC 16 COLD TWD 600UL 0.18 97 P2 12 DCB +0.47 TEH TEC 16 COLD TWD 600UL 94 100 0.86 119 P2 31 VS2 -0.79 TEH TEC 26 COLD TWD 600UL 0.69 54 P2 28 VS2 +0.79 TEH TEC 26 COLD TWD 600UL 0.27 29 P2 15 VS4 +0.87 TEH TEC 26 COLD TWD 600UL 33 101 0.37 139 P2 21 DCT +0.00 TEH TEC 17 COLD
Framatome ANP Inc. 1/23/2005 08:32 Attacbment 8 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G B Page 7 of 10 Total Number of Bobbin 1-39% TWD Indications left in service for Cycle 15 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 35 101 0.52 69 P2 ==D 25 VS3 -0.99 TEN TEC 16 COLD 60 OUL 37 101 0.18 77 P2 TWD 12 VS3 -0.87 TEH TEC 17 COLD 600UL 47 101 0.36 46 P2 TWD 20 VS3 +0.86 TEH TEC 16 COLD 60OUL 51 101 0.41 86 P2 TWD 14 VS3 +0.80 TEH TEC 16 COLD 60OUL 91 101 0.18 117 P2 TWD 9 VS2 -0.79 TEH TEC 25 COLD 60OUL 93 101 0.28 30 P2 TWD 15 VS3 -0.50 TEH TEC 26 COLD 60OUL 0.55 94 P2 TWD 25 VS2 -0.94 TEH TEC 26 COLD 600UL 135 101 0.90 82 P2 TWD 29 VS1 +0.74 TEH TEC 58 COLD 600UL 30 102 0.28 137 P2 TWD 17 VS3 +0.88 TEH TEC 16 COLD 600UL 34 102 0.49 73 P2 TWD 24 VS3 +0.64 TEH TEC 16 COLD 60OUL 0.17 158 P2 TWD 12 VS3 -0.84 TEH TEC 16 COLD 60OUL 92 102 0.18 34 P2 TWD 11 VS2 +0.83 TEH TEC 26 COLD 600UL 94 102 0.24 11 P2 TWD 12 VS3 -0.80 TEH TEC 25 COLD 60OUL 98 102 0.14 169 P2 TWD 8 VS4 -0.97 TEH TEC 25 COLD 60OUL 27 103 0.24 153 P2 TWD 15 VS3 -0.76 TEH TEC 16 COLD 600UL 29 103 0.36 29 P2 TWD 20 VS3 -0.81 TEH TEC 17 COLD 60OUL 31 103 0.26 138 P2 TWD 16 VS3 -0.74 TEH TEC 16 COLD 60OUL 35 103 0.27 62 P2 TWD 17 VS3 -0.66 TEH TEC 16 COLD 600UL 87 103 0.16 22 P2 TWD 8 VS2 -0.92 TEH TEC 25 COLD 60OUL 97 103 0.30 174 P2 TWD 16 DNB +3.71 TEH TEC 26 COLD 60OUL 20 104 0.20 142 P2 TWD 13 VS3 +0.90 TEH TEC 17 COLD 60OUL 24 104 0.27 116 P2 TWD 17 VS3 +0.72 TEH TEC 16 COLD 60OUL 26 104 0.34 44 P2 TWD 19 VS3 +0.80 TEH TEC 17 COLD 60OUL 28 104 0.20 138 P2 TWD 14 VS3 +0.80 TEH TEC 16 COLD 60OUL TWD 34 104 0.46 27 P2 24 VS3 -0.96 TEH TEC 17 COLD 60OUL TWD 38 104 0.26 38 P2 16 VS3 +0.74 TEH TEC 17 COLD 600UL TWD 40 104 0.55 151 P2 25 VS3 -0.87 TEH TEC 16 COLD 60OUL TWD TEC COLD 60OUL 94 104 0.21 21 P2 11 08C +0.80 TEH 25 