ML24290A114

From kanterella
Jump to navigation Jump to search
CGS FPTI 2024011
ML24290A114
Person / Time
Site: Columbia Energy Northwest icon.png
Issue date: 10/17/2024
From: Nick Taylor
NRC/RGN-IV/DORS/EB2
To: Schuetz R
Energy Northwest
References
IR 2024010
Download: ML24290A114 (13)


Text

October 17, 2024

Robert Schuetz, Chief Executive Officer Energy Northwest MD 1023 P.O. Box 968 Richland, WA 99352

SUBJECT:

COLUMBIA GENERATING STATION - FIRE PROTECTION TEAM INSPECTION REPORT 05000397/2024010

Dear Robert Schuetz:

On October 7, 2024, the U.S. Nuclear Regulatory Commission (NRC) completed an inspection at Columbia Generating Station and discussed the results of this inspection with Grover Hettel, Executive Vice President/Chief Nuclear Officer and other members of your staff. The results of this inspection are documented in the enclosed report.

No NRC-identified or self-revealed findings were identified during this inspection.

A licensee-identified violation which was determined to be of very low safety significance is documented in this report. We are treating this violation as a non-cited violation (NCV) consistent with Section 2.3.2 of the Enforcement Policy.

If you contest the violation or the significance or severity of the violation documented in this inspection report, you should provide a response within 30 days of the date of this inspection report, with the basis for your denial, to the U.S. Nuclear Regulatory Commission, ATTN:

Document Control Desk, Washington, DC 20555-0001; with copies to the Regional Administrator, Region IV; the Director, Office of Enforcement; and the NRC Resident Inspector at Columbia Generating Station.

This letter, its enclosure, and your response (if any) will be made available for public inspection and copying at http://www.nrc.gov/reading-rm/adams.html and at the NRC Public Document Room in accordance with Title 10 of the Code of Federal Regulations 2.390, Public Inspections, Exemptions, Requests for Withholding.

R. Schuetz 2 Sincerely, Nicholas H. Taylor, Chief Engineering Branch 2 Division of Operating Reactor Safety Docket No. 05000397 License No. NPF-21

Enclosure:

As stated cc w/ encl: Distribution via LISTSERV Signed by Taylor, Nicholas on 10/17/24

ML24290A114 x Non-Sensitive x Publicly Available x SUNSI Review Sensitive Non-Publicly Available

OFFICE DORS/EB2/SRI DORS/EB2/BC

NAME SMakor NTaylor SIGNATURE /RA/ /RA/

DATE 10/17/24 10/17/24 U.S. NUCLEAR REGULATORY COMMISSION Inspection Report

Docket Number: 05000397

License Number: NPF-21

Report Number: 05000397/2024010

Enterprise Identifier: I-2024-010-0012

Licensee: Energy Northwest

Facility: Columbia Generating Station

Location: Richland, WA

Inspection Dates: August 12 to August 29, 2024

Inspectors: S. Makor, Senior Reactor Inspector N. Okonkwo, Reactor Inspector A. Saunders, Reactor Inspector

Approved By: Nicholas H. Taylor, Chief Engineering Branch 2 Division of Operating Reactor Safety

Enclosure

SUMMARY

The U.S. Nuclear Regulatory Commission (NRC) continued monitoring the licensees performance by conducting a fire protection team inspection at Columbia Generating Station, in accordance with the Reactor Oversight Process. The Reactor Oversight Process is the NRCs program for overseeing the safe operation of commercial nuclear power reactors. Refer to https://www.nrc.gov/reactors/operating/oversight.html for more information. A licensee-identified non-cited violation is documented in report section: 71111.21N.05.

List of Findings and Violations

No findings or violations of more than minor significance were identified.

Additional Tracking Items

None.

2 INSPECTION SCOPES

Inspections were conducted using the appropriate portions of the inspection procedures (IPs) in effect at the beginning of the inspection unless otherwise noted. Currently approved IPs with their attached revision histories are located on the public website at http://www.nrc.gov/reading-rm/doc-collections/insp-manual/inspection-procedure/index.html. Samples were declared complete when the IP requirements most appropriate to the inspection activity were met consistent with Inspection Manual Chapter (IMC) 2515, Light-Water Reactor Inspection Program - Operations Phase. The inspectors reviewed selected procedures and records, observed activities, and interviewed personnel to assess licensee performance and compliance with Commission rules and regulations, license conditions, site procedures, and standards.

