NRC 2003-0054, May 2003 Monthly Operating Report for Point Beach Units 1 and 2
ML031690346 | |
Person / Time | |
---|---|
Site: | Point Beach ![]() |
Issue date: | 06/09/2003 |
From: | Cayia A Nuclear Management Co |
To: | Document Control Desk, Office of Nuclear Reactor Regulation |
References | |
GL-97-002, NRC 2003-0054 | |
Download: ML031690346 (5) | |
Text
iN Committed to Nuclear Excele Point Beach Nuclear Plant Operated by Nuclear Management Company, LLC NRC 2003-0054 GL 97-02 June 09, 2003 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, D.C. 20555 DOCKETS 50-266 AND 50-301 POINT BEACH NUCLEAR PLANT, UNITS 1 AND 2 MONTHLY OPERATING REPORTS Attached are monthly operating reports for Units 1 and 2 of the Point Beach Nuclear Plant for the calendar month of May 2003.
Sincerely, Site resident KML Attachment cc: J. D. Loock, PSCW NRC Regional Administrator NRC Resident Inspector NRC Project Manager e-LI--,
Ie3q 6590 Nuclear Road
- Two Rivers, Wisconsin 54241 Telephone: 920.755.2321
1, UNII SHUTDOWNS DOCKET NO. 50-266 UNIT NAME: Point Beach, Unit 1 DATE: 6/06/2003 COMPLETED BY: Kim M. Locke TELEPHONE: 755-6420 REPORTING PERIOD: Mav 2003 (Month/Year)
NO. DATE TYPE DURATION REASON (1) METHOD OF CAUSE/CORRECTIVE ACTIONS F: FORCED (HOURS) SHUITING S: SCHEDULED DOWN (2) COMMENTS N/A N/A N/A N/A N/A N/A N/A (1) Reason (2) Method A. Equipment Failure (Explain) 1 Manual B. Maintenance or Test 2 Manual Trip/Scram C. Refueling 3 Automatic Trip/Scram D. Regulatory Restriction 4. Continuation E. Operator Training/license Examination F .Administrative 5. Other (Explain)
G. Operational Error (Explain) H .Other (Explain)
SUMMARY
Unit I average daily power for the month of May was 513.6 MWe.
No Significant Operating Event occurred on Unit in May:
There were no LER's on Unit I in the month of May.
I, I OPERATING DATA REPORT DOCKET NO. 50-266 UNIT NAME POINT BEACH NUCLEAR PLANT - UNIT 1 DATE 06/03/03 COMPLETED BY Kim M. Locke TELEPHONE 920-755-6420 REPORTING PERIOD May - 2003
- 1. DESIGN ELECTRICAL RATING (MWE-NET) 522.0
- 2. MAXIMUM DEPENDABLE CAPACITY (MWE-NET) 516.0 MONTH YEAR TO DATE CUMULATIVE
- 3. NUMBER OF HOURS REACTOR WAS CRITICAL 744.0 3,623.0 235,222.4
- 4. NUMBER OF HOURS THE GENERATOR WAS ON LINE 744.0 3,623.0 231,681.5
- 5. UNIT RESERVED SHUTDOWN HOURS 0.0 0.0 846.9
- 6. NET ELECTRICAL ENERGY (MWH) 382,114.5 1,849,246.0 107,400,555.0 DATA REPORTED AND FACTORS CALCULATED AS REQUESTED IN NRC GENERIC LETTER 97-02 DATED MAY 15, 1997
UNIT SHUTDOWNS DOCKET NO. 50-301 UN1T NAME: Point Beach, Unit 2 DATE: 6/06/2003 COMPLETED BY: Kim M. Locke TELEPHONE: 755-6420 REPORTING PERIOD: May 2003 (Month/Year)
NO. DATE TYPE DURATION REASON (1) METHOD OF CAUSE/CORRECTIVE ACTIONS F: FORCED (HOURS) SHUTING S: SCHEDULED DOWN (2) COMMENTS N/A N/A N/A N/A N/A N/A N/A (1) Reason (2) Method A. Equipment Failure (Explain) 1 Manual B. Maintenance or Test 2 Manual Trip/Scram C. Refueling 3 Automatic Trip/Scram D. Regulatory Restriction 4. Continuation E. Operator Training/license Examination F .Administrative 5. Other (Explain)
G .Operational Error (Explain) H .Other (Explain)
SUMMARY
Unit 2 average daily power for the month of May was 485.1 MWe.
