i BAW-1638 May 1981 l

l l

ANALYSIS OF CAPSULE V Virginia Electric & Power Company North Anna Unit No. 1

- Reactor Vessel Materials Surveillance Program -

l l

l l

l Babcock & Wilcox

(

B408210393 8408;6

[

PDR ADOCK 05000339 l

PDR L

~

BAW-1638 May 1981 ANALYSIS OF CAPSULE V Virginia Electric & Power Company North Anna Unit No. 1

- Reactor Vessel Materials Surveillance Program --

by A. L. Lowe, Jr., PE W. A. Pavinich J. K. Schmotzer C. L. Whitmarsh B&W Contract No. 582-7116 BABCOCK & WILCOX Nuclear Power Group Nuclear Power Generation Division P. O. Box 1260 Lynchburg, Virginia 24505 Babcock & \\Milcox j

i CONTENTS Page 1.

INTRODUCTION.

1-1 2.

POST-IRRADIATION TESTING.

2-1 2.1.

Visual Examination and Inventory.

2-1 2.2.

Thermal Monitors.

2-1 2-2 2.3.

Tension Testing 2-2 2.4.

CVN Impact Testing.

3.

DISCUSSION OF CAPSULE RESULTS 3-1 3-1 3.1.

Tensile Properties.

3-1 3.2.

Charpy Impact Properties.

4.

NEUTRON DOSIMETRY 4-1 4.1.

Introduction.

4-1

)

4.2.

Analytical Approach 4-2 4-3 4.3.

Results 4-5 4.4.

Summary of Results.

i 5-1 5.

SUMMARY

OF RESULTS.

l 6-1 6.

CERTIFICATION 7.

REFERENCES.

7-1 APPENDIXES A.

Surveillance Material Properties.

A-1 j

B.

Preirradiation Tensile Data B-1 C.

Preirradiation Charpy Impact Data C-1 l

D.

Threshold Detector Information.

D-1 E.

LRC-TP-78 E-1 L

F.

LRC-TP-80 F-1 l

i

- ii -

Babcock & WilCOX l

L

L List of Tables f

L Page Table 2-1.

Tensile Properties of North Anna Unit 1, Capsule V, Base 18 and Weld Metals Irradiated to 2.49 x 10 nyt 2-3 2-2.

Charpy Impact Data for North Anna Unit 1. Capsule V, 18 Base Metal Irradiated to 2.49 x 10 nyt 2-3 2-3.

Charpy Impact Data for North Anna Unit 1, Capsu?e V, Weld Metal Irradiated to 2.49 x 10 s nyt 2-4 2

3-1.

Comparison of Tensile Test Results.

3-4 3-2.

Observed Vs Predicted Changes in Irradiated Charpy Impact Properties 3-5 4-1.

Surveillance Capsule Detectors.

4-5 4-2.

Dosimeter Activations 4-6 4-3.

Neutron Flux and Fluence.

4-6 4-4.

Predicted Lifetime Fluence to Pressure Vessel for E > 1 Mev 4-7 A-1.

Heat Treatment History.........

A-2 A-2.

Quantitative Chemical Analysis, wt %.......

A-3 B-1.

Preirradiation Tensile Properties of Forging Material (Base Metal) and Weld Metal B-2 C-1.

Preirradiation Charpy V-Notch Impact Data for North Anna Unit 1 Reactor Pressure Vessel Lower Shell Forging 03, Heat No. 990400/292332, Axial Orientation.

C-2 C-2.

Preirradiation Charpy V-Notch Impact Data for North Anna Unit 1 Reactor Pressure Vessel Lower Shell Forging 03, Heat No. 990400/292332, Tangential Orientation C-3 C-3.

Preirradiation Charpy V-Notch Impact Data for North Anna Unit 1 Reactor Pressure Vessel Core Region Weld Heat-Affected Zone Material C-4 C-4.

Preirradiation Charpy V-Notch Impact Data for North Anna Unit 1 Reactor Pressure Vessel Core Region Weld Metal C-5 D-1.

North Anna Neutron Dosimeters - Capsule V Irradiation Ended September 25, 1979, 24:00 D-2 D-2.

Dosimeter Activation Cross Sections D-4 List of Figures Figure 2-1.

Charpy Impact Data From Irradiated Base Metal, Axial Orientation.

2-5 2-2.

Charpy Impact Data From Irradiated Base Metal, 2-6 Tangential Orientation 2-7 2-3.

Charpy Impact Data From Irradiated Weld Metal.

2-4.

Charpy Impact Data From Irradiated Base Metal, Heat-Affected-Zone 2-8 3-1.

Irradiated Vs Unirradiated Charpy Impact Properties of Base Metal, Axial Orientation 3-6 3-2.

Irradiated Vs Unirradiated Charpy Impact Properties of Base Metal, Tangential Orientation.

3-7

- 111 -

Babcock & )Milcox

)

1 Figures (Cont'd)

Figure Page 3-3.

Irradiated Vs Unirradiated Charpy Impact Properties of Weld Metal 3-8 3-4.

Irradiated Vs Unirradiated Charpy Impact Properties of Base Metal, Heat-Affected-Zone.

3-9 4-1.

Relative Fast Flux at Specimen and Dosimeter Locations in Surveillance Capsule V.

4-7 4-2.

Axial Shape of Fast Flux at the Pressure Vessel Surface.

4-8 4-3.

Calculated Maximum End-of-Life Fluence as a Function of Penetration in the Pressure Vessel.

4-9 4-4.

Azimuthal Variation of Fast Flux at the Pressure Vessel Surface 4-10 C-1.

Charpy Impact Data From Unirradiated Base Metal, Axial Orientation.

C-6 C-2.

Charpy Impact Data From Unitradiated Base Metal, Tangential Orientation C-7 C-3.

Charpy Impact Data From Unirradiated Weld Metal....

C-8 C-4.

Charpy Lmpact From Unirradiated Base Metal, Heat-Affected-Zone C-9 l

)

)

)

- iv -

Babcock & WilCOX l

i

l 1

1.

INTRODUCTION This report describes the results of the examination of the first capsule from the Virginia Electric Power Company's North Anna Unit No. I reactor vessel sur-l veillance program. Capsule "V" is a part of the continuing surveillance pro-gram which monitors the effects of neutron irradiation on the reactor pressure vessel materials under actual operating conditions.

The specific objectives of the program are to monitor the effects of neutron irradiation on the tensile and impact properties of the reactor pressure ves-sel materials under actual operating conditions and to verify the fluence cal-culations to which the materials are exposed. The surveillance program for the North Anna Unit No. I reactor pressure vessel materials was designed and recommcnded by Westingh' use Electric Company. The surveillance program and o

the pre-irradiation mechanical properties of the reactor vessel materials are described in WCAP-8771.1 The surveillance program was planned to cover the 40-year design life of the reactor pressure vessel and is based on ASTM E-185-i 73, Annex A1, " Standard Recommended Practice for Surveillance Tests for Nu-clear Reactor Vessels."

4 This report summarizes the testing and the post-irradiation data obtained from the testing and analysis of the tensile and Charpy specimens as well as the evaluation of the thermal monitors.

In addition, the dosimeters were measured and the fluence values for both the capsule materials and the reactor vessel were calculated. The wedge-opening-loading (WOL) specimens were not tested at this time and were placed in storage to be tested later if the need for the data developa.

1-1 Babcock & )Milcox i

i 1

2.

POST-lRRADIATION TESTING 2.1.

Visual Examination and Inventory All samples were visually examined for signs of abnormalities. The contents of the capsule were inventoried and compared with the program characterization report inventory. All of the specimens were covered with a tightly adherent black substance of unknown origin. This condition may have been caused by residue from cleaning or from the capsule assembly. There was no evidence of rust or of the penetration of reactor coolant into the capsule.

The inventory of specimens was consistent with Figure 2-6 of the Westinghouse l

pre-irradiation report with th'e exception of a discrepancy involving Charpy base metal specimens. This figure indicates 12 tangential (VT series) and 8 axial (VL series) specimens, while Table 2-1 of the same report shows 8 tan-gential and 12 axial specimens. The capsule actually contained 12 specimens marked "VT" and 8 marked "VL."

For the post-irradiation data (Figures 2-2 and 2-3) to correlate with the pre-irradiation data (see Figures C-1 and C-2), it is necessary to assume that Table 2-1 was correct and that the VT specimens were axial in orientation and the VL specimens were transverse. Test data presented in this report (see Figures 3-1 and 3-2) support this assumption.

All flux wires and thermal monitors were also covered with the black substance mentioned earlier.

As a result, Pyrex-encapsulated thermal monitors could not be visually examined.

2.2.

Thermal Monitors Surveillance capsule V contained a temperature monitor holder block contain-ing two fusible alloys with different melting points. Because of the black substance, the Pyrex-encapsulated thermal monitors could not be visually ex-amined. Consequently, they were radiographed for evaluation.

Neither of the two thermal monitors were melted, although the low temperature monitor had slumped.

From these data it was concluded that the irradiated specimens had 2-1 Babcock & Wilcox

been exposed to a maximum temperature in the range of 579F or less during the reactor vessel operating period. There appeared to be no significant signs of a temperature gradient along the capsule length.

2.3.

Tension Testing All tension tests were conducted in accordance with Technical Procedure LRC-TP-78 (see Appendix E); four specimens were tested. One weld metal and one axial i

base metal specimen were tested at 550F. The other weld metal and axial base metal specimens were tested at room temperature. A constant displacement rate of 0.005 in./ min was imposed on each specimen until fracture. Percent total elongation, percent reduction in cross-sectional area, 0.2% offset yield strength, and ultimate tensile strength were determined in accordance with ASTM E8-69 and A370-73. These data are presented in Table 2-1.

2.4.

CVN Impact Testing All impact tests were conducted in accordance with Technical Procedure LRC-TP-80 (see Appendix F).

The four groups of specimens (axially oriented base metal, transversely oriented base metal, weld metal, and heat-affected zone metal) were tested at temperatures between -40 and 280F. Absorbed energy, test tem-perature, percent shear fracture, and lateral expansion were determined in accordance with ASTM Specifications E23-73 and A370-73. Plots of test tem-perature versus absorbed energy, percent shear, and lateral expansion were prepared for each specimen. These data are presented in Table 2-2 and Fig-ures 2-1 through 2-4.

2-2 Babcock & Wilcox

Table 2-1.

