ENCLOSURE 1
)
NUCLEAR REGULATORY COMMISSION In the Matter of
)
)
DUQUESNE LIGHT COMPANY
)
Docket No. 50-334 OHIO EDIS0N COMPANY
)
PENNSYLVANIA POWER COMPANY
)
)
i-(BeaverValleyPowerStation,
)
Unit No. 1)
)
EXEMPTION I.
The Duquesne Light Company, Ohio Edison Cs mpany, and Pennsylvania Power 1
l Company (the licensees), are holders of Facility Operating License No. DPR-66 which authorizes operation of the Beaver Vally Power Station, Unit No.1.
i t
i The license provides, among other things, that it is subject to all rules, regulations and Orders of the Commission now or hereafter in effect.
l The facility comprises a pressurized water reactor at the licensee's site located in Beaver County, Pennsylvania.
II.
f>
On November 19, 1980, the Commission published a revised Section 10 CFR 50.48 and a new Appendix R to 10 CFR 50 rcgarding fire protection features of i
nuclear power plants (45 F.R. 76602). The revised Section 50.48 and Appendix R became effective on February 17, 1981. Section 50.48(c) establishing the schedules for satisfying the provisions of Appendix R.
Section III of Appendix R contains fifteen subscriptions, lettered A through 0), each of which specifies requirements for a particular aspect of the fire protection features at a nuclear power plant. One of these fifteen subsections III.G., is the subject of this exemption request.
III.G. specifies detailed requirements for fire 820 5180 0 6 Y
~
I
. - ~ ~
...~
}
7590-01 l
4 protection of th equipment used for safe shutdown by means of separation and barriers (III.G.2). If the requirements for separation and barriers could not u
be met in an area, alternative safe shutdown capability, independent of that area and equipment in that area, was required (III.G.3.).
Section 50.48(c) required completion of all modifications to meet the provisions of Appendix R within a specified time from the effective date of this fire protection rule, February 17, 1981, except for modifications to provide alternative safe shutdown capability. These latter modifications (III..G.3) require NRC review and approval. Hence, Section 50.48(c) requires their completion within a certain time after NRC approval. The date for submittal of design descriptions of any modifications to provide alternative i
i i
safe shutdown capability was specified as March 19, 1981.
}
By letter dated March 18, 1981, as amended December 1,1981, and i
i January 20, 1982 Duquesne Light Company requested exemptions from 10 CFR I
t 50.48(c) with respect to thf requirements of Section III.G of Appendix R as 1
follows :
(1) that the date in paragraph (c) (5) for submitting plans and schedules for meeting the provisions of paragraphs (c) (2),
(c) (3) and (c) (4) with respect to certain requirements of Sections III.G of Appendix R to Part 50 be extended to July 1, 1
1982.
h (2) that the date in paragraph (c) (5) for submf tting design descriptions
'))
of modifications needed to satisfy Section III.G.3 of Appendix R i
be extended to July 1,1982.
'Y l
___._m 7590-01 j
1 3-
- )
(3) that the implementation date in paragraph (c) (2) for installation of modifications required by Section III.G.2 of Appendix R, that
-i do not require prior NRC approval or plant shutdown, be extended to nine months after July 1,1982.
(4) that the implementation date in paragraph (c) (3) for the
.1
- }
install-tion of modifications required by Section III.G.2 of Appendix R, that do not require prior NRC approval, but require plant shutdown, be extended to the third scheduled refueling outage.
When this Fire Protection Rule was approved by the Commission, it was understood that the time required for each licensee to re-examine those previously-approved configurations at its plant to determine whether they meet the requirements of Section III.G of Appendix R to 10 CFR 50 was not For well known and would vary depending upon the degree of conformance.
each item of non-conformance that was found, a fire hazards analysis had to be performed to determine whether the existing ccnfiguration provided sufficient fire protection. If it did, a basis had to be formulated for an exemption If it did not, modifications to either meet the requirements of request.
Appendix R or to provide some other acceptable configuration, that could be justified for an exemption, had to be designed. Where fire protection 3
f features alone could not ensure proection of safe shutdown capability, il alternate safe shutdown capability had to be designad as required by Section III.G.3 of Appendix R.
Depending upon the extensiveness and number of the i
areas involved, the time required for this re-examination, reanalysis and i.I
7590-01 J
. ]
redesign could vary from a few months to a year or more. The Commission decided, however, to require one, short-term date for all ifcensecs in the I
interest of ensuring a best-effort, expedited completion of compliance with the-Fire Proection Rule, recognizing that there would be a number of licensees who could not meet these time restraints but who could then request appropriate relief through the exemptian process. Licensees for 44 of the 72 plants to which Appendix R applies (plants with an operacing license issued prior to January 1,1979) have requested such schedular relief.
