ML20080G335

From kanterella
Jump to navigation Jump to search

Forwards Response to NRC 941117 RAI Re Thermo-Lag Related to Ampacity Derating Issues
ML20080G335
Person / Time
Site: Prairie Island  
Issue date: 01/31/1995
From: Wadley M
NORTHERN STATES POWER CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
GL-92-08, GL-92-8, TAC-M85592, TAC-M85593, NUDOCS 9502070192
Download: ML20080G335 (15)


Text

T l

p sz

==

g Northem States Power Company Prairie Island Nuclear Generating Plant 1717 Wakonade Dr. East Welch, Minnesota 55089 January 31, 1995 Generic Letter 92-08 US Nuclear Regulatory Commission Attn:

Document Control Desk Washington, DC 20555 PRAIRIE IS1AND NUCLEAR GENERATING PIANT Docket Nos. 50-282 License Nos. DPR-42 50-306 DPR-60 Response to the November 17, 1994 Request for Additional Information Regarding Thermo-Lag Related Ampacity Derating Issues (TAC Nos. M85592 and M85593)

In a letter dated November 17, 1994, the Nuclear Regulatory Commission (NRC) has transmitted a Request for Additional Information (RAI) Regarding Thermo-Lag Related Ampacity Derating Issues for Prairie Island Nuclear Generating Plant.

This letter provides NSP's response (see Attachment 1) to the first 12 concerns expressed in the RAI. As discussed in our letter to the NRC of December 21, 1994, we will respond to the remaining concerns by the end of June 1995.

We are planning to replace all Thermo-Lag material at Prairie Island with a qualified alternate material. The derating factors will be based on that new material. We intend to confirm these plans within 2 months.

Because of the likelihood of replacement and subsequent recalculation of ampacity deratings, you may choose not to review the response which we are providing with this letter. We will keep you informed of our plans.

In this letter we have made no new NRC commitments.

l$f

[$[

9502070192 950131 Q, A d. N

) $ @ 9 4

.v:onc, PDR N gfj I

P ADOCK 05000282 PDR qt

i

~

NORTHERN STATES POWER COMPANY US NRC January 31, 1995 Page 2 Please contact Jack Leve111e (612-388-1121, Ext. 4662) if you require further information, j])?ly4esA4 5E

/

Michael D Wadley Plant Manager Prairio Island Nuclear Generating Plant cc:

Regional Administrator - Region III, NRC NRR Project Manager, NRC Senior Resident Inspector, NRC Kris Sanda, State of Minnesota Attachments: (1) Response to Ampacity Derating Issues (Concerns 1 - 12)

(2) Affidavit i

f i

t I

I 3192-08.5

Response to Ampacity Derating Issues (Concerns 1 - 12)

General Calculation Approach snd Methodology The calculation approach used simplified heat transfer methodology to calculate the ability of fire wrap to transfer and reject heat to the ambient.

Analysis of each individual cable loading was used to estimate the heat being generated inside the wrapped section.

The rate of heat transfer across the fire wrap and the heat rejection from the wrapped tray to the ambient environment are then used to predict the temperature rise across the wrap and the resulting steady state temperature within the wrapped section of tray.

The estimated steady state temperature inside the fire wrap is then used to derate the enclosed cables per industry standards to the new calculated steady state temperature.

The assumptions and calculations are then validated by correlation with field test results.

ASHRAE methodology was selected since the problem and characteristics of the type of material used to wrap the tray is similar to that encountered and are well documented by this organization.

The calculations supporting the report are based on the simplifying assumption that the entire envelope within the wrapped tray will reach a uniform steady state temperature wi*h a minimal temperature gradient across the enclosed tray section.

(Reference paragraph 4, on page 3-2 of the study.) The heat transfer mechanism out of the enclosed envelope considered in the supporting calculations is assumed to be via conduction through the fire wrap, and via convection and radiation at the surface boundaries of the fire wrap.

This assumption is justified for several reasons:

a.

The thermal resistance of the fire wrap is large (8 Hr(Ft')(*F)/ BTU) with respect to other thermal resistances in the system such as the wrap to air boundary resistances (0.765 Hr(Ft')(*F)/ BTU), metallic tray, and metallic cable armor.

This large thermal resistance effectively isolates the inner envelope from the outer environment. This thermal isolation allows consideration of the inner envelope as a uniform isolated system.

b.

