Semantic search
Jump to navigation
Jump to search
Issue date | Title | Topic | |
---|---|---|---|
ML20210H221 | 22 July 1999 | Notice of Violation from Insp on 990314-0424.Violation Noted:Sss Was Not Inoperable for Thirteen Days Because Electrical Breakers Associated with SSS Motor Control Ctr Were Mispositioned | Probabilistic Risk Assessment |
ML20207A588 | 17 February 1999 | Notice of Violation from Insp on 981213-990123.Violation Noted:Licensee Made Change to Procedures as Described in Updated Final Safety Analysis Rept & Failed to Perform Written Safety Evaluation | |
ML20154C430 | 14 September 1998 | Notice of Violation from Insp on 980705-0815.Violation Noted:Licensee Failed to Establish Adequate Surveillance Procedures | |
ML20236V735 | 27 July 1998 | Notice of Violation from Insp on 980524-0704.Violation Noted:Licensee Failed to Identify & Take Prompt C/A Following Unit 1 Upper Surge Tank over-temp Events on 960120,980111 & 0507 | |
ML20236J747 | 11 June 1998 | Notice of Violation from Insp on 980222-0411.Violation Noted:Adminstrative & Surveillance Procedures Not Implemented as Evidenced by Listed Examples | |
ML20217G555 | 23 March 1998 | Notice of Violation from Insp on 980111-0221.Violation Noted:Licensee Failed to Perform Written Safety Evaluation for Closing Valves 1CA-6 & 2CA-6 | |
ML20203L625 | 9 February 1998 | Notice of Violation from Insp on 971123-980110.Violation Noted:Changes to Radiological Conditions in 1B Residual Heat Removal Pump Room Not Logged to Reflect Changes in Dress Requirements | |
ML20199L630 | 2 February 1998 | Notice of Violation from Insp & Exam on 971117-21 & 971201-19.Violation Noted:As of 971219,selected Officers from Site Security Force Had Not Been Retrained to Perform non-licensed Operator Emergency Tasks for Starting Ssf | Safe Shutdown |
ML20197F248 | 19 December 1997 | Notice of Violation from Insp on 971012-1122.Violation Noted:Licensee Failed to Follow Radiation Protection Procedures in That,Current Radiation Dose Rates Were Not on Vacuum Cleaner Label as Required | |
ML20199G035 | 10 November 1997 | Notice of Violation from Insp on 970831-1011.Violations Noted:Licensee Failed to Follow Procedures for Security Badge Access Control as Evidenced.On 970909,security Failed to Destroy & Unassign Access Badge of Terminated Individual | |
ML20211L305 | 26 September 1997 | Notice of Violation from Insp on 970720-0830.Violation Noted:On 970727,technician Failed to Correctly Review Drawing Number CNEE-2792-01.02,connection Diagram,Main Steam Sys Terminal Cabinet 2SMTC1,rev 12 | |
ML20210N711 | 18 August 1997 | Notice of Violation from Insp on 970608-0719.Violation Noted:On 970424,operations Test Group Technician Failed to Open Valve 2NV-873 as Required by Step 2.2.3 of PT/2/A/4200/01C,resulting in Closed Test Vent Flowpath | Safe Shutdown Local Leak Rate Testing |
ML20149F906 | 7 July 1997 | Notice of Violation from Insp on 970427-0607.Violation Noted:Control Room Annunciator Alarm Response for Main Feedwater Containment Isolation Valve Low Nitrogen Actuator Pressure Inadequate | |
ML20148F929 | 23 May 1997 | Notice of Violation from Insp on 970323-0426.Violation Noted:Improper Sequencing of Valves to Isolate & Drain Containment Penetrations Resulted in Loss of Inventory from Component Cooling Water Sys | Fire Protection Program |
ML20141K661 | 16 May 1997 | Errata to NOV from Insp on 960324-0504.Violation Noted: Licensee Failed to Accomplish Activities Affecting Quality IAW Procedures as Evidenced by Listed Info | |
ML20137X329 | 16 April 1997 | Notice of Violation from Insp on 970210-14.Violation Noted:Licensee Failed to Include Number of Structures,Sys & Components within Scope of Maint Rule as Required | Maintenance Rule Program |
ML20140B758 | 17 March 1997 | Notice of Violation from Insp on 970112-0215.Violation Noted:Activities Affecting Quality Were Not Accomplished, IAW Documented Prescribed Procedures & QA Condition Matls Were Not Stored in QA Controlled Hold Area | |