The licensees for the remaining 28 plants made submittals to meet the f
schedular requirements of 50.48(c). All of these submittals, however, were deficient in some rer.cects.
In general, much of the infomation requested in a generic letter (81-12) dated February 20, 1981, to the licensees of all
)
72 plants, was not provided. Therefore, additional time is being used to
,s i
complete those submittals also.
III.
Prior to the issuance of Appendix R, the Beaver Valley Power Station, i
Unit No. I had been reviewed against the criteria of Appendix A to the i
Branch Technical Position 9.5-1 (BTP 9.5-1).
The BTP 9.5-1 was developed l
to resolve the lessons learned from the fire at Browns Ferry Nuclear Plant.
1 It is broader in scope than Appendix R, formed the nucleus of the criteria t
developed further in Appendix R and in its present, revised form constitutes the section of the Standard Review Plan used for tne review of applications I
for construction permits and operating licenses of new plants. The review j
i.-
m
....--...~-
7590-01 i
i was completed by the NRC staff and its fire protection consultants and a Fire Protection Safety Evaluation (FPSER) was issued with Amendment 18 to Facilty Operating License No. DPR-66. A few items remain unresolved.
Further discourse between the licensee and the NRC staff result $d in resolution of one of these items as documented in our letter dated December 23, 1980.
By letter dated November 24, 1980, the staff position was documented relative to the specific requirements that must be satisfied in order to resolve the remaining open items and meet the requirements of Appendix R.
The plant modifications specified in the FPSER have now been completed. Therefore, Beaver Valley Power Station, Unit No. I has been upgraded to a high degree J
of fire protection already and the extensive reassessment involved in this request for additional time is to quantify, in detail, the differences between what was recently approved and the specific requirements of Section III.G to Appendix R of 10 CFR 50.
The licensee also stated in the request for exemption that all other l
requirements of the Fire Protection Rule would be met on the schedules required by 10 CFR 50.48. As mentioned earlier there are 14 other subsections l
which contain criteria for other aspects of fire protection features. One of these,Section III.L., provides the criteria for Alternate Safe Shutdown capability and thus affects the final reassessment and redesign, if necessary, o
of this feature at Beaver Valley Power Station, Unit No.1.
Nevertheless,
this means that compliance with the remaining requirements of the Fire Protection Rule have been or will be completed cn or before the implementation dates required by the Rule.
i 4
_... _ _.. _ ~ _
7590-01
. Based on the above considerations, we find that the licensee has completed a substantial part of the fire protection features at Beaver Valley Power Station, Unit No.1, in conformance with the requirements of the Fire Protection Rule and is applying significant effort to ccmplete the reassessment of any remaining modifications which might be necessary for strict conformance with Section III.G. We find that because of the already-completed upgrading of these facilities, there is not undue risk to the health and' safety of the public involved with continued operation until the completion of this reassessment on July 1,1982. Therefore, an exemption should be granted to 1
allow such time for completion. However, because we have found that most submittals of this reanalysis to data from other licensees have not been complete; that is, not all of the information requested by Generic Letter 81-12 dated February 20, 1981, was provided, we are adding a condition to this exemption that requires all such information to be submitted by the i
date granted.
I IV.
Accordingly, the Commission has determined that, pursuant to 10 CFR 50.12, an exemption is authorized by law and will not endanger life or property or the common defense and security and is otherwise in the public interest and hereby grants the following exemptions with respect to the requirements of Section III.G. of Appendix R to 10 CFR 50:
(1) that the date in paragraph (c) (5) for submitting plans and schedules for meeting the provisions of paragraphs (c) (2),
(c) (3) and (c) (4) with respect to certain requirements of i
l.
t
~
.1, 1
7590-01 l Sections III.G of Appendix R to Part 50 be extended to July 1, L
1982.
(2) that the date in paragraph (c) (5) for submitting design descriptions of modifications needed to satisfy Section III.G.3 of Appendix R be extended to July 1,1982.
(3) that the implementation date in paragraph (c) (2) for installation of modifications required by Section III.G.2 of Appen' dix R, that do not require prior NRC approval or plant shutdown, be extended to nine months after July 1,1982.
