Advises That Response to NRC Bulletin 88-001, Defects in Westinghouse Circuit Breakers, Satisfactory
ML20150D397
Person / Time
Site: Mcguire, Catawba, McGuire, 05000000
Issue date: 07/05/1988
From: Hood D
Office of Nuclear Reactor Regulation
To: Tucker H
DUKE POWER CO.
References
IEB-88-001, IEB-88-1, TAC-65955, TAC-65956, TAC-67653, TAC-67654, TAC-67685, TAC-67686, NUDOCS 8807130455
Download: ML20150D397 (4)


Text

B~ f p

July 5, 1988 Docket Nos.: 50-413/414

/

50-369/370

./

Mr. H. B.= Tucker, Vice President Nuclear _ Production Department Duke Power Company 422 South Church Street Charlotte, North Carolina 28242

Dear Mr. Tucker:

i NRC BULLETIN 88-01, "DEFECTS IN WESTINGHOUSE CIRCUIT BREAKERS,"

SUBJECT:

CATAWBA AND MCGUIRE NUCLEAR STATIONS, (TACS 65955/65956/67685/

67686/67653/67654)

On Fe ruary 5,1988, NRC Bulletin 88-01 was issued and requested holders of operating licenses or construction permits to provide letters of confirmation to the NRC of the completion of specified inspections on Westinghouse DS series circuit breakers, s

Your response dated April 5,1988, confirmed that you have performed the requested inspections on all relevant circuit breakers at the McGuire and Catawba Nuclear Stations and that corrective actions, when needed, have been compeleted in accordance with the NRC Bulletin. Thus, your response to Bulletin 88-01 is satisfactory, and no further reply is necessary.

Sincerely, Original signed by:

g713o4558807o5 Darl Hood, Project Manager ADock 05000369 Project Directorate II-3 o

PNU Division of Reactor Projects I/II cc:

See.next page DISTRIBUTION:

ipocRet F1Je; NRC PDR Local POR POII-3 Reading S. Varga 14-E-4 G. Lainas 14-H-3

0. Matthews 14-H-25 H. Rood 14-H-25 D. Hond 14-H-25 N-[

K. Jabbour E. Jordan HNBB-3302 i

B. Grimes 9-A-2 0

ACRS (10)

H-1016 Catawba Reading 4 /

2.5(f Vn

>sH 1])W McGuire Reading PM:PDII-3 PM:PDII-3 D:PDII-3 (A]

h!-3 MRo KJabbour DHood:pw Matthews 7/

88 7/J/88 g/J/88 7 / 5 / 43

July 5, 1988 Docket Nos.:

50-413/414 50-369/370 Mr. H. B. Tucker, Vice President Nuclear Production Department Duke Power Company 422 South Church Street Charlotte, North Carolina 28242

Dear Mr. Tucker:

SUBJECT:

NRC BULLETIN 88-01, "DEFECTS IN WESTINGHOUSE CIRCUIT BREAKERS,"

l CATAWBA AND MCGUIRE NUCLEAR STATIONS, (TACS 65955/65956/67685/

67686/67653/67654)

On February 5,1988, NRC Bulletin 88-01 was issued and requested holders of operating licenses or construction perraits to provide letters of confirmation to the NRC of the completion of specified inspections on Westinghouse DS series circuit breakers.

Your response dated April 5,1988, confirmed that you have perfo~ed the requested inspections on all relevant circuit breakers at the Mcbuire and Catawba Nuclear Stations and that corrective actions, when needed, have been compeleted in accordance with the NRC Bulletin. Thus, your response to Bulletin 88-01 is satisfactory, and no further reply is necessary.

