NUCLEAR POWER BUSINESS UNIT 01 86 j

OPERATING INSTRUCTIONS MINOR Revision 6 8

INSTRUMENT AIR K2A/K2B AND SERVICE AIR January 25,1997 K3A/K3B COMPRESSOR RUN-IN OPERATING INSTRUCTIONS RECORD PROCEDURE VERIFIED CURRENT AND CHECKED FOR TEAFORARY CHANGES IF FIELD COPIES REQUIRED. U5E PBF.0026:1AW NP 12 4 AND DO E CONF 1.ETE TH!5 BLOCK BY:

DATE 1.0 PURPOSE The purpose of this instruction is to:

1.1 Provide guidance for compressor run-in following ring replacement.

1.2 Provide a means for obtaining after run-in data to be placed in machinery history.

1.3 The procedure for K2A and K2B (Section 5.0) is derived from Joy technical manual, TFI 5.11.2, Control No. 01193, Section 4, Page 6.

1.4 The procedure for K3 A (Section 7.0) is derived from Joy technical manual, TFI 5.11.1, Control No. 000303, Section 4, Page 7.

1.5 The procedure for K3B (Section 7.0) is derived from Joy technical manual, TFI 5.11.1, Control No. 000406, Section 4, Page 7.

2.0 REFERENCES

IR 96-006, NPC Inspection Report; NRC Commitment for Operations procedures PMT/QC reviews.

3.0 PRECAUTIONS AND LIMITATIONS 3.1 While running in a compressor, prescure is adjusted by throttling the 1%" aftercooler air side vent.

3.2 Manual operation of the Total Closure valves and installed jumpers that provide manual load and unload control defeat the agastat for compressor loading delay. Ensure the compressor is started unloaded and remains unloaded for the first seven seconds to allow speed and oil pressure to build.

3.3 It is good practice to secure a compressor when it is unloaded because of the reduced load on breaker contacts.

9702180318 970210 Page1of11 INFORMATIO.V USE PDR ADOCK 050003011 P

PDR

NUCLEAR POWER BUSINESS UNIT OI86 OPERATING INSTRUCTIONS MINOR Resision 6 INSTRUMENT AIR K2A/K2B AND SERVICE AIR January 25,1997 K3A/K3B COMPRESSOR RUN-IN OPERATING INSTRUCTIONS 3.4 When shifting a compressor's mode of operation, pause approximately five seconds prior to selecting the alternate mode. This allows the compressor Total Closure Butterfly valves and/or unloader valves time to reposition, interstage pressure and the motor EMF to decay prior to restart of the motor.

3.5 If at any time there is evidence of ring seizure, the compressor should be run at a lower pressure and consequently a lower temperature level until free. Then proceed to a higher pressure level.

3.6 The only overpressure protection available for the compressor during operation with the compressor discharge valve shut is the compressor relief valve.

4.0 INITIAL CONDITIONS FOR INSTRUMENT AIR COMPRESSOR RUN-IN One instrument air compressor in operation supplying instrument air loads with the other compressor isolated following maintenance and requiring a run-in.

5.0 PROCEDURE FOR K2A AND K2B '

5.1 Check for proper oillevel.

5.2 Check shut the discharge valve for the compressor to be nm in.

(IA-1 for K2A or IA-2 for K2B).

5.3 Open the 1%" aftercooler air side vent (IA-228 for K2A or I A-231 for K2B).

NOTE:

The air receiverpressure indicator on the compressor gauge board will be isolated when the total closure valve operating air supply isolation valve is shut.

5.4 Shut the total closure valve operating air supply isolation valve for the compressor to be run-in (IA-206 for K2A or IA-215 for K2B). Uncap and open the total closure valve operating air supply line vents (IA-218 and IA-219 for K2A or IA-220 and IA-221 for K2B).

NOTE:

The total closure valve may now be manually operated via wrenchflats machined on the actuator shaft extension protrudingfrom the side of the actuator.