(4) that the implementation date in paragraph (c) (3) for the j
installation of modifications required by section III.G.2 of i
Appendix R, that do not require prior NRC approval, but require plant shutdown, be extended to the third refueling outage that is presently scheduled for April 1983.
provided the following condition is met:
t The design descriptions of alternative or dedicated shutdown systems to comply with Section III.G.3., as required by 550.48(c)(5) shall include a point-by-point response to each item in Section 8 of to generic letter 81-12 dated February 20,1981 and to each item in Enclosure 2 to Generic Letter 81-12, dated i
February 20, 1981.
If tha licensee does not meet the above condition, the licensee will be found in violation of 10 CFR 50.48(c) even though the subnittal may be made within the time granted by the exemption. If such a violation occurs, imposition of a civil penalty will be considered under Section 234 of the
7590-01
- Atomic Energy Act, as amended. Such a violation will be a continuing one beginning with the date set in the exemption for submittal and terminating when all inadequ are corrected.
A delay in the detennination of inadequacy by the staff, caused by the work-load associated with reviewing all of the submittals falling due near the same time, will not relieve the licensee of the responsbility for complete 1 ness fo the submittal, nor will such delay cause any penalty that I
may be imposed to be mitigated.
The NRC staff has determined that the granting of this exemption will i
l not result in any significant environmental impact and that pursuant to 10 CFR 51.5(d)(4) an environmental impact statement or negative declaration l
i and environmental impact appraisal need not be prepared in connection with 1
this action.
FOR THE NUCLEAR REGULATORY COMMISSION kMPA $
~
Harold R. Denton, Director Office of Nuclear Reactor Regulation Dated at Bethesda, P,aryland this 4th day of May,1982 i
1
tNCLUbUHt 2 t
i CLARIFICATION OF GEllERIC LETTER On February 20, 1981, generic letter 81-12 was forwarded to all reactor licensees The letter restated the require-with plants licensed prior to January 1,1979.
ment of Section 50.48 to 10 CFR Part 50 that each licensee wuuld be required to reassess areas of the plant where cables or equipment including associated non-safety circuits of redundant trains of systems necessary to achieve and maintain hot shutdown conditions are located to detemine whether the require-Additionally, ments of Section III.G.2 of Appendix R to 10 CFR 50 were satisfied. and Enclosure 2 of the generic letter requested additional infomation concerning those areas of the plant requiring alternative shutdown Section 8 of Enclosure 1 requested infomation for the systems,
{j capability.
equiprent and procedures of alternative shutdown capability and Enclosure 2 t
defined associated circuits and requested information concerning associated circuits for those areas requiring alternative shutdown.
In our review of licensee submittals and meetings with licensees, it has become apparent that the request for information should be clarified since a lack i
of clarity could result in the submf ssion of either insufficient or e,xcessive Thus, the staff has rewritten Section 8 of Enclosure 1 and 1-H information.
' of the February 20, 1981 generic letter. Additionally, further clarificatior of the definition of associated circuits has been provided to
]
aid in the reassessments to detemine compliance with the requirements of l.j In developing this' rewrite we ha've Sections III.G.2 and III.G.3 of Appendix R.
The enclosed considered the comment of the Nuclear Utility Fire Protection Group.
3 rewrite of the Enclosures contains no new requirements but merely attempts J
to clarify the request for additional infomation.
,1
- 1 1
~
x.
2 I.
Licensees who have not responded to the February 20, 1981 generic letter, may choose to respond to the enclosed request for information. Since the enclosed request for information is not new, but merely clarification of our previous letter, responding to it should not delay any submittals. in progress that are based upon February 20, 1981 letter. Licensees whose response to the February 20, 1981 letter, has been found incomplete resulting in staff identifications of a major unresolved item (iie., associated circuits),
]
may choose to respond to pertinent sections of the enclosed request for infor-mation in order to close open items (i.e., open item for. associated circuits.
i
'I use rewrite of Enclosure 2).
.i If additional clarification is needed, please contact the staff Project
'I ibnager for your plant.
^
i ATTACHMENT 1 REWRITE OF SECTION 8 REQUEST FOR ADDITIONAL INFORMATION The following is a rewrite of the staff's request for additionel formation
~l concerning design modification to meet the requirenents of Section III.G.3 of Appendix P..
The following cor,tains no new requests but is merely a rewording of Section 8 of Enclosure 1 of the February 20, ~ 1981 generic letter.
1.
Identify those areas of the plant that will not mset the requirements of Section III.G.2 of Appendix R and, thus alternative shutdown will be provided
, or an exemption. from the requirements of Section III.G.2 of Appendix R will be provided. Additionally provide a statement that all other areas of the plant are or will be in compliance with Section III.G.2 of Appendix R.