High thermal conductivity of metallic cable tray and the metallic cable armor contributes to minimizing temperature gradients within the wrapped section.

Partial direct contact between the armored cables and the Kaowool will also contribute to a relatively uniform ambient temperature at equilibriuN. inside the wrapped

tray, c.

The tests used to validate the calculations monitored the ambient temperature outside the tray and the surface temperature on the jacket of the cable in the tray with the dominant heat release.

This test.ng validated that the calculation techniques were within g192-08.5

Page 2 of 12 reasonable accuracy, and demonstrated that more rigorous calculations accounting for heat transfer mechanisms within the enclosed section were not necessary.

Roanonses to Concerns The following section responds to each area of concern identified by the NRC.

The response numbering corresponds to the numbering in the NRC letter.

Each concern contained in the RAI has been briefly restated with our response following.

1.

Applicability of ICEA P-46-426 Ampacity Tables Comment The ICEA P-46-426 ampacity tables " apply specifically to cables where significant air gaps are maintained between the cables such that even in a "still" ambient environment significant convective buoyancy driven air flow currents will develop in the vicinity of the cables and cable tray."

Response

As discussed in the General Calculation Approach and Methodology section, the calculation methodology is based on the assumption that the entire envelope within the wrapped tray from the cable jacket to the fire wrap will reach a uniform steady state temperature.

This method is more conservative than the ICEA standard. As noted in the staff comments, the ICEA standard relies on convective cooling of the cables.

This type of a cooling process requires that the jacket temperature of the cables be higher than the ambient temperature.

Thus the ampacity values determined from ICEA result in a jacket steady state operating temperature higher than the ambient temperature around the cable.

The model used in the report assumes that once the system is in equilibrium, tl.e temperature of the cable jacket will be the same as the ambient.

The cables are then derated accordingly. Therefore, analytical consideration of the convective driven air currents is not deemed necessary.

Note that consistent with this approach, the validating testing monitored the ambient temperature outside the tray and the surface temperature on the jacket of the cable.

2.

Maintained Spacine Correction Factors Comment Cable ampacity ratings from ICEA P-46-426 are based on 1/4 to 1 diameter maintained cable spacing.

This spacing is not consistent with typical cable installation practices in tray.

S192-06.5

Page 3 of 12

Response

The use of the correction factors associated with

" maintained" spacing is appropriate.

PINGP installation standards require maintained spacing and a single layer of cables in all power cable trays. USAR Section 8.7.1 states "the cables are clamped in the ladder to ensure a specified spacing exists...".

The Fluor Power Services Field Standards Nos. 13 and 14 used during construction of the plant delineate the spacing required.

The current PINGP Field Standards for electrical installation (STD 1.21.VI Rui. Orig Note 4) also requires similar spacing distance between cables.

The spacing required by these installation standards meets the 1/4 to 1 cable diameter spacing required by the ICEA Standard to use the " maintained spacing" derating factors.

3.

Four Sides in Heat Transfer Analysis Comment The Stone & Webster analysis assumes that heat transfer is equally effective from all four sides of the barrier.

Response

Based on the calculation assumptions, effective heat transfer will exist at all four sides of the barrier, and the calculation is conservative.

Consideration of heat transfer through the sides of the fire wrap is consistent with the assumption that components inside the wrapped section of the tray will reach a uniform equilibrium temperature as discussed in the General Calculation Approach and Methodology section. Under steady state conditions, heat transfer will occur through all boundaries of the tray section. The supporting calculations used the same heat transfer factor through all faces of the tray.

This factor was the average for horizontal up and horizontal down surfaces. Use of this factor is analytically accurate for the top and bottom surfaces of the section, and conservative for the side sections. The ability of vertical surfaces to remove heat is greater than the average of horizontal up and horizontal down surfaces.

Comment An isolating air gap between the cable tray side rails and the fire barrier will impede heat flow.

i

Response

For the reasons discussed in the General Calculation Approach and Methodology section, the uniform steady state conditions assumed in the model preclude the need to account for detailed internal heat transfer mechanisms. Test results validate this approach.

3192-08.5

Page 4 of 12 4.

ASHRAE Correlations Comment The " efficiency of the convective heat transfer in a confined space is significantly lower than that which takes place in an open environment.

