Proposed Tech Specs Re Increased Operational Flexibility During Periods of Elevated River Water Temp & Maintain Ultimate Heat Sink Operation within Design
ML20249A818
Person / Time
Site: Hope Creek 
Issue date: 06/12/1998
From:
Public Service Enterprise Group
To:
Shared Package
ML20249A811 List:
References
LCR-H98-02, LCR-H98-2, LR-N98274, NUDOCS 9806180280
Download: ML20249A818 (5)


Text

Document C ntral Deck LR-N98274 LCR H98-02 HOPE CREEK GENERATING STATION FACILITY OPERATING LICENSE NPF-57 DOCKET NO. 50-354 REVISIONS TO THE TECHNICAL SPECIFICATIONS (TS)

TECHNICAL SPECIFICATION PAGES WITH PROPOSED CHANGES The following Technical Specifications for Facility Operating License No. NPF-57 are affected by this change request:

Technical Specification Page 3.7.1.1 3/4 7-la 3.7.1.2 3/4 7-3 3.7.1.3 3/4 7-5 1

9906190290 990612 fT PDR ADOCK 05000354'-

j P

PDR3 i

1- _. _. _. _ _. _ _ _

I PLANT SYSTEMS I

LIMITING CCNDIT:CN FCR CPERAT:CN Continued)

ACT!ON

+ Continued)

With one SACS pump in each subsystem.incperable, and if

3. a.

continued plant operation is permitted by LCC 3.7.1.3, restore least one incperable pump to CPERABLE status within *2 hours at or ce in at least HCT SHUTDCWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in 2;LD 3HUCDCWN within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.***

l b.

With one SACS heat exchanger in each subsystem incperacle.

immediately initiate measures to place the unit in at least HCT SKUTDCWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in CCLD SHUTDCKN within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

With both SACS subsystems otherwise snoperable, immediately 4.

initiate measures to place the unit in at least HOT SKUTCCWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDCWN* in the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, b.

In OPERATIONAL CCNDITICN 3 or 4 with the SACS subsystem, which is f

associated with an RHR loop required CPERABLE by Specification 3.4.9.1 or 3.4.9.2, having two SACS pumps or one heat exchanger inoperable, declare the associated RHR loop inoperable and take the ACTICN required by Specification 3.4,9.1 or 3.4.9.2, as applicable.

  • Whenever both SACS subsystems are inoperable, if unable to attain CCLD SNUTDOWN as required by this ACTION, maintain reactor coolant removal temperature as low as practical by use of alternate heat methods.
      • Two diesel generators and service water pumps associated with the

. )

required CPERABLE SACS pumps must be CPERABLE.

I j

l au Secs Mr.A exe %.cs.

  • ^

HCPE' CREEK 3/4 7-la Amendment No. 106 i

s 9

-g

E' PLANT 5V5TEMS STAT!!N'3EP'i~0E WATER 3YSTEM LIMITINd Cd!CITION PCR' CPEPATION 1,* I I At ; east the follcwing independen station service water system locps.

l

.itn sa:n.:cp :: prised sf:

4-Two IPERA3LE statien servi:e water pumps, and An PERABLE flew path capable of taking suction from the Celaware

.b.

River ' ultimate heat sink) and transferring the water to the 3ACS heat exchangers, shall te OPERABLE:

a.

In OPERATIONAL CCNDITICN 1, 2 and 3, two loops.

b.

In OPERATIONAL CONDITICN 4, 5 and *. one loop.

APPLICABILITY: CPERATICNAL CONDITIONS 1, 2,

3, 4,

5 and *.

ACTION:

a.

In CPERATICNAL CCNDITION 1, 2,

or 3:

With one station service water pump inoperable, and if

- ' n-c -<---

1..

445445 opesib'sii4.y continued plant operation is permitted by LCO 3.7.1.3, restore

. (..A 's 6+5 pct =4eb the incpe able pump to CPERABLE status within 30 days or be in p

A at lea -

THUTDCWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD j

i N Iwof ad

    • Mt 3gu7po."" *.

tn the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.**

If the conditien

[

" can not be met, be in at least HOT SHUTDOWN N MC.'Tiod $pt t.*h t h dspecift - a within the next 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> and in COLD SHUTDCWN within the y

3) following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, O C4Eva $4 4teent 2.

