NRC 2002-0049, May 2002 Monthly Operating Report for Point Beach Units 1 & 2

From kanterella
Jump to navigation Jump to search
May 2002 Monthly Operating Report for Point Beach Units 1 & 2
ML021690137
Person / Time
Site: Point Beach  NextEra Energy icon.png
Issue date: 06/05/2002
From: Webb T
Nuclear Management Co
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
GL-97-002, NRC 2002-0049
Download: ML021690137 (6)


Text

Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, WI 54216-9511 Two Rivers, WI 54241 920.388.2560 920.755.2321 NMexc Committed to NuclearExcellence Kewaunee / Point Beach Nuclear Operated by Nuclear Management Company, LLC NRC 2002-0049 GL 97-02 June 05, 2002 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, D.C. 20555 Ladies/Gentlemen:

Dockets 50-266 And 50-301 Point Beach Nuclear Plant, Units 1 And 2 Monthly Operating Reports Attached are monthly operating reports for Units 1 and 2 of the Point Beach Nuclear Plant for the calendar month of May 2002.

Sincerely, T.J. W Regulatory Affairs Manager KML Attachment cc: J. D. Loock, PSCW NRC Region mll NRC Senior Resident Inspector NRC Project Manager

ýý4

Docket 50-266 and 50-301 NRC-2002-0049 ATTACHMENT 1 Letter from Thomas J. Webb (NMC)

To Document Control Desk (NRC)

Dated June 05, 2002 Re: Monthly Operating Report - May 2002

OPERATING DATA REPORT DOCKET NO. 50-266 UNIT NAME POINT BEACH NUCLEAR PLANT - UNIT 1 DATE 06/04/02 COMPLETED BY Kim M. Locke TELEPHONE 920-755-6420 REPORTING PERIOD May - 2002

1. DESIGN ELECTRICAL RATING (MWE-NET) 515.0
2. MAXIMUM DEPENDABLE CAPACITY (MWE-NET) 510.0 MONTH YEAR TO DATE CUMULATIVE 744.0 3,623.0 227,232.8
3. NUMBER OF HOURS REACTOR WAS CRITICAL
4. NUMBER OF HOURS THE GENERATOR WAS ON LINE 744.0 3,623.0 223,717.0 0.0 0.0 846.9
5. UNIT RESERVER SHUTDOWN HOURS
6. NET ELECTRICAL ENERGY (MWH) 376,086.5 1,827,358.0 103,402,878.0 DATA REPORTED AND FACTORS CALCULATED AS REQUESTED IN NRC GENERIC LETTER 97-02 DATED MAY 15, 1997

UNIT SHUTDOWNS DOCKET NO. 50-266 UNIT NAME: Point Beach, Unit 1 DATE: 06/04/02 COMPLETED BY: Kim M. Locke TELEPHONE: 755-6420 REPORTING PERIOD: May 2002 (Month/Year)

NO. DATE TYPE DURATION REASON (1) METHOD OF CAUSE/CORRECTIVE ACTIONS F: FORCED (HOURS) SHUTTING S: SCHEDULED DOWN (2) COMMENTS N/A N/A N/A N/A N/A N/A N/A (1) Reason (2) Method A. Equipment Failure (Explain) 1 Manual B. Maintenance or Test 2 Manual Trip/Scram C. Refueling 3 Automatic Trip/Scram D. Regulatory Restriction 4. Continuation E. Operator Training/license Examination F .Administrative 5. Other (Explain)

G. Operational Error (Explain) H .Other (Explain)

SUMMARY

Unit 1 average daily power for the month of May was 505.5 MWe.

There were no Licensee Event Reports (LERs) submitted to the NRC.

There were no Significant Operating Events.

UNIT SHUTDOWNS DOCKET NO. 50-301 UNIT NAME: Point Beach, Unit 2 DATE: 06/04/02 COMPLETED BY: Kim M. Locke TELEPHONE: 755-6420 REPORTING PERIOD: May 2002 (Month/Year)

NO. DATE TYPE DURATION REASON (1) METHOD OF CAUSE/CORRECTIVE ACTIONS F: FORCED (HOURS) SHUTTING S: SCHEDULED DOWN (2) COMMENTS 3 04/12/02 S 318.1 C 1 This shutdown is carried over from April.

318.1 are the shutdown hours for May.

(1) Reason (2) Method A. Equipment Failure (Explain) 1 Manual B. Maintenance or Test 2 Manual Trip/Scram C. Refueling 3 Automatic Trip/Scram D. Regulatory Restriction 4. Continuation E. Operator Training/license Examination F .Administrative 5. Other (Explain)

G .Operational Error (Explain) H .Other (Explain)

SUMMARY

Unit 2 average daily power for the month of May was 266.4 MWe.

There were no Licensee Event Reports (LERs) submitted to the NRC.

There were no Significant Operating Events.

OPERATING DATA REPORT DOCKET NO. 50-301 UNIT NAME POINT BEACH NUCLEAR PLANT - UNIT 2 DATE 06/04/02 COMPLETED BY Kim M. Locke TELEPHONE 920-755-6420 REPORTING PERIOD May - 2002

1. DESIGN ELECTRICAL RATING (MWE-NET) 515.0
2. MAXIMUM DEPENDABLE CAPACITY (MWE-NET) 512.0 MONTH YEAR TO DATE CUMULATIVE
3. NUMBER OF HOURS REACTOR WAS CRITICAL 451.3 2,837.2 220,618.8
4. NUMBER OF HOURS THE GENERATOR WAS ON LINE 425.9 2,798.6 217,652.8
5. UNIT RESERVER SHUTDOWN HOURS 0.0 0.0 302.2
6. NET ELECTRICAL ENERGY (MWH) 198,169.5 1,381,571.0 102,165,078.0 DATA REPORTED AND FACTORS CALCULATED AS REQUESTED IN NRC GENERIC LETTER 97-02 DATED MAY 15, 1997