TWD TEH TEC 25 COLD 600UL 126 104 0.42 109 P2 14 VS1 -0.83 TWD COLD 600UL 47 105 0.33 59 P2 19 VS3 -0.60 TEH TEC 17 TWD TEH COLD 600UL 0.39 19 P2 21 VS3 +0.77 TEC 17 24 106 0.30 137 P2 TWD 16 VS3 +0.72 TEH TEC 18 COLD 600UL 28 106 0.29 60 P2 TWD 16 VS3 +0.82 TEH TEC 18 COLD 600UL 32 106 0.48 69 P2 TWD 22 VS3 -1.01 TEH TEC 18 COLD 60OUL 42 106 0.18 113 P2 TWD 11 VS3 -0.32 TEH TEC 19 COLD 600UL 50 106 0.45 93 P2 TWD 23 VS3 +0.91 TEH TEC 19 COLD 600UL 29 107 0.29 31 P2 TWD 16 VS3 +0.68 TEH TEC 18 COLD 600UL 34 108 0.47 61 P2 TWD 23 VS3 -0.89 TEH TEC 19 COLD 60OUL 88 108 0.19 145 P2 TWD 16 05H +0.93 TEH TEC 28 COLD 600UL 96 108 0.66 119 P2 TWD 30 VS2 -0.86 TEH TEC 28 COLD 60OUL 0.22 51 P2 TWD 18 VS4 +0.86 TEH TEC 28 COLD 60OUL 93 109 0.14 140 P2 TWD 13 VS2 -0.92 TEH TEC 28 COLD 600UL 97 109 0.28 113 P2 TWD 20 VS2 -0.97 TEH TEC 28 COLD 600UL 0.21 28 P2 TWD 17 VS2 +0.85 TEH TEC 28 COLD 600UL 133 109 0.23 74 P2 TWD 12 08H +0.73 TEH TEC 58 COLD 600UL 0.21 104 P2 TWD 11 08H -0.75 TEH TEC 58 COLD 60OUL 50 110 0.22 135 P2 TWD 13 VS3 -0.89 TEH TEC 18 COLD 60OUL 0.21 133 P2 TWD 12 VS3 +0.66 TEH TEC 18 COLD 60OUL 132 110 0.31 103 P2 TWD 15 VS5 +0.85 TEH TEC 58 COLD 600UL 35 111 0.16 148 P2 TWD 11 VS3 -0.79 TEH TEC 19 COLD 60OUL 89 111 0.66 101 P2 TWD 29 VS4 -0.71 TEH TEC 35 COLD 600UL 34 112 0.17 157 P2 TWD 11 VS3 -0.73 TEH TEC 24 COLD 600UL TWD TEC 60OUL 90 112 0.11 138 P2 6 06H +0.87 TEH 36 COLD TWD TEC 60OUL 122 112 0.29 57 P2 15 VS4 -0.88 TEH 36 COLD
Framatome ANP Inc. 1/23/2005 08:32 Attacbfent 8 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G B Page 8 of 10 Total Number of Bobbin 1-39% TWD Indications left in service for Cycle 15 ROW LINE VOLTS DEG IND %TW LOCATION EXT EXT CAL # LEG PROBE C'HN 126 112 0.54 36 =WD 24 VS1 -0.84 TEH TEC 36 COLD 6==OUL P2 128 112 0.36 93 P2 TWD 19 DCT -0.10 TEH TEC 35 COLD 60OUL 25 113 0.21 129 P2 TWD 10 VS3 -0.72 TEH TEC 23 COLD 60OUL 96 114 1.10 127 P2 TWD 36 VS2 -0.81 TEH TEC 35 COLD 600UL 1.01 99 P2 TWD 35 VS2 -0.14 TEH TEC 35 COLD 600UL 0.68 69 P2 TWD 29 VS2 +0.52 TEH TEC 35 COLD 600UL 0.44 140 P2 TWD 22 VS3 -0.89 TEH TEC 35 COLD 600UL 0.74 69 