Revises 890914 Partial Response to Item 1 Re NUREG-0737, Item II.D.1, Performance Testing of Relief & Safety Valves, Per 871020 Request.Porv & PORV motor-operated Block Valves Decsriptions Encl
ML18054B298
Person / Time
Site: Palisades Entergy icon.png
Issue date: 12/12/1989
From: Smedley R
CONSUMERS ENERGY CO. (FORMERLY CONSUMERS POWER CO.)
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
RTR-NUREG-0737, RTR-NUREG-737, TASK-2.D.1, TASK-TM TAC-44604, NUDOCS 8912180095
Download: ML18054B298 (5)


Text

consumers Power POWERINli MICHlliAN'S PRDliRESS General Offices: 1945 West Parnall Road, Jackson,' Ml 49201 * (517) 788-0550 December 12, 1989 Nuclear Regulatory Commission Document Control Desk Washington, DC 20555 DOCKET 50-255 - LICENSE DPR PALISADES PLANT -

NUREG 0737 II.D.l, PERFORMANCE TESTING OF RELIEF AND SAFETY VALVES (TAC 44604) - ADDITIONAL INFORMATION NRC letter dated October 20, 1987 requested 10 items of additional information regarding NUREG 0737, Item II.D.l - Performance Testing of Relief and Safety Valves. Consumers Power Company (CPC) letters dated September 14, 1988, May 25, 1988 and March 30, 1989 responded to all of the Items in the request except Item 1. The letter dated September 14, 1988 provided a partial response to Item 1. Attachments 1 & 2 to this letter revise that partial response to Item 1 (block valve and PORV descriptions) provided in our September 14, 1988 letter.

NRC letter dated November 9, 1989 transmitted a Technical Evaluation Report (TER) which evaluates the Palisades compliance with NUREG 0737, Item II.D.l, Performance Testing of Relief and Safety Valves, and requested additional information regarding functional qualification of the new PORV and block valves. That information will duplicate the information requested by Item 1 of the October 20, 1987 RAI. Therefore, as discussed with the NRC Palisades Project Manager, CPC considers all items of the October 20, 1987 RAI to be complete. A description of the functional qualification of the new PORVs and block valves will be provided in our response to the November 9, 1989 Technical Evaluation Report.

Richard W Smedley Staff Licensing Engineer CC Administrator, Region III, USNRC NRC Resident Inspector - Palisades Attachments OC1189-0224-NL04

=:*~? :L 21 :3(>(> :>'5 E:*::-1 121 :2 1

PDR ADOCK 0!:5000:255 A CAf5' ENERGY COMPANY p F'DC

ATTACHMENT 1 Consumers Power Company Palisades Plant Docket 50-255 POWER-OPERATED RELIEF VALVES Revision 1 December 12, .1989 1 Page OC1189-0224-NL04

POWER-OPERATED RELIEF VALVES Valve:

Manufacturer Target Rock Model No/Catalogue No 100 Type Globe "Y" Type Design Pressure 2500 psi Design Temperature 700°F I Size-Inlet 4" Size-Outlet 4" Rating-Inlet-ANSI Pressure Class 1736 Weld End I Rating-Outlet-ANSI Pressure Class 900 Weld End I Pressure-Operating 2075 psia Pressure-Relief 2250 psia r Pressure Drop at Each Rated Capacity Critical tJ.p/stm 137 psi water Temperature-Operating 652.7°F Temperature-Relief 641. 03 °F Set Pressure* 2400 psia Capacity (For Each Operating Condition) 159.511/sec stm 165.711/sec wtr.

C , K-Factor Cv=219/K-4.46 I EXd/End (Straight Through) 18. 00 11 Wei~ht With Operator and Centzr of Gravity 50711/10-3/4" above £ Throat Cross Section Area (in ) at Full Lift 5. 774 I Lift, in 1.00 I Material:

Hard Facing Material Stellite 6 Body SS 316 Bonnet SS 316 Seat SS316 SS hardfaced Disc 17-4 PH Guide & Ring(s) 440C/17-7 PH Spring A-286 Operator:

Manufacturer Target Rock Type Solenoid Electric-Voltage Required Inrush & Holding, 125 VDC, 3.5 amps Amperes in rush & holding Nema Size, Coil Insulation Rating CL H insulation AIR-PSI (Minimum/Maximum & CFM)

Opening Time (seconds) <2.0 sec I Closing time (seconds) <2.0 sec I Limit Switches - (Number, Type, Rating). 4/reed switches, 3 amps OC1189-0224-NL04

ATTACHMENT 2 Consumers Power Company Palisades Plant Docket 50-255 PORV MOTOR OPERATED BLOCK VALVES Revision 1 December 12, 1989 1 Page OC1189-0224-NL04

PORV MOTOR OPERATED BLOCK VALVES Valve:

Manuafacturer Edward Valve I Model No/Catalogue No Fig 12011 Type Wedge Gate Design Pressure 2500 psi Design Temperature 700°F Size-Inlet 4-in <j>Weld end Size-Outlet 4-in <j>Weld end Rating-Inlet-ANSI Pressure Class (Std or Spec) 1550 lb. ANSI Special Class Rating-Outlet-ANSI Pressure Class (Std or Spec) 1550 lb. ANSI Special Class Pressure Drop at Each Rated Capacity Pressure Maximum Temperature Maximum C , K-Factor 760 Ei{d/End (Straight Through) 16-in*

Weight With Operator and Center of Gravity 535 CG 18-in CL Material:

Hard Facing Material SA-351 GR CF8M Body SS SA-351 GR CF8M Bonnet-Type* SS SA-182 GR F316 Seat/Type Disc/Type SS SA-487 GR CA6NM Trim Packing Garlock 98 11/

Garfoil Ctr Rings Operator:

Manufacturer Limitorque Model Number SMB-00-25 Nema Size RPM (Motor)

Voltage - Nominal 1700 I Time/Open (Seconds) for Each 460 VAC I Operating Condition 22 sec. max I Time/Close (Seconds) for Each Operating Condition 22 sec. max I Motor Size Rating I Current, Starting, Operating, Maximum Torque Set Handwheel Manual Operator (Yes/No) Yes I Limit Seitches (Number, Type, Rating) 4 NAMCO EA 180 Torque Switches (Number, Type, Rating)

OC1189-0224-NL04