05000285/LER-1982-017, Advises That Faulty Conax feed-through Assemblies, Identified in 821001 LER 82-017,replaced & Valve VA-81A Returned to Svc,Per NUREG-0737,Item II.F.1.6, Containment Hydrogen Monitors

From kanterella
Jump to navigation Jump to search
Advises That Faulty Conax feed-through Assemblies, Identified in 821001 LER 82-017,replaced & Valve VA-81A Returned to Svc,Per NUREG-0737,Item II.F.1.6, Containment Hydrogen Monitors
ML20073E405
Person / Time
Site: Fort Calhoun Omaha Public Power District icon.png
Issue date: 04/05/1983
From: William Jones
OMAHA PUBLIC POWER DISTRICT
To: Clark R
Office of Nuclear Reactor Regulation
References
RTR-NUREG-0737, RTR-NUREG-737, TASK-2.F.1, TASK-TM LIC-83-078, LIC-83-78, NUDOCS 8304150127
Download: ML20073E405 (1)


LER-2082-017, Advises That Faulty Conax feed-through Assemblies, Identified in 821001 LER 82-017,replaced & Valve VA-81A Returned to Svc,Per NUREG-0737,Item II.F.1.6, Containment Hydrogen Monitors
Event date:
Report date:
2852082017R00 - NRC Website

text

i l

Omaha Public Power District 1623 Harnetj Ornaha. Nebraska 68102 402/536 4000 April 5, 1983 LIC-83-078 Mr. Robert A. Clark, Chief II . S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Division of Licensing Operating Reactors Branch No. 3 Washinqton, D.C. 20555

Reference:

Docket No. 50-285

Dear Mr. Clark:

NUREG-0737, Item II.P.1.6 Containment Hydrogen Monitors Omaha Public Power District's letter and attached Licensee Event Report (LER 82-017) to the Commission dated October 1, 1982, identifled the valve failures associated with one of the two containment hydrogen monitors. VA-81A was isolated following the valve failures pending completion of repairs.

The valve failures were originally traced to damaged sole-noid coils. Further investigation has shown the cause to be fallure of the Conax feed-through assemblies. The faulty assemblies have been replaced and VA-81A has been returned to service.

l

, Sincerely,

,.jp

)

_/ ) ]) 0 M C.s, I

Jones Division Manager Produ'ction Operations WCJ/TLP:jmm cc: LeBoeuf, Lamb, Leiby & MacRae OY 1333 New Hampshire Avenue, N.W. Il I Washington, D.C. 20036 Mr. L. A. Yandell, NRC Senior Resident Inspector 8304150127 830405 PDR ADOCK 05000285 S PDR 6 5124 t mployment with Equal Opportunity Male,remaie