I I
For each of those fire areas of the plant requiring an alternative shutdown systun(s) provide a complete set of responses to the following requests for each fire area:
List the system (s) or portions thereof used to provide the shutdown a.
i capability with the loss of offsite power.
l b.
For those systems identified in "la" for which alternative or dedicated shutdown capability must be provided, list the equipment and components of the normal shutdown system in the fire area and identify the functions of the circuits of the normal shutdown system in the fire area (power to what i
equipment, control of what components and instrumentation). Describe
{
the system (s) or portions thereof used to provide the alternative shutdown lR capabilJty for the fire area and provide a table that lists the equipment and components of the alternative shutdown system for the fire area.
I l
3
. For each alternative system identify the function of the new circuits being provided.
Identify the location (fire zone) of the alternative shutdown equipment and/or circuits that bypas: the fire area and verify that the alternative shutdown equipment and/or circuits are separated from the fire area in accordance with Section III.G.2.
Provide drawings of the alternative shutdown system (s) which highlight any c.
connections to the normal shutdown systems (P& ids for piping ano components, elementary wiring diagrams of electrical cabling). Show the electrical location of all breakers for power cables, and isolation devices for l
control and instrumentation circuits for the alternative shutdown systems
{
for that fire area.
d.
Verify that changes 'to safety systems will not degrade safety systems; I
(e.g., new isolation switches and control switches should meet design criteria and standards in the FSAR for electrical equipment in the system that the switch is to be installed; cabinets that the switches are te be mounted in should also meet the same criteria (FSAR) as other safety related cabinets and panels; to avoid inadvertent isolation from the control room, the isolation switches should be keylocked or alarmed in the control room if in the " local" or " isolated" position; periodic checks should be made to verify that the switch is in the proper position for normal operation; and a single transfer switch or' other new device should not be a scurce of a failure which causes loss of recunoant safety systems).
e.'
Verify that licensee procedures have been or will, be develo' ped which describe the tasks to be perfomed to effect the shutdown method.
Provide a summary
.of these procedures outlining operator actions.
3-(
f..
Verify that the manpower required to perform the shutdown functions using the procedures of e5 as well as to provide fire brigade members to fight the fire is available as required by the fire brigade technical spect-fications.
9 Provide a commitment to perform adequate acceptance tests of the alter-
~
native shutdown capability.
These tests should verify that:
equipment operates from the local control station when the transfef or isolation switch is placed in the " local" position and that the equipment cannot be operated from the control room; and that equipment operates from the i
control room but cannot be operated at the local control station when i
the transfer isolation switch is in the " remote" position.
h.
Provide Technical Specificaticns of the surveillance requirements and limiting conditions for operation for that equipment not already covered by existing Technical Specifications.
For example, if new isolation and control switches are added to a shutdown system, the existing Technical Specification surveillance requirements should be supplemented to verify system / equipment functions from the alternate shutdown station at testing intervals consistent with the guidelines of Regulatory Guide 1.22 and IEEE 338.
Credit may be taken for other existing tests using group overlap test concepts.
t
/~
4 i.
For new equipment compruing the alternative shutdown capability, verify that the systems available are adequate to perform the necessary shut-down function. The functions required should be based on previous analyses, if possible (e.g., in the FSAR), such as a loss of normal ac power or shutdown on Group 1 isolation (BWR). The equipment required for the alternative capability should be the sa:re or equivalent to that relied on in the above analysis.
j, Verify that repair procedures for cold shutdown systems are developed and material for repairs is maintained on site.
Provide a summary of i
these procedures and a list of the material needed for repairs.
.k i
i i
1 i
l i
ATTACHMENT 2 SAFE SHUTDOWN CAPAMLITY
~
The following discusses the requirements for. protecting redundant and/or alternative equipment needed for safe shutdown in the event of a fire. The requirements of Appendix R address hot shutdown equipment which must be f
free of fire damage. The followl.ng requirements also apply to cold s,hutdown i
equipment if tha licensee elects to denonstrate that the. equip:;ent is to be, free of. fire. damage. AppendE R does allow. repairable damage to cold shutdown ecutoment.
I i
Using the requirements of Sections III.G and III.L of Appendix R, the capa-i bility~to achieve hot shutdown must exist given a fire in any area of the plant in conjunction with a loss of offsite power for 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />.Section III.G of Appendix R provides four methods for ensuring that the hot shutdown capa-bility is protected from fires. The first three options as defined in Section III.G.2 provides methods for protection from fires of equipment needed for hot shutdown:
1.
Redundant systems including cables, equipment, and associated circuits l
may be separated by a three-hour fire rated barrier; or, I.
