~._

ELECTRICAL PCtfE1 SYSTEMS SbRVIIthANCE 13g0Iw5 4.8.2.1 Each of the above required batteries and chargers shall be demon-strated OPERABLE:

a.

At least once per 1 days by verifying that:

i 1.

The parameters in Table 4.8.2.1-1 meet the Category A limits, and 2.

Total battery terminal voltage for each 125 volt battery as greater than or equal to 129 volts on float charge and for each 250-volt battery the terminal voltage is greater than or equal to 258 volts on float charge.

b.

At least once per 92 days and within 7 days after a battery discharge with battery terminal voltage below log volts for a 125 volt battery l

or 210 volts for a 250 volt battery, or battery overcharge with battery aerminal voltage above 140 volts for a 125-volt battery or 280 volte cor a 250-volt battery, by vertfying that:

1.

The parameters in Table 4.8.2.1 1 meet the Category a limits,

~~

J.

There is no visible corrosion at either terminals or connectors, or the connection resistance of these items is less than 150 x 10 ohms, excluding cable intercell connections, and 3.

The average electrolyte temperature of each sixth cell of connected cells is above 4+* W hv F.

c.

At least once per 18 months by verifying that:

1.

The cells, cell plates and battery racks show no visual indication of physical damage or abnormal deterioration, 2.

The cell to-cell and terminal connections are clean, tight, free of corrosion and coated with anti corrosion material, 3.

The resistance of each cell-to-cell and terminal connection is less than or equal to 150 x 10** ohms, excluding cable intercell connections, and 4.

The battery charger will supply the current listed below at the voltage listed below for at least 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />.

l CURRErf QEggg Mini - Voltaan (AMPERRE) 1AD413, 1AD414 129 200 18D413, 130414 1CD413, 1CD414 1CD444, 1D0414 1DD444, 1DD413 10D423, 10D433 258 50 HOPE CREEK 3/4 8 13 Amendeent No. 87 9811030201 981022 PDR ADOCK 05000354 P

PDR