ML091320540: Difference between revisions

From kanterella
Jump to navigation Jump to search
(Created page by program invented by StriderTol)
(Created page by program invented by StriderTol)
Line 3: Line 3:
| issue date = 05/12/2009
| issue date = 05/12/2009
| title = IR 05000315-09-006 (Drs); 05000316-09-006 (Drs), on November 2, 2009, Donald C. Cook Nuclear Plant - Notification to Perform a Triennial Fire Protection Baseline Inspection While Transition to 10 CFR Part 50.48(C) Is in Progress
| title = IR 05000315-09-006 (Drs); 05000316-09-006 (Drs), on November 2, 2009, Donald C. Cook Nuclear Plant - Notification to Perform a Triennial Fire Protection Baseline Inspection While Transition to 10 CFR Part 50.48(C) Is in Progress
| author name = Daley R C
| author name = Daley R
| author affiliation = NRC/RGN-III/DRS/EB3
| author affiliation = NRC/RGN-III/DRS/EB3
| addressee name = Jensen J
| addressee name = Jensen J
Line 15: Line 15:
| page count = 10
| page count = 10
}}
}}
See also: [[followed by::IR 05000315/2009006]]
See also: [[see also::IR 05000315/2009006]]


=Text=
=Text=

Revision as of 22:53, 11 July 2019

IR 05000315-09-006 (Drs); 05000316-09-006 (Drs), on November 2, 2009, Donald C. Cook Nuclear Plant - Notification to Perform a Triennial Fire Protection Baseline Inspection While Transition to 10 CFR Part 50.48(C) Is in Progress
ML091320540
Person / Time
Site: Cook  American Electric Power icon.png
Issue date: 05/12/2009
From: Robert Daley
Engineering Branch 3
To: Jensen J
Indiana Michigan Power Co
References
IR-09-006 IR-09-006
Download: ML091320540 (10)


See also: IR 05000315/2009006

Text

UNITED STATES NUCLEAR REGULATORY COMMISSION REGION III 2443 WARRENVILLE ROAD, SUITE 210 LISLE, IL 60532-4352

May 12, 2009 Mr. Joseph Jensen

Senior Vice President and Chief Nuclear Officer Indiana Michigan Power Company Nuclear Generation Group One Cook Place

Bridgman, MI 49106 SUBJECT: DONALD C. COOK NUCLEAR PLANT - NOTIFICATION TO PERFORM A TRIENNIAL FIRE PROTECTION BASELINE INSPECTION WHILE TRANSITION TO 10 CFR PART 50.48(C) IS IN PROGRESS INSPECTION REPORT 05000315/2009006(DRS); 05000316/2009006(DRS) Dear Mr. Jensen: On November 2, 2009, the U.S. Nuclear Regulatory Commission (NRC) will begin a triennial fire protection baseline inspection at the Donald C. Cook Nuclear Plant. This inspection will be performed in accordance with Inspection Procedure 71111.05TTP, the NRC's baseline fire protection inspection procedure for plants in the process of implementing the National Fire

Protection Association (NFPA) Standard 805 (10 CFR Part 50.48(c)). The inspection guidance is different from the regular triennial inspections in that the inspectors will concentrate on the fire protection program infrastructure and the adequacy of compensatory measures implemented for identified departures from code requirements. The inspectors will not routinely inspect for or evaluate circuit related issues. The schedule for the inspection is as follows: Information gathering visit: October 6 - 8, 2009; and On-site inspection activity: November 2 - 6, 2009, and November 16 - 20, 2009. The purpose of the information gathering visit is: (1) to obtain information and documentation needed to support the inspection; (2) to become familiar with the Donald C. Cook Nuclear Plant's fire protection programs, fire protection features, post-fire safe shutdown capabilities, and plant layout; and (3) to arrange administrative details, such as office space, availability of

knowledgeable office personnel and to ensure unescorted site access privileges. Experience has shown that the baseline fire protection inspections are extremely resource intensive both for the NRC inspectors and the licensee staff. In order to minimize the inspection impact on the site and to ensure a productive inspection for both organizations, we have enclosed a request for documents needed for the inspection. These documents have been

divided into four groups. The first group lists information necessary to aid the inspection team in choosing specific focus areas for the inspection. It is requested that this information be

