  • a o

E MISSISSIPPI POWER & LIGHT COMPANY Helping Bull yississippi

( P. O. BOX 1640.g ABb8 . MISSISSIPPI 39205 Q Nary 16,1984 NUCLE AR PRODUCTION DEPARTMENT U. S. Nuclear Regulatory Commission Region II 101 Marietta St., N.W., Suite 2900 Atlanta, Georgia 30303 Attention: Mr. J. P. O'Reilly, Regional Administrator

Dear Mr. O'Reilly:

SUBJECT:

Grand Gulf Nuclear Station Unit 1 Docket No. 50-416 License No. NPF-13 File 0260/L-835.0 Special Report 83-114/0 -

Control Room Temperature Exceeds Technical Specification Limit AECM-84/0011 On December 15, 1983, the temperature in the Control Room exceeded the Technical Specification limit of 77'F for a period of more than eight hours.

The maximum recorded temperature was 80*F. Control Room temperatures exceeded the temperature limit intermittently for a cumulative time of 17 hours1.967593e-4 days <br />0.00472 hours <br />2.810847e-5 weeks <br />6.4685e-6 months <br />.

All Control Room equipment is qualified to a maximum of 90*F. therefore, an analysis to demonstrate operability of this equipment is not r ired. To provide further clarification, the 90*F limit is the lowest maxims temperature.

There was no affect on the availability of or operability of equipment within this area. This is being submitted as a Special Report pursuant to Technical Specification 3.7.8 and 6.9.2. This is a final report.

Yours truly, L. F. Dale Manager of Nuclear Services EBS/SHH: sad cc: (See Next Page)

<,,,c)A}.C Q 8401260088 840116 -

gDRADOCK05000 Member Middle South Utilities System I b

a

(, AECM-84/0011

  1. E MISSISSIPf"I POWER O LICHT COMPANY cc: Mr. J..B. Richard-Mr. R. B. McGehee Mr. T. B. Conner Mr. G. B. Taylor Mr. Richard C. DeYoung, Director Office of Inspection & Enforcement U. S. Nuclear Regulatory Commission Washington, D. C. 20555 Document Control Desk U. S. Nuclear Regulatory Commission Washington, D. C. 20555