Tensile Properties of North Anna Unit 1, Capsule V, 1

10 " nyt Base and Weld Metals Irradiated to 2.49 x

    • "E "E^ I "'

Test Specimen temp.,

Yield, Ult.,

Uniform Total Red'n of ID No.

F YS UTS UE TE area, %

Base Metal -- Transverse VT-3 76 80.4 99.3 12.0 20.9 54.9 VT-4 548 64.7 95.7 10.0 18.4 47.0 i

Weld Metal VW-4 78 70.8 84.5 13.0 19.3 65.0' VW-3 548 63.6 84.5 11.7 19.0 56.5 1

I Table 2-2.

Charpy Impact Data for North' Anna Unit 1, Capsule V, 18 Base Metal Irradiated to 2.49 x 10 nyt i

Test Shear Specimen temp.,

Abs. energy, Lat. exp.,

fracture, ID No.

F ft-lb 10~3 in.

Base Metal - Axial VT-19 0

12.5 7.0 0

VT-14 40 15.5 11.5 0

VT-16 60 29.0 23.5 14 VT-13 73 39.0 29.0 0

VT-22 100 40.0 32.0 34 VT-15 120 41.0 35.0 42 VT-24 130 51.0 42.0 38 i

VT-18 140 59.0 48.0 98 VT-23 160 60.0 50.0 98 VT-21 195 79.0 66.0 100 VT-20 240 68.5 60.0 100 VT-17 280 77.0 68.0 100 Base Metal - Tangential VL-15 0

7.0 4.0 0

VL-13 40 36.0 26.5 0

VL-9 60 51.0 40.0 5

VL-16 73 32.0 23.0 25 VL-12 100 50.0 39.0 43 2-3 Babcock & Wilcox

Table 2-2.

(Cont'd)

Test Shear Specimen temp.,

Abs. energy, Lat. exp.,

fracture, ID No.

F ft-lb 10-3 in.

VL-10 120 76.5 57.5 56 i

VL-11 196 113.0 78.0 89 VL-14 280 122.0 86.0 100 Base Metal -- Heat-Affected Zone VH-18

-40 66.0 48.0 3

VH-13 0

19.5 8.0 10 VH-16 40 22.5 15.0 60 VH-19 50 16.5 15.0 40 VH-20 60 49.5 30.5 89 VH-23 73 89.0 66.0 62 VH-21 100 81.0 55.0 71 VH-15 120 67.5 42.0 55 VH-24 160 93.0 67.0 99 VH-22 198 105.0 71.0 100 VH-14 240 113.0 70.0 100 VH-17 280 102.0 74.0 100 l

Table 2-3.

Charpy Impact Data for North Anna Unit 1 Capsule V, 18 Weld Metal Irradiated to 2.49 x 10 nyt i

Test Shear 1

Specimen temp.,

Abs. energy, Lat. exp.,

fracture.

l ID No.

F ft-lb 10-s in.

VW-20

-40 4.5 4.5 0

i VW-22 0

25.0 25.5 50 VW-24 40 26.0 29.0 46 VF-17 60 33.0 31.5 28 i

VW-16 73 39.0 31.0 34 VW-23 90 47.0 49.0 89 VW-21 100 60.0 56.0 25 i

VW-14 120 73.0 62.0 72 VW-15 160 62.5 52.5 96 VW-18 198 92.5 73.0 100 VW-13 240 100.0 80.0 100 VW-19 280 87.0 77.0 100 d

2-4 Babcockah VWilcox

_ - ~

Figure 2-1.

Charpy Impact Data From Irradiated Base Metal, Axial Orientation l#

I i

i i

i i

i r

i I

n -

1y2 ____________ ________________-

32s I

I 0

. 08 g

g g

g g

g g

g g

g g

E

!.06-G 2

O.04 e-___

5 E

g.02-

=

I I

I I

I I

I I

I I

O 200 i

g g

g g

g g

g g

DATA SLmutY 180-I, N.A.

me T, (35 mLa) +110F g

Tcv (50 ri c ) +130F Ig TCv (30 FT-La) +45F

(.USE(avs) 75 ft-lb p140 RT,

+70 F

$120-s R4 100-0 EbR-e I

1 e

g_

~

Marenig SA508, C12

_____ __ __~

Oniseraison Axial l

20-FLusact 2.49E18 nyt ltur sto, 990400/292337 I

I I

I I

I I

I 0-00

-40 0

40 80 120 160 200 240 280 320 360 400 Test Tswenarune, F 2-5 Babcock & Wilcox

1 Figure 2-2.

Charpy Impact Data From Irradiated Base Metal, Tangential Orientation I

3 I

I I

I I

I i

l

= 75 -

.Ij. _--________ __________________

n 5 25-I f

  • I I

I I

i i

l I

n g'"

N I

I I

i i

i i

l i

8.u-I t[.04-o 4.02-2 E

a I

I I

I I

I I

I I

I O

I I

I I

I I

I l

DATA SWHWtY 130. T,,

M.A.

T, (35 m ) @F c

_ T,(50 at-a.s) +80F c

gg T, (30 rio) +33F cg (34) 122 ft-lb ple RT,7

+20F O

$120-3:

.I21%-

23m-W k

~ 60-eo-

- f. - -

Maren t at SA508. C12 D~

Fummes 2.49E18 nyt

]

Hut flo. 990400/292332 l

I f

I l

l l

I i

o-m

-e o

e a

120 tu m

2e zoo 320 5m aoo Test Tawenarues, F 2-6 Babcock & Wilcox j

=.

Figure 2-3.

Charpy Impact Data From Irradiated Weld Metal i

100 g

i g

g g

g g

    • 75 -

I y,0 - _ _ _ _. _ _

i 5 25 I

I I

f I

I I

I I

I O

t

. 08 g

g g

g g

g 7

g g

5

.!.06-i t

  • 04 5

Ji g.02-e=

I I

I I

I I

I I

I I

0 I

I i

l I

i I

l DATA ENWlY ISO-T,,,

N.A.

T, (35 mLa) 6 c

N

, T,(50 FT-La) c gg

+52F i, (30 FT-u) g C,-USE (a n) 95 ft-lb g l40 ti,7

+36F O

$120-s R4 100-I 1 80-g k

g_

~

Marsang _ Weld Metal

~

20-FLussics 2.49E18 nyt lleAt No.

N.A.

I I

I I

I I

I O

-00

-40 0

40 80 120 160 200 240 280 320 360 400 Test Issesnarune, F 2-7 Babcock & Wilcox

Figure 2-4.

Charpy Impact Data From Irradiated Base Metal. Heat-Affected-Zone E

I I

I I

i 1

i i

6 I

I e

75 -

I e

e yw -_______

___________________~

5 3 25 I

I I

I I

I I

I I

0

. 08 g

g g

g g

g j

g g

e

!..m 3

e t* 04-

$2 dS.02-li I

I I

I I

I I

I I

I 0

I I

i i

i i

i i

DATA SWMlY 180-T N.A.

oer T 05 mLa) +65r gy

+60r 16@ TCV (50 et-ts)

T, 00 rT-La) 4r g

(.yggtag) 105 ft-lb

.1%- 37 5F t

met C

$120 E

$4 im-3 e

3M-e W

t e. - - - _ - _

Mafeelg Base Metal-IIAZ "

y,g, 20-e Ftugacg 2.49E18 nyt lisar no. 990400/292332 I

I I

I I

I I

0-m

-e o

e so uo, iso zoo 2e m'

n'o m'

ao Test feweenwee, F 2-8 Babcock & Wilcox

3.

DISCUSSION OF CAPSULE RESULTS 3.1.

Tensile Properties Table 3-1 compares irradiated and unirradiated tensile properties. At both ambient and elevated temperatures, the ultimate and yield strength changes in the base metal as a result of irradiation and the corresponding changes in duc-tility are within the range expected. There is some strengthening, as indi-cated by increases in ultimate and yield strength and small decreases in duc-tility properties. Some of the changes observed in the weld metal are so small as to be considered within experimental error. The changes in the properties of the base metal at both room temperature and 550F are greater than those ob-

,-served for the weld metal, indicating a greater sensitivity of the base metal to irradiation damage. These observations are further supported by the fact that the base metal chemistry contains more of those elements that influence radiation sensitivity than are contained in the weld metal.

It should be noted that the relative irradiation sensitivity of the two materials was J

found to be reversed from that normally observed in these data.

However, the number of tensile specimens is appropriately limited, which could affect the statistical significance of the data and thus not reflect the long-term be-l havior of the materials.

In either case, the changes in tensile properties are not significant relative to the analysis of the reactor vessel materials at this period in service life since the Charpy data govern the adjustment to pressure-temperature heatup and cooldown curves.

1.2.

Charpy Impact Properties i

l The behavior of the Charpy V-notch impact data is more significant to the cal-culation of the reactor system's operating limitations. Table 3-2 compares the observed changes in irradiated Charpy impact properties with the predicted changes as shown in Figures 3-1 through 3-4.

i l

3-1 Babcock & Wilcox l

The 50-f t-lb transition temperature shif t for the base metal was slightly less than_the shift that would be predicted according to Regulatory Guide 1.99.

This means that the Regulatory Guide is a conservative predictor for the base metal.- However, the weld metal shift was greater than the shift that would be predicted using Regulatory Guide 1.99.

Similar differences were observed for the 30-ft-lb transition temperature shift except that the magnitude of dif ference between the observed and predicted increased relative to the dif-ferences at the 50-ft-lb level.

The less-than-ideal comparison may be attributed to the spread in the data of the unitradiated material combined with the fact that there was a minimum of data points to establish the irradiated curve. These two variables can con-tribute to increasing the error between the observed and predicted values.

Under these conditions, the comparison indicates that the estimating curves in RG 1.99 for medium-copper materials at medium fluence levels are conserva-tive for predicting the 50-ft-lb transition temperature shifts. The estimat-ing curves for high-copper material at medium fluence levels are not in good agreement with the observed data and do not conservatively predict the expected shift values.

The increase in the 35-mil lateral expansion transition temperature is com-pared with the shift in RT curve data in a manner similar to the comparison NDT made for the 50-ft-lb transition temperature shift. These data show behavior similar to that seen in the comparison of the observed and predicted 50-f t-lb transition data.

The data for the decrease in Charpy USE with irradiation showed good agreement with predicted values for the base metal. However, the weld metal data com-pare well with the predicted value.

