REGULATORY INFORMATION DISTRIBUTION SYSTEM (RIDS)

ACCESSION NBR:9910290294 DOC.DATE: 99/10/21 NOTARIZED- NO DOCKET FACIL:50-335 St. Lucie Plant', Unit 1, Florida Power & Light Co. 05000335 AUTH. NAME AUTHOR AFFILIATION STALL,J.A. Florida Power & Light Co.

RECIP.NAME RECIPIENT AFFILIATION Records Management Branch (Document Control Desk)

SUBJECT:

Forwards rev 3 to Emergency Response Data Sys (ERDS) Data Point Library for St Lucie Unit 1.Rev provides replacement pages & follows format recommeneded by iWREG 1394, "ERDS Implementation," rev 1 App C.

DISTRIBUTION CODE: A026D" COPIES RECEIVED:LTR ENCL SIZE-TITLE: Emergency Response Data System (ERDS)

NOTES:

RECIPIENT COPIES RECIPIENT COPIES ID CODE/NAME LTTR ENCL ID CODE/NAME LTTR ENCL AEOD/IRB 01 1 1 GLEAVES,W 1 1 INTERNAL: ACRS 1 1 AEOD 1 1 L CENTE~ 1 1 IRO 1 1 GN2 ER~ 1 1 RGN2 FILE 1 1 EXTERNAL: NRC PDR NOTE TO ALL "RIDS" RECIPIENTS:

PLEASE HELP US TO REDUCE WASTE. TO HAVE YOUR NAME OR ORGANIZATION REMOVED FROM OR REDUCE THE NUMBER OF COPIES RECEIVED BY YOU OR YOUR ORGANIZATION, DISTRIBUTION LIS CONTACT THE DOCUMENT CONTR DESK (DCD) ON EXTENSION 415-2083 TOTAL NUMBER OP COPIES REQUIRED: LTTR 9 ENCL 9

Florida Power & Light Company, 6351 S. Ocean Drive, Jensen Beach, FL 34957 October 21, 1999 PPL L-99-229 10 CFR 50 Appendix E U. S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, D. C. 20555 RE: St. Lucie Unit 1 Docket No. 50-335 Emergency Response Data System Data Point Lib Revision 3 Pursuant to 10 CFR 50, Appendix E Section VI.3.a, Florida Power.& Light Company (FPL) submits Revision 3 of the Emergency Response Data System (ERDS) Data Point Library for St.

Lucie Unit 1. The revision provides replacement pages and follows the format recommended by NUREG 1394, Emergency Response Data System (EROS) Implementan'on, Revision 1 Appendix C (Data Point Library). The last revision of the St. Lucie Unit 1 Emergency Response Data System (ERDS) Data Point Library was submitted by FPL letter L-98-224 dated September 8, 1998.

The attachment is-the replacement pages for the St. Lucie Unit 1 ERDS Data Point Library-Revision 3.

In preparation of this and our previous submittal (I 98-224), FPL identified a potential omission in 10 CFR 50.4(b)(5), Emergency plan and related submittals. The potential omission is that the ERDS Data Point Library submittals required by 10 CFR 50, Appendix E VI.3 should be added to 10 CFR 50.4(b)(5), and that 10 CFR 50, Appendix E should be modified to reference 10 CFR 50.4. This would eliminate any confusion regarding the addressee or distribution of the required submittals. The CFR still contains this omission.

Please contact us ifthere are any questions regarding this submittal.

Very truly yours, J. A. Stall Vice President St. Lucie Plant JAS/GRM cc: Regional Administrator, Region II, USNRC Senior Resident Inspector, USNRC, St. Lucie Plant 99i0290294 99i02i PDR ADQCK 05000335 F PDR an FPL Group company

t

gi.

St. Lucie Unit 1 Docket No. 50-335 L-98-229 Attachment Attachment St. Lucie Unit 1 ERDS Revision 3 Data Point Library Updates SL1

St. Lucie Unit 1 Docket No. 50-335 L-98-229 Attachment UNIT 1 DPL UPDATES REVISION 3

,:Pa e Plant- Point:.De'seri tion Ori 'inal:Ran e u dated:ran Reason. for U date 12 Feedwater Flow A e.'.00 0.00 to to Venturi cleaned and 6.040E+06 ~

6,050,080.0 recalibrated 13 Feedwater Flow B 0.00 to 0.00 to Venturi cleaned and 6.038E+06 6,048,095.0 recalibrated

SL1 DATA POINT'ISRARY REFERENCE FILE Page 12 of 47

~

. REV 03 Date: ........., .......

