Responds to NRC Bulletin 90-001, Loss of Fill Oil in Transmitters Mfg by Rosemount. No Rosemount Transmitters Models 1153 Series B,1153 Series D & 1154 Mfg Prior to 890711 Supplied by Different Vendor
ML17223A849
Person / Time
Site: Saint Lucie  NextEra Energy icon.png
Issue date: 07/18/1990
From: Bohlke W
FLORIDA POWER & LIGHT CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
REF-PT21-90 IEB-90-001, IEB-90-1, L-90-258, NUDOCS 9007230269
Download: ML17223A849 (10)


Text

ACCELERATED I+TRIBUTION DEMONS+ATION SYSTEM REGULATORY INFORMATION DISTRIBUTION SYSTEM (RIDS)

ACCESSION NBR:9007230269 'OC.DATE: 90/07/18 NOTARIZED: YES DOCKET FACIL:50-335 St. Lucie Plant, Unit 1, Florida Power & Light Co. 05000335 50-389 St. Lucie Plant, Unit 2, Florida Power & Light Co. 05000389 AUTH. NAME AUTHOR AFFILIATION BOHLKE,W.H. Florida Power & Light Co.

RECIP.NAME RECIPIENT AFFILIATION Document Control Branch (Document Control Desk)

SUBJECT:

Responds to NRC Bulletin 90-001, "Loss of Fill-Oil in Transmitters Mfg by Rosemount."

DISTRIBUTION CODE: IE39D COPIES RECEIVED:LTR ENCL SIZE:

TITLE: NRC Bulletin 90-001, Loss of Fill Oil in Transmitters Mfg y NOTES:

RECIPIENT COPIES RECIPIENT COPIES ID CODE/NAME PD2-2 LA LTTR ENCL ID CODE/NAME PD2-2 LTTR .ENCL 1 0 PD 1 1 NORRIS,J 1 1 INTERNAL NRR LE I N 1 1 NRR PERCH,R 1 1 NRR RAMSEY,Z 2 2 I NRR/ DR S/RVI B 1 1 RES=-PXEE ORM~ 1 1 RES FARMER, W 1 1 RGN2 FILE 01 1 1 EXTERNAL: LPDR 1 1 NRC PDR NSIC 1 1 NOTE TO ALL "RIDS" RECIPIENTS:

PLEASE HELP US TO REDUCE WASTE! CONTACT THE DOCUMENT CONTROL DESK, ROOM P 1-37 (EXT. 20079) TO ELIMINATEYOUR NAME FROM DISTRIBUTION LISTS FOR DOCUMENTS YOU DON'T NEED!

TOTAL NUMBER OF COPIES REQUIRED: LTTR 14 ENCL 13

I I

P.O. Box 14000, Juno Beach, FL 33408-0420 i,8 1990 APL pygmy L-90-258 10 CFR 50.54 (f)

U.S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, D. C. 20555 Gentlemen:

Res St. Lucie Units 1 and 2 Docket Nos. 50-335 and 50-389 NRC Bulletin 90-01 Loss of Pill-Oil in Transmitters Manufactured b Rosemount Bulletin 90-01, "Loss of Fill-Oil in Transmitters Manufactured by Rosemount,u requested that licensees take appropriate corrective actions for Model 1153 Series B, Model 1153 Series D, and Model 1154 transmitters manufactured by Rosemount that may be leaking fill-oil.

In accordance with the bulletin, Florida Power and Light provides the attached response relative to the St. Lucie Plant.

Should there be any questions concerning this response, please contact us ~

Very truly yours, W. H. Bohlke Vice President Nuclear Engineering and Licensing WHB/JMP/jat Copies to: Stewart D. Ebneter, Regional Administrator, Region II, USNRC Senior Resident Inspector, USNRC, St. Lucie Plant 9007230 QP 90071P POR ADOCK 05000335 9 PDC oo FPL Group company ger~

rr

STATE OF FLORIDA )

) ss.

COUNTY OF PALMBEACH )

W.H. Bohlke, being first duly sworn, deposes and says:

That he is Vice President - Nuclear Engineering and Licensing of Florida Power and Light Company, the Licensee herein; That he has executed the foregoing document; that the statements made in this document are true and correct to the best of his knowledge, information, and belief, and that he is authorized to execute the document on behalf of said Licensee.