}
2.
Redundant systens including cables, equipment and associated circuits may i
t be separated by a horizontal distance of more than 20 feet with no inter-i vening combustibles.
In addition, fire detection and an automatic fire suppression system are required; or, S
3.
Redundant systems including cables, equipment and associated circuits ma.)
~
by enclosed by a one-hour fire rated barrier.
In addition, fire detectors and ar. automatic fire suppression system are required.
k f
i i
u _..
r
- j
' The last option as defined by Section III.G.3 provides an alternative shutdown capability to the redundant trains damaged by a fire.
'I Alternative shutdown equipment must be independent of the cables, eauf p-4.
ment and associated circuits of the redundant systems damaged by the fire.
l Associated Circuits of Concern The following discussion provides A) a definition of associated circuits for Appendix R consideration, B) the guidelines for protecting the safe' shutdown capability from the fire-induced failures of associated circuits and C) the in-formation required by the staff to review associated circuits. The definition
~
f, of associated circuits has not changed from the February 20, 1981 generic letter; l
but is merely clarified.
It is important to note that our interest is only with those circuit (cables) whose fire-induced failure could effect shutdown.
The guidelines for protecting the safe shutdown capability from the fire-induced failures of associated circuits are not requirements. These guidelines should be used only as guidancs when needed. These guidelines do not limit the alter-t natives available to the licensee for protecting the shutdown capability.
All proposed methods for protection of the shutdown capability from fire-induced failures will be evaluated by the staff for acceptability..
1 A.
Our concern is that circuits within the fire area will receive fir.e damage which can affect shutdown capability and thereby prevent post-fire safe shutdown. Associated Circuits
- of Concern are defined as those cables (safety related, non-safety related, Class 1E, and non-Class 1E) that:
j I
{
- The definition for associated circuits is not exactly the same 1
as the definition presented in IEEE-384-1977.
i I
..w
e.-
- Have a physical separation less than that required by Section III.G.2 1.
of Appendix R, and; 2.
Have one of the following:
a commor. power source with the shutdown equipment (redundant or a.
alternative) and the power source is not electrically protected from the circuit of ccacern by coordinated breakers, fuses, or similar devices (see diagram 2a), or a connection to circuits of equipment whose spurious operation b.
would adversely affect the shutdown capability (e.g., RHR/RCS isolation valves, ADS valvos PORVs, steam generator atmospheric dump valves, instrumentation, steam bypass, etc.) (see diagram 2b), or i'
a common enclosure (e.g., raceway, panel, junction) with the shutdown c.
cables (redundant and alternative) and, I
(1) are not electrically protected by circuit breakers, fuses or simi-a lar devices, or propagation of the fire into the common (2)will allow enclosure, (see diagram 2c).
s f i
)
o I
i fa l
I,
. -,,. +
. m....
e _.
E l
EXAMPLES OF ASSOCIATED CIRCUITS OF CONCERN _
1 i
4 F18E. 6BEA FI8e. ARE A
.FinF. AREA l
\\
\\
\\
3
\\
ll
\\
T
\\
\\
l x
\\
. :'1
?'
\\
- ei
\\s s
x 6
s N
\\
\\
6 N
1 x'
i m
-}l N
N
\\
S s
\\
k N
e
\\
\\
-g
.l" l
's
.\\
j
\\
.)
_I
\\
j N
N
, '1 j V
\\
\\
b-
.N 4
al if N
B
\\
P s
\\
<g F
3
<l s
\\
I l-N 1-g g
\\
\\
h\\'\\\\\\ \\.\\ \\x i
x l
\\NANNu NNN i
\\NNNN NNN l
cor,,,.s 1
l Euctosa#E r
- vatve, i
l E mf ed wAo e spulens The area barriers shown above meet 7
theappropriatesub-paragraphs (a-f) o - bus oper.hs coahl. affec/
of section III.G-2 of Appendix R.
l, l
skaddwn l
Diagram 2A Diagram 2B Diagram 2C
. - - ~
-. ~....
. The following guidelines are for protecting the shutdown capability from B.
fire-induced failures of circuits (cables) in the fire area. The guidance provided below for interrupting devices applies only to new devices installed to provide electrical isolation of associated circuits of concern, or as The shutdown capability part of the alternative or dedicated shutdown system.
may ba protected from the adverse effect of damage to associated circuits of concern by the following methods:
Provide protectio'n between the associated circuits cf concern and 1.
the shutdown circeits as per Section III.G.2 of Appendix R, or I
t For a common power source case of associated circuit:
l 2.
a.
