ML20235S2972 October 1987Hood D
Office of Nuclear Reactor Regulation
Summary of 870923 Meeting W/Westinghouse Re Technical Basis for Westinghouse Recommended Actions,Criteria & Conclusions in to Utils That Use Models DS-416,DSL-416, DS-420,DS-206 & DSL-206 Switchgear in Class 1E SvcMeeting
ML20236A61416 October 1987Hood D
Office of Nuclear Reactor Regulation
Advises That Util Insp of Reactor Trip Breakers Revealed Catawba Pole Shaft Which Had Welds W/Indications of Cracking.Forwards Informal Technical Communication from Franklin Research Ctr Re Initial ObservationOther
ML20236A84916 October 1987Hood D
Office of Nuclear Reactor Regulation
Forwards I.6177-5-1, Interim Rept on McGuire Reactor Trip Breaker 2B Failure Evaluation & Rcommended Corrective Actions from Westingtonhouse. Rept Explains Mechanical Binding Which Kept Breaker from Opening on 870702Other
ML20236D10521 October 1987Hood D
Office of Nuclear Reactor Regulation
Provides Record of 871020 Telcon Between D Hood,D Sellers & V Hodge of NRC & J Mcvicker & Cowne of Bg&E Re Unit 1 480 Volt Circuit Breaker W/Broken Weldment Connecting Ctr Pole Lever to Pole Shaft.Util Exam Results in 860918 MemoOther
ML20236F54723 October 1987Hood D
Office of Nuclear Reactor Regulation
Documents 871020 Telcon W/Util Re Unit 2 Circuit Breaker Pole Shaft Weld FailureOther
ML20236F96527 October 1987Hood D
Office of Nuclear Reactor Regulation
Notification of 871103 Meeting W/Util & Westinghouse in Philadelphia,Pa to Discuss Results of Franklin Research Ctr Exam of Cracks in Pole Shaft Welds of Reactor Trip BreakerMeeting
ML20236S01818 November 1987Hood D
Office of Nuclear Reactor Regulation
Summarizes 871020 Telcon Between NRC & Util Re Two Broken Fillet Welds on Pole Shaft Assembly of Circuit Breaker That Energizes Emergency Fire Protection Pumps for Facility. Photographs Attached to 870710 Memo to NRC EnclOther
ML20149M19816 February 1988Taylor J
DAIRYLAND POWER COOPERATIVE
Advises That Since Util No Longer Operating Reactor Licensee Due to 870430 Shutdown & 870804 Amend,Modifying License DPR-45 to Possess But Not Operate Status,Generic Ltr 88-01 Determined Inapplicable to FacilityOther
3F0288-18, Responds to NRC Bulletin 88-001 Re Defects in Westinghouse Circuit Breakers.Plant Does Not Use Westinghouse Circuit Breaker Models DS-206,DSL-206,DS-416,DSL-416 & DS-42023 February 1988Duke Energy
Eric Simpson
Responds to NRC Bulletin 88-001 Re Defects in Westinghouse Circuit Breakers.Plant Does Not Use Westinghouse Circuit Breaker Models DS-206,DSL-206,DS-416,DSL-416 & DS-420Other
ML20196H35325 February 1988Taylor J
DAIRYLAND POWER COOPERATIVE
Responds to NRC Bulletin 88-001, Defects in Westinghouse Circuit Breakers. No Westinghouse Ds Series Circuit Breakers Installed at FacilityOther
ML20147G8541 March 1988YANKEE ATOMIC ELECTRIC CO.
