' NUCLEAR POWER BUSINESS UNIT ORT 72 OPERATIONS REFUELING TESTS MINOR Revision 8 3'

ELECTRICAL PENETRATION LEAK TEST January 25,1997 UNIT 1 Date RECORD DSS raoCEouxE vEn:HED CURRENT AND CifECKED FOR TEMPORARY CilANGES IF FIELD CoPtEs REoutRED. USE PBF-0026s IAW NP 1.2 4 AND DO E COMPLETE Tills BLOCK.

BY:

DATE:

1.0 PURPOSE The purpose of ORT 72 is to perform a refueling interval leak test the envelope for electrical penetrations E21 and E22 which are located in the El. 26' Pipeway No. 2, upper level.

2.0 BEFERENCES IR 96-006, NRC Inspection Report, NRC Commitment for Operations procedure PMT/QC reviews.

3.0 PRECAUTIONS AND LIMITATIONS 3.1 Penetration E21 and E22 may be ganged together for leak testing purposes.

3.2 All electrical penetrations must be leak tested with nitrogen.

4.0 INITIAL CONDITIONS Permission to Perform Test The conditions required by this test are consistent with required plant conditions including equipment operability. Permission is granted to perform this test.

l DSS Time Date 5.0 PROCEDURE NOTE:

Thispenetration nugg be leak tested with nitrogen.

\\

5.1 Open the isolation valve downstream of pressure gauge for the penetration 1

to be tested and remove the test cap.

1 5.2 Remove the pressure gauge and Whitey valve assembly.

9702180370 970210 Page1of3 CONTINUOUS USE PDR ADDCK 05000301 P

PM

' NUCLEAR POWER BUSINESS UNIT ORT 72 OPERATIONS REFUELING TESTS MINOR Revision 8 ELECTRICAL PENETRATION LEAK TEST January 25.1997

- (...

UNIT l INITIALS i

NOTE:

Minimize the amount of time the leak rate tester is connected to the mechanicalpenetration.

5.3 Connect the test rig to the penetration test connection and test per 01-58.

5.4 Upon completion of the test, vent the penetration per 01-58.

5.5 Disconnect the test rig and replace the pressure gauge and Whitey valve assembly.

5.6 Repressurize the penetration to 15 psig. Close the isolation valve and replace the test cap.

PMT 5.7 Snoop disturbed fittings for leakage and tighten / initiate work order, as 4

required.

4 6.0 EVALUATION TO BE COMPLETED BY OPERATIONS MANAGER OR HIS REPRESENTATIVE.

l 6.1 Individual leakages compared to allowable value and included in tabulation of total leak rate 6.2 Results acceptable,0.6 L, not exceeded.

Yes No (If no, give details in the Remarks section and notify the Regulatory Services manager to determine reportability.)

6.3 Data Analyzed By Date Remarks:

Page 2 of 3 CONTINUOUS USE

' NUCLEAR POWER BUSINESS UNIT ORT 72 4

OPERATIONS REFUELING TESTS MINOR Revision 8 3

4 ELECTRICAL PENETRATION LEAK TEST January 25,1997 UNIT 1 LEAK TEST DATA SHEET l

Penetrations E21 and E22 Pressure Leak Rate Time (psig)

(sccm)

Test Instrument ID Range (Circle one): Low Mid High Comments:

Test Operator Date i

a Page 3 of 3 CONTINUOUS USE

,