REACTOR SAFETY

71111.21N.05 - Fire Protection Team Inspection (FPTI)

Structures, Systems, and Components (SSCs) Credited for Fire Prevention, Detection, Suppression, or Post-Fire Safe Shutdown Review (IP Section 03.01) (6 Samples)

The inspectors verified that components and/or systems will function as required to support the credited functions stated for each sample. Additional inspection considerations are located in the fire hazards analysis (FHA) or safe shutdown analysis (SSA).

(1) High Pressure Core Spray (HPCS), DG-1 (2) Cable Spreading Room, RC-2 (3) Reactor Building - General Equipment Area El. 422, R-1EL 422 (4) Main Control Room, Non-abandonment, RC-10 (5) Reactor Building El. 522, R1-E522 (6) Inspected Probabilistic Risk Assessment (PRA) Configuration Control (PCC) using the Operating Experience Smart Sample (OpESS) 2023-02 to verify that the licensee has a process in place to reasonably ensure PCC activities.

Fire Protection Program Administrative Controls (IP Section 03.02) (2 Samples)

The inspectors verified that the selected control or process is implemented in accordance with the licensees current licensing basis. If applicable, ensure that the licensees fire protection program contains adequate procedures to implement the selected administrative control. Verify that the selected administrative control meets the requirements of all committed industry standards.

(1) Fire Suppression (2) Fire Brigade Training and Drill

Fire Protection Program Changes/Modifications (IP Section 03.03) (7 Samples)

The inspectors verified the following:

a. Changes to the approved fire protection program do not constitute an adverse effect on the ability to safely shutdown.
b. The adequacy of the design modification, if applicable.
c. Assumptions and performance capability stated in the safe shutdown analysis have not been degraded through changes or modifications.

3

d. The fire protection program documents, such as the updated final safety analysis report, fire protection report, fire hazard analysis, and safe shutdown analysis were updated consistent with the fire protection program or design change.
e. Post-fire safe shutdown operating procedures, such as abnormal operating procedures, affected by the modification were updated.

(1) 0000019213, FO-P-3 and FP-M-P/3 Replacement - Urgent (2) 0000019824, FP-E/S-CO2 Power Supply Replacement (3) 0000014640, Replace 115 KV Oil Circuit Breaker (OCB) with New ABB SF6 (4) 000016611, Deactivate Existing Stack Monitor (5) 000018889, FP-HT-1A and FP-HT-1B Fitting Configuration Change - Urgent Modification (6) 0000019016, FP-HT-1G, FP-HT-1H, and FP-HT-1R Fitting Configuration Change (7) 0000019286, Replace Plant Emergency Lighting Battery Units

INSPECTION RESULTS

Licensee-Identified Non-Cited Violation 71111.21N.05 This violation of very low safety significance was identified by the licensee and has been entered into the licensee corrective action program and is being treated as a non-cited violation, consistent with Section 2.3.2 of the Enforcement Policy.

Violation: Facility Operating License (FOL) Condition 2.c.14, "Fire Protection Program,"

specified that Energy Northwest, shall implement and maintain in effect all provisions of the approved fire protection program as described in Section 9.5.1 and Appendix F of the Final Safety Analysis Report (FSAR). Specifically, FSAR Section 13.2.2.5.2 Offsite Fire Department, states in part that, the offsite fire department that supplements the Fire Brigade will attend familiarization training associated with the Columbia Generating Station plant layout, operational precautions, radiation protection, and special hazards associated with fires at a nuclear power plant. This offsite fire department will participate in at least one fire drill each year.

Contrary to the above, the licensee determined that the offsite fire department did not participate in at least one fire drill each year and a violation of their license condition had occurred. Specifically, the licensee documented on December 14, 2024, in action request (AR) 453566 multiple attempts to conduct cooperative drill exercises with Hanford Fire Department in 2023 and 2024. The licensee generated an action request to address the drill cancellations, to schedule and conduct the annual fire drill with the off-site department in accordance with EPlan, to make changes to the EPlan, and to completes a drill scheduled for September 26, 2024. Additionally, the licensee engaged legal to clarify the duties and expectation associated with the interagency agreement with Hanford Fire Department.