Devincentis J
Responds to NRC Bulletin 88-001 Re Westinghouse Ds Series Circuit Breakers Used in safety-related Applications.Plant Does Not Have Any Westinghouse Ds Series Circuit BreakersOther
ML20147F9984 March 1988Portland General Electric
Cockfield D
Submits Response to NRC Bulletin 88-001 Re Defects in Westinghouse Circuit Breakers.Author Does Not Utilize Any Westinghouse Circuit Breakers,As Identified in Subj Bulletin,In Class 1E Applications at FacilityOther
ML20150B1827 March 1988Duke Energy
Tucker H
Responds to NRC Bulletin 88-001 Re Defects in Westinghouse Circuit Breakers.Plant Does Not Use Westinghouse Circuit Breakers in Class 1E Applications So Bulletin 88-001 Does Not Apply to PlantOther
ML20148A8907 March 1988Duquesne Light Company
Sieber J
Responds to NRC Bulletin 88-001 Re Defects in Westinghouse Circuit Breakers.Unit 1 Has No Westinghouse Ds Circuit Breakers Used in Class 1E Application.Unit 2 Reactor Trip & Bypass Breakers Insp Initiated Per Info Notice 87-035Other
ML20150A8999 March 1988Fay C
WEC Energy Group
Provides Response to NRC Bulletin 88-001, Defects in Westinghouse Circuit Breakers. Util Determined That Westinghouse Series Ds Circuit Breakers Not Employed at Plant.Insp Required by Bulletin Not Applicable to PlantOther
ML20150C40711 March 1988FirstEnergy
Standerfer F
Responds to NRC Bulletin 88-001, Defects in Westinghouse Circuit Breakers. Util Determined That Westinghouse Type Ds Circuit Breakers Not Used at PlantOther
BECO-88-050, Notifies That Westinghouse Circuit Breakers Not in Use or Planned to Be Used in safety-related Applications at Util, in Response to NRC Bulletin 88-00115 March 1988Bird R
Eversource Energy
Notifies That Westinghouse Circuit Breakers Not in Use or Planned to Be Used in safety-related Applications at Util, in Response to NRC Bulletin 88-001Other
ML20148B66616 March 1988Larson CResponds to 880205 NRC Compliance Bulletin 88-001, Defects in Westinghouse Circuit Breakers. Westinghouse Ds Series Circuit Breakers Not Used in Class IE Svc at PlantOther
NRC-88-0072, Responds to NRC Bulletin 88-001, Defects in Westinghouse Circuit Breakers. Util Does Not Utilize Subj Circuit Breakers24 March 1988DTE Energy
Sylvia B
Responds to NRC Bulletin 88-001, Defects in Westinghouse Circuit Breakers. Util Does Not Utilize Subj Circuit BreakersOther
ML20148K22525 March 1988NORTHEAST UTILITIES
Mroczka E
CONNECTICUT YANKEE ATOMIC POWER CO.
Northeast Nuclear Energy
Responds to NRC Bulletin 88-001, Defects in Westinghouse Circuit Breakers. Two Reactor Trip Breakers & Two Reactor Trip Bypass Breakers Subj to Bulletin Used at Millstone Unit 3.Main Pole Shaft Weld Insps Completed by 880225Other
ML20151G79128 March 1988SACRAMENTO MUNICIPAL UTILITY DISTRICT
Andognini G
Confirms That Westinghouse Ds Breakers Not Used at Facility, Per IE Bulletin 88-001, Defects in Westinghouse Circuit BreakersOther
W3P88-0051, Responds to NRC Bulletin 88-001 Re Defects in Westinghouse Circuit Breakers.Util Does Not Use Westinghouse Series Ds Circuit Breakers & Not Subj to Insps Requested in Bulletin29 March 1988Burski R
LOUISIANA POWER & LIGHT CO.
Responds to NRC Bulletin 88-001 Re Defects in Westinghouse Circuit Breakers.Util Does Not Use Westinghouse Series Ds Circuit Breakers & Not Subj to Insps Requested in BulletinOther
ML20151A94530 March 1988Xcel Energy
Robert Williams
Responds to IE Bulletin 88-001 Re Westinghouse Ds/Dsl Circuit Breakers.Ref Components Not Utilized at FacilityOther
0CAN048804, Responds to NRC Bulletin 88-001, Defects in Westinghouse Circuit Breakers. Informs That No Instances of Circuit Breakers Being Installed in safety-related Applications Identified at Plant1 April 1988Entergy
Howard D
Responds to NRC Bulletin 88-001, Defects in Westinghouse Circuit Breakers. Informs That No Instances of Circuit Breakers Being Installed in safety-related Applications Identified at PlantOther
ML20151B2024 April 1988Southern Nuclear
Mcdonald R
Responds to NRC Bulletin 88-001 Re Defects in Westinghouse Circuit Breakers.Insp of All Westinghouse DS-415 Reactor Trip & Bypass Breakers Completed on 880308 & Results EnclOther
RBG-27645, Responds to NRC Bulletin 88-001, Defects in Westinghouse Circuit Breakers. Util Does Not Utilize Any Circuit Breakers Subj to Bulletin in Class 1E Svc at Plant4 April 1988GULF STATES UTILITIES CO.