NOTE:

Normaloilpressure is30-40psig.

5.5 Unload the compressor by manually fully closing total closure valve. Start the compressor and run unloaded for a minimum of 30 minutes.

i Page 2 of11 INFORMATION USE

NUCLEAR POWER BUSINESS UNIT OI86 OPERATING INSTRUCTIONS MINOR Revision 6 INSTRUMENT AIR K2A/K2B AND SERVICE AIR January 25,1997

. ff:

K3A/K3B COMPRESSOR RUN-IN OPERATING INSTRUCTIONS 5.6 With the aftercooler air side vent valve full open, load the compressor by manually fully opening the total closure valve. Adjust the aRercooler air side vent valve for a compressor discharge pressure of 30 psig. Run for one hour.

5.7 Adjust the anercocler air side vent valve for a compressor discharge pressure of 50 psig.

Run for one hour.

NOTE:

Ring seiwre tendency will be checked by noting abnormal coastdown behavior such as abnormalknocking noise, vibration, or rate ofspeed decrease. Normal coastdown time is about 5 to 6 seconds. Ring seimre may be noted by operation temperatures in excess ofnormal values.

5.8 Unload the compressor by manually fully shutting the total closure valve. Shut down the compressor by placing its control switch to off and check for signs of ring seizure tendency (see Precautions and Limitations 3.5).

5.9 If the pistons are free, restart the compressor. ARer the compressor is up to speed, load the compressor by manually fully opening the total closure valve.

5.10 Compressor run-in should continue according to the following substeps. Run-in should be done at discharge pressure plateaus of 70 psig,80 psig,90 psig and 100 psig.

5.10.1 Adjust the anercooler air side vent valve for the desired discharge pressure-plateau and run the compressor for one hour.

5.10.2 Unload the compressor by manually fully shutting the total closure valve.

Immediately shut down the compressor and check for signs of ring seizure tendency during coastdown (see Precautions and Limitations 3.5).

5.10.3 If the pistons are free, restart the compressor. ARer the compressor is up to speed, load the compressor by manually fully opening the total closure valve.

Repeat Steps 5.10.1, 5.10.2 and 5.10.3 for each of the pressure plateaus in Step 5.10.

5.11 Upon completion of the one hour run at 100 psig, unload the compressor by manually fully shutting the total closure valve. Immediately shut down the compressor and check for signs ofring seizure tendency during coastdown (see Precautions and Limitations 3.5).

Page 3 of 11 INFORMATION USE O

9 4

.4

' NUCLEAR POWER BUSINESS UNIT OI 86 f

OPERATING INSTRUCTIONS MINOR Revision 6 INSTRUMENT AIR K2A/K2B AND SERVICE AIR January 25,1997 K3A/K3B COMPRESSOR RUN-IN OPERATING INSTRUCTIONS 5.12 If the pistons are free, restart the compressor. After the compressor is up to speed, load the compressor by fully opening the total closure valve. Run the compressor for an additional 3 to 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> at a discharge pressure of 100 psig. Ensure compressor operating conditions normal:

5.12.1 Oil pressure 30-40 psig.

4 5.12.2 Inter cooler pressure (loaded) 20-26 psig.

5.12.3 Inter cooler pressure (unloaded) 23-27 "HG Vac" 5.12.4 Discharge air temperature <325 F 5.12.5 After cooler air outlet temperature <90*F 5.12.6 Compressor SW return temperature 95-105 F 5.13 Unload the compressor by manually fully shutting the total closure valve. Immediately 4

shut down the compressor and check for signs of ring seizure tendency during coastdown (see Precautions and Limitations 3.5).

5.14 If pistons are free, compressor run-in is complete. Shut and cap the total closure valve operating air supply line vents (IA-218 and IA-219 for K2A or IA-220 and IA-221 for' K2B). Open the total closure valve operating air supply isolation valve (IA-206 for K2A or IA-215 for K2B) and verify that air receiver pressure indicated on the compressor gauge board is normal.