P2 TWD 30 VS3 +0.18 TEH TEC 35 COLD 60OUL 0.59 147 P2 TWD 27 VS4 +0.89 TEH TEC 35 COLD 60OUL 51 115 0.20 121 P2 TWD 12 VS3 +0.85 TEH TEC 24 COLD 60OUL 52 116 0.20 152 P2 TWD 10 VS3 +0.92 TEH TEC 23 COLD 60OUL 0.10 17 P2 TWD 4 VS3 -0.92 TEH TEC 23 COLD 600UL 54 116 0.15 32 P2 TWD 10 VS3 +1.00 TEH TEC 24 COLD 60OUL 19 117 0.28 24 P2 TWD 14 VS3 +0.82 TEH TEC 23 COLD 60OUL 89 117 0.63 52 P2 TWD 28 VS2 -0.85 TEH TEC 36 COLD 600UL 0.36 106 P2 TWD 12 07H -0.88 TEH TEC 36 COLD 600UL 32 118 0.22 138 P2 TWD 13 VS3 +0.04 TEH TEC 24 COLD 600UL 54 118 0.24 37 P2 TWD 14 VS3 +0.97 TEH TEC 24 COLD 60OUL 112 118 0.18 19 P2 TWD 10 VS1 +0.60 TEH TEC 36 COLD 60OUL 96 120 0.38 152 P2 TWD 20 VS3 -0.89 TEH TEC 33 COLD 600UL 0.22 79 P2 TWD 14 VS3 +0.77 TEH TEC 33 COLD 600UL 5 121 0.10 125 P2 TWD 7 04C +0.96 TEH TEC 61 COLD 60OUL 51 121 0.24 12 P2 TWD 17 VS3 -0.83 TEH TEC 22 COLD 600UL 0.33 54 P2 TWD 21 VS3 +0.71 TEH TEC 22 COLD 60OUL 97 121 0.19 13 P2 TWD 11 VS2 -0.80 TEH TEC 34 COLD 60OUL 94 122 0.28 65 P2 TWD 16 VS2 -0.95 TEH TEC 34 COLD 60OUL 102 122 0.21 72 P2 TWD 12 VS1 -0.65 TEH TEC 34 COLD 60OUL 52 124 0.26 87 P2 TWD 18 VS3 -0.95 TEH TEC 22 COLD 60OUL 54 124 0.87 25 P2 TWD 30 VS3 +0.00 TEH TEC 20 COLD 60OUL 62 124 0.11 157 P2 TWD 7 05C +0.98 TEH TEC 20 COLD 60OUL 94 124 0.39 61 P2 TWD 20 VS2 -0.80 TEH TEC 34 COLD 60OUL 0.36 71 P2 TWD 19 VS3 -0.96 TEH TEC 34 COLD 60OUL 55 125 0.90 113 P2 TWD 31 VS3 -0.99 TEH TEC 20 COLD 600UL 36 126 0.14 148 P2 TWD 12 VS3 -0.93 TEH TEC 22 COLD 600UL 94 126 0.39 80 P2 TWD 21 VS2 -0.98 TEH TEC 33 COLD 60OUL 0.29 155 P2 TWD 17 VS3 -0.84 TEH TEC 33 COLD 60OUL 0.19 22 P2 TWD 12 VS4 +0.80 TEH TEC 33 COLD 600UL 93 127 0.12 76 P2 TWD 8 VS3 +0.60 TEH TEC 34 COLD 600UL 95 127 0.34 69 P2 TWD 19 VS2 -0.43 TEH TEC 33 COLD 60OUL 88 128 0.27 61 P2 TWD 15 08C -0.72 TEH TEC 34 COLD 600UL 85 129 0.21 65 P2 TWD 12 DHB +0.00 TEH TEC 34 COLD 60OUL 95 129 0.11 52 P2 TWD 8 VS2 +0.77 TEH TEC 33 COLD 60OUL 1 131 0.12 171 P2 TWD 8 04H +0.91 07H TEH 16 HOT 60OUL 87 131 0.21 157 P2 TWD 13 VS2 -0.67 TEH TEC 33 COLD 60OUL TWD 95 131 0.38 83 P2 21 VS2 -0.51 TEH TEC 33 COLD 60OUL TWD 39 133 