Rev 17 to Ort 59, Train Spray Sys CIV Leakage Test for Unit 1
ML20138K470
Person / Time
Site: Point Beach  
Issue date: 01/31/1997
From:
WISCONSIN ELECTRIC POWER CO.
To:
Shared Package
ML20138K159 List: ... further results
References
ORT-59, NUDOCS 9702180359
Download: ML20138K470 (9)


Text

m,7..,. y~ g.m w.,, p> <

y. 4,, f y,r. " ~

m.-

~

n i

+ ' - '

.s

(,- 1

.1sp NUCLEAR 709fERBUSINESSUNIT l

. l ORT 59

_q mi D,, OPERATIONS REF'JELING TESTS:

.. MINOR l

j 4

M, W

.,;...,e.

,3.-

Revision 17 y

r.,

i t

gq. ; TRAIN A SPRAY SYSTEM CIV LEAKAGE TEST :

January 31,1997 '

UNIT f '

'J- {

M4

/a.

< a

, va s' a 1

s

e.,-

y y/ iDowT a.>

RECORD!

m s

A '~. M DssP PmxxounsvaarmDcunaswr ANDCpscKEDPCRMMPCRARY CHANGES FRELD '

'l 9l Q@'Yh',.'",

CDP 55 REQURBD. USE PSF 40E IAW NP 1.24 AND DO M2I COMPLETE THIS BLOCK J

y{

L BYr '

i q[. >

+

+

4 DATE:

a d't (j

^

(F y

'}1,0? RPRPOSE

^

To perform a 10 CFR 5_0 Appe.ndix J Type C leakage' test for penetration P-54,

. og,

valves ISI-862A,' 862G, 864A, and 868A.-. '

a-a i

~.

4 21 0 M' REFERENCES y

.,c s,'

gy-l IR 96 006, NRC fa5-* ion Report, NRClCommitmein for Operations procedure PMT/QC '

^'

a.

E4 f

.y PRECAUTIONS AND LIMITATIONS'.

i

- 3.0 d

6.

g 13.1) 1.acate the Volumetrics tester in an area which will limit personal exposure.

f N "t,

c 3.2l Do not allow liquids to ' enter the Vohnumerics tester or damage may occur, kN a

.9, 23.3.

All liquids must be drained from piping subsystem prior to attaching the test rig.

l

e h'

' 31-During the test, the SI test line is removed from service. The SI pump control switches

must be in pullout position, but one SI pump may be operable for reduced inventory l

! operation or boration flow path. With the associated SI pump mini-recirc shut, a pump f discharge flow path must be established prior to manually starting the pump.

a INmALS i

r L4.0; INITIAL CONDmONS t

H g.

x L4.lg ; The RCS is in cold or refueling shutdown.

z.;

y 7

4.2 : ! No testing requiring the use of the test recire line via ISI-897A&B w 1 be j

A enruhacked during the duration of this test.

_. ii i g.

g '

'\\

sq ;

, :.,i:.!

. C

+

ye f^.\\:: Q,;.

..w M., : 7 f

i M C?'q/

fi;;,

4 V(

F O 4y.

r:

s

1-

. w',L.,& -

v;

<?l8

+

m~

p, x' :p,.o

,k_

Ml 9702180359 970210

'l ngN.

A,E W.u

.v i

i Page 1..of 9 ' -, ~'

. CONTINUOUS USE,

j d

PDR ADOCK 05000301

~

'-g..

-+

w p

ppR

~

%.-~nn.ww, acam

- - ~

c w

gy weg x N

+

i R UCI2ARPOWERBUSINESSUNIT L ORT 59 u r OPERATIONSREFUELINGTESTS MINOR:L

, y.

.j

, g s.

LRevision 171 u

gn,W NIT FTRAIN A SPRAY SYSTEM CIV LEAKAGE TEST -

~ January 31; 1997--

p.;

4 h' e n

~

INITIALS.-

5 (.

f u q._

m.. -,

,.1 L a 4 -.. -

m

.e

' 4,37 U, Volumetrics test' rig is available outside containment.

f p-'

A

,.R9,y

m

~

a

~-

r a@. df p,, mission to Perform Test :

n >

47 s

= ;

4,'

l jThe conditions required by this test are consistent with required plant -

m,'

?. conditions including equipment operabilityc Permission is granted to

JP '

Lperform this test.