Significance/Severity: Green. This deficiency was more than minor because the finding is associated with the Protection Against External Factors attribute of the Mitigating Systems Cornerstone since it could affect the availability, reliability, and capability of systems that respond to a fire event to prevent undesirable consequences. The inspectors processed this finding using the guidance of Inspection Manual Chapter 0609, appendix F, Fire Protection Significance Determination Process. The inspectors determined from step 1.2, Assign a Fire Finding Category, that the fire prevention and administrative controls was the best category associated with the training programs element for the deficiency. From appendix F,

4 attachment 2, Degradation Rating Guidance, the inspectors determined the deficiency had a low degradation since it was similar to the examples of low degradation and would not have a significant effect on the likelihood that a fire would occur. Based on the criteria in Attachment 2, the inspectors assigned a Low degradation rating and the fire protection finding screened to green (Yes to question 1.3.1-A).

Corrective Action

References:

AR 00461113, AR 454002454002 and AR 453566453566

EXIT MEETINGS AND DEBRIEFS

The inspectors verified no proprietary information was retained or documented in this report.

  • On August 29, 2024, the inspectors presented the fire protection team inspection results to Dave Brown, Site Vice President and other members of the licensee staff.
  • On October 7, 2024, the inspectors presented the inspection re-exit inspection results to Grover Hettel, Executive Vice President/Chief Nuclear Officer and other members of the licensee staff.

5 DOCUMENTS REVIEWED

Inspection Type Designation Description or Title Revision or Procedure Date 71111.21N.05 Calculations NE-02-85-19 Post Fire Safe Shut down (PFSS) Analysis 015 71111.21N.05 Calculations NE-02-85-19 Post Fire Safe Shutdown Analysis 015 71111.21N.05 Calculations NE-02-94-35 System Impacts on Post Fire Safe Shutdown 007 71111.21N.05 Corrective AR 00434841, 00424777, 00461045, 00254065, 00446317, Action 00446636, 00440385, 00454272, 00394803, 00315334 Documents 71111.21N.05 Corrective AR 00461045, 425259-78, 454002, 453566 Action Documents Resulting from Inspection 71111.21N.05 Drawings 1.10.1 Notifications and Reportable Events 046 71111.21N.05 Drawings D002.92 CVI 217-00,84,13 Fire Detection & Alarm System 005 Installation Dwg.,

71111.21N.05 Drawings E502-2 Main One-Line Diagram 069 71111.21N.05 Drawings E533-21VF-1 4160V Switchgear E-SM-8 017 71111.21N.05 Drawings E537-3C Connection Wiring Diagram Control Cabinet Termination 031 Cabinets 71111.21N.05 Drawings E539-15 Connection Wiring Diagram Reactor Instrumentation and 025 Control 71111.21N.05 Drawings E539-16 Connection Wiring Diagram Reactor Instrumentation and 025 Control 71111.21N.05 Drawings E839-01 Electrical Grounding Supply System 008 71111.21N.05 Drawings E948-1 Appendix R Post Fire Safe Shutdown (PFSS) Protected 018 Raceways General Notes, Legend and drawing Index 71111.21N.05 Drawings E948-2 Appendix R Post Fire Safe Shutdown (PFSS) Protected 017 Raceways Reactor Building & DG/RW Corridor Elevation 441'-0" and 471'-0" 71111.21N.05 Drawings E948-2A Appendix R Post Fire Safe Shutdown (PFSS) Protected 008 Raceways Reactor Building Elevation 501'-0" and 522'-0" 71111.21N.05 Drawings E948-2B Appendix R Post Fire Safe Shutdown (PFSS) Protected 010 Raceways Reactor Building Elevations 548"-0" and 572'-