J. Jensen -2- provided to the lead inspector via mail or electronically no later than September 7, 2009. The second group also lists information and areas for discussion necessary to aid the inspection team in choosing specific focus areas for the inspection and to ensure that the inspection team is adequately prepared for the inspection. It is requested this information be available during the information gathering visit (October 6 - 8, 2009). The third group of requested documents

consists of those items that the team will review, or need access to, during the inspection. Please have this information available by the first day of the on-site portion of the inspection (November 2, 2009). The fourth group lists the information necessary to aid the inspection team in tracking issues identified as a result of the inspection. It is requested that this information be provided to the lead inspector as the information is generated during the inspection. It is

important that all of these documents are up to date and complete in order to minimize the number of additional documents requested during the preparation and/or the on-site portions of the inspection. The lead inspector for this inspection is Mr. George M. Hausman. We understand that our regulatory contact for this inspection is Mr. John Nimtz of your organization. If there are any questions about the inspection or the material requested, please contact the lead inspector at (630) 829-9743 or via e-mail at George.Hausman@nrc.gov. In accordance with 10 CFR 2.390 of the NRC's "Rules of Practice," a copy of this letter and its enclosure will be available electronically for public inspection in the NRC Public Document Room or from the Publicly Available Records (PARS) component of NRC's document system (ADAMS). ADAMS is accessible from the NRC Web site at http://www.nrc.gov/reading-rm/adams.html (the Public Electronic Reading Room). Sincerely, /RA/ Robert C. Daley, Chief Engineering Branch 3

Division of Reactor Safety Docket Nos.: 50-315; 50-316 License Nos.: DPR-58; DPR-74 Enclosure: Fire Protection Inspection Document Request cc w/encl: L. Weber, Site Vice President J. Gebbie, Plant Manager O. Isiogu, Michigan Public Service Commission Michigan Department of Environmental Quality Planning Manager, Emergency Management and Homeland Security Division, Michigan State Police Department

T. Strong, State Liaison Officer

J. Jensen -2- provided to the lead inspector via mail or electronically no later than September 7, 2009. The second group also lists information and areas for discussion necessary to aid the inspection team in choosing specific focus areas for the inspection and to ensure that the inspection team is adequately prepared for the inspection. It is requested this information be available during the information gathering visit (October

6 - 8, 2009). The third group of requested documents consists of those items that the team will review, or

need access to, during the inspection. Please have this information available by the first day of the on-

site portion of the inspection (November 2, 2009). The fourth group lists the information necessary to aid

the inspection team in tracking issues identified as a result of the inspection. It is requested that this information be provided to the lead inspector as the information is generated during the inspection. It is important that all of these documents are up to date and complete in order to minimize the number of

additional documents requested during the preparation and/or the on-site portions of the inspection. The lead inspector for this inspection is Mr. George M. Hausman. We understand that our regulatory contact for this inspection is Mr. John Nimtz of your organization. If there are any questions about the

inspection or the material requested, please contact the lead inspector at (630) 829-9743 or via e-mail at George.Hausman@nrc.gov. In accordance with 10 CFR 2.390 of the NRC's "Rules of Practice," a copy of this letter and its enclosure will be available electronically for public inspection in the NRC Public Document Room or from the

Publicly Available Records (PARS) component of NRC's document system (ADAMS). ADAMS is

accessible from the NRC Web site at http://www.nrc.gov/reading-rm/adams.html (the Public Electronic Reading Room). Sincerely, /RA/ Robert C. Daley, Chief Engineering Branch 3 Division of Reactor Safety Docket Nos.: 50-315; 50-316 License Nos.: DPR-58; DPR-74 Enclosure: Fire Protection Inspection Document Request

cc w/encl: L. Weber, Site Vice President J. Gebbie, Plant Manager O. Isiogu, Michigan Public Service Commission

Michigan Department of Environmental Quality

Planning Manager, Emergency Management and Homeland

Security Division, Michigan State Police Department T. Strong, State Liaison Officer DISTRIBUTION