Reactor Uni t: ...~....~........... ~... SL1~ ~

10/06/99 t\ lh D ata Feeder..~...............~.........

~

~ N/A NRC ERDS Parameter: ..............MN FD FL 1/A Point ID: .QA0025-1 Plant Spec Point Desc:.. ~ ......FEEDWATER FLOW A Generic/Cond Desc: ........ .....Stm Gen A Main Feedwater

~

Flow Analog/Digital: ..................~...A Engr Units/Dig States:. ~ ~ ......LBM/HR Engr Units Conversion:. ......N/A ~ ~

Minimum Instr Range:.............0.00 Maximum Instr Range.............6050080.0 /R03 Zero Point

Reference:

........ .N/A ~ ~

Reference Point Notes:... .....N/A ~

PROC or SENS: ...............~........ ~ ~ P Number of Sensors: Levels

................3 How Processed: ........................ REDUNDANT SENSOR ALGORITHM Sensor Locations: .................. TURBINE BUILDING 43 FT. LVL Alarm/Trip Set Points:.... ....VARIABLE ~

NI Detector Power Supply Cut-Off Power ...... .....N/A

~ ~

NI Detector Power Supply Turn-on Power Level . ~...........N/A

~

Instrument Failure Mode.... ..N/A ~

Temperature Compensation for DP Transmitters........

Level Refer'ence Leg:......... .N/A ~

"A" steam generator main feedwater Unique System

Description:

.This parameter is the flow. It is derived from Steam Generator Main Feedwater Flow signals FT09-3A1-1, FT09-3A2-1, and FT09-3A3-1 which are square roots. These signals are processed with a redundant sensor algorithm. This function obtains the average of .the current values that have a good status and are close to the statistical majority.

SL1 DATA POINT LIBRARY REFERENCE FILE Page 13 of 47 REV 03 Date: .......,................, .......10/06/99 Reactor Unit: ......,......~.......... .SL1 ~

Data Feeder: ...........,............ . N/A ~ ~ ~

NRC ERDS Parameter: .... ..... ...MN FD FL 2/B

~ ~

Point ID: ...................,..............QA0026-1 Plant Spec Point Desc:........ FEEDWATER FLOW B ~

~

Generic/Cond Desc: ............... Stm Gen B Main Feedwater Flow

~

Analog/Di gi tal:.....~... ..,..... ..A~ ~

Engr Units/Dig States: ~ ~ ~ ~ ~.... LBM/HR Engr Units Conversion: ~.......N/A ~

Minimum Instr Range: .......... 0.00 ~ ~ ~

Maximum Instr Range:...........6048095.0 /R02 Zero Point

Reference:

... ... ..N/A ~ ~ ~

Reference Point Notes: ......N/A ~ ~ ~

PROC or SENS r ~ ~ ~~ ~~~~~~ ~~~~~ ~ ~ ~ ~~~ ~~~~ P Number of Sensors ~............. 3 ~ ~

How Processed: .......... .,.. .. ..REDUNDANT SENSOR ALGORITHM

~ ~ ~ ~ ~ ~

Sensor Locations: ..., ~.... ..~..... TURBINE BUILDING 43 FT. LVL

~

Alarm/Trip Set Points:... .....VARIABLE ~

NI Detector Power supply Cut-Off Power Level:.~....,....N/A NI Detector Power Supply Turn-on Power Level:.. ...... AN/A ~ ~

Instrument Failure Mode:.....N/A Temperature Compensation for DP Transmitters:.......

Level Refer ence Leg:,.....~....N/A Unique System

Description:

.This parameter is the "B" steam generator main feedwater flow. It is derived from Steam Generator Main Feedwater Flow .signals FT09-3B1-1, FT09-3B2-1, and FT09-3B3-1 which are square roots. These signals are processed with a redundant sensor algorithm. This function obtains the average of the current values that have a good status and are close to the statistical majority.