AECM-83-0529, Updated RO 83-035/1:on 830415,Fire Door 1A401 Blocked Open to Prevent Possibility of Personnel Injury Due to High Differential Pressure Across Door.Door Restored on 830717

From kanterella
Jump to navigation Jump to search
Updated RO 83-035/1:on 830415,Fire Door 1A401 Blocked Open to Prevent Possibility of Personnel Injury Due to High Differential Pressure Across Door.Door Restored on 830717
ML20085H625
Person / Time
Site: Grand Gulf Entergy icon.png
Issue date: 09/01/1983
From: Dale L
MISSISSIPPI POWER & LIGHT CO.
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
AECM-83-0529, AECM-83-529, RO-83-035-1, RO-83-35-1, NUDOCS 8309120179
Download: ML20085H625 (2)


Text

,

a MISSISSIPPI POWER &Mid,HT COM,PANY Y Helping Build Mississippi . p 'h, EulMdMaddE P. O. B O X 16 4 0, J A C K S O N , M I S S I S S I P P I Yk32 0 5 NUCLEAR PnoDUCTioN DEPARTMENT b h ,'

U. S. Nuclear Regulatory Commission Region II 101 Marietta St., N.W., Suite 2900 Atlanta, Georgia 30303 Attention: Mr. J. P. O'Reilly, Regional Administrator

Dear Mr. O'Reilly:

SUBJECT:

Grand Gulf Nuclear Station Unit 1 Docket No. 50-416 License No. NPF-13 File 0260/L-835.0 Special Report 83-035/1 -

Update Report - Fire Door 1A401 Blocked Open AECM-83/0529 This is an update to a previous report submitted on May 20, 1983. The condition for which the report was submitted occurred on April 15, 1983, when fire door 1A401 (double-door entrance from Turbine Building to the Auxiliary Building, elevation 166 feet) was blocked open to prevent the possibility of personnel injury due to the high differential pressure across the door (opens rapidly and with force) and to ease access for plant personnel utilizing the pathway since this door was in heavy use. The high differential pressure is a result of the fact that this is a secondary containment boundary (secondary containment integrity is not required in the present plant mode-Cold Shutdown). Technical Specification 3.7.7 requires the door to be closed at all times. Since the door was blocked open for more than 7 days, this report was submitted as a Special Report pursuant to Technical Specification 6.9.2.

Fire door 1A401 was restored to operability on July 17, 1983. This is a final report.

Yours truly, L. F. Dale Manager of Nuclear Services EBS/SHH: sap cc: (See Next Page) 8309120179 830901 PDR ADOCK 05000416 .

S PDR - y g p1 b '

Member Middle South Utilities System f}' )

L

4

'

  • AECM-83/0529 MIMIMIPPI POWER & LIGHT COMPANY cc: Mr. J. B. Richard Mr. R. B. McGehee Mr. T. B. Conner Mr. G. B. Taylor Mr. Richard C. DeYoung, Director Office of Inspection & Enforcement U. S. Nuclear Regulatory Commission Washington, D. C. 20555 Document Control Desk U. S. Nuclear Regulatory Commission Washington,_D. C. 20555

~