Sincerely, Original signed by:

Darl Hood, Project Manager Project Directorate II-3 Division of Reactor Projects I/II cc:

See next page DISTRIBUTION:

Docket File NRC POR Local POR PDII-3 Reading S. Varga 14-E-4 G. Lainas 14-H-3 D. Matthews 14-H-25 M. Rood 14-H-25

0. Hood 14-H-25 X. Jabbour E. Jordan MNBB-3302 B. Grimes 9-A-2 ACRS (10)

H-1016 Catawba Reading McGuire Reading

)

LA g l-3 PM:POII-3 PM:PDII-3 0:PDII-3

NRooc, XJabbour DHo N:pw DMatthews 7/ $88 7 /J/88 7 / S /88 7 / 5/88

/

f p

Mr. H. B. Tucker Duke Power Company Catawba Huclear Station cc:

A.V. Carr, Esq.

North Carolina Electric Membership Duke Power Company Corp.

422 South Church Street 3400 Sumner Boulevard Charlotte, North Carolina 28242 P.O. Box 27306 Raleigh, North Carolina 27611 J. Michael McGarry, III. Esq.

Bishop, Liberman, Cook, Purcell Saluda River Electric Cooperative, and Reynolds Inc.

1200 Seventeenth Street, N.W.

P.O. Box 929 Washington, D. C.

20036 Laurens, South Carolina 29360 North Carolina MPA-1 Senior Resident Inspector Suite 600 Route 2, Box 179N 3100 Smoketree Ct.

York, South Carolina 29745 P.O. Box 29513 Raleigh, North Carolina 27626-0513 Regional Administrator, Region II U.S. Nuclear Regulatory Commission, S. S. Kilborn 101 Marietta Street, NW, Suite 2900 Area Manager, Mid-South Area Atlanta, Georgia 30323 ESSD Projects Westinghouse Electric Corp.

Mr. Heyward G. Shealy, Chief D C West Tower - Bay 239 Bureau of Radiological Health P.O. Box 355 South Carolina Department of Health Pittsburgh, Pennsylvania 15230 and Environmental Control 2600 Bull Street County Manager of York County Columbia, South Carolina 29201 York County Courthouse York South Carolina 29745 Karen E. Long Assistant Attorney General Richard P. Wilson, Esq.

N.C. Department of Justice Assistant Attorney General P.O. Box 629 S.C. Attorney General's Office Raleigh, North Carolina 27602 P.O. Box 11549 Columbia, South Carolina 29211 Spence Perry, Esquire General Counsel Piedmont Municipal Power Agency Federal Emergency Management Agency 100 Hernorial Drive Room 840 Greer, South Carolina 29651 500 C Street Washington, D. C.

20472 Mr. Michael Hirsch Federal Emergency Management Agency Brian P. Cassidy, Regional Counsel Office of the General Counsel Federal Emergency Management Agency, Roora 840 Reg'an :

500 C Street, S.W.

J. W. McCormach POCH Washington, D. C.

204:'2 Boston, Massachusotts 02109

I Mr. H. S. Tucker Duke Power Company McGuire Nuclear Station cc:

fir. A.V. Carr, Esq.

Dr. John M. Barry Duke Power Company Department of Environmental Health P. O. Box 33189 Mecklenburg County 422 South Church Street 1200 Blythe Boulevard Charlotte,iiorth Carolina 28242 Charlotte, North Carolina 28203 County Manager of Mecklenburg County Mr. Dayne H. Brown, Chief 720 East Fourth Street Radiation Protection Branch Charlotte, North Carolina 28202 Division of Facility Services Department of Human Resources 701 Barbour Drive Mr. Robert Gill Raleigh, North Carolina 27603-2008 Duke Power Company Nuclear Production Department P. O. Box 33189 Charlotte, North Carolina 28242 J. Michael McGarry, III, Esq.

Bishop, Liberman, Cook, Purcell and Reynolds 1200 Seventeenth Street, N.W.

Washington, D. C.

20036 Senior Resident Inspector c/o U.S. Nuclear Regulatory Commission Route 4, Box 529 Hunterville, North Carolina 28078 Regional Administrator, Region II U.S. Nuclear Regulatory Commission, 101 Marietta Street, N.W., Suite 2900 Atlanta, Georgia 30323 S. S. Kilborn Area Manager, Mid-South Area ESSD Projects Westinghouse Electric Corporation PNC West Tower - Bay 239 P. O. Box 355 Pittsburgh, Pennsylvania 15230