See next page DOCUMENT NAME: G:\DRS\Work in Progress\Ltr 05__09 DC Cook Request for Information GMH.doc

Publicly Available Non-Publicly Available Sensitive Non-Sensitive To receive a copy of this document, indicate in the concurrence box "C" = Copy without attach/encl "E" = Copy with attach/encl "N" = No copy

OFFICE RIII E RIII RIII RIII RIII NAME GHausman: ls RDaley DATE 05/08/09 05/12/09 OFFICIAL RECORD COPY

Letter to Mr. Joseph Jensen from Mr. Robert C. Daley dated May 12, 2009. SUBJECT: DONALD C. COOK NUCLEAR PLANT - NOTIFICATION TO PERFORM A TRIENNIAL FIRE PROTECTION BASELINE INSPECTION WHILE TRANSITION TO 10 CFR PART 50.48(C) IS IN PROGRESS INSPECTION REPORT 05000315/2009006(DRS); 05000316/2009006(DRS) DISTRIBUTION:

Tamara Bloomer RidsNrrDorlLpl3-1 Resource RidsNrrPMDCCook Resource RidsNrrDirsIrib Resource Patrick Hiland

Kenneth Obrien Jared Heck Allan Barker Carole Ariano

Linda Linn DRPIII DRSIII

Patricia Buckley Tammy Tomczak ROPreports Resource

FIRE PROTECTION INSPECTION DOCUMENT REQUEST

1 Enclosure Inspection Report: 05000315/2009006(DRS); 05000316/2009006(DRS)

Inspection Dates: October 6 - 8, 2009, (Information Gathering Visit) November 2 - 6, 2009, (On-site Inspection Activity) November 16 - 20, 2009, (On-site Inspection Activity) Inspection Procedures

IP 71111.05TTP, "Fire Protection-NFPA 805 Transition Period (Triennial)"

IP 71152, "Identification and Resolution of Problems" Inspectors: George M. Hausman, Lead Inspector (630) 829-9743

George.Hausman@nrc.gov

Mohammad Munir Robert A. Winter (630) 829-9797 (630) 829-9758

Mohammad.Munir@nrc.gov

Robert.Winter@nrc.gov

I. Information Requested Prior To the Information Gathering Visit The following information is requested by September 7, 2009. If you have any questions regarding this request, please call the lead inspector as soon as possible. All information

should be sent to Mr. George M. Hausman (e-mail address George.Hausman@nrc.gov). Electronic media is preferred. The preferred file format is a searchable "pdf" file on a compact disk (CD). The CD should be indexed and hyper-linked to facilitate ease of use, if possible. Please provide four copies of each CD submitted (one for each inspector and for

a senior reactor analysis). 1. The reactor plant's Individual Plant Examination for External Events (IPEEE) for fire, results of any post-IPEEE reviews for fire, and listings of actions taken and/or plant modifications conducted in response to IPEEE information for fire. Alternatively, probabilistic risk analyses for fire and associated information, if it exists and is more

recent than the IPEEE. 2. A copy of the current version of the fire protection program (FPP), fire hazards analysis (FHA), safe shutdown analysis (SSA), updated safety analysis report (USAR), technical specifications and license. 3. A list of fire areas requiring alternative shutdown capability, (i.e., those areas for which 10 CFR Part 50, Appendix R, Section III G requirements are satisfied under Section III.G.3), or where both safe shutdown trains can be affected. 4. Plant operating procedures, which would be used and describe shutdown for a postulated fire (for both areas requiring alternative shutdown and areas which do not require alternative shutdown). Only those procedures with actions specific to shutdown

in the event of a fire need be included. 5. A copy of the current fire protection system "Health Report," if available.

FIRE PROTECTION INSPECTION DOCUMENT REQUEST

2 Enclosure 6. A copy of the current plant drawings referred to as "Horse Notes," if available. 7. Status of NFPA 805 (10 CFR Part 50.48(c)) implementation. II. Information Requested During the Information Gathering Visit (OCTOBER 6-8, 2009) The following information is requested to be provided to the inspection team during the on-site information gathering visit. Except for Item 1, it is requested that the following information be provided on four sets of CDs (searchable, if possible). In addition, two sets of hard copy drawings are requested for Items 4.a. through 4.f. 1. One set of hard-copy documents for facility layout drawings, which identify plant

fire area delineation; areas protected by automatic fire suppression and detection;

and locations of fire protection equipment.