0.18 8 P2 12 VS3 -0.99 TEC TEN 22 HOT 60OUL TWD 111 133 0.24 32 P2 16 05C +0.14 TEH TEC 31 COLD 60OUL TWD 54 134 0.25 45 P2 15 VS3 -0.88 TEC TEH 22 HOT 600UL TWD 0.27 106 P2 16 DCB +3.72 TEC TEH 22 HOT 60OUL TWD 60 134 0.43 74 P2 23 VS3 -0.69 TEC TEH 23 HOT 60OUL TWD 88 134 0.15 27 P2 10 VS2 -0.83 TEH TEC 32 COLD 60OUL TWD 104 134 0.26 130 P2 16 VS1 +0.70 TEH TEC 32 COLD 600UL TWD 55 135 0.21 30 P2 13 DCT +0.00 TEC TEH 22 HOT 60OUL P 2 TWD 87 135 0.28 124 17 VS2 -0.89 TEH TEC 32 COLD 60OUL
Framatome ANP Inc. 1/23/2005 08:32 Attacbment 8 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: SIG B Page 9 of 10 Total Number of Bobbin 1-39% TWD Indications left in service for Cycle 15 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 0.15 72 P2 =WD 10 VS3 -0.73 TEH TEC 32 COLD 60=UL 89 135 0.14 15 P2 TWD 10 VS2 +0.86 TEH TEC 31 COLD 60OUL 0.15 147 P2 TWD 11 VS2 -0.64 TEH TEC 31 COLD 60OUL 0.37 114 P2 TWD 22 DCB +0.00 TEH TEC 31 COLD 60OUL 42 136 0.27 40 P2 TWD 18 VS3 -0.71 TEC TEH 23 HOT 60OUL 94 136 0.39 132 P2 TWD 21 VS4 +0.91 TEH TEC 32 COLD 60OUL 0.15 51 P2 TWD 10 VS4 -0.28 TEH TEC 32 COLD 60OUL 108 136 0.60 126 P2 TWD 28 02C -0.85 TEH TEC 31 COLD 60OUL 35 137 0.34 102 P2 TWD 21 VS3 -0.87 TEC TEH 23 HOT 60OUL 0.25 34 P2 TWD 17 DHB +0.78 TEC TEH 23 HOT 60OUL 57 137 0.17 55 P2 TWD 11 VS3 +0.67 TEC TEH 22 HOT 60OUL 103 137 0.14 14 P2 TWD 10 VS2 +0.60 TEH TEC 31 COLD 60OUL 56 138 0.20 151 P2 TWD 13 VS3 -0.61 TEC TEH 22 HOT 60OUL 0.19 164 P2 TWD 12 VS3 +0.94 TEC TEH 22 HOT 60OUL 70 138 0.56 133 P2 TWD 26 VS3 +0.91 TEC TEH 23 HOT 60OUL 80 138 0.22 143 P2 TWD 15 08C -1.08 TEC TEH 23 HOT 60OUL 88 138 0.29 139 P2 TWD 19 DCB +0.00 TEH TEC 31 COLD 60OUL 92 138 0.18 24 P2 TWD 13 VS2 +0.83 TEH TEC 31 COLD 60OUL 55 139 0.88 85 P2 TWD 31 VS3 +0.98 TEC TEH 23 HOT 60OUL 94 140 0.18 15 P2 TWD 12 VS2 +1.38 TEH TEC 32 COLD 60OUL 39 141 0.40 159 P2 TWD 19 VS3 +0.87 TEC TEH 26 HOT 60OUL 77 141 0.29 30 P2 TWD 17 DCT +0.07 TEC TEH 27 HOT 60OUL 44 142 0.27 125 P2 TWD 16 07C -1.03 TEC TEH 27 HOT 60OUL 56 142 0.38 156 P2 TWD 19 07C -1.00 TEC TEH 26 HOT 60OUL 92 142 0.36 99 P2 TWD 21 VS2 +0.62 TEH TEC 