The following Significant Operating Event occurred on Unit 2 in May:
Steam Leak from 2P-28A, Steam Generator Feed Pump casing.
The following LER's were sent to the NRC in the month of May:
2003-002 TS Required shutdown due to TSAC 3.1.6.B.2 not met 2003-001 Containment Accident Fan Backfraft Damper Fan Failure 2003-003 Failure to place instrument channel in trip as specified by LCO 3.3.1
OPERATING DATA REPORT DOCKET NO. 50-301 UNIT NAME POINT BEACH NUCLEAR PLANT - UNll 2 DATE 06/03/03 COMPLETED BY Kim M. Locke TELEPHONE 920-755-6420 REPORTING PERIOD May - 2003
- 1. DESIGN ELECTRICAL RATING (MWE-NET) 522.0
- 2. MAXIMUM DEPENDABLE CAPACITY (MWE-NET) 518.0 MONTH YEAR TO DATE CUMULATIVE
- 3. NUMBER OF HOURS REACTOR WAS CRITICAL 744.0 3,577.0 229,330.1
- 4. NUMBER OF HOURS THE GENERATOR WAS ON LINE 744.0 3,535.4 226,301.1
- 5. UNIT RESERVED SHUTDOWN HOURS 0.0 0.0 302.2
- 6. NET ELECTRICAL ENERGY (MWH) 360,884.5 1,785,159.0 106,572,962.5 DATA REPORTED AND FACTORS CALCULATED AS REQUESTED IN NRC GENERIC LETTER 97-02 DATED MAY 15,1997
Text
iN Committed to Nuclear Excele Point Beach Nuclear Plant Operated by Nuclear Management Company, LLC NRC 2003-0054 GL 97-02 June 09, 2003 U.S. Nuclear Regulatory Commission ATTN: Document Control Desk Washington, D.C. 20555 DOCKETS 50-266 AND 50-301 POINT BEACH NUCLEAR PLANT, UNITS 1 AND 2 MONTHLY OPERATING REPORTS Attached are monthly operating reports for Units 1 and 2 of the Point Beach Nuclear Plant for the calendar month of May 2003.
Sincerely, Site resident KML Attachment cc: J. D. Loock, PSCW NRC Regional Administrator NRC Resident Inspector NRC Project Manager e-LI--,
Ie3q 6590 Nuclear Road
- Two Rivers, Wisconsin 54241 Telephone: 920.755.2321
1, UNII SHUTDOWNS DOCKET NO. 50-266 UNIT NAME: Point Beach, Unit 1 DATE: 6/06/2003 COMPLETED BY: Kim M. Locke TELEPHONE: 755-6420 REPORTING PERIOD: Mav 2003 (Month/Year)
NO. DATE TYPE DURATION REASON (1) METHOD OF CAUSE/CORRECTIVE ACTIONS F: FORCED (HOURS) SHUITING S: SCHEDULED DOWN (2) COMMENTS N/A N/A N/A N/A N/A N/A N/A (1) Reason (2) Method A. Equipment Failure (Explain) 1 Manual B. Maintenance or Test 2 Manual Trip/Scram C. Refueling 3 Automatic Trip/Scram D. Regulatory Restriction 4. Continuation E. Operator Training/license Examination F .Administrative 5. Other (Explain)
G. Operational Error (Explain) H .Other (Explain)
SUMMARY
Unit I average daily power for the month of May was 513.6 MWe.