2. Licensing Information: a. The facility's license, including the fire protection license condition; b. All Nuclear Regulatory Commission (NRC) Safety Evaluation Reports (SERs) applicable to fire protection (specifically including those SERs referenced by the plant fire protection license condition) and all licensing correspondence

referenced by the SERs; c. All licensing correspondence associated with the comparison to Standard Review Plan (NUREG-0800), Section 9.5.1 or equivalent for licensing purposes; d. Exemptions from 10 CFR Part 50.48 and 10 CFR Part 50, Appendix R, and associated licensing correspondence; e. The FPP and applicable portions of the USAR, as referenced by the fire protection license condition; f. For pre-1979 plants (i.e., "Appendix R" plants), a listing of all 10 CFR Part 50, Appendix R sections and paragraphs that are applicable to the plant under 10 CFR Part 50.48(b)(1); g. For pre-1979 plants, all licensing correspondence associated with those sections of 10 CFR Part 50, Appendix R, that are not applicable to the plant under 10 CFR Part 50.48(b)(1). Specifically, the licensing correspondence associated with those fire protection features proposed or implemented by the licensee that have been accepted by the NRC staff as satisfying the provisions of Appendix A to Branch

Technical Position (BTP) APCSB 9.5-1 reflected in the NRC fire protection SERs issued before February 19, 1981, (10 CFR Part 50.48(b)(1)(i)); or those fire protection features, which were accepted by the NRC staff in comprehensive fire protection SERs issued before Appendix A to BTP APCSB 9.5-1 was published in August 1976 (10 CFR Part 50.48(b)(1)(ii));

FIRE PROTECTION INSPECTION DOCUMENT REQUEST

3 Enclosure h. For post-1979 plants, all licensing correspondence associated with the comparison to Standard Review Plan (NUREG-0800), Section 9.5.1 or equivalent for licensing purposes; and i. For NFPA 805 transition plants provide: (1) all correspondence to and responses from the NRC; (2) a list of all areas showing assessment review status; (3) assessments for all areas that have been completed; and (4) a list of all identified non-conformances, and their respective compensatory measure(s). 3. Fire Protection Program: a. If not already provided under request II.(2)(e) above, FPP documents including FHA and post-fire SSA; b. A listing of changes made to the FPP (including associated adverse to SSA) since the last triennial fire protection inspection; c. For pre-1979 plants, a listing of the protection methodologies identified under 10 CFR Part 50, Appendix R, Section III.G used to achieve compliance for selected fire zones/areas (to be determined during information gathering visit). That is, please specify whether 3-hour rated fire barriers; (Section III.G.2.a), 20 foot

separation along with detection and suppression; (Section III.G.2.b), 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> rated fire barriers with detection and suppression; (Section III.G.2.c), or alternative shutdown capability; (Section III.G.3) is used as a strategy for each selected fire zone/area; d. A list of Generic Letter 86-10 evaluations (i.e., a list of adverse to safe shutdown evaluations); e. A list of applicable codes and standards related to the design of plant fire protection features. The list should include National Fire Protection Association (NFPA) code versions committed to (i.e., the NFPA codes of record); f. List of plant deviations from code commitments and associated evaluations; and g. Plant layout drawings, which identify plant fire area delineation, areas protected by automatic fire suppression and detection, and the locations of fire protection equipment. 4. Facility Information: a. Piping and instrumentation (flow) diagrams showing the components used to achieve and maintain hot standby and cold shutdown for fires outside the control room and those components used for those areas requiring alternative shutdown capability; b. Plant layout and equipment drawings, which identify the physical plant locations of hot standby and cold shutdown equipment for selected fire zones/areas (to be determined during information gathering visit

);