5.15 Shut the 1%" aftercooler air side vent valve.

NOTE:

Make a copy of the attached instrument air conspressor data sheetprior to recording data.

5.16 With the discharge valve still shut on the newly run-in compressor, record data for the on-line compressor on the instrument air compressor data sheet.

5.17 Open the discharge valve for the newly run-in compressor and record data for the on-line compressor to estimate any back leakage through the newly run-in compressor. Load times should not differ by more than 25% between the newly run-in compressor and the on-line compressor.

I rMI 5.,18 Start the newly run-in compressor in constant and observe the compressor for proper operation.

Page 4 of11 INFORMATION USE

NUCLEAR POWER BUSINESS UNIT OI86 OPERATING INSTRUCTIONS MINOR Revision 6 INSTRUMENT AIR K2A/K2B AND SERVICE AIR January 25,1997 K3A/K3B COMPRESSOR RUN-IN OPERATING INSTRUCTIONS i

5.19 If compressor performance is satisfactory as determined by freedom of piston movement during run-in and normal operating conditions as noted in Step 5.12, then secure the previously running compressor by placing it's control switch to off and shutting it's discharge valve.

5.20 Record data for newly run-in compressor.

5.21 Open the compressor discharge valve on the stopped compressor. Record data for newly run-in compressor to determine amount of back leakage through the offline compressor.

5.22 Align compressors as follows to provide for more even run time or as directed by the DSS.

ODD MONTH EVEN MONTH K2A CONSTANT K2A AUTO K2B AUTO K2B CONSTANT 5.23 Attach completed instrument air compressor data sheet to Maintenance work control document.

6.0 INITIAL CONDITIONS FOR SERVICE AIR COMPRESSOR RUN.IN One service air compressor in operation supplying service air loads with the other compressor isolated following maintenance and requiring a run-in.

7.0 PROCEDURE FOR K3A AND K3B 7.1 Check for proper oillevel.

7.2 Check shut the discharge valve for the compressor to be run-in, (SA-2 for K3A or SA-3 for K3B).

7.3 Open the IM" aftercooler air side vent. (SA-33 for K3A; SA-57 for K3B.)

7.4 Shut the unloader outlet isolation valve (SA-23 for K3A, SA-24 for K3B). Remove the Swagelok cap at the outlet of SA-23 or SA-24 and install P-tubing jumper between this sensing line and IA-39 at PI-3005 on the instrument air compressor gaugeboard (refer to Figure 1).

NOTE:

Normaloilpress is30-40psig.

7.5 Unload the compressor by closing vent valve IA-40 and opening IA-39 (see Precaution 3.2). S, tart the compressor and mn unloaded for a minimum of 30 minutes.

Page 5 of11 INFORMATION USE 1

' NUCLEAR POWER BUSINESS UNIT 0186 OPERATING INSTRUCTIONS MINOR Revision 6 INSTRUMENT AIR K2A/K2B AND SERVICE AIR January 25,1997 K3A/K3B COMPRESSOR RUN IN OPERATING INSTRUCTIONS 7.6 With the aftercooler air side vent valve full open, load the compressor by shutting I A-39 and opening vent valve IA-40. Adjust the aftercooler air side vent valve for a compressor discharge pressure of 30 psig. Run for one hour.

7.7 Adjust the aftercooler air side vent valve for a compressor discharge pressure of 50 psig and run for one hour.

NOTE:

Ring sei:.ure tendency will be checked by noting abnormal coastdown behavior such as abnormal knocking noise, vibration, or rate ofspeed decrease. Normal coastdown time:

For K.fA = 17 to 21 sec For K1B = 7 to 11 sec Ring sei:,ure may be noted by operating temperature in excess of normal value 7.8 Unload the compressor by shutting vent valve IA-40 and opening IA-39. Immediately shut down the compressor. Check for ring seizure tendency during coastdown (See Precautions and Limitations 3.5).