I Provide load fuse / breaker (interrupting devices) to feeder l
fuse / breaker coordination to prevent loss of th redundant or t
I I
To ensure that the following alternative shutdown power source.
f coordination criteria are met the 'following should apply:
(1) The associated circuit of concern interrupting devices (breakers or fuses) time-overcurrent trip characteristic for all circuits faults should cause the interrupting device to interrupt the fault current prior to initiation f
of a trip of any upstream interrupting device which will l
cause a loss of the common power source,
,(2) The power source shall supply t'he necessary fault current a
for sufficient time to ensure the proper coordination i
without loss of function of the shutdown loads, n
l
-,,y
....~ -.. :..,
. '}
The acceptability of a particular interrupting device is considered demonstrated if the following criteria are met:
(i) The interrupting device design shall be factory tested to verify overcurrent protection as designed in accordance with the applicable UL, ANSI, or NEMA standards.
(ii) For low and medium voltage switchgear (480 V and above) circuit breaker / protective relay periodic testing shall demonstrate that the overall coordination scheme remains within the limits specified in the design criteria. This testing may be performed as a series of overlapping tests.
i (iii) Molded case circuit breakers shall peridically be manually exercised and inspected to insure ease of operation. On l
a rotating refueling outage basis a sample of these breakers shall be tested to determine that breaker drift is within that allowed by the design criteria. Breakers should be tested in accordance with an accepted QC testing methodology such as MIL STD 10 5 D.
1 (iv) Fuses when used as interrupting devices do not require periodic testing, due to their stability, lack of drift,
}
and high reliability. Administrative controls must insure that replacement fuses with ratings other than those n
selected for proper coordinating are not accidentally used.
b.
For cir cuits of equipment and/or comconents whose spurious operation j
would affect the capability to safely shutdown:
-.~.
Y
\\
. (1) provide a means to isolate the equipment and/or components from the fire area prior to the fire (i.e., remove power cables, open circuit breakers); or (2) provide electrical isolation that prevents spurious cperation.
Potential isolation devices include breakers, fuses, ampli-fiers, control switches, current XFRS, fiber. optic couplers, relays and transducers; or (3) provide a means to detect spurious operations and then proce-dures to defeat the maloperation of equipment (i.e., closure of the block valve if PORV spuriously operates, opening of the breakers to remove spurious operation of safety injection);
For comon enclosure cases of associated circuits:
l c.
j (1) provide appropriate measures to prevent propagation of the l
fire; and (2) provide electrical protection (i.e., breakers, fuses or i
similardevices)
We recognize that there are different approaches which may be used to C.
reach the same objective of determining the interaction of associated circuits with shutdown systems. One approach is to start with the fire area, identify what is in the fire area, and' determine the interaction i<
between what is in the fire area and the shutdown systems which are l
We have e. titled this approach, "The Fire Area n
outside the fire area.
Approach." A second approach which we have named "The Systems Approach"
!I would be to define the shutdown systems around a fire area and then determine
~......
k.
those circuits that are located in the fire area that are associated ll with the shutdown system. We have prepared twa sets of requests f,or information, one for each approach. The licensee may choose to respond to either set of requests depending on the approach selected by the licensee.
FIRE AREA APPROACH For eac.h fire area where an alternative or dedicated shutdown method, 1.
in accordance with Section III.*G.3 of Appendix R is provided, the following information is required to demonstrate that associated circuits will not prevent operation or cause maloperation of the alternative or dedicated shutdown methed:
Provide a table that lists all the power cables in the fire area l
a.
that connect to the same power supply of the alternative or dedicated shutdown method and the function of each power cable listed (i.e., power for RHR pump).
i f
Provide a table that lists all the cables in the fire area that b.
were considered for pessible spurious operation which would adversely
~
affect shutdown and the functior of each cable listed.
Provide a table that lists all ti.e cables in the fire area that c.
share a common enclosure with circuits of the alternative or dedicated shutdown systems and the function of each cable listed.
d.
Show that fire-induced failures (hot shorts, open circuits or shorts to ground) of each of the cables listed in a; b, and c will not prevent operation or cau,se maloperation of the alternative or dedicated shutdown method.
?
2
1-
____.a
. For each cable listed in a, b and c where new electrical isolation has e.
been provided or modification to existir.g electrical isolation has been made, provide detailed electrical schematic drawings that show how each cable is isolated from the fire area.
SYSTEMS APPROACH 1.
For each area where an alternative or dedicated shutdown method, in accordance with Section III.G.3 of Appendix R is provided, the following information is required to demonstrate that associated circuits will not prevent operation or cause maloperation of the alternative or dedicated shutdown method:
I i
Describe the methodology used to assess the potential of associated a.
circuit adversly affecting the alternative or dedicated shutdown.
