AECM-89-0056, Special Rept 89-002:on 890225,turbine Bldg Ventilation Exhaust Accident Range Radiation Monitor Removed from Svc. Channels 3 & 4 Failed & Channel 4 Remained in Check Source. Monitor Retested Satisfactorily & Restored to Svc on 890302

From kanterella
Jump to navigation Jump to search
Special Rept 89-002:on 890225,turbine Bldg Ventilation Exhaust Accident Range Radiation Monitor Removed from Svc. Channels 3 & 4 Failed & Channel 4 Remained in Check Source. Monitor Retested Satisfactorily & Restored to Svc on 890302
ML20236B666
Person / Time
Site: Grand Gulf Entergy icon.png
Issue date: 03/09/1989
From: Cesare J
SYSTEM ENERGY RESOURCES, INC.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
89-002, 89-2, AECM-89-0056, AECM-89-56, NUDOCS 8903210219
Download: ML20236B666 (2)


Text

, . _ _ _ _ - _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ - _ _ _ _ _ _ _ _ _ _ _ _ - _ _ _ _

~

t m, ,

ca . .

a EVETEM ENEINiiY MSOUMEE, UNC.

Jc*d G CESM JR f1 March 9, 1989

.U.S. Nuclear Regulatory Commission Mail Station P1-137-Washington, D.C. 20555 Attentioni Document Control Desk

' Gentlemen:

SUBJECT:

Crand Gulf Nuclear Station Unit 1 Docket No. 50-416 License No. NPF-29 Special Report 89-002/0 Inoperability of Accident Monitor Exceeds 72 Hours AECM-89/0056 A Turbine Building ventilation exhaust accident range radiation monitor was removed from service on February 25, 1989 at 0600 to perform a surveillance ,

as required by Technical Specification Table 4.3.7.5-1. Channels 3 and 4 -I failed and channel 4 remained in check source.

An investigation into the problem revealed the following defective components: flow switch, channel 4 check source mechanism, interface box, and detector' cable. The detector cable was reworked and the remaining defective components were replaced. The monitor retested satisfactorily and was restored to service on March 2, 1989 at 1550.

This Special Report is being submitted pursuant to Action 81 of Technical Specification Table 3.3.7.5-1 since the instrument channel inoperability exceeded 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />. The preplanned alternate method of monitoring as required by Action 81 is to utilize the Eberline Spring Monitoring System per procedure 08-S-04-220.  !

The effluent monitoring instrumentation was operable during this time period.

Yours truly, 8903210219 spo309 ,

{DR ADOCK 05000416 PDC  ;

JGC:jrs cc: (See next page) N >I'p ,

O P. O BOX 23070 l 3CKSOri MG563M1 T/z25-3070 l (col) 920210 J14AECM890308 - 1 A MMWh UWes Cm '

. ."'. -AECM-89/0056 Page 2 cc: Mr. W. T. Cottle Mr. T.:H. Cloninger Mr. R. B. McGehee Mr. N. S. Reynolds Mr. H. L. Thomas Mr. H. O. Christensen Mr. Stewart D. Ebneter Regional Administrator U.S. Nuclear Regulatory Commission Region 11 101 Marietta St. , N.W. , Suite 2900 Atlanta, Georgia 30323 Mr. L. L. Kintner, Project Manager Office of Nuclear Reactor Regulation U.S. Nuclear Regulatory Commission Mail Stop 14820 Washington, D.C. 20555 l