F p Stug
{
{,
g Q
UNITED STATES
{)
g NUCLEAR REGULATORY COMMISSION C
l WASHINGTON, D. C. 20555
%..... #o February 4,1982
~
MEMORANDUM FOR:
H. Denton i
J. Carter D. Eisenhut R. Purple T. Novak G. Lainas R. Tedesco H. Thompson R. Vollmer T. Muiley R. Mattson T. Ippolito J. Sniezek C. Mic.helson C. J. Heltemes THRU:
Dennis M. Crutchfield, Chief Operating Reactors Branch #5, D FROM:
James E. Lyons, Project Manager Operating Reactors Branch #5, DL
SUBJECT:
DAILY HIGHLIGHT - R. E. GINNA The ruptured tube in the Ginna steam generator was inspected in May 1981.
The ECT results showed that there was 20% penetration (an OD signal) 3 to 6 in, above the tubesheet. The failed tube is in row 42, column 55 which is near the periphery of steam generator.
It.is located in the " wedge area" of the steam generator. This is the section of the support plates that does not have flow holes. Three of the six previous small leaks that have been experienced have been in that area.
There is no sludge pile in that area.
N S/
w W
l Janl.es E. Lyons, Pro ecJ Manager l
x Opeiating Reactors Branch #5
' Division of Licensing
,5 l
l
~
U1OO70038 820010 l
l POR FOIA
.LONOS2-309 PDR
,