The description of the methodology should include the methods ysed to identify the circuits which share a comon power supply or a comon enclosure with the alternative or dedicated shutdown i
system and the circuits whose spurious operation would affect shutdown. Additionally, the description should include the i
methods used to identify if these circuits are associated circuits i
of concern due to their location in the fire area.
i
}
b.
Provide a table that lists all associated circuits of concern located in the fire area.
Show that fire-induced failures (hot shorts, open circuits or c.
i shorts to ground) of each of tha cables listed in b will not prevent operation or cause maloperation of the alternatite or dedicated shutdown method.
\\
'l.
d.
For each cable listed in b where new electrical isolation has been f
~
provided, provide detailed electrical schematic drawings that show how each cable is isolated from the fire area.
Provide a location at the site or other office,s where all the e.
tables and drawings generated by th s metho'dilogy approac_h for the associated circuits review may be audited to verify,the information provided above.
HIGH-LOW PRESSURE INTERFACE For either approach chosen the following concern dealing with high-low pressure interface should be addressed.
I 2.
The residual heat removal system is generally a low pressure system that interfaces with the high pressure primary coolant system. To preclude a LOCA through this interface, we requi.re compliance with i^
the recommendations of Branch Technical Position RSB 5-1.
Thus, the interface most likely consists of two redundant and independent motor operated valves. These two motor operated valves and their associdted cables may be subject to a single f. ire hazard. It is our concern that this-single fire could cause the two valves to open resulting in a fire initiated LOCA through the high-low pressure system interface. To assure that this interface and other high-low pressure interfaces are adequately protected from the effects of a 1
single fire, we require the following information:
Identify each high-low pressure interface that uses redundant a.
electrically controlled dev' ices'(such as two series motor operated j
valves) to isolate or preclude rupture of any primary coolant boundary.
}
. For each set of redundant valves identified in a., verify the b.
redundant cabling (power and control) have adequate physical separation as required by Section III.G.2 of Appendix R.
th:t For each case where adequate sep ration is r.ct previdej, shot:
c.
fire induced failures (hot short, open circuits or short to ground) of the cables will not cause maloperation and result in a 1.0CA.
E 4
i h
ln l
(
I l
tm.t.usunt.5 CRIT'ERIA FOR EVAL'UATING EXEMPTI0t1S TO SECTI0tl III G OF APPENDIX R OF 10 CFR PART 50
)
Paragraph 50.48 Fire Protection of 10 CFR Part 50 requires that all nuclear power plants licensed prior to January 1,1979 satisfy the requirements of Section III.G of Appendix R to 10 CFR Part 50.
It also requires that alternative fire protection configurations, previously approved by an SER be reexamined for compliance with the requirements of Section III.G.Section III.G is related to fire protection features for ensuring that systems and associated circuits used to achieve and maintain safe shutdown are free of fire damage.
Fire protiction configurations must either meet the specific require-ments of Section III.G or an alternative fire protection configuration must be justified by a fire hazard analysis.
The general criteria for accepting an alternative fire protection configur-ations are the following:
The alternative assures that one train of equipment necessary to achieve hot shutdown from either the control room or emergency control stations is free of fire damage.
The alternative assures that fire damage t.o at least one train of equipment necessary to achieve cold shutdown is limited such that it can be repaired within a reasonable time (minor repairs with components stored on-site).
Fire retardant coatings are not used as fire barriers.
Modifications required to meet Section III.G would.not enhance fire protection safety above that provided by either existing or proposed alternat,ives.
Modifications required to meet Section III.G would be detrimental to overall facility safety.
Because of the broad spectrum of potential configurations for which t
exemptions may be requested, specific criteria that account for all of J
the parameters that are important to fire protection and consistent with safety requirements of all plant-unique corfigurations have not been However, our evaluations of deviations from these require-developed.
ments in our grevious reviews and in the request's for III.G exemptions
)
receiv d to date have identified some recurring configurations for which specific criteria have been develop'ed.
-r'*
1 i A passive Section III.G 2 accepts three methods of fire protection.Where a fixed barrier e
ij 3-hour fire barrier should be used where possible.
cannot be installed, an automatic suppression systen in combination with
'I a fire barrier or a separation distance free of combustibles is used if the configurations of systems to be protected and in-situ combustibles are such that there is reasonable assurance that the protected systems will If this latter condition is not met, alternative shutdown capa-bility is required and a fixed suppression system installed in the fire survive.