~

+.

~ M.

4

? DSS-Time' Date o

c'.o.

pJ; N l',

jf MP:15,06 TISOLATE AND DRAIN SYSTEM FOR TESTING ~

3 4

n.

n W

G jg'.1 S Shut ISI-870A, IP-14A RWST suction MOV.

e m

1 6

\\

M L

$5.2' AVerify shut 1S1-871 A, Train "A" RHR/ Spray X-conn MOV. -

.. s:

a,

..p J/'

r'

-d red ' tag:

T13 '. ; Position an.

r m,

y ; b, ' % :.

c M

R TNOTE:L J Tqging shut 1S1-868A ands) ins "Ct" r' Qasure" Wp

,vf1 psymiremesas.

m

~

p,,;,;,,

T-t im

'. I SI-868A, "A" train' spray CIV.........................................

Shut.

s 1 B52-14 A, IP-14A bkr on IB-03...................................

Rack out 31B52-19A,' 1P-14B bkr on IB-04 ;.....................................

Rack out

[

  • 1 A52-59,1 P-15 A bkr on 1 A-051......................................

Rack out s

* ! A52-85,' 1 P-15B bkr on' 1 A-06.i....................................

Rack out 31B52-323J,' ISI-870A bkr on 18-32..................................

Open q.

l 1B52-323M,;l SI-871 A bkr on 1B-32................................

Open ISI-870A,'IP-14A RWST suction MOV handwheel..........

Shut c.i

'i U

L 1 SI-871 A, lP-14A/RHR x-conn MOV handwheel.............

Shut T,

+

l ISI-874A, NeOH supply to' eductor........................

Shut y

a n

1 SI-864D, IP-14A 3/4" recirc...........................................

. Shut i

T 1 SI-873 A,11P-14A 2" recire..............................................

Shut

~

y e..

  • One SI pump breaker may be racked in with the respective pump control -

+g

. R switch in " Pull.out," if required for reduced _ inventory operation.

.N v

m f*

.,-Q y u

{:' ?..

3 4

[~

3

.g g

m.

.v

.?

M - ys - K,

' 2 (-' '

s g > y%.o w%

< yg.i t'.

~ Page 2 of 9 '

CONTINUOUS USE -

og y

e..

- ikW r?(.

..3

,2 pg.

lu 3

l 1

g

~...

NUCLEAR POWER CUSINESS UNIT ORT 59 -

. OPERATIONS REFUELING TESTS MINOR Revision 17

-TRAIN A SPRAY SYSTEM CIV LEAKAGE TEST

' January 31,1997.

UNIT 1 e

Date RECORD DSS-rnoCsDunsvaarmDcunaswr ANDC)mCKEDFCETDe0RARYCHANGs3 FFED caras maounizD. uss rar.coasi Aw wr i.24 AND DO EZI COMPLETE DG3 BLOCK BY:

DATE:

).0 PURPOSE To perform a 10 CFR 50 Appendix J Type C leakage test for penetration P-54, valves ISI-862A,862G,864A, and 868A.

1 2,0.

REFERENfES IR 96-006, NRC Inspection Report, NRC Commitment for Operations procedure PMT/QC l

reviews.

3.0 PRECAUTIONS AND LIMITATIONS l

t 3.1 -

Locate the Volumetrics tester in an area which will limit personal exposure.

\\

3.2 Do not allow liquids to enter the Volumetrics tester or damage may occur.

{

3.3 All liquids must be drained from piping subsystem prior to m*+=eMag the test rig.

l t

3.4 During the test, the SI test line is removed from service. The SI pump control switches must be in pullout position, but one SI pump may be operable for reduced inventory operation or boration flow path. With the associated SI pump mini-recirc shut, a pump l

discharge flow path must be established prior to manually starting the pump.

l INITIALS 4.0 INITIAL CONDITIONS i

i 4.1

' The RCS is in cold or refueling shutdown.

