Responds to NRC 850228 Ltr Re Violations Noted in Insp Repts 50-335/85-04 & 50-389/85-04.Corrective Actions:Pump & Valve Summary Book Updated to Indicate Current Status of Surveillance & Test Activities of safety-related Equipment
ML17301A182
Person / Time
Site: Saint Lucie  NextEra Energy icon.png
Issue date: 03/29/1985
From: WILLIAMS J W
FLORIDA POWER & LIGHT CO.
To: GRACE J N
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
Shared Package
ML17301A181 List:
References
L-85-127, NUDOCS 8505220334
Download: ML17301A182 (3)


See also: IR 05000335/1985004

Text

~5APg3~9,c/7FLORIDAPOWER&LIGHTCOMPANYNN291S86L-85-127Dr.3.NelsonGraceRegionalAdministrator,

RegionIIU.S.NuclearRegulatory

Commission,

Suite2900101MariettaStreetN.W.Atlanta,Georgia30323DearDr.Grace:Re:St.LucieUnits1and2DocketNos.50-335,50-389InsectionReort335/85-00

and389/85-00

FloridaPower4LightCompanyhasreviewedthesubjectinspection

reportandaresponseisattached.

Thereisnoproprietary

information

inthereport.Verytrulyyours,IGroupViresidentNuclearEnergy3WW/SAY/jsAttachment

cc:HaroldF.Reis,EsquirePNS-LI-85-125v

e8508220334

8504-16PDRADOCK05000335PEOPlE...

SERVINGPEOPLE

ATTACHMENT

Re:St.Lucie:Units1and2DocketNos.-50-335,50-389IEInsectionRert335/85-00

and389/85-00

FindingTechnical

Specification

6.8.l.c.(Units1and2)requiresthatprocedures

beimplemented

forsurveillance

andtestactivities,

ofsafety-related

equipment.

Paragraphs

8.2.5.Band8.2.8.AofAdministrative

Procedure

0010132,theapplicable

procedure

forinservice

testing(IST)ofASMEpumpsandvalves,requiresthatentriesbemadeinthecontrolroom"PumpandValveSummary"booktoindicatethecurrentstatusoftesting.Contrarytotheabove,on3anuary30,1985,procedure

0010132hadnotbeenproperlyimplemented

inthatentriesindicating

testingstatushadnotbeenmadefor:Unit1Chargingpump1B,3uly1980;Unit2Hydrazine

pumps2Aand2B,April-3une1980;Unit2HighPressureSafetyInjection

(HPSI)pump2A,3anuary-February

1980;andUnit2LowPressureSafetyInjection

(LPSI)pump2A,3anuary-February

1980..Response1.FPLconcurswiththefinding.2.Thereasonforthefindingwaspersonnel

oversight

inthattheentrieswerenotmadeinPumpandValveSummaryBooktoindicatethecurrentstatusofthetestingasrequiredbyprocedure.

3.ThePumpandValveSummaryBookhasbeenupdatedtoindicatethecurrentstatusofsurveillance

andtestactivities

ofsafety-related

equipment.

0.FPLismakingappropriate

procedure

changestomodifythemethodandresponsibility

formaintaining

thepumpssummarydata.5.Fullcompliance

isexpectedtobeachievedby3une30,1985.