It is area of concern, if it contains a large concentration of cables.
essential to remember that these alternative requirements are not deemed However, they provide adequate protection for those to be equivalent.
configurations in which they are accepted.
When the fire protection features of each fire area are evaluated, the The defense-whole system of such features must be kept in perspective.
in-depth principle of fire protection programs is aimed at achieving an Strengthening any one adequate balance between the different features.
can compensate in some measure for weaknesses, known or unknown in others.
The adequacy of fire protection for any particular plant safety system or area is determined by analysis of the effects of postulated fire relative to maintaining the ability to safely shutdown the plant and minimize radio-During thes,e active releases to the environment in the event of a fire.
evaluations it is necessary to consider the two-edged nature of fire protection features recognized in General Design Cr An evaluation must be made for each fire area for which an e
~
is requested.
i parameters:
'A.
Area Description walls, floor, and ceiling construction ceiling height room volume ventilation
,{
congestion l2 B.
Safe Shutdown Capability number of redundant systems in area whether or not system or equiment is required for hot shutdown
/
type of equipment / cables involved repair time for cold shutdown equipmnt within this area separation between redundant components and in-situ conc 2ntration of combustibles i
alternative shutdown capability y
3l I
1 l
.,~m..-
.s.
,.s 3-C.
Fire Hazard Analysis l
type and configuration of combustibles in area quantity of combustibles ease of ignition and propagation heat release rate potential transient and installed combustibles suppression damage to equipment whether the area is continuously manned traffic through the area accessibility of the area D.
Fire Protection Existing or Committed fire detection systems fire extinguishing systems ho,se station / extinguisher 4
radiant heat shields 3
A specific description of the fire protection features of the configuration Low is required to justify the compensating features of the alternative.
fire loading is not a sufficient basis for granting an exemption in areas where there are cables.
j If necessary, a team of. experts, including a fire protection engineer, This visual will visit the site to determine the existing circumstances.
inspection is also considered in the review process.
The majority of the III.G exemption requests received to date are being Licensees have not identified denied because they lack specificity.
the extent of the exemption requested, have not provided a technical basis For the request and/or have not provided a specific description of the a
alternative. We expect to receive requests for exemption of the following nature:
1.
Fixed fire barriers less than 3-hour rating.
Fire barrier without an automatic fire suppression system.
2.
Less than 20 feet separation of cables with fire propagation 3.
retardants (e.g., coatings, blankets, covered trays) and an automatic suppression system.
For large opa.1 areas with few components to be protected and few in-situ 4.
combustibles, no automatic suppression system with separation as in Item 3 above.
5.
No fixed suppression in the contr'o1 room.
i
i t,
6.
No fixed suppression in areas without a large concentration of cables for which 61ternative shutdown capability has been prcvided.
Our fire research test program is conducting tests to provide information that will be useful to determine the boundary of acceptable conditions for fire protection configurations which do not include a fire rated barrier.
Based on deviations recently approved, specific criteria for certain recurring configurations are as follows:
Fire Barrier Less than Three Hours This barrier is a wall, floor, ceiling or an enclosure which separates one fire area from another.
Exemptions may be granted for a lower rating (e.g., one hour or two hours)
The fire where the fire loading is no more than 1/2 of the barrier rating.
j rating of the barrier shall be no less than one hour.
3 Exemptions may be granted for a fixed barrier with a lower fix rating supplemented by a water curtain.
I, An Automatic Suppression System With Either One Hour Fire Barrier or l
ZD-Foot Separation This barrier is an enclosure which separates those portions of one division which are within 20 feet of the redundant division. The suppressant may be water or gas.
Exemptions may be granted for configurations of redundant systems which
'have compensating features.
For example:
}
Separation distances less than 20 feet may be deemed acceptable where:
A.
l 1
Fire propagation retardants (i.e., cable - coatings, covered trays, 1
1.
conduits, or mineral wool blankets) assure that fire propagation l
through in-situ combustibles will not occur or will be delayed 1
sufficiently to enstire adequate time for detection and suppression.
i Distance above a floor level exposure fire and below ceiling ' assures 2.
that redundant systems will not be simultaneously subject to an una;ceptable temperature or heat flux.
l The ommission of an automatic suppression system may be deemed acceptable l
B.
where:
1 1
1.
Distance above a floor level exposure fire and below ceiling assures that redundant systems will not be simultaneously subject to an unacceptable temperature or heat flux.
~_
'I o
5-
.2.
The fire area is required to be manned continuously by the provisions in the Technical Specifications.
e f
f 4
t 1,-
~. t 24 N
.