In view of the lack of data for low-copper weldments at the low to medium fluence values that were used to develop the estimating curves, the predictive techniques should improve as additional data are obtained from which better prediction curves can be developed.

Results from other capsules indicate that the RT estimating curves have NDT 18 2

greater inaccuracies at the low neutron fluence levels (55 x 10 n/cm ).

This inaccuracy is attributed to the limited data at the low fluence values and to the fact that the majority of the data used to define the curves in RG 1.99 are based on the shift at 30-ft-lb as compared to the current requirement of 50-ft-1b.

For most materials, the shifts measured at 50-ft-1b/35 MLE are 3-2 Babcock 8 Wilcox

expected to be higher than those measured at 30-ft-lb.

The significance of the shifts at 50-ft-1b and/or 35 MLE is not well understood at present, especially for materials having USEs that approach the 50-f t-lb level and/or the 35-MLE level. Materials with this characteristic may have to be evaluated at transi-tion energy levels lower than 50 f t-lb.

The lack of good agreement of the change in Charpy USE is further support of the inaccuracy of the prediction curves at the lower fluence levels. Although the prediction curves are conservative in that they predict a larger drop in USE certain materials than are observed for a given fluence and copper content,

the conservatism can unduly restrict the operational limitations. These data support the contention that the USE drop curves will have to be modified as more reliable data become available; until that time the design curves used to predict the decrease in USE have adequate conservatism.

l 3-3 Babceck & )Milcox

I l

Table 3-1.

Comparison of Tensile Test Results Room temp test Elevated temp test Unirr Irrad 550F 548F Base Metal (a)

Fluence, 10 a n/cm

(>l MeV) 0 2.49 0

2.49 1

2 Ult. tensile strength, ksi 92.5 99.3 86.2 95.7 0.2% yield strength, ksi 70.7 80.4 55.6 64.7 Elongation, %

18.8 20.9 23.3 18.4

'RA, %

58.8 54.9 54.5 47.0 Weld Metal Fluence, 10 s n/cm

(>l MeV) 0 2.49 0

2.49 1

Ult. tensile strength, kai 79.4 84.5 78.7 84.5 0.2% yield strength, kai 64.2 70.8 60.9 63.6 Elongation, %

19.2 19.3 19.0 19.0 RA, %

71.0 65.0 60.0 56.5

(*) Transverse-axial.

I I

i i

I l

3-4 Babcock & Wilcox i

t Table 3-2.

Observed Vs Predicted Changes in Irradiated Charpy Impact Properties Material Observed Predicted (*

1 Increase in 30-f t-lb trans temp, F i

Base material Axial 21 87 Tangential 39 87 Heat-affected zone 55 87 Weld metal 78 53 Increase in 50-f t-lb trans temp, F Base material Axial 45 87 Tangential 68 87 Heat-affected zone 58 87 Weld metal 71 53 Increase in 35-MLE trans temp, F Base material Axial 36 87(b)

Tangential 73 87(b)

Heat-affected zone 45 87 (b)

Weld metal 80 53(D)

Decrease in Charpy USE, f t-lb Base material Axial 10 14 Tangential 25 22 Heat-affected zone 40 19 Weld metal 3

15 (a)These values, predicted per Regulatory Guide 1.99, Revision 1.

Based on the assumption that MLE as well as 50-ft-lb tran-sition temperature is. used to control the shif t in RTNDT*

3-5 Babcock & Wilcox

1 Figure 3-1.

Irradiated Vs Unirradiated Charpy Impact Properties of Base Metal, Axial Orientation f

E I

I I

I I

e i

a l

I

  • 75 Ejw -_________

I Unirradiated 25-2.49 x 10" nyt f

I I

I I

I I

I I

0 1

1 1

I l

l l

1 1

I

'l i

i i.06-Ig AT = 36F-

.04-

/

5 r____________._._

f.02 - Unirradiated

'_ 2.49 = 10" ave

]

  • 3 i

1 1

I I

I I

i 1

1 g

I I

I I

1 I

I i

180-160-

.140-f C

$120-54 100-1 i

p AUse = 10 ft-lb 2

Y i

3 80-Unitradiated

~

N~

AT = 45F "

p W

3 l

2.49 = 10:s gyg i.

40-AT = 21F -too l

biterat SA508. c12 i

Onnentation Axial 20-Ftweeg N.A.

Heat ho, 990400/292332 I

I I

I I

I I

I 0

1 C0

-40 0

40 80 120, 160 200 240 200 320 360 400 Test itmeenarues, F 3-6 Babcock & Wilcox

Figure 3-2.

Irradiated Vs Unirradiated Charpy Impact Properties of Base Metal, Tangential Orientation 100 g

i g

g g

i

~ is f

Unitradiated j, -______

10 ' nyt 1

5 2.49 x 32s-I I

I I

I I

I 5

0

. 08 g

g g

g g

g 5

g.06-Unirradiated

=

2.49 = 10 ' nyt 1

AT = 73F a.04-l-

e4 g.02-

=

.5 I

I I

I I

I I

I I

I 0

E I

i i

l i

I i

i 180-160-314-d a

AUse = 25 ft-lb

$'120-

'L-

=

a 5

.3100-Unieradiated 5

a 3 80-2.49 = 10 nyt 18 AT = 68 F O

I 60 --

AT = 39" y

I Martnig SA508. C12

- - - - - - - _ - - - On s amration Tanaenttal~~

20-FLuameg N.A.

b tllo. 990400/292332 I

I I

I I

I I

I 0-00

-40 0

40 80 120 _ 160 200 240 280 320 360 400 Test Tampenatune, F 3-7 Babcock & Wilcox

Figure 3-3.

Irradiated Vs Unitradiated Charpy Impact Properties of Weld Metal U

i i

1 I

I I

I i

"O

~

Unirradiated 1

g 1.49 x 10 :,,g

.-y, l

1 32s _

l I

l I

I I

i 1

1 u

.08 g

g g

g g

f Unirradiated s

AT = 80F

=

M w.04-5 E

2.49 = 10 ' nyt 1

g.02-I I

l l

t i

I I

I I

200 i

i g

g g

g g

g g

g 180-160-3140-

$120-E

- AUse = 3 f t-lb

.,100-p 0

3-3 80-Unirradiated 1

5 2.49 x 10 ' nyt

.I AT = 71F C

O g

40-AT = 78F

[____"~l MarantAL Weld Metal

)

20 Fusenet M_A_

NaAt flo.

N.A.

1 1

1 I

f I

i i

i

. b

-80

-4 0

40 80 120 160 200 240 280 320 360 Test Tanetaarunt, F i

4 i

i l

i 3-8 Babcock & Wilcox l

Figure 3-4.

Irradiated Vs Unirradiated Charpy Impact Properties of Base Metal. Heat-Affected-Zone W

l i

I I

i i

i s

a

    • 75 -

-!y, - - - - - - - - - - - - - - - - - - - - - - - - - - - -

I Unirradiated 3 25 -

2.49 = 10** avt I

0

. 08 g

g g

g g

i i

g y

g E

.06-ST = AST

- r

=.04-7 E

f.02 Unirradiated 1

2.4f =.3 e oyg l':<

I I

I I

i I

I I

I I

O I

I i

I i

l i

180 -

160-

$140-T i:

gg,,,,

AUSE = 40 ft-lb ij100-Unirradiated 2.49 = 10 ' nyt 8

a so-W t

AT = 58F c

r so._

[EI 40 AT = $3F

    • ~

Onr. station N.A.

20 FLw ca N.A.

g ggo,990400/292332 1

1 I

I I

I I

f e

i e

-1so -no

.a

.no o

no no no m

m 20 m

m r.., r.

..r... r 3-9 Babcock & WilcoX

I A

?

s J

k 4.

NEUTRON DOSIMETRY 4.1.

Introduction A significant aspect of the surveillance program is to provide a correlation between the neutron fluence above 1 Mev and the radiation-induced property changes noted in surveillance specimens. To permit such a correlation, acti-vation detectors with reaction thresholds in the energy range of interest are placed in each surveillance capsule. The reactions of interest for the de-tectors are given in Table 4-1.

Because of a long half-life of 30 years and an effective energy range of >0.5 187 237 Mev, the measurements of Cs production from fission reactions in Np and assU are more directly applicable than the other dosimeter reactions to anal-ytical determinations of fast (E > 1 MeV) fluence during cycle 1.

The other dosimeter reactions are useful as corroborating data for shorter time inter-vals and/or higher energy fluxes.

Short-lived isotope activities are repre-sentative of reactor conditions over the latter portion of the irradiation period (full cycle) only, whereas reactions with a threshold energy > 3 or 4 Mev do not record a significant part of the total fast flux.

The energy-dependent neutron flux is not directly available from activation detectors because the dosimeters record only the integrated effect of the neutron flux on the target material as a function of both irradiation time and neutron energy. To obtain an accurate estimate of the time-average of neutron flux incident upon the detector, the following parameters must be known: the operating history of the reactor, the energy response of the given detector, end the neutron spectrum at the detector location. Of these parameters, the definition of the neutron spectrum is the most difficult to obtain.

Essen-tially, two means are availabic to obtain the spectrum: iterative unfolding of experimental foil data and analytical methods. Due to a lack of sufficient threshola

-11 detectors satisfying both the threshold energy and half-life requirements necessary for a surveillance program, calculated spectra are used in this analysis.

4-1 Babcock & Wilcox

4.2.

Analytical Approach Energy-dependent neutron fluxes at the detector locations were determined by a discrete ordinates solution of the Boltzmann transport equation with the two-dimensional code DOT 35.2 The North Anna 1 reactor was modeled from the core out to the primary concrete shield in R-theta geometry (based on a plan view along the core midplane and one-eighth core symmetry in the azimuthal dimension). Also included was an explicit model of a surveillance capsule at the proper location. The center of capsule V was positioned 192.84 cm from the core center and 15.0* off-axis.

The reactor model contained the follow-ing regions: core, liner, bypass coolant, core barrel, inlet coolant, thermal shield, pressure vessel, cavity, and shield tank.

Input parameters to the code included a pin-by-pin, time-averaged power distribution, CASK 23E 22-group 8

microscopic neutron cross sections, S rder of angular quadrature, and P e

3 expansion of the scattering cross section matrix.