ML20128R086 | 7 October 1996 | Notice of Violation from Insp on 960728-0907.Violation Noted:On 960804,residual Heat Removal Sys Was Inadequate Which Resulted in Failure of Valve 2ND-53 | |
ML20059G159 | 30 December 1993 | Notice of Violation from Insp on 931117-19 & 1129-1203. Violation Noted:On 931130,licensee Written Plan & Schedule Did Not Provide for Code Required Surface Exams on safe-end to Pipe Weld Safety Injection Accumulator Tanks | |
ML20059K689 | 29 October 1993 | Notice of Violation from Insp on 930905-1002.Violation Noted:Instrumentation & Electrical Technicians Failed to Adequatley Implement Catawba Nuclear Site Directive 4.2.2 & Procedure IP/O/A/3890/01 | |
ML20127E836 | 6 January 1993 | Notice of Violation from Insp on 921108-1212.Violation Noted:Design Control Measures Associated W/Ca Sys Were Inadequate & Design Deficiencies Rendered Sys Inoperable | |
ML20062A101 | 3 October 1990 | Notice of Violation from Insp on 900803-0905.Violation Noted:Shift Supervisor Failed to Follow Procedural Requirements | |
ML20059H016 | 31 August 1990 | Notice of Violation from Insp on 900624-0802.Violation Noted:Failure to Follow Instrumentation Procedures During Conduct of Plant Mod & Failure to Perform Adequate 10CFR50.59 Safety Evaluation Prior to Securing Annulus Door | |
ML20056A575 | 23 July 1990 | Notice of Violation from Insp on 900611-19.Violation Noted: Control Room Operator Failure to Verify That Manual Valve Closed Resulting in Inadvertent Diversion of Reactor Coolant to Refueling Water Storage Tank | |
ML20056A509 | 20 July 1990 | Notice of Violation from Insp on 900527-0623.Violation Noted:Solenoids on 3 Pilot Valves Associated W/Unit 2 High Pressure Fire Protection Sys Installed Backwards During Const | |
ML20247C702 | 31 August 1989 | Notice of Violation from Insp on 890616-28.Violation Noted: from 890602-16,both Channels of Reactor Vessel Water Level Instrumentation Inoperable in Modes 1,2 & 3 Due to Closure of Isolation Valves on upper-range Pressure Transmitters | Reactor Vessel Water Level |
ML20247R721 | 25 July 1989 | Notice of Violation from Insp on 890528-0701.Violation noted:post-accident Liquid Sampling Sys Periodic Test Inadequate to Ensure Valve Locked Closed After Use on 890602 in That Valve Discovered Open & Unlocked | High Radiation Area |
ML20246P705 | 10 July 1989 | Notice of Violation from Insp on 890405-0510.Violation Noted:On 890413,valve 1-KC-9 Not Locked in Position While Unit 1 at 100% Power & on 890412 & 0502,operators Did Not Frisk Upon Leaving Contaminated Area | |
ML20246C076 | 27 June 1989 | Notice of Violation from Insp on 890326-0429.Violations Noted:Selected Control Room Drawings Do Not Reflect as-built Conditions & Support Documents Necessary to Discern Scope of Mods Not Available in Control Room | |
ML20246N445 | 4 May 1989 | Notice of Violation from Insp on 890403-07 & 13.Violation noted:1988 Semiannual Effluent Release Rept Listed Two Abnormal Releases,But Did Not Include Descriptions of Events | |
ML20245G298 | 20 April 1989 | Notice of Violation from Insp on 890226-0325.Violation Noted:Licensee Failed to Implement Procedure in That While Attempting to Close 1SV-27A,operator Inadvertently Closed 1SM-7,Steam Generator 1A MSIV | |
ML20244A897 | 29 March 1989 | Notice of Violation from Insp on 890204-25.Violation Noted:Procedure PT/1/A/4200/55, CA Check Valve Leak Rate Test Inadequate to Ensure Auxiliary Feedwater Suction Piping Vented After Filling | |
ML20246L659 | 3 March 1989 | Notice of Violation from Insp on 890130-0203.Violations Noted:Two Licensee Employees Not Provided W/Info & Instructions Re Entering High Radiation Area & Area Not Posted | High Radiation Area |
