AECM-83-0193, RO 83-008-0:on 830218,during Cold Shutdown,Fire Door 1A315 Alarmed on Fire Protection Computer.Caused by Out of Alignment Magnet in Magnetic Switch.Magnet Adjusted.Door Returned to Operation After Functional Test

From kanterella
Jump to navigation Jump to search
RO 83-008-0:on 830218,during Cold Shutdown,Fire Door 1A315 Alarmed on Fire Protection Computer.Caused by Out of Alignment Magnet in Magnetic Switch.Magnet Adjusted.Door Returned to Operation After Functional Test
ML20072S818
Person / Time
Site: Grand Gulf Entergy icon.png
Issue date: 03/25/1983
From: Mcgaughy J
MISSISSIPPI POWER & LIGHT CO.
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
AECM-83-0193, AECM-83-193, RO-83-008-0, RO-83-8, NUDOCS 8304070352
Download: ML20072S818 (2)


Text

.

e .-

\

MISSISSIPPI POWER & LIGHT COMPANY Helping Build Mississippi P. O. B O X 164 0, J AC K S O N, MIS SIS SIP PI 3 9 2 05 March 25, 1983 JAMES P. McGAUGHY. JR.

vece passineser CO c.a Office of Inspection & Enforcement >

U. S. Nuclear Regulatory Commission Region II g  ;}

7; o 101 Marietta St., N.W., Suite 2900 -

Atlanta, Georgia 30303 .E p u ,

E5 Attention: Mr. J. P. O'Reilly, Regional Administrator ,, 7 .

Dear Mr. O'Reilly:

I

SUBJECT:

Grand Gulf Nuclear Station Unit 1 Docket No. 50-416 License No. NPF-13 File 0260/L-835.0 Special Report 83-008/0 - Fire Door lA315 Alarmed and Would Not Reset AECM-83/0193 On February 18, 1983, during cold shutdown, fire door lA315 (electrical penetration room) alarmed ca the fire protection computer. After verification that the door was clorad, tne alarm was deactivated and voluntary entry into the action statement of Technical Specification 3.7.7 was initiated.

This condition had no affect on the health and safety of the public and did not constitute a threat to plant safety. Upon investigation, maintenance personnel found the magnet in the magnetic switch out of alignment. The magnet was adjusted and after a functional test the door was returned to operation. The 7 day time limit of the Limiting Condition for Operation was exceeded by 14 days. This is a Special Report submitted pursuant to Technical Specification 6.9.2.

Your truly, I 1 if JPM: sap -* '

cc: (See Next Page) 8304070352 830325

PDR ADOCK 05000416 S PDR U Fi ,j a g ( ,

E ' .*L .t )

Member Middle South Utilities System

, AECM-83/0193 MISSISSIPPI POWER Q LICHT CEMPANY Pcgn 2 cc: Mr. J. B. Richard Mr. R. B. McGehee Mr. T. B. Conner Mr. G. B. Taylor Mr. Richard C. DeYoung Director Office of Inspection & Enforcement U. S. Nuclear Regulatory Commission Washington, D. C. 20555 Document Control Desk U. S. Nuclear Regulatory Commission Washington, D. C. 20555