Search by property
Jump to navigation
Jump to search
This page provides a simple browsing interface for finding entities described by a property and a named value. Other available search interfaces include the page property search, and the ask query builder.
List of results
- IR 05000460/1982009 + (ML20055A043)
- 05000327/LER-1982-076-03, /03L-0:on 820613,ice Bed Temp Monitoring Sys Declared Inoperable Due to Failure to Meet Surveillance Requirements.Caused by Broken Wire to Ac Power Supply.Wire Repaired & Moved to Prevent Recurrence + (ML20055A044)
- IR 05000295/1982015 + (ML20055A045)
- 05000369/LER-1982-047, Forwards LER 82-047/03L-0 + (ML20055A046)
- ML20055A048 + (ML20055A048)
- ML20055A049 + (ML20055A049)
- ML20055A051 + (ML20055A051)
- ML20055A053 + (ML20055A053)
- 05000369/LER-1982-047-03, /03L-0:on 820603,surveillance Interval of Boron Concentration in Boron Acid Storage Tank a Exceeded Tech Specs.Caused by Personnel Error.Operator Counseled.All Operations Personnel Informed of Implications + (ML20055A054)
- ML20055A055 + (ML20055A055)
- ML20055A056 + (ML20055A056)
- ML20055A058 + (ML20055A058)
- IR 05000416/1982050 + (ML20055A059)
- ML20055A060 + (ML20055A060)
- 05000339/LER-1982-035, Forwards LER 82-035/03L-0 + (ML20055A061)
- IR 05000335/1982020 + (ML20055A063)
- IR 05000508/1982012 + (ML20055A064)
- 05000339/LER-1982-025-03, /03L-0:on 820613,individual Rod Position Indication for Rod P-08 in Control Bank D Deviated from Group Demand Position More than 12 Steps.Caused by Instrument Drift.Rod P-08 Recalibr & Returned to Svc + (ML20055A065)
- ML20055A066 + (ML20055A066)
- ML20055A068 + (ML20055A068)
- 05000339/LER-1982-035-03, /03L-0:on 820609,RCS Identified Leakage Found to Be Greater than Tech Spec Max.Caused by Packing Leak on Manual Loop Drain Isolation Valves 2-RC-30 & 2-RC-39. Packaging Tightened & Valve 2-RC-30 Replaced + (ML20055A072)
- ML20055A073 + (ML20055A073)
- ML20055A074 + (ML20055A074)
- ML20055A075 + (ML20055A075)
- ML20055A076 + (ML20055A076)
- 05000280/LER-1982-036-03, /03L-0:on 820611,motor Operated Valve CS-203C Failed to Close During Performance of PT-17.1.Caused by Loose Field Wiring Disconnect Device at Motor Control Ctr Cubicle.Plug Reinserted & Valve Returned to Svc + (ML20055A078)
- ML20055A079 + (ML20055A079)
- IR 05000424/1982015 + (ML20055A080)
- ML20055A081 + (ML20055A081)
- ML20055A082 + (ML20055A082)
- ML20055A084 + (ML20055A084)
- ML20055A085 + (ML20055A085)
- ML20055A086 + (ML20055A086)
- IR 05000508/1982011 + (ML20055A088)
- 05000325/LER-1982-063, Forwards LER 82-063/03L-0 + (ML20055A089)
- 05000280/LER-1982-074-03, /03L-0:on 820618,following Check of Svc Water Piping,Pump 1-SW-P-10B Failed to Auto Start.Caused by Drift of Low Pressure Setpoint of Pressure Switch PS-SW-105.Switch Replaced + (ML20055A091)
- 05000335/LER-1982-022, Forwards LER 82-022/03L-0 + (ML20055A092)
- ML20055A094 + (ML20055A094)
- IR 05000280/1982017 + (ML20055A097)
- ML20055A098 + (ML20055A098)
- 05000250/LER-1982-008, Forwards LER 82-008/03L-0 + (ML20055A099)
- ML20055A101 + (ML20055A101)
- ML20055A102 + (ML20055A102)
- 05000280/LER-1982-026-03, /03L-0:on 820618,electrical Penetration Found Improperly Sealed.Caused by Personnel Failure to Restore Penetration to Original State Following Cable Installation. Penetration Sealed + (ML20055A104)
- ML20055A105 + (ML20055A105)
- ML20055A106 + (ML20055A106)
- 05000250/LER-1982-008-03, /03L-0:on 820609,3A High Head Safety Injection Pump Failed to Start from Manual Operation of Normal Control Switch.Cause Not Determined.Breaker Control Panel Fuses Replaced & Breaker Racked Out & Backed in + (ML20055A108)
- ML20055A109 + (ML20055A109)
- ML20055A110 + (ML20055A110)
- ML20055A112 + (ML20055A112)
- 05000327/LER-1982-078, Forwards LER 82-078/03L-0 + (ML20055A113)