7.9 If the piston is free, restart the compressor. After the compressor is up to speed, load the compressor by shutting IA-39 and opening vent valve IA-40.

7.10 Compressor run-in should continue according to the following steps It should be done at discharge pressure plateaus of 70 psig,80 psig,90 psig and 100 psig.

7.10.1 Adjust the aftercooler air side vent valve for the desired discharge pressure plateau and run the compressor for OBE hour.

7.10.2 Unload the compressor by shutting vent valve IA-40 and opening IA-39.

Immediately Aut down the compressor. Check for ring seizure tendency during coastdown (See Precautions and Limitations 3.5).

i 7.10.3 If the piston is free, restart the compressor. After the compressor is up to speed, load the compressor by shutting IA-39 and opening vent valve IA-40.

Repeat Steps 7.10.1,7.10.2 and 7.10.3 for each of the pressure plateaus in Step 7.10.

7.11 Upon completion of the one hour run at 100 psig, unload the compressor by shutting vent valve IA-40 and opening IA-39. Immediately shut down the compressdr/ Check for ring j

seizure tendency during coastdown (See Precautions and Limitations 3.5).

Page 6 of 11 INFORMATION USE O

O O

NUCLEAR POWER BUSINESS UNIT 01 86 OPERATING INSTRUCTIONS MINOR Revision 6 J

INSTRUMENT AIR K2A/K2B AND SERVICE AIR January 25,1997 K3 A/K3B COMPRESSOR RUN-IN OPERATING INSTRUCTIONS l

fMT 7.12 If the piston is free, restart the compressor. After the compressor is up to speed, load the compressor by shutting IA-39 and opening vent valve IA-40. Run the compressor for an additional 3 to 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> at a discharge pressure of 100 psig. Ensure compressor operating conditions normal:

7.12.1 Oil pressure 30-40 psig.

7.12.2 Inter cooler pressure (loaded) 20-26 psig 7.12.3 Compressor SW return temperature <105 F 7.13 Unicad the compressor by shutting vent valve IA-40 and opening IA-39. Immediately shut down the compressor. Check for ring seizure tendency during coastdown (See Precautions and Limitations 3.5).

7.14 If compressor performance is satisfactory as determined by freedom of piston movement during mn-in and normal conditions per Step 7.12, shut IA-39 and open IA-40. Remove the P-tubing jumper and install Swagelok caps at the compressor and IA-39. Shut IA-40.

Open the unloader outlet isolation valve SA-23 for K3 A or SA-24 for K3B. Shut the aftercooler air side vent valve.

NOTE:

Attempt to perform thefollowing steps during a period oflow S.A. air usage NOTE:

Make a copy of the service air compressor data sheet prior to recording data.

7.15 Establish a S. A. header bleed in the air compressor room at the N. E. Hose Station SA-98 (1 turn open).

l l

7.16 With the discharge valve still shut on the newly run-in compressor record data for the on-line compressor on the service air compressor data sheet.

7.17 Open the discharge valve for the newly mn-in compressor and record data for the online compressor to estimate any back leakage through the newly run-in compressor.

7.18 Start the newly run-in compressor.

7.19 Secure the previously running compressor by placing its control switch to off and shutting its discharge valve.

7.20 Record data for newly run-in compressor.

7.21 Open the compressor discharge valve on the stopped compressor and record data for the newly run-in compressor to estimate any back leakage through the stopped compressor.

Page 7 of 11 INFORMATION USE e

NUCLEAR POWER BUSINESS UNIT 0186 OPERATING INSTRUCTIONS MINOR Revision 6 INSTRUMENT AIR K2A/K2B AND SERVICE AIR January 25,1997 K3A/K3B COMPRESSOR RUN-IN OPERATING INSTRUCTIONS 7.22 Secure service air header bleed by shutting SA-98.