The ASHRAE correlations do not account for this behavior."

Response

The study did not assume or specifically take credit for any convective heat transfer within the wrapped envelope.

For the reasons discussed in the General Calculation Approach and Methodology section, the uniform steady state conditions assumed in the model preclude the need to account for detailed internal heat transfer mechanisms. Test results validate this approach.

Comment The Stone & Webster calculation methodology assumes that radiative heat transfer within the protected envelope takes place from the cables to the air and then from the air to the fire barrier.

In reality, the primary mechanism for radiative exchange is direct transfer from the cable to the barrier."

Response

The study did not assume or specifically take credit for

" radiative heat transfer place from the cables to the air and then from the air to the fire barrier.

For the reasons discussed in the General Calculation Approach and Methodology section, the uniform steady state conditions assumed in the model preclude the need to account for detailed internal heat transfer mechanisms. Test results validate this approach.

5.

Marinite Board Comment The effects of the Marinite board are neglected in the Stone

& Webster study.

Response

The configuration using Marinite board was considered as a possibility in preliminary phases of the study. However, NSP decided not to use this configuration, thus detailed derate analysis did not need to account for it.

6.

Zetex or Foil Coverines Comment The effects of "special coverings such as foil or Zetex are neglected" in the Stone & Webster study.

Response

The configuration using special coverings such as foil or Zetex was considered as a possibility in preliminary phases of the study. However, NSP decided not to use this sis 2-os.s

r Attactment 1 Page 5 of 12 configuration, thus det. led derate analysis did not need to account for it.

7.

Calculation Errors Comment The column headings for 1-hour and 3-hour barrier systems are reversed.

Response

The column headings for the M20R 1-hour and 3-hour barriers 1

- are not reversed. The column heading for the 1-hour 3M barrier is correct.

The data for the 3-hour barrier is in error. This error was discovered in September 1983 and the supporting calculation was corrected.

The error results in a one to three *C error.

This represents less than a 5%

error in the tray derating values.

Since NSP did not use the 3M product, the error had no impact.

Comment Using the values in the report, the calculated value of the "U"

factor for Kaowool differs significantly from the value used by Stone & Webster in the study.

Response

The table on page 3-3 of the report has two errors.

Both errors are typographical in nature, resulting from the conversion of information from the supporting calculations to the report.

In both bases the correct numbers were used in the supporting calculations, and therefore these errors l

do not affect the results or conclusions presented in the report.

First, the table on page 3-3 correctly identifies a 1-hour Kaowool barrier as two inches in thickness (2 one-inch J

wraps); however, the corresponding thermal resistivity listed is for a single wrap (1 one-inch wrap) of Kaowool.

The correct thermal resistivity value for two wraps is 8 Hr(Ft') (" F)/ BTU. Using the correct thermal resistivity, the j

correct "U" factor of 0.05535 W/ft'/*C can be calculated.

The correct "U" factor of 0.05535 W/ft'/'C was used in all applicable calculations.

Secondly, the U value listed in Table 2 of the study is

)

0.05532 W/ft'/'C.

The correct value and the value used in the supporting calculations was 0.05535 W/f t'/*C.

8.

Zero Ampere Values Comment Provide further clarification of conductor currents listed in Tables 4 and 5 with zero ampere values.

g192-08.5 8

\\

Fase 6 of 12

)

Response

The loads listed in the tables as having zero amps are cables servicing equipment, such as motor operated valves.

Motor operated valves can be identified in Tables 4 and 5 by the equipment number prefix MV included in the service column. This assumption is valid since motor operated valves in power plants have infrequent limited duty cycles.

These cables will only be energized during opening or closing operations.

Cycle time of motor operated valves ranges from several seconds to several minutes. These intermittent and infrequent loads have negligible impact on the ultimate steady state temperature of a wrapped tray system.

9.

Control Cable Ampacity Comment The analysis cites an average conductor current of.79 amperes and a total heat gain of 0.57 watts per foot.

The subject analysis does not reflect an estimate of load diversity of the cables in the subject tray.

Estimates of heat release based on a single (average) are likely to underestimate the heat generation. An alternate method is to calculate a representative current based on the square root of the sum of the squares.

Response

Consideration of each control cable in the subject tray was performed as part of the supporting calculation.