8 j

4.2 No testing requiring the use of the test recirc line via ISI-897A&B will be il cohd during the duration of this test.

_l d

8

'i 9702t80359 970210 Page1of9 CONTINUOUS USE PDR ADOCK 05000301 p

PDR a.

NUCLEAR POWER BUSINESS UNIT ORT 59 OPERATIONS REFUELING TESTS MINOR Revision 17 TRAIN A SPRAY SYSTEM CIV LEAKAGE TEST January 31,1997 UNIT I INITIALS 4.3 A Volumetrics test rig is available outside containment.

4.4 Permission to Perform Test The conditions required by this test are consistent with required plant conditions including equipment operability. Permission is granted to perform this test.

DSS Time Date 5.0 ISOLATE AND PRAIN SYSTEM FOR TESTING 5.1 Shut ISI-870A, IP-14A RWST suction MOV.

5.2 Verify shut ISI-871 A, Train "A" RHR/ Spray X-conn MOV.

l 5.3 Position and red tag:

NOTE:

Tagging shut ISI-868A satisfies " Containment Oosure" requirements.

Position 1SI-868A, "A" train spray CIV.....

Shut IB52-14A, IP-14A bkr on IB-03....

Rack out IB52-19A, IP-14B bkr on IB-04.

Rack out

  • l A52-59, IP-ISA bkr on 1 A-05...

Rack out

'l A52-85, IP-15B bkr on I A-06..

Rack out 1B52-323J,1SI-870A bkr on 1B-32...........................

Open 1B52-323M,1 SI-871 A bkr on 1B-32.....................

Open 1SI-870A, IP-14A RWST suction MOV handwheel..........

Shut ISI-871 A, IP-14 A/RHR x-conn MOV handwheel..........

Shut 1SI-874A, NaOH supply to eductor..............................

Shut 1 SI-864D,1P-14A 3/4" recire.................................

Shut 1 SI-873A, IP-14A 2" recire...........................

Shut

'~~~

  • One SI pump breaker may be racked in with the respective pump control switch in " Pull-out," if required for reduced inventory operation.

O Page 2 of 9 CONTINUOUS USE

NUCLEAR POWER BUSINESS UNIT -

ORT 59 OPERATIONS REFUELING TESTS MINOR Revision 17 TRAIN A SPRAY SYSTEM CIV LEAKAGE TEST January 31,1997 t

f]

UNIT 1

.b INITIALS J

5.4 Shut the following valves:

ISI-862C, IFT-962 sensing line isolation 1SI-862D, IFT-962 sensing line isolation ISI-864B, IP-14B test line isolation 1SI-864C,1P-14B 3/4" recire 1SI-873B, IP-14B 2" recire ISI-879A, containment SI test line l

4 ISI-897B, test line AOV aCAUTIONa IF AN SI PUMP BREAKER IS RACKED IN, THE CONTROL ROOM OPERATOR SHALL BE INFORMED WHEN THE ASSOCIATED IP-ISA OR B MINI-RECIRC IS SHUT.

1 ISI-876A, IP-15A mmi-rectro j

1SI-876B, IP-ISB mun-rectre 5.5 Attach drain hoses from ISI-883, ISI-D24, and ISI-D31 to a floor drain f

O 5.6 Open the following valves to drain system:

ISI-860A, IP-14A discharge MOV ISI-860B, IP-14A discharge MOV 151-884, test line manual isolation I

151-883, test line sample / drain ISI-864A, IP-14A test line isolation i

'ISI-D11, IP-14A casing drain ISI-D24, IP-14A discharge check valve bonnet drain ISI-D31, high flow recirc ori6ce drain 1 SI-862G, high flow recire manual isolation 2

]

ISI-869A, Train "A" air test connivent 5.7 Remove 1/2" pipe plug from the 2" pipe tee in the eductor line above the

~~ ~

eductor to facilitate draining at 1SI-D11 and 1SI-D24.