W.H. Bohlke Subscribed and sworn to before me this Z- dayof 19'otary Public, in and for the County of Palm Beach, State of Florida

<Orl4Y gU8L IC 5gj[F. OR FLORIDA AT, 4QQL 11'NM155108 PUB QEQ 2h 19~1

-My Commission expires

Attachment FLORIDA POWER AND LIGHT ST. LUCIE UNITS 1 AND 2 NRC BULLETIN 90-01 LOSS OF FILL-OIL IN TRANSMITTERS MANUFACTURED BY ROSEMOUNT Florida Power and Light provides the following information relative to St. Lucie Units 1 and 2 in response to NRC Bulletin 90-01:

Re rtin Re uirement 1.a

1. Provide, within 120 days after receipt of this bulletin, a response that:

a) Confirms that Items 1, 2, 3, 4, and 5 of Requested Actions for Operating Reactors have been completed.

Florida Power and Light confirms that the following actions have been completed:

AllRosemount transmitters models 1153 Series B, 1153 Series D and 1154 manufactured prior to July 11, 1989 currently utilized in either safety-related systems or systems installed in accordance with 10 CFR 50.62 have been identified. Transmitter identification was performed using the plant instrument index, the total equipment data base and field inspection. No transmitters were identified as being manufactured by Rosemount but supplied by a different vendor.

2. Transmitters from inanufacturing lots having a high failure fraction due to loss of fill-oil have been identified. All such transmitters have been removed from service in the reactor protection and engineered safety features systems on both St. Lucie units.
3. Plant transmitter calibration records have been reviewed. There are no transmitters

which have exhibited symptoms of loss of fill-oil in service in any safety-related systems or systems in service in accordance with 10 CFR 50.62 in either St. Lucie unit at this time.

4. An 'enhanced surveillance program is in place for all Rosemount transmitters identified in Item 1.
5. A basis for continued operation has been formulated in accordance with Bulletin 90-01 guidelines.

Re rtin R firemen 1.

Provide, within 120 days after receipt of this bulletin, a response that:

b) Identifies the indicated manufacturer, the model number, the system the transmitter was utilized in; the approximate amount of time at pressure; the corrective actions taken; and the disposition of Rosemount Model 1153 Series B, Model 1153 Series D, and Model 1154 transmitters that are believed to have exhibited symptoms indicative of loss of fill-oilor have been confirmed to have experienced a loss of fill-oil. This should include Model 1153 Series B, Model 1153 Series D and Model 1154 transmitters manufactured after July 11, 1989.

Table One of this Attachment provides the requested information.

Re ortin R uiremen 1.c Provide, within 120 days after receipt of this bulletin, a response that:

c) Identifies the system in which the Model 1153 Series B, 1153 Series D, and Model 1154 transmitters from the manufacturing lots that have been identified by Rosemount as having a high failure fraction due to loss of fill-oil are utilized and provides a schedule for replacement of these transmitters which are in use in the reactor protection or engineered safety features actuation systems.

FPL Res onse:

There are no safety-related transmitters from the manufacturing lots 1

IH that have been identified by Rosemount as having a high failure fraction currently in service in either St. Lucie Unit 1 or St. Lucie Unit 2.

There are no safety-related transmitters from the manufacturing lots that have been identified by Rosemount as having a high failure fraction currently in service in the reactor protection systems or the engineered safeguards systems in either St. Lucie Unit 1 or St.

Lucie Unit 2; therefore, no schedule for replacement is required.

Re rtin Re ii m n 2

2. Model 1153 Series B, Model 1153 Series D and Model 1154 transmitters that, subsequent'o providing the response required by Item 1 above, exhibit symptoms of loss of fill-oilor are confirmed to have experienced a loss of fill-oilshould be reviewed for teportability under existing NRC regulations. Ifdetermined not to be reportable, addressees are requested to document and maintain, in accordance with existing plant procedures, information consistent with that requested in Item 1) above for each transmitter identified.

Transmitters which exhibit symptoms of loss of fill-oilor are confirmed to have experienced a loss of fill-oilwillbe reviewed for reportability under existing NRC regulations. Ifdetermined not to be reportable, information such as the model number; the system the transmitter was utilized in; the approximate amount of time at pressure; the corrective actions taken; and the disposition of the transmitter will be documented and maintained.

Table One Reporting Requirement 1.b TRANSMITTERS SUSPECTED TO HAVE EXPERIENCED A LOSS OF FILL-OIL Transmitter Transmitter ~Sstem Time at Pressure Corrective Actions Dis osition of Transmitter Manufacturer Model Number Rosemount 1153GD9PB, Unit 1 56 months The transmitter has been The transmitter is being Serial Number Reactor Coolant removed from service. decontaminated prior to shipment 408575 System- to Rosemount for further Pressurizer analysis.

Rosemount 1153DB5, Unit 2 8 months The transmitter has been The transmitter was sent to Serial Number Component removed from service. Rosemount for further analysis.

328254 Cooling Water Based upon test results, Rosemount determined that the transmitter had not experienced a loss of fill-oil.