FIRE PROTECTION INSPECTION DOCUMENT REQUEST

4 Enclosure c. Plant layout drawings, which identify the general location of the post-fire emergency lighting units; d. One-line schematic drawings of the electrical distribution system for 4160 Volts alternating current (Vac) down to 480Vac; e. One-line schematic drawings of the electrical distribution system for 250 Volts direct current (Vdc) and 125Vdc systems as applicable; f. Logic diagrams showing the components used to achieve and maintain hot standby and cold shutdown; and g. Safe shutdown cable routing database (requested electronically such as on compact disc, if available. 5. Operations Response for Fire Protection: a. Pre-fire plans for selected fire zones/areas (to be determined during information gathering visit); and b. Plant operating procedures, which would be used and describe shutdown for a postulated fire in selected fire zones/areas (to be determined during information gathering visit). 6. Corrective Actions: a. Listing of open and closed fire protection condition reports (i.e., problem identification forms and their resolution reports) since the date of the last triennial fire protection inspection; and b. Listing of fire impairments since the date of the last triennial fire protection inspection. 7. General Information: a. A listing of abbreviations and/or designators for plant systems; b. Organization charts of site personnel down to the level of fire protection staff personnel; and c. A phone list for on-site licensee personnel. 8. On-site Discussions. In addition, during the information gathering visit, it is requested that licensee staff be available for the following: a. Informal discussion on plant procedures operators would use in the event of fire and under what conditions would the plant be shutdown using alternative shutdown methodology;

FIRE PROTECTION INSPECTION DOCUMENT REQUEST

5 Enclosure b. Informal discussion on the plant's safe shutdown cable routing database and the plant-wide cable routing database, as applicable; and c. A tour of alternative shutdown and risk significant fire areas. III. Information Requested to be Available on First Day of Inspection (November 2, 2009) The following information is requested to be provided on the first day of inspection. It is requested that this information be provided on four sets of CDs (searchable, if possible). 1. Program Procedures: a. List of the FPP implementing procedures (e.g., administrative controls, surveillance testing, fire brigade); b. List of maintenance and surveillance testing procedures for alternative shutdown capability and fire barriers, detectors, pumps, and suppression systems; c. List of maintenance procedures, which routinely verify fuse breaker coordination in accordance with the post-fire safe shutdown coordination analysis; d. List of procedures and/or instructions that control the configuration of the reactor plant's FPP, features, and post-fire safe shutdown methodology and system

design; and e. List of procedures and/or instructions that govern the implementation of plant modifications, maintenance, and special operations, and their impact on fire protection. 2. Design and Equipment Information: a. Coordination calculations and/or justifications that verify fuse/breaker coordination for selected fire zones/areas (to be determined during information gathering visit) that are fed off of the same electrical buses as components in the protected safe shutdown train; b. Copies of significant fire protection and post-fire safe shutdown related design change package descriptions (including their associated 10 CFR Part 50.59 evaluations) and Generic Letter (GL) 86-10 (or adverse to safe shutdown) evaluations; c. Gaseous suppression system pre-operational testing, if applicable, for selected fire zones/areas (to be determined during information gathering visit

); d. Hydraulic calculations and supporting test data, which demonstrate operability for water suppression systems, if applicable, for selected fire zones/areas (to be determined during information gathering visit

);

FIRE PROTECTION INSPECTION DOCUMENT REQUEST

6 Enclosure e. Alternating current (ac) coordination calculations for 4160Vac down to 480Vac electrical systems; f. Vendor manuals and information for fire protection equipment (such as detection, suppression systems, fire pumps), applicable to selected fire zones/areas (to be determined during information gathering visit). It is acceptable to make vendor manuals available to the inspectors in lieu of providing a copy; and g. List of all fire protection or Appendix R calculations. 3. Assessment and Corrective Actions: a. The three most recent fire protection Quality Assurance (QA) audits and/or fire protection self-assessments; and b. Corrective action documents (e.g., condition reports, including status of corrective actions) generated as a result of the three most recent fire protection Quality Assurance (QA) audits and/or fire protection self-assessments. 4. Any updates to information previously provided. IV. Information Requested to Be Provided Throughout the Inspection 1. Copies of any corrective action documents generated as a result of the inspection team's questions or queries during this inspection. 2. Copies of the list of questions submitted by the inspection team members and the status/resolution of the information requested (provided daily during the inspection to each inspection team member).