Because of computer storage limitations, it was necessary to use 2 geometric models to cover the distance from the core to the primary shield. A boundary source output from the initial model A (core into the pressure vessel) was used to " bootstrap" a model B, which included the capsule.

Flux output from the DOT 35 calculations required only an axial distribution adjustment. Thus, fluxes were multiplied by an axial shape factor to account for the capsule elevation. Capsule V extended about 50 inches above and be-low the core midplano. This factor ranged from 1.06 to 1.19 for various dosi-meter locations in the capsule and was 1.20 at the maximum location in the pressure vessel.

The calculation described above provides the neutron flux as a function of energy at the detector position.

These calculated data are usednin the fol,

lowing equations to obtain the calculated activities used for comparison with the experimental values.

The basic equation for the activity D (in pCi/g) is given below.

ike'A(T-r)

M

-A t

d D

3)-e M

=

F 1

A 3.

x 10" i E n i

j=1 4-2 Babcock 8.Wilcox

I C = normalizing constant, ratio of measured to calculated flux, N = Avogadro's number, A = atomic weight of target material 1, f

f = either weight fraction of target isotope in nth material f

or fission yield of desired isotope, o (E) = group-averaged cross sections for material n, listed in Table D-3,

&(E) = group-averaged fluxes calculated by DOT analysis, F = fraction of full power during jth time interval, t 7

A = decay constant of ith material, f

t) = interval of power history.

T = sum of total irradiation time, i.e.,

residual time in reac-tor, and wait time between reactor shutdown and counting, T = cumulative time from reactor startup to end of jth time I

d

period, i.e.,

J t) = [tk' k=1 The normalizing constant C can be obtained by equating the right side of equa-tion 4-1 to the measured activity. With C specified, the neutron fluence greater than 1 Mev can be calculated from Is Mev M

&(E > 1.0 Mev) = C

[

$ [Ft (4-2) 3 E=1 j=1 where M is the number of irradiation time intervals; the other values are as defined above.

4.3.

Results Calculated activities are compared to dosimeter measurements in Table 4-2.

The fission wire data indicate about a 20% underprediction of fast flux (E >

1 Mev) by the analytical mode described herein; non-fission wires were within

-4 to +12% of measurements. Although many factors could account for this discrepancy, including the presence of impurities in the wires and possible 4-3 Babcock & Wilcox

gamma-induced fission reactions, the comparison was considered good for this type of problem. Fission wire data were corroborated with additional fission product reactions not reported here. A value of 1.15 was conservatively se-lected for the normalization factor and then applied to calculated fluxes in the pressure vessel. Thus, fast flux (E > 1 Mev) was determined to be 6.98 2

(+10) n/cm -s in the capsule (center dosimeter location at core midplane) and 2

6.76 (+10) n/cm -s in the pressure vessel at the maximum location (Table 4-3).

Corresponding fluence values for cycle 1 (413 EFPD at 2775 MW) were 2.49 (+18) 2 and 2.41 (+18) n/cm, respectively.

Flux exposures for E > 0.1 Mev were greater by more than a factor of two.

The maximum location in the pressure vessel was at the inside surface along a major axis (across the flats diame-ter) and about 80 cm below core midplane. The capsule lead factor (ratio of fast flux in the capsule to maximum fast flux in the pressure vessel) was 1.03 based on a central capsule location.

Flux magnitude is sensitive to location within an object as large as a sur-veillance capsule. Therefore, suf ficient detail was included in the calcula-tional model to provide flux values that were spatially averaged over each specimen. Data presented in Figure 4-1 show a difference of more than 25%

between maximum and minimum specimen fluence (or flux) at the same elevation.

The ef fect of axial position can be seen in Figure 4-2.

Thus, the midplane values listed in Table 4-3 can be converted to other locations within a cap-sule by a radial factor (Figure 4-1) and a ratio of axial factors, local to midplane (Figure 4-2).

Cycle 1 fluence was extrapolated to the 32-year vessel design life by assuming proportionality to fast flux escaping the core from fuel management critical-ity analyses of cycles 2 through 4.

Cycle 4 was presumed to be representative of an equilibrium cycle. This procedure accounts for the changes in relative power distribution resulting f rom fuel shuf fling between fuel cycles and ef-fectively translates cycle.1 results to equilibrium cycle results. Lifetime fluences at several pressure vessel locations are listed in Table 4-4.

Flu-ence as a function of penetration through the pressure vessel is shown in Figure 4-3.

To facilitate estimation of flux (and/or fluence) at other capsule locations, the azimuthal variation of fast flux is plotted in Figure 4-4.

Although the data were calculated at the vessel surface, they should also be applicable at 4-4 Babcock & Wilcox

l' the capsule radius. Since all other capsule locations are located at angles over 15* off axis, the corresponding lead factors will be less than the cap-l sule V lead factor.

4.4.

Sunnaary of Results 1.

The average fast fluence at the capsule center for the midplane elevation 1

was 2.49 x 10 e n/cm (E > 1 Mev) af ter the first fuel cycle (413 EFPD).

l The maximum value at the pressure vessel wall was calculated to be 2.41 l

28 2

j x 10 n/cm,

2.

Extrapolation to the 32-year vessel design life based on assumed equilib-rium cycle conditions resulted in values of 5.8 (+19), 3.4 (+18), and 8.5 2

(+18) n/cm for maximum locations at the vessel surface, at T/4, and at 3T/4, respectively.

Table 4-1.

Surveillance Capsule Detectors Energy Isotope Detector reaction range Mev half-life 8 "Fe (n, p) 3 "Mn

>2.5 313 days ssNi(n.p) s eco

>2.3 71.2 days sscu(n a)88Co

>5.0 5.27 years 2ss (n.f)187Cs

>1.1 30.1 years U

237Np (n, f)18 7Cs

>0.5 30.1 years 4-5 Babcock 8.Wilcox

Table 4-2.

Dosimeter Activations A

B measured calculated C = A/B

activity, activity, normalization Reaction pCi/g pCi/g constant 5 "Fe (n. p) 3 "Mn 891(*)

964 0.92 5 'Ni(n.p) 5 8Co 1550(D) 1630 0.95 I

'8Cu (n. a) ' 'Co 2.08 2.58 0.81 a ss (n.f)18'Cs 3.28 2.85 1.15 l

U 237Np(n.f)187Cs 21.3 18.7 1.14 (a) Average of five dosimeter wires f rom Table D-2.

(b) Average of three dosimeter locations in calculational model.

Table 4-3.

Neutron Flux and Fluence Fast fluence for Fast flux, cycle 1 (413 EFPD),

2 2

n/cm -s n/cm E > 1 Mev Capsule, central 6.98 (+10) 2.49 (+18) dosimeter loc'n(a)

Pressure vessel 6.76 (+10) 2.,41 (+18) surface (max)

E > 0.1 Mev l

Capsule, central 1.72 (+11) 6.14 (+18) i.

dosimeter loc'n Pressure vessel 1.72 (+11) 6.14 (+18) surface (max) f

("} Approximate geometric center of specimens at core midplane.

4-6 Ehnbcock & VWilcox

...,.,. -. -. - -. -, - - - - - - - - -.. - - - - - - - - -, ~, -

I I

Table 4-4.

Predicted Lifetime Fluence to Pressure Vessel for E > 1 Mev Vessel surface T/4 3T/4 Average fast flux, 2

n/cm s 5.7 (+10) 3.4 (+10) 8.4 (+9) 2 Fast fluence, n/cm 5.8 (+19) 3.4 (+19) 8.5 (+18)

Figure 4-1.

Relative Fast Flux at Specimen and Dosimeter Locations in Surveillance Capsule V Specimen Specimen 1.05 0.86 u

Core 8

A B

C 1

1.09 1.00 0.92

+

m Specimen Specimen Major Axis 1.10 0.91 A.B.C:

Dosimeter wire positions.

4-7 Babcock s.Wilcox

Figure 4-2.

Axial Shape of Fast Flux at the Pressure Vessel Surface 1.3 1.2 1.1 1.0 g

5 O

0.9

?

,e 0.8 g 0.7 b

.6 8

h 0

g e

Dosimeter 1

2 34 5

6 0.5 y

Positions w

0.4 a:

0.3 0.2 0.1 K

0 i

e i

i e

i i

i i

i g

r

-180

-140

-100

-60

-20 0

+20

+60

+100

+140

+180 r.*

Distance From Core Midplane, cm 3

n M

Figure 4-3.

Calculated Maximum End-of-Life Fluence as a Function of Penetration in the Pressure Vessel 8-7 6

5 204.66 cm 4

3 T/4 2

01 d

8 8

E 214.41 cm e

$ 10 '

1 5

9 z

8 7

6 3T/4 Lead Factor at T/4 = 1.7 5

Lead Factor at 3T/4 = 6.8 4

3 2

I I

I I

l l

196 200 204 208 212 216 220 Radius, cm 4-9 Babcock & Wilcox

FiRure 4-4.

Azimuthal Variation of Fast Flux at the Pressure Vessel Surface 10 9

8 7

$5 6

O m

"a 4a 5

E h

8 h

4 Capsule V t

.5 a

3 l

2 i

i i

f i

1 0

10 20 30 40 50 Angle From Major Axis, degrees 4-10 Babcock & Wilcox

5.

SUMMARY

OF RESULTS The analysis of the reactor vessel material contained in North Anna Unit 1 Capsule V, led to the following conclusions:

18 2

1.

The capsule received an average fast fluence of 2.49 x 10 n/cm (E > 1 Mev). The predicted fast fluence for the reactor vessel T/4 location at the end of the first fuel cycle is 1,41 x 10 e nfc,2 (E > 1 Mev).

1 18 2

2.

The fast fluence of 2.49 x 10 n/cm (E > 1 Mev) increased the RTNDT the reactor vessel core region shell materials in the capsule to a maxi-mum of 70F.

3.

Based on the ratio of the fast flux at the surveillance capsule location to that at the vessel wall and an 80% load factor, the projected fast fluence the North Anna Unit I reactor pressure vessel will receive in 32 2

EFPY operation is 5.8 x 10" n/cm (E > 1 Mev).

4.

The increase in the RT f r the base plate material was conservative NDT compared to that predicted by the currently used design curves of ARTNDT versus fluence.

5.

The increase in the RT f r the weld metal was not in good agreement NDT with that predicted by the currently used design curves of ART versus NDT fluence.

6.