Text

Kewaunee Nuclear Power Plant Point Beach Nuclear Plant N490 Highway 42 6610 Nuclear Road Kewaunee, WI 54216-9511 Two Rivers, WI 54241 920.388.2560 920.755.2321 NMexc Committed to NuclearExcellence Kewaunee / Point Beach Nuclear Operated by Nuclear Management Company, LLC NRC 2002-0049 GL 97-02 June 05, 2002 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, D.C. 20555 Ladies/Gentlemen:

Dockets 50-266 And 50-301 Point Beach Nuclear Plant, Units 1 And 2 Monthly Operating Reports Attached are monthly operating reports for Units 1 and 2 of the Point Beach Nuclear Plant for the calendar month of May 2002.

Sincerely, T.J. W Regulatory Affairs Manager KML Attachment cc: J. D. Loock, PSCW NRC Region mll NRC Senior Resident Inspector NRC Project Manager

ýý4

Docket 50-266 and 50-301 NRC-2002-0049 ATTACHMENT 1 Letter from Thomas J. Webb (NMC)

To Document Control Desk (NRC)

Dated June 05, 2002 Re: Monthly Operating Report - May 2002

OPERATING DATA REPORT DOCKET NO. 50-266 UNIT NAME POINT BEACH NUCLEAR PLANT - UNIT 1 DATE 06/04/02 COMPLETED BY Kim M. Locke TELEPHONE 920-755-6420 REPORTING PERIOD May - 2002

1. DESIGN ELECTRICAL RATING (MWE-NET) 515.0
2. MAXIMUM DEPENDABLE CAPACITY (MWE-NET) 510.0 MONTH YEAR TO DATE CUMULATIVE 744.0 3,623.0 227,232.8
3. NUMBER OF HOURS REACTOR WAS CRITICAL
4. NUMBER OF HOURS THE GENERATOR WAS ON LINE 744.0 3,623.0 223,717.0 0.0 0.0 846.9
5. UNIT RESERVER SHUTDOWN HOURS
6. NET ELECTRICAL ENERGY (MWH) 376,086.5 1,827,358.0 103,402,878.0 DATA REPORTED AND FACTORS CALCULATED AS REQUESTED IN NRC GENERIC LETTER 97-02 DATED MAY 15, 1997

UNIT SHUTDOWNS DOCKET NO. 50-266 UNIT NAME: Point Beach, Unit 1 DATE: 06/04/02 COMPLETED BY: Kim M. Locke TELEPHONE: 755-6420 REPORTING PERIOD: May 2002 (Month/Year)

NO. DATE TYPE DURATION REASON (1) METHOD OF CAUSE/CORRECTIVE ACTIONS F: FORCED (HOURS) SHUTTING S: SCHEDULED DOWN (2) COMMENTS N/A N/A N/A N/A N/A N/A N/A (1) Reason (2) Method A. Equipment Failure (Explain) 1 Manual B. Maintenance or Test 2 Manual Trip/Scram C. Refueling 3 Automatic Trip/Scram D. Regulatory Restriction 4. Continuation E. Operator Training/license Examination F .Administrative 5. Other (Explain)

G. Operational Error (Explain) H .Other (Explain)

SUMMARY

Unit 1 average daily power for the month of May was 505.5 MWe.

There were no Licensee Event Reports (LERs) submitted to the NRC.

There were no Significant Operating Events.

UNIT SHUTDOWNS DOCKET NO. 50-301 UNIT NAME: Point Beach, Unit 2 DATE: 06/04/02 COMPLETED BY: Kim M. Locke TELEPHONE: 755-6420 REPORTING PERIOD: May 2002 (Month/Year)

NO. DATE TYPE DURATION REASON (1) METHOD OF CAUSE/CORRECTIVE ACTIONS F: FORCED (HOURS) SHUTTING S: SCHEDULED DOWN (2) COMMENTS 3 04/12/02 S 318.1 C 1 This shutdown is carried over from April.

318.1 are the shutdown hours for May.

(1) Reason (2) Method A. Equipment Failure (Explain) 1 Manual B. Maintenance or Test 2 Manual Trip/Scram C. Refueling 3 Automatic Trip/Scram D. Regulatory Restriction 4. Continuation E. Operator Training/license Examination F .Administrative 5. Other (Explain)

G .Operational Error (Explain) H .Other (Explain)

SUMMARY

Unit 2 average daily power for the month of May was 266.4 MWe.

There were no Licensee Event Reports (LERs) submitted to the NRC.

There were no Significant Operating Events.

OPERATING DATA REPORT DOCKET NO. 50-301 UNIT NAME POINT BEACH NUCLEAR PLANT - UNIT 2 DATE 06/04/02 COMPLETED BY Kim M. Locke TELEPHONE 920-755-6420 REPORTING PERIOD May - 2002

1. DESIGN ELECTRICAL RATING (MWE-NET) 515.0
2. MAXIMUM DEPENDABLE CAPACITY (MWE-NET) 512.0 MONTH YEAR TO DATE CUMULATIVE
3. NUMBER OF HOURS REACTOR WAS CRITICAL 451.3 2,837.2 220,618.8
4. NUMBER OF HOURS THE GENERATOR WAS ON LINE 425.9 2,798.6 217,652.8
5. UNIT RESERVER SHUTDOWN HOURS 0.0 0.0 302.2
6. NET ELECTRICAL ENERGY (MWH) 198,169.5 1,381,571.0 102,165,078.0 DATA REPORTED AND FACTORS CALCULATED AS REQUESTED IN NRC GENERIC LETTER 97-02 DATED MAY 15, 1997