Booker J
Responds to NRC Bulletin 88-001, Defects in Westinghouse Circuit Breakers. Util Does Not Utilize Any Circuit Breakers Subj to Bulletin in Class 1E Svc at PlantOther
ML20148Q7247 April 1988Southern Nuclear
Gucwa L
Responds to NRC Bulletin 88-001, Defects in Westinghouse Circuit Breakers. No Westinghouse Models DS-206,DSL-206, DS-416,DSL-416 or DS-420 Breakers in Class 1E Circuits at HatchOther
ML20151H7797 April 1988FirstEnergy
Fiedler P
Informs That Westinghouse Ds Circuit Breakers Not Utilized in Any 1E Application at Plant But Used in non-1E Applications & Will Be Included in Util Preventive Maint ProgramOther
ML20151E4198 April 1988Exelon
(FORMERLY PHILADELPHIA ELECTRIC
Kowalski S
Responds to 880205 NRC Bulletin 88-01 Re Defects in Westinghouse Circuit Breakers for Facilities.Westinghouse Ds Series Circuit Breakers Not Used at Plants.Other Provisions of Bulletin Do Not Apply to PlantsOther
ML20151E86811 April 1988Ameren
Schnell D
Forwards Response to NRC Bulletin 88-001 Re Defects in Westinghouse Circuit Breakers in Class 1E Svc.All Required long-term & short-term Insps CompletedOther
ML20151H96513 April 1988American Electric Power
Alexich M
Responds to NRC Bulletin 88-001, Deficiencies in Westinghouse Circuit Breakers. Bulletin Addresses Deficiencies Exclusive to Westinghouse Ds/Dsl Type Circuit Breakers & Outlines Specific Insps to Be PerformedOther
ML20151G11513 April 1988Mcdonald D
Office of Nuclear Reactor Regulation
Ack Receipt of in Response to NRC Bulletin 88-001 Re Westinghouse Circuit Breakers.Plant Does Not Use or Plan Use of Circuit Breakers,Therefore Matter ClosedOther
ML20205P68820 April 1988Maine Yankee
Randazza J
Responds to NRC Bulletin 88-001, Defects in Westinghouse Circuit Breakers. No Circuit Breakers Subj to Bulletin Installed in PlantOther
ML20155E3929 June 1988Southern Nuclear
Hairston W
Responds to NRC Bulletin 88-001 Re Defects in Westinghouse Circuit breakers.Sixty-six of sixty-seven Breakers Required New Pole Shafts Due to Failure of Welds to Meet Bulletin Requirements Resulting from InspOther
ML20150B52630 June 1988Duquesne Light Company
Sieber J
Informs That All Class 1E DS-416 Breakers Now in Use Comply W/Nrc Bulletin 88-001 Re Defects in Westinghouse Circuit BreakersOther
ML20150D3975 July 1988Hood D
Office of Nuclear Reactor Regulation
Advises That Response to NRC Bulletin 88-001, Defects in Westinghouse Circuit Breakers, SatisfactoryOther
ML20151E01814 July 1988Dromerick A
Office of Nuclear Reactor Regulation
Advises That Util 880407 Response to NRC Bulletin 88-001, Defects in Westinghouse Circuit Breakers, SatisfactoryOther
ML20151Q9202 August 1988Craig Harbuck
Office of Nuclear Reactor Regulation
Informs That Response to NRC Bulletin 88-001, Defects in Westinghouse Circuit Breakers, SatisfactoryOther
ML20154D2339 September 1988Office of Nuclear Reactor Regulation
Wigginton D
Informs That Response to NRC Bulletin 88-001, Defects in Westinghouse Circuit Breakers, Satisfactory & No Further Reply NecessaryOther
ML20154E1549 September 1988Office of Nuclear Reactor Regulation
Rooney V
Advises That 880408 Response to NRC Bulletin 88-001, Defects in Westinghouse Circuit Breakers, SatisfactoryOther
ML20155A45629 September 1988Office of Nuclear Reactor Regulation
Mcneil S
Requests Addl Info Re Util 880908 Response to NRC Bulletin 88-001, Defects in Westinghouse Circuit Breakers. Response Requested within 70 Days of Ltr DateOther
ML20235J16817 February 1989Office of Nuclear Reactor Regulation
Labarge D
Advises That 880314 Response to NRC Bulletin 88-001, Defects in Westinghouse Circuit Breakers Satisfactory. Westinghouse Ds Series Circuit Breakers Not Used in safety-related Applications at PlantOther
ML20235J16517 February 1989Luminant
William Cahill
Provides Final Response to NRC Bulletin 88-001, Defects in Westinhouse Circuit Breakers. Alignment Check Specified in 871201 Submittal Satisfactorily Performed During Installation of Replacement Pole Shaft in BreakersOther
ML20247C71915 May 1989Exelon
Richter M
Forwards Supplemental Response to NRC Bulletin 88-001 Re Westinghouse Series Ds Circuit Breakers.Insp Info CorrectedSupplement
ML20247K07524 May 1989Southern Nuclear
Hairston W
Responds to NRC Bulletin 88-001 Re Defects of Westinghouse Circuit Breakers.All forty-seven Westinghouse Type Ds Breakers Inspected Were Found to Have Acceptable Breaker Mechanism AlignmentOther
A07039, Responds to NRC Bulletin 88-001, Defects in Westinghouse Circuit Breakers. Pole Shafts for All Four Breakers Replaced During Recently Completed Refueling Outage24 July 1989NORTHEAST UTILITIES
Mroczka E
Northeast Nuclear Energy
Responds to NRC Bulletin 88-001, Defects in Westinghouse Circuit Breakers. Pole Shafts for All Four Breakers Replaced During Recently Completed Refueling OutageOther