ML20236A216 | 2 March 1989 | Notice of Violation from Insp on 881127-0204.Violation Noted:Failure to Declare Equipment Inoperable & Perform Written Safety Evaluation & 890126 Partial Obstruction of Unit 1 Pit Drain | |
ML20206J582 | 16 November 1988 | Notice of Violation from Insp on 880926-1025.Violations Noted:Two Instrument & Electrical Technicians Working W/O Procedures & Procedures AP-0-A-5500-34 & Omp 2-29 Inadequate | Condition Adverse to Quality Operability Determination |
ML20195B716 | 24 October 1988 | Notice of Violation & Proposed Imposition of Civil Penalty in Amount of $50,000.Noncompliance Noted:Lack of Environ Qualification for Certain Components of Electrical Equipment in Isolated Sys | Boric Acid Hydrostatic |
ML20205K089 | 17 October 1988 | Notice of Violation from Insp on 880826-0925.Violation Noted:Air Regulator for Valve 1CF-89 Replaced & Returned to Svc on 880721,w/o Being Tested to Demonstrate That Parameter Affected,Within Acceptable Limits | |
ML20207J801 | 16 September 1988 | Notice of Violation from Insp on 880719-22.Violation Noted: Licensee Failed to Adhere to Radiological Control Procedures in That on 880604,operations Personnel Stopped Leaking Valve W/O Waiting for Surveys,Evaluations or Job Coverages | |
ML20154A614 | 2 September 1988 | Notice of Violation from Insp on 880801-05.Violation Noted:No Objective Evidence Exists That Catawba Safety Review Group Reviews NRC Issuances,Industry Advisories or Other Sources Which May Indicate Areas for Improving Safety | |
ML20153C526 | 19 August 1988 | Notice of Violation from Insp on 880626-0725.Violation Noted:Failure to Maintain Two Operable Channels Per Valve for PORV Block Valve Position Indicators from Initial Licensing Until 880520 | |
ML20151E553 | 8 July 1988 | Notice of Violation from Insp on 880526-0625.Violation Noted:Personnel Exceeded Overtime Guidelines on Numerous Occasions During Jan & Feb 1988 W/O Prior Approval | |
ML20195K119 | 17 June 1988 | Notice of Violation from Insp on 880426-0527.Violation Noted:Failure to Establish Measures to Assure That Stopwatches Properly Controlled,Calibr & Adjusted & Valve Not Tested Before Returning to Svc | |
ML20195E426 | 13 June 1988 | Notice of Violation from Insp on 880310-18.Violation Noted:W/Unit 2 in Mode 1 & Operating at 20% Power,Three Independent Steam Generator Auxiliary Feedwater Pumps Not Operable During Actual Turbine Trip | |
ML20154D108 | 6 May 1988 | Notice of Violation from Insp on 880326-0425.Violation Noted:Diesel Generator 2B Inoperable for Period Exceeding Tech Spec Limits & Licensee Failed to Place Unit in Hot Standby & Subsequently in Hot Shutdown | |
ML20151B344 | 31 March 1988 | Notice of Violation from Insp on 880225-0325.Violation Noted:Failure to Follow Tech Spec Administrative Requirements for Approval of Mods | |
ML20148E687 | 18 March 1988 | Notice of Violation from Insp on 880202-04.Violation Noted: Failure to Establish Adequate Measures to Control Eddy Current Testing of Steam Generator Tubes | Eddy Current Testing |
ML20148E943 | 14 March 1988 | Notice of Violation from Insp on 880111-15.Violations Noted: Unit 2 Entered Mode 5 Exceeding by Approx 96 Hrs Time Required to Shutdown | Unanalyzed Condition |
ML20148H736 | 10 March 1988 | Notice of Violation from Insp on 880126-0225.Violations Noted:On 880123,RCS Pressure Allowed to Exceed 1,955 Psig & on 880109,equipment Operator Designated to Remove Safety Tag 410 Removed Tag & Repositioned Switch W/O Approval | Condition Adverse to Quality |
ML20149H357 | 4 February 1988 | Notice of Violation from Insp on 871226-880125.Violation Noted:Failure to Maintain Automatic Valve in Flow Path in Open Position When Above 10% Rated Thermal Power | |
IR 07100126/2012025 | 11 January 1988 | Revised Notice of Violation from Insp on 871126-1225. Violation Noted:On 871113,licensee Failed to Properly Classify Start Attempt Number 548 on Diesel Generator 1A as Invalid Failure |