The current techniques used for predicting the change in Charpy impact upper shelf properties due to irradiation are conservative considering the difficulties in accurately' defining the upper shelf.

7.

The analysis of the neutron dosimeters demonstrated that the analytical techniques used to predict the neutron flux and fluence were accurate.

8.

The thermal monitors indicated that the capsule design was satisfactory for maintaining the specimens within the desired temperature range.

5-1 Babcock 8.Wilcox

6.

CERTIFICATION The specimens were tested, and the data obtained f rom Virginia Electric &

Power Company's North Anna Unit I surveillance capsule V were evaluated using accepted techniques and established standard methods and procedures in accor-dance with the requirements of 10 CFR 50. Appendixes G and H.

EJA

/M '... EE $0Y lW/

A.'L.'I2we,Jr..[/E Date Project Technical Manager This report has been reviewed for technical content and accuracy.

W a)

S/

l Q. Aadland Da'te Component Engineering 6-1 Babcock & Wilcox

7.

REFERENCES 1

J. A. Davidson and J. H. Phillips Virginia Electric & Power Company North Anna Unit 1 Reactor Vessel Radiation Program WCAP-8771. Westinghouse, Pittsburgh, September 1976.

2 DOT 3.5 -- Two-Dimensional Discrete Ordinates Radiation Transport Code, (CCC-276), Oak Ridge National Laboratory WANL-TME-1982, December 1969.

8 CASK -- 40-Group Coupled Neutron and Gamma-Ray Cross Section Data, Radia-tion Shielding Information Center, RSIC-DLC-23.

7-1 Babcock & Wilcox

APPENDIX A 1

Surveillance Material Properties A-1 Babcock & Wilcox

3 The Rotterdam Dockyard Company supplied the Westinghouse Electric Corporation with sections of SA508 Class 2 forging used in the core region of the North Anna Unit No. I reactor pressure vessel for the Reactor Vessel Radiation Sur-veillance Program. The sections of material were removed f rom a 10-inch lower shell course forging 03 of the pressure vessel heat treated as shown in Table A-1.

The Rotterdam Dockyard Company also supplied a weldment made from sec-tions of forging 03 and adjoining intermediate shell course forging 04 using weld wire representative of that used in the original fabrication. The forg-ings were produced by Rheinstahl Huttenwecke. The heat treatment history and quantitative chemical analysis of the pressure vessel surveillance material are presented in Tables A-1 and A-2, respectively.

Table A-1.

Heat Treatment History Temperature, Material F

Time, h Coolant Lower shell 1616-1725 2.5 Water-quenched forg ng 03, 1202-1292 7.5 Furnace-cooled Ifeat No.

to 842F 990400/292332 1130 1 25 14.75 Furnace-cooled Weld metal 1130 1 25 10.75 Furnace-cooled l

A-2 Babcock s, Wilcox

l 1

l Table A-2.

Quantitative Chemical Analysis, wt %

)

Forging 03 heat Rotterdam 1

No. 990400/292332 dock f

Element (Westinghouse )

analysis

~W weld metal a

analysis C

0.20 0.19 0.06

{

S 0.011 0.014 0.012 l

N2 0.015 0.015

{

Co 0.020 0.006 i

Cu 0.16 0.15 0.086 Si 0.26 0.22 0.35

.Mo 0.61 0.63 0.49 i

j Ni 0.79 0.80 0.11 Mn 0.68 0.68 1.29

]

Cr 0.30 0.30 0.025 V

0.037 0.02 0.001 P

0.019 0.010 0.020 4

i Sn 0.017 0.003 A1 0.021 0.009 1

i l

"All elements not listed are less than 0.010 wt %.

4 i

4 1

i l

i h

i i

A-3 Babcock & Wilcox 1

l APPENDIX B l

Preirradiation Tensile Data B-1 Babcock & Wilcox

Table B-1.

Preirradiation Tensile Properties of Forging Material (Base Metal) and Weld Metall Ultimate Test Yield tensile Percent Percent temperature,

strength, strength, total reduction F

kai kai elongation la area Forging Material Room 70.1 92.4 18.8 60.7 Room 71.3 92.7 18.8 57.0 Average 70.7 92.5 18.8 58.8 1

550 58.0 87.2 20.6 52.0 550 53.1 85.3 26.0 57.0 Average 55.6 86.2 23.3 54.5 Weld Metal Room 63.2 78.3 18.9 71.0 Room 65.2 80.4 19.5 71.0 Average 64.2 79.4 19.2 71.0 550 60.2 76.9 20.0 63.0 550 61.7 80.5 18.0 57.0 l

Average 60.9 78.7 19.0 60.0 i

i i

i i

l i

a-2 Babcock &Wilcox

APPENDIX C l

Preirradiation Charpy Impact Data c-1 Babcock a, Wilcox

Table C-1.

Preirradiation Charpy V-Notch Impact Data for North Anna Unit 1 Reactor Pressure Vessel l

Lower Shell Forging 03, Heat No. 990400/

1 292332, Axial Orientation Test Impact Lateral Shear

temp, energy, expansion,
fracture, F

ft-lb mils

-15 16 7

10

-15 17 10 10

-15 15 10 10 45 31.5 21 35 45 30 20 35 45 25 21 30 75 47.5 37 30 75 43.5 37 23 75 47.5 33 27 105 62.5 50 55 105 56.5 50 55 105 59 50 55 150 80.5 66 90 150 84.5 100 72 150 67.5 78 62 210 85 69 100 210 82.5 68 100 210 86.5 73 100 C-2 Babcock &Wilcox e

.= -.

Table C-2.

Preirradiation Charpy V-Notch Impact Data for

~ North Anna Unit 1 Reactor Pressure Vessel Lower Shell Forging 03, Heat No. 990400/

292332 Tangential Orientation!

Tes t Impact Lateral Shear

temp, energy, expansion,
fracture, F

ft-lb mils

-15 30 21 9

-15 9

5 0

-15 19 16 3

40 66 48 40 40 84 60 45 40 78 59 56 74 96.5-67 38

.74 101 74 64 74 73.5 59 38 125 116 74 77 125 115.

78 92 125 99 67.5 79 170 143 80 100 170 147 83 100 170 144 81 100 210 126.5 88 100 210 123 84.5 100 210 127 80 100 l'

I i

C-3 Babcock & Wilcox e

rug, y%-tC-r e-c-----F w*-en*m

-'-e-+---r-+----+--m--------e-

-+r+-vWy--?

k-

-en

---W&

y y-

-qwy w--

e-w w-7+w

Table C-3.

Preirradiation Charpy V-Notch Impact Data for North Anna Unit 1 Reactor Pressure Vessel Core Region Weld Heat-Af fected Zone Material Test Impact Lateral Shear

temp, energy, expansion,
fracture, F

ft-lb mils

-125 21 13 9

-125 4.5 2.5 5

-125 13 6

5

-80 25.5 13 3

-80 76.5 47 29

-80 53 21 18

-25 22.5 13 18 i

-25 47 26 23

-25 31.5 15 13 40 104 65 81 40 62 43.5 45 40 78.5 46 42 100 156.5 78 100 100 127.5 81 79 100 125.5 73 90 170 152.5 72 100 170 166 82 100 170 109 74 100 C-4 Babcock & Wilcox u

Table C-4.

Preirradiation Charpy V-Notch Impact Data for North Anna Unit 1 Reactor Pressure Vessel Core Region Weld Metal Test Impact Lateral Shear

temp, energy, expansion,
fracture, F

ft-lb mils

-110 9

9 0

- 110 5

9 0

-110 13 7

0 0

74.5 61 48 0

58 52 54 0

60 70 43 48 37.5 39.5 31 48 40 45 51 48 42 49.5 40 75 83 68 79 75 81 71.5 81 75 49.5 50 65 175 106 89 100 175 106 88 100 175 94 76 96 250 87 79 100 250 90.5 81 100 250 84.5 77 100 C-5 Babcock & \\Milcox

_a

Figure C-1.

Charpy Impact Data From Unirradiated Base Metal, Axial Orientation 1

i i

i I

1 I

I I

I i

e l

w5 a

3yw __________

l 3

2.

.X 25 -

I l

I a1 I

I i

1 I

I I

t I

g l

l I

i i

I

.i I

l l

l 1

=

5 06-5 k;.0a 2

a l 02 2

i i

i i

i i

i i

r i

e I

I I

I i

i l

i DATA SimulY l

180-T,

-12F

)

g Tcv (35 MI

  • I'#

+85F TCV (50 eT-u) 160 T, (30 n-u) 46r 1

c C,-USE ( m )

85 ft-ib alW RT

+25F f

ROT

$120-I2100-3 2

w M-W t

60-

.-______g

~

Mattatat, SA508. C12 3

20-Fuance None Maar Slo. 990400/292332 I

I I

I I

I I

I 0-00

-40 0

40 80 120 160 200 240 280 320 360 400 itit Tswenaruns, F C-6 Babcock & Wilcox

Figure C-2.

Charpy Impact Data From Unirradiated Base Metal, Tangential Orientation 100 g

i g

y 3 -.y g

g te /$

J 5-j w _______

2 g

3 25-I I

I I

I I

I I

I I

I g

l g g

g

. 08 g

g

.g

~=

$.06-4.m-e a

f.02-I I

I I

I I

I I

I I

I O

I I

I I

I I

I I

DATA SIN %RY 180. T,,,

-127 Tg (35 m)

+7F

+12F

,Tu (50 FT-u) g in (30 FT-u)

-6F

(-USE (an) t35 fe-1b 3140 RT,3

-12F C

gg_

I 100-3 5

0 80-U t

60

~

MArra tat SA508, cl2

~

Onstmiation Tangential"-

_______ ~

20-FLuanct None Haarflo. 990400/292332 I

I I

I I

I I

I 0-00

-40 0

40 80 120, 160 200 240 280 320 360 400 inst itwinarunt, F c-7 Babcock & Wilcox

Figure C-3.

Charpy Impact Data From Unirradiated Weld Metal 2

_3 100 g

i g

3 g

i i

    • 75 -

O 3

-fg -______y_

~__________________-

3 25 -

g 'l f

I 1

1 I

I I

I I

l

.08 g

g g

g

{

!.06-

3..s._ _ _ _ _ _

>a d.02-5 2

.3 I

I I

I I

I I

I I

I I

0 200 i

i i

g g

g g

g g

g g

DATA Surt%ItY 180- T,,,

-12F Tcy (35 eu) -13F

+25F TCV (50 FT-u) 160

-26F Tcy (30 Fr-u) 95 ft-lb

(-USE(an)

.10 gi

-12F y

NDT

$120-6 5

  • 2

.2 100-5 5

J. 80-8

~

W k

60 g

8 Martarat Weld Metal 20-FLuthct None HEAT 110.

N.A.