31 COLD 60OUL 63 143 0.22 147 P2 TWD 13 VS3 -0.77 TEC TEH 26 HOT 60OUL 95 143 0.60 148 P2 TWD 25 VS2 -0.65 TEH TEC 27 COLD 60OUL 54 144 0.22 63 P2 TWD 13 DCT +0.00 TEC TEH 26 HOT 60OUL 94 144 0.37 130 P2 TWD 18 VS2 -0.87 TEH TEC 27 COLD 60OUL 0.13 156 P2 TWD 7 VS3 -0.98 TEH TEC 27 COLD 60OUL 0.30 25 P2 TWD 16 VS4 +0.81 TEH TEC 27 COLD 60OUL 53 145 0.15 162 P2 TWD 10 DCB +1.93 TEC TEH 26 HOT 600UL 52 146 0.13 32 P2 TWD 9 07C -0.91 TEC TEH 27 HOT 600UL 0.14 66 P2 TWD 10 VS3 +0.79 TEC TEH 27 HOT 600UL 0.34 28 P2 TWD 19 VS3 -0.76 TEC TEH 27 HOT 600UL 0.15 168 P2 TWD 10 06C +0.16 TEC TEH 27 HOT 600UL 76 146 0.21 16 P2 TWD 14 VS3 +0.80 TEC TEH 27 HOT 60OUL 0.34 59 P2 TWD 19 VS2 +0.85 TEC TEH 27 HOT 600UL 0.15 137 P2 TWD 10 VS4 -0.98 TEC TEH 27 HOT 600UL 85 147 0.27 69 P2 TWD 14 VS2 -0.99 TEH TEC 27 COLD 60OUL 33 151 0.11 53 P2 TWD B VS3 +1.08 TEC TEH 29 HOT 60OUL P2 TWD 60OUL 53 151 0.16 22 11 DCB +0.00 TEC TEH 29 HOT TWD 60OUL 60 152 0.24 25 P2 15 VS3 +0.50 TEC TEH 29 HOT P2 TWD 600UL 0.16 36 11 VS4 -0.91 TEC TEH 29 HOT P2 TWD 60OUL 64 152 0.39 92 21 VS2 -0.53 TEC TEH 29 HOT P2 TWD 60OUL 0.21 39 14 VS4 -0.67 TEC TEH 29 HOT P2 TWD 60OUL 69 153 0.26 28 16 VS4 -0.87 TEC TEH 29 HOT P2 TWD 60OUL 54 154 0.37 30 11 VS3 +0.02 TEC TEH 29 HOT P2 TWD 60OUL 61 155 0.10 8 8 VS2 +0.64 TEC TEH 29 HOT P2 TWD 60OUL 62 158 0.10 68 7 VS3 -0.96 TEC TEH 28 HOT P2 TWD 60OUL 55 159 0.31 25 18 DHT +0.00 TEC TEH 29 HOT P2 TWD 600UL 36 162 0.15 152 10 01H +0.83 TEC TEH 33 HOT P2 TWD 60OUL 40 162 0.35 116 17 01C -0.93 TEC TEH 33 HOT P2 TWD 60OUL 42 162 0.41 98 20 01C +0.91 TEC TEH 32 HOT
Framatome ANP Inc. 1/23/2005 08:32 Attacbernt 8 CSI-NDE-05-020 Customer Name: St. Lucie Unit 2 Component: S/G B Page 10 of 10 Total Number of Bobbin 1-39% TWD Indications left in service for Cycle 15 ROW LINE VOLTS DEG CHN IND %TW LOCATION EXT EXT CAL # LEG PROBE 27 163 0.49 62 P=2 TWD 22 VS3 +0.61 TEC TEH 33 HOT 60=OUL 35 163 0.17 9 P 2 TWD 10 01H +0.78 TEC TEH 33 HOT 60OUL 36 164 0.35 85 P 2 TWD 18 01C +0.02 TEC TEH 32 HOT 60OUL TWD 12 166 0.31 112 P 2 16 01C -0.98 TEC TEH 33 HOT 60OUL Total Tubes : 367 Total Records: 490