No Significant Operating Event occurred on Unit in May:
There were no LER's on Unit I in the month of May.
I, I OPERATING DATA REPORT DOCKET NO. 50-266 UNIT NAME POINT BEACH NUCLEAR PLANT - UNIT 1 DATE 06/03/03 COMPLETED BY Kim M. Locke TELEPHONE 920-755-6420 REPORTING PERIOD May - 2003
- 1. DESIGN ELECTRICAL RATING (MWE-NET) 522.0
- 2. MAXIMUM DEPENDABLE CAPACITY (MWE-NET) 516.0 MONTH YEAR TO DATE CUMULATIVE
- 3. NUMBER OF HOURS REACTOR WAS CRITICAL 744.0 3,623.0 235,222.4
- 4. NUMBER OF HOURS THE GENERATOR WAS ON LINE 744.0 3,623.0 231,681.5
- 5. UNIT RESERVED SHUTDOWN HOURS 0.0 0.0 846.9
- 6. NET ELECTRICAL ENERGY (MWH) 382,114.5 1,849,246.0 107,400,555.0 DATA REPORTED AND FACTORS CALCULATED AS REQUESTED IN NRC GENERIC LETTER 97-02 DATED MAY 15, 1997
UNIT SHUTDOWNS DOCKET NO. 50-301 UN1T NAME: Point Beach, Unit 2 DATE: 6/06/2003 COMPLETED BY: Kim M. Locke TELEPHONE: 755-6420 REPORTING PERIOD: May 2003 (Month/Year)
NO. DATE TYPE DURATION REASON (1) METHOD OF CAUSE/CORRECTIVE ACTIONS F: FORCED (HOURS) SHUTING S: SCHEDULED DOWN (2) COMMENTS N/A N/A N/A N/A N/A N/A N/A (1) Reason (2) Method A. Equipment Failure (Explain) 1 Manual B. Maintenance or Test 2 Manual Trip/Scram C. Refueling 3 Automatic Trip/Scram D. Regulatory Restriction 4. Continuation E. Operator Training/license Examination F .Administrative 5. Other (Explain)
G .Operational Error (Explain) H .Other (Explain)
SUMMARY
Unit 2 average daily power for the month of May was 485.1 MWe.
The following Significant Operating Event occurred on Unit 2 in May:
Steam Leak from 2P-28A, Steam Generator Feed Pump casing.
The following LER's were sent to the NRC in the month of May:
2003-002 TS Required shutdown due to TSAC 3.1.6.B.2 not met 2003-001 Containment Accident Fan Backfraft Damper Fan Failure 2003-003 Failure to place instrument channel in trip as specified by LCO 3.3.1
OPERATING DATA REPORT DOCKET NO. 50-301 UNIT NAME POINT BEACH NUCLEAR PLANT - UNll 2 DATE 06/03/03 COMPLETED BY Kim M. Locke TELEPHONE 920-755-6420 REPORTING PERIOD May - 2003
- 1. DESIGN ELECTRICAL RATING (MWE-NET) 522.0
- 2. MAXIMUM DEPENDABLE CAPACITY (MWE-NET) 518.0 MONTH YEAR TO DATE CUMULATIVE
- 3. NUMBER OF HOURS REACTOR WAS CRITICAL 744.0 3,577.0 229,330.1
- 4. NUMBER OF HOURS THE GENERATOR WAS ON LINE 744.0 3,535.4 226,301.1
- 5. UNIT RESERVED SHUTDOWN HOURS 0.0 0.0 302.2
- 6. NET ELECTRICAL ENERGY (MWH) 360,884.5 1,785,159.0 106,572,962.5 DATA REPORTED AND FACTORS CALCULATED AS REQUESTED IN NRC GENERIC LETTER 97-02 DATED MAY 15,1997