O V

t Page 3 of 9 CONTINUOUS USE, e

4

NUCLEAR POWER BUSINESS UNIT ORT 59 OPERATIONS REFUELING TESTS MINOR Revision 17 TRAIN A SPRAY SYSTEM CIV LEAKAGE TEST January 31,1997 UNIT 1 INITIALS NOTE:

Ifpost-maintenance or operability testing ofISP862A, 862G, or 864A is not required, then N/A allofSection 6.0.

6.0 SEAT LEAK. AGE TEST OF 1SI-862A. 862G AND 864A 6.1 When drainage ceases at 1SI-D31, then shut ISI-862G and ISI-D31.

6.2 Open 1SI-V21 as a vent path for ISI-862G.

6.3 When drainage ceases at ISI-D11, then reinstall the 1/2" pipe plug at the eductor 2" suction line tee and shut ISI-D11.

6.4 Attach SA to the test connection for IPI-933A and pressurize slightly

(<10 psig) to blow water downstream of ISI-860A&B out the ISI-D24 drain connection.

6.5 When drainage ceases at ISI-D24, remove the SA connection from IPI-933A. Shut and cap the IPI-933A test connection.

6.6 Attach the Volumetrics test rig to ISI-869A.

6.7 Shut ISI-D24.

6.8 Verify valve alignment per Dwg. B-IVLT-54P.

Pressurize the system to 65 i f psig, then crack open ISI-D24 and verify 6.9 no water on the seat ofISI-862A. Reshut ISI-D24 and cap.

6.10 Test the test volume per 01-58 and record data on the data sheet.

6.11 If total system leakage is >l 500 secm, then quantify individual valve N

leakage as follows:

6.11.1 To measure ISI-862A leakage, connect an Omega rotameter at ISI-D11 and record flow.

seem 6.11.2 To measure ISI-862G leakage, connect an Omega rotameter at ISI-V21 and record flow.

scem Page 4 of 9 CONTINUOUS USE

_. _ _ ~. _ _

NUCLEAR POWER BUSINESS UNIT ORT 59 OPERATIONS REFUELING TESTS MINOR Revision 17 TRAIN A SPRAY SYSTEM CIV LEAKAGE TEST.

January 31,1997

-(Q

' UNIT 1 V

INTHALS

]

\\

'6.11.3

. To measure 1SI-864A leakage, connect an Omega rotameter at j

ISI-883 and record flow.

+

1 seem 1

5 t

~ 6.11.4 To quantify 1SI-868A leakage, total the previous three i

j.

rotameter readings and subtract from the Volumetrics rig value.

j 1'

l Record scem i

6.12 When the test is complete, shut 1SI-869A and detach the test rig.

i s

i 6.13-Open ISI-869A and vent the test volume to atmospheric pressure.

4 r

o 6.14 Perform post-test valve alignment:

f j

Position i

1 SI-879B, containment SI test line............................................

Shut f

1 SI-884, test line mammi isolation...........................................

Shut i

j(

l SI-883, test line sample / drain.................................................

Shut i

iSI-D11,1P-14A casing drain.................

Shut i

1SI-V21, high flow recirc line vent....................................

Shut r

p 1SI-869A, header air test connection.............

Shut 1SI-862C,1FT-%2 sensing line..........

Open 1 SI-862D, IFT-962 sensing line...,....................

Open 1SI-860A,1P-14A discharge MOV...............................

Shut l

I SI 860B, IP-14A discharge MOV..........................................

Shut 1 SI-864C, 1 P-14B 3/4" recirc..................................................

LO 1 SI-876A, IP-15 A mini-recirc..................................................

LO t

[

l SI-876B, IP-1 SB mini-recire.................................................

LO

[:

1 SI-897B, test line AOV........................................................... Gag Open

,I j

1 SI-879A, containment SI test line...........................................

Open k

t i

E r

(

a I

S Page 5 of 9 CONTINUOUS USE l

4

NUCLEAR POWER BUSINESS UNIT ORT 59 OPERATIONS REFUELINO TESTS MINOR Revision 17 TRAIN A SPRAY SYSTIIM CIV LEAKAGE TEST January 31,1997 UNIT 1 INITIALS NOTE:

Ifpost-maintenance or operability testing ofISI-868A is not required, then N/A allofSection 7.0.