6 Inspection Type Designation Description or Title Revision or Procedure Date 0"

71111.21N.05 Drawings EWD-62E-0-46 Electrical Wiring Diagram T.G. Bldg, LP CO2 Sys. Zone 3-005 CD Storage Tank FP-TK-1 71111.21N.05 Drawings EWD-9E-017 Electrical Wiring Diagram Residual Hear Removal System 018 MOV RHR-V-3B 71111.21N.05 Drawings EWD-9E-019 Electrical Wiring Diagram Residual Hear Removal System 026 MOV RHR-V-4B 71111.21N.05 Drawings EWD-9E-028 Electrical Wiring Diagram Residual Hear Removal System 024 MOV RHR-V-16B 71111.21N.05 Drawings EWD-9E-064 Electrical Wiring Diagram Residual Hear Removal System 014 MOV RHR-V-74B 71111.21N.05 Drawings FM 892-7 Sprinkler and Hose Station Plan, El. 437-0, 441-0 and 007 MISC Floor 71111.21N.05 Drawings M 507-1 Flow Diagram Circulating Water System Turbine 184 Generator & Yard.

71111.21N.05 Drawings M 515-3 Flow diagram Fire Protection System CO2 Distribution 009 71111.21N.05 Drawings M 560 General Arrangements, Ground Arrangements Ground 035 Floor Plan Turbine Generator Bldg.

71111.21N.05 Drawings PFP-DG-Building Pre-Fire Plan Diesel Generator Building 006 71111.21N.05 Drawings PFP-RB-422 Pre-Fire Plan Reactor 422 009 71111.21N.05 Engineering 17692 Replace motor FP-M-P/2B 001 Changes 71111.21N.05 Engineering EC 11897 Replacement of Electric Fire Protection Pump Controllers 000 Changes FP-CP-2A and FP-CP-2B 71111.21N.05 Engineering EC 14640 Replace 115 KV Oil Circuit Breaker (OCB) With New ABB 00 Changes (SF6) 71111.21N.05 Engineering EC 15499 CW-P-1B CONDITION MONITORING SYSTEM 002 Changes 71111.21N.05 Engineering EC 16611 Vent Stack Monitor Removal 01 Changes 71111.21N.05 Engineering CAB-01032009-Cable History Record Cable: 2RHR-0815 000 Evaluations 6014 71111.21N.05 Miscellaneous N/A Emergency Response (HFD) Interaction agreement (9 9/1/11 11)

7 Inspection Type Designation Description or Title Revision or Procedure Date 71111.21N.05 Miscellaneous AR-SA: 454272 Focused Self-Assessment Report Fire Protection Program 000 71111.21N.05 Miscellaneous AU-FP-21 Quality Services Audit Report -Fire Protection Program 10/20/2021

71111.21N.05 Miscellaneous BI 24-0220 Barrier Impairment Permit for Radwaste 484 door C313 08/06/2024 71111.21N.05 Miscellaneous BIP 23-0048 Barrier Impairment Permit BIP 23-0048 7/05/2023

71111.21N.05 Miscellaneous Contract HFD Executed Amendment 34 Extension 12/31/2019 Number: 314208

71111.21N.05 Miscellaneous DRD-209 Design Specification for Division 200 Section Post-Fire 009 Safe Shutdown (PFSS) Analysis Requirements.

71111.21N.05 Miscellaneous EC 0018253 NE-02-94-35 Removal of CAC Skids EC 17976 04/17/2020 71111.21N.05 Miscellaneous EPRI Report Fire Protection Equipment Surveillance Optimization and July 2003 1006756 Maintenance Guide

71111.21N.05 Miscellaneous FPSA-2-FQ-0001 CGS Fire PRA Summary and Qualification (FQ) Notebook 001 71111.21N.05 Miscellaneous FPSA-2-FQ-0001 CGS Fire PRA Summary and Qualification (FQ) Notebook 01 71111.21N.05 Miscellaneous FSAR Table F.2-FSAR Table F.2-1 Code Deviations 12/2023 1

71111.21N.05 Miscellaneous LCS 1.10 1.10 Fire Protection 073

71111.21N.05 Miscellaneous N/A Crew C 2024 UB (NRC) Drill Report-Critique 8/14/24 71111.21N.05 Miscellaneous NO 36 Control room alarms for CO2-Trouble alarms in the N/A control room for the CO2 system can be found in 4.FCP.3.

