ML17292A476

From kanterella
Revision as of 13:14, 29 October 2019 by StriderTol (talk | contribs) (Created page by program invented by StriderTol)
Jump to navigation Jump to search
Monthly Operating Rept for Aug 1996 for WNP-2. W/960912 Ltr
ML17292A476
Person / Time
Site: Columbia Energy Northwest icon.png
Issue date: 08/31/1996
From: Kasko B, Galen Smith
WASHINGTON PUBLIC POWER SUPPLY SYSTEM
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
GO2-96-182, NUDOCS 9609230116
Download: ML17292A476 (8)


Text

CATEGORY j.

REGULARLY INFORMATION DZSTRZBUTIOYSTEM (RIDE)

ACCESSIONrNBR:9609230116 DOC.DATE: 96/08/31 NOTARIZED: NO DOCKET FACIL:50-397 WPPSS Nuclear Project, Unit 2, Washington Public Powe 05000397 AUTH. NAME AUTHOR AFFILIATION KASKO,B. Washington Public Power Supply System SMITHF'G.O. Washington Public Power Supply System RECIP.NAME RECIPIENT. AFFILIATION

SUBJECT:

Monthly operating rept for Aug 1996 for WNP-2.

W/960912 ltr.

DISTRIBUTION CODE: IE24D COPIES RECEIVED:LTR ENCL SIZE:

TITLE: Monthly Operating Report (per Tech Specs)=

NOTES:

E RECIPIENT COPIES RECIPIENT COPIES ID CODE/NAME LTTR ENCL ID CODE/NAME LTTR ENCL PD4-2 PD 1 1 COLBURN,T 1 1 INTERNAL: ACRS 1 1 AEOD/SPD/RRAB 1 1 CENTER 1 1 1 NRR/DRPM/PECB 1 1 1 1 EXTERNAL: LITCO BRYCEFJ H 1 1 NOAC 1 1 NRC PDR 1 1 D

0 M

NOTE TO ALIi "RIDS" RECIPIENTS:

PLEASE HELP US TO REDUCE WASTE! CONTACT THE DOCUMENT CONTROL DESK, ROOM OWFN SD-5(EXT. 415-2083) TO ELIMINATE YOUR NAME FROM DISTRIBUTION LISTS FOR DOCUMENTS YOU DON'T NEED!

i TOTAL NUMBER OF COPIES REQUIRED: LTTR '10,,ENCL'10

  • I

0 a<

~ 8 1

$

WASHINGTON PUBLIC POWER SUPPLY SYSTEM P.O. Box 968 ~ 3000 George Washington Way ~ Richland, Washington 99352-0968 ~ (509) 372-5000 September 12, 1996 G02-96-182 Docket No. 50-397 U. S. Nuclear Regulatory Commission Document Control Desk Washington, D. C. 20555 Gentlemen:

Subject:

WNP-2 OPERATING LICENSE NPF-21 MONTHLYOPERATING REPORT AUGUST 1996 Transmitted herewith is the Monthly Operating Report for the month of August 1996 as required by Technical Specification 6.9;1.6.

Respectfully, G. O. Smith Plant General Manager Mail Drop 9270 CC: LJ Callan - NRC RIV TG Colburn - NRR KE Perkins, Jr. - NRC RIV, WCFO NRC Sr. Resident Inspector - 927N NS Reynolds - Winston & Strawn INPO ANI Library UtilityData Institute DL Williams - BPA / 399 g ~

9609230i i6 960832 P PDR ADQCK 05000397 R PDRt 23903'

OPERATING STATUS REPORT for WNP-2 Date: September 1, 1996 Docket: 50-397

2. Reporting Period: AUGUST 1996 Outage + On-line Hours: 744.0
3. Utility Contact: Bernice Kasko (509) 377-4473 4, Licensed Thermal Power (MW, ): 3486
5. Nameplate Rating (Gross MW, ): 1199
6. Design Electrical Rating (Net MW,): 1153
7. Maximum Dependable Capacity - summer (Gross MW,): 1153
8. Maximum Dependable Capacity - summer (Net MW, ): 1107
9. Ifchanges occur above since last report, give reasons: none
10. Power to which restricted, if any (Net MW,): none
11. Reasons for restrictions, if any:

MONTH YEAR CUMULATIVE

12. Report Period Hours 744.0 5,855.0 102,703.2
13. Hours Reactor Critical 744.0 3,307.8 72,943.6
14. Rx Reserve Shutdown Hours 0.0 985.9 1,730.8
15. Hours Generator On-Line 744.0 3,070.6 70,321.1
16. Unit Reserve Shutdown Hours 0.0 997.4 1,956.2
17. Gross Thermal Energy (MWH) 1,665,767 7,804,875 208,262,425
18. Gross Electrical Energy (MWH) 532,550 2,563,200 70,140,680
19. Net Electrical Energy (MWH) 507,382 2,424,801 67,183,119
20. Unit Service Factor 100.0% 52.4% 68.5%
21. Unit Availability Factor 100.0% 69.5% 70.4%
22. Unit Capacity Factor (MDC Net) 61.6% 37.4% 59.9%
23. Unit Capacity Factor (DER Net) 59.1% 35.9% 59.0%
24. Unit Forced Outage Rate 0.0% 3.9% 10.7%
25. Forced Outage Hours 0.0 123.3 8,443.0
26. Shutdowns scheduled over the next 6 months (type, date, duration): None
27. Ifcurrently shutdown, estimated startup date:

Note: Cumulative Unit Capacity Factors (MDC & DER) are calculated with weighted averages.

AVERAGE DAILY UNIT POWER LEVEL DOCKET NO.: 50-397 UNIT: WNP-2 DATE: September 1, 1996 COMPLETED BY: B Kasko TELEPHONE: (509) 377M73 REPORT PERIOD: AUGUST 1996 AVERAGE DAILYPOWER LEVEL AVERAGE DAILYPOWER LEVEL DAY (Net MWe) DAY (Net MWe) 635 16 678 17 682 692 18 686 694 19 685 697 20 679 695 21 683 691 22 680 689 23 678 677 24 677 10 666 25 674 686 26 673 12 702 27 668 13 682 28 711 14 677 29 679 15 678 30 669 31 729 INSTRUCTIONS On this form, list the average daily unit power level in MWe (net) for each day in the reporting month. Compute to the nearest whole megawatt.

These figures will be used to plot a graph for each reporting month. Note that when maximum dependable capacity is used for the net electrical rating of the unit, there may be occasions when the daily average power level exceeds the 100% line (or the restricted power level line). In such cases, the average daily unit power output sheet should be footnoted to explain the apparent anomaly.

r UNIT SHUTDOWNS AND POWER REDUCTIONS DOCKET NO.: 50-397 ~

UNIT NAME: WNP-2 DATE: September 1, 1996 COMPLETED BY: B Kasko TELEPHONE: (509) 37W473 REPORT PERIOD: AUGUST 1996 No. Date Type Hours Reason Method LER Number System Component Cause and Corrective Action To Prevent Recurrence None

SUMMARY

WNP-2 ramped up to 68% power and held there due to problems encountered during testing of the newly installed ASDs and Digital Feedwater Control Systems. At the end of the month WNP-2 was operating at 69% power and continuing with the ASD and Digital Feedwater test plan.

TYPE REASON METHOD SYSTEM & COMPONENT forced

-

'AAquipmana Failum E - Operator Training & anua REG-01 1 Extu its &H S Scheduled B - Maintenance or Test License Examination 2 - Manual Scram C - Refueling F - Administration 3 - Auto Scram D - Regulatory Restriction -

G Operational Error 4 - Continued H - 01her 5 - Reduced Load 9 - Other

O. I I

~ ~

Y