The 0.79 ampere value is not an arithmetic average, but rather the square root of the sum of the squares of the estimated current in each conductor of each cable in the tray.

This methodology resulted in the.57 watts /ft. average reported in the study. The resulting heat gain calculation is conservative in that each cable was evaluated to determine the service, an estimate of current was developed for each type service, and the estimated current was assumed to be continuous in every conductor in every cable.

The estimated currents for each type of service are documented in the report on page 3-5.

In addition to the conservatism resulting from neglecting conductor duty cycle, each cable typically has one or more spare conductors which will have zero current. Also, many control cables typically contain conductors for red and green indicating lights and only one or the other will be illuminated at any one time.

Conductors serving motor operated valve open and close coils also have a very limited duty cycle as described in the response to comment 8.

The heat load for each cable was calculated by summing the 15dl for each cable. The average current corresponding to this heat release is 0.79 amperes per conductor.

This number is provided for information only and was not used as an input or value in any calculations.

s192-08.5

Page 7 of 12 The detailed tray analysis and analysis are documented in Stone & Webster Calculation 12911.23-E-4.

10. Charrine Pumo Feeder Test Results Comment Page 4-3 of the report notes that in order to compare measured temperatures to the predicted temperatures, the predicted temperatures must be adjusted to the conditions existing at the time of the survey.

Since the predicted values are based on full load operation of all equipment served by the tray, only the equipment in service at the time of the test should be considered in the comparison calculations. The report also states that all other feeders in the trays are assumed to be out of service since they serve safeguards equipment (i.e. RHR pumps, SI pumps, MOVs, and containment spray pumps).

In the report, only the analysis for tray LAG-LA30 assumed all other loads were out of service during the test.

For the other trays, the other loads must be set to zero in order to properly compare the predicted current values with the measured current values.

Response

All testing was done during full power operation.

The assumption on page 4-3 of the report that the RHR pumps, SI pumps, MOVs, and containment spray pumps are out of service is valid during full power operation.

The statement that

"...all other feeders in the trays being studied are assumed to be out of service" is not accurate. This statement should address only the equipment identified above (RHR pumps, SI pumps, MOVs, and containment spray pumps). The assumption that all other cables were out of service, as stated in the report, is caly applicable to only tray 1AG-LA30.

Each of the other two trays, 2AG-LB5 and 2AG-LB8, were modified to include cables serving a component cooling water pump and two cooling fans.

These loads operate continuously during power operation and should be considered in making a comparison of the field results to the calculated values of temperature rise. The revised comparison of the measured and predicted values is as follows:

Measured Revised Original Temperature Calculated Calculated Tray ID Rise Temp Rise Temp Rise 1AG-LA30 35 'F 39 'F 39 'F 2AG-LES 26 'F 28 'F 38 'F 2AG-128 23 'F 33 'F 26 'F s192-08.$

+

Attactment 1 Pass 8 of 12 Based on this adjustment, and the clarification of the U value per comment 7, the predicted temperature and the measured temperature rises still correlate to the measured temperatures.

In all cases, the measured versus the predicted temperature differences are conservative.

(Comparison spreadsheets are attached to this response calculating these values.)

11. Diesel Generator Feeder Trav Test Results Comment Main diesel generator power feed cable testing was not completed. After fifteen hours, temperatures inside were still rising.

The testing concluded that the cable was undersized for this application.

Response

Section 4.3 of the study presents the results of the Diesel Generator Feeder Tray Test.

The results do not claim to validate the thermal model since the test was terminated prior to achieving a steady state temperature.

i The report documents the observed rate of temperature rise l

for this tray and compares it to that predicted by the model.

This predicted and observed temperature rise correlation is presented in the report for information but does not influence or change the results or conclusions.

This information, together with the model's steady state temperature prediction, was used to verify that the i

generator cable as installed did not have adequate margin to I

operate in the elevated ambient temperature inside a 1-hour Kaowool fire wrap.

Informal calculations prior to the test indicated that the maximum allowable ambient temperature for this cable to operate at full power was 61 'C.

This translates to a maximum allowable temperature rise of 21 *C (38 'F) for this cable. The test was terminated when it j

became clear that this temperature would be exceeded in both i

trays.

Kaowool was subsequently replaced with a Thermo-Lag configuration.