7.0 SEAT LEAKAGE TEST OF 1SI-868A 7.1 Verify ISI-868A is tagged shut for Containment Closure."

NOTE:

Attaching to and opening ISI-868C does not violate " Containment Closure. "

7.2 Attach the Volumetrics test rig to the stem leak-off test connection of ISI-868A.

7.3 Open ISI-869A as a veut path.

Pressurize to 65 i f psig.

7.4 7.5 Open ISI-E68C and test per 01-58. Record test data on the data sheet.

i 7.6 When the test is complete, deprer. surae and disconnect the test rig.

{

7.7 Shut ISI-868C and red lock.

/

7.8 Cap or plug the ISI-868A stem leak-off test connection.

/

7.9 Shut and cap ISI-869A.

8.0 RESTORATION OF SPRAY SYSTEM. TRAIN "A" NOTE:

CL-7B willbeperformed as afinal verification ofsystem alignment for criticality.

8.1 Clear the ORT 59 red tag series and align the tagged components per the DSS.

8.2 Lock open ISI-868A. Lock No.

O 4

Page 6 of 9 CONTINUOUS USE G

NUCLEAR POWER BUSINESS UNIT ORT 59 OPERATIONS REFUELING TESTS MINOR Revision 17 TRAIN A SPRAY SYSTEM CIV LEAKAGE TEST January 31,1997 l

"p UNIT 1 INITIALS 8.3 Fill and vent IP-14A. IfIP-14A cannot be filled and vented at this time, i

then leave a turnover note with the DSS and DOS to fill and vent prior to operation of IP-14A.

f.MI 8.4

. Leak check the 1/2" pipe plug at the 2" eductor suction line tee after the system is filled.

9.0 EVALUATION TO BE COMPLETED BY OPERATIONS MANAGER OR HIS REPRESENTATIVE.

9.1 Individual leakages compared to allowable value and included in tabulation

]

of totalleak rate.

9.2 Results acceptable, no limits exceeded.

Yes No

,O

  • (If no, give details in the remarks section and notify the Regulatory Services manager to determine reportability.)

9.3 Data analyzed By Date Remarks:

.j'

_~

~

=.

l 4

i

. O Page 7 of 9 CONTINUOUS USE 9

e

- NUCLEAR POWER BUSINESS UNIT ORT 59 OPERATIONS REFUELING TESTS MINOR Revision 17 TRAIN A SPRAY SYSTEM CIV LEAKAGE TEST January 31,1997 UNIT 1 LEAK TEST DATA SHEET 1SI-862A. 862G AND 864A Ilmc Pressure (osig)

Leak Rate (sccm)

Test Instrument ID Range: Lo, Med, Hi(circle one)

ISI-868A O

Ilmc Pressure (osie)

Leak Rate (secm)

Test Instrument ID Range: Lo, Med, Hi(circle one)

La Comments:

I Test Operator Date Page 8 of 9

, CONTINUOUS USE

NUCLEARPOWER BUSINESS UNIT ORT 59 OPERATIONS REFUELING TESTS MINOR Revision 17 TRAIN A SPRAY SYSTEM CIV LEAKAGE TEST January 31,1997 O

UNIT I N

n V8L9 C D

e a 5 84

- ass 4 m

S XM3 I

--4

-l-oncu ymn e

nun

"~~

i

-O-Mi pA H

i n

f Kasz

/

f f

NN 7

m

,u

-,_pa o

AgT X.

Q ano w ou r

TO TEST ISI-862A. 862G AND 864A SHUT INITIALS ISI-868A ISI-862C ISI-862D ISI-862G ISI-864A ISI-D24 OPEN.

ISI-V21 ISI-860A ISI-860B

~

ISI-D11 ISI-884 1SI-883 '

1SI-869A

,]

> -Q

~

DWG. B-IVLT-54P Page 9 of 9 CONTINUOUS USE 9