I f

f I

f I

f I

e i

.b

-80

-40 0

40 80 120 160 200 24 280 320 360 Test Temnaruns, F C-8 Babcock & Wilcox

l

)

f Figure C-4.

Charpy Impact From Unirradiated Base Metal, Heat-Affected-Zone U

l 4

I i

i I

t3 I i

i u n-Ey2 -__________ __________________

1 1

32s-e e

o I

+

I I

I I

I I

I I

I 0

.08 3

g g

g g

7-g g

e s.06-2 e

i.0t4-34 e

4.02-8 o

I I

I I

I I

I I

I I

I 0

I I

i i

i I

i i

DATA SlprIARY 180- T,,,

-22F Tcv (35 m)

+20F

+2F TCV (50 ri-ts) 160 T W 77-ta)

-M gy 145 ft-tb.

C, 'JSE (ave)

. 140 RT,,,

-22F 5

s i2a-o 100-a i, 80-W k

60--

e 40-Parte:At Base Metal-HAZ -

20-FLutect None HEAT Mo. 990400/292332 9

I f

I I

f I

f i

i

- 60

-120

-80

-40 0

40 80 120 160 200 240 280 320 Test Tamenatunt, F C-9 Babcock 8.Wilcox

APPENDIX D Threshold Detector Information D-1 Babcock & Wilcox

Table D-1.

North Anna Neutron Dosimeters - Capsule V Irradiation Ended September 25, 1979, 24:00 Dostmeter Mass Nucit de Activity / Gram Activity /Grm Material Location (9f aas)

Resc t ion Nuclide ActivityLCQ of Meterial(.Ct/q)g,)

of TargethCf/q)gggy 54,g,,,)54 Iron T-Fe

.0524 54 7

m Mn 2.79 53.3 916 Fe(n,y)$IFe "Fe 6.03

115, 34,800 b4Fe(n.p)$#

54 MT-Fe

.0544 Mn m

2.76 50.8 873 8Fe(n,y)$'Fe 59Fe 6.58 121.

36,700 Mid-Fe

.0442 54,

,)54, 54m 2.35 El m

8Fe(n,y) Fe 59Fe 5.13 116.

35.200 MB-Fe

.048?

Ufe(n.p)S4 54 m

Mn 2.42 50.2 863 I

59 Fe(n,y1 7,

59Fe 5.40 112 33,900 54,g,,,)54, 54 8-Fe

.0368 7

m 1.91 52.0 893 Fe(n.p)"Fe 59 8

Fe

4. 34 118.

35,800 59,g,,v)60C0 00 Cobalt-Aluminum T Co

.0082 g

00 2.01 245.

163,000I8) 6-Ce

.0070 I'Co(n,y )60,

60 g

Co 1.81 258.

172,000 59Co(n,y)60Co Co 0.0568 88.8 59,200IdI 60 Cobalt-aluminum T-Co

.0064 f

B-Co

.0063 Co(n,y)"Co "Co

0. 5 56 88.3 58.900 N

Copper NT-Cu

.0532 Cu(n.e)60Co Co 0.0745 1.40 2.04 00 03Cu(n.e)60,

60 Mid-Cu

.0512 g

Co 0.0758 1.48 2.16 0 Cu(n.o) Oco ko 4.0815 1.40 2.04 MB-Cu

.0582 htchel MT-Ni

.0486 58, g g,,,)58,

58 g

Co 51.0 1050.

1550.

60Ni(n.p)"Co 60Co 0.100 2.05 7.84 Mid-Nt

.0534 bi(n.p) 8Co 00 57.7 1080.

1590.

58 60,q g,,,)MCo Co 0.115 2.15 8.22 60 MS-Ni

.0576 Ni(n.p)58Co Co 59.3 1030.

1520 58 60,gg,,,)60,

60 g

Co 0.119 2.06 7.87 G3 as U"

OO O

3C' to k

=

0 t?

X

~

Table D-1.

(Cont'd)

Oos tmeter flass Nuclide Activity / Gram Activity / Gram Raterial Location (grams)

Reaction Nuclide Activity (utt) of Material (9Ci/gl{,)

of Target (vCi/e1(b.c) 238 (,,7)p,p, br 0 0,,

Dostmeter 81ock 0.0136 p

0.974 71.6 84.4 'I I

3 Ru 1.24 91.2 108.

Ru 0.317 23.3 27.5 y,

Cs 0.0378 2.78 3.28 Ce

.837 54.6 64.5 Ce 0.589 43.3

$1, y 95 hp0 Desleeter Block 0.0075 237,,g,,7 37,p, 2r 4.02 536.

608 2

I'I 1032u 4.10 547 621 U nu 0.900 120 136 IIICs 0.141 18.8 21.3 Ce 6.63 884.

1000 I4"Ce 1.99 266.

302, 12556 0.0244 3.25 3.69 t3iW (a) The materials are deffned to be f ron cobalt. copper. nickel. U 0 and Mp0 -

3g 2

(d) Data provided by Art Lowe indicate the cobalt-aluminum wire is 0.155 cobalt (b) The target nuclides are listed on the left side under the column headed AEACTION.

(e) Westinghouse-supplied data Ifsts the quantity of U as 12 mg and the quantity (c) The following weight percents were used to calculate the activity per gram of of Np as 1711 mg. Only part of each was recovered from the capsules.

target nuclide:

238 54 8ath are stated to be '99.95 pure *, using the formula weights for U03 8 *"#

fe 5.82 wt1 237Np02 yields target weight fractions of 0.848 and 0.881.

Se 0.33 ott Co 100. wt1 63Cu 68.5 wt bi 67.77 wt1 bi 26.16 wt1 K

8w P

w to M

i

Dosimeter Activation Cross Sections ("

Table D-2.

Energy range,

_G_

Mev Np 23eU seNi 5"Fe 83 237 Cu 1

13.3

-15.0 2.323 1.050 0.4830 0.4133 4.478 (-2) 2 10.0

-12.2 2.341 0.9851 0.5735 0.4728 5.361 (-2) 3 8.18

-10.0 2.309 0.9935 0.5981 0.4772 3.378 (-2) 4 6.36

-8.18 2.093 0.9110 0.5921 0.4714 1.246 (-2) 5 4.96

-6.36 1.541 0.5777 0.5223 0.4321 3.459 (-3) 6 4.06

-4.96 1.532 0.5454 0.4146 0.3275 6.348 (-4) 7 3.01

-4.06 1.614 0.5340 0.2701 0.2193 7.078 (-5) 8 2.46

-3.01 1.689 0.5272 0.1445 0.1080 3.702 (-6) 9 2.35

-2.46 1.695 0.5298 9.154 (-2) 5.613 (-2) 6.291 (-7) 10 1.83

-2.35 1.677 0.5313 4.856 (-2) 2.940 (-2) 1.451 (-7) 11 1.11

-1.83 1.596-0.2608 1.180 (-2) 2.948 (-3) 1.317 (-9) 12 0.55

-1.11 1.241 9.845 (-3) 6.770 (-4) 6.999 (-5) 0 13 0.111

-0.55 0.2341 2.432 (-4) 1.174 (-6) 1.578 (-8)

O 14 0.0033 -0.111 0.0069 3.616 (-5) 1.023 (-7) 1.389 (-9)

O t,

L

(*)ENDF/BV values flux-weighted with a fission spectrum combined with a 1/E inter-mediate energy distribution.

K 8w P

E l

i L-----------------------------------------

t APPENDIX E LRC-TP-78 I

l l

E-1 Babcock & Wilcox

RESEARCH AND DEVELOPMENT DIVISION 1-27-81 TECHNICAL PROCEDURE DATE j

l 1.

Introduction

/

1.1 This Technical Procedure outlines a method for the static tension testing of metallic solid round cross-sectional specimens at both room and elevated I

temperatures. The test shall provide data for the evaluation of yield and tensile strengths, approximate elastic modulus, and various ductility param-l eters. The room temperature portion of this procedures is in accordance with ASTM Method E8-78 unless otherwise specified. ASTM Method E21-70 was the guide for the elevated temperature portion and actual conformance will be indicated where applicable.

1.2 This procedure is designed to document the commitments made by the testing organization during the performance of the tension test.

Specifically, these commitments are in regards to operator qualification, equipment calibrations, test and analysis procedures, and the test record.

1.3 Results obtained from specimens tested according to this procedure will be acceptable for B&W's Reactor Vessel Material Surveillance Program (RVSP). This procedure has been written primarily for the purpose of testing the two specimens currently in the surveillance program: A 0.357 inch diameter specimen and a 0.180 inch diameter specimen.

1.4 The scope of this procedure does not include detailed instrument settings and test parameters required by the person who performs the test.

Mention will be made, however, whenever a referenced ASTM Method contains information of interest to said person.

Note: The latest edition of the applicable ASTM methods supersedes those listed

(:

in this procedure.

E-2 rnocEoURE No. f.RC-TP _7,8 7

PAoE NO.

1

RESEARCH AMD DEVELOPfAENT DIVisl0N 10/27/78 DATE TECHNICAL PROCEDURE 2.

Operator Qualification Individuals performing the static tension test shall be qualified 2.1 by training and experience and shall have demonstrated competency to perform the tests in accordance with this procedure to the satis-faction of the LRC Project Leader.

r I

E-3 PROCEDURE NO.

LRC-TP-78 rAos No.

2 J

RESEARCH AND DEVELOPMENT DIVISION 10/27/78 TECHNICAL PROCEDURE 9

3.

Specimen

\\

3.1 Specimen Geometry _

The specimen shall be any round cross-sectional specimen. The gage The length shall be four times the diameter of the specimen.

ends of the specimen outside the gage length shall be of a shape I

to fit the grips of the testing machine such that the loads a're applied axially.

3.2 Specimen Preparation in order to measure the deformation of the specimen, two fiducial marks shall be imprinted at the boundaries of the gage length. These marks may be stamped lightly with a punch, scribed lightly with dividers or a razor, or drawn with ink, as required by the LRC Project Leader. Care should be taken to place the marks with the name angular orientation with respect to one another.