71111.21N.05 Miscellaneous OER Number: Columbia Response to IN 89-52 resolution 4/13/93 8311 OB

71111.21N.05 Miscellaneous SC000044 Security Annual Fire Tour Refresher N/A

71111.21N.05 Miscellaneous Spec 16A Section 16A Electrical Installation 011

71111.21N.05 Miscellaneous Spec 50A.2 DIVISON 50 SECTION 50A.2 PANELS AND RACKS 003

8 Inspection Type Designation Description or Title Revision or Procedure Date

71111.21N.05 Miscellaneous TC# 25 E-TR-B Rainbow Report - Oil test report N/A

71111.21N.05 Procedures 71111.21N.05 Procedures 1.3.10 Plant Fire Protection Program Implementation 041 71111.21N.05 Procedures 1.3.10B Active Fire System Operability and Impairment Control 017 71111.21N.05 Procedures 1.3.56 Conduct of Maintenance 016 71111.21N.05 Procedures 1.3.57 Barrier Impairment 047 71111.21N.05 Procedures 10.2.53 Scaffolding 054 71111.21N.05 Procedures 10.25.105 Motor Control Center and Switchgear Maintenance 043 71111.21N.05 Procedures 10.25.55 Grounding System Installation 010

71111.21N.05 Procedures 15.3.5 Fire Damper Operational Inspection 021 71111.21N.05 Procedures 15.3.6 Control Room Halon Pressure Check, Weight Check, 011 Nozzle Inspection, and PGCC Barrier Inspection 71111.21N.05 Procedures ABN-CR-EVAC Control Room Evacuation and Remote Cooldown 049

71111.21N.05 Procedures ABN-FIRE Fire 047

71111.21N.05 Procedures ABN-FIRE-CR Control Room Fire 005 71111.21N.05 Procedures AMPBD-FP Aging Management Program Basis Document - Fire 002 Protection Program 71111.21N.05 Procedures CS-01 Critical System List 010

71111.21N.05 Procedures EC 18889 FP-HT-1A AND FP-HT-1B FITTING CONFIGURATION 001 CHANGE 71111.21N.05 Procedures EC 19016 FP-HT-1G, FP-HT-1H, AND FP-HT-1R FITTING 000 CONFIGURATION CHANGE 71111.21N.05 Procedures EP-01 Emergency Plan, Columbia Generating Station 068

71111.21N.05 Procedures FPF 1.4-6 FPEE for Fire Damper Operational Inspections 002

9 Inspection Type Designation Description or Title Revision or Procedure Date 71111.21N.05 Procedures IP-ENG-001 Standard Design Process 003 71111.21N.05 Procedures OI-69 Time Critical Operator Actions 018

71111.21N.05 Procedures PPM 10.25.55 Grounding System Installation 010 71111.21N.05 Procedures SD000193 Circulating Water and Tower Makeup 026

71111.21N.05 Procedures SOP-CW-Chem-Circulating Water Chemical Maintenance 027 Maint.

71111.21N.05 Procedures SOP-CW-Chem. Circulating Water and Cooling Tower Chemistry 026

71111.21N.05 Procedures SOP-CW-Circulating Water and Cooling Towers Shutdown 010 Shutdown 71111.21N.05 Procedures SOP-Elec-Removing/Restoring TR-B, From/To Service 011 115KV-OPS

71111.21N.05 Procedures SWP-FPP-01 Nuclear Fire Protection Program 012 71111.21N.05 Procedures SWP-LIC-03 Licensing Document Change Process 022

71111.21N.05 Procedures TPD-22 Fire Brigade Training Program Description 010 71111.21N.05 Work Orders 02149189 PPM 15.3.1-Perform Annual Hydrant Hose Change out 71111.21N.05 Work Orders 02168207 PPM 15.3.1-Perform Annual Hydrant Hose Changeout 71111.21N.05 Work Orders 02185105 PPM 15.3.1-Perform Annual Hydrant Hose Changeout 71111.21N.05 Work Orders FPSI No. 23-FIRE PROTECTION SYSTEM IMPAIRMENT PERMIT 000 0151 71111.21N.05 Work Orders FPSI NO. 24-FIRE PROTECTION SYSTEM IMPAIRMENT PERMIT 000 0082 71111.21N.05 Work Orders WO 02191535 01, 02197049 01, 02066673 45, 222238801, 02153091 01, 02074274 01, 02029593 01, 02197233 01, 02066675-01, 02186472 01

10