With one station service water pump in each locp inoperable, g,q(/ ' 4 7,%9 yg>

and if continued plant operation is permitted by LCO 3.7.1.3, restore at least one inoperable pump to CPERABLE status

{

gg) l within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least HOT SHUTDOWN within the next

' l 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.***

3.

With one station service water ' system loop otherwise j

inoperable, and if continued plant operation is permitted by i

LCO 3.7.1.3 9/ restore the inoperable station service water system loop to OPERABLE status with at least one OPERABLE pump within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or.be in at least HOT SHL"I'DCWN within the next

12 hours and in COLD SHUTDOWN within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.**

I i

  • Two diesel generators and SACS. pumps associated with the required OPERABLE i

service. water pumps must be OPERABLE.

HCPE. CREEK

- __ _ 3/4 7-3 Amendment No. 106 ff g g.

(

l e

f-l

}

Ptxtr systems

'_*L7: MATE HEAT s!NK LIMITlNG CONDITION FOR OPERATION l

3

.'.3

  • he ultimate neat sink.0elaware River) shall be OPERABLE with:

t l

A inimum river water level at or above elevati:n.9' O Mean Sea a.

Leve'. L'SGS datum 90' O PSE&G datum), and 87.

l An average river water temperature et 'ess than or equal to 15.

b

_ - _ - - -- w 3

5 and

  • p --

a.s

-.4, _4,_ _ _-

3 2

AP PL ! ABILITY - _O PEpi'""*f AL_ CONDITI_ONS_1

c. n n.c u.. r e.
~<3 r~_

,g,a,

_m g,,

+

f......e x s s m.c

.r.

p4M 4.4 b. A *^'*atah W*hel h(ake,ry. V-W #

te<, !*

  • d ectff*(q{c)4cL t ;; N.

4 ph

  • Ve =e=

- - r--1 Witn the [1ver water temperature in excess of d b *F, continued Operation is permitted provided that all of th followind" conditions are 4

lo8N0*F, M9 :-;. r...f satisfied: ultimate heat sink temperature is ever W rd-4&scharga valvo w y.r.--h u..w wuw y a. win.g y.c;.

.y.

s"=55bMI all SSWS pumps are OPERABLE, all SACS pumps are OPERABLE, all EDGs are OPERABLE and the SACS loops have no cross-connected loads (unless they are automatically isolated during a LOP and/or LOCA), otherwise, with the satisfied requirements of the above specification not a.

In OPERATIONAL CONDITIONS 1, 2 or 3, be in at least HOT SHUTDOWN within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the next 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

b.

In OPERATIONAL CONDITIONS 4 or 5, declare the SACS system and the station service water system inoperable and take the ACTICN required by Specification 3.7.1.1 and 3.7.1.2, In Operational Condition *, declare the plant service water system c.

inoperable and take the ACTION required by Specification 3.7.1.2.

The provisions of Specification 3.0.3 are not applicable.

SLTVEILLANCE REQUIREMENTS 4.7.1.3 The ultimate heat sink shall be determined OPERABLE:

By verifying the river water level to be greater than or equal to a.

the minimum limit at least once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

By verifying river water temperature to be within its limit:

b.

1) at least once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> when the river water temperature is less than or equal to 82*F.

least once per 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> when the river water temperature is

)

at l

greater than 92*F.

  • When handling irradiated fuel'in the secendary containment.

HOPE CREEK 3/4 7-5 Amendment No. [;m C._-

_.a._

Document C ntral Deck LR-N98274 Atta:hment 4 LCR H98-02 HOPE CREEK GENERATING STATION FACILITY OPERATING LICENSE NPF-57 DOCKET No. 50-354 REVISIONS TO THE TECHNICAL SPECIFICATIONS (TS)

ENGINEERING EVALUATIONS ASSOCIATED WITH THE PROPOSED CHANGES