I l

1 E-4 raoCEDURE NO. LRC-TP-78 PAGE NO.

3

fiESEARCH AND DEVELOPMENT DIVISION 10/27/73 TECHMICAL PROCEDURE DATE 4.

Equipment 4.1 Testing Machine The machine used for tension testing shall have sufficient capacity to load each specimen to failure.

4.2 Grips The machine shall be equipped with suitable gripping devices to transmit the applied load to the test specimen. To minimize bending and ensure uniaxial loading within the gage length, the axis of the specimen shall coincide with the center line of the heads of the testing machine.

4.3 Axial Extension Instrument An appropriate set of equipment for measuring axial extension shall be used to an elongation greater than that corresponding to the 0.2% off-Afterwards, axial extension may be obtained from the set yield point.

stroke output of the testing machine.

4.4 Heating Element The heating apparatus shall provide uniform heating along the gage length of the test specimen to within

  • 5 F (* 3 C) of the nominal test temperature at the onset of the test. This paragraph conforms to ASTM Method E21-70, section 7.4.4.

4.5 Temperature Measurement Apparatus The temperature neasurement apparatus shall be of sufficient accuracy and sensitivity to monitor the test temperature within limits specified in 4.4.

Temperature shall be measured with thermocouples in conjunction with potentiometers or voltmeters.

This paragraph conforms to ASTM Method E21-70, sections 4.3.1 and 4.3.2.

E-5 PRoCEoORE NO. LRC-TP-78 PAGE NO.

4

RESEARCH AND DEVELOPMENT DIVISION TECHNICAL PROCEDURE DATE

)

4.6 Calibrations 4.6.1 Load The load cell with its associated electronics shall be calibrated against standards traceable to the National Bureau of Standards (NBS) at least annually by a qualified service representative. The calibration of the electronics will be checked at the onset of each day of testing by checking the electrical output of the system when under the stimulus of a fixed calibration voltage (which simulates a load).

4.6.2 Stroke The stroke (displacement) monitoring portion of the tension test machine shall be calibrated at least annually by a qualified service representative against standards traceable to the NBS.

4.6.3 Strain The strain monitoring portion of the tension test apparatus is composed of four parts - a 4-pole axial extensometer, a clip-on strain gaged extension transducer (with cabic), a signal conditioning unit, and output recorder. The 4-pole extensometer will not require calibration.

The transducer, signal conditioner, and output recorder shall be calibrated at Icast annually, although not necessarily concurrently, against standards traceable to the NBS. The calibration of the transducer, signal conditioner, and output recorder shall be checked as a unit at the onset of each day of testing. This shall be done by the comparison between the output recorder's response to the movement of an NBS traceable micrometer.

t I

4.6.4 Temperature The electronics portion of the temperature measurement system shall be calibrated at least annually against standards traceable to the NBS.

i The thermocouple alone need not receive calibration, however the thermo-o couple-electronics system shall be checked at least daily against an ASTM industrial grade (or better) thermometer at ambient temperature. The thermocouple wire shall be replaced at least monthly.

E-6 raoctount No. LRC-TP-78 rAoe no.

g

DESEARCH AND DEVELOPMENT DIVI 5!ON 10/28/78

.ECiff!! CAL PROCEDURE mrg l

i l

l 4.6.5 Diametral Measurement The instrument used for diametral measurement shall be calibrated at least anually against standards traceable to the NBS.

l l

l l

i i

l l

E-7 PROCEDURC NO.

LRC-TP-78 PAGE NO.

]

RESEARCH AND DEVELOPMENT DIVISION 10/27/78 TECliNICAL PROCEDURE o g 5.

Test and Specimen Parameters 5.1 Speed of Testing Testing shall be performed in stroke (displacement) or strain control.

Epceds [in distance / time or distance /(gage length x time)] shall be designated by the LRC Project Leader. Speeds may be increased after

.the 0.2% offset yield point is passed, also by designation of the LRC Proj ect Leader.

5.2 Temperature The nominal test temperature shall be designated by the LRC Project Leader. The testing shall not begin until thermal equilibrium is reached. The time of holding at temperature prior to the start of the test shall not be less than 20 minutes.

5.3 Specimen Measurement The cross-sectional area, A, of the specimen shall be determined by the following equation:

(OD )2 A

=

w 4

0 0

4 where OD is the outside diameter at the gage section before testing.

o l

The value, OD, shall be either measured directly from the specimen or o

taken from an existing data sheet.

i 5.4 Test Record The test record shall include a graph of load-strain (load-displacement) behavior. The load and strain (displacement) ranges shall be selected to provide adequate data resolution for the specified test conditions. Pertinent procedural parameters shall j

be listed by the operator on the Static Tension Test Record Report (see attachment).

i l

E-8 rnoccount No. LRC-TP-78 PAGE NO.

4

CESEARCH AND DEVELOPMENT DIVISION

.ECHNICAL PROCEDURE DATE 6.

Analysis Procedure l

The results listed below shall be determined by the methods described in ASTM Method E8-69.

For convenience, summaries of these methods are deacribed below.

6.1 Uniform Strain Strain shall be reported as the increase in the gage length expressed as a percentage of the initial gage length, as follows:

'Atl c ='

I x 100%

U tios where:

c = Uniform strain, %

(dimensionless)

U At = Increase in the gage length (in.)

i = Initial gage length (in.)

o The increase in the gage length is found from the load-elongation chart.

Uniform strain includes all elongation which occurs until the maximum load is reached.

Should the extensometer be removed before the maximum load is reached, the gage length (after removal) shall be the original length of the reduced diameter section.

Both plastic uniform strain and elastic strain data are available from the load-strain chart. Uniform strain may be reported either as a summation of the two, or plastic uniform strain alone, to the preference of the LRC project leader. In either case, the type of strain reported shall be recorded on the Static Tension Test Record Report (see attachment).

6.2 Total Elongation The total elongation includes the entire specimen deformation within the specimen after its failure. The equation to be used for the determination of total clongation is the same as that given in Section 6.1 (Uniform The increase in Strain), but with cT (totel strain) substituted for cU.

the gage length (AL) shall be found by placing the broken ends of the From specimen together and measuring the distance between fiducial marks.

this measurement is subtracted the original distance between the marks giving AL.

E-9 rnoctount No. LRC-TP-78 rion no.

y

1 I

RESEARCH AND DEVELOPMENT DIVISION 10/27/78 DATE TECHNICAL PROCEDURE 6.3 Yield Strength i

The yield strength shall be determined by the 0.2% offset method, as "8

o

=P

/A, yg 0.2%

where:

0.2% offset yield stress or strength (psi) o

=

yg (lbs) ad at 0.2% offset strain P

=

0.2%

(in.2)

A, = original cross sectional area A straight The load at 0.2% offset strain (P.2%) is f und as follows.

O line is drawn through the elastic portion of the curve on the loa 6-strain (The slope of this line approximates the material's elastic chart.

modulus.)

The increase in the gage length corresponding to 0.2% strain is calculated as follows:

.002) 1, At

=

0.2%

where:

n rease in the gage length at 0.2% strain (in.)

AL

=

O.2%

An of fset of this amount relative to the elastic line is then plotted along A second line, parallel to the first but passing through the abscissa.

the 0.2% of fset strain point, is drawn on the chart. At the point where this line intersects the load-strain curve, the load (P.2%) can be O

determined.

6.4 Tensile Strength The tensile strength shall be calculated as follows:

I "TS MAX ^o

~

where:

(psi) agg = tensile strength

= maximum 1 ad sustained by specimen (Ibs)

PMAX (in.2)

A = original cross-sectional area 0

6 i

E-10 LRC-TP-78 PROCEDURE NO.

rion no.

g

h RESEARCH AND DEVELOPMENT DIVISION 10/27/78 TECHNICAL PROCEDURE DATE l

l 6.5 Reduction of Area The reduction of area is the difference between the final cross-sectional area at the fracture and the original cross-sectional area expressed as The final cross-a percentage of the original cross-sectional area.

thus sectional area is calculated from the final diameter,

,(OD )2 f

A

=-

g 4

where:

OD = the final dimaeter (in.)

f The final diameter shall be taken by placing the broken specimen edges The together and measuring the specimen at its smallest section.

reported OD shall be the average of not less than three measurements f

taken at different angular orientations. The reduction of area (RA) shall then be calculated as

[A' - A RA =l x 100%

(

^o 6.6 Report _

6.6.1 The test report shall include a graph of load-strain (load-displacement) behavior. Test results shall be included on the l

Static Tension Test Record Report (see attachment).

6.6.2 Photographs, diagrams, or other exhibits requested by the LRC Project Leader shall be attached to the repart and noted on the report.

6.6.3 Notes shall be made in a record book with regards to main-tenance, adjustments and calibrations.

E-Il rnocEouRE No. LRC-TP-7_8

'^

9

/

APPENDIX F LRC-TP-80 F-1 Babcock & Wilcox

RESEARCH AND DEVELOPMENT DIVISION TECI:ICAL PROCEDURE DATE

\\

1.

Introduction 1.1 This Technical Procedure outlines a method for notched bar impact testing of metallic specimens using the Charpy apparatus for the evaluation of impact energy, percent shear fracture, and Jateral expansion. ASTM Methods A370-77, E23-72, and 10 CFR 50 Appendix G are the governing documents. Deviations from and conformance to particula'r specifications are noted in the procedure.

1.2 This procedure is designed to document the commitments made by the testing organization during the performance of the Charpy Specifically, these commitments are in regards to operator test.

qualification, equipment calibrations, test and analysis procedures, and the test record.

Results obtained from Charpy specimens tested according to this 1.3 precedure shall be acceptable for B&W's Reactor Vessel Surveillance Program (RVSP).

1.4 The scope of this procedure does not include detailed instrument settings and test parameters required by the person who performs Mention will be made, however, whenever a referenced the test.

ASTM Method contains information of interest to said person.

R The latest edition of the applicable ASTM methods supersedes those listed Note:

in this procedure.

)

1 F-2 rnocCouRE No.LRC-TP-80 PAoE NO.

1

RESEARCH AND DEVELOPMENT DIVISION TECif*JICAL PROCEDURE 12/12/78 og 2.