7.23 Align compressors as follows to provide for more even run time or as directed by the DSS.

ODD MONTH EVEN MONTH

't K3A CONSTANT K3A AUTO K3B AUTO K3B CONSTANT 7.24 Attach completed service air compressor data sheet to Maintenance work control document.

4 i

Page 8 of 11 INFORMATION USE

' NUCLEAR POWER BUSINESS UNIT 01 86 OPERATING INSTRUCTIONS MINOR Revision 6 3

INSTRUMENT AIR K2A/K2B AND SERVICE AIR January 25,1997 K3A/K3B COMPRESSOR RUN-IN OPERATING INSTRUCTIONS FIGURE I Second Stage Unicaders First Stage Unioaders 5A'23 CONTROL (SA-24)

PANEL K4A

'M (K48)

P-TUBING IA 39 IA 4 IA 38 V

1A-37 I

(

)

i i

Page 9 of11 INFORMATION USE 9

NUCLEAR POWER BUSINESS UNIT 01 86 OPERATING INSTRUCTIONS MINOR Revision 6 8

INSTRUMENT AIR K2A/K2B AND SERVICE AIR January 25,1997 C.

K3A/K3B COMPRESSOR RUN-IN OPERATING i

INSTRUCTIONS

)

INSTRUMENT AIR COMPRESSOR MAINTENANCE HISTORY DATA SHEET FOR BOTH INSTRIJMENT AIR COMPRESSORS FOLLOWING J

OVERHAUL AND BREAK-IN OF EITHER AIR COMPRESSOR Sten-5.16 Running Compressor K2 Time Loaded Min Sec Time Unloaded Min Sec Header Air Flow (FI-3081) @ 105 psig on PI-3005 scfm Header Air Flow (FI-3082) @ 105 psig on PI-6320 scfm Step-5.17 Running Compressor K2 Time Loaded Min Sec-Time Unloaded Min Sec Header Air Flow (FI-3081) @ 105 psig on PI-3005 scfm Header Air Flow (FI-3082) @ 105 psig on PI-6320 scfm Sten-5.20 Running Compressor K2 Time Loaded Min Sec Time Unloaded Min Sec Header Air Flow (FI-3081) @ 105 psig on PI-3005 scfm Header Air Flow (FI-3082) @ 105 psig on PI-6320 scfm Sten-5.21 Running Compressor K2 Time Loaded Min Sec Time Unloaded Min Sec Header Air Flow (FI-3081) @ 105 psig on PI-3005 scfm _

Header Air Flow (FI-3082) @ 105 psig on PI-6320 scfm Initials Date' Work Control Document No.

Time Maintenance Review By Disposition: Work Control Document Page 'u of 11 INFORMATION USE j

NUCLEAR POWER BUSINESS UNIT 0186 OPERATING INSTRUCTIONS MINOR Revision 6 INSTRUMENT AIR K2A/K2B AND SERVICE AIR January 25,1997 K3 A/K3B COMPRESSOR RUN-IN OPERATING INSTRUCTIONS SERVICE AIR COMPRESSOR MAINTENANCE HISTORY DATA SHEEI

~

FOR BOTH SERVICE INSTRUMENT AIR COMPRESSORS FOLLOWING OVERHAUL AND BREAK-IN OF EITHER AIR COMPRESSOR Step-7.16 Running Compressor K3 Time Loaded Min Sec Time Unloaded Min Sec Sicp-7.17 1

Running Compressor K3 Time Loaded Min Sec Time Unloaded Min Sec j

Step-7.20 Running Compressor K3 Time Loaded Min Sec Time Unloaded Min Sec Step-7,21 Running Compressor K3 Time Loaded Min Sec Time Unloaded

. Min Sec j

Initials Date Time Work Control Document No.

Maintenance Review By Disposition: Work Control Document Page11 of1I INFORMATION USE O