12. Control Tray Test Results Comment It is not clear to what extent the concerns of comment 7 affect the test results.

Response

Comment 7 concerns have been addressed and resolved in the response to comment 7 and do not affect the test results presented for the control trays.

Comment Apparently a different U value was used in the calculations.

s192-08.5

AttacInnit 1 Page 9 of 12

Response

The control tray used in the test LAM-TA9 is a 30" tray.

The per square foot "U" value used for this tray is the same as was used for all of the other trays.

The associated area results in dissipation value of 0.30448 Watts /*C per linear foot of 30 inch tray.

Comment Detailed calculations are not tabulated for the control power trays in the same manner as cited for the power cable applications. Additional detailed information should be provided on actual loads present in the tray at the time of the test.

Response

As identifies in response 7, a detailed tabulation and heat release calculation is provided in the supporting calculation for this tray.

Actual loads in control trays (444 individual conductors) are extremely difficult to measure or predict.

For control trays, the calculation methodology is intended to develop a bounding case limit, and the test is intended to demonstrate that actual conditions are well below the bounding conditions.

s192-08.5

JAG.tA30 Agg.ctanent 1 page 10 of 12 From Study, Table 5, Page 1 of 29 TRAY 1AG-1A30 TRAY LOSS FACTOR 0.13640 cau.

CeNe FLA Chms/Ft Watts /Ft 1K1-3 W

0.00 2.60E-03 0.00000 1Ki-4 MV 0.00 3.90E-03 0.00000 1K1-11 MV 0.00 3.90E 03 0.00000 IK1-14 MV 0.00 3.90E43 0.00000 1K1-21 CHARGING PUMP 134.00 3.90E-04 7.00643 1K1-26 MV 0.00 3.90E-03 0.00000 tKi 33 MV 0.00 3.90E-03 0.00000 HEAT GENERATED 7.00643 Watts /Ft DELTA TEMP 50.62450 C

DELTA TEMP 91.12411 F

Adjusted to test conditions TRAY 2AG.LB5 TRAYLDSS FACTOR 0.13840 CaMe CaWe FLA Ohms /Ft WattsfFt 1K1-3 W

0.00 2A0E43 0A0000 1K14 W

0.00 3.90E-03 0.00000 1Ki-11 MV 0.00 3.90E43 0.00000 1K1-14 W

0.00 3.90E-03 0A0000 l

1Ki-21 CHARGING PUMP 88.00 3.00E-04 3.02171 1K126 MV 0.00 3.90E-03 0.00000 1K1-33 MV 0.00 3.90E43 0.00000 HEAT GENERATED 3.02171 Watts /Ft DELTA TEMP 21.83316 C

DELTA TEMP 3929966 F

5192-08.$

2AG4BS Page 11 of 12 From Study, Table 5, Page 17 of 29 TRAY 2AG4B5 TRAY LOSS FACTOR 0.30448 Cable

)

Cdde FLA ChmsEt WattrJFt j

i 2DCB 34 2 SOVS 4D0 2.60E-03 0.04160 2HVB-16 COOUNG FANS 3.00 3.90E-03 0.03510 2HVB-33 COOUNG FANS 2.50 3.90E-03 0.02438 2KA2-3 MV 0.00 3.90E43 0.00000 2K2-1 MV 0.00 3.90E43 0.00000 i

2K2,2 MV 0.00 3.90E-03 0.00000 2K2-4 CHARGING PUMP 152.00 3.90E 04 9.01518 2K2-8 MV 0.00 3.9CE-03 0.00000

(

2K2-7 MV 0.00 3.90E-03 0.00000 25403-1 COMPONENT COOUNG PUMP 32.20 1.54E-03 1.59414 25404-1 RHR PUMP 25.00 1.54E 03 0.96094 26406-1 St PUMP 100.00 8.14E-04 6.13000 i