Operator Qualification 2.1 Individuals performing the Charpy impact test sha11 be qualified by training and experience and shall have demonstrated competency to perform the tests in accord with this procedure to the satisfaction of the LRC Project Leader. This paragraph is in compliance with 10 CFR 50, Appendix G.

I F-3

~ ~ '

rnoctount No. LRC-TP-80 PAOt No.

2

RESEARCH AfdD DEVELOPMENT DIVISION 12/12/78 TECHNICAL FROCEDURE DATE 3.

Specimen 3.1 Specimen Geometry _

The specimen shall be a Charpy impact test specimen, Type A, that conforms to ASTM E23-72, Section 7 and ASTM A370-77, Section 20.2.1.

3. 2 Number of Tests ASTM Method A370-77, Section 20.1.2 states that a test shall be composed of three specimens taken from a single test coupon or location. Due to the scarcity of specimens, one specimen shall compose a test.

Consistent with this, this procedure is also in violation of Section 22.1, which requires an arithmetic average of three specimens as the result of a test.

i f

l l

d l

i F-4 LRC-TP-80 rmoctouRE NO.

PAoE NO.

3

RESEARCH AND DEVELOPMENT DIVISION 12/12/M TECHNICAL PROCEDURE DATE 1

4.

Equipment 4.1 Testing Machine The Charpy impact test machine shall be a pendulum type of rigid construction and of capacity at least 125% of that required to break each specimen. The machine shall be rigidly mounted to either a concrete floor not less than 6 inches thick or a base of a weight at least 40 times that of the pendulum. The machine shall conform to specifications described in ASTM E23-72 Sections 4.1, 4.2.2, 4.2.3 and 4.2.4.

4.2 Self-Centering Tongs A set of tongs as shown in Figure 12 of ASTM E23-72 shall be used to center the specimens within the testing machine's anvils. This conforms to ASTM Methods E23-72, Sections 4.2.1 and 8.3.

4.3 Instrumented System The impact machine shall be equipped with a "Dynatup" strain-gaged instrumented tup, signal conditioning unit, and data storage unit suitable for recording both load and energy vs. time behavior.

4.4 Temperature conditioning The temperature conditioning aspects of the impact test s'.iall be done in conformance with ASTM Methods E23-72 section 8.2 and Methods A370-77 section 21.3.

The temperature chamber shall be of liquid immersion type. The device used to measure the temperature of the bath shall be placed near the center of a group of the specimens. The fluid shall be agitated continuously. The temperature chambers shall have a grid raised at least 1" from the bottom upon which the specimens shall rest. The fluid shall be of sufficient depth so that the specimens when immersed shall be covered by at least 1".

~

F-5 PPoctoVRE No. LRC-TP-80'_

rAos No.

4

(

RESEARCH AND DEVELOPMENT DIVISION 12/1 1'78 TECHNICAL PROCEDURE DATE 4.4.1 Low Temperature Testing For testing at temperatures between -196C and room temperature, the chamber must be capable of providing the nominal test temperature to within +0 and -1.5C (+0 and -3F).

4.4.2 High Temperature Testing For testing at temperatures between room temperature and 260C, the chamber must be capable of providing the nominal test temperature to within +1.5C and -0 (+3F and 0).

4.5 Temperature Measurement The temperature of the immersion baths shall be measured with industrial grade ASTM mercury-in-glass thermometers.

4.6 Lateral Expansion Measurement Lateral expansion of the specimen after impact shall be measured with a dial indicator rigidly mounted to a fixture. The fixture shall provide reference supports for locating the broken specimen halves properly with respect to the dial indicator. The dial indicator shall be equipped with a flat anvil to provide proper contact with the specimen. This device shall conform to ASTM Method A370-77 Section 23.2.3.1.

4.7 Percent Shear Fracture Determination Should the percent shear fracture be detemined according to ASTM Method A370-77 Section 23.2.2.1, Me%a i, the dth and height of I

the f racture surface shall be v..e *. ed th a di.2 caliper.

F-6 PRoCEoORE No.LRC-TP-80 PAGE No.

5

RESEARCH AND DEVELOPMENT DIVISl!N 12/12/78 TECHNICAL PROCEDURE DATE 5.

Inspections and Calibrations 5.1 Impact Machine 5.1.1 Initial Inspection The impact machine shall conform to ASTM Methods E23-72, Sections 4 and 5 at the time of installation. These speci-fications and tolerances need not be inspected periodically unless the machine is disassembled, fails to indicate the proper energies when checked against standardized Watertown specimens, or is suspected of a deviation for any other reason.

5.1.2 Annual Calibration Check The accuracy of the impact machine shall be checked against standardized specimens from the Army Materials and Mechanics Research Center (Watertown) at least annually. Should the machine be moved, repaired, adjusted, or should there exist any reason to doubt the accuracy of the results, then it shall be checked against Watertown specimens immediately, without regard to the time interval. This paragraph conforms to ASTM Method E23-72, Sections 6 and 11.

5.1.3 Daily Check At least once daily, the machine shall be checked by a free sving of the pendulum. With the indicator at the initial position, a free swing of the pendulum shall indicate zero energy. This paragraph conforms to ASTM Methods E23-72 Section 8.1.

A second daily check may be mandated by the R&D Project Leader. An aluminum calibration specimen may be tested at room temperature in a manner otherwise identical to that l

used for subsequent tests.

t F-7 rnoccount No. LRC-TP-80_

PAoE No.

g

h RESEARCH AND DEVELOPMENT DIVISH3N J

TECHfdCAL PROCEDURE 1/27/81 DATE 5.2 Instrumented System The data storage unit (s) of the instrumented impact system shall be calibrated at least annually against standards traceable to the National Bureau of Standards (NBS). The system as a whole will be checked by the comparison of the energy value as recorded by the instrumented system with that as indicated on the impact machine.

This shall be done on a random basis, at least once daily.

5.3 Temperature Measurement The thermometer used for temperature measurement shall be calibrated R

against standards traceable to the NBS within 3 months prior to the' test.

5.4 Lateral Expansion Measurement The dial indicator used for the measurement of lateral expansion shall be calibrated at least annually against standards traceable to the NBS.

5.5 Percent Shear Fracture Determination Should a dial caliper be used in the determination of percent shear fracture, it shall be calibrated at least annually against standards traceable to the NBS.

i

\\

i l

F-8 PRoCEoURE No. LRC-TP-80 PAGE NO.

7

-AESEARCH AND DEVELOPMENT DIVist!N 1/27/81 TECHTJICAL PROCEDURE DATE 6.

Test Procedure 6.1 Temperature The nominal test temperature for each test shall be designated by the LRC project leader. Specimens shall remain immersed in the liquid medium for not less than 5 minutes at low temperatures (less than room temperature) and not less than 10 minutes at high temperatures (greater than room temperature). This paragraph is in conformance with ASTM Method E23-72, Section 8.2 and Method A370-77, Section 21.3.

6.2 Placement of Specimens Self-centering tongs shall be used in order to assure alignment of the specimen within the machine anvils. The specimen-gripping portion of the tongs shall be cooled or heated with the specimens, This except when transferring the specimen into the test machine.

paragraph is in conformance with ASTM Method E23-72, Sections 8.2 and 8.3 and Method A370-77, Section 21.3.5.

6.3 Preparation of the Machine The pendulum shall be placed in its latched position. The energy R

indicator shall be set at its maximum energy position. The "Dynatup" instrumented system and the computer data acquisition system shall be prepared to receive data.

6.4 Operation of the Test The specimen shall be removed from the immersion bath with the tongs and centered between the machine's anvils. The pendulum shall then be released from its latched position. This entire operation shall be completed within 5 seconds. The preceding operational sequence conforms to ASTM Method E23-72, Section 8.4.1.

Should the specimen fail to break,or jam in the machine, the procedure as outlined in ASTM Method E23-72, Sections 8.4.3 or 8.4.4 shall be followed.

To prevent recording an erroneous value caused by jarring the indicator when locking the pendulum in its upright position, the energy value shall be read f rom the indicator prior to locking the pendulum for the next test.

The preceding sentence is in conformance with ASTM Fethod E23-72, Section 8.4.5.

F-9 rnoctount No. LRC-TP-80 PAoE NO.

g

RESEARCH AND DEVELOPMENT DIVISION j

TECHNICAL PROCEDURE DATE 7.

Analysis Procedure 7.1 Impact Energy The Charpy Impact Energy shall be read to the nearest interger as indicated on the Charpy machine's energy indicator. The maximum B

energy signal on the oscilloscope (E,, ) shall be read to the nearest determinable value.

7.2 Determination of Lateral Expansion Lateral expansion shall be measured according to ASTM Method A370-77, Section 23.2.3.1.

The following is a synopsis of that section:

1i l

The broken specimen halves shall be retrieved and cleared of any I

burrs which may exist on the surface, other than the protrusions to be measured. The specimen halves shall be measured by individually placing them against the reference supports, with the protrusion against the gage anvil. Two measurements shall be made on each specimen half: one measurement on each side. The larger of the two measurements corresponding to a given specimen side is the expansion of that side of the specimen. Total lateral expansion is the sum of the larger measurtaents for the two sides.

7.3 Determination of Percent Shear Fracture The determination of percent shear fracture shall be done in accordance with either Method (1) or (2) of ASTM Methods A370-77 Section 23.2.2.1.

Method (1) involves the use of dial caliper in the measurement of either specimen half's fracture surface as shown in Figure 14 of Method A370-77. The measurements shall be used in conjunction with Table 4 of Method A370-77 to find the percent shear fracture. Method (2) involves the comparison of j

the appearance of the fracture surface with the comparator chart, Figure 14 of Method' A370-77. The choice of Method (1) or (2) shall be made by the LRC project leader on an individual specimen basis.

F-10 rnocEoURC No.LRC-TP-80 PAGE NO.

1Q 1

RESEARCH AND DEVELOPMENT DIVISION

!I !

TECHNICAL PROCEDURE DATE 1

7.4 Test Report The test report shall be as shown in Figure 7.1 "Charpy Impact Test Record". This report shall include those results called for in ASDi Methods A370-77 Section 23.3 and ASH 1 Methods E23-72 Sections 10.1.4, 10.1.5, 10.1.6, and 10.1.7.

The remaining information requested in ASTM Methods E23-72, Section 10 has been omitted from the test report as it is either superfluous or available elsewhere in the procedure.

F-il rRocEDURE NO.LRC-TP-80 PAos No.