25409-1 CSPUMP 32.80 1.54E43 1.65410 l

HEAT GENERATED 19.46144 Watts /Ft DELTA TEMP 63.91697 C

DELTA TEMP 115.05054 F

1 l

Adjusted to test conditions TRAY 2AG4B5 TRAY LOSS FACTOR 0.30448 Cable FLA OhmsEt Watts /Ft Catdo 2DCS-34 2-SOVS 4.00 2.60E 03 0.04160 2HVB-16 COOUNG FANS 3hD 3.90E-03 0.03510 2NVB-33 COOUNG FANS 2.60 3.90E-03 0.02438 2KA2 3 MV OD0 3.90E 03 0.00000 2K2-1 MV 0.00 3.90E43 0.00000 2M2 2 MV ODO 3.90E43 0.00000 2K24 CHARGING PUMP 88.00 3.90544 3.02171 2K24 MV 0.00 3.90E 03 0.00000 2KM MV 0.00 3.90E-03 0.00000 26403-1 COMPONENT COOUNG PUMP 32.20 1.54E 03 1.59414 25404-1 RHR PUMP 0.00 1.54E-03 0.00000 25405-1 St PUMP 0.00 8.14E44 0.00000 25409-1 CS PUMP 0.00 1.54E-03 0.00000 HEAT GENERATED 4.71693 Watts /Ft DELTATEMP 15.49174 C

DELTA TEMP 27.88513 F

$192-06.S

d 2AG4E8 Attechment, 1 Page 12 of 12 From Study, Table 5, Page 19 Of 29 TRAY 2AGJ.B8 TRAY LOSS FACTOR 0.2(912 Cable CaWe FLA Otwns/Pt Watts /Ft 2DCB,34 2 SOVS 4.00 2.60E43 0.04100 2HVS-18 COOUNG FANS 3.00 3.90E43 0.03510 2HVB 33 COOL 940 FAHS 2.50 3.90E-03 0.02436 2KA23 MV 0.00 3.90E-03 0.00000 1

2K2-2 MV 0.00 3.90E-03 0.00000 2K2-4 CHARGtNG PUMP 152.00 3.90E-04 9.01518 f

2K2-7 MV 0.00 3.90E-03 0.00000 25403-1 COMPONENT COOUNG PUMP 32.20 1.54E-03 1.59414 HEAT GEMERATED 10.71040 Watts /Ft DELTA TEMP 42.99292 C

DELTA TEMP 77.38726 F

A(usted to test conditions TRAY 2AG-LB6 TRAY LOSS FACTOR 0.24912 2DCB-34 2-SOVS 4.00 2.60E-03 0.04150 l

2HVB-18 COOUNG FANS 3.00 3.90E-03 0.03510 2HVB-33 COOUNG FANS 2.50 3.90E 43 0.02438 2KA2-3 MV 0.00 3.90E-03 0.00000 2K2-2 MV o.00 3.90E43 0.00000 2K24 CHARGING PUMP 88.00 3.90E-04 3.02171 2K2-7 MV 0.00 3.90E-03 0.00000 25403-1 COMPONENT COOUNG PUMP 3220 1.545-03 1.69414 25405-1 St PUMP 0.00 6.14E-04 0.00000 25409-1 CS PUMP 0.00 1.54E-03 0.00000 HEAT CENERATED 4.61565 WattsEt DELTA TEMP 10.52862 C

DELTA TEMP 33.35152 F

i 3102-08.5

AFFIDAVIT UNITED STATES NUCLEAR REGUIATORY COMMISSION NORTHERN STATES POWER COMPANY PRAIRIE ISIAND NUCLEAR CENERATING PIANT DOCKET NO. 50-282 50-306 THERMO-LAG 330-1 FIRE BARRIERS Northern States Power Company, a Minnesota corporation, with this letter is submitting information requested by Generic Letter 92-08, Thermo-Lag 330-1 Fire Barriers, pursuant to 10 CFR 50.54(f).

This letter contains no restricted or other defense information.

NORTHERN STATES POWER COMPANY By

' Michael D Wadley Plant Manager Prairie Island Nuclear Generating Plant On this h d ay of

_ /97[before me a notary public in and for said County, personally Uppeared ichael D Wadley, Plant Manager of Prairie Island Nuclear Generating Plant and being first duly sworn acknowledged that he is authorized to execute this document on behalf of Northern States Power Company, that he knows the contents thereof, and that to the best of his knowledge, informsti;n, and belief the statements made in it are true and that it is not inter os d or de y.

dd

, -^^ ^^:.::::^::::::::::::::- :: y a MARCIA K. LaCORE NOTARY PUBUC MINNESOTA l

HENNEPN COUNTY

t Wy Commmien Expres Jan. 31,2000 w-
: :::. :: ::::::::::::::::::: :: a s

s192-08.5

-